October 2016
Water Mist BIF No 9
1
fire suppression systems depends on the ability of the fire
water to conduct away heat. The CPVC supplier should
Table 1 : Water mist system components
be contacted for advice prior to specifying its suitability in consist of the same three main parts as a
water mist systems in terms of pressure limits and flow rates. sprinkler/waterspray system
It is a characteristic of the mechanisms by which
water mist controls or extinguishes fires that the mist
generated consists of a range of small droplets. These small, A water supply Usually a pumped supply with strainers
lightweight, droplets remain airborne longer and to some to prevent clogging of nozzles or a rack
degree will swirl around obstructions, as well as being drawn cylinders containing water pressurised by
into combustion air streams. stored gas in high pressure cylinders
High heat release fires can enable conversion of these An alarm To provide a local alarm, in case of
small droplets into steam enabling fire to be extinguished by system activation
oxygen displacement at the flame front. The mist, delivered
at high momentum to be effective, can be affected by a A distribution Pipework (copper, stainless or galvanised
series of physical conditions including air movement, either system steel) and nozzles which activate
natural or forced and even by the fire dynamics2 automatically, either individually (after
operation of the heat sensing element in
Boundary conditions affect water mist dispersion so
the nozzle) or all at the same time following
applications in smaller rooms, such as bedrooms, and operation of a fire detection system where
protection effectively in open areas each need to be tested open nozzles have been specified. The
to verify performance. Extrapolation of test parameters and nozzle design in combination with the
results is generally not permissible. correct water pressure creates a range of
Serious concerns regarding the ‘ad hoc’ nature of hybrid small mist droplets which attack the fire.
systems3 have been expressed by a number of authorities
and industry members mainly due to the use of uncertified
components and lack of system test data. To obviate this,
it is suggested that the checklist provided in Table 4 below
should be used when considering the use of a mist system.
Table 2 : Water mist systems
Water mist for Residential and Domestic generally fall into one of two categories
Applications, and for Commercial and
Industrial applications Low Pressure High Pressure
BAFSA recommends where there is an intention to install a
water mist system in a residential occupancy the design and Head pressure, typically 5-10 Head pressure typically not
bar but less than 12 bar Steel less than 35 and usually at
installation must comply with BS 8458 2016.
or copper – pipework 20 – least 50 bar.. For cylinder
BAFSA recommends where there is an intention to 65mm based systems, system
install a water mist system in a commercial occupancy the pressure may be up to 200 or
design and installation must comply with BS 8489 2016. Normally use stored even 300 bar Smaller bore,
Part 1 sets out the design and installation requirements, with water and electric pumps stainless pipework, typically
subsequent parts providing fire test criteria for turbines, Maintenance schedule similar 12mm – 30mm.
to sprinkler/waterspray
industrial oil cookers, local applications, and low hazard
systems Can be either stored water
applications. Other fire test protocols may also be used. (tanks) & high pressure
The installer must be listed under a water mist specific Fire service may be able to pumps, or high pressure
third party certification scheme. supplement stored water cylinders Maintenance
Forthcoming guidance from BAFSA should be followed, supply by pumping-in schedule similar to sprinkler/
as should the system or component, manufacturer’s subject to availability of waterspray systems
connections. Can share water
specifications. As always, insurers’ views should be sought for
supply with other water Fire service may be able to
properties where they have an interest before any contract is based fire protection system supplement stored water for
entered into (See below, Insurers’ Views). (but in the case of sprinkler tank systems provided filters
The end-user or occupier should be made aware of the systems this would create a are in place.. Cylinder systems
necessary maintenance regime. non compliance with BS EN cannot share existing water
It should be noted that as at the time of writing, the 12845) Nominal water flux supplies with other water
density typically 2 – 3.5 lpm/ based fire protection. Typical
range of mist heads available cannot be fully concealed (as
m3 Wet and dry systems water flux density 1 – 2 lpm/
available (dry using separate m3
2 Jackman L and Annable K: 2010.’Hence water mist system fire detection)
designs for larger spaces will often require Wet and dry systems available
(dry using separate fire
3 ‘Hybrid systems’ are those where, for example, a range of detection)
components is sourced from different manufacturers or suppliers,
some of which may not intended or suitable for the type of
use being considered. (Eg mist heads listed for marine use but
installed in a residential system).
2
Table 3 : Standards for Mist Systems can sprinkler heads) and that the use of recessed mist heads
should comply with the manufacturer’s technical data and
the requirements of the AHJ.
Document Description
Published Standards and Specifications
BS 8489 part 1: Standard providing guidance At present, there are a number of standards and other
2016 for the design, installation and documents applicable to water mist technology for land
maintenance of water mist systems based applications and a summary of these is given below.
for commercial and industrial The water mist industry has grown from a small base from
risks. Must be read in conjunction twenty five years ago and, whilst this has provided some
with the supplier design real world experience, it does not have the legacy of more
requirements. than a hundred years of test data and real-world experience
that the sprinkler industry benefits from. Thus these water
BS 8489 part 4: Test requirements for mist systems
mist standards cannot be said to provide the same proof of
2016 protecting flammable liquid fires
performance nor cover the extent of the range of hazards
BS 8489 part 5: Test requirements for mist systems included in BS EN 12845.
2016 protecting machinery spaces and It is essential that specifiers, end users and regulators
turbines up to 80m3. take great care when reviewing the performance claims of
any particular system proposed. The recently published
BS 8489 part 6 Test requirements for mist systems
BS documents are full British Standards created to reflect
2016 protecting industrial oil cookers.
industry best practice. At present the CEN water mist
BS 8489 part 7: Test requirements for water mist document, EN TS 14972, is a ‘Technical Specification’ and
2016 systems for the protection of low not a European Standard and is envisaged to be several years
hazard occupancies. away from being so. Various American documents also cover
watermist. NFPA 750 code covers the design and installation
BS 8458: 2016 Standard providing guidance
of mist systems in accordance with manufacturers’ design
for the design, installation and
manuals. Underwriters Laboratories (UL) 2167 covers test
maintenance of water mist
protocols for various hazards (see Table 3). Factory Mutual
systems for residential and
(FM) 5560 sets out the design and test requirements for
domestic premises. Must be read
systems underwritten by them (see Table 3).
in conjunction with the supplier
design requirements.
Suitable Applications for Water Mist
EN/TS 14972 European technical specification The new British Standards, BS8489 and BS 8458 for both
providing guidance for the design, Industrial and commercial systems and residential and
installation and maintenance of domestic cover applications for water mist systems. The
water mist systems for commercial standards also include test criteria that are applicable for
and industrial risks. Must be read product to be tested against to confirm the suitability of the
in conjunction with the supplier system for use in that particular application.
design requirements. Where the standards do not cover specific applications
FM 5560 Test standard for water mist it is imperative that any proposed system is certificated or
systems covering machinery listed by a suitable approvals scheme for which there is full-
spaces, combustion turbines, scale successful test data and the test/s and data are directly
light hazard, wet benches, local applicable to the intended occupancy.
application, oil cookers, sub-floors Premises such as warehouses and large industrial
and chip board presses. buildings are not currently deemed suitable for protection
by water mist systems, however, development work is
FM DS 4-2 Guidance on installation of ongoing so it is essential to check with the proposed system’s
systems approved to FM 5560. manufacturer or supplier for information on which types
UL 2167 Test standard for water mist of hazards their systems are deemed to be suitable and for
systems covering machinery which applications their systems are certificated.
spaces, combustion turbines, Insurers’ views should be sought for properties where
light hazard, ordinary hazard and they have an interest before any contract is entered into (See
residential below, Insurers’ Views).
3
Certification (using the LPCB brand) may be setting up a References
similar installers’ scheme and also developing a scheme to Jackman C and Annable K: ‘Research testing with water
complement their testing and certification of components. mist systems for commercial office buildings’ 24 March
In order to discharge their duty under the Regulatory 2010. http://www.info4fire.com/in-depth-content/full/
Reform (Fire Safety) Order 2005 (in England and Wales research-testing-with-water-mist-systems-for-commercial
– similar but different legislation applies in Scotland and -office-buildings
Northern Ireland) successfully, persons deemed to be
dutyholders ie ‘Responsible’ or ‘Competent’ persons under the BAFSA recommends that specifiers and end-users use
Order should be aware that utilisation of third-party, certified the following checklist:
installers and suppliers is the most effective way to be sure
that the specified duties in respect of fire protection systems
intended for the safety of life has been complied with. Civil
and criminal liabilities may attach where systems intended for Checklist for specifiers and end-users
the protection of life fail to operate as intended due to non- when reviewing water mist proposals
compliances with published standards or the manufacturers
instructions. In addition, the use of non-approved or non-
certificated systems may result in a breach of insurance policy Has the system been tested and approved by a third
wordings and result in the denial of a claim. party approval body such as LPCB, VdS, UL or FM
for the specific application intended?
Insurers’ Views Has all testing been carried out by a capable
In the UK insurers play a leading role in the specification laboratory such as BRE, FM, UL, SINTEF, VdS, SP,
of fire suppression systems and they have a great deal of VTT or CNPP?
experience in this area. Until recently, most insurers were
unwilling to consider the installation of mist systems. Whilst Are products and components specific to the system
some water mist applications have gained ready insurer approved for such use by a qualified third party
acceptance for hazards such as industrial oil cookers and approval body?
combustion turbines, some insurers still express concerns
regarding their lack of real fire experience of mist systems Can all claims made by the system supplier be verified?
and are unwilling to issue blanket approvals for the use of Is there a formal agreement between manufacturer
water mist. and installer? Has the installer received training from
Where insurers are likely to have an interest in the levels the manufacturer?
of protection for a new building or structure it is essential
to determine their views before any fire suppression systems Does the testing and approval data correspond to the
are procured. Failure to do so can result in denial of a claim. intended use of the system?
It should be remembered that insurers tend to adopt very
Does the geometry of the space to be protected,
conservative approaches to new technology so in the case
including ceiling height, correspond to the testing
of proposals to install protection that falls outside the
and approval data?
bounds of recognised fire tests nor include extrapolations,
or unwarranted assumptions. Where insurers are the AHJ, ensure compliance with
While there may be systems that have non-UK 3rd party the insurer’s requirements /questionnaire / checklist.
approvals for specific applications and sizes, these will be
specific to the individual systems tested so that specifiers,
users and authorities having jurisdiction must satisfy
Presented by:
themselves that the approvals claimed are relevant to the
specific application.
The Fire Protection Association in support of the
insurers’ group, RISC Authority, have developed a series
of questionnaires for use by those offering, procuring or
approving the installation of water mist systems. At present
these address both pre-purchase considerations as well as post
contract design details. These very comprehensive documents
can be downloaded at no cost from www.riscauthority.co.uk.