Académique Documents
Professionnel Documents
Culture Documents
SCHOOL OF ENGINEERING
DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING
QUESTION BANK
UNIT I - INTRODUCTION
PART - A (2 MARKS)
3. A generator rated at 35MVA, 10kV has a reactance of 20%. Calculate its p.u reactance
for a base of 50 MVA and 12 kV.
4. Form the bus admittance matrix for the system whose reactance diagram is shown
below:
1. Draw the per unit impedance diagram for the power system shown in the below figure
with the following components and their corresponding ratings. Neglect resistance and
use a base of 75 MVA, 220 kV in 50 Ω line.
2. Preserving all the three nodes in the reactance diagram of a typical power system
shown below, determine Z bus for the system shown in the following figure.
3. Prepare a per phase systematic of the system shown in the below figure and show all
the impedance in per unit on a 100 MVA, 132 kV base in the transmission line circuit
on the necessary data are given as follows.
5. The data for a system whose single line diagram is shown in the following figure is as
follows:
Choose the base power as 10 MVA and appropriate base voltage for different parts.
Draw the impedance diagram with values of per unit impedances of various components
clearly marked. Also find the generator current, the transmission-line current, the load
current and the load voltage.
6. For a network shown in the following figure, form the bus admittance matrix.
Za = j0.6; Zb = j0.4; Zc = j0.5 = Zd; Ze = j0.2; Zm = j0.1. All data are in pu.
PART - A (2 MARKS)
Obtain the voltage magnitude and phase angle of bus 2 by performing two iterations
by N-R method. Use appropriate assumptions if necessary.
3. The one-line diagram of a power system is shown in the figure. Using GS method,
perform load flow analysis to obtain the complex bus bar voltages. Start the iteration
Taking the acceleration factor as 1.4, determine all the bus voltages at the end of first
iteration using Gauss – Seidel method.
6. The following are the bus specifications of single line diagram of a power system.
Bus code P Q V
0
1 - - 1.06/0 (slack bus)
2 -0.5 0.1≤ Q2 ≤1 1.05
3 -0.4 0.3 -
4 -0.2 0.1 -
Using FDLF method, perform load flow analysis and obtain the voltages at all the
buses.
UNIT III – FAULT ANALYSIS – BALANCED FAULTS
PART - A (2 MARKS)
PART - B
1. Perform fault analysis by using Z-bus matrix and find the fault current, bus voltages
and the line currents when a symmetrical fault with a fault impedance of Z f=0.16 p.u
occurs at i) Bus 1 and ii) Bus 2 in the following system. Each generator is represented
by an emf behind the transient reactance.
All the impedances are in p.u and on a common 100 MVA base.
2. A 3-phase generator connected through a five cycle circuit breaker to a transformer is
rated at 100 MVA, 18kV, with synchronous, transient and subtransient reactances of
110%, 25% and 20% respectively. It is operated on no-load and at rated voltage. When
a 3-phase fault occurs between the breaker and the transformer, find:
i)the Short circuit current in the circuit breaker, ii) the initial symmetrical rms
current in the circuit breaker, iii) the maximum possible dc component of the short
circuit current in the breaker iv) the current to be interrupted by the breaker and v)
the interrupting MVA.
3. In the network of figure 3.3, a symmetrical fault occurs at bus 2.Determine
a) the initial symmetrical rms current in the fault b) the voltages at the buses 1,3
and 4 during the fault c) the current contributions to the fault from lines
3 – 2, 1-2, 4-2. Neglecting all the prefault currents, assume a prefault voltage
at bus 2 as 1+j0 p.u
4. The bus impedance matrix of a four bus system with values in p.u is given by,
Generators are connected to buses 1 and 2 and their subtransient reactances were
included when finding Zbus. Neglecting prefault current, find the subtransient current
in p.u for a 3-phase fault on bus 3. Assume a prefault voltage of 1.0 p.u. If the
subtransient reactance of the generator in bus 2 is j0.2 p.u, find the subtransient fault
current supplied by the generator.
5. For the shown system, determine the fault current supplied by the generator operating
under no-load with a voltage of 6.9kV. At ‘F’, three phase fault has occurred.
6. The system shown in the figure is delivering 500 MVA at 11 kV, 0.8 lagging power
factor into a bus which may be regarded as infinite. Particulars of various components
are:
Generator = 600 MVA, 12 kV, X d’ = 0.35 pu
Transformer each = 80 MVA, 12/66 kV, X = 0.08 pu
Line: Reactance 12 Ω, resistance negligible
Calculate the symmetrical current that the circuit breakers A and B will be called upon
to interrupt in the event of a three phase fault occurring at F near the circuit breaker B.
PART – B
1. Determine the positive, negative and zero sequence networks for the system shown
below.
Assume zero sequence reactances for the generator and synchronous motors as 0.06
p.u and that of the transmission line is j300 Ω. Current limiting reactors of 3.5 Ω are
connected in the neutral of the generator and motor no 2.
2. A single line to ground fault occurs on the bus 1 of the system of below figure .
Find :
(i) Fault current
(ii) Short circuit current on the transmission line in all the three phases
(iii) Voltage of the healthy phase of the bus 1
Given : Rating of each machine 1200 kVA, 600 V with X 1 = X2 = 10% and X0 = 5%.
Each three phase transformer is rated 1200 kVA, 600 V/ 3300 V (Δ/Y) with the
leakage reactance of 5%. The reactances of transmission line are X 1 = X2 = 20% and X0
= 40% on the base of 1200 kVA, 3300 V. The reactances of neutral grounding reactors
are 5% on the kVA and voltage base of the machine.
3. A salient pole generator without dampers is rated at 20 MVA, 13.8kV and has a direct
axis subtransient reactance of 0.25 p.u. The negative and zero sequence reactances are
0.35p.u and 0.10 p.u respectively. The neutral of the generator is solidly grounded.
Find the subtransient currents and line to line voltages at the fault under subtransient
conditions when an L-L fault occurs between phase ‘b’ and ‘c’ at the terminals of the
generator. Assume that the generator is unloaded and operating at rated terminal
voltage when the fault occurs. Neglect resistance.
4. Forming the bus impedance matrix for the following network, determine the bus
voltages and line currents during when LLG fault occurs at bus 3 through a fault
impedance Zf = j0.1.
6. For the system shown below, determine the fault current and fault MVA for a L-L
fault occurring between the phases b and c at bus no. 4.
PART - A (2 MARKS)
1. The d-axis transient reactance of a 60Hz synchronous generator having the inertia
constant of 5MJ/MVA is 0.25 p.u. It is connected to an infinite bus through a three
phase transformer with reactance 0.2 p.u. Two transmission lines with p.u. reactances
of 0.3 each are in parallel between the buses where the latter are between the
transformer and the infinite bus. The generator delivers a real power and a reactive
power of 0.8 p.u and 0.074 p.u respectively.
i) A temporary three-phase fault occurs at the sending end of the line. When the
fault is cleared, both lines are intact. Determine the critical clearing angle and
the critical fault clearing time.
ii) A three-phase fault occurs at the middle of one of the lines, the fault is cleared
and the faulted line is isolated. Determine the critical clearing angle.
Draw the equal area criterion for both the cases.
Prefault 0.5 pu
During fault 1.0 pu
Post fault 0.75 pu
Calculate the swing curve using intervals of 0.05 sec and assuming that the fault is
cleared at 0.15 sec.
Obtain the numeric solution of the swing equation up to 0.15s using modified Euler’s
method.
6. The generator in the below figure supplies 125MW and 156 MVAR.
The tie line reactance is 0.08p.u. Xd’=0.3 p.u. The inertia constant is 4 p.u on a 100
MVA base. For a duration of 0.1s, a three phase fault occurs at bus P. At the end of
0.1s, the fault disappears without any circuit breaker opening. Write the swing equation
for faulted and post fault conditions. Solve the same by Runge-Kutta method.