Vous êtes sur la page 1sur 39

CONTROL LOGIC

DIAGRAM
34K-101

Project Essar Oil refinery project Engineering Review Status


ABB Document 08000-SD-001819 R-Reviewed without comments
Number

RN1-Reviewed with non-


SSC PO Number 3860 C 000017 technical comments

RN2-Reviewed with comments as


ABB reference Number 08000-0603 noted

ABB SDR Code(s) RJ-Rejected


(See POR)

Equipment Number(s)
(If applicable and not indicated 34 K - 101 FI-For information only
nearby the Document Title
block)

4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn Gesing TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 1
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 COVER
39 Bl.
B-4 TURBOLOG DSP BASIC/4
THE OUTPUT REMAINS IN LOGIC STATUS "1"
& IF ALL INPUTS ARE IN LOGIC STATUS "1"
M-4 TURBOLOG DSP COMPACT M-4

OVS OVERSPEED PROTECTION UNIT


THE OUTPUT REMAINS IN LOGIC STATUS "1"
>
=1 IF ANY OF THE INPUTS IS IN LOGIC STATUS "1"
BN BENTLY NEVADA 3500 MONITORING SYSTEM

HMI HUMAN MACHINE INTERFACE


ON DELAY INPUT
t1 0
I O THE OUTPUT CHANGES FROM "0" TO "1"
AFTER TIME DELAY OF t1 OUTPUT DCS DISTRIBUTED CONTROL SYSTEM
12 sec.
t1
MCC MOTOR CONTROL CENTER

PLC PROGRAMMABLE LOGIC CONTROL


OFF DELAY INPUT
0 t2
I O THE OUTPUT CHANGES FROM "1" TO "0"
AFTER TIME DELAY OF t2 OUTPUT UCP UNIT CONTROL PANEL
12 sec.
t2
LCP LOCAL CONTROL PANEL

1 THE OUTPUT STATUS IS THE OPPOSITE OF THE INPUT MNSW MAIN SWITCH

R-S FLIP-FLOP MMS MACHINE MONITORING SYSTEM


S WITH PREFERENTIAL STATUS "RESET"
1 0

R
1 1 CNT CONTROL

SGS SAFE GUARD SYSTEM


1 THE OUTPUT CHANGES TO STATUS "1" WHEN INPUT CHANGES TO STATUS "1"
THE OUTPUT MANITAINS STATUS "1" FOR A TIME "T". AFTER THIS TIME
OUTPUT GOES TO STATUS "0"

INPUT

OUTPUT
T T

4 FINAL 28.08.2006 Ges/Ges Date 28.01.2006 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn Gesing TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 2
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SYMBOLS & ABBREVIATIONS
39 Bl.
Table of contents
Title Drawn Revision Title Drawn Revision
No. Document Sheet Remarks No. Document Sheet Remarks
Date Date Date Date
This dwg. is the property of MAN Turbomaschinen AG and is solely for the use of the party to which it is handed over. Diese Zeichnung ist Eigentum der MAN Turbomaschinen AG und nur mit ihrem Einvernehmen zu verwenden.

Gesing 4 GESING 4
1 10000253530 1 COVER
31 10000253530 31 SEAL STEAM CONTROL
28.01.06 28.08.2006 28.01.06 28.08.2006
Gesing 4 GESING 4
2 10000253530 2 SYMBOLS & ABBREVIATIONS
32 10000253530 32 GC ANTI SURGE CONTROL
28.01.2006 28.08.2006 28.01.06 28.08.2006
CONTENTS Gesing 1 GESING 4
3 10000253530 3 33 10000253530 33
06.05.2006 06.05.2006 GC ANTI SURGE CONTROL 28.01.06 28.08.2006
Gesing 4 GESING 4
4 10000253530 4 SPARE
34 10000253530 34 SURGE
28.01.06 28.08.2006 28.01.06 28.08.2006
Gesing 4 GESING 4
5 10000253530 5 SPARE
35 10000253530 35 SPEED CONTROL
28.01.06 28.08.2006 28.01.06 28.08.2006
Gesing 4 GESING 4
6 10000253530 6 SPARE
36 10000253530 36 SPEED CONTROL
28.01.06 28.08.2006 28.01.06 28.08.2006
Gesing 4 GESING 4
7 10000253530 7 SPARE
37 10000253530 37 SPEED CONTROL
28.01.06 28.08.2006 28.01.06 28.08.2006
Gesing 4 GESING 4
8 10000253530 8 SPARE
38 10000253530 38 FLOW CONTROL
28.01.06 28.08.2006 28.01.06 28.08.2006
Gesing 4 GESING 4
9 10000253530 9 SPARE
39 10000253530 39 IGV-CONTROL
28.01.06 28.08.2006 01.04.2006 28.08.2006
GESING 4
10 10000253530 10
OIL RESERVOIR HEATER 28.01.06 28.08.2006
GESING 4
11 10000253530 11 OIL RESERVOIR HEATER 28.01.06 28.08.2006
GESING 4
12 10000253530 12 OIL RESERVOIR MIST FAN 28.01.06 28.08.2006
GESING 4
13 10000253530 13 AUX. OIL PUMP 28.01.06 28.08.2006
GESING 4
14 10000253530 14 GLAND STEAM VACUUM FAN 28.01.06 28.08.2006
GESING 4
15 10000253530 15 COND. PUMP 2 28.01.06 28.08.2006
GESING 4
16 10000253530 16 ROTOR TURNING GEAR 28.01.06 28.08.2006
GESING 4
17 10000253530 17
DEBRIS FILTER 28.01.06 28.08.2006
GESING 4
18 10000253530 18 MAIN COND PUMP ESD 28.01.06 28.08.2006
GESING 4
19 10000253530 19 SPARE 28.01.06 28.08.2006
GESING 4
20 10000253530 20 BENTLY NEVADA TURBINE 28.01.06 28.08.2006
GESING 4
21 10000253530 21 BENTLY NEVADA TURBINE 28.01.06 28.08.2006
GESING 4
22 10000253530 22 BENTLY NEVADA COMPRESSOR 28.01.06 28.08.2006
GESING 4
23 10000253530 23 BENTLY NEVADA COMPRESSOR 28.01.06 28.08.2006
GESING 4
24 10000253530 24
OVS 28.01.06 28.08.2006
GESING 4
25 10000253530 25 ALARM-SIGNALS 28.01.06 28.08.2006
GESING 4
26 10000253530 26 START UP INTERLOCKING 28.01.06 28.08.2006
GESING 4
27 10000253530 27 SHUTDOWN DELAYED 28.01.06 28.08.2006
GESING 4
28 10000253530 28
SHUTDOWN / START UP 28.01.06 28.08.2006
GESING 4
29 10000253530 29 LOGIC HARDWIRED 28.01.06 28.08.2006
GESING 4
30 10000253530 30 SPARE 28.01.06 28.08.2006
Remarks :

Date 28.08.2006 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.

Drawn Gesing
ESSARAX Title CUSTOMER CONTENTS TK5
1 Revision 06.05.2006 Ges/Ges Checked Sheet 3
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 39 Bl.
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn Gesing TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 4
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPARE
39 Bl.
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn Gesing TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 5
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPARE
39 Bl.
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn Gesing TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 6
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPARE
39 Bl.
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn Gesing TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 7
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPARE
39 Bl.
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn Gesing TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 8
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPARE
39 Bl.
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn Gesing TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 9
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPARE
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1

2 2
34HS 065-1 1 0=OFF 34HY 065-1 /11.4
OIL RESERVOIR HEATER START OIL RESERVOIR HEATER ON
3 LCP 1=START S
1 0 1=ON
OELTANK HEIZUNG EIN
3
OELTANK HEIZUNG START MCC
1 1
R
4 4

5 5

6 6
/26.5 34LSL 021 0=LOW
OIL RESERVOIR
7 1=OK 7
OELTANK
34HS 065-2 0=STOP 0=OFF 34HY 065-2 /11.8

8 LCP OIL RESERVOIR HEATER STOP


& OIL RESERVOIR HEATER OFF
8
OELTANK HEIZUNG STOP OELTANK HEIZUNG AUS MCC

9 & 9

10 10
/11.15 34TSH 065 0=HH 34TAH 065
11 OIL RESERVOIR HEATER
1 1=HH
OIL RESERVOIR HEATER
11
OELTANK HEIZUNG OELTANK HEIZUNG LCP

12 12
/11.18 34TC 065 0=H
OIL RESERVOIR HEATER
13 13
OELTANK HEIZUNG
t=5s
14 t1 0 14
34XA 065
15 on delay & S
1 0 1=FAIL
OIL RESERVOIR HEATER FAILURE
15
OELTANK HEIZUNG STOERUNG LCP
1 1
R
16 1 16
/17.16 /12.16 34HS 321 1
/15.17 FAILURE
ALARM ACKNOWLEDGE
17 /14.16 LCP
/13.18 17
ALARM QUITTIERUNG

18 18
/11.4 34YSH 065 34YBH 065
OIL RESERVOIR HEATER ON OIL RESERVOIR HEATER ON
19 1=ON 1=ON
OELTANK HEIZUNG LÄUFT
19
OELTANK HEIZUNG EIN LCP

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 10
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 OIL RESERVOIR HEATER
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs Outputs Dest. Line

1 1
LV MCC Note:
2 HEATER ON means: 2
BY OTHERS main switch is closed
and heater is in standby or
3 both relais are energized and heater is working 3
/10.3 34HY 065-1 0=OFF 34YSH 065 /10.19
OIL RESERVOIR HEATER ON OIL RESERVOIR HEATER ON
4 1=ON 1=ON
OELTANK HEIZUNG EIN
4
OELTANK HEIZUNG EIN HEATER
ON

5 +24VDC 5

6 6

7 7
/10.8 34HY 065-2 0=OFF
OIL RESERVOIR HEATER OFF
8 8
OELTANK HEIZUNG AUS
OIL RESERVOIR HEATER OIL RESERVOIR HEATER

9 ON = 1 OFF = 1
FIELD 9

10 OIL RESERVOIR HEATER 10

11 11

12 12

13 13

14 14
MANUAL RESET
IN CASE OF TSHH 0=HH 34TSH 065 /10.11
OIL RESERVOIR HEATER
15 TSHH
OELTANK HEIZUNG
15
T
16 80 °C
+24VDC 16

17 17
0=H 34TC 065 /10.13
OIL RESERVOIR HEATER
18 TSH
OELTANK HEIZUNG
18
T
19 0...70 °C
+24VDC 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 11
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 OIL RESERVOIR HEATER
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1

2 2
2s
34HS 304-1 1
OIL RESERVOIR MIST FAN START
3 LCP 1=START 3
OELDUNSTABSAUGGEBLAESE START

4 4

5 5
t=3s
1 34HY 304-1
OIL RESERVOIR MIST FAN START
6 1=START
OELDUNSTABSAUGGEBLAESE START
MCC
6

7 >
=1 S 7
1 0
t=3s
1 1
/13.8 34PSL 291 0=LOW R 1 0=STOP 34HY 304-2
8 OIL SIMULATION LINE 1=OK 1 1 OIL RESERVOIR MIST FAN STOP MCC
8
OEL SIMULIERLEITUNG OELDUNSTABSAUGGEBLAESE STOP

9 9

10 10

11 11
34HS 304-2 0=STOP
12 LCP OIL RESERVOIR MIST FAN STOP
& 12
OELDUNSTABSAUGGEBLAESE STOP

13 13
t=5s
14 t1 0 14
34XA 304
15 on delay & S
1 0 1=FAIL
OIL RESERVOIR MIST FAN FAILURE LCP
15
OELDUNSTABSAUGGEBLAESE STOERUNG
1 1
/17.16 34HS 321 1 R
/15.17
16 /14.16 LCP
/13.18
ALARM ACKNOWLEDGE
1 16
ALARM QUITTIERUNG

FAILURE
17 17
/26.16 34YSH 304 34YBH 304
OIL RESERVOIR MIST FAN RUNNING OIL RESERVOIR MIST FAN RUNNING
18 MCC 1=RUN 1=RUN
OELDUNSTABSAUGGEBLAESE LAEUFT
LCP
18
OELDUNSTABSAUGGEBLAESE LAEUFT

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 12
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 OIL RESERVOIR MIST FAN
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1
t=3s
1 34HY 302-1
AUX. OIL PUMP START
2 1=START
HILFSOELPUMPE START
MCC
2
t=2s
34HS 302-1 1
3 LCP AUX. OIL PUMP START 1=START >
=1 S 3
HILFSOELPUMPE START 1 0
t=3s
1 1
R 1 0=STOP 34HY 302-2
4 1 1 AUX. OIL PUMP STOP MCC
4
HILFSOELPUMPE STOP

5 5

6 6

7 7
/12.8 34PSL 291 0=LOW
OIL SIMULATION LINE
8 1=OK 8
OEL SIMULIERLEITUNG
&
10 Min.
9 (RUNDOWN TIME) 9
/29.9 34SZSHH 001-1 0=TRIP 0 t2
/28.4
ST SPEED (OVS) UNIT TRIPED
10 /35.6
/15.10 10
PLC DT UEBERDREHZAHLSCHUTZ UNIT TRIPED

34YSH 305 OFF DELAY >


=1 S
1 0
MCC ST TURNING GEAR RUNNING
11 1=RUN
1 1 11
DT ROTORDREHVORRICHTUNG LAEUFT R
34US 001-1-7
OVS ST OVS UNIT ZERO SPEED
12 1=ZERO 12
DT UEBERDREHZAHLSCHUTZ NULLDREHZAHL

13 13

14 14
t=2s
34HS 302-2 0=STOP 1
AUX. OIL PUMP STOP
15 LCP
15
HILFSOELPUMPE STOP
&
t=5s
16 t1 0 16
34XA 302
17 on delay & S
1 0 1=FAIL
AUX. OIL PUMP FAILURE LCP
17
HILFSOELPUMPE STOERUNG
1 1
/17.16 34HS 321 1 R
/15.17
18 /14.16 LCP
/12.16
ALARM ACKNOWLEDGE
1 18
ALARM QUITTIERUNG
FAILURE

19 19
34YSH 302 34YBH 302
AUX. OIL PUMP RUNNING AUX. OIL PUMP RUNNING
20 MCC 1=RUN 1=RUN
HILFSOELPUMPE LAEUFT
LCP
20
HILFSOELPUMPE LAEUFT

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 13
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 AUX. OIL PUMP
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1

2 2
2s
34HS 306-1 1
GLAND STEAM VACUUM FAN START
3 LCP 1=START 3
WRASENDAMPF ABSAUGGEBLAESE START

4 4

5 5
t=3s
1 34HY 306-1
GLAND STEAM VACUUM FAN START
6 1=START
WRASENDAMPF ABSAUGGEBLAESE START
MCC
6

7 S
1 0
7
t=3s
1 1
R 1 0=OFF 34HY 306-2
8 1 1 GLAND STEAM VACUUM FAN OFF MCC
8
WRASENDAMPF ABSAUGGEBLAESE AUS

9 9

10 10

11 11
34HS 306-2 0=STOP
12 LCP GLAND STEAM VACUUM FAN STOP
& 12
WRASENDAMPF ABSAUGGEBLAESE STOP

13 13
t=5s
14 t1 0 14
34XA 306
15 on delay & S
1 0 1=FAIL
GLAND STEAM VACUUM FAN FAILURE LCP
15
WRASENDAMPF ABSAUGGEBLAESE STOERUNG
1 1
/17.16 34HS 321 1 R
/15.17
16 /13.18 LCP
/12.16
ALARM ACKNOWLEDGE
1 16
ALARM QUITTIERUNG

FAILURE
17 17
34YSH 306 34YBH 306
GLAND STEAM VACUUM FAN RUNNING GLAND STEAM VACUUM FAN RUNNING
18 MCC 1=RUN 1=RUN
WRASENDAMPF ABSAUGGEBLAESE LAEUFT
LCP
18
WRASENDAMPF ABSAUGGEBLAESE LAEUFT

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 14
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 GLAND STEAM VACUUM FAN
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1
t=3s
1 34HY 303-1
ST COND CONDENSATE PUMP 2 START
2 1=START
DT KONDENSATPUMPE 2 START
MCC
2
t=2s
34HS 303-1 1
3 LCP ST COND CONDENSATE PUMP 2 START >
=1 S 3
DT KONDENSATPUMPE 2 START 1 0
t=3s
1 1
R 1 0=STOP 34HY 303-2
4 1 1 ST COND CONDENSATE PUMP 2 STOP MCC
4
DT KONDENSATPUMPE 2 STOP

5 5

6 6

7 7
34LSH 027
ST CONDENSER
8 1=H 8
DT KONDENSATOR
&

9 9
/29.9 34SZSHH 001-1 0=TRIP
/28.4
ST SPEED (OVS) UNIT TRIPED
10 /35.6
/13.10 10
PLC DT UEBERDREHZAHLSCHUTZ UNIT TRIPED

11 11

12 12
t=2s
34HS 303-2 0=STOP 1
LCP ST COND CONDENSATE PUMP 2 STOP
13 13
DT KONDENSATPUMPE 2 STOP
&
/26.8 34LSL 027 0=LOW
ST CONDENSER
14 1=OK 14
DT KONDENSATOR
/18.11 34LSLL 027 0=LL t=5s
ST CONDENSER LEVEL ALARM LL
15 t1 0 15
DT KONDENSATOR FUELLSTAND ALARM LL
34XA 303
16 on delay & S
1 0 1=FAIL
ST COND CONDENSATE PUMP 2 FAILURE LCP
16
DT KONDENSATPUMPE 2 STOERUNG
1 1
/17.16 34HS 321 1 R
/14.16
17 /13.18 LCP
/12.16
ALARM ACKNOWLEDGE
1 17
ALARM QUITTIERUNG

FAILURE
18 18

19 19
34YSH 303 34YBH 303
MCC ST COND CONDENSATE PUMP 2 RUNNING ST COND CONDENSATE PUMP 2 RUNNING
20 1=RUN 1=RUN
DT KONDENSATPUMPE 2 RUNNING
LCP
20
DT KONDENSATPUMPE 2 LÄUFT

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 15
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 COND. PUMP 2
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1
2s
/1.K2 34HS 305-1 1
/3.H3
LCP ST TURNING GEAR START
2 /21. 1=START 2
DT ROTORDREHVORRICHTUNG START
34US 001-1 &
/28.
/31.4
ST OVS UNIT ZERO SPEED
>
=1
3 /25.19 1=ZERO 3
DT UEBERDREHZAHLSCHUTZ NullDrz
>
=1
4 4

5 5
T=20S t=3s
/34. 34US 313 t1 0 1 34HY 305-1 /2.H7
/21.
UCP POWER SUPPLY ON ST TURNING GEAR START
6 UCP 1=ON 1=START
DT ROTORDREHVORRICHTUNG START
MCC
6
UCP SPANNUNGSVERSORGUNG AN
ON DELAY
7 & S
1 0
7
t=2s t=3s
1 1
/27. 34SSLL 001 1=LL 1 R 1 0=STOP 34HY 305-2 /2.H7
/36.8 /21.
8 B-4 ST SPEED CONTROL SPEED LL 1 1 ST TURNING GEAR STOP MCC
8
DT DREHZAHLREGLUNG DREHZAHL LL DT ROTORDREHVORRICHTUNG STOP

9 9
t=2s
10 1 10
>
=1
11 11

12 12
/1.K2 34HS 305-2 0=STOP
/3.H3
LCP ST TURNING GEAR STOP
13 /21.
13
DT ROTORDREHVORRICHTUNG STOP
t=5s
14 t1 0 14
27.9
LUBE OIL PRESSURE LOW 34XA 305 /1.K2
/3.G3
15 & on delay & S
1 0 1=FAIL
ST TURNING GEAR FAILURE /21. LCP
15
0=LOW DT ROTORDREHVORRICHTUNG STOERUNG
1 1
/21. 34GSH 036-2 R
16 ST TURNING GEAR COVER MOUNTED 1=OK 1 16
DT DREHVORRICHTNG SCHUTZHAUBE MONTIERT

FAILURE
17 17
/3.L2 /14.1634HS 321 1
/33. /13.18
/12.16 ALARM ACKNOWLEDGE
18 /17.16 LCP
/15.17 18
ALARM QUITTIERUNG
/2.H7 34YSH 305 34YBH 305 /1.K1
/21. /3.G3
ST TURNING GEAR RUNNING ST TURNING GEAR RUNNING
19 /13.11 1=RUN 1=RUN
DT ROTORDREHVORRICHTUNG LAEUFT
/21. LCP
19
DT ROTORDREHVORRICHTUNG LAEUFT

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 16
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 ROTOR TURNING GEAR
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1

2 2

3 3

4 4

5 5
t=3s
1 34HY 307-1
ST COND DEBRIS FILTER START
6 1=START
DT KOND DEBRIS FILTER START
MCC
6
2s
34HS 307-1 1
LCP ST COND DEBRIS FILTER START
7 1=START S
1 0
7
DT KOND DEBRIS FILTER START t=3s
1 1
R 1 0=OFF 34HY 307-2
8 1 1 ST COND DEBRIS FILTER OFF MCC
8
DT KOND DEBRIS FILTER AUS

9 9

10 10

11 11
34HS 307-2 0=STOP
12 LCP ST COND DEBRIS FILTER STOP & 12
DT KOND DEBRIS FILTER STOP

13 13
t=5s
14 t1 0 14
34XA 307
15 on delay & S
1 0 1=FAIL
ST COND DEBRIS FILTER FAILURE LCP
15
DT KOND DEBRIS FILTER STOERUNG
1 1
/15.17 34HS 321 1 R
/14.16
16 /13.18 LCP
/12.16
ALARM ACKNOWLEDGE
1 16
ALARM QUITTIERUNG

FAILURE
17 17
34YSH 307 34YBH 307
ST COND DEBRIS FILTER RUNNING ST COND DEBRIS FILTER RUNNING
18 MCC 1=RUN 1=RUN
DT KOND DEBRIS FILTER LAEUFT
LCP
18
DT KOND DEBRIS FILTER LAEUFT

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 17
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 DEBRIS FILTER
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1

2 2
2 (NEW SHEET)
3 3
34HS 323-1 1
ST COND PUMP LIVE STEAM ESD VALVE OPEN
4 LCP 4
DT KOND PUMP FRISCHDAMPF SSV ÖFFNEN
34UZ 029
ST COND PUMP LIVE STEAM ESD VALVE SOV
5 S
1 0 1=ON
DT KOND PUMP FRISCHDAMPF SSV SOV
FIELD
5
1 1
R
6 6

7 7

8 8
34HS 323-2 0=OFF 1
LCP ST COND PUMP LIVE STEAM ESD VALVE CLOSE
9 9
DT KOND PUMP FRISCHDAMPF SSV SCHLIESSEN

10 & 10
/15.15 34LSLL 027 0=LL
ST CONDENSER LEVEL ALARM LL
11 THRESHOLD 11
DT KONDENSATOR FUELLSTAND ALARM LL

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 18
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 MAIN COND PUMP ESD
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs Outputs Dest. Line

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 19
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPARE
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs BENTLY NEVADA 3500 MACHINE MONITORING SYSTEM Outputs Dest. Line

1 1
NOTE:
34GZSHH 028-1 if the signal is OK,
ST SHAFT AXIAL DISPLACEMENT
2 1=HH
the output relais will be energzied, signal will be "1" 2
DT WELLE AXIALVERSCHIEBUNG
34GZSHH 028-2 & if the signal not OK,
ST SHAFT AXIAL DISPLACEMENT
3 1=HH the output relay will be deenergized, signal will "0" 3
DT WELLE AXIALVERSCHIEBUNG
34GZSLL 028-1 0=HH 34GZSHH 028 /28.11

4 ST SHAFT AXIAL DISPLACEMENT 1=LL >


=1 1 1 ST SHAFT AXIAL DISPLACEMENT PLC
4
DT WELLE AXIALVERSCHIEBUNG DT WELLE AXIALVERSCHIEBUNG

34GZSLL 028-2 &


ST SHAFT AXIAL DISPLACEMENT
5 1=LL 5
DT WELLE AXIALVERSCHIEBUNG

6 6
34GSH 028-1
ST SHAFT AXIAL DISPLACEMENT
7 1=H 7
DT WELLE AXIALVERSCHIEBUNG
34GSH 028-2 &
ST SHAFT AXIAL DISPLACEMENT
8 1=H 8
DT WELLE AXIALVERSCHIEBUNG
34GSL 028-1 0=H 34GSH 028
9 ST SHAFT AXIAL DISPLACEMENT 1=L >
=1 1 ST SHAFT AXIAL DISPLACEMENT PLC
9
DT WELLE AXIALVERSCHIEBUNG DT WELLE AXIALVERSCHIEBUNG

34GSL 028-2 &


ST SHAFT AXIAL DISPLACEMENT
10 1=L 10
DT WELLE AXIALVERSCHIEBUNG

11 11
34VZSHH 001-1
ST JOURN. BRG. INLET SIDE
12 1=HH 12
DT RADIALLAGER EINTRITTSSEITE
34VZSHH 001-2 0=HH 34VZSHH 001 /27.20

13 ST JOURN. BRG. INLET SIDE 1=HH >


=1 1 1 ST JOURN. BRG. INLET SIDE PLC
13
DT RADIALLAGER EINTRITTSSEITE DT RADIALLAGER EINTRITTSSEITE

34VSH 001-1
ST JOURN. BRG. INLET SIDE
14 1=H 14
DT RADIALLAGER EINTRITTSSEITE
34VSH 001-2 0=H 34VSH 001
15 ST JOURN. BRG. INLET SIDE 1=H >
=1 1 ST JOURN. BRG. INLET SIDE PLC
15
DT RADIALLAGER EINTRITTSSEITE DT RADIALLAGER EINTRITTSSEITE

16 16
34VZSHH 002-1
ST JOURN. BRG. OUTLET SIDE
17 1=HH 17
DT RADIALLAGER AUSTRITTSSEITE
34VZSHH 002-2 0=HH 34VZSHH 002 /27.19

18 ST JOURN. BRG. OUTLET SIDE 1=HH >


=1 1 1 ST JOURN. BRG. OUTLET SIDE PLC
18
DT RADIALLAGER AUSTRITTSSEITE DT RADIALLAGER AUSTRITTSSEITE

34VSH 002-1
ST JOURN. BRG. OUTLET SIDE
19 1=H 19
DT RADIALLAGER AUSTRITTSSEITE
34VSH 002-2 0=H 34VSH 002
20 ST JOURN. BRG. OUTLET SIDE 1=H >
=1 1 ST JOURN. BRG. OUTLET SIDE
20
PLC
DT RADIALLAGER AUSTRITTSSEITE DT RADIALLAGER AUSTRITTSSEITE

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 20
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 BENTLY NEVADA TURBINE
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs BENTLY NEVADA 3500 MACHINE MONITORING SYSTEM Outputs Dest. Line

1 1
NOTE:
34TSH 056-1-1 if the signal is OK,
ST THRUST BRG. OUTBOARD
2 1=H
the output relais will be energzied, signal will be "1" 2
DT AUESSERES AXILALLAGER
34TSH 056-1-2 if the signal not OK,
ST THRUST BRG. OUTBOARD
3 1=H the output relay will be deenergized, signal will "0" 3
DT AUESSERES AXILALLAGER
34TSH 056-2-1 0=H 34TSH 056-1
4 ST THRUST BRG. INBOARD 1=H >
=1 1 ST THRUST BRG. TEMP HIGH PLC
4
DT INNERES AXIALLAGER DT AXIALLAGER TEMP HOCH

34TSH 056-2-2
ST THRUST BRG. INBOARD
5 1=H 5
DT INNERES AXIALLAGER

6 6
34TSH 056-3-1
ST JOURN. BRG. INLET SIDE
7 1=H 7
DT RADIALLAGER EINTRITTSSEITE
34TSH 056-3-2
ST JOURN. BRG. INLET SIDE
8 1=H 8
DT RADIALLAGER EINTRITTSSEITE
34TSH 056-4-1 0=H 34TSH 056-3
9 ST JOURN. BRG. OUTLET SIDE 1=H >
=1 1 ST JOURN. BRG. TEMP HIGH PLC
9
DT RADIALLAGER AUSTRITTSSEITE DT RADIALLAGER TEMP HOCH

34TSH 056-4-2
ST JOURN. BRG. OUTLET SIDE
10 1=H 10
DT RADIALLAGER AUSTRITTSSEITE

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 21
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 BENTLY NEVADA TURBINE
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs BENTLY NEVADA 3500 MACHINE MONITORING SYSTEM Outputs Dest. Line

1 1
NOTE:
34GZSHH 029-1 if the signal is OK,
AX COMPR SHAFT AXIAL DISPLACEMENT
2 1=HH
the output relais will be energzied, signal will be "1" 2
AX KOMPR. WELLE AXIALVERSCHIEBUNG
34GZSHH 029-2 & if the signal not OK,
AX COMPR SHAFT AXIAL DISPLACEMENT
3 1=HH the output relay will be deenergized, signal will "0" 3
AX KOMPR. WELLE AXIALVERSCHIEBUNG
34GZSLL 029-1 0=HH 34GZSHH 029 /28.12

4 AX COMPR SHAFT AXIAL DISPLACEMENT 1=LL >


=1 1 1 AX COMPR SHAFT AXIAL DISPLACEMENT PLC
4
AX KOMPR. WELLE AXIALVERSCHIEBUNG AX KOMPR. WELLE AXIALVERSCHIEBUNG

34GZSLL 029-2 &


AX COMPR SHAFT AXIAL DISPLACEMENT
5 1=LL 5
AX KOMPR. WELLE AXIALVERSCHIEBUNG

6 6
34GSH 029-1
AX COMPR SHAFT AXIAL DISPLACEMENT
7 1=H 7
AX KOMPR. WELLE AXIALVERSCHIEBUNG
34GSH 029-2 &
AX COMPR SHAFT AXIAL DISPLACEMENT
8 1=H 8
AX KOMPR. WELLE AXIALVERSCHIEBUNG
34GSL 029-1 0=H 34GSH 029
9 AX COMPR SHAFT AXIAL DISPLACEMENT 1=L >
=1 1 AX COMPR SHAFT AXIAL DISPLACEMENT PLC
9
AX KOMPR. WELLE AXIALVERSCHIEBUNG AX KOMPR. WELLE AXIALVERSCHIEBUNG

34GSL 029-2 &


AX COMPR SHAFT AXIAL DISPLACEMENT
10 1=L 10
AX KOMPR. WELLE AXIALVERSCHIEBUNG

11 11
34VZSHH 003-1
AX COMPR JOURN. BRG. DE
12 1=HH 12
AX KOMPR. RADIALLAGER DE
34VZSHH 003-2 0=HH 34VZSHH 003 /27.18

13 AX COMPR JOURN. BRG. DE 1=HH >


=1 1 1 AX COMPR JOURN. BRG. DE PLC
13
AX KOMPR. RADIALLAGER DE AX KOMPR. RADIALLAGER DE

34VSH 003-1
AX COMPR JOURN. BRG. DE
14 1=H 14
AX KOMPR. RADIALLAGER DE
34VSH 003-2 0=H 34VSH 003
15 AX COMPR JOURN. BRG. DE 1=H >
=1 1 AX COMPR JOURN. BRG. DE PLC
15
AX KOMPR. RADIALLAGER DE AX KOMPR. RADIALLAGER DE

16 16
34VZSHH 004-1
AX COMPR JOURN. BRG. NDE
17 1=HH 17
AX KOMPR. RADIALLAGER NDE
34VZSHH 004-2 0=HH 34VZSHH 004 /27.17

18 AX COMPR JOURN. BRG. NDE 1=HH >


=1 1 1 AX COMPR JOURN. BRG. NDE PLC
18
AX KOMPR. RADIALLAGER NDE AX KOMPR. RADIALLAGER NDE

34VSH 004-1
AX COMPR JOURN. BRG. NDE
19 1=H 19
AX KOMPR. RADIALLAGER NDE
34VSH 004-2 0=H 34VSH 004
20 AX COMPR JOURN. BRG. NDE 1=H >
=1 1 AX COMPR JOURN. BRG. NDE
20
PLC
AX KOMPR. RADIALLAGER NDE AX KOMPR. RADIALLAGER NDE

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 22
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 BENTLY NEVADA COMPRESSOR
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs BENTLY NEVADA 3500 MACHINE MONITORING SYSTEM Outputs Dest. Line

1 1
NOTE:
34TSH 056-5-1 if the signal is OK,
AX COMPR THRUST BRG. OUTBOARD
2 1=H
the output relais will be energzied, signal will be "1" 2
AX KOMPR. AUESSERES AXILALLAGER
34TSH 056-5-2 if the signal not OK,
AX COMPR THRUST BRG. OUTBOARD
3 1=H the output relay will be deenergized, signal will "0" 3
AX KOMPR. AUESSERES AXILALLAGER
34TSH 056-6-1 34TSH 056-5
4 AX COMPR THRUST BRG. INBOARD 1=H >
=1 1 0=H
AX COMPR THRUST BRG. PLC
4
AX KOMPR. INNERES AXIALLAGER AX KOMPR. AXIALLAGER

34TSH 056-6-2
AX COMPR THRUST BRG. INBOARD
5 1=H 5
AX KOMPR. INNERES AXIALLAGER

6 6
34TSH 056-7-1
AX COMPR JOURN. BRG. DE
7 1=H 7
AX KOMPR. RADIALLAGER DE
34TSH 056-7-2
AX COMPR JOURN. BRG. DE
8 1=H 8
AX KOMPR. RADIALLAGER DE
34TSH 056-8-1 34TSH 056-7
9 AX COMPR JOURN. BRG. NDE 1=H >
=1 1 0=H
AX COMPR JOURN. BRG. PLC
9
AX KOMPR. RADIALLAGER NDE AX KOMPR. RADIALLAGER

34TSH 056-8-2
AX COMPR JOURN. BRG. NDE
10 1=H 10
AX KOMPR. RADIALLAGER NDE

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 23
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 BENTLY NEVADA COMPRESSOR
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs


BRAUN OVERSPEED PROTECTION SYSTEM Outputs Dest. Line

1 1
BRAUN FOR DETAILS SEE MAN TURBO DRAWING
/1.F13 34XS 001-1 10000166652 sheet 2
/17.C1
ST OVS UNIT RESET OVERSPEED
2 /28.2
2
PLC DT UEBERDREHZAHLSCHUTZ RESET
PROTECTION UNIT
3 3
/28.10 34UZS 001-1-4 0=TRIP
ST OVS UNIT EXTERNAL TRIP
4 EXTERNAL TRIP 1 X2 5 4
PLC DT UEBERDREHZAHLSCHUTZ EXTERNER TRIP
/28.11 34UZS 001-1-5 0=TRIP 0=HH 34SZSHH 001-1A /29.3
ST OVS UNIT EXTERNAL TRIP ST SPEED (OVS) TRIP
5 EXTERNAL TRIP 2
6
DT UEBERDREHZAHLSCHUTZ TRIP
5
PLC DT UEBERDREHZAHLSCHUTZ EXTERNER TRIP UCP
/28.12 34UZS 001-1-6 0=TRIP
ST OVS UNIT EXTERNAL TRIP
6 EXTERNAL TRIP 3 6
PLC DT UEBERDREHZAHLSCHUTZ EXTERNER TRIP

7 X2 7 7
0=HH 34SZSHH 001-1B /29.6
ST SPEED (OVS) TRIP
8 8
DT UEBERDREHZAHLSCHUTZ TRIP
8
UCP

9 9

10 10

11 11
34SZE 001-1-1 SPEED PROBE
ST SPEED (OVS)
12 12
DT UEBERDREHZAHLSCHUTZ
34SZE 001-1-2 SPEED PROBE
ST SPEED (OVS)
13 X1 13
DT UEBERDREHZAHLSCHUTZ
4
34SZE 001-1-3 0=FAULT 34UA 001-1-1
SPEED PROBE 5
ST SPEED (OVS) ST OVS UNIT SYSTEM FAULT CH-A
14 X1 DT UEBERDREHZAHLSCHUTZ FEHLER CH-A
14
DT UEBERDREHZAHLSCHUTZ PLC
10
0=FAULT 34UA 001-1-2
11
ST OVS UNIT SYSTEM FAULT CH-B
15 X1 DT UEBERDREHZAHLSCHUTZ FEHLER CH-B
15
PLC
16
0=FAULT 34UA 001-1-3
17
ST OVS UNIT SYSTEM FAULT CH-C
16 DT UEBERDREHZAHLSCHUTZ FEHELR CH-C
16
PLC

17 X1 17
6
34SS 001-1-4
7
ST OVS UNIT ZERO SPEED CH-A
18 X1 1=ZERO
DT UEBERDREHZAHLSCHUTZ NullDrz CH-A
18
PLC
12
34SS 001-1-5
13
ST OVS UNIT ZERO SPEED CH-B
19 X1 1=ZERO
DT UEBERDREHZAHLSCHUTZ NullDrz CH-B
19
PLC
18
34SS 001-1-6
19
ST OVS UNIT ZERO SPEED CH-C
20 1=ZERO
DT UEBERDREHZAHLSCHUTZ NullDrz CH-C
20
PLC

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 24
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 OVS
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line


0=FAULT 34UA 001-1-1 /28.
ST OVS UNIT SYSTEM FAULT CH-A
1 DT UEBERDREHZAHLSCHUTZ FEHLER CH-A
1
DCS

0=FAULT 34UA 001-1-2 /28.


ST OVS UNIT SYSTEM FAULT CH-B
2 DT UEBERDREHZAHLSCHUTZ FEHLER CH-B
2
DCS

0=FAULT 34UA 001-1-3 /28.


ST OVS UNIT SYSTEM FAULT CH-C
3 DT UEBERDREHZAHLSCHUTZ FEHELR CH-C
3
DCS
/1.F12 34UA 001-1-1 0=FAULT 34XA 002 /1.L2

4
/28.
/24.14 ST OVS UNIT SYSTEM FAULT CH-A
1 >
=1 24 1=ALARM
COMMON PRE-ALARM
/1.E2
/33.
4
/26.4
OVS DT UEBERDREHZAHLSCHUTZ FEHLER CH-A ALLG. VORALARM DCS
/1.F12 34UA 001-1-2 0=FAULT
/28.
5 /24.15 ST OVS UNIT SYSTEM FAULT CH-B
1 5
OVS DT UEBERDREHZAHLSCHUTZ FEHLER CH-B NOTE
/1.F12 34UA 001-1-3 0=FAULT
/28. FOR FURTHER INPUTS TO OR-BLOCK
6 /24.16 ST OVS UNIT SYSTEM FAULT CH-C
1 SEE 24 IN MAN-TURBO P&ID`s ESSARAX 814775 6
OVS DT UEBERDREHZAHLSCHUTZ FEHELR CH-C

7 7

8 8
/11. 34YA 308
AX COMPR SURGE DETECTOR SENSOR FAULT
9 1=FAIL MODBUS 9
B-4 AX KOMPR. PUMPSCHUTZ GEBERSTÖRUNG
/9. 34GA 033
/33.17
AX COMPR BLOW OFF VALVE POSITION FAIL.
10 1=FAIL MODBUS 10
B-4 AX KOMPR. ABBLASEVENTIL STELLUNGSFEHLER
/26. 34GA 034
/36.10
ST LIVE STEAM CONTROL VALVE POS. FAIL
11 MODBUS 11
B-4 DT FRISCHDAMPFREGELVENTIL STELLUNGSFEHLER

12 12
/23. 34PZSH 225-1 0=H
ST EXHAUST (p > 0,9 kg/cm²a)
13 13
DT AUSTRITT (p > 0,9 kg/cm²a)
/23. 34PZSH 225-2 0=H 34PZAH 225 /1.D7
/3.E4
14 ST EXHAUST (p > 0,9 kg/cm²a)
& 1=H
ST EXHAUST (p > 0,9 kg/cm²a) /22.
14
DT AUSTRITT (p > 0,9 kg/cm²a) DT AUSTRITT (p > 0,9 kg/cm²a)

/23. 34PZSH 225-3 0=H


ST EXHAUST (p > 0,9 kg/cm²a)
15 15
DT AUSTRITT (p > 0,9 kg/cm²a)
2 out of 3

34PZSH 225 /23.


voting

/31.13
16 1 1=H
ST EXHAUST (p > 0,9 kg/cm²a)
16
DT AUSTRITT (p > 0,9 kg/cm²a)

17 17
/1.E12 34SS 001-1-4
/28.
ST OVS UNIT ZERO SPEED CH-A
18 /24.18 1=ZERO 18
OVS DT UEBERDREHZAHLSCHUTZ NullDrz CH-A
2 out of 3

/1.E12 34SS 001-1-5 34US 001-1 /28.


voting

/28. /31.4
ST OVS UNIT ZERO SPEED CH-B ST OVS UNIT ZERO SPEED
19 /24.19 1=ZERO 1=ZERO
DT UEBERDREHZAHLSCHUTZ NullDrz
/16.3
19
OVS DT UEBERDREHZAHLSCHUTZ NullDrz CH-B
/1.E12 34SS 001-1-6
/28.
ST OVS UNIT ZERO SPEED CH-C
20 /24.20 1=ZERO 20
OVS DT UEBERDREHZAHLSCHUTZ NullDrz CH-C

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 25
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 ALARM-SIGNALS
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1

2 2
28.20
COMMON TRIP
3 1=OK 3
0=TRIP
34XA 002
COMMON PRE-ALARM
4 1=ALARM 4
ALLG. VORALARM
/10.7 34LSL 021 0=LOW
OIL RESERVOIR
5 1=OK 5
OELTANK
34TSL 067 0=LOW
OIL FILTER UPSTREAM
6 1=OK 6
VOR OELFILTER
34LSL 022 0=LOW
OVERHEAD RESERVOIR
7 1=OK 7
HOCHBEHAELTER
/15.14 34LSL 027 0=LOW
ST CONDENSER
8 1=OK 8
DT KONDENSATOR
28.1
START UP INTERLOCKS OK
9 & 9
1=OK

10 10
34GSH 038-1
AX COMPR INLET GUIDE VANES OPEN
11 1=OPEN 11
AX KOMPR. VORLEITSCHAUFEL OFFEN
34GSH 031
AX COMPR BLOW OFF VALVE OPEN
12 1=OPEN 12
AX KOMPR. ABBLASEVENTIL OFFEN
34GSL 032
AX COMPR UNLOADING FLAP OPEN
13 1=OPEN 13
AX KOMPR. ENTLASTUNGSKLAPPE OFFEN
34GSL 035
ST LIVE STEAM CONTROL VALVE CLOSED
14 1=CLOSE 14
DT FRISCHDAMPFREGELVENTIL GESCHL.

15 15
/12.18 34YSH 304
OIL RESERVOIR MIST FAN RUNNING
16 1=RUN 16
OELDUNSTABSAUGGEBLAESE LAEUFT

17 17
34XS 313
MACHINE MONITORING SYSTEM OK RELAIS
18 1=OK 18
BN MASCHINENUEBERWACHUNGSSYSTEM OK RELAIS

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 26
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 START UP INTERLOCKING
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1
34PZSHH 225-1 0=HH 34PZAHH 225-1
2 ST EXHAUST (p > 1,2 kg/cm²a)
1 1=HH
ST EXHAUST
2
DT AUSTRITT (p > 1,2 kg/cm²a) DT AUSTRITT LCP

34PZSHH 225-2

2 oo 3
0=HH
ST EXHAUST (p > 1,2 kg/cm²a)
3 3
DT AUSTRITT (p > 1,2 kg/cm²a)
34PZSHH 225-3 0=HH 34LZAHH 024
4 ST EXHAUST (p > 1,2 kg/cm²a)
1 1=HH
ST CONDENSER
4
DT AUSTRITT (p > 1,2 kg/cm²a) DT KONDENSATOR LCP

34LZSHH 024-1 0=HH


ST CONDENSER
5 5
DT KONDENSATOR
34LZSHH 024-2

2 oo 3
0=HH
ST CONDENSER
6 6
DT KONDENSATOR
34LZSHH 024-3 0=HH 34PZALL 284-1
7 ST CONDENSER
1 1=LL
LUBE OIL HEADER
7
DT KONDENSATOR SCHMIEROELSAMMELLEITUNG LCP

34PZSLL 284-1 0=LL


LUBE OIL HEADER
8 8
SCHMIEROELSAMMELLEITUNG
34PZSLL 284-2 0=LL 2 oo 3 LUBE OIL PRESSURE LOW 16.15
LUBE OIL HEADER
9 9
SCHMIEROELSAMMELLEITUNG 0=LOW
34PZSLL 284-3 0=LL
LUBE OIL HEADER
10 10
SCHMIEROELSAMMELLEITUNG
34TDAHH 120
11 1 1=HH
ST DIFF TEMP VALVE CHEST INTERMED.
11
DT DIFF TEMP VENTILGEHAEUSE MITTE LCP

34TDSHH 120 0=HH


12 ST DIFF TEMP VALVE CHEST INTERMED. 1=OK >
=1 12
DT DIFF TEMP VENTILGEHAEUSE MITTE

13 13
/38.2 34SSL 001 0=LOW
/32.4
ST SPEED CONTROL MIN GOVERNOR SPEED
14 1=OK 14
B-4 DT DREHZAHLREGLUNG MIN REGELDREHZAHL

15 15
/32.17 34US 026-7 TRIP DELAYED 28.18

16 AX COMPR SURGE DETECTOR 3rd SURGE 1=SURGE 1 & 16


AX KOMPR. PUMPSCHUTZ 3. PUMNPSTOSS 0=TRIP
/22.18 34VZSHH 004 0=HH
AX COMPR JOURN. BRG. NDE
17 17
BN AX KOMPR. RADIALLAGER NDE
/22.13 34VZSHH 003 0=HH
AX COMPR JOURN. BRG. DE
18 18
BN AX KOMPR. RADIALLAGER DE
/20.18 34VZSHH 002 0=HH
ST JOURN. BRG. OUTLET SIDE
19 19
BN DT RADIALLAGER AUSTRITTSSEITE
/20.13 34VZSHH 001 0=HH
ST JOURN. BRG. INLET SIDE
20 20
BN DT RADIALLAGER EINTRITTSSEITE

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 27
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SHUTDOWN DELAYED
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line


26.9
START UP INTERLOCKS OK 34XS 001-1 /24.2
ST OVS UNIT RESET
1 DT UEBERDREHZAHLSCHUTZ RESET
1
1=OK t=2s
& & OVS

34HS 315 1
ST LIFT OFF ESD VALVE
2 2
DT ANHEBEN SSV
34SZAHH 001-1
3 & S
1 0 1=HH
ST SPEED (OVS) TRIP
3
DT UEBERDREHZAHLSCHUTZ TRIP
t=2s LCP
1 1
/29.9 34SZSHH 001-1 0=TRIP 1 R
/35.6
4 /15.10
/13.10
ST SPEED (OVS) UNIT TRIPED
1 1 4
UCP DT UEBERDREHZAHLSCHUTZ UNIT TRIPED

5 5
34HS 318-B
TRIP RESET
t=2s
6 1
6
SCHNELLABSCHALTUNG RESET
LCP
>
=1
34HS 318-A
TRIP RESET
7 7
UCP SCHNELLABSCHALTUNG RESET

8 8

9 9
0=TRIP 34UZS 001-1-4 /24.4
ST OVS UNIT EXTERNAL TRIP
10 DT UEBERDREHZAHLSCHUTZ EXTERNER TRIP
10
OVS
/20.4 34GZSHH 028 0=HH 0=TRIP 34UZS 001-1-5 /24.5
ST SHAFT AXIAL DISPLACEMENT ST OVS UNIT EXTERNAL TRIP
11 BN
DT UEBERDREHZAHLSCHUTZ EXTERNER TRIP
11
DT WELLE AXIALVERSCHIEBUNG OVS
/22.4 34GZSHH 029 0=HH S 0=TRIP 34UZS 001-1-6 /24.6
AX COMPR SHAFT AXIAL DISPLACEMENT 1 0 ST OVS UNIT EXTERNAL TRIP
12 1 1 DT UEBERDREHZAHLSCHUTZ EXTERNER TRIP
12
BN AX KOMPR. WELLE AXIALVERSCHIEBUNG S R OVS
1 0
34HZS 003 0=TRIP
1 1
13 CONTROL PANEL CONSOLE 00-CON-1 (CCB)
& & R 13
CONTROL PANEL CONSOLE 00-CON-1 (CCB)
34HZS 001 0=TRIP
LOCAL CONTROL PANEL ESD BUTTON
14 14
NOTAUSTASTER OERTLICHE BEDIENTAFEL
4
LCP

34HZS 316 0=TRIP 34UZA 001-4 CO

15 ESD BUTTON COMPR. SKID


1 1=TRIP
COMMON TRIP-ALARM OXYDICER
15
FIELD NOTAUSTASTER KOMPR. SKID

34HZS 002 0=TRIP


(FIELD MODIFICATION) ALLG. ABSCHALT-ALARM

34UZA 001-3
SGS

REACTOR
16 CONTROL PANEL ESD BUTTON
1 1=TRIP
COMMON TRIP-ALARM
SGS 16
UCP NOTAUSTASTER STEUERSCHRANK ALLG. ABSCHALT-ALARM

34UZA 001-2 COMPR.

17 1 1=TRIP
COMMON TRIP-ALARM ESD
17
ALLG. ABSCHALT-ALARM
t=2s VALVE

27.16
TRIP DELAYED 0 t2 34UZA 028-1
18 & 1 1=TRIP
COMMON TRIP-ALARM
18
0=TRIP ALLG. ABSCHALT-ALARM LCP
OFF DELAY 34UZA 028
COMMON TRIP-ALARM
19 MODBUS
ALLG. ABSCHALT-ALARM
19
t=5s DCS

34HS 319 1 COMMON TRIP 26.3

20 ST NORMAL STOP 1=STOP 1 & 1=OK 32.7


20
LCP DT NORMAL STOP 0=TRIP 35.9

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 28
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SHUTDOWN / START UP
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs


HARDWIRED LOGIC IN UCP Outputs Dest. Line

1 1

2 2
/24.5 34SZSHH 001-1A 0=HH 1=ON 34UZ 037
ST SPEED (OVS) TRIP ST LIVE STEAM CONTROL VALVE ON OFF
3 0=OFF
DT FRISCHDAMPFREGELVENTIL EIN AUS
3
OVS DT UEBERDREHZAHLSCHUTZ TRIP FIELD

4 4

5 5
/24.8 34SZSHH 001-1B 0=HH 0=OFF 34UZ 025
ST SPEED (OVS) TRIP ST LIVE STEAM TRIP VALVE ON / OFF
6 1=ON
DT FRISCHDAMPF-SSV EIN AUS
6
OVS DT UEBERDREHZAHLSCHUTZ TRIP FIELD

7 7

8 8
0=TRIP 34SZSHH 001-1 /28.4
/35.6
9 & ST SPEED (OVS) UNIT TRIPED /15.10
/13.10 9
DT UEBERDREHZAHLSCHUTZ UNIT TRIPED

10 10
PLC

11 11
/32.7 34XS 308-2 0=OFF 34UZ 026
12 AX COMPR ASC SOV ON 1=OK & 1=ON
AX COMPR UNLOADING FLAP SOV ON OFF
12
PLC AX KOMPR. ASC SOV EIN AX KOMPR. ENTLASTUNGSKLAPPE SOV EIN AUS FIELD

13 13
/34.6 34US 026-2
14 AX COMPR SURGE DETECTOR 1st SURGE 1=SURGE 1 14
AX KOMPR. PUMPSCHUTZ PUMNPSTOSS
/33.6 34XS 308-1
AX COMPR ASC SAFETY LINE REACHED
15 1=OK 15
B-4 AX KOMPR. ASC SICHERHEITSLINIE

1=ON 34UZ 037


16 & 0=OFF
AX COMPR BLOW OFF VALVE ON OFF
16
AX KOMPR. ABBLASEVENTIL EIN AUS FIELD

17 17

18 t=5s 18
1
& 34UZ 027
19 & 1=ON
AX COMPR DISCHARGE CHECK VALVE SOV
19
AX KOMPR. AUSTRITT RUECKSCHLAGKLAPPE FIELD

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 29
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 LOGIC HARDWIRED
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs Outputs Dest. Line

1 1

2 2

3 3

4 4

5 5

6 6

7 7

8 8

9 9

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 30
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPARE
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 NOTE 1
t=2s
34HS 313-1 1 SEE ALSO MAN TURBO DRAWING:
ST SEAL STEAM CONTROL ON
2 1=ON
- CONTROL SCHEMATIC (DWG No. 10000253528, Sheet2) 2
UCP DT SPERRDAMPFREGELUNG EIN

3 & 3
34US 001-1
ST OVS UNIT ZERO SPEED
4 1=ZERO 4
DT UEBERDREHZAHLSCHUTZ NullDrz
t=60s
5 t1 0 5

6 ON DELAY
6

7 7

8 8

9 9
34XS 273
ST SEAL STEAM CONTROL RELEASE
10 S
1 0 1=ON
DT SPERRDAMPFREGELUNG FREIGABE
10
t=2s B-4
1 1
34HS 313-2 0=OFF 1 >
=1 R
11 ST SEAL STEAM CONTROL OFF
1 11
UCP DT SPERRDAMPFREGELUNG AUS

12 & 12
34PZSH 225
ST EXHAUST (p > 0,9 kg/cm²a)
13 1=H 13
DT AUSTRITT (p > 0,9 kg/cm²a)

14 14

15 15
34TSLL 119
16 ST SEAL STEAM SUPPLY OUTLET SIDE 0=LL 1 16
DT SPERRDAMPFZUFUHR AUSTRITTSSEITE
&
t=180s
17 t1 0
17

18 ON DELAY 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 31
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SEAL STEAM CONTROL
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1
t=2s
34HS 310-3 1 0=STOP 34XS 308-2-2 /34.10
AX COMPR ASC MANUAL RELEASE AX COMPR SURGE DETECTOR RELEASE
2 1=OK
AX KOMPR. PUMPSCHUTZ FREIGABE
2
LCP AX KOMPR. ASC HANDFREIGABE M-4

&
3 3
/38.2 34SSL 001 0=LOW 0=STOP 34XS 308-2-1 /33.8
/27.14
4 ST SPEED CONTROL MIN GOVERNOR SPEED 1=OK & 1=OK
AX COMPR ASC RELEASE
4
B-4 DT DREHZAHLREGLUNG MIN REGELDREHZAHL AX KOMPR. ASC FREIGABE
S B-4
1 0
1 1
5 & R 5
t=2s
34HS 054-1 0=OPEN 1
AX COMPR ASC VALVE MAN QUICK OPEN
6 6
LCP AX KOMPR. ASC RUECKSETZ
28.20
COMMON TRIP 0=OFF 34XS 308-2 /29.12

7 1=OK & 1=OK


AX COMPR ASC SOV ON
7
0=TRIP AX KOMPR. ASC SOV EIN UCP

8 8
/33.5 34XS 308-1-1 34YBH 308-1
AX COMPR ASC SAFETY LINE REACHED AX COMPR ASC SAFETY LINE REACHED
9 1=OK MODBUS 1=OK
AX KOMPR. ASC SICHERHEITSLINIE
9
UCP AX KOMPR. ASC SICHERHEITSLINIE DCS

10 10

11 11

12 12
/34.5 34US 026-1 34YBH 308-2
AX COMPR SURGE DETECTOR 1st SURGE AX COMPR SURGE DETECTOR 1st SURGE
13 1=SURGE MODBUS 1=SURGE
AX KOMPR. PUMPSCHUTZ 1. PUMNPSTOSS
13
UCP AX KOMPR. PUMPSCHUTZ 1. PUMNPSTOSS DCS

14 14
/34.9 34US 026-4 34YBH 308-3
AX COMPR SURGE DETECTOR 2nd SURGE AX COMPR SURGE DETECTOR 2nd SURGE
15 1=SURGE MODBUS 1=SURGE
AX KOMPR. PUMPSCHUTZ 2. PUMNPSTOSS
15
UCP AX KOMPR. PUMPSCHUTZ 2. PUMNPSTOSS DCS

16 16
/27.16 34US 026-7 34YBH 308-4
AX COMPR SURGE DETECTOR 3rd SURGE AX COMPR SURGE DETECTOR 3rd SURGE
17 1=SURGE MODBUS 1=SURGE
AX KOMPR. PUMPSCHUTZ 3. PUMNPSTOSS
17
UCP AX KOMPR. PUMPSCHUTZ 3. PUMNPSTOSS DCS

18 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 32
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 GC ANTI SURGE CONTROL
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs TURBOLOG DSP BASIC-4 Outputs Dest. Line

1 1

2 2

3 3

4 4
HARDWIRED IN UCP 34XS 308-1-1 /32.9
AX COMPR ASC SAFETY LINE REACHED
5 1=OK
AX KOMPR. ASC SICHERHEITSLINIE
5
PLC

ANTI SURGE 34XS 308-1 /29.15


AX COMPR ASC SAFETY LINE REACHED
6 CONTROLLER 1=OK
AX KOMPR. ASC SICHERHEITSLINIE
6
UCP

34GC 033
AX COMPR BLOW OFF VALVE SETPOINT
7 AX KOMPR. ABBLASEVENTIL SOLLWERT
7
FIELD
/32.4 34XS 308-2-1 0=STOP VISULISATION ON Human Machine Interface (HMI)
AX COMPR ASC RELEASE
8 1=OK 8
PLC AX KOMPR. ASC FREIGABE
SAFETY LINE REACHED

9 CONTROLLER OUTPUT 9
VALVE FEED BACK FAULT
34HS 310-1 34UI 023-51
10 AX COMPR ASC INCREASE MANUAL SETPOINT MANUAL SETPOINT Yh AX COMPR ASC MANUAL SETPOINT
10
LCP AX KOMPR. ASC AX KOMPR. ASC HANDSOLLWERT LCP

34HS 310-2
11 AX COMPR ASC DECREASE MANUAL SETPOINT SUCTION TEMPERATURE (TI-34064) 11
LCP AX KOMPR. ASC HANDSOLLWERT VERRINGERN
SUCTION NOZZLE DIFF. PRESSUR (PDT-34282)
DISCHARGE PRESSUR (PI-34005)
12 12
BLOW OFF VALVE ACTUAL POSITION (UI-34023-41)
34TT 064 34UI 023-41
AX COMPR SUCTION NOZZLE AX COMPR ASC VALVE POSITION
13 FIELD
AX KOMPR. ASC VENTILSTELLUNG
13
AX KOMPR. SAUGSTUTZEN LCP
SUCTION THROUGHFLOW
34PDT 282-1
14 FIELD AX COMPR SUCTION NOZZLE ENTHALPY DIFFERENCE (HEAD) 14
MAX

AX KOMPR. SAUGSTUTZEN
34PDT 282-2
15 FIELD AX COMPR SUCTION NOZZLE EFFECTIVE CONTROL DIFFERENCE 15
AX KOMPR. SAUGSTUTZEN Setpoint for Anti Surge Control Valve
34PT 005 CONTROLLER OUTPUT
FIELD AX COMPR DISCHARGE
16 16
AX KOMPR. AUSTRITT DISTANCE FROM OPERATING POINT TO CONTROL LINE
34GT 033 34GA 033
FAILURE VALVE POSITION
FIELD AX COMPR BLOW OFF VALVE ACTUAL VALUE AX COMPR BLOW OFF VALVE POSITION FAIL.
17 1=FAIL
AX KOMPR. ABBLASEVENTIL STELLUNGSFEHLER
17
AX KOMPR. ABBLASEVENTIL ISTWERT PLC

18 INCREASE MANUAL SETPOINT 18


DECREASE MANUAL SETPOINT
ASC-VALVE QUICK OPEN
19 19
ASC MAUNAL RELEASE

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked QUI Sheet 33
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 GC ANTI SURGE CONTROL
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs TURBOLOG DSP COMPACT M-4 Outputs Dest. Line

1 1
34PDT 283-1 34UR 026
AX COMPR SUCTION NOZZLE AX COMPR SURGE DETECTOR SURGE COUNTER
2 FIELD 2

MAX
AX KOMPR. SAUGSTUTZEN AX KOMPR. PUMPSCHUTZ PUMNPSTOSSZÄHLER UCP
SURGE
34PDT 283-2
AX COMPR SUCTION NOZZLE DETECTOR
3 FIELD 3
AX KOMPR. SAUGSTUTZEN
34TT 062 HARDWIRED IN UCP 34UA 026-2
4 FIELD AX COMPR SUCTION NOZZLE 1 1=SURGE
AX COMPR SURGE DETECTOR 1st SURGE
4
AX KOMPR. SAUGSTUTZEN AX KOMPR. PUMPSCHUTZ PUMNPSTOSS UCP

34TT 001 34US 026-1 /32.13


FIELD AX COMPR SUCTION AX COMPR SURGE DETECTOR 1st SURGE
5 1=SURGE
AX KOMPR. PUMPSCHUTZ 1. PUMNPSTOSS PLC 5
AX KOMPR. ANSAUGUNG
34US 026-2 /29.14
AX COMPR SURGE DETECTOR 1st SURGE
6 1=SURGE
AX KOMPR. PUMPSCHUTZ PUMNPSTOSS
6
34HS 053
AX COMPR SURGE DETECTOR RESET
7 7
UCP AX KOMPR. PUMPSCHUTZ RUECKSETZEN

HARDWIRED IN UCP 34UA 026-4


AX COMPR SURGE DETECTOR 2nd SURGE
8 1=SURGE
AX KOMPR. PUMPSCHUTZ 2. PUMNPSTOSS
8
UCP

34US 026-4 /32.15


AX COMPR SURGE DETECTOR 2nd SURGE
9 1=SURGE
AX KOMPR. PUMPSCHUTZ 2. PUMNPSTOSS
9
PLC
/32.2 34XS 308-2-2 0=STOP
AX COMPR SURGE DETECTOR RELEASE
10 1=OK 10
PLC AX KOMPR. PUMPSCHUTZ FREIGABE

34UA 026-7
AX COMPR SURGE DETECTOR 3rd SURGE
11 1=SURGE
AX KOMPR. PUMPSCHUTZ 3. PUMNPSTOSS
11

12 12

13 13

14 14
0=FAIL 34US 026-6
AX COMPR SURGE DETECTOR WATCHDOG
15 AX KOMPR. PUMPSCHUTZ WATCHDOG
15

16 16

17 17

18 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 34
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SURGE
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs ABB AC-410 Outputs Dest. Line

1 1

2 2

3 3
t=2s
34HS 312-1 1
ST SPEED CONTROL ON
4 4
LCP DT DREHZAHLREGLUNG EIN

5 & 5
/29.9 34SZSHH 001-1 0=TRIP 0=OFF 34SX 001-4
/28.4
ST SPEED (OVS) UNIT TRIPED ST SPEED CONTROL RELEASE
6 /15.10
/13.10
S
1 0 1=ON
DT DREHZAHLREGLUNG FREIGABE
6
UCP DT UEBERDREHZAHLSCHUTZ UNIT TRIPED B-4
1 1
R
7 7

8 8
28.20
COMMON TRIP
9 1=OK 9
0=TRIP

10 10

11 11

12 12

13 13

14 14

15 15

16 16

17 17

18 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 35
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPEED CONTROL
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs TURBOLOG DSP BASIC-4 Outputs Dest. Line


/1.J11 34SX 001-4 0=OFF
/27. RELEASE
ST SPEED CONTROL RELEASE
1 /35.6 1=ON 1
PLC DT DREHZAHLREGLUNG FREIGABE t=2s STEAM TURBINE
/1.K15 34HS 050 1 0=OFF 34YBH 310-1 /1.K16
/3.J4 AUTO ACCEL. SPEED CONTROL /27.
ST ACCELERATE ST SPEED CONTROL RUNNING
2 /28.
1=ON
DT DREHZAHLREGLUNG LÄUFT
/3.J6
2
DT BESCHLEUNIGEN LCP
/1.K14 34HS 052-1 34YBH 310-2 /1.K16
/3.J4 MAN + /27.
ST SPEED INCREASE ST SPEED CONTROL AUTO ACTIVE
3 /28.
for details 1=AUTO
DT DREHZAHLREGLUNG AUTO ACTIVE
/3.J6
3
DT DREHZAHL ERHOEHEN LCP
see sheet 37
/1.K14 34HS 052-2 34YBH 310-3 /1.K15
/3.J3 MAN - /27.
ST SPEED DECREASE ST SPEED CONTROL MAN ACTIVE
4 /28.
1=MAN
DT DREHZAHLREGLUNG MAN ACTIVE
/3.J5
4
DT DREHZAHL VERRINGERN LCP
/1.K10 34HIC 309
/1.K13 EXTERNAL SETPOINT
SIC MAN. OPERATION FROM DCS SETPOINT
5 /33.
5
DCS SIC MANUELBETRIEB VON DCS SOLLWERT

0=HIGH 34SSH 001 /27.


ST SPEED CONTROL MAX. GOVERNOR SPEED
6 1=OK
DT DREHZAHLREGLUNG MAX. REGELDREHZAHL
6
PLC
/23. 34SE 001-2-1 0=LOW 34SSL 001 /27.
SPEED ACTUAL VALUE /38.2
ST SPEED (GOVERNOR) ST SPEED CONTROL MIN GOVERNOR SPEED
7 1=OK
DT DREHZAHLREGLUNG MIN REGELDREHZAHL
/32.4
/27.14 7
FIELD DT DREHZAHLREGELUNG PLC
/23. 34SE 001-2-2 1=LL 34SSLL 001 /27.
SPEED ACTUAL VALUE /16.8
ST SPEED (GOVERNOR) ST SPEED CONTROL SPEED LL
8 DT DREHZAHLREGLUNG DREHZAHL LL
8
FIELD DT DREHZAHLREGELUNG PLC
38.5
FIC CONTROL DEVIATION TO SIC xd from FIC
9 9
34GA 034 /26.
/25.11
ST LIVE STEAM CONTROL VALVE POS. FAIL
10 MODBUS
DT FRISCHDAMPFREGELVENTIL STELLUNGSFEHLER
10
t=2s
/1.K16 34HS 312-2 1
/27.
ST SPEED CONTROL AUTO
11 /3.J5
S
1=AUTO / 0=MAN
11
LCP DT DREHZAHLREGLUNG AUTO t=2s 1 0
/1.K15 34HS 312-3 1 1 1
ST SPEED = 85%
/27.
ST SPEED CONTROL MAN
R
12 /3.J5
1 = 85% 12
LCP DT DREHZAHLREGLUNG MAN 0 <> 85%
EXTERNAL SETPOINT ON/OFF
/1.K10
/1.K13
34HS 309 0=OFF &
SIC MAN. OPERATION FROM DCS ON/OFF
13 /33. 1=ON 13
DCS SIC MANUELBETRIEB VON DCS EIN/AUS
/3.L4 34HS 311-4 0=LOCAL
/2.K2
AX COMPR FLOW CONTROL LOCAL/REMOTE
14 /12.
/38.8
1=REM. 14
LCP AX KOMPR. DURCHFLUSSREGELUNG LOKAL/FERN
xd FROM FIC ENABLE/DISABLE
/3.K6
/2.K4
34YBH 309-1 &
AX COMPR FLOW CONTROL RUNNING
15 /12.
/38.2
1=ON 15
AX KOMPR. DURCHFLUSSREGELUNG LÄUFT
34GC 034 /26.
CONTROLLER OUTPUT
ST LIVE STEAM CONTROL VALVE SETPOINT
16 DT FRISCHDAMPFREGELVENTIL SOLLWERT
16
FIELD
/26. 34GT 034
VALVE ACTUAL VALUE
ST LIVE STEAM CONTROL VALVE ACTUAL VALUE
17 17
FIELD DT FRISCHDAMPFREGELVENTIL ISTWERT

18 18
39.14
FIC MANUAL MODE FIC MANUAL
19 1 = MANUAL 19
NOTE 3
- if MAIN AIR BLOWER FLOW CONTROL is in MANUAL MODE
20 Steam Turbine Speed Setpoint is fixed 20
at 85% nominal speed (82,8rev/s)

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 36
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPEED CONTROL
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs TURBOLOG DSP BASIC-4 Outputs Dest. Line

1 RELEASE (1=RELEASE)
1
ACCEL
2 AUTO ACCEL.
2

3 MAN +
3
0

NOTE 4
4 MAN -
1 CONTROL 4
DEVIATION

5 EXTERNAL SPEED SETPOINT


5

S
6 6

NOTE1
0
7 SPEED ACTUAL VALUE REL 7

MAX
1

8 SPEED ACTUAL VALUE


MAX 8
S
9 9
xd MIN

NOTE 3
GOV. SPEED MIN
xd from FIC

NOTE2
10 10
xd MAX
GOV. SPEED

11 1=AUTO / 0=MAN PIC CONTROLLER OUTPUT


11

EXTERNAL SETPOINT ON/OFF


12 1=ON / 0=OFF 12

xd FROM FIC ENABLE/DISABLE


13 1=ON / 0=OFF 13

FIC MANUAL TURBINE SPEED CONTROLER (TSC)


14 1=MANUAL 14

15 15
NOTE 1 NOTE 5
16 IF S = 1 -> EXTERNAL SETPOINT IS ACTIVE IF BOTH SPEED PROBES FAIL 16
IF S = 0 -> SETPOINT FROM ACCEL SPEED CONTROLLER WILL BE DISABLED
AND OUTPUT WILL BE SET TO ZERO
17 NOTE 2 17
IF S = 1 -> xd FROM FIC IS ACTIVE
IF S = 0 -> CONTROL DEVIATION IS ACTIVE
18 18
NOTE 3
IF RELEASE = 0 -> CONTROLLER OUTPOUT IS FORCED TO 0
19 19
NOTE 4
IF FIC MANUAL = 1 -> SPEED SETPOINT IS FIXED AT 85%
20 EXTERNAL SPEED SETPOINT AND xd from FIC ARE DISABLED THAN 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 37
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 SPEED CONTROL
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs TURBOLOG DSP BASIC-4 Outputs Dest. Line

1 1
/32.4 34SSL 001 0=LOW 34YBH 309-1
/27.14
ST SPEED CONTROL MIN GOVERNOR SPEED AX COMPR FLOW CONTROL RUNNING
2 1=OK 1=ON
AX KOMPR. DURCHFLUSSREGELUNG LÄUFT
2
DT DREHZAHLREGLUNG MIN REGELDREHZAHL LCP

34YBH 309-2
AX COMPR FLOW CONTROL AUTO ACTIVE
3 Release 1=AUTO
AX KOMPR. DURCHFLUSSREGELUNG AUTO ACTIVE
3
LCP
& S
1 0 34YBH 309-3
AX COMPR FLOW CONTROL MAN ACTIVE
4 R
1 1
MAIN AIR BLOWER 1=MAN
AX KOMPR. DURCHFLUSSREGELUNG MAN ACTIVE
4
LCP

34HS 311-1 FLOW CONTROL 36.9


1 FIC CONTROL DEVIATION TO SIC
AX COMPR FLOW CONTROL ON
5 1=ON 5
LCP AX KOMPR. DURCHFLUSSREGELUNG EIN
>
=1
6 6
34HS 311-5 0=OFF 1
AX COMPR FLOW CONTROL OFF
7 7
LCP AX KOMPR. DURCHFLUSSREGELUNG AUS

34HS 311-4 0=LOCAL


AUTO/ 34FI 003
8 AX COMPR FLOW CONTROL LOCAL/REMOTE 1=REM. >
=1 MODBUS
AIR FLOW FLOW ACTUAL VALUE
8
LCP AX KOMPR. DURCHFLUSSREGELUNG LOKAL/FERN NOTE MAN DURCHFLUSS DURCHFLUSS ISTWERT PLC
1=MAN
IF FLOW CONTROL IS IN REMOTE MODE
9 SETPOINT TRACKING WILL BE ACTIVE 9
-> SETPOINT = ACTUAL VALUE
-> CONTROL DEVIATION xd = 0
10 10
0=HIGH 34FSAH 003
AIR FLOW FLOW HIGH
11 MODBUS
DURCHFLUSS DURCHFLUSS HOCH
11
PLC

34HS 056-1 34UI 003


12 AIR FLOW FLOW INCREASE
& + MODBUS
AIR FLOW FLOW-SETPOINT
12
LCP DURCHFLUSS DURCHFLUSS ERHOEHEN DURCHFLUSS DURCHFLUSS-SOLLWERT PLC

34HS 056-2
13 AIR FLOW FLOW DECREASE
& - 13
LCP DURCHFLUSS DURCHFLUSS VERRINGERN
39.14
FIC MANUAL MODE
14 1=MANUAL 14

15 15
34FT 003
AX COMPR PROCESS LINE DISCHARGE
16 16
FIELD AX KOMPR. AUSTRITT PROZESSLEITUNG
34PT 004
AX COMPR PROCESS LINE DISCHARGE
17 17
FIELD AX KOMPR. AUSTRITT PROZESSLEITUNG
34TT 002
AX COMPR PROCESS LINE DISCHARGE
18 18
FIELD AX KOMPR. AUSTRITT PROZESSLEITUNG

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 28.01.06 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 38
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 FLOW CONTROL
39 Bl.
Zeile Ursprung Eingaenge Ausgaenge Ziel Zeile

Line Source Inputs TURBOLOG DSP BASIC-4 Outputs Dest. Line

1 1

2 MANUAL 2
INLET
3 GUIDE VANE 3
/3.L4
/2.K1
34HS 056-1 CONTROLLER
4 /32.
/38.12
AIR FLOW FLOW INCREASE
& 4
LCP DURCHFLUSS DURCHFLUSS ERHOEHEN

5 5

6 6
/3.L3 34HS 056-2
/2.K1
7 /32.
/38.13 LCP
AIR FLOW FLOW DECREASE
& 7
DURCHFLUSS DURCHFLUSS VERRINGERN
34GC 037 /10.
AX COMPR INLET GUIDE VANES SETPOINT
8 AX KOMPR. VORLEITSCHAUFEL SOLLWERT
8
FIELD

9 9

10 10
/3.L5 34HS 311-3 1 RELEASE
/2.K2
AX COMPR FLOW CONTROL MAN
11 /12. S
1 0
11
LCP AX KOMPR. DURCHFLUSSREGELUNG MAN & 1 1
ST SPEED = 85% R 1=ON 34UZ 037 /2.G5
/10.
AX COMPR INLET GUIDE VANES ON / OFF
12 1 = 85% 0=OFF
AX KOMPR. VORLEITSCHAUFEL EIN / AUS
12
0 <> 85% FIELD

13 13
/3.L5 34HS 311-2 1 >
=1 FIC MANUAL MODE 36.19
/2.K3
AX COMPR FLOW CONTROL AUTO
14 /12.
LCP 1=MANUAL 38.14
14
AX KOMPR. DURCHFLUSSREGELUNG AUTO
/10. 34GSH 038-2 &
AX COMPR INLET GUIDE VANES OPEN
15 1=OPEN 15
AX KOMPR. VORLEITSCHAUFEL OFFEN

16 16
/10. 34GT 037
AX COMPR INLET GUIDE VANES ACTUAL VALUE
17 17
FIELD AX KOMPR. VORLEITSCHAUFEL ISTWERT

18 18

19 19

20 20

21
21
4 FINAL 28.08.2006 Ges/Ges Date 01.04.2006 Field of application Title CONTROL LOGIC DIAGRAM Drawing No. of Recipient Dept.
3 FINAL 23.06.2006 Ges/Ges Drawn GESING TK5
ESSARAX Title CUSTOMER
2 Revision 06.05.2006 Ges/Ges Checked GES Sheet 39
R. Nature of Revision Date Drawn/Checked Norm 814775 Drawing No. 10000253530 IGV-CONTROL