Vous êtes sur la page 1sur 28

METER ERROR CALCULATION

Time (SEC)
Root 3 1.732 30
Voltage 11000 V Editable
Current 180 A Non-Editable
PF 1 1
PF 0.8 0.8
0.786
Real Time Instantaneous Values
Claimed Observed
Parameters Expected Value Actual Value
Error % Error %
-0.5 -0.498 -0.40
-0.8 -0.798 -0.25
-0.9 -0.899 -0.11
Avg. PF 1.00 1.00 -0.01
0.9 0.901 0.11
0.8 0.802 0.25
0.5 0.502 0.40
45.0 -100.00
90.0 -100.00
Current R
135.0 -100.00
180.0 -100.00
45.0 -100.00 63.51
90.0 -100.00 47.6325
Current Y
135.0 -100.00 31.755
180.0 -100.00 15.8775
45.0 -100.00
90.0 -100.00
Current B
135.0 -100.00
180.0 -100.00
2750.0 -100.00
5500.0 -100.00
Voltage KV (RY)
8250.0 -100.00
11000.0 -100.00
2750.0 -100.00
5500.0 -100.00
Voltage KV (YB)
8250.0 -100.00
11000.0 -100.00
±0.2
2750.0 -100.00
5500.0 -100.00
Voltage KV (BR)
8250.0 -100.00
11000.0 -100.00
857.3 858.0 0.08
1714.7 1718.0 0.19
KW (PF 1.00)
2572.0 2576.0 0.15
KW (PF 1.00)
3429.4 3437.0 0.22
685.9 686.5 0.09
1371.7 1374.0 0.16
KW (PF 0.8 Lag)
2057.6 2061.0 0.16
2743.5 2745.0 0.06
857.3 854.5 -0.33
1714.7 1706.0 -0.51
KVA
2572.0 2560.0 -0.47
3429.4 3418.0 -0.33
514.4 513.2 -0.23
1028.8 1024.0 -0.47
KVAR (PF 0.8 Lag)
1543.2 1536.0 -0.47
2057.6 2049.0 -0.42
47 -100.00
48 -100.00
49 -100.00
Frequency 50 ±0.2 -100.00
51 -100.00
52 -100.00
53 -100.00

KW TRANSDUCER

Test Meter Reading Claimed Observed


Sl.No. Injected KW
In mA Error in mA Error in mA
Expected Actual
Output-1 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.06 0.06
3 1250 12 12.1 ±0.25 0.10
4 1875 16 16.1 0.10
5 2500 20 20.11 0.11
Output-2 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.07 0.07
3 1250 12 12.11 ±0.25 0.11
4 1875 16 16.1 0.10
5 2500 20 20.12 0.12
Injected Initial Expected Actual Final Claimed Observed
Parameters
KW Reading Final Value Value Error % Error %
KWH 3429.36 1232.91 1261.49 1261.54 ±0.2 0.00 0.05
KVAH 3429.36 1353.478 1382.06 1549.664 ±0.2 12.13 167.61

2300 2260 0.9826086957

0.982609
0.491304

1.732 11000 1785 0.999 3250 170.7565218


1.732 11000 1785 0.999 2437.5 128.0673913
1.732 11000 1785 0.999 1625 85.3782609
1.732 11000 1785 0.999 812.5 42.68913045

4 8 12 16 20
Ammeter 0 575 1150 1725 2300
0 0.25 0.5 0.75 1
PF -0.5 -0.75 1 0.75 0.5
-60 -41.4 0 41.4 60
MW 0 8.5 17 25.5 34
0 0.194 0.388 0.5825 0.7766
MVA 0 10.75 21.5 32.25 43
0 0.2455 0.491 0.7365 0.9826 0.8
MVAR 0 5.25 10.5 15.75 21
-41.4 0.8 0 0.2 0.4 0.6 0.8
V 0 3.30 6.6 9.9 13.2
0 19.05 38.11 57.16 76.21
Hz 45 47.50 50 52.5 55
0.948647343
0.7114855075
0.474323672
0.237161836
METER ERROR CALCULATION

Root 3 1.732
Voltage 33000 V Editable
Current 100 A Non-Editable
PF 1 1
PF 0.8 0.8
0.786
Real Time Instantaneous Values
Claimed Observed
Parameters Expected Value Actual Value
Error % Error %
-0.5 -0.5 0.00
-0.8 -0.8 0.00
-0.9 -0.9 0.00
Avg. PF 1.00 1.00 0.00
0.9 0.9 0.00
0.8 -100.00
0.5 0.5 0.00
25.0 -100.00
50.0 599.9 1099.80
Current R
75.0 -100.00
100.0 1200.4 1100.40
25.0 -100.00 63.51
50.0 599.8 1099.60 47.6325
Current Y
75.0 -100.00 31.755
100.0 1200.3 1100.30 15.8775
25.0 -100.00
50.0 600.1 1100.20
Current B
75.0 -100.00
100.0 1200.1 1100.10
8250.0 -100.00
16500.0 5495.0 -66.70
Voltage KV (RY)
24750.0 -100.00
33000.0 10999.0 -66.67
8250.0 -100.00
16500.0 5496.0 -66.69
Voltage KV (YB)
24750.0 -100.00
33000.0 11000.0 -66.67
±0.2
8250.0 -100.00
16500.0 5496.0 -66.69
Voltage KV (BR)
24750.0 -100.00
33000.0 10998.0 -66.67
1428.9 5720.0 300.31
2857.8 11430.0 299.96
KW (PF 1.00)
4286.7 17150.0 300.07
KW (PF 1.00)
5715.6 22880.0 300.31
1143.1 4570.0 299.78
2286.2 9150.0 300.22
KW (PF 0.8 Lag)
3429.4 13720.0 300.07
4572.5 18300.0 300.22
1428.9 5720.0 300.31
2857.8 11430.0 299.96
KVA
4286.7 17150.0 300.07
5715.6 22880.0 300.31
857.3 3430.0 300.07
1714.7 6860.0 300.07
KVAR (PF 0.8 Lag)
2572.0 10290.0 300.07
3429.4 13710.0 299.78
47 46.996 -0.01
48 -100.00
49 -100.00
Frequency 50 49.998 ±0.2 0.00
51 -100.00
52 -100.00
53 52.995 -0.01

KW TRANSDUCER

Test Meter Reading Claimed Observed


Sl.No. Injected KW
In mA Error in mA Error in mA
Expected Actual
Output-1 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.06 0.06
3 1250 12 12.1 ±0.25 0.10
4 1875 16 16.1 0.10
5 2500 20 20.11 0.11
Output-2 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.07 0.07
3 1250 12 12.11 ±0.25 0.11
4 1875 16 16.1 0.10
5 2500 20 20.12 0.12
Injected Initial Expected Actual Final Claimed Observed
Parameters
KW Reading Final Value Value Error % Error %
KWH 5715.6 1221.687 1269.32 1417.88 ±0.2 11.70 148.56
KVAH 5715.6 1353.478 1401.11 1549.664 ±0.2 10.60 148.56

2300 2260 0.9826086957

0.982609
0.491304

1.732 11000 1785 0.999 21000 1103.349833


1.732 11000 1785 0.999 15750 827.5123749
1.732 11000 1785 0.999 10500 551.6749166
1.732 11000 1785 0.999 5250 275.8374583

4 8 12 16 20
Ammeter 0 575 1150 1725 2300
0 0.25 0.5 0.75 1
PF -0.5 -0.75 1 0.75 0.5
-60 -41.4 0 41.4 60
MW 0 8.5 17 25.5 34
0 0.194 0.388 0.5825 0.7766
MVA 0 10.75 21.5 32.25 43
0 0.2455 0.491 0.7365 0.9826 0.8
MVAR 0 5.25 10.5 15.75 21
-41.4 0.8 0 0.2 0.4 0.6 0.8
V 0 3.30 6.6 9.9 13.2
0 19.05 38.11 57.16 76.21
Hz 45 47.50 50 52.5 55
0.479717319
0.359787989
0.239858659
0.1199293297
METER ERROR CALCULATION

Root 3 1.732
Voltage 6300 V Editable
Current 625 A Non-Editable
PF 1 1
PF 0.8 0.8
0.786
Real Time Instantaneous Values
Claimed Observed
Parameters Expected Value Actual Value
Error % Error %
-0.5 -100.00
-0.8 -100.00
-0.9 -100.00
Avg. PF 1.00 -100.00
0.9 -100.00
0.8 -100.00
0.5 -100.00
156.3 -100.00
312.5 -100.00
Current R
468.8 -100.00
625.0 624.6 -0.06
156.3 -100.00 63.51
312.5 -100.00 47.6325
Current Y
468.8 -100.00 31.755
625.0 624.8 -0.03 15.8775
156.3 -100.00
312.5 -100.00
Current B
468.8 -100.00
625.0 625.4 0.06
1575.0 -100.00
3150.0 -100.00
Voltage KV (RY)
4725.0 -100.00
6300.0 6303.0 0.05
1575.0 -100.00
3150.0 -100.00
Voltage KV (YB)
4725.0 -100.00
6300.0 -100.00
±0.2
1575.0 -100.00
3150.0 -100.00
Voltage KV (BR)
4725.0 -100.00
6300.0 -100.00
1704.9 -100.00
3409.9 -100.00
KW (PF 1.00)
5114.8 -100.00
KW (PF 1.00)
6819.8 6824.0 0.06
1364.0 -100.00
2727.9 2732.0 0.15
KW (PF 0.8 Lag)
4091.9 -100.00
5455.8 5462.0 0.11
1704.9 -100.00
3409.9 3413.0 0.09
KVA
5114.8 -100.00
6819.8 6824.0 0.06
1023.0 -100.00
2045.9 2046.0 0.00
KVAR (PF 0.8 Lag)
3068.9 -100.00
4091.9 4095.0 0.08
47 -100.00
48 -100.00
49 -100.00
Frequency 50 ±0.2 -100.00
51 -100.00
52 -100.00
53 -100.00

KW TRANSDUCER

Test Meter Reading Claimed Observed


Sl.No. Injected KW
In mA Error in mA Error in mA
Expected Actual
Output-1 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.06 0.06
3 1250 12 12.1 ±0.25 0.10
4 1875 16 16.1 0.10
5 2500 20 20.11 0.11
Output-2 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.07 0.07
3 1250 12 12.11 ±0.25 0.11
4 1875 16 16.1 0.10
5 2500 20 20.12 0.12
Injected Initial Expected Actual Final Claimed Observed
Parameters
KW Reading Final Value Value Error % Error %
KWH 6819.75 214.146 270.98 270.548 ±0.2 -0.16 -0.43
KVAH 6819.75 314.168 371.00 370.576 ±0.2 -0.11 -0.42

196.35 253.055
211.374 268.085
2300 2260 0.9826086957

0.982609
0.491304

1.732 11000 1785 0.999 21000 1103.349833


1.732 11000 1785 0.999 15750 827.5123749
1.732 11000 1785 0.999 10500 551.6749166
1.732 11000 1785 0.999 5250 275.8374583

4 8 12 16 20
Ammeter 0 575 1150 1725 2300
0 0.25 0.5 0.75 1
PF -0.5 -0.75 1 0.75 0.5
-60 -41.4 0 41.4 60
MW 0 8.5 17 25.5 34
0 0.194 0.388 0.5825 0.7766
MVA 0 10.75 21.5 32.25 43
0 0.2455 0.491 0.7365 0.9826 0.8
MVAR 0 5.25 10.5 15.75 21
-41.4 0.8 0 0.2 0.4 0.6 0.8
V 0 3.30 6.6 9.9 13.2
0 19.05 38.11 57.16 76.21
Hz 45 47.50 50 52.5 55
0.479717319
0.359787989
0.239858659
0.1199293297
METER ERROR CALCULATION

Root 3 1.732
Voltage 400 V Editable
Current 300 A Non-Editable
PF 1 1
PF 0.8 0.8
0.786
Real Time Instantaneous Values
Claimed Observed
Parameters Expected Value Actual Value
Error % Error %
-0.5 -100.00
-0.8 -100.00
-0.9 -100.00
Avg. PF 1.00 -100.00
0.9 -100.00
0.8 -100.00
0.5 -100.00
75.0 -100.00
150.0 -100.00
Current R
225.0 -100.00
300.0 -100.00
75.0 -100.00 63.51
150.0 -100.00 47.6325
Current Y
225.0 -100.00 31.755
300.0 299.9 -0.03 15.8775
75.0 -100.00
150.0 -100.00
Current B
225.0 -100.00
300.0 -100.00
100.0 -100.00
200.0 -100.00
Voltage KV (RY)
300.0 -100.00
400.0 400.5 0.13
100.0 -100.00
200.0 -100.00
Voltage KV (YB)
300.0 -100.00
400.0 -100.00
±0.2
100.0 -100.00
200.0 -100.00
Voltage KV (BR)
300.0 -100.00
400.0 -100.00
52.0 -100.00
103.9 -100.00
KW (PF 1.00)
155.9 -100.00
KW (PF 1.00)
207.8 208.0 0.08
41.6 -100.00
83.1 83.3 0.19
KW (PF 0.8 Lag)
124.7 -100.00
166.3 166.6 0.20
52.0 -100.00
103.9 104.0 0.08
KVA
155.9 -100.00
207.8 208.0 0.08
31.2 -100.00
62.4 62.3 -0.08
KVAR (PF 0.8 Lag)
93.5 -100.00
124.7 124.6 -0.08
47 -100.00
48 47.99 -0.02
49 -100.00
Frequency 50 49.99 ±0.2 -0.02
51 -100.00
52 51.99 -0.02
53 -100.00

KW TRANSDUCER

Test Meter Reading Claimed Observed


Sl.No. Injected KW
In mA Error in mA Error in mA
Expected Actual
Output-1 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.06 0.06
3 1250 12 12.1 ±0.25 0.10
4 1875 16 16.1 0.10
5 2500 20 20.11 0.11
Output-2 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.07 0.07
3 1250 12 12.11 ±0.25 0.11
4 1875 16 16.1 0.10
5 2500 20 20.12 0.12
Injected Initial Expected Actual Final Claimed Observed
Parameters
KW Reading Final Value Value Error % Error %
KWH 207.84 3.711 5.44 5.423 ±0.2 -0.37 -0.02
KVAH 207.84 4.022 5.75 5.735 ±0.2 -0.33 -0.02

2300 2260 0.9826086957

0.982609
0.491304

1.732 11000 1785 0.999 21000 1103.349833


1.732 11000 1785 0.999 15750 827.5123749
1.732 11000 1785 0.999 10500 551.6749166
1.732 11000 1785 0.999 5250 275.8374583

4 8 12 16 20
Ammeter 0 575 1150 1725 2300
0 0.25 0.5 0.75 1
PF -0.5 -0.75 1 0.75 0.5
-60 -41.4 0 41.4 60
MW 0 8.5 17 25.5 34
0 0.194 0.388 0.5825 0.7766
MVA 0 10.75 21.5 32.25 43
0 0.2455 0.491 0.7365 0.9826 0.8
MVAR 0 5.25 10.5 15.75 21
-41.4 0.8 0 0.2 0.4 0.6 0.8
V 0 3.30 6.6 9.9 13.2
0 19.05 38.11 57.16 76.21
Hz 45 47.50 50 52.5 55
0.479717319
0.359787989
0.239858659
0.1199293297
METER ERROR CALCULATION

Root 3 1.732
Voltage 400 V Editable
Current 175 A Non-Editable
PF 1 1
PF 0.8 0.8
0.786
Real Time Instantaneous Values
Claimed Observed
Parameters Expected Value Actual Value
Error % Error %
-0.5 -100.00
-0.8 -100.00
-0.9 -100.00
Avg. PF 1.00 -100.00
0.9 -100.00
0.8 -100.00
0.5 -100.00
43.8 -100.00
87.5 -100.00
Current R
131.3 -100.00
175.0 -100.00
43.8 -100.00 63.51
87.5 -100.00 47.6325
Current Y
131.3 -100.00 31.755
175.0 174.9 -0.06 15.8775
43.8 -100.00
87.5 -100.00
Current B
131.3 -100.00
175.0 -100.00
100.0 -100.00
200.0 -100.00
Voltage KV (RY)
300.0 -100.00
400.0 400.5 0.13
100.0 -100.00
200.0 -100.00
Voltage KV (YB)
300.0 -100.00
400.0 -100.00
±0.2
100.0 -100.00
200.0 -100.00
Voltage KV (BR)
300.0 -100.00
400.0 -100.00
30.3 -100.00
60.6 -100.00
KW (PF 1.00)
90.9 -100.00
KW (PF 1.00)
121.2 121.3 0.05
24.2 -100.00
48.5 48.6 0.13
KW (PF 0.8 Lag)
72.7 -100.00
97.0 97.1 0.15
30.3 -100.00
60.6 60.7 0.07
KVA
90.9 -100.00
121.2 121.3 0.05
18.2 -100.00
36.4 36.4 -0.06
KVAR (PF 0.8 Lag)
54.6 -100.00
72.7 72.7 -0.07
47 -100.00
48 47.99 -0.02
49 -100.00
Frequency 50 49.99 ±0.2 -0.02
51 -100.00
52 51.99 -0.02
53 -100.00

KW TRANSDUCER

Test Meter Reading Claimed Observed


Sl.No. Injected KW
In mA Error in mA Error in mA
Expected Actual
Output-1 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.06 0.06
3 1250 12 12.1 ±0.25 0.10
4 1875 16 16.1 0.10
5 2500 20 20.11 0.11
Output-2 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.07 0.07
3 1250 12 12.11 ±0.25 0.11
4 1875 16 16.1 0.10
5 2500 20 20.12 0.12
Injected Initial Expected Actual Final Claimed Observed
Parameters
KW Reading Final Value Value Error % Error %
KWH 121.24 6.883 7.89 7.874 ±0.2 -0.24 -0.02
KVAH 121.24 7.428 8.44 8.42 ±0.2 -0.22 -0.02

2300 2260 0.9826086957

0.982609
0.491304

1.732 11000 1785 0.999 21000 1103.349833


1.732 11000 1785 0.999 15750 827.5123749
1.732 11000 1785 0.999 10500 551.6749166
1.732 11000 1785 0.999 5250 275.8374583

4 8 12 16 20
Ammeter 0 575 1150 1725 2300
0 0.25 0.5 0.75 1
PF -0.5 -0.75 1 0.75 0.5
-60 -41.4 0 41.4 60
MW 0 8.5 17 25.5 34
0 0.194 0.388 0.5825 0.7766
MVA 0 10.75 21.5 32.25 43
0 0.2455 0.491 0.7365 0.9826 0.8
MVAR 0 5.25 10.5 15.75 21
-41.4 0.8 0 0.2 0.4 0.6 0.8
V 0 3.30 6.6 9.9 13.2
0 19.05 38.11 57.16 76.21
Hz 45 47.50 50 52.5 55
0.479717319
0.359787989
0.239858659
0.1199293297
METER ERROR CALCULATION

Root 3 1.732
Voltage 11000 V Editable
Current 1600 A Non-Editable
PF 1 1
PF 0.8 0.8
0.786
Real Time Instantaneous Values
Claimed Observed
Parameters Expected Value Actual Value
Error % Error %
-0.5 -0.5 0.00
-0.8 -0.8 0.00
-0.9 -0.9 0.00
Avg. PF 1.00 1.00 ±0.2 -0.10
0.9 0.9 0.00
0.8 0.8 0.00
0.5 0.5 0.00
400.0 -100.00
800.0 799.6 -0.05
Current R
1200.0 -100.00
1600.0 1600.5 0.03
400.0 -100.00 63.51
800.0 800.5 0.06 47.6325
Current Y
1200.0 -100.00 31.755
1600.0 1600.2 0.01 15.8775
400.0 -100.00
800.0 800.1 0.01
Current B
1200.0 -100.00
1600.0 1599.9 -0.01
2750.0 -100.00
5500.0 5495.0 -0.09
Voltage KV (RY)
8250.0 -100.00
11000.0 10999.0 -0.01
2750.0 -100.00
5500.0 -100.00
Voltage KV (YB)
8250.0 -100.00
11000.0 -100.00
±0.5
2750.0 -100.00
5500.0 -100.00
Voltage KV (BR)
8250.0 -100.00
11000.0 -100.00
7620.8 7620.0 -0.01
15241.6 15250.0 0.06
KW (PF 1.00)
22862.4 22880.0 0.08
KW (PF 1.00)
30483.2 30490.0 0.02
6096.6 6100.0 0.06
12193.3 12200.0 0.06
KW (PF 0.8 Lag)
18289.9 18295.0 0.03
24386.6 24400.0 0.06
7620.8 7620.0 -0.01
15241.6 15250.0 0.06
KVA
22862.4 22880.0 0.08
30483.2 30490.0 0.02
4572.5 4570.0 -0.05
9145.0 9140.0 -0.05
KVAR (PF 0.8 Lag)
13717.4 13710.0 -0.05
18289.9 18280.0 -0.05
47 46.998 0.00
48 -100.00
49 -100.00
Frequency 50 49.99 ±0.2 -0.02
51 -100.00
52 -100.00
53 52.999 0.00

KW TRANSDUCER

Test Meter Reading Claimed Observed


Sl.No. Injected KW
In mA Error in mA Error in mA
Expected Actual
Output-1 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.06 0.06
3 1250 12 12.1 ±0.25 0.10
4 1875 16 16.1 0.10
5 2500 20 20.11 0.11
Output-2 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.07 0.07
3 1250 12 12.11 ±0.25 0.11
4 1875 16 16.1 0.10
5 2500 20 20.12 0.12
Injected Initial Expected Actual Final Claimed Observed
Parameters
KW Reading Final Value Value Error % Error %
KWH 30483.2 2409.74 2663.77 2653.69 ±0.2 -0.38 -10.08
KVAH 30483.2 2696.487 2950.51 2940.428 ±0.2 -0.34 -10.09

2300 2260 0.9826086957

0.982609
0.491304

1.732 11000 1785 0.999 21000 1103.349833


1.732 11000 1785 0.999 15750 827.5123749
1.732 11000 1785 0.999 10500 551.6749166
1.732 11000 1785 0.999 5250 275.8374583

4 8 12 16 20
Ammeter 0 575 1150 1725 2300
0 0.25 0.5 0.75 1
PF -0.5 -0.75 1 0.75 0.5
-60 -41.4 0 41.4 60
MW 0 8.5 17 25.5 34
0 0.194 0.388 0.5825 0.7766
MVA 0 10.75 21.5 32.25 43
0 0.2455 0.491 0.7365 0.9826 0.8
MVAR 0 5.25 10.5 15.75 21
-41.4 0.8 0 0.2 0.4 0.6 0.8
V 0 3.30 6.6 9.9 13.2
0 19.05 38.11 57.16 76.21
Hz 45 47.50 50 52.5 55
0.479717319
0.359787989
0.239858659
0.1199293297
METER ERROR CALCULATION

Root 3 1.732
Voltage 11000 V Editable
Current 180 A Non-Editable
PF 1 1
PF 0.8 0.8
0.786
Real Time Instantaneous Values
Claimed Observed
Parameters Expected Value Actual Value
Error % Error %
-0.5 -100.00
-0.8 -100.00
-0.9 -100.00
Avg. PF 1.00 -100.00
0.9 -100.00
0.8 -100.00
0.5 -100.00
45.0 -100.00
90.0 -100.00
Current R
135.0 -100.00
180.0 -100.00
45.0 -100.00 63.51
90.0 -100.00 47.6325
Current Y
135.0 -100.00 31.755
180.0 -100.00 15.8775
45.0 -100.00
90.0 -100.00
Current B
135.0 -100.00
180.0 -100.00
2750.0 -100.00
5500.0 -100.00
Voltage KV (RY)
8250.0 -100.00
11000.0 -100.00
2750.0 -100.00
5500.0 -100.00
Voltage KV (YB)
8250.0 -100.00
11000.0 -100.00
±0.2
2750.0 -100.00
5500.0 -100.00
Voltage KV (BR)
8250.0 -100.00
11000.0 -100.00
857.3 857.1 -0.03
1714.7 -100.00
KW (PF 1.00)
2572.0 -100.00
KW (PF 1.00)
3429.4 3435.0 0.16
685.9 -100.00
1371.7 -100.00
KW (PF 0.8 Lag)
2057.6 -100.00
2743.5 -100.00
857.3 854.2 -0.37
1714.7 -100.00
KVA
2572.0 -100.00
3429.4 3413.0 -0.48
514.4 -100.00
1028.8 -100.00
KVAR (PF 0.8 Lag)
1543.2 -100.00
2057.6 -100.00
47 -100.00
48 -100.00
49 -100.00
Frequency 50 ±0.2 -100.00
51 -100.00
52 -100.00
53 -100.00

KW TRANSDUCER

Test Meter Reading Claimed Observed


Sl.No. Injected KW
In mA Error in mA Error in mA
Expected Actual
Output-1 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.06 0.06
3 1250 12 12.1 ±0.25 0.10
4 1875 16 16.1 0.10
5 2500 20 20.11 0.11
Output-2 4-20 mA
1 0 4 4.01 0.01
2 625 8 8.07 0.07
3 1250 12 12.11 ±0.25 0.11
4 1875 16 16.1 0.10
5 2500 20 20.12 0.12
Injected Initial Expected Actual Final Claimed Observed
Parameters
KW Reading Final Value Value Error % Error %
KWH 3429.36 1221.687 1250.27 1417.88 ±0.2 13.41 167.62
KVAH 3429.36 1353.478 1382.06 1549.664 ±0.2 12.13 167.61

2300 2260 0.9826086957

0.982609
0.491304

1.732 11000 1785 0.999 21000 1103.349833


1.732 11000 1785 0.999 15750 827.5123749
1.732 11000 1785 0.999 10500 551.6749166
1.732 11000 1785 0.999 5250 275.8374583

4 8 12 16 20
Ammeter 0 575 1150 1725 2300
0 0.25 0.5 0.75 1
PF -0.5 -0.75 1 0.75 0.5
-60 -41.4 0 41.4 60
MW 0 8.5 17 25.5 34
0 0.194 0.388 0.5825 0.7766
MVA 0 10.75 21.5 32.25 43
0 0.2455 0.491 0.7365 0.9826 0.8
MVAR 0 5.25 10.5 15.75 21
-41.4 0.8 0 0.2 0.4 0.6 0.8
V 0 3.30 6.6 9.9 13.2
0 19.05 38.11 57.16 76.21
Hz 45 47.50 50 52.5 55
0.479717319
0.359787989
0.239858659
0.1199293297

Vous aimerez peut-être aussi