Machine Test Summary

Explorer
Machine MOTOR PRUEBA BAKER
Database PRUEBA BAKER
Location
Building
Report Date Sunday, July 20, 2014
Explorer SN# 1133
Nameplate Data:
kW 18.50 Manufacture
RPM 1760 Model
Volts 460 Serial No.
Amps 31.50 Insulation
Enclosure Design

Date/Time Overall Status Date/Time Overall Status


07/20/2014 12:19:17 Caution

Notes:
La salida del transformador es de 440v y se observa que al motor le esta llegando 418.2v
Y el motor es de 460v (nominal).
Test Results

Machine MOTOR PRUEBA


BAKER
Database PRUEBA BAKER Tested by
Location Tested for
Building Explorer SN# 1133
Date/Time 07/20/2014 12:19:17 Test Type Electrical
PM

Name Plate Measured


kW 18.50 1.13
RPM 1760 1799.9
Volts 460 418.2
Amps 31.5 9.8
pf [pu] N/A 0.19
Nema Derating [p.u.] 1.0 1.0
Torque [N-m] 100.4 6.0
Efficiency N/A 81.9
Percent Load N/A 6.1

Test Value Status Caut. Level Warn. Level


% Over Voltage 9.09 Good 10.0 20.0
% Unbalance 0.39 Good 2.0 3.5
% THD 3.41 Good 7.0 9.0
Total Distortion 3.21 Good 10.0 12.0
% Current 31.79 Good 110.0 120.0
Ef. Service Factor 0.06 Good 1.1 1.3
Rotor Bar [db] 0.00 N/A N/A N/A
% Op. Point 0.00 Good 20.0 30.0
% Loss Diff. 0.00 N/A N/A N/A
Payback 0.00 N/A N/A N/A

Notes:
Test Details

Machine MOTOR PRUEBA


BAKER
Database PRUEBA BAKER Tested by
Location Tested for
Building Explorer SN# 1133
Date/Time 07/20/2014 12:19:17 Test Type Electrical
PM

Voltage and Current Waveforms Phasor Diagram

Rotor Bar Torque Ripple