Vous êtes sur la page 1sur 3

1809 10th Street, Suite 400

Plano, TX, 75074

Telephone: (972) 202-8800


Facsimile: (972) 202-8801
www.intertek.com

08/28/12
Revised:03/31/2016 Letter Report No: 100651474DAL-001
Project No. G100651474

Mr. Ahmad Arabiat Phone: 96264050940


PO Box 141351 Fax: 96264051086
Amman - 11814 E-mail: a-arabiat@petra-eng.com.jo

Subject: Compliance Report for “NEMA Type 4X Enclosure” evaluation of Power Box, Control Box and Power
Factor Box.

Dear Mr. Arabiat,

This letter represents the results of the evaluation of the above referenced equipments to the requirements
contained in the following standards:

• Standard for Safety Enclosures for Electrical Equipment Non-Environmental Considerations, UL 50,
Issued:2007/09/04 Ed:12 /CSA C22.2 No. 94.1-07 First Edition

• Standard for Safety Enclosures for Electrical Equipment, Environmental Considerations, UL 50E,
Issued:2007/09/04 Ed:1/ CSA C22.2 No. 94.2-07 First Edition

This investigation was authorized by Petra R&D; application Q500359203 dated 02/10/2012. Production sample,
Model Power Box, ID No. DAL1208151040-001, was received on 08/15/2012 and 03/24/2016. The Power Box
sample and the design of the Control box, and Power factor box were evaluated 08/23/2012 to 08/28/2012 at the
Intertek, Dallas facility.

As per the evaluation conducted all three enclosures meets the requirement of “NEMA Type 4X Enclosures”. Only
the Power Box enclosure was evaluated, however construction of the Power Box enclosure represents the
Control Box and Power Factor Box.

MODEL SIMILARITY:

Width (mm) Height (mm) Depth (mm) Thickness (mm)


Smallest Panel 300 500 150 1.25
Biggest Panel 2000 2500 400 1.5

Following tests were performed on Power Box enclosure for compliance.


UL 50/ UL 50E/
Test Description CSA C22.2 No. 94.1 CSA C22.2 No. 94.2

Hosedown test N/A 8.6

Page 1 of 3

This report is for the exclusive use of Intertek’s Client and is provided pursuant to the agreement between Intertek and its Client. Intertek’s responsibility and liability are limited to the terms
and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the agreement, for any loss, expense or damage occasioned by the use
of this report. Only the Client is authorized to permit copying or distribution of this report and then only in its entirety. Any use of the Intertek name or one of its marks for the sale or
advertisement of the tested material, product or service must first be approved in writing by Intertek. The observations and test results in this report are relevant only the sample tested. This
report by itself does not imply that the material, product or service is or has ever been under an Intertek certification program.

Intertek Testing Services NA, Inc. SD 12.1.2 8/10/10) Informative


Petra Engineering Industries Company Letter Report: 100651474DAL-001
08/28/2012
Revised: 03/31/2016

Following components are to be considered as critical components.


# Component Manufacturer Model no. Technical specification Marks of
conformity
1) Enclosure Box Petra Various Painted Galvanized steel. Constructional
Engineering Flange dimensions:30mm.
Dimensions:

1) Power Box:
1700mmHX1160mmWX370mm,

2) Control box:
700mmHX760mmWX370mmD.

3) Power Factor Box:


700mmHX960mmWX350mmD
2) Enclosure door Petra Various Painted Galvanized steel. Constructional
Engineering Dimensions:

1) Power Box: 1700mmHX1160mmW,.

2) Control box: 700mmHX760mmW.

3) Power Factor Box:


700mmHX960mmW,
3) Hinges Industrilas 321331 Zinc die-cast chrome, 61mm long, 15mm Constructional
dia, using four M5 screws.
4) Gasket Industrilas 427042 EPDM rubber, 50°C - 15 0°C RU
5) Cable glands KSS AG series Mounting hole diameter range: 12mm to RU
61mm, Flammability rating V-2, IP68
rated
6) Tubings Guangzhou NL206 Polymide 6 material, temperature ratings: RU
Jieyin Electric series -40C to 120C, IP68 rated
Appliances
Co. Ltd.
7) ON/OFF ABB OHB65L6 Pistol Handle, Rated for NEMA type 4X. UL
Handle

Photos:

Page 2 of 3

Intertek Testing Services NA, Inc. SD 12.1.2 (8/10/10) Informative


Petra Engineering Industries Company Letter Report: 100651474DAL-001
08/28/2012
Revised: 03/31/2016

Note: All control panels shall be marked with “TYPE 4X ENCLOSURE”.

If there are any questions regarding the results contained in this report, or any of the other services offered by
Intertek, please do not hesitate to contact the undersigned. Please note, this Letter Report does not represent
authorization for the use of any Intertek certification marks.

Completed by: Jigneshkumar Dabhi Reviewed by: Jeremy Maxwell


Title: Compliance Investigator Title: Compliance Investigator

Signature: Signature
Revised by: Ramzi Amawi Reviewed by: Sudesh Kamble
Title: Director of Operations Title: Sr. Staff Engineer

Signature: Signature

Page 3 of 3

Intertek Testing Services NA, Inc. SD 12.1.2 (8/10/10) Informative

Vous aimerez peut-être aussi