Vous êtes sur la page 1sur 128

CHILLER REPLACEMENT

CONTRACTORS GUIDE
YCAL – 15 to 65 TONS YLAA – 70 to 175 TONS
AIR COOLED SCROLL CHILLER AIR COOLED SCROLL CHILLER

YVAA – 150 to 500 TONS YCWL – 50 to 200 TONS


AIR COOLED SCREW CHILLER WATER COOLED SCROLL CHILLER
AIR-COOLED

YCAL
15 TO 40
Pages 12-23

YCAL
41 TO 65
Pages 24-29

CHILLER REPLACEMENT
YLAA
70 TO 90

CONTRACTORS GUIDE
Pages 36-43

YLAA
91 TO 130
Pages 44-53
YCAL – 15 to 65 TONS YLAA – 70 to 175 TONS
AIR COOLED SCROLL CHILLER AIR COOLED SCROLL CHILLER

YLAA
131 TO 175
Pages 54-63

YVAA
150 TO 200
Pages 68-73

YVAA
201 TO 500
Pages 74-85

YVAA – 150 to 500 TONS YCWL – 50 to 200 TONS


AIR COOLED SCREW CHILLER WATER COOLED SCROLL CHILLER WATER COOLED

YCWL
50 TO 90
Pages 92-109

YCWL
91 TO 130
Pages 110-117

YCWL
131 TO 200
Pages 118-125
In-stock Chillers Ready for Quick Shipment
When You Need Cooling Fast!
Complete packages for quick ‘Plug & Play’ installation
Unit Benefits
Air-cooled Scroll Chillers Air-cooled Screw Chillers

Air-cooled chillers using scroll-compressor technology rang- Air-cooled chillers using YORK® VSD Screw technology rang-
ing from 15 to 175 tons. Standard feature include: ing from 150 to 500 tons. Standard features include:
• Voltages: 200V, 230V, 380V, 460V, 380-415V/50Hz, 575V • Voltages: 200V, 230V, 380V, 400V, 460V, 380-415V/50Hz,
• Chilled-water supply range: 40 - 55°F; brine supply to 10°F 575V
• Ambient operation between 0 - 115°F • Chilled-water supply range: 40 - 55°F; brine supply to 15°F
• Single-point power connection reduces wiring costs • Ambient operation between 0 - 125°F
• Non-fused disconnect switch simplifies installation and • Single-point power connection reduces wiring costs
servicing • Non-fused disconnect switch simplifies installation and
• Control transformer eliminates separate control wiring servicing
• Micro-computer control panel is very user-friendly • Control transformer eliminates separate control wiring
• Low-noise fans reduce radiated sound • VSD increases reliability at start-up and shut-down
• Victaulic-grooved water connections reduce installation • Micro-computer control panel is very user-friendly
costs • Low-noise fans reduce radiated sound
• Complies with ASHRAE Standard 90.1 on energy efficiency • Victaulic-grooved water connections reduce installation
• Options are available upon request costs
• Complies with ASHRAE Standard 90.1 on energy efficiency
• Options are available upon request

2 JOHNSON CONTROLS
Water-cooled Scroll Chillers Need temporary cooling?

If you need cooling while we are customizing your unit,


Water-cooled chillers using scroll-compressor technology Johnson Controls can provide a rental unit. We make
ranging from 50 to 200 tons. Standard features include: available a wide range of products including chillers,
• Voltages: 200V, 230V, 380V, 460V, 380-415V/50Hz, 575V rooftop units, air handlers, towers and peripheral
equipment. Our service includes delivery, installation,
• Chilled-water supply range: 40 - 55°F; brine supply to 15°F
start-up, maintenance, and financing. If interested in
• Single-point power connection reduces wiring costs this option please contact the JCI Rental Department at:
• Non-fused disconnect switch simplifies installation and
servicing
1-800-JCI-RNTL (1800-524-7685)
• Control transformer eliminates separate control wiring
• Micro-computer control panel is very user-friendly
www.johnsoncontrols.com/rental
• Complies with ASHRAE Standard 90.1 on energy
efficiency
• Non-reversing heat pump function (leaving condenser
temperature control)
• Options are available upon request

Need more than the standard unit? Need Replacement Parts?

If you need a chiller quickly but need some customization Your brand HVAC parts source for air cooled, water cooled,
of features, Johnson Controls can make it happen. and absorption chillers. We are able to ship out the HVAC
Customization features include: parts that you need as soon as possible. If you need items
•  Suction-pressure readouts urgently (for a hospital, school or other critical application) we
can prioritize this requirement and work with our supplier for
•  Service-Isolation valves
expediting. If you have a need for replacement parts please
•  Hot gas by-pass contact the JCI Parts Department at :
•  Brine cooling as low as 10°F
•  Functional witness testing 1-800-932-1701
•  Hydronics package
•  Epoxy Coated Cond. Coils
•  Options are available upon request

jOHNSON CONTROLS 3
Ways to Reduce Your Risk, Expand Your Business and
Increase Your Profits

  OPTION I
Use Variable Speed Technology to Create Chiller Replacement Opportunities

Compressor motor control via a variable frequency drive allows you as the installing contractor to give your
customer more tonnage without changing the electrical power supply. Also, emergency generator size can be
reduced when feeding chillers with variable speed compressors.

For Example: Your customer has an existing chiller that produces 165 tons at ARI conditions. The MCA for this
chiller is 374 amps and the existing wire and breaker size was installed to meet this MCA. Your customer is short
on capacity during peak hours of the day. YORK has an YVAA0248CEV that produces 225 tons with an MCA of
374. This will give you an extra 61 tons without changing out the wires or breakers.

On the other hand, if your customer doesn’t have a need for additional capacity, and the installation requires electri-
cal power component upgrades, the first cost savings when using smaller breakers, wire and conduit is substantial.

$310 Average Wire Savings Potential For a Smaller Circuit


Breaker Frame Size

$2,100

$3,500

  OPTION II
Use Energy Performance to Differentiate Your Replacement Offering

The YORK Latitude variable speed air-cooled chiller allows you as the installing contractor to offer your customers
a replacement alternative that is as much as 25% more efficient than existing chillers.

For Example: Your customer wants to replace an existing 350-ton chiller. You as the installing contractor can
offer either a standard efficiency chiller or the YORK optimized variable speed chiller. The optimized offering will
save the customer over $17,000/year*. With this level of annual savings, you can offer your customer a $21,250
additive alternate with a 1.25 year simple payback. The price premium for the optimized offering is $7,000, which
allows you to capture $14,250 of additional gross profit.

*see the next page for the Average Energy Cost (AEC) calculation

4 JOHNSON CONTROLS
Annual Savings / Average Energy Cost (AEC) Calculation

Input Variables:

IPLV = Integrated Part Load Value (kW/TON) = (12) / (IPLV EER)


FLT = Full Load Tons (tons)
ACL = Average Chiller Load (tons) = (FLT) x (0.58)
RATE = Commercial Energy Cost ($/kWh)
OH – Average Chiller Operating Hours (hrs)

Output Functions:

AEC = (IPLV) x (ACL) x (RATE) x (OH)


Annual Savings = AEC Existing or Base Bid – AEC New

Example
Input Variables:

IPLV Existing or Base Bid = 15.4 EER


IPLV New = 19.0 EER
FLT Existing or Base Bid = 350 tons
FLT New = 350 tons
RATE = $0.1016/kWh
OH = 5000 hrs

Calculations:

AEC Existing or Base Bid = (IPLV) x (ACL) x (RATE) x (OH)


AEC Existing or Base Bid = (12 / (IPLV EER)) x ((FLT) x (0.58)) x (RATE) x (OH)
AEC Existing or Base Bid = (12 / 15.4 EER) x (350 tons x 0.58) x ($0.1016/kWh) x (5000 hrs)
AEC Existing or Base Bid = $80,356.36

AEC New = (IPLV) x (ACL) x (RATE) x (OH)


AEC New = (12 / (IPLV EER)) x ((FLT) x (0.58)) x (RATE) x (OH)
AEC New = (12 / 19.0 EER) x (350 tons x 0.58) x ($0.1016/kWh) x (5000 hrs)
AEC New = $65,130.95

Annual Savings = AEC Existing or Base Bid – AEC New


Annual Savings = $80,356.36 - $65,130.95
Annual Savings = $15,225.41 / year

jOHNSON CONTROLS 5
6 JOHNSON CONTROLS
YCAL
15 to 65 Tons
Air Cooled Scroll Chiller

jOHNSON CONTROLS 7
8 JOHNSON CONTROLS
YCAL Rigging
WARNING ­— To ensure warranty coverage, this equipment must be commissioned and serviced
by an authorized Johnson Controls Service Mechanic or a qualified service person experienced in
chiller installation. Installation must comply with all applicable codes, particularly in regard to elec-
trical wiring and other safety elements such as relief valves, HP cutout settings, design working
pressures, and ventilation requirements consistent with the amount and type of refrigerant charge.
Lethal voltages exist within the control panels. Before servicing, open and tag all disconnect
switches.

Installation Check List


The following items must be checked before placing the units in operation.
  1. Inspect the unit for shipping damage.
  2.  Rig Unit using spreader bars.
  3. Open the unit only to install water piping system. Do not remove protective covers from water connections
until piping is ready for attachment. Check water piping to ensure cleanliness.
  4.  Pipe unit using good piping practice (see ASHRAE handbook section 215 and 195).
  5. Check to see that the unit is installed and operated within limitations (Refer to Operational and Voltage
Limitations located in Section 1 of the YCAL Operations and Maintenance Guide [Form 150.62-NM8]).
The following pages outline detailed procedures to be followed to install and startup the chiller.

Handling
These units are shipped as completely assembled units containing full operating charge, and care should be taken to
avoid damage due to rough handling.

WARNING —The unit should be lifted by inserting hooks through the holes provided in the unit
base rails. Spreader bars should be used to avoid crushing the unit frame rails with lifting chains.

Inspection EXAMPLE OF PROPER LIFTING


Immediately upon receiving the unit, it should be inspected for pos-
sible damage which may have occurred during transit. If damage is
evident, it should be noted in the carrier’s freight bill. A written request
for inspection by the carrier’s agent should be made at once. See
Instruction manual, Form 50.15-NM for more information and details.

Location and Clearances


These units are designed for outdoor installations on ground level,
rooftop, or beside a building. Location should be selected for mini-
mum sun exposure and to insure adequate supply of fresh air for the
condenser. The units must be installed with sufficient clearances for
air entrance to the condenser coil, for air discharge away from the
condenser, and for servicing access.
In installations where winter operation is intended and show accumu-
lations are expected, additional height must be provided to ensure
normal condenser air flow.
Clearances are listed under Dimensions in Section 1 of the YCAL
Operations and Maintenance Guide form 150.62-NM8.

jOHNSON CONTROLS 9
AIR COOLED SCROLL CHILLER
YCAL Style E - 15 to 65 TONS (R-410A)
BENEFITS
• Maintenance free, hermetic scroll compressor utilizes fewer moving parts to minimize breakdown
• Components and circuitry designed for lower minimum circuit ampacities (MCA) to allow use of smaller
wire for reduced power wiring costs
• Electronic, digital-based controls ensure reliable, solid-state monitoring and control
• Units ship with full ref. charge and undergo factory pressure and operational testing to minimize field setup
time
• Two refrigerant circuits on units over 35 tons allows redundant operation
• Industry’s only 18-month air cooled warranty that covers all parts
• Wide range of options to fit any design requirement. (Acoustical treatments, Hydrokit packages etc)

UPGRADE OPTIONS
• Remote Cooler
• Power Options --> 200, 230, 380, 460, 575 (Not available on all models, refer to Engineering Guide):
• Single Point Terminal Block, Non-fused Disconnect Switch, Circuit Breaker, Control Transformer
• Control Options:
• Low Ambient Kit extends operating range to 0 deg. F from +25 deg. F
• Discharge Pressure Transducers and Readout Capability (standard) allows unit to sense and display
discharge pressure
• Low Temperature Brine for chilling below 30 deg. F
• Motor Current Module allows monitoring of compressor motor current, provides extra protection against
compressor reverse rotation, phase-loss and phase imbalance
• Hot Gas Bypass for continuous, stable operation at capacities as low as 5% capacity
• Service Isolation Valve - suction and discharge (ball type) isolation valves are added to unit per system;
includes a system high pressure relief valve in compliance with ASHRAE 15
• Pre-coated, Post-coated Epoxy Dipped or Copper Fin condenser coils
• Unit Enclosure Options:
• Wire Panels (full unit-standard): coated, heavy gauge welded wire mesh mounted on exterior of unit to
prevent unauthorized access
• Louvered Panels (full unit): to protect condenser coils, visually screen internal components and prevent
unauthorized access
• Sound Attenuation:
• Compressor Acoustic Sound Blanket
• Ultra Quiet fans
• Vibration Isolators - 1" spring, 2" spring or neoprene pad isolators for mounting under unit base rails

10 JOHNSON CONTROLS
AIR COOLED SCROLL CHILLER
YCAL Style E - 15 to 65 TONS
PACKAGE DESCRIPTION: Cooler:
• Shipped complete from the factory ready for field • Equipped with a heater controlled by separate
installation and use thermostat for freeze protection to –20 deg. F
• Fully charged with HFC-410A and initial oil charge • Covered by closed cell foam insulation
• Baked on powder paint • Inlet and outlet are grooved for compatibility with
• Heavy gauge, formed galvanized steel base field supplied victaulic connections
• Operational and Pressure Tested
Controls:
Compressors:
• All controls housed in a NEMA 3R/12 cabinet with
• Suction-gas cooled, hermetic scroll compressors gasket sealed, hinged & latched door
• Large internal volume and oil reservoir provides • LCD, 40-character display with backlight
greater liquid tolerance • Color coded, sealed keypad
• Crankcase heaters for extra protection against • Standard controls permit operation from 25 to
liquid migration 125 deg F.

Condenser:
• Low noise, direct drive, maximum efficiency fans
with corrosion resistant aluminum hub and com-
posite blades; statically and dynamically balanced
• Totally enclosed air over (TEAO) type fan motors,
current protected and permanently sealed
• Seamless, internally enhanced copper fin & tube
coils arranged in staggered rows; mechanically
expanded to full-height aluminum fins
• Design Working Pressure 650 PSIG
• Integral subcooling included

jOHNSON CONTROLS 11
Air Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCAL0019EE46 15.4 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.0 / 2.9
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 14.6 / 4.3
Design Flow Rate (gpm) 37.0 Min. Ambient Temp. (°F) 25.0 Physical Data
Pressure Drop (ft.) 6.3 Max. Ambient Temp. (°F) 115.0 Rigging Wt. (lbs.) 1454
Fluid Water Operating Wt. (lbs.) 1481
Fouling Factor 0.00010
Water Volume (gal) 3.3

Electrical Data
Circuit 1 2 3 4
Compressor RLA 18.6/18.6
Compressor Start Current (LRA) 114.0/114.0
Fan QTY/FLA (each) 2/1.3

Single Point
Min. Circuit Ampacity 44.9
Min. Non-Fused Disconnect (Amps) 60
Min. Dual Element Fuse Size (Amps) 50
Max. Dual Element Fuse Size (Amps) 60
Min. Circuit Breaker (Amps) 50
Max. Circuit Breaker (Amps) 60
Wire Lugs Per Phase* 1
Wire Range (Lug Size) (1)#14 - #2/0
Total Amps 39.8 Operating Condition Electrical Data
Inrush (PW) Amps 114.0 Compressor kW 17.6
Starter Type Across the Line Total Fan kW 1.0
Total kW 18.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Notes: Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 15.4 17.6 10.0 / 2.9
50.0 70.2 9.1 6.3 16.0 / 4.7

12 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING 5/8" DIA MOUNTING HOLES(TYP)
1 1/16" 402 365
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE PANEL COMPR
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE 44 3/8"
END CAP END END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
WIDTH
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL 32 1/8"

jOHNSON CONTROLS
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
6 1/8"
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,454, OPERATING - 1,481.
374 340 1 1/16"
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.6", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS ORIGIN 2 1/4"
Y TOP VIEW 5"
IN CHILLED WATER PIPING NEAR THE EVAPORATOR. 17"
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
C
G X

3 1/4"
6 3/4"
7/8" TYP.
R-410A CHILLER

3 15/16" VIEW B-B


BOTTOM OF PANEL 1"
9 1/16"
CONTROL
PANEL

2" VICTAULIC CONN (TYP)


46 1/16" LIQUID IN
B B 38 3/16"
45 1/4" (2) 3.0 X 1.50
RIGGING HOLES 3 3/8"
BOTH ENDS 2 1/4"
2 1/4" 13 3/4"
11 5/8"

(2) 7.0 X 2.25


11"
TO ACCESS PANEL 16 1/4" FORKLIFT HOLES
BOTH SIDES (2) 3.0 X 1.50
15 5/8" RIGGING HOLES
8 5/16" 8 5/16" 44 1/2" BOTH SIDES
2" VICTAULIC CONN (TYP) 18 3/4"
74 1/2"
LIQUID OUT 44 5/16" 97 1/8"
BASE WIDTH
109 3/16"
LEFT END FRONT VIEW

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.64-EG1
MODEL: YCAL0019EE46 Contractor : UNIT Dwg. Lev. : 03/05
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 15.4 TONS
MODEL: YCAL0019EE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

13
YCAL
15 TO 40
Air Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCAL0022EE46 18.7 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.0 / 2.9
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 15.5 / 4.5
Design Flow Rate (gpm) 44.8 Min. Ambient Temp. (°F) 25.0 Physical Data
Pressure Drop (ft.) 4.9 Max. Ambient Temp. (°F) 115.0 Rigging Wt. (lbs.) 1567
Fluid Water Operating Wt. (lbs.) 1597
Fouling Factor 0.00010
Water Volume. (gal) 3.6

Electrical Data
Circuit 1 2 3 4
Compressor RLA 20.0/20.0
Compressor Start Current (LRA) 125.0/125.0
Fan QTY/FLA (each) 2/1.3

Single Point
Min. Circuit Ampacity 48.1
Min. Non-Fused Disconnect (Amps) 60
Min. Dual Element Fuse Size (Amps) 60
Max. Dual Element Fuse Size (Amps) 60
Min. Circuit Breaker (Amps) 60
Max. Circuit Breaker (Amps) 60
Wire Lugs Per Phase* 1
Wire Range (Lug Size) (1)#14 - #2/0
Total Amps 42.6 Operating Condition Electrical Data
Inrush (PW) Amps 125.0 Compressor kW 21.5
Starter Type Across the Line Total Fan kW 1.0
48.1 Total kW 22.5

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Notes: Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 18.7 21.5 10.0 / 2.9
50.0 72.1 11.5 7.2 16.9 / 5.0

14 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING 5/8" DIA MOUNTING HOLES(TYP)
1 1/16" 434 394
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE PANEL COMPR
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE 44 3/8"
END CAP END END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
WIDTH
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL 32 1/8"

jOHNSON CONTROLS
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
6 1/8"
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,567, OPERATING - 1,597.
403 366 1 1/16"
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.5", Y= 22.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS ORIGIN 2 1/4"
Y TOP VIEW 5"
IN CHILLED WATER PIPING NEAR THE EVAPORATOR. 17"
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
C
G X

3 1/4"
6 3/4"
7/8" TYP.
R-410A CHILLER

3 15/16" VIEW B-B


BOTTOM OF PANEL 1"
9 1/16"
CONTROL
PANEL

2" VICTAULIC CONN (TYP)


46 1/16" LIQUID IN
B B 38 3/16"
45 1/4" (2) 3.0 X 1.50
RIGGING HOLES 3 3/8"
BOTH ENDS 2 1/4"
2 1/4" 13 3/4"
11 5/8"

(2) 7.0 X 2.25


11"
TO ACCESS PANEL 16 1/4" FORKLIFT HOLES
BOTH SIDES (2) 3.0 X 1.50
15 5/8" RIGGING HOLES
8 5/16" 8 5/16" 44 1/2" BOTH SIDES
2" VICTAULIC CONN (TYP) 18 3/4"
74 1/2"
LIQUID OUT 44 5/16" 97 1/8"
BASE WIDTH
109 3/16"
LEFT END FRONT VIEW

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.64-EG1
MODEL: YCAL0022EE46 Contractor : UNIT Dwg. Lev. : 03/05
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 18.7 TONS
MODEL: YCAL0022EE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

15
YCAL
15 TO 40
Air Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCAL0028EE46 25.6 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.1 / 3.0
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 13.4 / 3.9
Design Flow Rate (gpm) 61.3 Min. Ambient Temp. (°F) 25.0 Physical Data
Pressure Drop (ft.) 8.9 Max. Ambient Temp. (°F) 115.0 Rigging Wt. (lbs.) 1798
Fluid Water Operating Wt. (lbs.) 1835
Fouling Factor 0.00010
Water Volume. (gal) 2.5

Electrical Data
Circuit 1 2 3 4
Compressor RLA 23.1/26.9
Compressor Start Current (LRA) 150.0/187.0
Fan QTY/FLA (each) 2/4.0

Single Point
Min. Circuit Ampacity 64.7
Min. Non-Fused Disconnect (Amps) 100
Min. Dual Element Fuse Size (Amps) 80
Max. Dual Element Fuse Size (Amps) 90
Min. Circuit Breaker (Amps) 80
Max. Circuit Breaker (Amps) 90
Wire Lugs Per Phase* 1
Wire Range (Lug Size) (1)#14 - #2/0
Total Amps 58.0 Operating Condition Electrical Data
Inrush (PW) Amps 187.0 Compressor kW 27.5
Starter Type Across the Line Total Fan kW 3.0
Total kW 30.5

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Notes: Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 25.6 27.5 10.1 / 3.0
50.8 71.9 15.7 11.7 14.3 / 4.2

16 JOHNSON CONTROLS
NOTES:
5/8" DIA MOUNTING HOLES(TYP)
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING 1 1/16" 456
495
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE COMPR
44 3/8" PANEL
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE END END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT; END CAP
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL WIDTH
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES: 32 1/8"

jOHNSON CONTROLS
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6'; 6 1/8"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 1,798, OPERATING - 1,835.
3. CENTER OF GRAVITY FROM ORIGIN: X= 63.1", Y= 22.9" . 1 1/16"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS 460 423
IN CHILLED WATER PIPING NEAR THE EVAPORATOR. ORIGIN 1 7/8"
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET Y 5"
17"
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM TOP VIEW
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.

C
G X

3 1/4"
6 3/4" R-410A CHILLER
7/8" TYP.

VIEW B-B 1"


3 15/16"
BOTTOM OF PANEL 9"
CONTROL
PANEL

2" VICTAULIC CONN (TYP)


LIQUID IN
50 1/16" B B
(2) 3.0 X 1.50
49 1/4" 42 1/8"
RIGGING HOLES
BOTH ENDS
3 3/8"
17 3/4" 2 1/4"
2 1/4" 15 1/2"
8 1/2"

(2) 7.0 X 2.25


TO ACCESS PANEL 13 3/8" 10 3/4"
FORKLIFT HOLES
15 5/8" BOTH SIDES (2) 3.0 X 1.50
8 5/16" 8 5/16" RIGGING HOLES
19" 50 1/2" BOTH SIDES
2" VICTAULIC CONN (TYP)
LIQUID OUT 80 1/2"
44 5/16"
BASE WIDTH 105 1/16"
118 5/16"

LEFT END FRONT VIEW

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.64-EG1
MODEL: YCAL0028EE46 Contractor : UNIT Dwg. Lev. : 03/05 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 25.6 TONS
MODEL: YCAL0028EE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

17
YCAL
15 TO 40
Air Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCAL0033EE46 28.6 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.5 / 3.1
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 14.5 / 4.2
Design Flow Rate (gpm) 68.4 Min. Ambient Temp. (°F) 25.0 Physical Data
Pressure Drop (ft.) 11.0 Max. Ambient Temp. (°F) 115.0 Rigging Wt. (lbs.) 2034
Fluid Water Operating Wt. (lbs.) 2077
Fouling Factor 0.00010
Water Volume. (gal) 5.2

Electrical Data
Circuit 1 2 3 4
Compressor RLA 26.9/26.9
Compressor Start Current (LRA) 187.0/187.0
Fan QTY/FLA (each) 2/4.0

Single Point
Min. Circuit Ampacity 66.7
Min. Non-Fused Disconnect (Amps) 100
Min. Dual Element Fuse Size (Amps) 80
Max. Dual Element Fuse Size (Amps) 90
Min. Circuit Breaker (Amps) 80
Max. Circuit Breaker (Amps) 90
Wire Lugs Per Phase* 1
Wire Range (Lug Size) (1)#14 - #2/0
Total Amps 61.8 Operating Condition Electrical Data
Inrush (PW) Amps 187.0 Compressor kW 29.6
Starter Type Across the Line Total Fan kW 3.0
Total kW 32.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Notes: Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 28.6 29.6 10.5 / 3.1
50.0 70.0 16.6 11.2 15.7 / 4.6

18 JOHNSON CONTROLS
NOTES:
5/8" DIA MOUNTING HOLES(TYP)
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING 1 1/16" 565
520
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
CONTROL
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE COMPR
44 3/8" PANEL
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE END END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT; END CAP
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL WIDTH
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES: 32 1/8"

jOHNSON CONTROLS
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6'; 6 1/8"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,034, OPERATING - 2,077.
3. CENTER OF GRAVITY FROM ORIGIN: X= 67.1", Y= 23.1" . 1 1/16"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS 475 516
IN CHILLED WATER PIPING NEAR THE EVAPORATOR. ORIGIN 1 7/8"
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET Y 5"
17"
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM TOP VIEW
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.

C
G X

3 1/4"
6 3/4" R-410A CHILLER
7/8" TYP.

VIEW B-B 1"


3 15/16"
BOTTOM OF PANEL 9"
CONTROL
PANEL

2" VICTAULIC CONN (TYP)


LIQUID IN
50 1/16" B B
(2) 3.0 X 1.50
49 1/4" 42 1/8"
RIGGING HOLES
BOTH ENDS
3 3/8"
17 3/4" 2 1/4"
2 1/4" 15 1/2"
8 1/2"

(2) 7.0 X 2.25


TO ACCESS PANEL 13 3/8" 10 3/4"
FORKLIFT HOLES
15 5/8" BOTH SIDES (2) 3.0 X 1.50
8 5/16" 8 5/16" RIGGING HOLES
19" 50 1/2" BOTH SIDES
2" VICTAULIC CONN (TYP)
LIQUID OUT 80 1/2"
44 5/16"
BASE WIDTH 105 1/16"
118 5/16"

LEFT END FRONT VIEW

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.64-EG1
MODEL: YCAL0033EE46 Contractor : UNIT Dwg. Lev. : 03/05
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 28.6 TONS
MODEL: YCAL0033EE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

19
YCAL
15 TO 40
Air Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCAL0043EE46 37.2 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.1 / 3.0
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 14.5 / 4.2
Design Flow Rate (gpm) 89.2 Min. Ambient Temp. (°F) 25.0 Physical Data
Pressure Drop (ft.) 6.1 Max. Ambient Temp. (°F) 115.0 Rigging Wt. (lbs.) 2942
Fluid Water Operating Wt. (lbs.) 2967
Fouling Factor 0.00010
Water Volume. (gal) 2.7

Electrical Data
Circuit 1 2 3 4
Compressor RLA 20.0/20.0 20.0/20.0
Compressor Start Current (LRA) 125.0/125.0 125.0/125.0
Fan QTY/FLA (each) 2/3.4 2/3.4

Single Point
Min. Circuit Ampacity 99.2
Min. Non-Fused Disconnect (Amps) 150
Min. Dual Element Fuse Size (Amps) 110
Max. Dual Element Fuse Size (Amps) 110
Min. Circuit Breaker (Amps) 110
Max. Circuit Breaker (Amps) 110
Wire Lugs Per Phase* 1
Wire Range (Lug Size) (1)#14 - #2/0
Total Amps 93.7 Operating Condition Electrical Data
Inrush (PW) Amps 125.0 Compressor kW 38.8
Starter Type Across the Line Total Fan kW 5.6
Total kW 44.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Notes: Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 37.2 38.8 10.1 / 3.0
75.0 83.3 30.0 24.4 12.0 / 3.5
50.0 69.0 21.1 14.2 14.9 / 4.4
25.0 55.0 11.5 6.6 17.3 / 5.1

20 JOHNSON CONTROLS
5/8" DIA MOUNTING HOLES(TYP)
NOTES: 1 1/16" 862 569
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE. COOLER COIL
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED END END

jOHNSON CONTROLS
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL 90 9/16"
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES: END CAP
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6'; WIDTH
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT. 45 1/8"
2. WEIGHTS (LB):SHIPPING - 2,942, OPERATING - 2,967.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.6", Y= 43.6" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET 925 611 1 1/16"
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR. ORIGIN 9 13/16" 9 13/16"
18 1/2" TOP VIEW

Y
6 3/4"
3 1/4" 7/8" TYP.
C X
G
3 15/16"
VIEW B-B
BOTTOM OF PANEL 5 5/16"
38"
LIQUID IN CONTROLPANEL

ELECTRICAL ACCESS
PANEL
47 3/4" 25 3/8" B B
46 15/16"
9 7/8" 25 3/16"
15 3/4" 13 5/8"

LIQUID OUT TWO LIFTING HOLES


3" VICTAULIC (TYP) 12 5/8" BOTH SIDES 13 15/16"
15 1/16"
45 1/8" 144 13/16"
90 1/4" BASE WIDTH
LEFT END FRONT VIEW

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.62-EG1
MODEL: YCAL0043EE46 Contractor : UNIT Dwg. Lev. : 01/02 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 37.2 TONS
MODEL: YCAL0043EE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

21
YCAL
15 TO 40
Air Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCAL0046EE46 39.4 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.2 / 3.0
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 14.7 / 4.3
Design Flow Rate (gpm) 94.5 Min. Ambient Temp. (°F) 25.0 Physical Data
Pressure Drop (ft.) 5.1 Max. Ambient Temp. (°F) 115.0 Rigging Wt. (lbs.) 2968
Fluid Water Operating Wt. (lbs.) 3000
Fouling Factor 0.00010
Water Volume. (gal) 3.5

Electrical Data
Circuit 1 2 3 4
Compressor RLA 20.7/20.7 20.0/20.0
Compressor Start Current (LRA) 125.0/125.0 125.0/125.0
Fan QTY/FLA (each) 2/3.4 2/3.4

Single Point
Min. Circuit Ampacity 100.8
Min. Non-Fused Disconnect (Amps) 150
Min. Dual Element Fuse Size (Amps) 110
Max. Dual Element Fuse Size (Amps) 110
Min. Circuit Breaker (Amps) 110
Max. Circuit Breaker (Amps) 110
Wire Lugs Per Phase* 1
Wire Range (Lug Size) (1)#14 - #2/0
Total Amps 95.1 Operating Condition Electrical Data
Inrush (PW) Amps 125.0 Compressor kW 41.0
Starter Type Across the Line Total Fan kW 5.6
Total kW 46.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Notes: Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 39.4 41.0 10.2 / 3.0
73.2 82.9 31.5 25.2 12.3 / 3.6
50.0 69.1 22.4 14.9 15.2 / 4.5
23.2 55.0 11.6 6.5 17.5 / 5.1

22 JOHNSON CONTROLS
5/8" DIA MOUNTING HOLES(TYP)
NOTES: 1 1/16" 875 570
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE. COOLER COIL
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED END END
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE

jOHNSON CONTROLS
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL 90 9/16"
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES: END CAP
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6'; WIDTH
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 2,968, OPERATING - 3,000. 45 1/8"
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.2", Y= 43.5" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM 941 613 1 1/16"
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR. 9 13/16"
ORIGIN 9 13/16"
16 11/16" TOP VIEW

Y
6 3/4"
3 1/4" 7/8" TYP.
C X
G

3 15/16"
VIEW B-B
5 5/16"
BOTTOM OF PANEL
38"
LIQUID IN CONTROLPANEL

ELECTRICAL ACCESS
PANEL
47 3/4" 25 3/8" B B
46 15/16"
9 7/8"
15 3/4" 25 3/16" 13 5/8"

LIQUID OUT TWO LIFTING HOLES


3" VICTAULIC (TYP) 12 5/8" BOTH SIDES 13 15/16"
15 1/16"
45 1/8"
144 13/16"
90 1/4" BASE WIDTH
LEFT END FRONT VIEW

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.62-EG1
MODEL: YCAL0046EE46 Contractor : UNIT Dwg. Lev. : 01/02 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 39.4 TONS
MODEL: YCAL0046EE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

23
YCAL
15 TO 40
Air Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCAL0052EE46 46.2 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.2 / 3.0
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 15.1 / 4.4
Design Flow Rate (gpm) 110.8 Min. Ambient Temp. (°F) 25.0 Physical Data
Pressure Drop (ft.) 9.2 Max. Ambient Temp. (°F) 115.0 Rigging Wt. (lbs.) 3170
Fluid Water Operating Wt. (lbs.) 3208
Fouling Factor 0.00010
Water Volume. (gal) 3.5

Electrical Data
Circuit 1 2 3 4
Compressor RLA 23.1/23.1 23.1/23.1
Compressor Start Current (LRA) 150.0/150.0 150.0/150.0
Fan QTY/FLA (each) 2/4.0 2/4.0

Single Point
Min. Circuit Ampacity 114.2
Min. Non-Fused Disconnect (Amps) 150
Min. Dual Element Fuse Size (Amps) 125
Max. Dual Element Fuse Size (Amps) 125
Min. Circuit Breaker (Amps) 125
Max. Circuit Breaker (Amps) 125
Wire Lugs Per Phase* 1
Wire Range (Lug Size) (1)#14 - #2/0
Total Amps 108.4 Operating Condition Electrical Data
Inrush (PW) Amps 150.0 Compressor kW 47.9
Starter Type Across the Line Total Fan kW 6.7
Total kW 54.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Notes: Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 46.2 47.9 10.2 / 3.0
75.0 83.4 37.3 30.7 12.0 / 3.5
50.0 69.5 26.6 17.6 15.2 / 4.5
25.0 55.0 15.1 7.8 19.1 / 5.6

24 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING 5/8" DIA MOUNTING HOLES(TYP)
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED 1 1/16" 873 623
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE COIL
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE END
END

jOHNSON CONTROLS
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6'; 90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'. END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT. WIDTH
2. WEIGHTS (LB):SHIPPING - 3,170, OPERATING - 3,208.
3. CENTER OF GRAVITY FROM ORIGIN: X= 61.9", Y= 42.2" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS 45 1/8"
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
999 713 1 1/16"

ORIGIN
9 13/16" 9 13/16"
18 1/2" TOP VIEW
6 3/4"
3 1/4" Y
7/8" TYP.

C X
3 15/16" VIEW B-B G
5 5/16"
BOTTOM OF PANEL 38"

CONTROL
LIQUID IN PANEL
25 3/8" B B
62 5/8"
ELECTRICAL ACCESS
61 7/8" PANEL

9 13/16" 25 3/16" 13 5/8"


15 3/4"

LIQUID OUT TWO LIFTING HOLES


3" VICTAULIC (TYP) 12 5/8" BOTH SIDES
13 15/16"
15 1/16"
45 1/8"
144 13/16"
90 1/4" BASE WIDTH
LEFT END FRONT VIEW

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK


Project Name : Contractors Guide Sold To : Date :
PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.62-EG1
MODEL: YCAL0052EE46 Contractor : UNIT Dwg. Lev. : 01/02 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 46.2 TONS
MODEL: YCAL0052EE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

25
YCAL
41 TO 65
Air Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCAL0056EE46 56.2 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.1 / 3.0
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 14.7 / 4.3
Design Flow Rate (gpm) 134.7 Min. Ambient Temp. (°F) 25.0 Physical Data
Pressure Drop (ft.) 9.9 Max. Ambient Temp. (°F) 115.0 Rigging Wt. (lbs.) 3206
Fluid Water Operating Wt. (lbs.) 3244
Fouling Factor 0.00010
Water Volume. (gal) 4.1

Electrical Data
Circuit 1 2 3 4
Compressor RLA 26.9/26.9 26.9/26.9
Compressor Start Current (LRA) 187.0/187.0 187.0/187.0
Fan QTY/FLA (each) 2/4.0 2/4.0

Single Point
Min. Circuit Ampacity 130.3
Min. Non-Fused Disconnect (Amps) 150
Min. Dual Element Fuse Size (Amps) 150
Max. Dual Element Fuse Size (Amps) 150
Min. Circuit Breaker (Amps) 150
Max. Circuit Breaker (Amps) 150
Wire Lugs Per Phase* 1
Wire Range (Lug Size) (1)#14 - #2/0
Total Amps 123.6 Operating Condition Electrical Data
Inrush (PW) Amps 187.0 Compressor kW 60.3
Starter Type Across the Line Total Fan kW 6.7
Total kW 67.0

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Notes: Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 56.2 60.3 10.1 / 3.0
75.0 83.6 45.5 38.8 12.0 / 3.5
50.0 69.4 32.2 22.6 14.9 / 4.4
25.0 55.0 18.0 10.2 18.1 / 5.3

26 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING 5/8" DIA MOUNTING HOLES(TYP)
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED 1 1/16" 889 625
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE COIL
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE END
END

jOHNSON CONTROLS
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6'; 90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'. END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT. WIDTH
2. WEIGHTS (LB):SHIPPING - 3,206, OPERATING - 3,244.
3. CENTER OF GRAVITY FROM ORIGIN: X= 61.5", Y= 42.2" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS 45 1/8"
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1,015 715 1 1/16"

ORIGIN
9 13/16" 9 13/16"
16 11/16" TOP VIEW
6 3/4"
3 1/4" Y
7/8" TYP.

C X
3 15/16" VIEW B-B G
5 3/16"
BOTTOM OF PANEL 38"

CONTROL
LIQUID IN PANEL
25 3/8" B B
62 5/8"
ELECTRICAL ACCESS
61 7/8" PANEL

9 7/8" 25 3/16" 28 9/16"


15 3/4"

LIQUID OUT TWO LIFTING HOLES


3" VICTAULIC (TYP) 12 5/8" BOTH SIDES
14"
15 1/16"
45 1/8"
144 13/16"
90 1/4" BASE WIDTH
LEFT END FRONT VIEW

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK


Project Name : Contractors Guide Sold To : Date :
PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.62-EG1
MODEL: YCAL0056EE46 Contractor : UNIT Dwg. Lev. : 01/02 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 56.2 TONS
MODEL: YCAL0056EE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

27
YCAL
41 TO 65
Air Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCAL0066EE46 66.1 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.1 / 3.0
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 15.1 / 4.4
Design Flow Rate (gpm) 158.4 Min. Ambient Temp. (°F) 25.0 Physical Data
Pressure Drop (ft.) 8.3 Max. Ambient Temp. (°F) 115.0 Rigging Wt. (lbs.) 4097
Fluid Water Operating Wt. (lbs.) 4142
Fouling Factor 0.00010
Water Volume. (gal) 4.9

Electrical Data
Circuit 1 2 3 4
Compressor RLA 33.9/33.9 26.9/26.9
Compressor Start Current (LRA) 250.0/250.0 187.0/187.0
Fan QTY/FLA (each) 2/4.0 2/1.3

Single Point
Min. Circuit Ampacity 146.0
Min. Non-Fused Disconnect (Amps) 200
Min. Dual Element Fuse Size (Amps) 175
Max. Dual Element Fuse Size (Amps) 175
Min. Circuit Breaker (Amps) 175
Max. Circuit Breaker (Amps) 175
Wire Lugs Per Phase* 1
Wire Range (Lug Size) (1)#6 - 350
Total Amps 137.6 Operating Condition Electrical Data
Inrush (PW) Amps 250.0 Compressor kW 72.1
Starter Type Across the Line Total Fan kW 6.7
Total kW 78.8

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


* Use Copper Conductors only
Notes: Installing contractor must include vent and drain accommodations in the chilled water piping near the evaporator.
A strainer, preferably 40 mesh, must be installed in the cooler inlet just ahead of the cooler. This is important to
protect the cooler from the entrance of large particles which could cause damage to the evaporator.

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 66.1 72.1 10.1 / 3.0
71.5 82.6 52.5 42.2 12.9 / 3.8
50.0 69.3 37.8 26.6 15.2 / 4.5
21.5 55.0 18.5 10.3 18.5 / 5.4

28 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING 5/8" DIA MOUNTING HOLES(TYP)
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED 1 1/16" 1,292 768
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE COIL
COOLER
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE END END
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL

jOHNSON CONTROLS
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
COIL SIDE - 6' COMPRESSOR SIDE - 4'; CONTROL SIDE - 6'; 90 9/16"
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'. END CAP
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT. WIDTH
2. WEIGHTS (LB):SHIPPING - 4,097, OPERATING - 4,142.
3. CENTER OF GRAVITY FROM ORIGIN: X= 59.7", Y= 44.9" .
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS 43 1/8"
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.
5. A STRAINER, PREFERABLY 40 MESH, MUST BE INSTALLED IN THE COOLER INLET
JUST AHEAD OF THE COOLER. THIS IS IMPORTANT TO PROTECT THE COOLER FROM
THE ENTRANCE OF LARGE PARTICLES WHICH COULD CAUSE DAMAGE TO THE EVAPORATOR.
1,306 776 1 1/16"

ORIGIN
9 13/16" 9 13/16"
12 13/16" TOP VIEW
6 3/4"
3 1/4" Y
7/8" TYP.

C X
3 15/16" VIEW B-B G
5 3/16"
BOTTOM OF PANEL 38"

CONTROL
LIQUID IN PANEL
25 3/8" B B
62 5/8"
ELECTRICAL ACCESS
61 7/8" PANEL

9 3/4" 28 9/16"
25 1/16"
15 3/4"

LIQUID OUT TWO LIFTING HOLES


3" VICTAULIC (TYP) BOTH SIDES
12 5/8" 16"
15 1/16"
43 1/8"
153 5/8"
90 1/4" BASE WIDTH
LEFT END FRONT VIEW

POWER: SINGLE POINT SUPPLY WITH TERMINAL BLOCK

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 150.62-EG1
MODEL: YCAL0066EE46 Contractor : UNIT Dwg. Lev. : 01/02 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 66.1 TONS
MODEL: YCAL0066EE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

29
YCAL
41 TO 65
30 JOHNSON CONTROLS
YLAA
70 to 175 Tons
Air Cooled Scroll Chiller

jOHNSON CONTROLS 31
32 JOHNSON CONTROLS
YLAA RIGGING

Typical Lifting Arrangement - 8 Fan Models

Use spreader bars to avoid lifting chains hitting


the chiller.

CAUTION — Never lift the chiller using


a forklift or by hooking to the top rails.
Use only the lifting holes provided.

Lifting instructions are placed on a label on the


chiller and on the shipping bag.

Typical Lifting Arrangement - 4 Fan Models

jOHNSON CONTROLS 33
AIR COOLED SCROLL CHILLER
YLAA - 70 to 175 TONS
BENEFITS
• Optimized design for R-410A refrigerant (No EPA Phase out date)
• Available in 2-tiers of efficiency:
• Standard Efficiency: 9.6 – 10.0 EER
• High Efficiency: 10.1 an above EER
• Best Part Load Efficiency with an IPLV as high as 15.9.
• The YLAA always qualifies for LEED credit through Enhanced Refrigerant Management.
• This chiller utilizes 30-50% less refrigerant than conventional scroll chiller design.
• Standard ambient operation from 30 to 115-deg F
• Maintenance free, hermetic scroll compressor utilizes fewer moving parts to minimize breakdown
• Components and circuitry designed for lower minimum circuit ampacities (MCA) to allow use of smaller
wire for reduced power wiring costs
• Electronic, digital-based controls ensure reliable, solid-state monitoring and control
• Units ship evacuated with initial oil charge and undergo factory pressure and operational testing to
minimize field setup time
• Two refrigerant circuits allows redundant operation.
• Industry’s only 18-month air cooled warranty that covers all parts
• Wide range of options to fit any design requirement. (Acoustical treatments, Hydrokit packages etc)

UPGRADE OPTIONS
• Remote Cooler
• Power Options --> 200, 230, 380, 460, 575 (Not available on all models, refer to Engineering Guide):
• Single Point Terminal Block, Terminal Block with Individual Circuit Breakers, Circuit Breaker, Non-fused
Disconnect Switch or Non-fused Disconnect Switch with Individual System Circuit Breakers
• Control Options: Low Ambient Kit extends operating range to 0 deg. F from +30 deg. F
• Discharge Pressure Transducers and Readout Capability allows unit to sense and display discharge
pressure
• Low Temperature Brine for chilling below 30 deg. F (which includes Electronic Expansion Valve)
• Motor Current Module allows monitoring of compressor motor current, provides extra protection against
compressor reverse rotation, phase-loss and phase imbalance
• Hot Gas Bypass for continuous, stable operation at capacities as low as 5% capacity
• Service Isolation Valve - suction and discharge (ball type) isolation valves are added to unit per system;
includes a system high pressure relief valve in compliance with ASHRAE 15
• Post-coated Epoxy Dipped
• Unit Enclosure Options:
• Wire Panels (full unit): coated, heavy gauge welded wire mesh mounted on exterior of unit to prevent
unauthorized access
• Louvered Panels (condenser coils only): louvered panels mounted over exterior condenser coil faces to
protect coils
• Louvered Panels (full unit): to protect condenser coils, visually screen internal components and prevent
unauthorized access
• Louvered (condensers)/Wire Panels (mechanicals): Louvered steel panels on external condenser coil
faces, heavy-gauge welded-wire mesh around base
• Sound Attenuation:
• Compressor Acoustic Sound Blanket
• Ultra Quiet fans
• Vibration Isolators - 1" spring, 2" spring or neoprene pad isolators for mounting under unit base rails

34 JOHNSON CONTROLS
AIR COOLED SCROLL CHILLER
YLAA - 70 to 175 TONS
PACKAGE DESCRIPTION: Evaporator:
• Shipped complete from the factory ready for field • Equipped with a heater controlled by separate
installation and use thermostat for freeze protection to –20 deg. F
• Fully charged with HFC-410A and initial oil charge • Covered by closed cell foam insulation
• Baked on powder paint • Inlet and outlet are grooved for compatibility with
• Heavy gauge, formed galvanized steel base field supplied victaulic connections
• Operational and Pressure Tested
Refrigerant Circuit:
Compressors:
• Independent circuits per compressor
• Suction-gas cooled, hermetic scroll compressors • Each refrigerant circuit includes: liquid line shutoff
• Large internal volume and oil reservoir provides valve with charging port, low side pressure relief
greater liquid tolerance device, filter-drier, solenoid valve, sight glass with
• Crankcase heaters for extra protection against moisture indicator, thermostatic expansion valves,
liquid migration and flexible, closed-cell foam insulated suction
line and suction pressure transducer.
Condenser:
Controls:
• Low noise, direct drive, maximum efficiency fans
with corrosion resistant aluminum hub and com- • All controls housed in a NEMA 3R/12 cabinet
posite blades; statically and dynamically balanced with gasket sealed, hinged & latched door
• The fan motors are Totally Enclosed Air-Over, • LCD, 40-character display with backlight
current protected. They feature ball bearings that • Color coded, sealed keypad
are double-sealed and permanently lubricated. • Standard controls permit operation from 30 to
• Condenser coils are made of a single material to 115 deg F.
avoid galvanic corrosion due to dissimilar metals.
Coils and headers are brazed as one piece.
• Design Working Pressure 650 PSIG
• Integral subcooling included

jOHNSON CONTROLS 35
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0070SE
Number of Compressors 6
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Cooling Capacity TR 71.8
Total Power Input kW 84.8
EER EER 10.2
IPLV EER 16
NPLV EER 16
Sound Pressure (Hemispherical Method) dB(A) 87
Sound Pressure Measured at ft 3.3

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 5.4
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 38.7 / 38.7
Total Flow Rate USGPM 171.2
Total Pressure Drop ft H2O 11.4
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 3"

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 122.5 / 122.5
Number of Fans 4
Altitude ft 0
Total Air Flow cfm 59329
Total Fan Power kW 6.7

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 160
Max. Fuse / CB Rating A 175
Min. Fuse / CB Rating A 175
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 3578
Operating Weight lb 3623
Refrigerant Charge lb 101
Overall Length in 116.1
Overall Width in 88.3
Overall Height in 94.2
36 JOHNSON CONTROLS
5/8" DIA
MOUNTING
HOLES (TYP)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
774 732
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:

jOHNSON CONTROLS
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 3,578, OPERATING - 3,622. POWER ENTRY
3. CENTER OF GRAVITY FROM ORIGIN: X= 56.8", Y= 51.3" . 13" WIDE X 7" HIGH
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

81 13/16"
13/16" 46 3/8"

3 1/4"
1 1/16"
CONTROL PANEL
BOTTOM DETAIL
1,087 1,030
19 5/8"
76 5/8"
ORIGIN

C X
G

3" INLET

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT
42 11/16"
32 3/8"

23 3/16" 23 3/16"
10"

88 5/16" - FRAME WIDTH 5 5/8" 46 1/2" 3" OUTLET


88 13/16" - OVERALL WIDTH 114 11/16" - FRAME LENGTH
121 11/16" - OVERALL LENGTH

Project Name :
YLAA Sold To : Date : 12/18/2012 11:37:46
PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0070SE46 Contractor : UNIT Dwg. Lev. : A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 71.8 TONS
MODEL: YLAA-B0070SE

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS


UNIT0

37
YLAA
70 TO 90
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0080SE
Number of Compressors 6
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Cooling Capacity TR 77.7
Total Power Input kW 94.4
EER EER 9.9
IPLV EER 15.4
NPLV EER 15.4
Sound Pressure (Hemispherical Method) dB(A) 88
Sound Pressure Measured at ft 3.3

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 6.7
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 38.7 / 39
Total Flow Rate USGPM 185.4
Total Pressure Drop ft H2O 9
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 3"

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 126.1 / 122.9
Number of Fans 4
Altitude ft 0
Total Air Flow cfm 59329
Total Fan Power kW 6.7

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 173
Max. Fuse / CB Rating A 200
Min. Fuse / CB Rating A 200
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 3898
Operating Weight lb 3954
Refrigerant Charge lb 106
Overall Length in 116.1
Overall Width in 88.3
Overall Height in 94.2
38 JOHNSON CONTROLS
5/8" DIA
MOUNTING
HOLES (TYP)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
822 750
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:

jOHNSON CONTROLS
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 3,898, OPERATING - 3,953. POWER ENTRY
3. CENTER OF GRAVITY FROM ORIGIN: X= 56.1", Y= 52.9" . 13" WIDE X 7" HIGH
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

81 13/16"
13/16" 46 3/8"

3 1/4"
1 1/4"
CONTROL PANEL
BOTTOM DETAIL
1,246 1,135
19 5/8"
76 5/8"
ORIGIN

C X
G

3" INLET

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT
42 11/16"
32 3/8"

23 3/16" 23 3/16"
10"

88 5/16" - FRAME WIDTH 5 5/8" 46 1/2" 3" OUTLET


88 13/16" - OVERALL WIDTH 114 11/16" - FRAME LENGTH
121 11/16" - OVERALL LENGTH

Project Name :
YLAA Sold To : Date : 12/18/2012 11:39:31
PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0080SE46 Contractor : UNIT Dwg. Lev. :
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 77.7 TONS
MODEL: YLAA-B0080SE

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS


UNIT0

39
YLAA
70 TO 90
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0090SE
Number of Compressors 5
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Cooling Capacity TR 83.9
Total Power Input kW 103.4
EER EER 9.7
IPLV EER 15.5
NPLV EER 15.5
Sound Pressure (Hemispherical Method) dB(A) 88
Sound Pressure Measured at ft 3.3

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 8.8
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 39.4 / 39.4
Total Flow Rate USGPM 199.7
Total Pressure Drop ft H2O 7
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 3"

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 126.1 / 127.2
Number of Fans 4
Altitude ft 0
Total Air Flow cfm 59329
Total Fan Power kW 6.7

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 192
Max. Fuse / CB Rating A 225
Min. Fuse / CB Rating A 225
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 4169
Operating Weight lb 4241
Refrigerant Charge lb 115
Overall Length in 116.1
Overall Width in 88.3
Overall Height in 94.2
40 JOHNSON CONTROLS
5/8" DIA
MOUNTING
HOLES (TYP)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
816 831
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';

jOHNSON CONTROLS
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,169, OPERATING - 4,242. POWER ENTRY
3. CENTER OF GRAVITY FROM ORIGIN: X= 58.1", Y= 53.7" . 13" WIDE X 7" HIGH
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

81 13/16"
13/16" 46 3/8"

3 1/4"
1 1/16"
CONTROL PANEL
BOTTOM DETAIL
1,285 1,310
19 5/8"
76 5/8"
ORIGIN

C X
G

3" OUTLET
3" INLET 3" INLET

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT
42 11/16"
32 3/8"

23 3/16" 23 3/16"
10"

88 5/16" - FRAME WIDTH 5 5/8" 46 1/2" 3" OUTLET


88 13/16" - OVERALL WIDTH 114 11/16" - FRAME LENGTH
121 11/16" - OVERALL LENGTH

Project Name :
YLAA Sold To : Date : 12/18/2012 11:52:29
PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0090SE46 Contractor : UNIT Dwg. Lev. : A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 83.9 TONS
MODEL: YLAA-B0090SE

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS


UNIT0

41
YLAA
70 TO 90
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0091HE
Number of Compressors 4
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Cooling Capacity TR 88.2
Total Power Input kW 98.3
EER EER 10.8
IPLV EER 15
NPLV EER 14.9
Sound Pressure (Hemispherical Method) dB(A) 88
Sound Pressure Measured at ft 3.3

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 8.8
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 39.2 / 39.2
Total Flow Rate USGPM 210.8
Total Pressure Drop ft H2O 7.7
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 3"

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 117.7 / 117.7
Number of Fans 6
Altitude ft 0
Total Air Flow cfm 88993
Total Fan Power kW 10.1

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 200
Max. Fuse / CB Rating A 250
Min. Fuse / CB Rating A 225
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 4718
Operating Weight lb 4791
Refrigerant Charge lb 115
Overall Length in 142.7
Overall Width in 88.3
Overall Height in 94.2
42 JOHNSON CONTROLS
5/8" DIA
MOUNTING
HOLES (TYP)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
571 840 534
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:

jOHNSON CONTROLS
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,718, OPERATING - 4,791. POWER ENTRY
3. CENTER OF GRAVITY FROM ORIGIN: X= 67.8", Y= 52.1" . 13" WIDE X 7" HIGH
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

81 13/16"
13/16" 46 3/8"

3 1/4"
1 1/16"
CONTROL PANEL
BOTTOM DETAIL
884 1,290 672
7 11/16"
69 3/4" 47 3/8"
ORIGIN

C X
G

3" INLET

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT
42 11/16"
32 3/8"

23 1/8" 23 5/16"
10"

88 5/16" - FRAME WIDTH 5 5/8" 46 1/2" 3" OUTLET


88 13/16" - OVERALL WIDTH 142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH

Project Name :
YLAA Sold To : Date : 12/18/2012 11:54:27
PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0091HE46 Contractor : UNIT Dwg. Lev. :
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 88.2 TONS
MODEL: YLAA-B0091HE

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS


UNIT1

43
YLAA
91 TO 130
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0100SE
Number of Compressors 5
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Cooling Capacity TR 95.8
Total Power Input kW 119.1
EER EER 9.7
IPLV EER 14.3
NPLV EER 14.3
Sound Pressure (Hemispherical Method) dB(A) 88
Sound Pressure Measured at ft 3.3

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 8.8
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 39.6 / 38.5
Total Flow Rate USGPM 228.2
Total Pressure Drop ft H2O 9
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 3"

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 122.7 / 123.6
Number of Fans 5
Altitude ft 0
Total Air Flow cfm 74161
Total Fan Power kW 8.4

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 223
Max. Fuse / CB Rating A 250
Min. Fuse / CB Rating A 250
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 4791
Operating Weight lb 4864
Refrigerant Charge lb 112
Overall Length in 142.7
Overall Width in 88.3
Overall Height in 94.2
44 JOHNSON CONTROLS
5/8" DIA
MOUNTING
HOLES (TYP)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
542 836 520
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:

jOHNSON CONTROLS
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,791, OPERATING - 4,863. POWER ENTRY
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.6", Y= 53.5" . 13" WIDE X 7" HIGH
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

81 13/16"
13/16" 46 3/8"

3 1/4"
1 1/16"
CONTROL PANEL
BOTTOM DETAIL
800 1,459 703
7 11/16"
69 3/4" 47 3/8"
ORIGIN

C X
G

3" INLET

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT
42 11/16"
32 3/8"

23 1/8" 23 5/16"
10"

88 5/16" - FRAME WIDTH 5 5/8" 46 1/2" 3" OUTLET


88 13/16" - OVERALL WIDTH 142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH

Project Name :
YLAA Sold To : Date : 12/18/2012 12:55:43
PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0100SE46 Contractor : UNIT Dwg. Lev. :
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 95.8 TONS
MODEL: YLAA-B0100SE

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS


UNIT1

45
YLAA
91 TO 130
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0101HE
Number of Compressors 5
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Cooling Capacity TR 98.5
Total Power Input kW 116.1
EER EER 10.2
IPLV EER 15.4
NPLV EER 15.4
Sound Pressure (Hemispherical Method) dB(A) 89
Sound Pressure Measured at ft 3.3

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 8.8
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 39.6 / 38.1
Total Flow Rate USGPM 234.6
Total Pressure Drop ft H2O 9.4
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 3"

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 125.2 / 117.7
Number of Fans 6
Altitude ft 0
Total Air Flow cfm 88993
Total Fan Power kW 10.1

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 227
Max. Fuse / CB Rating A 250
Min. Fuse / CB Rating A 250
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 4954
Operating Weight lb 5026
Refrigerant Charge lb 126
Overall Length in 142.7
Overall Width in 88.3
Overall Height in 94.2
46 JOHNSON CONTROLS
5/8" DIA
MOUNTING
HOLES (TYP)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
560 875 545
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:

jOHNSON CONTROLS
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 4,954, OPERATING - 5,027. POWER ENTRY
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.8", Y= 53.2" . 13" WIDE X 7" HIGH
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

81 13/16"
13/16" 46 3/8"

3 1/4"
1 1/16"
CONTROL PANEL
BOTTOM DETAIL
818 1,501 728
7 11/16"
69 3/4" 47 3/8"
ORIGIN

C X
G

3" INLET

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT
42 11/16"
32 3/8"

23 1/8" 23 5/16"
10"

88 5/16" - FRAME WIDTH 5 5/8" 46 1/2" 3" OUTLET


88 13/16" - OVERALL WIDTH 142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH

Project Name :
YLAA Sold To : Date : 12/18/2012 12:58:34
PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0101HE46 Contractor : UNIT Dwg. Lev. :
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 98.5 TONS
MODEL: YLAA-B0101HE

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS


UNIT1

47
YLAA
91 TO 130
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0115SE
Number of Compressors 4
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Cooling Capacity TR 113.9
Total Power Input kW 140.9
EER EER 9.7
IPLV EER 14.6
NPLV EER 14.6
Sound Pressure (Hemispherical Method) dB(A) 88
Sound Pressure Measured at ft 3.3

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 8.8
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 38.3 / 38.3
Total Flow Rate USGPM 272.6
Total Pressure Drop ft H2O 12.4
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 3"

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 124 / 124
Number of Fans 6
Altitude ft 0
Total Air Flow cfm 88993
Total Fan Power kW 10.1

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 256
Max. Fuse / CB Rating A 300
Min. Fuse / CB Rating A 300
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 5029
Operating Weight lb 5101
Refrigerant Charge lb 119
Overall Length in 142.7
Overall Width in 88.3
Overall Height in 94.2
48 JOHNSON CONTROLS
5/8" DIA
MOUNTING
HOLES (TYP)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
582 866 545
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:

jOHNSON CONTROLS
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 5,029, OPERATING - 5,102. POWER ENTRY
3. CENTER OF GRAVITY FROM ORIGIN: X= 68", Y= 53.5" . 13" WIDE X 7" HIGH
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

81 13/16"
13/16" 46 3/8"

3 1/4"
1 1/16"
CONTROL PANEL
BOTTOM DETAIL
941 1,442 728
7 11/16"
69 3/4" 47 3/8"
ORIGIN

C X
G

3" INLET

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT
42 11/16"
32 3/8"

23 1/8" 23 5/16"
10"

88 5/16" - FRAME WIDTH 5 5/8" 46 1/2" 3" OUTLET


88 13/16" - OVERALL WIDTH 142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH

Project Name : New Project Sold To : Date : 12/11/2012 8:18:19


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0115SE46 Contractor : UNIT Dwg. Lev. : A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 113.9 TONS
MODEL: YLAA-B0115SE

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS


UNIT0

49
YLAA
91 TO 130
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0120SE
Number of Compressors 4
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Cooling Capacity TR 119.6
Total Power Input kW 143.3
EER EER 10
IPLV EER 14.8
NPLV EER 14.8
Sound Pressure (Hemispherical Method) dB(A) 88
Sound Pressure Measured at ft 3.3

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 13.2
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 40.6 / 40.6
Total Flow Rate USGPM 285.3
Total Pressure Drop ft H2O 8.4
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 3"

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 125.1 / 125.1
Number of Fans 6
Altitude ft 0
Total Air Flow cfm 88993
Total Fan Power kW 10.1

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 256
Max. Fuse / CB Rating A 300
Min. Fuse / CB Rating A 300
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 5183
Operating Weight lb 5293
Refrigerant Charge lb 128
Overall Length in 142.7
Overall Width in 88.3
Overall Height in 94.2
50 JOHNSON CONTROLS
5/8" DIA
MOUNTING
HOLES (TYP)
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
578 906 600
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. RECOMMENDED MINUMUM CLEARANCES:

jOHNSON CONTROLS
SIDE TO WALL - 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THEN ONE ADJACENT WALL MAY BE HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 5,183, OPERATING - 5,293. POWER ENTRY
3. CENTER OF GRAVITY FROM ORIGIN: X= 69.5", Y= 53.2" . 13" WIDE X 7" HIGH
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMODATIONS
IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

81 13/16"
13/16" 46 3/8"

3 1/4"
1 1/16"
CONTROL PANEL
BOTTOM DETAIL
937 1,486 789
7 11/16"
69 3/4" 47 3/8"
ORIGIN

C X
G

3" INLET

94 3/8" - OVERALL HEIGHT


88 5/8" - FRAME HEIGHT
42 11/16"
32 3/8"

23 1/8" 23 5/16"
10"

88 5/16" - FRAME WIDTH 5 5/8" 46 1/2" 3" OUTLET


88 13/16" - OVERALL WIDTH 142 1/4" - FRAME LENGTH
149 5/16" - OVERALL LENGTH

Project Name : New Project Sold To : Date : 12/11/2012 8:21:24


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0120SE46 Contractor : UNIT Dwg. Lev. : A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 119.6 TONS
MODEL: YLAA-B0120SE

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS


UNIT0

51
YLAA
91 TO 130
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0136SE
Number of Compressors 6
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Net Cooling Capacity TR 129.9
Total Power Input kW 154.3
EER EER 10.1
IPLV EER 15.5
NPLV EER 16.5
Sound Power dB(A) 93

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 10
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 37.2 / 39.6
Total Flow Rate USGPM 310.7
Total Pressure Drop ft H2O 13.4
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 4"
Min Fluid Flow Rate USGPM 120
Max Fluid Flow Rate USGPM 625

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 126.9 / 113.2
Number of Fans 8
Altitude ft 0
Total Air Flow cfm 120776
Total Fan Power kW 13.4

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 285
Max. Fuse / CB Rating A 300
Min. Fuse / CB Rating A 300
Unit Short Circuit Current Withstand [kA] 5
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 6103
Operating Weight lb 6187
Refrigerant Charge lb 146
Overall Length in 187.7
Overall Width in 88.3
Overall Height in 94.2
Software Version YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

52 JOHNSON CONTROLS
NOTES:
5/8" DIA
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING MOUNTING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE. HOLES (TYP)
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL POWER ENTRY

jOHNSON CONTROLS
PERFORMANCE DEGRADATION. 13" WIDE X 7" HIGH

RECOMMENDED MINUMUM CLEARANCES:


SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
46 3/8"

81 5/8"
NO MORE THAN ONE ADJACENT WALL MAY 13/16"
BE HIGHER THAN THE UNIT.

2. WEIGHTS (LB): SHIPPING - 6,102; OPERATING - 6,186. CONTROL PANEL


BOTTOM DETAIL
3. CENTER OF GRAVITY FROM ORIGIN: X= 82.6"; Y= 51.9" .

3 5/16"
1 3/16"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.

6 1/2"
69" 75 1/2"
ORIGIN

C X
G

4" INLET

4" OUTLET

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT
23 3/16" 58" 59 13/16"
10"

88 1/4" - FRAME WIDTH 5 3/8"


32 3/8"

88 3/4" - OVERALL WIDTH 186 1/4" - FRAME LENGTH

Project Name : cg ylaa Sold To : Date : 5/21/2013 15:16:15


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0136SE46 Contractor : Dwg. Lev. :
AHRI CAPACITY 129.9 TONS
MODEL: YLAAB0136SE

UNIT A JOHNSON CONTROLS COMPANY


NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS
UNIT1

53
YLAA
91 TO 130
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0142HE
Number of Compressors 6
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Net Cooling Capacity TR 132.1
Total Power Input kW 152.3
EER EER 10.4
IPLV EER 14.4
NPLV EER 16.2
Sound Power dB(A) 96

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 13.2
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 39.2 / 41.5
Total Flow Rate USGPM 315.4
Total Pressure Drop ft H2O 10
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 4"
Min Fluid Flow Rate USGPM 150
Max Fluid Flow Rate USGPM 625

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 123.1 / 116.4
Number of Fans 8
Altitude ft 0
Total Air Flow cfm 120776
Total Fan Power kW 13.4

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 285
Max. Fuse / CB Rating A 300
Min. Fuse / CB Rating A 300
Unit Short Circuit Current Withstand [kA] 5
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 6333
Operating Weight lb 6444
Refrigerant Charge lb 157
Overall Length in 187.7
Overall Width in 88.3
Overall Height in 94.2
Software Version YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

54 JOHNSON CONTROLS
NOTES:
5/8" DIA
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING MOUNTING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE. HOLES (TYP)
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL POWER ENTRY

jOHNSON CONTROLS
PERFORMANCE DEGRADATION. 13" WIDE X 7" HIGH

RECOMMENDED MINUMUM CLEARANCES:


SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
46 3/8"

81 5/8"
NO MORE THAN ONE ADJACENT WALL MAY 13/16"
BE HIGHER THAN THE UNIT.

2. WEIGHTS (LB): SHIPPING - 6,334; OPERATING - 6,444. CONTROL PANEL


BOTTOM DETAIL
3. CENTER OF GRAVITY FROM ORIGIN: X= 83"; Y= 52.1" .

3 5/16"
1 3/16"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.

6 1/2"
69" 75 1/2"
ORIGIN

C X
G

4" INLET

4" OUTLET

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT
23 3/16" 58" 59 13/16"
10"

88 1/4" - FRAME WIDTH 5 3/8"


32 3/8"

88 3/4" - OVERALL WIDTH 186 1/4" - FRAME LENGTH

Project Name : cg ylaa Sold To : Date : 5/21/2013 15:16:37


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0142HE46 Contractor : UNIT Dwg. Lev. :
AHRI CAPACITY 132.1 TONS
MODEL: YLAAB0142HE

A JOHNSON CONTROLS COMPANY


NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS
UNIT2

55
YLAA
131 TO 175
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0156HE
Number of Compressors 5
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Net Cooling Capacity TR 147.3
Total Power Input kW 173.2
EER EER 10.2
IPLV EER 15.5
NPLV EER 15.8
Sound Power dB(A) 97

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 10
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 36.9 / 38.7
Total Flow Rate USGPM 351.9
Total Pressure Drop ft H2O 16.7
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 4"
Min Fluid Flow Rate USGPM 120
Max Fluid Flow Rate USGPM 625

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 118.8 / 117.1
Number of Fans 10
Altitude ft 0
Total Air Flow cfm 150440
Total Fan Power kW 16.8

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 319
Max. Fuse / CB Rating A 350
Min. Fuse / CB Rating A 350
Unit Short Circuit Current Withstand [kA] 5
Wire Lugs Per Phase 1
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 7269
Operating Weight lb 7353
Refrigerant Charge lb 172
Overall Length in 232.7
Overall Width in 88.3
Overall Height in 94.2
Software Version YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

56 JOHNSON CONTROLS
NOTES:
5/8" DIA
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING MOUNTING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED HOLES (TYP)
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. POWER ENTRY
13" WIDE X 7" HIGH

jOHNSON CONTROLS
RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY 13/16" 46 3/8"

81 5/8"
BE HIGHER THAN THE UNIT.
CONTROL PANEL
2. WEIGHTS (LB): SHIPPING - 7,269; OPERATING - 7,352.
BOTTOM DETAIL
3. CENTER OF GRAVITY FROM ORIGIN: X= 95.8"; Y= 51.2" .

3 5/16"
1 3/8"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.
7 11/16"
69" 42 1/2" 93 5/8"
ORIGIN

C X
G

4" INLET

4" OUTLET

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT
23 3/16" 58" 43" 82 7/8"
10"

88 1/4" - FRAME WIDTH 5 3/8"


32 3/8"

88 3/4" - OVERALL WIDTH 230 1/4" - FRAME LENGTH

Project Name : cg ylaa Sold To : Date : 5/21/2013 15:16:58


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0156HE46 Contractor : UNIT Dwg. Lev. :
AHRI CAPACITY 147.3 TONS
MODEL: YLAAB0156SE

A JOHNSON CONTROLS COMPANY


NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS
UNIT3

57
YLAA
131 TO 175
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0170SE
Number of Compressors 6
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Net Cooling Capacity TR 170.5
Total Power Input kW 208.6
EER EER 9.8
IPLV EER 15.1
NPLV EER 15.9
Sound Power dB(A) 97

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 10
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 37 / 37
Total Flow Rate USGPM 407.4
Total Pressure Drop ft H2O 22.1
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 4"
Min Fluid Flow Rate USGPM 120
Max Fluid Flow Rate USGPM 625

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 121.3 / 121.3
Number of Fans 10
Altitude ft 0
Total Air Flow cfm 150440
Total Fan Power kW 16.8

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 372
Max. Fuse / CB Rating A 400
Min. Fuse / CB Rating A 400
Unit Short Circuit Current Withstand [kA] 5
Wire Lugs Per Phase 2
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 7624
Operating Weight lb 7708
Refrigerant Charge lb 179
Overall Length in 232.7
Overall Width in 88.3
Overall Height in 94.2
Software Version YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

58 JOHNSON CONTROLS
NOTES:
5/8" DIA
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING MOUNTING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED HOLES (TYP)
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. POWER ENTRY
13" WIDE X 7" HIGH

jOHNSON CONTROLS
RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY 13/16" 46 3/8"

81 5/8"
BE HIGHER THAN THE UNIT.
CONTROL PANEL
2. WEIGHTS (LB): SHIPPING - 7,624; OPERATING - 7,707.
BOTTOM DETAIL
3. CENTER OF GRAVITY FROM ORIGIN: X= 97.1"; Y= 52.2" .

3 5/16"
1 3/8"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.
7 11/16"
69" 42 1/2" 93 5/8"
ORIGIN

C X
G

4" INLET

4" OUTLET

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT
23 3/16" 58" 43" 82 7/8"
10"

88 1/4" - FRAME WIDTH 5 3/8"


32 3/8"

88 3/4" - OVERALL WIDTH 230 1/4" - FRAME LENGTH

Project Name : cg ylaa Sold To : Date : 5/21/2013 15:17:18


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0170SE46 Contractor : UNIT Dwg. Lev. :
A JOHNSON CONTROLS COMPANY
Dwg. Scale : NTS
AHRI CAPACITY 170.5 TONS
MODEL: YLAAB0170SE

NOT FOR CONSTRUCTION For : TAG: UNIT4

59
YLAA
131 TO 175
Air Cooled Scroll Chiller
Performance Specification
Unit Type and Size
ID YLAA-B0175HE
Number of Compressors 6
Compressor Type Scroll - Hermetic
Number of Compressor Circuits 2

Technical Data
Refrigerant Type R410A
Net Cooling Capacity TR 176
Total Power Input kW 211.1
EER EER 10
IPLV EER 15.1
NPLV EER 16
Sound Power dB(A) 97

Evaporator
Evaporator Type Plate Heat Exchanger
Fluid Volume USGAL 14.3
Fluid Type Water
Entering Liquid Temperature °F 54
Leaving Liquid Temperature °F 44
EvaporatingTemperature °F 39.6 / 39.6
Total Flow Rate USGPM 420
Total Pressure Drop ft H2O 16.4
Fouling Factor h.ft².F/Btu 0.0001
Fluid Connection Diameter in 4"
Min Fluid Flow Rate USGPM 180
Max Fluid Flow Rate USGPM 650

Condenser (Air Cooled)


Ambient Air Temperature °F 95
Condensing Temperature °F 122 / 122
Number of Fans 10
Altitude ft 0
Total Air Flow cfm 150440
Total Fan Power kW 16.8

Electrical Data
Nominal Voltage / Voltage Limits 460-3-60 / 414-506
Min. Circuit Ampacity A 372
Max. Fuse / CB Rating A 400
Min. Fuse / CB Rating A 400
Unit Short Circuit Current Withstand [kA] 5
Wire Lugs Per Phase 2
Wire Range (Lug Size) #4 - 500 kcmil

Weights and Dimensions


Shipping Weight lb 7772
Operating Weight lb 7891
Refrigerant Charge lb 187
Overall Length in 232.7
Overall Width in 88.3
Overall Height in 94.2
Software Version YW13.02a

Certified in accordance with the AHRI Air-Cooled Water Chilling Packages Using Vapor Compression Cycle
Certification Program, which is based on AHRI Standard 550/590 (I-P). Certified units may be found in the AHRI
Directory at www.ahridirectory.org Auxiliary components included in total KW - Oil heaters, Chiller controls.
Auxiliary power is already included in the compressor and fan power

60 JOHNSON CONTROLS
NOTES:
5/8" DIA
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING MOUNTING
SNOW, FOR WINTER OPERATION) OR AIR RECIRCULATION ENSURES RATED HOLES (TYP)
PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE.
SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED
BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION. POWER ENTRY
13" WIDE X 7" HIGH

jOHNSON CONTROLS
RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL - 6'
REAR TO WALL - 6'
CONTROL PANEL TO WALL - 4'
TOP - NO OBSTRUCTIONS ALLOWED
DISTANCE BETWEEN ADJACENT UNITS - 10'.
NO MORE THAN ONE ADJACENT WALL MAY 13/16" 46 3/8"

81 5/8"
BE HIGHER THAN THE UNIT.
CONTROL PANEL
2. WEIGHTS (LB): SHIPPING - 7,771; OPERATING - 7,890.
BOTTOM DETAIL
3. CENTER OF GRAVITY FROM ORIGIN: X= 97.4"; Y= 52" .

3 5/16"
1 3/8"
4. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN
ACCOMODATIONS IN CHILLED WATER PIPING NEAR THE
EVAPORATOR.
7 11/16"
69" 42 1/2" 93 5/8"
ORIGIN

C X
G

4" INLET

4" OUTLET

94 3/8" - OVERALL HEIGHT


88 1/2" - FRAME HEIGHT
23 3/16" 58" 43" 82 7/8"
10"

88 1/4" - FRAME WIDTH 5 3/8"


32 3/8"

88 3/4" - OVERALL WIDTH 230 1/4" - FRAME LENGTH

Project Name : cg ylaa Sold To : Date : 5/21/2013 15:17:39


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
Engineer : York Contract# : Form :
MODEL: YLAA0175HE46 Contractor : UNIT Dwg. Lev. :
AHRI CAPACITY 176 TONS
MODEL: YLAAB0175HE

A JOHNSON CONTROLS COMPANY


NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS
UNIT5

61
YLAA
131 TO 175
62 JOHNSON CONTROLS
YVAA
150 to 500 Tons
Air Cooled Screw Chiller

jOHNSON CONTROLS 63
YVAA RIGGING
Lifting Unit
Container lugs should be inserted into the holes provided in the bottom of the frame rail.
Use spreader bars to avoid lifting chains hitting the chiller. Various methods of spreader bar arrangements may
be used; keeping in mind the intent is to keep the unit stable and to keep the chains from hitting the chiller and
causing damage.

WARNING — Never lift the chiller using a forklift or by hooking the top rails. Use only the lifting
holes provided.

Lifting instructions are placed on a label on the chiller and on the shipping bag.

64 JOHNSON CONTROLS
Delivery and Storage
To ensure consistent quality and maximum reliability, all units are tested and inspected before leaving the factory.
Units are shipped completely assembled and containing refrigerant under pressure. Units are shipped without
export crating unless crating has been specified on the Sales Order.
If the unit is to be put into storage, prior to installation, the following precautions should be observed.
  •  The chiller must be “blocked” so that the base is not permitted to sag or bow.
  •  Ensure that all openings, such as water connections, are securely capped.
  •  Do not store where exposed to ambient air temperatures exceeding 43°C (110°F).
  • The condensers should be covered to protect the coils and fins from potential damage and corrosion,
particularly where building work is in progress.
  • The unit should be stored in a location where there is minimal activity in order to limit the risk of accidental
physical damage.
  •  To prevent inadvertent operation of the pressure relief devices the unit must not be steam cleaned.
  •  It is recommended that the unit is periodically inspected during storage.

Inspection
Remove any transit packing and inspect the unit to ensure that all components have been delivered and that no
damage has occurred during transit. If any damage is evident, it should be noted on the carrier’s freight bill and a
claim entered in accordance with the instructions given on the advice note.
Major damage must be reported immediately to your local Johnson Controls representative.

Moving the Chiller


Prior to moving the unit, ensure that the installation site is suitable for installing the unit and is easily capable of sup-
porting the weight of the unit and all associated services.
The units are designed to be lifted using shackles or safety hooks. A spreader bar or frame should be used in
order to prevent damage to the unit from the lifting chains. (Refer to Figure 4 on Page 20 of the Operations and
Maintenance Guide [Form 201.28-NM1.1 (812)] for hooks.)
Units are provided with lifting eyes in the sites of the base frame, which can be attached directly using container
lugs, shackles or safety hooks (Refer to Figure 4 on Page 20 of the Operations and Maintenance Guide [Form
201.28-NM1.1 (812)] for proper lifting illustration).

WARNING — The unit must only be lifted by the base frame at the points provided. Never move the
unit on rollers, or lift the unit using a forklift truck.

Care should be taken to avoid damaging the condenser cooling fins when moving the unit.

Lifting Weights
For details of weights and weight distribution, refer to the data shipped in the chiller information packet and unit
nameplate.

jOHNSON CONTROLS 65
AIR COOLED SCREW CHILLER
YVAA - 150 to 500 TONS (R-134A)
BENEFITS
• Continuous function, microprocessor controlled Variable Speed Drive (VSD) for valve less, smooth capacity
control to 10% of chiller capacity
• Chiller speed matched to system requirements at off-peak conditions resulting in lower energy usage
• Use of VSD reduces compressor moving parts by 50%
• Soft motor start with no electrical inrush reduces components stress, heat buildup
• Operating efficiencies at off-design conditions results in IPLVs as high as 19.8 EER
• Standard full load power factor of 95%, maintained throughout operating range resulting in improved
energy savings
• Superior acoustic operation at off-design conditions
• HFC-R134a standard for long term availability and zero ODP
• Wide range of options to fit any design requirement
• Competitors MCA is an average of 10% higher than YORK’s
• Lower MCA allows for smaller wiring and smaller circuit breakers therefore lower costs
• Allows for replacing chiller and increasing tonnage without replacing electrical components
• Industry’s only 18-month air cooled warranty that covers all parts.

UPGRADE OPTIONS
• Remote Cooler
• Factory mounted non-fused disconnect switch or circuit breaker
• Epoxy Post Coated, Pre Coated or Post Coated for tube and fin
• Seamless internally enhanced copper fin & tube coils arranged in staggered rows; mechanically bonded to
full eight aluminum fins
• Evaporator Options:
• 1-1/2" Insulation (double thickness)
• Raised Face Flange Accessory for cooler nozzles
• Flow Switch Accessory: Vapor proof, SPDT, NEMA 3R switch, 150psig
• Suction service isolation valve per circuit (discharge valve standard)
• Unit Enclosure Options:
• Wire Panels (full unit): coated, heavy gauge welded wire mesh mounted on exterior of unit to prevent
unauthorized access to refrigerant components
• Louvered Panels (condenser coils only): Painted to match unit; louvered panels mounted over exterior
condenser coils faces to visually screen unit, protects coils
• Louvered Panels (full unit): Painted to match unit; to protect condenser coils, visually screen internal
components and prevent unauthorized access
• Louvered (condensers)/Wire Panels (mechanicals): Louvered steel panels on external condenser coil
faces, heavy-gauge welded-wire mesh around base to prevent unauthorized access
• Sound Attenuation:
• SilentNightTM controls to force lower sound levels on demand or per user schedule
• Ultra quiet fans, compressor sound blankets and/or acoustical enclosures
• Vibration Isolation: Neoprene, 1" spring isolators or 2" spring isolators

66 JOHNSON CONTROLS
AIR COOLED SCREW CHILLER
YVAA - 150 to 500 TONS
PACKAGE DESCRIPTION: Evaporator:
• Self contained, designed for outdoor installation • High efficiency Hybrid falling film cooler;
• Baked on powder paint refrigerant in shell and water in tubes
• Heavy gauge, formed galvanized steel base • Removable heads to access copper tubes
• Factory mounted control transformer • Air vent and water drain connections
• ARI-Standard 550/590-11 Rated & Certified • Heater protection to -20 deg. F ambient
• All exposed wiring routed through liquid-tight, • Insulated with ¾" closed cell foam
non-metallic conduit • Design working pressure 150 PSIG water side
and 235 PSIG on refrigerant side
Compressors:
Refrigerant circuit:
• Reliable VSD driven semi-hermetic twin screw
• High efficiency, accessible hermetic motor with • Independent circuits per compressor
redundant overload protection • Computer controlled bending of refrigerant pipe
• Temperature actuated body cartridge heater reduces over 60% of pipe brazed joints
• Acoustically tuned discharge gas muffler • Liquid line components include: manual shutoff
• Design pressure of compressor 450 PSIG valve with charging port, removable core filter-
drier, solenoid valve, sight glass with moisture
indicator, electronic expansion valves
Condenser:
• Discharge line proided with manual compressor
• Low noise, full airflow cross section fans for shutoff service valve
maximum efficiency; statically & dynamically bal- • External Oil separators with no moving parts, 450
anced for low vibration operation; positioned in PSIG design working pressure
extended orifices for low sound
• High efficiency, direct drive, 3-phase totally
Controls:
enclosed fan motors with double sealed, perma-
nently lubricated ball bearings • All controls housed in a NEMA 3R cabinet with
• Condenser coils are made of a single material to gasket sealed, hinged & latched door
avoid galvanic corrosion due to dissimilar metals. • VSD section includes dedicated inverter for each
Coils and headers are brazed as one piece compressor
• Design Working Pressure 450 PSIG • Control display accessible without opening main
cabinet doors
• LCD, 80-character display with backlight
Electrical:
• Color coded, sealed keypad
• Competitors MCA is an average of 10% higher • Standard controls permit operation from 0 to
than YORK’s 125 deg F ambient temperature
• Lower MCA allows for smaller wiring and smaller
circuit breakers therefore lower costs
• Allows for replacing chiller and increasing ton-
nage without replacing electrical components

jOHNSON CONTROLS 67
Air Cooled Screw Chiller
Performance Specification
Unit Tag Qty. Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
1 YVAA0153BAF46 150.0 460/3/60 R134a
Pin:
BASE MODEL POWER CONTROLS PIPING COMP EVAPORATOR COND CABINET MISC WARR

  YVAA0153BAF46BA VSXX XTAXLXXXX60 44XOXXX S189W 1SXXA2B MXF PXXXX XXXX BXSX
5 10 15 20 25 30 35 40 45 50 55 60 65

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.0 Min. Flow Rate (gpm) 250.0 EER / COP 10.1 / 3.0
LWT (°F) 44.0 Max. Flow Rate (gpm) 950.0 IPLV 15.1 / 4.4
Design Flow Rate (gpm) 359.6 Minimum Unit Capacity 10 %
Pressure Drop (ft.) 5.6 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 95.0 Rigging Wt. (lbs.) 11518
Fouling Factor 0.00010 Altitude (ft.) 0 Operating Wt. (lbs.) 11979
Water Volume (gal) 58.0 Ambient Temp. Min (°F) 0.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 109 109
Fan QTY/FLA (each) 4/3.3 4/3.3

Single Point
Min. Circuit Ampacity 275
Recommended Fuse/CB Rating 350
Max. Inverse Time CB Rating 350
Max. Dual Element Fuse Size (Amps) 350
Unit Short Circuit Withstand (STD) 30kA
Wire Lugs Per Phase* 2
Wire Range (Lug Size) #2 - 600 KCM
Unit Power Factor 0.95
Control KVA 2.0 Operating Condition Electrical Data
Starter Type VSD Compressor kW 162.6
Total Fan kW 14.8
Total kW 177.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 150.0 162.6 10.1 / 3.0
75.0 80.0 112.5 86.2 13.3 / 3.9
50.0 65.0 75.0 43.0 16.3 / 4.8
25.0 55.0 37.5 18.2 17.6 / 5.2

SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0153BAF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 95.0 95.0 96.0 98.0 95.0 87.0 83.0 78.0 99.0
75.0 80.0 95.0 95.0 96.0 95.0 92.0 86.0 82.0 78.0 97.0
50.0 65.0 94.0 94.0 95.0 94.0 91.0 85.0 81.0 77.0 96.0
25.0 55.0 91.0 91.0 92.0 91.0 88.0 82.0 78.0 73.0 92.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0153BAF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 68.0 68.0 69.0 71.0 68.0 60.0 56.0 51.0 72.0
75.0 80.0 68.0 68.0 69.0 68.0 65.0 59.0 55.0 51.0 70.0
50.0 65.0 67.0 67.0 68.0 67.0 64.0 58.0 54.0 50.0 69.0
25.0 55.0 64.0 64.0 65.0 64.0 61.0 55.0 51.0 46.0 65.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

Performance at AHRI Conditions


YVAA0153BAF46
Evaporator Data Condenser Data Performance Data
EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.1 / 3.0
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 15.1 / 4.4
Flow Rate (gpm) 359.6 Capacity (Tons) 150.0
Pressure Drop (ft.) 5.6
Fluid Water
Fouling Factor 0.00010
Water Volume (gal) 58.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
68 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR 3/4" MOUNTING HOLES (TYP)
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, 6 15/16"
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE POWER ENTRY
1 3/8" (TYP) 10" WIDE X 13" HIGH
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE 644 2,147 2,147 1,052

jOHNSON CONTROLS
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
4"
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE 60"
HIGHER THEN THE UNIT. 1 1/2"
2. WEIGHTS (LB):SHIPPING - 11,518, OPERATING - 11,980.
3. CENTER OF GRAVITY FROM ORIGIN: X= 101.8", Y= 44.0". A A
VIEW B-B

VSD / POWER PANEL


4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.

14 1/8" POWER ENTRY IS ON BOTTOM OF PANEL

780 2,116 2,116 978

CONTROL ENTRY
71 1/4" 62 9/16" 10 3/8" 3" WIDE X 11 1/2" HIGH
48 11/16"

2 15/16"
Y

X
C
G 12"

VIEW A-A

6" (WATER OUTLET)


94 1/2" B B

6" (WATER INLET)

26 9/16"

47 5/16"

(4) RIGGING HOLES


44 1/8" 15 1/8" EACH SIDE 3 X 2
88 3/16"
75 15/16" 56 1/8" 41 1/4" 18 1/4"
203 1/4"

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.
POWER: SINGLE POINT WITH TERMINAL BLOCK

Project Name : stp Sold To : Date : 12/6/2012 11:43:34


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCREW CHILLER Engineer : York Contract# : Form : 201.28-EG1
MODEL: YVAA0153BAF46 Contractor : UNIT Dwg. Lev. : 01/11 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 150.0 TONS
MODEL: YVAA0153BAF46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

69
YVAA
150 TO 200
Air Cooled Screw Chiller
Performance Specification
Unit Tag Qty. Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
1 YVAA0183ABF46 175.0 460/3/60 R134a
Pin:
BASE MODEL POWER CONTROLS PIPING COMP EVAPORATOR COND CABINET MISC WARR

  YVAA0183ABF46BA VSXX XTAXLXXXX60 44XOXXX S192W 1SXXA2B MXF PXXXX XXXX BXSX
5 10 15 20 25 30 35 40 45 50 55 60 65

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.0 Min. Flow Rate (gpm) 200.0 EER / COP 10.4 / 3.0
LWT (°F) 44.0 Max. Flow Rate (gpm) 750.0 IPLV 15.4 / 4.5
Design Flow Rate (gpm) 419.5 Minimum Unit Capacity 10 %
Pressure Drop (ft.) 11.4 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 95.0 Rigging Wt. (lbs.) 12019
Fouling Factor 0.00010 Altitude (ft.) 0 Operating Wt. (lbs.) 12460
Water Volume (gal) 48.0 Ambient Temp. Min (°F) 0.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 139 111
Fan QTY/FLA (each) 6/3.3 4/3.3

Single Point
Min. Circuit Ampacity 322
Recommended Fuse/CB Rating 450
Max. Inverse Time CB Rating 450
Max. Dual Element Fuse Size (Amps) 450
Unit Short Circuit Withstand (STD) 30kA
Wire Lugs Per Phase* 2
Wire Range (Lug Size) #2 - 600 KCM
Unit Power Factor 0.95
Control KVA 2.0 Operating Condition Electrical Data
Starter Type VSD Compressor kW 184.4
Total Fan kW 17.9
Total kW 202.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 175.0 184.4 10.4 / 3.0
75.0 80.0 131.3 97.8 13.5 / 4.0
50.0 65.0 87.5 49.4 16.5 / 4.8
25.0 55.0 43.7 22.0 17.9 / 5.2

SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0183ABF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 96.0 96.0 97.0 98.0 94.0 88.0 84.0 80.0 99.0
75.0 80.0 96.0 96.0 97.0 96.0 94.0 87.0 83.0 79.0 98.0
50.0 65.0 94.0 95.0 95.0 95.0 91.0 86.0 82.0 78.0 96.0
25.0 55.0 91.0 91.0 92.0 91.0 88.0 82.0 78.0 73.0 93.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0183ABF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 69.0 69.0 70.0 71.0 67.0 61.0 57.0 53.0 72.0
75.0 80.0 69.0 69.0 70.0 69.0 67.0 60.0 56.0 52.0 71.0
50.0 65.0 67.0 68.0 68.0 68.0 64.0 59.0 55.0 51.0 69.0
25.0 55.0 64.0 64.0 65.0 64.0 61.0 55.0 51.0 46.0 66.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

Performance at AHRI Conditions


YVAA0183ABF46
Evaporator Data Condenser Data Performance Data
EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.4 / 3.0
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 15.4 / 4.5
Flow Rate (gpm) 419.5 Capacity (Tons) 175.0
Pressure Drop (ft.) 11.4
Fluid Water
Fouling Factor 0.00010
Water Volume (gal) 48.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
70 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR 3/4" MOUNTING HOLES (TYP)
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, 17 11/16"
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE POWER ENTRY
1 1/4" (TYP) 10" WIDE X 13" HIGH
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE 1,660 1,088 1,088 1,659 711

jOHNSON CONTROLS
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES: 4"
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE 60"
HIGHER THEN THE UNIT.
1 1/2"
2. WEIGHTS (LB):SHIPPING - 12,019, OPERATING - 12,460.
3. CENTER OF GRAVITY FROM ORIGIN: X= 128.4", Y= 44.2". A A

VSD / POWER PANEL


4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION. VIEW B-B

14 1/8" POWER ENTRY IS ON BOTTOM OF PANEL

1,729 1,084 1,084 1,654 704

CONTROL ENTRY
47 5/8" 66 1/8" 10 3/8" 3" WIDE X 11 1/2" HIGH
46 3/4" 38 3/4"

2 15/16"
Y

X
C
G 12"

VIEW A-A

6" (WATER OUTLET)


94 1/2" B B

6" (WATER INLET)

25 9/16"

47 5/16"

(4) RIGGING HOLES


44 1/8" 14 1/8" EACH SIDE 3 X 2
88 3/16"
77 1/4" 82 13/16" 42 1/16" 18 1/4"
247"

POWER: SINGLE POINT WITH TERMINAL BLOCK


YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

Project Name : stp Sold To : Date : 12/6/2012 11:51:6


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCREW CHILLER Engineer : York Contract# : Form : 201.28-EG1
MODEL: YVAA0183ABF46 Contractor : UNIT Dwg. Lev. : 01/11 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 175.0 TONS
MODEL: YVAA0183ABF46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

71
YVAA
150 TO 200
Air Cooled Screw Chiller
Performance Specification
Unit Tag Qty. Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
1 YVAA0233BEF46 200.0 460/3/60 R134a
Pin:
BASE MODEL POWER CONTROLS PIPING COMP EVAPORATOR COND CABINET MISC WARR

  YVAA0233BEF46BA VSXX XTAXLXXXX60 44XOXXX S176W 1SXXA2B MXF PXXXX XXXX BXSX
5 10 15 20 25 30 35 40 45 50 55 60 65

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.0 Min. Flow Rate (gpm) 250.0 EER / COP 10.5 / 3.1
LWT (°F) 44.0 Max. Flow Rate (gpm) 950.0 IPLV 15.2 / 4.5
Design Flow Rate (gpm) 479.4 Minimum Unit Capacity 10 %
Pressure Drop (ft.) 9.2 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 95.0 Rigging Wt. (lbs.) 13288
Fouling Factor 0.00010 Altitude (ft.) 0 Operating Wt. (lbs.) 13750
Water Volume (gal) 58.0 Ambient Temp. Min (°F) 0.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 158 135
Fan QTY/FLA (each) 7/3.3 5/3.3

Single Point
Min. Circuit Ampacity 375
Recommended Fuse/CB Rating 500
Max. Inverse Time CB Rating 500
Max. Dual Element Fuse Size (Amps) 500
Unit Short Circuit Withstand (STD) 30kA
Wire Lugs Per Phase* 2
Wire Range (Lug Size) #2 - 600 KCM
Unit Power Factor 0.95
Control KVA 2.0 Operating Condition Electrical Data
Starter Type VSD Compressor kW 208.4
Total Fan kW 21.1
Total kW 229.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 200.0 208.4 10.5 / 3.1
75.0 80.0 150.0 111.2 13.5 / 4.0
50.0 65.0 100.0 56.5 16.2 / 4.7
25.0 55.0 50.0 23.9 17.3 / 5.1

SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 97.0 97.0 98.0 97.0 94.0 88.0 84.0 80.0 99.0
75.0 80.0 97.0 97.0 98.0 97.0 93.0 88.0 84.0 80.0 99.0
50.0 65.0 96.0 96.0 97.0 96.0 93.0 87.0 83.0 78.0 97.0
25.0 55.0 93.0 93.0 94.0 94.0 90.0 84.0 80.0 76.0 95.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 70.0 70.0 71.0 70.0 67.0 61.0 57.0 53.0 72.0
75.0 80.0 70.0 70.0 71.0 70.0 66.0 61.0 57.0 53.0 72.0
50.0 65.0 69.0 69.0 70.0 69.0 66.0 60.0 56.0 51.0 70.0
25.0 55.0 66.0 66.0 67.0 67.0 63.0 57.0 53.0 49.0 68.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

Performance at AHRI Conditions


YVAA0213ADF46
Evaporator Data Condenser Data Performance Data
EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.5 / 3.1
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 15.2 / 4.5
Flow Rate (gpm) 479.4 Capacity (Tons) 200.0
Pressure Drop (ft.) 9.2
Fluid Water
Fouling Factor 0.00010
Water Volume (gal) 58.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
72 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR 3/4" MOUNTING HOLES (TYP)
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, 73 5/16"
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE POWER ENTRY
1 1/4" (TYP) 10" WIDE X 13" HIGH
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE 659 659 2,230 1,423 947 947

jOHNSON CONTROLS
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES: 4"
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE 60"
HIGHER THEN THE UNIT.
1 1/2"
2. WEIGHTS (LB):SHIPPING - 13,288, OPERATING - 13,750.
3. CENTER OF GRAVITY FROM ORIGIN: X= 134.7", Y= 44.1". A A

VSD / POWER PANEL


4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION. VIEW B-B

14 1/8" POWER ENTRY IS ON BOTTOM OF PANEL

670 670 2,247 1,430 933 933

CONTROL ENTRY
41 5/8" 66 1/8" 10 3/8" 3" WIDE X 11 1/2" HIGH
72 5/16" 51 3/4" 38 3/4"

2 15/16"
Y

X
C
G 12"

VIEW A-A

6" (WATER OUTLET)


94 1/2" B B

6" (WATER INLET)

26 9/16"

47 5/16"

(5) RIGGING HOLES


44 1/8" 15 1/8" EACH SIDE 3 X 2
88 3/16"
57 5/8" 77 5/8" 76 13/16" 42 1/16" 18 1/4"
291 3/16"

POWER: SINGLE POINT WITH TERMINAL BLOCK


YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

Project Name : stp Sold To : Date : 12/6/2012 12:52:26


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCREW CHILLER Engineer : York Contract# : Form : 201.28-EG1
MODEL: YVAA0233BEF46 Contractor : UNIT Dwg. Lev. : 01/11
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 200.0 TONS
MODEL: YVAA0233BEF46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

73
YVAA
150 TO 200
Air Cooled Screw Chiller
Performance Specification
Unit Tag Qty. Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
1 YVAA0273DGF46 250.0 460/3/60 R134a
Pin:
BASE MODEL POWER CONTROLS PIPING COMP EVAPORATOR COND CABINET MISC WARR

  YVAA0273DGF46BA VSXX XTAXLXXXX60 44XOXXX S188W 1SXXA2B MXF XXXXX XXXX BXSX
5 10 15 20 25 30 35 40 45 50 55 60 65

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.0 Min. Flow Rate (gpm) 300.0 EER / COP 10.8 / 3.2
LWT (°F) 44.0 Max. Flow Rate (gpm) 1150.0 NPLV 16.0 / 4.7
Design Flow Rate (gpm) 598.3 Minimum Unit Capacity 10 %
Pressure Drop (ft.) 15.2 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 95.0 Rigging Wt. (lbs.) 16275
Fouling Factor 0.00010 Altitude (ft.) 0 Operating Wt. (lbs.) 17103
Water Volume (gal) 82.0 Ambient Temp. Min (°F) 0.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 175 175
Fan QTY/FLA (each) 7/3.3 7/3.3

Single Point
Min. Circuit Ampacity 444
Recommended Fuse/CB Rating 600
Max. Inverse Time CB Rating 600
Max. Dual Element Fuse Size (Amps) 600
Unit Short Circuit Withstand (STD) 30kA
Wire Lugs Per Phase* 2
Wire Range (Lug Size) #2 - 600 KCM
Unit Power Factor 0.95
Control KVA 2.0 Operating Condition Electrical Data
Starter Type VSD Compressor kW 253.5
Total Fan kW 24.2
Total kW 277.7

Notes: * Use Copper Conductors only

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 250.0 253.5 10.8 / 3.2
75.0 80.0 187.5 135.2 14.0 / 4.1
50.0 65.0 125.0 68.3 17.2 / 5.0
25.0 55.0 62.5 29.0 18.9 / 5.5

SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0273DGF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 97.0 97.0 98.0 97.0 94.0 88.0 84.0 80.0 99.0
75.0 80.0 97.0 97.0 98.0 97.0 93.0 88.0 84.0 80.0 99.0
50.0 65.0 96.0 96.0 97.0 96.0 93.0 87.0 83.0 78.0 97.0
25.0 55.0 93.0 93.0 94.0 94.0 90.0 84.0 80.0 76.0 95.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0213ADF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 71.0 71.0 72.0 73.0 70.0 63.0 59.0 54.0 74.0
75.0 80.0 71.0 71.0 72.0 71.0 67.0 62.0 58.0 53.0 72.0
50.0 65.0 69.0 69.0 70.0 70.0 66.0 61.0 57.0 52.0 71.0
25.0 55.0 66.0 67.0 67.0 67.0 63.0 58.0 54.0 49.0 68.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

Performance at AHRI Conditions


YVAA0273DGF46
Evaporator Data Condenser Data Performance Data
EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.8 / 3.2
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 16.0 / 4.7
Flow Rate (gpm) 599.8 Capacity (Tons) 249.9
Pressure Drop (ft.) 15.3
Fluid Water
Fouling Factor 0.00010
Water Volume (gal) 82.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
74 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR 3/4" MOUNTING HOLES (TYP)
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, 42 7/8"
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE POWER ENTRY

jOHNSON CONTROLS
1 5/16" (TYP) 10" WIDE X 13" HIGH
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE 1,389 2,135 2,778 1,539 710
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
4"
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE 60"
HIGHER THEN THE UNIT. 1 1/2"
2. WEIGHTS (LB):SHIPPING - 16,275, OPERATING - 17,103.
3. CENTER OF GRAVITY FROM ORIGIN: X= 168.3", Y= 44.0". A A

VSD / POWER PANEL


4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION. VIEW B-B

14 1/8" POWER ENTRY IS ON BOTTOM OF PANEL

1,518 1,946 3,036 1,372 681

CONTROL ENTRY
79 13/16" 70 5/8" 10 3/8" 3" WIDE X 11 1/2" HIGH
100 5/16" 40 3/16"

2 15/16"
Y

X
C
G 12"

VIEW A-A

6" (WATER OUTLET)


94 11/16" B B

6" (WATER INLET)

26 3/4"

47 1/2"

(6) RIGGING HOLES


44 1/8" 15 5/16" EACH SIDE 3 X 2
88 3/16"
59 1/8" 83 1/4" 60 3/16" 48 5/16" 60 1/4" 12 3/8"
335 3/16"

POWER: SINGLE POINT WITH TERMINAL BLOCK

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

Project Name : adsfasdfa Sold To : Date : 3/6/2013 8:56:2


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCREW CHILLER Engineer : York Contract# : Form : 201.28-EG1
MODEL: YVAA0273DGF46 Contractor : UNIT Dwg. Lev. : 01/11 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 250.0 TONS
MODEL: YVAA0273DGF46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

75
YVAA
201 TO 500
Air Cooled Screw Chiller
Performance Specification
Unit Tag Qty. Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
1 YVAA0343EKF46 300.0 460/3/60 R134a
Pin:
BASE MODEL POWER CONTROLS PIPING COMP EVAPORATOR COND CABINET MISC WARR

YVAA0343EKF46BA VSXX XTAXLXXXX60 44XOXXX S179W 1SXXA2B MXF PXXXX XXXX BXSX
5 10 15 20 25 30 35 40 45 50 55 60 65

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.0 Min. Flow Rate (gpm) 400.0 EER / COP 10.9 / 3.2
LWT (°F) 44.0 Max. Flow Rate (gpm) 1500.0 IPLV 15.5 / 4.5
Design Flow Rate (gpm) 719.1 Minimum Unit Capacity 10 %
Pressure Drop (ft.) 11.8 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 95.0 Rigging Wt. (lbs.) 19315
Fouling Factor 0.00010 Altitude (ft.) 0 Operating Wt. (lbs.) 20175
Water Volume (gal) 113.0 Ambient Temp. Min (°F) 0.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 209 209
Fan QTY/FLA (each) 9/3.3 9/3.3

Single Point
Min. Circuit Ampacity 533
Recommended Fuse/CB Rating 700
Max. Inverse Time CB Rating 700
Max. Dual Element Fuse Size (Amps) 700
Unit Short Circuit Withstand (STD) 30kA
Wire Lugs Per Phase* 3
Wire Range (Lug Size) #2 - 600 KCM
Unit Power Factor 0.95
Control KVA 2.0 Operating Condition Electrical Data
Starter Type VSD Compressor kW 300.3
Total Fan kW 30.5
Total kW 330.8

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 300.0 300.3 10.9 / 3.2
75.0 80.0 225.0 162.5 13.9 / 4.1
50.0 65.0 150.0 85.1 16.5 / 4.8
25.0 55.0 75.0 38.1 17.8 / 5.2

SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0343EKF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 99.0 99.0 100.0 99.0 98.0 92.0 87.0 83.0 102.0
75.0 80.0 99.0 99.0 100.0 100.0 98.0 91.0 88.0 84.0 102.0
50.0 65.0 97.0 97.0 98.0 98.0 95.0 89.0 85.0 81.0 100.0
25.0 55.0 94.0 94.0 95.0 94.0 92.0 87.0 83.0 79.0 96.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0343EKF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 72.0 72.0 73.0 72.0 71.0 65.0 60.0 56.0 75.0
75.0 80.0 72.0 72.0 73.0 73.0 71.0 64.0 61.0 57.0 75.0
50.0 65.0 70.0 70.0 71.0 71.0 68.0 62.0 58.0 54.0 73.0
25.0 55.0 67.0 67.0 68.0 67.0 65.0 60.0 56.0 52.0 69.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

Performance at AHRI Conditions


YVAA0343EKF46
Evaporator Data Condenser Data Performance Data
EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.9 / 3.2
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 15.5 / 4.5
Flow Rate (gpm) 719.1 Capacity (Tons) 300.0
Pressure Drop (ft.) 11.8
Fluid Water
Fouling Factor 0.00010
Water Volume (gal) 113.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
76 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS

jOHNSON CONTROLS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR 3/4" MOUNTING HOLES (TYP)
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, 132 3/16"
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE POWER ENTRY
1 3/8" (TYP) 10" WIDE X 13" HIGH
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE 863 1,910 2,260 2,260 1,995 801
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
4"
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE 60"
HIGHER THEN THE UNIT. 1 1/2"
2. WEIGHTS (LB):SHIPPING - 19,316, OPERATING - 20,175.
3. CENTER OF GRAVITY FROM ORIGIN: X= 187.5", Y= 44.0". A A

VSD / POWER PANEL


4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION. VIEW B-B

14 1/8" POWER ENTRY IS ON BOTTOM OF PANEL

863 1,951 2,259 2,259 1,966 790

CONTROL ENTRY
79 13/16" 70 5/8" 10 1/4" 3" WIDE X 11 1/2" HIGH
84 7/16" 97 1/2" 40 3/16"

2 15/16"
Y

X
C
G 12"

VIEW A-A

8" (WATER OUTLET)


94 11/16" B B

8" (WATER INLET)

29 1/2"

47 1/2"

(7) RIGGING HOLES


44 1/8" 15 1/2" EACH SIDE 3 X 2
88 3/16"
1000" 61 3/4" 60 3/16" 48 5/16" 60 1/4" 12 3/8"
423 1/8"

POWER: SINGLE POINT WITH TERMINAL BLOCK

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

Project Name : stp Sold To : Date : 12/6/2012 13:34:33


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCREW CHILLER Engineer : York Contract# : Form : 201.28-EG1
MODEL: YVAA0343EKF46 Contractor : UNIT Dwg. Lev. : 01/11
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 300.0 TONS
MODEL: YVAA0343EKF46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

77
YVAA
201 TO 500
Air Cooled Screw Chiller
Performance Specification
Unit Tag Qty. Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
1 YVAA0373FJF46 350.0 460/3/60 R134a
Pin:
BASE MODEL POWER CONTROLS PIPING COMP EVAPORATOR COND CABINET MISC WARR

YVAA0373FJF46BA VSXX XTAXLXXXX60 44XOXXX S196W 1SXXA2B MXF XXXXX XXXX BXSX
5 10 15 20 25 30 35 40 45 50 55 60 65

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.0 Min. Flow Rate (gpm) 460.0 EER / COP 10.4 / 3.0
LWT (°F) 44.0 Max. Flow Rate (gpm) 1540.0 NPLV 15.0 / 4.4
Design Flow Rate (gpm) 837.7 Minimum Unit Capacity 10 %
Pressure Drop (ft.) 11.2 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 95.0 Rigging Wt. (lbs.) 22346
Fouling Factor 0.00010 Altitude (ft.) 0 Operating Wt. (lbs.) 23405
Water Volume (gal) 96.0 Ambient Temp. Min (°F) 0.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 327 178
Fan QTY/FLA (each) 7/3.3 7/3.3

Single Point
Min. Circuit Ampacity 658
Recommended Fuse/CB Rating 800
Max. Inverse Time CB Rating 800
Max. Dual Element Fuse Size (Amps) 800
Unit Short Circuit Withstand (STD) 30kA
Wire Lugs Per Phase* 2
Wire Range (Lug Size) #2 - 600 KCM
Unit Power Factor 0.95
Control KVA 3.0 Operating Condition Electrical Data
Starter Type VSD Compressor kW 372.6
Total Fan kW 31.8
Total kW 404.4

Notes: * Use Copper Conductors only

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 350.0 372.6 10.4 / 3.0
75.0 80.0 262.5 203.4 13.3 / 3.9
50.0 65.0 175.0 105.5 16.1 / 4.7
25.0 55.0 87.5 44.4 17.4 / 5.1

SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0373FJF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 99.0 99.0 100.0 103.0 100.0 97.0 96.0 85.0 105.0
75.0 80.0 99.0 100.0 100.0 100.0 97.0 91.0 88.0 83.0 102.0
50.0 65.0 98.0 98.0 99.0 98.0 95.0 89.0 86.0 83.0 100.0
25.0 55.0 96.0 96.0 97.0 97.0 92.0 87.0 84.0 81.0 98.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0373FJF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 72.0 72.0 73.0 76.0 73.0 70.0 69.0 58.0 78.0
75.0 80.0 72.0 73.0 73.0 73.0 70.0 64.0 61.0 56.0 75.0
50.0 65.0 71.0 71.0 72.0 71.0 68.0 62.0 59.0 56.0 73.0
25.0 55.0 69.0 69.0 70.0 70.0 65.0 60.0 57.0 54.0 71.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

Performance at AHRI Conditions


YVAA0373FJF46
Evaporator Data Condenser Data Performance Data
EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.4 / 3.0
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 15.0 / 4.4
Flow Rate (gpm) 839.7 Capacity (Tons) 349.9
Pressure Drop (ft.) 11.3
Fluid Water
Fouling Factor 0.00010
Water Volume (gal) 96.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
78 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR 3/4" MOUNTING HOLES (TYP)

jOHNSON CONTROLS
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, 2 1/2"
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING POWER ENTRY
ISOLATORS RECOMMENDED MINUMUM CLEARANCES: 2 1/2" 10" WIDE X 13" HIGH
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE SECTION B-B
HIGHER THEN THE UNIT.
2. WEIGHTS (LB):SHIPPING - 22,346, OPERATING - 23,405.
3. CENTER OF GRAVITY FROM ORIGIN: X= 200.3", Y= 46.6".
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH
A A

2 15/16"
142 78 70 10
60 5/8" 63 7/8"
11/16" 11/16" 11/16" 5/16"

12"

SECTION A-A

8" WATER OUTLET 8" WATER INLET

B B
94
11/16"

42 1/8"
28
13/16"

15 (6) RIGGING HOLES EACH SIDE 3 X 2


13/16" 133 60 12
44 1/8" 63 7/8" 56 5/8" 108 1/2"
11/16" 5/16" 5/16"
END VIEW
88
5/16" 467 1/8"

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

Project Name : adsfasdfa Sold To : Date : 3/5/2013 14:21:26


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCREW CHILLER Engineer : York Contract# : Form : 201.28-EG1
MODEL: YVAA0373FJF46 Contractor : UNIT Dwg. Lev. : 01/11 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 350.0 TONS
MODEL: YVAA0373EKF46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

79
YVAA
201 TO 500
Air Cooled Screw Chiller
Performance Specification
Unit Tag Qty. Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
1 YVAA0443FMF46 400.0 460/3/60 R134a
Pin:
BASE MODEL POWER CONTROLS PIPING COMP EVAPORATOR COND CABINET MISC WARR

YVAA0443FMF46BA VDXX XTAXLXXXX60 44XOXXX S172W 1SXXA2B MXF PXXXX XXXX BXSX
5 10 15 20 25 30 35 40 45 50 55 60 65

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.0 Min. Flow Rate (gpm) 460.0 EER / COP 10.6 / 3.1
LWT (°F) 44.0 Max. Flow Rate (gpm) 1540.0 IPLV 14.8 / 4.3
Design Flow Rate (gpm) 958.8 Minimum Unit Capacity 10 %
Pressure Drop (ft.) 14.3 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 95.0 Rigging Wt. (lbs.) 25942
Fouling Factor 0.00010 Altitude (ft.) 0 Operating Wt. (lbs.) 27001
Water Volume (gal) 96.0 Ambient Temp. Min (°F) 0.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 287 287
Fan QTY/FLA (each) 12/3.3 12/3.3

Single Point
Min. Circuit Ampacity 398 398
Min. Non-Fused Disconnect (Amps) 600 600
Min. Dual Element Fuse Size (Amps) 600 600
Max. Dual Element Fuse Size (Amps) 600 600
Min. Circuit Breaker (Amps) 600 600
Max. Circuit Breaker (Amps) 600 600
Wire Range (Lug Size) * #2 - 600 KCM #2 - 600 KCM
Unit Power Factor 0.95 0.95
Control KVA 3.0 Operating Condition Electrical Data
Starter Type VSD Compressor kW 414.4
Total Fan kW 38.0
Total kW 452.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 400.0 414.4 10.6 / 3.1
75.0 80.0 300.0 231.7 13.2 / 3.9
50.0 65.0 200.0 120.9 15.8 / 4.6
25.0 55.0 100.0 53.3 17.3 / 5.1

SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0443FMF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 100.0 100.0 101.0 102.0 99.0 95.0 93.0 88.0 104.0
75.0 80.0 100.0 100.0 101.0 102.0 100.0 92.0 90.0 85.0 104.0
50.0 65.0 99.0 99.0 100.0 100.0 96.0 90.0 87.0 85.0 101.0
25.0 55.0 96.0 96.0 97.0 98.0 93.0 87.0 84.0 82.0 98.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0443FMF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 73.0 73.0 74.0 75.0 72.0 68.0 66.0 61.0 77.0
75.0 80.0 73.0 73.0 74.0 75.0 73.0 65.0 63.0 58.0 77.0
50.0 65.0 72.0 72.0 73.0 73.0 69.0 63.0 60.0 58.0 74.0
25.0 55.0 69.0 69.0 70.0 71.0 66.0 60.0 57.0 55.0 71.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

Performance at AHRI Conditions


YVAA0443FMF46
Evaporator Data Condenser Data Performance Data
EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.6 / 3.1
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 14.8 / 4.3
Flow Rate (gpm) 958.8 Capacity (Tons) 400.0
Pressure Drop (ft.) 14.3
Fluid Water
Fouling Factor 0.00010
Water Volume (gal) 96.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
80 JOHNSON CONTROLS
NOTES:
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR 3/4" MOUNTING HOLES (TYP)
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, 287"

jOHNSON CONTROLS
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL 2 1/2"
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE POWER ENTRY
HIGHER THEN THE UNIT. 2 1/2" 10" WIDE X 13" HIGH
2. WEIGHTS (LB):SHIPPING - 25,942, OPERATING - 27,001.
3. CENTER OF GRAVITY FROM ORIGIN: X= 213.7", Y= 44.0".
SECTION B-B
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION.
A A
CONTROL ENTRY
3" WIDE X 11 1/2" HIGH

56" 56" 143" 79" 51" 73" 71" 10"


3"

12"

SECTION A-A

8" WATER OUTLET 8" WATER INLET


88"

B B
95"

42"
29"

(8) RIGGING HOLES EACH SIDE 3 X 2


16"
44 1/8" 67" 42" 146" 52" 57" 109" 60" 12" END
VIEW

88" 555"

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

Project Name : stp Sold To : Date : 12/6/2012 13:47:41


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCREW CHILLER Engineer : York Contract# : Form : 201.28-EG1
MODEL: YVAA0443FMF46 Contractor : UNIT Dwg. Lev. : 01/11 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 400.0 TONS
MODEL: YVAA0443FMF46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

81
YVAA
201 TO 500
Air Cooled Screw Chiller
Performance Specification
Unit Tag Qty. Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
1 YVAA0523HMF46 450.0 460/3/60 R134a
Pin:
BASE MODEL POWER CONTROLS PIPING COMP EVAPORATOR COND CABINET MISC WARR

YVAA0523HMF46BA VDXX XTAXLXXXX60 44XOXXX S183W 1SXXA2B MXF PXXXX XXXX BXSX
5 10 15 20 25 30 35 40 45 50 55 60 65

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.0 Min. Flow Rate (gpm) 550.0 EER / COP 10.9 / 3.2
LWT (°F) 44.0 Max. Flow Rate (gpm) 1880.0 IPLV 15.4 / 4.5
Design Flow Rate (gpm) 1078.7 Minimum Unit Capacity 10 %
Pressure Drop (ft.) 14.8 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 95.0 Rigging Wt. (lbs.) 28427
Fouling Factor 0.00010 Altitude (ft.) 0 Operating Wt. (lbs.) 29784
Water Volume (gal) 147.0 Ambient Temp. Min (°F) 0.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 312 312
Fan QTY/FLA (each) 13/3.3 13/3.3

Single Point
Min. Circuit Ampacity 423 423
Min. Non-Fused Disconnect (Amps) 700 700
Min. Dual Element Fuse Size (Amps) 700 700
Max. Dual Element Fuse Size (Amps) 700 700
Min. Circuit Breaker (Amps) 700 700
Max. Circuit Breaker (Amps) 700 700
Wire Range (Lug Size) * #2 - 600 KCM #2 - 600 KCM
Unit Power Factor 0.95 0.95
Control KVA 3.0 Operating Condition Electrical Data
Starter Type VSD Compressor kW 452.4
Total Fan kW 41.1
Total kW 493.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 450.0 452.4 10.9 / 3.2
75.0 80.0 337.5 251.2 13.7 / 4.0
50.0 65.0 225.0 131.9 16.4 / 4.8
25.0 55.0 112.5 58.2 18.2 / 5.3

SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0523HMF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 101.0 101.0 102.0 102.0 101.0 96.0 92.0 87.0 104.0
75.0 80.0 100.0 101.0 102.0 103.0 100.0 93.0 92.0 86.0 104.0
50.0 65.0 99.0 99.0 100.0 100.0 96.0 91.0 87.0 85.0 101.0
25.0 55.0 96.0 96.0 97.0 97.0 93.0 87.0 84.0 81.0 98.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0523HMF46 ( Equipped with Low Sound Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 74.0 74.0 75.0 75.0 74.0 69.0 65.0 60.0 77.0
75.0 80.0 73.0 74.0 75.0 76.0 73.0 66.0 65.0 59.0 77.0
50.0 65.0 72.0 72.0 73.0 73.0 69.0 64.0 60.0 58.0 74.0
25.0 55.0 69.0 69.0 70.0 70.0 66.0 60.0 57.0 54.0 71.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

Performance at AHRI Conditions


YVAA0523HMF46
Evaporator Data Condenser Data Performance Data
EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.9 / 3.2
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 15.4 / 4.5
Flow Rate (gpm) 1078.6 Capacity (Tons) 450.0
Pressure Drop (ft.) 14.8
Fluid Water
Fouling Factor 0.00010
Water Volume (gal) 147.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
82 JOHNSON CONTROLS
3/4" MOUNTING HOLES (TYP)

jOHNSON CONTROLS
NOTES: 309"
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, 2 1/2"
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL POWER ENTRY
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING 2 1/2" 10" WIDE X 13" HIGH
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT SECTION B-B
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT. A A
2. WEIGHTS (LB):SHIPPING - 28,427, OPERATING - 29,784.
3. CENTER OF GRAVITY FROM ORIGIN: X= 222.4", Y= 44.0". CONTROL ENTRY
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION. 3" WIDE X 11 1/2" HIGH

57" 78" 143" 79" 51" 73" 71" 10"

3"

12"

SECTION A-A

8" WATER OUTLET 8" WATER INLET 132"

B B
95"

42"
30"

16" (8) RIGGHING HOLES EACH SIDE 3 X 2 END


END
VIEWVIEW
44 1/8" 79" 59" 146" 52" 57" 109" 60" 12"

88" 599"

YVAA can be tailored and tuned to your needs. Please contact your
JCI Representative for further capacities and efficiencies.

Project Name : stp Sold To : Date : 12/6/2012 13:57:16


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCREW CHILLER Engineer : York Contract# : Form : 201.28-EG1
MODEL: YVAA0523HMF46 Contractor : UNIT Dwg. Lev. : 01/11 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 450.0 TONS
MODEL: YVAA0523HMF46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

83
YVAA
201 TO 500
Air Cooled Screw Chiller
Performance Specification
Unit Tag Qty. Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
1 YVAA0523HMG46 500.0 460/3/60 R134a
Pin:
BASE MODEL POWER CONTROLS PIPING COMP EVAPORATOR COND CABINET MISC WARR

YVAA0523HMG46BA VDXX XTAXLXXXX60 44XOXXX S200W 1SXXA3B MXG XXXXX XXXX BXSX
5 10 15 20 25 30 35 40 45 50 55 60 65

Evaporator Data Evaporator Data (Cont.) Performance Data


EWT (°F) 54.0 Min. Flow Rate (gpm) 400.0 EER / COP 10.5 / 3.1
LWT (°F) 44.0 Max. Flow Rate (gpm) 1400.0 IPLV 14.4 / 4.2
Design Flow Rate (gpm) 1199.9 Minimum Unit Capacity 10 %
Pressure Drop (ft.) 51.4 Condenser Data Physical Data
Fluid Water Ambient Temp. Design (°F) 95.0 Rigging Wt. (lbs.) 29365
Fouling Factor 0.00010 Altitude (ft.) 0 Operating Wt. (lbs.) 30722
Water Volume (gal) 147.0 Ambient Temp. Min (°F) 0.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 341 341
Fan QTY/FLA (each) 13/5.1 13/5.1

Single Point
Min. Circuit Ampacity 478 478
Min. Non-Fused Disconnect (Amps) 800 800
Min. Dual Element Fuse Size (Amps) 800 800
Max. Dual Element Fuse Size (Amps) 800 800
Min. Circuit Breaker (Amps) 800 800
Max. Circuit Breaker (Amps) 800 800
Wire Range (Lug Size) * #2 - 600 KCM #2 - 600 KCM
Unit Power Factor 0.95 0.95
Control KVA 3.0 Operating Condition Electrical Data
Starter Type VSD Compressor kW 495.3
Total Fan kW 74.7
Total kW 570.0

Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Ambient (°F) Capacity (Tons) Compressor kW Unit Efficiency
100.0 95.0 500.0 495.3 10.5 / 3.1
75.0 80.0 375.0 272.8 12.8 / 3.8
50.0 65.0 250.0 151.9 15.5 / 4.5
25.0 55.0 125.0 63.4 16.2 / 4.7

SOUND POWER LEVELS (In Accordance with AHRI 370) – Octave Band Center Frequency, Hz
YVAA0523HMG46 ( Equipped with High Airflow Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K LWA
100.0 95.0 103.0 117.0 116.0 110.0 107.0 103.0 96.0 90.0 113.0
75.0 80.0 103.0 117.0 116.0 110.0 106.0 102.0 94.0 89.0 112.0
50.0 65.0 101.0 115.0 114.0 107.0 103.0 99.0 91.0 87.0 110.0
25.0 55.0 99.0 113.0 112.0 105.0 101.0 97.0 90.0 85.0 108.0

SOUND PRESSURE LEVELS in dB at 30.0 (ft.) **


YVAA0523HMG46 ( Equipped with High Airflow Fans )
Load % Ambient (°F) 63 125 250 500 1K 2K 4K 8K dBA
100.0 95.0 76.0 90.0 89.0 83.0 80.0 76.0 69.0 63.0 86.0
75.0 80.0 76.0 90.0 89.0 83.0 79.0 75.0 67.0 62.0 85.0
50.0 65.0 74.0 88.0 87.0 80.0 76.0 72.0 64.0 60.0 83.0
25.0 55.0 72.0 86.0 85.0 78.0 74.0 70.0 63.0 58.0 81.0
** Chiller is assumed to be a point source on a reflecting surface (hemispherical radiation)

Performance at AHRI Conditions


YVAA0523HMG46
Evaporator Data Condenser Data Performance Data
EWT (°F) 54.0 Ambient Temp. (°F) 95.0 EER / COP 10.5 / 3.1
LWT (°F) 44.0 Altitude (ft.) 0 EER IPLV/COP IPLV 14.4 / 4.2
Flow Rate (gpm) 1199.9 Capacity (Tons) 500.0
Pressure Drop (ft.) 51.4
Fluid Water
Fouling Factor 0.00010
Water Volume (gal) 147.0
If you need a model or capacity between nominal sizes shown here, we can configure units within 1 ton increments. Please contact you JCI Sales Representative for selections and pricing.
84 JOHNSON CONTROLS
3/4" MOUNTING HOLES (TYP)

jOHNSON CONTROLS
528 5/16"

NOTES: 309"
1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS
(INCLUDING SNOW, FOR WINTER OPERATION) OR AIR
RECIRCULATION ENSURES RATED PERFORMANCE, RELIABLE
OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS
MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, 2 1/2"
RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE
DIMINISHED PERFORMANCE. YORK'S UNIT CONTROLS WILL OPTIMIZE
OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT;
HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL
PERFORMANCE DEGRADATION, ACCESS TO THE UNIT CONTROL POWER ENTRY
CENTER ASSUMES THE UNIT IS NO HIGHER THEN ON SPRING 2 1/2" 10" WIDE X 13" HIGH
ISOLATORS RECOMMENDED MINUMUM CLEARANCES:
SIDE TO WALL 6' REAR TO WALL - 6'; CONTROL PANEL TO WALL - 4';
TOP - NO OBSTRUCTIONS ALLOWED; DISTANCE BETWEEN ADJACENT SECTION B-B
UNITS - 10'. NO MORE THEN ONE ADJACENT WALL MAY BE
HIGHER THEN THE UNIT. A A
2. WEIGHTS (LB):SHIPPING - 29,365, OPERATING - 30,722.
3. CENTER OF GRAVITY FROM ORIGIN: X= 225.1", Y= 44.0". CONTROL ENTRY
4. WATER CONNECTIONS ARE GROOVED FOR VICTAULIC CONNECTION. 3" WIDE X 11 1/2" HIGH

57" 78" 143" 79" 51" 73" 71" 10"

3"

12"

SECTION A-A

8" WATER OUTLET


8" WATER INLET 132"

B B
95"

42"
30"

16" (8) RIGGHING HOLES EACH SIDE 3 X 2 END


END
VIEWVIEW
44 1/8" 79" 59" 146" 52" 57" 109" 60" 12"

88" 599"

Project Name : examples - Small tonnage BOM Sold To : Date : 4/26/2013 9:55:8
PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
AIR-COOLED SCREW CHILLER Engineer : York Contract# : Form : 201.28-EG1
MODEL: YVAA0523HMG46 Contractor : UNIT Dwg. Lev. : 01/11
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 500.0 TONS
MODEL: YVAA0523HMG46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

85
YVAA
201 TO 500
86 JOHNSON CONTROLS
YCWL
50 to 200 Tons
Water Cooled Scroll Chiller

jOHNSON CONTROLS 87
88 JOHNSON CONTROLS
YCWL RIGGING
Delivery and Storage
To ensure consistent quality and maximum reliability, all units are
tested and inspected before leaving the factory. Units are shipped
completely assembled and containing refrigerant under pressure.
Units are shipped without export crating unless this has been
specified on the Sales Order.
If the unit is to be put into storage, before installation, the following
precautions should be observed:
Ensure that all openings, such as water connections, are securely
capped.
Do not store where exposed to ambient air temperatures exceeding
107°F (42°C).
The unit should be stored in a location where there is minimal activity
to limit the risk of accidental physical damage.
To prevent inadvertent operation of the pressure relief devices the
unit must not be steam cleaned.
It is recommended that the unit is periodically inspected during
storage.

Inspection
Immediately upon receiving the unit, it should be inspected for pos-
sible damage which may have occurred during transit. If damage
is evident, it should be noted in the carrier’s freight bill. A written
request for inspection by the carrier’s agent should be made at once.
See “Instruction Manual”, Form 50.15-NM for more information and details.
Major damage must be reported immediately to your local Johnson Controls representative.

Moving the Unit


Before moving the unit, ensure that the installation site is suitable for installing the unit and is capable of supporting
the weight of the unit and all associated services.
The units are designed to be lifted using either lifting chains or a fork lift.

Lifting by Crane / Hoist


A spreader frame should be used to prevent damage to the unit from the lifting chains (Refer to page 34 of the
Operations and Maintenance Guide [Form 201.26-NM1]).

NOTE: The unit must only be lifted a the points provided.

jOHNSON CONTROLS 89
WATER COOLED SCROLL CHILLER
YCWL - 50 to 200 TONS
BENEFITS
• IPLV as high as 25.4 EER provide cost effective operation
• Designed for low acoustics without additional sound treatment
• Wide range of options to fit any design requirement
• HFC-410A Standard for zero ODP and low global warming potential; long service life
• Multiple scroll compressors offer redundancy and accurate capacity matching
• Native BACnet MSTP & Modbus communications for BAS integration

UPGRADE OPTIONS
• Low temperature brine chilling to 15°F
• Power Options:
• Single Point Power Connection to Terminal Block, Non-fused Disconnect or Circuit Breaker
• Multiple Point Power Connection to Circuit Breakers for retrofit projects
• Compressor Overloads to limit MCA (ideal for retrofit applications)
• Heat Pump (non-reversing) option to 130°F leaving condenser water temperature for energy conservation
• Remote Condenser YCRL variant for remote condenser applications
• Evaporator Options:
• Victaulic Flange Accessory for cooler nozzles
• Flow switch: Vapor proof, SPDT, NEMA 4X switch, 150 psig
• Vibration Isolators - Neoprene isolators, 1" spring isolators or 2" spring isolators

90 JOHNSON CONTROLS
WATER COOLED SCROLL CHILLER
YCWL - 50 to 200 TONS
PACKAGE DESCRIPTION: Evaporator:
• Completely assembled with all piping and wiring • High efficiency DX cooler, refrigerant in tubes and
ready for field installation chilled liquid through baffled shell
• Pressure and operational tested • Two independent circuits per chiller
• Provided with HFC-410A charge and initial oil • Removable heads to access copper tubes
charge • Water vent and drain connections
• Can be provided with optional overspray coat of • Insulated with 3/4" closed cell foam
Caribbean Blue enamel paint • Design working pressure 150 PSIG waterside and
400 PSIG on refrigerant side
Compressors:
Refrigerant Circuit:
• Reliable suction-gas cooled hermetic scrolls
• High efficiency motors with redundant overload • Tandem or trio compressors per circuit
protection • Liquid line components include: shut-off valve
• Microprocessor controlled compressor staging with charging port, high-absorption removable
regulates chiller capacity to 15% of maximum core filter-drier, solenoid valve, sight glass with
• Design Working Pressure 560 PSIG moisture indicator, thermal or electronic expan-
sion valves (depending on options)
• Entire suction line and liquid line between ex-
Condenser:
pansion valve and cooler insulated with flexible
• Cleanable, thru-tube type with removable heads closed-cell foam insulation
• Integral subcooling standard
• Equipped with relief valves
Controls:
• Steel shell and copper tubes
• All controls housed in a NEMA 1 cabinet with
gasket sealed, hinged & latched door
• LCD, 40-character display with backlight
• Color coded, 32-button sealed keypad

jOHNSON CONTROLS 91
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0056SE46 52.4 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.1 / 4.7
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 21.3 / 6.2
Flow Rate (gpm) 125.6 Flow Rate (gpm) 153.2 Physical Data
Pressure Drop (ft.) 12.2 Pressure Drop (ft.) 10.6 Rigging Wt. (lbs.) 3515
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 3648
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 22.4 Water Vol. (gal) 19.4

Electrical Data
Circuit 1 2 3 4
Compressor RLA 23.1/23.1 23.1/23.1
Compressor Start Current (LRA) 150.0/150.0 150.0/150.0

Single Point
Min. Circuit Ampacity 98.0
Min. Non-Fused Disconnect (Amps) 150.0
Min. Circuit Breaker (Amps) 110.0
Max. Circuit Breaker (Amps) 110.0
Wire Range (Lug Size) * (1)#12 - #1
Grounding Wire Lug Size
Total Amps 92.4 Operating Condition Electrical Data
Inrush (PW) Amps 150.0 Compressor kW 39.2
Starter Type Across the Line Total kW 39.2

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 52.4 85.0 95.0 39.2 16.1 / 4.7
75.0 41.1 76.4 84.0 26.3 18.8 / 5.5
50.0 29.0 67.1 72.4 15.4 22.6 / 6.6
25.0 14.2 65.0 67.6 7.3 23.3 / 6.8

92 JOHNSON CONTROLS
119 5/8"
X
15 1/16" 101 13/16"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO 25 7/8" 50" Y
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20" ORIGIN
FRONT TO WALL: 36" 915 (LB) 915 (LB)
9 7/8"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)

jOHNSON CONTROLS
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 3,515, OPERATING - 3,648.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 9.8" 9 7/8"
909 (LB) 909 (LB)
5/8" MOUNTING HOLES (TYP)

50"
34" 9"

34 5/8" 1"
OVERALL WIDTH
17 11/16"
POWER ENTRY IS ON TOP OF PANEL
8 15/16" TO RIGGING HOLES 12" WIDE X 6" HIGH
23 1/2"

29" 1 1/2" RIGGING HOLES 6 5/8" EVAP 6 5/8" EVAP


LIQUID INLET LIQUID OUTLET
VICTAULIC VICTAULIC
CONNECTION CONNECTION
4 1/2" CONDENSER
WATER OUTLET 64 1/2"
VICTAULIC
CONNECTION 5 1/2"
35 1/2"
4 1/2" CONDENSER 30 3/8"
WATER INLET
VICTAULIC
CONNECTION 9 1/16"

84 1/2" 8 5/8"
14 1/2" 15 1/2" TO COOLER CONN
5 1/8" 107 3/4"
29"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0056SE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 52.4 TONS
MODEL: YCWL0056SE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

93
YCWL
50 TO 90
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0064SE46 59.9 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 15.7 / 4.6
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 19.9 / 5.8
Flow Rate (gpm) 143.6 Flow Rate (gpm) 175.8 Physical Data
Pressure Drop (ft.) 15.7 Pressure Drop (ft.) 13.4 Rigging Wt. (lbs.) 3883
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 4016
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 22.4 Water Vol. (gal) 19.4

Electrical Data
Circuit 1 2 3 4
Compressor RLA 26.9/26.9 26.9/26.9
Compressor Start Current (LRA) 187.0/187.0 187.0/187.0

Single Point
Min. Circuit Ampacity 114.0
Min. Non-Fused Disconnect (Amps) 150.0
Min. Circuit Breaker (Amps) 125.0
Max. Circuit Breaker (Amps) 125.0
Wire Range (Lug Size) * (1)#10 - 300
Grounding Wire Lug Size
Total Amps 107.6 Operating Condition Electrical Data
Inrush (PW) Amps 187.0 Compressor kW 45.7
Starter Type Across the Line Total kW 45.7

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 59.9 85.0 95.0 45.7 15.7 / 4.6
75.0 47.1 76.4 84.1 31.1 18.2 / 5.3
50.0 33.3 67.2 72.5 19.1 20.9 / 6.1
25.0 16.3 65.0 67.6 9.2 21.2 / 6.2

94 JOHNSON CONTROLS
119 5/8"
X
15 1/16" 101 13/16"
NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO 25 7/8" 50" Y
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20" ORIGIN
FRONT TO WALL: 36" 966 (LB) 966 (LB)
9 7/8"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)

jOHNSON CONTROLS
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 3,883, OPERATING - 4,016.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.3" 9 7/8"
1,042 (LB) 1,042 (LB)
5/8" MOUNTING HOLES (TYP)

50"
34" 9"

34 5/8" 1"
OVERALL WIDTH
17 11/16"
POWER ENTRY IS ON TOP OF PANEL
8 15/16" TO RIGGING HOLES 12" WIDE X 6" HIGH
23 1/2"

29" 1 1/2" RIGGING HOLES 6 5/8" EVAP 6 5/8" EVAP


LIQUID INLET LIQUID OUTLET
VICTAULIC VICTAULIC
CONNECTION CONNECTION
4 1/2" CONDENSER
WATER OUTLET 64 1/2"
VICTAULIC
CONNECTION 5 1/2"
35 1/2"
4 1/2" CONDENSER 30 3/8"
WATER INLET
VICTAULIC
CONNECTION 9 1/16"

84 1/2" 8 5/8"
14 1/2" 15 1/2" TO COOLER CONN
5 1/8" 107 3/4"
29"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0064SE46 Contractor : UNIT Dwg. Lev. : 10/07
AHRI CAPACITY 59.9 TONS
MODEL: YCWL0064SE46

A JOHNSON CONTROLS COMPANY


NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

95
YCWL
50 TO 90
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0064HE46 62.4 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.5 / 4.8
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 20.2 / 5.9
Flow Rate (gpm) 149.6 Flow Rate (gpm) 181.7 Physical Data
Pressure Drop (ft.) 7.4 Pressure Drop (ft.) 6.6 Rigging Wt. (lbs.) 4533
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 4848
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 59.8 Water Vol. (gal) 26.9

Electrical Data
Circuit 1 2 3 4
Compressor RLA 26.9/26.9 26.9/26.9
Compressor Start Current (LRA) 187.0/187.0 187.0/187.0

Single Point
Min. Circuit Ampacity 114.0
Min. Non-Fused Disconnect (Amps) 150.0
Min. Circuit Breaker (Amps) 125.0
Max. Circuit Breaker (Amps) 125.0
Wire Range (Lug Size) * (1)#10 - 300
Grounding Wire Lug Size
Total Amps 107.6 Operating Condition Electrical Data
Inrush (PW) Amps 187.0 Compressor kW 45.5
Starter Type Across the Line Total kW 45.5

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 62.4 85.0 95.0 45.5 16.5 / 4.8
75.0 48.5 76.0 83.6 31.0 18.8 / 5.5
50.0 33.4 66.4 71.5 18.9 21.2 / 6.2
25.0 16.3 65.0 67.5 9.2 21.3 / 6.2

96 JOHNSON CONTROLS
124 3/8" X
19 13/16" 101 13/16"
NOTES: Y
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO 25 7/8" 50"
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20" ORIGIN
1,174 (LB) 1,174 (LB)
FRONT TO WALL: 36"
TOP: 43" 9 7/8"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)

jOHNSON CONTROLS
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,533, OPERATING - 4,848.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.2" 9 7/8"
1,250 (LB) 1,250 (LB)
5/8" MOUNTING HOLES (TYP)

50"
34" 9"

1"
33 13/16"
OVERALL WIDTH

17 11/16" 23 1/2" POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH
12 1/4" TO RIGGING HOLES

6 5/8" EVAP 6 5/8" EVAP


LIQUID INLET LIQUID OUTLET
29" 1 1/2" RIGGING HOLES VICTAULIC VICTAULIC
CONNECTION CONNECTION
67 5/8"

4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION 7 1/8"

35 1/2" 32"
4 1/2" CONDENSER
WATER INLET
VICTAULIC
CONNECTION 8 1/4"

14 1/2" 11 3/4" TO COOLER CONN 85" 8 3/8"


29" 5 1/8" 107 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0064HE46 Contractor : UNIT Dwg. Lev. : 10/07 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 62.4 TONS
MODEL: YCWL0064HE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

97
YCWL
50 TO 90
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0074SE46 67.8 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 15.2 / 4.5
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 20.2 / 5.9
Flow Rate (gpm) 162.5 Flow Rate (gpm) 200.2 Physical Data
Pressure Drop (ft.) 19.9 Pressure Drop (ft.) 16.8 Rigging Wt. (lbs.) 4061
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 4194
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 22.4 Water Vol. (gal) 19.4

Electrical Data
Circuit 1 2 3 4
Compressor RLA 30.4/30.4 26.9/26.9
Compressor Start Current (LRA) 225.0/225.0 187.0/187.0

Single Point
Min. Circuit Ampacity 122.0
Min. Non-Fused Disconnect (Amps) 150.0
Min. Circuit Breaker (Amps) 150.0
Max. Circuit Breaker (Amps) 150.0
Wire Range (Lug Size) * (1)#10 - 300
Grounding Wire Lug Size
Total Amps 114.6 Operating Condition Electrical Data
Inrush (PW) Amps 225.0 Compressor kW 53.6
Starter Type Across the Line Total kW 53.6

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 67.8 85.0 95.0 53.6 15.2 / 4.5
72.2 52.5 76.0 83.5 34.1 18.5 / 5.4
50.0 38.7 67.8 73.2 21.8 21.2 / 6.2
22.2 16.2 65.0 67.3 9.2 21.2 / 6.2

98 JOHNSON CONTROLS
125 15/16" X
21 3/8" 101 13/16"
NOTES: Y
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO 25 7/8" 50"
SERVICE THE UNITS ARE AS FOLLOWS: ORIGIN
REAR TO WALL: 20" 990 (LB) 990 (LB)
FRONT TO WALL: 36" 9 7/8"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)

jOHNSON CONTROLS
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,061, OPERATING - 4,194.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.4" 9 7/8"
1,106 (LB) 5/8" MOUNTING HOLES (TYP) 1,106 (LB)

50"
34" 9"
33 13/16" 1"
OVERALL WIDTH
17 11/16"

8 15/16" TO RIGGING HOLES 23 1/2" POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH

6 5/8" EVAP 6 5/8" EVAP


1 1/2" RIGGING HOLES LIQUID INLET LIQUID OUTLET
29" VICTAULIC VICTAULIC
CONNECTION CONNECTION

4 1/2" CONDENSER 68 7/8"


WATER OUTLET
VICTAULIC
CONNECTION
5 1/2"
35 1/2" 4 1/2" CONDENSER
WATER INLET 30 3/8"
VICTAULIC
CONNECTION
9 1/16"

84 1/2" 8 5/8"
14 1/2" 15 1/2" TO COOLER CONN

29" 5 1/8" 107 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0074SE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 67.8 TONS
MODEL: YCWL0074SE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

99
YCWL
50 TO 90
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0074HE46 72.7 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.3 / 4.8
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 20.7 / 6.1
Flow Rate (gpm) 174.4 Flow Rate (gpm) 212.0 Physical Data
Pressure Drop (ft.) 6.0 Pressure Drop (ft.) 8.6 Rigging Wt. (lbs.) 4911
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 5406
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 59.8 Water Vol. (gal) 26.9

Electrical Data
Circuit 1 2 3 4
Compressor RLA 30.4/30.4 26.9/26.9
Compressor Start Current (LRA) 225.0/225.0 187.0/187.0

Single Point
Min. Circuit Ampacity 122.0
Min. Non-Fused Disconnect (Amps) 150.0
Min. Circuit Breaker (Amps) 150.0
Max. Circuit Breaker (Amps) 150.0
Wire Range (Lug Size) * (1)#10 - 300
Grounding Wire Lug Size
Total Amps 114.6 Operating Condition Electrical Data
Inrush (PW) Amps 225.0 Compressor kW 53.4
Starter Type Across the Line Total kW 53.4

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 72.7 85.0 95.0 53.4 16.3 / 4.8
72.2 54.6 75.0 82.3 33.7 19.4 / 5.7
50.0 38.9 66.4 71.5 21.4 21.9 / 6.4
22.2 16.2 65.0 67.1 9.1 21.3 / 6.2

100 JOHNSON CONTROLS


123 5/16"

18 3/4" 101 13/16"


NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO X
29" 50"
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20" 1,294 (LB) 1,294 (LB)
FRONT TO WALL: 36" ORIGIN
Y
TOP: 43" 9 7/8"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)

jOHNSON CONTROLS
2. WEIGHTS (LB):SHIPPING - 4,911, OPERATING - 5,406.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.3"
9 7/8"
1,409 (LB) 1,409 (LB)
5/8" MOUNTING HOLES (TYP)
50"

34"

33 13/16" 1"
9"
OVERALL WIDTH

17 11/16"
23 1/2" POWER ENTRY IS ON TOP OF PANEL
12 3/4" TO RIGGING HOLES
12" WIDE X 6" HIGH

8 5/8" EVAP 8 5/8" EVAP


LIQUID INLET LIQUID OUTLET
29" 1 1/2" RIGGING HOLES
VICTAULIC VICTAULIC
CONNECTION CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION 74 5/8"

4 1/2" CONDENSER
40" WATER INLET
VICTAULIC 33 1/4"
CONNECTION 7 1/8"

8 1/4"

14 1/2" 16" TO COOLER CONN 83" 9 3/8"

29" 5 1/8" 107 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0074HE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 72.7 TONS
MODEL: YCWL0074HE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

101
YCWL
50 TO 90
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0084SE46 76.6 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 15.8 / 4.6
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 21.4 / 6.3
Flow Rate (gpm) 183.5 Flow Rate (gpm) 224.6 Physical Data
Pressure Drop (ft.) 24.9 Pressure Drop (ft.) 9.5 Rigging Wt. (lbs.) 4489
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 4684
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 22.4 Water Vol. (gal) 26.9

Electrical Data
Circuit 1 2 3 4
Compressor RLA 30.4/30.4 30.4/30.4
Compressor Start Current (LRA) 225.0/225.0 225.0/225.0

Single Point
Min. Circuit Ampacity 129.0
Min. Non-Fused Disconnect (Amps) 150.0
Min. Circuit Breaker (Amps) 150.0
Max. Circuit Breaker (Amps) 150.0
Wire Range (Lug Size) * (1)#10 - 300
Grounding Wire Lug Size
Total Amps 121.6 Operating Condition Electrical Data
Inrush (PW) Amps 225.0 Compressor kW 58.3
Starter Type Across the Line Total kW 58.3

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 76.6 85.0 95.0 58.3 15.8 / 4.6
75.0 61.0 76.9 84.6 39.7 18.4 / 5.4
50.0 44.3 68.2 73.6 23.5 22.7 / 6.7
25.0 21.9 65.0 67.7 11.1 23.8 / 7.0

102 JOHNSON CONTROLS


NOTES: 125 15/16"
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO X
SERVICE THE UNITS ARE AS FOLLOWS: 21 3/8" 101 13/16"
REAR TO WALL: 20"
FRONT TO WALL: 36" 25 7/8" 50" Y
TOP: 43"
1,093 (LB) 1,093 (LB) ORIGIN
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
9 7/8"

jOHNSON CONTROLS
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,489, OPERATING - 4,684.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.6"

1,249 (LB) 9 7/8"


1,249 (LB)
5/8" MOUNTING HOLES (TYP)

50"

34"
33 13/16"
OVERALL WIDTH 1"
9"
17 11/16"

8 15/16" TO RIGGING HOLES 23 1/2"


POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH

1 1/2" RIGGING HOLES 6 5/8" EVAP


LIQUID OUTLET
6 5/8" EVAP VICTAULIC
29" 4 1/2" CONDENSER LIQUID INLET CONNECTION
WATER OUTLET VICTAULIC
VICTAULIC CONNECTION
CONNECTION
68 7/8"

4 1/2" CONDENSER
WATER INLET
35 1/2" VICTAULIC 30 3/8"
CONNECTION 7 1/8"

8 1/4"

14 1/2" 15 1/2" TO COOLER CONN 84 1/2" 8 5/8"


29" 5 1/8" 107 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0084SE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 76.6 TONS
MODEL: YCWL0084SE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

103
YCWL
50 TO 90
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0084HE46 82.6 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.8 / 4.9
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 21.9 / 6.4
Flow Rate (gpm) 198.0 Flow Rate (gpm) 239.5 Physical Data
Pressure Drop (ft.) 7.6 Pressure Drop (ft.) 10.6 Rigging Wt. (lbs.) 5089
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 5584
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 59.8 Water Vol. (gal) 26.9

Electrical Data
Circuit 1 2 3 4
Compressor RLA 30.4/30.4 30.4/30.4
Compressor Start Current (LRA) 225.0/225.0 225.0/225.0

Single Point
Min. Circuit Ampacity 129.0
Min. Non-Fused Disconnect (Amps) 150.0
Min. Circuit Breaker (Amps) 150.0
Max. Circuit Breaker (Amps) 150.0
Wire Range (Lug Size) * (1)#10 - 300
Grounding Wire Lug Size
Total Amps 121.6 Operating Condition Electrical Data
Inrush (PW) Amps 225.0 Compressor kW 58.9
Starter Type Across the Line Total kW 58.9

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 82.6 85.0 95.0 58.9 16.8 / 4.9
75.0 64.4 76.2 83.8 39.7 19.5 / 5.7
50.0 44.7 66.6 71.8 23.0 23.3 / 6.8
25.0 21.9 65.0 67.5 11.0 23.8 / 7.0

104 JOHNSON CONTROLS


125 11/16"

21 1/8" 101 13/16"


NOTES:
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO X
29" 50"
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20" 1,318 (LB) 1,318 (LB)
FRONT TO WALL: 36" ORIGIN
Y
TOP: 43" 9 7/8"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)

jOHNSON CONTROLS
2. WEIGHTS (LB):SHIPPING - 5,089, OPERATING - 5,584.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.5"
9 7/8"
1,474 (LB) 1,474 (LB)
5/8" MOUNTING HOLES (TYP)
50"

34"

33 13/16" 1"
9"
OVERALL WIDTH

17 11/16"
23 1/2" POWER ENTRY IS ON TOP OF PANEL
12 3/4" TO RIGGING HOLES
12" WIDE X 6" HIGH

8 5/8" EVAP 8 5/8" EVAP


LIQUID INLET LIQUID OUTLET
29" 1 1/2" RIGGING HOLES
VICTAULIC VICTAULIC
CONNECTION CONNECTION
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION 74 5/8"

4 1/2" CONDENSER
40" WATER INLET
VICTAULIC 33 1/4"
CONNECTION 7 1/8"

8 1/4"

14 1/2" 16" TO COOLER CONN 83" 9 3/8"

29" 5 1/8" 107 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0084HE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 82.6 TONS
MODEL: YCWL0084HE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

105
YCWL
50 TO 90
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0094SE46 85.9 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.2 / 4.7
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 21.5 / 6.3
Flow Rate (gpm) 205.8 Flow Rate (gpm) 250.8 Physical Data
Pressure Drop (ft.) 13.2 Pressure Drop (ft.) 11.5 Rigging Wt. (lbs.) 5023
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 5338
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 37.3 Water Vol. (gal) 85.0

Electrical Data
Circuit 1 2 3 4
Compressor RLA 42.9/42.9 30.4/30.4
Compressor Start Current (LRA) 250.0/250.0 225.0/225.0

Single Point
Min. Circuit Ampacity 157.0
Min. Non-Fused Disconnect (Amps) 200.0
Min. Circuit Breaker (Amps) 175.0
Max. Circuit Breaker (Amps) 200.0
Wire Range (Lug Size) * (1)#10 - 300
Grounding Wire Lug Size
Total Amps 146.6 Operating Condition Electrical Data
Inrush (PW) Amps 250.0 Compressor kW 63.8
Starter Type Across the Line Total kW 63.8

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 85.9 85.0 95.0 63.8 16.2 / 4.7
72.6 66.6 76.0 83.6 41.6 19.2 / 5.6
50.0 47.8 67.2 72.5 25.4 22.5 / 6.6
22.6 21.9 65.0 67.4 11.0 23.8 / 7.0

106 JOHNSON CONTROLS


X
NOTES: 125 15/16"
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO 21 3/8" 101 13/16"
SERVICE THE UNITS ARE AS FOLLOWS: Y
REAR TO WALL: 20" 25 7/8" 50"
FRONT TO WALL: 36"
TOP: 43" 1,242 (LB) 1,242 (LB) ORIGIN

jOHNSON CONTROLS
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN) 9 7/8"
2. WEIGHTS (LB):SHIPPING - 5,023, OPERATING - 5,338.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.9", Y= 10.7"
9 7/8"
1,427 (LB) 5/8" MOUNTING HOLES (TYP) 1,427 (LB)

50"
34" 9"
1"
33 13/16"
OVERALL WIDTH
17 11/16"
12 1/4" TO RIGGING HOLES 23 1/2" POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH

6 5/8" EVAP
LIQUID INLET 6 5/8" EVAP
29" VICTAULIC LIQUID OUTLET
1 1/2" RIGGING HOLES
CONNECTION VICTAULIC
72 1/4" CONNECTION

4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
7 1/8"
CONNECTION
4 1/2" CONDENSER
35 1/2" 32"
WATER INLET
VICTAULIC
CONNECTION
8 1/4"

85" 8 3/8"
14 1/2" 11 3/4" TO COOLER CONN
5 1/8" 107 3/4"
29"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0094SE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 85.9 TONS
MODEL: YCWL0094SE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

107
YCWL
50 TO 90
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0094HE46 89.4 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.9 / 5.0
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 21.9 / 6.4
Flow Rate (gpm) 214.3 Flow Rate (gpm) 258.5 Physical Data
Pressure Drop (ft.) 8.7 Pressure Drop (ft.) 5.4 Rigging Wt. (lbs.) 5773
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 6412
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 59.8 Water Vol. (gal) 44.1

Electrical Data
Circuit 1 2 3 4
Compressor RLA 42.9/42.9 30.4/30.4
Compressor Start Current (LRA) 250.0/250.0 225.0/225.0

Single Point
Min. Circuit Ampacity 157.0
Min. Non-Fused Disconnect (Amps) 200.0
Min. Circuit Breaker (Amps) 175.0
Max. Circuit Breaker (Amps) 200.0
Wire Range (Lug Size) * (1)#10 - 300
Grounding Wire Lug Size
Total Amps 146.6 Operating Condition Electrical Data
Inrush (PW) Amps 250.0 Compressor kW 63.5
Starter Type Across the Line Total kW 63.5

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 89.4 85.0 95.0 63.5 16.9 / 5.0
72.6 68.5 75.6 83.1 41.1 20.0 / 5.9
50.0 47.9 66.4 71.6 25.1 23.0 / 6.7
22.6 21.9 65.0 67.3 10.9 24.1 / 7.1

108 JOHNSON CONTROLS


121 3/4"
NOTES: X
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO 17 3/16" 101 13/16"
SERVICE THE UNITS ARE AS FOLLOWS:
27 1/2" 50" Y
REAR TO WALL: 20"
FRONT TO WALL: 36" 1,510 (LB) 1,510 (LB) ORIGIN
TOP: 43" 9 7/8"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,773, OPERATING - 6,412.

jOHNSON CONTROLS
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.6"

1,696 (LB) 1,696 (LB) 9 7/8"

5/8" MOUNTING HOLES (TYP)


50"
34"
1"
9"

33 7/8"
OVERALL WIDTH
17 11/16" 23 1/2" POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
12 3/4" TO RIGGING HOLES

1 1/2" RIGGING HOLES


8 5/8" EVAP
29" 8 5/8" EVAP LIQUID OUTLET
5 9/16" CONDENSER LIQUID INLET VICTAULIC
WATER OUTLET VICTAULIC CONNECTION
VICTAULIC CONNECTION
CONNECTION 76 5/8"

5 9/16" CONDENSER
42"
WATER INLET
35 1/4"
VICTAULIC
CONNECTION 8 5/8"

8 1/2"

15" 16" TO COOLER CONN 83" 9 3/8"

30" 5 3/16" 108 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0094HE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 89.4 TONS
MODEL: YCWL0094HE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

109
YCWL
50 TO 90
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0104SE46 92.8 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.2 / 4.7
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 20.9 / 6.1
Flow Rate (gpm) 222.5 Flow Rate (gpm) 271.0 Physical Data
Pressure Drop (ft.) 11.0 Pressure Drop (ft.) 13.1 Rigging Wt. (lbs.) 5157
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 5472
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 37.3 Water Vol. (gal) 26.9

Electrical Data
Circuit 1 2 3 4
Compressor RLA 42.9/42.9 42.9/42.9
Compressor Start Current (LRA) 250.0/250.0 250.0/250.0

Single Point
Min. Circuit Ampacity 182.0
Min. Non-Fused Disconnect (Amps) 200.0
Min. Circuit Breaker (Amps) 200.0
Max. Circuit Breaker (Amps) 225.0
Wire Range (Lug Size) * (1)#4 - 500
Grounding Wire Lug Size
Total Amps 171.6 Operating Condition Electrical Data
Inrush (PW) Amps 250.0 Compressor kW 68.9
Starter Type Across the Line Total kW 68.9

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 92.8 85.0 95.0 68.9 16.2 / 4.7
75.0 72.6 76.3 83.9 46.5 18.7 / 5.5
50.0 50.9 66.9 72.2 27.6 22.2 / 6.5
25.0 24.9 65.0 67.5 13.2 22.6 / 6.6

110 JOHNSON CONTROLS


124 1/8" X
NOTES: 19 9/16" 101 13/16"
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS: 25 7/8" 50" Y
ORIGIN
REAR TO WALL: 20" 1,260 (LB) 1,260 (LB)
FRONT TO WALL: 36"
TOP: 43" 9 7/8"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,157, OPERATING - 5,472.

jOHNSON CONTROLS
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.8"
1,476 (LB) 1,476 (LB) 9 7/8"

5/8" MOUNTING HOLES (TYP)


50"
34"

1"
33 13/16" 9"
OVERALL WIDTH

17 11/16" 23 1/2"
POWER ENTRY IS ON TOP OF PANEL
12 1/4" TO RIGGING HOLES 12" WIDE X 6" HIGH

6 5/8" EVAP
LIQUID OUTLET
6 5/8" EVAP
VICTAULIC
29" LIQUID INLET
CONNECTION
1 1/2" RIGGING HOLES VICTAULIC
CONNECTION
71 3/4"
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION 7 1/8"
38 1/2"
4 1/2" CONDENSER 32"
WATER INLET
VICTAULIC
CONNECTION
8 1/4"

14 1/2" 15 1/2" TO COOLER CONN


29" 85" 8 3/8"
5 1/8" 107 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0104SE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 92.8 TONS
MODEL: YCWL0104SE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

111
YCWL
91 TO 130
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0118SE46 110.5 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 15.6 / 4.6
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 23.5 / 6.9
Flow Rate (gpm) 264.8 Flow Rate (gpm) 324.5 Physical Data
Pressure Drop (ft.) 15.1 Pressure Drop (ft.) 17.8 Rigging Wt. (lbs.) 4983
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 5298
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 37.3 Water Vol. (gal) 26.9

Electrical Data
Circuit 1 2 3 4
Compressor RLA 54.5/54.5 42.9/42.9
Compressor Start Current (LRA) 310.0/310.0 250.0/250.0

Single Point
Min. Circuit Ampacity 208.4
Min. Non-Fused Disconnect (Amps) 250.0
Min. Circuit Breaker (Amps) 225.0
Max. Circuit Breaker (Amps) 310.0
Wire Range (Lug Size) * (1)#4 - 500
Grounding Wire Lug Size
Total Amps 194.8 Operating Condition Electrical Data
Inrush (PW) Amps 310.0 Compressor kW 84.9
Starter Type Across the Line Total kW 84.9

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 117.2 85.0 95.0 83.1 16.9 / 5.0
71.8 89.7 75.6 83.0 49.7 21.7 / 6.4
50.0 64.4 67.0 72.1 29.4 26.3 / 7.7
21.8 27.7 65.0 67.2 11.9 27.9 / 8.2

112 JOHNSON CONTROLS


124 1/8" X
NOTES: 19 9/16" 101 13/16"
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS: 25 7/8" 50" Y
ORIGIN
REAR TO WALL: 20" 1,236 (LB) 1,236 (LB)
FRONT TO WALL: 36"
TOP: 43" 9 7/8"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 4,983, OPERATING - 5,298.

jOHNSON CONTROLS
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.8"
1,413 (LB) 1,413 (LB) 9 7/8"

5/8" MOUNTING HOLES (TYP)


50"
34"

1"
33 13/16" 9"
OVERALL WIDTH

17 11/16" 23 1/2"
POWER ENTRY IS ON TOP OF PANEL
12 1/4" TO RIGGING HOLES 12" WIDE X 6" HIGH

6 5/8" EVAP
LIQUID OUTLET
6 5/8" EVAP
VICTAULIC
29" LIQUID INLET
CONNECTION
1 1/2" RIGGING HOLES VICTAULIC
CONNECTION
71 3/4"
4 1/2" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION 7 1/8"
38 1/2"
4 1/2" CONDENSER 32"
WATER INLET
VICTAULIC
CONNECTION
8 1/4"

14 1/2" 15 1/2" TO COOLER CONN


29" 85" 8 3/8"
5 1/8" 107 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0118SE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 110.5 TONS
MODEL: YCWL0118SE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

113
YCWL
91 TO 130
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0118HE46 117.2 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.9 / 5.0
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 24.7 / 7.2
Flow Rate (gpm) 280.8 Flow Rate (gpm) 334.0 Physical Data
Pressure Drop (ft.) 14.1 Pressure Drop (ft.) 8.4 Rigging Wt. (lbs.) 5733
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 6372
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 59.8 Water Vol. (gal) 44.1

Electrical Data
Circuit 1 2 3 4
Compressor RLA 54.5/54.5 42.9/42.9
Compressor Start Current (LRA) 310.0/310.0 250.0/250.0

Single Point
Min. Circuit Ampacity 208.4
Min. Non-Fused Disconnect (Amps) 250.0
Min. Circuit Breaker (Amps) 225.0
Max. Circuit Breaker (Amps) 310.0
Wire Range (Lug Size) * (1)#4 - 500
Grounding Wire Lug Size
Total Amps 194.8 Operating Condition Electrical Data
Inrush (PW) Amps 310.0 Compressor kW 83.1
Starter Type Across the Line Total kW 83.1

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 117.2 85.0 95.0 83.1 16.9 / 5.0
71.8 89.7 75.6 83.0 49.7 21.7 / 6.4
50.0 64.4 67.0 72.1 29.4 26.3 / 7.7
21.8 27.7 65.0 67.2 11.9 27.9 / 8.2

114 JOHNSON CONTROLS


123 5/16"
NOTES: X
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO 18 3/4" 101 13/16"
SERVICE THE UNITS ARE AS FOLLOWS:
25 7/8" 50" Y
REAR TO WALL: 20"
FRONT TO WALL: 36" 1,505 (LB) 1,505 (LB) ORIGIN
TOP: 43" 9 7/8"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 5,733, OPERATING - 6,372.

jOHNSON CONTROLS
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.7"

1,681 (LB) 1,681 (LB) 9 7/8"

5/8" MOUNTING HOLES (TYP)


50"
34"
1"
9"

33 7/8"
OVERALL WIDTH
17 11/16" 23 1/2" POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
12 3/4" TO RIGGING HOLES

1 1/2" RIGGING HOLES


8 5/8" EVAP
29" 8 5/8" EVAP LIQUID OUTLET
5 9/16" CONDENSER LIQUID INLET VICTAULIC
WATER OUTLET VICTAULIC CONNECTION
VICTAULIC CONNECTION
CONNECTION 76 5/8"

5 9/16" CONDENSER
42"
WATER INLET
35 1/4"
VICTAULIC
CONNECTION 8 5/8"

8 1/2"

15" 16" TO COOLER CONN 83" 9 3/8"

30" 5 3/16" 108 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0118HE46 Contractor : UNIT Dwg. Lev. : 10/07 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 117.2 TONS
MODEL: YCWL0118HE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

115
YCWL
91 TO 130
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0132SE46 127.4 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.1 / 4.7
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 23.4 / 6.9
Flow Rate (gpm) 305.3 Flow Rate (gpm) 372.0 Physical Data
Pressure Drop (ft.) 16.5 Pressure Drop (ft.) 14.8 Rigging Wt. (lbs.) 5463
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 6027
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 59.8 Water Vol. (gal) 35.2

Electrical Data
Circuit 1 2 3 4
Compressor RLA 54.5/54.5 54.5/54.5
Compressor Start Current (LRA) 310.0/310.0 310.0/310.0

Single Point
Min. Circuit Ampacity 231.6
Min. Non-Fused Disconnect (Amps) 400.0
Min. Circuit Breaker (Amps) 310.0
Max. Circuit Breaker (Amps) 310.0
Wire Range (Lug Size) * (1)#4 - 500
Grounding Wire Lug Size
Total Amps 218.0 Operating Condition Electrical Data
Inrush (PW) Amps 310.0 Compressor kW 94.7
Starter Type Across the Line Total kW 94.7

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 127.4 85.0 95.0 94.7 16.1 / 4.7
75.0 100.2 76.5 84.1 61.0 19.7 / 5.8
50.0 70.8 67.2 72.4 33.7 25.2 / 7.4
25.0 34.7 65.0 67.5 15.9 26.2 / 7.7

116 JOHNSON CONTROLS


123 5/16"

18 3/4" 101 13/16"


NOTES: X
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO 25 7/8" 50"
SERVICE THE UNITS ARE AS FOLLOWS:
REAR TO WALL: 20" 1,415 (LB) 1,415 (LB) ORIGIN Y
FRONT TO WALL: 36"
9 7/8"
TOP: 43"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)

jOHNSON CONTROLS
2. WEIGHTS (LB):SHIPPING - 5,463, OPERATING - 6,027.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 50.8", Y= 10.7" 9 7/8"
1,598 (LB) 1,598 (LB)
5/8" MOUNTING HOLES (TYP)

50"
34"
1"
9"
33 13/16"
OVERALL WIDTH
17 11/16"
POWER ENTRY IS ON TOP OF PANEL
23 1/2" 12" WIDE X 6" HIGH
12 3/4" TO RIGGING HOLES

8 5/8" EVAP
8 5/8" EVAP LIQUID OUTLET
29" LIQUID INLET VICTAULIC
VICTAULIC CONNECTION
1 1/2" RIGGING HOLES CONNECTION

74 1/2"
5 9/16" CONDENSER
WATER OUTLET
VICTAULIC
CONNECTION 8 1/8"
40"
5 9/16" CONDENSER 33 1/4"
WATER INLET
VICTAULIC
CONNECTION 7 3/4"

14 1/2" 16" TO COOLER CONN 83" 9 3/8"


29" 5 1/4" 108 1/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0132SE46 Contractor : UNIT Dwg. Lev. : 10/07 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 127.4 TONS
MODEL: YCWL0132SE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

117
YCWL
91 TO 130
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0157SE46 144.0 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.5 / 4.8
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 23.5 / 6.9
Flow Rate (gpm) 345.1 Flow Rate (gpm) 419.0 Physical Data
Pressure Drop (ft.) 17.3 Pressure Drop (ft.) 15.3 Rigging Wt. (lbs.) 6163
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 6891
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 57.6 Water Vol. (gal) 52.4

Electrical Data
Circuit 1 2 3 4
Compressor RLA 54.5/54.5 54.5/54.5
Compressor Start Current (LRA) 310.0/310.0 310.0/310.0

Single Point
Min. Circuit Ampacity 231.6
Min. Non-Fused Disconnect (Amps) 400.0
Min. Circuit Breaker (Amps) 250.0
Max. Circuit Breaker (Amps) 250.0
Wire Range (Lug Size) * () -
Grounding Wire Lug Size
Total Amps 218.0 Operating Condition Electrical Data
Inrush (PW) Amps 310.0 Compressor kW 104.7
Starter Type Across the Line Total kW 104.7

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 144.0 85.0 95.0 104.7 16.5 / 4.8
75.0 113.5 76.5 84.2 68.1 20.0 / 5.9
50.0 80.2 67.3 72.5 38.0 25.3 / 7.4
25.0 39.3 65.0 67.5 17.9 26.3 / 7.7

118 JOHNSON CONTROLS


MODEL: YCWL0157SE46
AHRI CAPACITY 144.0 TONS

YCWL
131 TO 200

jOHNSON CONTROLS 119


Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0157HE46 148.5 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 17.1 / 5.0
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 24.2 / 7.1
Flow Rate (gpm) 355.9 Flow Rate (gpm) 422.4 Physical Data
Pressure Drop (ft.) 11.6 Pressure Drop (ft.) 12.4 Rigging Wt. (lbs.) 6863
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 7807
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 77.0 Water Vol. (gal) 59.1

Electrical Data
Circuit 1 2 3 4
Compressor RLA 54.5/54.5 54.5/54.5
Compressor Start Current (LRA) 310.0/310.0 310.0/310.0

Single Point
Min. Circuit Ampacity 231.6
Min. Non-Fused Disconnect (Amps) 400.0
Min. Circuit Breaker (Amps) 250.0
Max. Circuit Breaker (Amps) 250.0
Wire Range (Lug Size) * () -
Grounding Wire Lug Size
Total Amps 218.0 Operating Condition Electrical Data
Inrush (PW) Amps 310.0 Compressor kW 104.3
Starter Type Across the Line Total kW 104.3

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 148.5 85.0 95.0 104.3 17.1 / 5.0
75.0 116.8 76.5 84.1 67.2 20.9 / 6.1
50.0 81.4 66.9 72.1 37.7 25.9 / 7.6
25.0 39.9 65.0 67.5 17.8 26.9 / 7.9

120 JOHNSON CONTROLS


MODEL: YCWL0157HE46
AHRI CAPACITY 148.5 TONS

YCWL
131 TO 200

jOHNSON CONTROLS 121


Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0177SE46 166.6 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 17.1 / 5.0
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 25.4 / 7.4
Flow Rate (gpm) 399.3 Flow Rate (gpm) 477.9 Physical Data
Pressure Drop (ft.) 14.2 Pressure Drop (ft.) 15.3 Rigging Wt. (lbs.) 7318
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 8262
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 77.0 Water Vol. (gal) 59.1

Electrical Data
Circuit 1 2 3 4
Compressor RLA 49.2/49.2/49.2 49.2/49.2
Compressor Start Current (LRA) 242.0/242.0/242.0 242.0/242.0

Single Point
Min. Circuit Ampacity 258.0
Min. Non-Fused Disconnect (Amps) 400.0
Min. Circuit Breaker (Amps) 300.0
Max. Circuit Breaker (Amps) 300.0
Wire Range (Lug Size) * (1)#4 - 500
Grounding Wire Lug Size
Total Amps 246.0 Operating Condition Electrical Data
Inrush (PW) Amps 242.0 Compressor kW 117.1
Starter Type Across the Line Total kW 117.1

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 166.6 85.0 95.0 117.1 17.1 / 5.0
80.0 141.0 78.8 87.1 80.8 20.9 / 6.1
60.0 108.3 71.0 77.2 52.8 24.6 / 7.2
40.0 73.3 65.0 69.1 31.0 28.4 / 8.3
20.0 35.6 65.0 67.0 15.2 28.2 / 8.3

122 JOHNSON CONTROLS


143 7/16"
X
NOTES: 14 7/8" 125 13/16"
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS: 37 5/8" 50" Y
REAR TO WALL: 20"
FRONT TO WALL: 36" 1,902 (LB) 1,902 (LB) ORIGIN
TOP: 43" 10 3/8"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)

jOHNSON CONTROLS
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 7,318, OPERATING - 8,262.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 62.9", Y= 11.7"

2,229 (LB) 10 3/8"


2,229 (LB)
5/8" MOUNTING HOLES (TYP)
50"

34"
1"
9"
34 13/16"
OVERALL WIDTH

17 11/16" 23 1/2" POWER ENTRY IS ON TOP OF PANEL


12" WIDE X 6" HIGH
17 3/4" TO RIGGING HOLES

1 1/2" RIGGING HOLES


8 5/8" EVAP
29" 8 5/8" EVAP LIQUID OUTLET
LIQUID INLET VICTAULIC
5 9/16" CONDENSER VICTAULIC CONNECTION
WATER OUTLET CONNECTION
VICTAULIC
CONNECTION 77 1/2"

5 9/16" CONDENSER
41" WATER INLET 36 1/4"
VICTAULIC
CONNECTION 7 1/8"

9"

102" 11 7/8"
15" 16" TO COOLER CONN
30" 5 3/16" 132 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0177SE46 Contractor : UNIT Dwg. Lev. : 10/07 A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 166.6 TONS
MODEL: YCWL0177SE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

123
YCWL
131 TO 200
Water Cooled Scroll Chiller
Performance Specification
Model No. Capacity (Tons) Volts/Ph/Hz Refrigerant
YCWL0198SE46 198.4 460/3/60 R410A

Evaporator Data Condenser Data Performance Data


EWT (°F) 54.0 EWT (°F) 85.0 EER / COP 16.8 / 4.9
LWT (°F) 44.0 LWT (°F) 95.0 EER IPLV/COP IPLV 24.8 / 7.3
Flow Rate (gpm) 475.6 Flow Rate (gpm) 566.2 Physical Data
Pressure Drop (ft.) 19.6 Pressure Drop (ft.) 20.4 Rigging Wt. (lbs.) 7673
Fluid Water Fluid Water 0.0 Operating Wt. (lbs.) 8617
Fouling Factor 0.00010 Fouling Factor 0.00025
Water Vol. (gal) 77.0 Water Vol. (gal) 59.1

Electrical Data
Circuit 1 2 3 4
Compressor RLA 49.2/49.2/49.2 49.2/49.2/49.2
Compressor Start Current (LRA) 242.0/242.0/242.0 242.0/242.0/242.0

Single Point
Min. Circuit Ampacity 308.0
Min. Non-Fused Disconnect (Amps) 400.0
Min. Circuit Breaker (Amps) 350.0
Max. Circuit Breaker (Amps) 350.0
Wire Range (Lug Size) * (1)#4 - 500
Grounding Wire Lug Size
Total Amps 295.2 Operating Condition Electrical Data
Inrush (PW) Amps 242.0 Compressor kW 141.9
Starter Type Across the Line Total kW 141.9

RATED AND CERTIFIED IN ACCORDANCE WITH AHRI STANDARD 550/590.


Notes:
* Use Copper Conductors only

Part Load Rating Data


Load % Capacity (Tons) Cond. EWT (°F) Cond. LWT (°F) Compressor kW Unit Efficiency
100.0 198.4 85.0 95.0 141.9 16.8 / 4.9
83.3 172.0 79.7 88.1 106.6 19.4 / 5.7
66.7 144.2 74.1 81.0 76.0 22.8 / 6.7
50.0 110.2 67.2 72.4 50.6 26.1 / 7.6
33.3 73.0 65.0 68.4 31.5 27.8 / 8.1
16.7 35.8 65.0 66.7 15.5 27.7 / 8.1

124 JOHNSON CONTROLS


143 7/16"
X
NOTES: 14 7/8" 125 13/16"
1. CLEARANCES - RECOMMENDED MINIMUM CLEARANCES TO
SERVICE THE UNITS ARE AS FOLLOWS: 37 5/8" 50" Y
REAR TO WALL: 20"
FRONT TO WALL: 36" 1,938 (LB) 1,938 (LB) ORIGIN
TOP: 43" 10 3/8"
TUBE CLEARANCE AND REMOVAL, 4 COMPR UNITS: 132" (NOT SHOWN)
TUBE CLEARANCE AND REMOVAL, 6 COMPR UNITS: 156" (NOT SHOWN)
2. WEIGHTS (LB):SHIPPING - 7,673, OPERATING - 8,617.
3. EACH RELIEF VALVE SHOULD BE PIPED IN A MANNER CONSISTENT WITH

jOHNSON CONTROLS
ASHRAE / ANSI 15 AND ALL LOCAL CODE REQUIREMENTS SO THAT IF THE
VALVE IS ACTIVATED THE RELEASE OF HIGH PRESSURE GAS AND LIQUID
CANNOT BE A DANGER OR CAUSE INJURY. REFER TO FORM 201.26.EG1
4. CENTER OF GRAVITY FROM ORIGIN: X= 62.9", Y= 11.7"

2,371 (LB) 10 3/8"


2,371 (LB)
5/8" MOUNTING HOLES (TYP)
50"

34"
1"
9"
34 13/16"
OVERALL WIDTH

17 11/16" 23 1/2"
POWER ENTRY IS ON TOP OF PANEL
12" WIDE X 6" HIGH
17 3/4" TO RIGGING HOLES

1 1/2" RIGGING HOLES


8 5/8" EVAP
29" 8 5/8" EVAP LIQUID OUTLET
LIQUID INLET VICTAULIC
5 9/16" CONDENSER VICTAULIC CONNECTION
WATER OUTLET CONNECTION
VICTAULIC
CONNECTION 77 1/2"

5 9/16" CONDENSER
41" WATER INLET 36 1/4"
VICTAULIC
CONNECTION 7 1/8"

9"

102" 11 7/8"
15" 16" TO COOLER CONN

30" 5 3/16" 132 3/4"

Project Name : Contractors Guide Sold To : Date :


PRODUCT DRAWING Location : Cust Purch Order# : Rev. Date :
WATER-COOLED SCROLL CHILLER Engineer : York Contract# : Form : 201.26-EG1
MODEL: YCWL0198SE46 Contractor : UNIT Dwg. Lev. : 10/07
A JOHNSON CONTROLS COMPANY
AHRI CAPACITY 198.4 TONS
MODEL: YCWL0198SE46

NOT FOR CONSTRUCTION For : TAG: Dwg. Scale : NTS

125
YCWL
131 TO 200
126 JOHNSON CONTROLS
Printed on recycled paper

Form: 050.05-TD1 (313) Supersedes: 050.05-TD1 (309)


© 2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA
www.johnsoncontrols.com