GRINNELL G-FIRE
Figure 40-5 Strap (Pipe Outlet)
Americas Only
General Technical
Description Data
The GRINNELL G-FIRE Figure 40-5 Approvals
Strap is an economical alternative to UL and ULC Listed
welded pipe outlets on steel pipe. The FM Approved
Figure 40-5 Strap can be used with full Sizes
lengths of pipe and eliminates welding, Pipe Run: 1-1/4 to 2-1/2 inch (DN32 to
decreasing waste and installation time. DN65)
The Figure 40-5 Strap can be used in Outlet Thread: 1/2 to 1 Inch NPT
wet, dry pipe, and deluge systems and
is rated to a maximum pressure of 175 Housing
psi (12 bar). Ductile iron conforming to ASTM A536,
Grade 65-45-12
NOTICE Protective Coatings
The Figure 40-5 Strap described herein Clear rust inhibitive coating
must be installed and maintained in Bolts/Nuts
compliance with this document, and • ANSI
with the applicable standards of the The U-bolt is made from carbon steel
NATIONAL FIRE PROTECTION ASSO- conforming to ASTM A307 Grade A and
CIATION (NFPA), in addition to the zinc-electroplated conforming to ASTM
standards of any authorities having B633. For fire protection pressure rating,
jurisdiction. Failure to do so may impair • The flange nuts are made from carbon
listing and approval information, contact
your TYCO representative.
the performance of this device. steel conforming to ASTM A563 Grade
Owners are responsible for maintaining A, and zinc electroplated per ASTM
their fire protection system and devices B633. Fitting Size Equivalent Ft. Length
in proper operating condition. Contact • Stainless Steel U-Bolts and Nuts are ANSI Inches (1 inch Sch. 40 pipe)
the installing contractor or product available upon request.
manufacturer with any questions. 1-1/4 x 1 8
Gasket
Refer to data sheet TFP1895 for additional 1-1/2 x 1
6
gasket information. 2x1

Care and
2-1/2 x 1 4

Hazen Williams coefficient = 120


Maintenance The 1 inch outlets can be used
The GRINNELL G-FIRE Figure 40-5 with a nipple leading directly to a
Strap must be maintained in accor- sprinkler. These fittings should be
dance with this section. used for hydraulically calculated
Before closing a fire protection system systems only.
main control valve for maintenance
work on the fire protection system TABLE A
that it controls, obtain permission to FIGURE 40-5 STRAP
shut down the affected fire protection FRICTION LOSS AS
system from the proper authorities EQUIVALENT PIPE LENGTH
and notify all personnel who may be (1 INCH OUTLETS ONLY)
affected by this decision.
After placing a fire protection system
in service, notify the proper authorities
and advise those responsible for moni-
IMPORTANT toring proprietary and/or central station
Refer to Technical Data Sheet alarms.
TFP2300 for warnings pertaining to
regulatory and health information.

Page 1 of 2 AUGUST 2018 TFP1720


TFP1720
Page 2 of 2

The owner is responsible for the


Nominal Nominal Dimensions Approx. inspection, testing, and maintenance of
O.D. Outlet Inches (mm)
Run Size Weight their fire protection system and devices
Inches Size
ANSI Inches Lbs. in compliance with this document, as
(mm) NPT A B C D
(DN) (kg)
well as with the applicable standards
1/2 2.00 1.50 3.50 1.20 0.84 of the NATIONAL FIRE PROTECTION
(50,8) (38,1) (88,9) (30,5) (0,4) ASSOCIATION, for example, NFPA
1-1/4 1.660 3/4 2.00 1.50 3.50 1.20 0.88 25, in addition to the standards of any
(32) (42,4) (50,8) (38,1) (88,9) (30,5) (0,4) authority having jurisdiction. Contact
1 2.31 1.68 3.50 1.20 1.13 the installing contractor or product
(58,7) (42,7) (88,9) (30,5) (0,5) manufacturer with any questions. Any
1/2 2.12 1.62 3.50 1.32 0.84 impairments must be immediately
(53,8) (41,1) (88,9) (33,5) (0,4) corrected.
1-1/2 1.900 3/4 2.12 1.62 3.50 1.32 0.88
(40) (48,3) (53,8) (41,1) (88,9) (33,5) (0,4) Automatic sprinkler systems are rec-
2.43 1.80 3.50 1.32 1.13 ommended to be inspected, tested,
1 (61,7) (45,7) (88,9) (33,5) (0,5) and maintained by a qualified Inspec-
2.36 1.86 3.74 1.55 0.88 tion Service in accordance with local
1/2 (59,9) (47,2) (95,0) (39,4) (0,4) requirements and/or national codes.
2 2.375 2.36 1.86 3.74 1.55 0.95
(50) (60,3) 3/4 (59,9)
2.67
(47,2)
2.04
(95,0)
3.74
(39,4)
1.55
(0,4)
1.16
Limited
1 (67,8)
2.61
(51,8)
2.11
(95,0)
4.25
(39,4)
1.80
(0,5)
0.90
Warranty
1/2 (66,3) (53,6) (108,0) (45,7) (0,4) For warranty terms and conditions, visit
2-1/2 2.875 2.61 2.11 4.25 1.80 0.99 www.tyco-fire.com.
(65) (73,0) 3/4 (66,3) (53,6) (108,0) (45,7) (0,5)
1 2.92
(74,2)
2.29
(58,2)
4.25
(108,0)
1.80
(45,7)
1.21
(0,5)
Ordering
Outlet Hole Size on Pipe is 1-3/16 inch (30,2 mm) diameter. Procedure
C GRINNELL Products are available glob-
1 ally through a network of distribution
centers. For the nearest distributor, visit
www.tyco-fire.com. When placing an
order, indicate the full product name.
2
Specify: G-FIRE Figure 40-5 Strap,
A Item Description (size), (quantity), P/N (specify):
B 1 Housing 1-1⁄4" x 1⁄2 NPT ������������������������������� STP1305ES
4 1-1⁄4" x 3⁄4 NPT ������������������������������� STP13075ES
2 Flanged Nut 1-1⁄4" x 1 NPT ����������������������������������� STP1310ES
3 Gasket 1-1⁄2" x 1⁄2 NPT ������������������������������� STP1505ES
1-1⁄2" x 3⁄4 NPT ����������������������������� STP15075ES
4 U-Bolt 1-1⁄2" x 1 NPT ����������������������������������� STP1510ES
3
2" x 1⁄2 NPT . . . . . . . . . . . . . . . . . . . STP2005ES
D 2" x 3⁄4 NPT . . . . . . . . . . . . . . . . . . STP20075ES
2" x 1 NPT . . . . . . . . . . . . . . . . . . . . . STP2010ES
2-1⁄2" x 1⁄2 NPT ������������������������������� STP2505ES
2-1⁄2" x 3⁄4 NPT ����������������������������� STP25075ES
FIGURE 1 2-1⁄2" x 1 NPT ����������������������������������� STP2510ES
FIGURE 40-5 STRAP (PIPE OUTLET)
NOMINAL DIMENSIONS

Pressure Rating
Nominal Pipe Sizes psi (bar)
Pipe Schedulea
ANSI Inches
UL ULC FM

1-1/4 x 1/2; 3/4; 1 175 175 175


10
1-1/2 x 1/2; 3/4; 1 (12) (12) (12)
2 x 1/2, 3/4; 1 175 175 175
2-1/2 x 1/2; 3/4; 1 40 (12) (12) (12)
NOTES
a. See Agency website for Listing/Approvals of other pipe specifications:
UL Website - see Online Certificate Directory, www.ul.com
FM Global Website - www.approvalguide.com

TABLE B
LISTED/APPROVED PRESSURE RATINGS

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association