SCHEDULE ‘A’

Technical details
GENERAL TECHNICAL PARTICULARS OF 400 kV/220 kV/132 kV/36 kV ISOLATORS
submitted by bidder
SR.No General Technical Parameter HCB
1 Minimum Turn Over 224 MINR (for FY 17)
2 Name of Manufacturer Siemens Ltd
3 Manufacturer's type designation 420kVHCB
4 Type Of isolator Horizontal Center Break
5 Highest system voltage (kV rms) 420kV
6 Rated Freq (Hz) 50 Hz
7 System Neutral Earthing Solidly earthed
8 No. of Phase (pole) Three
Within limits as per
9 IEC 62271-102
Temperature rise
10 Safe duration of overload
a 150% of rated current 5 mintues
b 120% of rated current 30 Minutes
9 Type of disconnect (AB) Horizontal center break
11 Rated normal current (Amps) 3150 Amps
12 Rated short time current withstand capacity of Main contacts for 3 seconds 40kA
13 Rated Peak current (kA p) of Main contacts 100kA peak
14 Basic insulation level
i) Lightning impulse withstand voltage: (kV peak
a To earth 1425 kV peak
b Across isolating distance 1665 kV peak
Rated power frequency
ii)
withstand voltage (kV rms)
a To earth 520kV rms
b Across isolating distance 610 kV rms
15 Minimum Creepage distance 10500 mm
16 Rated Mech. Term load
Within the limits of values
a Across load (kg) as specified in IEC 62271-
102.
Within the limits of values
b Straight load (kg) as specified in IEC 62271-
102.
17 Minimum Clearances (mm)
a Phase to phase 3500
b Phase to earth 4000
c Height of lowest live point above ground level (mm) 8200
d Phase to phase spacing(mm) for installation 7000
18 Derating factor for specified site condition 1
19 OPERATING MECHANISM
20 Motor details:
a Make REMI/ELCEN/CGL
415V AC, 3 phase 50Hz,
b 373W, Direct online
Operating voltage, type & rated power & Starter starting
c Class of insulation Class F
d Temperature rise Class B
21 OPERATING MECHANISM BOX (Main Switch)
22 Cubicle sheet/gauge thickness Aluminum sheet/3 mm
23 Rain hood – Material details Aluminum sheet/3 mm
24 Ingress Protection class IP67-MOM/IP 67-BOM
25 Auxiliary switch details
a Make MANI
b No. of contacts 8NO+8NC+2MBB
c Capacity 220V DC
d DC breaking capacity & time constant 2A & 20ms
26 OPERATING MECHANISM BOX (Earth Switch)
27 Cubicle sheet/gauge thickness Aluminum sheet/3 mm
28 Rain hood – Material details Aluminum sheet/3 mm
29 Ingress Protection class IP67-MOM/IP 67-BOM
30 Metal & cross section Area of moving Blade (Main Switch) 2000 sq.mm
31 Metal & cross section Area of moving Blade (Earth Switch) 892.61 sq.mm
Minimum no of operations the isolator should make without deterioration of
32
contact 1000
33 Insulator base plate material details MS
34 Required Document submitted in physical/Electronic form Yes
35 Whether Performance certificate along with purchase order enclosed Yes
36 Whether in house Testing Laboratory NABL accredited No
Whether facility for carrying out Temperature rise test available at
37
manufacturer’s works. Yes
Whether required test set up for carrying out Lightning Impulse test available
38
at manufacturer’s works. No
Whether required test set up for Composite error test available manufacturer’s
39
works. Not Applicable
40 Type test report enclosed (Conducted within last 5 years)