Vous êtes sur la page 1sur 9

489

Generator Protection
Generator Protection System

Economical protection, monitoring


and metering for generators

Key Benefits
• Complete, secure protection of small to medium • Enhanced generator troubleshooting through the use of
sized generators IRIG-B time synchronized event records, waveform
• Easy to use generator protection system supported by capturing, and data loggers
and industry leading suite of software tools. • Simplified setpoint verification testing using built in
• Advanced protection and monitoring features including waveform simulation functionality
the use of RTDs for stator and bearing thermal • Cost effective access to information through industry
protection and Analog Inputs for vibration monitoring standard communication hardware (RS232, RS485,
• Global acceptance as a member of the most renown 10BaseT Ethernet) and protocols (Modbus RTU,
protection relay product family in the market. Modbus TCP/IP, DNP 3.0)
• Draw-out construction allowing for minimized downtime • Available for use in most extreme harsh locations with
and easy removal/installation of the 489 during the available Harsh Chemical Environment Option
maintenance routines • GL Certification for below deck shipboard applications
• Large, user-friendly front panel interface allowing for
real-time power monitoring and setpoint access with a
display that is easily readable in direct sunlight

Applications
• Synchronous or induction generators operating at • Primary or backup protection in cogeneration applications
25Hz, 50Hz or 60Hz

Features
Protection and Control Monitoring and Metering
• Generator stator differential • Metering – current, voltage, power, Energy,
• 100% stator ground frequency, power factor
• Demand – current, watts, vars, VA
• Loss of excitation
• Temperature – 12 RTD inputs
• Distance backup
• Vibration and Speed – 4 analog transducer inputs
• Reverse power (anti-motoring)
• Event Recorder – 256 time tagged events
• Overexcitation
• Oscillography – 12 samples/ cycle up to 128 cycles in length
• Ground directional overcurrent
• Inadvertent energization • Trending – 8 parameters with up to a 5 second sample rate
• Breaker failure EnerVistaTM Software
• Stator and bearing thermal monitoring • State of the art software for configuration and
• Stator and bearing vibration monitoring commissioning GE Multilin products
• Negative sequence overcurrent • Document and software archiving toolset to ensure
reference material and device utilities are up-to-date
Communications • Ease to use real time monitoring, control, and data
• Networking interfaces - RS232, RS485, archiving software available
10Mbps copper Ethernet • EnerVista Integrator providing easy integration of data in the
TM

• Multiple protocols - ModBus™ RTU, ModBus™ 489 into new or existing monitoring and control systems
TCP/IP, DNP 3.0 Level 2

g Digital Energy
Multilin
101
489 Generator Protection System

Protection and Control 100% Stator Ground generator motoring that can cause
Generator Protection

100% stator ground fault protection is damage the prime mover. Independent
The 489 Generator Protection System
provided through an overvoltage element settings for power pickup levels and
provides comprehensive protection, metering,
and an adaptive voltage differential feature operational delays are available for both
and monitoring of small to medium sized
responding to the unbalance of the third alarming and tripping of each element.
synchronous or induction generators
harmonic at the machine terminals and at
operating at 25, 50 or 60 Hz. The 489 is Breaker Failure
ideally suited for primary or backup generator
the neutral point. The 489 compares the
The embedded breaker failure function
protection as well as for use in cogeneration
machine neutral voltage and ground
in the 489 allows for improved system
applications. Protection features found in the
current to determine if ground directional
dependability without the additional cost
489 include:
faults are within or outside the generator.
of providing an independent breaker

Generator Stator Differential Backup Phase Distance failure relay. Upon detection of a breaker
failure condition, the 489 can be
Two separate phase distance elements
The 489 utilizes high-speed dual slope configured to operate one of its 4 available
provide time-delayed backup protection
differential protection for detecting and
for generator faults that have not digital outputs to signal upstream devices
clearing of stator phase faults.
otherwise been cleared by the primary to quickly isolate the fault.
Advanced CT saturation detection
system and generator protections. The
algorithms maintain immunity to Loss of Excitation
distance characteristic can compensate
saturation conditions that may be Generator loss of excitation protection is
for a unit delta/wye power transformer
caused due to external disturbances provided through two negative offset mho
that is located between the generator
through the use of a directional check characteristics as per IEEEC37.102 and
and the end of the zone of protection.
that provides additional supervision and
has independent pickup delay setting for
ensures the fault is internal to the
Sensitive Directional Power each characteristic. The loss of excitation
generator before triggering it to trip.
The 489 provides low forward power element will be blocked from tripping if a

and reverse power elements to prevent VT fuse fail condition is detected or if the
Voltage Supervision characteristic is

ANSI Device Numbers & Functions


Functional Block Diagram
489 GENERATOR Device Function
Number
PROTECTION SYS TEM
52 Trip Coil
12

21P
Overspeed protection

Phase distance

Supervision 27P 24 Volts/Hz


27P Phase undervoltage

47 27/50 Accidental generator energization


27TN/59N 100% stator earth fault
32 Directional power
59P 38 Bearing overtemperature (RTD)
39 Bearing vibration
81O 40 Loss of excitation
46 Stator current unbalance
81U 47 Phase reversal
49 Thermal overload
40 50BF Breaker failure
24 50P Phase instantaneous overcurrent
21P 50G Ground instantaneous overcurrent
51P Phase time overcurrent
32 51G Ground time overcurrent
38 51_2 Negative Sequence Time Overcurrent
41 51V Voltage restrained time overcurrent
GENERATOR 12 59P Phase overvoltage
67G Ground directional overcurrent
81O Overfrequency
27/50
49 81U Underfrequency
51V 86 Lockout
39 87G Generator differential
VTFF VTFF VT fuse failure
Output
76 46
relays Output
49 86 6

relays
50BF
50P 87G 10BaseT

R S23 2
RS485
67G 50G 51G RS485 4 Analog
+

27TN/59N - outputs
+ 4 Analog
-
inputs
808783E6.cdr

102 www.GEDigitalEnergy.com
489 Generator Protection System

enable and the voltage is measured to time and continuous negative sequence demand metering are built into the relay as

Generator Protection
be above the user defined level. current rated limits. a standard feature. Current and voltage
parameters are available as total RMS
Abnormal Frequency Protection magnitude, and as fundamental frequency
Operation of generators at off-nominal magnitude and angle. Metered values can
frequencies can have extremely detrimental be read from the relay using one of the
effects on both the generator itself and the available communications ports or on the
associated prime mover, in particular with relay’s front panel display.
steam turbine generators operating below
normal frequency. The 489 provides Event Recording
overfrequency and underfrequency elements The 489 simplifies power generator
needed to provide protection of generators troubleshooting by creating a sequence of
from operation at off-nominal frequencies. The events record that timestamps and logs
489 has alarm level settings to alert events of internal relay operations and the
operations of abnormal frequency conditions operation of external devices connected to
as well as multiple trip levels that have the relay’s inputs. With each of the last 256

A negative mho element can be used to detect a independent tripping delay settings for each events the 489 stores, the relay will create
loss of excitation of the generator magnitude of abnormal frequency detected. a detailed event report that includes the
time and date of the event, and the
Stator Thermal Protection instantaneous value of all of the voltages,
The 489 provides thermal modeling Overcurrent Backup phase currents, and differential currents
overload protection to prevent generator Three voltage restrained overcurrent that were measured at the time the event
damage caused by generator overheating. elements provide backup protection for occurred.
The thermal model algorithms incorporate system faults. The pickup level for the
current unbalance biasing and RTD biasing inverse time curves of the overcurrent Oscillography
which provides accurate modeling of the elements are adjusted in conjunction Postmortem analysis of generator faults
actual generator temperature. The 489 can with the measured phase-to-phase can be performed using the waveform
be configured to trip the generator offline voltage. This feature is provided to capture feature in the 489. The 489
when the generator’s thermal limits are protect against prolonged generator samples the currents and voltages inputs
reached, or close an Alarm contact that contribution to a fault on the system. at a rate of 12 times per cycle and can
signals operations personnel to take record records up to 128 cycles in length.
appropriate actions. The recorded waveforms can be retrieved
Monitoring and Metering and viewed using the EnerVista 489 Setup
Bearing Overtemperature The 489 includes high accuracy metering Software and allows users to examine the
Twelve RTD inputs are provided that and recording for all AC signals. Voltage, magnitudes and relationships of the
may be configured to monitor and current, frequency, power, energy, and measured signals at the time of the fault.
protect against bearing overtemperature
K=1.0 4.0 15 40 100
conditions. The 489 provides the option 1000
for using RTD voting which requires that
two RTDs simultaneously indicate an
overtemperature condition before it will
trip the generator offline. RTD voting
100
provides additional security against
tripping of generators when an invalid
overtemperature signal is received from 10
Time(Seconds)

a malfunctioning RTD.

1
Negative Sequence Overcurrent
Rotor thermal protection is provided
through monitoring of negative sequence
current, which is a significant contributor to
0.1
rotor heating, to ensure it does not
increase above the generator’s capability
limits. The 489 provides a negative
sequence definite time overcurrent alarm
element and a negative sequence timed 0.01 0.1 1 10 100

overcurrent curve tripping element to Negative Sequence Current / Rated Current


The negative sequence overcurrent element is adaptable to ensure negative
ensure the generator stays within it’s short
sequence currents stay within the specific capability limits of a given generator

www.GEDigitalEnergy.com 103
489 Generator Protection System

Analog Outputs
Four analog outputs are available for
Generator Protection

signaling the value of measured analog


quantities to external process control
devices such as PLCs. The analog
outputs can be ordered to operate over
a 4 to 20mA range or a 0 to 1mA range
and can be configured to signal a
representation of most analog quantities
measured by the 489 including currents,
voltages, frequency, RTD temperature,
power and demand.

Communications
T h e 4 8 9 provides advan c e d
communications technologies for remote
Analyze generator faults using waveforms that are captured at the time
of generator faults or system instabilities data and engineering access, making it
easy and flexible to use and integrate into
IRIG-B Time Synchronization Protection elements can be configured to new or existing monitoring and control
control the Trip contact, the Alarm contact, systems. Multiple communication ports
The 489 supports receiving an input from
or the 3 Auxiliary contacts whenever the are available including a front panel
an IRIG-B time synchronization clock that
element operates. The status of each of RS232 serial port for easy local
will synchronize the 489 internal clock with
these contact are also displayed on LEDs computer access, two RS485 serial
other devices found in the substation or
found on the relays front panel. ports and a 10Mbps copper Ethernet
distributed across the power system. IRIG-
port that provide direct integration in
B time synchronization will provide
Digital Inputs most communications architectures.
timestamping of events in the Event The 489 supports the most popular industry
Record with 1ms accuracy thereby Eight digital inputs are available for
standard protocols enabling easy, direct
providing a means of accurately monitoring the status of external
integration into most DCS and SCADA
determining the sequence of operation of contacts, tachometers, or control
systems. Protocols supported include:
events that occurred across multiple switches. With these inputs, the relay
devices in the power system. can identify the status of the associated
• Modbus RTU
breakers and receive commands from
Simulation Mode operational staff such as controlling the • Modbus TCP/IP
The 489 has a built in simulation feature output relays, resetting the thermal • DNP 3.0 Level 2
that allows for testing the functionality and limits, or triggering a waveform capture.
relay response to programmed conditions
without the need for external inputs. When
RTD Inputs User Interfaces
Twelve RTD inputs allow the 489 to monitor
placed in simulation mode the 489
both the generator stator and bearing Keypad and Display
suspends reading of the actual inputs and
temperature. A built in voting feature adds
substitutes them with the simulated values. The 489 has a keypad and 40 character
Pre-trip, fault, and post fault states can be additional security by ensuring that two RTDs
display for local monitoring and relay
simulated, with currents, voltages, system monitoring the same device both detect the
configuration without the need for a
frequency, RTD temperatures, and analog overtemperature condition before tripping the
computer. Up to 20 user-selected default
inputs configurable for each state. generator offline.
messages can be displayed when the
Analog Inputs relay is protecting the generator. In the
Automation Four analog inputs are available for
event of a trip, or an alarm, the display
will automatically default to the proper
The 489 offers a multitude of different providing protection and monitoring of
message indicating the cause of the
analog and digital inputs and outputs to generator bearing vibration. The analog
operation.
allow the 489 to be seamlessly integrated inputs are field programmable to
into most generator automation schemes. measure transducer signals that LED Indicators
operator over a range of 0 to 1 mA, 0 to
The 489 front panel features 22 LED
Outputs Relays 20 mA, or 4 to 20 mA.
indicators that provide a quick indication
The 489 provides six output contacts for of 489 status, generator status, and
the purpose of controlling or signaling output relay status.
other devices and operations personnel.

104 www.GEDigitalEnergy.com
489 Generator Protection System

EnerVistaTM Software EnerVistaTM Launchpad that ensures critical documentation is


EnerVista™ Launchpad is a powerful up-to-date and available when needed.

Generator Protection
The EnerVista™ Suite is an industry-leading
software package that provides users with Documents made available include:
set of software programs that simplify every
all of the setup and support tools needed
aspect of using the 489 relay. The EnerVista TM
for configuring and maintaining GE Multilin • Manuals
suite provides all the tools to monitor the
products. The setup software within • Application Notes
status of your protected asset, maintain the
Launchpad allows configuring devices in
relay and integrate information measured by • Guideform Specifications
real-time by communicating using serial,
the 489 into DCS or SCADA monitoring • Brochures
Ethernet, or modem connections, or offline
systems. Convenient COMTRADE and
by creating setting files to be sent to • Wiring Diagrams
Sequence of Events viewers are an integral
devices at a later time. • FAQs
part of the 489 Setup software included with
Included in Launchpad is a document
every relay to carry out post-mortem event • Service Bulletins
analysis.
archiving and management system

489 FRONT
Features
LARGE DISPLAY
Forty character display for viewing
setpoints and actual value mess-
ages. Diagnostic messages are
489 STATUS INDICATORS displayed when there is a trip or
489 status alarm condition. Default messages
Generator status are displayed after a period of
Output relays
inactivity.

NUMERIC KEYPAD
Numeric keys allow for simple
entry of setpoint values. Control
keys allow simple navigation CONTROL AND
through setpoint and actual value PROGRAMMING KEYS
message structures. Help key Menu, Escape, Reset, Enter,
provides context sensitive help Menu Up, and Menu Down
messages keys for complete acess
without a computer.

VALUE KEYS
Value Up, and Value Down keys
to change setpoint values DRAWOUT HANDLE
With provision for a wire
lead seal to prevent unauth-
PROGRAM PORT INTERFACE orized removal
RS232 for connection to a
computer, 9600 baud

489 REAR ANALOG SIGNALS


RTD INPUTS Four isolated 4-20 mA analog outputs
Twelve RTD inputs are may be used to replace costly
individually field programmable transducers. They may be field

programmed to reflect any measured


parameter.
to measure platinum, nickel,

or copper type RTDs. Four 0-1 or 4-20 mA analog inputs may


be used to monitor any transducer

RS485 COMMUNICATIONS signal. Possible applications include


Two independent RS485 vibration and field current monitoring.
communication ports may be
accessed simultaneously using
ModbusRTU and DNP 3.0 protocol DIGITAL INPUTS
at baud rates up to 19200 bps. Access jumper input provides
setpoint programming security.
Breaker status input tells 489 if

OUTPUT RELAYS the generator is online or offline.


Six, trip duty, form C output relays Seven assignable digital inputs may

be field programmed for a variety of


may be assigned to trip, alarm
and control functions. functions including tachometer.

TRIP COIL SUPERVISION


Monitors the trip circuit for continuity
when the generator is online and
alarms if that continuity is broken.

VT INPUTS GROUND
Four VT inputs provide wye or open Separate safety and filter ground.
delta system voltage sensing as All inputs meet C37.90 EMI, SWC,
well as neutral voltage sensing. RFI interference immunity.

AC/DC CONTROL POWER


Universal power supply
90-300 VDC 70-265 VAC

CT INPUTS
Seven CT inputs provide three-
phase output, three-phase neutral
and ground current sensing.

www.GEDigitalEnergy.com 105
489 Generator Protection System

Typical Wiring
Generator Protection

g Multilin 489
Generator Protection System

HUB
Ethernet
Option (T)

106 www.GEDigitalEnergy.com
489 Generator Protection System

Viewpoint Monitoring Viewpoint Maintenance EnerVista™ Integrator

Generator Protection
Viewpoint Monitoring is a simple-to-use Viewpoint Maintenance provides tools that EnerVistaTM Integrator is a toolkit that
and full-featured monitoring and data will create reports on the operating status allows seamless integration of GE
recording software package for small of the relay, simplify the steps to download Multilin devices into new or existing
systems. Viewpoint Monitoring provides fault and event data, and reduce the work automation systems. Included in
a complete HMI package with the required for cyber-security compliance EnerVista Integrator is:
following functionality: audits. Tools available in Viewpoint
• Plug & Play Device Monitoring Maintenance include: • OPC/DDE Server
• System Single-Line Monitoring & Control • Settings Security Audit Report • GE Multilin Drivers
• Annunciator Alarm Screens • Device Health Report • Automatic Event Retrieval
• Trending Reports • Single Click Fault Data Retrieval • Automatic Waveform Retrieval
• Automatic Event Retrieval
• Automatic Waveform Retrieval

Technical Specifications
Protection Protection Protection
OVERCURRENT ALARM OVERVOLTAGE REACTIVE POWER
Pick-up Level: 0.10 to 1.50 x FLA in steps of Pick-up Level: 1.01 to 1.50 x rated V in steps of 0.01 Block From Online: 0 to 5000 s in steps of 1
0.01 average phase current Curve Shapes: Inverse Time, definite time alarm Pickup Level: 0.02 to 1.50 x rated Mvar (positive
Time Delay: 0.1 to 250.0 s in steps of 0.1 Time Delay: 0.2 to 120.0 s in steps of 0.1 and negative)
Pickup Accuracy: as per Phase Current Inputs Pickup Accuracy: as per Voltage Inputs Time Delay: 0.2 to 120.0 s in steps of 0.1
Timing Accuracy: ±100 ms or ±0.5% of total time Timing Accuracy: ±100 ms or ±0.5% of total time Pickup Accuracy: see power metering
OFFLINE OVERCURRENT VOLTS/HERTZ Timing Accuracy: ±100ms or ±0.5% of total time
Pick-up Level: 0.05 to 1.00 x CT in steps of 0.01 of Pick-up Level:1.00 to 1.99 x nominal REVERSE POWER
any one phase in steps of 0.01 Block From Online: 0 to 5000 s in steps of 1
Time Delay: 3 to 99 cycles in steps of 1 Curve Shapes: Inverse Time, definite time alarm Pickup Level: 0.02 to 0.99 x rated MW
Time Delay: 0.1 to 120.0 s in steps of 0.1 Time Delay: 0.2 to 120.0 s in steps of 0.1
Pickup Accuracy: as per Phase Current Inputs Pickup Accuracy:
as per voltage inputs Pickup Accuracy: see power metering
Timing Accuracy: +50ms at 50/60 Hz Timing Accuracy:
±100 ms at ? 1.2 x Pickup Timing Accuracy: ±100 ms or ±0.5% of total time
INADVERTENT ENERGIZATION ±300 ms at < 1.2 ´ Pickup LOW FORWARD POWER
Arming Signal: undervoltage and/or offline from Block From Online: 0 to 15000 s in steps of 1
breaker status VOLTAGE PHASE REVERSAL
Pickup Level: 0.02 to 0.99 x rated MW
Pick-up Level: 0.05 to 3.00 x CT in steps of 0.01 of Time Delay: 0.2 to 120.0 s in steps of 0.1
any one phase Configuration: ABC or ACB phase rotation Pickup Accuracy: see power metering
Time Delay: no intentional delay Timing Accuracy: 200 to 400 ms Timing Accuracy: ±100 ms or ±0.5% of total time
Pickup Accuracy: as per Phase Current Inputs UNDERFREQUENCY PULSE OUTPUT
Timing Accuracy: +50 ms at 50/60 Hz Required Voltage: 0.50 to 0.99 x rated voltage in Parameters: + kwh, +kvarh, -kvarh
PHASE OVERCURRENT Phase A Interval: 1 to 50000 in steps of 1
Voltage Restraint: Programmable fixed characteristic Block From Online: 0 to 5 sec. in steps of 1 Pulse Width: 200 to 1000 ms in steps of 1 ms
Pick-up Level: 0.15 to 20.00 x CT in steps of 0.01 of
Pickup Level: 20.00 to 60.00 in steps of 0.01 RTDS 1 TO 12
Curve Shapes: 1 level alarm, two level trip Pickup: 1 to 250°C in steps of 1
any one phase
definite time Pickup Hysteresis: 2°C
Curve Shapes: ANSI, IEC, IAC,
Time Delay: 0.1 to 5000.0 sec. in steps of 0.1
Flexcurve, Definite Time Time Delay: 3 sec.
Pickup Accuracy: ±0.02 Hz
Time Delay: 0.000 to 100.000 s in steps of 0.001 Timing Accuracy: ±100 ms or ±0.5% of total time OVERLOAD / STALL PROTECTION / THERMAL MODEL
Pickup Accuracy: as per Phase Current Inputs OVERFREQUENCY Overload Curves: 15 Standard Overload Curves
Timing Accuracy: +50 ms at 50/60 Hz Required Voltage: 0.50 to 0.99 x rated voltage in Custom Curve
or ±0.5% total time Phase A Voltage Dependent Custom Curve
NEGATIVE SEQUENCE OVERCURRENT Block From Online: 0 to 5 sec. in steps of 1 Curve Biasing: Phase Unbalance
Pickup Level: 3 to 100% FLA in steps of 1 Pickup Level: 25.01 to 70.00 in steps of 0.01 Hot/Cold Curve Ratio
Curve Shapes: I22t trip defined by k, Curve Shapes: 1 level alarm, 2 level trip Stator RTD
definite time alarm definite time Online Cooling Rate
Time Delay: 0.1 to 100.0 s in steps of 0.1 Time Delay: 0.1 to 5000.0 s in steps of 0.1 Offline Cooling Rate Line Voltage
Pickup Accuracy: as per Phase Current Inputs Pickup Accuracy: ±0.02 Hz Overload Pickup: 1.01 to 1.25
Timing Accuracy: ±100ms or ± 0.5% of total time Timing Accuracy: ±100 ms or ±0.5% of total time Pickup Accuracy: as per Phase Current Inputs
GROUND OVERCURRENT NEUTRAL OVERVOLTAGE (FUNDAMENTAL) Timing Accuracy: ±100 ms or ±2% of total time
Pickup Level: 0.05 to 20.00 x CT in steps of 0.01 Pick-up Level: 2.0 to 100.0 V secondary in
Curve Shapes: ANSI, IEC, IAC, steps of 0.01
Flexcurve, Definite Time Time Delay: 0.1 to 120.0 s in steps of 0.1 DIGITAL INPUT
Time Delay: 0.00 to 100.00 s in steps of 0.01 Pickup Accuracy: as per Neutral Voltage Input GENERAL INPUT A TO G (DIGITAL INPUT)
Pickup Accuracy: as per Ground Current Input Timing Accuracy: ±100 ms or ±0.5% of total time Configurable: Assignable Digital Inputs 1 to 7
Timing Accuracy: +50 ms at 50/60 NEUTRAL UNDERVOLTAGE (3RD HARMONIC) Time Delay: 0.1 to 5000.0 s in steps of 0.1
Hz or ±0.5% total time Blocking Signals: Low power and low voltage if Block From Online: 0 to 5000 s in steps of 1
PHASE DIFFERENTIAL open delta Timing Accuracy: ±100 ms or ±0.5% of total time
Pickup Level: 0.05 to 1.00 x CT in steps of 0.01 Pickup Level: 0.5 to 20.0 V secondary in steps SEQUENTIAL TRIP (DIGITAL INPUT)
of 0.01 Configurable: Assignable to Digital Inputs 1 to 7
Curve Shapes: Dual Slope
if open delta VT;
Time Delay: 0 to 100 cycles in steps of 1 Pickup Level: 0.02 to 0.99 x rated MW in steps of 0.01
adaptive if wye VT
Pickup Accuracy: as per Phase Current Inputs Low Forward Power / Reverse Power
Time Delay: 5 to 120 s in steps of 1
Timing Accuracy: +50 ms at 50/60 Hz Time Delay: 0.2 to 120.0 s in steps of 0.1
Pickup Accuracy:
or ±0.5% total time Pickup Accuracy: see power metering
at < 20.0 V secondary: as per Neutral Voltage Input
GROUND DIRECTIONAL ±3.0 s Timing Accuracy: ±100 ms or ±0.5% of total time
Timing Accuracy:
Pickup Level: 0.05 to 20.00 x CT in steps of 0.01 LOSS OF EXCITATION (IMPEDANCE) FIELD BREAKER DISCREPANCY (DIGITAL INPUT)
Time Delay: 0.1 to 120.0 s in steps of 0.1 Pickup Level: 2.5 to 300.0 secondary in steps Configurable: Assignable to Digital Inputs 1 to 7
Pickup Accuracy: as per Phase Current Inputs of 0.1 with adjustable impedance Time Delay: 0.1 to 500.0 s in steps of 0.1
Timing Accuracy: ±100 ms or ±0.5% of total time offset Timing Accuracy: ±100 ms or ±0.5% of total time
HIGH-SET PHASE OVERCURRENT Time Delay: 0.1 to 10.0 s in steps of 0.1 TACHOMETER (DIGITAL INPUT)
Pickup Level: 0.15 to 20.00 x CT in steps of 0.01 Pickup Accuracy: as per Voltage and Phase Current Configurable: Assignable to Digital Inputs 4 to 7
Time Delay: 0.00 to 100.00 s in steps of 0.01 Inputs RPM Measurement: 100 to 7200 RPM
Pickup Accuracy: as per Phase Current Inputs Timing Accuracy: ±100 ms or ±0.5% of total time Duty Cycle of Pulse: >10%
Timing Accuracy: ±50 ms at 50/60 Hz DISTANCE (IMPEDANCE) Pickup Level: 101 to 175 x rated speed in steps
or ±0.5% total time Pickup Levels: 0.1 to 500.0 secondary in steps Time Delay: 1 to 250 s in steps of 1
UNDERVOLTAGE of 0.1 Timing Accuracy: ±0.5 s or ±0.5% of total time
Pickup Level: 0.50 to 0.99 x rated V in steps of 0.01 50 to 85° reach in steps of 1
Curve Shapes: Inverse Time, definite time alarm 1 Time Delay: 0.0 to 150.0 s in steps of 0.1
Time Delay: 0.2 to 120.0 s in steps of 0.1
Pickup Accuracy: as per Voltage and Phase Current
Inputs
Pickup Accuracy: as per Voltage Inputs Timing Accuracy: 150 ms ±50 ms or ±0.5% of total
Timing Accuracy: ±100 ms or ±0.5% of total time time
Elements: Trip and Alarm

www.GEDigitalEnergy.com 107
489 Generator Protection System

Technical Specifications (continued)


Generator Protection

ANALOG INPUTS INPUTS communications


Phase Current INPUTS RTD INPUTS RS232 Port: 1, Front Panel, non-isolated
CT Primary: 10 to 50000 A RTD (3 wire Types): 100 Platinum RS485 Ports: 2, Isolated together at 36 Vpk
CT Secondary: 1 A or 5 A (must be specified 100 Nickel, 120 Nickel Baud Rates: RS485: 300 - 19,200 Baud
with order) RTD Sensing 10 Copper RS232: 9600 Baud
Conversion Range: 0.02 to 20 x CT Parity: None, Odd, Even
Accuracy: at < 2 x CT: ±0.5% of 2 x CT Current: 5mA Ethernet: 10Mbbs Copper RJ45
at > 2 x CT: ±1% of 20 x CT Isolation: 36 Vpk (isolated with analog Protocol: Modbus® RTU / Modbus® TCP/IP
Burden: Less than 0.2 VA at rated load inputs and outputs) DNP 3.0 Level 2
CT Withstand: 1 second at 80 times rated current Range: –50 to +250°C
2 seconds at 40 times rated current Accuracy: ±2°C for Platinum and Nickel environmental
continuous at 3 times rated current ±5°C for Copper Temperature Range:
GROUND CURRENT INPUTS Lead Resistance: 25 Max per lead for Pt and Operating: -40 °C to +60 °C
Ni type 3 Max per lead for Ambient Storage: -40 °C to +85 °C
CT Primary: 10 to 10000 A (1 A / 5 A CTs)
Cu type Ambient Shipping: -40 °C to +85 °C
CT Secondary: 1 A / 5 A or 50:0.025 (HGF CTs)
No Sensor: >1000
Conversion Range: 0.02 to 20 x CT for 1 A / 5 A Humidity: Operating up to 95% (non
Short/Low Alarm: < –50°C condensing) @ 55C
CTs 0.0 to 100 A pri. for 50:0.025 TRIP COIL SUPERVISION Altitude: Up to 2000 m
Applicable Voltage: 20 to 300 V DC / V AC
CTs(HGF) Trickle Current: 2 to 5 mA
Pollution degree: 2
50:0.025 CT ± 0.1 A at < 10 A product tests
Accuracy: ± 1.0 A at ³ 10 to 100 A
1A/5A CT at < 2 x CT: ±0.5% of 2 x CTat > 2 x
Accuracy: CT: ±1% of 20 x CT
GROUND CT INPUT BURDEN OUTPUTS Thermal Cycling: Operational test at ambient,
ANALOG OUTPUTS reducing to –40°C and then
VA increasing to 60°C
1A/5A 1A 0.024 0.024 Type: Active
Range: 4 to 20 mA, 0 to 1 mA (must be Dielectric Strength: 2.0 kV for 1 minute from relays,
5A 0.605 0.024 CTs, VTs, power supply to
20 A 9.809 0.024 specified with order)
50:0.025 0.025 A 0.057 90.7 Accuracy: ±1% of full scale Safety Ground
HGF 0.1 A 0.634 90.7 Maximum 4 to 20 mA input: 1200,
0.5 A 18.9 75.6 Load: 0 to 1 mA input: 10 k type tests
Isolation: 36 Vpk Dielectric voltage withstand: EN60255-5
GROUND CT WITHSTAND TIME OUTPUT RELAYS Impulse voltage withstand: EN60255-5
CT 1 SEC 2 SEC. CONTINUOUS Configuration: 6 Electromechanical Form C
1A/5A 80 x CT 40 x CT 3 x CT Contact Material: Silver alloy Insulation resistance: EN60255-5
Operate Time: 10 ms Damped Oscillatory: IEC61000-4-18,
50:0.025 HGF N/A N/A 150 mA
Max ratings for 100000 operations IEC60255-22-1
PHASE VOLTAGE INPUTS Electrostatic Discharge: EN61000-4-2,
VOLTAGE M/C M/C 0.2 BREAK MAX IEC60255-22-2
VT Ratio: 1.00 to 240.00:1 in steps of 0.01 CONT. SEC LOAD RF immunity: EN61000-4-3,
VT Secondary: 200 V AC (full-scale) DC 30 VDC 10 A 30A 10 A 300 W IEC60255-22-3
Conversion Range: 0.02 to 1.00 x Full Scale Resistive 125 VDC 10 A 30A 0.5 A 62.5 W Fast Transient Disturbance: EN61000-4-4,
Accuracy: ±0.5% of Full Scale 250 VDC 10 A 30A 0.3 A 75 W IEC60255-22-4
Max. Continuous: 280 V AC DC 30 VDC 10 A 30A 5A 150 W Surge Immunity: EN61000-4-5,
Burden: > 500 K Inductive 125 VDC 10 A 30A 0.25 A 31.3 W IEC60255-22-5
NEUTRAL VOLTAGE INPUTS L/R= 40 ms 250 VDC 10 A 30A 0.15 A 37.5 W Conducted RF Immunity: EN61000-4-6,
VT Ratio: 1.00 to 240.00:1 in steps of 0.01 AC 120 VAC 10 A 30A 10 A 2770 VA IEC60255-22-6
VT Secondary: 100 V AC (full-scale) Resistive 250 VAC 10 A 30A 10 A 2770 VA Radiated & Conducted CISPR11, CISPR22,
Conversion Range: 0.005 to 1.00 x Full Scale AC 120 VAC 10 A 30A 4A 480 VA Emissions: IEC60255-25
Accuracy: ±0.5% of Full Scale Inductive 250 VAC 10 A 30A 3A 750 VA Sinusoidal Vibration: IEC60255-21-1
Max. Continuous: 280 V AC P.F. = 0.4 Power magnetic Immunity: IEC61000-4-8
Burden: > 500 K POWER SUPPLY Voltage Dip & interruption: IEC61000-4-11
DIGITAL INPUTS Ingress Protection: IEC60529
Inputs: 9 opto-isolated inputs CONTROL POWER Environmental (Cold): IEC60068-2-1
External Switch: dry contact < 400 Options: LO / HI Environmental (Dry heat): IEC60068-2-2
489 Sensor Supply: +24 V DC at 20 mA maximum (must be specified with order) Relative Humidity Cyclic: IEC60068-2-30
ANALOG Transducer INPUTS LO Range: DC: 20 to 60 V DC EFT: IEEE/ANSI C37.90.1
Current Inputs: 0 to 1 mA, 0 to 20mA or 4 to AC: 20 to 48 V AC at 48 to 62 Hz ESD: IEEE/ANSIC37.90.3
20 mA (setpoint) Hi Range: DC: 90 to 300 V DC
Input Impedance: 226 ±10% AC: 70 to 265 V AC at 48 to 62 Hz
Conversion Range: 0 to 21 mA Power: 45 VA (max), 25 VA typical
Accuracy: ±1% of full scale certification
Type: passive ISO: Manufactured under an ISO9001
AC ANALOG INPUTS FREQUENCY TRACKING registered system.
Analog In Supply: +24 V DC at 100 mA maximum Frequency Va for wye, Vab for open delta
Sampling Interval 50 ms CSA/UL: UL508, UL1053, C22.2.No 14
Tracking: 6 V minimum, 10 Hz/sec. CE: Conforms to EN60255-5, EN50263

Please refer to Multilin 489 Generator Protection System Instruction Manual for complete technical specifications

Ordering
489 * * * * *
Current Input Relays P1 1 A phase CT secondaries
P5 5 A phase CT secondaries
Power Supply Options LO DC: 24 – 60 V; AC: 20 – 48 V @ 48 – 62 Hz
HI DC: 90 – 300 V; AC: 70 – 265 V @ 48 – 62 Hz
Analogue Outputs A1 0 – 1 mA analog outputs
A20 4 – 20 mA analog outputs
Enhancements E Enhanced display, larger LCD, improved keypad
T Enhanced display, larger LCD, improved keypad plus 10BaseT Ethernet Port
Environmental Protection H Harsh (Chemical) Environment Conformal Coating

Accessories for the 489 Visit www.GEMultilin.com/489 to:


  •   
489 Generator Protection Learning CD TRCD-SR489-C-S-1 •  View Guideform specifications
  •   
Multilink Ethernet Switch ML1600-HI-A1-A1 •  Download the instruction manual
  •   
Multinet Multinet-FE •  Review applications notes and support documents
  •   
Viewpoint Maintenance VPM-1 •  Buy a 489 online
  •   
Viewpoint Monitoring VP-1 •  View the 489 brochure
108 www.GEDigitalEnergy.com 090824-v10

Vous aimerez peut-être aussi