Wood Group ESP - Mfg

Vector IV Drive Shop Testing

DATE:
EQUIPMENT INFORMATION

DESCRIPTION SERIAL # PART # RATING/MISC


Vector IV Drive kva in out
WGCT Controller VSS- firmware
WGCT Display
SSU/DB firmware

WGCT Controller Type/Status


Power Supply vac vdc
Input Relays L/R STRT 1 2 3 4

Output Relays 5 6 7 8 9 10

Com Ports 1 2 usb host usb device

Options exp event exp mem radio com

backspin dh sensor exp I/O AC wf

usb port dialup

Page 1
Wood Group ESP - Chad
Exxon-Mobil Chad Vector IV Drive Shop Testing

DATE:
PRE-POWER CHECKS

Vector IV Converter Diode Modules


Meter Lead Diode Reading (vdc) Vector SWF
(+) (-) Nominal Actual Meter Lead Reading (ohms)
+ DC TB1-R OL (+) (-) Nominal Actual
+ DC TB1-S OL SWTB-U SWTB-V charge/inf
+ DC TB1-T OL SWTB-U SWTB-W charge/inf
- DC TB1-R 0.325 SWTB-V SWTB-W charge/inf
- DC TB1-S 0.325 SWTB-U Gnd charge/inf
- DC TB1-T 0.325 SWTB-V Gnd charge/inf
+ DC - DC Charge SWTB-W Gnd charge/inf
SWTB-U C21 0.3
Vector IV Inverter IGBT Modules SWTB-U C22 0.3
Meter Lead Diode Reading (vdc) SWTB-V C23 0.3
(+) (-) Nominal Actual SWTB-U C24 0.2
Inv + TB1-U charge/inf SWTB-V C25 0.2
Inv + TB1-V charge/inf SWTB-W C26 0.2
Inv + TB1-W charge/inf
TB1-U Inv + 0.350 Vector IV Choke Thermal Switches
TB1-V Inv + 0.350 Meter Lead Reading (ohms)
TB1-W Inv + 0.350 (+) (-) Nominal Actual
Inv - TB1-U 0.350 TSTB-1 TSTB-7 0.6
Inv - TB1-V 0.350 TB13-1 TB14-3 0.4
Inv - TB1-W 0.350 TB4-16 TB4-29 0.4
TB1-U Inv - charge/inf
TB1-V Inv - charge/inf
TB1-W Inv - charge/inf

Page 2
Wood Group ESP - Chad
Vector IV Drive Shop Testing

DATE:
POWER UP CHECKS

480VAC Input Voltage - Vector DC Buss Checks - Vector


Meter Lead Reading (VAC) Meter Lead Reading (VDC)
(+) (-) Nominal Actual (+) (-) Nominal Actual
MCP1-L1 MCP1-L2 480 DC + DC - 678
MCP1-L1 MCP1-L3 480
MCP1-L2 MCP1-L3 480 120VAC Control Voltage - Controller
MCP1-1 Gnd 277 Meter Lead Reading (VAC)
MCP1-2 Gnd 277 (+) (-) Nominal Actual
MCP1-3 Gnd 277 PT2-F10 PT2-X2 120
PT1-F4 PT1-F5 480 VCS-15 VCS-17 120
CB2-1 CB2-2 480 24PS-7 24PS-6 120
MBS power light ON

120VAC Control Voltage - Vector TB4 120VAC Control Voltage - Vector TB3
Meter Lead Reading (VAC) Meter Lead Reading (VAC)
(+) (-) Nominal Actual (+) (-) Nominal Actual
PT1-XF PT1-X2 120 TB3-20 TB4-21 NOT OFF 120
TB4-1 TB4-21 120
TB4-2 TB4-21 120 TB3-24 TB4-21 Cntl Pwr 120
TB4-3 TB4-21 120 TB3-26 TB4-21 Auto 120
TB4-4 TB4-21 120 TB3-27 TB4-21 Remote 120
TB4-5 TB4-21 120 TB3-30 TB4-21 Run Enable 120
TB4-6 TB4-21 120
TB4-7 TB4-21 120
TB4-8 TB4-21 120
TB4-9 TB4-21 120
TB4-10 TB4-21 120
TB4-17 TB4-21 120
TB4-18 TB4-21 120

Page 3
Vector IV Actual Basic Access Parameters Ver. 4.008
Wood Group ESP,
Inc.
Monitor Motor Control Speed Command Dynamic Control Utilty Communication Inputs & Outputs
Metering Motor Data Min Max Spd Mode & Limits Min Max Ramp Rates Min Max Drive Memory Min Max Masks & Owners Min Max Analog Inputs Min Max
1 Output Freq 0.0 42 OL Amps 115% of Drv Rtd 0.0 1200 81 Min Speed 30.0 Hz 20.0 60.0 140 Accel Time 1 10.0 Sec 0 3600.0 196 Parm Access Lvl Basic 276 Logic Mask 000110 320 Anlg In Config xxxxxxxx00
2 Cmd Speed 0.0 895 OL Delay Time 3 Sec 0 300 892 Min Spd Delay 0 Sec 0 1800 142 Decel Time 1 10.0 Sec 0 3600.0 197 Reset to Dflt Ready 277 Start Mask 00111111 322 Anlg In1 Hi 10.000 V -10.000 10.000
3 Output Cur 0.0 148 Cur Lmt Val 150% Drv Rtd 150.0 900.0 82 Max Speed 60.0 Hz 5.0 120.0 Stop/Brake Modes 201 Language English 279 Direction Mask 00111111 323 Anlg In1 Lo 0.000V -10.000 10.000
6 Output Volt 0.0 189 Cur Lmt Time 0 Sec 0.0 30.0 84 Skip Freq 1 5.0 Hz -400.0 400.0 155 Stop/Brk Mode A Coast Diagnostics 280 Reference Mask 00111111 881 Anlg A Units "None"
7 Output Pwr 0.0 187 UL Level 50% Drv Rtd 0.0 4800 85 Skip Freq 2 5.0 Hz -400.0 400.0 Restart Modes 209 Drive Status 1 none 288 Stop Owner none 880 Anlg A Eng Max 0.00 0.00 20000
12 DC Bus V 0.0 188 UL Time 12 Sec 0.0 300.0 86 Skip Freq 3 5.0 Hz -400.0 400.0 168 Strt at Pwr Up Disable 210 Drive Status 2 none 289 Start Owner none 879 Anlg A Eng Min 0.00 0.00 20000
878 Analog A Val 0.00 Volts per Hertz 87 Skip Freq Band 0.0 Hz 0.0 30.0 174 Auto Rstrt Tries 0 0 9 211 Drive Alarm 1 none 291 Dir Owner none 325 Anlg In2 Hi 10.000 V -10.000 10.000
882 Analog B Val 0.00 69 Strt/Acc Boost 0 VAC 0.0 120.0 Speed References 175 Auto Rstrt Delay 30.0 Mins 0.0 180.0 212 Drive Alarm 2 none 292 Ref Owner none 326 Anlg In2 Lo 0.000V -10.000 10.000
Drive Data 70 Run Boost 0 VAC 0.0 120.0 90 Spd Ref A Sel DPI Port 2 894 Run Verify Time 60.0 Min 1.0 720.0 213 Spd Ref Source none 885 Anlg B Units "None"
26 Rated kW 0.00 71 Break Volts 120 V 0.0 480.0 93 Spd Ref B Sel Prst Spd 1 167 Pwr Up Delay 0.0 Secs 0.0 10800 214 Start Inhibits none 884 Anlg B Eng Max 0.00 0.00 20000
27 Rated V 0.0 72 Break Freq 15 Hz 0.0 400.0 96 TB Man Ref Sel DPI Port 5 Power Loss 216 Dig In Status none 883 Anlg B Eng Min 0.00 0.00 20000
28 Rated A 0.0 41 Base Volts Drv Rtd 0.0 480.0 Discrete Speeds 184 Pwr Loss Mode Decel 217 Dig Out Status none 886 Anlg Enable Disable
43 Base Freq 60 Hz 5.0 400.0 101 Preset Spd 1 30.0 Hz -60.0 60.0 185 Pwr Loss Time 0.5 Sec 0.0. 60.0 218 Drive Temp 17.40% 0.0 100.0 887 Anlg Low Lim 0.00 0.00 20000
54 Max Voltage Drv Rtd 120.0 480.0 102 Preset Spd 2 30.0 Hz -60.0 60.0 186 Pwr Loss Level 0.0 VDC 0.0 999.9 Faults 888 Anlg High Lim 0.00 0.00 20000
55 Max Freq 100 Hz 5.0 130.0 103 Preset Spd 3 30.0 Hz -60.0 60.0 238 Fault Config 1 01101x10 889 Anlg Delay 0.0 Mins 0.0 200.0
104 Preset Spd 4 30.0 Hz -60.0 60.0 Alarms Analog Outputs
105 Preset Spd 5 30.0 Hz -60.0 60.0 259 Alrm Cnfg 1 1x111111 340 Anlg Out Config xxxxxxxx00
106 Preset Spd 6 30.0 Hz -60.0 60.0 342 Anlg Out1 Sel Out Freq
107 Preset Spd 7 30.0 Hz -60.0 60.0 345 Anlg Out2 Sel Out Amps
Digital Inputs
361 Dig In1 Sel Stop/CF
362 Dig In2 Sel Start
363 Dig In3 Sel ESP Auto
364 Dig In4 Sel ESP Rem
365 Dig In5 Sel NC Aux Flt
366 Dig In6 Sel Enable
Digital Outputs
380 Dig Out1 Sel Mtr OL
384 Dig Out2 Sel UL
388 Dig Out3 Sel Run/Rstrt

Page 4
Wood Group ESP - Chad
Exxon-Mobil Chad Vector Drive Shop Testing

20-COMM-H COMMUNICATIONS MODULE SETUP

DATE:

NODE ADDRESS ROTARY DIP SWITCHES


Function Setting
LEFT SWITCH (TENS DIGIT) 0
RIGHT SWITCH (ONES DIGIT) 2

PROTOCOL SELECT ROTARY DIP SWITCH


Function Setting
PROTOCOL SELECT RTU

* = Parameter setting is important for proper operation. All other parameters have no effect on operation

20-COMM-H PARAMETERS
Parameter # Description Setting Default Minimum Maximum Type Comment
* 01 DPI Port 5 5 0 7 Read Only
02 DPI Data Rate 0 = 125 kbps 0 = 125 kbps 0 = 125 kbps 1 = 500 kbps Read Only
03 Net Addr Cfg 1 1 0 247 Read/Write Applies if node switches set to 00
04 Net addr Actual 2 1 0 1 Read Only Node address switches set to 02
* 05 Net Rate Cfg 1 = 9600 1 = 9600 0 = 4800 3 = 38400 Read/Write
* 06 Net Rate Actual 1 = 9600 1 = 9600 0 = 4800 3 = 38400 Read Only
* 07 Net Parity Cfg 0 = None 0 = None 0 = None 2 = Even Read/Write Requires module reset (Param 14)
* 08 Net Parity Actual 0 = None 0 = None 0 = None 2 = Even Read Only
* 09 Stop Bits Actual 0 = 1 bit 0 = 1 bit 0 = 1 bit 1 = 2 bits Read Only
10 Net Chksum Type 0=CRC16(0) 0=CRC16(0) 0=CRC16(0) 2=CRC16(-1) Read Only
11 Network Timeout 10 Sec 10 Sec 0 180 Read Only
12 Ref / Fdbk Size 0 = 16-bit 0 = 16-bit 0 = 16-bit 1 = 32-bit Read Only
13 Datalink size 0 = 16-bit 0 = 16-bit 0 = 16-bit 1 = 32-bit Read Only
* 14 Reset Module 0 = Ready 0 = Ready 0 = Ready 2=Set Defaults Read/Write 1=Reset Module, 2= Set Defaults
* 15 Comm Flt Action 1 = Stop 0 = Fault 0 = Fault 4=SendFltCfg Read/Write 1=Stop, 2=ZeroData, 3=Hold Last
16 DPI I/O Cfg xxx0 0001 xxx0 0001 xxx0 0001 Read/Write
17 DPI I/O Active xxx0 0001 xxx0 0001 xxx0 0001 Read Only
18 Flt Cfg Logic 0000000000000000 0000000000000000 0000000000000000 1111111111111111 Read/Write
19 Flt Cfg Ref 0 0 0 4294967295 Read/Write
20 Flt Cfg A1 In 0 0 0 4294967295 Read/Write
21 Flt Cfg A2 In 0 0 0 4294967295 Read/Write
22 Flt Cfg B1 In 0 0 0 4294967295 Read/Write
23 Flt Cfg B2 In 0 0 0 4294967295 Read/Write
24 Flt Cfg C1 In 0 0 0 4294967295 Read/Write
25 Flt Cfg C2 In 0 0 0 4294967295 Read/Write
26 Flt Cfg D1 In 0 0 0 4294967295 Read/Write
27 Flt Cfg D2 In 0 0 0 4294967295 Read/Write
28 Clear Counters 0 = Ready 0 = Ready 0 = Ready 1 = Clear Read/Write
29 N2 Ref Scale 32767 32767 0 4294967295 Read/Write
* 30 Stop Bits Cfg 0 = 1 bit 1 = 2 bits 0 = 1 bit 1 = 2 bits Read/Write Requires module reset (Param 14)
31 RTU Ref Adj 100% 100% 0% 200% Read/Write
Wood Group ESP - Chad
Exxon-Mobil Chad Vector Drive Shop Testing

DATE:
CONTROLLER SETUP

0 - Initial System Setup Display 0 - Initial System Setup Display


General Parameters Discrete I/O Parameters
Setup Default Parameter Register Setup Default Parameter Register
30 Min Man Restart Delay No DI-1 Output
3 Ea Max Man Restarts Yes DI-1 Normally Open
No Yes Wait for Restart Timer 0 DI-1 Alarm Code
Prog Restart Delay No DI-2 Output
1 Min 60 Min Strts Cntr Reset Delay Yes DI-2 Normally Open
0 Sec Pwr Fail Restart Delay 0 DI-2 Alarm Code
YES no Rem Lockout Override En No DI-3 Output
Avg OLD Alarm Yes DI-3 Normally Open
Avg ULD Alarm 0 DI-3 Alarm Code
Avg OVL Alarm No DI-4 Output
Avg UVL Alarm NO Yes DI-4 Normally Open
Avg I Limit Alarm 0 DI-4 Alarm Code
Data Archive Parameters Setup Default Parameter Register
Setup Default Parameter Register Yes DO-5 Output
60 Sec Raw data avg interval Yes DO-5 Normally Open
200 Ea Max # event log entries 243 0 DO-5 Alarm Code
0.50 %FS AC In Amps DeadBand Yes DO-6 Output
0.50 %FS AC In Volts DeadBand Yes DO-6 Normally Open
0.50 %FS AC In Pwr DeadBand 0 DO-6 Alarm Code
35 Days Historical Lifetime Yes DO-7 Output
Motor Control Parameters Yes DO-7 Normally Open
Setup Default Parameter Register 0 DO-7 Alarm Code
20 hz 10 Hz Start Frequency Yes DO-8 Output
0 Sec 2 Sec Start Delay Yes DO-8 Normally Open
3 Sec 10 Sec Accel Time 0 DO-8 Alarm Code
0A I Limit Amps Yes DO-9 Output
Yes DO-9 Normally Open
0 DO-9 Alarm Code
Yes DO-10 Output
Yes DO-10 Normally Open
0 DO-10 Alarm Code
0.0 Hz AC In Pwr DB %FS
2.00 %FS Historical Lifetime
0 Amps I Limit Value

Page 5
Wood Group ESP - Chad
Exxon-Mobil Chad Vector Drive Shop Testing

DATE:
CONTROLLER SETUP

6 - Control Parameters Display 6 - Control Parameters Display


Drive Scan Parameters Analog Input Parameters
Setup Default Parameter Register Setup Default Parameter Register
1 0 Port Number WH PRES AI-01 Point 1 Name
2 0 Device Address KPAX10 Point 1 EU
500 mSec 0 mSec Timeout 2100 0.000 Point 1 Span
AB Vector None Drive Type 0.000 Point 1 Offset
0.5 '% 0.00 % Span Drive I Deadband 0 % span Point 1 Filter Const
0.5 '% 0.00 % Span Drive V Deadband YES No Point 1 mA input
35 0 Days Drive History Lifetime 0.50% span Point 1 Hist Deadband
35 Days Point 1 Hist Lifetime
6 - Control Parameters Display FL PRES AI-02 Point 2 Name
DH Sensor Scan Parameters KPA Point 2 EU
Setup Default Parameter Register 2500 0.000 Point 2 Span
1 0 Port Number 0.000 Point 2 Offset
1 0 Device Address 0 % span Point 2 Filter Const
9600 0 Baudrate YES No Point 2 mA input
150 mSec 0 mSec Timeout 0.50% span Point 2 Hist Deadband
0 mSec 0 mSec RTS On Time 35 Days Point 2 Hist Lifetime
0 mSec 0 mSec RTS Off Time
10 Sec 0 Sec Polling Interval 1 - Current Status Display
SG V None Device Type PID Loop 1 Parameters
Setup Default Parameter Register
Manual Status
45 Hz 0 Hz Setpoint
99 0 Input Point
1 0 Output Point

Page 6
Wood Group ESP - Chad
Exxon-Mobil Chad Vector Drive Shop Testing

DATE:
CONTROLLER SETUP

6 - Control Parameters Display 6 - Control Parameters Display


DH Analog Input Parameters DH Analog Input Parameters
Setup Default Parameter Register Setup Default Parameter Register
INP PRES AI-09 Point 9 Name VIBRATN AI-13 Point 13 Name
BAR Point 9 EU G'S Point 13 EU
344 0.000 Point 9 Span 10 0.000 Point 13 Span
0.000 Point 9 Offset 0.000 Point 13 Offset
0 % span Point 9 Filter Const 0 % span Point 13 Filter Const
No Point 9 mA input No Point 13 mA input
0.05 0.50% span Point 9 Hist Deadband 2.00 0.50% span Point 13 Hist Deadband
35 Days Point 9 Hist Lifetime 35 Days Point 13 Hist Lifetime
INP TEMP AI-10 Point 10 Name LEAK CUR AI-14 Point 14 Name
DEG C Point 10 EU MA Point 14 EU
300 0.000 Point 10 Span 30 0.000 Point 14 Span
0.000 Point 10 Offset 0.000 Point 14 Offset
0 % span Point 10 Filter Const 0 % span Point 14 Filter Const
No Point 10 mA input No Point 14 mA input
0.10 0.50% span Point 10 Hist Deadband 1.00 0.50% span Point 14 Hist Deadband
35 Days Point 10 Hist Lifetime 35 Days Point 14 Hist Lifetime
MTR TEMP AI-11 Point 11 Name UH VOLTS AI-15 Point 15 Name
DEG C Point 11 EU VOLTS Point 15 EU
300 0.000 Point 11 Span 100 0.000 Point 15 Span
0.000 Point 11 Offset 0.000 Point 15 Offset
0 % span Point 11 Filter Const 0 % span Point 15 Filter Const
No Point 11 mA input No Point 15 mA input
0.10 0.50% span Point 11 Hist Deadband 0.00 0.50% span Point 15 Hist Deadband
35 Days Point 11 Hist Lifetime 35 Days Point 15 Hist Lifetime
SPARE AI-12 Point 12 Name DTYCYCLE AI-16 Point 16 Name
Point 12 EU Point 16 EU
0.000 Point 12 Span 100 0.000 Point 16 Span
0.000 Point 12 Offset 0.000 Point 16 Offset
0 % span Point 12 Filter Const 0 % span Point 16 Filter Const
No Point 12 mA input No Point 16 mA input
0.00 0.50% span Point 12 Hist Deadband 0.00 0.50% span Point 16 Hist Deadband
35 Days Point 12 Hist Lifetime 35 Days Point 16 Hist Lifetime

Page 7
Wood Group ESP - Chad
Exxon-Mobil Chad Vector Drive Shop Testing

DATE:
CONTROLLER SETUP

7 - AlarmSetpoints Display 7 - AlarmSetpoints Display


Alarm Parameters Definition - General Alarms Alarm Parameters Definition - General Alarms
Setup Default Parameter Register Setup Default Parameter Register
0.000 A OL Alarm Setpoint 0.000 V I OV Alarm Setpoint
0.0 Sec OL Enable Delay 0.0 Sec I OV Enable Delay
0.0 Sec OL Trip Delay 0.0 Sec I OV Trip Delay
0 3 Ea OL Max Restarts 0 3 Ea I OV Max Restarts
3 30 Min OL Restart Delay 3 30 Min I OV Restart Delay
Bypass Stop OL Alarm Action Bypass Stop I OV Alarm Action
0.000 A UL Alarm Setpoint 0.000 A I UV Alarm Setpoint
5.0 Sec UL Enable Delay 0.0 Sec I UV Enable Delay
0.0 Sec UL Trip Delay 0.0 Sec I UV Trip Delay
0 3 Ea UL Max Restarts 0 3 Ea I UV Max Restarts
3 30 Min UL Restart Delay 3 30 Min I UV Restart Delay
Bypass Stop UL Alarm Action Bypass Stop I UV Alarm Action
0.000 '% I Unbal Alarm Setpoint 0.000 Hz IFreq Hi Alarm Setpoint
5.0 Sec I Unbal Enable Delay 0.0 Sec IFreq Hi Enable Delay
0.0 Sec I Unbal Trip Delay 0.0 Sec IFreq Hi Trip Delay
0 3 Ea I Unbal Max Restarts 0 3 Ea IFreq Hi Max Restarts
3 30 Min I Unbal Restart Delay 3 30 Min IFreq Hi Restart Delay
Bypass Stop I Unbal Alarm Action Bypass Stop IFreq Hi Alarm Action
0.000 V OV Alarm Setpoint 0.000 A IFreq Lo Alarm Setpoint
0.0 Sec OV Enable Delay 0.0 Sec IFreq Lo Enable Delay
0.0 Sec OV Trip Delay 0.0 Sec IFreq Lo Trip Delay
0 3 Ea OV Max Restarts 0 3 Ea IFreq Lo Max Restarts
3 30 Min OV Restart Delay 3 30 Min IFreq Lo Restart Delay
Bypass Stop OV Alarm Action Bypass Stop IFreq Lo Alarm Action
0.000 V UV Alarm Setpoint 0.000 '% PFac Lo Alarm Setpoint
0.0 Sec UV Enable Delay 5.0 Sec PFac Lo Enable Delay
0.0 Sec UV Trip Delay 0.0 Sec PFac Lo Trip Delay
0 3 Ea UV Max Restarts 0 3 Ea PFac Lo Max Restarts
3 30 Min UV Restart Delay 3 30 Min PFac Lo Restart Delay
Bypass Stop UV Alarm Action Bypass Stop PFac Lo Alarm Action
90 Hz 0.000 Hz Freq Hi Alarm Setpoint 10.000 A GF Alarm Setpoint
0.0 Sec Freq Hi Enable Delay 0.0 Sec GF Enable Delay
0.0 Sec Freq Hi Trip Delay 0.0 Sec GF Trip Delay
0 3 Ea Freq Hi Max Restarts 0 3 Ea GF Max Restarts
3 30 Min Freq Hi Restart Delay 3 30 Min GF Restart Delay
Bypass Stop Freq Hi Alarm Action Bypass Stop GF Alarm Action
20 Hz 0.000 A Freq Lo Alarm Setpoint 45 Hz BS Max Freq
0.0 Sec Freq Lo Enable Delay 1 Min BS Delay after Mtr Stop
0.0 Sec Freq Lo Trip Delay 5 Min BS Delay after BS Stop
0 3 Ea Freq Lo Max Restarts 0.0 Sec DH Enable Delay
3 30 Min Freq Lo Restart Delay 0.0 Sec DH Trip Delay
Bypass Stop Freq Lo Alarm Action 0 3 Ea DH Max Restarts
0.000 V Vlt Unbal Alarm Setpt 3 30 Min DH Restart Delay
0.0 Sec Vlt Unbal Enable Delay Bypass Stop DH Alarm Action
0.0 Sec Vlt Unbal Trip Delay 0.0 Sec DrvCom Enable Delay
0 3 Ea Vlt Unbal Max Restarts 0.0 Sec DrvCom Trip Delay
3 30 Min Vlt Unbal Restart Delay 0 3 Ea DrvCom Max Restarts
Bypass Stop Vlt Unbal Alarm Action 3 30 Min DrvCom Restart Delay
Bypass Stop DrvCom Alarm Action
10.0 Sec DrvFlt Enable Delay
0 3 Ea DrvFlt Max Restarts
3 30 Min DrvFlt Restart Delay
Bypass Stop DrvFlt Alarm Action

Page 8
Wood Group ESP - Chad
Exxon-Mobil Chad Vector Drive Shop Testing

DATE:
CONTROLLER SETUP

7 - Alarm Setpoints Display 7 - AlarmSetpoints Display


Analog Limit Alarms Definition Discrete Alarms Definition
Setup Default Parameter Register Setup Default Parameter Register
0.0 AI 01 Lo Alarm Setpoint 0.0 Sec DI-1 Enable Delay
0.0 Sec AI 01 Lo Enable Delay 0.0 Sec DI-1 Trip Delay
0.0 Sec AI 01 Lo Trip Delay 0 3 Ea DI-1 Max Restarts
0 Accel Table 3 30 Min DI-1 Restart Delay
0 3 Ea AI 01 Lo Max Restarts Bypass Stop DI-1 Alarm Action
3 30 Min AI 01 Lo Restart Delay 0.0 Sec DI-2 Enable Delay
Bypass Bypass AI 01 Lo Alarm Action 0.0 Sec DI-2 Trip Delay
0.0 AI 01 Hi Alarm Setpoint 0 3 Ea DI-2 Max Restarts
0.0 Sec AI 01 Hi Enable Delay 3 30 Min DI-2 Restart Delay
0.0 Sec AI 01 Hi Trip Delay Bypass Stop DI-2 Alarm Action
0 Accel Table 10.0 Sec DI-3 Enable Delay
0 3 Ea AI 01 Hi Max Restarts 30.0 Sec DI-3 Trip Delay
3 30 Min AI 01 Hi Restart Delay 0 3 Ea DI-3 Max Restarts
Bypass Bypass AI 01 Hi Alarm Action 3 30 Min DI-3 Restart Delay
0.0 '% AI 01 Hi Warning Band Bypass Stop DI-3 Alarm Action
0.0 AI 02 Lo Alarm Setpoint 0.0 Sec DI-4 Enable Delay
0.0 Sec AI 02 Lo Enable Delay 0.0 Sec DI-4 Trip Delay
0.0 Sec AI 02 Lo Trip Delay 0 3 Ea DI-4 Max Restarts
0 Accel Table 3 30 Min DI-4 Restart Delay
0 3 Ea AI 02 Lo Max Restarts Stop Stop DI-4 Alarm Action
3 30 Min AI 02 Lo Restart Delay 0.0 Sec DI-5 Enable Delay
Bypass Bypass AI 02 Lo Alarm Action 0.0 Sec DI-5 Trip Delay
0.0 AI 02 Hi Alarm Setpoint 0 3 Ea DI-5 Max Restarts
0.0 Sec AI 02 Hi Enable Delay 3 30 Min DI-5 Restart Delay
0.0 Sec AI 02 Hi Trip Delay Bypass Stop DI-5 Alarm Action
0 Accel Table 10.0 Sec DI-6 Enable Delay
0 3 Ea AI 02 Hi Max Restarts 30.0 Sec DI-6 Trip Delay
3 30 Min AI 02 Hi Restart Delay 0 3 Ea DI-6 Max Restarts
Bypass Bypass AI 02 Hi Alarm Action 3 30 Min DI-6 Restart Delay
0% 0.0 '% AI 02 Hi Warning Band Bypass Stop DI-6 Alarm Action
0.0 Sec DI-7 Enable Delay
0.0 Sec DI-7 Trip Delay
0 3 Ea DI-7 Max Restarts
3 30 Min DI-7 Restart Delay
Bypass Stop DI-7 Alarm Action
10.0 Sec DI-8 Enable Delay
30.0 Sec DI-8 Trip Delay
0 3 Ea DI-8 Max Restarts
3 30 Min DI-8 Restart Delay
Bypass Stop DI-8 Alarm Action
0.0 Sec DI-9 Enable Delay
0.0 Sec DI-9 Trip Delay
0 3 Ea DI-9 Max Restarts
3 30 Min DI-9 Restart Delay
Bypass Stop DI-9 Alarm Action
10.0 Sec DI-10 Enable Delay
30.0 Sec DI-10 Trip Delay
0 3 Ea DI-10 Max Restarts
3 30 Min DI-10 Restart Delay
Bypass Stop DI-10 Alarm Action

Page 9
Wood Group ESP - Chad
Exxon-Mobil Chad Vector Drive Shop Testing

DATE:
CONTROLLER SETUP

7 - Alarm Setpoints Display 7 - Alarm Setpoints Display


DH Analog Limit Alarms Definition DH Analog Limit Alarms Definition
Setup Default Parameter Register Setup Default Parameter Register
0.0 AI 09 Lo SP 0.0 AI 13 Lo SP
0.0 Sec AI 09 Lo EN Delay 0.0 Sec AI 13 Lo EN Delay
0.0 Sec AI 09 Lo Trip Delay 0.0 Sec AI 13 Lo Trip Delay
0 Accel Table 0 Accel Table
0 3 Ea AI 09 Lo Max Rstrts 0 3 Ea AI 13 Lo Max Rstrts
3 30 Min AI 09 Lo Rstrt Delay 3 30 Min AI 13 Lo Rstrt Delay
Bypass Bypass AI 09 Lo Action Bypass Bypass AI 13 Lo Action
0.0 AI 09 Hi SP 0.0 AI 13 Hi SP
0.0 Sec AI 09 Hi EN Delay 0.0 Sec AI 13 Hi EN Delay
0.0 Sec AI 09 Hi Trip Delay 0.0 Sec AI 13 Hi Trip Delay
0 Accel Table 0 Accel Table
0 3 Ea AI 09 Hi Max Rstrts 0 3 Ea AI 13 Hi Max Rstrts
3 30 Min AI 09 Hi Rstrt Delay 3 30 Min AI 13 Hi Rstrt Delay
Bypass Bypass AI 09 Hi Action Bypass Bypass AI 13 Hi Action
0.0 '% AI 09 Hi Warn Band 0.0 '% AI 13 Hi Warn Band
0.0 AI 10 Lo SP 0.0 AI 14 Lo SP
0.0 Sec AI 10 Lo EN Delay 0.0 Sec AI 14 Lo EN Delay
0.0 Sec AI 10 Lo Trip Delay 0.0 Sec AI 14 Lo Trip Delay
0 Accel Table 0 Accel Table
0 3 Ea AI 10 Lo Max Rstrts 0 3 Ea AI 14 Lo Max Rstrts
3 30 Min AI 10 Lo Rstrt Delay 3 30 Min AI 14 Lo Rstrt Delay
Bypass Bypass AI 10 Lo Action Bypass Bypass AI 14 Lo Action
0.0 AI 10 Hi SP 0.0 AI 14 Hi SP
0.0 Sec AI 10 Hi EN Delay 0.0 Sec AI 14 Hi EN Delay
0.0 Sec AI 10 Hi Trip Delay 0.0 Sec AI 14 Hi Trip Delay
0 Accel Table 0 Accel Table
0 3 Ea AI 10 Hi Max Rstrts 0 3 Ea AI 14 Hi Max Rstrts
3 30 Min AI 10 Hi Rstrt Delay 3 30 Min AI 14 Hi Rstrt Delay
Bypass Bypass AI 10 Hi Action Bypass Bypass AI 14 Hi Action
0.0 '% AI 10 Hi Warn Band 0.0 '% AI 14 Hi Warn Band
0.0 AI 11 Lo SP 0.0 AI 15 Lo SP
0.0 Sec AI 11 Lo EN Delay 0.0 Sec AI 15 Lo EN Delay
0.0 Sec AI 11 Lo Trip Delay 0.0 Sec AI 15 Lo Trip Delay
0 Accel Table 0 Accel Table
0 3 Ea AI 11 Lo Max Rstrts 0 3 Ea AI 15 Lo Max Rstrts
3 30 Min AI 11 Lo Rstrt Delay 3 30 Min AI 15 Lo Rstrt Delay
Bypass Bypass AI 11 Lo Action Bypass Bypass AI 15 Lo Action
0.0 AI 11 Hi SP 0.0 AI 15 Hi SP
0.0 Sec AI 11 Hi EN Delay 0.0 Sec AI 15 Hi EN Delay
0.0 Sec AI 11 Hi Trip Delay 0.0 Sec AI 15 Hi Trip Delay
0 Accel Table 0 Accel Table
0 3 Ea AI 11 Hi Max Rstrts 0 3 Ea AI 15 Hi Max Rstrts
3 30 Min AI 11 Hi Rstrt Delay 3 30 Min AI 15 Hi Rstrt Delay
Bypass Bypass AI 11 Hi Action Bypass Bypass AI 15 Hi Action
0.0 '% AI 11 Hi Warn Band 0.0 '% AI 15 Hi Warn Band
0.0 AI 12 Lo SP 0.0 AI 16 Lo SP
0.0 Sec AI 12 Lo EN Delay 0.0 Sec AI 16 Lo EN Delay
0.0 Sec AI 12 Lo Trip Delay 0.0 Sec AI 16 Lo Trip Delay
0 Accel Table 0 Accel Table
0 3 Ea AI 12 Lo Max Rstrts 0 3 Ea AI 16 Lo Max Rstrts
3 30 Min AI 12 Lo Rstrt Delay 3 30 Min AI 16 Lo Rstrt Delay
Bypass Bypass AI 12 Lo Action Bypass Bypass AI 16 Lo Action
0.0 AI 12 Hi SP 0.0 AI 16 Hi SP
0.0 Sec AI 12 Hi EN Delay 0.0 Sec AI 16 Hi EN Delay
0.0 Sec AI 12 Hi Trip Delay 0.0 Sec AI 16 Hi Trip Delay
0 Accel Table 0 Accel Table
0 3 Ea AI 12 Hi Max Rstrts 0 3 Ea AI 16 Hi Max Rstrts
3 30 Min AI 12 Hi Rstrt Delay 3 30 Min AI 16 Hi Rstrt Delay
Bypass Bypass AI 12 Hi Action Bypass Bypass AI 16 Hi Action
0.0 '% AI 12 Hi Warn Band 0.0 '% AI 16 Hi Warn Band

Page 10
Wood Group ESP - Chad
Exxon-Mobil Chad Vector Drive Shop Testing

DATE:
CONTROLLER SETUP

8 - Input Calibration Display 9 - System Parameters Display


Transformer Ratios Setup Default Parameter Register
Setup Default Parameter Register 0 Change Level 0 PW
xfmr tap 1 Downhole No Enable Termiflex Scan
5 300 CT Amps:5 Com 1 - On Board Serial Ports
480 V 0 Volts PT Volts:120 Setup Default Parameter Register
Calibrate AC Values 19200 9600 Baud
Setup Default Parameter Register None Parity
0 Amps Ia Meas 8 Bits Data
Ib Meas 1 Addr
Ic Meas Modbus RTU Protocol
Meas V 0 Volts Vca Meas Normal Modbus Mapping
Meas V 0 Volts Vab Meas 50 mSec 100mSec RTS On Delay
Meas V 0 Volts Vbc Meas 20 mSec 50 mSec RTS Off Delay
No Apply Calibration No Password Required
Calibrate Analog Values Com 2 - On Board Serial Ports
Setup Default Parameter Register Setup Default Parameter Register
Point # 19200 9600 Baud
Input Value None Parity
Apply Calibration 8 Bits Data
Cal Freq Out Control control net id 1 Addr
Modbus RTU Protocol
16 bit Normal Modbus Mapping
100mSec RTS On Delay
50 mSec RTS Off Delay
No Password Required
On Board Serial Ports
Setup Default Parameter Register
&K0X3 Modem Init String
No Enable Com Relay

Page 11