Original Instructions
Topic Page
Specifications 1
Table 1 - Specifications
Summary of Changes 1
Introduction 1 Attribute 440N-Z21W1PA, 440N-Z21W1PB, 440N-Z21W1PH
This unit is not to be used as a mechanical stop. Guard stops and guides Outputs
must be fitted. Safety Output (Solid State Relay) 2 x N.C. 50 mA
This device is intended to be part of the safety-related control system of Auxiliary 1 x PNP N.O. 200 mA
a machine. Before installation, a risk assessment must be performed to ResponseTime
determine whether the specifications of this device are suitable for all
Switch response time 5 ms
foreseeable operational and environmental characteristics. Refer to
Table 1 for Certification information and ratings. Series response time 5 ms
Safety Output Short-Circuit Protection Provided by the approved safety relays To prevent damage, it is recommended
that a 2 mm (0.08 in.) gap be
Actuator
Auxiliary Overload Protection Internal resettable fuse maintained between the actuator and
sensor.
24V Supply Reverse Polarity Protection Incorporated
Sensor
Electrical Life 1 x 106 cycles
53 8
(2.1) 4
2mm Gap
20 16 12 8 4 0 -4 -8 -12 -16 -20 -24
4.2 5.5 0
(0.17) Ø (0.22) 24
0 20
16
12
8
48.0 (1.89) 4
2mm Gap
22.0 (0.87) 16.5 20 16 12 8 4 0 -4 -8 -12 -16 -20 -24
(0.65)
20.0
(0.79)
29.0 16
(1.14) 12
8
4
0 2 mm G a p 2 mm G a p
20 16 12 8 4 0 -4 -8 -12 -16 -20-24
0
4.2 5.5
(0.17) Ø (0.22)
20
16
12
Mounting Information 4
8
Use non-removable screws, bolts, or nuts to mount the switch and actuator. Do 2mm Gap
0
20 16 12 8 4 -4 -8 -12 -16 -20-24
not over torque the mounting hardware. It is recommended to use M3 screws
and washers throughout.
Maximum torque is 1 N•m (8.86 in•lb). Use nonmagnetic mounting LED Operation and Diagnostics
hardware.
Position the switch and actuator so they are aligned with each other. Table 2 - Unit Indicators (per IEC 60073)
State Status Troubleshooting
Mounting for Maximum Misalignment Check supply, check wiring to
Off Not powered
controller A
Mount the Sensor to the fixed part of the guard and the Actuator to the
movable section. Keep the Sensor and Actuator within the sensing range Off Overload Check AUX connections
detailed as shown in Figure 3. Device If actuator present check
Output LED Red Actuator not present
Minimum distance between sensors is 50 mm (1.97 in.). misalignment.
Green Actuator present —
IMPORTANT To obtain maximum switching distance, center the switches Actuator present
Green Actuation not present on other Check wiring to controller. Check
± 4 mm (0.24 in.). flashing actuators on other switches
switches or wiring fault
Not +24V
connected Aux Declaration of Conformity
2 1 This is to declare that the products shown in this document conform
3 8 7 Gnd
4 6 with the Essential Health and Safety Requirements (EHSRs) of the
Safety A 5
Safety B
European Machinery Directive (98/37/ED Machinery Directive, 2004/
Safety B
Safety A
108/EC EMC Directive). These products also conform to
EN 60947-5-3, EN 1088, EN ISO 12100 parts 1 & 2, EN 60204-1 and
Pin Wire Color Signal have Third Party Approval.
1 White PNP Aux For a comprehensive certificate, visit: https://
2 Brown +24V www.rockwellautomation.com/global/certification/overview.page
3 Green Not connected
4 Yellow Safety B Approved Monitoring Relay Units
5 Gray Safety A
MC2 can only be used with the approved relays. Use of other devices
not listed is at your own risk.
6 Pink Safety B
Only 24V DC MSR Relays or MSR Relays configured for 24V DC
7 Blue 0V operation are compatible with MC2.
8 Red Safety A
Table 4 - Approved Monitoring Relay Unit List and Max Number of
Series MC2s
Recommended Mating Cable
Max Number of MC2 Units
Monitoring Relay
The standard cable lengths are 2 m, 5 m, and 10 m. Use catalog number Catalog Number in Series
Series
889D-F8AB-2 [2 m (6.5 ft)] for the standard length or replace the 2 24V DC Supply Voltage
with 5 [5 m (16.4 ft)] or 10 [10 m (32.8 ft)] for remaining options. GSR Series -5% -10% -15%
GSR CI 440R-S13R2 8 10 10
IMPORTANT When the MC2 is used with any MSR100 series relay, for the GSR DI 440R-D22R2 8 10 10
diagnostic function to operate correctly the red and gray
GSR SI 440R-S12R2 8 10 10
wires (Safety A) must be connected to S11 and S12.
GSR DIS 440R-D22S2 8 10 10
CR30 440C-CR30 8 10 10
Power Supply Requirements MSR Series
24V DC + 10°/-15° has to be supplied by a power supply that complies MSR30RT/RTP 440R-N23197/440R-N23198 10 10 10
with IEC/EN 60204 and IEC/EN 61558-1. Such a power supply meets
the electrical safety requirements and maintains the minimum power of MSR 100 Series
20.4V DC during 20 ms even in the event of voltage dips. MSR124RT
440R-G23110/440R-G23108/
10 10 10
440R-G23107
When using an approved relay with a MC2 and the same power supply
MSR126T/R 440R-N23117/440R-N23123 10 10 10
is utilized for all devices, the relay will provide surge protection for the
MC2. If a separate power supply is used for the MC2, then extra MSR126.1T/.1R 440R-N23114/440R-N23120 10 10 10
protection will be required. MSR127T/TP 440R-N23126/440R-N23132 10 10 10
MSR127R/RP 440R-N23129/440R-N23135 10 10 10
Safety Ratings MSR131RTP 440R-C23139 10 10 10
An MC2 can achieve up to Cat 4/PLe, SIL CL3 when individually MSR138DP 440R-M23151 10 10 10
monitored by an approved Monitoring Relay Unit (see 9.1) that itself MSR138.1DP 440R-M23084 10 10 10
achieves Cat 4/PLe SIL CL3.
MSR142RTP 440R-G23216 10 8 -
Two or more MC2 sensors connected in series with an approved relay,
MSR178DP 440R-M23227 10 10 10
achieves up to CAT3/PLd/SIL CL2.
Troubleshooting
Figure 4 - Series Circuit — Two Guards Open
Actuator Actuator
LED - Green LED - Red LED - Flashing Green LED - Red LED - Flashing Green
Aux - OFF Aux - ON Aux - OFF Aux - ON Aux - OFF
The auxiliary contacts close at the same time as the first safety contact opens
S11 S12
Safety A Safety A Safety A Safety A Safety A
S21 S22
Safety B Safety B Safety B Safety B Safety B
24V Aux 24V Aux 24V Aux 24V Aux 24V Aux
LED - Green LED - Green LED - Flashing Green LED - Flashing Green LED - Flashing Green
Aux - OFF Aux - OFF Aux - OFF Aux - OFF Aux - OFF
Yellow (4)
Safety B+
Safety A- Gray (5)
Red (8)
Safety A+
0V Blue (7)
+24V Brown (2)
MC2
L2 L3
L1
K1
K2
41
42
33
34
23
24
13
14
S52 S12
S34
Grey
MSR127TP
S22
Pink
S11
S21
Red Yellow
A1
A2
+24V
0V
IMPORTANT To maintain the correct diagnostic operation, the red wire (QD
pin 8) must be connected to S11.
Yellow Red
Pink
MSR127TP
Gray
A2 S21 S22 S34
Brown (2)
A1 S11 S52 S12 13
14
+24v
Blue (7)
Fuses 0v
24
23
24
24
Gray(5)
Safety A-
24
24
Pink (6)
Safety B-
Actuator in place LED Green
Not
Pink
Brown (2)
+24v
Red
Blue (7)
Yellow
0v
K1
Red (8) Safety A+
M
MC 2 S2
L1 L2 L3
Gray(5)
Safety A-
Yellow (4) Safety B+
K2
Actuator
Pink (6)
Safety B-
Actuator in place LED Green
Blue (7)
Yellow
0v
Red (8) Safety A+
M C 2 S3
Gray(5)
Safety A-
Yellow (4) Safety B+
Actuator
Pink (6)
Safety B-
Actuator NOT in place LED Red
Indication
Green (3) Connected
Brown (2)
+24v
Red Blue (7)
Yellow
0v
Red (8) Safety A+
M C 2 S4
Gray(5)
Safety A-
Yellow (4) Safety B+
Actuator
Pink (6)
Safety B-
White (1) Aux
Not Actuator in place Flashing LED Green
Gray
Pink
Green (3) Connected
Brown (2)
+24v
Red
Yellow
Blue (7) 0v
Red (8) Safety A+
M C 2 S5
Gray(5)
Safety A-
Yellow (4) Safety B+
Actuator
Pink (6)
Brown (2)
+24v
MC2
A2
A1
Blue (7) 0v
Red (8) Safety A
GSR DI
Gray (5)
Safety A
Yellow (4) Safety B
Pink (6)
14
13
K1
Fuses
24
23
K2
K2
K1
RESET
Brown (2)
+24v
MC2
Blue (7)
7
Magnetically Coded Non-contact Switch (MC2)
Magnetically Coded Non-contact Switch (MC2)
Technical Support Center Knowledgebase Articles, How-to Videos, FAQs, Chat, User https://rockwellautomation.custhelp.com/
Forums, and Product Notification Updates.
Local Technical Support Phone Numbers Locate the phone number for your country. http://www.rockwellautomation.com/global/support/get-support-now.page
Find the Direct Dial Code for your product. Use the code to
Direct Dial Codes route your call directly to a technical support engineer. http://www.rockwellautomation.com/global/support/direct-dial.page
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete the
How Are We Doing? form at http://literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400