Ref. No. : IDN-1709-CCR-142.

1
Rev. No. : 0
Page No. : 1 of 3

Bid No. :
Customer :
Bid Title :-
Bidder : LS-VINA Cable & System
Document Title :

Calculation of Continuous Current Ratings


for
150kV 1Cx630sqmm XLPE Power Cable

(IEC 60287-1-1, Edition 2.0 2014-11)

(Single point bonding in Air )

0 11-Apr-18 For Information B.D.Tan V.H.Duong T.M.Trung


Rev. No. Date Descriptions Prepared By Reviewed By Approved By
Ref. No. : IDN-1709-CCR-142.1
Rev. No. :0
Page No. : 2 of 3

Calculation of Continuous Current Ratings


(Single point bonding in trench, in Air)

1. Conditions of Calculation
1) Cable : 150kV 1Cx630sqmm XLPE Cable
2) Method of Laying : Trefoil formation
3) Air ambient temperature : 40 [ºC]
4) Maximum operating temperature : 90 [ºC]
5) Trench temperature rises above air ambient temperature : 10 [ºC]
6) Conductor temperature rise above trench temperature : 40 [ºC] (Δθ)
7) Axial Spacing of Cable axis : 100 [mm]
8) Earthing System : Single point bonding

2. The Results of Calculation


1) AC Resistance of Conductor at Maximum Operating Temperature, R
R0 DC Resistance at 20ºC 4.690E-05 [Ω/m]
R' DC Resistance at 90ºC 6.013E-05 [Ω/m]
R AC Resistance at Operating Temperature 6.178E-05 [Ω/m]
2) Dielectric Loss, Wd
tanδ Loss Factor of the Insulation 0.001
ε Relative Permittivity 2.5
C Capacitance 2.010E-10 [F/m]
Wd Dielectric Loss 0.478 [W/m]
3) Loss Factor of Sheath or Screen, λ1
RS Sheath Resistance at Maximum Operating Temperature 6.379E-05 [Ω/m]
λ1 Loss Factor of Sheath or Screen 0.111
4) Thermal Resistance between Conductor and Sheath, T1 0.547 [K.m/W]
5) Thermal Resistance of Outer Covering (Serving), T3 0.081 [K.m/W]
6) External Thermal Resistance, T4 One circuit 0.507 [K.m/W]

3. Permissible Continuous Current Rating, I


 Δθ  Wd 0.5T 1  n(T 3  T4 ) 
I
 0 .5

 730.7 [A]
 RT1  nR(1  λ 1 )(T 3  T4 ) 
Ref. No. : IDN-1709-CCR-142.1
Rev. No. :0
Page No. : 3 of 3

Calculation of Continuous Current Ratings


(Single point bonding in trench, in Air)

1. Conditions of Calculation
1) Cable : 150kV 1Cx630sqmm XLPE Cable
2) Method of Laying : Flat formation
3) Air ambient temperature : 40 [ºC]
4) Maximum operating temperature : 90 [ºC]
5) Trench temperature rises above air ambient temperature : 11.5 [ºC]
6) Conductor temperature rise above trench temperature : 38.5 [ºC] (Δθ)
7) Axial Spacing of Cable axis : 180 [mm]
8) Earthing System : Single point bonding

2. The Results of Calculation


1) AC Resistance of Conductor at Maximum Operating Temperature, R
R0 DC Resistance at 20ºC 4.690E-05 [Ω/m]
R' DC Resistance at 90ºC 6.013E-05 [Ω/m]
R AC Resistance at Operating Temperature 6.155E-05 [Ω/m]
2) Dielectric Loss, Wd
tanδ Loss Factor of the Insulation 0.001
ε Relative Permittivity 2.5
C Capacitance 2.010E-10 [F/m]
Wd Dielectric Loss 0.478 [W/m]
3) Loss Factor of Sheath or Screen, λ1
RS Sheath Resistance at Maximum Operating Temperature 6.349E-05 [Ω/m]
λ1 Loss Factor of Sheath or Screen 0.065
4) Thermal Resistance between Conductor and Sheath, T1 0.547 [K.m/W]
5) Thermal Resistance of Outer Covering (Serving), T3 0.081 [K.m/W]
6) External Thermal Resistance, T4 One circuit 0.316 [K.m/W]

3. Permissible Continuous Current Rating, I


 Δθ  Wd 0.5T 1  n(T 3  T4 ) 
I
 0 .5

 799.8 [A]
 RT1  nR(1  λ 1 )(T 3  T4 ) 