iACCL

AUTOMATIC CHANGEOVER
WITH CURRENT LIMITER

iACCL M600

“Seamless, uninterrupted
changeover between power
sources”

Sequential time- undervoltage/ separate control for Inverse time


delayed switching overvoltage protection power/lighting load* tripping curve

www.elmeasure.com
Why Elmeasure iACCl ?
iACCL is a smart programmable device that is compatible to limit and allocate power based on requirements.
In a conventional approach, manual source transfer could lead to the disruption of key functions in expensive equipment.
While iACCL overcomes the problem by automatic switching of mains supply to standby generator during mains failure.
Also, power is automatically switched off for 5 seconds and reinstates automatically during overload conditions.
iACCL standouts with its ability to set parameters on site such as a programmable number of tripping cycles, current, over
voltage and under voltage protection. Also, single phase iACCL* is built with a separate control for power and lighting load
to reduce wiring cost.

30sA
Intelligent Tripping
iACCL operates on the principle of an inverse

SET AMPS
curve with continuous monitoring of phase
current and provides a faster trip time for high
overload conditions.
sA
sT sT
SET TIME

iACCL Operation:
Availability of mains supply:
During the availability of mains supply, the device will operate the
load using mains supply.

Power outage/main supply failure:


The device will automatically detect the mains failure and initiates
the changeover to the standby generator with a delay of 5 to 30s.
The transfer delay is provided to avoid abrupt loading of a generator.
Also, the current limiting feature will ensure the load is
disconnected, when it is connected beyond the preset limit. A
programmable setting of 1 to 10 cycles is provided to turn off non-
essential loads during generator operation.

Mains supply restored:


On reinstating mains supply, the load is automatically transferred
with a delay of 5s to a mains supply.
Salient Features

1 Operates with single phase and three phase supply.

On-Site current programmability based on loads for


2 both mains and generator.

3 Load protection from over-voltage and under-voltage.

Field configurable overcurrent setting and tripping


4 for mains supply and generator.

Protection against neutral current flow beyond the


5 threshold.

Individual phase overload monitoring in 3 phase


6 iACCL.

Sequential time-delayed switching to avoid sudden


7 overloading of the generator.

Microcontroller based automatic source


8 changeover with neutral isolation.

Inbuilt display and measurement of I, V, F and Kwh


9 on the generator side and mains side for iACCL M600

Reduced wiring cost as single phase iACCL has


10 seperate control for power and lighting load

Applications

Commercial centres Airports & Railways Medical Facilities Banking & Finance Infrastructure &
Telecommunications.
iACCL

AUTOMATIC CHANGEOVER
WITH CURRENT LIMITER
FOR A SEAMLESS, UNINTERRUPTED CHANGEOVER
BETWEEN POWER SOURCES!

Features : Mechanical Specification :

Single Phase

Dimension Bezel: 90 x 72 mm Dimension Bezel: 96 x 96 mm

90 mm

96mm
72mm 67mm

Three Phase

144 mm
/ 7.5 mm

15 mm

144 mm 127 mm
105 mm

DG Phase selection - Programmable


15 mm

EB healthy selection - Programmable 124 mm


1 mm

40A to 63A

Unique Features :

218mm
195mm

163mm

Inbuilt display and measurement of A, V, F & kWh on the


generator side and mains side for iACCL M600
305. mm

310. mm
285mm
310mm

265mm
183. mm

186. mm
198mm

10mm
5 mm

operations. 10 mm
238mm
5mm

iACCl M100 Single Phase.

elmeasure.com
Datasheet

M400 M100 M300 M300 M300 M600 M600 M600


ELECTRICAL CHARACTERISTICS
Rated Current 25/32A 25/32A 40-63A 80A 100-125A 40-63A 80A 100-125A
No. of Poles 1P+N 1P+N+1 3P+N
Power Load

Rated Operating Voltage 240VAC 415/240VAC


Rated Frequency 50Hz
Time Duration Transfer: 5-30s Programmable, Restore : 5s
Utilization Category AC3 AC1 (Tripping based on AC3)
Protection Class IP 20
Duty Uninterrupted
Cycle time 6 Sec to 150 Sec, No. of Cycles 5 to 10 (default 5 Cycles)
Accuracy Class 1
PROGRAMMING FEATURES
Baud rate
Parity
Device id
Password
Energy Selection
DG under voltage
Parameters DG over voltage
DG Maximum Current Limit
EB Maximum Current Limit EB Maximum Current Limit
DG Start time
Cycle time
No. of Cycles 1 to 10
DG Output selection EB and DG Output selection
METERING PARAMETERS
EB Source Current, Voltage, (PF, W, Wh optional)
DG Source Current, Voltage, PF, W, Wh
COMMUNICATION
Device ID & Parity 1 to 247 & Odd, Even, None (Prefered Even)
Protocol & Interface Modbus. RTU & RS 485
Baud rate 4800 bps to 19200 bps (Preferred 9600 bps)
Isolation 2000 volts AC isolation for 1 minute between communication & other circuits
DISPLAY
Display type LED 1 row
Instantaneous Digits 4
Integrated Digits 4 4 6
FAULT TRIPPING
EB Source Over Voltage Over Current, Under / Over Voltage
Phase Missing
DG Source Under / Over Voltage, Over Current
NA Phase Missing
MECHANICAL CHARACTERISTICS
Mounting (Vertical) Din Rail Surface Mounting Surface Mounting
Outline Dimension
90X72X67 90X90X75 144X144 182X217 265X210 144X144 182X217 265X210
(M400 R) (M 100 R) X120 mm X145 mm X166 mm X120 mm X145 mm X166 mm

Weight in kg 280 grams 350 grams 2.1 kg 4.5 kg 7 kg 2.1 kg 4.5 kg 7 kg

Torque 1 N-m 1 N-m 2 N-m 2 N-m 2.5 N-m 2 N-m 2 N-m 2.5 N-m

Wire gauge 11 AWG 11 AWG 6 AWG 4 AWG 1 AWG 6 AWG 4 AWG 1 AWG
STANDARDS
Compliance IEC 60947-6-1 IS / IEC 60898 - 1
USE ENVIRONMENT CHARACTERISTICS
Temperature Ambient: -5 to +550 C, Storage: -25 to +750 C, Operating: -10 to +550 C, Operating Humidity: 5 to 85% RH
Environmental Class B
Pollution degree 2

elmeasure.com
Registered Office Sales Offices
BENGALURU BENGALURU
PLOT NO.: 47-P, HARDWARE PARK, KIADB, #57, EBENEZER ENCLAVE, NORRIS ROAD, NEAR
HUVINAYAKANAHALLI, JALA HOBLI, YELAHANKA TALUK, NANJAPPA CIRCLE LANGFORD TOWN,
BENGALURU - 562 149. KARNATAKA INDIA BENGALURU - 560 025. KARANATAKA, INDIA

COIMBATORE
Manufacturing Units # 150, RA J ILLAM, NVM LAYOUT NEW SIDDHAPUDHUR
UNIT I COIMBATORE - 641 019. TAMIL NADU, INDIA
PLOT NO.: 47-P, HARDWARE PARK, KIADB,
HUVINAYAKANAHALLI, JALA HOBLI, YELAHANKA TALUK,
BENGALURU - 562 149. KARNATAKA, INDIA CHENNAI
# 945, GROUND FLOOR, MIG, FIRST MAIN ROAD, TNHB
COLONY, VELACHERY,
CHENNAI – 600 042. TAMIL NADU, INDIA
UNIT II
GOWTHAM GARDEN NO. 4, VEERAPANDI
COIMBATORE - 641 019. TAMIL NADU, INDIA
SECUNDERABAD
# 51, 1ST FLOOR, CHANDRAGIRI COLONY, NEAR RTA,
THRIMUGHERRY,
UNIT III SECUNDERABAD - 500 015. TELANGANA, INDIA
#764, 4TH PHASE, 707, YELAHANKA NEW TOWN,
BENGALURU - 560 064. KARNATAKA, INDIA
MUMBAI
# 101, MILLENIUM PLAZA BEHIND SAKINAKA
TELEPHONE EXCHANGE, ANDHERI - KURLA ROAD
SAKINAKA, ANDHERI (EAST)
MUMBAI - 400 072. MAHARASTRA, INDIA
Service Hotline:
support@elmeasure.com
DELHI
+91 639-1010-320 # G-10, G-11, GROUND FLOOR, BAISOYA COMPLEX,
NAYABANS, SECTOR-15,
Monday to Friday 8:00 am. to 5:00 pm. IST NOIDA – 201301. INDIA.

PC/IACCL/V0.2/1118

Vous aimerez peut-être aussi