Vous êtes sur la page 1sur 35

Perkins Logic Control

Governors (LCG1&2)
Kit Pour l’ancien LCG1
Programming LCG1 connection
Ignition on/off switch
Lead

12v Supply

Magnetic Pick-Up
& ignition/power
PC connection
LCG Sans couvercle et sans
régulateur
Metering valve link arm

Governor Spring
Installation du LCG1
Actuateur
Schéma de cablage LCG1
12 1 +12v
LCG power
MPU +ve 11 2 0v

10 3
+12v for lower speed MPU -ve

9 4 +12v for raise speed

8 5

+12v for 1800 rpm (60Hz)


7 6

0v for 1500 rpm (50Hz)

Note: Speed changes cannot be


made when the engine is
running. The speed setting must
be chosen before supplying
power to the LCS (pin 1 and 2)
Load Sharing

0v to +5v input
or
-3v to +3v input
Getting Started – Using LCG1
Software
Perkins Logic Control

Governor (LCG2)
Aperçu

Différences principales entre les


régulateus LCG 1 et LCG 2
Aperçu du LCG 2
•Improvements LCG 2 over LCG 1 include:

– Improved accuracy
– Can be adjusted ‘Live’
– Better control
– Faster processor
– More features,12/24volt, CAN,
– Better resolution (Input, Output and Setpoint)
– Fully on screen configurable
– Increased operating temperature range
– Better service/application development tool
Entrées et Sorties

• Power supply 12 or 24 Volt (10 to 32 Volt)


Must be fed directly from the battery
Unit is Reverse polarity protected.

• Speed input
– Magnetic Pick Up, MPU.
– Max Frequency 12Khz
– Signal Voltage range, 1V RMS up to 42 V RMS (Root
Mean Squared)
– Selectable number of teeth for speed pick-up (up to 255)
LCG 2 Schéma de cablage
LCG2 power
12 1 +12v/24v

MPU + 11 2

+12v to raise speed 10 3 MPU -

9 4 +12v to lower speed


LCG2 power
8 5 0v

7 6

For 1800 R/M (60Hz) 12 V Note


Speed changes cannot be made
when the engine is running

0v to +5v input The speed setting must be made


before supplying power to pins 1
or and 5
-3v to +3v input

Load Sharing
LCG 2 Adapteur pour programmation

Existing Harness

To LCG 2 Governor

RS232 - TTL converter

Lead to PC Serial Port


Programmation & Connections
Programming
Adaptor
Programming
LCG2
New Engine Loom
New 1100
Engines TTL-RS232 RS232 to PC
Programming Programming
Adaptor Pin Adaptor
1000 & old
1100 Engines. LCG2
Old Engine Loom
Aftermarket TTL-RS232 RS232 to PC
solution

Running New New Engine Loom


1100 Engines LCG2

1000 & old Pin Adaptor


1100 Engines. Old Engine Loom
Aftermarket LCG2
solution
Program Installation

• Installer le programme sur votre PC

• Connecter le PC via l’interface pour

l’alimenter et le régulateur

• Using software select calibration file

• Download calibration file to unit


Overview Screen
Quick View Area "

Overview area

Quick View Area "


Pas d’alimentation sur le
régulateur
Procedure de chargement de
la configuration dans le
régulateur LCG2
Choisir
l’emplacement
dans lequel
vous avez
sauvegarder le
fichier
Controle du fichier
configuration dans le
régulateur LCG2
Vérifier les PID (Proportional
Integral and Derivative
settings)
Overview screen

Vous aimerez peut-être aussi