1. ALL EQUIPMENT SHALL BE INSTALLED IN APPROXIMATE LOCATIONS AS SHOWN ON THE DRAWINGS.

2. ALL EQUIPMENT SHALL BE MOUNTED ON OR SUPPORTED WITH VIBRATION ISOLATOR


UNITS OR ASSEMBLIES AS SPECIFIED AND OR AS SHOWN ON THE DRAWINGS.

73KLS RANGE HOOD


3. INSTALLATION OF ALL WORKS SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER, IMPROPERLY SET WORK
OR FINISH AS DETERMINED BY THE ARCHITECT SHALL BE REMOVED AND REPLACED AT NO EXTRA COST.

4. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND CLEAN.


DUCTING
5. DEVIATIONS AND REVISIONS FROM PLANS SHALL BE REFERRED TO THE ARCHITECT/ENGINEER FOR REVIEW AND APPROVAL.
3 STOCK ROOM
M1 KITCHEN AREA
6. ALL DIMENSIONS ARE IN MILLIMETER UNLESS OTHERWISE SPECIFIED. SCALE NTS

7. ALL MECHANICAL WORKS SHALL BE IN ACCORDANCE WITH THE LATEST MECHANICAL ENGINEERS CODE AND STANDARD. REST ROOM

8. MECHANICAL CONTRACTOR SHALL VERIFY SITE PRIOR TO ACTUAL INSTALLATION.


DISHWASHING
9. THE MECHANICAL CONTRACTOR SHALL CONDUCT TESTING, BALANCING AND COMMISSIONING OF ALL THE HVAC EQUIPMENT. AREA

10. KITCHEN EXHAUST AIR DUCT SHALL BE G.I SHEET GA #20 FOR FRESH AIR, GA #18 FOR EXHAUST DUCTS
INSULATED WITH 50mm THK, 48 KG/CU.M DENSITY WITH ALUMINUM FOIL VAPOR BARRIER FIBERGLASS BOARD.
EE ROOM
CHARCOAL
11. ALL EXHAUST AND FRESH AIR DUCTS SHALL BE AS PER STANDARD USING OF G.I SHEET GALVABOND MATERIALS. AREA
OFFICE AREA

RANGE HOOD
12. ALL VENTILATING EQUIPMENT CONTROL PANEL SWITCH SHALL BE LOCATED AT LOCATION SPECIFIED

BY THE PROJECT-IN-CHARGE.

13. AS-BUILT PLANS SHALL BE SUBMITTED BY THE AWARDED CONTRACTOR AFTER COMPLETION OF WORKS.

14. SUPPLY, EXHAUST AND FRESH AIR GRILLES/DIFFUSERS SHALL BE PROVIDED WITH VOLUME CONTROL DAMPER. 8
M1 SCALE 1:100
15. EXHAUST AND FRESH AIR BLOWER MOTOR SHALL BE "WEG" JAPANESE OR U.S BRAND.
SCHEDULE OF CENTRIFUGAL FAN
AND BLOWER
16. EXHAUST SYSTEM AND EXHAUST HOOD SHOULD BE PROVIDED WITH FILTER AND OIL COLLECTOR.
EQUIPMENT QTY. D E S C R I P T I O N

17. EXHAUST AND FRESH AIR BLOWER SHALL BE PROVIDED WITH STEEL PLATFORM AT THE EXPENSE OF CENTRIFUGAL EXHAUST BLOWER / KTM-270-CB (BI) (SISW) , 27" WHEEL DIA.
WITH CAPACITY OF 7500 CFM x 2" S.P. MADE OF B.I SHEET MATERIALS.
THE MECHANICAL CONTRACTOR. CEB - 1 1 STATICALLY AND DYNAMICALLY BALANCED. PAINTED W/ 2-COATS OF EPOXY PRI.
INDUSTRIAL PAINT FINISHED. V-BELT DRIVEN BY 7.5HP, 3-PHASE, 220V, 60Hz,
1750 RPM TEFC WEG ELECTRIC MOTOR.
18. THE PLANS ARE DIAGRAMMATIC LAYOUTS ONLY, ANY MATERIALS AND FITTINGS NOT SHOWN OR NOT SPEFICIED
FRESH AIR BLOWER / KTM-270-CB (BI) (SISW) , 24" WHEEL DIA.
FAB - 1 1 WITH CAPACITY OF 6000 CFM x 1.5" S.P. V-BELT DRIVEN BY 5HP
SHALL BE INCLUDED WITH CONTRACTOR SCOPE OF WORKS TO COMPLETE THE SYSTEM AND OPERATIONAL. 3-PHASE, 220V, 60Hz, 1750 RPM TEFC WEG ELECTRIC MOTOR.

4
M1 SCALE NTS

73KLS RANGE HOOD


5
M1 SCALE NTS

DUCTING

STOCK ROOM
KITCHEN AREA

REST ROOM

DISHWASHING
AREA

SCHEDULE OF EXHAUST AND FRESH AIR


DUCT GAUGES AND HANGERS EE ROOM
DIMENSION G.I SHT SIZE OF SUPPORT DISTANCE CHARCOAL
LONGEST U.S STD ANGLE BAR OF HANGERS
AREA
SIDE GAUGES ( mm ) ( mm ) OFFICE AREA

RANGE HOOD
UP TO 300 26 25 x 25 x 3 1200

325 TO 750 24 38 x 38 x 4 1200

775 TO 1500 24 38 x 38 x 4 1200


1525 TO 2550 20 50 x 50 x 6 1200

1 2 6 7 9
M1 SCALE 1:100
M1 SCALE NTS M1 SCALE NTS M1 SCALE NTS M1 SCALE NTS