Académique Documents
Professionnel Documents
Culture Documents
【versions:V1.0】
Catalog
Motor Setting............................................................................................................................... - 10 -
IO Setting ...................................................................................................................................... - 12 -
- 1 -
Physical Interface RS-485,RS-232
Main Interface
Current sorting
weight
System Setup
System settings require login privileges. Different permissions will display different
settings. The default login information is as follows:
Password:000000(Default password)
- 2 -
About HMI
Restore module default parameters: input 123456 can restore the default
parameters of the module and restart the module
Update Control Module program: Enter 123456 to update the control module program.
Support language: the module supports both Chinese and English languages.
Manufacturer Information: you can enter factory information for the equipment, you
can fill in the equipment model, the name of the equipment manufacturer.
- 3 -
Formula Setting
The system can support up to 20 formulations, change the formula name and quantity unit,
and set the corresponding speed and precision of the equipment for different formulations.
Unit of quantity: the default unit of quantity is package, which can be changed to achieve
different formulations showing corresponding units of quantity. The units of quantity supported
Weight measuring speed: the speed of disc motor can be set to realize the speed control
Re-weighing threshold: when the weight is greater than the threshold, the system
average compensation mode, and set the percentage of valid data, usually 50%.
- 4 -
Dynamic compensation weight: when the dynamic weight deviation occurs, the dynamic
Step-by-step action delay: the delay time corresponding to a certain detection action,
usually after changing the speed of the classification motor, the corresponding delay time
action, the specific execution time usually depends on the way and structure of the mechanical
part.
Grading minimum: the minimum value of the weight eligible range of the weighing object,
Classification maximum: the maximum value of the weight eligible range of the weighing
Maximum number of sub-silos: when the cumulative number of the detection results is greater
than the system alarm, the default value of 0 means that the function will not be started.
Maximum weight of sub-silos: when the cumulative weight of the inspection results is
- 5 -
greater than this, the system alarms, default is 0 means that the function will not be started.
Weighing Setting
Load scale: weighing is placed on the scale platform for calibration and calibration.
The calibration flow description: (1) Enter the weight value (2) to clear the item of the
weighing table and then point the calibration (3) to the weight (4) point with the corresponding
weight value to load the calibration, then remove the weight and complete the calibration.
Manual zeroing range: sets the range of manual zeroing (relative to the percentage of the
maximum quantum range), deters manual zeroing by default, and runs the main interface without
a clear button;
Feeding action delay: after the set time is extended, the tray is loaded
- 6 -
Devices Setting
Full scale: It is the largest weighing range of weighing platform. It can choose weight
units, support g
and kg.
Division value: For smooth display of weight value, can achieve stable weight display
/ 20g. Default is 0. 1 g.
Photoelectric mode: depending on the photoelectric access mode of the equipment, it can
be set up without photoelectric mode, double photoelectric mode, photoelectric entry mode,
- 7 -
Display Decimal: you can set the decimal place of display weight, can be set to no
Slave address: set touch screen 485 interface MODBUS,RTU slave address, baud rate is
IO start / stop mode: the system can access the external start / stop button, select the
start / stop mode according to different button types, optional level mode and pulse mode.
IO pause / resume mode: the system can access the external pause / resume button and
IO purge overflow alarm: the system can access the external purge overflow alarm status
button (effective when the overflow alarm in the formula is turned on), select stop mode
IO Peeling Mode: The system can access the external button to clear the tare weight, and
IO zero-clearing mode: the system can access zero-clearing external buttons, depending
Cumulative overflow alarm time: The duration of the overflow alarm can be specified by
- 8 -
setting this value, in milliseconds, that is, the output duration of the corresponding IO
Continuous failure alarm: when the corresponding check result is continuously counted to
the set number, the system alarms, and the function of the alarm when the continuous N-packet
alarm, and can be classified at the same time; orange is selected, and the classification is
given alarm.
Feeding action delay: after the set time is extended, the tray is loaded
Feeding action execution: time for pallet feeding
Grade 1 pallet position: grade 1 action pallet sequence number, initial position detection
Grade 2 pallet position: grade 2 action pallet sequence number, initial position detection
- 9 -
detection pallet number 1, added in turn.
Grading 4 pallet position: grade 4 action tray sequence number, the initial position
Grading 5 pallet position: grade 5 action tray sequence numberthe initial position
Grading 6 pallet position: grade 6 action tray sequence number, the initial position
Grading 7/8/9 pallet position: grade 7/8/9 action tray sequence number, the initial
Grading 10 pallet position: grade 10 action tray sequence number, the initial position
Motor Setting
Communication baud rate: used to set the communication baud rate and check bit of the
- 10 -
module. If the frequency converter is connected to the converter, the baud rate of the converter
must be the same as that of the converter, the slave address of the feed converter is 1, and
the address of the transducer on the scale platform is 2. The address of the elimination
inverter is 3.
Motor register address setting: RS485 Modbus RTU communication. Frequency register address,
start value and stop value, direction register address, forward value and reverse value can
be set respectively.
Speed Correction
- 11 -
Disc motor: Input height voltage, frequency value, and then point start, how to write
to the actual speed.
Enter medium voltage, frequency value, and then point start, how to write to
the actual speed.
Enter a low voltage, frequency value, and then point start, how to write to
the actual speed.
IO Setting
IO Setting:You can debug by clicking on the corresponding IO port number, which indicates
- 12 -
Y0~Y11 function: can set each IO port corresponding output function, the output port can
be set to: start-up operation, stability indication, zero-bit indication, feeding action,
8, 9, 10.
X0~X5 function: can set each IO port corresponding input function, input port can be set
to: start / stop button, pause / resume button, peeling input, zero input, clear alarm, pallet
Report Statistics
Data report: all weight check data will be viewed, corresponding to 1 / 10 level.
- 13 -
Delete Earliest Data: The oldest data in the file will be deleted.
Interface Specification
- 14 -
B RS485 communication negative pole B terminal
The rated power supply voltage is 24 VDC and the rated current is 250 mA.
The instrument shielded (SH) can be connected to the external shielded wire or to the
negative (GND) of the instrument power supply. By default, the NH end and the GND end are
short connected with the 0R resistance when they leave the factory, but the external shield
is not connected. If the external shield is connected, the resistance should be removed.
RS232 communication interface is a standard MODBUS interface, used to set the internal
parameters of the instrument. The default communication baud rate is 115200, and the check bit
is even check.
RS485 communication is used to drive the frequency converter to control the speed of the motor.
Communication baud rate is 9600, even check, transmission protocol is standard MODBUS protocol.
The excitation voltage of the sensor is 5V DC. The instrument uses the sensor 1 signal
Switch input: 6, the function of each input can be set in the IO setting interface.
- 15 -
Input common end: common power supply (COM connection power), common power supply-(COM
connection power supply -), X0-X2 common com 1 terminal, X3-X5 common com 2 terminal.
(Internal diagram)
The analog output is the analog voltage output, and the output range is 0-5VDC, which is mainly
used for controlling the DC motor controller to control the rotation speed of the motor.
Ethernet port:
Quantity Way
2 Can realize concatenation or redundant communication in daisy chain
mode
- 16 -
DB9 Port:
There are 12 IO ports, among which Y10 and Y11 are high speed output ports, the highest
output frequency can be up to 100 KHz, and the functions of each input port can be set up
in IO interface.
- 17 -
(Internal Diagram)
- 18 -