Vous êtes sur la page 1sur 130

Air

Circuit-Breakers (ACBs)

5/2 Introduction

Circuit-breakers/
non-automatic circuit-breakers
up to 6300 A, SENTRON WL
5/4 General data
5/28 3-pole, fixed-mounted design
5/30 3-pole, withdrawable design
5/32 4-pole, fixed-mounted design
5/34 4-pole, withdrawable design
5/36 Options
5/44 Accessories/spare parts
5/56 Project planning aids

Circuit-breakers, approved acc. to


UL 489, up to 5000 A,
SENTRON WL
5/68 General data
5/73 3-pole, fixed-mounted design
5/74 3-pole, withdrawable design
5/75 Accessories/spare parts

Non-automatic circuit-breakers
for DC,
up to 4000 A, SENTRON WL
5/77 General data
5/78 3- and 4-pole, fixed-mounted design
5/79 3- and 4-pole, withdrawable design
5/80 Accessories/spare parts
5/81 Project planning aids

Circuit-breakers up to 3200 A,
discontinued series
5/82 General data
5/100 3-pole, fixed-mounted design
5/101 3-pole, withdrawable design
5/102 4-pole, fixed-mounted design
5/103 4-pole, withdrawable design
5/104 Options
5/108 Accessories/spare parts
5/116 Project planning aids

Non-automatic circuit-breakers
up to 3200 A, discontinued series
5/126 3-pole, fixed-mounted design
5/127 3-pole, withdrawable design
5/128 4-pole, fixed-mounted design
5/129 4-pole, withdrawable design
5/130 Options

Siemens LV 30 · 2004
Air Circuit-Breakers (ACBs)

Introduction

■ Overview

Size I II III
Circuit-breakers/non-automatic circuit-breakers
up to 6300 A, SENTRON WL

Rated current In A 630, 800, 1000, 1250, 800, 1000, 1250, 1600, 2000, 2500, 4000, 5000, 6300
1600 3200
Number of poles 3-pole, 4-pole 3-pole, 4-pole 3-pole, 4-pole
Rated operating voltage Ue AC V up to 690 up to 690/1000 up to 690/1000
DC V
Rated ultimate short-circuit kA 50/65 55/80/100 100
breaking capacity

5
at AC 415 V
Endurance Operat- 20000 15000 10000
ing cycles
Service position 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 °

N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2 N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2 N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2

Degree of protection
with cover IP55 IP55 IP55
without cover IP20 IP20 IP20
Dimensions 3-/4-pole Fixed-mounted Withdrawable Fixed-mounted Withdrawable Fixed-mounted Withdrawable
B T W mm 320/410 320/410 460/590 460/590 704/914 704/914
H mm 434 465.5 434 465.5 434 466.5
H

D mm 291 471 291 471 291 471


NSS0_00535

Electronic overcurrent trip units of SENTRON WL circuit-breakers


E T U 7 6 B

- 6 7  # * - 6 7 " # * - 6 7 # # *
- 6 7 # * - 6 7 % *
R a t in g P lu g
R a t in g P lu g
R a t in g P lu g =
R a t in g P lu g

R a t in g P lu g
N S E 0 _ 0 1 1 1 0
N S E 0 _ 0 1 1 0 6

N S E 0 _ 0 1 1 0 9

N S E 0 _ 0 1 1 1 1
N S E 0 _ 0 1 1 0 7

1 2
N S E 0 _ 0 1 1 0 8

O F F : c s c w

G F M A T 5 5 B -7 6 B
G F M A T 4 5 B G F M A T 5 5 B -7 6 B
g
A L A R M

T E S T Q U E R Y C L E A R
T E S T Q U E R Y C L E A R T E S T Q U E R Y C L E A R T E S T Q U E R Y C L E A R
T E S T Q U E R Y C L E A R

Type ETU15B ETU25B ETU27B ETU45B ETU55B ETU76B


Overload protection ✓ ✓ ✓ ✓ ✓ ✓
Short-time delayed short-circuit – ✓ ✓ ✓ ✓ ✓
protection
Instantaneous short-circuit ✓ ✓ ✓ ✓ ✓ ✓
protection
Neutral conductor protection – – ✓ ✓ ✓ ✓
Ground-fault protection – – ✓ ❑ ❑ ❑
Zone Selective Interlocking – – – ❑ ❑ ❑
LCD, 4-line – – – ❑ – –
LCD, graphic – – – – – ✓
Communication via – – – ❑ ❑ ❑
PROFIBUS DP
Measurement functions – – – ❑ ❑ ❑
Selectable parameter sets – – – – ✓ ✓
Parameters freely programmable – – – – ✓ ✓
✓ Standard
- Not available
❑ Optional

5/2 Siemens LV 30 · 2004


Air Circuit-Breakers (ACBs)

Introduction

I, II, III II I II
Circuit-breakers, approved acc. Non-automatic circuit-breakers Circuit-breakers, up to 3200 A, discontinued series
to UL 489, up to 5000 A, for DC, up to 4000 A, Non-automatic circuit-breakers, up to 3200 A, discontinued
SENTRON WL SENTRON WL series
1000, 1600, 2000, 2500, 3000, 1000, 2000, 4000 630, 800, 1000, 1250, 1600 2000, 2500, 3200
4000, 5000
3-pole 3-pole, 4-pole 3-pole, 4-pole 3-pole, 4-pole
up to 600 */347 up to 690 up to 690
up to 1000
65/100 30/25/20 65 80
(at DC 300/600/1000 V)

20000/15000/10000 15000 20000 20000 5


3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 ° 3 0 °

N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2 N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2 N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2 N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2

IP55 IP54 IP54


IP20 IP20 IP20
For dimensions see Fixed-mounted Withdrawable Fixed-mounted Withdrawable Fixed-mounted Withdrawable
circuit-breakers/ 460/590 460/590 300/390 280/370 400/520 380/500
non-automatic circuit-breakers 434 465,5 470 485 470 485
up to 6300 A, SENTRON WL
291 471 330 445 330 445

Siemens LV 30 · 2004 5/3


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

■ Overview
SENTRON WL:
Superior individual products integrated into uniform power dis-
tribution systems – up to and including industry-specific indus-
trial and infrastructure solutions

% *
+

&
) ,
(

-
$

5 9

/
= .
7
:
6

;
0

<

1
8 5
3

2
4

$ Guide frame 2 EMERGENCY-STOP pushbutton, key operated


% Main connection, front, flange, horizontal, vertical 3 Motorized operating mechanism
& Position indicator switch 4 Operating cycles counter
( Grounding contact, leading 5 Breaker status sensor (BSS)
) Shutter 6 Electronic overcurrent trip unit (ETU)
* COM15 PROFIBUS module 7 Reset solenoid
+ External CubicleBUS modules 8 Breaker data adapter (BDA)
, Closing solenoid, auxiliary release 9 4-line LCD module
- Auxiliary conductor plug-in system : Ground-fault protection module
. Auxiliary switch block ; Rating plug
/ Door sealing frame < Measuring function module
0 Interlocking set for baseplate = Circuit-breaker
1 Transparent panel, function insert

5/4 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

■ Benefits ■ Design
Low space requirements • Rated currents: 630 A to 6300 A
• 3 sizes for different rated current ranges (see illustration "Over-
The SENTRON WL devices require very little space. Size I view of SENTRON WL circuit-breakers/non-automatic circuit-
devices (up to 1600 A) fit into a 400 mm wide switchgear panel. breakers")
Size III devices (up to 6300 A) are the smallest of their kind and
with their construction width of 704 mm fit into a 800 mm wide • 3 and 4-pole versions
switchgear panel. • Rated operational voltage up to AC 690 V and 1000 V. Special
versions up to AC 1000 V available
Modular design
• 3 different switching capacity classes in the range from 50 kA
Components like auxiliary releases, motorized operating mech- to 100 kA for AC applications and one switching capacity class
anisms, overcurrent trip units, current sensors, auxiliary circuit for DC applications.
signaling switches, automatic reset devices and interlocks can
all be exchanged or retrofitted at a later stage, thus allowing the The SENTRON WL circuit-breakers are supplied complete with
circuit-breaker to be adapted to new, changing requirements. operating mechanism (manual operating mechanism with me-
chanical closing), electronic overcurrent trip unit and auxiliary
The main contact elements can all be replaced in order to in- switches (2 NO contacts + 2 NC contacts in the standard ver-
crease the endurance of the circuit-breaker. sion), and can be equipped with auxiliary releases.
Retrofittable modules for electronic overcurrent trip units Installation types
Modularity is one of the main features of the new SENTRON WL Fixed-mounted or withdrawable version

5
circuit-breakers.
Special LCDs, ground-fault modules, rated current modules, Ambient temperatures
and communication modules for the electronic overcurrent trip
units are available for retrofitting. The SENTRON WL circuit-breakers are climate-proof in accor-
dance with DIN IEC 68 Part 30-2. They are intended for use in
Rating plugs enclosed areas where no severe operating conditions (e.g. dust,
corrosive vapors, damaging gases) are present.
It is no longer necessary to replace the transformers in order to
change the rated current. The rating plugs, which have been in- When installed in dusty and damp areas, suitable enclosures
tegrated into the electronic overcurrent trip units and are easily must be provided.
accessible, are exchanged instead. In this way, the circuit-
breaker is quickly set to the new rated current and is also Coordinated dimensions
marked accordingly. The dimensions of SENTRON WL circuit-breakers of the same in-
stallation type only differ in terms of the width of the device which
Communication depends on the number of poles and the frame size.
The use of modern communication-capable circuit-breakers Due to the nature of the design, the dimensions of devices with
opens up completely new possibilities in terms of start-up, cali- a withdrawable design are determined by the dimensions of the
bration, diagnosis, testing, maintenance, and power manage- guide frames, which are slightly larger.
ment.
This allows many different ways of reducing costs and improving Non-automatic circuit-breakers
productivity in industrial plants, buildings and infrastructure One special type of circuit-breaker is utilized as a non-automatic
projects to be achieved. circuit-breaker. The non-automatic circuit-breakers are de-
signed without an electronic overcurrent trip unit system and do
■ Area of application not perform any protection duties for the system.
• As incoming-feeder, distribution, tie, and outgoing-feeder cir- One potential application is the use as a bus coupler in systems
cuit-breakers in electrical installations. with parallel feed-ins.
• For switching and protecting motors, capacitors, generators, The designs and specifications can be selected according to
transformers, busbars and cables. those of the circuit-breakers.
• Application as an EMERGENCY-STOP switch in conjunction Operating mechanisms
with an EMERGENCY-STOP device (DIN VDE 0113,
IEC 60 204-1). The switches are available with various optional operating
mechanisms:
Due to the reinforced use of electronic control systems, the de-
mands made on air circuit-breakers in terms of operator control • Manual operating mechanism with mechanical closing
and monitoring of network processes have increased. (standard design)
• Manual operating mechanism with mechanical and electrical
The extensive, coordinated SENTRON range of devices covers
closing
all applications between 16 A and 6300 A with compact and air
circuit-breakers. • Motorized operating mechanism with mechanical and electri-
cal closing.
The AC devices are available as circuit-breakers and non-auto-
matic circuit-breakers. DC devices are only available as non-au- The operating mechanisms with electrical closing can be used
tomatic circuit-breakers. for synchronization tasks.
Specifications
SENTRON WL circuit-breakers satisfy:
• IEC 60947-2
• DIN VDE 0660 Part 101
• climate-proof to DIN IEC 68 Part 30-2.
Also available with UL 489.
For further specifications, see Annex.

Siemens LV 30 · 2004 5/5


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
C ir c u it- b r e a k e r B r e a k in g c a p a c ity D im e n s io n s
m a x . ra te d c u rre n t n m a x (A ) c u a t 4 4 0 V A C (k A ) o r F ix e d - m o u n te d , D ra w -o u t
c c a t 3 0 0 V D C (k A ) 3 - /4 - p o le 3 - /4 - p o le

6 3 0 0 7 0 4 / 9 1 4 7 0 4 / 9 1 4 W id th
S iz e III

5 0 0 0
H 4 3 4 / 4 3 4 4 6 0 / 4 6 0 H e ig h t

1 0 0
4 0 0 0 2 9 1 / 2 9 1 3 8 5 / 3 8 5 D e p th

3 2 0 0
4 6 0 / 5 9 0 4 6 0 / 5 9 0 W id th
2 5 0 0

2 0 0 0
S iz e II

1 6 0 0 4 3 4 / 4 3 4 4 6 0 / 4 6 0 H e ig h t
D C N S H
1 2 5 0

5
1 )
3 0 5 5 8 0 1 0 0
1 0 0 0
2 9 1 / 2 9 1 3 8 5 / 3 8 5 D e p th
8 0 0

1 6 0 0 3 2 0 / 4 1 0 3 2 0 / 4 1 0 W id th

1 2 5 0
S iz e I

1 0 0 0 4 3 4 / 4 3 4 4 6 0 / 4 6 0 H e ig h t
N S
8 0 0 5 0 6 5
2 9 1 / 2 9 1 3 8 5 / 3 8 5 D e p th
6 3 0

N S E 0 _ 0 0 8 8 7 i
T h e d im e n s io n fo r th e d e p th o f th e c ir c u it- b r e a k e r is fr o m th e c ir c u it- b r e a k e r r e a r to th e in n e r s u r fa c e o f th e c lo s e d s w itc h g e a r d o o r .
1 ) S iz e II,   c u = 5 5 k A ; d e liv e r a b le fo r n m a x = 2 0 0 0 A a n d 2 5 0 0 A
Overview of SENTRON WL circuit-breakers/non-automatic circuit-breakers
Main circuit connections
All circuit-breakers are equipped with horizontal main circuit
connections on the rear for up to 5000 A as standard (horizontal
connection to busbars).
N S E 0 _ 0 0 9 6 9 a
N S E 0 _ 0 0 9 6 8 a
N S E 0 _ 0 0 9 6 7 a

N S E 0 _ 0 0 9 7 9

Circuit-breakers with a max. rated current of 6300 A are


equipped with vertical main circuit connections (for vertically
installed busbars).
Horizontal Front connection with single Vertical
The following options are available: connection hole or double hole connection
• Accessible from the front, one hole (for vertically installed
busbars)
• Accessible from the front, two holes (holes in accordance with
DIN 43673) (for vertically installed busbars)
N S E 0 _ 0 0 9 7 1 a
N S E 0 _ 0 0 9 7 0 a

• At the rear, vertical (for vertically installed busbars)


N S E 0 _ 0 0 9 7 3 a
N S E 0 _ 0 0 9 7 2 a
N S E 0 _ 0 0 9 6 7 a

• Connecting flange (for direct connection to guide frame up to


4000 A).
Auxiliary circuit connections Horizontal Front connection with single Vertical Flange
The type of connection for the auxiliary switches depends on the connection hole or double hole connection connection
type of installation:
• Withdrawable version Main current connections – connection types
The internal auxiliary switches are connected to the male con-
nector on the switch side. When the breaker is fully inserted, Connection using Screwless
N S E 0 _ 0 0 9 7 6 a
N S E 0 _ 0 0 9 7 5 a

the blades make a connection with the slide module in the screw connection connection system
guide frame. Various adapters can then be used to complete system (SIGUT) (tension spring)
(standard) (option)
the wiring (see illustration "Connection options for auxiliary
circuit connections").
Connection options for auxiliary circuit connections
• Fixed-mounted version
In this case the auxiliary circuit plugs are engaged directly onto
the circuit-breaker. The connectors are equipped with coding
pins that prevent them being mistakenly interchanged.

5/6 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
Operator panel • The withdrawable circuit-breaker cannot be moved when it is
in the ON position
The operator panel is designed to protrude from a cutout in the
door providing access to all operator controls and displays with • Coding of the rated current between the guide frame and the
the door closed. withdrawable circuit-breaker.
The operator panels for all circuit-breakers (fixed-mounted/with- Withdrawable short-circuit, ground, and bridging units
drawable designs, 3-/4-pole) are identical. The operator panel
ensures degree of protection IP20. Portable positively-driven ground and short-circuit devices are
used for the disconnected system sections to verify isolation
Safety and reliability from the supply at the workplace.
To protect the circuit-breakers and plant against unauthorized Withdrawable grounding units allow simple and comfortable
switching as well as the maintenance and operator personnel, grounding. They are simply inserted into the guide frames in
the system contains many blocking devices. Others can be ret- place of the corresponding withdrawable circuit-breakers. This
rofitted. ensures that these devices are always first connected with the
Other safety features include: ground electrode and then with the components to be grounded.
• Incoming supply from above or below, as required The ground terminals are fitted to the side of the switch enclo-
• Locking of the guide frame with the circuit-breaker removed, as sure and establish the connection when inserted into the guide
standard frame.
• Locking of the withdrawable circuit-breaker against movement,
as standard Short-time current of the ground 15 kA (500 ms)
• High degree of protection with cover IP55 terminal
• Mechanical closing lockout after overload or short-circuit trip-
ping as standard
Rated operational voltage
Specification
1000 V
DIN VDE 0683
5
• The circuit-breaker is always equipped with the required num-
ber of auxiliary supply connectors
All withdrawable terminals are short-circuited and grounded on
• Devices with electronic overcurrent trip units from ETU45B and delivery.
higher are always equipped with temperature sensors on BSS
and COM15 module. Qualified electricians can easily convert it to a withdrawable
bridging unit by following the enclosed instructions.
Standard version
In addition, the withdrawable unit can be adapted to each rated
SENTRON WL circuit-breakers are equipped with the following current of a frame size.
features as standard:
Withdrawable short-circuit and grounding unit
• Mechanical ON and OFF pushbutton
• Manual drive with mechanical request The withdrawable short-circuit and grounding unit consists of a
breaker enclosure with penetration blades which are connected
• Switch position indication with the short-circuiting link.
• Ready-to-close indicator
Depending on the version, the short-circuiting links are arranged
• Memory status indicator at the top or bottom. The ground and short-circuit connections
• Auxiliary switches (2 NO + 2 NC) are established when the device is inserted.
• Rear horizontal main circuit connections for fixed mounted and It must be ensured that the side to be short-circuited and
withdrawable versions up to 5000 A, and rear vertical main cir- grounded is not live. For this reason it is recommended that the
cuit connections for 6300 A applications withdrawable unit is only wound in when the door is closed.
• For 4-pole circuit-breakers, the fourth pole (N) is installed on Withdrawable bridging unit
the left and is 100% loadable
• Contact erosion indicator for the main contacts The withdrawable bridging unit consists of a breaker enclosure
in which all disconnection components and the operating mech-
• Auxiliary circuit plug system with SIGUT screw-type terminals. anism have been replaced with simple connections between the
Delivery inclusive of all auxiliary circuit connectors to internal upper and lower contacts.
specifications including coding device for the prevention of in-
correct installation of fixed-mounted circuit-breakers
• Mechanical "tripped" indicator for electronic overcurrent trip
unit system
• Mechanical closing lockout after tripping operation
• Control panel cannot be taken off with the switch in the ON
position
• User manual on CD-ROM (for printed version see options)
Additional features of the withdrawable design:
• Main contacts:
Laminated receptacles in the guide frame, penetration blades
on the withdrawable circuit-breaker
• Position indicator in the control panel of the withdrawable
circuit-breaker
• Captive manual crank lever for moving the withdrawable
circuit-breaker
• Guide frame with guide rails for easy moving of the withdraw-
able circuit-breaker
• The withdrawable circuit-breaker can be locked to prevent it
being pushed out of position

Siemens LV 30 · 2004 5/7


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
Circuit-breaker
$ Arc chute
(2 8 ) (1 )
% Carrying handle
& Labeling plates
(2 )
(2 7 ) ( Motor cutout switch (option) or
"Electrical ON" (option)
) Name plate for circuit-breaker
(2 6 ) (3 ) * Spring charge indicator
(4 ) + "Mechanical ON" button
(2 5 ) , Rated current indication
(5 )
- Positioning pictogram
(2 4 ) . Operating cycles counter (option)
(6 ) / Hand-operated lever
(2 3 ) 0 Crank handle
(7 ) 1 Withdrawable unit drive shaft
(2 2 )
2 Equipment plate
(2 1 ) 3 Grounding connection
(8 ) 4 Position indicator
5 Table for ground-fault protection

5 (2 0 ) (9 ) 6 Safety lock for crank handle (option)


7 Mechanical unlocking of
crank handle (option)
(1 9 ) (1 0 )
8 Electronic overcurrent trip unit
(1 1 )
9 Rating plug
(1 8 )
: "Mechanical OFF" button or
"EMERGENCY-STOP" mushroom push-
(1 7 ) (1 2 ) button (option)
(1 3 ) ; Ready-to-close indicator
(1 6 ) < Switch position indication
(1 4 )
(1 5 ) = "Tripped" indicator (reset button)
N S E 0 _ 0 0 9 6 5 a > “Secure OFF"
locking device (option)
? Operator panel
@ Male connector for auxiliary connections

Guide frame

$ Arc chute cover (option)


% Blow-out openings
(1 ) & Opening for crane hook
(2 ) ( Shutter (option)
) Locking device (shutter) (option)
* Name plate for guide frame
(1 8 ) (3 ) + Isolating contacts
, Ground terminal Ø 14 mm
- Locking device for racking rail
. Locking device against movement when
cabinet door is open (option)
(1 7 ) (4 )
/ Door interlock for guide frame
(option)
(5 )
0 Racking rail
(1 6 )
(6 ) 1 Factory-set rated current coding
2 Sliding contact for breaker grounding
(option)
(7 )
3 Equipment-dependent coding (option)
(1 5 )
4 Shutter actuator (option)
(1 4 ) 5 Position indication switch (option)
(8 ) 6 Sliding contact module for auxiliary con-
(1 3 ) ductors (number depends on equipment)

(1 2 )

(9 )
(1 1 )
(1 0 ) N S E 0 _ 0 0 9 6 6 a

5/8 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
Auxiliary releases Automatic resetting of closing lockout
Up to two auxiliary releases can be installed at the same time. When the ETU is activated, reclosing of the circuit-breaker is
The following are available: prevented until the trip unit is either electrically or manually reset.
If the "Automatic resetting of closing lockout" option is used, the
1 shunt release circuit-breaker is ready to close immediately after tripping. Re-
or 1 undervoltage release setting the manual "tripped" indicator is not included in this op-
or 2 shunt releases tion.
or 1 shunt release
+ 1 undervoltage release. Tripped signal switch
Shunt release If the circuit-breaker has tripped due to an overload, short-cir-
cuit, ground fault or extended protection function, the tripped
When the operating voltage is connected to the shunt release, signal switch can indicate this. This signal switch is available as
the circuit-breaker is opened immediately. The shunt release is an option. If the circuit-breaker is used for communication, this
available in the variants 5 % ON-time for overexcitation and option is supplied as standard.
100 % ON-time for permanent excitation. This means that it is
also possible to block the circuit-breaker against being jogged Ready-to-close signal switch
into closing. The SENTRON WL circuit-breakers are equipped with an optical
An energy storage device for shunt releases allows the circuit- ready-to-close indicator as standard. In addition, the ready-to-
breaker to be opened even if the control voltage is no longer close status can be transmitted by means of a signal switch as
available. an option. If the switch is used for communication, the signal
switch is supplied as standard.
Undervoltage release
The undervoltage release causes the circuit-breaker to be
opened if the operating voltage falls below a certain value or is
Locking devices
Locking device in OFF position
5
not applied. The circuit-breaker cannot be opened manually or This function prevents closing of the circuit-breaker and fulfills
by means of an electrical ON command if the undervoltage re- the specifications for main switches to EN 60204 (VDE 0113) –
lease is not connected to the rated voltage. The undervoltage re- disconnector unit. This lockout only affects this switch.
lease has no delay as standard. A delay can be set by the cus-
tomer in the range between td < 80 ms and td < 200 ms. If the circuit-breaker is replaced, closing is no longer prevented
unless the new circuit-breaker is also protected against unautho-
In addition, an undervoltage release with a delay in the range rized closing.
from 0.2 to 3.2 s is available.
To activate the locking device, the circuit-breaker must be
Alarm switch for auxiliary releases opened. The locking device is disabled when the circuit-breaker
One signal contact is used for each auxiliary release to deter- is closed. The lock is only activated when the key is removed.
mine the positions of the auxiliary releases. The safety key can only be removed in the OFF position.

Closing solenoid Locking device for "electrical ON"

The closing solenoid is used to close the circuit-breaker electri- This prevents unauthorized electrical closing from the operator
cally by means of a local electrical ON command or by a remote panel. Mechanical closing and remote closing remain possible.
unit. The lock is only activated when the key is removed.

Motorized operating mechanism Locking device for "mechanical ON"

The operating mechanism is used to load the storage spring au- This prevents unauthorized mechanical closing. The mechanical
tomatically. ON button can only be activated if the key is inserted (key oper-
ation). Closing with the "electrical ON" button and remote closing
The operating mechanism is activated if the storage spring has remain possible. The lock is only activated when the key is re-
been unloaded and the control voltage is available. moved.
It is switched off automatically after loading. This does not affect "Secure OFF", switch-independent locking device against unau-
manual loading of the storage spring. thorized closing
Indicators, signals, and operator controls This special switch-independent function for withdrawable cir-
cuit-breakers prevents closing and fulfills the specifications for
Motor STOP switch main switches to EN 60204 (VDE 0113) – disconnector unit. Un-
Control switch for switching off the motorized operating mecha- authorized closing remains impossible even after the circuit-
nism (automatic loading). breaker has been exchanged.
Operating cycles counter To activate the lock, the circuit-breaker must be opened. The
locking device is disabled when the circuit-breaker is closed.
The motorized operating mechanism can be supplied with a The lock is only activated when the key is removed. The safety
5-digit operating cycles counter. The display is incremented by key can only be removed in the OFF position.
"1" as soon as the storage spring is fully loaded.
Resetting the manual "tripped" signal
When the circuit-breaker has tripped, this is indicated by the red
protruding reset button on the ETU. When the reset button is ac-
tivated, the tripping solenoid and tripped signal are reset. If this
display is to be reset remotely, the reset button can be equipped
with a reset solenoid.
This option allows the circuit-breaker to be reset both manually
and electrically.

Siemens LV 30 · 2004 5/9


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
Locking device for manual crank Additional equipment for guide frames
Prevents removal of the crank. The circuit-breaker is protected Shutters
against movement. The lock is only activated when the key is re-
moved. The sealing strips of the shutter seal the laminated contacts of
the guide frame when the withdrawable circuit-breaker is re-
Locking device for "mechanical OFF" moved and therefore implement shock protection.
Prevents unauthorized mechanical opening from the operator The sealing strips can be manually opened using the strip le-
panel. The mechanical OFF button can only be activated if the vers.
key is inserted (key operation). Remote opening remains possi-
ble. The lock is only activated when the key is removed. The position of the sealing strips can be locked in various posi-
tions using padlocks for securing against tampering.
Locking device for hand-operated lever
Rated current coding unit between circuit-breaker and guide
The hand-operated lever can be locked with a padlock. The stor- frame
age spring cannot be loaded manually.
Withdrawable circuit-breakers and guide frames are equipped
Locking device against resetting the "tripped" indicator with a rated current coding unit as standard.
A lockable cover prevents manual resetting of the "tripped" indi- This ensures that only circuit-breakers whose penetration blades
cator after overcurrent tripping. This locking device is supplied are suited to the laminated contacts of the guide frame can be
together with the transparent cover for electronic overcurrent trip inserted into a guide frame (see diagram below).
units.
Sealing devices
5 Sealing cap for "electrical ON" button
The "electrical ON" button is equipped with a sealing cap as
standard. (1)
Sealing cap for "mechanical ON and OFF" buttons
The locking set contains covering caps which can be sealed. (4)

Sealing device for electronic overcurrent trip units (2)


NSE01031

The transparent cover can be sealed. The configuration sections (3) (5)
are covered to prevent unauthorized access. Openings allow NSE01032

access to the query and test button. (1) Guide frame, interior of l/h side; interior of r/h side similar
Blocking devices (2) Coding pin on racking rail in guide frame
(3) Racking rail
Closing lockout when cabinet door is open (4) Withdrawable circuit-breaker, r/h side; l/h side similar
Ready-to-close is deactivated mechanically when the cabinet (5) Coding pin on guide frame
door is open. The circuit-breaker can neither be mechanically
nor electrically closed. The blocking signal is transmitted by Rated current coding unit between circuit-breaker and guide frame
means of a Bowden wire.
Blocking device against movement for withdrawable circuit-
Equipment-dependent coding
breakers when the cabinet door is open.
Withdrawable circuit-breakers and guide frames can be retrofit-
The manual crank is blocked when the cabinet door is open and
ted with an equipment-dependent coding unit.
cannot be removed. The withdrawable circuit-breaker cannot be
moved. The lock only affects the inserted manual crank. This allows different designs of circuit-breakers and guide
frames to be uniquely assigned. If the circuit-breaker and guide
Locking of the control cabinet door
frame have been assigned different codes, the circuit-breaker
The control cabinet door cannot be opened if cannot be inserted.
• the fixed-mounted circuit-breaker is closed (the blocking sig- 36 different coding options can be selected.
nal is transmitted via the Bowden wire) or
Position indicator switch for guide frames
• if the withdrawable circuit-breaker is in the connected position.
The guide frame can be retrofitted with position indicator
Blocking mechanism via "mechanical ON and OFF" buttons
switches. These can be used to determine the position of the cir-
The "mechanical ON" and "OFF" buttons are covered with a cap cuit-breaker in the guide frame.
which only allows activation with a tool. These covering caps are
The position indicator switches have factory-fitted 1.5 m long ca-
part of the locking set.
bles and are mounted on the supporting plate. Two versions are
available (see table below).

5/10 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
Positions of the withdrawable circuit-breaker in the guide
frame
Display Position indicator Main circuit Auxiliary circuit Control cabinet door Shutter
Maintenance position disconnected disconnected open closed
(2) CONNECT

(1)
TEST

(4) DISCON

NSE01033
NSE01037

Disconnected position CONNECT


disconnected disconnected closed closed
(3)
TEST

DISCON

NSE01034 NSE01038

Test position CONNECT


disconnected connected closed closed

TEST

DISCON

NSE01035
NSE01039

Connected position CONNECT


connected connected closed open

TEST

DISCON
5
NSE01036 NSE01040

(1) Auxiliary circuit (2) Main circuit (3) Control cabinet door (4) Shutter

Mutual mechanical circuit-breaker interlocking Phase barriers


The module for mutual mechanical interlocking can be used for The plant engineering company can manufacture phase barriers
one or two SENTRON WL circuit-breakers and can be adapted made of insulating material for the arcing fault barriers. The rear
easily to the corresponding versions. The fixed-mounted and panel of the fixed-mounted circuit-breakers or guide frames are
withdrawable circuit-breaker versions are fully compatible and equipped with guide grooves.
can therefore be used in a mixed configuration in an installation.
This also applies to circuit-breakers 3WN6 and 3WN1. Arc chute cover
The circuit-breakers can be mounted alongside each other or The arc chute cover is available as optional equipment for the
one above the other, whereby the spacing of the circuit-breakers guide frame (standard for versions in accordance with UL 489).
is determined solely by the length of the Bowden cable. The The arc chute cover protects switchgear components which are
Bowden cables are supplied in standard lengths of 2 m. Inter- located directly above the circuit-breaker.
lock signals are looped through via the Bowden cables. Inter- Door sealing frame and cover
locking is only effective in the connected position in the case of
withdrawable circuit-breakers. The mechanical lifetime of the SENTRON WL circuit-breakers have degree of protection IP20
Bowden wires is 10,000 operating cycles. as standard. However, if the switchgear is to be equipped with a
higher degree of protection, a door sealing frame with IP40 and
Also see the following table for mutual mechanical interlocking a cover with IP55 are available.
of circuit-breakers.

Mutual mechanical interlocking of circuit-breakers – examples


Mutual interlocking of two Interlocking between three Mutual interlocking of three Interlocking of three circuit-
circuit-breakers circuit-breakers circuit-breakers breakers, two of them mutual

G G G
S1 S2 S1 S3 S1 S3
S1 S2 S3

S2 S1 S2 S3 S2

NSE01041 NSE01042 NSE01043 NSE01044 NSE01045

Siemens LV 30 · 2004 5/11


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

■ Functions
Functions of the electronic overcurrent trip units

ETU15B ETU25B ETU27B

Rating Plug
Rating Plug

NSE00882a
NSE00880a

NSE00881a
TEST QUERY CLEAR
TEST QUERY CLEAR

R R
R

5 t
s d

s d
s d
t s d
g
i t g

N S E 0 _ 0 0 9 5 0 b N S E 0 _ 0 0 9 5 1 b N S E 0 _ 0 0 9 5 2 b

ETU15B ETU25B ETU27B


Basic protection functions
Overload protection L ✔ ✔ ✔
Short-time delayed short-circuit protection S – ✔ ✔
Instantaneous short-circuit protection I ✔ ✔ ✔
Neutral conductor protection N – – ✔
Ground-fault protection G – – ✔

Additional functions
N-conductor protection can be switched on/off – – ✔
Short-time delayed short-circuit protection can be switched on/off – – –
Non-delayed short-circuit protection can be switched on/off – – –
Thermal image can be switched on/off – – –
Load monitoring – – –
Short-time delayed short-circuit protection can be switched – – –
to I2t
Non-delayed short-circuit protection adjustable ✔ – –
Overload protection switchable to I4t – – –
Overload protection can be switched on/off – – –
N-conductor protection adjustable – – –
Selectable parameter sets – – –

Configuration and displays


Configuration via rotary coding switches (10 steps) ✔ ✔ ✔
Configuration via communication (absolute values) – – –
Configuration via user interface of ETU (absolute values) – – –
Configuration of expanded protection functions – – –
LCD alphanumerical – – –
Graphic LCD – – –

Measurement function
Measurement function – – –
Measurement function Plus – – –

Communication
CubicleBUS – – –
Communication via PROFIBUS DP – – –
Communication via Ethernet – – –
✔ Standard – Not available ❑ Optional
Detailed information about the functions of the electronic overcurrent trip units is given in the following.

5/12 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

ETU76B

ETU45B ETU55B

Rating Plug
Rating Plug
=

Rating Plug
12

OFF : cs cw

GFM AT 55B-76B
GFM AT 45B GFM AT 55B-76B
g
ALARM

NSE00884a
NSE00883a

NSE00886a
TEST QUERY CLEAR
TEST QUERY CLEAR TEST QUERY CLEAR

IR IR IR
tR tR tR

Isd
t sd
Isd
t sd
Isd
t sd
5
Ig Ig Ig
Ii Ii Ii
tg tg tg
NSE0 00953a NSE0 00953a NSE0 00953a

ETU45B ETU55B ETU76B

✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
❑ ❑ ❑

✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔
✔ ✔ ✔

✔ ✔ ✔
✔ ✔ ✔
– ✔ ✔
✔ ✔ ✔
– ✔ ✔

✔ – –
– ✔ ✔
– – ✔
❑ ❑ ❑
❑ – –
– – ✔

❑ ❑ ❑
❑ ❑ ❑

✔ ✔ ✔
❑ ❑ ❑
❑ ❑ ❑

Siemens LV 30 · 2004 5/13


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
Electronic overcurrent trip units (ETU) "Tripped" indication/
The electronic overcurrent trip unit is controlled by a micropro- reset button
cessor and operates independently of an auxiliary voltage. It en-
ables systems to be adapted to the different protection require-
ments of distribution systems, motors, transformers and
generators.
Communication capability Text display
with 15°
The international standard PROFIBUS DP can be used to trans- inclination,
mit data such as current values, switching states, reasons for rotatable 180°
tripping etc. to central computers.
Data acquisition and energy management are possible in con- Microswitch
junction with the measurement function. for switchable
overload
A new internal circuit-breaker data bus allows switchboard characteristic
panel communication between the circuit-breaker and second-
ary devices in the circuit-breaker panel:
• Actuation of analog displays
• Ability to test the communication build-up with circuit-breakers
• Display of release status and tripping reasons

5
• Input module for reading in further switchgear panel signals Rated current
and for transmission of these signals to the PROFIBUS DP module /
• Various output modules for displaying measured values. rating plug

This means that it is not only possible to monitor the device re-
motely, but also to transmit current values from the entire system Ground-fault
protection
and perform switching operations remotely. module
I2t and I4t characteristic for overload protection (retrofittable)

The best protection for the whole switchgear is achieved by set- Example of configuration for ETU45B
ting the tripping characteristic to an optimum value. In order to Rated current module / rating plug
achieve optimal discrimination for upstream fuses or medium
voltage protection systems, the inclination of the characteristic The rated current module is an exchangeable module which al-
can be selected for the overload range. lows the user to reduce the rated device current so as to adapt
it optimally to the plant; e.g. if a new plant section is taken into
The overload protection L (long time protection) for the elec- operation. The rated current module must be selected to fit the
tronic overcurrent trip units ETU45B, ETU55B, and ETU76B al- rated current of the plant.
lows the characteristic to be switched between I2t and I4t.
Selectable parameters
The I4t characteristic improves discrimination for downstream
circuit-breakers and fuses. In the case of quick changes of power supply conditions, e.g. for
switchovers from transformer to generator operation or if a sec-
Electronic overcurrent trip units ETU tion of the supply is shutdown when the shift changes,
Modularity has also been strictly emphasized during the devel- SENTRON WL allows the relevant protection parameters to be
opment of the electronic overcurrent trip units. These are some quickly adapted to the new conditions.
of the modules which can be easily retrofitted at any time: The ETUs contain two independent tripping characteristics
(parameter sets). The switchover is completed within 200 ms
• Ground-fault protection modules
and is performed with the help of an external signal.
• Communication
• Measurement function
• Displays
• Rated current modules (rating plugs)
This allows quick adaptation to new local mains specifications.
In addition, new innovative functions have been included in the
ETUs.

5/14 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
ETU15B electronic overcurrent trip unit

O p tio n : s a fe ty lo c k
p re v e n ts p re s s in g o f Application:
M e c h a n ic a l R E S E T re s e t b u tto n a fte r
fo r r e c lo s in g lo c k o u t o v e rc u rre n t re le a s e Simple building and plant protec-
tion without time-selective grading
up to 3200 A
Features:
• Adjustable overload protection
In d ic a to r : o v e r c u r r e n t E T U 1 5 B with I2t characteristic with
r e le a s e a c tiv a te d preset delay time
In d ic a to r : o v e r lo a d a la r m In d ic a to r : fa u lt in tR = 10 seconds at 6 × IR
o v e r c u r r e n t r e le a s e
• Non-delayed short-circuit pro-
R o ta r y s w itc h fo r s e ttin g tection adjustable in the range
v a lu e , o v e r lo a d r e le a s e
from 2 to 8 × In
• Overload display
R o ta r y s w itc h fo r s e ttin g • Protection function is set by
v a lu e , in s ta n ta n e o u s S e a lin g r in g means of the rotary coding
s h o r t- c ir c u it r e le a s e
switch
For technical details see table
"Function overview of the
electronic overcurrent trip unit sys- 5
N S E 0 _ 0 0 9 5 4

T e s t s o c k e t tem" under "Technical specifica-


tions".

ETU25B electronic overcurrent trip unit

O p tio n : s a fe ty lo c k
Application:
p re v e n ts p re s s in g o f
re s e t b u tto n a fte r Classical building, motor and plant
M e c h a n ic a l R E S E T
fo r r e c lo s in g lo c k o u t o v e rc u rre n t re le a s e protection with time-selective co-
ordination for up to 6300 A
Features:
• Adjustable overload protection
In d ic a to r : o v e r c u r r e n t
with I2t characteristic
r e le a s e a c tiv a te d E T U 2 5 B preset delay time
In d ic a to r : o v e r lo a d a la r m
tR = 10 seconds at 6 × IR
R a tin g P lu g In d ic a to r : fa u lt in
o v e r c u r r e n t r e le a s e • Short-time delayed short-circuit
R a te d c u r r e n t m o d u le
protection adjustable in the
R o ta r y s w itc h fo r s e ttin g In d ic a to r : c a u s e o f r e le a s e range from 1.25 to 12 × In and
v a lu e , o v e r lo a d r e le a s e
• Non-delayed short-circuit pro-
R o ta r y s w itc h fo r s e ttin g R o ta r y s w itc h fo r d e la y ,
v a lu e , in s ta n ta n e o u s s h o r t- c ir c u it r e le a s e
tection preset to
s h o r t- c ir c u it r e le a s e 20 × In/max. 50 kA
S h o r t- c ir c u it p r o te c tio n • Can be adapted to the required
fix e d s e ttin g S e a lin g r in g
plant currents through retrofitta-
N S E 0 _ 0 0 9 5 5

ble rated current module to en-


sure overload protection in the
Q u e ry p u s h b u tto n
T e s t p u s h b u tto n
range from 100 A to 6300 A.
C le a r p u s h b u tto n
T E S T Q U E R Y C L E A R

T e s t s o c k e t
• Overload display
• Indicates the reason for tripping
by means of an LED
• Test option for the trip unit
• Protection functions are
set by means of the
rotary coding switch
For technical details see table
"Function overview of the elec-
tronic overcurrent trip unit system"
under "Technical specifications".

Siemens LV 30 · 2004 5/15


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
ETU27B electronic overcurrent trip unit
Application:
O p tio n : s a fe ty lo c k
p re v e n ts p re s s in g o f Classical building, motor and plant
M e c h a n ic a l R E S E T re s e t b u tto n a fte r
fo r r e c lo s in g lo c k o u t o v e rc u rre n t re le a s e protection with time-selective
coordination for up to 6300 A
N S E 0 _ 0 0 9 5 6 a

Features:
The same as ETU25B but also
In d ic a to r : o v e r c u r r e n t including
r e le a s e a c tiv a te d E T U 2 7 B N - c o n d u c to r p r o te c tio n
o n /o ff • Reversible neutral conductor
In d ic a to r : o v e r lo a d a la r m O F F O N

R a tin g P lu g In d ic a to r : fa u lt in protection
R a te d c u r r e n t m o d u le o v e r c u r r e n t r e le a s e
• Permanently integrated ground-
R o ta r y s w itc h fo r s e ttin g N fault protection. Calculation of
v a lu e , o v e r lo a d r e le a s e In d ic a to r : c a u s e o f r e le a s e the ground-fault current through
R o ta r y s w itc h fo r s e ttin g R o ta r y s w itc h fo r d e la y , vectorial summation current for-
v a lu e , in s ta n ta n e o u s s h o r t- c ir c u it r e le a s e mation
s h o r t- c ir c u it r e le a s e
S h o r t- c ir c u it p r o te c tio n S e a lin g r in g
For technical details see table
fix e d s e ttin g "Function overview of the elec-
O F F
R o ta r y s w itc h fo r d e la y ,
R o ta r y s w itc h fo r s e ttin g e a r th - fa u lt p r o te c tio n
tronic overcurrent trip unit system"
v a lu e , e a r th - fa u lt p r o te c tio n under "Technical specifications".
5 Q u e ry p u s h b u tto n
T e s t p u s h b u tto n
T E S T Q U E R Y C L E A R
C le a r p u s h b u tto n
T e s t s o c k e t

ETU45B electronic overcurrent trip unit


Application:
O p tio n : s a fe ty lo c k
M e c h a n ic a l R E S E T p re v e n ts p re s s in g o f Low-cost all-round system for
fo r r e c lo s in g lo c k o u t re s e t b u tto n a fte r
S c r o ll u p o v e rc u rre n t re le a s e intelligent buildings and all types of
In d ic a to r s : O p tio n : a lp h a n u m e r ic d is p la y industrial applications –
O v e r c u r r e n t r e le a s e S c r o ll d o w n
"CubicleBUS integrated"
a c tiv a te d
In d ic a to r : fa u lt in Features:
O v e r lo a d a la r m o v e r c u r r e n t r e le a s e
C O M M U N IC A T IO N T h e rm a l m e m o ry o n /o ff The same as ETU25B but also
E X P A N D E D E T U 4 5 B N -c o n d u c to r p r o te c tio n o n /o ff including
O F F O N
S e ttin g v a lu e • Adjustable time-lag class
R a te d c u r r e n t m o d u le N -c o n d u c to r o v e r lo a d
R a tin g P lu g for overload protection
R o ta r y s w itc h fo r s e ttin g =
T ra n s fe r o f o v e r lo a d
v a lu e , o v e r lo a d r e le a s e c h a ra c te r is tic I2 t / I 4 t • Selectable characteristic for over-
1

R o ta r y s w itc h fo r s e ttin g
1
1
R o ta r y s w itc h fo r d e la y ,
load and short-delayed short-cir-
1
v a lu e , in s ta n ta n e o u s 1
o v e r lo a d r e le a s e cuit range (current discrimination)
s h o r t- c ir c u it r e le a s e for more accurate discrimination
R o ta r y s w itc h fo r d e la y ,
R o ta r y s w itc h fo r s e ttin g s h o r t- c ir c u it r e le a s e
1 2

adaptation to upstream fuses and


v a lu e , s h o r t- c ir c u it In d ic a to r: c a u s e o f r e le a s e
p r o te c tio n I i= O F F : IC S = I C W protection devices
M A X = 0 .8 x IC W
S e a lin g r in g • Thermal image as restart protec-
S e le c to r fo r
O p tio n : e a r th - fa u lt m o d u le
e a r th - fa u lt p r o te c tio n S 1
G F M A T 4 5 B
tion for tripped motor outgoing
In d ic a to r : e a r th - fa u lt a la r m
R o ta r y s w itc h fo r s e ttin g g A L A R M
feeders
v a lu e , e a r th - fa u lt
p r o te c tio n In d ic a to r : e a r th - fa u lt tr ip p e d • Reversible and adjustable neutral
R o ta ry s w itc h fo r d e la y ,
conductor protection
R o ta ry s w itc h fo r s e ttin g 2
v a lu e , e a r th - fa u lt a la r m T E S T Q U E R Y C L E A R e a rth -fa u lt p r o te c tio n t g / I t g
• Modular ground-fault module with
T e s t p u s h b u tto n C le a r p u s h b u tto n alarm and tripping functions which
Q u e ry p u s h b u tto n T e s t s o c k e t can be set separately
N S E 0 _ 0 0 9 5 7
• Communication interface,
measurement function (Plus),
optional connection of external
modules or for retrofitting
• Extended protection functions
possible with measurement func-
tion
• Optional high-contrast display with
viewing angle adjustment option
• The protection functions can be
set by means of a rotary coding
switch or sliding-dolly switch
For technical details see table
"Function overview of the
electronic overcurrent trip unit sys-
tem" under "Technical specifica-
tions".

5/16 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
ETU55B electronic overcurrent trip unit

O p tio n : s a fe ty lo c k Application:
p re v e n ts p re s s in g o f
M e c h a n ic a l R E S E T re s e t b u tto n a fte r The trip unit for special
fo r r e c lo s in g lo c k o u t o v e rc u rre n t re le a s e safety requirements which can be
set via exclusive external parame-
In d ic a to r s : ter access for generator and motor
O v e r c u r r e n t r e le a s e protection as well as industrial
a c tiv a te d
O v e r lo a d a la r m
applications – "CubicleBUS
integrated"
C O M M U N IC A T IO N
E T U 5 5 B
E X P A N D E D Features:
R a te d c u r r e n t m o d u le R a tin g P lu g In d ic a to r : fa u lt in
o v e r c u r r e n t r e le a s e The same as ETU45B but also
including
F ie ld s fo r n o tin g • Two protection parameter sets
s e ttin g v a lu e s
F ie ld s fo r n o tin g which can be stored separately
s e ttin g v a lu e s in the trip unit (switchover
In d ic a to r : c a u s e o f r e le a s e is performed via external signal)
O F F : c s c w

O p tio n : e a r th - fa u lt m o d u le
• With overload protection which
G F M A T 5 5 B -7 6 B
In d ic a to r s : can be deactivated for use in
E a r th - fa u lt a la r m
F ie ld s fo r n o tin g modern drive technology
E a r th - fa u lt tr ip p e d

5
s e ttin g v a lu e s
F ie ld s fo r n o tin g
• Adjustable delay of
T e s t p u s h b u tto n
s e ttin g v a lu e s delayed short-circuit protection
T E S T Q U E R Y C L E A R
C le a r p u s h b u tto n up to 4000 ms
Q u e ry p u s h b u tto n
T e s t s o c k e t • Neutral conductor protection
N S E 0 _ 0 0 9 5 8 adjustable up to IN = 2 × In
• Setting of protection functions by
means of Breaker Data Adapter
(BDA) or via communication in-
terface
For technical details see table
"Function overview of the
electronic overcurrent trip unit sys-
tem"

ETU76B electronic overcurrent trip unit

O p tio n : s a fe ty lo c k
Application:
p re v e n ts p re s s in g o f
M e c h a n ic a l R E S E T re s e t b u tto n a fte r The multi-talent with graphical
fo r r e c lo s in g lo c k o u t
E T U 7 6 B
o v e rc u rre n t re le a s e display for system analysis –
"CubicleBUS integrated"
Features:
In d ic a to r s : The same as ETU55B but also
O v e r c u r r e n t r e le a s e including
a c tiv a te d
G r a p h ic a l d is p la y • Graphical display of all
O v e r lo a d a la r m
C O M M U N IC A T IO N
parameters and events/
C o n tr o l k e y s fo r s e ttin g curve trends
E X P A N D E D
th e r e le a s e p a r a m e te r s • Storage of events and causes for
In d ic a to r : c a u s e o f r e le a s e tripping for detailed fault analysis
R a tin g P lu g
In d ic a to r : fa u lt in
o v e r c u r r e n t r e le a s e • Graphics display with high con-
R a te d c u r r e n t m o d u le trast, backlit display, and sleep
mode.
O p tio n : e a r th - fa u lt m o d u le In d ic a to r s :
G F M A T 5 5 B -7 6 B
E a r th - fa u lt a la r m For technical details see table
E a r th - fa u lt tr ip p e d
F ie ld s fo r n o tin g
"Function overview of the
s e ttin g v a lu e s F ie ld s fo r n o tin g electronic overcurrent trip unit sys-
s e ttin g v a lu e s tem" under "Technical specifica-
T e s t p u s h b u tto n tions".
T E S T Q U E R Y C L E A R C le a r p u s h b u tto n
Q u e ry p u s h b u tto n T e s t s o c k e t

N S E 0 _ 0 0 9 6 0

Siemens LV 30 · 2004 5/17


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
Ground-fault protection S e le c to r fo r In d ic a to r :
e a r th - fa u lt e a r th - fa u lt
Ground-fault releases "G" sense fault currents that flow to ground d e te c tio n a la r m
and that can cause fire in the plant. Multiple circuit-breakers S 1
connected in series can have their delay times adjusted so as to g A L A R M A L A R M t g (s ) 1 2 tg
provide graduated discrimination. A .5 .1
G
B .4 .2
When setting the parameters for the electronic overcurrent trip C .3 .3
unit it is possible to choose between "alarm" and "trip" in the D .2 .4
R o ta ry s w itc h
E .1 .5
event that the set current value is exceeded. The reason for trip- fo r s e ttin g
N S E 0 _ 0 0 9 6 1
ping is indicated by means of an LED when the query button is R o ta r y s w itc h v a lu e , e a rth -
activated. fo r s e ttin g v a lu e , fa u lt p r o te c tio n d e la y
e a r th - fa u lt a la r m tg /I2 tg
Modules Ground-fault module GFM A 45B

The electronic overcurrent trip unit versions ETU45B, ETU55B


and ETU76B can be retrofitted with a ground-fault module. The S e le c to r fo r In d ic a to r s : E a r th - fa u lt
electronic overcurrent trip unit ETU27B is fitted with this module e a r th - fa u lt
a la r m
d e te c tio n
as standard. G F M A T 4 5 B E a r th - fa u lt
R o ta ry s w itc h S 1
tr ip p e d
Two versions can be ordered: fo r s e t tin g g T R IP A L A R M A L A R M t g (s ) 1 2 tg
v a lu e ,
• GFM AT: Alarm and tripping e a rth -f a u lt G A .5 .1
B .4 .2
p ro te c tio n T R IP
• GFM A: Only alarm. C .3 .3
D .2 .4
O F F R o ta ry s w itc h

5
E .1 .5
fo r s e ttin g
N S E 0 _ 0 0 9 6 2
R o ta r y s w itc h v a lu e , e a rth -
fo r s e ttin g v a lu e fa u lt p r o te c tio n d e la y
e a r th - fa u lt a la r m tg /I t
2
g
Ground-fault module GFM AT 45B

F ie ld fo r In d ic a to r :
n o t in g E a r th - fa u lt
tra n s fe r G F M A 5 5 B -7 6 B a la r m
1
e a rth -fa u lt
d e te c t io n A L A R M A L A R M
1 g = A
1 2 t
t g = m s
F ie ld fo r F ie ld s fo r
N S E 0 _ 0 0 9 6 3
n o tin g s e ttin g n o tin g s e ttin g
v a lu e s v a lu e s
Ground-fault module GFM A 55B-76B

F ie ld fo r In d ic a to r s : E a r th - fa u lt
n o t in g a la r m
tra n s fe r G F M A T 5 5 B -7 6 B E a r th - fa u lt
g S 1
e a rth -fa u lt tr ip p e d
d e te c t io n A L A R M A L A R M
1 g = A

T R IP T R IP 1 2t
1 g = A t g = m s
F ie ld s fo r F ie ld s fo r
n o tin g s e ttin g N S E 0 _ 0 0 9 6 4
n o tin g s e ttin g
v a lu e s v a lu e s
Ground-fault module GFM AT 55B-76B

5/18 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data
Measurement method Setting
Vectorial summation current formation How the module is set depends on the measurement method
used (see above):
The N-conductor current and the three phase currents are mea-
sured directly. Measurement method 1: in position Sum I
Measurement method 2: in position G.
The electronic overcurrent trip unit determines the ground-fault
current by means of vectorial summation current formation for This setting can be implemented for the electronic overcurrent
the three phase currents and the N-conductor current. trip unit versions ETU55B and ETU76B with Menu/Comm.
Direct measurement of the ground-fault current Ground-fault protection with I2t characteristic
A current transformer with the transformation ratio 1200 A/1A is With the exception of the electronic overcurrent trip unit ETU27B,
used for measurement of the ground-fault current. The trans- all versions of the ground-fault modules are supplied with an I2t
former can be installed directly in the grounded neutral point of characteristic which can be activated.
a transformer.
This characteristic reduces the thermal load of the PE conductor
for ground faults with delayed tripping.
L1 Selection criteria for SENTRON WL circuit-breakers
SENTRON WL L2
Basic criteria for selecting circuit-breakers are:
L3
N • Max. short-circuit current at mounting location of circuit-
T5 PE breaker I k″ max.

5
NSE 00946 This value determines the short-circuit breaking capacity
or short-circuit current carrying capacity of the circuit-breaker.
• It is compared with the value Icu, Ics, Icw of the circuit-breaker
Three-pole circuit-breakers, current transformers in the neutral conductor and essentially determines the size of the circuit-breaker.
See "Overview of SENTRON WL circuit-breakers/non-auto-
L1 matic circuit-breakers".
L2 • Rated current In which is to flow through the branch circuit. This
SENTRON WL
L3 value must not be larger than the maximum rated current for
N the circuit-breaker.
The rated current for the SENTRON WL is set with the rating
T6 plug. See "Overview of SENTRON WL circuit-breakers/non-au-
PE tomatic circuit-breakers".
T6: 1200 A/1 A NSE 00947 • Ambient temperature
for the circuit-breaker.
Four-pole circuit-breakers, current transformers in the grounded neutral This is usually the temperature inside the switchgear cabinet.
point of the transformer.
• Version of the circuit-breaker
L1 • Minimum short-circuit current,
L2 which flows through the switching device. The trip unit must still
SENTRON WL L3 detect this value as a short-circuit and must respond by trip-
N ping.

T6
Protection functions of the circuit-breaker.
PE These are determined by the selection of the corresponding
electronic overcurrent trip unit. See table "Functions of the elec-
NSE 00948
T6: 1200 A/1 A tronic overcurrent trip units" under "Functions".

Four-pole circuit-breakers, current transformers in the grounded neutral


point of the transformer.

It is also possible to use a summation current transformer.

L 1
L 2
S E N T R O N W L L 3
N

P E

N S E 0 _ 0 1 2 5 1
T6: 1200 A/1 A

Use of a summation current transformer

Siemens LV 30 · 2004 5/19


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

■ Technical specifications
Short-circuit breaking capacity
Size I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S N S H H
up to AC 415 V
Icu kA 50 65 55 80 100 100
Ics kA 50 65 55 80 100 100
Icm kA 105 143 121 176 220 220
up to AC 500 V
Icu kA 50 65 55 80 100 100
Ics kA 50 65 55 80 100 100
Icm kA 105 143 121 176 220 220
up to AC 690 V
Icu kA 42 50 50 75 85 85
Ics kA 42 50 50 75 85 85
Icm kA 88 105 105 165 187 187
up to AC 1000 V

5
Icu kA – – – – 45 50
Ics kA – – – – 45 50
Icm kA – – – – 95 105

Rated short-time withstand current Icw of circuit-breakers


Size I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S N S H H
0.5 s kA 42 65 55 80 100 100
1s kA 42 50 55 65 80 100
2s kA 29.5 35 39 46 651)/702) 80
3s kA 24 29 32 37 501)/652) 65

Short-circuit breaking capacity Icc of non-automatic circuit-breakers


Size I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S N S H H
up to AC 500 V kA 42 65 55 80 100 100
up to AC 690 V kA 42 50 50 75 85 85
1) Size II with In max ≤ 2500 A.
2) Size II with In max = 3200 A.

5/20 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

Size I II
Type up to 3WL11 12 3WL11 16 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20
3WL11 10
Rated current In at 40 °C, at 50/60 Hz
Main conductor A up to 1000 1250 1600 800 1000 1250 1600 2000
Neutral conductor (only with 4-pole versions) A up to 1000 1250 1600 800 1000 1250 1600 2000
Rated operating voltage Ue at 50/60 Hz AC V up to 690 up to 690 up to 690 up to up to up to up to up to
(1000 V design, see options) 690/1000 690/1000 690/1000 690/1000 690/1000
Rated insulation voltage Ui AC V 1000 1000 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
Main circuits kV 12 12 12 12 12 12 12 12
Auxiliary circuits kV 4 4 4 4 4 4 4 4
Control circuits kV 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5
Isolating function to EN 60947-2 yes yes yes yes yes yes yes yes
Utilization category B
Permissible ambient temperature
in operation (in operation with LCD max. 55 °C) °C –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70 –25/+70
Storage (special conditions for LCDs must be °C –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70 –40/+70
observed)
Permissible load up to 55 °C (Cu bare) A 1000 1250 1600 800 1000 1250 1600 2000
at rear horizontal main up to 60 °C (Cu bare) A 1000 1250 1600 800 1000 1250 1600 2000
circuit connections up to 70 °C (Cu painted A 1000 1210 1490 800 1000 1250 1600 2000

5
black)
Power loss at In
with AC symmetrical load
Fixed-mounted circuit-breaker W 100 105 150 40 45 80 85 180
Withdrawable circuit-breaker W 195 205 350 85 95 165 175 320
Operating times
Make-time ms 35 35 35 35 35 35 35 35
Break-time ms 38 38 38 34 34 34 34 34
Electr. make-time (via activation solenoid)2) ms 80 80 80 100 100 100 100 100
Electr. break-time (via shunt release) ms 73 73 73 73 73 73 73 73
Electr. break-time (instantaneous undervoltage release) ms 73 73 73 73 73 73 73 73
Break-time through ETU, instantaneous short-circuit ms 501) 501) 501) 501) 501) 501) 501) 501)
release
Service life
mechanical (without maint.) Operating cycles 10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
mechanical (with maint.)3) Operating cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
electrical (without maint.) Operating cycles 10 000 10 000 10 000 7500 7500 7500 7500 7500
1000 V design Operating cycles – – – 1000 1000 1000 1000 1000
electrical (with maint.)3) Operating cycles 20 000 20 000 20 000 15 000 15 000 15 000 15 000 15 000
Operating frequency
690 V design 1/h 60 60 60 60 60 60 60 60
1000 V design 1/h – – – 20 20 20 20 20
Minimum interval between tripping operation by over- ms 80 80 80 80 80 80 80 80
current release and next making operation of the cir-
cuit-breaker (only with autom. mechanical resetting of
the lockout device)
Service position 3 0 ° 3 0 ° 3 0 ° 3 0 °
D h max.
= 1 mm

and/
or
N S E 0 0 0 0 6 1 N S E 0 0 0 0 6 2 NSE00927

Degree of protection IP20 without cabinet door, IP30 with door mounting frame, IP55 with cover
Main conductor Copper bars, Qty. 1 × 2× 2× 1× 1× 2× 2× 3×
minimum bare mm2 60 × 10 40 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10 50 × 10
cross-sections Copper bars, Qty. 1 × 2× 2× 1× 1× 2× 2× 3×
painted black mm2 60 × 10 40 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10 50 × 10
Auxiliary conductors (Cu) Standard connection = strain-
Max. no. of relief clamp
auxiliary conductors × without end sleeve 2 × 0.5 mm2 (AWG 20) to 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
cross-section with end sleeve to 1 × 0.5 mm2 (AWG 20) to 1 × 1.5 mm2 (AWG 16)
(solid/stranded) DIN 46228 T.2
with twin end sleeve 2 × 0.5 mm2 (AWG 20) to 2 × 1.5 mm2 (AWG 16)
optional conn. = tension spring
without end sleeve 2 × 0.5 mm2 (AWG 20) to 2 × 2.5 mm2 (AWG 14)
with end sleeve to 2 × 0.5 mm2 (AWG 20) to 2 × 1.5 mm2 (AWG 16)
DIN 46228 T.2
Weights 3-pole Fixed-mounted circ.-br. kg 43 43 43 56 56 56 56 56
Withdrawable circ.-br. kg 45 45 45 60 60 60 60 60
Guide frame kg 25 25 25 31 31 31 31 31
4-pole Fixed-mounted circ.-br. kg 50 50 50 67 67 67 67 67
Withdrawable circ.-br kg 54 54 54 72 72 72 72 72
Guide frame kg 30 30 30 37 37 37 37 37
1) Break-time on instantaneous short-circuit release with ETU15B = 85 ms. 3) Maintenance means: replace main contact elements and arc chutes (see
2) Make-time via activation solenoid for synchronization purposes Operator's Guide).
(short-time excited) 50 ms.

Siemens LV 30 · 2004 5/21


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

Size II III
Type 3WL12 25 3WL12 32 3WL13 40 3WL13 50 3WL13 63
Rated current In at 40 °C, at 50/60 Hz
Main conductor A 2500 3200 4000 5000 6300
Neutral conductor (only on 4-pole versions) A 2500 3200 4000 5000 6300
Rated operating voltage Ue at 50/60 Hz AC V up to 690/1000 up to 690/1000 up to 690/1000 up to 690/1000 up to 690/1000
(1000 V design, see options)
Rated insulation voltage Ui AC V 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp
Main circuits kV 12 12 12 12 12
Auxiliary circuits kV 4 4 4 4 4
Control circuits kV 2.5 2.5 2.5 2.5 2.5
Isolating function to EN 60947-2 yes yes yes yes yes
Utilization category B (except switching capacity class DC)
Permissible ambient temperature
in operation (in operation with LCD max. 55 °C) °C –25/+70 –25/+70 –25/+70 –25/+70 –25/+70
Storage (special conditions for LCDs must be observed) °C –40/+70 –40/+70 –40/+70 –40/+70 –40/+70
Permissible load up to 55 °C (Cu bare) A 2500 3200 4000 5000 5920
up to 60 °C (Cu bare) A 2500 3020 4000 5000 5810
up to 70 °C (Cu painted A 2280 2870 4000 5000 5500
black)
Power loss at In

5 with AC symmetrical load


Fixed-mounted circuit-breaker
Withdrawable circuit-breaker
W 270
W 520
410
710
520
810
630
1050
900
1600
Operating times
Make-time ms 35 35 35 35 35
Break-time ms 34 34 34 34 34
Electr. make-time (via activation solenoid) 2) ms 100 100 100 100 100
Electr. break-time (via shunt release) ms 73 73 73 73 73
Electr. break-time (instantaneous undervoltage release) ms 73 73 73 73 73
Break-time through ETU, instantaneous short-circuit ms 501) 501) 50 50 50
release
Service life
mechanical (without maint.) Operating cycles 10000 10000 5000 5000 5000
mechanical (with maint.)3) Operating cycles 15000 15000 10000 10000 10000
electrical (without maint.) Operating cycles 7500 4000 2000 2000 2000
1000 V design Operating cycles 1000 1000 1000 1000 1000
electrical (with maint.)3) Operating cycles 15000 15000 10000 10000 10000
Operating frequency
690 V design 1/h 60 60 60 60 60
1000 V design 1/h 20 20 20 20 20
Minimum interval between tripping operation by over-cur- ms 80 80 80 80 80
rent release and next making operation of the circuit-
breaker (only with autom. mechanical resetting of the lock-
out device)
3 0 ° 3 0 ° 3 0 ° 3 0 °
D h max.
= 1 mm

Service position
and/
or
N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2 NSE00927

Degree of protection IP20 without cabinet door, IP30 with door mounting frame, IP55 with cover
Main conductor Copper bars, Qty. 2 × 3× 4x 6x 6x
minimum bare mm2 100 × 10 100 × 10 100 x 10 100 x 10 120 x 10
cross-sections Copper bars, Qty. 2 × 3× 4× 6× 6×
painted black mm2 100 × 10 100 × 10 100 × 10 100 × 10 120 × 10
Auxiliary conductors (Cu) Standard connection = strain-relief
Max. no. of clamp
auxiliary conductors × without end sleeve 2 × 0.5 mm2 (AWG 20) to 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
cross-section with end sleeve to 1 × 0.5 mm2 (AWG 20) to 1 × 1.5 mm2 (AWG 16)
(solid/stranded) DIN 46228 T.2
with twin end sleeve 2 × 0.5 mm2 (AWG 20) to 2 × 1.5 mm2 (AWG 16)
optional connection = tension spring
without end sleeve 2 × 0.5 mm2 (AWG 20) to 2 × 2.5 mm2 (AWG 14)
with end sleeve to 2 × 0.5 mm2 (AWG 20) to 2 × 1.5 mm2 (AWG 16)
DIN 46228 T.2
Weights 3-pole Fixed-mounted circuit- kg 59 64 82 82 90
breaker
Withdrawable circuit-breaker kg 63 68 88 88 96
4-pole Guide frame kg 39 45 60 60 70
Fixed-mounted circuit- kg 71 77 99 99 108
breaker
Withdrawable circuit-breaker kg 76 82 106 106 108
Guide frame kg 47 54 84 84 119
1) Break-time on instantaneous short-circuit release with ETU15B = 85 ms. 3) Maintenance means: replace main contact elements and arc chutes
2) Make-time via activation solenoid for synchronization purposes (see Operator's Guide).
(short-time excited) 50 ms.

5/22 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

Size I ... III


Manual operating mechanism with mechanical closing
Closing/ Max. force required to operate the hand lever N ≤ 230
charging stored-energy Required number of strokes on the hand lever 9
feature
Manual operating mechanism with mechanical and electrical closing
Charging stored-energy
feature
Closing solenoid (CC) Operating range 0.85 ... 1.1 × Us
Extended operating range for battery operation for DC 24 V, DC 48 V 0.7 ... 1.26 × Us
DC 60 V, DC 110 V
DC 220 V
Power input AC/DC VA/W 15/15
Minimum command duration at Us for the closing solenoid ms 60
Short-circuit protection 1 A TDz (time-lag)/1 A
Smallest permissible DIAZED fuse (operational class gL)/
miniature circuit-breaker with C-characteristic
Manual/motorized operating mechanism with mechanical and electrical closing
Manual operating mecha- For data see above.
nism

5
Motor Operating range 0.85 ... 1.1 × Us
Extended coil voltage tolerance for battery operation for DC 24 V, DC 48 V 0.7 ... 1.26 × Us
DC 60 V, DC 110 V
DC 220 V
Power input to motor AC/DC VA/W 110/110
Time required to charge the stored-energy mechanism at 1 × Us s ≤ 10
Closing solenoid For data see above.
For motor and Short-circuit protection 2 A TDz (time-lag)/1 A
closing solenoid Motor and closing solenoid for the same rated control supply voltages
Smallest permissible DIAZED fuse (operational class gL)/ at Us = 24–30 V 2A
miniature circuit-breaker with C-characteristic (for different at Us = 48–60 V 2A
rated control supply voltages at Us = 110–127 V 1A
at Us = 220–250 V 1A
Electronic trip unit signals
Measuring accuracy of the electronic trip unit Protection functions to
EN 60947;
current indication ≤ 5 %;
measurement functions
base quantities ≤ 1 %;
measurement functions
derived quantities ≤ 4 %
Auxiliary releases
shunt release (ST) For continuous command Operating value pickup > 0.7 × Us
(F1, F2) (100 % ON-time), (circuit-breaker is tripped)
locks out on momentary- Operating range 0.85 ... 1.1 × Us
contact commands
Extended operating range for DC 24 V, DC 48 V 0.7 ... 1.26 × Us
for battery operation DC 60 V, DC 110 V
DC 220 V
Rated control supply voltage Us AC 50/60 Hz V 110; 230
DC V 24; 30; 48; 60; 110; 220
Power input AC/DC VA/W 15/15
Minimum command duration at Us ms 60
Opening time of circuit-breaker AC/DC ms 80
at Us = 100 %
Short-circuit protection 1 A TDz (time-lag)/1 A
Smallest permissible DIAZED fuse (operational class gL)/
miniature circuit-breaker with C-characteristic
With stored energy feature Rated control supply voltage Us AC 50/60 Hz V 110; 230
consisting of shunt release DC V 110; 220
and capacitor storage Operating range 0.85 ... 1.1 × Us
device
Power input AC/DC VA/W 1/1
Storage time at Us/recharging time at Us max. 5 min/min. 5 s
Opening time of circuit-breaker, short-circuit protection as with "for continuous com-
mand"

Siemens LV 30 · 2004 5/23


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

Size I ... III


Auxiliary releases
Undervoltage release Operating values pickup ≥ 0.85 × Us (circuit-breaker can
UVR (F3) and be closed)
UVR-td (F4) dropout 0.35 ... 0.7× Us
(circuit-breaker is tripped)
Operating range 0.85 ... 1.1
Extended operating range for battery operation for DC 24 V, DC 30 V, 0.85 ... 1.26
DC 48 V, DC 110 V,
DC 220 V
Rated control supply voltage Us AC 50/60 Hz V 110 ... 127/208 ... 240/380 ... 415
DC V 24/30/48/110/220 ... 2501)
Power input (pickup/continuous duty) AC VA 200/5
DC W 200/5
Opening time of circuit-breaker at Us = 0 ms 200
Design UVR (F3)
Instantaneous ms 80
With delay ms 200
Design UVR-td (F8)
With delay, td = 0.2 ... 3.2 s s 0.2 ... 3.2
Reset via additional NC contact – direct switching-off ms ≤ 100
Short-circuit protection 1 A TDz (time-lag) 1 A

5 Smallest permissible DIAZED fuse (operational class gL)/


miniature circuit-breaker with C-characteristic
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage Ui AC/DC V 500
Rated operating voltage Ue AC/DC V 500
Switching capacity AC Rated operating voltage Ue V 24 ... 230 380/400 500
50/60 Hz Rated operating current
Ie/AC-12 A 10 10 10
Ie/AC-15 A 4 3 2
DC Rated operating voltage Ue V 24 48 110 220
Rated operating current
Ie/DC-12 A 10 8 3.5 1
Ie/DC-13 A 8 4 1.2 0.4
Short-circuit protection Largest permissible DIAZED fuse (operational class gL) 10 A TDz, 10 A Dz
Largest permissible miniature circuit-breaker with C-characteristic 10 A
1) 24 V and 30 V only with undervoltage release UVR (F3).

5/24 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

Size I ... III


Ready-to-close signaling switch (S20) (to DIN VDE 0630)
Switching capacity AC Rated operating voltage Ue V 110 220
Rated operating current Ie A 0.14 0.1
DC Rated operating voltage Ue V 24 220
Rated operating current Ie A 0.2 0.1
Short-circuit protection Largest permissible DIAZED fuse (operational class gL) 2A Dz (quick)
"Tripped" switch Signal duration after tripping on req.
Tripped signaling switch (S24) (to DIN VDE 0630)
Switching capacity AC Rated operating voltage Ue V 230
Rated operating current Ie/AC-12 A 6
DC Rated operating voltage Ue V 24 110 220
Rated operating current Ie/DC-12 A 6 0.4 0.2
Short-circuit protection Largest permissible DIAZED fuse (operational class gL) 6A Dz (quick)
"Tripped" switch Signal duration after tripping until manual or electrical
remote-controlled reset (option)
Position indicator switch on guide frame
Type of contact Signal: "Circuit-breaker in connected position" 3W 1W
"Circuit-breaker in test position" 2W or 1W
"Circuit-breaker in disconnected 1W 1W
position"
Rated insulation voltage Ui AC 50/60 Hz
DC
V 440
V 250 5
Rated operating voltage Ue V 250
Switching capacity Rated operating Ie/AC-12 110/127 V 13 A, 220/230 V 13 A,
current Ie 320/400 V 0.6 A
Ie/AC-15 110/127 V 5 A, 220/230 V 4 A,
320/440 V 3 A
Ie/DC-12 24 V 13 A, 30 V 10 A, 48 V 2.5 A,
110 V 0.8 A, 220/250 V 0.6 A
Ie/DC-13 24 V 3.0 A, 220/250 V 0.1 A
Short-circuit protection Largest permissible DIAZED fuse (operational class gL) 8 A TDz (slow)
Largest permissible miniature circuit-breaker with C-characteristic 8 A TDz (slow)

Siemens LV 30 · 2004 5/25


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

Functional overview of the electronic trip unit system


Protection functions ETU15B ETU25B ETU27B
Configuration via D D D&S
Overload protection ✓ ✓ ✓
Function can be switched on/off – – –
Setting range IR = In × ... 0.5-0.6-0.7-0.8- 0.4-0.45-0.5-0.55-0.6- 0.4-0.45-0.5-0.55-0.6-
0.9-1 0.65-0.7-0.8-0.9-1 0.65-0.7-0.8-0.9-1

R
L Switchable
2 4
overload protection
(I t- or I t-dependent function)
– – –

Setting range for time-lag class tR at I2t 10 s fixed 10 s fixed 10 s fixed


Setting range for time-lag class tR at I4t – – –
R Thermal image can be switched on/off – – –
Phase loss sensitivity – at tsd = 20 ms (M) at tsd = 20 ms (M)
Neutral conductor protection – – ✓
N Function can be switched on/off
N conductor setting range IN = In × ...





1
Short-time delayed short-circuit protection – ✓ ✓
Function can be switched on/off – – –
Setting range Isd = In × ... – 1.25-1.5-2-2.5-3-4-6-8-10-12 1.25-1.5-2-2.5-3-4-6-8-10-12
s d
S s d
Setting range for delay time tsd
Switchable short-time delayed short-circuit protection


0-M-100-200-300-400

0-M-100-200-300-400

(I2t-dependent function)
Setting range for delay time tsd at I2t – – –
Zone Selective Interlocking function – – –
i Instantaneous short-circuit protection ✓ ✓ ✓

5 I
N S E 0 _ 0 0 8 8 8 b Function can be switched on/off
Setting range Ii = In × ...

2-3-4-5-6-7-8

fixed for Ii ≥ 20 × In, max. 50 kA

fixed for Ii ≥ 20 × In, max. 50 kA
Ground-fault protection – – ✓ fixed-mounting
Tripping and alarm function – – –
Tripping function can be switched on/off – – ✓
Alarm function can be switched on/off – – –
Detection of the ground-fault current via summation cur- – – ✓
g rent formation with internal or external neutral conductor
transformer
G Detection of ground-fault current via external transformer –
Setting range of the operating current Ig for release –



A-B-C-D-E
g Setting range of the operating current Ig for alarm – – –
N S E 0 _ 0 0 8 8 9 a Setting range of the delay time tg – – 100-200-300-400-500 ms
Switchable ground-fault protection characteristic – – –
(I2t-dependent function)
Setting range for delay time tg at I2t – – –
Zone Selective Interlocking G-function – – –
Parameter sets switchable
Switchable between parameter sets A and B – – –
LCD
Alphanumeric LCD (4-line) – – –
Graphical LCD (24 V, external power supply required) – – –
Communication
CubicleBUS integrated – – –
Communication-capable via PROFIBUS DP – – –
Measurement function
Measurement function-capable with meas. func- – – –
tion/meas. function Plus
LED display
Electronic trip unit active ✓ ✓ ✓
Alarm ✓ ✓ ✓
ETU fault ✓ ✓ ✓
L-release – ✓ ✓
S-release – ✓ ✓
I-release – ✓ ✓
N-release – – ✓
NSE00890
G-release – – ✓
G-alarm – – –
Release via extended protection function – – –
Communication – – –
Signals from signaling switches with external CubicleBUS modules (Opto or relays)
Overload warning – – –
Load shedding, load receiving – – –
Leading signal overload release 200 ms – – –
Temperature alarm – – –
Phase unbalance – – –
Instantaneous short-circuit release – – –
Short-time delayed short-circuit release – – –
Overload release – – –
Neutral conductor release – – –
NSE00891
Ground-fault protection release – – –
Ground-fault alarm – – –
Auxiliary relay – – –
ETU fault – – –

Increment size for adjustment of menu/comm or comm Delay-time figures given in ms. ✓ Available.
From ... to Increment size From ... to Increment size M = motor protection, corresponds to 20 ms. – Not available.
0 ... 1 0.1 1 000 ... 1 600 50 D = rotary coding switch ❑ Optional.
1 ... 100 1 1600 ... 10 000 100 D & S = rotary coding switch and sliding-dolly switch
100 ... 500 5 10 000 ... max. 1 000 K = communication
M/K = menu/communication
500 ... 1 000 10

5/26 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
General data

Protection functions ETU45B: ETU55B ETU76B:


Configuration via D&S K M/K
Overload protection ✓ ✓ ✓
Function can be switched on/off – ✓ ✓
Setting range IR = In × ... 0.4-0.45-0.5-0.55-0.6- 0.4 ... 1 0.4 ... 1
0.65-0.7-0.8-0.9-1
Switchable overload protection ✓ ✓ ✓
(I2t- or I4t-dependent function)
Setting range for time-lag class tR at I2t 2-3-5-5.5-8-10-14-17-21-25-30 s 2 ... 30 s 2 ... 30 s
Setting range for time-lag class tR at I4t 1-2-3-4-5 s 1 ... 5 s 1 ... 5 s
Thermal image can be switched on/off ✓ ✓ ✓
Phase loss sensitivity at tsd = 20 ms (M) ✓ (on/off) ✓ (on/off)
Neutral conductor protection ✓ ✓ ✓
Function can be switched on/off ✓ ✓ ✓
N conductor setting range IN = In × ... 0.5 ... 1 0.2 ... 2 0.2 ... 2
Short-time delayed short-circuit protection ✓ ✓ ✓
Function can be switched on/off ✓ ✓ ✓
Setting range Isd = In × ... 1.25-1.5-2-2.5-3-4-6-8-10-12 1.25 In ... 0.8 × Icw 1.25 In ... 0.8 × Icw
Setting range for delay time tsd M-100-200-300-400 ms M-80 ... 4000 ms M-80 ... 4000 ms
Switchable short-time delayed short-circuit protection ✓ ✓ ✓
(I2t-dependent function)
Setting range for delay time tsd at I2t 100-200-300-400 ms 100 ... 400 ms 100 ... 400 ms
Zone Selective Interlocking function by CubicleBUS module by CubicleBUS module by CubicleBUS module
Instantaneous short-circuit protection ✓ ✓ ✓
Function can be switched on/off
Setting range Ii = In × ...
Ground-fault protection

1.5-2.2-3-4-6-8-10-12-0.8 x Ics
❑ Module can be retrofitted

1.5 × In ... 0.8 × Ics
❑ Module can be retrofitted

1.5 × In ... 0.8 × Ics
❑ Module can be retrofitted
5
Tripping and alarm function ✓ ✓ ✓
Tripping function can be switched on/off ✓ ✓ ✓
Alarm function can be switched on/off – ✓ ✓
Detection of the ground-fault current via summation cur- ✓ ✓ ✓
rent formation with internal or external neutral conductor
transformer
Detection of ground-fault current via external transformer ✓ ✓ ✓
Setting range of the operating current Ig for release A-B-C-D-E A ... E A ... E
Setting range of the operating current Ig for alarm A-B-C-D-E A ... E A ... E
Setting range of the delay time tg 100-200-300-400-500 ms 100 ... 500 ms 100 ... 500 ms
Switchable ground-fault protection characteristic ✓ ✓ ✓
(I2t-dependent function)
Setting range for delay time tg at I2t 100-200-300-400-500 ms 100 ... 500 ms 100 ... 500 ms
Zone Selective Interlocking G-function by CubicleBUS module by CubicleBUS module by CubicleBUS module
Parameter set switchover
Switchable between parameter set A and B – ✓ ✓
LCD
Alphanumeric LCD (4-line) ❑ – –
Graphical LCD (24 V, external power supply required) – – ✓
Communication
CubicleBUS integrated ✓ ✓ ✓
Communication-capable via PROFIBUS DP ✓ ✓ ✓
Measurement function
Measurement function-capable with meas. func- ✓ ✓ ✓
tion/meas. function Plus
LED display
Electronic trip unit active ✓ ✓ ✓
Alarm ✓ ✓ ✓
ETU fault ✓ ✓ ✓
L-release ✓ ✓ ✓
S-release ✓ ✓ ✓
I-release ✓ ✓ ✓
N-release ✓ ✓ ✓
G-release ✓ (only with ground-fault prot. mod.) ✓ (only with ground-fault prot. mod.) ✓ (only with ground-fault prot. mod.)
G-alarm ✓ (only with ground-fault prot. mod.) ✓ (only with ground-fault prot. mod.) ✓ (only with ground-fault prot. mod.)
Release via extended protection functions ✓ ✓ ✓
Communication ✓ ✓ ✓
Signals from signaling switches with external CubicleBUS modules (optical or relays)
Overload warning ✓ ✓ ✓
Load shedding, load receiving ✓ ✓ ✓
Leading signal overload release 200 ms ✓ ✓ ✓
Temperature alarm ✓ ✓ ✓
Phase unbalance ✓ ✓ ✓
Instantaneous short-circuit release ✓ ✓ ✓
Short-time delayed short-circuit release ✓ ✓ ✓
Overload release ✓ ✓ ✓
Neutral conductor release ✓ ✓ ✓
Ground-fault protection release ✓ (only with ground-fault prot. mod.) ✓ (only with ground-fault prot. mod.) ✓ (only with ground-fault prot. mod.)
Ground-fault alarm ✓ (only with ground-fault prot. mod.) ✓ (only with ground-fault prot. mod.) ✓ (only with ground-fault prot. mod.)
Auxiliary relay ✓ ✓ ✓
ETU fault ✓ ✓ ✓

Setting range of the operating current Ig


Size I and Size II Size III
A 100 A 400 A
B 300 A 600 A
C 600 A 800 A
D 900 A 1000 A
E 1200 A 1200 A
Siemens LV 30 · 2004 5/27
Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
3-pole, fixed-mounted design

■ Selection and ordering data


Size Max. rated circuit- Rated current1) ECO switching capacity N, PS* Weight Standard switching capacity S, PS* Weight
breaker current In Icu/440 V per PU Icu/440 V per PU
In max. Order No. approx. Order No. approx.
Order No. supplement Order No. supplement
see Page 5/36 see Page 5/36
A A kA DT kg kA DT kg
Horizontal main circuit connection
I 630 630 50 B 3WL11 06-2@@32-.... 1 unit 43.000 65 B 3WL11 06-3@@32-.... 1 unit 43.000
I 800 800 50 B 3WL11 08-2@@32-.... 1 unit 43.000 65 B 3WL11 08-3@@32-.... 1 unit 43.000
I 1000 1000 50 B 3WL11 10-2@@32-.... 1 unit 43.000 65 B 3WL11 10-3@@32-.... 1 unit 43.000
I 1250 1250 50 B 3WL11 12-2@@32-.... 1 unit 43.000 65 B 3WL11 12-3@@32-.... 1 unit 43.000
I 1600 1600 50 B 3WL11 16-2@@32-.... 1 unit 43.000 65 B 3WL11 16-3@@32-.... 1 unit 43.000
II 800 800 – – 80 B 3WL12 08-3@@32-.... 1 unit 56.000
II 1000 1000 – – 80 B 3WL12 10-3@@32-.... 1 unit 56.000
II 1250 1250 – – 80 B 3WL12 12-3@@32-.... 1 unit 56.000
II 1600 1600 – – 80 B 3WL12 16-3@@32-.... 1 unit 56.000
II 2000 2000 55 B 3WL12 20-2@@32-.... 1 unit 56.000 80 B 3WL12 20-3@@32-.... 1 unit 56.000
II 2500 2500 55 B 3WL12 25-2@@32-.... 1 unit 59.000 80 B 3WL12 25-3@@32-.... 1 unit 59.000
II 3200 3200 – – 80 B 3WL12 32-3@@32-.... 1 unit 64.000
Vertical main circuit connection
I 630 630 50 B 3WL11 06-2@@31-.... 1 unit 43.000 65 B 3WL11 06-3@@31-.... 1 unit 43.000

5
I 800 800 50 B 3WL11 08-2@@31-.... 1 unit 43.000 65 B 3WL11 08-3@@31-.... 1 unit 43.000
I 1000 1000 50 B 3WL11 10-2@@31-.... 1 unit 43.000 65 B 3WL11 10-3@@31-.... 1 unit 43.000
I 1250 1250 50 B 3WL11 12-2@@31-.... 1 unit 43.000 65 B 3WL11 12-3@@31-.... 1 unit 43.000
I 1600 1600 50 B 3WL11 16-2@@31-.... 1 unit 43.000 65 B 3WL11 16-3@@31-.... 1 unit 43.000
II 800 800 – – 80 B 3WL12 08-3@@31-.... 1 unit 56.000
II 1000 1000 – – 80 B 3WL12 10-3@@31-.... 1 unit 56.000
II 1250 1250 – – 80 B 3WL12 12-3@@31-.... 1 unit 56.000
II 1600 1600 – – 80 B 3WL12 16-3@@31-.... 1 unit 56.000
II 2000 2000 55 B 3WL12 20-2@@31-.... 1 unit 56.000 80 B 3WL12 20-3@@31-.... 1 unit 56.000
II 2500 2500 55 B 3WL12 25-2@@31-.... 1 unit 59.000 80 B 3WL12 25-3@@31-.... 1 unit 59.000
II 3200 3200 – – 80 B 3WL12 32-3@@31-.... 1 unit 64.000
Front main circuit connection, single hole
I 630 630 50 B 3WL11 06-2@@33-.... 1 unit 43.000 65 B 3WL11 06-3@@33-.... 1 unit 43.000
I 800 800 50 B 3WL11 08-2@@33-.... 1 unit 43.000 65 B 3WL11 08-3@@33-.... 1 unit 43.000
I 1000 1000 50 B 3WL11 10-2@@33-.... 1 unit 43.000 65 B 3WL11 10-3@@33-.... 1 unit 43.000
I 1250 1250 50 B 3WL11 12-2@@33-.... 1 unit 43.000 65 B 3WL11 12-3@@33-.... 1 unit 43.000
I 1600 1600 50 B 3WL11 16-2@@33-.... 1 unit 43.000 65 B 3WL11 16-3@@33-.... 1 unit 43.000
II 800 800 – – 80 B 3WL12 08-3@@33-.... 1 unit 56.000
II 1000 1000 – – 80 B 3WL12 10-3@@33-.... 1 unit 56.000
II 1250 1250 – – 80 B 3WL12 12-3@@33-.... 1 unit 56.000
II 1600 1600 – – 80 B 3WL12 16-3@@33-.... 1 unit 56.000
II 2000 2000 55 B 3WL12 20-2@@33-.... 1 unit 56.000 80 B 3WL12 20-3@@33-.... 1 unit 56.000
II 2500 2500 55 B 3WL12 25-2@@33-.... 1 unit 59.000 80 B 3WL12 25-3@@33-.... 1 unit 59.000
II 3200 3200 – – 80 B 3WL12 32-3@@33-.... 1 unit 64.000
Front main circuit connection, double hole
I 630 630 50 B 3WL11 06-2@@34-.... 1 unit 43.000 65 B 3WL11 06-3@@34-.... 1 unit 43.000
I 800 800 50 B 3WL11 08-2@@34-.... 1 unit 43.000 65 B 3WL11 08-3@@34-.... 1 unit 43.000
I 1000 1000 50 B 3WL11 10-2@@34-.... 1 unit 43.000 65 B 3WL11 10-3@@34-.... 1 unit 43.000
I 1250 1250 50 B 3WL11 12-2@@34-.... 1 unit 43.000 65 B 3WL11 12-3@@34-.... 1 unit 43.000
I 1600 1600 50 B 3WL11 16-2@@34-.... 1 unit 43.000 65 B 3WL11 16-3@@34-.... 1 unit 43.000
II 800 800 – – 80 B 3WL12 08-3@@34-.... 1 unit 56.000
II 1000 1000 – – 80 B 3WL12 10-3@@34-.... 1 unit 56.000
II 1250 1250 – – 80 B 3WL12 12-3@@34-.... 1 unit 56.000
II 1600 1600 – – 80 B 3WL12 16-3@@34-.... 1 unit 56.000
II 2000 2000 55 B 3WL12 20-2@@34-.... 1 unit 56.000 80 B 3WL12 20-3@@34-.... 1 unit 56.000
II 2500 2500 55 B 3WL12 25-2@@34-.... 1 unit 59.000 80 B 3WL12 25-3@@34-.... 1 unit 59.000
II 3200 3200 – – 80 B 3WL12 32-3@@34-.... 1 unit 64.000
Non-automatic circuit-breakers2) Order No. supplements Order No. supplements
without electronic trip unit AA AA
without electronic trip unit, communication/ AB AB
measurement function optional3) ■
Electronic trip units
Design without ground-fault protection
ETU15B: protection functions LI BB BB
ETU25B: protection functions LSI CB CB
ETU45B: protection functions LSIN4) EB EB
ETU45B: protection functions LSIN4) with 4-line display FB FB
ETU55B: protection functions LSIN4) JB JB
ETU76B: prot. functions LSIN4) with pixel graphics display NB NB
Design with ground-fault protection
ETU27B: protection functions LSING4) DG DG
ETU45B: protection functions LSING4)6) EG EG
ETU45B: protection functions LSING4) with 4-line display6) FG FG
ETU55B: protection functions LSING4)6) JG JG
ETU76B: prot. functions LSING4) w. pixel graphic display6) NG NG
Standard Order No. supplements (for further Order No. supplements see Page 5/36)
Manual operating mechanism with mechanical closing
Without 1st and 2nd aux. releases; aux. sw. 2 NC + 2 NO 1AA2 1AA2
For footnotes see Page 5/29.

5/28 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
3-pole, fixed-mounted design

Size Max. rated circuit-breaker Rated current1) High switching capacity H, Icu/440 V PS* Weight
current In Order No. per PU
In max. Order No. supplements approx.
see Page 5/36
A A kA DT kg
Horizontal main circuit connection
II 800 800 100 B 3WL12 08-4@@32-.... 1 unit 56.000
II 1000 1000 100 B 3WL12 10-4@@32-.... 1 unit 56.000
II 1250 1250 100 B 3WL12 12-4@@32-.... 1 unit 56.000
II 1600 1600 100 B 3WL12 16-4@@32-.... 1 unit 56.000
II 2000 2000 100 B 3WL12 20-4@@32-.... 1 unit 56.000
II 2500 2500 100 B 3WL12 25-4@@32-.... 1 unit 59.000
II 3200 3200 100 B 3WL12 32-4@@32-.... 1 unit 64.000
III 5) 4000 4000 100 C 3WL13 40-4@@32-.... 1 unit 82.000
III5) 5000 5000 100 C 3WL13 50-4@@32-.... 1 unit 82.000
Vertical main circuit connection
II 800 800 100 B 3WL12 08-4@@31-.... 1 unit 56.000
II 1000 1000 100 B 3WL12 10-4@@31-.... 1 unit 56.000
II 1250 1250 100 B 3WL12 12-4@@31-.... 1 unit 56.000
II 1600 1600 100 B 3WL12 16-4@@31-.... 1 unit 56.000
II 2000 2000 100 B 3WL12 20-4@@31-.... 1 unit 56.000
II 2500 2500 100 B 3WL12 25-4@@31-.... 1 unit 59.000
II 3200 3200 100 B 3WL12 32-4@@31-.... 1 unit 64.000
III 5)
III 5)
III 5)
4000
5000
6300
4000
5000
6300
100
100
100
C
C
C
3WL13 40-4@@31-....
3WL13 50-4@@31-....
3WL13 63-4@@31-....
1 unit
1 unit
1 unit
82.000
82.000
82.000
5
Front main circuit connection, single hole
II 800 800 100 B 3WL12 08-4@@33-.... 1 unit 56.000
II 1000 1000 100 B 3WL12 10-4@@33-.... 1 unit 56.000
II 1250 1250 100 B 3WL12 12-4@@33-.... 1 unit 56.000
II 1600 1600 100 B 3WL12 16-4@@33-.... 1 unit 56.000
II 2000 2000 100 B 3WL12 20-4@@33-.... 1 unit 56.000
II 2500 2500 100 B 3WL12 25-4@@33-.... 1 unit 59.000
II 3200 3200 100 B 3WL12 32-4@@33-.... 1 unit 64.000
III 5) 4000 4000 100 C 3WL13 40-4@@33-.... 1 unit 82.000
Front main circuit connection, double hole
II 800 800 100 B 3WL12 08-4@@34-.... 1 unit 56.000
II 1000 1000 100 B 3WL12 10-4@@34-.... 1 unit 56.000
II 1250 1250 100 B 3WL12 12-4@@34-.... 1 unit 56.000
II 1600 1600 100 B 3WL12 16-4@@34-.... 1 unit 56.000
II 2000 2000 100 B 3WL12 20-4@@34-.... 1 unit 56.000
II 2500 2500 100 B 3WL12 25-4@@34-.... 1 unit 59.000
II 3200 3200 100 B 3WL12 32-4@@34-.... 1 unit 64.000
III 5) 4000 4000 100 C 3WL13 40-4@@34-.... 1 unit 82.000
Order No. supplements
Non-automatic circuit-breakers2)
without electronic trip unit AA
without electronic trip unit, communication/measurement function optional3) ■ AB
Electronic trip units
Design without ground-fault protection
ETU15B: protection functions LI5) BB
ETU25B: protection functions LSI CB
ETU45B: protection functions LSIN4) EB
ETU45B: protection functions LSIN4) with 4-line display FB
ETU55B: protection functions LSIN4) JB
ETU76B: protection functions LSIN4) with pixel graphics display NB
Design with ground-fault protection
ETU27B: protection functions LSING4) DG
ETU45B: protection functions LSING4) 6) EG
ETU45B: protection functions LSING4) with 4-line display 6) FG
ETU55B: protection functions LSING4) 6) JG
ETU76B: protection functions LSING4) with pixel graphics display 6) NG
Standard Order No. supplements (for further Order No. supplements see Page 5/36)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2
Footnotes for pages 5/28 and 5/29: 4) Current transformers for vectorial summation current formation or for pro-
1) Rated current determined by rated current module. tection of the neutral conductor and current transformers for detection of
On the standard design the supplied module is equal to the max. circuit- the ground-fault current in the grounded star point of the transformer must
breaker rated current. be ordered separately, see Page 5/46.
If a lower rated current is required, adaptation by order code on page 5/37. 5) Size III circuit-breakers are not available with electronic trip unit design
2) Permissible short-time current rating Icc and rated short-circuit making ETU15B.
capacity Icm for non-automatic circuit-breakers - see Page 5/20. 6) ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
3) Required accessories "PROFIBUS communication setup" or "Measurement and tripping), see Page 5/46.
function Plus": Order No. with "–Z" and order code "F02" or "F05" respec- ■ Start of delivery on request
tively, see Page 5/38.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/29


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
3-pole, withdrawable design

Size Max. rated Rated current1) ECO switching capacity N, PS* Weight Standard switching capacity S, PS* Weight
circuit-breaker In Icu/440 V per PU Icu/440 V per PU
current In max. Order No. approx. Order No. approx.
Order No. supplement Order No. supplement
see Page 5/36 see Page 5/36
A A kA DT kg kA DT kg
Without guide frame (for guide frames see Page 5/45)
I 630 630 50 B 3WL11 06-2@@35-.... 1 unit 45.000 65 B 3WL11 06-3@@35-.... 1 unit 45.000
I 800 800 50 B 3WL11 08-2@@35-.... 1 unit 45.000 65 B 3WL11 08-3@@35-.... 1 unit 45.000
I 1000 1000 50 B 3WL11 10-2@@35-.... 1 unit 45.000 65 B 3WL11 10-3@@35-.... 1 unit 45.000
I 1250 1250 50 B 3WL11 12-2@@35-.... 1 unit 45.000 65 B 3WL11 12-3@@35-.... 1 unit 45.000
I 1600 1600 50 B 3WL11 16-2@@35-.... 1 unit 45.000 65 B 3WL11 16-3@@35-.... 1 unit 45.000
II 800 800 – – 80 B 3WL12 08-3@@35-.... 1 unit 60.000
II 1000 1000 – – 80 B 3WL12 10-3@@35-.... 1 unit 60.000
II 1250 1250 – – 80 B 3WL12 12-3@@35-.... 1 unit 60.000
II 1600 1600 – – 80 B 3WL12 16-3@@35-.... 1 unit 60.000
II 2000 2000 55 B 3WL12 20-2@@35-.... 1 unit 60.000 80 B 3WL12 20-3@@35-.... 1 unit 60.000
II 2500 2500 55 B 3WL12 25-2@@35-.... 1 unit 63.000 80 B 3WL12 25-3@@35-.... 1 unit 63.000
II 3200 3200 – – 80 B 3WL12 32-3@@35-.... 1 unit 68.000
With guide frame, horizontal main circuit connection
I 630 630 50 B 3WL11 06-2@@36-.... 1 unit 70.000 65 B 3WL11 06-3@@36-.... 1 unit 70.000
I 800 800 50 B 3WL11 08-2@@36-.... 1 unit 70.000 65 B 3WL11 08-3@@36-.... 1 unit 70.000
I 1000 1000 50 B 3WL11 10-2@@36-.... 1 unit 70.000 65 B 3WL11 10-3@@36-.... 1 unit 70.000

5 I
I
II
1250
1600
800
1250
1600
800
50
50

B
B
3WL11 12-2@@36-....
3WL11 16-2@@36-....

1 unit
1 unit
70.000
70.000
80
65
65
B
B
B
3WL11 12-3@@36-....
3WL11 16-3@@36-....
3WL12 08-3@@36-....
1 unit
1 unit
70.000
70.000
1 unit 91.000
II 1000 1000 – – 80 B 3WL12 10-3@@36-.... 1 unit 91.000
II 1250 1250 – – 80 B 3WL12 12-3@@36-.... 1 unit 91.000
II 1600 1600 – – 80 B 3WL12 16-3@@36-.... 1 unit 91.000
II 2000 2000 55 B 3WL12 20-2@@36-.... 1 unit 91.000 80 B 3WL12 20-3@@36-.... 1 unit 91.000
II 2500 2500 55 B 3WL12 25-2@@36-.... 1 unit 102.000 80 B 3WL12 25-3@@36-.... 1 unit 102.000
II 3200 3200 – – 80 B 3WL12 32-3@@36-.... 1 unit 113.000
With guide frame, vertical main circuit connection
I 630 630 50 B 3WL11 06-2@@37-.... 1 unit 70.000 65 B 3WL11 06-3@@37-.... 1 unit 70.000
I 800 800 50 B 3WL11 08-2@@37-.... 1 unit 70.000 65 B 3WL11 08-3@@37-.... 1 unit 70.000
I 1000 1000 50 B 3WL11 10-2@@37-.... 1 unit 70.000 65 B 3WL11 10-3@@37-.... 1 unit 70.000
I 1250 1250 50 B 3WL11 12-2@@37-.... 1 unit 70.000 65 B 3WL11 12-3@@37-.... 1 unit 70.000
I 1600 1600 50 B 3WL11 16-2@@37-.... 1 unit 70.000 65 B 3WL11 16-3@@37-.... 1 unit 70.000
II 800 800 – – 80 B 3WL12 08-3@@37-.... 1 unit 91.000
II 1000 1000 – – 80 B 3WL12 10-3@@37-.... 1 unit 91.000
II 1250 1250 – – 80 B 3WL12 12-3@@37-.... 1 unit 91.000
II 1600 1600 – – 80 B 3WL12 16-3@@37-.... 1 unit 91.000
II 2000 2000 55 B 3WL12 20-2@@37-.... 1 unit 91.000 80 B 3WL12 20-3@@37-.... 1 unit 91.000
II 2500 2500 55 B 3WL12 25-2@@37-.... 1 unit 102.000 80 B 3WL12 25-3@@37-.... 1 unit 102.000
II 3200 3200 – – 80 B 3WL12 32-3@@37-.... 1 unit 113.000
With guide frame, connecting flange
I 630 630 50 B 3WL11 06-2@@38-.... 1 unit 70.000 65 B 3WL11 06-3@@38-.... 1 unit 70.000
I 800 800 50 B 3WL11 08-2@@38-.... 1 unit 70.000 65 B 3WL11 08-3@@38-.... 1 unit 70.000
I 1000 1000 50 B 3WL11 10-2@@38-.... 1 unit 70.000 65 B 3WL11 10-3@@38-.... 1 unit 70.000
I 1250 1250 50 B 3WL11 12-2@@38-.... 1 unit 70.000 65 B 3WL11 12-3@@38-.... 1 unit 70.000
I 1600 1600 50 B 3WL11 16-2@@38-.... 1 unit 70.000 65 B 3WL11 16-3@@38-.... 1 unit 70.000
II 800 800 – – 80 B 3WL12 08-3@@38-.... 1 unit 91.000
II 1000 1000 – – 80 B 3WL12 10-3@@38-.... 1 unit 91.000
II 1250 1250 – – 80 B 3WL12 12-3@@38-.... 1 unit 91.000
II 1600 1600 – – 80 B 3WL12 16-3@@38-.... 1 unit 91.000
II 2000 2000 55 B 3WL12 20-2@@38-.... 1 unit 91.000 80 B 3WL12 20-3@@38-.... 1 unit 91.000
II 2500 2500 55 B 3WL12 25-2@@38-.... 1 unit 102.000 80 B 3WL12 25-3@@38-.... 1 unit 102.000
II 3200 3200 – – 80 B 3WL12 32-3@@38-.... 1 unit 113.000
Non-automatic circuit-breakers2) Order No. supplements Order No. supplements
without electronic trip unit AA AA
without electronic trip unit, communication/ AB AB
measurement function optional3) ■
Electronic trip units
Design without ground-fault protection
ETU15B: protection functions LI BB BB
ETU25B: protection functions LSI CB CB
ETU45B: protection functions LSIN4) EB EB
ETU45B: protection functions LSIN4) with 4-line display FB FB
ETU55B: protection functions LSIN4) JB JB
ETU76B: prot. func.LSIN4) with pixel graphics display NB NB
Design with ground-fault protection
ETU27B: protection functions LSING4) DG DG
ETU45B: protection functions LSING4)6) EG EG
ETU45B: prot. functions LSING4) with 4-line display6) FG FG
ETU55B: protection functions LSING4)6) JG JG
ETU76B: prot. func. LSING4) w. pixel graphics display6) NG NG
Standard Order No. supplements (for further Order No. supplements for circuit-breakers and guide frames, see Page 5/36)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch
2 NC + 2 NO 1AA2 1AA2
For footnotes see Page 5/31.

5/30 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
3-pole, withdrawable design

Size Max. rated circuit-breaker Rated current1) High switching capacity H, Icu/440 V PS* Weight
current In Order No. per PU
In max. Order No. supplements approx.
A A kA DT see Page 5/36 kg
Without guide frame (for guide frames see Page 5/45)
II 800 800 100 B 3WL12 08-4@@35-.... 1 unit 60.000
II 1000 1000 100 B 3WL12 10-4@@35-.... 1 unit 60.000
II 1250 1250 100 B 3WL12 12-4@@35-.... 1 unit 60.000
II 1600 1600 100 B 3WL12 16-4@@35-.... 1 unit 60.000
II 2000 2000 100 B 3WL12 20-4@@35-.... 1 unit 60.000
II 2500 2500 100 B 3WL12 25-4@@35-.... 1 unit 63.000
II 3200 3200 100 B 3WL12 32-4@@35-.... 1 unit 68.000
III 5) 4000 4000 100 C 3WL13 40-4@@35-.... 1 unit 88.000
III 5) 5000 5000 100 C 3WL13 50-4@@35-.... 1 unit 88.000
III 5) 6300 6300 100 C 3WL13 63-4@@35-.... 1 unit 96.000
With guide frame, horizontal main circuit connection
II 800 800 100 B 3WL12 08-4@@36-.... 1 unit 91.000
II 1000 1000 100 B 3WL12 10-4@@36-.... 1 unit 91.000
II 1250 1250 100 B 3WL12 12-4@@36-.... 1 unit 91.000
II 1600 1600 100 B 3WL12 16-4@@36-.... 1 unit 91.000
II 2000 2000 100 B 3WL12 20-4@@36-.... 1 unit 91.000
II 2500 2500 100 B 3WL12 25-4@@36-.... 1 unit 102.000
II 3200 3200 100 B 3WL12 32-4@@36-.... 1 unit 113.000
III 5)
III5)
4000
5000
4000
5000
With guide frame, vertical main circuit connection
100
100
C
C
3WL13 40-4@@36-....
3WL13 50-4@@36-....
1 unit 148.000
1 unit 148.000 5
II 800 800 100 B 3WL12 08-4@@37-.... 1 unit 91.000
II 1000 1000 100 B 3WL12 10-4@@37-.... 1 unit 91.000
II 1250 1250 100 B 3WL12 12-4@@37-.... 1 unit 91.000
II 1600 1600 100 B 3WL12 16-4@@37-.... 1 unit 91.000
II 2000 2000 100 B 3WL12 20-4@@37-.... 1 unit 91.000
II 2500 2500 100 B 3WL12 25-4@@37-.... 1 unit 102.000
II 3200 3200 100 B 3WL12 32-4@@37-.... 1 unit 113.000
III 5) 4000 4000 100 C 3WL13 40-4@@37-.... 1 unit 148.000
III 5) 5000 5000 100 C 3WL13 50-4@@37-.... 1 unit 148.000
III 5) 6300 6300 100 C 3WL13 63-4@@37-.... 1 unit 166.000
With guide frame, connecting flange
II 800 800 100 B 3WL12 08-4@@38-.... 1 unit 91.000
II 1000 1000 100 B 3WL12 10-4@@38-.... 1 unit 91.000
II 1250 1250 100 B 3WL12 12-4@@38-.... 1 unit 91.000
II 1600 1600 100 B 3WL12 16-4@@38-.... 1 unit 91.000
II 2000 2000 100 B 3WL12 20-4@@38-.... 1 unit 91.000
II 2500 2500 100 B 3WL12 25-4@@38-.... 1 unit 102.000
II 3200 3200 100 B 3WL12 32-4@@38-.... 1 unit 113.000
III 5) 4000 4000 100 C 3WL13 40-4@@38-.... 1 unit 148.000
Order No. supplements
Non-automatic circuit-breakers 2)
without electronic trip unit AA
without electronic trip unit, communication/measurement function optional3) ■ AB
Electronic trip units
Design without ground-fault protection
ETU15B: protection functions LI5) BB
ETU25B: protection functions LSI CB
ETU45B: protection functions LSIN4) EB
ETU45B: protection functions LSIN4) with 4-line display FB
ETU55B: protection functions LSIN4) JB
ETU76B: protection functions LSIN4) with pixel graphics display NB
Design with ground-fault protection
ETU27B: protection functions LSING4) DG
ETU45B: protection functions LSING4)6) EG
ETU45B: protection functions LSING4) with 4-line display6) FG
ETU55B: protection functions LSING4)6) JG
ETU76B: protection functions LSING4) with pixel graphics display6) NG
Standard Order No. supplements (for further Order No. supplements for circuit-breakers and guide frames, see Page 5/36)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2
Footnotes for pages 5/30 and 5/31: 4) Current transformers for vectorial summation current formation or for pro-
1) Rated current determined by rated current module. tection of the neutral conductor and current transformers for detection of
On the standard design the supplied module is equal to the max. rated the ground-fault current in the grounded star point of the transformer must
type current. be ordered separately, see Page 5/46.
If a lower rated current is required, adaptation by order code on page 5/37. 5) Size III circuit-breakers are not available with electronic trip unit design
2) Permissible short-time current rating Icc and rated short-circuit making ETU15B.
capacity Icm for non-automatic circuit-breakers - see Page 5/20. 6) ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
3) Required accessories "PROFIBUS communication setup" and "Measure- and tripping), see Page 5/46.
ment function Plus": Order No. with "–Z" and order code "F02" and"F05" ■ Start of delivery on request
respectively, see Page 5/38.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/31


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
4-pole, fixed-mounted design

Size Max. rated circuit- Rated current1) ECO switching capacity N, PS* Weight Standard switching capacity S, PS* Weight
breaker current In Icu/440 V per PU Icu/440 V per PU
In max. Order No. approx. Order No. approx.
Order No. supplements Order No. supplements
see Page 5/36 see Page 5/36
A A kA DT kg kA DT kg
Horizontal main circuit connection
I 630 630 50 B 3WL11 06-2@@42-.... 1 unit 50.000 65 B 3WL11 06-3@@42-.... 1 unit 50.000
I 800 800 50 B 3WL11 08-2@@42-.... 1 unit 50.000 65 B 3WL11 08-3@@42-.... 1 unit 50.000
I 1000 1000 50 B 3WL11 10-2@@42-.... 1 unit 50.000 65 B 3WL11 10-3@@42-.... 1 unit 50.000
I 1250 1250 50 B 3WL11 12-2@@42-.... 1 unit 50.000 65 B 3WL11 12-3@@42-.... 1 unit 50.000
I 1600 1600 50 B 3WL11 16-2@@42-.... 1 unit 50.000 65 B 3WL11 16-3@@42-.... 1 unit 50.000
II 800 800 – – 80 B 3WL12 08-3@@42-.... 1 unit 67.000
II 1000 1000 – – 80 B 3WL12 10-3@@42-.... 1 unit 67.000
II 1250 1250 – – 80 B 3WL12 12-3@@42-.... 1 unit 67.000
II 1600 1600 – – 80 B 3WL12 16-3@@42-.... 1 unit 67.000
II 2000 2000 55 B 3WL12 20-2@@42-.... 1 unit 67.000 80 B 3WL12 20-3@@42-.... 1 unit 67.000
II 2500 2500 55 B 3WL12 25-2@@42-.... 1 unit 71.000 80 B 3WL12 25-3@@42-.... 1 unit 71.000
II 3200 3200 – – 80 B 3WL12 32-3@@42-.... 1 unit 77.000
Vertical main circuit connection
I 630 630 50 B 3WL11 06-2@@41-.... 1 unit 50.000 65 B 3WL11 06-3@@41-.... 1 unit 50.000
I 800 800 50 B 3WL11 08-2@@41-.... 1 unit 50.000 65 B 3WL11 08-3@@41-.... 1 unit 50.000
I 1000 1000 50 B 3WL11 10-2@@41-.... 1 unit 50.000 65 B 3WL11 10-3@@41-.... 1 unit 50.000

5 I
I
II
1250
1600
800
1250
1600
800
50
50

B
B
3WL11 12-2@@41-....
3WL11 16-2@@41-....

1 unit
1 unit
50.000
50.000
80
65
65
B
B
B
3WL11 12-3@@41-....
3WL11 16-3@@41-....
3WL12 08-3@@41-....
1 unit
1 unit
1 unit
50.000
50.000
75.000
II 1000 1000 – – 80 B 3WL12 10-3@@41-.... 1 unit 75.000
II 1250 1250 – – 80 B 3WL12 12-3@@41-.... 1 unit 75.000
II 1600 1600 – – 80 B 3WL12 16-3@@41-.... 1 unit 75.000
II 2000 2000 55 B 3WL12 20-2@@41-.... 1 unit 75.000 80 B 3WL12 20-3@@41-.... 1 unit 75.000
II 2500 2500 55 B 3WL12 25-2@@41-.... 1 unit 71.000 80 B 3WL12 25-3@@41-.... 1 unit 71.000
II 3200 3200 – – 80 B 3WL12 32-3@@41-.... 1 unit 77.000
Front main circuit connection, single hole
I 630 630 50 B 3WL11 06-2@@43-.... 1 unit 50.000 65 B 3WL11 06-3@@43-.... 1 unit 50.000
I 800 800 50 B 3WL11 08-2@@43-.... 1 unit 50.000 65 B 3WL11 08-3@@43-.... 1 unit 50.000
I 1000 1000 50 B 3WL11 10-2@@43-.... 1 unit 50.000 65 B 3WL11 10-3@@43-.... 1 unit 50.000
I 1250 1250 50 B 3WL11 12-2@@43-.... 1 unit 50.000 65 B 3WL11 12-3@@43-.... 1 unit 50.000
I 1600 1600 50 B 3WL11 16-2@@43-.... 1 unit 50.000 65 B 3WL11 16-3@@43-.... 1 unit 50.000
II 800 800 – – 80 B 3WL12 08-3@@43-.... 1 unit 67.000
II 1000 1000 – – 80 B 3WL12 10-3@@43-.... 1 unit 67.000
II 1250 1250 – – 80 B 3WL12 12-3@@43-.... 1 unit 67.000
II 1600 1600 – – 80 B 3WL12 16-3@@43-.... 1 unit 67.000
II 2000 2000 55 B 3WL12 20-2@@43-.... 1 unit 67.000 80 B 3WL12 20-3@@43-.... 1 unit 67.000
II 2500 2500 55 B 3WL12 25-2@@43-.... 1 unit 71.000 80 B 3WL12 25-3@@43-.... 1 unit 71.000
II 3200 3200 – – 80 B 3WL12 32-3@@43-.... 1 unit 77.000
Front main circuit connection, double hole
I 630 630 50 B 3WL11 06-2@@44-.... 1 unit 50.000 65 B 3WL11 06-3@@44-.... 1 unit 50.000
I 800 800 50 B 3WL11 08-2@@44-.... 1 unit 50.000 65 B 3WL11 08-3@@44-.... 1 unit 50.000
I 1000 1000 50 B 3WL11 10-2@@44-.... 1 unit 50.000 65 B 3WL11 10-3@@44-.... 1 unit 50.000
I 1250 1250 50 B 3WL11 12-2@@44-.... 1 unit 50.000 65 B 3WL11 12-3@@44-.... 1 unit 50.000
I 1600 1600 50 B 3WL11 16-2@@44-.... 1 unit 50.000 65 B 3WL11 16-3@@44-.... 1 unit 50.000
II 800 800 – – 80 B 3WL12 08-3@@44-.... 1 unit 67.000
II 1000 1000 – – 80 B 3WL12 10-3@@44-.... 1 unit 67.000
II 1250 1250 – – 80 B 3WL12 12-3@@44-.... 1 unit 67.000
II 1600 1600 – – 80 B 3WL12 16-3@@44-.... 1 unit 67.000
II 2000 2000 55 B 3WL12 20-2@@44-.... 1 unit 67.000 80 B 3WL12 20-3@@44-.... 1 unit 67.000
II 2500 2500 55 B 3WL12 25-2@@44-.... 1 unit 71.000 80 B 3WL12 25-3@@44-.... 1 unit 71.000
II 3200 3200 – – 80 B 3WL12 32-3@@44-.... 1 unit 77.000
Non-automatic circuit-breakers2) Order No. supplements Order No. supplements
without electronic trip unit AA AA
without electronic trip unit, communication/ AB AB
measurement function optional3) ■
Electronic trip units
Design without ground-fault protection
ETU15B: protection functions LI BB BB
ETU25B: protection functions LSI CB CB
ETU45B: protection functions LSIN4) EB EB
ETU45B: protection functions LSIN4) with 4-line display FB FB
ETU55B: protection functions LSIN4) JB JB
ETU76B: prot. func. LSIN4) with pixel graphics display NB NB
Design with ground-fault protection
ETU27B: protection functions LSING4) DG DG
ETU45B: protection functions LSING4)6) EG EG
ETU45B: prot. functions LSING4) with 4-line display6) FG FG
ETU55B: protection functions LSING4)6) JG JG
ETU76B: prot. func. LSING4) with pixel graphics display6) NG NG
Standard Order No. supplements (for further Order No. supplements see Page 5/36)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch
2 NC + 2 NO 1AA2 1AA2
For footnotes see Page 5/33.

5/32 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
4-pole, fixed-mounted design

Size Max. rated circuit-breaker Rated current1) High switching capacity H, Icu/440 V PS* Weight
current In Order No. per PU
In max. Order No. supplements approx.
see Page 5/36
A A kA DT kg
Horizontal main circuit connection
II 800 800 100 B 3WL12 08-4@@42-.... 1 unit 67.000
II 1000 1000 100 B 3WL12 10-4@@42-.... 1 unit 67.000
II 1250 1250 100 B 3WL12 12-4@@42-.... 1 unit 67.000
II 1600 1600 100 B 3WL12 16-4@@42-.... 1 unit 67.000
II 2000 2000 100 B 3WL12 20-4@@42-.... 1 unit 67.000
II 2500 2500 100 B 3WL12 25-4@@42-.... 1 unit 71.000
II 3200 3200 100 B 3WL12 32-4@@42-.... 1 unit 77.000
III 5) 4000 4000 100 C 3WL13 40-4@@42-.... 1 unit 106.000
III5) 5000 5000 100 C 3WL13 50-4@@42-.... 1 unit 106.000
Vertical main circuit connection
II 800 800 100 B 3WL12 08-4@@41-.... 1 unit 75.000
II 1000 1000 100 B 3WL12 10-4@@41-.... 1 unit 75.000
II 1250 1250 100 B 3WL12 12-4@@41-.... 1 unit 75.000
II 1600 1600 100 B 3WL12 16-4@@41-.... 1 unit 75.000
II 2000 2000 100 B 3WL12 20-4@@41-.... 1 unit 75.000
II 2500 2500 100 B 3WL12 25-4@@41-.... 1 unit 71.000
II 3200 3200 100 B 3WL12 32-4@@41-.... 1 unit 77.000
III5)
III5)
III 5)
4000
5000
6300
4000
5000
6300
100
100
100
C
C
C
3WL13 40-4@@41-....
3WL13 50-4@@41-....
3WL13 63-4@@41-....
1 unit 106.000
1 unit 106.000
1 unit 106.000
5
Front main circuit connection, single hole
II 800 800 100 B 3WL12 08-4@@43-.... 1 unit 67.000
II 1000 1000 100 B 3WL12 10-4@@43-.... 1 unit 67.000
II 1250 1250 100 B 3WL12 12-4@@43-.... 1 unit 67.000
II 1600 1600 100 B 3WL12 16-4@@43-.... 1 unit 67.000
II 2000 2000 100 B 3WL12 20-4@@43-.... 1 unit 67.000
II 2500 2500 100 B 3WL12 25-4@@43-.... 1 unit 71.000
II 3200 3200 100 B 3WL12 32-4@@43-.... 1 unit 77.000
III5) 4000 4000 100 C 3WL13 40-4@@43-.... 1 unit 106.000
Front main circuit connection, double hole
II 800 800 100 B 3WL12 08-4@@44-.... 1 unit 67.000
II 1000 1000 100 B 3WL12 10-4@@44-.... 1 unit 67.000
II 1250 1250 100 B 3WL12 12-4@@44-.... 1 unit 67.000
II 1600 1600 100 B 3WL12 16-4@@44-.... 1 unit 67.000
II 2000 2000 100 B 3WL12 20-4@@44-.... 1 unit 67.000
II 2500 2500 100 B 3WL12 25-4@@44-.... 1 unit 71.000
II 3200 3200 100 B 3WL12 32-4@@44-.... 1 unit 77.000
III 5) 4000 4000 100 C 3WL13 40-4@@44-.... 1 unit 106.000
Order No. supplements
Non-automatic circuit-breakers2)
without electronic trip unit AA
without electronic trip unit, communication/measurement function optional3) ■ AB
Electronic trip units
Design without ground-fault protection
ETU15B: protection functions LI5) BB
ETU25B: protection functions LSI CB
ETU45B: protection functions LSIN4) EB
ETU45B: protection functions LSIN4) with 4-line display FB
ETU55B: protection functions LSIN4) JB
ETU76B: protection functions LSIN4) with pixel graphics display NB
Design with ground-fault protection
ETU27B: protection functions LSING4) DG
ETU45B: protection functions LSING4)6) EG
ETU45B: protection functions LSING4) with 4-line display6) FG
ETU55B: protection functions LSING4)6) JG
ETU76B: protection functions LSING4) with pixel graphics display6) NG
Standard Order No. supplements (for further Order No. supplements see Page 5/36)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2
Footnotes for pages 5/32 and 5/33: 4) Current transformers for vectorial summation current formation or for pro-
1) Rated current determined by rated current module. tection of the neutral conductor and current transformers for detection of
On the standard design the supplied module is equal to the max. rated the ground-fault current in the grounded star point of the transformer must
type current. be ordered separately, see Page 5/46, or they can be ordered by adding
If a lower rated current is required, adaptation by order code on page 5/37. the supplement "–Z" and order code "F23 ", see Page 5/37.
2) Permissible short-time current rating Icc and rated short-circuit making 5) Size III circuit-breakers are not available with electronic trip unit design
capacity Icm for non-automatic circuit-breakers - see Page 5/20. ETU15B.
3) Required accessories "PROFIBUS communication interface" or "Measure- 6) ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
ment function Plus": Order No. with "–Z" and order code "F02" or "F05" and tripping), see Page 5/46.
respectively, see Page 5/38. ■ Start of delivery on request

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/33


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
4-pole, withdrawable design

Size Max. rated Rated current1) ECO switching capacity N, PS* Weight Standard switching capacity S, PS* Weight
circuit-breaker In Icu/440 V per PU Icu/440 V per PU
current In max. Order No. approx. Order No. approx.
Order No. supplements Order No. supplements
see Page 5/36 see Page 5/36
A A kA DT kg kA DT kg
Without guide frame (for guide frames see Page 5/45)
I 630 630 50 B 3WL11 06-2@@45-.... 1 unit 54.000 65 B 3WL11 06-3@@45-.... 1 unit 54.000
I 800 800 50 B 3WL11 08-2@@45-.... 1 unit 54.000 65 B 3WL11 08-3@@45-.... 1 unit 54.000
I 1000 1000 50 B 3WL11 10-2@@45-.... 1 unit 54.000 65 B 3WL11 10-3@@45-.... 1 unit 54.000
I 1250 1250 50 B 3WL11 12-2@@45-.... 1 unit 54.000 65 B 3WL11 12-3@@45-.... 1 unit 54.000
I 1600 1600 50 B 3WL11 16-2@@45-.... 1 unit 54.000 65 B 3WL11 16-3@@45-.... 1 unit 54.000
II 800 800 – – 80 B 3WL12 08-3@@45-.... 1 unit 75.000
II 1000 1000 – – 80 B 3WL12 10-3@@45-.... 1 unit 75.000
II 1250 1250 – – 80 B 3WL12 12-3@@45-.... 1 unit 75.000
II 1600 1600 – – 80 B 3WL12 16-3@@45-.... 1 unit 75.000
II 2000 2000 55 B 3WL12 20-2@@45-.... 1 unit 75.000 80 B 3WL12 20-3@@45-.... 1 unit 75.000
II 2500 2500 55 B 3WL12 25-2@@45-.... 1 unit 76.000 80 B 3WL12 25-3@@45-.... 1 unit 76.000
II 3200 3200 – – 80 B 3WL12 32-3@@45-.... 1 unit 82.000
With guide frame, horizontal main circuit connection
I 630 630 50 B 3WL11 06-2@@46-.... 1 unit 84.000 65 B 3WL11 06-3@@46-.... 1 unit 84.000
I 800 800 50 B 3WL11 08-2@@46-.... 1 unit 84.000 65 B 3WL11 08-3@@46-.... 1 unit 84.000
I 1000 1000 50 B 3WL11 10-2@@46-.... 1 unit 84.000 65 B 3WL11 10-3@@46-.... 1 unit 84.000

5 I
I
II
1250
1600
800
1250
1600
800
50
50
B
B

3WL11 12-2@@46-....
3WL11 16-2@@46-....

1 unit
1 unit
84.000
84.000
80
65
65
B
B
B
3WL11 12-3@@46-....
3WL11 16-3@@46-....
3WL12 08-3@@46-....
1 unit
1 unit
1 unit
84.000
84.000
109.000
II 1000 1000 – – 80 B 3WL12 10-3@@46-.... 1 unit 109.000
II 1250 1250 – – 80 B 3WL12 12-3@@46-.... 1 unit 109.000
II 1600 1600 – – 80 B 3WL12 16-3@@46-.... 1 unit 109.000
II 2000 2000 55 B 3WL12 20-2@@46-.... 1 unit 109.000 80 B 3WL12 20-3@@46-.... 1 unit 109.000
II 2500 2500 55 B 3WL12 25-2@@46-.... 1 unit 123.000 80 B 3WL12 25-3@@46-.... 1 unit 123.000
II 3200 3200 – – 80 B 3WL12 32-3@@46-.... 1 unit 136.000
With guide frame, vertical main circuit connection
I 630 630 50 B 3WL11 06-2@@47-.... 1 unit 84.000 65 B 3WL11 06-3@@47-.... 1 unit 84.000
I 800 800 50 B 3WL11 08-2@@47-.... 1 unit 84.000 65 B 3WL11 08-3@@47-.... 1 unit 84.000
I 1000 1000 50 B 3WL11 10-2@@47-.... 1 unit 84.000 65 B 3WL11 10-3@@47-.... 1 unit 84.000
I 1250 1250 50 B 3WL11 12-2@@47-.... 1 unit 84.000 65 B 3WL11 12-3@@47-.... 1 unit 84.000
I 1600 1600 50 B 3WL11 16-2@@47-.... 1 unit 84.000 65 B 3WL11 16-3@@47-.... 1 unit 84.000
II 800 800 – – 80 B 3WL12 08-3@@47-.... 1 unit 109.000
II 1000 1000 – – 80 B 3WL12 10-3@@47-.... 1 unit 109.000
II 1250 1250 – – 80 B 3WL12 12-3@@47-.... 1 unit 109.000
II 1600 1600 – – 80 B 3WL12 16-3@@47-.... 1 unit 109.000
II 2000 2000 55 B 3WL12 20-2@@47-.... 1 unit 109.000 80 B 3WL12 20-3@@47-.... 1 unit 109.000
II 2500 2500 55 B 3WL12 25-2@@47-.... 1 unit 123.000 80 B 3WL12 25-3@@47-.... 1 unit 123.000
II 3200 3200 – 80 B 3WL12 32-3@@47-.... 1 unit 136.000
With guide frame, connecting flange
I 630 630 50 B 3WL11 06-2@@48-.... 1 unit 84.000 65 B 3WL11 06-3@@48-.... 1 unit 84.000
I 800 800 50 B 3WL11 08-2@@48-.... 1 unit 84.000 65 B 3WL11 08-3@@48-.... 1 unit 84.000
I 1000 1000 50 B 3WL11 10-2@@48-.... 1 unit 84.000 65 B 3WL11 10-3@@48-.... 1 unit 84.000
I 1250 1250 50 B 3WL11 12-2@@48-.... 1 unit 84.000 65 B 3WL11 12-3@@48-.... 1 unit 84.000
I 1600 1600 50 B 3WL11 16-2@@48-.... 1 unit 84.000 65 B 3WL11 16-3@@48-.... 1 unit 84.000
II 800 800 – – 80 B 3WL12 08-3@@48-.... 1 unit 109.000
II 1000 1000 – – 80 B 3WL12 10-3@@48-.... 1 unit 109.000
II 1250 1250 – – 80 B 3WL12 12-3@@48-.... 1 unit 109.000
II 1600 1600 – – 80 B 3WL12 16-3@@48-.... 1 unit 109.000
II 2000 2000 55 B 3WL12 20-2@@48-.... 1 unit 109.000 80 B 3WL12 20-3@@48-.... 1 unit 109.000
II 2500 2500 55 B 3WL12 25-2@@48-.... 1 unit 123.000 80 B 3WL12 25-3@@48-.... 1 unit 123.000
II 3200 3200 – – 80 B 3WL12 32-3@@48-.... 1 unit 136.000
Non-automatic circuit-breakers2) Order No. supplements Order No. supplements
without electronic trip unit AA AA
without electronic trip unit, communication/measure- AB AB
ment function optional3) ■
Electronic trip units
Design without ground-fault protection
ETU15B: protection functions LI BB BB
ETU25B: protection functions LSI CB CB
ETU45B: protection functions LSIN4) EB EB
ETU45B: protection functions LSIN4) with 4-line display FB FB
ETU55B: protection functions LSIN4) JB JB
ETU76B: prot. functions LSIN4) with pixel graphics display NB NB
Design with ground-fault protection
ETU27B: protection functions LSING4) DG DG
ETU45B: protection functions LSING4)6) EG EG
ETU45B: protection functions LSING4) with 4-line display6) FG FG
ETU55B: protection functions LSING4)6) JG JG
ETU76B: prot. func. LSING4) with pixel graphics display6) NG NG
Standard Order No. supplements (for further Order No. supplements for circuit-breakers and guide frames, see Page 5/36)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch
2 NC + 2 NO 1AA2 1AA2
For footnotes see Page 5/35.

5/34 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
4-pole, withdrawable design

Size Max. rated circuit-breaker Rated current1) High switching capacity H, Icu/440 V PS* Weight
current In Order No. per PU
In max. Order No. supplements approx.
A A kA DT see Page 5/36 kg
Without guide frame (for guide frames see Page 5/45)
II 800 800 100 B 3WL12 08-4@@45-.... 1 unit 75.000
II 1000 1000 100 B 3WL12 10-4@@45-.... 1 unit 75.000
II 1250 1250 100 B 3WL12 12-4@@45-.... 1 unit 75.000
II 1600 1600 100 B 3WL12 16-4@@45-.... 1 unit 75.000
II 2000 2000 100 B 3WL12 20-4@@45-.... 1 unit 75.000
II 2500 2500 100 B 3WL12 25-4@@45-.... 1 unit 76.000
II 3200 3200 100 B 3WL12 32-4@@45-.... 1 unit 82.000
III 5) 4000 4000 100 C 3WL13 40-4@@45-.... 1 unit 106.000
III 5) 5000 5000 100 C 3WL13 50-4@@45-.... 1 unit 106.000
III5) 6300 6300 100 C 3WL13 63-4@@45-.... 1 unit 227.000
With guide frame, horizontal main circuit connection
II 800 800 100 B 3WL12 08-4@@46-.... 1 unit 109.000
II 1000 1000 100 B 3WL12 10-4@@46-.... 1 unit 109.000
II 1250 1250 100 B 3WL12 12-4@@46-.... 1 unit 109.000
II 1600 1600 100 B 3WL12 16-4@@46-.... 1 unit 109.000
II 2000 2000 100 B 3WL12 20-4@@46-.... 1 unit 109.000
II 2500 2500 100 B 3WL12 25-4@@46-.... 1 unit 123.000
II 3200 3200 100 B 3WL12 32-4@@46-.... 1 unit 136.000
III 5)
III 5)
4000
5000
4000
5000
With guide frame, vertical main circuit connection
100
100
C
C
3WL13 40-4@@46-....
3WL13 50-4@@46-....
1 unit 190.000
1 unit 190.000 5
II 800 800 100 B 3WL12 08-4@@47-.... 1 unit 109.000
II 1000 1000 100 B 3WL12 10-4@@47-.... 1 unit 109.000
II 1250 1250 100 B 3WL12 12-4@@47-.... 1 unit 109.000
II 1600 1600 100 B 3WL12 16-4@@47-.... 1 unit 109.000
II 2000 2000 100 B 3WL12 20-4@@47-.... 1 unit 109.000
II 2500 2500 100 B 3WL12 25-4@@47-.... 1 unit 123.000
II 3200 3200 100 B 3WL12 32-4@@47-.... 1 unit 136.000
III 5) 4000 4000 100 C 3WL13 40-4@@47-.... 1 unit 190.000
III 5) 5000 5000 100 C 3WL13 50-4@@47-.... 1 unit 190.000
III 5) 6300 6300 100 C 3WL13 63-4@@47-.... 1 unit 227.000
With guide frame, connecting flange
II 800 800 100 B 3WL12 08-4@@48-.... 1 unit 109.000
II 1000 1000 100 B 3WL12 10-4@@48-.... 1 unit 109.000
II 1250 1250 100 B 3WL12 12-4@@48-.... 1 unit 109.000
II 1600 1600 100 B 3WL12 16-4@@48-.... 1 unit 109.000
II 2000 2000 100 B 3WL12 20-4@@48-.... 1 unit 109.000
II 2500 2500 100 B 3WL12 25-4@@48-.... 1 unit 123.000
II 3200 3200 100 B 3WL12 32-4@@48-.... 1 unit 136.000
III 5) 4000 4000 100 C 3WL13 40-4@@48-.... 1 unit 190.000
Order No. supplements
Non-automatic circuit-breakers2)
without electronic trip unit AA
without electronic trip unit, communication/measurement function optional3) ■ AB
Electronic trip units
Design without ground-fault protection
ETU15B: protection functions LI5) BB
ETU25B: protection functions LSI CB
ETU45B: protection functions LSIN4) EB
ETU45B: protection functions LSIN4) with 4-line display FB
ETU55B: protection functions LSIN4) JB
ETU76B: protection functions LSIN4) with pixel graphics display NB
Design with ground-fault protection
ETU27B: protection functions LSING4) DG
ETU45B: protection functions LSING4)6) EG
ETU45B: protection functions LSING4) with 4-line display6) FG
ETU55B: protection functions LSING4)6) JG
ETU76B: protection functions LSING4) with pixel graphics display6) NG
Standard Order No. supplements (for further Order No. supplements for circuit-breakers and guide frames, see Page 5/36)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2
Footnotes for pages 5/34 and 5/35: 4) Current transformers for vectorial summation current formation or for pro-
1) Rated current determined by rated current module. tection of the neutral conductor and current transformers for detection of
On the standard design the supplied module is equal to the max. rated the ground-fault current in the grounded star point of the transformer must
type current. be ordered separately, see Page 5/46, or they can be ordered by adding
If a lower rated current is required, adaptation by order code on page 5/37. the supplement "–Z" and order code "F23 ", see Page 5/37.
2) Permissible short-time current rating Icc and rated short-circuit making 5) Size III circuit-breakers are not available with electronic trip unit design
capacity Icm for non-automatic circuit-breakers - see Page 5/20. ETU15B.
3) Required accessories "PROFIBUS communication setup" or "Measurement 6) ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
function Plus": Order No. with "–Z" and order code "F02" or "F05" respec- and tripping), see Page 5/46.
tively, see Page 5/38. ■ Start of delivery on request

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/35


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Options

■ Selection and ordering data


Order No. supplement
3WL 1. . . - . . . . . - 7 7 7 7
Operating mechanism
Manual operating mechanism with mechanical closing 1
Manual operating mechanism with mechanical
and electrical closing,
closing solenoid suitable for continuous duty, 100 % ON-time
Closing solenoid
AC 50/60 Hz V DC V
110 110 2
230 220 3

Manual/motorized operating mechanism with mechanical


and electrical closing,
closing solenoid suitable for continuous duty, 100 % ON-time
Motor Closing solenoid
AC 50/60 Hz V DC V AC 50/60 Hz V DC V
208-240 220-250 230 220 4
110-127 110-125 110 110 5

5
– 24 – 24 6
To order different voltages for
motorized operating mechanism and closing solenoid:
"1" at the 13th digit of the Order No. and order codes,
see Page 5/38.
1st auxiliary release
Without 1st auxiliary release A
Shunt release suitable for continuous duty, 100 % ON-time
AC 50/60 Hz V DC V
– 24 B
– 30 C
– 48 D
– 60 E
110 110 F
230 220 G
2nd auxiliary release
Without 2nd auxiliary release A
Shunt release suitable for continuous duty, 100 % ON-time
AC 50/60 Hz V DC V
– 24 B
– 30 C
– 48 D
– 60 E
110 110 F
230 220 G
Undervoltage release, instantaneous (≤ 80 ms),
short-time delay (≤ 200 ms)
AC 50/60 Hz V DC V
– 24 J
– 30 K
– 48 L
110–127 110–125 M
208–240 220–250 N
380–415 – P
Undervoltage release, can be delayed between 0.2 s and 3.2 s
AC 50/60 Hz V DC V
– 48 Q
110–127 110–125 R
208–240 220–250 S
380–415 – T
Auxiliary switches
1st auxiliary switch block
2 NO + 2 NC 2
1st + 2nd auxiliary switch block
4 NO + 4 NC 4
6 NO + 2 NC 7
5 NO + 3 NC 8

5/36 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Options

Add "–Z" to the complete Order No. and Order Order No. with "–Z"
indicate the appropriate order code(s). code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . – . . . . . – . . . . –Z
and additional order code(s)
@@@ + . . . + . . .
Code for
"further versions"–Z
Operator's Guide
Printed version (version on CD-ROM included in the
scope of supply of the circuit-breaker German/English ÜÓÒ
French/Italian ÜÓÓ #
Spanish/Portuguese ÜÓÔ
Rated voltage AC/DC 1000 V
Only for circuit-breakers with high switching capacity (8th digit of the Order No. is a "4")
Size II4) up to 2000 A
up to 2500 A
up to 3200 A
Size III4) up to 4000 A ÜÒÃ #
up to 5000 A
up to 6300 A
Rated current module / rating plug

5
Size I Size II Size III Rated current In
A
Only one module is possible per × × – 250 ÁÒÔ
circuit-breaker × × – 315 ÁÒÕ
(not in conjunction with electronic trip
unit ETU15B). × × – 400 ÁÒÖ
As standard the overcurrent × × – 500 ÁÒÃ
releases are equipped with a rated
current module. × × – 630 ÁÒØ
The supplied rated current module is × × – 800 ÁÒÚ
equal to the max. rated circuit-
breaker current.
× × – 1000 ÁÓÒ #
× × × 1250 ÁÓÔ
× × × 1600 ÁÓØ
– × × 2000 ÁÔÒ
– × × 2500 ÁÔÃ
– × × 3200 ÁÕÔ
– – × 4000 ÁÖÒ
– – × 5000 ÁÃÒ
– – × 6300 ÁØÕ
Indication/operator control elements, door sealing frame
5-digit mechanical ÂÒÓ #
operating cycles counter1)
Electrical ON button Button with sealing cap ÂÓÓ
in the operator control panel2)
only possible with circuit-breakers
Key operation with lock CES ÂÓÔ #
with closing solenoid Key operation with lock IKON ÂÓÖ
Storage status 1 NO contact ÂÔÒ
signaling switch 2) (S21)
Ready-to-close signaling switch 1 NO contact ÂÔÔ
#
(S20)
Signaling switch2) for the first auxiliary release (S22) ÂÔØ
for the second auxiliary release (S23) ÂÔÙ
#
îÔÃ
Motor shutdown switch on the
operator control panel3) #
îÔÖ
EMERGENCY-STOP button Mushroom-head pushbutton instead of
the mechanical OFF button #
Door sealing frame ïÖÒ #
Neutral conductor transformer
Internal transformer Size I áÔÕ
for neutral conductor
(ETU with N conductor protection
Size II #
required) Size III
Overload and short-circuit Only possible with 4-pole circuit-breakers áÕÒ #
protection of neutral conductor with ETU27B, ETU45B, ETU55B or ETU76B
as for one-pole load only with internal transformer for neutral
conductor. Delivery as of July 2004.
1) Only possible with motorized operating mechanism. 4) If ordering withdrawable circuit-breaker and guide frame separately,
2) Not possible with "PROFIBUS communication interface" option, order code specify order code "A05" for withdrawable circuit-breaker and guide frame.
"F02". × available
3) Only for circuit-breakers with motorized operating mechanism, not possi- – not available
ble with order codes "C11", "C12", "C14".

Siemens LV 30 · 2004 5/37


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Options

Add "–Z" to the complete Order No. and Order Order No. with "–Z"
indicate the appropriate order code(s). code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . – . . . . . – . . . . –Z
and additional order code(s)
@@@ + . . . + . . .
Code for
"Further versions"–Z
Lockout device and remote reset
Automatic reset of the lockout device æÒÓ #
Tripped signaling switch1) 1 changeover æÒÙ #
Remote reset solenoid for display and reset button
including automatic reset of the lockout device
AC 50/60 Hz V DC V
– 24 æÓÒ
– 48 æÓÓ
120 125 æÓÔ #
220–240 250 æÓÕ

Motorized operating mechanism and closing solenoid

5 Motorized operating mechanism


Only possible if the 13th digit of the Order No. = "1"
Motor
AC 50/60 Hz V DC V
– 24–30 èÒÓ
– 48–60 èÒÕ
110–127 110–125 èÒÃ #
208–240 220–250 èÒØ

Closing solenoid suitable for continuous duty, 100 % ON-time – Only possible if the 13th digit of the Order No. = "1"
Activation solenoid
AC 50/60 Hz V DC V
– 24 èÔÓ
– 30 èÔÔ
– 48 èÔÕ #
– 60 èÔÖ
110 110 èÔÃ
230 220 èÔØ

Closing solenoid2) – unsuitable for continuous duty, 5 % ON-time – Only possible if the 13th digit of the Order No. = "1"
Activation solenoid
AC 50/60 Hz V DC V
– 24 èÕÓ
– 48 èÕÕ
110–127 110–125 èÕÃ #
208–240 220–250 èÕØ

Communication and measurement function 3)


Breaker status sensor (BSS) connection áÒÓ
PROFIBUS communication interface5) áÒÔ
including COM15 and Breaker status sensor (BSS)
Measurement function (without PROFIBUS communication áÒÖ #
interface)4)
Measurement function Plus (without PROFIBUS communication áÒÃ
interface)4)
EMC filter
EMC filter áÕÓ #
Delivery as of July 2004
1) Not possible with "PROFIBUS communication interface" option, order code
"F02".
2) Overexcited, i.e. closing time 25 ms (standard 60 ms).
3) For further information, see Section "Communication-capable circuit-break-
ers".
4) Additional voltage transformers are required for connection of the mea-
surement function, see Page 5/51.
5) If ordering withdrawable circuit-breaker and guide frame separately, spec-
ify order code "F02" for withdrawable circuit-breaker only.

5/38 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Options

Add "–Z" to the complete Order No. and Order No. with "–Z"
indicate the appropriate order code(s). 1234 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . – . . . . . – . . . . –Z
and additional order code(s)
@@@
Code for
"Further versions" –Z
Order Order code
code for for withdraw-
fixed-moun- able version
ted version
Interlocks, covers, position indicator switches
Mutual mechanical interlocking
(Interlocking module Fixed-mounted circuit-breaker îÃà # –
with Bowden wire 2 m)
For withdrawable circuit-breaker – íÃÃ
with guide frame

For guide frame – íÃØ

For withdrawable circuit-breaker – íÃÙ

Arc chute cover2) 3-pole


íÓÒ
5
Size I –
Size II – íÓÒ
Size III – íÓÒ

4-pole
Size I – íÓÒ
Size II – íÓÒ
Size III – íÓÒ

Shutters 3-pole
2 parts Size I – íÔÓ
lockable Size II – íÔÓ
with padlocks 1) Size III – íÔÓ

4-pole
Size I – íÔÓ
Size II – íÔÓ
Size III – íÔÓ

Position indicator switch for guide Connected Test Discon-


frames position position nected
position

1 CO 1 CO 1 CO – íÓÃ

3 CO 2 CO 1 CO – íÓØ
1) Padlocks not included in scope of supply.
2) Not possible with option "rated voltage AC/DC 1000 V", order code "A05".
Not possible with DC version.
Not possible with fixed-mounted design.

Siemens LV 30 · 2004 5/39


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Options

Add "–Z" to the complete Order No. and Order Order No. with "–Z"
indicate the appropriate order code(s). code 1234 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . – . . . . . – . . . . –Z
and additional order code(s)
@@@
Code for
"Further versions"–Z
Order Order code for
code for withdrawable
fixed-moun- version
ted version
Locking devices
Locking device against
unauthorized closing,
in the operator control panel
The disconnector unit fulfills the require- Made by CES îÒÓ îÒÓ
ments for main circuit-breakers to Made by IKON îÒÕ îÒÕ
EN 60204 (VDE 0113)
Mounting set FORTRESS or Castell1) îÒÃ îÒÃ
Made by KIRK-Key1) ■ îÒØ # ■ îÒØ
Mounting set for padlocks2) îÒÙ îÒÙ
Made by Ronis îÒÚ îÒÚ
Made by Profalux îÒÛ îÒÛ

5 EMERGENCY-STOP button Mushroom-head pushbutton instead of


the mechanical OFF button îÔÖ # îÔÖ

Locking device against Made by CES – íØÓ


unauthorized closing, Made by IKON – íØÕ
for withdrawable circuit-breakers
The disconnector unit fulfills the require- Made by Ronis – íØÚ
ments for main circuit-breakers to Made by Profalux – íØÒ
EN 60204 (VDE 0113),
consisting of a lock in the cabinet door, Made by KIRK-Key – ■ íØØ
active in the connected position;
the function is retained when the circuit-
breaker is replaced
Locking device
for operating mechanism hand lever îÕÕ # îÕÕ
with padlock2)
Locking device to prevent Made by CES – îÙÓ
movement of the withdrawable Made by IKON – îÙÕ
circuit-breaker
Safety lock for fitting to circuit-breaker Made by O.M.R. – ■ îÙÙ
Made by Profalux – îÙÃ
Made by Ronis – îÙØ
Made by KIRK-Key – ■ îÙÖ
Locking devices
Locking device to prevent Made by CES – íÚÓ
movement of the withdrawable Made by IKON – íÚÕ
circuit-breaker
in disconnected position, Made by O.M.R. – ■ íÚÖ
consisting of Bowden wire and lock Made by Profalux – íÚÃ
in the cabinet door
Made by Ronis – íÚØ
Mounting set for padlocks2) – íÚÚ
Locking device to prevent opening of the cabinet îÕÒ
door in:
ON position (fixed mounted version)/
in connected position (withdrawable
version) íÕÒ

to prevent closing with the cabinet îÖÒ # íÖÒ


door open
(on withdrawable version active in con-
nected position)

to prevent movement with the cabinet – íÃÒ


door open
Connection system for auxiliary conductors
Connections for screwless
connection system (tension spring) éØÓ # ëØÓ

1) Locks must be ordered from the manufacturer.


2) Padlock not included in the scope of supply.
■ Start of delivery on request.

5/40 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Options

Add "–Z" to the complete Order No. and Order Order No. with "–Z"
indicate the appropriate order code(s). code 1234 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . – . . . . . – . . . . –Z
and additional order code(s)
@@@
Code for
"Further versions"–Z
For withdrawable circuit-breaker including guide frame Order code
or guide frame only for 3- and
To select this connection system the 12th 4-pole
digit of the Order No. for the
circuit-breaker must be a "6"
Connection system for main circuit connections
Top and bottom: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
single hole Size II, up to 2500 A ëÒÒ
Size II, up to 3200 A
Size III, up to 4000 A
Top and bottom: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
double hole Size II, up to 2500 A ëÒÓ
Size II, up to 3200 A
Size III, up to 4000 A
Top:
accessible from front,
double hole
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A ëÒØ
5
Bottom: Size II, up to 3200 A
accessible from front, Size III, up to 4000 A
single hole
Top: Size I, up to 1600 A
rear horizontal, Size II, up to 2000 A
double hole Size II, up to 2500 A ëÒÙ
Bottom: Size II, up to 3200 A
accessible from front, Size III, up to 4000 A
single hole
Top: Size I, up to 1600 A
rear vertical Size II, up to 2000 A
Bottom: Size II, up to 2500 A ëÒÚ
accessible from front, Size II, up to 3200 A
single hole Size III, up to 4000 A
Top: Size I, up to 1600 A #
connecting flange Size II, up to 2000 A
Bottom: Size II, up to 2500 A ëÒÛ
accessible from front, Size II, up to 3200 A
single hole Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
single hole Size II, up to 2500 A ëÓÓ
Bottom: Size II, up to 3200 A
accessible from front, Size III, up to 4000 A
double hole
Top: Size I, up to 1600 A
rear horizontal Size II, up to 2000 A
Bottom: Size II, up to 2500 A ëÓÔ
accessible from front, Size II, up to 3200 A
double hole Size III, up to 4000 A
Top: Size I, up to 1600 A
rear vertical Size II, up to 2000 A
Bottom: Size II, up to 2500 A ëÓÕ
accessible from front, Size II, up to 3200 A
double hole Size III, up to 4000 A
Top: Size I, up to 1600 A
connecting flange Size II, up to 2000 A
Bottom: Size II, up to 2500 A ëÓÖ
accessible from front, Size II, up to 3200 A
double hole Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
single hole Size II, up to 2500 A ëÓØ
Bottom: Size II, up to 3200 A
rear horizontal Size III, up to 4000 A

Siemens LV 30 · 2004 5/41


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Options

Add "–Z" to the complete Order No. and Order Order No. with "–Z"
indicate the appropriate order code(s). code 1234 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . – . . . . . – . . . . –Z
and additional order code(s)
@@@
Identification code for
"Further versions"–Z
For withdrawable circuit-breaker with guide frame Order code
or guide frame for 3 and
4-pole
To select this connection system the 12th
digit of the Order No. for the
circuit-breaker must be a "6"
Connection system for main circuit connections
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
double hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A ëÓÙ
rear horizontal Size III, up to 4000 A
Top: Size I, up to 1600 A
rear vertical Size II, up to 2000 A
Bottom: Size II, up to 2500 A
rear horizontal Size II, up to 3200 A ëÓÚ
Size III, up to 4000 A

5
Size III, up to 5000 A
Top: Size I, up to 1600 A
connecting flange Size II, up to 2000 A
Bottom: Size II, up to 2500 A
rear horizontal Size II, up to 3200 A ëÓÛ
Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
single hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A ëÔÓ
front vertical Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
double hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A ëÔÔ
rear vertical Size III, up to 4000 A
Top: Size I, up to 1600 A
rear horizontal Size II, up to 2000 A
Bottom: Size II, up to 2500 A
rear vertical Size II, up to 3200 A ëÔÕ #
Size III, up to 4000 A
Size III, up to 5000 A
Top: Size I, up to 1600 A
connecting flange Size II, up to 2000 A
Bottom: Size II, up to 2500 A
rear vertical Size II, up to 3200 A ëÔÖ
Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
single hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A ëÔØ
connecting flange Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
double hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A ëÔÙ
connecting flange Size III, up to 4000 A
Top: Size I, up to 1600 A
rear horizontal Size II, up to 2000 A
Bottom: Size II, up to 2500 A
connecting flange Size II, up to 3200 A ëÔÚ
Size III, up to 4000 A
Top: Size I, up to 1600 A
rear vertical Size II, up to 2000 A
Bottom: Size II, up to 2500 A
connecting flange Size II, up to 3200 A ëÔÛ
Size III, up to 4000 A

5/42 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Options

Add "–Z" to the complete Order No. and Order Order No. with "–Z"
indicate the appropriate order code(s). code 1234 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . – . . . . . – . . . . –Z
and additional order code(s)
@@@
Identification code for
"Further versions"–Z
For fixed-mounted circuit-breakers Order code
To select this connection system the 12th for 3 and
digit of the Order No. for the 4-pole
circuit-breaker must be a "2"
Connection system for main circuit connections
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
double hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A éÓÒ
accessible from front, Size III, up to 4000 A
single hole
Top: Size I, up to 1600 A
rear horizontal Size II, up to 2000 A
Bottom: Size II, up to 2500 A
accessible from front, Size II, up to 3200 A éÓÓ
single hole Size III, up to 4000 A
Top:
rear vertical
Bottom:
Size I, up to 1600 A
Size II, up to 2000 A
Size II, up to 2500 A
5
accessible from front, Size II, up to 3200 A éÓÔ
single hole Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
single hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A éÓÖ
accessible from front, Size III, up to 4000 A
double hole
Top: Size I, up to 1600 A
rear horizontal Size II, up to 2000 A
Bottom: Size II, up to 2500 A
accessible from front, Size II, up to 3200 A éÓÃ
double hole Size III, up to 4000 A
Top: Size I, up to 1600 A
rear vertical Size II, up to 2000 A
Bottom: Size II, up to 2500 A
accessible from front, Size II, up to 3200 A éÓØ #
double hole Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
single hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A éÓÚ
front horizontal Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
double hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A éÓÛ
rear horizontal Size III, up to 4000 A
Top: Size I, up to 1600 A
rear vertical Size II, up to 2000 A
Bottom: Size II, up to 2500 A
front horizontal Size II, up to 3200 A éÔÒ
Size III, up to 4000 A
Size III, up to 5000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
single hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A éÔÔ
rear vertical Size III, up to 4000 A
Top: Size I, up to 1600 A
accessible from front, Size II, up to 2000 A
double hole Size II, up to 2500 A
Bottom: Size II, up to 3200 A éÔÕ
rear vertical Size III, up to 4000 A
Top: Size I, up to 1600 A
rear horizontal Size II, up to 2000 A
Bottom: Size II, up to 2500 A éÔÖ
rear vertical Size II, up to 3200 A
Size III, up to 4000 A
Size III, up to 5000 A

Siemens LV 30 · 2004 5/43


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

■ Overview
Determination of the number of auxiliary supply connectors required
This selection is only required if the guide frame is ordered under a The required number of auxiliary supply connectors
separate Order No.. depends on:
• operating mechanism type
X6 X5 • electronic trip unit with/without current transformer
X7
NSE0_01104

X8
• type and number of auxiliary releases
• number of auxiliary switches
• COM15 communication link

Number of auxil- Terminal


iary supply con-
nectors
a First auxiliary supply connector X6 always required. 1 X6
b Operating mechanism
b1 Manual operating mechanism with stored-energy feature with mechanical closing 0
b2 Manual operating mechanism with stored-energy feature with mechanical and electrical closing 0 X6
b3 Manual/motorized operating mechanism with stored-energy feature with mechanical and electrical closing +1 X5
c Electronic trip unit
c1 Electronic trip unit ETU15B, ETU25B, ETU27B 0
c2 Electronic trip unit ETU45B, ETU55B, ETU76B (internal CubicleBUS) +1 X8

5
Terminals for external current transformer for overload protection in the neutral conductor and ground-fault protection
c3 Current transformer fitted in the neutral conductor (required with 3-pole circuit-breakers if c2 is not selected) +1 X8
c4 Current transformer in the star point of the transformer (required if c2 or c3 is not selected) +1 X8
d Auxiliary release
d1 With/without 1st auxiliary release (shunt release F1) 0 X6
d2 2nd auxiliary release (shunt release F2, undervoltage release F3, undervoltage release F4 that can be delayed) +1 X5
e Auxiliary switch block
e1 1st auxiliary switch block 2 NO + 2 NC 0 X6
e2 1st and 2nd auxiliary switch block 4 NO + 4 NC or 6 NO + 2 NC or 5 NO + 3 NC (required if b3 or d2 is not selected) +1 X5
f Communication module
f1 Without communication module COM15 0
f2 With communication module COM15 - +1 X7
occupies the entire terminal block X7, making the following options no longer possible:
• Tripped signaling switch S24
• Stored-energy status indication S21
• Electrical ON button S10
• Signaling switch on first and second auxiliary release S22 + S23
g Optional signals/accessories
g1 Tripped signaling switch S24 (only possible if f2 is not selected) +1 X7
g2 Stored-energy status indication S21 (only possible if f2 is not selected, required if g1 is not selected) +1 X7
g3 Electrical ON button S10 (only possible if f2 is not selected, required if g1 or g2 is not selected) +1 X7
g4 Signaling switch on first auxiliary release S22 (only possible if f2 is not selected, required if g1, g2 or g3 is not selected) +1 X7
g5 Signaling switch on second auxiliary release S23 (only possible if f2 is not selected, required if g1, g2, g3 or g4 is not +1 X7
selected)
g6 Ready-to-close signaling switch S20 0 X6
g7 Motor shutdown switch S12 (only possible if motorized operating mechanism is selected) 0 X5
g8 Remote reset magnet F7 (required if c2 is not selected) +1 X8
h Total number of auxiliary supply connectors (max. 4)

5/44 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

■ Selection and ordering data


Guide frame for AC circuit-breakers/non-automatic circuit-breakers
Size Max. rated circuit- Guide frame for 3-pole Guide frame for 4-pole
breaker current circuit-breakers/non-automatic circuit-breakers circuit-breakers/non-automatic circuit-breakers
In max. DT Order No. PS* Weight DT Order No. PS* Weight
(Order No. supplements per PU (Order No. supplements per PU
required according to approx. required according to approx.
table below) kg table below) kg
A
Front main circuit connection, single hole
I 1000 B 3WL9 211-1AA@@-@@A 1 1 unit 25.000 B 3WL9 211–1BA@@-@@A 1 1 unit 30.000
I 1600 B 3WL9 211-2AA@@-@@A 1 1 unit 25.000 B 3WL9 211–2BA@@-@@A 1 1 unit 30.000
II 2000 B 3WL9 212-3AA@@-@@A 1 1 unit 31.000 B 3WL9 212–3BA@@-@@A 1 1 unit 37.000
II 2500 B 3WL9 212-4AA@@-@@A 1 1 unit 39.000 B 3WL9 212–4BA@@-@@A 1 1 unit 47.000
II 3200 B 3WL9 212-5AA@@-@@A 1 1 unit 45.000 B 3WL9 212–5BA@@-@@A 1 1 unit 54.000
III 4000 B 3WL9 213-6AA@@-@@A 1 1 unit 60.000 B 3WL9 213–6BA@@-@@A 1 1 unit 84.000
Front main circuit connection, double hole
I 1000 B 3WL9 211-1AB@@-@@A 1 1 unit 25.000 B 3WL9 211-1BB@@-@@A 1 1 unit 30.000
I 1600 B 3WL9 211-2AB@@-@@A 1 1 unit 25.000 B 3WL9 211-2BB@@-@@A 1 1 unit 30.000
II 2000 B 3WL9 212-3AB@@-@@A 1 1 unit 31.000 B 3WL9 212-3BB@@-@@A 1 1 unit 37.000
II 2500 B 3WL9 212-4AB@@-@@A 1 1 unit 39.000 B 3WL9 212-4BB@@-@@A 1 1 unit 47.000
II 3200 B 3WL9 212-5AB@@-@@A 1 1 unit 45.000 B 3WL9 212-5BB@@-@@A 1 1 unit 54.000

5
III 4000 B 3WL9 213-6AB@@-@@A 1 1 unit 60.000 B 3WL9 213-6BB@@-@@A 1 1 unit 84.000
Horizontal main circuit connection
I 1000 B 3WL9 211-1AC@@-@@A 1 1 unit 25.000 B 3WL9 211-1BC@@-@@A 1 1 unit 30.000
I 1600 B 3WL9 211-2AC@@-@@A 1 1 unit 25.000 B 3WL9 211-2BC@@-@@A 1 1 unit 30.000
II 2000 B 3WL9 212-3AC@@-@@A 1 1 unit 31.000 B 3WL9 212-3BC@@-@@A 1 1 unit 37.000
II 2500 B 3WL9 212-4AC@@-@@A 1 1 unit 39.000 B 3WL9 212-4BC@@-@@A 1 1 unit 47.000
II 3200 B 3WL9 212-5AC@@-@@A 1 1 unit 45.000 B 3WL9 212-5BC@@-@@A 1 1 unit 54.000
III 4000 B 3WL9 213-6AC@@-@@A 1 1 unit 60.000 B 3WL9 213-6BC@@-@@A 1 1 unit 84.000
III 5000 B 3WL9 213-7AC@@-@@A 1 1 unit 60.000 B 3WL9 213-7BC@@-@@A 1 1 unit 84.000
Vertical main circuit connection
I 1000 B 3WL9 211-1AD@@-@@A 1 1 unit 25.000 B 3WL9 211-1BD@@-@@A 1 1 unit 30.000
I 1600 B 3WL9 211-2AD@@-@@A 1 1 unit 25.000 B 3WL9 211-2BD@@-@@A 1 1 unit 30.000
II 2000 B 3WL9 212-3AD@@-@@A 1 1 unit 31.000 B 3WL9 212-3BD@@-@@A 1 1 unit 37.000
II 2500 B 3WL9 212-4AD@@-@@A 1 1 unit 39.000 B 3WL9 212-4BD@@-@@A 1 1 unit 47.000
II 3200 B 3WL9 212-5AD@@-@@A 1 1 unit 45.000 B 3WL9 212-5BD@@-@@A 1 1 unit 54.000
III 4000 B 3WL9 213-6AD@@-@@A 1 1 unit 60.000 B 3WL9 213-6BD@@-@@A 1 1 unit 84.000
III 5000 B 3WL9 213-7AD@@-@@A 1 1 unit 60.000 B 3WL9 213-7BD@@-@@A 1 1 unit 84.000
III 6300 B 3WL9 213-8AD@@-@@A 1 1 unit 70.000 B 3WL9 213-8BD@@-@@A 1 1 unit 119.000
Main circuit connection, connecting flange
I 1000 B 3WL9 211-1AE@@-@@A 1 1 unit 25.000 B 3WL9 211-1BE@@-@@A 1 1 unit 30.000
I 1600 B 3WL9 211-2AE@@-@@A 1 1 unit 25.000 B 3WL9 211-2BE@@-@@A 1 1 unit 30.000
II 2000 B 3WL9 212-3AE@@-@@A 1 1 unit 31.000 B 3WL9 212-3BE@@-@@A 1 1 unit 37.000
II 2500 B 3WL9 212-4AE@@-@@A 1 1 unit 39.000 B 3WL9 212-4BE@@-@@A 1 1 unit 47.000
II 3200 B 3WL9 212-5AE@@-@@A 1 1 unit 45.000 B 3WL9 212-5BE@@-@@A 1 1 unit 54.000
III 4000 B 3WL9 213-6AE@@-@@A 1 1 unit 60.000 B 3WL9 213-6BE@@-@@A 1 1 unit 84.000
Number of auxiliary supply connectors
none 0 0
1 connector 1 1
2 connectors 2 2
3 connectors 3 3
4 connectors 4 4
Required number of auxiliary supply connectors, see
table on page 5/44
Type of auxiliary circuit connections
without 0 0
with screw-type terminals (SIGUT) 1 1
with screwless connection system 2 2
(tension spring)
Position indicator switches
without 0 0
Option 1 1 1
connected position 1 changeover,
test position 1 changeover,
disconnected position 1 changeover
Option 2 2 2
connected position 3 changeovers,
test position 2 changeovers,
disconnected position 1 changeover
Shutters
without A A
with shutter, Size I B B
2 parts, Size II
lockable Size III
Add "–Z" to the complete Order No. Order No. with "–Z" 1234 5 6 7 8 9 10 11 12 13 14 15 16
and indicate the appropriate order code(s). and additional order 3WL9 2 1 . – . . . . . – . . . . –Z
code @@@
Rated voltage AC 1000 V ÜÒÃ
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see Pages 5/37 to 5/43.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/45


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
Electronic trip unit ETU and measurement function option
with protection function Measurement function
ETU15B LI without C 3WL9 311-5AA00-0AA1 1 unit on req.
ETU25B LSI without C 3WL9 312-5AA00-0AA1 1 unit on req.
ETU27B LSING without C 3WL9 312-7AA00-0AA1 1 unit on req.
ETU45B: LSIN(G) without C 3WL9 314-5AA00-0AA1 1 unit on req.
(without display) with measurement func. C 3WL9 314-5AA10-0AA1 1 unit on req.
with measurement func- C 3WL9 314-5AA20-0AA1 1 unit on req.
tion Plus
ETU55B LSIN(G) without C 3WL9 315-5AA00-0AA1 1 unit on req.
with measurement func. C 3WL9 315-5AA10-0AA1 1 unit on req.
with measurement func- C 3WL9 315-5AA20-0AA1 1 unit on req.
tion Plus 4
ETU76B: LSIN(G) without C 3WL9 317-6AA00-0AA1 1 unit on req.
with measurement func. C 3WL9 317-6AA10-0AA1 1 unit on req.
with measurement func- C 3WL9 317-6AA20-0AA1 1 unit on req.
tion Plus 4
Rated current module / rating plug
5 For sizes I, II
Rated current In (A)
250 B 3WL9 111-0AA51-0AA0 1 unit on req.
315 B 3WL9 111-0AA52-0AA0 1 unit on req.
= 3 2 0 0 A
400 B 3WL9 111-0AA53-0AA0 1 unit on req.
n
500 B 3WL9 111-0AA54-0AA0 1 unit on req.
N S E 0 _ 0 0 9 9 2 a
630 B 3WL9 111-0AA55-0AA0 1 unit on req.
3WL9 111-0AA64-0AA0 800 B 3WL9 111-0AA56-0AA0 1 unit on req.
1000 B 3WL9 111-0AA57-0AA0 1 unit on req.
G F M A T 4 5 B
S 1

G
g T R IP
A
A L A R M A L A R M t g (s )
.5
1 2 tg
.1
For size I, II, III 1250 B 3WL9 111-0AA58-0AA0 1 unit on req.
B
C
D
T R IP
.4
.3
.2
.2
.3
.4
1600 B 3WL9 111-0AA61-0AA0 1 unit on req.
O F F E .1 .5

N S E 0 _ 0 1 0 2 7 a For size II, III 2000 B 3WL9 111-0AA62-0AA0 1 unit on req.


3WL9 111-0AT51-0AA0 2500 B 3WL9 111-0AA63-0AA0 1 unit on req.
3200 B 3WL9 111-0AA64-0AA0 1 unit on req.
For size III 4000 B 3WL9 111-0AA65-0AA0 1 unit on req.
5000 B 3WL9 111-0AA66-0AA0 1 unit on req.
6300 B 3WL9 111-0AA67-0AA0 1 unit on req.
Ground-fault module
N S E 0 _ 0 0 9 9 0 a
GFM AT 45B (only for ETU45B) alarm only B 3WL9 111-0AT51-0AA0 1 unit on req.
3WL9 111-0AA2.-0AA0 GFM AT 45B (only for ETU45B) alarm and release B 3WL9 111-0AT53-0AA0 1 unit on req.
GFM AT 55B–76B (only for ETU55B, ETU76B) alarm only B 3WL9 111-0AT54-0AA0 1 unit on req.
GFM AT 55B–76B (only for ETU55B, ETU76B) alarm and release B 3WL9 111-0AT56-0AA0 1 unit on req.
Display
4-line display for ETU45B B 3WL9 111-0AT81-0AA0 1 unit on req.
Transformers
N S E 0 _ 0 0 9 9 1 a
Internal transformers for neutral conductor Size I B 3WL9 111-0AA11-0AA0 1 unit on req.
3WL9 111-0AA3.-0AA0 including wiring kit Size II B 3WL9 111-0AA12-0AA0 1 unit on req.
Size III B 3WL9 111-0AA13-0AA0 1 unit on req.
N S E 0 _ 0 0 9 8 3 a

External transformers for neutral conductor Size I B 3WL9 111-0AA21-0AA0 1 unit on req.
(T5, see Page 5/19) Size II B 3WL9 111-0AA22-0AA0 1 unit on req.
Size III B 3WL9 111-0AA23-0AA0 1 unit on req.
- 6 7 # * External transformers for neutral conductor Size I B 3WL9 111-0AA31-0AA0 1 unit on req.
R a tin g P lu g
(T5, see Page 5/19) Size II B 3WL9 111-0AA32-0AA0 1 unit on req.
with copper connection pieces Size III B 3WL9 111-0AA33-0AA0 1 unit on req.
Locking devices, operator control elements
Sealable cover for ETU15B to ETU55B B 3WL9 111-0AT45-0AA0 1 unit on req.
T E S T Q U E R Y C L E A R for ETU76 B 3WL9 111-0AT46-0AA0 1 unit on req.
Automatic reset of the lockout device B 3WL9 111-0AK01-0AA0 1 unit on req.
3WL9 111-0AT45-0AA0
Remote reset solenoid2) DC 24 V B 3WL9 111-0AK03-0AA0 1 unit on req.
for mechanical "tripped" indicator DC 48 V B 3WL9 111-0AK04-0AA0 1 unit on req.
AC 120 V, DC 125 V B 3WL9 111-0AK05-0AA0 1 unit on req.
F 7
AC 208-240 V/ B 3WL9 111-0AK06-0AA0 1 unit on req.
DC 220-250 V
Retrofittable internal CubicleBUS wiring for con- for ETU45B to B 3WL9 111-0AK30-0AA0 1 unit on req.
nection to terminal X8 (without male connector1)) ETU76B
Retrofittable internal wiring for connection of the D 3WL9 111-0AK31-0AA0 1 unit on req.
external N- and G-transformers
N S E 0 _ 0 0 9 9 9 a
to terminal X8 (without male connector)
3WL9 111-0AK0.-0AA0

1) Required if communication is retrofitted. 4 Start of delivery March 2004.


2) Can only be used in conjunction with "automatic reset of lockout device",
e.g. "–Z" + "K01", 3WL9 111-0AK01-0AA0.

5/46 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
Locking devices
Protective covers for mechanical ON/OFF without safety lock B 3WL9 111-0BA21-0AA0 1 unit on req.
consisting of 2 transparent covers each made by CES B 3WL9 111-0BA22-0AA0 1 unit on req.
NSE00980

for sealing or for attaching padlocks2), made by IKON B 3WL9 111-0BA24-0AA0 1 unit on req.
cover with 6.35 mm hole
(for tool actuation),
3WL9 111-0BA22-0AA0 lock mount for safety lock
for key operation
Locking device against unauthorized closing, Mounting set FORTRESS or B 3WL9 111-0BA31-0AA0 1 unit on req.
in the operator control panel CASTELL1)
Disconnector unit ■ Made by Ronis B 3WL9 111-0BA33-0AA0 1 unit on req.
meets requirements for main circuit-breakers Made by KIRK-Key B 3WL9 111-0BA34-0AA0 1 unit on req.
to EN 60204 (VDE 0113) Made by Profalux B 3WL9 111-0BA35-0AA0 1 unit on req.
Made by CES B 3WL9 111-0BA36-0AA0 1 unit on req.
Made by IKON B 3WL9 111-0BA38-0AA0 1 unit on req.
NSE00981 Mounting set for padlocks2) B 3WL9 111-0BA41-0AA0 1 unit on req.
Locking device against unauthorized closing, Made by CES B 3WL9 111-0BA51-0AA0 1 unit on req.
for withdrawable circuit-breakers Made by IKON B 3WL9 111-0BA53-0AA0 1 unit on req.
Disconnector unit ■ Made by KIRK-Key B 3WL9 111-0BA57-0AA0 1 unit on req.
3WL9 111-0BA31-0AA0 meets requirements for main circuit-breakers Made by Ronis B 3WL9 111-0BA58-0AA0 1 unit on req.
to EN 60204 (VDE 0113)
consisting of lock in the cabinet door,
active in connected position; function is retained
Made by Profalux B 3WL9 111-0BA50-0AA0 1 unit on req.
5
when circuit-breaker is replaced
Locking device for B 3WL9 111-0BA71-0AA0 1 unit on req.
operating mechanism handle with padlock2)
NSE00982
Locking device to prevent Made by CES B 3WL9 111-0BA73-0AA0 1 unit on req.
3WL9 111-0BA53-0AA0 movement of the withdrawable circuit-breaker Made by IKON B 3WL9 111-0BA75-0AA0 1 unit on req.
Safety lock for mounting on Made by Profalux B 3WL9 111-0BA76-0AA0 1 unit on req.
the circuit-breaker Made by Ronis B 3WL9 111-0BA77-0AA0 1 unit on req.
■ Made by KIRK-Key B 3WL9 111-0BA80-0AA0 1 unit on req.
Locking devices
to prevent movement of the withdrawable Made by CES B 3WL9 111-0BA81-0AA0 1 unit on req.
circuit-breaker in disconnected position, Made by IKON B 3WL9 111-0BA83-0AA0 1 unit on req.
consisting of Bowden wire and lock Made by Profalux B 3WL9 111-0BA85-0AA0 1 unit on req.
in the cabinet door Made by Ronis B 3WL9 111-0BA86-0AA0 1 unit on req.
Mounting set for padlocks2) B 3WL9 111-0BA87-0AA0 1 unit on req.
to prevent opening of the cabinet door in ON Fixed-mounted version B 3WL9 111-0BB12-0AA0 1 unit on req.
position (can be defeated)
NSE00984
to prevent opening of the cabinet door Guide frames B 3WL9 111-0BB13-0AA0 1 unit on req.
3WL9 111-0BA71-0AA0 (can be defeated)

to prevent movement of circuit-breaker when Guide frames B 3WL9 111-0BB15-0AA0 1 unit on req.
cabinet door is open
Interlocking
Mutual mechanical interlocking, Fixed-mounted circuit-breaker B 3WL9 111-0BB21-0AA0 1 unit on req.
with 2000 mm Bowden wire
NSE00986 (one required for each circuit-breaker) Module for withdrawable B 3WL9 111-0BB24-0AA0 1 unit on req.
3WL9 111-0BA76-0AA0 circuit-breaker with frame
When ordered separately
Module for guide frame B 3WL9 111-0BB22-0AA0 1 unit on req.
Module for withdrawable circuit- B 3WL9 111-0BB23-0AA0 1 unit on req.
breaker

Adapter for size III


NSE00987 Withdrawable circuit-breaker B 3WL9 111-0BB30-0AA0 1 unit on req.
3WL9 111-0BA83-0AA0 Bowden wire
2000 mm B 3WL9 111-0BB25-0AA0 1 unit on req.
3000 mm B 3WL9 111-0BB26-0AA0 1 unit on req.
4500 mm B 3WL9 111-0BB27-0AA0 1 unit on req.
6000 mm B 3WL9 111-0BB28-0AA0 1 unit on req.

3WL9 111-0BB12-0AA0

NSE00989

3WL9 111-0BB21-0AA0

1) Locks must be ordered from the manufacturer.


2) Padlock not included in the scope of supply.
■ Start of delivery on request.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/47


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
Indicators, operator control elements
Ready-to-close indicator switch B 3WL9 111-0AH01-0AA0 1 unit on req.
Signaling switch 4) 5) First or second auxiliary B 3WL9 111-0AH02-0AA0 1 unit on req.
releases
Tripped signaling switch 4) 5) B 3WL9 111-0AH04-0AA0 1 unit on req.
Operating cycles counter, mechanical3) B 3WL9 111-0AH07-0AA0 1 unit on req.
Stored energy status signaling switch 4) 5) B 3WL9 111-0AH08-0AA0 1 unit on req.
Position indicator switch for guide frames 1st block (3 microswitches) B 3WL9 111-0AH11-0AA0 1 unit on req.
N S E 0 _ 0 0 9 9 3 a 2nd block (6 microswitches) B 3WL9 111-0AH12-0AA0 1 unit on req.
3WL9 111-0AH01-0AA0 Electrical ON button 1) 4) (button+wiring)5) with sealing cap B 3WL9 111-0AJ02-0AA0 1 unit on req.
with CES mounting set B 3WL9 111-0AJ03-0AA0 1 unit on req.
with BKS mounting set B 3WL9 111-0AJ04-0AA0 1 unit on req.
with IKON mounting set B 3WL9 111-0AJ05-0AA0 1 unit on req.
Motor shutdown switch 2) B 3WL9 111-0AJ06-0AA0 1 unit on req.
(mounting on operator control panel)
N S E 0 _ 0 0 9 9 4 a

EMERGENCY-STOP button B 3WL9 111-0BA72-0AA0 1 unit on req.

5 Mushroom-head pushbutton instead of the


mechanical OFF button
Test device
Manual test device for electronic trip unit ETU15B to ETU76B B 3WL9 111-0AT31-0AA0 1 unit on req.
For testing the overcurrent tripping functions
Capacitor store unit
3WL9 111-0AH02-0AA0
Capacitor store unit Rated control supply voltage/
for shunt release rated operating voltage
Storage time 5 min. AC 50/60 Hz V DC V
Rated control supply voltage must correspond 110-127 110-115 B 3WL9 111-0BA13-0AA0 1 ST 0,500
with rated control supply voltage of shunt release.
220-240 220-250 B 3WL9 111-0BA14-0AA0 1 ST 0,500
EMC Filter
N S E 0 _ 0 0 9 9 5 a EMC Filter Delivery as of July 2004 X 3WL9 111-0AK32-0AA0 1 ST on req.
3WL9 111-0AH07-0AA0

N S E 0 _ 0 0 9 9 6 a

3WL9 111-0AH12-0AA0

N S E 0 0 0 9 9 7 a
3WL9 111-0AJ0.-0AA0

N S E 0 _ 0 0 9 9 8 a

3WL9 111-0AJ06-0AA0

NSE00985
3WL9 111-0BA72-0AA0

1) Not possible with motor shutdown switch.


2) Not possible with electrical ON button.
3) Only in conjunction with motorized operating mechanism.
4) Not possible with communication connection option, order code "F02".
5) X7 manual connector required for circuit-breakers or guide frames. If this is
not already available, please order additionally (see Pages 5/44 and 5/49).

5/48 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
Auxiliary conductor connections
Male connector for circuit-breakers B 3WL9 111-0AB01-0AA0 1 unit on req.
NSE00978

Prolongation for male connector 1000 V version B 3WL9 111-0AB02-0AA0 1 unit on req.
(male connector must be ordered separately)
3WL9 111-0AB01-0AA0 Male connector and prolongation for 1000 V B 3WL9 111-0AB10-0AA0 1 unit on req.
Manual connector for circuit-breaker Screw-type terminals B 3WL9 111-0AB03-0AA0 1 unit on req.
or guide frame (SIGUT)
Screwless type terminals B 3WL9 111-0AB04-0AA0 1 unit on req.
(tension spring)
Coding kit for fixed mounting (X5 to X8) B 3WL9 111-0AB07-0AA0 1 unit on req.
N S E 0 _ 0 1 2 6 8

Sliding contact module for guide frame B 3WL9 111-0AB08-0AA0 1 unit on req.
Blanking block for circuit-breakers B 3WL9 111-0AB12-0AA0 1 unit on req.
Auxiliary releases
3WL9 111-0AB03-0AA0 Closing solenoid/shunt release
DC 24 V 100 % ON-time B 3WL9 111-0AD01-0AA0 1 unit on req.
DC 30 V B 3WL9 111-0AD02-0AA0 1 unit on req.
DC 48 V
DC 60 V
B
B
3WL9 111-0AD03-0AA0
3WL9 111-0AD04-0AA0
1 unit
1 unit
on req.
on req. 5
N S E 0 _ 0 1 2 6 9

DC 110 V/AC 110 V B 3WL9 111-0AD05-0AA0 1 unit on req.


DC 220 V/AC 230 V B 3WL9 111-0AD06-0AA0 1 unit on req.

DC 24 V 5 % ON-time B 3WL9 111-0AD11-0AA0 1 unit on req.


3WL9 111-0AB04-0AA0 DC 48 V B 3WL9 111-0AD12-0AA0 1 unit on req.
DC 110-125 V/AC 110-127 V B 3WL9 111-0AD13-0AA0 1 unit on req.
DC 220-250 V/AC 208-240 V B 3WL9 111-0AD14-0AA0 1 unit on req.
Undervoltage releases
instantaneous
DC 24 V B 3WL9 111-0AE01-0AA0 1 unit on req.
DC 30 V B 3WL9 111-0AE02-0AA0 1 unit on req.
DC 48 V B 3WL9 111-0AE03-0AA0 1 unit on req.
DC 110-125 V/AC 110-127 V B 3WL9 111-0AE04-0AA0 1 unit on req.
DC 220-250 V/AC 208-240 V B 3WL9 111-0AE05-0AA0 1 unit on req.
AC 380-415 V B 3WL9 111-0AE06-0AA0 1 unit on req.
NSE00974

delayed
DC 48 V B 3WL9 111-0AE11-0AA0 1 unit on req.
DC 110-125 V/AC 110-127 V B 3WL9 111-0AE12-0AA0 1 unit on req.
3WL9 111-0AB07-0AA0 DC 220-250 V/AC 208-240 V B 3WL9 111-0AE13-0AA0 1 unit on req.
AC 380-415 V B 3WL9 111-0AE14-0AA0 1 unit on req.
Operating mechanism
Motorized operating mechanism
DC 24-30 V B 3WL9 111-0AF01-0AA0 1 unit on req.
DC 48-60 V B 3WL9 111-0AF02-0AA0 1 unit on req.
DC 110-125 V/AC 110-127 V B 3WL9 111-0AF03-0AA0 1 unit on req.
a
7 7 DC 220-250 V/AC 208-240 V B 3WL9 111-0AF04-0AA0 1 unit on req.
0 9
_ 0
S E 0 Auxiliary contacts
N

3WL9 111-0AB08-0AA0 Auxiliary contact block 2 NO + 2 NC B 3WL9 111-0AG01-0AA0 1 unit on req.


2 NO B 3WL9 111-0AG02-0AA0 1 unit on req.
1 NO + 1 NC B 3WL9 111-0AG03-0AA0 1 unit on req.

3WL9 111-0AD06-0AA0 NSE01001 NSE01002


NSE01003

3WL9 111-0AE0.-0AA0 3WL9 111-0AE1.-0AA0 3WL9 111-0AF0.-0AA0 3WL9 111-0AG03-0AA0

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/49


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
Door sealing frame, hood, shutter
Door sealing frame B 3WL9 111-0AP01-0AA0 1 unit on req.
Protective cover, IP55 B 3WL9 111-0AP02-0AA0 1 unit on req.
cannot be used in conjunction with door sealing frames,
cover removable and can be opened on both sides
Shutters
3-pole Size I B 3WL9 111-0AP04-0AA0 1 unit on req.
Size II B 3WL9 111-0AP06-0AA0 1 unit on req.
Size III B 3WL9 111-0AP07-0AA0 1 unit on req.
NSE01020

3WL9 111-0AP01-0AA0 4-pole Size I B 3WL9 111-0AP08-0AA0 1 unit on req.


Size II B 3WL9 111-0AP11-0AA0 1 unit on req.
Size III B 3WL9 111-0AP12-0AA0 1 unit on req.
Arc chute
Arc chute
690 V Size I B 3WL9 111-0AS01-0AA0 1 unit on req.

5 Size II
Size III
B
B
3WL9 111-0AS02-0AA0
3WL9 111-0AS03-0AA0
1 unit
1 unit
on req.
on req.

NSE0_01028a 1000 V Size II B 3WL9 111-0AS05-0AA0 1 unit on req.


Size III B 3WL9 111-0AS06-0AA0 1 unit on req.
3WL9 111-0AP02-0AA0
Arc chute cover1)
Parts kit for guide frame
3-pole Size I B 3WL9 111-0AS32-0AA0 1 unit on req.
Size II B 3WL9 111-0AS36-0AA0 1 unit on req.
Size III B 3WL9 111-0AS38-0AA0 1 unit on req.

4-pole Size I B 3WL9 111-0AS42-0AA0 1 unit on req.


Size II B 3WL9 111-0AS44-0AA0 1 unit on req.
Size III B 3WL9 111-0AS46-0AA0 1 unit on req.
Withdrawable part coding
3WL9 111-0AP0.-0AA0
Withdrawable part coding B 3WL9 111-0AR12-0AA0 1 unit on req.
by customer, for 36 coding variants
Ground-fault protection
Ground-fault protection between guide frame and with-
drawable circuit-breaker Size I, II B 3WL9 111-0BA01-0AA0 1 unit on req.
For 30 kA switching capacity2) Size III B 3WL9 111-0BA02-0AA0 1 unit on req.
Contact module for guide frame
Contact module for withdrawable circuit-breaker
3-pole Size I B 3WL9 111-0BA05-0AA0 1 unit on req.
NSE01007

Size II B 3WL9 111-0BA06-0AA0 1 unit on req.


Size III B 3WL9 111-0BA07-0AA0 1 unit on req.
3WL9 111-0AS0.-0AA0

4-pole Size I B 3WL9 111-0BA08-0AA0 1 unit on req.


Size II B 3WL9 111-0BA04-0AA0 1 unit on req.
Size III B 3WL9 111-0BA10-0AA0 1 unit on req.
Support bracket
Support bracket B 3WL9 111-0BB50-0AA0 1 set 4.800
for mounting fixed-mounted circuit-breakers
NSE01008
on vertical plane,
3WL9 111-0AS3.-0AA0 only for sizes I and II (1 set = 2 units)
NSE-01022

NSE01009 NSE0 01018a NSE01019

3WL9 111-0AR12-0AA0 3WL9 111-0BA02-0AA0 3WL9 111-0BA07-0AA0 3WL9 111-0BB50-0AA0

1) Not possible with 1000 V version, DC version, fixed-mounted version 2) 60 kA switching capacity is achieved with 2 modules each.

5/50 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
CubicleBUS modules1)
Digital output module with rotary coding switch, optical coupler outputs B 3WL9 111-0AT25-0AA0 1 unit on req.
Digital output module with rotary coding switch, relay outputs B 3WL9 111-0AT26-0AA0 1 unit on req.
Digital output module, configurable, optocoupler outputs B 3WL9 111-0AT30-0AA0 1 unit on req.
Digital output module, configurable, relay outputs B 3WL9 111-0AT20-0AA0 1 unit 0.400
NSE-01023 Digital input module B 3WL9 111-0AT27-0AA0 1 unit on req.
3WL9 111-0AT23-0AA0 Analog output module B 3WL9 111-0AT23-0AA0 1 unit on req.
Zone Selective Interlocking module B 3WL9 111-0AT21-0AA0 1 unit on req.
Parameterization systems
Breaker Data Calibration, operation, monitoring, and diagnosis of B 3WL9 111-0AT28-0AA0 1 unit on req.
Adapter SENTRON circuit-breakers via local interface; Breaker
(BDA) Data Adapter, connecting cable to SENTRON circuit-
breaker and to programming device (e.g. notebook); can
be run with Internet Explorer with JAVA2 VM 1.4.0-01
BDA Plus Same as BDA, but with additional Ethernet interface for B 3WL9 111-0AT33-0AA0 1 unit on req.
connection to Ethernet/Intranet/Internet

5
Connecting cable Connecting cable for connection of BDA and BDA Plus to C 3WL9 111-0BC20-0AA0 1 unit on req.
for BDA and LCD ETU trip unit of circuit-breaker SENTRON VL,
BDA Plus length 1 m
Connecting cable Connecting cable for connection of BDA Plus to terminal B 3WL9 111-0BC21-0AA0 1 unit on req.
for BDA Plus X8 of circuit-breaker SENTRON WL.
Required if neither COM 15 nor other external CubicleBUS
NSE-01024 modules are available, length 2 m.
3WL6 111-0AB01 Parameterization Calibration, operation, monitoring, and diagnosis of A 3ZS2 311-0CC10-0YA0 1 unit on req.
software SENTRON circuit-breakers via PROFIBUS DP; runs under
Switch ES Power Windows 95, Windows 98, Windows NT, Windows 2000
1 2 3 4 5 6 7 8 9
and Windows XP Professional, requires additional
PROFIBUS card e.g. CP5613
Device
Accessories for communication
CubicleBus
PROFIBUS DP
Factory-connected 0.2 m long, for connection to SENTRON WL with COM15 B 3WL9 111-0BC04-0AA0 1 unit on req.
cables for 1 m long, for connection to SENTRON WL with COM15 B 3WL9 111-0BC02-0AA0 1 unit on req.
CubicleBUS
modules 2 m long, for connection to SENTRON WL with COM15 B 3WL9 111-0BC03-0AA0 1 unit on req.
NSE-01025

3WL9 111-0AT15-0AA0 2 m long, for connection to SENTRON WL without COM15 B 3WL9 111-0BC05-0AA0 1 unit on req.
SENTRON manual Detailed description of the communication functions for
for communica- SENTRON circuit-breakers. Installation, connection, com-
tion solutions missioning and description of Switch ES Power and BDA.
German X E20001-A201-P307 1 unit on req.
English X E20001-A201-P307-X-7600 1 unit on req.
S45 Free download under:
S43
www.siemens.de/energieverteilung
Voltage
S42 transformer, 3-pole, 230 V/100 V, class 0.5 B 3WL9 111-0BB70-0AA0 1 unit on req.
for SENTRON WL
S40
with measurement 380–440 V/100 V, class 0.5 B 3WL9 111-0BB63-0AA0 1 unit on req.
function and mea- 500–690 V/100 V, class 0.5 B 3WL9 111-0BB64-0AA0 1 unit on req.
S44
surement function
NSE01026
Plus
S41
Retrofitting and spare parts
3WL9 111-0AT16-0AA0
PROFIBUS Retrofit kit for PROFIBUS communication including B 3WL9 111-0AT12-0AA0 1 unit on req.
retrofit kit COM15, BSS and set of cables for all
SENTRON WL circuit-breakers with ETU45B, ETU55B
and ETU76B trip units
COM15 PROFIBUS module B 3WL9 111-0AT15-0AA0 1 unit on req.
Breaker status sensor (BSS) B 3WL9 111-0AT16-0AA0 1 unit on req.
Measurement function, without voltage transformer B 3WL9 111-0AT02-0AA0 1 unit on req.
Measurement function Plus, without voltage transformer B 3WL9 111-0AT03-0AA0 1 unit on req.
All communication components, CubicleBUS modules and measurement functions are
available for the ETU45B, ETU55B and ETU76B trip units.
1) Each CubicleBUS module is supplied with a 0.2 m factory-fitted cable to
connect the modules with each other. A longer factory-fitted cable is
required for connection to the circuit-breaker.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/51


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
Main circuit connections, fixed mounting
3WL9 111-0AL06-0AA0 Specified for each connection
Front-accessible
main circuit connections, Size I, up to 1000 A B 3WL9 111-0AL01-0AA0 1 unit on req.
single hole at top
Size I, 1250 A ... 1600 A B 3WL9 111-0AL02-0AA0 1 unit on req.
Size II, up to 2000 A B 3WL9 111-0AL03-0AA0 1 unit on req.
Size II, up to 2500 A B 3WL9 111-0AL04-0AA0 1 unit on req.
NSE-01010
Size II, up to 3200 A B 3WL9 111-0AL05-0AA0 1 unit on req.
3WL9 111-0AL56-0AA0 Size III, up to 4000 A B 3WL9 111-0AL06-0AA0 1 unit on req.
Front-accessible Size I, up to 1000 A B 3WL9 111-0AL51-0AA0 1 unit on req.
main circuit connections, Size I, 1250 A ... 1600 A B 3WL9 111-0AL52-0AA0 1 unit on req.
single hole at bottom
Size II, up to 2000 A B 3WL9 111-0AL53-0AA0 1 unit on req.
Size II, up to 2500 A B 3WL9 111-0AL54-0AA0 1 unit on req.
Size II, up to 3200 A B 3WL9 111-0AL55-0AA0 1 unit on req.
3WL9 111-0AL14-0AA0 Size III, up to 4000 A B 3WL9 111-0AL56-0AA0 1 unit on req.

5 Front-
accessible
main circuit connections
Size I, up to 1000 A
Size I, 1250 A ... 1600 A
B
B
3WL9 111-0AL07-0AA0
3WL9 111-0AL08-0AA0
1 unit
1 unit
on req.
on req.
to DIN 43673, Size II, up to 2000 A B 3WL9 111-0AL11-0AA0 1 unit on req.
double hole at top Size II, up to 2500 A B 3WL9 111-0AL12-0AA0 1 unit on req.
Size II, up to 3200 A B 3WL9 111-0AL13-0AA0 1 unit on req.
NSE-01011
Size III, up to 4000 A B 3WL9 111-0AL14-0AA0 1 unit on req.
Front- Size I, up to 1000 A B 3WL9 111-0AL57-0AA0 1 unit on req.
3WL9 111-0AL64-0AA0 accessible Size I, 1250 A ... 1600 A B 3WL9 111-0AL58-0AA0 1 unit on req.
main circuit connections
to DIN 43673, Size II, up to 2000 A B 3WL9 111-0AL61-0AA0 1 unit on req.
double hole at bottom Size II, up to 2500 A B 3WL9 111-0AL62-0AA0 1 unit on req.
Size II, up to 3200 A B 3WL9 111-0AL63-0AA0 1 unit on req.
Size III, up to 4000 A B 3WL9 111-0AL64-0AA0 1 unit on req.
Rear Size I1), up to 1600 A B 3WL9 111-0AM01-0AA0 1 unit on req.
vertical Size II2), up to 3200 A B 3WL9 111-0AM02-0AA0 1 unit on req.
main circuit connections
Size III, up to 6300 A B 3WL9 111-0AM03-0AA0 1 unit on req.

NSE-01012

3WL9 111-0AM03-0AA0

1) In the case of vertical connection size I, up to 1000 A 1 vertical connection


3WL9 111–0AM01-0AA0 is required,
up to 1600 A 2 vertical connections
3WL9 111-0AM01-0AA0 are required.
2) In the case of vertical connection size II, up to 2500 A 1 vertical connection
3WL9 111–0AM02–0AA0 is required,
up to 3200 A 2 vertical connections
3WL9 111-0AM02-0AA0 are required.

5/52 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
Main circuit connections, withdrawable version
NSE-01013 Specified for each connection
3WL9 111-0AN06-0AA0 Front-accessible
main circuit connections, Size I, up to 1000 A B 3WL9 111-0AN01-0AA0 1 unit on req.
single hole top or bottom
Size I, 1250 A ... 1600 A B 3WL9 111-0AN02-0AA0 1 unit on req.
Size II, up to 2000 A B 3WL9 111-0AN03-0AA0 1 unit on req.
Size II, up to 2500 A B 3WL9 111-0AN04-0AA0 1 unit on req.
Size II, up to 3200 A B 3WL9 111-0AN05-0AA0 1 unit on req.
Size III, up to 4000 A B 3WL9 111-0AN06-0AA0 1 unit on req.
Front- Size I, up to 1000 A B 3WL9 111-0AN07-0AA0 1 unit on req.
NSE-01014 accessible Size I, 1250 A ... 1600 A B 3WL9 111-0AN08-0AA0 1 unit on req.
main circuit connections
3WL9 111-0AN14-0AA0 to DIN 43673, Size II, up to 2000 A B 3WL9 111-0AN11-0AA0 1 unit on req.
double hole at top or bottom Size II, up to 2500 A B 3WL9 111-0AN12-0AA0 1 unit on req.
Size II, up to 3200 A B 3WL9 111-0AN13-0AA0 1 unit on req.
Size III, up to 4000 A B 3WL9 111-0AN14-0AA0 1 unit on req.
Support
for front and DIN connecting bars
3-pole for 3 bars Size I B 3WL9 111-0AN41-0AA0 1 unit on req.
5
Size II B 3WL9 111-0AN42-0AA0 1 unit on req.
Size III B 3WL9 111-0AN43-0AA0 1 unit on req.

4-pole for 4 bars Size I B 3WL9 111-0AN44-0AA0 1 unit on req.


Size II B 3WL9 111-0AN45-0AA0 1 unit on req.
Size III B 3WL9 111-0AN46-0AA0 1 unit on req.
Rear Size I, up to 1000 A B 3WL9 111-0AN15-0AA0 1 unit on req.
vertical Size I, 1250 A ... 1600 A B 3WL9 111-0AN16-0AA0 1 unit on req.
main circuit connections
Size II, up to 2000 A B 3WL9 111-0AN17-0AA0 1 unit on req.
NSE-01017
Size II, up to 2500 A B 3WL9 111-0AN18-0AA0 1 unit on req.
3WL9 111-0AN41-0AA0 Size II, up to 3200 A B 3WL9 111-0AN21-0AA0 1 unit on req.
Size III, up to 5000 A B 3WL9 111-0AN22-0AA0 1 unit on req.
Size III, up to 6300 A (3 busbar connec- B 3WL9 111-0AN23-0AA0 1 unit on req.
tion pieces for 3-pole circuit-breakers)
Size III, up to 6300 A (4 busbar connec- B 3WL9 111-0AN20-0AA0 1 unit on req.
NSE-01015 tion pieces for 4-pole circuit-breakers)
3WL9 111-0AN23-0AA0 Size III, up to 6300 A (4 busbar connec- B 3WL9 111-0AN10-0AA0 1 unit on req.
tion pieces for 4-pole circuit-breakers)
Rear Size I, up to 1000 A B 3WL9 111-0AN32-0AA0 1 unit on req.
horizontal Size I, 1250 A ... 1600 A B 3WL9 111-0AN33-0AA0 1 unit on req.
circuit connections
Size II, up to 2000 A B 3WL9 111-0AN34-0AA0 1 unit on req.
Size II, up to 2500 A B 3WL9 111-0AN35-0AA0 1 unit on req.
Size II, up to 3200 A B 3WL9 111-0AN36-0AA0 1 unit on req.
Size III, up to 5000 A B 3WL9 111-0AN37-0AA0 1 unit on req.
Connecting flange Size I, up to 1000 A B 3WL9 111-0AN24-0AA0 1 unit on req.
Size I, 1250 A ... 1600 A B 3WL9 111-0AN25-0AA0 1 unit on req.
Size II, up to 2000 A B 3WL9 111-0AN26-0AA0 1 unit on req.
Size II, up to 2500 A B 3WL9 111-0AN27-0AA0 1 unit on req.
NSE-01016

Size II, up to 3200 A B 3WL9 111-0AN28-0AA0 1 unit on req.


Size III, up to 4000 A B 3WL9 111-0AN31-0AA0 1 unit on req.
When using front-accessible main circuit connections
3WL9 111-0AN24-0AA0 (withdrawable circuit-breakers) supports are required.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/53


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
Conversion set
For converting fixed-mounted circuit-breakers to withdrawable
circuit-breakers
Guide frames and sliding contact modules must be ordered separately.
3-pole Size I B 3WL9 111-0BC11-0AA0 1 unit on req.
Size II B 3WL9 111-0BC12-0AA0 1 unit on req.
Size III B 3WL9 111-0BC13-0AA0 1 unit on req.
4-pole Size I B 3WL9 111-0BC14-0AA0 1 unit on req.
Size II B 3WL9 111-0BC15-0AA0 1 unit on req.
Size III B 3WL9 111-0BC16-0AA0 1 unit on req.
Auxiliary contacts
Specified for each connection (depending on the number of poles on the circuit-breaker, order 3 or 4 units)
For basic circuit-breaker Size In max Switching capacity Number
type class of poles
3WL11 06–@..@.–.... I up to 1000 A N/S 3/4 B 3WL9 111-0AM50-0AA0 1 unit on req.
... 2 3
10 3 4

5 3WL11 12–@..@.–....
... 2 3
I up to 1600 A N/S 3/4 B 3WL9 111-0AM51-0AA0 1 unit on req.

16 3 4
3WL12 08–@..@.–.... II up to 2000 A N/S 3 B 3WL9 111-0AM52-0AA0 1 unit on req.
... 2 3
20 3 3
NSE-01021
3WL12 25–@..@.–.... II up to 2500 A N/S 3 B 3WL9 111-0AM54-0AA0 1 unit on req.
3WL9 111-0AM50-0AA0 2 3
3 3
3WL12 32–@..@.–.... II up to 3200 A N/S 3 B 3WL9 111-0AM56-0AA0 1 unit on req.
2 3
3 3
3WL12 08–@..@.–.... II up to 2000 A N/S/H 4 B 3WL9 111-0AM53-0AA0 1 unit on req.
... 2 4
20 3 4
3WL12 25–@..@.–.... II up to 2500 A N/S/H 4 B 3WL9 111-0AM55-0AA0 1 unit on req.
2 4
3 4
3WL12 32–@..@.–.... II up to 3200 A N/S/H 4 B 3WL9 111-0AM57-0AA0 1 unit on req.
2 4
3 4
3WL12 08–@..@.–.... II up to 2000 A H 3/4 B 3WL9 111-0AM53-0AA0 1 unit on req.
... 4 3
20 4 4
3WL12 25–@..@.–.... II up to 2500 A H 3/4 B 3WL9 111-0AM55-0AA0 1 unit on req.
4 3
4 4
3WL12 32–@..@.–.... II up to 3200 A H 3/4 B 3WL9 111-0AM57-0AA0 1 unit on req.
4 3
4 4
3WL13 40–@..@.–.... III up to 5000 A H 3/4 B 3WL9 111-0AM58-0AA0 1 unit on req.
... 4 3
50 4 4
3WL13 63–@..@.–.... III up to 6300 A H 3/4 B 3WL9 111-0AM60-0AA0 1 unit on req.
4 3
4 4

5/54 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Accessories/spare parts

Circuit diagram in as-supplied state Version Size DT Order No. PS* Weight
per PU
approx.
kg
Withdrawable short-circuit, ground, and bridging units
Top and 3-pole

NSE0_01118
bottom up to 1600 A I C 3WL9 111-0BD01-0AA0 1 unit on req.
parts of system
are up to 3200 A II C 3WL9 111-0BD03-0AA0 1 unit on req.
L1 L2 L3
short-circuited up to 6300 A III C 3WL9 111-0BD05-0AA0 1 unit on req.
and grounded
NSE0_01113
4-pole
NSE0_01119

up to 1600 A I C 3WL9 111-0BD02-0AA0 1 unit on req.


(as-supplied state)
up to 3200 A II C 3WL9 111-0BD04-0AA0 1 unit on req.
N L1 L2 L3 up to 6300 A III C 3WL9 111-0BD06-0AA0 1 unit on req.

Conversion for the following applications is possible

5
NSE0_01118

L1 L2 L3 L1 L2 L3

NSE0_01116
NSE0_01113 NSE0_01112
NSE0_01119

N L1 L2 L3 N L1 L2 L3

NSE0_01117
Top and bottom part of system are short-circuited and grounded Top and bottom part of system are short-circuited and grounded,
(as-supplied state) incoming supply from below

NSE0_01120
N S E 0 _ 0 1 1 2 2 a

L1 L2 L3

NSE0_01115 NSE0_01114
NSE0_01121
N S E 0 _ 0 1 1 2 3 a

N L1 L2 L3

Withdrawable bridging unit, incoming and outgoing side are permanently Bottom part of system is short-circuited and grounded,
connected to each other incoming supply from above

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/55


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids

■ Overview
Structure of the Order No. 3WL1 ÔÔÒ – ÖéâÕÓ– ÓáÜÔ An important prerequisite for computer-
based order processing is that order
Example numbers must be structured according
5th position: Size Size II Ô to standardized criteria.
They are used as an unambiguous
6th and 7th Max. rated circuit- Iu and In max = 2000 A ÔÒ means of communication for various
positions: breaker current In max purposes:
• Offer processing
8th position: Switching capacity High switching capacity Ö Selection and configuration
class "H": 100 kA • Order processing
Ordering
9th position: Electronic trip units ETU76 with pixel graphics é Order confirmation
display ... Handling warehouse products
Order processing at the
10th position: Electronic trip unit ... with ground-fault protection â supply bases
supplement Delivery and shipment
• Reporting and
planning
11th position: Number of poles 3-pole Õ
• Service and warranty
12th position: Installation type Fixed-mounted design, main terminals on rear, Ó The standardized structure ensures that
vertical only one Order No. has to be adminis-
tered for one device.
Ó
5
13th position: Operating mechanism Manual operating mechanism This saves time and effort during
with mechanical closing planning, project engineering, ordering
and stock keeping, and consequently
14th position: 1st auxiliary switch Shunt release á above all it saves costs.
AC 50/60 Hz 110 V The example opposite explains the
various positions within an
15th position: 2nd auxiliary switch Without 2nd auxiliary release Ü order number.

16th position: Auxiliary switches 2 NO + 2 NC Ô

Accessories: with first order (components are already mounted)


Example 3WL1 ÔÓØ – ÖåâÕÓ– Ó á Ü Õ– Õ áÒ Ô Additional accessory components can
be ordered ready-mounted.
These supplements are identified
–Z with order code Communication connection Õ áÒ Ô by "–Z".
"Standard" + Breaker Status Sensor (BSS)
+ communication module COM15 for con- Even with additional components, one
nection to PROFIBUS DP Order No. is sufficient.

Accessories: for retrofitting (components for subsequent fitting)


Example Additional accessories which are not
intended to be ready-mounted in the
3WL9 ÓÓÓ – ÒÁ ÜÔÓ – Ò Ü Ü Ò factory, such as spare parts for storage,
Protective cover for mechanical ON/OFF can also be ordered separately from
without lock the circuit-breaker.
Accessories for retrofitting are identified
by the item No. 3WL9.

Documentation
Operator's Guide German/English Order No. 3ZX18 12–0WL00–0AN0 Delivery time C
complete set French/Italian Order No. 3ZX18 12–0WL00–0AJ0 on request
Spanish/Portuguese Order No. 3ZX18 12–0WL00–0AL0 on request
Manual German Order No. E20001–A201–P307
Communication English Order No. E20001–A201–P307–X–7600

Free download of the documentation from


www.siemens.de/energieverteilung

■ Further information
Up-to-date information on the Internet at:
www.siemens.de/sentron

5/56 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids

■ Characteristics 10000 NSE00600a

t [s]
Every electronic trip unit type and every setting has its own char- 1000
acteristic. Only a selection is shown in the following. The charac-
teristics show the largest and smallest setting range of 100
SENTRON WL circuit-breakers with 1000 A rated current at
440 V rated voltage with various trip units. In order to obtain a
complete tripping characteristic, the relevant parts of the char- 10
acteristics have to be combined. The characteristics show the
behavior of the electronic trip unit when it is activated by a cur- 1
rent that is already flowing before the tripping operation. If the
overcurrent tripping occurs immediately after switch on and the .1
electronic trip unit is therefore not yet enabled, the opening time
is extended, depending on the level of the overcurrent by up to
15 ms. In order to determine the total break-times of the circuit- .01
100 1000 10000 100000
breakers, approximately 15 ms must be added to the opening
I [A]
times shown for the arcing time. Refer to the following table for
tolerances. SENTRON WL circuit-breaker with In= 1000 A and electronic
trip unit ETU27B (ground-fault protection G)
The characteristics shown apply to ambient temperatures at the
circuit-breaker between –5 and +55 °C. The trip unit can be op-
erated at ambient temperatures of –20 to +70 °C. An extended
Inverse-time delayed overload range L
tolerance band can apply at these temperatures.
10000 NSE00598a
I2t = constant
Overlapping of the inverse-time delayed overload range L 5
of I2t and I4t
t [s]

1000 Inverse-time delayed overload range L


I4t = constant
100 Short-time delayed short-circuit range S
Instantaneous short-circuit range I
10
Ground-fault protection range G
1
Tolerances for the operating currents
.1 L: tripping operations between 1.05 and 1.2 x IR
S: –0 %, +20 %
I: –0 %, +20 %
.01 G: –0 %, +20 %
100 1000 10000 100000
I [A] Tolerances for the tripping times
L: –20 %, +0 %
SENTRON WL circuit-breaker with In= 1000 A and electronic S: –0 %, +60 ms
trip unit ETU15B I: <50 ms
G: –0 ms, +60 ms
10000 NSE00599b
t [s]

1000

100

10

.1

.01
100 1000 10000 100000
I [A]

SENTRON WL circuit-breaker with In= 1000 A and electronic


trip unit ETU25B or ETU27B (tripping characteristic "ground-fault protec-
tion" G for ETU27B see below)

Siemens LV 30 · 2004 5/57


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids
Every electronic trip unit type and every setting has its own char- 10000 NSE00603a
acteristic. Only a selection is shown in the following. The charac-

t [s]
teristics each show the largest and smallest setting range of 1000
SENTRON WL circuit-breakers with 1000 A rated current at
440 V rated voltage with various trip units.
100
In order to obtain a complete tripping characteristic the relevant
parts of the characteristics have to be combined. 10
The characteristics show the behavior of the electronic trip unit
when it is activated by a current that is already flowing before the 1
tripping operation. If the overcurrent tripping occurs immediately
after switch on and the electronic trip unit is therefore not yet en-
.1
abled, the opening time is extended, depending on the level of
the overcurrent by up to 15 ms. In order to determine the total
break-times of the circuit-breakers, approximately 15 ms must .01
be added to the opening times shown for the arcing time. Refer 100 1000 10000 100000
to the following table for tolerances. I [A]

The characteristics shown apply to ambient temperatures at the SENTRON WL circuit-breaker with In = 1000 A and electronic
circuit-breaker between –5 and +55 °C. The trip unit can be op- trip unit ETU45B or ETU55B
erated at ambient temperatures of –20 to +70 °C. An extended Ground-fault protection range G
tolerance band can apply at these temperatures.

5
10000 NSE00602b
10000 NSE00601a
t [s]

1000
t [s]

1000

100
100

10
10

1
1

.1
.1

.01
.01 100 1000 10000 100000
100 1000 10000 100000
I [A]
I [A]
SENTRON WL circuit-breaker with In = 1000 A and electronic
SENTRON WL circuit-breaker with In = 1000 A and electronic trip unit ETU45B or ETU55B
trip unit ETU45B or ETU55B Short-time delayed short-circuit range S
Inverse-time delayed overload range L

10000 NSE00604a
t [s]

1000 Inverse-time delayed overload range L


I2t = constant

100
Overlapping of the inverse-time delayed overload range L
of I2t and I4t

10
Inverse-time delayed overload range L
I4t = constant

1
Short-time delayed short-circuit range S
Instantaneous short-circuit range I
.1 Ground-fault protection range G

.01
100 1000 10000 100000 Further characteristics are shown in the manual and the plan-
I [A] ning and configuring tool SIMARIS deSign, or ask your Siemens
contact person.
SENTRON WL circuit-breaker with In = 1000 A and electronic
trip unit ETU45B or ETU55B Tolerances for the operating currents
Instantaneous short-circuit range I L: tripping operations between 1.05 and 1.2 × IR
S: –0 %, +20 %
I: –0 %, +20 %
G: –0 %, +20 %
Tolerances for the tripping times
L: –20 %, +0 %
S: –0 %, +60 ms
I: <50 ms
G: –0 ms, +60 ms

5/58 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids

■ Dimension drawings
Voltage transformer for SENTRON WL External transformer for neutral conductors (without copper
with measurement function and measurement function Plus connection pieces)
Size I, 3WL9 111-0AA21-0AA0
2 7 7
6 0
1 6
8
R 1 3 ,1
1 2 5

8 ,9

N S E 0 _ 0 1 3 7 5
9 6 ,8
2 2
8 1
N S E 0 _ 0 1 1 0 3 a R 2 2
9 9

4 0
F o r m o u n tin g o n
3 5 m m s ta n d a rd 1 8 5 1
m o u n t in g r a il 3 6
7 0
Current transformers for 8 3
overload protection in the neutral conductor Size II, 3WL9 111-0AA22-0AA0
External transformer for neutral conductors with copper
connection pieces
R 2 7

1 1 5
1 3 1
Size I, 3WL9 111-0AA31-0AA0

5 4

N S E 0 _ 0 1 3 7 6
1 5 4 1

6 5 ,5 5
Ø 1 3 ,5

8 8 5 1
4 4

9 5
1 1 3 3
1 7 0
1 3 0
6 8
5 1

Size III, 3WL9 111-0AA23-0AA0

1 6 1
N S E 0 _ 0 0 6 0 6 a

R 1 5
5 5 9 7

1 0 7
1 2 3

N S E 0 _ 0 1 3 7 7
4 5

8 3
3 1

Size II, 3WL9 111-0AA32-0AA0


3

1 6 0 5 1
3 0 3 0 3 × 1 0
5 0 ,5 1 8 4
Ø 1 3 ,5
Door cutout for operator’s panel
Door cutout with edge protection
4 4

2 9 5
Cutout after mounting of
1 3 0

1 7 0
6 8
5 1

edge protection
N S E 0 _ 0 0 6 0 7 a

3 4 0

9 0 1 3 1
1 1 3
2 4 0

Size III, 3WL9 111-0AA33-0AA0

3 0 3 0 3 0 3 × 1 0 5 2
Ø 1 3 ,5
N S E 0 _ 0 0 1 6 4 b

Door cutout for operator’s panel when using


4 4

door sealing frame


1 3 0
6 8

1 7 0
5 1

Option with/without door sealing


3 1 4
3 0 0
N S E 0 _ 0 0 6 0 8 a

1 2 0 4 0
1 6 0 1 2 3 Ø 5 ,5 3 )
1 8 4 N S E 0 _ 0 0 6 1 0 c

■ Dimensions for option with door interlocking R 5 R 5


1 8 5

1) Mounting surface
1 4 0

2) Center SENTRON WL operator’s panel 2 )


Ø 5 ,5
3) 8 borings for mounting of door sealing frames
3 5 0

4) 3 borings for mounting of door interlockings


1 4 0

1 8 0
1 7 5

4 0 1 2 0

Ø 5 ,5
6 5

1 2
1 1 ,5

1 ) 2 1 4 )
4 0

Siemens LV 30 · 2004 5/59


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids
Door cut-out for operator panel using the protection cover IP55
Protection cover IP55

N S E 0 _ 0 1 0 3 0 a
4 x R 5

°
4 x 5 ,5 8 0
3 4 0

2 9 5
1 1 6

4 4 4
7 7
N S E 0 _ 0 1 0 2 9 b

7 0

C ir c u it- b r e a k e r m o u n tin g le v e l

3 5 2 C ir c u it- b r e a k e r
m o u n tin g le v e l
3 3 0 1 4 9

1 7
Safety distances to earthed parts Safety distances to live parts

5 Nominal rated voltage


V/AC
above
auxiliary connector
mm
lateral
(each)
mm
behind

mm
Nominal rated voltage
V/AC
above
auxiliary connector
mm
lateral
(each)
mm
behind

mm
Size I, fixed-mounted design Size I, fixed-mounted design
440 751) 0 0 440 150 20 20
690 751) 0 0 690 300 50 125
Size I, withdrawable design, Size I, withdrawable design,
without arc chute cover without arc chute cover
440 501) 0 0 440 150 20 14
690 501) 0 0 690 300 50 14
Size I, withdrawable design, Size I, withdrawable design,
with arc chute cover with arc chute cover
440 0 02) 0 440 14 100 14
690 0 02) 0 690 14 100 14
Size II, fixed-mounted design Size II, fixed-mounted design
440 751) 0 0 440 250 50 20
690 751) 0 0 690 600 100 140
1000 180 0 0 1000 430 100 125
Size II, withdrawable design, Size II, withdrawable design,
without arc chute cover without arc chute cover
440 501) 0 0 440 250 50 14
690 501) 0 0 690 600 100 30
1000 100 0 0 1000 350 100 14
Size II, withdrawable design, Size II, withdrawable design,
with arc chute cover with arc chute cover
440 0 02) 0 440 14 50 14
690 0 02) 0 690 14 225 14
Size III, fixed-mounted design Size III, fixed-mounted design
440 751) 0 0 440 75 20 20
690 751) 0 0 690 500 100 125
1000 180 0 0 1000 430 100 125
Size III, withdrawable design, Size III, withdrawable design,
without arc chute cover without arc chute cover
440 501) 0 0 440 50 20 14
690 501) 0 0 690 500 100 14
1000 100 0 0 1000 350 100 14
Size III, withdrawable design, Size III, withdrawable design,
with arc chute cover with arc chute cover
440 0 02) 0 440 14 50 14
690 0 02) 0 690 14 200 14
1) Value for plate; 0 mm for strut und grid pattern
2) 40 mm (Size II: 70 mm) for plates, which hide lateral apertures in the with-
drawable frame
All Safety distances above circuit-breaker refer to the upper
edge of auxiliary plug and not to the upper edge of the arc
chute! See dimension drawings on pages 5/61 to 5/66, parts 4
and 5.

5/60 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids
Size I, up to 1600 A, fixed-mounted design, 3- and 4-pole
Standard design Optional connection variants
Horizontal connection Front connection (single)
4) 47 55 55 55 55

35
5)
Æ 13,5

NSE00612b
275
439,5

3)
434

NSE00613b
421
451
11)
6
123,5
NSE00611

270 15
300 10

35
60 90 90 90

26
11
390 c 82

Front connection (double hole)


to DIN 43673
9 ) Ø 13,5
1 ) 6 0 ,5 47 55 55 55 55

40
N S E 0 _ 0 0 6 1 4 b
8 )

80
3 3 ,5
NSE00615b

3)
5
a

NSE00616b
421
5 4 1 ,5

11)
541
3 2 7 ,5

3 )
6
2 7 5

34
1 5 0

80
a

5 ,5
7 6

40
14
4 5 c 82 60 90 90 90
6 )
1 5 0
2 1 0 1 0 6
2 3 0 1 2 7

Vertical connection
90 90 90 60 1 1 ) 3 5 NSE00619 b
35

55
Ø 13,5

11)
6 0

7) 3)
3 0

3)
7)
2 6 7 ,5

N S E 0 _ 0 0 6 1 8 c

ØM8
1 2 7 ,5

1 1 3 ,5
NSE00617a

139 58 1 3 ,5
320 1 2 8 ,5 60 90 90 90
410

NSE00620

3)

60 90 90 90

——— 4-pole design


Rated circuit-breaker current
1) Mounting space for removal of the arc chutes. A a b c
3) Slots (4 mm wide, 5 mm deep) for supporting phase barriers up to 1000 10 10 10
in the system.
1250–1600 15 15 15
4) Auxiliary connector with screw-type terminals (SIGUT).
5) Auxiliary connector with screwless connection system (tension spring).
Safety clearances to grounded parts as well as to live parts, see
6) Dimension to inside surface of the closed cabinet door. page 5/60.
7) Fixing points for mounting the circuit-breaker in the system.
8) "Secure OFF" locking device.
9) Key operation.
11) Termination surface.

Siemens LV 30 · 2004 5/61


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids
Size I, up to 1600 A, withdrawable design, 3- and 4-pole
Standard design Optional connection variants
Horizontal connection Front connection (single)
320 62,5 3 5 0
NSE00621

270 2 6 0

NSE00622a
5) 4) 5 5 5 5 5 5 5 5
1 3 ,5

3 5
N S E 0 _ 0 0 6 2 3 b
6
275

403
465,5

1 1 )

3 7 3
3 )

2 8 7
123,5

6 9
11
10) 13 30 169,5
210 55
300 1 5 9 0 9 0 9 0

3 5
2 6
Front connection (double hole)
3 5 0
N S E 0 _ 0 0 6 2 4 b 7 ) 8 ) to DIN 43673
2 6 0
9 ) 62,5 1 3 ,5 5 5 5 5 5 5 5 5

5 NSE00625a
a

4 0

8 0
3 2 7 ,5

3 )
4 6 0

a
2 7 5

6
493
3 1

1 1 )
1 5 0

3 7 3

2 8 7
1 0 )
7 6

N S E 0 _ 0 0 6 2 6 b
2 7 2 2 0 4 5
4 0

3 6 7 ,5 5 8
3 8 2 ,5 8 8 ,5 6 )
34

4 2 1 2 1 ,5

6 9
1 4 0 ,5

8 0
4 0

c 169,5
1 4

1 5 9 0 9 0 9 0
Vertical connection
3 5 0
38

55 55 55 55 2 6 0
11)
b
38
Ø 13,5
Ø 13,5
N S E 0 _ 0 0 6 2 9 a
60

11)
30
NSE00627a

267,5

2 8 7
127,5

3 )

139 68
NSE00628a 150
270 25
320 165
6 9

410
1 5 9 0 9 0 9 0
Flange connection 3 5 0
NSE00630
14 2 6 0
5 5 5 5 5 5 5 5
NSE00631

N S E 0 _ 0 0 6 3 2 a

M 1 2
3)
3 3

5 9
2 8 7
2 6

3 )
2 8 2 ,5

5 9
1 4 2 ,5

10) 15
10) 121
6 9

55 90 90 90

1 5 9 0 9 0 9 0
——— 4-pole design
Rated circuit-breaker current
3) Slots (4 mm wide, 5 mm deep) for supporting phase barriers A a b c
in the system.
4) Auxiliary connector with screw-type terminals (SIGUT). up to 1000 10 10 10
5) Auxiliary connector with screwless connection system (tension spring). 1250–1600 15 15 15
6) Dimension to inside surface of the closed cabinet door.
7) SENTRON WL in connected position.
Safety clearances to grounded parts as well as to live parts, see
8) SENTRON WL in test position. page 5/60.
9) SENTRON WL in disconnected position.
10) Fixing holes 10 mm.
11) Terminal face.

5/62 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids
Size II, up to 3200 A, fixed-mounted design, 3- and 4-pole
Standard design Optional connection variants
Horizontal connection Front connection (single)
5) 4) 47 90 90 90 90

35
40 40

NSE00634c
275
435,5
434

NSE00635c
451

421
11)
3)
123,5

35
10
NSE00633

270 85
440 90 130 130 130 13,5

26
11
570 c 82

Front connection (double hole)


to DIN 43673
90 90 90 90

40
1 ) 47 40 40

80
1 2 )

5
NSE00637c

3)
a

NSE00638c
421
5 4 1 ,5

6 11)
541
3 2 7 ,5

3 )
4 5 1 ,5

14
2 7 5

34

80
1 5 0
a

7 6

90 130 130 130 13,5

40
N S E 0 _ 0 0 6 3 6 c 5 ,5
4 5 c 82
6 )
1 5 0
2 1 0 1 0 6
2 3 0 1 2 7

Vertical connection
130 130 130 90
Ø 13,5

b
90 30
35

NSE00641
30

30
30

11)
Æ 13,5 7) 3)
7) ÆM8
290

98
134,5

35
NSE00639b

139 128 NSE00640b


460 90 130 130 130
113,5
590 11)
128,5

NSE00642

3)

90 130 130 130

——— 4-pole design


Rated circuit-breaker current
1) Mounting space for removal of the arc chutes. A a b c
3) Slots (4 mm wide, 5 mm deep) for supporting phase barriers up to 2000 10 10 10
in the system.
2500 15 15 20
4) Auxiliary connector with SIGUT screw-type terminals.
3200 30 30 20
5) Auxiliary connector with tension spring connection.
6) Dimension to inside surface of the closed cabinet door. Safety clearances to grounded parts as well as to live parts, see
7) Fixing points for mounting the circuit-breaker in the system.
page 5/60.
11) Terminal face.
12) Top edge of circuit-breaker – only AC 1000 V design.
* Clearance to grounded parts.

Siemens LV 30 · 2004 5/63


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids
Size II, up to 3200 A, withdrawable design, 3- and 4-pole
Standard design Optional connection variants
Horizontal connection Front connection (single)
5 3 0

N S E 0 _ 0 0 6 4 5 c
5) 4) 62,5 4 0 0
NSE00643a
9 0 9 0 9 0 9 0

NSE00644b
4 0 4 0

3 5
1 3 ,5
275
465,5
6
461

403
3 )
1 1 )

3 7 3

2 8 7
123,5

2 6
169,5

11
270 40 10)

6 9
10)
350 55 4 5 ,1
480 5 5 1 3 0 1 3 0 1 3 0

3 5
Front connection (double hole)
to DIN 43673
1 2 ) 5 3 0

N S E 0 _ 0 0 6 4 8 c
62,5 4 0 0

1 3 ,5
N S E 0 _ 0 0 6 4 6 b 7 ) 8 ) 9 0 9 0 9 0 9 0
9 )
NSE00647b
4 0 4 0

4 0
5

8 0
a

3 2 7 ,5
5 1 7

6
4 6 0

493

4 0 ,5 3 )
2 7 5

1 1 )

3 7 3

2 8 7
a
1 5 0

34

1 0 )
7 6

2 2 0 4 5

1 4
3 6 7 ,5 5 8 c
4 0
3 1

6 9
3 8 2 ,5 8 8 ,5

8 0
169,5
2 7 1 2 1 ,5
4 2 1 4 0 ,5 4 0 5 5 4 5 1 3 0 1 3 0 1 3 0
Vertical connection
5 3 0
30 30 11) 4 0 0
NSE00650a

38 b N S E 0 _ 0 0 6 5 1 a
30
38

30

Ø 13,5
11)
3 )
NSE00649a

2 8 7
290

100
135

139 138
270 95 6 9
460 157 5 5 4 5 1 3 0 1 3 0 1 3 0
590 172

Flange connection
90 90 90 90 5 3 0
NSE00653

4 0 0
NSE00652a

M 1 2 9 0
N S E 0 _ 0 0 6 5 4 a

4 0
3 3
2 6

3)
5 9

3 )
2 8 7
2 8 2 ,5

5 9
1 4 2 ,5

6 9

10) 10) 121


55 45 130 130 130 4 5 1 3 0 1 3 0 1 3 0

——— 4-pole design


Rated circuit-breaker current
3) Slots (4 mm wide, 5 mm deep) for supporting phase barriers A a b c
in the system.
up to 2000 10 10 10
4) Auxiliary connector with SIGUT screw-type terminals.
2500 15 15 20
5) Auxiliary connector with tension spring connection.
3200 30 30 20
7) SENTRON WL in connected position.
8) SENTRON WL in test position. Safety clearances to grounded parts as well as to live parts, see
9) SENTRON WL in disconnected position.
page 5/60.
10) Fixing holes, diameter 10 mm.
11) Terminal face.
12) Top edge of circuit-breaker – only AC 1000 V design.
* Clearance to grounded parts.

5/64 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids
Size III, up to 6300 A, fixed-mounted design, 3- and 4-pole
Standard design Optional connection variants
Horizontal connection Front connection (single)
5) 4) 47 160 160 160 160

35
NSE00655
50 50
13,5

NSE00656c
3)

275

NSE00657c
6

439
434

421
11)

451
123,5

26
270 205 12 130 210 210 210

35
20

11
680
890 82

Front connection (double hole)


to DIN 43673
1 ) Ø 1 3 ,5 1 6 0 1 6 0 1 6 0 1 6 0
N S E 0 _ 0 0 6 5 8 c 4 7
5 0 5 0 5 0 5 0
1 2 )

4 0

8 0
5
3 0

N S E 0 _ 0 0 6 5 9 d
5 4 1 ,5

3 )

N S E 0 _ 0 0 6 6 0 c
3 )
3 2 7 ,5
4 5 1 ,5

6 1 1 )

4 2 1
5 4 1
2 7 5
1 5 0
3 0

7 6

1 4
5 ,5
3 4

4 5

8 0
3 5 1 5 0 6 )
2 1 0 1 0 6 1 3 0 2 1 0 2 1 0 2 1 0
2 0
4 0
2 3 0 1 2 7
8 2

Vertical connection
2 1 0 2 1 0 2 1 0 107 20
30

3 0 1 6 0 1 5 1 3 0 10
3 5

NSE00663
15

1 1 )
7 ) 1 3 ,5 7 ) 3)
11)
M 1 0 40
330,5

120
94,5
N S E 0 _ 0 0 6 6 1 b

1 3 9 2 4 8
7 0 4 85 210 210 210
40
NSE00662a

9 1 4 Ø 13,5
142
162

NSE00664a

3)

130 210 210 210 130

——— 4-pole design Safety clearances to grounded parts as well as to live parts, see
1) Mounting space for removal of the arc chutes. page 5/60.
3) Slots (4 mm wide, 5 mm deep) for supporting phase barriers
in the system.
4) Auxiliary connector with SIGUT screw-type terminals.
5) Auxiliary connector with tension spring connection.
6) Dimension to inside surface of the closed cabinet door.
7) Fixing points for mounting the circuit-breaker in the system.
11) Terminal face.
12) Top edge of circuit-breaker – only AC 1000 V design.
* Clearance to grounded parts.

Siemens LV 30 · 2004 5/65


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids
Size III, up to 6300 A, withdrawable design, 3- and 4-pole
Standard design Optional connection variants
Horizontal connection, up to 5000 A Front connection (single hole),
5) 4)
up to 4000 A 8 4 0

N S E 0 _ 0 0 6 6 7 c
NSE00665a 6 3 0
62,5 1 6 0 1 6 0
1 6 0 1 6 0

1 3 ,5
NSE00666b
5 0 5 0

3 5
275
466,5
461

403
123,5

1 1 )

2 8 7
3 7 3
10) 10) 270 160
590 10)
800 57

6 9
20

11
8 5 2 1 0 2 1 0 2 1 0
169,5

3 5
5 9 0

2 6
5 7 8 0 0
Front connection (double hole)
1 2 ) to DIN 43673, up to 4000 A 8 4 0

N S E 0 _ 0 0 6 7 0 c
62,5 6 3 0
7 ) 8 )

1 3 ,5
N S E 0 _ 0 0 6 6 8 b
1 6 0 1 6 0 1 6 0 1 6 0
9 )
NSE00669b
5 0 5 0

4 0
5
3 0

8 0
3 )
5 1 7
3 2 7 ,5
4 6 0

6
493
3 0

1 1 )

2 8 7
3 7 3
2 7 5
1 5 0

1 0 )
7 6

1 4

6 9
4 0 ,5 2 2 0 4 5 6 )

8 0
4 0
3 1

3 6 7 ,5 5 8 20
3 8 2 ,5 8 8 ,5
34

169,5 8 5 2 1 0 2 1 0 2 1 0
4 0

2 7 1 2 1 ,5 5 9 0
4 2 1 4 0 ,5 5 7 8 0 0
Vertical connection, up to 6300 A
30 8 4 0
38
NSE00672a

30 30 Ø 13,5 6 3 0
11) 7 0 4
2 0
1 0
30
38

N S E 0 _ 0 0 6 7 3 b

11)
330,5
NSE00671a

124,5

2 8 7
94,5

139 260 24
270 217 177
6 9
704 Ø 13,5 197
914 a b b 2 1 0
5 7 5 9 0
8 0 0
9 1 4
Flange connection, up to 4000 A
8 4 0
NSE00675

160 160 160 160


6 3 0
NSE00674

7 0 4
N S E 0 _ 0 0 6 7 6 a

1 6 0 1 6 0 1 6 0 1 6 0
1 2
3 3
M

5 9
2 8 7
2 6
2 8 2 ,5

57 85 210 210 210


5 9
1 4 2 ,5

5
6 9

3 0
121 5 7 8 5 2 1 0 2 1 0 2 1 0
5 9 0
8 0 0
9 1 4

——— 4-pole design


Rated circuit-breaker current
3) Slots (4 mm wide, 5 mm deep) for supporting A a b
phase barriers in the system.
4) Auxiliary connector with SIGUT screw-type terminals. 4000 40 210
5) Auxiliary connector with tension spring connection. 5000 40 210
6) Dimension to inside surface of the closed cabinet door. 6300 5 245
7) SENTRON WL in connected position.
8) SENTRON WL in test position.
Safety clearances to grounded parts as well as to live parts, see
9) SENTRON WL in disconnected position. page 5/60.
10) Fixing holes, diameter 10 mm.
11) Terminal face.
12) Top edge of circuit-breaker – only AC 1000 V design.
* Clearance to grounded parts.

5/66 Siemens LV 30 · 2004


Circuit-Breakers/Non-Automatic Circuit-Breakers up to 6300 A,
SENTRON WL
Project planning aids

■ Circuit diagrams
Terminal assignment diagram

o p tio n a l In te rn e K le m m e n E x te r n e B e s c h a ltu n g
Z u b e h ö r / A c c e s s o r ie s B e s c h a ltu n g T e r m in a ls E x te r n a l w ir in g
( H ilfs s c h a lte r S 1 , S 2 = S ta n d a r d ) In te r n a l w ir in g L / L +
( A u x ilia r y s w itc h S 1 , S 2 = S ta n d a r d ) s / c
N / L –

z .B . W a n d le r im T r a n s fo rm a to r-
F e rn -R ü c k s e tz m a g n e t / 1 4 S te rn p u n k t o d e r S u m m e n s tro m -
R e m o te r e s e t b e ll a la r m & tr ip p e d in d ic a to r F 7 w a n d le r 1 2 0 0 A /1 A
1 3
e .g . c u rre n t tra n s fo rm e r in th e
G - W a n d le r / G tra n s fo rm e r S 2 1 2 s ta r p o in t o f p o w e r tr a n s fo rm e r
o r a s u m m a tio n c u r r e n t
G - W a n d le r / G tra n s fo rm e r S 1 1 1 tra n s fo rm e r 1 2 0 0 A /1 A
N - W a n d le r / N s e n s o r S 2 1 0 B r ü c k e , w e n n k e in N - W a n d le r
N
N - W a n d le r / N s e n s o r S 1 9 S h o r t te r m in a ls if n o N - s e n s o r
e x t. S p a n n u n g s w a n d le r S te r n / e x t. v o lta g e tr a n s fo r m e r C o m 8 L 1
e x t. S p a n n u n g s w a n d le r / e x t. v o lta g e tr a n s fo r m e r L 3 7 L 2
e x t. S p a n n u n g s w a n d le r / e x t. v o lta g e tr a n s fo r m e r L 2 6 L 3
e x t. S p a n n u n g s w a n d le r / e x t. v o lta g e tr a n s fo r m e r L 1 5 N
0 V D C 4

5
2 4 V D C in p u t
2 4 V D C 3
B U S + 2 A b s c h lu s s w id e r s ta n d ,
w e n n k e in e x te rn e s C B -m o d u l
B U S 1
T e rm in a tio n r e s is to r ,
if n o t e x te rn a l C B -m o d u le
N ic h t v o r h a n d e n b e i K o m m u n ik a tio n s fu n k tio n " F 0 2 " . A u f
d e r P o s itio n v o n " - X 7 " b e fin d e t s ic h d a s M o d u l C O M 1 5 .

1 4
A u s g e lö s t- M e ld e s c h a lte r /
N o t a v a ila b le w ith c o m m u n ic a tio n c o n n e c tio n " F 0 2 " .

F 1 , 2
O U T

tr ip s ig n a llin g s w itc h S 2 4 1 3
1 2
O p e n

( O p tio n F 0 2 )
9
+
–

1 1
Y 1

S p e ic h e r z u s ta n d s m e ld u n g /
C lo s e

" S p r in g c h a r g e d " s ig n a l S 2 1 1 0
+
–

E le k tr is c h " E IN " / L o c a l e le c tr ic c lo s e S 1 0 9 L / L + s / c
C O M 1 5 m o d u le is a t p o s itio n " - X 7 " .

5
F re e
+

8
–

7
F re e

6
D P W r ite
E n a b le

M e ld e s c h a lte r a m e r s te n H ilfs a u s lö s e r / S 2 2 5
1

S ig n a lin g c o n ta c t a t th e 1 s t a u x ilia r y r e le a s e
4
IN

E x te rn a l

3
In te rn a l

M e ld e s c h a lte r a m z w e ite n H ilfs a u s lö s e r / S 2 3 2


S ig n a lin g c o n ta c t a t th e 2 n d a u x ilia r y r e le a s e
1

1 4 L / L +
E r s te r H ilfs a u s lö s e r F 1 " f" / 1 s t a u x ilia r y r e le a s e F 1 " S T " s / c
1 3 N / L –
1 2
S 1 "S " / "N O "
1 1
1 0
S 1 "Ö " / "N C "
9
E in s c h a ltm a g n e t / C lo s in g s o le n o id 8 N / L –
s / c
7 L / L +
6
5
E in s c h a ltb e r e its c h a fts m e ld u n g / " R e a d y to c lo s e " s ig n a l S 2 0
4
S 2 "S " / "N O "
3
2
S 2 "Ö " / "N C "
1

n u r F 4 " S c h n e ll A U S " / F 4 o n ly " q u ic k O F F " 1 4 N O T -A U S o d e r B rü c k e


E M E R G E N C Y O F F
n u r F 4 " S c h n e ll A U S " / F 4 o n ly " q u ic k O F F " 1 3 o r s h o r t te r m in a ls
Z w e ite r H ilfs a u s lö s e r : F 2 " S T " , F 3 " U V R " , F 4 " U V R td " / 1 2 L / L +
2 n d a u x ilia r y r e le a s e : F 2 " S T " , F 3 " U V R " , F 4 " U V R td " s / c
1 1 N / L –
1 0
S 3 "S " o d e r S 7 "S " / S 3 "N O " o r S 7 "N O "
9
8
S 3 "Ö " o d e r S 7 "S " / S 3 "N C " o r S 7 "N O "
7
6
S 4 "S " o d e r S 8 "S " / S 4 "N O " o r S 8 "N O "
5
4
S 4 "Ö " o d e r S 8 "S " / S 4 "N C " o r S 8 "N O "
N S E 0 _ 0 0 6 0 5 h

3
M o to r a n tr ie b / C h a r g in g m o to r M 2 L / L +
s / c
o p t.: M o to r a b s te lls c h a lte r / o p t. m o to r m a in s w itc h S 1 2 1 N / L –

Siemens LV 30 · 2004 5/67


Circuit-Breakers, Approved acc. to UL 489, up to 5000 A,
SENTRON WL
General data

■ Technical specifications
Short-circuit breaking capacity
Size I II III
Type 3WL51 3WL52 3WL53
Switching capacity class S H H
up to AC 480 V kA 65 100 100
up to AC 600 V ,/347 V kA 50 – 85
up to AC 600 V kA – 85 –

Rated short-time withstand current


Size I II III
Type 3WL51 3WL52 3WL53
Switching capacity class S H H
at max. delay time tsd = 0.4 s kA 65 85 85

Further technical specifications


Size I II
Type 3WL51 10 3WL51 16 3WL52 20
Rated current In at 40 °C, at 50/60 Hz

5 Main conductor
Rated voltage Ue at 50/60 Hz
A
AC V
up to 1000
600 ,/347
1600
600 ,/347
2000
600
Ambient temperature of the system °C –25/+40 –25/+40 –25/+40
Power loss at rated current
with AC symmetrical load
Fixed-mounted circuit-breaker W 100 150 180
Withdrawable circuit-breaker W 195 350 320
Operating times
Make-time ms 35 35 35
Break-time ms 38 38 34
Electr. make-time (via activation solenoid)1) ms 80 80 100
Electr. break-time (via shunt release) ms 73 73 73
Electr. break-time (instantaneous undervoltage release) ms 73 73 73
Break-time due to ETU, instantaneous short-circuit release ms 50 50 50
Service life
mechanical (without maintenance) Operating cycles 10000 10000 10000
mechanical (with maintenance)2) Operating cycles 20000 20000 15000
electrical (without maintenance) Operating cycles 4000 4 000 4000
Operating frequency 1/h 60 60 60
Minimum interval ms 80 80 80
between tripping operation by electronic trip unit and next
making operation of the circuit-breaker
(only with autom. mechanical resetting of the lockout device)
Minimum dimension
Circuit-breaker section 3-pole mm 400 × 460 × 380 400 × 460 × 380 500 × 460 × 380
(width × height × depth)
D h max.

Service position 3 0 ° 3 0 ° 3 0 ° 3 0 °
= 1 mm

and/
or

N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2 NSE00927

Main conductor Qty. 2 2 2


minimum mm2 6.4 × 76.2 6.4 × 76.2 6.4 × 102
cross-sections or
inches 1/4 × 3 1/4 × 3 1/4 × 4
Auxiliary conductors (Cu) Standard connection = strain-relief clamp
Max. no. of without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
auxiliary conductors × cross- with end sleeve to 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
section (solid/stranded) DIN 46228 Part 2
with twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Optional connection = tension spring
without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
with end sleeve to 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
DIN 46228 Part 2
Weights
3-pole Fixed-mounted circuit-breaker kg 43 43 56
Withdrawable circuit-breaker kg 45 45 60
Guide frame kg 25 25 31
1) Make-time via activation solenoid for synchronization purposes (short-time
excited) 85 ms.
2) Maintenance means: replace the main contact elements and arc chutes
(see Operator's Guide).

5/68 Siemens LV 30 · 2004


Circuit-Breakers, Approved acc. to UL 489, up to 5000 A,
SENTRON WL
General data

Size II III
Type 3WL52 25 3WL52 30 3WL53 40 3WL53 50
Rated current In at 40 °C, at 50/60 Hz
Main conductor A 2500 3000 4000 5000
Rated voltage Ue at 50/60 Hz AC V 600 600 up to 600 ,/347 up to 600 ,/347
Ambient temperature of the system °C –25/+40 –25/+40 –25/+40 –25/+40
Power loss at rated current
with AC symmetrical load
Fixed-mounted circuit-breaker W 270 410 520 630
Withdrawable circuit-breaker W 520 710 810 1050
Operating times
Make-time ms 35 35 35 35
Break-time ms 34 34 34 34
Electr. make-time (via activation solenoid)1) ms 100 100 100 100
Electr. break-time (via shunt release) ms 73 73 73 73
Electr. break-time (instantaneous undervoltage release) ms 73 73 73 73
Break-time due to ETU, instantaneous short-circuit release ms 50 50 50 50
Service life
mechanical (without maintenance) Operating cycles 10000 10000 5000 5000
mechanical (with maintenance)2) Operating cycles 15000 15000 10000 10000
electrical (without maintenance) Operating cycles 4000 4000 1000 1000
Operating frequency 1/h 60 60 60 60

5
Minimum interval ms 80 80 80 80
between tripping operation by electronic trip unit and next
making operation of the circuit-breaker
(only with autom. mechanical resetting of the lockout device)
Minimum dimension
Circuit-breaker section 3-pole mm 500 × 460 × 380 500 × 460 × 380 800 × 460 × 380 800 × 460 × 380
(width × height × depth)
3 0 ° 3 0 ° 3 0 ° 3 0 °

D h max.
Service position

= 1 mm
and/
or

N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2 NSE00927

Main conductor Qty. 2 4 4 4 4


minimum mm2 6.4 × 127 6.4 × 63.5 6.4 × 102 10 × 120 10 × 120
cross-sections
or 1/4 × 5 1/4 × 2–1/2 1/4 × 4 1/4 × 53) 1/4 × 53)
inches
Auxiliary conductors (Cu) Standard connection = strain-relief clamp
Max. no. of without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
auxiliary conductors × cross- with end sleeve to 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
section (solid/stranded) DIN 46228 T.2
with twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
optional connection = tension spring
without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
with end sleeve to 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
DIN 46228 T.2
Weights
3-pole Fixed-mounted circuit-breaker kg 59 64 82 82
Withdrawable circuit-breaker kg 63 68 88 88
Guide frame kg 39 45 60 60
1) Make-time via activation solenoid for synchronization purposes (short-time
excited) 50 ms.
2) Maintenance means: replace the main contact elements and arc chutes
(see Operator's Guide).
3) 1/4 × 5 for fixed-mounted circuit-breakers on request.

Siemens LV 30 · 2004 5/69


Circuit-Breakers, Approved acc. to UL 489, up to 5000 A,
SENTRON WL
General data

Size I ... III


Manual operating mechanism with mechanical closing
Closing/ Max. force required to operate the hand lever N ≤ 230
charging stored-energy Required number of strokes on the hand lever 9
feature
Manual operating mechanism with mechanical and electrical closing
Charging stored-energy
feature
Closing solenoid (CC) Operating range 85 ... 110 %
Extended operating range for battery operation for DC 24 V, DC 48 V 70 ... 126 %
DC 60 V, DC 110 V
DC 220 V
Power input AC/DC VA/W 15/15
Minimum command duration rated voltage for the closing solenoid ms 60
Short-circuit protection Fuse 1A
Manual/motorized operating mechanism with mechanical and electrical closing
Manual operating
mechanism
Motor Operating range 85 ... 110 %
Extended operating range for battery operation for DC 24 V, DC 48 V 70 ... 126 %

5 DC 60 V, DC 110 V
DC 220 V
Power input to motor AC/DC VA/W 110/110
Time required to charge the stored-energy mechanism at 1 × rated S ≤ 10
voltage
Closing solenoid
For motor and Short-circuit protection Fuse 2A
closing solenoid Motor and closing solenoid for the same rated control supply voltages
Smallest permissible fuse at 24–30 V 2A
at 48–60 V 2A
at 110–127 V 1A
at 220–250 V 1A
Electronic trip unit signals
Measuring accuracy of the electronic trip unit protection functions to
UL 489
Current indication ≤ 5 %;
Measurement functions
base quantities ≤ 1 %;
Measurement functions
derived quantities ≤ 4 %
Auxiliary releases
Shunt release (ST) (F1, For continuous command Operating value Pickup > 0.7 × rated voltage
F2)/ (100 % ON-time), (circuit-breaker is tripped)
Closing solenoid locks out on momentary- Operating range 85 ... 110 %
contact commands
Extended operating range for battery for DC 24 V, DC 48 V 70 ... 126 %
operation DC 60 V, DC 110 V
DC 220 V
Rated voltage AC 50/60 Hz V 110; 230
DC V 24; 30; 48; 60; 110; 220
Power input AC/DC VA/W 15/15
Minimum command duration at rated ms 60
voltage
Opening time of the circuit-breaker AC/DC ms 80
at rated voltage
Short-circuit protection 1A
Smallest permissible fuse
With stored energy feature Rated voltage AC 50/60 Hz V 110; 230
consisting of shunt release DC V 110; 220
and capacitor storage Operating range 85 ... 110 %
device
Power input AC/DC VA/W 1/1
Storage time/recharging time at rated voltage max. 5 min/min. 5 s
Opening time of circuit-breaker, short-circuit protection ms 80

5/70 Siemens LV 30 · 2004


Circuit-Breakers, Approved acc. to UL 489, up to 5000 A,
SENTRON WL
General data

Size I ... III


Auxiliary releases
Undervoltage release Operating values pickup ≥ 0.85 × Us (circuit-breaker can
UVR (F3) and be closed)
UVR-td (F4) 0.35 ... 0.7 × Us (circuit-breaker
dropout is tripped)
Operating range 0.85 ... 1.1
Extended operating range for battery operation for DC 24 V, DC 30 V, 0.85 ... 1.26
DC 48 V, DC 110 V,
DC 220 V
Rated control supply voltage Us AC 50/60 Hz V 110 ... 127/208 ... 240/380 ... 415
DC V 24/30/48/110/220 ... 2501)
Power input (pickup/continuous duty) AC VA (200 = pickup) 5
DC W (200 = pickup) 5
Opening time of circuit-breaker at Us = 0 ms 200
Design UVR (F3)
Instantaneous ms 80
With delay ms 200
Design UVR-td (F8)
With delay, td = 0.2 ... 3.2 s S 0.2 ... 3.2
Reset via additional NC contact, direct switching-off ms ≤ 100
Short-circuit protection 1A
Smallest permissible fuse
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8) 5
Rated insulation voltage Ui AC/DC V 300
Rated operating voltage Ue AC/DC V 240
Switching capacity AC A 300 heavy duty A 10
50/60 Hz
DC P 300 heavy duty A 10
Ready-to-close signaling switch (S20) (to UL 1054)
Switching capacity Rated operating voltage V 250
Rated operating current A 3
1) 24 V and 30 V only with undervoltage release UVR (F3).

Siemens LV 30 · 2004 5/71


Circuit-Breakers, Approved acc. to UL 489, up to 5000 A,
SENTRON WL
General data

Functional overview of the electronic trip unit system


Basic functions ETU25B ETU45B:
Overload protection ✓ ✓
Setting range IR = In × ... 0.4-0.45-0.5-0.55-0.6- 0.4-0.45-0.5-0.55-0.6-
0.65-0.7-0.8-0.9-1 0.65-0.7-0.8-0.9-1
Switchable overload protection – ✓ (using sliding-dolly switch)
L (Setting
2 4
I t- or I t-dependent function)
range for time-lag class t 2
R at I t 10 s fixed 2-3-5-5.5-8-10-14-17-21-25-30 s
R Setting range for time-lag class tR at I4t – 1-2-3-4-5 s
Thermal image – ✓ (on/off using sliding-dolly switch)
Phase loss sensitivity at tsd = 20 ms (M) at tsd = 20 ms (M)
Neutral conductor protection – ✓
R
N Function can be switched on/off
N conductor setting range IN = In × ...


✓ using sliding-dolly switch
0.5 ... 1
Short-time delayed short-circuit protection ✓ ✓
Function can be switched on/off – ✓ (using rotary coding switch)
Setting range Isd = In × ... 1.25-1.5-2-2.5-3-4-6-8-10-12 1.25-1.5-2-2.5-3-4-6-8-10-12
S Setting range for delay time tsd
Switchable short-time delayed short-circuit protection
0-M-100-200-300-400

M-100-200-300-400 ms
✓ (using rotary coding switch)
s d (I2t-dependent function)
Setting range for delay time tsd at I2t – 100-200-300-400 ms
s d Zone Selective Interlocking function – by CubicleBUS module
Instantaneous short-circuit protection ✓ ✓

i
I Function can be switched on/off
Setting range Ii = In × ...

fixed for Ii ≥ 20 × In, max. 50 kA
✓ (using rotary coding switch)
1.5-2.2-3-4-6-8-10-12-0.8 × Ics

5 N S E 0 _ 0 0 8 8 8 b Ground-fault protection
Tripping and alarm function
Tripping function can be switched on/off



❑ Module can be retrofitted

✓ (using rotary coding switch)
Detection of the ground-fault current via summation cur- – ✓
rent formation with internal or external neutral conductor
g transformer
Detection of ground-fault current via external – ✓
G transformer
Setting range of the operating current Ig for release – A-B-C-D-E1)
g
Setting range of the operating current Ig for alarm – A-B-C-D-E1)
N S E 0 _ 0 0 8 8 9 a
Setting range of the delay time tg – 100-200-300-400-500 ms
Switchable ground-fault protection characteristic – ✓
(I2t-dependent function)
Setting range for delay time tg at I2t – 100-200-300-400-500 ms
Zone Selective Interlocking function – by CubicleBUS-Modul
LCD
Alphanumeric LCD (4-line) – ❑
Communication
CubicleBUS integrated – ✓
Communication-capable via PROFIBUS-DP – ✓
Measurement function
Meas. func.-capable with meas. func./meas. func. Plus – ✓
LED display
Electronic trip unit active ✓ ✓
Alarm ✓ ✓
ETU fault ✓ ✓
L-release ✓ ✓
S-release ✓ ✓
I-release ✓ ✓
NSE00890 N-release – ✓
G-release – ✓ (only with ground-fault protec. module)
G-alarm – ✓ (only with ground-fault protec. module)
Release via extended protection function – ✓
Communication – ✓
Signals from signaling switches with external CubicleBUS modules (optical or relays)
Overload warning – ✓
Load shedding, load receiving – ✓
Leading signal overload release 200 ms – ✓
Temperature alarm – ✓
Phase unbalance – ✓
Instantaneous short-circuit release – ✓
Short-time delayed short-circuit release – ✓
Overload release – ✓
NSE00891 Neutral conductor release – ✓
Ground-fault protection release – ✓ (only with ground-fault protec. module)
Ground-fault alarm – ✓ (only with ground-fault protec. module)
Auxiliary relay – ✓
ETU fault – ✓

Delay-time figures given in ms. ✓ Available. 1) Setting range of the operating current
M = motor protection, corresponds to 20 ms. – Not available. Size I and size II Size III
❑ Optional. A 100 A 400 A
B 300 A 600 A
C 600 A 800 A
D 900 A 1000 A
E 1200 A 1200 A

For tripping characteristics and dimensions as for "Circuit-


breakers/non-automatic circuit-breakers up to 6300 A,
SENTRON WL", see Pages 5/57 to 5/67.

5/72 Siemens LV 30 · 2004


Circuit-Breakers, Approved acc. to UL 489, up to 5000 A,
SENTRON WL
3-pole, fixed-mounted design

■ Selection and ordering data


Size Max. rated Rated current1) Switching capacity 480 V PS* Weight
circuit-breaker In per PU
Order No.
current In max. approx.
Order No. supplements
A A kA DT see Page 5/36 kg
Horizontal main circuit connection
I 1000 1000 65 B 3WL51 10-3@@32-.... 1 unit 43.000
I 1600 1600 65 B 3WL51 16-3@@32-.... 1 unit 43.000
II 2000 2000 100 B 3WL52 20-4@@32-.... 1 unit 56.000
II 2500 2500 100 B 3WL52 25-4@@32-.... 1 unit 59.000
II 3000 3000 100 B 3WL52 30-4@@32-.... 1 unit 64.000
III 4000 4000 100 C 3WL53 40-4@@32-.... 1 unit 82.000
III 5000 5000 100 C 3WL53 50-4@@32-.... 1 unit 82.000
Vertical main circuit connection
I 1000 1000 65 B 3WL51 10-3@@31-.... 1 unit 43.000
I 1600 1600 65 B 3WL51 16-3@@31-.... 1 unit 43.000
II 2000 2000 100 B 3WL52 20-4@@31-.... 1 unit 56.000
II 2500 2500 100 B 3WL52 25-4@@31-.... 1 unit 59.000
II 3000 3000 100 B 3WL52 30-4@@31-.... 1 unit 64.000
III 4000 4000 100 C 3WL53 40-4@@31-.... 1 unit 82.000
III 5000 5000 100 C 3WL53 50-4@@31-.... 1 unit 82.000
Front main circuit connection, single hole
I 1000 1000 65 B 3WL51 10-3@@33-.... 1 unit 43.000 5
I 1600 1600 65 B 3WL51 16-3@@33-.... 1 unit 43.000
II 2000 2000 100 B 3WL52 20-4@@33-.... 1 unit 56.000
II 2500 2500 100 B 3WL52 25-4@@33-.... 1 unit 59.000
II 3000 3000 100 B 3WL52 30-4@@33-.... 1 unit 64.000
III 4000 4000 100 C 3WL53 40-4@@33-.... 1 unit 82.000
Front main circuit connection, double hole
I 1000 1000 65 B 3WL51 10-3@@34-.... 1 unit 43.000
I 1600 1600 65 B 3WL51 16-3@@34-.... 1 unit 43.000
II 2000 2000 100 B 3WL52 20-4@@34-.... 1 unit 56.000
II 2500 2500 100 B 3WL52 25-4@@34-.... 1 unit 59.000
II 3000 3000 100 B 3WL52 30-4@@34-.... 1 unit 64.000
III 4000 4000 100 C 3WL53 40-4@@34-.... 1 unit 82.000
Order No. supplements
Electronic trip units
Design without ground-fault protection
ETU25B: protection functions LSI CB
ETU45B: protection functions LSIN2) EB
ETU45B: protection functions LSIN2) with 4-line display FB
Design with ground-fault protection
ETU45B: protection functions LSING2) 3) EG
ETU45B: protection functions LSING2)3) with 4-line display FG
Standard Order No. supplements (for further Order No. supplements see Page 5/36)
Manual operating mechanism with mechanical closing 1AA2
Without 1st and 2nd auxiliary release; auxiliary switch
2 NC + 2 NO

Further Order No. supplements see Page 5/36


Note: max. voltage for auxiliary circuits 240 V.
1) Rated current determined by rated current module.
On the standard design the supplied module is equal to the max. rated
type current. If a lower rated current is required, adaptation by order code
on page 5/76.
2) Current transformers for vectorial summation current formation or for pro-
tection of the neutral conductor and current transformers for detection of
the ground-fault current in the grounded star point of the transformer
should be ordered separately, see Pages 5/37 and 5/46.
3) ETU45B with ground-fault protection module GFM AT (alarm and tripping),
see Page 5/76.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/73


Circuit-Breakers, Approved acc. to UL 489, up to 5000 A,
SENTRON WL
3-pole, withdrawable design

Size Max. rated Rated current1) Switching capacity 480 V PS* Weight
circuit-breaker In per PU
Order No.
current In max. approx.
Order No. supplements
A A kA DT see Page 5/36 kg
Without guide frame (for guide frames see Page 5/75)
I 1000 1000 65 B 3WL51 10-3@@35-.... 1 unit 45.000
I 1600 1600 65 B 3WL51 16-3@@35-.... 1 unit 45.000
II 2000 2000 100 B 3WL52 20-4@@35-.... 1 unit 60.000
II 2500 2500 100 B 3WL52 25-4@@35-.... 1 unit 63.000
II 3000 3000 100 B 3WL52 30-4@@35-.... 1 unit 68.000
III 4000 4000 100 C 3WL53 40-4@@35-.... 1 unit 88.000
III 5000 5000 100 C 3WL53 50-4@@35-.... 1 unit 88.000
With guide frame, horizontal main circuit connection
I 1000 1000 65 B 3WL51 10-3@@36-.... 1 unit 70.000
I 1600 1600 65 B 3WL51 16-3@@36-.... 1 unit 70.000
II 2000 2000 100 B 3WL52 20-4@@36-.... 1 unit 91.000
II 2500 2500 100 B 3WL52 25-4@@36-.... 1 unit 102.000
II 3000 3000 100 B 3WL52 30-4@@36-.... 1 unit 113.000
III 4000 4000 100 C 3WL53 40-4@@36-.... 1 unit 148.000
III 5000 5000 100 C 3WL53 50-4@@36-.... 1 unit 148.000
With guide frame, vertical main circuit connection

5
I 1000 1000 65 B 3WL51 10-3@@37-.... 1 unit 70.000
I 1600 1600 65 B 3WL51 16-3@@37-.... 1 unit 70.000
II 2000 2000 100 B 3WL52 20-4@@37-.... 1 unit 91.000
II 2500 2500 100 B 3WL52 25-4@@37-.... 1 unit 102.000
II 3000 3000 100 B 3WL52 30-4@@37-.... 1 unit 113.000
III 4000 4000 100 C 3WL53 40-4@@37-.... 1 unit 148.000
III 5000 5000 100 C 3WL53 50-4@@37-.... 1 unit 148.000
With guide frame, connecting flange
I 1000 1000 65 B 3WL51 10-3@@38-.... 1 unit 70.000
I 1600 1600 65 B 3WL51 16-3@@38-.... 1 unit 70.000
II 2000 2000 100 B 3WL52 20-4@@38-.... 1 unit 91.000
II 2500 2500 100 B 3WL52 25-4@@38-.... 1 unit 102.000
II 3000 3000 100 B 3WL52 30-4@@38-.... 1 unit 113.000
III 4000 4000 100 C 3WL53 40-4@@38-.... 1 unit 148.000
Order No. supplement
Electronic trip units
Design without ground-fault protection
ETU25B: protection functions LSI CB
ETU45B: protection functions LSIN2) EB
ETU45B: protection functions LSIN2) with 4-line display FB
Design with ground-fault protection
ETU45B: protection functions LSING2) 3) EG
ETU45B: protection functions LSING2)3) with 4-line display FG
Standard Order No. supplements (for further Order No. supplements for circuit-breakers and guide frames, see Page 5/36)
Manual operating mechanism with mechanical closing 1AA2
Without 1st and 2nd auxiliary release; auxiliary switch
2 NC + 2 NO

Further Order No. supplements see Page 5/36


Note: max. voltage for auxiliary circuits 240 V.
1) Rated current determined by rated current module.
On the standard design the supplied module is equal to the max. rated
type current. If a lower rated current is required, adaptation by order code
on page 5/76.
2) Current transformers for vectorial summation current formation or for pro-
tection of the neutral conductor and current transformers for detection of
the ground-fault current in the grounded star point of the transformer
should be ordered separately, see Pages 5/37 and 5/46.
3) ETU45B with ground-fault protection module GFM AT (alarm and tripping),
see Page 5/76.

5/74 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers, Approved acc. to UL 489, up to 5000 A,
SENTRON WL
Accessories/spare parts

■ Selection and ordering data


Guide frame for circuit-breakers approved to UL 489
Size Max. rated circuit- Guide frame for 3-pole PS* Weight
breaker current circuit-breakers per PU
In max. Order No. approx.
(Order No. supplements
required according to
A DT table below) kg
Front main circuit connection, single hole
I 1000 B 3WL9 251-1AA@@-@@A 1 1 unit 25.000
I 1600 B 3WL9 251-2AA@@-@@A 1 1 unit 25.000
II 2000 B 3WL9 252-3AA@@-@@A 1 1 unit 31.000
II 2500 B 3WL9 252-4AA@@-@@A 1 1 unit 39.000
II 3000 B 3WL9 252-5AA@@-@@A 1 1 unit 45.000
III 4000 B 3WL9 253-6AA@@-@@A 1 1 unit 60.000
Front main circuit connection, double hole
I 1000 B 3WL9 251-1AB@@-@@A 1 1 unit 25.000
I 1600 B 3WL9 251-2AB@@-@@A 1 1 unit 25.000
II 2000 B 3WL9 252-3AB@@-@@A 1 1 unit 31.000
II 2500 B 3WL9 252-4AB@@-@@A 1 1 unit 39.000
II 3000 B 3WL9 252-5AB@@-@@A 1 1 unit 45.000
III 4000 B 3WL9 253-6AB@@-@@A 1 1 unit 60.000
Horizontal main circuit connection
I 1000 B 3WL9 251-1AC@@-@@A 1 1 unit 25.000
5
I 1600 B 3WL9 251-2AC@@-@@A 1 1 unit 25.000
II 2000 B 3WL9 252-3AC@@-@@A 1 1 unit 31.000
II 2500 B 3WL9 252-4AC@@-@@A 1 1 unit 39.000
II 3000 B 3WL9 252-5AC@@-@@A 1 1 unit 45.000
III 4000 B 3WL9 253-6AC@@-@@A 1 1 unit 60.000
III 5000 B 3WL9 253-7AC@@-@@A 1 1 unit 60.000
Vertical main circuit connection
I 1000 B 3WL9 251-1AD@@-@@A 1 1 unit 25.000
I 1600 B 3WL9 251-2AD@@-@@A 1 1 unit 25.000
II 2000 B 3WL9 252-3AD@@-@@A 1 1 unit 31.000
II 2500 B 3WL9 252-4AD@@-@@A 1 1 unit 39.000
II 3000 B 3WL9 252-5AD@@-@@A 1 1 unit 45.000
III 4000 B 3WL9 253-6AD@@-@@A 1 1 unit 60.000
III 5000 B 3WL9 253-7AD@@-@@A 1 1 unit 60.000
Main circuit connection, connecting flange
I 1000 B 3WL9 251-1AE@@-@@A 1 1 unit 25.000
I 1600 B 3WL9 251-2AE@@-@@A 1 1 unit 25.000
II 2000 B 3WL9 252-3AE@@-@@A 1 1 unit 31.000
II 2500 B 3WL9 252-4AE@@-@@A 1 1 unit 39.000
II 3200 B 3WL9 252-5AE@@-@@A 1 1 unit 45.000
III 4000 B 3WL9 253-6AE@@-@@A 1 1 unit 60.000
Number of auxiliary supply connectors
none 0
1 connector 1
2 connectors 2
3 connectors 3
4 connectors 4
For required number of auxiliary supply
connectors, see table on page 5/44
Type of auxiliary terminals
without 0
with screw-type terminals (SIGUT) 1
with screwless connection system 2
(tension spring)
Position indicator switches
without 0
Option 1 1
connected position 1 changeover,
test position 1 changeover,
disconnected position 1 changeover
Option 2 2
connected position 3 changeovers,
test position 2 changeovers,
disconnected position 1 changeover
Shutters
without A
with shutter, Size I B
2-part, Size II
lockable Size III

All other accessory parts must be ordered by specifying "–Z"


and the corresponding order code, see Page 5/39.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/75


Circuit-Breakers, Approved acc. to UL 489, up to 5000 A,
SENTRON WL
Accessories/spare parts

Designation DT Order No. PS* Weight


per PU
approx.
kg
Electronic trip units with protection function
ETU25B LSI C 3WL9 352-5AA00-0AA1 1 unit on req.
ETU45B without measurement function LSIN(G) C 3WL9 354-5AA00-0AA1 1 unit on req.
ETU45B with measurement function LSIN(G) C 3WL9 354-5AA10-0AA1 1 unit on req.
Rated current module / rating plug Rated current In (A)
For size I, II 250 B 3WL9 111-2AA51-0AA0 1 unit on req.
315 B 3WL9 111-2AA52-0AA0 1 unit on req.
400 B 3WL9 111-2AA53-0AA0 1 unit on req.
500 B 3WL9 111-2AA54-0AA0 1 unit on req.
630 B 3WL9 111-2AA55-0AA0 1 unit on req.
800 B 3WL9 111-2AA56-0AA0 1 unit on req.
1000 B 3WL9 111-2AA57-0AA0 1 unit on req.
For size I, II, III 1250 B 3WL9 111-2AA58-0AA0 1 unit on req.
1600 B 3WL9 111-2AA61-0AA0 1 unit on req.
For size II, III 2000 B 3WL9 111-2AA62-0AA0 1 unit on req.

5
n = 3 2 0 0 A
2500 B 3WL9 111-2AA63-0AA0 1 unit on req.
N S E 0 _ 0 0 9 9 2 a
3000 B 3WL9 111-2AA77-0AA0 1 unit on req.
3WL9 111-2AA65-0AA00 For size III 4000 B 3WL9 111-2AA65-0AA0 1 unit on req.
5000 B 3WL9 111-2AA66-0AA0 1 unit on req.
Ground-fault module
GFM A 45B (only for ETU45B) alarm only B 3WL9 111-2AT51-0AA0 1 unit on req.
GFM AT 45B (only for ETU45B) alarm and tripping B 3WL9 111-2AT53-0AA0 1 unit on req.
Display
4-line display for ETU45B B 3WL9 111-1AT81-0AA0 1 unit on req.
CubicleBUS modules1)
Digital output module with rotary coding switch, optical coupler outputs C 3WL9 111-1AT25-0AA0 1 unit on req.
Digital output module with rotary coding switch, relay outputs C 3WL9 111-1AT26-0AA0 1 unit on req.
Digital output module, configurable, optical coupler outputs C 3WL9 111-1AT30-0AA0 1 unit on req.
Digital output module, configurable, relay outputs C 3WL9 111-1AT20-0AA0 1 unit on req.
Digital input module C 3WL9 111-1AT27-0AA0 1 unit on req.
Analog output module C 3WL9 111-1AT23-0AA0 1 unit on req.
Zone Selective Interlocking module C 3WL9 111-1AT21-0AA0 1 unit on req.
Tools for configuration, operation, and
NSE-01023 monitoring
3WL9 111-1AT23-0AA0 Breaker Data Adapter (BDA) B 3WL9 111-2AT28-0AA0 1 unit on req.
Configuration, control, diagnostics, and test of SENTRON circuit-breakers via
local interface; Breaker Data Adapter, connecting cable to SENTRON circuit-
breakers for programming device (e.g. notebook); can be run with Internet
Explorer with JAVA2 VM
BDA Plus B 3WL9 111-2AT33-0AA0 1 unit on req.
Same as BDA, but with additional Ethernet inter-
face for connection to Ethernet/Intranet/Internet
Retrofitting and spare parts for
communication via PROFIBUS
COM15 PROFIBUS module2) C 3WL9 111-1AT65-0AA0 1 unit on req.
Breaker status sensor (BSS) C 3WL9 111-1AT16-0AA0 1 unit on req.
Measurement function, without voltage transformer X 3WL9 111-1AT02-0AA0 1 unit on req.
Test devices
Manual test device for electronic trip units D 3WL9 111-2AT31-0AA0 1 unit on req.

For further mechanical accessories see Pages 5/46 to 5/55.


For tripping characteristics and dimensions as for "Circuit-break-
ers/non-automatic circuit-breakers up to 6300 A, SENTRON WL",
see Pages 5/57 to 5/67.
1) Every CubicleBUS module is supplied with a factory-fitted 0.2 m cable.
2) Contains a 2 m CubicleBUS cable in addition.

5/76 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Non-Automatic Circuit-Breakers for DC, up to 4000 A,
SENTRON WL
General data

■ Technical specifications
Size II
Type 3WL12 10 3WL12 20 3WL12 40
Rated current In at 40 °C
Main conductor A up to 1000 2000 4000
Rated operating voltage Ue DC V up to 600/1000 up to 600/1000 up to 600/1000
(1000 V design, see Page 5/37)
Rated insulation voltage Ui AC V 1000 1000 1000
Rated impulse withstand voltage Uimp
Main circuits kV 12 12 12
Auxiliary circuits kV 4 4 4
Control circuits kV 2.5 2.5 2.5
Isolating function to EN 60947-2 yes yes yes
Permissible ambient temperature
Operation °C –25/+75 –25/+75 –25/+75
Storage °C –40/+70 –40/+70 –40/+70
Permissible load up to 40 °C A 1000 2000 4000
at rear horizontal main up to 55 °C A 1000 2000 3640
circuit connections up to 60 °C A 1000 2000 3500
(Cu painted black) up to 70 °C A 1000 1950 3250
Power loss at In
with AC symmetrical load
Withdrawable circuit-breaker
Operating times
W 280 770 1640 5
Make-time ms 35 35 35
Break-time ms 34 34 34
Electr. make-time (via closing solenoid)1) ms 100 100 100
Electr. break-time (via shunt release) ms 73 73 73
Electr. break-time (instantaneous undervoltage release) ms 73 73 73
Service life3)
mechanical (without maintenance) Operating cycles 10 000 10 000 10 000
mechanical (with maintenance)2) Operating cycles 15 000 15 000 15 000
electrical (without maintenance) Operating cycles 6 000 6000 4000
1000 V design Operating cycles 1 000 1 000 1 000
electrical (with maintenance)2) Operating cycles 15 000 15 000 15 000
Operating frequency
600 V design 1/h 60 60 60
1000 V design 1/h 20 20 20
3 0 ° 3 0 °
D h max.

Service position 3 0 ° 3 0 °
= 1 mm

and/
or
N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2 NSE00927

Degree of protection IP20 without cabinet door, IP30 with door mounting frame,
IP55 with cover
Auxiliary conductors (Cu) Standard connection = strain-relief clamp
Max. no. of without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16); 1 × 2.5 mm2 (AWG 14)
auxiliary conductors × cross- with end sleeve to DIN 46228 Part 2 1 × 0.5 mm2 (AWG 20) ... 1 × 1.5 mm2 (AWG 16)
section (solid/stranded) with twin end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
optional connection = tension spring
without end sleeve 2 × 0.5 mm2 (AWG 20) ... 2 × 2.5 mm2 (AWG 14)
with end sleeve to DIN 46228 Part 2 2 × 0.5 mm2 (AWG 20) ... 2 × 1.5 mm2 (AWG 16)
Weights 3-pole Fixed-mounted circuit-breaker kg 56 56 64
Withdrawable circuit-breaker kg 60 60 68
Guide frames kg 31 31 45
4-pole Fixed-mounted circuit-breaker kg 67 67 77
Withdrawable circuit-breaker kg 72 72 82
Guide frames kg 37 37 54
1) Make-time via closing solenoid for synchronization purposes 3) Further technical specifications on request.
(short-time excited) 50 ms.
2) Maintenance means: replace main contact elements and arc chutes (see
Operator's Guide).

Short-circuit breaking capacity


Size II
Type 3WL12
Switching capacity class DC
up to DC 300 V Icc kA 30
up to DC 600 V Icc kA 25
up to DC 1000 V Icc kA 20
Rated short-time withstand current Icw
0.5 s kA –
1s kA 301)/252)/203)
2s kA –
3s kA –
1) at Ue = DC 300 V. 3) at Ue = DC 1000 V.
2) at Ue = DC 600 V.
Siemens LV 30 · 2004 5/77
Non-Automatic Circuit-Breakers for DC, up to 4000 A,
SENTRON WL
3- and 4-pole, fixed-mounted design

■ Selection and ordering data


Size Max. rated circuit- 3-pole non-automatic PS* Weight 4-pole non-automatic PS* Weight
breaker current circuit-breakers per PU circuit-breakers per PU
In max. Order No. approx. Order No. approx.
A DT Order No. supplements kg DT Order No. supplements kg
see Page 5/36 see Page 5/36
Horizontal main circuit connection
II 1000 B 3WL12 10-8@@32-.... 1 unit 56.000 B 3WL12 10-8@@42-.... 1 unit 67.000
II 2000 B 3WL12 20-8@@32-.... 1 unit 56.000 B 3WL12 20-8@@42-.... 1 unit 67.000
II 40001) B 3WL12 40-8@@32-.... 1 unit 64.000 B 3WL12 40-8@@42-.... 1 unit 77.000
Vertical main circuit connection
II 1000 B 3WL12 10-8@@31-.... 1 unit 56.000 B 3WL12 10-8@@41-.... 1 unit 75.000
II 2000 B 3WL12 20-8@@31-.... 1 unit 56.000 B 3WL12 20-8@@41-.... 1 unit 75.000
II 40001) B 3WL12 40-8@@31-.... 1 unit 64.000 B 3WL12 40-8@@41-.... 1 unit 77.000
Front main circuit connection, single hole
II 1000 B 3WL12 10-8@@33-.... 1 unit 56.000 B 3WL12 10-8@@43-.... 1 unit 67.000
II 2000 B 3WL12 20-8@@33-.... 1 unit 56.000 B 3WL12 20-8@@43-.... 1 unit 67.000
Front main circuit connection, double hole
II 1000 B 3WL12 10-8@@34-.... 1 unit 56.000 B 3WL12 10-8@@44-.... 1 unit 67.000
II 2000 B 3WL12 20-8@@34-.... 1 unit 56.000 B 3WL12 20-8@@44-.... 1 unit 67.000
Non-automatic circuit-breakers2) Order No. supplements Order No. supplements

5 without electronic trip unit AA


Standard Order No. supplements (for further Order No. supplements see Page 5/36)
AA

Manual operating mechanism with 1AA2 1AA2


mechanical closing

Rated voltage DC 1000 V: order with "–Z" and order code "A05".
All other accessory parts must be ordered with "–Z" and order
codes, see "Circuit-breakers/non-automatic circuit-breakers up
to 6300 A, SENTRON WL", "Options", Page 5/36 onwards.

1) Provisons to dissipate heat must be made on the line side.


2) For permissible short-time current rating Icw and short-circuit switching
capacity Icc for non-automatic circuit-breakers, see Page 5/77.

5/78 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Non-Automatic Circuit-Breakers for DC, up to 4000 A,
SENTRON WL
3- and 4-pole, withdrawable design

Size Max. rated circuit- 3-pole non-automatic PS* Weight 4-pole non-automatic PS* Weight
breaker current circuit-breakers per PU circuit-breakers per PU
In max. Order No. approx. Order No. approx.
A DT Order No. supplements kg DT Order No. supplements kg
see Page 5/36 see Page 5/36
Without guide frame (for guide frames see Page 5/80)
II 1000 B 3WL12 10-8@@35-.... 1 unit 60.000 B 3WL12 10-8@@45-.... 1 unit 75.000
II 2000 B 3WL12 20-8@@35-.... 1 unit 60.000 B 3WL12 20-8@@45-.... 1 unit 75.000
II 40001) B 3WL12 40-8@@35-.... 1 unit 68.000 B 3WL12 40-8@@45-.... 1 unit 82.000
With guide frame, horizontal main circuit connection
II 1000 B 3WL12 10-8@@36-.... 1 unit 91.000 B 3WL12 10-8@@46-.... 1 unit 109.000
II 2000 B 3WL12 20-8@@36-.... 1 unit 91.000 B 3WL12 20-8@@46-.... 1 unit 109.000
II 40001) B 3WL12 40-8@@36-.... 1 unit 113.000 B 3WL12 40-8@@46-.... 1 unit 136.000
With guide frame, vertical main circuit connection
II 1000 B 3WL12 10-8@@37-.... 1 unit 91.000 B 3WL12 10-8@@47-.... 1 unit 109.000
II 2000 B 3WL12 20-8@@37-.... 1 unit 91.000 B 3WL12 20-8@@47-.... 1 unit 109.000
II 40001) B 3WL12 40-8@@37-.... 1 unit 113.000 B 3WL12 40-8@@47-.... 1 unit 136.000
With guide frame, connecting flange
II 1000 B 3WL12 10-8@@38-.... 1 unit 91.000 B 3WL12 10-8@@48-.... 1 unit 109.000
II 2000 B 3WL12 20-8@@38-.... 1 unit 91.000 B 3WL12 20-8@@48-.... 1 unit 109.000
II 40001) B 3WL12 40-8@@38-.... 1 unit 113.000 B 3WL12 40-8@@48-.... 1 unit 136.000

5
Non-automatic circuit-breakers2) Order No. supplements Order No. supplements
without electronic trip unit AA AA
Standard Order No. supplements (for further Order No. supplements see Page 5/36)
Manual operating mechanism with 1AA2 1AA2
mechanical closing

Rated voltage DC 1000 V: order with "–Z" and order code "A05".
All other accessory parts must be ordered with "–Z" and order
codes, see "Circuit-breakers/non-automatic circuit-breakers up
to 6300 A, SENTRON WL", "Options", Page 5/36 onwards.

1) Provisons to dissipate heat must be made on the line side.


2) For permissible short-time current rating Icw and short-circuit switching
capacity Icc for non-automatic circuit-breakers, see Page 5/77.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/79


Non-Automatic Circuit-Breakers for DC, up to 4000 A,
SENTRON WL
Accessories/spare parts

■ Selection and ordering data


Guide frames for DC non-automatic circuit-breakers
Size Max. rated circuit- Guide frame for 3-pole PS* Weight Guide frame for 4-pole PS* Weight
breaker current In max non-automatic per PU non-automatic per PU
circuit-breakers approx. circuit-breakers approx.
Order No. Order No.
(Order No. supplements (Order No. supplements
required according to required according to
A DT table below) kg DT table below) kg
Front main circuit connection, single hole
II 2000 B 3WL9 212-3DA@@-@@A 1 1 unit 31.000 B 3WL9 212–3EA@@-@@A 1 1 unit 37.000
Front main circuit connection, double hole
II 2000 B 3WL9 212-3DB@@-@@A 1 1 unit 31.000 B 3WL9 212-3EB@@-@@A 1 1 unit 37.000
Horizontal main circuit connection
II 2000 B 3WL9 212-3DC@@-@@A 1 1 unit 31.000 B 3WL9 212-3EC@@-@@A 1 1 unit 37.000
II 4000 B 3WL9 212-6DC@@-@@A 1 1 unit 60.000 B 3WL9 212-6EC@@-@@A 1 1 unit 84.000
Vertical main circuit connection
II 2000 B 3WL9 212-3DD@@-@@A 1 1 unit 31.000 B 3WL9 212-3ED@@-@@A 1 1 unit 37.000
II 4000 B 3WL9 212-6DD@@-@@A 1 1 unit 60.000 B 3WL9 212-6ED@@-@@A 1 1 unit 84.000
Main circuit connection connecting flange

5 II
II
2000
4000
B
B
3WL9 212-3DE@@-@@A 1
3WL9 212-6DE@@-@@A 1
1 unit
1 unit
31.000
60.000
B
B
3WL9 212-3EE@@-@@A 1
3WL9 212-6EE@@-@@A 1
1 unit
1 unit
37.000
84.000

Number of auxiliary supply connectors


none 0 0
1 connector 1 1
2 connectors 2 2
3 connectors 3 3
4 connectors 4 4
For required number of auxiliary supply
connectors, see table on Page 5/44
Type of auxiliary circuit connections
without 0 0
with SIGUT screw-type terminals 1 1
with tension spring connection 2 2
Position indicator switches
without 0 0

Option 1 1 1
operation 1 changeover,
test 1 changeover,
disconnected 1 changeover
Option 2 2 2
operation 3 changeover,
test 2 changeover,
disconnected 1 changeover
Shutters
without A A

with shutter, 2 parts, lockable B B

Rated voltage DC 1000 V: order with "–Z" and order code "A05".
All other accessory parts must be ordered with "–Z" and order
codes, see "Circuit-breakers/non-automatic circuit-breakers up
to 6300 A, SENTRON WL", "Options", Page 5/39 onwards.

5/80 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Non-Automatic Circuit-Breakers for DC, up to 4000 A,
SENTRON WL
Project planning aids

■ Circuit diagrams
Examples of application
Rated operating Required series for 3-pole non-automatic circuit-breakers for 4-pole non-automatic circuit-breakers
voltage breaks at rated voltage
Operating currents up to 4000 A/ Operating currents up to 4000 A/conducting path
conducting path
up to 300 V + 10 %

1-pole, 2-pole 1-pole, 2-pole


2 parallel conducting 4 parallel conducting paths, 2 parallel conducting
paths, only with grounded-neutral paths
only with grounded neu- system
tral system
over 300 V + 10 %
up to 600 V + 10 %

2-pole,
only with grounded-
neutral system
1-pole,
2 parallel conducting paths,
2-pole
5
only with grounded-neutral
system
over 600 V + 10 %
up to 1000 V + 10 %

1-pole, 2-pole, 1-pole,


only with grounded- only with grounded-neutral only with grounded-neu-
neutral system system tral system

The connection to the circuit-breakers is not dependent on di-


rection and polarity; the circuit diagrams can be adapted
accordingly.
If the parallel or series connections are made directly to the
connecting bars, for thermal reasons the continuous load on the
circuit-breakers must only be 80 % of the permissible operating
current. If the parallel or series connection is made at a distance
of 1 m from the connecting bars, the circuit-breaker can be used
at full operating current load.
] grounded neutral system
@ load
Dimensions as for "Circuit-breakers/non-automatic circuit-break-
ers up to 6300 A, SENTRON WL", Pages 5/60 to 5/67.

Siemens LV 30 · 2004 5/81


Circuit-Breakers up to 3200 A, Discontinued Series

General data

■ Overview

5
1 Withdrawable circuit-breaker 6 ON button, mechanical with sealing cap 12 Guide rails
2 Indication and reset button after 7 OFF button, mechanical 13 Auxiliary circuit plug-in system
tripping for 8 ON button, electrical 14 Crank hole
– tripped signaling switch and 9 Electronic trip unit 15 Hand lever
– mechanical closing lockout 10 Indication of switch position 16 Position indicator switch
3 Spring charge indicator 11 Guide frame 17 Transparent cover
4 Contact position indicator
5 Ready-to-close indicator

Left: 3WN6 circuit-breaker, withdrawable version, size I, 3-pole


Right: 3WN6 circuit-breaker, fixed-mounted version, size I, 3-pole

Motorized operating mechanism Electronic trip unit

5/82 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

General data

■ Benefits ■ Design
Safety and reliability Versions
• High degree of protection with door sealing frame in the case Breaking capacity: 65/80 kA
of exclusively local operation of the circuit-breaker Rated current: 630 to 3200 A
• Incoming supply from above or below, as required Rated operating voltage: AC 690 V
• Locking of the withdrawable circuit-breaker against moving, as The 3WN6 circuit-breakers are supplied complete with an oper-
standard ating mechanism, electronic trip unit and auxiliary switches and
• Locking of the guide frame with the circuit-breaker removed, as are fitted with auxiliary releases.
standard The non-automatic circuit-breakers are supplied without elec-
• Alarm switch for overload and short-circuit tripping with tronic trip unit
mechanical closing lockout
Basic configuration
Easy to operate • Electronic trip unit for overload protection and short-circuit pro-
• Unambiguous ON-OFF indicator with auxiliary switch for signal tection, short-circuit releases also delayed for time-based dis-
• Ready-to-close indicator with alarm switch as safety standard. crimination, with LEDs for the cause of tripping, LED status in-
dicator, query and test button
Modular • Mechanical closing lockout
Many components, such as auxiliary releases, motorized oper- • "Tripped" switch
ating mechanisms, electronic trip units and current transformers
5
• Ready-to-close indicator with alarm switch
can be replaced or retrofitted to adapt the circuit-breaker to
changing requirements. • Auxiliary supply connector: The circuit-breaker is equipped
with the required number of connectors
Communication-capable (see illustration "Communication • Rear horizontal connection of the main conductors
via PROFIBUS DP")
The international standard PROFIBUS DP can be used to trans- Operating mechanisms (see illustration "Motorized operat-
mit data such as current values, switching states, reasons for ing mechanism")
tripping etc. to central computers. This makes it possible not The circuit-breakers are available with various optional operat-
only to monitor the circuit-breakers but also to operate them ing mechanisms:
remotely. • Manual operating mechanism with memory, with mechanical
This supports energy management and significant savings in closing
energy costs.
For further information see also section "Communication-capa- • Manual operating mechanism with mechanical and electrical
ble circuit-breakers". closing
• Motorized operating mechanism that can also be operated
Minimal power loss and therefore low energy consumption manually, with mechanical and electrical closing.
The low power consumption of the electrical components also The operating mechanisms with electrical closing can be used
saves money when it comes to purchasing the control-power for synchronization tasks.
transformers. Where space is at a premium or ventilation is
limited. Electronic trip units (see illustration "Electronic trip unit")

■ Area of application The electronic trip unit is controlled by a microprocessor and op-
erates independently of an external voltage. It enables systems
to be adapted to the different protection requirements of distri-
Specifications bution systems, motors, transformers and generators.
IEC 60947-2, DIN VDE 0660 Part 101,
When the circuit-breakers are used in IT networks that are not
climate-proof to IEC 68 Part 2-30
grounded with converters connected in parallel to a common DC
Approval according to maritime classification
link rail, suitable filter measures must be taken. Please address
see "Annex".
any questions to your regional Siemens contact. For more infor-
Operating conditions mation on electronic trip units see "Electronic trip units" and
"Functions", "Electronic trip units – General description".
The 3WN6 circuit-breakers are climate-proof in accordance with
DIN IEC 68 Part 2-30. EMERGENCY-STOP facility
They are intended for use in enclosed areas where no severe op- The 3WN6 circuit-breakers can be used as an EMERGENCY-
erating conditions (e.g. dust, corrosive vapors, damaging STOP facility to DIN VDE 0113 if the circuit-breaker is equipped
gases) are present. with an undervoltage release and is used in conjunction with an
EMERGENCY-STOP control device.
When installed in dusty or damp areas, suitable enclosures must
be provided. If damaging gases (e.g. hydrogen sulfide) are Auxiliary and alarm switches
present in the surrounding air, sufficient incoming fresh air must • Ready-to-close
be supplied. If all the conditions are fulfilled, so that the circuit-breaker is
The permissible ambient temperatures and the associated rated ready to close, this is indicated visually on the operator panel
currents are listed in the technical specifications. as well as by means of an indicator switch (S7).
• Contact position-independent auxiliary switches
The circuit-breakers are supplied with 2 NO and 2 NC contacts
or with 2 NO and 2 NC and 2 CO contacts according to order.

Siemens LV 30 · 2004 5/83


Circuit-Breakers up to 3200 A, Discontinued Series

General data

S IM A T IC H M I
S IM A T IC S 5 /S 7 v is u a liz a tio n

D P /3 W N 6
E T 2 0 0 X in te rfa c e a n d 3 U F S S IM O C O D E -D P
d is tr ib u te d 3 W N 6 c ir c u it- m o to r p r o te c tio n
S 7 -3 0 0 M A S T E R D R IV E I/O d e v ic e b re a k e r a n d c o n tr o l d e v ic e

D P /A S -In te rfa c e
g a te w a y

S ig n a llin g
c o lu m n
M M M
3 3 3

A N S E 0 _ 0 1 1 2 5

C o m p a c t
s ta rte r
M o d u le s in IP 6 7 in IP 6 5
B E R O p r o x im ity s w itc h

5
S IG N U M a c tu a to rs M
3

Communication via PROFIBUS DP

• "Tripped" switch and mechanical closing lockout Withdrawable circuit-breaker


As standard, the circuit-breaker is equipped with an S11 alarm The withdrawable version comprises a withdrawable circuit-
switch and a mechanical closing lockout for the common over- breaker, a guide frame and a hand crank for moving the with-
load and short-circuit signal and, depending on the setting and drawable circuit-breaker. The guide frames are fitted with guide
version of the electronic trip unit, the ground-fault signal. rails as standard for easy handling of the withdrawable circuit-
The tripped signal and the standard mechanical mechanism to breaker.
prevent closing remain active until the reset button is operated
on the circuit-breaker. When the circuit-breaker has tripped, • Auxiliary supply connections
this is indicated by the protruding reset button. The auxiliary supply connections make contact automatically
If the circuit-breaker has to be ready to close immediately after when the circuit-breaker slides into the guide frame (test posi-
tripping, an automatic mechanical reset mechanism is avail- tion, connected position).
able, but this does not reset the electrical signal from the • Switch positions in the guide frame
"tripped" switch S11. The "tripped" signal then has to be reset The withdrawable version has three switch positions in the
by operating the Reset button. switchgear cabinet behind the cabinet door:
The electronic trip unit offers a further option to display the - Connected position
cause for tripping (see trip unit, under "Functions", "Electronic (main circuit and auxiliary circuit ready)
trip unit – General description"). - Test position
(main circuit disconnected, auxiliary circuit ready)
Fixed-mounted and withdrawable version - Disconnected position
Fixed-mounted and withdrawable circuit-breakers (main circuit and auxiliary circuit disconnected)
• Protective measures against arcing gases In the disconnected position, the withdrawable circuit-breaker
For 3WN6 circuit-breakers with voltages up to AC 415 V, complies with the "isolation condition" with a visible isolating dis-
screening from vertical busbars is not necessary. tance in the main circuit and auxiliary circuit.
In the case of voltages up to AC 690 V, the arc chute cover The circuit-breaker must always be switched off before it is
(accessory) can be used to protect against flashover. moved. The "OFF" button must be held down when the slide in
Electrical add-on devices on the side of the circuit-breaker the crank hole is opened.
must be separately covered. Also see notes under "Project
planning aids", "Dimension drawings".
• Operator panel
The operator panel is designed to protrude from a cutout in the
door providing access to all operator controls and displays
with the door closed.
• Door sealing frame
The door sealing frame seals the cabinet door with the operator
panel. With the cabinet door closed, the IP degree of protection
is achieved for the circuit-breaker.

5/84 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

General data
Guide frames
Closing of the crank hole is only possible in the circuit-breaker
positions (connected, test or disconnected position). The circuit-
breaker position is shown on a display on the circuit-breaker.
The circuit-breaker is moved with the help of a hand crank. The
connected position as well as the disconnected position is
achieved by moving the circuit-breaker to the end stop.
• Position indicator switches
The position indicator switches are operated by the withdraw-
able circuit-breaker via an additional mechanical device. Apart
Fixed-mounted circuit-breakers
from indicating the position, they also indicate that the circuit-
breaker is present in the guide frame. This version is suitable Main circuit termi- Main circuit termi- Main circuit terminals
nals rear, nals accessible accessible from front,
for interlock circuits including other protective devices. horizontal from front, double hole at top and
• Shutters (standard) single hole at top bottom, holes in
Inadvertent touching of live main contacts or busbars is pre- and bottom accordance with
DIN 43673
vented by covering with a shutter. The shutter is constructed in
two parts and allows the upper or lower connection areas to be
opened separately for the purpose of checking that they are
not live. The divided shutter can be interlocked in the open or
closed position and two padlocks can be fitted.

5
• Coding unit
To prevent circuit-breakers of the same size but of different de-
signs being mixed up in a switchgear cabinet, the withdraw-
able circuit-breakers and guide frames can be equipped with
a coding device. The coding device provides coding protec-
tion for up to 35 circuit-breakers.
Withdrawable circuit-breakers
The circuit-breakers in the withdrawable version are factory-
Rear, Rear Terminal accessible
fitted with a rated current coding as standard. horizontal vertical terminal from front at top and
This prevents a withdrawable circuit-breaker being used in a connections with at top and bottom bottom, holes in
guide frame that has a different rated current. guide rails accordance with
(standard) DIN 43673, double
• Blocking mechanisms hole. Single hole:
Fixed-mounted circuit-breakers: shorter bar
To protect the operating personnel and the switchgear, the
fixed-mounted circuit-breakers can be fitted with a locking Main circuit connections
mechanism that prevents the switchgear cabinet door being
opened when the circuit-breaker is closed.
Withdrawable version:
For the protection of the operating personnel and the switch- Position
gear, the withdrawable versions can be equipped with the indicating
following locking devices: switch
- Blocking device to prevent opening of the cabinet door, ac-
tive in the connected position.
- Blocking device to prevent closing with the cabinet door Guide
Shutter
rail
open, active in the connected position.
- Blocking mechanism against movement with the cabinet
door open
If the cabinet door is opened, the manual crank used to move
the circuit-breaker cannot be positioned.
• Blocking mechanism against insertion of the withdrawable
circuit-breaker
The guide rails can be interlocked with one slide each and
locked with two padlocks.
• Blocking mechanism against moving the withdrawable circuit-
breaker Guide frame
A padlock prevents access to the crank hole and application
of the crank (max. shackle diameter: 8 mm; possible with all
versions) or the same can be achieved with an additionally
available safety lock (see "Functions", "Opening, closing and
locking devices").

Locking device to prevent insertion of the withdrawable circuit-breaker

Siemens LV 30 · 2004 5/85


Circuit-Breakers up to 3200 A, Discontinued Series

General data
Electronic trip units

Electronic trip unit version B "azn" Electronic trip unit version E/F "aznNg"

Electronic trip unit version J/K "aznNg" Electronic trip unit version P "aznNg";
Electronic trip unit version N "aznN" without ground-fault release

5/86 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

General data

■ Functions
Electronic trip units - General description
The new generation of solid-state microprocessor-based elec-
tronic trip units
Overload protection ("a")
Inverse-time delayed overload release for overload protection of load
feeders and cables.

N S E 0 _ 0 1 1 2 6

Selective short-circuit delayed short-circuit protection ("z")

5
N S E 0 _ 0 1 1 2 7

Instantaneous short-circuit protection ("n")

N S E 0 _ 0 1 1 2 8

Ground-fault protection ("g") Electronic trip units - versions B and N


For sensing of fault currents that flow to ground and that can cause fire in
the plant.
In all electronic trip units, the following functions are included as
standard:
• Integrated function test
The test button can be used to test the electronic trip unit
using an integrated test function with or without tripping of the
N S E 0 _ 0 1 1 2 9 circuit-breaker (the solid-state trip unit, trip solenoid and
breaker mechanism are tested).
• Active LED
Correct operation of the electronic trip unit is indicated by the
"heartbeat" of a green flashing LED.
When the operating current exceeds the response threshold of
the overload protection, this is indicated by rapid flashing.
• Cause of tripping
The cause of tripping can be queried locally and displayed
(by pressing the "Query" button).
• µP faults
A microprocessor fault is signaled by a warning indicator
(also optionally via an optocoupler as well).
• Overtemperature
If the temperature in the electronic trip unit exceeds 85 °C, this
is indicated by an LED (also optionally via an optocoupler).

Indication on electronic trip unit


version N

Siemens LV 30 · 2004 5/87


Circuit-Breakers up to 3200 A, Discontinued Series

General data
Comprehensive additional functions – in accordance with the - Direct acquisition of the ground-fault current by means of a
design of the electronic trip unit, e.g.: current transformer in the grounded neutral point of the trans-
former. The current transformer is installed directly into the
grounded neutral point of the transformer.
L 1
L 2
3 W N 6
L 3
N S E 0 _ 0 1 1 3 0
2 N
• Short time-delay short-circuit release with I t-dependent delay
for improved discrimination to the downstream fuses
T 6
• Short-circuit protection with "Zone Selective Interlocking" for P E
significant reduction of the stress and damage in a distribution N S E 0 _ 0 1 1 3 2

system thanks to short delay times.


Three-pole circuit-breakers, current transformers in the grounded
• Load shedding/load receiving neutral point of the transformer.
• Communication via PROFIBUS DP Electronic trip unit version Current transformer T6 must be con-
• LCD operating current display nected to auxiliary current connec-
tion
Ground-fault protection • C, E, J, P 400.13
• Description 400.14
Ground-fault releases "g" sense fault currents that flow to
ground and that can cause fire in the plant. Multiple circuit-
5 breakers connected in series can have their delay times ad-
justed so as to provide graduated discrimination.
3 W N 6
L 1
L 2
L 3
When setting the parameters for the electronic trip unit it is pos-
sible to choose between "Alarm on detection" and "Trip circuit- N
breaker on detection".
T 6
The reason for tripping is indicated by means of an LED when
P E
the query button is activated.
• Measurement methods N S E 0 _ 0 1 1 3 3

- Vectorial summation formation with current transformer in


Four-pole circuit-breakers, current transformers in the grounded neutral
neutral conductor point of the transformer (connection as for three-pole circuit-breakers)
The neutral conductor current is measured directly and is
evaluated for neutral conductor overload protection. Additional functions 1
The electronic trip unit determines the ground-fault current by • External DC 24 V supply
means of vectorial summation current formation for the three e.g. for parameterization (i.e. setting the protection parameters
phase currents and the N-conductor current. and additional functions), activation of operating current indi-
cation (version D, E/F, H, J/K, N/P) if no load current is flowing
L 1
L 2
in the main circuits.
3 W N 6
L 3 • µP-fault
N The alarm LED is activated for all versions if the microproces-
T 5 P E sor is faulty. For the additional functions 1 and 2, a signal can
N S E 0 _ 0 1 1 3 1 also be issued via the optical coupler. The circuit-breaker is not
tripped in this case. However, the protection function is se-
Three-pole circuit-breakers, current transformers in the neutral
conductor cured by means of a redundant bypass.
Electronic trip unit version Current transformer T5 must be con-
• Temperature alarm
nected to auxiliary current connec- If the temperature in the electronic trip unit exceeds the limit
tion value of 85 °C, this is indicated by means of an LED. For the
• C, D, E, H, J 400.13 additional functions 1 and 2, a signal can also be issued via the
400.14 optical coupler.
• N, P 300.1 Additional functions 2
300.2
• External DC 24 V power supply
(see additional functions 1)
For 4-pole circuit-breakers, the fourth current transformer for • µP fault
the N-conductor is installed internally, for the electronic trip (see additional functions 1)
unit version E and J it must be mounted externally to the in- • Temperature alarm
coming or outgoing feeder side. (see additional functions 1)
Electronic trip unit version Current transformer T5 must be • Leading signal "a" trip
connected to auxiliary current
connection The leading signal (via optical coupler) for the overload trip is
used to deactivate the downstream thyristor control devices.
• E, J 400.13
400.14 The overload tripping operation is then performed after
200 ms.

5/88 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

General data
• Load monitoring Short-circuit protection with Zone Selective Interlocking
Load monitoring is adjustable via two selectable operating val-
ues for load receiving and load shedding (IAW1, IAW2) and a The Zone Selective Interlocking function permits full discrimina-
common delay time (td, AW). tion for the very short delay time of tzsi = 50 ms regardless of the
number of staggered levels and location of the short-circuit in
• "g" alarm the distribution system.
Signal via optical coupler on ground fault Reduction of the break time reduces the stress and damage that
• Zone Selective Interlocking can occur in a distribution system considerably.
(see short-circuit protection with Zone Selective Interlocking If the Zone Selective Interlocking function is set and a short-cir-
"ZSI"). cuit occurs, every circuit-breaker through which the short-circuit
flows interrogates the next circuit-breaker immediately down-
Hand-held device stream for presence of the short-circuit current in the next lower
• Description staggered level.
The hand-held device is connected to the electronic trip unit by
means of a connecting lead and a snap-on power supply
adapter. A DC 24 V power supply can be connected to the
adapter to activate the trip unit. This hand-held device can also
be used for the communication-capable motor protection and Q 1 1
control device 3UF5 (SIMOCODE-DP) for configuration and K 3
operation.
• Functions Q 2 1 Q 2 2
Reading and writing the protection parameters for electronic
K 2

5
trip unit versions H, J/K, N, and P.
Connecting and setting operating values for the additional
functions of the electronic trip unit versions D, E/F, H, J/K, N,
Q 3 1 Q 3 2 Q 3 3
and P.
The settings read out from the trip unit can be temporarily

N S E 0 _ 0 1 1 3 4
stored in the hand-held device and written to a different elec- Q 4 1
tronic trip unit. K 1
M

Hand-held device

Siemens LV 30 · 2004 5/89


Circuit-Breakers up to 3200 A, Discontinued Series

General data
Functional overview of the electronic trip unit system
Function

Basic functions
Overload protection Inverse-time delayed Adjustment of the current setting Ir from 40 % to 100 % In
overload release "a" Graduation 5 %
for the phases Graduation freely programmable
a
c Time-lag class Tc = opening time at 6 × Ir, setting Tc
Thermal image
"Phase-failure sensitivity" (reversible)
N S E 0 _ 0 1 1 3 6
for the neutral conductor1) Adjustment of the current setting In
Time-lag class Tc of the neutral conductor as for the phases
Short-circuit protection Short-time delayed Setting the operating current Id
short-circuit release "z"
Setting the delay time td
z With I2td-dependent delay, delay time td
Instantaneous short-circuit Setting the operating current Ii
N S E 0 _ 0 1 1 3 5
release "n"

5
n
N S E 0 0 1 1 3 7

Ground-fault protection Ground-fault release "g"1) Setting the operating current Ig

Setting the delay time tg


With I2tg-dependent delay, delay time tg
g

N S E 0 0 1 1 3 8
LCD display Operating current indication
LED display Status indication Flashing LED when electronic trip unit activated
"Tripped" indication "a" release
"z/n" release
"z" release
"n" release
"N" release N
"g" release/alarm
Alarm indication µP fault
θ, temperature > 85 °C
phase unbalance
O p t freely assignable indication
Test Internal self-test and display via LED
Connection of the test device to test connector X3
Basic configuration
Signal by Ready-to-close Circuit-breaker can be safely closed
signaling switch (1 NO) "Tripped" switch Latching; active after "a", "z", "n", "g"2) release
with/without mechanical closing lockout
Additional function
Signal via Additional functions 1 External DC 24 V supply (e.g. for parameterization), current input 250 mA
optocoupler outputs µP fault
θ, temperature > 85 °C
linked with phase unbalance
Additional functions 2 External DC 24 V supply (e.g. for parameterization), current input 250 mA
µP fault
θ, temperature > 85 °C
linked with phase unbalance
Leading signal "a" release (200 ms to release)/load shedding
Load monitoring; operating value 50 to 150 %, 1 to 15 s
"g" alarm
Zone Selective Interlocking between 3WN and 3WS
Communication via PROFIBUS DP
Data transmission Communication module in conjunction with additional functions 2 and interface DP/3WN6
Data transmission and Measurement module in conjunction with additional functions 2 and interface DP/3WN6
measured-value acquisition

All specified delay times are minimum non-release times 1) With 3-pole circuit-breakers a current transformer is required in addition if
(circuit-breaker opening time approx. 20 ms). there is asymmetrical loading of the phases. In the case of 4-pole circuit-
breakers a current transformer in the neutral conductor is fitted internally in
the circuit-breaker (exception: electronic trip units E and J). For current
transformers to be ordered separately see Page 5/108.

5/90 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

General data

Electronic trip unit V "zn" B "azn" C/G "aznNg" D "aznN" E/F "aznNg" H "aznN" J/K "aznNg" N "aznN" P "aznNg"
version (r 10th pos. 7 7
of Order No.)

4 4 4 4 4 4
4 4
10 s3) 10 s3) 2–30 s 2–30 s 2–30 s 2–30 s 2–30 s 2–30 s
4 4 4 4q 4 4
✕ x x x 4 4 4 4
50 or 50 or 50 or 20–100 % 20–100 % 20–100 % 20–100 %
100 % 100 % 100 %
1.25–12×Ir 1.5–12×Ir 1.25–12×Ir 1.25–12×Ir 1.25–12×Ir 0.5–12×In 0.5–12×In 1.25 × Ir – 40 kA 1.25 × Ir – 40 kA
Ir =40–100 % In
0; 20–500 ms 0; 20–400 ms 0; 20–400 ms 20–400 ms 20–400 ms 20–4000 ms4) 20–4000 ms4) 20–400 ms 20–400 ms
80–300 ms 80–300 ms 80–300 ms 80–300 ms 80–300 ms 80–300 ms
>15×In >15×In >15×In >1.5–12×In >1.5–12×In >1.5–12×In >1.5–12×In Size I: Size I:
and Ii =∞ with Ii =∞ with Ii =∞ with Ii =∞ up to 50 kA up to 50 kA
with setting with setting with setting with setting Size II: Size II:
Ii =∞ then Ii =∞ then Ii =∞ then Ii =∞ then up to 65 kA up to 65 kA
Icu =Ics =Icw Icu =Ics =Icw Icu =Ics =Icw Icu =Ics =Icw
(lowest value
decisive)
(lowest value
decisive)
(lowest value
decisive)
(lowest value
decisive) 5
0.2–0.6×In 0.2–0.6×In 20 % In 20 % In
up to 1200 A up to 1200 A
100–500 ms 100–500 ms 100–500 ms 100–500 ms
100–500 ms 100–500 ms 100–500 ms

4 4 4 4
4 4 4 4 4 4 4 4 4
4 4 4 4 4 4 4 4
4 4 4
4 4 4 4 4 4
4 4 4 4 4 4
4 4 4 4 4 4 4
4 4 4 4
4 4 4 4 4 4 4 4 4
4 4
4 4
47 47 47 47 4 4
4 4 4 4 4 4 4 4 4
4 4 4 4 4 4 4 4 4

4 4 4 4 4 4 4 4 4
4 4 4 4 4 4 4 4 4

x x x x 4 4
x x x x x x
x x x x x x
x7 x7 x7 x7 x x
x x x x 4 4
x x x x x x
x ✕ ✕ ✕ ✕ x
x7 x7 x7 x7 ✕ x
x7 ✕7 x7 x7 x x
x7 x7 x7 x7 x x
x x x
x x x x x x

x x x x x x
x x

2) "g" release occurs with "Trip" setting on the electronic trip unit. 4 Function available as standard
3) Where there is heavy starting of motors, the time setting Tc = 10 s may not x Function optional (additional cost)
be sufficient: use version D, E/F, H, J/K or P. 7 Deselect/set function with hand-held device
4) For td > 500 ms: Icu = Icw = Ics (lowest value decisive) and Id automatically Function active when td is set to 20 ms
limited to 15 kA. ✕ Available with electronic trip unit B only from date of manufacture 02.96

Siemens LV 30 · 2004 5/91


Circuit-Breakers up to 3200 A, Discontinued Series

General data
Communication module (Z = F01) The following signal and protection functions for tripping are
• The electronic trip units are internally equipped with an addi- available:
tional communication module for communication via • Asymmetrical phase for voltage and current
PROFIBUS DP (in this case please use the prefix Z with the • Undercurrent/overcurrent
Order Number i.e. Z=F01). The data are transferred over a 3 m
plug-in connection (included in scope of supply) to an external • Underfrequency/overfrequency
DP/3WN6 interface. This converts the data for PROFIBUS DP. • Reversed flow of energy
The following useful data are available depending on the ver-
sion and accessories of the circuit-breaker: The data can also be displayed locally by the electronic trip unit.
- Analog measured values: The voltage transformers for the measurement module must be
Phase currents IL1, IL2, IL3, Imax and Imin, mounted externally. They are mounted on a 35 mm mounting rail.
N-conductor current IN The voltage transformers are included in the scope of supply of
Ground-fault current Ig the measurement module.
- Event signals: The measurement module cannot be retrofitted.
Type of previous tripping operation (a, z, n, g, N),
µP fault, Opening, closing and locking devices
temperature alarm, • ON and OFF buttons
phase symmetry, - Mechanical ON button
load shedding, load receiving, overload In the standard version, the mechanical ON button is a push-
- Operating states: button. In operating mechanisms with electrical closing, the
Switch on/off, mechanical ON button is fitted with a sealing cap. As an al-
ready indication, ternative to a pushbutton, a safety lock (CES, BKS, IKON) can

5 status of the voltage/undercurrent release,


storage spring loaded,
position (test and connected position)
also be supplied.
If the key is removed in the "0" position, it is no longer possible
to close the circuit-breaker mechanically.
of the withdrawable circuit-breaker, - "Electrical ON" button
test of the electronic trip unit The "electrical ON" button is intended for normal activation
- Remote configuration during service. External electrical interlocks can be imple-
- Read out configuration data: mented easily using the "electrical ON" button. A sealing cap
Settings for the protection functions is available for the "electrical ON" button.
- Rated current for the circuit-breaker, - Mechanical OFF button
number of poles, In the standard version, the mechanical OFF button is a push-
identification code for circuit-breaker button. An additional sealing cap secures the button against
- Diagnostics data: unauthorized operation.
Average current for previous fifteen minutes
- Remote control: As an alternative to the OFF button, the following are avail-
To open and close the circuit-breaker provided that it is able:
equipped with electrical querying and a shunt release. - Safety lock
• Remote configuration The key can be removed in the OFF position to ensure that the
The additional functions and protection functions can be set circuit-breaker cannot be closed mechanically. The same key
via the bus. The electronic trip unit checks whether the values can then be used to unlock another circuit-breaker.
for the protection parameters are valid and within range. - EMERGENCY-STOP button
This mushroom button latches in the OFF position when it is
Measurement module (Z = F05) pressed and prevents the circuit-breaker closing until the
The electronic trip unit versions N and P can be also be latching is reset by rotating the mushroom button.
equipped with a measurement module (please quote the follow- - Locking device against closing
ing Order No. when ordering: Z=F05 instead of Z=F01). The A flap of the locking device covers the "electrical ON" button
measurement module consists of the communication module and continuously depresses the "mechanical OFF" button.
with additional measurement functions and external voltage The locking device can be secured with up to 4 padlocks.
transformers. In this way, the voltage and frequency are ac-
quired in addition to the current values, which makes the follow-
ing additional operating values available:
• Voltage UactL, UmaxL, UminL
(15-minute value for max. and min.)
ULL1, ULL2, ULL3 (conductor/conductor voltage)
• Frequency fact, fmax, fmin
(15-minute value for max. and min.)
• Power factor
• Active power P
• Reactive power Q
• Apparent power S
• Active work W
• Direction of phase rotation.
These values can be used for energy management by switching
loads on/off to avoid expensive load peaks.

5/92 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

General data
- CASTELL, FORTRESS or KIRK-KEY lock
These locking devices are supplied with a mounting set. The
lock must be ordered from the manufacturer of the locks.
When the lock is activated, the circuit-breaker is locked
against closing.
The disconnection condition is fulfilled in the OFF position. An
additional access block with a flap for CASTELL, FORTRESS
and KIRK-KEY locks prevents insertion of the key. This device
can be locked with up to four padlocks.
• Locking device against moving the withdrawable circuit-
breaker
Access to the crank hole and application of the crank is pre-
vented by means of one or more padlocks. An additional safety
lock which can be supplied on request also prevents access to
the crank hole in position I (key can be removed). This also pre-
vents movement of the withdrawable circuit-breaker in the
guide frame.
• Locking device in the cabinet door
A safety lock which is fixed to the cabinet door prevents the
circuit-breaker from closing. Interlocking is only effective in the
connected position in the case of withdrawable circuit-break-
ers. The signal is transmitted via a Bowden wire.
For locking mechanisms please refer to "Installation", "Guide
frames". 5
• Transparent cover over electronic trip unit
The standard transparent cover can be sealed. The configura-
tion sections are covered to prevent unauthorized access.
Openings allow access to the query and test button. A hinged
flap covers the whole operator panel of the electronic trip unit.
• Motor switch
An additional motor switch can deactivate automatic loading of
the storage spring on closing. This means that the control sup-
ply does not need to be switched off for maintenance mea-
sures to the circuit-breaker.
• Operating cycles counter
A five-digit operating cycles counter is available for the 3WN6
circuit-breakers. The display is incremented by "1" as soon as
the storage spring is fully loaded.
• Auxiliary release
Up to two auxiliary releases can be installed at the same time.
The following are available: 1 Operating cycles counter
2 Transparent cover over electronic trip unit
1 shunt release 3 Motor switch
or 1 undervoltage release 4 Sealing cap for mechanical ON button
or 2 shunt releases 5 EMERGENCY-STOP button instead of the OFF button
or 1 shunt release 6 Safety lock to prevent opening of the crank hole
+ 1 undervoltage release 7 Padlock to prevent opening of the crank hole
8 Safety lock instead of the mechanical ON button
The shunt release "f" has been designed for permanent excita- 9 Locking device for mechanical OFF button and
tion. This means that it is also possible to block the circuit- electrical ON button
breaker against being jogged into closing. 10 Installation location for CASTELL, FORTRESS, or KIRK-KEY lock
An energy storage device for shunt releases allows the circuit-
breaker to be opened even if the control voltage is no longer Opening, closing and locking devices
available.
The undervoltage release "r" is available without delay as stan-
dard (jumper-selectable to 100 ms by customer).
In addition, the undervoltage release "rc" with a delay in the
range from 0.2 to 3.2 s is available.
For further information on the selection, ordering and project
engineering of communication-capable circuit-breakers, refer to
section 3 "Communication-capable circuit-breakers" and the
manual "Communication links for 3VF, 3WN6, 3WN1/3WS1
circuit-breakers to PROFIBUS DP"
Order No. E20001-P285-A644-V1.

Undervoltage release "rc" with delay for mounting


in 3WN6 circuit-breaker

Siemens LV 30 · 2004 5/93


Circuit-Breakers up to 3200 A, Discontinued Series

General data
Module for mutual mechanical interlocking
The module for mutual mechanical interlocking can be used for
one or two 3WN6 circuit-breakers and can be adapted easily to
the corresponding versions.
The fixed-mounted and withdrawable circuit-breaker versions
are fully compatible and can therefore be used in a mixed con-
figuration in an installation.
The circuit-breakers can be mounted alongside each other or
one above the other, whereby the spacing of the circuit-breakers
is determined solely by the length of the Bowden cable. The
Bowden cables are supplied in standard lengths of 2 m. Inter-
lock signals are looped through via the Bowden cables. Inter-
locking is only effective in the connected position in the case of
withdrawable circuit-breakers.
The mechanical lifetime of the Bowden cables is 10,000 operat-
ing cycles. 3WN6 circuit-breaker, 4-pole, with interlocking module and Bowden wire
The interlocking module is mounted on the right-hand side of the
fixed-mounted circuit-breaker (see illustration) or the guide
frame.

Interlocking module with Bowden wire

Example Version Switch status Description


1 A B 2 circuit-breakers alongside each other:
G 0 0 One circuit-breaker can only be closed when the other has been switched off.
1 0 Each circuit-breaker has an interlocking module and a Bowden wire.
N S E 0 _ 0 1 1 3 9

A B 0 1

2 A B C 3 circuit-breakers one above the other:


N S E 0 _ 0 1 1 4 0

0 0 0 Any two circuit-breakers can always be closed, with the third one being interlocked.
1 0 0 Each circuit-breaker has an interlocking module and a Bowden wire.
A C 0 1 0 An additional Bowden wire must be ordered separately for each circuit-breaker.
B
0 0 1
1 1 0
0 1 1
1 0 1
3 A B C 3 circuit-breakers one above the other:
N S E 0 _ 0 1 1 4 1

0 0 0 When one circuit-breaker is closed the other two circuit-breakers cannot be closed.
1 0 0 The interlocking mechanism of each circuit-breaker consists of an interlocking module and a
0 1 0 Bowden wire. An additional Bowden wire must be ordered separately for each circuit-breaker.
0 0 1
A B C

4 A1 B A2 3 circuit-breakers alongside each other:


G 0 0 0 Two circuit-breakers can be closed and opened independently of each other,
while the third is only ready to close when the two others are open.
N S E 0 _ 0 1 1 4 2

1 0 0
A 1 B A 2 0 0 1 If the third circuit-breaker is closed, the other two circuit-breakers cannot be closed. All three
1 0 1 circuit-breakers each have an interlocking module and a Bowden wire. A Bowden wire must
0 1 0 be ordered separately.

5/94 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

General data
Transfer control device
The transfer control device allows automatic network switcho-
vers from a standard-network supply to an emergency-network
supply. Standard and emergency-network supply:
AC 380/400 V
A transformer is generally used for standard-network supplies.
The emergency-network supply is usually provided by a gener-
ator or transformer.
The transfer control device monitors the infeed side of both cir-
cuit-breakers. If the standard-network supply fails, the emer-
gency network is switched on automatically. When the standard-
network returns, it is also reactivated automatically.
The switchover requires two circuit-breakers with the basic
configuration
3WN6 _ _ _- _ _ _ 58 - 1KA _
(the blank spaces can be configured as required) and one trans- Transfer control device
fer control device 3WX36 66-7JA00.
The transfer control device can be mounted to the wall or
installed in the control cabinet. It can be installed in the control
cabinet without an enclosure.
The transfer control device can be used to implement automatic
network switchovers to IEC 60947-6-1. N e tw o r k - s w itc h in g
5
c o n tr o l u n it
G
The two 3WN6 circuit-breakers must be mutually interlocked for
this purpose. (See "Accessories/spare parts", "For fixed-
mounted and withdrawable circuit-breakers", "Mutual mechani-
cal interlocking".)
3 W N 6 3 W N 6

A N S E 0 _ 0 1 1 4 3

0 0 0 0

A U T A U T A U T A U T

0 M a in n e tw o r k A U T O M A T IC B a c k -u p n e tw o rk

M a in o r b a c k - u p n e tw o r k a v a ila b le M a in n e tw o r k a v a ila b le M a in n e tw o r k a v a ila b le B a c k - u p n e tw o r k a v a ila b le

Q N : O F F Q G : O F F Q N : O N Q G : O F F Q N : O N Q G : O F F Q N : O F F Q G : O N

M a in n e tw o r k fa ils a n d b a c k - u p M a in n e tw o r k fa ils a n d b a c k - u p R e tu r n to m a in n e tw o r k
n e tw o r k is a v a ila b le n e tw o r k is a v a ila b le

Q N : O N Q G : O F F Q N : O F F Q G : O N
D e la y ³ T 1 ?

(1 ,5 to 3 0 s ) N o B a c k - u p n e t w o r k f a ils
R e tu r n to m a in n e tw o r k

Y e s
Q N : O N Q G : O F F Q N : O F F Q G : O N
Q N : O F F Q G : O N
A N S E 0 _ 0 1 1 4 4

R e tu r n to m a in n e tw o r k

D e la y ³ T 1 ?

(2 to 1 0 0 s ) N o

Y e s

Q N : O N Q G : O F F

Mode of operation of the transfer control device

Siemens LV 30 · 2004 5/95


Circuit-Breakers up to 3200 A, Discontinued Series

General data

■ Technical specifications
Size I II
Type 3WN6 0 3WN6 2 3WN6 4 3WN6 5 3WN6 6 3WN6 7
Rated current In at 55 °C, Main conductor A 630 1000 1600 2000 2500 3200
at 50/60 Hz Neutral conductor A 630 1000 1600 2000 2500 3200
(only on 4-pole vers.)
Rated operating voltage Ue AC V up to 690
at 50/60 Hz
Rated impulse Main circuits7) kV 8
withstand voltage Uimp Auxiliary circuits kV 4
Utilization category B
Rated short-circuit up to AC 415 V kA 143 176
making capacity Icm up to AC 500 V kA 143 176
(peak value) up to AC 690 V kA 110 110
Rated service short-circuit up to AC 415 V kA 65 80
breaking capacity Ics up to AC 500 V kA 65 80
(rms value) up to AC 690 V kA 50 50
Rated ultimate short-circuit up to AC 415 V kA 65 80
breaking capacity Icu up to AC 500 V kA 65 80
(rms value) up to AC 690 V kA 50 50
Permissible ambient temperatures Operation °C –20 ... +70

5
Storage °C –40 ... +80
Rated short-time withstand current Icw 0.5 s kA 50 50 65
at 50/60 Hz 1s kA 35/501) 50 65
2s kA 25/301) 30 60
3s kA 20/251) 25 50
4s kA 17/201) 20 40
Permissible load up to 55 °C A 630 1000 1600 2000 2500 3200
for fixed-mounted and withdrawable circuit- at 60 °C A 630 1000 1600 2000 2350 2860
2 3 4
breakers at cabinet interior temperature ) ) ) at 70 °C A 630 1000 1530 2000 2330 2650
Rated rotor operating voltage Uer V 2000
Power loss at In Fixed-mounted cir.-br. W 40 90 140 170 260 420
with 3-phase symmetr. load Withdrawable circuit- W 80 205 310 310 510 760
(without line-side busbars and metal breaker including
components2)4) guide frame
Service life
with maintenance5) mechanical Op. 20000 20000
electrical cycles 20000 20000
without maintenance5) mechanical Op. 10000 10000
electrical6) cycles 6000 2000
Operating frequency 1/min 1
Minimum interval ms 80
between tripping operation by electronic trip unit and next making
operation of the circuit-breaker (only with automatic mechanical
resetting of the lockout device)
Service position 3 0 ° 3 0 ° 3 0 ° 3 0 °
and/
or
N S E 0 _ 0 0 0 6 1 N S E 0 _ 0 0 0 6 2

Degree of protection Circuit-breaker IP20, when fitted in cabinet or frame


Operator panel with door sealing frame IP54
Main conductor Copper bars, bare Qty. 1 × 2× 2× 2× 3× 3×
minimum cross-sections mm2 50 × 10 40 × 10 60 × 10 100 × 10 100 × 10 100 × 10
Copper bars, painted black Qty. 1 × 1× 2× 2× 2× 3×
mm2 40 × 10 60 × 10 50 × 10 80 × 10 100 × 10 100 × 10
2
Auxiliary conductors (Cu) Max. no. of solid and 1 × 0.5 ... 2.5 mm ; 1 × AWG 14
aux. conduc- finely stranded with 2 ×1.0 mm2
tors × cross- end sleeves
section
Weights 3-pole Fixed-mounted circuit-breaker 34 34 36 57 59 61
circuit- approx. kg
breakers Withdrawable circuit-breaker 36 36 38 59 61 63
approx. kg
Guide frame approx. kg 22 22 23 35 37 37
4-pole Fixed-mounted circuit-breaker 47 47 49 70 72 74
circuit- approx. kg
breakers Withdrawable circuit-breaker 49 49 51 72 74 76
approx. kg
Guide frame approx. kg 27 27 28 46 48 48
1) Figures apply to circuit-breakers with order code "K03", see "Options". 4) These values apply in the case of sinusoidal current (50/60 Hz). The heat-
2) For fixed-mounted circuit-breakers with horizontal connection, for with- ing/losses increase in the event of harmonics and higher frequencies.
drawable circuit-breakers with vert. conn., see manual for 3WN6 circuit- 5) Maintenance: replacement of the contact set.
breakers. 6) Per contact set. Disconnect. of the rated current In and power factor = 0.8.
3) The temperatures apply to the air surrounding the upper third of the circuit- 7) Rated insulation voltage Ui = AC 1000 V.
breaker.

5/96 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

General data

Operating mechanisms
Manual operating mechanism with memory, with mechanical closing
Closing Max. force required to operate the hand lever N 210
Charging stored- Required number of strokes on the hand lever 5
energy feature
Manual operating mechanism with mechanical and electrical closing
Charging stored- see "Manual operating mechanism with stored-energy
energy feature feature with mechanical closing"
Closing Operating range 0.7 ... 1.1 × Us
solenoid (Y1) Extended operating range for battery operation1) for DC 24 V, DC 48 V, 0.7 ... 1.26 × Us
DC 60 V, DC 110 V,
DC 220 V
Power input AC/DC VA/W 15
Minimum command duration at Us for the activation ms 60
solenoid
Total closing time at Us after start of
closing command for the activation solenoid,
suitable for synchronizing tasks ms 80
Short-circuit protection
Smallest permissible DIAZED fuse (operational class 1 A TDz (time-lag)/1 A
gL)/miniature circuit-breaker with C-characteristic
Manual/motor operating mechanism with mechanical and electrical closing
Manual operating
mechanism
see "Manual operating mechanism with stored-energy
feature with mechanical closing" 5
Motor Operating range 0.7 ... 1.1 × Us
Extended operating range for battery operation1) for DC 24 V, DC 48 V, 0.7 ... 1.26 × Us
DC 60 V, DC 110 V,
DC 220 V
Power input to motor AC/DC VA/W 40
Time required to charge the stored-energy mechanism 1 × Us s 20
Closing see "Manual operating mechanism with stored-energy
solenoid feature with mechanical and electrical closing"
Short-circuit protection
Motor and activation solenoid for the same rated control supply voltages:
For motor and Smallest permissible DIAZED fuse (operational class at Us = 24 V 2 A TDz (time-lag)/2 A
closing solenoid gL)/miniature circuit-breaker with C-characteristic at Us = 110–127 V 1 A TDz (time-lag)/1 A
at Us = 220–250 V 1 A TDz (time-lag)/1 A
Auxiliary releases
Shunt Operating value pickup ≥ 0.7 × Us (circuit-breaker is tripped)
release "f" Operating range 0.7 ... 1.1 × Us
(F1, F2)
For continuous command (100 % duty ratio),
locks out on momentary-contact commands
Extended operating range for for DC 24 V, DC 30 V, 0.7 ... 1.26 × Us
battery operation1) DC 48 V, DC 60 V,
DC 110 V, DC 220 V
Rated control supply voltage Us AC 50/60 Hz V 110–127, 220–240
DC V 24,48, 60, 110–125, 220–250
Power input AC/DC VA/W 15
Minimum command duration at Us ms 60
Opening time of circuit-breaker at AC/DC ms ≤ 80
Us = 100 %
Short-circuit protection
Smallest permissible DIAZED fuse (operational class 1 A TDz (time-lag)/1 A
gL)/miniature circuit-breaker with C-characteristic
With Rated control supply AC 50/60 Hz V 110–127, 220–240
stored energy voltage Us DC V 110–125, 220–250
feature consist- Operating range 0.85 ... 1.1 × Us
ing of
f release and Power input AC/DC VA/W 1
3WX31 56-1J.01 Storage time2) at Us/recharging time3) at Us max. 5 min/min. 5 s
storage device
Opening time of circuit-breaker, short-circuit protection as with "for continuous command"
1) The operating range is only permissible for the specified rated voltages
and corresponds to the battery charging voltage.
2) Storage time = maximum time after which tripping by the shunt release is
still assured after loss of the auxiliary voltage supply. The precondition for
this is that the stored energy feature was fully charged.
3) Recharging time = minimum time for recharging the stored energy feature
after tripping by the shunt release.

Siemens LV 30 · 2004 5/97


Circuit-Breakers up to 3200 A, Discontinued Series

General data

Auxiliary releases
Undervoltage Operating values pickup ≥ 0.85 × Us (circuit-breaker can be closed)
release "r" (F3) and dropout (0.35 ... 0.7) × Us (circuit-breaker is tripped)
"rc" (F8) Operating range 0.85 ... 1.1 × Us
Extended operating range in battery for DC 24 V, DC 30 V, 0.7 ... 1.26 × Us
operation1) DC 48 V, DC 60 V,
DC 110 V, DC 220 V
Rated control supply voltage Us AC 50/60 Hz V 110–127, 220–240, 380–415
DC V 24, 48, 60, 110–125, 220–250
Power input AC VA 15
DC W 15
Opening time of circuit-breaker at Us = 0
Design "r" (F3)
Instantaneous ms ≤ 100
With 100 ms delay ms ≤ 300
Design "rc" (F8)
With delay, td = 0.2 ... 3.2 s s 0.2 ... 3.2
Reset via additional NC contact – direct switching-off
ms ≤ 100
Short-circuit protection
Smallest permissible DIAZED fuse (operational class gL) 1 A TDz (time-lag)1 A
/miniature circuit-breaker with C-characteristic

5 Contact position-driven auxiliary switches (S1, S2, S3, S4)


Rated insulation voltage Ui AC/DC V 400 V
Rated operating voltage Ue 400 V
Switching capacity AC, 50/60 Hz Rated operating voltage Ue V up to 24 110 220/230 380/400
Rated operating current Ie/AC-12 A 10 10 10 10
Rated operating current Ie/AC-15 A 6 6 6 4
DC Rated operating voltage Ue V 24 48 110 220
Rated operating current Ie/DC-12 A 10 8 3.5 1
Rated operating current Ie/DC-13 A 10 4 1.2 0.4
Short-circuit protection2) Largest permissible DIAZED fuse (operational class gL/gG) 10 A TDz, 16 A Dz
Largest permissible miniature circuit-breaker with C-characteristic 10 A
Ready-to-close signaling switch (S7) and "tripped" signaling switch (S11), to DIN VDE 0630
Switching capacity AC, 50/60 Hz Rated operating voltage Ue V 10 220
Rated operating current Ie A 0.14 0.1
DC Rated operating voltage Ue V 24 220
Rated operating current Ie A 0.2 0.1
Short-circuit Largest permissible DIAZED fuse (operational class gL) 2 A Dz (quick)
protection2)
Tripped" signaling switch (S11) Signal duration after tripping continuous, until reset
1) The operating range is only permissible for the specified rated voltages
and corresponds to the battery charging voltage.
2) Without any welding of the contacts only at Ik ≤ 1 kA in accordance with
DIN VDE 0660 Part 200.

5/98 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

General data
T

Electronic trip unit signals


Electronic trip unit µP fault, ϑ alarm, leading tripped signaling "a",
signals via optocou- "g" alarm, Zone Selective Interlocking, load monitoring.
pler After activation of the electronic trip unit it sends a sig-
nal (contactless) via optocoupler.
Max. rated operating voltage Ue DC V 24
Max. rated operating current Ue DC mA 20
Measuring accuracy of the electronic trip unit Protection functions to EN 60947; current indication
and communication function (F01): ± 5 %;
measurement function (F05): ± 3 %
Position indicator switch on guide frame
Type of contact Signal: "Circuit-breaker in connected position" 3 NO + 3 NC 1 NO + 1 NC
"Circuit-breaker in test position" 2 NO + 2 NC or 1 NO + 1 NC
"Circuit-breaker in disconnected position" 1 NO + 1 NC 1 NO + 1 NC
Rated insulation voltage Ui AC/DC V 400 (415)
Rated operating voltage Ue V AC 240/DC 230
Switching capacity Rated operating current Ie Ie/AC-1 A 8 up to AC 240 V
Ie/AC-15 A 3 up to AC 240 V
Ie/DC-13 A 10/DC 24 V; 5/DC 48 V; 1.5/DC 115 V; 0.6/DC 230 V
Short-circuit Largest permissible DIAZED fuse (operational class gL) 8 A TDz (slow)
protection1) Largest permissible miniature circuit-breaker with 8A
C-characteristic

5
Transfer control device
Degree of protection IP40
Weight approx. 10 kg
Voltage deviation 0 ... 0.55 × Ue
Frequency deviation not monitored
Contact transfer time 200 ms + T1 adjustable (1.5 s ... 30 s)
Switchover time 200 ms
Return transfer time 200 ms + T2 adjustable (5 s ... 100 s)
Break-time 65 ms
Ambient temperature –25 ... +55 °C
Storage temperature –50 ... +80 °C
1) Without any welding of the contacts only at Ik ≤ 1 kA in accordance with
DIN VDE 0660 Part 200.

Siemens LV 30 · 2004 5/99


Circuit-Breakers up to 3200 A, Discontinued Series

3-pole, fixed-mounted design

■ Selection and ordering data


Version DT Order No. PS* Weight per
PU approx.
Rated operating voltage Ue up to AC 690 V 3 WN 6 7 7 1 – 7 7 7 7 7 – 7 7 7 7 kg

Size/ Size Rated current In Adjustment range of


rated current In setting current Ir
I 630 A 252– 630 A A 0 D 1 unit 47.000
1000 A 400–1000 A A 2 F 1 unit 34.000
1600 A 640–1600 A A 4 H 1 unit 36.000
II 2000 A 800–2000 A A 5 J 1 unit 57.000
2500 A 1000–2500 A A 6 K 1 unit 59.000
3200 A 1280–3200 A A 7 M 1 unit 61.000
Installation type Main terminals see Page 5/85
Fixed mounted Main terminals, rear, horizontal (standard) 6
Main connections accessible from front, 3
single hole at top and bottom
up to 1000 A
1250 A, 1600 A
2000 A

5 2500 A, 3200 A
Main terminals accessible from front, double hole at top and 2
bottom, holes in accordance with DIN 43673
up to 1000 A
1250 A, 1600 A
2000 A
2500 A, 3200 A
Electronic Version V "zn" 0 V
trip units Version B "azn" 0 B
(see
functional Version C "aznNg"1) 0 C
overview, Version D "aznN"1)
Page 5/90)
Basic functions with LCD display 1 D
Basic functions and additional functions 2
7 D
with LCD display
Version E "aznNg"1)
Basic functions with LCD display 1 E
Basic functions and additional functions 2
7 E
with LCD display
Version H "aznN"1)2)
Basic functions and additional functions 2 7 H
Version J "aznNg"1)2)
Basic functions and additional functions 2 7 J
Version N "aznN"1)
Basic functions and additional functions 2 7 N
Version P "aznNg"1)
Basic functions and additional functions 2 7 P
Circuit-breakers also available with rated short-time withstand current 11th to
Icw = 50 kA/1 s, see Page 5/105. 16th positions
of the Order
No. see Page
5/104.
1) Current transformers for overload protection in the neutral conductor and
current transformers for ground-fault protection must be ordered sepa-
rately, see Page 5/108.
2) A hand-held device or the Win3WN6 software is required for operation.

5/100 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers up to 3200 A, Discontinued Series

3-pole, withdrawable design

Version DT Order No. PS* Weight per


PU approx.
Rated operating voltage Ue up to AC 690 V 3 WN 6 7 7 1 – 7 7 7 7 7 – 7 7 7 7 kg

Size/ Size Rated current In Adjustment range of


rated current setting current Ir
In I 630 A 252– 630 A A 0 D 1 unit 49.000
1000 A 400–1000 A A 2 F 1 unit 36.000
1600 A 640–1600 A A 4 H 1 unit 38.000
II 2000 A 800–2000 A A 5 J 1 unit 59.000
2500 A 1000–2500 A A 6 K 1 unit 61.000
3200 A 1280–3200 A A 7 M 1 unit 63.000
Installation type Main terminals see Page 5/85 Additional weight for
guide frame
Withdrawable Withdrawable circuit-breaker without guide frame 7 without
design Withdrawable circuit-breaker with guide frame 8
Other Standard design: rear,
versions of the horizontal terminals with guide rails
guide frame up to 1000 A 27.000
see Page 5/110. 1250 A, 1600 A 23.000
2000 A 35.000
2500 A
3200 A
37.000
37.000 5
Electronic Version V "zn" 0 V
trip units Version B "azn" 0 B
(see
functional Version C "aznNg"1) 0 C
overview, Version D "aznN"1)
Page 5/90)
Basic functions with LCD display 1 D
Basic functions and additional functions 2
7 D
with LCD display
"1
Version E "aznNg )
Basic functions with LCD display 1 E
Basic functions and additional functions 2
7 E
with LCD display
"1 2
Version H "aznN ) )
Basic functions and additional functions 2 7 H
Version J "aznNg"1)2)
Basic functions and additional functions 2 7 J
Version N "aznN"1)
Basic functions and additional functions 2 7 N
Version P "aznNg"1)
Basic functions and additional functions 2 7 P
Circuit-breakers also available with rated short-time withstand current 11th to
Icw = 50 kA/1 s, see Page 5/105. 16th positions
of the Order
No. see Page
5/104.
1) Transformers for overload protection in the neutral conductor and trans-
formers for ground-fault protection must be ordered separately, see
Page 5/108.
2) A hand-held device or the Win3WN6 software is required for operation.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/101


Circuit-Breakers up to 3200 A, Discontinued Series

4-pole, fixed-mounted design

Version DT Order No. PS* Weight per


PU approx.
Rated operating voltage Ue up to AC 690 V 3 WN 6 7 7 3 – 7 7 7 7 7 – 7 7 7 7 kg

Size/ Size Rated current In Adjustment range of


rated current In setting current Ir
I 630 A 252– 630 A A 0 D 1 unit 47.000
1000 A 400–1000 A A 2 F 1 unit 47.000
1600 A 640–1600 A A 4 H 1 unit 49.000
II 2000 A 800–2000 A A 5 J 1 unit 70.000
2500 A 1000–2500 A A 6 K 1 unit 72.000
3200 A 1280–3200 A A 7 M 1 unit 74.000
Installation type Main terminals see Page 5/85
Fixed mounted Main terminals, rear, horizontal (standard) 6
Main connections accessible from front, 3
single hole at top and bottom
up to 1000 A
1250 A, 1600 A
2000 A
2500 A, 3200 A

5
Main terminals accessible from front, double hole at top and 2
bottom, holes in accordance with DIN 43673
up to 1000 A
1250 A, 1600 A
2000 A
2500 A, 3200 A
Electronic Version V "zn" 0 V
trip units Version B "azn" 0 B
(see
functional Version G "aznNg"1) 0 G
overview, Version D "aznN"1)
Page 5/90)
Basic functions with LCD display 1 D
Basic functions and additional functions 2
7 D
with LCD display
Version E "aznNg"2)
Basic functions with LCD display 1 E
Basic functions and additional functions 2
7 E
with LCD display
Version F "aznNg"1)
Basic functions with LCD display 1 F
Basic functions and additional functions 2
7 F
with LCD display
Version H "aznN"1)4)
Basic functions and additional functions 2 7 H
Version J "aznNg"2)4)
Basic functions and additional functions 2 7 J
Version K "aznNg"1)4)
Basic functions and additional functions 2 7 K
Version N "aznN"1)
Basic functions and additional functions 2 7 N
Version P "aznNg"1)3)
Basic functions and additional functions 2 7 P
Circuit-breakers also available with rated short-time withstand current 11th to
Icw = 50 kA/1 s, see Page 5/105. 16th positions
of the Order
No. see Page
5/104.
1) 4th current transformer is already fitted in the neutral conductor of the cir-
cuit-breaker.
2) Current transformers for overload protection in the neutral conductor and
current transformers for ground-fault protection must be ordered sepa-
rately, see Page 5/108.
3) The current transformer mounted in the star point of the transformer must
be ordered separately, see Page 5/108.
4) A hand-held device or the Win3WN6 software is required for operation.

5/102 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers up to 3200 A, Discontinued Series

4-pole, withdrawable design

Version DT Order No. PS* Weight per


PU approx.
Rated operating voltage Ue up to AC 690 V 3 WN 6 7 7 3 – 7 7 7 7 7 – 7 7 7 7 kg

Size/ Size Rated current In Adjustment range of


rated current In setting current Ir
I 630 A 252– 630 A A 0 D 1 unit 49.000
1000 A 400–1000 A A 2 F 1 unit 49.000
1600 A 640–1600 A A 4 H 1 unit 51.000
II 2000 A 800–2000 A A 5 J 1 unit 72.000
2500 A 1000–2500 A A 6 K 1 unit 74.000
3200 A 1280–3200 A A 7 M 1 unit 76.000
Installation type Main terminals see Page 5/85 Additional weight for
guide frame
Withdrawable Withdrawable circuit-breaker without guide frame 7 without
design Withdrawable circuit-breaker with guide frame 8
Other Standard design: Rear,
versions of the horizontal terminals with guide rails
guide frame up to 1000 A 27.000
see Page 5/110. 1250 A, 1600 A 28.000
2000 A 46.000

5
2500 A 48.000
3200 A 48.000
Electronic Version V "zn" 0 V
trip units Version B "azn" 0 B
(see
functional Version G "aznNg"1) 0 G
overview, Version D "aznN"1)
Page 5/90)
Basic functions with LCD display 1 D
Basic functions and additional functions 2
7 D
with LCD display
Version E "aznNg"2)
Basic functions with LCD display 1 E
Basic functions and additional functions 2
7 E
with LCD display
Version F "aznNg"1)
Basic functions with LCD display 1 F
Basic functions and additional functions 2
7 F
with LCD display
"1 4
Version H "aznN ) )
Basic functions and additional functions 2 7 H
Version J "aznNg"2)4)
Basic functions and additional functions 2 7 J
Version K "aznNg"1)4)
Basic functions and additional functions 2 7 K
Version N "aznN"1)
Basic functions and additional functions 2 7 N
Version P "aznNg"1)3)
Basic functions and additional functions 2 7 P
Circuit-breakers also available with rated short-time withstand current 11th to
Icw = 50 kA/1 s, see Page 5/105. 16th positions
of the Order
No. see Page
5/104.
1) 4th transformer is already fitted in the neutral conductor of the circuit-
breaker.
2) Transformers for overload protection in the neutral conductor and trans-
formers for ground-fault protection must be ordered separately, see
Page 5/108.
3) The current transformer mounted in the star point of the transformer must
be ordered separately, see Page 5/108.
4) A hand-held device or the Win3WN6 software is required for operation.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/103


Circuit-Breakers up to 3200 A, Discontinued Series

Options

■ Selection and ordering data


Version Order No.

3 WN 6 7 7 1 – 7 7 7 7 7 – 7 7 7 7

Operating Manual operating mechanism with stored-energy feature, with


0 5
mechanism mech. closing
Manual operating mechanism with mechanical and electrical
closing
Activation solenoid
AC 50/60 Hz V DC V
24 24 1 1
48 48 1 4
– 60 1 5
110–127 110–125 1 6
220–240 220–250 1 8
Manual/motor-operated mechanism with stored-energy
M feature with mechanical and electrical closing
Motor Closing
AC 50/60 Hz V DC V AC 50/60 Hz V DC V
– 24 24 24 5 1

5 –

48
60
48

48
60
5 4
5 5
110–127 110–125 – 24 7 1
110–127 110–125 – 48 7 4
110–127 110–125 – 60 7 5
110–127 110–125 110–127 110–125 5 6
110–127 110–125 220–240 220–250 7 8
220–240 220–250 – 24 8 1
220–240 220–250 – 48 8 4
220–240 220–250 – 60 8 5
220–240 220–250 110–127 110–125 8 6
220–240 220–250 220–240 220–250 5 8
1st auxiliary Without 1st auxiliary release 0A
release Shunt release "f", F1
AC 50/60 Hz V DC V
24 24 1 B
U – 30 1 E
48 48 1 F
– 60 1 G
110–127 110–125 1H
220–240 220–250 1K
Undervoltage release "r", F3
(instantaneous 0 ms, short-delay 200 ms)
AC 50/60 Hz V DC V
– 24 3 B
U< – 30 3 E
– 48 3 F
– 60 3 G
110–127 110–125 3H
220–240 220–250 3K
380–415 – 3M
Undervoltage release "rc", F8
(can be delayed 0.2 to 3.2 s)
AC 50/60 Hz V DC V
U < ,t 110–127 – 4H
220–240 – 4K
380–415 – 4M
2nd auxiliary Without 2nd auxiliary release A
release Shunt release "f", F2
AC 50/60 Hz V DC V
24 24 B
– 30 E
48 48 F
– 60 G
110–127 110–125 H
220–240 220–250 K
Auxiliary switch 1st auxiliary switch block
2 NO + 2 NC 1
1st + 2nd auxiliary switch block
2 NO + 2 NC + 2 CO 3

5th to 10th positions


of the Order No.
see Pages 5/100 to 5/103.

5/104 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

Options

When ordering circuit-breakers in the following versions: Order Order No. with "–Z"
Add "–Z" to the complete Order No. and code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
3WN6 . . . – . . . . . – . . . . – Z
indicate the appropriate order code(s).
and additional order code(s)
#+. . . + . . .
Code for
"Further versions"–Z
For fixed-mounted and withdrawable circuit-breakers

bus
Communication
module3)
for electronic trip unit versions
D, E/F, H, J/H, N and P
áÒÓ #
I Additionally required:
additional functions 2,
interface DP/3WN6 "3RK10 00"
(see Page 5/109)

bus
Measurement
module3)
for electronic trip unit versions N and P. The mea- áÒÃ
surement module consists of the communication #
I,U,cos module with additional measurement functions
and external voltage transformers (see Page
5/123), additionally required: additional functions
2, interface DP/3WN6 "3RK10 00"
(see Page 5/109)
Automatic mechanical reset
of the lockout device after overcurrent tripping
æÒÓ #
#
5
Rated short-time Rated current of the circuit-breaker

Icw
æÒÕ
withstand 630 A,
current Icw 800 A,
50 kA/1 s 1000 A
at AC 50/60 Hz (see
Technical specifica- 3-pole circuit-breaker
tions on Page 5/96). 4-pole circuit-breaker
Trip
"Tripped" signaling switch
1 CO instead of 1 NO (1 NO = standard)
æÒÙ #
00035 With 5-digit
operating cycles counter
ÂÒÓ #
Motor switch on
operator panel
only in the case of circuit-breakers with
motor/manual operating mechanism with
îÓÕ #
stored-energy feature (S9)

With locking with 3SB1 Made by CES îÒÓ


device safety lock Normal lock No. SSG 10
for the actuating instead of the
button or OFF button2)
Made by IKON
Normal lock No. 360012 K1
îÒÕ #
EMERGENCY- (key removable
STOP button in OFF position)
Special closure with locking device îÔÒ
see Accessories for max. 4 padlocks
Page 5/112. (shackle diameter 4 ... 8 mm)
with EMERGENCY-STOP button (self-latching) îÓÔ
instead of the OFF button
with 3SB1 Made by CES îÒÃ
safety lock Normal lock no. SSG 10
instead of the
mechanically
Made by IKON
Normal lock no. 360012 K1
îÒÙ #
acting
ON button with
sealing cap
(key removable
in non-actuated
position)
Mounting set for FORTRESS lock1)
Interlock to be obtained from the manufacturer of
îÓÖ #
the locks
FORTRESS lock (H31LH/65°/standard)
Mounting set for CASTELL lock1)
Interlock to be obtained from the manufacturer of
îÓÃ #
the locks CASTELL lock (FS 2)
Mounting set for KIRK-KEY lock1) îÓØ #

0
With sealing cap Cannot be combined with safety lock
over OFF button
îÔÓ #
to prevent unautho-
rized opening
With sealing cap over "electrical ON" button
to prevent unauthorized closing
îÔÔ #

1) Locks must be ordered from the manufacturer.


2) This makes mechanical or electrical ON commands ineffective.
3) See also section on "Communication-capable circuit-breakers".

Siemens LV 30 · 2004 5/105


Circuit-Breakers up to 3200 A, Discontinued Series

Options

When ordering circuit-breakers in the following versions: Order Order No. with "–Z"
Add "–Z" to the complete Order No.and code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
3WN6 . . . – . . . . . – . . . . – Z
indicate the appropriate order code(s).
and additional order code(s)
#+. . . + . . .
Code for
"Further versions"–Z
For fixed-mounted circuit-breakers
Blocking device to prevent opening of the cabinet door with the
circuit-breaker closed
îÔÃ #
to prevent closing of the circuit-breaker with the îÔÖ
cabinet door open
Mutual mechani-
cal interlock for
Interlock module with a Bowden wire (2 m); when îÃÕ
interlocking three circuit-breakers #
3WN61) circuit- an additional Bowden wire is required,
breaker see Page 5/112.

With locking with safety lock Made by CES îØÓ


device consisting Normal lock no. SSG 10
of lock in the cabi-
net door and inter-
Made by IKON
Normal lock no. 360012 K1
îØÕ #
lock module with
Bowden wire
(1.5 m)

5 to prevent unautho-
rized closing of the
circuit-breaker
Mounting set for CASTELL lock îØÃ
Interlock to be obtained from the lock manufac-
turer CASTELL lock (FS 2)
Mounting set for FORTRESS lock1)
Interlock to be obtained from the lock manufac-
îØÖ #
turer FORTRESS lock (H31LH/AC 65°/standard)
Arc chute
cover2)
up to 1600 A Size I ÂÕÃ #
NSS0_00559

2000 ... 3200 V Size II

For withdrawable circuit-breaker


Locking
device
with safety lock Made by CES
Normal lock no. SSG 10
îÙÓ #
to prevent move-
ment of the with-
drawable circuit-
Made by IKON
Normal lock no. 360012 K1
îÙÕ #
breaker (a safety
lock prevents open-
ing of the crank
Made by Profalux îÙÃ #
hole)
Made by Ronis îÙØ #
1) New technical design since 01 July 1998 (previously order code "S55").
2) Required for protection against flashover at voltages > 415 V.
Not to be used with vertical, front-accessible main circuit connections.

5/106 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

Options

When ordering circuit-breakers in the following versions: Order Order No. with "–Z"
Add "–Z" to the complete Order No. and code 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
3WN6 . 8 . – . . . . . – . . . . – Z
indicate the appropriate order code(s).
Withdrawable and additional order code(s)
circuit-breaker with
guide frame
#+. . . + . . .
Guide frame Order No. with "–Z"
1 2 3 4 5 6 7 8 9 10 11 12
3WX3 6 8 3 – . A . . 0 – Z
and additional order code(s)
#+. . . + . . . + . . .
Code for
"Further versions"–Z
For withdrawable circuit-breakers with guide frame
For guide frames
íÕÛ
Bus connecting
lead for communi-
between guide frame and
connecting lead to interface #
cation (only DP/3WN6, including circuit-breaker
required if guide presence signaling switch
frame is ordered
separately)
up to 1600 A íÒÔ
Main terminal for
rated current
Front-accessible
connection at top and bottom, up to 2000 A #
2 Main terminals see holes in up to 2500 A,
Page 5/85. connecting bars to
DIN 43673 (double hole)
3200 A
5
up to 1600 A íÒÕ
Front-accessible
connection at top and bottom, up to 2000 A #
1 single-hole connecting bars up to 2500 A,
3200 A

Rear up to 1600 A íÒÙ #


vertical terminal up to 2000 A
at top and bottom up to 2500 A,
3200 A
íÓÕ
13 14 With position indi-
cator (actuated by
Connected
position
Test position
1 NO + 1 NC
Discon-
nected posi- íÓÖ #
withdrawable cir- 1 NO + 1 NC 2 NO + 2 NC tion
cuit-breaker) 3 NO + 3 NC 1 NO + 1 NC
1 NO + 1 NC
With shutter, up to 1600 A íÔÒ #
two-part 2000 ... 3200 A

Mutual mechani- Interlock module with a Bowden wire íÃÕ #


cal interlock for (2 m); when interlocking three circuit-breakers an
3WN6 circuit- additional Bowden wire is required, see Page
breaker 5/112.

Locking device with safety lock Made by CES íØÓ


consisting of lock Normal lock No. SSG 10
in the cabinet door Made by IKON íØÕ #
and interlock mod- Normal lock no. 360012 K1
ule with Bowden
wire (1.5 m) to pre- Mounting set for CASTELL lock íØÃ
vent unauthorized Interlock to be obtained from the lock manufacturer
closing of the cir- CASTELL lock (FS 2) #
cuit-breaker, active Mounting set for FORTRESS lock íØÖ
in connected posi- Interlock to be obtained from the lock manufacturer
tion FORTRESS lock (H31LH/
AC 65°/standard)
Locking with safety lock Made by CES íÚÓ
device Normal lock no. SSG 10
to prevent move- Made by IKON íÚÕ
ment of the with- Normal lock no. 360012 K1
drawable circuit-
breaker out of the Made by Profalux íÚÃ
#
disconnected posi-
tion Made by Ronis íÚØ

Blocking device to prevent opening of the cabinet door, íÕÒ


when circuit-breaker is in connected position
íÖÒ
to prevent closing with the cabinet door open
(only active in connected position) #
to prevent movement with the cabinet door open íÃÒ
(active in disconnected, test and connected posi-
tion)
Arc chute
cover1)
up to 1600 A Size I íÕÃ #
NSS0_00559

2000 ... 3200 A Size II

1) Required for protection against flashover.

Siemens LV 30 · 2004 5/107


Circuit-Breakers up to 3200 A, Discontinued Series

Accessories/spare parts

■ Selection and ordering data


For fixed-mounted and withdrawable circuit-breakers
Current transformers for neutral conductor overload protection and ground-fault protection
Only one of the two measuring methods is permissible in conjunction with the electronic trip unit. The overload protection for the neutral con-
ductor takes effect when the current transformer is fitted in the neutral conductor. The ground-fault current is calculated by means of sum-
mation current formation of the phases and the neutral conductor. In the case of electronic trip unit version P, overload protection in the
neutral conductor is achievable with 4 transformers (in L1, L2, L3, N) and ground-fault protection by summation current formation, or with a
5th transformer in the neutral point direct measurement of the ground-fault current and overload protection in the neutral conductor (without
summation current formation).
Type of detection (see Page 5/88) Elec- Primary 5th and 9th posi- Required DT For 1 set PS* Weight
Designation tronic trip rated cur- tions of order or 1 unit per PU
unit ver- rent Order No. for quantity approx.
sion of the circuit-breaker per circuit-
trans- 3WN6@..-.@...-.... breaker
former
Order No. kg
Vectorial summation with current
transformer in the neutral con-
ductor
Current transformers for C, D, E, 315 A 0 A 1 unit C 3WX36 43–1CA00 1 unit on req.
3-pole circuit-breakers H, J 400 A 0 B C 3WX36 43–1CB00 1 unit on req.
500 A 0 C C 3WX36 43–1CC00 1 unit on req.

5
630 A 0 D C 3WX36 43–1CD00 1 unit on req.
315 A 1 E 1 unit C 3WX36 43–1CE00 1 unit on req.
1000 A 2 F C 3WX36 43–1CF00 1 unit on req.
1250 A 3 G C 3WX36 43–1CG00 1 unit on req.
1600 A 4 H C 3WX36 43–1CH00 1 unit on req.
1250 A 5 G 1 unit C 3WX36 43–1FG00 1 unit on req.
1600 A 5 H C 3WX36 43–1FH00 1 unit on req.
2000 A 5 J C 3WX36 43–1FJ00 1 unit on req.
2500 A 6 K C 3WX36 43–1FK00 1 unit on req.
3200 A 7 M C 3WX36 43–1FM00 1 unit on req.
For 4-pole circuit-breakers N, P 630 A 0 D 1 unit C 3WX36 43–2BA00 1 unit 3.000
the fourth current transformer is fitted 800 A 1 E
internally. If electronic trip unit version 1000 A 2 F
E is chosen for 4-pole circuit-break- 1250 A 3 G
ers, the fourth current transformer 1600 A 4 H
must be mounted externally and be 2000 A 5 J 1 unit C 3WX36 43–2FA00 1 unit 3.000
selected from the table opposite. 2500 A 6 K
3200 A 7 M
Direct detection of ground-fault
current by means of a current
transformer in the grounded neu-
tral point of the transformer.
Current transformers for 3- and C, E, P, J 315 A 0 A 1 unit C 3WX36 43–1CA00 1 unit on req.
4-pole circuit-breakers (3-pole); 400 A 0 B C 3WX36 43–1CB00 1 unit on req.
E, P, J 500 A 0 C C 3WX36 43–1CC00 1 unit on req.
(4-pole) 630 A 0 D C 3WX36 43–1CD00 1 unit on req.
800 A 1 E 1 unit C 3WX36 43–1CE00 1 unit on req.
1000 A 2 F C 3WX36 43–1CF00 1 unit on req.
1250 A 3 G C 3WX36 43–1CG00 1 unit on req.
1600 A 4 H C 3WX36 43–1CH00 1 unit on req.
1250 A 5 G 1 unit C 3WX36 43–1FG00 1 unit on req.
1600 A 5 H C 3WX36 43–1FH00 1 unit on req.
2000 A 5 J C 3WX36 43–1FJ00 1 unit on req.
2500 A 6 K C 3WX36 43–1FK00 1 unit on req.
3200 A 7 M C 3WX36 43–1FM00 1 unit on req.
Designation Rated control supply voltage/ Order For 1 set
rated operational voltage quantity or 1 unit
AC 50/60 Hz DC
Storage device 110–127 V 110–115 V 1 unit D 3WX31 56–1JG01 1 unit 0.500
td for shunt release 220–240 V 220–250 V D 3WX31 56–1JJ01 1 unit 0.500
Rated control supply voltage must
match the rated control supply volt-
age of the shunt release
Function tester 110–127/220–240 V – 1 unit A 3WX36 47–5JA01 1 unit 1.300
test for electronic trip unit
for version B, C, D, E, F, G, V, N, P
Also suitable for electronic trip units of
3WN1 and 3WS1 circuit-breakers
Transfer control device 1 unit D 3WX36 66–7JA00 1 unit 11.400
for automatic switchover
between two fixed-mounted or
withdrawable circuit-breakers
(see Page 5/95)
Door sealing frame 1 unit A 3WX36 86–0JA00 1 unit 1.000

5/108 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers up to 3200 A, Discontinued Series

Accessories/spare parts

Designation Order DT For 1 unit PS* Weight


quantity Order No. per PU
approx.
kg
For fixed-mounted and withdrawable circuit-breakers
Interface DP/3WN6 Required once for each communication- 1 unit A 3RK10 00–0JC80–0BA2 1 unit 0.563
capable circuit-breaker

PROFIBUS connector For connecting the interface to 1 unit X 6ES7 972–0BB41–0XA0 1 unit 0.051
PROFIBUS DP

Power supply DC 24 V For interface DP/3WN6 1 unit e.g. 4AV21 02–2EB00–0A,


24 V Current input max. 800 A see Catalog LV10 "Con-
(including electronic trip unit of trolgear and switchgear for
the circuit-breaker) industry", section 13
"SIDAC-S power supplies"
System manual Communication interface of the 1 unit X E20001–P285–A644–V1 1 unit on req.
3VF, 3WN6, 3WN1/3WS1 circuit-breakers
with PROFIBUS DP

Software module Recommended for SIMATIC S5 and S7;


programming aid for handling communi-
cation, 3.5" floppy disks
1 unit A 3RK18 00–0AA00–0AA0 1 unit 0.106
5
Hand-held device For parameterization, operation and 1 unit A 3WX36 47–6JA00 1 unit 1.300
monitoring for 3WN6 circuit-breakers with
electronic trip unit D, E/F, H, J/K, N/P
SET

3 Line adapter for 3WX36 47–6JA00 1 unit A 3WX36 47–6JA01 1 unit 1.300
hand-held device required
4

4 Power supply unit is required if the 1 unit A 3WX36 47–6JA02 1 unit 1.300
3WN6 circuit-breaker does not have an
additional DC 24 V supply

Designation Rated current Size Number Order For 1 set


of poles quantity Order No.
For fixed-mounted circuit-breakers
Support bracket 1 set B 3WX36 81–0JA00 1 set 4.800
including screws for attaching
the fixed-mounted circuit-breaker
Connecting bars up to 1000 A I 3-pole 1 set1) A 3WX36 21–7AA00 1 set 2.000
for vertical connection 4-pole 1 set2) A 3WX36 21–7AB00 1 set 2.700
1250 ... 1600 A I 3-pole 1 set1) A 3WX36 21–7BA00 1 set 4.100
2
4-pole 1 set ) A 3WX36 21–7BB00 1 set 5.400
2000 A II 3-pole 1 set1) A 3WX36 21–7DA00 1 set 5.500
4-pole 1 set2) A 3WX36 21–7DB00 1 set 7.400
2500 ... 3200 A II 3-pole 1 set1) A 3WX36 21–7FA00 1 set 4.800
2
4-pole 1 set ) A 3WX36 21–7FB00 1 set 6.500
1) 1 set = 3 units
2) 1 set = 4 units

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/109


Circuit-Breakers up to 3200 A, Discontinued Series

Accessories/spare parts

Version DT Order No. PS* Weight


per PU
approx.
Guide frame, standard design 3WX 3 6 8 3 – 7 A 7 7 0 kg
3-pole 4-pole

In
Rated 1000 A, size I B 2 1 unit 22.000 27.000
current In 1600 A, size I B 4 1 unit 23.000 24.000
of withdrawable
circuit-breaker 2000 A, size II B 5 1 unit 35.000 46.000
2500 A, size II B 6 1 unit 37.000 48.000
3200 A, size II B 7 1 unit 37.000 48.000

Auxiliary supply 1 auxiliary supply connector B


connectors 2 auxiliary supply connectors C
(see table below for
required quantity) 3 auxiliary supply connectors D
4 auxiliary supply connectors E

Number of poles 3-pole 1


4-pole 3

For other versions such as

5
front connection,
position indicator switch,
shutter see Page 5/107.

Designation Required order DT Order No. PS* Weight


quantity per per PU
circuit-breaker approx.
kg
Coding device 1 set A 3WX36 62–1JC00 1 set 0.200
to prevent mix-up of equal-sized
withdrawable circuit-breakers in a switchboard

The required number of auxiliary supply • operating mechanism type


connectors depends on: • electronic trip unit with/without additional functions with/without current transformer
• type and number of auxiliary releases
• number of auxiliary switches
a First auxiliary supply connector, for standard signals, always required 1
b Operating mechanism

b1 Manual operating mechanism with stored-energy feature, with mechanical closing +0


b2 Manual operating mechanism with mechanical and electrical closing +1
b3 Manual/motor-operated mechanism with stored-energy feature with mechanical and electrical closing +1
c Electronic trip units

c1 with basic functions +0


c2 with additional functions 1 or 2 +2

Connections for external current transformers for overload protection in the neutral conductor and
ground-fault protection

c3 Current transformer installed in the neutral conductor (required with 3-pole circuit-breakers if +1
c2 is not selected)
c4 Current transformer installed in the neutral point of the transformer +1
(required if c2 is not selected)
d Auxiliary releases

d1 without/with 1st auxiliary release (shunt release "f", F1; undervoltage release "r", F3) +0
d2 1st auxiliary release (delayable undervoltage release "rc", F8)
(required if b2 or b3 is not selected) +1
d3 2nd auxiliary release (shunt release "f", F2, required if b2 or b3 is not selected) +1
e Auxiliary switches

e1 1st auxiliary switch block 2 NO + 2 NC +0


e2 1st and 2nd auxiliary switch block 2 NO + 2 NC + 2 CO (required if b2 or b3 or d3 is not +1
selected)
f Communication module or measurement module

f1 without communication module and without measurement module +0


f2 with communication module or measurement module (required if c2 or c3 or c4 is not selected) +2
g "Tripped" signaling switch (S22) and ready-to-close signaling switch, floating

g1 with "tripped" signaling switch (S22) and ready-to-close signaling switch, floating +2
(required if c2 or c3 or c4 or f2 is not selected)
h Total number of auxiliary supply connectors (maximum of 4)

5/110 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers up to 3200 A, Discontinued Series

Accessories/spare parts

When retrofitting, the circuit-breaker Order No. must


be added to the name plate on the operator panel and to the
side wall of the circuit-breaker in accordance with the installation instructions.
Designation Required DT For 1 set PS* Weight
order quan- or 1 unit per PU
tity per cir- approx.
cuit-breaker Order No. kg
For fixed-mounted and withdrawable circuit-breakers
Sealing cap over OFF or ON button to prevent unauthorized opening or 1 unit A 3WX36 63–1JK00 1 unit 0.010
closing
5-digit operating cycles counter 1 unit A 3WX36 64–0CA00 1 unit on req.
00035
Auxiliary release1) Rated control supply
voltage
AC 50/60 Hz DC
V V
Shunt release "f" for – 24 1 unit A 3WX36 51–1JB00 1 unit 0.800
1st and 2nd auxiliary release (F1 and F2) – 30 A 3WX36 51–1JE00 1 unit 0.800
U and closing solenoid (Y1) – 48 A 3WX36 51–1JF00 1 unit 0.800
– 60 A 3WX36 51–1JG00 1 unit 0.800
110–127 110–125 A 3WX36 51–1JH00 1 unit 0.800
220–240 220–250 A 3WX36 51–1JK00 1 unit 0.800

5
Undervoltage release "r" (F3) – 24 1 unit A 3WX36 53–1JB00 1 unit 0.800
instantaneous 0 ms, short-delay 200 ms – 30 A 3WX36 53–1JE00 1 unit 0.500
U< – 48 A 3WX36 53–1JF00 1 unit 0.500
– 60 A 3WX36 53–1JG00 1 unit 0.500
110–127 110–125 A 3WX36 53–1JH00 1 unit 0.800
220–240 220–250 A 3WX36 53–1JK00 1 unit 0.800
380–415 – A 3WX36 53–1JM00 1 unit 0.800
Undervoltage release "rc" 110–127 – 1 unit A 3WX36 54–1JH00 1 unit 0.850
U < ,t (F8) 220–240 – A 3WX36 54–1JK00 1 unit 0.850
can be delayed 0.2 ... 3.2 s 380–415 – A 3WX36 54–1JM00 1 unit 0.850
Auxiliary switches1) 2 CO 1 set A 3WX36 16–1CE00 1 set 0.070
Motorized operating consisting of motor, closing solenoid (Y1),
M mechanism and
electrical closing1)
electrical ON button and wiring

(possible if Rated control supply voltage


11th position of Motor Closing solenoid
Order No. for
circuit-breaker is "0") AC 50/60 Hz DC AC 50/60 Hz DC
V V V V
110–127 110–125 110–127 110–125 1 set A 3WX36 31–1JH00 1 set 2.400
220–240 220–250 220–240 220–250 A 3WX36 31–1JK00 1 set 2.400

Motorized operating Precondition: 11th + consisting of motor and


M mechanism1) 12th positions of Order wiring; rated control supply
(retrofit possible, for No. for circuit-breaker voltage of motor
precondition see table
alongside) 3WN6...-...@@-.... AC 50/60 Hz DC
V V
11 – 24 1 set A 3WX36 32–1JB00 1 set 1.600
14 – 48 A 3WX36 32–1JF00 1 set 1.600
15 – 60 A 3WX36 32–1JG00 1 set 1.600
1 1 110–127 110–125 1 set A 3WX36 32–1JH00 1 set 1.600
1 4
1 5
1 6
1 1 220–240 220–250 1 set A 3WX36 32–1JK00 1 set 1.600
1 4
1 5
1 6
1 8
Electrical closing1) consisting of closing solenoid (Y1),
(possible if electrical ON button and wiring; rated control supply
11th position of voltage of closing solenoid (Y1)
Order No. for AC 50/60 Hz DC
circuit-breaker is "0") V V
– 24 1 set A 3WX36 33–1JB00 1 set 0.800
– 48 A 3WX36 33–1JF00 1 set 0.800
– 60 3WX36 33–1JG00 1 set 0.800
A
110–127 110–125 1 set A 3WX36 33–1JH00 1 set 0.800
2290–240 220–250 A 3WX36 33–1JK00 1 set 0.800

1) When units are retrofitted, the number of auxiliary supply connectors (see
Page 5/110) must be checked. Additionally required auxiliary supply con-
nectors must be ordered as shown on Page 5/113 or 5/114.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/111


Circuit-Breakers up to 3200 A, Discontinued Series

Accessories/spare parts

When retrofitting, the circuit-breaker Order No. must


be added to the name plate on the operator panel and to the
side wall of the circuit-breaker in accordance with the installation instructions.
Designation Required order DT For 1 set PS* Weight
quantity per cir- or 1 unit per PU
cuit-breaker approx.
Order No. kg
For fixed-mounted and withdrawable circuit-breakers
Mutual mechani- An interlock module with a Bowden wire (2 m)
cal interlock for one fixed-mounted circuit-breaker 1 unit A 3WX36 66–3JA00 1 unit 3.000
for 3WN6 circuit- for one withdrawable circuit-breaker4) 1 unit A 3WX36 66–4JA00 1 unit 1.000
breaker Interlocking of three circuit-breakers
additional Bowden wire required for each
circuit-breaker
Bowden wire (2 m) 1 unit A 3WX36 66–8JA00 1 unit 0.200
Bowden wire (3 m) 1 unit A 3WX36 66–8JA01 1 unit 0.500
Bowden wire (4.5 m) A 3WX36 66–8JA02 1 unit on req.
Bowden wire (6 m) A 3WX36 66–8JA03 1 unit on req.
Locking either Safety lock Made by CES 1 unit A 3WX36 63–1JA00 1 unit 0.120
device (3SB1) instead Normal lock no. SSG 10
consisting of of the OFF Made by BKS A 3WX36 63–1JB00 1 unit 0.120
safety locks or button2) Normal lock no. S1
padlocks

5 to prevent unau- Made by IKON A 3WX36 63–1JC00 1 unit 0.120


thorized closing Normal lock no. 360012 K1
of the circuit- or Locking device for max. 4 padlocks 1 unit A 3WX36 63–1JG00 1 unit 0.200
breaker (shackle diameter 4 ... 8 mm)3)
with EMERGENCY-STOP button (self-latching) 1 unit A 3WX36 61–0JA00 1 unit 0.100
instead of the OFF button
Safety lock Made by CES 1 unit A 3WX36 63–2JA00 1 unit 0.120
(3SB1) instead Normal lock no. SSG 1
of the mechani- Made by BKS A 3WX36 63–2JB00 1 unit 0.120
cal ON button2) Normal lock no. S1
Made by IKON A 3WX36 63–2JC00 1 unit 0.120
Normal lock no. 360012 K1
Mounting set5) for CASTELL or 1 set A 3WX36 63–6JE00 1 set 0.100
FORTRESS lock1)
Interlock to be obtained from the lock manu-
facturer CASTELL lock (FS 2) or FORTRESS
lock (H31LH/65°/standard)
Mounting set5) for KIRK-KEY lock1) 1 unit A 3WX36 63–6JE30 1 unit 0.700
Access lock to CASTELL, FORTRESS 1 unit A 3WX36 63–6JE10 1 unit on req.
or KIRK-KEY lock1)
when the key is removed the key opening is
covered; lockable with up to 4 padlocks
1) Locks must be ordered from the manufacturer.
2) Locks with special closure must be ordered according to Catalog LV10
"Controlgear for industry", section 9 "Control and signaling devices".
3) The locking device for padlocks cannot be used together with a safety lock
instead of an OFF button.
4) Can be retrofitted to circuit-breakers supplied after 01 July 1998.
5) The 3WX36 63–6JE locking system meets the isolation conditions to
IEC 60947-1 and IEC 60947-1/A1.

5/112 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers up to 3200 A, Discontinued Series

Accessories/spare parts

When retrofitting, the circuit-breaker Order No. must


be added to the name plate on the operator panel and to the
side wall of the circuit-breaker in accordance with the installation instructions.
Designation Rated current In Size Number of poles Required order DT For 1 set PS* Weight
quantity per or 1 unit per PU
circuit-breaker approx.
Order No. kg
For fixed-mounted circuit-breakers
Connecting bars up to 1000 A I 3- and 4-pole 1 unit1) A 3WX36 21–1AA00 1 unit on req.
for front-accessible
N S E 0 _ 0 1 1 4 5

N S E 0 _ 0 1 1 4 6

connection 1250 and 1600 A I 3- and 4-pole 1 unit1) A 3WX36 21–1BA00 1 unit on req.
Vertical single-hole bar
1)
2000 A II 3- and 4-pole 1 unit A 3WX36 21–1DA00 1 unit on req.

2500 and 3200 A II 3- and 4-pole 1 unit1) A 3WX36 21–1FA00 1 unit on req.

1
Vertical double-hole bar up to 1000 A I 3- and 4-pole 1 unit ) A 3WX36 21–1AA01 1 unit on req.
(holes to DIN 43673)
1250 and 1600 A I 3- and 4-pole 1 unit1) A 3WX36 21–1BA01 1 unit on req.

1
2000 A II 3- and 4-pole 1 unit ) A 3WX36 21–1DA01 1 unit on req.
N S E 0 _ 0 1 1 4 7

N S E 0 _ 0 1 1 4 8

2500 and 3200 A II 3- and 4-pole 1 unit1) A 3WX36 21–1FA01 1 unit on req.
5
Locking device consist- with safety lock Made by CES 1 set A 3WX36 68–1JA00 1 set on req.
ing of lock in the cabi- Normal lock no. SSG 10
net door and interlock Made by BKS A 3WX36 68–1JB00 1 set on req.
module with Bowden Normal lock no. S1
wire (1.5 m) to prevent
unauthorized closing of Made by IKON A 3WX36 68–1JC00 1 set on req.
the circuit-breaker Normal lock no. 360012 K1
Made by O. M. R. A 3WX36 68–1JD00 1 set on req.
Normal lock no. 73034
Mounting set for CASTELL or FORTRESS lock. 1 set A 3WX36 68–1JE00 1 set on req.
Interlock to be obtained from the lock manufac-
turer CASTELL lock (FS 2) or FORTRESS lock
(H31LH/65°/standard)
Auxiliary supply 1 unit A 3WX36 25–1JC00 1 unit 0.080
connectors
Blocking device to prevent opening of the cabinet door with the 1 unit A 3WX36 67–2JA00 1 unit 0.700
fixed-mounted circuit-breaker closed
to prevent closing of the circuit-breaker with the 1 unit A 3WX36 67–1JA00 1 unit 0.700
cabinet door open
Arc chute cover2) up to 1600 A I 3-pole 1 unit B 3WX36 14–0GA00 1 unit on req.
4-pole 1 unit B 3WX36 14–0HA00 1 unit on req.
2000 and 3200 A II 3-pole 1 unit B 3WX36 14–0KA00 1 unit on req.
4-pole 1 unit B 3WX36 14–0LA00 1 unit on req.
For guide frames
Connecting bar for up to 1000 A I 3- and 4-pole 1 unit1) A 3WX36 23–1AA00 1 unit on req.
additional terminal
N S E 0 _ 0 1 1 4 6

accessible from the 1250 and 1600 A I 3- and 4-pole 1 unit1) A 3WX36 23–1BA00 1 unit on req.
front
Vertical single-hole bar
Vertical double-hole bar up to 1000 A I 3- and 4-pole 1 unit1) A 3WX36 23–1AA01 1 unit on req.
(holes to DIN 43673)
1250 and 1600 A I 3- and 4-pole 1 unit1) A 3WX36 23–1BA01 1 unit on req.
N S E 0 _ 0 1 1 4 8

Connecting bar for rear up to 1000 A I 3- and 4-pole 1 unit1) A 3WX36 23–3AA00 1 unit on req.
vertical connection
1250 and 1600 A I 3- and 4-pole 1 unit1) A 3WX36 23–3BA00 1 unit on req.

2000 A II 3-pole 1 set = 3 units A 3WX36 23–4AB00 1 set 2.600


4-pole 1 set = 4 units A 3WX36 23–4AC00 1 set 3.500
2500 and 3200 A II 3-pole 1 set = 3 units A 3WX36 23–4BB00 1 set 5.400
4-pole 1 set = 4 units A 3WX36 23–4BC00 1 set 7.100
1) Please determine the number of connecting bars required yourself.
2) Required for protection against flashover at voltages > AC 415 V.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/113


Circuit-Breakers up to 3200 A, Discontinued Series

Accessories/spare parts

Designation Rated current In Size Number of poles Required DT For 1 set PS* Weight
order or 1 unit per PU
quantity approx.
per circuit- Order No. kg
breaker
For guide frames
Connecting bars for 2000 A II 3- and 4-pole 1 unit2) A 3WX36 23–1DA00 1 unit on req.
front-accessible con-
N S E 0 _ 0 1 1 4 6

nection vertical 2500 and 3200 A II 3- and 4-pole 1 unit2) A 3WX36 23–1EA00 1 unit on req.
single-hole bar

Vertical double-hole 2000 A II 3- and 4-pole 1 unit2) A 3WX36 23–1DA01 1 unit on req.
bar (holes to
DIN 43673) 2500 and 3200 A II 3- and 4-pole 1 unit2) A 3WX36 23–1EA01 1 unit on req.
N S E 0 _ 0 1 1 4 8

13 14 Position Connected Test Discon- Precondition


indicator switch position position nected
(actuated by withdraw- position
able circuit-breaker) 1 NO + 1 NO + 1 NO + possible if no 1 set A 3WX36 84–1JA10 1 set on req.
1 NC 1 NC 1 NC pos. switch mounted yet = 1 unit
3 NO + 2 NO + 1 NO + possible if no 1 set A 3WX36 84–1JC10 1 set on req.

5
3 NC 2 NC 1 NC pos. switch mounted yet = 1 unit
2 NO + 1 NO + — possible if position switch 1 set A 3WX36 84–1JB10 1 set on req.
2 NC 1 NC with 1 NO + 1 NC mounted = 1 unit
for each position with guide
frame
(order code "R13")
Shutters Protection against touching the main contacts
For 3-pole guide frames for rated current up to
1600 A 1 unit A 3WX36 84–3CA00 1 unit 0.500
2000 A ... 3200 A 1 unit A 3WX36 84–3DA00 1 unit on req.
For 3-pole guide frames for rated current up to
1600 A 1 unit A 3WX36 84–3CB00 1 unit on req.
2000 A ... 3200 A 1 unit A 3WX36 84–3DB00 1 unit on req.
Arc chute up to 1600 A I 3-pole 1 unit B 3WX36 14–0GB00 1 unit on req.
cover1) 4-pole 1 unit B 3WX36 14–0HB00 1 unit on req.
2000 ... 3200 A II 3-pole 1 unit B 3WX36 14–0KB00 1 unit on req.
4-pole 1 unit B 3WX36 14–0LB00 1 unit on req.
Auxiliary supply For guide frames – for spare parts and retrofitting 1 unit A 3WX36 27–1JA00 1 unit 0.160
connectors
For withdrawable circuit-breakers
Blocking device to prevent opening of the cabinet door, when circuit-breaker is 1 unit A 3WX36 67–1JC00 1 unit on req.
in connected position
to prevent closing with the door open (only in connected pos.) A 3WX36 67–1JB00 1 unit on req.
to prevent movement with the cabinet door open A 3WX36 67–3JA00 1 unit on req.
Locking with safety lock Made by CES 1 unit A 3WX36 68–2JA00 1 unit on req.
device Normal lock no. SSG 10
to prevent unautho- Locking Made by BKS A 3WX36 68–2JB00 1 unit on req.
rized closing of the device active in Normal lock no. S1
circuit-breaker connected position
(lock in the Made by IKON A 3WX36 68–2JC00 1 unit on req.
cabinet door and Normal lock no. 360012 K1
interlock module) Made by O. M. R. C 3WX36 68–2JD00 1 unit on req.
Normal lock no. 73034
Mounting set for CASTELL or FORTRESS lock. 1 set C 3WX36 68–2JE00 1 set on req.
Interlock to be obtained from the lock manufacturer CASTELL
lock (FS 2) or FORTRESS lock (H31LH/65°/standard)
Locking with safety lock Made by CES 1 unit A 3WX36 67–4JA10 1 unit on req.
device Made by BKS A 3WX36 67–4JB10 1 unit on req.
to prevent movement
of the withdrawable Made by IKON A 3WX36 67–4JC10 1 unit on req.
circuit-breaker out of Made by O. M. R. C 3WX36 67–4JD10 1 unit on req.
the disconnected posi-
tion Made by Profalux C 3WX36 67–4JF10 1 unit on req.
Made by Ronis C 3WX36 67–4JG10 1 unit on req.
Locking with safety lock Made by CES 1 unit A 3WX36 67–4JA00 1 unit on req.
device Normal lock no. SSG 10
to prevent movement Made by BKS A 3WX36 67–4JB00 1 unit 0.200
of the withdrawable Normal lock no. S1
circuit-breaker
(the safety Made by IKON A 3WX36 67–4JC00 1 unit on req.
lock prevents Normal lock no. 360012 K1
opening of the Made by O. M. R. C 3WX36 67–4JD00 1 unit on req.
crank hole) Normal lock no. 73034
Made by Profalux C 3WX36 67–4JF00 1 unit on req.
Made by Ronis C 3WX36 67–4JG00 1 unit on req.
1) Required for protection against flashover at voltages > AC 415 V.
2) Please determine the number of connecting bars required yourself.

5/114 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Circuit-Breakers up to 3200 A, Discontinued Series

Accessories/spare parts

Designation Size Number of poles Required order DT For 1 unit PS* Weight
quantity per per PU
circuit-breaker approx.
Order No. kg
Conversion set I 3-pole 1 unit A 3WX36 88–0GA00 1 unit on req.
from fixed-mounted to 4-pole A 3WX36 88–0HA00 1 unit on req.
withdrawable variant II 3-pole 1 unit A 3WX36 88–0KA00 1 unit on req.
= single operating 4-pole A 3WX36 88–0LA00 1 unit on req.
mechanism

Designation For circuit-breaker Rated current Size Number of Required order DT For 1 set PS* Weight
Type poles quantity per or 1 unit per PU
circuit-breaker approx.
Order No. kg
For fixed-mounted and withdrawable circuit-breakers
Main contact 3WN6 0.1 to 3WN6 2.1 up to 1000 A I 3-pole 3 units B 3WY36 21–0AA00 1 unit 2.000
elements, complete 3WN6 0.1-.....-....-Z K03 up to 1000 A I 3-pole 3 units B 3WY36 21–0AA10 1 unit on req.
to
3WN6 2.1-.....-....-Z K03
3WN6 0.3 to 3WN6 2.3 up to 1000 A I 4-pole 4 units B 3WY36 21–0AA00 1 unit 2.000
3WN6 0.3-.....-....-Z K03 up to 1000 A I 4-pole 4 units B 3WY36 21–0AA10 1 unit on req.
to
3WN6 2.3-.....-....-Z K03
3WN6 3.1 to 3WN6 4.1 1250 ... 1600 A I 3-pole 3 units B 3WY36 21–0BA00 1 unit 3.000
5
3WN6 3.3 to 3WN6 4.3 1250 ... 1600 A I 4-pole 4 units B 3WY36 21–0BA00 1 unit 3.000
3WN6 5.1 2000 A II 3-pole 3 units B 3WY36 21–0DA00 1 unit 5.300
3WN6 5.3 2000 A II 4-pole 4 units B 3WY36 21–0DA00 1 unit 5.300
3WN6 6.1 2500 A II 3-pole 3 units B 3WY36 21–0EA00 1 unit 7.000
3WN6 6.3 2500 A II 4-pole 4 units B 3WY36 21–0EA00 1 unit 7.000
3WN6 7.1 3200 A II 3-pole 3 units B 3WY36 21–0FA00 1 unit 7.300
3WN6 7.3 3200 A II 4-pole 4 units B 3WY36 21–0FA00 1 unit 7.300
Arc chute 3WN6 0.1 to 3WN6 4.1 up to 1600 A I 3-pole 3 units B 3WY36 11–0CA00 1 unit 1.800
3WN6 0.3 to 3WN6 4.3 up to 1600 A I 4-pole 4 units B 3WY36 11–0CA00 1 unit 1.800
3WN6 5.1 to 3WN6 7.1 2000 ... 3200 A II 3-pole 3 units B 3WY36 11–0FA00 1 unit 2.500
3WN6 5.3 to 3WN6 7.3 2000 ... 3200 A II 4-pole 4 units B 3WY36 11–0FA00 1 unit 2.500
Crank handle For withdrawable circuit- 1 set A 3WX36 84–0JA00 1 set on req.
breaker

Main contact elements

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/115


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids

■ Characteristics
The characteristics show the behavior of the electronic trip unit mine the total break-times of the circuit-breakers, approximately
when it is activated by a current that is already flowing before the 15 ms must be added to the opening times shown for the arcing
tripping operation. If the overcurrent tripping occurs immediately time.
after switch on and the electronic trip unit is therefore not yet en-
abled, the opening time is extended, depending on the level of Tolerances according to IEC 60947.
the overcurrent by approximately 3 to 10 ms. In order to deter-
Tripping characteristics "a" and "z": "z" = definite-time delayed
O p e n in g tim e O p e n in g tim e
6 0 N S E 0 _ 0 1 1 4 9 6 0 A N S E 0 _ 0 1 1 5 0

2 0 0 0 2 0 0 0 N c o n - P h a s e s ,
3 0 3 0 d u c to r, N c o n d u c to r,
2 0 1 0 0 0 2 0 1 0 0 0
N = 5 0 % r N = 1 0 0 % r
1 0 5 0 0 1 0 5 0 0
a
5 5
2 0 0 2 0 0 1 ,2 5 x
a d ju s ta b le a s 2 d a d ju s t a b le a s
2 1 0 0 1 ,5 x 1 0 0 1 ,5 x
m u ltip le s o f r 2 x m u ltip le s o f r
1 5 0 2 x 1 5 0
3 x 3 x
4 x 4 x
2 0 5 x
2 0 5 x
6 x
6 x 1 0 8 x
1 0 8 x 1 0 x
1 0 x 5 1 2 x
5 1 2 x
z c = 1 0 s

5
c = 1 0 s 2
2
1 g
1 g m s
m s 0 ,5 4 0 0
0 ,5 4 0 0 (3 0 0 )
(3 0 0 ) (2 2 0 )
0 ,2 (2 2 0 ) 0 ,2 1 5 0
1 5 0 0 ,1 8 0
0 ,1 8 0
0 ,0 5 2 0 M
0 ,0 5 2 0 M 0
0 0 ,0 2
0 ,0 2 0 ,0 1
0 ,0 1 0 ,0 0 5
0 ,0 0 5 0 ,4 0 ,6 1 2 4 6 8 1 0 2 0 4 0 6 0 1 0 0 x r
1 2 4 6 8 1 0 2 0 4 0 6 0 1 0 0 2 0 0 x r
C u rre n t
r
r C u rre n t

Tripping characteristics of electronic trip units – version B Tripping characteristics of electronic trip units – version C/G
Key to illustrations above:
Inverse-time delayed electronic trip unit "a" Short-time delayed short-circuit release "z"
Ir Current setting (adjustable) Id Operating current (adjustable)
IN Current setting (50 or 100 % Ir) for den N conductor td Delay time (adjustable)
Tc Time-lag class (permanently set to 10 s)

Tripping characteristic "n" Tripping characteristic "g": definite-time delayed


O p e n in g tim e O p e n in g tim e
6 0 A N S E 0 _ 0 1 1 5 1 6 0 N S E 0 _ 0 1 1 5 2

3 0 2 0 0 0 3 0 2 0 0 0
2 0 1 0 0 0 2 0 1 0 0 0
1 0 5 0 0 1 0 5 0 0
5 5 g a d ju s t a b le a s
2 0 0 2 0 0 m u ltip le s o f n
2 1 0 0 2 1 0 0
1 5 0 1 5 0
0 ,3 x 0 ,5 x
2 0 0 ,2 x 0 ,4 x 0 ,6 x
2 0
1 0 1 0
i
a d ju s ta b le to
5 5
> 1 5 x n
2 2
1 1 g
m s
0 ,5 0 ,5 5 0 0
3 0 0
0 ,2 2 0 0
0 ,2
0 ,1 1 0 0
0 ,1
0 ,0 5
0 ,0 5
0 ,0 2
0 ,0 2
0 ,0 1
0 ,0 1
0 ,0 0 5
0 ,0 0 5
1 2 4 6 8 1 0 2 0 4 0 6 0 1 0 0 2 0 0 x n
n C u rre n t 0 ,1 0 ,2 0 ,4 0 ,6 1 2 4 6 1 0 2 0 x n
n
C u rre n t

Tripping characteristics of electronic trip units – versions B and C/G Tripping characteristics of electronic trip units – version C/G
In Transformer primary rated current In Transformer primary rated current
Instantaneous short-circuit release "n" Ground-fault release "g"
Ii Operating current (permanently set) Ig Operating current (adjustable)
tg Delay time (adjustable)

5/116 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids

■ Dimension drawings
3WN6 fixed-mounted circuit-breakers, 3-pole
Horizontal connection
1 1 4
9 2 2 3 9

45
8
5

d
500
i
470

100
330

d
SA2-5317a
SA2-5315a

165
7
SA2-5316a
40

10 4
a c c
175 100 14

5
b
330
410
e Fixing holes for support bracket $ Clearance for lifting out the arc chute
∅12,5 f
% Space for auxiliary supply connectors
k

& Space above arc chute


l

( Auxiliary supply connectors


) Switchboard door
* Recessed grip
400
SA2-5318a

455

+ M8 nut
, Slots (4 mm deep) for line-side phase barriers
∅ 11 - Center line of circuit-breaker
SA2-5319a

270 Safety clearances


m No additional safety clearance is required to adjacent grounded
35

n parts above the circuit-breaker (on fixed-mounted circuit-breakers


identified with 3).
The clearance between the connection point and the support for
the busbars must not exceed 250 mm.

Front connection 9 9

20
SA2-5321a SA2-5324a
20

SA2-5320a SA2-5323a

40
8 8
360
360
35

35

40

∅ 13,5
20

g
h 320 e h 320 ∅ 13,5 g
20

Single hole c c Double hole e


Holes in bars to DIN 43673 c c

Up to a rated operating voltage of AC 415 V


Rated current a b c d e f g h i k l m n the busbars running vertically (such as in the case of front-
A accessible connection) do not have to be screened if the
630 ... 1000 300 320 90 8 60 30 – 8 530 18 40 300 338 busbar system is not arranged above the circuit-breaker.
In contrast, live bare conductors and
1250 ... 1600 300 320 90 15 60 30 – 20 530 18 40 300 338 busbars at voltages above AC 415 V that are arranged
2000 400 420 120 15 80 40 40 20 560 22 44 400 438 above the circuit-breaker and when power is supplied from
2500 ... 3200 400 420 120 30 80 40 40 20 560 22 44 400 438 above must be insulated against flashover by interphase
barriers or by a busbar cover or by an arc chute cover (use
Main conductor connection accessory for horizontal or vertical connection only).
Optional electrical equipment directly above (if no arc
Terminal screws with strain washers M12 chute cover is used) or to the side of the circuit-breaker
(inside diameter = 12 mm to DIN 6769-Fst) should be protected by a cover . Also after the attachment
Recommended tightening torque Nm 70 of additional barriers or covers it must be ensured that the
dissipation of heat from the circuit-breaker is not impeded.
Required strength of screws 8.8 to DIN 267

Siemens LV 30 · 2004 5/117


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids


3WN6 circuit-breakers, withdrawable version, 3-pole
Horizontal connection
58 a
44 b
6
10 c 6
1
SA2-5326b SA2-5327a

2 2 3 4

d
485

100
330
SA2-5325b

d
165

5
40

a 3,5
ø9 25 e
b
5 250 75 14 c c
408
15 430

5
e a Disconnected position
15

f ø12,5 b Test position


37

c Connected position
$ Auxiliary conductor plug-in system
% Guide frame
& Switchboard door
( Slots (6 mm deep) for line-side interphase barriers
) Holes for attaching the guide frame
* Center line of circuit-breaker
SA2-5328b

For safety clearances see Page 5/117.

270

Vertical connection 6

SA2-5329a S A2 -5 3 30 a

2 3 4

ø13,5
d
e
f
l

d
k

d
ø9 25 n n
m 250 75 14
15 h
i

Rated current a b c d e f h i k l m n
A
630 up to 1000 280 320 90 8 60 30 455 470 157.5 115 37 90
1250 up to 1600 280 320 90 15 60 30 455 470 157.5 115 37 90
2000 380 420 120 15 80 40 465 480 157.5 115 40 140
2500 up to 3200 380 420 120 30 100 50 465 480 150 130 40 140

5/118 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids


3WN6 circuit-breakers, withdrawable version, 3-pole
Front connection
4
4 SA2-5333a

SA2-5331b SA2-5332a
1 2

3
3

360
300
20

20
65

35
Æ9 60 b a
250 75 90 90 ∅13,5 120 120 ∅13,5
c d
Single hole, 630 to 1600 A Single hole, 2000 to 3200 A
e

Rated current a b c d e
4
5
A 4 SA2-5335b

630 ... 1000 60 – 8 390 408 SA2-5334a

1250 ... 1600 60 – 15 390 408


2000 80 40 20 420 445
2500 ... 3200 100 50 20 420 445
3
$ Guide frame 3

360
300

% Switchboard door
& Slots (6 mm deep, 3.5 mm wide)
40

40
for line-side phase barriers
( Center line of circuit-breaker
65

35
20

60
For safety clearances see Page 5/117. b a ∅13,5
90 90 ∅13,5

20
120 120
Double hole, 630 to 1600 A Double hole, 2000 to 3200 A
Holes in bars to DIN 43673 Holes in bars to DIN 43673

Siemens LV 30 · 2004 5/119


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids


3WN6 fixed-mounted circuit-breakers, 4-pole
Horizontal connection
1 1 4
9 2 2 3 L3 L2 9 L1 N

45
8
5

d
6
500
i
470

100
330

SA2-5423a

d
SA2-5422a

165
7
SA2-5316a
40

10 4
p c c c
175 100 14
a
b 330
410

5 N L1 L2 L3 Fixing holes for support bracket $ Clearance for lifting out the arc chute
e
∅12,5
% Space for auxiliary supply connectors
f
& Space above arc chute
k
l

( Auxiliary supply connectors


) Switchboard door
* Recessed grip
400
455

+ Nut M 8
, Slots (4 mm deep) for line-side phase barriers
∅ 11 - Center line of operator panel
SA2-5319a
SA2-5424a

For safety clearances see Page 5/117.


270 m
35

Front connection L3 L2 9 L1 N L3 L2 9 L1 N

20
SA2-5425a SA2-5426a
20

SA2-5320a SA2-5323a

40
8
8
360
360
35

35

40

∅ 13,5
20

g
h 320 h 320
e ∅ 13,5 g
20

c c c e
Single hole Double hole c c c
Holes in bars to DIN 43673

Rated current a b c d e f g h i k l m n p
A
630 ... 1000 390 410 90 8 60 30 – 8 530 18 40 390 428 150
1250 ... 1600 390 410 90 15 60 30 – 15 530 18 40 390 428 150
2000 520 540 120 15 80 40 40 20 560 22 44 520 558 200
2500 ... 3200 520 540 120 30 80 40 40 20 560 22 44 520 558 200

5/120 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids


3WN6 circuit-breakers, withdrawable version, 4-pole
Horizontal connection
58 a
44 b
10 c
1 6 2 L3 L2 6 L1 N
SA2-5427a SA2-5326b SA2-5428a

2 3 4

d
485

100
330

165

d
5
40

p ø9 25 3,5
a e
5 250 75 14
b c c c
408
15 430

5
N L1 L2 L3 a Disconnected position
e b Test position
37
15

f Ø12,5
c Connected position
$ Auxiliary conductor plug-in system
% Guide frame
& Switchboard door
( Slots (6 mm deep) for line-side phase barriers
) Holes for attaching the guide frame
* Center line of operator panel
SA2-5429a

For safety clearances see Page 5/117.

270

Vertical connection L3 L2 6 L1 N
SA2-5329a SA2-5430a

2 3
4
ø13,5
d
e
f
l

d
k

d
ø9 25 n n o
m 250 75 14
15 h
i

Rated current a b c d e f h i k l m n o p
A
630 ... 1000 370 410 90 8 60 30 455 470 157.5 115 37 90 90 140
1250 ... 1600 370 410 90 15 60 30 455 470 157.5 115 37 90 90 140
2000 500 540 120 15 80 40 465 480 157.5 115 40 140 120 190
2500 ... 3200 500 540 120 30 100 50 465 480 150 130 40 140 120 190

Siemens LV 30 · 2004 5/121


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids


3WN6 circuit-breakers, withdrawable version, 4-pole
Front connection
SA2-5331b
L3 L2 4 L1 N
1 2 L3 L2 4 L1 N SA2-5432a

SA2-5431a

3
3

360
300
20

20
Æ9

65

35
250 75
c d 60 b a
e 90 90 90 ∅ 13,5 120 120 120 ∅ 13,5
Single hole, 630 to 1600 A Single hole, 2000 to 3200 A

5
4
Rated current a b c d e 4
A SA2-5433a SA2-5434a

630 ... 1000 60 – 8 390 408


1250 ... 1600 60 – 15 390 408
2000 80 40 20 420 445
2500 ... 3200 100 50 20 420 445
3
$ Guide frame 3
300

360
% Switchboard door
40

& Slots (6 mm deep, 3.5 mm wide)


for line-side phase barriers
65

( Center line of operator panel

40
60
20

35
For safety clearances see Page 5/117. 90 90 90 ∅ 13,5
b a

20
120 120 120 ∅13,5
Double hole, 630 to 1600 A Double hole, 2000 to 3200 A
Holes in bars to DIN 43673 Holes in bars to DIN 43673

3WN6 circuit-breakers, 3- and 4-pole


Door cut-out for operator panel Door cut-out
using the door sealing frame with edge protector
Cut-out after mounting
157,5 157,5
∅ 5,5
the edge protector
120 40
b Cut-out when the circuit-breaker is installed
in a switchgear cabinet and with the door
R5
arranged centrally.
185
140

Section width Fixed-mounted Withdrawable


b b
350

340

400 275 292


140

180

500 275 290


205

600 275 288


205

40 120
35

∅ 5,5*
SA2-5322a
30
7

12 9 NSK-5907a
29 1
300
$ Mounting surface
* 3 holes, dia. ∅ 5.5 mm; only drill when using door interlocking.

5/122 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids


Accessories for 3WN6 circuit-breakers, 3- and 4-pole
Mutual mechanical interlocking (1)/locking device to prevent closing (2),
consisting of lock in the control cabinet door and interlock module with Bowden wire
For fixed-mounted circuit-breakers For withdrawable circuit-breakers

NS1-5354a
NS1-5355a NS1-5356a

1
1

e
NS1-5353a

d
a b c
c
a b

$ Clearance for interlock module


(without Bowden wire) Clearance for a b c d e
(1) 90 90 50 65 270

5
(2) 58 215 10 250 115

3WX31 56–1J.01 storage device for shunt release


and enclosure for voltage transformer for measurement module
62,5 1 2
73,2
90
80

70

$ Mounting feet
SA2-5336a 118,2 % Standard mounting rail to EN 50022-35
2,5

100 121

Current transformer for neutral conductor overload protection and ground-fault protection
for sizes I and II

k l L K Current trans- Current Size A B C D E F


former trans- approx
former .
C

primary
rated
current
D

In
E
F

3WX36 43–1. .00 A


CA 315 I 92 60 86.5 140 5…15 107
CB 400
NS1-5334a
CC 500
B 60 CD 630
A 105 CE 800
CF 1000
3WX36 43–1..00 CG 1250
CH 1600
FJ 3200 II 128 80 99 167 5…35 136
FK 2500
FM 3200

Locking device for Transfer control device


"electrical ON" and
"mechanical OFF" buttons $
52
400
340
322

NSK-8273

$
\ 284
150 216 320
Dimensions for holes,
NSK5908

outer dimensions
NSK-8272

32
max.78
Installation in cabinet,
side view and front view

Siemens LV 30 · 2004 5/123


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids

■ Circuit diagrams
Example of an overall circuit diagram
Motor/manual operating mechanism with stored-energy feature, with ready-to-close signaling switch, with
electronic trip unit version b "azn", with overvoltage release "r" (F3)
or shunt release "f" (F1), with shunt release "f" (F2), with "tripped"
signaling switch, with auxiliary switch 2 NO + 2 NC + 2 CO, with motor switch

L 1 L 1 L 1 L 1
(L + ) (L + ) (L + ) (L + )
-S .. -S .. -S ..

L 1
L 2
L 3
N
"O N "
-S ..

X 1 0 0 8 X 1 0 0 1 1 X 1 0 0 1 0 X 2 0 0 3 X 2 0 0 1 X 1 0 0 1 3 X 2 0 0 1 4 1 2 -Q 0 1 1 3 5 X 2 0 0 6 4 1 0 8 X 1 0 0 3 7 5

-S 1 0 B "a z n "
"a "
"O N "
I "z "

v
v
-S 9 I "n "

v
v
R

e it h e r
S 8 -F 1 o r -F 3

5
S 1 1 -F 5
-F 1
-F 3
M
-Q 1 S 1 S 2 S 3 S 4
-Q 0 1
P
S 7
"M E C H
-T 1
O N " -Y 1
-F 2
-T 2
-T 3
"M E C H
O F F "

N S 1 -5 3 1 1 a
X 1 0 0 9 X 1 0 0 1 2 X 2 0 0 2 X 1 0 0 1 4 X 2 0 0 1 3 -Q 0 1 2 4 6 X 2 0 0 7 5 1 1 9 X 1 0 0 4 2 6

N N N
(L 2 ) (L 2 ) (L 2 )
L 1
L 2
L 3
N

(L -) (L -) (L -)

A1 Electronic trip unit


S1/S2 1st auxiliary switch block
S3/S4 2nd auxiliary switch block
S7 Ready-to-close
signaling switch
S8 Storage spring contact
S9 Motor switch
S10 "Electrical ON" button
S11 "Tripped" switch
F1 1st shunt release "f"
F2 2nd shunt release "f"
F3 Undervoltage release "r"
F5 Trip solenoid
M1 Motor for
"charging store"
P Storage spring
Q01 Hand-operated lever for
"charging store"
Q1 Main contacts
T1/T2/T3 Current transformer
X100/X200 Terminals
Y1 Closing solenoid
R Indication and reset button
for overcurrent tripping

5/124 Siemens LV 30 · 2004


Circuit-Breakers up to 3200 A, Discontinued Series

Project planning aids


Indicator switches for the switch positions in the guide frame
Order code "R13" Order code "R14"
3WX36 84–1JA10 3WX36 84–1JC10
Discon- Test Connected Discon- Test Connected
nected position position nected position position
position position
NS1-5347

NS1-5348
-S30 3 1 -S31 3 1 -S33 3 1 -S30 3 1 -S31 3 1 -S32 3 1 -S33 3 1 -S34 3 1 -S35 3 1

4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4 2

1 2
v

v
v

3 1 2 3
v
v

v
v

v
Contact
position with:
Circuit-breaker in 5
disconnected
position
Circuit-breaker in
test position

Circuit-breaker in
connected position

Contact
closed

Contact
open

Circuit diagram for optional equipment


–F1A <21> 1st shunt release –F1
Storage device for 1st or 2nd shunt release <22> Auxiliary switch for <21>
(–F1 or –F2) <27> 2nd shunt release –F2
<28> Auxiliary switch for <27>
NS1-5198a

3
<91> or <92> External "electrical <OFF>" by –F1 or –F2
<91>
V2 -S.. <92>
button only
4
R1 R2 9 (+)

~ V1 +
~
C1 C2 R4 V3 K1 X200. 3 X100. 13
(+) 1 ~
V4
R5 K1
~
( ) 2
K1
R3
R6 C3 F1 F2
10 ( )

X200. 2 X100. 14

3WX31 56-1JG01 and 3WX31 56-1JJ01 storage devices


for shunt release with stored energy feature

■ Further information
For planning guides with further descriptions relating to design,
operating principle, installation and retrofitting see manual
"3WN6 circuit-breakers for low voltage"
Order No.: E20001-P285-A571-V2 (in German)
For further information on the selection, ordering and project
planning of communication-capable circuit-breakers, refer to the
section "Communication-capable circuit-breakers" and the man-
ual "Communication links for 3VF, 3WN6, 3WN1/3WS1 circuit-
breakers to PROFIBUS DP"
Order No. E20001-P285-A644-V1 (in German only).

Siemens LV 30 · 2004 5/125


Non-Automatic Circuit-Breakers up to 3200 A, Discontinued Series

3-pole, fixed-mounted design

Version DT Order No. PS* Weight per


Rated operating voltage Ue up to AC 690 V PU approx.
without electronic trip unit system 3 WN 6 7 7 1 – 0 WA 7 7 – 7 7 7 7 kg

Size/ Size Rated current In


rated current In I 1000 A 2 1 unit 34.000
1600 A 4 1 unit 36.000
II 2000 A 5 1 unit 57.000
2500 A 6 1 unit 59.000
3200 A 7 1 unit 61.000
Installation type Main circuit connections see Page 5/85
Fixed-mounted Main circuit connections, rear, horizontal (standard) 6
Main circuit connections accessible from front, 3
single hole at top and bottom
up to 1000 A
1250 A, 1600 A
2000 A
2500 A, 3200 A
Main circuit connections accessible from front, 2
double hole at top and bottom,
holes in accordance with DIN 43673

5
up to 1000 A
1250 A, 1600 A
2000 A
2500 A, 3200 A
Circuit-breakers also available with rated short-time withstand current 11th to
Icw = 50 kA/1 s, see Page 5/105. 16th positions
of the Order
No. see Page
5/130.

5/126 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Non-Automatic Circuit-Breakers up to 3200 A, Discontinued Series

3-pole, withdrawable design

Version DT Order No. PS* Weight per


Rated operating voltage Ue up to AC 690 V PU approx.
without electronic trip unit system 3 WN 6 7 7 1 – 0 WA 7 7 – 7 7 7 7 kg

Size/ Size Rated current In


rated current In I 1000 A 2 1 unit 36.000
1600 A 4 1 unit 38.000
II 2000 A 5 1 unit 59.000
2500 A 6 1 unit 61.000
3200 A 7 1 unit 63.000
Installation type Main circuit connections see Page 5/85
Withdrawable Withdrawable circuit-breaker without guide frame 7
design Withdrawable circuit-breaker with guide frame
8
Other Standard version: Rear,
versions of the horizontal terminals with guide rails
guide frame up to 1000 A 27.000
see Page 5/110. 1250 A, 1600 A 23.000
2000 A 35.000
2500 A 37.000
3200 A 37.000
Circuit-breakers also available with rated short-time withstand current 11th to

5
Icw = 50 kA/1 s, see Page 5/105. 16th positions
of the Order
No. see Page
5/130.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/127


Non-Automatic Circuit-Breakers up to 3200 A, Discontinued Series

4-pole, fixed-mounted design

Version DT Order No. PS* Weight per


Rated operating voltage Ue up to AC 690 V PU approx.
without electronic trip unit system 3 WN 6 7 7 3 – 0 WA 7 7 – 7 7 7 7 kg

Size/ Size Rated current In


rated current In I 1000 A 2 1 unit 47.000
1600 A 4 1 unit 49.000
II 2000 A 5 1 unit 70.000
2500 A 6 1 unit 72.000
3200 A 7 1 unit 74.000
Installation type Main circuit connections see Page 5/85
Fixed mounted Main circuit connections, rear, horizontal (standard) 6
Main circuit connections accessible from front, 3
single hole at top and bottom
up to 1000 A
1250 A, 1600 A
2000 A
2500 A, 3200 A
Main circuit connections accessible from front, 2
double hole at top and bottom,
holes in accordance with DIN 43673

5
up to 1000 A
1250 A, 1600 A
2000 A
2500 A, 3200 A
Circuit-breakers also available with rated short-time withstand current 11th to
Icw = 50 kA/1 s, see Page 5/105. 16th positions of
the Order No.
see Page 5/130.

5/128 Siemens LV 30 · 2004 * This quantity or a multiple thereof can be ordered.


Non-Automatic Circuit-Breakers up to 3200 A, Discontinued Series

4-pole, withdrawable design

Version DT Order No. PS* Weight per


Rated operating voltage Ue up to AC 690 V PU approx.
without electronic trip unit system 3 WN 6 7 7 3 – 0 WA 7 7 – 7 7 7 7 kg

Size/ Size Rated current In


rated current In I 1000 A 2 1 unit 49.000
1600 A 4 1 unit 51.000
II 2000 A 5 1 unit 72.000
2500 A 6 1 unit 74.000
3200 A 7 1 unit 76.000
Installation type Main circuit connections see Page 5/85
Withdrawable Withdrawable circuit-breaker without guide frame 7
design Withdrawable circuit-breaker with guide frame
8
Other Standard version: Rear,
versions of the horizontal circuit connections with guide rails
guide frame up to 1000 A 27.000
see Page 5/110. 1250 A, 1600 A 28.000
2000 A 46.000
2500 A 48.000
3200 A 48.000
Circuit-breakers also available with rated short-time withstand current 11th to

5
Icw = 50 kA/1 s, see Page 5/105. 16th positions
of the Order
No. see Page
5/130.

* This quantity or a multiple thereof can be ordered. Siemens LV 30 · 2004 5/129


Non-Automatic Circuit-Breakers up to 3200 A, Discontinued Series

Options

■ Selection and ordering data


Version Order No.

3 WN 6 7 7 1 – 0 WA 7 7 – 7 7 7 7

Operating Manual operating mechanism with stored-energy feature, with


0 5
mechanism mech. closing
Manual operating mechanism with stored-energy feature, with
mechanical and electr. closing
Closing solenoid
AC 50/60 Hz V DC V
24 24 1 1
48 48 1 4
– 60 1 5
110–127 110–125 1 6
220–240 220–250 1 8
Manual/motor-operated mechanism with stored-energy
M feature with mechanical and electrical closing
Motor Closing
AC 50/60 Hz V DC V AC 50/60 Hz V DC V
– 24 24 24 5 1

5 –

48
60
48

48
60
5 4
5 5
110–127 110–125 – 24 7 1
110–127 110–125 – 48 7 4
110–127 110–125 – 60 7 5
110–127 110–125 110–127 110–125 5 6
110–127 110–125 220–240 220–250 7 8
220–240 220–250 – 24 8 1
220–240 220–250 – 48 8 4
220–240 220–250 – 60 8 5
220–240 220–250 110–127 110–125 8 6
220–240 220–250 220–240 220–250 5 8
1st auxiliary Without 1st auxiliary releases 0A
release Shunt release "f", F1
AC 50/60 Hz V DC V
24 24 1 B
U – 30 1 E
48 48 1 F
– 60 1 G
110–127 110–125 1H
220–240 220–250 1K
Undervoltage release "r", F3
(instantaneous 0 ms, short-delay 200 ms)
AC 50/60 Hz V DC V
– 24 3 B
U< – 30 3 E
– 48 3 F
– 60 3 G
110–127 110–125 3H
220–240 220–250 3K
380–415 – 3M
Undervoltage release "rc", F8
(delayable 0.2 ... 3.2 s)
AC 50/60 Hz V DC V
U < ,t 110–127 – 4H
220–240 – 4K
380–415 – 4M
2nd auxiliary Without 2nd auxiliary release A
release Shunt release "f", F2
AC 50/60 Hz V DC V
24 24 B
– 30 E
48 48 F
– 60 G
110–127 110–125 H
220–240 220–250 K
Auxiliary switches 1st auxiliary switch block
2 NO + 2 NC 1
1st + 2nd auxiliary switch block
2 NO + 2 NC + 2 CO 3
For technical specifications, options, accessories/spare parts 5th and 6th positions of the Order No.
and project planning aids see "Circuit-breakers, up to 3200 A, see Pages 5/126 to 5/129.
discontinued series".

5/130 Siemens LV 30 · 2004

Vous aimerez peut-être aussi