Académique Documents
Professionnel Documents
Culture Documents
Hyosung Kim
Kongju National University
275 Budae, Cheonan, Chungnam, 330-717 Korea
Tel.: +82 / (41) 521-9167
Fax: +82 / (41) 563-3689
E-Mail: hyoskim@kongju.ac.kr
URL: http://control.kongju.ac.kr
Acknowledgements
This research was supported by Basic Technical Research Program in 2012 funded by Korea Electric
Power Company (KEPCO) (No. R13TA04).
Keywords
«DC power supply», «Magnetic device», «Safety», «Circuit Breaker», «Arc extinguisher»
Abstract
Removing the fault current in DC circuits is comparably difficult since the DC current has
non zero-crossing point like in AC current [1,2]. Thus, developing dedicated DC circuit
breakers is necessary to get safety for human body and electrical facilities [3,4]. This paper
proposed a novel DC circuit breaker against inductive loads. The performance of the proposed
DC circuit breaker was verified by an experimental circuit breaker test system.
Introduction
There is increasing interest in DC distribution systems according to increased DC type load due to
rapid increase in digital products and expansion of DC type distributed generation technology such as
PV generation etc. [1,2]. However it is difficult to break arc current when short-circuit occurs in load
side because electric current in DC has non zero point like AC [3]. Accordingly, development of
appropriate breaking technology in DC is required in order to protect the system from fault current to
secure safety of human body, powered equipment and instruments [4].
The size of arc voltage generated between both electric contacts becomes an important variable for
circuit breaker. Breaking of short-circuit is relatively easy for AC circuit since there is a point at which
the current passes through zero for every half cycle. However for DC circuit, it is relatively difficult to
break short-circuit since high arc voltage between the electric contacts is required to attenuate the flow
of fault current which does not become zero by itself. There is possibility of large scale fire if circuit
breaker does not acquire enough arc voltage to eliminate the arc current in DC distribution network.
This is one of the important factors why popularization of DC distribution network has been reluctant
despite its many advantages.
This paper proposes arc extinguishing technique by concentrated tandem-disposed magnets for low-
voltage DC circuit breakers and also proposes ways to attenuate arc voltage by developing diode-
resistor branch for inductive loads [5,6]. Proposed theory is verified by experimental set-up for testing
inductive load DC breaking characteristics in compliance to Standard for Low-Voltage DC Power
Circuit Breakers Used in Enclosures of IEEE C37.14-2004.
The strength of magnetic force which generates magnetic arc extinguishing is proportional to the size
of magnet flux density at contact points. When single magnet is used as shown in Fig. 2a), the
effective magnet flux density reduces by being inversely proportional to the square of distance to the
contact points since magnet flux disperses in radial shape. This paper proposed tandem-disposed dual
magnets to increase the magnet flux density at contact points as shown in Fig. 2b).
(1)
(2)
As shown in Equation (2), arc voltage applied on breaker’s electric contact points reduces significantly
compared to Equation (1), due to removal of back EMF from load inductor by diode-resistor branch.
RD resistor has a major function of releasing energy that was stored in load inductor to let load current
reach to zero quickly. However, small amount of voltage drop, IRD is added to arc voltage.
Test Conditions
Experiment shall be conducted for pure resistive load and inductive load. Pure resistive load pertains to
application in digital load such as servers in internet data center (IDC) in which load current is typically
5A or below. This experiment shall test circuit breaking properties for pure resistive load of
300VDC/10A in consideration of some tolerance. Accordingly, resistive load was selected to be 30Ω to
allow 10A of electric current to circuit.
For load inductance to test breaker performance in inductive load that is generally applied such as in
homes and buildings, inductance of 600mH was applied to satisfy the time constant 0.02s ~ 0.06s of
durability test conditions for circuit breakers as outlined in IEEE Standards C37.14 [8]. Here, time
constant is calculated as shown in Equation (3). Table 1 shows parameters for circuit breaker
experiment system.
(3)
In order to reduce the long trip time, this paper conducted experiment by using electric contacts on
magnetic arc-extinguisher like the one shown in Figure 2a. As shown in Figure 8, test results showed
that trip time reduced to 15ms, which is approximately 97% improvement and also empirically
verified the excellence of electric contacts proposed in this study.
Figure 9 shows the experimental results of each arc extinguisher for electric contacts. Results of using
the proposed focused magnetic arc-extinguisher further reduced the trip time of 12ms as shown in
Figure 9a). Moreover, unstable arc voltage stabilized when using focused magnetic arc-extinguisher as
shown in Figure 9b).
Figure 11 shows test results of applying hybrid arc extinguisher as proposed in Figure 4 in order to
attenuate the occurrence of high inductive voltage from inductive loads. Through application of the
proposed hybrid arc extinguisher in DC circuit breaker, reduction in arc voltage to 311V and decrease
in trip time to 22ms were clearly observed.
Figure 12 shows the experimental result that compares the circuit breaking performance according to
contact speeds from using magnet arc extinguisher as shown in Figure 2a) and using hybrid arc
extinguisher as shown in Figure 4. As shown in previous section of the experiment, linear reduction in
trip time according to increase in contact speed was observed but there was not much relative decrease
of trip time at contact speeds higher than 100mm/sec.
Fig. 10 Experimental waveforms for Inductive load Fig. 11 Experimental waveforms for Inductive load
by magnet arc extinguishing circuit by hybrid arc extinguishing circuit
(magnet distance: 20[mm], speed: 150[mm/sec]) (magnet distance: 20[mm], speed: 150[mm/sec])
Figure 13 shows the analysis of experiment results according to contact speed and distance between
magnet and electric contact points as proposed in this study. It was observed that trip time improved as
magnet distance became nearer. However, it is not desirable to decrease magnet distance to be less
than 20mm because magnet might be damaged due to high arc current that occurs during circuit
breaking of inductive loads.
References
[1] H. Kim, “DC distribution systems and circuit breaking technology”, The Journal of the Korean
Institute of Power Electronics, Vol. 15, No. 5, pp. 40-46, 2010. 10.
[2] T. Babasaki, T. Tanaka, Y. Nozaki, T. Aoki, F. Kurokawa, "Developing of Higher Voltage Direct -
Current Power-feeding Prototype System", International Conference on INTELEC 2009. pp. 1-5,
2009.
[3] Giovanna Postiglione, DC Distribution System for Home and Office, Master thesis on Department
of Electric Power Engineering, Chalmers, Glothenburg, Sweden, 2001.
[4] K. Lee, “Prospect of DC distribution systems and safety issues”, The Journal of the Korean
Institute of Power Electronics, Vol. 14, No. 2, pp. 21-26, 2009. 04.
[5] S. Baek, T. Yuba, K. Kiryu, A. Nakamura, H. Miyazawa, M. Noritake, K. Hirose, "Development
of plug and socket-outlet for 400 volts direct current distribution system", Power Electronics and
ECCE Asia (ICPE & ECCE), 2011 IEEE 8th International Conference on, pp. 218-222, 2011,
June.
[6] Sung-min Lee, Hyosung Kim, “Development of DC Circuit Breaker using Magnet Arc
Extinguisher”, The Transactions of Korean Institute of Power Electronics, Vol. 17, No. 1, pp. 21-
26, 2012. 02.
[7] K. Asakura, J. Inamori, K. Murai, T. Tanaka, T. Babasaki, “Development of higher-voltage direct
current power feeding system in telecommunications buildings and data centers,” International
Conference on ECCE Asia, pp.2005-2009, 2011.
[8] C37.14-2002, IEEE Standard for Low-Voltage DC Power Circuit Breakers Used in Enclosures,
2002.
[9] IEC 60947-2 Ed.40, Low-voltage switchgear and controlgear - Part 2: Circuit-breakers.
[10] IEC 60898-1, Electrical Accessories-Circuit-Breakers for Overcurrent Protection for Household
and similar Installations-Part 1: Circuit-Breakers for A.C. Operation, Vol. 28, pp. 105-112, 1992,
January/February.
[11] C37.16-2000-IEEE standard for preferred ratings, related requirements, and application
recommendations for low-voltage AC (635 V and below) and DC (3200 V and below) power
circuit breakers.