Académique Documents
Professionnel Documents
Culture Documents
The LV installation which forms the subject of this study is shown in figure 1
above. This study includes discrimination and coordination of protection
between the LV equipment and the protection located upstream of each MV/LV
power supply transformer.
Figure 1 - Installation example (with 1600 kVA MV/LV transformers) with
indication of the order in which discrimination is examined
The selections refer to Schneider Electric circuit breakers (Master pact NW
and Compact NSX type).
The installation includes 2 medium voltage 20 kV incoming lines protected by a
fuse, each equipped with an MV/LV transformer with characteristics 20 kV/410
V, 1600 kVA, and an incoming LV circuit breaker (A) or (B). A section switch
(C) can be used to operate both parts of the installation together or separately,
in order to optimize availability of power in the event of failure of one of the two
incoming lines.
Contents
1. Dimensioning the protective equipment
1. Rating of devices (A) and (B) installed on LV incoming lines
2. Rating of fuses installed on MV incoming lines
3. Breaking capacity for the various devices
1. Determining the short-circuit currents at different points in the
installation
2. Selecting breaking capacity
2. Selecting devices to ensure discrimination
1. Principle
2. Discrimination between circuit breakers (F) and (D)
3. Discrimination between circuit breakers (G) and (E)
4. Discrimination between circuit breakers (E) and (C)
5. Discrimination between circuit breakers (D) and (C)
6. Discrimination between circuit breakers (C) and (B) or circuit breakers (C)
and (A)
7. Discrimination between circuit breakers (A) or (B) and MV fuses
1. Settings for standard selective trip units
2. Settings for trip units with IDMTL curves
Given the cable impedances, the short-circuit current crossing the circuit
breakers located at (F) and (G) is no more than approximately 50 kA.
Go back to contents ↑
CBs (D) and (E) must have a breaking capacity higher than 72 kA,
CBs (A), (B) and (C), a breaking capacity higher than 36 kA is adequate.
CBs (F) and (G) must have a breaking capacity of 50 kA minimum.
Go back to contents ↑
Go back to contents ↑
Go back to contents ↑
Go back to contents ↑
Go back to contents ↑