M check list for high pressure fire misting system ( high pressure & booter& jockey pumps , deluge, wet )
1 change operation mode of 15 pumps to off mode
2 turn on manually pump# 1 , after pump pressure reach upto 140 bar ,check & fill column of P#1 which is the below mentioned
3 turn off pump#1 , reduce the pressure to 100 bar
4 turn on manually pump# 2 after pump pressure reach upto 140 bar ,check & fill column of P#2 which is the below mentioned
5 repeat the above mentioned for 13 remaining pumps
6 when pressure reach to 140 bar soleniod valve must be opened
7 to ensure that safety valve open at 160 bar , close manual valve or disconnect power of soleniod valve & pressure valve for increasing of pressure upto 160 bar
8 take pressure reading from control panel & mech pressure gauge , for flow rate read from control panel
9 change operation mode of 15 pumps to auto mode
10 make drain to reduce pressure under 20 bar , ensure that three pumps will start one by one each one second
11 after 15 second if the pressure not reach 100 bar other three pumps will start

S.N item P#1 P#2 P#3 P#4 P#5 P#6 P#7 P#8 P#9 P#10 P#11 P#12 P#13 P#14 P#15
set #1 set#2 set#3
1
check E/M consultants inspection requests ,
there arent comments
2 check pump frame
1 check for abnormal noise &vibration

2 check for any leakage from pump,connection &


fittings

3 check pump pressure ,it must reach upto 140 bar

4 check soleniod valve for overflow


5 safety valve / open at 160 bar

6 are safety valve drain connected to return line to


tank
7 manual air drain
8 non return valve
9 strainer
10 record running current value

11 check overload relay ( by reduce setting value) or


remove wire No. (96 or 95)

12 check phase failure relay remove wire No.( 11 or 14


)
13 check contactor ,termination no loss ,no heat
14 check indication lamps & selector switches

15 pump running signal sent from fogtech to fire


control panel

16 general fault signal sent from fogtech to fire control


panel
17 pressure valve#1/ open at 140 bar
18 pressure valve#2/ open at 140 bar
19 differential pressure switch 0.6 bar
20 differential pressure switch 0.8 bar
21 pressure sensor
22 flow sensor
23 pressure sensor for manifold #1
24 pressure sensor for manifold #2
25 pressure sensor for main pipe
26 tank level sensor
deluge system
the below are connected to fire control panel
1 location:
2 valve tag
3 limit switch for manual valve
4 solenoid valve
5 limit switch for drain valve
6 check pipes are supported properly
7 check nozzles location no obstruction for its job
8 check manual valves
9 limit switch for F.H.C

wet system
the below are connected as per mentioned
1 location:
2 valve tag
3 limit switch for manual valve/fire control panel
4 flow switch / fogtech panel
5 check pipes are supported properly
6 check nozzles location no obstruction for its job
7 check drain line
8 check manual valves
interface between fire control panel & fogtech panel
pump starting signal sent from fire control panel to
fogtech

alarm signal sent from fogtech panel to fire control


panel that fogtech has problem
jockey pump
1 check E/M consultants inspection requests ,
there arent comments
2 check pump frame
3 check for abnormal noise &vibration
4 check for any leakage from pump,connection &
fittings
5 check manual valves
6 check nonreturn valve
7 pressure gauge
8 record running current value

9 check overload relay ( by reduce setting value) or


remove wire No. (96 or 95)

10 check
)
phase failure relay remove wire No.( 11 or 14

11 check contactor ,termination no loss ,no heat


12 check indication lamps & selector switches
check that pump will automatically start under 33
13 bar , turn off at 35 bar

booster pump
pump#1 pump#2
1
check E/M consultants inspection requests ,
there arent comments
2 check pump frame
3 check for abnormal noise &vibration

4 check for any leakage from pump,connection &


fittings
5 check manual valves
6 check non return valve
7 pressure gauge
8 record running current value
9 check overload relay ( by reduce setting value) or
remove wire No. (96 or 95)

10 check phase failure relay remove wire No.( 11 or 14


)
11 check contactor ,termination no loss ,no heat
12 check indication lamps & selector switches
check that pump will automatically if hp pumps
13 start ,that pressure will be 3 bar
limit switch for manual valve
solenoid valve
limit switch for drain valve
check pipes are supported properly
check nozzles location no obstruction for its job
check manual valves
limit switch for F.H.C