10.11.17 Utpal
Checked by Project CE-08 Line-7
Priyadarishi
Azadpur Station - AZU
ASS-1 Approved by Dinesh Sharma Document no DMRC-CE08/L1-DTD-ASS-DOC-00064
ACDB RTU 3C 2.5 F 02 ACDB RTU 3CX2.5 Cu. 1 2T13 X5-1 230V AC Supply to RTU
ASS1 ASS1 2 2T14 X5-2
3
ACDB MVCB-11 3C 2.5 F 03 ACDB AZP ASS1 MVCB-11 3CX2.5 Cu. 1 2T19 X4-1 230V AC Supply to 33kV GIS
ASS1 ASS1 2 2T20 X4-3
3
ACDB BC-1 3.5C 25 F 04 ACDB Battery Charger-1 3.5CX25 Cu. 1 2T1 X-1 415 V Supply to Battery Charger Mod-1
ASS1 ASS1 2 2T2 X-2
3 2T3 X-3
3.5 2T4 X-7
ACDB BC-2 3.5C 25 F 05 ACDB Battery Charger-2 3.5CX25 Cu. 1 2T5 X-1 415 V Supply to Battery Charger Mod-2
ASS1 ASS1 2 2T6 X-2
3 2T7 X-3
3.5 2T8 X-7
DCDB TR1 3C 2.5 F 06 DCDB Aux Trafo TR1 3CX2.5 Cu. 1 2T25 WTI-N0 WTI aux. supply to the transformer
ASS1 ASS1 2 2T26 WTI-T0
3
ACDB RTU 3C 2.5 F 07 ACDB RTU 3CX2.5 Cu. 1 T1-1 DIX4-4 Lack of voltage in ACDB (Signal to SCADA)
ASS1 ASS1 2 T1-2 DIX4-19
3
BC DCDB 2C 25 F 08 Battery Charger DCDB 2CX25 Cu. 1 X-9 IT1 Incomer to DCDB from Battery Charger
ASS1 ASS1 2 X-8 IT2
Battery BC 2C 25 F 09 Battery Battery Charger 2CX25 Cu. 1 +ve X-11 Incomer to Battery Charger from Battery
ASS1 ASS1 2 -ve X-10
DCDB RTU 3C 2.5 F 10 DCDB RTU 3CX2.5 Cu. 1 2T5 X1-1 DC Supply feeder-1 To RTU (for RTU)
ASS1 ASS1 2 2T6 X1-2
3
DCDB RTU 3C 2.5 F 11 DCDB RTU 3CX2.5 Cu. 1 2T7 X2-1 DC Supply feeder-2 To RTU (for RTU)
ASS1 ASS1 2 2T8 X2-2
3
DCDB MVCB-11 3C 4 F 12 1 2T3 X3-5 DC Supply feeder To GIS MVCB-12 Motor Circuit
DCDB AZP ASS1 MVCB-11 3CX4 Cu.
ASS1 ASS1 2 2T4 X3-7
3
DCDB MVCB-11 3C 4 F 13 1 2T1 X3-1 DC Supply feeder To GIS MVCB-12 Control Circuit
DCDB AZP ASS1 MVCB-11 3CX4 Cu.
ASS1 ASS1 2 2T2 X3-3
3
MVCB-11 RTU 19C 1.5 F 17 AZP ASS1 MVCB-11 RTU 19CX1.5 Cu. 1 1XS-8 DIX2-13 L/R Mode in local
MVCB-1 TR1 6C 2.5 F 21 AZP ASS1 MVCB-1 Aux Trafo TR1 6CX2.5 Cu. 1 XT-4 LIMIT SWITCH Common
Trafo feeder ASS1 2 XT-5 LIMIT SWITCH Transformer Encl. Door Open
3 XT-3 WTI-24 Winding temp high alarm
4 XT-2 WTI-26 Winding temp high trip
5 XT-1 WTI-21 Common
6 Spare
MVCB-1 MDB 3C 2.5 F 22 AZP ASS1 MVCB-1 LV MDB 3CX2.5 Cu. 1 XC-5 ACB 1 LVCB open Status
Trafo feeder ASS1 2 XC-6 ACB 2 LVCB open Status
3 spare
MVCB-1 MDB 3C 2.5 F 23 AZP ASS1 MVCB-1 LV MDB 3CX2.5 Cu. 1 X5-5 EPB 1 LV inter trip
Trafo feeder ASS1 2 X5-6 EPB 2
3
MVCB-1 MDB 4C 6 F 24 AZP ASS1 MVCB-1 LV MDB 4CX6 Cu. 1 XT1-411 IC7A LV CT I/P
Trafo feeder ASS1 2 XT1-421 IC8A LV CT I/P
3 XT1-431 IC9A LV CT I/P
4 XT1-432 IC10 LV CT I/P
MVCB-1 MDB 2C 6 F 25 AZP ASS1 MVCB-1 Aux Trafo TR1 2CX6 Cu. 1 XT1-511 IC7 Neutral CT at LV panel end
Trafo feeder LV REF 2 XT1-512 IC8
BC-2 RTU 12C 1.5 F 28 Battery Charger-2 RTU 12CX1.5 Cu. 1 TS1-CN4-3 DIX5-3 Charger Healthy
ASS1 ASS1 2 TS2-X45 DIX4-16 Float
3 TS2-X46 DIX4-17 BOOST
4 TS1-CN8-1 DIX5-2 AC fail
5 TS1-CN4-1 DIX5-4 Charger Fail
6 TS1-CN3-1 DIX5-7 DC under voltage
7 TS1-CN2-1 DIX5-8 DC over voltage
8 TS1-CN6-1 DIX5-5 Input MCB trip
9 TS1-CN8-1 DIX5-6 Output MCB trip
10 TS2-X44 DIX5-1 COMMON
11
12
MKP AZP XX X G 29 MKP-AIS AZP-MVCB-12 FO 1 Tx Rx Cable Differential Fiber Optic Cable
MKP ASS AZP ASS1 2 Rx Tx
MVCB-11 RTU 3C 1.5 30 MVCB-12 RTU 3CX1.5 Cu. 1 X9-2 COMX1-2 Positive Looping of Rs 485
Ring Feeder-11 ASS1 2 X9-4 COMX1-1 Negative MODBUS
3 X9-6 COMX1-3 Ground Communication Port