FOAM CHAMBER AND WATER SPRAY
NKGSB-PRS-DS-007-A4-A NOZZLE

1 GENERAL INFORMATION
2 Tag No
3 Name Foam Chamber (Foam discharge Outlet) and Water Spray Ring & Nozzle
4 Design Code API 2021, NFPA 11 : Foam System for Fire Protection
5 Api 2030, NFPA !5 : Water spray system for Fire Protection
6 TANK INFORMATION DATA
7 Tank No 35T5 and 35T6
8 Service Black Product
9 Flash Point o
C range from 60 -88
10 Capacity m3 19080 (net working) 21208.54 (liquid stored)
11 Roof Type of Tank Dome Roof
12 Tank inside Diameter x H m 36.8 x 21.07
13 FIRE PROTECTION DEMAND & REQUIREMENT
14 FOAM EXTINGUISHING (FIGHTING) WA
15 Case / basis Full surface Fire Area to be protecte
16 Total Surface Area m2 1063.62 Shell area to be pro
17 Foam Application Rate L/min.m2 4.1 roof area to be pro
18 Foam Type used Aqueeous Film-Forming Foam Water spray Applic
19 Foam Concentration Use % 3 Flowrate required
20 Foam solution discharge L/min 4360.83
21 GPM 1152.01
22
23 SPECIFICATION AND SIZING INFORMATION
24 FOAM DISCHARGE OUTLET (FOAM CHAMBER)
25 Type Fixed
26 Foam Outlet Type Type II
27 Application Surface
28 Quantity required per Tank 2 ea
29 Rate Per Foam Chamber req
30 Size inlet flange (to pipe) 4 inch
31 outlet flange (to tank shell 8 inch
32 Material of Foam Chamber Corrosio resistant steel
33 Foam chamber position 520 mm Distance from top angle of Shell to Foam Nozzle Cent
34
35 WATER SPRAY RING & NOZZLE
36 For Shell Protecti
37 Pipe arrangement Double circle ring with overlaping section, and individual riser per sectio
38 No. of ring requred 2
39 No. of section per ring 2 (2 half circle ring)
40 Flow rate for each section minimum 515 GMP
41 Pipe size req Riser minimum 6 inch
42 Ring minimum 4 inch
43 Material of Pipe Corrosion resistant steel (inci for fitings and hangers)
44 Spray nozzle type used Open water spray nozzle
45 Spray discharge type Directionaldisharge
46 Nozzle orifice size minimum 6 mm
47 Flow Type spray angle
48 K - factor
49 Ppressure 30 psi as minimum operating pressure
50 Flow capacity of one spray nozzele
51 Quantity of spray nozzle mm2/s
52 Material of Spray Nozzle brass or stainiess s
53 Spray nozzle position
54 For Roof Protection :
55 Pipe a rrangement one circle ring
56 No. of ring requred 2
57 No. of section per ring none
58 Flow rate req'd minimum 1272.72 GMP
59 Pipe size req Riser minimum 8 inch
60 Ring minimum 6 inch
61 Material of Pipe Corrosion resistnt steel (inci forfitings and hangers)
62 Spray nozzle type used Open water spray nozzle
63 Spray discharge type Directionaldisharge
64 Nozzle orifice size minimum
65 Flow Type
66 Spray Angel
67 K - factor
68 Pressure 30 psi as minimum operating pressure
69 Flow capacity of one spray nozzel
70 Quantity of spray nozzle req'd
71 Material of Spray Nozzle brass or stainiess sreel
72 Spray nozzle position
73 Notes :
74 1) Plan ref to dwg layout water spray system
75 2) Nozzle shall be selected and positioned such that spray pattern meet or overlap at the protected su
76 - This data/ spec sheet applies to Tank 35T5 and Tank 35T6
77 - VTA = Vendor to be advice
78 - TBC = To be confirmed by vendor
79 -
80
81
82
83
84
86
87
Nama PT PT. Sinar Fajar Se
Brand National Foam
Scope of supply Foam Chamber and Water
Quantity TBA
Delivery Time TBA
Rev. A
Delivery Terms TBA
ATER SPRAY Term of payment TBA
Page 1 of 1
Warranty & Guar 1 year
Final Price
General Information
TB
pray Ring & Nozzle

A Tank Information Data

### (geometric)

UIREMENT FIRE PROTECTION DEMAND & REQUIR


WATER SPRAY (COOLING) Foam Extinguishing (fighting)
Area to be protected Shell and Roof of Tank comply
Shell area to be protected 792 comply
roof area to be protected 979.23 comply
Water spray Applic L/min.m2 4.1 comply
Flowrate required Shell L/m3898.35 comply
GMP1029.83 comply
for Roof L/min
4817.82 comply
1272.72 comply
N SPECIFICATION AND SIZING INFORMA
FOAM DISCHARGE OUTLET (FOAM CHA
comply
comply
comply
VTA 3
VTA
VTA comply
VTA comply
VTA comply
Foam Nozzle Center comply

ZLE WATER SPRAY RING & NOZZLE

ual riser per section note 1

1640.27 GPM

comply
comply
12.7mm
VTA 160 deg
VTA 103.7 LPM/Bar^0.5

VTA 179.6 LPM for NO 34 Tyco D3


VTA 140
Brass
note 2

note 1

1992.2 GPM

comply
comply
12.7mm
VTA
VTA 160 deg
VTA 103.7 LPM/Bar^0.5

VTA 179.6 LPM for NO 34 Tyco D3


VTA 40
Brass
note 2

at the protected surface


PT. Sinar Fajar Sejati
National Foam
Foam Chamber and Water spray Nozzle
TBA
TBA
TBA
TBA
1 year

General Information

Tank Information Data

FIRE PROTECTION DEMAND & REQUIREMENT


Foam Extinguishing (fighting) Water Spray (Cooling)
comply
2434.68
739.53
10.2
24833.7
6561.09
7543.23
1992.93
SPECIFICATION AND SIZING INFORMATION
FOAM DISCHARGE OUTLET (FOAM CHAMBER)

WATER SPRAY RING & NOZZLE


DATA SHEET

Nomor Dokumen Rev. B


WATER SPRAY NOZZLE
NKGSB-PRS-DS-006-A4-A Page 4 of 4
1 GENERAL INFORMATION
2 Tag No
3 Name Foam Chamber (Foam discharge Outlet) and Water Spray Ring & Nozzle
4 Design Code Api 2030, NFPA 15 : Water spray system for Fire Protection
5
6 TANK INFORMATION DATA
7 Tank No 35T5 and 35T6
8 Service Black Product
9 Flash Point o
C range from 60 -88
10 Capacity m3 19080 (net working) 21209 (liquid stored) 22410 (geometric)
11 Roof Type of Tank Dome Roof
12 Tank inside Diameter x Height m 36.8 x 21.07
13 FIRE PROTECTION DEMAND & REQUIREMENT
14 WATER SPRAY (COOLING)
15 Area to be protected Shell and Roof of Tank
16 Shell area to be protected m2 ### Note 2
17 roof area to be protected m 749.50
2
Note 2
18 Water spray Application Rate L/min.m2 4.1 Note 1
19 Flowrate required for Shell L/min ### Note 2
20 GMP 5314.3
21 for Roof L/min 2639.8 Note 2
22 GMP 697.36
23 SPECIFICATION AND SIZING INFORMATION
24 WATER SPRAY RING & NOZZELE
25 For Shell Protection :
26 Pipe arrangement Double circle ring with overlaping section, and individual riser per section
27 No. of ring requred 2
28 No. of section per ring 2 (2 half circle ring)
29 Flow rate for each section 2657.1 GMP Note 2
30 Pipe size req Riser 6 inch
31 Ring 4 inch
32 Material of Pipe Corrosion resistant steel (inc for fitings and hangers)
33 Spray nozzle type used Open water spray nozzle
34 Spray discharge type Directional discharge
35 Nozzle orifice size 12.7 mm Note 2
36 Flow Type
37 Spray Angel 160 Note 2
38 K - factor 103.7 Note 2
39 Pressure 2 bar as minimum operating pressure
40 Flow capacity of one spray noz179.61 L/min 47.449 GPM Note 2
41 Quantity of spray nozzle req'd 56 ea/ring Note 2
42 Material of Spray Nozzle Brass
43 Spray nozzle position
44 For Roof Protection :
45 Pipe a rrangement one circle ring
46 No. of ring requred 1
47 No. of section per ring none
48 Flow rate req'd 1394.9 GMP Note 2
49 Pipe size req Riser 8 inch
50 Ring 6 inch
51 Material of Pipe Corrosion resistnt steel (inci forfitings and hangers)
52 Spray nozzle type used Open water spray nozzle
53 Spray discharge type Directional discharge
54 Nozzle orifice size 12.7 mm Note 2
55 Flow Type
56 Spray Angel 110 Note 2
57 K - factor 103.7 Note 2
58 Pressure 30 psi as minimum operating pressure
59 Flow capacity of one spray noz 146.65 L/min 38.742 GPM Note 2
60 Quantity of spray nozzle req'd 36 ea Note 2
61 Material of Spray Nozzle Brass
62 Spray nozzle position
63
64
65
66 Note
67 1. Reference NFPA 11, 2016 Edition ; API 2030
68 2. Reference Doc No : NKGSB-PRS-CL-007-A4-A Fire Water Demand Calculation, Water Spray Ring and Nozzle Sizing Selection
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
Fire Water Demand Calculation, Water Spray Ring and Nozzles Selection

Storage Tank Unit


Diameter (D) 36.8 m
Height (H) 21.07 m
Dome roof height (h) 6.483 m

Protected Area Calculation Unit


Shell area 2434.68 m2
Roof area 749.5035823746 m2
Total area 3184.18 m2

Minimum Fire Water Requirement Unit


Design application rate 4.1 lpm/m2
Min water requirement (Shell) 1 Ring, 2 section 9982.19 lpm
Min water requirement (Roof) 3072.96 lpm
Total water requirement 13055.16 lpm

Spray nozzle Calc and actual fire water requirem


Parameter Unit Roof
Section Facing Up
Nozzle TYCO D3 Protectospray
Orifice size No.34
Selected K-factor lpm/bar^0,5 103.7
Min nozzle D mm 12.7
Spray angle o
65
Fixed Angle Nozzle Arrangement o
45
Max axial distance (Coverage area for each nozzle) m 3.9
Distance Ring - Tank m 0.8
Diameter Ring m 6
circumference of Ring m 18.85
Nozzle quantity ea 8
Distance nozzle - nozzle m 2.36
Tot Nozzle quantity 18
Min Pressure Nozzle Bar 2
P1/2 Bar 1.41
flow capacity of one spray nozzle lpm 146.65
Fire water demand (for nozzle) lpm 1173.2
Total Fire Water Demand (Roof + Shell Tank) lpm 2639.8
Total Fire Water Demand (Roof + Shell Tank) Gpm 697.43
1 GPM 3.785
515 GPM 1949.275
1272.72 GPM 4817.2452
al fire water requirement
Roof Shell (Ring 1) Shell (Ring 2)
Facing down Section 1 Section 2 Section 1 Section 2 sebelumnya 1,4 bar
TYCO D3 Protectospray TYCO D3 Protectospray TYCO D3 Protectospray
No.34 No. 34 No. 34 No.34 No.34
103.7 103.7 103.7 103.7 103.7 (based on flow per-nozzle)
12.7 12.7 12.7 12.7 12.7
65 125 125 125 125
30 150 150 90 90 (Refer coverage nozzle, tyco)
4.2 1.1 1.1 2.0 2.0
0.8 0.8 0.8 0.8 0.8
6 38.4 38.4 38.4 38.4
18.85 60.32 60.32 60.32 60.32
10 28 28 28 28
1.88 2.15 2.15 2.15 2.15 (catalog)
18 56 56 130
2 3 3 3 3 260
1.41 1.73 1.73 1.73 1.73
146.65 179.61 179.61 179.61 179.61
1466.5 5029.2 5029.2 5029.2 5029.2
2639.8 10058.4 10058.4 22756.5
697.43 2657.43 2657.43 6012.3
6012.29
22756.5
20116.730899 20116.7309
LPM 5314.8562482 22756.50
LPM
LPM
2

per-nozzle)

e nozzle, tyco)
Water requirment
Zone (Area)
GPM
Fire Zone - 1 (Warehouse,Workshop,Guard House and Maintenance too#REF!
Fire Zone -2 (Cooling tower, Condensate tank, WTP, and WWTP) 0
Fire Zone - 3 (Boiler Package) 0
Fire Zone - 4 (HRSG & Steam Boiler) 0
Fire Zone - 5 a. Interbus trafo with Outdor Hydrant 0
b. Auxillary trafo with Outdor Hydrant 0
Water requirment
M3/Hr
#REF!
0
0
0
0
0
PROSES

Nomor Dokumen Rev. A


DATA SHEET
NKGSB-PRS-DS-007-A4-A FOAM CHAMBER Page 1 of 2

PEMBERI KERJA : PT. PERTAMINA (PERSERO) RU-IV CILACAP

KONTRAKTOR : KSO NINDYA - GSB

NAMA PROYEK : PEMBANGUNAN 2 UNIT TANKI BLACK PRODUCT DI

PT. PERTAMINA (PERSERO) RU-IV CILACAP

LOKASI : PT. PERTAMINA (PERSERO) RU-IV CILACAP - JAWA TENGAH

NO. SPMP : 130/E20000/2019-S2

A 30/07/2019 All Issued for Review FI NB MR


PreparedChecked Review Review CheckedApproval