Vous êtes sur la page 1sur 634

o

o
design
handbook
Precast and Prestressed Concrete
FIFTH EDITION
MNL 120-99

175 W. JACKSON BOULEVARD


CHICAGO, ILLINOIS 60604
312 786-0300 312 786-0353
Copyright © 1999
By Precast/Prestressed Concrete Institute
First edition, first printing, 1971
First edition, second printing, 1972
Second edition, first printing, 1978
Second edition, second printing, 1980
Third edition, first printing, 1985
Fourth edition, first printing, 1992
Fifth edition, first printing, 1999

All rights reserved. This book or any part thereof may not
be reproduced in any form without the written permission
of the Precast/Prestressed Concrete Institute.

ISBN 0-937040-60-6

Printed in U.S.A.

PCI Design Handbook/Fifth Edition


Precast and Prestressed Concrete
FIFTH EDITION

PCI Industry Handbook Committee

(,
A. Fattah Shaikh, P.E., Chairperson

Roger J. Becker, P.E. Phillip J. Iverson, P.E. Joseph A. Miller, P.E.


E. Fred Brecher, P.E. Daniel P. Jenny, Secretary Scott L. Muka, S.E., P.E.
Thomas J. D’Arcy, P.E. James E. A. King, P.E. Kurt L. Salm, S.E., R.A.
John D. Garlich, P.E. Rafael A. Magana, P.E. Kim Seeber, P.E.
Harry A. Gleich, P.E. Michael J. Malsom, S.E., P.E. Irwin J. Speyer, P.E.
Timothy A. Holien, P.E. Leslie D. Martin, S.E. Helmuth Wilden, P.E.
Mohammad Iqbal, P.E. Robert F. Mast, P.E.

Editor
Raths, Raths & Johnson, Inc.

PCI Design Handbook/Fifth Edition


FOREWORD

The Precast/Prestnessed Concrete - Institute, a Changes have beery made7throughout the docu­
non-profit- corporation, was founded-in T954 for the ment. Some of particular importance include:
purpose of advancing the design, -manufacture, and
use of structural precast and; prestressed concrete
• Updated to the ACI Building Code 318-95,
and architectural precast concrete in the United
other current PCI publications, and publica­
States and Canada.
tions of other technical associations.
To meet this purpose, PCI continually dissemi­
nates information on the latest concepts, techniques • New load tables for 12 ft. wide double tees
and design data to the architectural and engineering have been added.
professions through regional and national programs • Prestressed column curves have been ex­
and technical publications. panded to include 9,000 and 10,000 psi con­
The First Edition of the PCI Design Handbook was crete strengths.
published in 1971 with its primary focus on structural
products and buildings. To fill a void in the design of • The Chapter 3 sections on structural integrity
architectural precast concrete, the PCI Manual for and seismic design have been completely re­
Structural Design o f Architectural Precast Concrete vised.
was published in 1977. In 1978, the Second Edition • Chapter 4 includes a new pocketed spandrel
of the PCI Design Handbookwas published. In keep­ beam design example.
ing with the tradition of continually updating informa­
• Chapter 6 has been reorganized and materi­
tion, an Industry Handbook Committee was formed in
al not specifically related to connections has
1979 to develop the Third Edition, which was pub­
been moved to Chapter 4.
lished in 1985. That edition provided, in a single
source, information on the design of both architectur­ • The headed stud section (6.5.2) has been re­
al precast concrete and structural precast and pre­ vised to incorporate the latest research and
stressed concrete. The Fourth Edition, published in coordination with ACI.
1992, continued to present both architectural and
• A new section 10.5 was added to explain
structural products and systems. This emphasis is
some design practices that require inter­
maintained in the Fifth Edition.
pretation of ACI 318-95.
Since 1992, the committee has continued to moni­
tor technical progress within the industry, with partic­ • The metric conversion section of Chapter 11
ular assistance from the many committees of PCI re­ has been expanded and includes a new ex­
sponsible for a variety of specific topics. This Fifth ample problem.
Edition is the culmination of those efforts, and repre­
sents current industry practice.
The members of the committee listed on the title Substantial effort has been made to ensure that all
page have made significant contributions of theirtime data and information in this Handbook are accurate.
and expertise. In addition, PCI committees have pro­ However, PCI cannot accept responsibility for any er­
vided reviews of specific areas. Many individuals rors or oversights in the use of material or in the prep­
within the industry have also provided advice and aration of engineering plans. The designer must rec­
comment. The Institute offers alt involved in this pro­ ognize that no handbook or code can substitute for
cess a special note of recognition and appreciation. experienced engineering judgment. This publication
The final review phase consisted of a Blue Ribbon is intended for use by professional personnel compe­
Review Committee, made up of Plant Engineers and tent to evaluate the significance and limitations of its
Consulting Engineers from each of the PCI Zones contents and able to accept responsibility for the ap­
and from Canada. These individuals were Mike De- plication of the material it contains.
Sutter, P.E., Bill Fossing, P.E., Peter Kluchert, P.E., The Institute considers each new Edition of the
James Linskens, P.E., Robert H. Murray, P.E., Jo­ PCI Design Handbook to be a living document. The
seph W. Retzner, P.E., John Salmons, P.E., Timothy user is encouraged to offer comments to PCI on the
Salmons, P.E., Donald J. Smith, P.E., Victor 0 . Stan- content and suggestions for improvement to be in­
go, P.E., Ted Wolfstahl, P.E., and James Zusy, P.E. corporated in the next edition. Questions concerning
To them, PCI extends its appreciation for their very the source and derivation of any material in the Hand­
important input. book should be directed to the Institute.

PCI Design Handbook/Fifth Edition


GUIDE TO CHAPTERS

C hapter 1—-Precast and Prestressed-Concrete:


Applications and Materials
1- 1 to 1 -3 6

Chapter 2— Product Information and Capability


2- 1 to 2 -5 6

Chapter 3—Analysis and Design of Precast,


Prestressed Concrete Structures
3 -1 to 3 -1 0 0

Chapter 4—Design ^3f Precast and Prestressed


Concrete Components
4- 1 to 4 -9 6

Chapter 5—Product Handling and Erection Bracing


5- 1 to 5 -3 6

Chapter 6—Design of Connections


6- 1 to 6 -7 4

Chapter 7—Selected Topics for Architectural Precast Concrete


7- 1 to 7 -2 4

Chapter 8—Tolerances for Precast and Prestressed Concrete


8- 1 to 8 -2 0

Chapter 9—Thermal, Acoustical, Fire and


Other Considerations
9- 1 to 9 -7 4

Chapter 10—Specifications and Standard Practices


1 0 - 1 to 1 0-62

Chapter 11—General Design Information


1 1 - 1 to 1 1-36

Index

PCI Design Handbook/Hfth-Edition


PCI Design Handbook/Fifth Edition
CHAPTER 1
PRECAST AND PRESTRESSED CONCRETE:
APPLICATIONS AND MATERIALS

1.1 General .......................................... , ................................................................... 1 -2


1.1.1 Background.......................................................................................... 1 -2
1.1.2 Features and General P rinciples....................................................... 1 -2
1.1.3 Common P roducts................................................................... , ......... 1 -3

1.2 Applications ......................................................................................................... 1 - 4


1.2.1 Building Structures ............................................................................. 1 -5
1.2.1.1 Residential BuiJdings...................................... 1 -5
1.2.1.2 Office Buildings ........................................ 1 -9
1.2.1.3 Warehouses and Industrial Buildings ............................... 1 -1 2
1.2.1.4 Other Building S tructures.................................................... 1—13
1.2.2 Parking S tructu re s............................................................................. 1 -1 4
1.2.3 Justice F acilities................................................................................ 1 -1 6
1.2.4 Precast Concrete Cladding ............................................................. 1 -1 7
1.2.5 Stadiums/Arenas .............................................................................. 1 -1 9
1.2.6 B ridges................................................................................................. 1-21
1.2.7 Other S tructures............................................................................. , . 1 - 2 2

1.3 Materials ............................................................................................................. 1 -2 4


1.3.1 Concrete ............................................................................................ 1 -2 4
1.3.1.1 Compressive Strength ........................................................ 1 -2 4
1.3.1.2 Tensile S tre n g th .................................................................... 1 -2 5
1.3.1.3 Shear S tre n g th ...................................................................... 1 -2 5
1.3.1.4 Modulus of Elasticity ............................................................ 1 -2 5
1.3.1.5 Poisson’s R atio...................................................................... 1 -2 5
1.3.1.6 Volume C h a n g e s................................................................. 1 -2 5
1.3.2 Grout, Mortar and Drypack ........................................ 1 -2 6
1.3.2.1 Sand-Cement M ixtures....................................................... 1 -2 6
1.3.2.2 Non-Shrink G ro uts............................................................... 1 -2 7
1.3.2.3 Epoxy Grouts ....................................................................... 1 -2 7
1.3.3 Reinforcement................... 1 -2 7
1.3.3.1 Prestressing T e n d o n s......................................................... 1 -2 7
1.3.3.2 Deformed Reinforcing Bars ................................................ 1 -2 8
1.3.3.3 Structural Welded Wire Reinforcem ent............................. 1 -2 8
1.3.4 Durability ............................................................................................ 1 -2 8
1.3.4.1 Freeze-Thaw and Chemical Resistance ............................ 1 -2 9
1.3.4.2 Protection of Reinforcement .............................................. 1-3 0
1.3.4.3 Protection of Connections .................................................. 1-3 2
1.3.4.4 Sulfate Attack .................................................. , .................. 1 -3 4

1.4 References ......................................................................................................... 1 -3 4

PCI Design Handbook/Fifth Edition 1 -1


PRECAST AND PRESTRESSED CONCRETE;
APPLICATIONS AND MATERIALS

1.1 General Development of standard-products was one ofthe.


major activities through the Y950s and the 1960s.
In the late 1970s 4©w relaxation .strand was
1.1.1 Background introduced which reduced the loss of prestress force
The growth of precast and prestressed concrete rs due to creep in the strand, thus allowing more effi­
a story of the vision and daring of a few notable linen. cient use of prestressing, resulting in longer spans or
These men took a new idea and maximized its poten­ smaller sections. Larger strand sizes have been
tial by modifying and improving existing methods, made available as well, such as 0.6 in. diameter
conceiving new methods, and inventing new de­ strand.
vices, all with a focus on mass production tech­ In the field of bridges there was the development
niques. An excellent portrayal of the beginnings and of spliced girders, segmental bridges, cable stayed
the growth of precast and prestressed concrete in bridges and cantilevered girder bridges.
North America and the early pioneers is given in a se­ During the 1980s it was recognized that durability
ries of papers developed to commemorate the is an important aspectof a structure. The precast and
25-Year Silver Jubilee of the founding of the Pre­ prestressed concrete industry responded by taking
stressed Concrete Institute which is now known as advantage of one of its natural strengths. Plant-cast
thePrecast/Prestressed Concrete Institute (PCI). concrete is more durable than site-cast concrete be­
The single-most important event leading to the cause it can be cast with lower water/cementitious
launching of the precast/prestressed concrete indus­ materials ratios under controlled conditions. This
try in North America was the construction in 1950 of natural durability was enhanced with the develop­
the famed Walnut Lane Memorial Bridge (Figure ment of admixtures that make the concrete matrix
1.1.1) in Philadelphia, Pennsylvania. From a technical more impermeable and that inhibit steel corrosion.
perspective it is surprising, and from a historical per­ Pretopped tees were developed for parking struc­
spective it is fascinating, that the Walnut Lane Memo­ tures to maximize the benefits of the durability of pre­
rial Bridge was constructed in prestressed concrete. cast, prestressed concrete at the wearing surface.
There was very little published information on the The past decade has seen the development of
subject and there was a total lack of experience with more complex architectural shapes and surface treat­
linear prestressing in this country. Furthermore, the ments. The high demands of owners and architects
length of bridge spans involved would have been a for quality finishes has led to the development of new
daring venture in the late 1940s anywhere in the surface textures and surface treatments. Thin-set
world. The bridge became a reality through a fortu­ brick and stone-faced panels and textures and colors
nate sequence of events, and the vision, courage and of infinite variety have been developed.
persistence of a few extraordinary individuals [1].
Following completion of the Walnut Lane Memo­ 1.1.2 Features and General Principles
rial Bridge, American engineers and the construction Precasting concrete in PCI certified plants ensur­
industry enthusiastically embraced prestressed con­ es manufacture of high quality architectural and
crete. Many of the early post-Walnut Lane Memorial structural products. Precasting also facilitates pro­
Bridge applications remained in bridge construction, duction of a wide variety of shapes-and sizes, and the
such as the lower Tampa Bay crossing now known as use of prestressing substantially extends the span
the Sunshine Skyway. Simultaneously, American en­ capability of the products. These techniques enable
gineers and constructors were conceiving new de­ architects and engineers to achieve highly innovative
vices, improving techniques and developing new ma­ and economically competitive buildings and other
terials. structures.
The 1950s were the years that brought into focus This handbook serves as the primary reference for
the 7-wire strand, precasting, long-line beds (Figure the use and design of precast and prestressed con­
1.1.2) , admixtures, high strength concrete, vacuum crete structures. This section enumerates some of
concrete, steam curing and many other innovations. the important and unique features of precast and pre­
With these developments, coupled with the technical stressed concrete. These include the following:
and logistic support provided by the Prestressed
Concrete Institute, which was chartered in 1954, the 1. Construction speed.
industry grew and the applications of precast and 2. Plant-fabrication quality control.
prestressed concrete began to appear in an impres­
sive variety of structures. 3. Fire resistance and durability.

1-2 PCI Design Handbook/Fifth Edition


4. With prestressing: greater span-depth ratios, sections o tth e s e and other commonly used prod­
rrrore controllable performance, less material ucts. The I-beam, boxbeam and bulb tee are used in
usage. bridge-construction. The inverted tee, ledgeLbeam
and rectangular beamare used tor-structural framing
5. With architectural precast concretes wide vari­
to support deck members. Square or rectangularcol-
ety o f highly attractive surfaces and shapes.
umns, with or without corbels, are an integral partof
6. Thermal and acoustical control. the column-beam-deck framing that makes rapid, all-
weather erection possible. Pilesare manufactured in
7. ATweafher construction. a variety of shapes, including round,square, hexago­
nal and octagonal, as welt as rectangular sheet piles.
To fully realize these benefits and thereby gain the Channel slabs are used to support heavy floor or roof
most economical and effective use o f the material, loads in short and medium span ranges.
the following general principles are offered:

1. Precast concrete is basically a “simple-span"


material. However continuity can be, and often
is, effectively achieved with properlyconceived
connection details.

2. Sizes and shapes of members are often limited


by production, hauling and erection consider­
ations.

3. Concrete is a massive material. This is an ad­


vantage for such matters as stability under
wind loads, thermal changes, acoustical vibra­
tion and as well as fire resistance. Also, the
high dead-to-live load ratio wiH provide a great­
er safety factor against gravity overloads.

4. Maximum economy is achieved with maximum


repetition. Standard or repetitive sections
should be used whenever possible.

5. Successful use is largely dependent on an ef­


fective structural layout and carefully con­ Figure 1.1.1
Walnut Lane Memorial Bridge: Recipient of the 1978 ASCE's
ceived connection details.
Outstanding Civil Engineering Achievement Award.
6. The effects of restraint of volume changes
caused by creep, shrinkage and temperature
change must be considered in every structure.

7. While architectural panels are often used only


as cladding, the inherent load-carrying capac­
ity of these products should not be overlooked.

8. Prestressing improves the economy and per­


formance of precast members, but is usually
only feasible with standard shapes which are
capable of being cast in “long-line” beds.

1.1.3 Common Products

Double tee and hollow-core slabs (Figure 1.1.3)


are the most widely used building products. Double
tees are efficient for spans in the range of 40 to 90 ft
although longer spans are possible with deeper sec­
tions. Hollow-core slabs are available in a variety of
widths ranging from 16 in. to 10 ft and are used for Figure 1.1.2
spans up to about 40 ft. Figure 1.1.4 shows cross Long-line prestressed double tee casting bed.

PCI Design Handbook/Fifth Edition 1 -3


Precast and presfressed concrete p roducts are
designed in accordance with the latest engineerirra
standards and produced in-plants where PCI's Ptant
Certification is a n integral part of plant production.
PGl Plant Certification (Figurel .1.5} assures specifi­
ers of a manufacturing plant’s audited capabilityJo
produce quality products. A minimum of two-unan­
nounced inspections each year by specially trained
engineers evaluates compliance. Performance stan­
dards are found in the PCI quality control manuals,
MNL-116 [2] and MNL-117 [3]. These manuals are
considered industry standards for quality assurance
and control. A plant that does not achieve a minimum
required score loses certification. Plant certification is
a prerequisite for PCI membership. Plants in Canada
subscribe to a similar Canadian plant certification
program based on Canadian Standards Association
(CSA) A-251 Standard. For more information on the
Figure 1.1.3 Plant Certification Program, see Sect. 9.5.
Erection of hollow-core deck members. The high quality standard products noted above
form the basis for configuring a wide variety of fram­
ing systems for buildings, bridges and other struc­
tures. The following pages provide an overview of
some of the applications. For other applications and
also for products and practices suitable in different
geographical zones, contact with the local producers
is highly recommended. A list of PCI Producer Mem­
bers is available from the Precast/Prestressed Con­
crete Institute.
With this edition of the handbook, PCI has initiated
the process of giving recognition to common industry
practices in the design of precast and prestressed
concrete structures. While generally the design pro­
cedures are based on the ACI Building Code (ACI
318) requirements, there are cases where substantial
experience and/or research results suggest alterna­
tive design approaches for improved structural per­
formance and economy. A new section (Section
Common precast and prestressed concrete products. 10.5) has been included in this edition to catalog
these alternative practices. The long-term objective is
to augment the ACI Building Code with common in­
dustry practices to develop the best designs taking
advantage of the many special features of precast
and prestressed concrete.

1.2 Applications

The developments in products, materials and


techniques noted in the previous section have made
precast/prestressed concrete competitive in a variety
of residential, commercial, industrial, transportation
and many other types of structures. A few examples
Figure 1.1.5 of applications to different types of structures are giv­
Assurance of quality through PCI Plant Certification. en in this section.

1-4 PCI Design Handbook/Fitth Edition


1.2.1 Building Structures walls (Figure. 1.2.6), or rigid frame action {Figure
1,2.7), or some combination'of these.
Owners and developers quickly recognize the
many inherent qualities of precast and-prestressed
1.2.1.1 Residential Buildings
concrete which make it suitable for many types of
building, .structures. Precast and prestressed con­ Precast and prestressed concrete enjoys broad
crete structures, assembled from high-quality plant acceptance in low-rise and mid-riseapartmentbuild-
produced products, provider superior flexibility for ings, hotels, motels, andnursing homes. Thesuperi-
achieving the required degrees of fire-resistance, orfire resistance and sound control features are spe­
sound control, energy efficiency and durability. The cifically recognized by owners and developers.
availability ofa variety of materials and finishes makes Two-hour fire containment within each living unit
it possible to render virtually any desired aesthetic provides safety for adjacent units. With this type of
character. Furthermore, the construction speed pos­ high quality precast concrete housing, fire insurance
sible with precast and prestressed concrete mini­ rates are reduced and often higher incomes can be
mizes on-site labor costs, reduces the cost of interim generated because of the safe, soundproof high
financing, and thus provides important overall econo­ quality environment and lifestyle offered.
my to the owner or developer. The holbw-core slab is a standard product in this
Both bearing wall construction (Figures 1.2.1 and type of construction. Figure 1.2.9 shows a typical
1.2.2) and beam-column framing (Figures 1.2.3 and apartment building with hollow-core floors, load bear­
1.2.4) have been successfully used for various height ing precast concrete walls and a durable mainte­
buildings. Resistance to lateral loads can be provided nance free exterior spandrel panel. Details of this type
by interior shear walls (Figure 1.2.5), exterior shear of construction are shown in Figure 1.2.10.

Provides economy by eliminating the need for a structural frame at the perimeter. The wall panels themselves can be selected from a variety
of standard sections or flat panels, and specially formed architectural precast shapes. Any of the standard precast deck units can be used for
roofs.

PCI Design Handbook/Fifth Edition 1 -5


Figure 1.2.2 Multi-story bearing wall construction
Precast bearing wall units can be cast in one-story or multi-story high units. The-units may be started at the second floor level with the first
floor framing consisting of beams and columns to obtain a more open space on the first level.

1 -6 PCT Design Handbook/Fifth Edition


Any of ttie standard precast beam and column sections shown in Chapter 2 can be used for single-story structures. Selection of the type of
beam to be used depends on considerations such as span length, level of superimposed loads, and also on depth of ceiling construction and
desired architectural expression.

Figure 1.2.4 Multi-story beam-column construction


Beam-column framing is suitable for both low-rise and high-rise buildings. Architectural and engineering considerations dictate whether the
beams are continuous with single-story columns, or whether multi-story columns are used with single span beams.

PCI Design Handbook/Fifth Edition 1-7


Figure 1.2.5 Interior shear wall system Figure 1.2.7 Rigid frame system
Lateral loads are transmitted by floor diaphragms to a structur­ AH lateral toads are transferred to a moment-resisting frame
al core of precast shear walls. The shear wall can be tied to­ that ties beams and columns together with rigid connections.
gether vertically and at comers to form a structural tube that The need for shear walls is eliminated.
cantilevers from the foundation.

Figure 1.2.6 Exterior shear wall system


In general, the exterior shear wall system permits greater de­
sign flexibility than the other interior shear wall system because
it eliminates the need for a structural core. By combining gravi­ Figure 1.2.8
ty load bearing function with lateral load resistance, the exteri­ Precast concrete walls and floors ensure fire containment and
or shear wall system is, in general, more economical. lower insurance rates.

1-8 PCI Design Handbook/Fifth Edition


1.2.1.2 OfficeBuildings

Significant time savings usually- result from the


choice of atotally precast conc^eetructure^The su­
perstructure is prefabricated^ while the on-site
foundations are being built. Potential-delays are re­
duced with the complete build ing_system being sup­
plied under one contract. Erection o f large precast
concrete components can proceed even during ad­
verse weather conditions to quickly enclose the
structure. The prestressed floors provide an immedi­
ate working platform to allow the interior tradesmen
an early start on the mechanical, electrical and interi­
or finishing work. The quality finishes and fast sched­
ules result in early occupancy, tenant satisfaction and
reduced financing costs. These factors make a pre­
cast and prestressed concrete building very suitable
for office buildings.
The uses of precast and prestressed concrete in
office building construction are many, from total
building systems to single products like precast con­
crete stairs. Precast and prestressed concrete
beams, columns and floors are used in frame sys­
tems; shearwalls can be used alone or in conjunction
with beams and columns to resist lateral loads. Pre­
cast concrete stairs, along with being economical,
provide immediate safe use of stairwells.

Figure 1.2.9
High quality concrete in precast concrete walls and pre­ Figure 1.2.10
stressed hollow-core floors provide sound resistance, tire safe­ Details of a load bearing wall-hollow-core floor building. Span­
ty and reduced maintenance cost in multi-family housing. drels can be load bearing if required.

PCI Design Handbook/Fifth Edition 1 -9


Architectural precast concrete is used w ith all
types-offramingsystems. it provides an economical,
fire resistant, soundproof; durable, maintenance-free
cladding That allows the architect much freedom of
expression and results in beautifuffacades. Architec­
tural precast-concrete is discussed more fully in Sect .
1.2.4 and in Chapter 7.

Figure 1.2.11
Precast concrete provides a quiet, sate, comfortable and high
quality place to live.

Figure 1.2.12
This total precast concrete office building is an example of the
beauty and economy that can be achieved using precast con­
crete. Real savings can be achieved by allowing the architec­ Figure 1.2.13
tural facade to also perform structurally. Architectural precast concrete panels can perform structurally.

1 -1 0 PCI Design Handbook/Fifth Edition


.gure 1.2.14 Figure 1.2.15
Using precast concrete beams and columns with hollow-core By varying minor details like rustication, architectural precast
floor slabs provides a quick, economical structure. The addi- concrete exteriors can be made expressive and economical,
tion of an architectural precast concrete facade provides the
owner with the security of a single source of responsibility for
the structure.

Figure 1.2.16
Office buildings quite often utilize precast concrete spandrels.

PCI Design Handbook/Fifth Edition 1-11


Figure 1.2.18
Precast and prestressed concrete flat panels are used for
warehouse walls. Hollow-core slabs are often used in this ap­
plication.

Figure 1.2.17
The light industrial office structure is erected and put into ser­
vice quickly using insulated precast concrete sandwich pan­
els.

1.2.1.3 Warehouses and industrial Buildings

The ability of prestressed concrete to span long


distances with shallow depths and carry heavy loads
is particularly suitable for warehouses and industrial
buildings. Standard prestressed concrete walls, insu­
lated ornon-insufated, are very economical for ware­
house and light manufacturing applications. Total
precast systems with prestressed roof diaphragms
and precast shear walls can provide owners with a
complete “structural package”. A wide variety of wall
finishes is available.
In heavy industrial projects, prestressed floor units
capable of carrying the typical heavy floor loads can
be combined with other precast components to
constructversatile, corrosion-resistant structural sys­
tems. The precast and prestressed concrete framing
can be designed to accommodate a variety of me­
chanical systems and to support bridge cranes for in­
dustrial uses. High quality precast concrete provides
protection against fire, dampness and a variety of
chemical substances. The smooth surfaces achiev­
able in precast concrete make it ideal for food proc­
essing, wet operations, computer components
manufacturing, as well as many other types of
manufacturing and storage operations where cleanli­
ness is of concern. Clear spans of 40 ft and 90 ft are Figure 1.2.19
possible using hollow-core slabs and double tees, re­ Erection of precast concrete wall panels is fast and can be per­
spectively. Even longer spans to about 150 ft can be formed year round even in cold climates. Roof diaphragms
obtained with bridge-type girders or special double and supporting beams and columns are often also precast
concrete.
tees.

1 -1 2 PCI Design Bandbook/Fifth Edition

*
A
1 .2 .1 .4 OtherBuilding Structures

The many benefits o f precast and prestressed-


concrete, make-it suitable-for many other types of
buildings in addition tctresidential, office, and indus-
trial buildings. Applications abound in educational in­
stitutions, commercial buildings such as shopping
mails, and public buildings including hospitals, li­
braries, and airport terminals. Precast and pre­
stressed concrete have also been effectively-used in
numerous retrofit projects.

Figure 1.2.22
Waste water treatment buildings benefit from the durability,
economy and aesthetic capability of precast concrete.

Figure 1.2.20
Precast concrete insulated sandwich panels provide excellent
insulation for cold storage facilities. Smooth interior finishes
make these panels an excellent choice for food processing

Figure 1.2.23
This airport terminal illustrates the long-span capability of pre­
cast and prestressed concrete.

Figure 1.2.21
Total precast concrete structures provide many answers for
heavy industrial applications. High quality plant produced con­ Figure 1.2.24
crete provides excellent corrosion resistance and durability. Long-span perforated precast, prestressed concrete girders
Heavy loads are no problem for prestressed concrete beams provide flexible, column-free interior space in this government
and slabs. administration and public services building.

PCI Design Handbook/Fifth Edition 1-


Figures '! .2.26 and 1.2.27 show a typical preeast
concrete parking structure with architectural load
bearing spandrels and stair tower walls. Long^span
'd o ub le tees are shown in Figure 1.2.28 bearing o na n
innovative “light” wall that adds openness and afeel-
ing of security. Figure T.2.29 shows a precast, pre-
stressechdouble tee being erectedinto aioad bearing
spandrel which- is pocketed to reduce load-induced
torsion. The doublelee is being set down on an interi­
or inverted tee beam spanning from column to col­
umn.

Figure 1.2.25
This boathouse incorporates a training center and restaurant.

1.2.2 Parking Structures

Architects, engineers, developers and owners


have made precast and prestressed concrete the
material of choice for their commercial, municipal and
institutional parking needs. Though classified and
constructed as buildings, parking structures are
unique; in some ways, they may be compared to
bridges with multiple decks. They are subjected to
moving loads from automobile traffic and the roof lev­ Figure 1.2.26
Long clear spans with architectural load bearing spandrels
el of a parking structure is exposed to weather in
make precast concrete an economical and aesthetically pref­
much the same way as a bridge deck. Furthermore, erable parking structure solution.
they are usually not enclosed and thus the entire
structure is subjected to ambient weather conditions.
Also, exposure to deicing salts in northern climates or
to salt-laden atmospheres in coastal locations re­
quires consideration to ensure long-time perfor­
mance.
The controlled conditions of a precast concrete
plant assures the parking structure owner of the qual­
ity concrete and workmanship that provides long­
term durability. The low water-cementitious materials
ratio concrete that precast concrete manufacturers
use has been proven to increase resistance to corro­
sion due to chlorides. Studies [4] have also shown
that accelerated curing makes precast concrete
more resistant to chlorides than field cured concrete.
These inherent durability characteristics along
with low cost, rapid erection in all weather conditions,
unlimited architectural expression and long clear
spans make precast concrete the natural choice for
parking structures.
Through surveys of existing structures and other
experiences, and through research and develop­
ment, significant improvements have been achieved
in the engineering state-of-the-art of parking struc­
tures [5]. This accumulated experience and knowl­
edge has been assembled in a comprehensive publi­ Figure 1.2.27
cation [6] by PCI that includes recommendations on Stair towers acting as shearwaHs resist lateral loads and pro­
planning, design, construction and maintenance. vide architectural features.

1 -1 4 PCI Design Handbook/Fifth Edition


Figure 1.2.28 Figure 1.2.30
Opened load bearing walls provide the security of visibility and Interior inverted tee beam is deep enough to also act as the car
openness as well as carrying vertical loads. stop. These beams bear on column corbels.

Figure 1.2.29
Erection of precast concrete components is fast and indepen­
dent of climate. Pocketed load bearing spandrels accept the
double tee, which then bears on the interior inverted tee beam.
Erection is readily accomplished even at jobsites with limited A lateral system without wails, is provided by braced moment
space. frames.

PCI Design Handbook/Fitth Edition 1 -15


punch list problems, Tnulti-trade confusion and, ulti­
mately, risk. These units can be quickly staeketfand
can .be substantially complete requiring littiefinishing
w orkfsee Figure 1.2.35).
Given the serious shortageof-justice facilities, sav­
ings-in totai project time is often a critical-consider­
ation in selection o fa structural material and system
for these projects. Case histories show that total pre­
cast concrete projects have resulted in saving one to
two years of construction time over the estimated
schedule for competing systems. These experiences
and the other considerations noted above have led to
rapid growth in the use of precast and prestressed
concrete irv justice facilities projects.
Figure 1.2.32
Special erection equipment is available for adding floors to ex­
isting parking structures.

Vertical expansion of precast concrete parking


structures can be economically accomplished with
special cranes that carry new members over erected
decks as shown in Figure 1.2.32. This erection meth­
od also allows precast concrete to be considered for
expansion of non-precast concrete structures.

1.2.3 Justice Facilities

Justice facilities encompass many types of build­


ing occupancies. These include jails, prisons, police
stations, courthouses, juvenile halls, and special
mental health or drug abuse centers.
Precast concrete has proven to be the favored ma­ Figure 1.2.33
The repetitive nature of cell layout and the typical quick occu­
terial for justice facilities because it has many inherent
pancy requirements make precast concrete an ideal solution
benefits which are important to these building types. to prison overcrowding.
In addition to the benefits noted previously, namely
fire resistance, durability, speed of erection and flexi­
bility for aesthetics, precast and prestressed con­
crete is ideal for building-in the desired level of physi­
cal security coupled with accommodation of security
hardware and communication systems. The thick­
ness and reinforcement of precast wall and slab sys­
tems, designed for gravity and lateral loads and vol­
ume changes, are sufficient even for maximum
security requirements. Typical precast products such
as load bearing insulated wall panels, cell walls and
floor planks are employed frequently in justice facili­
ties. Also, the modular nature of precast and pre­
stressed concrete products facilitates pre-installation
of necessary security and communication hardware
in the plant, greatly simplifying field installation work
as well as saving valuable time along the project’s
critical path.
The use of precast concrete box modules in a
Figure 1.2.34
one-, two-, or four-cell format has greatly reduced
Precast double-cell module being lifted into place.
field labor, erection time, over all construction time,

1-16 PCI Design Handbook/Fifth Edition


Figure 1.2.35
Box module cells are often supplied with electric conduit and
boxes, furniture, window and door embedments, and me­
chanical and plumbing chases cast in.

1.2.4 Precast Concrete Cladding

Architectural precast concrete cladding provides


many degrees of freedom for architectural expres­
sion with the economy of mass production of precast
elements. The cladding may serve only as an enclo­ Figure 1.2.37
sure for the structure, or may be designed to support The Transamerica Corporation building in San Francisco is 48
gravity loads as well. Attention is currently also being stories tall. Floor-height, double-window units, weighing 3.5
tons each make up half of the total precast concrete pieces
given to the use of cladding to contribute to resist­
used.
ance to lateral loads of the structural frame [7].
Architectural precast concrete can be cast in al­
most any color, form or texture to meet aesthetic and
practical requirements [8]. Special sculptured effects
can provide such visual expression as strength and
massiveness, or grace and openness. Design flexibil­
ity is possible in both color and texture by varying ag­
gregate and matrix color, size of aggregates, finish­
ing processes and depth of exposure. PCI has
developed a guide to assist designers in selecting
colors and textures for architectural precast concrete
[25]. Additional flexibility of aesthetic expression is
achieved by casting various other materials as ve­
neers on the face of precast concrete panels. Natural
stone, such as polished and thermal-finished granite,
limestone and marble, and clay products such as
brick, tile and terra cotta have been frequently used
as veneer materials [8].
In addition to the freedom of aesthetic expression
Interior finishes are durable and maintenance free. Sound­ achievable with load bearing or non-load bearing ar­
proof and fire resistant, precast concrete adds to security and chitectural precast concrete, there are a number of
limits vandalism. other important functional and construction advan­

PCI Design Handbook/Fifth Edition 1-17


tages. Insulated wall panels., consisLoftwo concrete
wythes with a continuous- layer of rigidnnsulation
sandwiched between. These types of panels contrib-
ute substantially to the overall thermal efficiency of a
building. In cast-in-place concrete construction, pre­
cast concrete cladding panels are sometimes used
as permanent concrete formwork, thus becoming an
integral part of the structure. Off-site pre-assembly o f
ali components comprising a total wall system, in­
cluding window sash and glazing, can also be very
cost effective. For more comprehensive information
on product and design, see Ret 8.
Glass fiber reinforced concrete (GFRC) is a recent
innovation in materials technology which has been
adopted for use in producing strong, thin, lightweight
architectural cladding panels [9]. GFRC is a portland
cement-based composite reinforced with randomly
dispersed, alkali-resistant glass fibers. The fibers Figure 1.2.39
The moldability of architectural precast concrete allows for an
serve as reinforcement to enhance flexural, tensile,
infinite number of sizes and shapes.
and impact strength of concrete. A major benefit of
GFRC is its lightweight which provides for substantial
economy resulting from reduced costs of product
handling, transportation, and erection, and which
also results in lower seismic loads.

Figure 1.2.38 Figure 1.2.40


The NBC tower in Chicago has 2500 pieces of precast con­ Repetition of size and shape, which allows multiple form use, is
crete with limestone veneer as its exterior. a key to economy.

1-18 PCI Design Handbook/Fifth Edition


Figure 1.2.42
This major sports stadium was built using total precast con­
crete after evaluating other systems.

Figure 1.2.41
Spandrel panels spanning from column to column can be load
rearing or solely architectural.

1.2.5 Stadiums/Arenas

Large stadiums and arenas (Figures 1.2.42 to


1.2.46) are impressive structures. Often these pro­
jects are built on tight schedules to accommodate
some important sporting event. Precast and pre­
stressed concrete has been the overwhelming
choice for many of these projects. The technique of
post-tensioning precast segments together has al­
lowed this versatile material to form complex cantile­
ver arm and ring beam construction which supports
the roofs of these structures. Post-tensioning is also
commonly employed to minimize the depth of pre­
cast concrete cantilevered raker beams which carry
the seating and provide unhindered viewing of the
playing surface.
Mass produced seating units have been manufac­
tured in a variety of configurations and spans to pro­
vide for quick installation and long lasting service.
Consult local producers for in stock riser sections.
Long spans and the ability to eliminate costly field
formwork makes precast and prestressed concrete
the best choice for many components of stadium
construction, especially seating which can be stan­
dardized to take advantage of repeated form utiliza­
tion. Components that would require tall scaffolding
towers to field-form, such as raker beams and ring
beams, can be simplified by precasting in a plant and
delivering and lifting them into place. Pedestrian
ramps, mezzanine floors, concession, toilet, and
dressing room areas can all be framed and Figure 1.2.43
constructed using precast and prestressed concrete Precast concrete risers, raker beams, columns and mezzanine
elements. floors are also precast concrete components.

PCI Design Handbook/Fifth Edition 1-1 9


Figure 1.2.44
Fast track construction allows compressed schedules. Site preparation and component manufacture can take place simultaneously.
Multiple erection crews speed erection.

Figure 1.2.45 Figure 1.2.46


Special framing is handled easily with precast concrete, elimi­ Repetition, simplicity and multiple form use allows this
nating expensive field formwork. to be framed economically with total precast concrete,

1-20 PCI Design Handbook/Fifth Edition


Figure 1.2.47
Smaller grandstands and huge stadiums all benefit from the
use of precast and prestressed concrete.

1.2.6 Bridges

Bridge construction gave the prestressing indus­


try its start in North America. Precast and prestressed
Figure 1.2.48
concrete is now the dominant structural material for
Quality, plant-produced precast and prestressed concrete re­
short- to medium-span bridges. With its inherent du­ sults in durability. Low maintenance, economy and the ability
rability, low maintenance and assured quality, pre­ to span long distances make precast and prestressed con­
cast and prestressed concrete is a natural product for crete the preferred system for bridges o f all spans. Here, pre­
bridge construction. The ability to quickly erect pre­ stressed concrete piling easily resists the marine environment.

cast concrete components in all types of weather with


little disruption of traffic adds to the economy of the
job. For short spans (spans to 100 ft), use of box sec­
tions and double tee sections has proved economi­
cal. However, the most common product for short- to
medium-spans is the I-girder. Spans to 150 or 160 ft
are not uncommon with I-girders and bulb tees.
Spliced girders allow spans as much as 300 ft [10].
Even longer spans (300 to 400 ft) can be achieved us­
ing precast box girder segments which are then post-
tensioned in the field. Using cable stays, the span­
ning capability of precast and prestressed concrete
has been increased to over 1000 ft.
A recent innovation in bridge construction has
been the use of precast concrete in horizontally
curved bridges. A study commissioned by PCI [11]
documents the technical feasibility and the economic
viability of this application.
Another growing application of precast and pre­
stressed concrete in bridge construction includes the
use of precast deck panels [12]. Used as stay-in-
place forms, the panels reduce field placement of re­ Figure 1.2.49
inforcing steel and concrete resulting jn considerable The length of this bridge with extensive repetition, form usage
and large quantity of product made it worthwhile to create a
savings. The panels become composite with the
special section to span from pile cap to pile cap. Precast con­
field-placed concrete for live bads. crete pile caps eliminate expensive overwater formwork. Pre­
Figures 1.2.48 to 1.2.52 show some of the applica­ cast and prestressed concrete piling added speed to the proj­
tions mentioned above. ect as well as durability in a harsh marine environment.

PCI Design Handbook/Fiftti Edition 1-21


1.2.7 Other Structures
The inherent qualities of precast~and prestressed
concrete-noted in previous sections and the high de­
gree of designtlexibitity also make it ideal fo ra wide
variety of special applications. Properties, such as
corrosion resistance, fire resistance,^durability and
fast installation, have been used to good advantage
in the co n stru ctio n ^ poles, piles, railroad ties, stor­
age tanks, retaining walls and sound barriers. Where
repetition and-standardization exist, precasting com­
ponents can economically provide the quality of plant
manufactured products while eliminating expensive
and risky field procedures. These applications are
too numerous to categorize here separately; only a
few examples are given in Figures 1.2.53 to 1.2.59.
Figure 1.2.50
Standard AASHTO shapes offer immediate availability, econo­
my, durability and b w maintenance.

Figure 1.2.53
Precasting the arched culvert allows quick erection with little
site disruption and no field formwork.

Figure 1.2.51
Standardization has optimized bridge designs.

Figure 1.2.52 Figure 1.2.54


These shallow depth 35 x 48 in. box beams offer a clean simple Precast concrete sound wall provides aesthetics and protects
design and provide excellent performance. residential neighborhood from highway noise.

1-22 PCI Design Handbook/Fifth Edition


Figure 1.2.57
Large circular storage tank is under construction. Vertically
prestressed precast concrete wall segments are braced tem­
porarily. Cast-in-place concrete joints and circumferential
post-tensioning complete the structure.

Figure 1.2.55
Precast and prestressed utility poles provide low maintenance,
durable, economical poles capable of carrying heavy line
loads.

Figure 1.2.56
This pier and ammunition loading dock for the U.S. Navy is a Figure 1.2.58
total precast concrete structure. Economic analysis shows pre­ Precast and prestressed concrete has proven to be a viable
cast and prestressed concrete to be the best solution. alternative to timber for railroad ties.

PCI Design Handbook/Fifth Edition 1-23


1.3.1.1 Compressive Strength

The compressiye strength of concrete, made with


aggregate of adeq uate strength, is governed by ei-
therthe strength of theoement paste or the bondhe-
tween the paste and the aggregate particles. At early
ages the bond strength is fewer than the paste
strength; a t later ages the reverse may be the case.
Forgiven cementitious materials and acceptable ag­
gregates the strength that may be developed by a
workable, properly placed mixture of cementitious
materials, aggregates, and water (under the same
mixing, curing, and testing conditions) is influenced
by (a) the ratio of water to cementitious materials, (b)
the ratio of cementitious materials to aggregate, (c)
grading, surface texture, shape and strength of ag­
Figure 1.2.59 gregate particles, and (d) maximum size of the aggre­
Famous amusement park building in background has precast
gate. Mix factors, partially or totally independent of
and prestressed roof and walls. Monorail guideway Is also pre­ water-cementitious ratio, which also affect the
cast and prestressed concrete. strength are (a) type and brand of cement, (b)
amount and type of admixture or pozzolan, and (c)
mineral composition, gradation and shape of the ag­
1.3 Materials
gregate.
This section provides a brief review of properties of Compressive strength is measured by testing 6 x
the major materials used in precast and prestressed 12 in. cylinders in accordance with ASTM C 42. The
concrete. Also, included is a discussion of the dura­ precast concrete industry also uses 4 x 8 in. cylinders
bility of concrete. Refs. 1 3 -2 4 provide more com­ and 4 in. cube specimens. Adjustment factors need
plete information on these subjects. to be applied to these non-standard specimens to
correlate with the standard 6 x 12 in. cylinders.
Because of the need for early strength gain, Type
1.3.1 Concrete
III cement is often used by precasters so that molds
Concrete properties, such as stress-strain rela­ may be reused daily. Structural precast concrete and
tionship, tensile strength, shear strength and bond often architectural precast concrete is made with
strength, are frequently expressed in terms of the gray cement that meets ASTM C 150. Type III and
compressive strength of concrete. Generally, these Type I white and buff Portland cements are frequently
expressions have been empirically established used in architectural products. These are usually as­
based on experimental data of concretes with com­ sumed to have the same characteristics (other than
pressive strengths less than 6000 psi. These expres­ color) as gray cement. Pigments are also available to
sions are given in this section and are applicable to achieve colored concrete, and have little effect on
most precast and prestressed concrete since it is strength at the recommended dosages. Cement
usually specified in the 5000 psi to 6000 psi compres­ types, use of other cementitious materials, and expe­
sive strength range. rience with color should be coordinated with the local
Use of the equations given in this section are valid producers.
for compressive strengths up to 10,000 psi. For Higher-strength concrete mixes (over 6000 psi)
strengths in excess of 10,000 psi recommendations are available in some areas. Local suppliers should
given in Refs. 13 and 14 should be followed. be contacted to furnish mix and design information.
Concrete with compressive strengths higher than Initial curing of precast concrete takes place in the
8000 psi has been used in columns of high-rise build­ form, usually by covering to prevent loss of moisture
ings, and in prestressed concrete piling and bridge and sometimes, especially in structural prestressed
girders. Often, higher strength is a result of using high products, by the application of radiant heat or live
performance concrete to achieve added durability. steam. Curing, in addition to the initial curing cycle at
Interest in a more widespread use is growing. The approximately 12 hours has been shown to rarely be
strict use of ACI standard mix design concepts will necessary to attain the specified strength. Control
not always resuit in the achievement of high-strength techniques for the most effective and economical ac­
concrete. Special procedures such as those given in celerated curing are reported in PCI publication TR
ACI 211.4 may be necessary. No. 1 [15).

1-24 PCI Design Handbook/Fittii Edition


Whenconcrete is subjected to freezing and thaw­ The modulus of elasticity of concrete and other
ing and-ofher aggressive environments, air entrain- masonry materials is not as well defined as, for exam­
m e n tis often specified (see Sect. 1.3.4=1). In some ple, steei. It is therefore definedby some approxima­
concrete mixes, reduction of strength may occur with tion, such as the “secant- modulus’1. Thus calcula­
air entrainment; tions which invofveiteuse have inherent imprecision,
but this is seldom critical enough to affect practical
performance. While it may be desirable in-some rare
1.3.1.2 Tensile Strength
instances to determine-modulus of elasticity by test,
A critical measure of performance of architectural especially with some lightweight concretes, the
precast concrete is its resistance to cracking, which equation given in ACI 318-95 is usually adequate for
is dependant on the tensile strength of concrete. design:
Nonprestressed reinforcement does not prevent
Ec = w 1533yfT (Eq. 1.3.2)
cracking, but controls crack widths after cracking oc­
curs. Tensile stresses in prestressed concrete, which where:
could result in cracking, are permitted by A C I318-95 Ec = modulus o f elasticity of concrete, psi
[16]. w = unit weight of concrete, pcf
Flexural tensile strength is measured by the mo­ Vc = compressive strength, psi
dulus of rupture. It can be determined by test, but the
modulus of rupture for structural design is generally For concrete compressive strengths greater than
assumed to be a function of compressive strength as 6000 psi, Eq. 1.3.2 may predicta higher modulus of
given by: elasticity than is actually achieved. See Design Aid
11.2.2. Alternative equations are given in Refs. 13
ir =KxJ% (Eq. 1.3.1) and 14.

where:
fr = modulus of rupture, psi 1.3.1.5 Poisson’s Ratio
fc = compressive strength, psi Poisson’s ratio is the ratio of transverse strain to
K = constant, usually between 8 and 10 but axial strain resulting from uniformly distributed axial
prescribed to be equal to 7.5 by ACI load. It generally ranges between 0.11 and 0.27, and,
318-95 for design, is usually assumed to be 0.20 for both nor­
mal weight and lightweight concrete.
X = 1.0 for normal weight concrete
0.85 for sand-lightweight concrete
0.75 for all-lightweight concrete 1.3.1.6 Volume Changes

Volume changes of precast and prestressed con­


crete are caused by variations in temperature, shrink­
1.3.1.3 Shear Strength
age due to air-drying, and by creep caused by sus­
Similar to tensile strength, the shear (or diagonal tained stress. If precast concrete is free to deform,
tension) strength of concrete can also be related to its volume changes are of little consequence. If these
compressive strength. The equations for shear members are restrained by foundations, connec­
strength specified in ACI 318-95 are given in Chapter tions, steel reinforcement, or connecting members,
4. The shear strength of lightweight concrete is deter­ significant stresses may develop over time.
mined by test. However, as an alternative to test, ACI The volume changes due to temperature varia­
318-95 permits the use of the coefficient, X, as de­ tions can be positive (expansion) or negative (con­
scribed above. traction), while volume changes from shrinkage and
creep are only negative.
Precast concrete members are generally kept in
1.3.1.4 Modulus of Elasticity
yard storage fo ra period of time. Thus, much of the
Modulus of elasticity, Ec, is the ratio of normal shrinkage will have taken place by the time of erec­
stress to corresponding strain in tension or compres­ tion. However, connection-details and joints must be
sion. It is the material property which determines the designed to accommodate the changes which will
deformability of a concrete member under load. occur after the precast member is erected and con­
Thus, it is used to calculate deflections, axial shorten­ nected to the structure. In most cases, the shorten­
ing and elongation, buckling and relative distribution ing that takes place prior to making the final con­
of applied forces in composite and non-homoge- nections will reduce the shrinkage and creep strains
neous structural members. to manageable proportions.

PCI Design Handbook/Fifth Edition 1 -25


Typical creep, shrinkage, and temperature strains Table 1.3.1 Coefficients of linear thermal-
and- design examples are giverr in Chapter 3. expansion of rock (aggregate)
TemperatureEffects. The coefficient ofthermal ex­ and concrete [17].
pansion of concrete varies withrthe aggregate used
Average coefficient
as shown in-Table 1.3.1. Range for normal weight
of thermal expansion
concrete is 5 ta 7 x 10 -6 in./in./°Fwhen madewith sili­ x 10-® in./in./°F
ceous aggregates and 3.5 to 5 x 10~® when made Type of rock
with calcareous aggregates. The range for structural (aggregate) Aggregate Concrete8
lightweight concretes is 3.6 to 6 x 10~® in,/in./°F de­ Quartzite, Cherts 6.1 - 7.0 6.6 - 7.1
pending on the type of aggregate and amount of nat­ Sandstones 5.6 - 6.7 . 5.6 - 6.5
ural sand. For design, coefficients of 6 x TQ-® in./ Quartz Sands &-Gravels -5.5 - 7.1 6.0 -8.7
in./°F for normal weight concrete and 5 x 10-® for Granites & Gneisses 3.2 - 5.3 3.8 - 5.3
Syenites,
sand-lightweight concrete are frequently used. If
Diorites, Andesite, 3.0 - 4.5 4.4-5.3
greater accuracy is needed, tests should be made on Gabbros, Diabas, Basalt
the specific concrete. Limestones 2.0 -B.6 3.4 - 5.1
Since the thermal coefficient for steel is also about Marbles 2.2 - 3.9 2.3
6x10-® in./in./°F, the thermal effects on precast and Dolomites 3.9 - 5.5 —
prestressed concrete may be evaluated by treating it Expanded Shale,
Clay & Slate 3.6 - 4.3
as plain concrete.
Expanded Slag — 3.9 - 6.2
Shrinkage and Creep. Precast concrete members Blast-Furnace Slag — 5.1 - 5.9
are subject to air-drying as soon as removed from Pumice — 5.2 - 6.0
molds or forms. During exposure to the atmosphere, Perlite — 4.2 - 6.5
the concrete slowly loses some of its original water Vermiculite — 4.6 - 7.9
causing a shrinkage volume change to occur. Barite — 10.0
Limonite, Magnetite — 4.6 - 6.0
When concrete is subjected to a sustained load,
None (Neat Cement) 10.3
the deformation may be divided into two parts; (1) an Cellular Concrete — 5j0 - 7.0
elastic deformation which occurs immediately, and 1:1 (Cement:Sand)b — 7.5
(2) a time-dependent deformation which begins im­ 1:3 (Cement:Sand)b — 6.2
mediately and continues over time. This time-depen­ 1:6 (Cement:Sand)b — 5.6
dent deformation is called creep. a. Coefficients for concretes made with aggregates from differ­
ent sources vary from these values, especially those for grav­
Creep and shrinkage strains vary with relative hu­
els, granites, and limestones. Fine aggregates generally are
midity, volume-surface ratio (or ratio of area to perim­ the same material as coarse aggregates.
eter), level of sustained load including prestress, con­ b. Tests made on 2-yr. old samples.
crete strength at time of load application, amount and
location of steel reinforcement, and other characteris­ 3. Expansive portland cement made with special
tics of the material and design. Typical creep and additives.
shrinkage strains are given in Table 3.12.3 along with 4. Gypsum or gypsum/portland cements.
multipliers in Tables 3.12.4, 3.12.5 and 3.12.6 to ac­ 5. Epoxy-cement resins.
count for the effects of the more significant variables
in masonry mortar about one-half of the portland
mentioned above. When high-strength concretes are
cement is replaced with lime. This improves its bond­
used, different values of shrinkage and creep may be
ing characteristics but reduces its strength. Such
needed. The joints between precast members typi­
mortar should not be used indiscriminately as a sub­
cally are detailed to relieve such strains.
stitute for grout.
Quality control of grout is as important as that of
1.3.2 Grout, Mortar and Drypack
concrete. Site-mixed grout should be made and
When water, sand and a cementitious material are tested at regular intervals according to ASTM C 1019
mixed together without coarse aggregate, the result which paratlels ASTM C 39 for concrete. For more
is called grout, mortar or drypack, depending on con­ general information on grout, see Ref. 18.
sistency. These materials have numerous applica­
tions: sometimes only for fire or corrosion protection, 1.3.2.1 Sand-Cement Mixtures
or for cosmetic treatment; other times to transfer Most grout is a simple mixture of portland cement,
loads through horizontal and vertical joints. sand and water. Proportions are usually one part
Different cementitious materials are used: Portland cement to 2 to 3 parts sand. The amount of
1. Portland cement. water depends on the method of placement of the
2. Shrinkage-compensating Portland cement. grout.

1 -26 PCI Design Handbook/Fifth Edition


FTowablegrouls are used to fill voids thatare either used when high strength is desired, or when im­
formed in the field orGast into the precast m em ber proved bondingto concrete isrrecessary. Ref._20 isa
They are used at joints thatare heaviiycongested-but comprehensive Teportnn the sifejeet b y Committee
not confined, thus requiring some formwork. These 503 of the American Concreteinstitute.
grouts usually have a high water-cerrrentilfeus materr- The physical properties-of epoxy compoundsvary
als ratio (typically about 0.5), resulting in few strength widely. Also, the epoxy grouts behave very differently
and high shrinkage. There is also a tendency for the than the sand-cement grouts. Fot example, thether-
solids to settle, leaving a layer of water on the top. mal expansion o f an epoxy grout can be as much as 7
Special ingredients or treatments can improve these times the thermal expansion of sand-cement grout. It
characteristics. is therefore important that use of these grouts be
For very small spaces in confined areas, grout based on experience and/or appropriate tests. Rec­
may be pumped or pressure injected. The confine­ ommended tests and methods are given in Ref. 20.
ment must be of sufficient strength to resist the pres­
sure. Less water may be used than for flowable
1.3.3 Reinforcement
grouts, hence less shrinkage and higher strength.
A stiffer grout, or mortar, is used when the joint is Reinforcement used in structural and architectural
not totally confined, for example in vertical joints be­ precast concrete includes prestressing tendons, de­
tween wall panels. This material will usually develop formed steel bars, and welded wire fabric.
strengths of 3000 to 6000 psi, and have much less Fibers, which are sometimes used to control
shrinkage than flowable grouts. shrinkage cracks, do not transfer loads and therefore
Drypack is the common name used for very stiff cannot be used to replace structural reinforcing such
sand-cement mixes. They are used if a relatively as welded wire reinforcement. This is particularly im­
high-strength is desired, for example, under column portant for structural toppings over precast concrete
base plates. Compaction is attained by hand tamp­ decks. The reinforcing in these toppings cannot be
ing* replaced with fibers.
When freeze-thaw durability is a factor, the grout
should be air-entrained. Air content of plastic grout or
mortar of 9 to 10% is required for adequate protec­ 1.3.3.1 Prestressing Tendons
tion. Tendons for prestressing concrete may be wires,
Typical Portland cement mortars have very slow strands or bars. In precast and prestressed structur­
early strength gain when placed in cold weather. al concrete, nearly all tendons are 7-wire strands con­
Heating the material is usually not effective, because forming to ASTM A 416. There is limited use of 2- and
the heat is rapidly dissipated to surrounding con­ 3-wire strands conforming to ASTM A 910. The
crete. Thus, unless a heated enclosure can be pro­ strands are pretensioned, that is, they are tensioned
vided, special proprietary mixes, usually containing prior to placement of the concrete. After the concrete
gypsum, may be indicated. Mixes containing a high has reached a predetermined strength, the strands
percentage of gypsum are known to deteriorate un­ are cut and the prestress force is transferred to the
der prolonged exposure to water. concrete through bond.
Two types of strand are covered in ASTM A 416
1.3.2.2 Non-Shrink Grouts and A 910: “low-relaxation” strand and “stress-re­
Shrinkage can be reduced, or more appropriately, lieved” strand. Over the past several years, use of
compensated for by the use of commercially avail­ low-relaxation strand has progressively increased to
able non-shrink, pre-mixed grouts. These mixes ex­ a point that currently the stress-relieved strand is sel­
pand during the initial hardening to offset the subse­ dom used. Thus, low-relaxation strand is used in the
quent shrinkage of the grout. Since the non-shrink load tables in Chapter 2 and in the various examples
grouts are primarily proprietary, their chemical com­ throughout this Handbook.
position is usually not available tostudy their potential Architectural precast concrete is also sometimes
effects on the interfacing materials, such as reinforce­ prestressed. Depending on the facilities available at
ment and inserts in the connection. Thus, it is advis­ the plant, the prestressing tendons may be either pre­
able that manufacturers’ recommendations should tensioned or post-tensioned. In post-tensioning, the
be carefully followed. For a general reference on the tendons are either placed in a conduit or are coated
characteristics and methods of testing of non-shrink so they will not bond to the concrete. The tendons
grouts, see Ref. 19. arethen tensioned after the concrete has reached the
predetermined strength. The compressive forces are
1.3.2.3 Epoxy Grouts transferred to the concrete from the strand by end fit­
Epoxy grouts are mixtures of epoxy resins and a tings on the strand, which bear directly against the
filler material, usually oven dried sand. These are end surfaces of the concrete member. When the

-PCLDesign Handbook/Fifth Edition 1 -27


tendons are placed in a conduit^ they-are usually Plain welded wire-reinforcement bonds to con­
groutecLafter tensioning (bonded post-tensioning). crete by-tbe mechanical anchorage at each welded
Wherrfhey are greased and^wrapped, orcoated, they wir-e-intersection. Deformed welded ^ ^ r e in f o r c e ­
usually are not grouted ^unbonded post-tensioning) . ment utilizes-wire deformations plus welded intersec-
T o r more information on posttensioning in general tionsfor bond and-anchorage: Welded wire fabric for
see Ret 21. architectural precast concrete is normally supplied in
Precast products ate typically prestressed with fiat sheets. Use of welded wire reinforcement from
7-wire strand, not prestressing bars. Prestressing rolls, particularly in the thin precast sections, is not
bars meeting ASTM A 722 have been usedin connec­ recommended because the rolled welded wire rein­
tions between members. The properties of prestress­ forcement carr not be flattened to the required place­
ing strand, wire and bars are given in Chapter 11. ment tolerance. In addition to using welded wire rein­
The ability of strands to properly bond shall be cer­ forcement in flatsheets, many plants have equipment
tified by the strand supplier. for bending sheets into various shapes, such as U-
shaped stirrups, four-sided cages, e ta
1.3.3.2 Deformed Reinforcing Bars
Available wire sizes, common stock sizes and oth­
Reinforcing bars are hot-rolled from steel with er information on welded wire reinforcement are giv­
varying carbon content. They are usually required to en in Chapter T1 and Ref. 23.
meet ASTM A 615, A 616 or A 617. These specifica­
tions are of the performance type, and do not closely
control the chemistry or manufacture of the bars. 1.3.4 Durability
Bars are usually specified to have a minimum yield of Concrete durability is of concern when the struc­
40,000 psi (Grade 40) or 60,000 psi (Grade 60). ture is exposed to an aggressive environment. The
Grade 40 bars will usually have lower carbon content designer, contractor, and owner must recognize the
than Grade 60, but not necessarily. It is possible to deleterious effects of (a) freeze-thaw in a wet environ­
weld these grades o f reinforcing bars after appropri­ ment, (b) chemical attack, including carbonation, (c)
ate preheating depending on carbon equivalency corrosion of embedded metals, and (d) aggregate
[27]. reactivity. The ideal approach is to make the con­
ASTM A 706 specifies a bar with controlled chem­ crete impermeable, which means making the con­
istry that is weldable. For bars that are not to be crete as uniformly dense as possible and designing
welded, see Sect. 6.5.1. to control cracking. In this respect, precast and pre­
In order for the reinforcing bar to develop its fuH stressed concrete has inherent advantages since it is
strength in the concrete, a minimum length of produced in a controlled environment that lends itself
embedment is required, or the bars may be hooked. to high quality concrete, and prestressing leads to ef­
Information on bar sizes, bend and hook dimensions fective crack control.
and development length are given in Chapter 11 and
Measures that should be considered for improved
Ref. 22.
durability are low water-cementitious materials ratio,
entrained air content, clear cover over reinforcement,
1.3.3.3 Structural Welded Wire Reinforcement
appropriate coating of prestressed and nonpres-
Structural welded wire reinforcement is a prefabri­ tressed reinforcement, chloride exclusion, corrosion
cated reinforcement consisting of parallel, cold- inhibitors, silica fume, proper mix design, low-alkali
drawn wires welded together in square or rectangular cement, non-reactive and abrasion resistant aggre­
grids. Each wire intersection is electrically resist­ gates, proper finishing, proper curing, surface seal­
ance-welded by a continuous automatic welder. ers, surface membranes, and, in parking structures,
Pressure and heat fuse the intersecting wires into a design for proper drainage.
homogeneous section and fix all wires in their proper Penetrating surface sealers can improve the dura­
position. bility of concrete by reducing moisture and chloride
Plain wires (ASTM A 185), deformed wires (ASTM penetration. Sealers have however, little ability to
A 497) or a combination of both may be used in bridge cracks and should not be expected to provide
welded wire fabric. Plain wire sizes are specified by protection from moisture absorption or chloride pen­
the letter W followed by a number indicating the etration at cracks. Some sealers have proven to be
cross-sectional area of the wire in hundredths of a more effective than others. Their evaluation should
square inch. For example, W16 denotes a plain wire be based on criteria established in Ref. 26. Silane
with a cross-sectional area of 0.16 in2 Similarly, de­ based sealers are hydrophobic and have been dem­
formed wire sizes are specified by the letter D fol­ onstrated to reduce chloride penetration into con­
lowed by a number which indicates area in hun­ crete as much as 95%.
dredths of a square inch.

1-28 PCI Design Handbook/Fifth Edition

M
1.3.4.1 Freeze-Thaw and Chemical. Resistance a “normal dosage” ofthe air-enfraiRing agent be used
insteadof specifying a particular range-of air content
The typical-dense mixes used for precast products -percentage. For precast- concrete elements
have high resistance to-freezing and thawing. En- .constructed above grade and oriented in a vertical
Irained airis~essentiaf to further Improve freeze-thaw position-, air contents as low as^2 to 3% will usuaiiy-
resistance in particularly severe environments. provide the required durability . The precast and pre­
Freeze-thaw damage, which manifests itself by scal­ stressed concrete industry .does not use~ainentrain-
ing of the surface, is magnified’when chloride based Ing portland cements.
deicing chemicals are used. Deicers can be, applied In addition to entrained air, other positive mea­
indirectly in various ways, such as by drippings from sures, such as adequate concrete cover over steel
the underside of vehicles. and rapid drainage of surface water may be essential
Table 1.3.2 (Table 4.2.1, A C I318-95) provides the in structures exposed to weather.
required air content for both severe and moderate ex­ Table 1.3.3 (Table4.2.2, ACI 318-95) provides the
posure conditions, for various maximum aggregate maximum permitted water-cementitious materials ra­
sizes. Severe exposure is defined as a climate where tio (or, for lightweight concrete, minimum f£) for con­
the concrete may be in almost continuous contact crete which is exposed to an aggressive environ­
with moisture prior to freezing, or where deicing salts ment. The water-cementitious materials ratios
come In contact with the concrete. Salt-laden air, as specified in Table 1.3.3 shall be calculated using the
found in coastal areas, is also considered a severe weight of cement meeting ASTM C 150, C 595, or C
exposure. A moderate exposure is one where deic­ 845 plus the weight of fly ash and other pozzolans
ing salts are not used, or where the concrete will only meeting ASTM C 618, slag meeting ASTM C989, and
occasionally be exposed to moisture prior to freezing. silica fume meeting ASTM C 1240, if any, except
Admixtures are added to the concrete during the mix­ when the concrete is exposed to deicing chemicals.
ing cycle to entrain air. Tolerance on air content is For concrete exposed to deicing chemicals, the maxi­
±1.5%. ACI 318-95 permits an air content one per­ mum weight of fly ash, other pozzolans, silica fume,
centage point lower than the tabular values for con­ or slag that is included in the concrete shall not ex­
crete strengths higher than 5000 psi. ceed the percentages ofthe total weight of cementi­
For some of the concrete mixtures, such as low- tious materials given in Table 1.3.4 (Table 4.2.3, ACI
slump mixtures in extruded products or gap-graded 318-95). In many plants, a water-cementitious mate­
mixtures in architectural precast concrete, it is difficult rials ratio of 0.35 is frequently used for added durabili­
to measure air content. Thus, it is recommended that ty of precast, prestressed concrete products.

Table 1.3.2 Total air content for frost-resistant Table 1.3.3 Requirements for special expo­
concrete. sure conditions.

Normal Air content, percent


maximum Exposure Maximum Minimum f c ,
aggregate Severe Moderate condition water- psi, normal
size,1 in. exposure exposure cementitious weight and
materials ratio, lightweight
% TA 6 by weight, aggregate
'A 7 5 VS normal weight concrete
aggregate
% 6 5
concrete
1 6 4VS
Concrete intended
VA 5 1A 4VS to have tow permeability 0.5 0 4000
5 4 when exposed to water

3b 4'A 3'A Concrete exposed to


freezing and thawing
0.4 5 4500
a. See ASTM C 33 for tolerances on oversize for various in a moist condition or
deicing chemicals
nominal maximum size designations.
b. These air contents apply to total mix, as for the preceding For corrosion protection
aggregate sizes. When testing these concretes, however, of reinforcement in con­
aggregate larger than 1'A in. is removed by handpicking or crete exposed to chlo­
sieving and air content is determined on the minus 11/j in. rides from deicing chemi­
0 .4 0 5000
fraction of mix. (Tolerance on air content as delivered applies cals, salt, salt water,
to this value.) Air content of total mix is computed from value brackish water, seawater,
determined on the minus VA in. fraction. or spray from these
sources.

PC) Design Handbook/Fifth Edition 1-2 9


Table T.3.4 Requirements for concrete ex­ the mix. Table T.3.5 {Table 4.4.1, ACf 318-95) indi-
posed to deicing chemicals. catesfbe maximum chloride ion content. These limits
are-intended for use with uncaated'reinforcement.
Chloride ion content values can be determined-in ac­
Cementitious materials - Maximum percentof
total cementitious cordance with ASTM C 1218
materials by weight® In order to provide corrosion protection to rein­
forcement, concrete cover should conform to ACT
Fly-ash or other- pozzolans conform­
in g to ASTM C 618
25 318-95, Sects. 7.7.2 and 7.7.3as listed in Table T.3.8
Concrete cover is minimum clear distance from the
Slag conforming to ASTM C 989 50
reinforcement to the face of the concrete. For ex­
Silica fume conforming to ASTM C 10 posed aggregate surfaces, the concrete cover is not
1240
measured from the original surface; instead, the
Total of fly ash or other pozzolans, 50»
slag, and silica fume
depth of the mortar removed between the pieces of
coarse aggregate (depth of reveal) should be sub­
Total of fly ash or other pozzolans 35b
and silica fume tracted. Attention must also be given to scoring, false
joints, and drips, as these reduce the cover.
a. The total cementitious material also includes ASTM C 150,
C 595 and C 845 cement. The maximum percentages also As noted above, high quality concrete provides
include fly ash or other pozzolans presenHn Type IP or l(PM) adequate corrosion protection for reinforcement for
blended cement, ASTM C 595; slag used in the manufacture
most conditions. Even in moderate to severe aggres­
of an IS or l(SM) blended cement, ASTM C 595; and silica
fume, ASTM C 1240, present in a blended cement. sive environments, concrete will provide adequate
b. Ply ash or other pozzolans and silica fume shall constitute protection with proper attention to mix design, steel
no more than 25 and 10 percent respectively, of the total stress level and the extent o f cracking under service
weight of the cementitious materials.
toads, and the depth of concrete cover. Only when
these protection measures are not feasible, it may be
1.3.4.2 Protection of Reinforcement necessary to consider other ways of protecting rein­
forcement, such as galvanizing, corrosion inhibitors
Reinforcing steel is protected from corrosion by
or epoxy coating. These are described as follows:
embedment in concrete. A protective iron oxide film
Galvanized Reinforcement. Except for exposed
forms on the surface of the bar, wire or strand as a
connections, there is rarely any technical need for
result of the high alkalinity of the cement paste. As galvanized reinforcement. With proper detailing and
long as the high alkalinity is maintained, the film is ef­ specifications, galvanizing may be superfluous.
fective in preventing corrosion. However, in architectural precast concrete, some
The protective high alkalinity of the cement paste manufacturers prefer galvanized welded wire fabric,
may be tost in the presence of oxygen, moisture, and because corrosion will not generally occur during
chlorides. Chlorides may be found in concrete ag­ prolonged storage of the mesh.
gregates, water, cementitious materials or admix­
tures, and hence may be present in the concrete
when cast. Concrete of low permeability and of suffi­ Table 1.3.5 Maximum chloride ion content for
cient cover over the steel will usually provide the nec­ corrosion protection of reinforce­
essary protection against chloride penetration due to ment.
the presence of deicer salts.
Moisture and oxygen atone can cause corrosion. Type of member Maximum water-soluble
chloride ion (Ci~) in concrete,
Cracking may allow oxygen and moisture to reach
percent by weight of cement
the embedded steel, resulting in conditions where
rusting of the steel and staining of the surface may Prestressed concrete 0.06
rapidly occur. Prestressing can control cracking; in
non-prestressed members, the choice of a sufficient­ Reinforced concrete
exposed to chloride In 0.15
ly tow stress level in the steel under permanent toads
service
can limit the width of cracks and the intrusion of wa­
ter, thus maintaining the integrity of the reinforce­ Reinforced concrete that
ment. will be dry or protected 1.00
from moisture in service
Calcium chloride as an admixture should not be
used in prestressed or reinforced concrete. Consid­
Other reinforced
eration should be given to the chloride ion content in 0.30
concrete construction
hardened concrete, contributed by the ingredients of

1-30 PCI Design Handbook/Fifth Edition


Table 1.3.6 Minimum covet requirements for forms are in close proximity-in fresh concrete, galv­
reinforcement in precast and anic cell problems may occur during the initial pro­
prestressed concrete.86 cesses of hydration: The reactions otzinc in concen­
trated alkaline material such as-concrete {pH o f
Condition Minimum cover 12.5—1^75) liberates hydrogen-gas. This-refease of
gas-bubbles results in the shadowing or reflection of
Exposed to earth orweatherb
reinforcement. Ways to avoid this occurrence, by
. Walt panels #11 and smaller—% in.
passivating either the galvanized steel or the con­
. Other members #6 through #11— VA in.
crete mix, are discussed in the PCI manual Architec­
#5, W31 orD31 wire,
and smaller—1Vi in. tural Precast Concrete [7].
Epoxy Coated Reinforcement. Epoxy coated rein­
Not exposed to earth forcing bars and welded wire fabric are also available
or weather for use in members which require special corrosion
• Wall panels, slabs and joists #11 and smaller—% in.
protection. Epoxy coated reinforcing bars should
• Beams and columns:
conform to ASTM A 775, and epoxy coated welded
Main steel Diameter of bar, but not
wire fabric should conform to ASTM A 884. The
less than % in. and
need not exceed V A in. epoxy provides excellent protection from corrosion if
Ties, stirrups or spirals All sizes—% in. the bar is uniformly coated. Bars generally are
coated when straight; subsequent bending should
a. Manufactured under plant control conditions.
have no adverse effect on the integrity of the coating.
b. Increase cover by 5Q2J> if tensile stress of prestressed
members exceeds 6 / f t .
If the coating is removed or damaged, the reinforce­
c. Cover requirements for # 5 bars and smaller apply to ment should be touched up with commercially avail­
prestressing steel. See Sect. 10.5 able epoxy compounds. Epoxy coating reduces
bond strength; reference should be made to Sect.
Galvanizing is not recommended for members
12.2.4 o f ACI318 for the required increase in develop­
subjected to chlorides, because a deleterious chemi­
ment length. Similarly, the requirements for crack
cal reaction can take place when the concrete is
control may need to be modified.
damp and chlorides are present. Therefore, the
Supplemental items must also be protected to re­
benefit obtained by galvanizing is questionable for
tain the full advantage of protecting the main rein­
members subjected to deicing salts and similar expo­
forcement. For example, bar supports should be sol­
sures.
id plastic and bar ties should be nylon-, epoxy-, or
Galvanized welded wire reinforcement is usually plastic-coated wire, rather than black wire. Epoxy
available as a stock item in selected sizes. Individual
coated reinforcing bars should be handled with nylon
wires are galvanized before they are welded together slings.
to form the fabric; zinc at each wire intersection is
Epoxy Coated Strand. Epoxy coated strand is a rel­
burned off during welding, but the resulting black
atively new product proposed for use in unusually
spots have not caused noticeable problems. After aggressive environments. It is covered by ASTM A
welding, the fabric is shipped without further treat­ 882.
ment. There is no current ASTM specification for gal­ In order for it to be used as bonded strand, the
vanized welded wire fabric. epoxy coating is impregnated with a grit to assure de­
When galvanized reinforcement is used in con­ velopment of bond; without grit, the epoxy coated
crete, it should not be coupled directly to ungalva­ strand had virtually no bond strength. With adequate
nized steel reinforcement, copper, or other dissimilar density and a proper distribution of the grit, the bond
materials. Polyethylene and similar tapes can be strength of the epoxy coated strand is comparable to
used to provide local insulation between dissimilar that of uncoated strand. Note that tests [24] have
materials. Galvanized reinforcement should be fas­ shown the transfer and the development lengths of
tened with ties of soft stainless steel, or zinc coated or the epoxy coated (with grit) strand to be somewhat
nonmetallic coated tie wire. shorter than the corresponding lengths for the un­
The use of galvanized reinforcement Glose to steel coated strand. Also, there are differences in some
forms or non galvanized reinforcement in fresh con­ other properties of the two types of strand. For exam­
crete may cause “shadowing" or reflection of the rein­ ple, the relaxation loss of epoxy coated strand is high­
forcement onto the final concrete surface. When gal­ er (about twice) than that of uncoated, low-relaxation
vanized and non galvanized reinforcement or steel strand.

PCI Design Handbook/Fifth Edition 1-31


The behavior of epoxy coated strand a t elevated- Galvanized Steei: In corrosive environments, hot.
temperatures is of concern due to softening of the dipgalvanizingof connection hardware is sometimes
epoxy. Putl-out tests [24] show that therej's a pro­ used. Connections should be designed to minimize
gressive reduction in bond strength initiating at about o r eliminate field weldingJf= galvanized; connections
125 °F with a virtually complete ioss of bond occur' are used. The-fumesfrem welded galvanized raateri-
ring at about 200 °F. These temperatures are fre­ al are very toxic and present a serious threat to the
quently reached during production. This behavior ne­ welder even with the u s e of protective equipment.
cessitates a careful monitoring, of concrete The process of welding destroys the protective coat­
temperature atiransfer of prestress. ing, requiring touch up with a zinc rich paint, so the
Because of the uncertainties in properties noted building owner has paid for hot dip galvanizing only to
above, particularly the behavior under elevated tem­ end up with a painted surface.
peratures, it is recommended that epoxy coated In order to ensure that the strength of the various
strand not be used for pretensioned, prestressed elements of a connection are not reduced by em­
concrete products. brittlement during the hot dip galvanizing process,
Corrosion Inhibitors. Corrosion inhibitors are used several precautions are recommended.
to extend the service life of concrete structures toy of­ When items of a connection assembly require
fering protection to embedded reinforcement against welding, such as anchor bars to plates, the following
chloride induced corrosion. Corrosion inhibitors are recommendations have been found to produce satis­
chemical admixtures that delay the initiation of corro­ factory results and are recommended by the Ameri­
sion and decrease the corrosion rate of steel in con­ can Hot Dip Galvanizers Association:
crete, without changing the concentration of the cor­
1. An uncoated electrode should be used when­
rosive agent.
ever possible to prevent flux deposits.
Chemical compounds classified as corrosion in­
hibitors by ACI 212 and ACI 222 are borates, chro­ 2. If a coated electrode is used, all welding flux
mates, molybdates, nitrites, and phosphates. Of residues must be removed by wire brushing,
these, calcium nitrite has been used successfully with flame cleaning, chipping, grinding, needle gun
precast and prestressed concrete since 1980. or abrasive blast cleaning. This is necessary
because welding flux residues are chembally
1.3.4.3 Protection of Connections inert in the normal pickling solutions used by
Painted Steel. In most building environments galvanizers; their existence will produce rough
painting of exposed steel in connections is sufficient and incomplete zinc coverage.
to prevent corrosion damage. There is a broad spec­ 3. A welding process such as metal-inert gas
trum of choices of paint systems from one coat of (MIG), tungsten-inert gas (TIG), or C 0 2shelled
primer to multicoat systems using zinc rich paint or arc is recommended when possible since they
epoxy systems. Long oil alkyds have the advantage produce essentially no slag.
of low cost surface preparation and the ease of ap­
plication and touch up. Their disadvantage is their 4. If special process welding is not available, se­
relatively short life span in corrosive conditions. lect a coated rod specifically designed for self-
Epoxy polyamidoamines have an extended life span slagging, as recommended by welding equip­
and are good in corrosive environments. Epoxy poly­ ment suppliers and refer to Item 2.
amidoamines have a higher material cost and surface
It should also be recognized that many parts of
preparation cost. Epoxy polyamidoamines are more
connection components are fabricated using cold
difficult to field touch up since they are a two part mix­
rolled steel or cold working techniques, such as
ture requiring controlled temperatures to apply. For
bending of anchor bars. In some instances, cold
both long oil alkyd and epoxy polyamidoamine sys­
working may cause the steel to become strain-age
tems the protection is lost once the surface is broken
embrittled. The embrittlement may not be evident un­
(scratch, incomplete coverage) since corrosion can
til after the work has been galvanized. This occurs
start undercutting adjacent areas. Zinc rich ure­
because aging is relatively slow at ambient tempera-
thanes minimize this problem by providing galvanic
tures-but is more rapid at the elevated temperature of
protection. Zinc rich urethane has the best corrosion
the galvanizing bath.
resistance and life expectancy and is relatively easy
It is recognized that any form o f cold working re­
to apply. The disadvantage of the zinc rich urethane
duces the ductility of steel. Operations such as
is that it comes in one color, brown. If other colors are
punching holes, notching, producing fillets of small
required epoxy or urethane paints may be used as a
radii, shearing and sharp bending may lead to strain-
top coat. Consult the local precast producers in the
age embrittlement of susceptible steels.
area for paint systems commonly used.

1-32 PCI Design Handbook/Fifth Edition


T h e following precautions are recommended by These precautions are also outlined in Ref. 6. An
the American Hot Dip Galvanizers Association: alternative to hot dip galvanizing is cold galvanizing:
using zinc rich paint.
1. S elect steel with a carbon content betow
Stainless-Steel. In highly corrosive-environments
0,25%.
stainless steel may be used for connections and
2. Choose steel with-low transition temperatures embedments. The AISI (American Iron and Steel In­
since-cold working raises the ductile-brittle stitute) 20Q and 300 series stainless steels contain
transition temperature and galvanizing (heat­ nickel and chromium and are essentially nonmagnet­
ing) may raise it even further. ic, and are referred to as austenitic stainless steels.
The AISI 200 series contains manganese in addition
3. For steels having a carbon content between to the nickel and chromium. The AISI 40Qseries con­
0.10% and 0.25% a bending radius of at least tain straight chromium and is referred to as ferritic
threetimes the section thickness (3t) should be stainless steel. They are magnetic and are less duc­
maintained. In some cases 6t yields even bet­ tile than the austenitic grades. AISI types 304 and
ter results. If less than 3t bending is unavoid­ 316 are the most commonly used in structural ap­
able, the material should be stress-relieved at plications. These types are a low carbon modification
1100 °F for one hour per inch of section thick­ of type 302 for limiting of carbide precipitation during
ness. welding. Type 316 has a higher corrosion resistance
4. Drill, rather than punch, holes in material thick­ than type 304 and is usually used for chemical han­
er than % in. If holes are punched they should dling equipment. There are types 304L and 316L
be punched undersize, then reamed an addi­ which are extra low carbon modifications of types 304
tional Vfe in. overall or drilled to size. and 316, respectively, and can be used where car­
bide precipitation is a problem. There are a limited
5. Edges of steel sections greater than % in. thick number of structural shapes and sizes available in
subject to tensile loads should be machined or stainless steel. Consult with the local steel suppliers
machine cut. for availability of different shapes and sizes.
Stainless steel can be welded by all common
6. In critical applications, the steel should be hot
methods, and the equipment used is basically the
worked above 1,200 °F in accordance with
same as that used for carbon steel.
steel makers recommendation. Where cold
The choice of electrodes should be made for com­
working cannot be avoided, stress-relieve as
patibility with the base metal. E308 electrode is used
recommended in Item 3 above.
with 304, E308L with 304L, E316 with 316, and E316L
with 316L When stainless steel and carbon materials
ASTM A 143 “Recommended Practice for Safe­
are to be joined, an E309 electrode should be used.
guarding against Embrittlement of Hot Dip Galva­
All stainless steel SMAW electrode coverings are
nized Structural Steel Products and Procedure for
of the low-hyd rogen type and must be protected from
Detecting Embrittlement" and CSA Specification
moisture. Electrodes should be purchased in
G164 “Galvanizing of Irregularly Shaped Articles,”
hermetically sealed containers, which can be stored
provide guidance on cold working and stress reliev­
for several months without deterioration. After open­
ing procedures. However, severe cold working of
ing, the electrodes should be reconditioned after 4
susceptible steels is better avoided, if at all possible.
hours of exposure.
Another area of concern is hydrogen embrittle­
Fillet welds should be designed using the same
ment. Hydrogen embrittlement is a duetile-to-brittle
guidelines as for carbon steel. Joints must be clean
change which occurs in certain high strength steels.
and dry. Moisture should be removed by heating or
Hydrogen released during the prickling operation,
by blowing with dry air. Slag needs to be thoroughly
prior to hot dipping, can cause this embrittlement.
removed and the weld completely cleaned before
This hydrogen can be absorbed into the steel during
starting a new pass. Only stainless steel wire brushes
the acid pickling, but at galvanizing temperatures it is
should be used for cleaning.
generally expelled from the steel.
Inspection of welds should include verification of
Hydrogen embrittlement is not common, but pre­
the proper electrode, proper storage of the electrode,
cautions should be taken if the steel involved has an
and operator certification, in addition to the non-de­
ultimate tensile strength exceeding approximately
structive testing required. The method and frequen­
150,000 psi, or if the pickling process is poorly con­
cy of testing should be as directed by the design en­
trolled, resulting irr long exposure to HCI. In those
gineer. Typically, the testing will be visual only.
cases, grit blasting is recommended instead of acid
pickling.

PCI Design Handbook/Fifth Edition 1-33


The welding of stainless steel produces more heat 8; “Architectural Precast Concrete,” Second Edi­
than conventional welding. That, andJhe fact th a t tion, MNL-122-89, Precast/Prestressed Gon-
stainless steel has- a coefficient of thermal expansion- creteInstitute, Chicago, IL, 1989.
greater than, structural steel can create adverse ex­
pansion of embedments during welding,Thus crack- 9. “Recommended Practice for Glass Rber Rein;
in g ’m the adjacentsonerete. Stainlesssteel embed­ forced Concrete Panels,” Third Edition,
MNL-128-93, Precast/Prestressed Concrete In­
ment edges should be -kept free from adjacent
concrete to allow expansion during welding without stitute, Chicago, IL, 1993.
spatting the concrete.
10. Abdel-Karim, A.M., and Tadros, Maher K.,
“Stretched-Out Precast Concrete I-Girder
1.3.4.4 Sulfate Attack Bridge Spans,” Concrete International, V. 13,
Chemical attack of concrete materials may occur No. 9, September 1991.
from sulfates found in ground water, soils, process­
11. ABAM Engineers, Inc. “Precast Prestressed
ing liquids, or sewage. The proper choice of cement
Concrete Horizontally Curved Bridge Beams,”
is particularly effective in resisting sulfate attack. ACI
PCI Journal, V. 33, No. 5, September-October
318-95, Sect. 4.3.1, and the references contained
1988.
therein, provide detailed guidance.
12. Ross Bryan Associates, Inc., “Recommended
1.4 References Practice for Precast Prestressed Concrete
Composite Bridge Deck Panels," PCI Journal,
V. 33, No. 2, M arch-April 1988.
1. “Reflections on the Beginnings of Prestressed
Concrete in America,” JR-H-81, Precast/Pre- 13. ACI Committee 363, “State-of-the-Art Report
stressed Concrete Institute, Chicago, 1L, 1981. on High-Strength Concrete,” ACI 363R-92, ACI
Manual o f Concrete Practice, Part 1, American
2. “Manual for Quality Control for Plants and Pro­ Concrete Institute, Farmington Hills, Ml.
duction of Precast and Prestressed Concrete
Products,” Fourth Edition, MNL-116-98, Pre- 14. Ahmad, Shuaib H., and Shah, S.P., “Structural
cast/Prestressed Concrete Institute, Chicago, Properties of High Strength Concrete and Its
II, 1998. Implications for Precast Prestressed Con­
crete.” PCI Journal, V. 30, No. 6, November-
3. “Manual for Quality Control for Plants and Pro­ December 1985.
duction of Architectural Precast Concrete Prod­
ucts,” Third Edition, MNL-117-96, Precast/Pre- 15. Pfeifer, D.W., Marusin, Stella, and Landgren,
stressed Concrete Institute, Chicago, IL, 1996. J.R., “Energy-Efficient Accelerated Curing of
Concrete,” Technical Report, TR-1-82, Precast/
4. Pfeifer, Donald W., Landgren, J.R., and Peren- Prestressed Concrete Institute, Chicago, IL,
chio, William, “Concrete, Chlorides, Cover and 1982.
Corrosion,” PCI Journal, V. 31, No. 4, Ju ly-A u ­
gust 1986. 16. “Building Code Requirements for Structural
Concrete,” ACI 318-95, and “Commentary,"
5. Chrest, A.P., Smith, M.S., and Bhuyan, S., ACI 318R-95, American Concrete Institute, Far­
“Parking Structures— Planning, Design, Con­ mington Hills, Ml, 1995.
struction, Maintenance and Repair.” Second
Edition, Chapman & Hall, New York, NY, 1996. 17. “Concrete Manual—A Manual for the Control of
Concrete Construction,” Eighth Edition, re­
6. “Parking Structures: Recommended Practice vised, U.S. Department of Interior, Bureau of
for Design and Construction,” MNL-129-88, Reclamation, Denver, CO, 1981.
Precast/Prestressed Concrete Institute, Chica­
go, IL, 1988. 18. “Cementitious Grouts and Grouting, ” E B 111T,
Portland Cement Association, Skokie, IL, 1990.
7. “Architectural Precast Concrete Cladding—Its
Contribution to Lateral Resistance of Build­ 19. “Corps of Engineers Specification for Non-
ings,” Proceedings, SP-CP, Precast/Pre­ Shrink Grout,” CRD-C588-78A, U.S. Army
stressed Concrete Institute, Chicago, IL, 1990. Corps of Engineers, 1978.

1-34 PCI Design Handbook/Fifth Edition


20. “Use ~of Epoxy Compounds with Concrete,” Strength erf -Epoxy-Coated Prestressing
ACI 503R^93, ACIManualof Concrete Practice, Strand ,” PCI Journal, \L 4T, No. 4, July-August.
Part 5, American Concrete Institute, Farming- 1996-
ton Hiiis, Ml.
25. “Architectural Precast C oncrete-C olor and
Texture Selection Guide,” First Edition,
21. “Post-Tensioning Manual;” Fifth Edition, Post-
CTG-92t Precast/Prestressed Concrete Insti­
Tensioning Institute, Phoenix, AZ, 1990.
tute, Chicago, IL, 1992;
22. “Manual o f Standard Practice,” 26th Edition,
26. “Concrete Sealers for Protection of Bridge
Concrete Reinforcing Steel Institute, Schaum­
Structures,” Report No. 244, National Coopera­
burg, IL, 1996.
tive Highway Research Program, Washington
DC, 1981.
23. “Structural Welded Wire Reinforcement Manu­
al of StandarcfPractice,” 4th Edition, Wire Rein­
27. “Structural Welding Code— Reinforcing Steel”
forcement Institute, McLean, VA, 1992.
AWS D1.4-92, American Welding Society, Mi­
ami, FL, 1992.
24. LeClaire, Philip J., and Shaikh, A. Fattah, “Ef­
fect of Elevated Temperature on the Bond

PCI Design Handbook/Fifth Edition 1 -35


1-36 PCI Design Handbook/Fifth Edition
9
CHAPTER 2
PRODUCT INFORMATION
AND CAPABILITY

2.1 General ................................................. 2 -2


2.1.1 Notation .............. 2 -2
2.1.2 Introduction........ ................................................................................. 2 -2

2.2 Explanation of Load Tables ............................................................................. 2 -3


2.2.1 Safe Superimposed L o a d ................................................................... 2 -3
2.2.2 Limiting Criteria.................................................................................... 2 -3
2.2.3 Estimated C am bers............................................................................. 2 -4
2.2.4 Design Parameters ............................................................................. 2 -4
2.2.5 Concrete Strength andUnit W e ig h ts.................................................. 2 -4
2.2.6 Prestressing S tra n d s........................................................................... 2 -5
2.2.7 Losses .................................................................................................. 2 -5
2.2.8 Strand Placement................................................................................ 2 -5
2.2.9 Columns and Load Bearing Wall Panels .......................................... 2 -5
2.2.10 Piles ...................................................................................................... 2 -6
2.2.11 References .......................................................................................... 2 -6

2.3 Stemmed Deck Members


Double Tee Load Tables.................................................................................. 2 -7

2.4 Flat Deck Members


Hollow-Core Slab Load Tables ..................................................................... 2 -2 5
Hollow-Core Slab Section P roperties........................................ 2-31
Solid Slab Load T a b le s.................................................................................. 2 -3 5

2.5 Beams
Rectangular Beams ........................................................................................ 2 -41
L-Beam s........................................................................................................... 2 -4 2
Inverted Tee B ea m s................................................. ..................................... 2 - 4 4

2.6 Columns and Load Bearing Wall Panels


Precast, Prestressed Colum ns.................................................................... 2 -4 7
Precast, Reinforced Colum ns......................................................................... 2 -4 9
Double Tee Wall Panels ................................................................................ 2-51
Hollow-Core and Sandwich Wall P a n e ls .......................... 2 -5 2
Solid and Sandwich Wall Panels................................................................... 2 -5 3

2.7 Piles
Piles................................................................................................................... 2 -5 5
Sheet P ile s....................................................................................................... 2 -5 6

PCI Design Handbook/Fifth Edition 2 — 1


PRODUCT INFORMATION AND CAPABILITY

2.1 General Pn nominal axial load strength of a com­


pression member at giveneccentric-'
ity
2.1.1 Notation
Pnb nominal axial load strength under
A =
cross-sectional area balanced conditions

Ag = gross cross-sectional area Pa ~~ nominal axialload strength of a com­


pression member with zero eccen­
b = width of compression or tension face
tricity
of member
Pu = factored axial load
bw = web width
s = section modulus
D = unfactored dead loads
Sb = section modulus with respect to the
©c ““ eccentricity of prestress force from bottom fiber of a cross section
the centroid of the section at the cen­
ter of the span St = section modulus with respect to the
top fiber of a cross section
ee eccentricity of prestress force from
the centroid of the section at the end t = thickness
of the span Vci nominal shear strength provided by
= specified compressive strength of concrete when diagonal cracking re­
f;
concrete sults from combined shear and mo­
ment
ft. = compressive strength of concrete at
Vow nominal shear strength provided by
time of initial prestress
concrete when diagonal cracking re­
fp s = stress in prestressed reinforcement sults from excessive principal tensile
at nominal strength of member stress in the web

fp u = ultimate strength of prestressing Vu = factored shear force


steel
v /s = volume-surface ratio
fs e = effective stress in prestressing steel
Yb = distance from bottom fiber to center
after losses
of gravity of section
% = specified yield strength of non-pre-
Yt distance from fop fiber to center of
stressed reinforcement
gravity of section
h = overall depth of member 5 = moment magnification factor
I = moment of inertia As/bd = ratio of non-prestressed ten­
P
L =■ unfactored live loads sion reinforcement

= span <l> = strength reduction factor


t

Mn = nominal moment strength of a mem­


ber 2.1.2 Introduction

= nominal moment strength under bal­ This chapter presents data on the shapes that are
Mnb
anced conditions standard in the precast, prestressed concrete indus­
try. Other shapes and modified standard shapes with
M0 = nominal moment strength of a com­ depth and width variations are also available in many
pression member with zero axial areas of the country. Designers should contact the lo­
load cal manufacturers in the geographic area of the pro­
= posed structure or project to determine the proper­
Mu applied factored moment at section
ties and dimensions of products available. This
N —
unfactored axial load section, plus the design methods and aids provided

2 -2 PCI Design Handbook/Fifth Edition


in other chapters of this Handbook, should enable 2.2.1 Safe Superimposed Load
the designer to carry oul-safe and economicahde^ The values for safe superimposed uniform service
signs. load are based-oathe capacity o f the member as gov-
These load tables are meant to be used for prelimi­ erned-by the ArdBuilding Code limitations omflexurai
n a r y design. The-limiting criteria for thesetables -ara strength, service load flexural stresses, orTin-the case
according to the ACI 318-95 SuMtng Code. For final of flat-deck, members without shear reinforcement,
design, the exceptions to stress limitations presented shear strength. A portion ofthe safe load shown is as-
in Sect. 10:5 of the handbook can be used. sumed to be dead load for the purpose of applying
load factors and determining cambers and deflec­
tions. For untopped deck members, TO psf of the ca­
pacity shown is assumed as superimposed dead
2.2 Explanation of Load Tables load, typical for roof members. For deck members
with topping, 15 psf of the capacity shown is as­
The load tables on the following pages show di­ sumed as superimposed dead load, typical of floor
mensions, section properties and load carrying capa­ members. The capacity shown is in addition to the
bilities of the shapes most commonly used through­ weight of the topping. For beams, 50% of the capacity
out the industry. These shapes include double tees, shown in the load table is assumed as superimposed
hollow-core and solid flat slabs, beams, girders, col­ dead load. Pretopped double tees are typically used
umns, piles and wall panels. The dimensions o f the for parking structures where superimposed dead
shapes shown in the tables may vary among loads are negligible. Thus all of the load shown in the
manufacturers. The variations are usually email and tables for 10DT26,10DT34,12DT30 and 12DT34 (as
the tables given here can still be used, particularly for well as corresponding LDT sections) is live load.
preliminary design. Manufacturers will in most cases
have their own catalogs with load tables and geomet­ Example: For an 8DT24/88-D1 untopped, (p.
ric properties for the members they produce. Hollow- 2 -9 ) with a 52 ft span, the capacity shown is 70 psf.
core slabs of different thicknesses, core sizes and The member can safely carry service loads of 10 psf
shapes are available in the market under various dead and 60 psf live.
trade names. Cross sections and section properties
of proprietary hollow-core slabs are shown on pages 2.2.2 Limiting Criteria
2-31 through 2 -3 4 . Load tables on pages 2 -2 5 The criteria used to determine the safe superim­
through 2 -3 0 are developed for non-proprietary hol­ posed bad and strand placement are based on
low-core sections of thicknesses most commonly Building Code Requirements for Structural Concrete
used in the industry. ACI 318-95. (This is referred to as “the Code,* “the
Load tables for stemmed deck members, flat deck ACI Building Code” or “ACI 318’ in this Handbook.)
members and beams show the allowable uniform su­ For design procedures, see Chapter 4 of this Hand­
perimposed service load, estimated camber at the book. A summary of the Code provisions used in the
time of erection, and the estimated long-term camber development of these load tables is as follows:
after the member time dependent deformations have
stabilized, but before the application of superim­ f . Capacity governed by design flexural strength:
posed live load. For deck members, except pre­ Load factors: 1,4D + 1.7L
topped double tees, the table at the top of the page
gives the information for the member with no topping, Strength reductbn factor, c|> = 0.90
and the table at the bottom of the page is for the same
Calculation of moments assumes simple
member with 2 in. of normal weight concrete topping
spans with roller supports. If the strands are ful­
acting compositely with the precast section. Values in
ly developed (see Sect. 4.2.3), the critical mo­
the tables assume a uniform 2 in. topping over the full
ment is assumed to be at midspan in members
span length, and assume the member to be un­
with straight strands, and at 0 A ( (( = span) in
shored at the time the topping is placed. Safe loads
products with strands depressed at midspan.
and cambers shown in the tables are based on the
(Note: The actual critical point can be deter­
dimensions and section properties- shown on the
mined by analysis, but will seldom vary signifi­
page, and will vary for members with different dimen­
cantly from 0.4€). Flexural strength is calcu­
sions.
lated using strain compatibility as discussed in
For beams, a single load table is used for several
Chapter 4.
sizes of members. The values shown are based on
sections containing the indicated number of pre­ 2. Capacity governed by service load stresses:
stressing strands. In some cases, more strands Flexural stresses immediately after transfer of
could be used. prestress:

PCI Design Handbook/Fifth Edition 2 -3


reinforcement must be provided, designed
a) Compression: G.6fd as described in Sect. 4.22.2.
b) End tension: W I T Note-3: For Stemmed Deck Members, the
c) r Midspan tension: Sv^T transverse (fiange) flexural -and shear
strengths and the service toad stresses are
Stresses at service loads, after all losses: not considered as limiting criteria. For
heavy uniform loads and/or concentrated
a) Compression: loads, these considerations may limit the
Extreme fiber stress in compression due to capacity or require transverse
reinforcement.
prestress plus sustained loads: 0.45fc
Note 4: Flat Deck Members show no values
Extreme fiber stress in compression due to
beyond a span/depth ratio of 50 for
prestress plus total load: 0.60fc
untopped members and 40 for topped
b) Tension: members. These are suggested
maximums for roof and floor members
Stemmed deck members and beams: respectively, unless a detailed analysis is
12v/fT made.

(Deflections must be determined based on


2.2.3 Estimated Cambers
bilinear moment-deflection relationships.
See Sect. 4.8.3.) The estimated cambers shown are calculated us­
ing the multipliers given in Sect. 4.8.5 of this Hand­
Flat deck members: 6
book. These values are estimates, and should not be
Critical point for service load moment is as­ used as absolute values. Attachment of non-structur-
sumed at midspan for members with al elements, such as partitions, folding doors and ar­
straight strands and at 0.4€ for members chitectural decoration to members subject to camber
with strands depressed at midspan, as de­ variations should be designed with adequate allow­
scribed above. ance for these variations. Calculation of topping
quantities should also recognize that the values can
3. Capacity governed by design shear strength: vary with camber.
Load factors: 1.4D + 1.7L
2.2.4 Design Parameters
Strength reduction factor, (|) = 0.85
The design of prestressed concrete is dependent
In flat deck members, since use o f shear rein­ on many variables. These include concrete strength
forcement is generally not feasible, the capac­ at release and at 28 days; unit weight of concrete;
ity may be limited by the design concrete shear strength grade, profile and placement of strand; jack­
strength. In this case, the safe superimposed ing tension and other. The load tables given here are
load is obtained by equating the correspond­ based on commonly used values; somewhat higher
ing factored shear force, Vu, to the lesser of 4*Vci allowable toads or longer spans may be achieved by
and (jjVc* (see Sect. 11.4.2 of ACI 318-95 and selecting other appropriate set of conditions. Howev­
Sect. 4.3 of this Handbook). er, in these cases, consultation with local producers
For stemmed deck members and beams, the is recommended.
design concrete shear strength is not used as a
limiting criterion since shear reinforcement can
be readily provided in such members. The de­ 2.2.5 Concrete Strength and Unit Weights
sign of shear reinforcement is illustrated in Twenty eight day cylinder strength for precast
Sect. 4.3. In stemmed deck members, usually concrete is assumed to be 5000 psi unless otherwise
minimum or no shear reinforcement (see Sect. indicated. Tables for units with composite topping
11.5.5 of ACI 318-95) is required. are based on the topping concrete being normal
weight concrete with a cylinder strength of 3000 psi.
Note 1: End stresses are calculated 50 strand
Concrete strength at time of strand tension re­
diameters from the end of the member, the
theoretical point of fufl transfer. lease is 3500 psi unless the value falls below the
heavy line shown (Note: this area is also shown as
Note 2: Release tension is not used as a limiting shaded) in the load table, indicating that a cylinder
criterion for beams. Supplemental top strength greater than 3500 psi is required. Novaiues

2-4 PCI Design Handbook/Fifth Edition


-are shown-when-the required release strength ex­ 2.2.8 Steand Placement
ceeds 45G0psi.
Quantity, size and profile of strands are shown in
The^eoncrete strengths used in theloadtables-are
the load tables under the column headed “Strand
n o t. Mended- to be iimitations-or recommendatfons-
Pattern”, for example, 88-S. The~ first digit indicates
for actual use. Some precast-concrete manufacturers
the total number of strands in the unit, the second
may- choose to use higher or tower concrete
digit Js the diameter-of the strand in 16thsof an inchr
strengths, resulting in slightly different load lable val­
(8/i6 equals 1/2 in. diameter), and the “S” indicates that
ues. For tow levels of prestress, the concrete release
the strands are straight. A “D1 * indicates that the
strength is usually governed by handling stresses.
strands are depressed at midspan. Some precast
Unit weight of concrete is assumed to be 150 pcf
producers choose to depress the strand at 2 points ,
for normal weight and 115 pcf for lightweight.
which provides a somewhat higher capacity.
For stemmed deck members and beams, the ec­
centricities o f strands at the ends and midspan are
shown in the load tables. Strands have been placed
so that the stress at 50 strand diameters from the end
2.2.6 Prestressing Strands (theoretical transfer point) will not exceed those spe­
cified above.
Prestressing strands are available in diameters For flat deck members, the toad table values are
from 1/4 in. to 0.6 in., grades 250 ksi and 270 ksi. The based on prestressing strand centered 11/2 in. from
predominant current use strand is the low-relaxation the bottom of the slab. Strand placement can vary
type; thus, the load tables are calculated for this type from as tow as 7A in. to as highas 2 Vs in.irom the bot­
of strand only. Since the relaxation toss of low-relax­ tom, which will change the capacity and camber val­
ation strand remains iinear up to an initial stress of ues shown. The higher strand placements give im­
0.75fpu [1], the tables have been developed assum­ proved fire resistance ratings (see Sect. 9.3 of this
ing this value of initial stress. Stress at transfer of pre­ Handbook for more information on fire resistance).
stress has been assumed at 90% of the initial stress. The lower strand placement may require higher re­
In developing the toad tables, the stress-strain be­ lease strengths, or top tension reinforcement at the
havior of the strand was modeled with the curves giv­ ends. The designer should contact the local supplier
en in Design Aid 11.2.5. These curves are of the same of flat prestressed concrete deck members for avail­
form as those used in previous editions of this Hand­ able and recommended strand placement locations.
book. However, changes in coefficients and the limit­
ing values were made for compliance with ASTM
2.2.9 Columns and Load Bearing Wall Panels
specification minimum values and for a better correla­
tion with experimental data. Interaction curves for selected precast, pre­
Other stress-strain models are also available and stressed columns, precast reinforced columns and
could be used in place of the curves used here. One various types of commonly used wall panels are pro­
such model has been validated by comparison with a vided on pp. 2 -4 7 to 2 -5 4 .
large number of tests [4]. This model and other valid These interaction curves are based on strength
stress-strain models are expected to produce allow­ design. Appropriate toad factors must be applied to
able toads which differ only slightly from the values the service toads and moments before entering the
calculated using the model depicted in Design Aid charts. The effect of slenderness is considered
11.2.5 and shown in the toad tables in this chapter. through magnification of moment as described in
Sect. 3.5.
For prestressed columns and wall panels, curves
are shown for both partially developed strands, usu­
ally appropriate for end moment capacity, and folly
2.2.7 Losses developed strands, usually appropriate for mid-span
moment capacity. This is discussed more completely
Losses were calculated in accordance with the in Sect. 4.9. The columns and wall panels which use
recommendations given in Ref. 2. This procedure in­ reinforcing bars assume full development of the bars.
cludes consideration of initial stress level (0.7fpu or The column curves are terminated at a value of Pu
higher), type of strand, exposure conditions and type = 0.80(f>Po, the maximum allowable toad for tied col­
of construction. A tower limit of 30,000 psi for low-re­ umns under ACI318-95. Most of the wall panel curves
laxation strands was used. This tower limit is arbitrary; show the tower portion of the curve only (flexure con­
other designers may choose not to impose this limit. trolling). Actual design loads will rarely exceed the
Additional information on tosses is given in Sect. 4.7. values shown.

PCI Design Handbook/Fifth Edition 2 -5


The curves for doubtsJee watt panels are fort>end- available in some areas for use in earth retaining
ing in the direction that causes tension in the stem. structures.
The curves forhottow-core walLpaneis are based on a
generic section as shown. They can be used with
2 .2 m References
small difference for atl-sections commonly marketed-
for watt panel use. 1. Martin, L.D., and Fellow, D .L, “Low-Relaxation
Strand-Practical Applications irrPrecast/Pre-
stressed Concrete,^ PCI Journal, V. 28, No. A,
July-A ugust 1983.
2.2.10 Piles
2. Zia, Paul, Preston, H.K., Scott, N.L., and Work­
man, E.B., “Estimating Prestress Losses,”
Allowable concentric service loads on prestressed
Concrete International, V. 1, No. 6, June 1979.
concrete piles, based on the structural capacity of the
pile alone, are shown in Table 2.7.1. The ability of the 3. PCI Committee on Prestressed Concrete Pil­
soil to carry these loads must be evaluated separate­ ing, “Recommended Practice for Design,
ly. Values for concrete strengths up to 10,000 psi are Manufacture and Installation of Prestressed
shown. The availability of these concrete strengths Concrete Piling,” PCI Journal, V. 38, No. 2,
should t>e checked with local manufacturers. The de­ M arch-April 1993.
sign of prestressed concrete piles is discussed in
Sect. 4.9.6 of this Handbook {3}. 4. Devalapura, Ravi K., and Tadros, Maher K.,
Section properties and allowable service load “Stress-Strain Modeling of 270 ksi Low-Relax­
bending moments for prestressed concrete sheet ation Prestressing Strands,” PCI Journal, V. 37,
pile units are shown in Table 2.7.2. These units are No. 2, M arch-April 1992.

2 -6 PCI Design Handbook/Fifth Edition


Strand Pattern Designation DOUBLE TEE SectioirProperties

8'-0" x 12" Untopped Topped


No. of strancf W

r~*
68-D1.
- straight D = depressed TJormal Weigftt Goncrete A
1
=
=
287
2,872
in*
in4

4,389 in4
Yb = 9.13 in. 10.45 in.
1--------No. o f depression points = 2.87 fa 3.55 in.
Yr
I------------- Diameter of strand in 16ths
s> = 315 fa 420 in3
st = 1,001 in3 1,236 in?
Safe loads shown include d ead load of TO
p sf for untopped m em bers and 15 p s f for wt = 299 plf 499 plf
topped members. Remainder is live toad. 37 psf 62 psf
Long-time cambers include superim posed VIS 1.22 in.
dead load but do not include live load.

Key Vc = 5,000 psi


178 — Safe superimposed service load, psf , — o vn nnn
0 .2 — Estimated camber at erection, in. V - 2 7 0 ,0 0 0 psi
0 .2 — Estimated iong-time camber, in.

8DT12
Table of safe superimposed service toad (psf) and cambers (in.) No Topping
Strand e.,in. Span, ft
Pattern ®e, tn. 12 14 16 18 20 22 24 2S 28 30 32 34 36 38 40 42 44

7.13
1W 137'W""62 61 45 34----------------------------------------------------
28-S 0.2 0.2 0.2 0.3 0.3 0.3 0.3
7.13
0.2 0.3 0.3 0.4 0.4 0.4 0.3
5.13
1SS 146 US 66 SS 55 43 34
48-S 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.7
5.13
0.5 0.6 0.7 0 7 0.8 0.7 0.7 0.6
3.13
165 126 6$ 76 82 ' 56 46 61
68-S 0.4 0.5 0.5 0.6 0.6 0.6 0.5 0.4
3.13
0.5 0.6 0.6 0.6 0.6 0.5 0.4 0.1
3.13 94 78 65 54 45 38 31
68-D1 1.4 1.5 1.6 1.6 1.7 1.7 1.6
6.63 16 1.7 17 1.6 15 1.3 1.0
1.13 38 32
88-D1 1.8 1.7
6.38 1.1 0.6

8DT12 + 2

Strength based on strain compatibility; bottom tension limited to se e pa g es 2 -2 -2 -6 for explanation.


Shaded values require release strengths higher than 3500 psi.

PCI Design Handbook/Fifth Edition 2 -7


strand Pattern Designation DOUBLE TEE Section Properties
No. of strand (6)
S = straight D-=- depressed 3 '-0 " x 12" Untapped Topped
u f ” Lightweight Concrete
68-D1 A = 287 in2- —
1 = 2,872 in'* 4,819 in4
n No. of depression points yt = 9.13 in. 10.82 in.
Diameter of strand in 16ths = 2.87 in. 3.18 in.
y*.
Safe loads shown include dead h a d o f 10- sb = 315 in3 445 in®
psf lor untopped members and 15 psf for -s, = 1,001 in3 1,515 in3
topped members. Remainder Js live load. wt = 2 29 plf 4 29 Plf
Long-time cambers include superimposed 29 psf 54 psf
dead load but do not include live load. V/S = 1.22 in.

Key
18 6 — Safe superimposed service load, psf fc = 5 , 0 0 0 p si
0.2 — Estimated camber at erection, in.
0 .3 — Estimated long-time camber, in. f pu = 2 7 0 , 0 0 0 p si

8LDT12
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand Span, ft
e«, In.
Pattern ®c,ln. 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
186 144 116 89 68 53 41 31
7.13
28-S 0.2 0.3 0.4 0.5 0.5 0.6 0.6 0.6
7.13
0.3 0.4 0.5 0.6 0.6 0.7 0.7 0.6
195 153 120 95 77 62 50 41 33
5 .1 3
48-S 0.6 0.7 0.8 1.0 1.1 1.2 1.3 1.3 1.3
5.13
0.8 0.9 1.1 1.2 1.3 1.3 1.4 1.3 1.2
169 133 106 86 70 57 47 39 32
3.13 0.8 0.9 1.0 1.0 1.1 1.1 1.1 1.0
68-S 0.6
3.13 0.8 1.0 1.1 1.1 1.1 1.1 1.0 0.8 0.5
72 61 52 45 38 33
3.13
68-D1 2.6 2.8 3.0 3.1 3.2 3.2 '
6.63 2.9 2.9 2.9 2.7 2.4 2.1

8LDT12+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping

Strand Span, ft
®e, In.
Pattern ®c, in. 12 14 16 18 20 22 24 26 28 30 32 34 36 38

7.13
26? Is ? 123 91 66 4? 33
28-S 0.2 0.3 0.4 0.5 0.5 0.6 0.6
7.13
0.2 0.3 0.4 0.4 0.4 0.3 0.2
175 134 103 80 62 48 36
5.13
48-S 0.7 0.8 1.0 1.1 1.2 1.3 1.3
5.13
0.7 0.8 0.8 0.7 0.6 0.5 0.2
162 126 99 79 62 47
3.13
68-S 0.8 0.9 1.0 1.0 1.1 1.1
3.13
0.7 0.7 0.6 0.5 0.3 0.1
72 59 46 33
3.13
68-D1 2.6 2.8 3.0 3.1
6.63 : 1.3 1.0 0.6 0.0 :■V ;

Strength based on strain compatibility; bottom tension limited to 12 see pages 2-2-2 - 6 for explanation.
Shaded values require release strengths higher than 3500 psi.

2 -8 PCI Design Handbook/Frfth Edition


Strand Pattem Designation DOUBLE TEE Section Properties
No. of strand (10)
S = straight D = depr-essed- 8 -0" x 24" Untopped Topped
Normal Weight Concrete =
A 401 in2 —
108-D1
J = 20,985= vin«- 27,720 in4
8'-0"
No. of depression points yb = 17.15- in. 19.27 in.
Diameter of strand; in 16ths A'-O" = 6.85 in. in.
2" yt 6.73

r- sb = 1,224 in® 1,438 in®


Safe loads shown include dead load o f 1 0
p sf for untopped m em bers and 15 p s f for s, = 3,063 in® 4,119 in®
wt = 418 ptf 618 plf
topped members. Remainder is live load.
Long-time cambers include superim posed 52 psf 77 psf
deadload but do not include live toad. V/S = 1.41 in.
- J L -3 %"
Key
173 — Safe superimposed service load, psf
0 .5 — Estimated camber at erection, in. f' = 5,000 psi
0 .7 — Estimated long-time camber, in. f pu = 270,000 psi

8DT24
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand ®«,ln. Span, ft


Pattern ®s, in. -30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74
11 1C 173 147 126 166 03 70 68 58 50 43 36 30
68-S 03 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.6 0.6 0.5
11 15
0.7 0.8 0.8 0.8 0.8 0.8 0.8 as 0.7 0.6 0.4 02
Q1C 180 155 134 116 100 6? 76 66 61 40 43 36 31
88-S 0.7 0.7 0.8 0.8 0.8 0.8 0.8 0.9 0.8 0.8 0.7 0.6 0.5
9 15
0.9 0.9 1.0 1.0 13 1.0 0.9 1.0 0.6 0.7 0.5 0.3 0.1
190 166 1 46 129 114 100 89 79 70 62 54 48 42 37 32
88-D1
9,15 1.1 1.2 1.3 1.4 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.2
1.5 1.5 1.6 1.7 1.8 1.8 1.8 1.8 1.7 1.6 1.5 1.4 12 0.9 0.5
145 129 116 103 92 83 74 66 59 53 47 42 37 32
108-D1
7.10 1.7 1.8 1J9 2.0 2.0 2.1 2.1 2.1 2.1 2.0 2.0 1.8 1.7 1.5
22 22 2.3 2.3 2.3 2.3 22 2.1 2.0 1.8 1.6 1.3 1.0 0.5
63 n 66 61 56 40 44 40 3S
128-D1 2.5 2.5 2.5 2.5 25 2.4 2.3 2.1 1.9
13^0
2.7 2.7 2.5 2.3 2.1 1.8 1.5 1.1 0.6
A OQ 61 66 “ 5T 45
148-D1 2.9 2.9 2.8 2.6
13.65
2.6 2.3 1.9 1.5

8DT24+2

Strength based on strain compatibility; bottom tension limited to 12/fjT; se e pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

PCI Design Handbook/Fifth Edition 2 -9


Strand Pattern Designation
DOUBLE TEE SectiorTProperties
- No. -at strand (10> Untopped Topped
8 -0" x 24"
- S = straight D —
LightweigbTConcrete A = 401 in * —
108-Q1 = 20,985 in4 2&,85? in4
!
________ 8'-0"'________
Vb- = 17.15 in. 19.94 in.
No. of tlepression points
. 2 '-c r 1 4'-0 "
Diameter of-strand in 16ths Yr = 6.85 in. 6.06 In .
2" = 1,224 in® 1 ,4 97 in3
Safe toads shown include d e a d load of 10 s, = 3,063 in3 4,926 in3
p sf for untopped m em bers and 15 p sf for =-
wt 320 p» 520 plf
topped members. Remainder is live load.
40 psf 65 psf
Long-time cam bers include superimposed
dead load but do not include live load. V/S = 1.41 in.
- 4 -« -3 % "
Key
1 1 8 — Safe superimposed service load, psf fc = 5,000 psi
1,1 — Estimated camber at erection, in.
1 .4 — Estimated long-time camber, in.
fpu = 270,000 psi

8LDT24
Table of safe superimposed service load (psfy and cambers (in.) No Topping
Strand Span, ft
Pattern ®c, in. 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80
US w 66 76 6$ 66 53 46 46 35 36
11.15
68 -S 11.15
1.1 1.2 1.2 1.3 1.3 1.4 1.4 1.4 1.3 1.3 1.2
1.4 1.4 1.5 1.5 1.5 1.5 1.4 1.4 1.2 1.0 0.8
144 126 110 97 86 76 67 59 53 47 41 36 32
9.15
88-S 1.2 1.3 1 .4 . 1.5 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4
9.15
1.6 1.6 1.7 1.8 1.8 1.8 1.8 1.7 1.6 1.5 1.3 1.6 0.7
176 156 139 124 111 99 89 80 72 64 58 52 47 42 38 34
9.15
88-D1 1.9 2.1 22 2 .4 2.5 2.7 26 2.9 30 3.0 3.1 3.1 3.0 3.0 2.9 2.8
14.40
2.4 2.6 2.8 2.9 30 31 3.2 3.2 3.2 3.1 2.9 2.8 2.6 2 .4 2.1 1.8
113 102 93 84 76 69 63 57 52 47 43 38 35 31
7.15
108-D1 33 3.4 36 3.7 3.8 3.9 4.0 4.1 4.1 40 39 3.8 3.6 3.4
14.15
3.9 40 4.1 4.1 4.1 4.0 3.9 3.8 3.5 3.2 2.8 2.4 1.9 1.3
65 56 54 56 45 41 S6 34
5.48
128-D1 4.8 4.9 4.9 4.9 4.8 4.7 4.5 4.3
13.9
4.7 4.5 4.2 3 .8 3.4 2.8 2.2 1.5
46 46
4.29
148-D1 5.6 5.5
13.65
3.8 3.2

8LDT24+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand ®«,tn . Span, ft
Pattern ®c, in. 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68
193 159 132 110 92 76 63 52 43 34
14.15
48-S 0.6 0.6 0.7 0.8 0.8 0.9 0.9 1.0 1.0 1.0
14.15
0.6 0.6 0.7 0.7 0.7 0.6 0.6 0.5 0.4 0.2

11.15
185 157 133 113 66 82 70 56 50 41 34
68 -S 11.15
0.9 0.9 1.0 1,1 1.2 1.2 1.3 1.3 1.4 1.4 1.4
0 .9 0.9 0.9 0.9 0.9 0.9 0.8 0.7 0.5 0.3 0.0
166 143 123 106 91 79 68 58 49 42 35
11.15
68-D1 1.2 1.4 1.5 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.0
14.65
1.2 1.3 1.3 1.3 1.3 1.2 1.1 0.9 0.7 0.5 0.2
200 175 153 134 117 103 90 79 70 61 53 46 40
9.15
88-D1 1 8 1.9 2.1 2 1 2.4 2.5 2.7 2.8 2.9 3.0 3.0 3.1 3.1
14.40
1.8 1.9 1.9 1.8 2.0 1.9 1.9 1.7 1.6 1.3 1.0 0.6 0 J2

7.15
106 64 84 74 66 58 51 45
108-D1 3.3 3.4 3.6 3.7 3.8 3.9 4,0 4.1
14.15
2.4 2.3 2.1 1.9 1.6 1.3 0.8 0.3
53 46
5.48
128-D1 13.90 • ■ '4.8 , 4.9
■ ; 0.7 0.1 ,
Strength based on strain compatibility; bottom tension limited to 12/fjT; see pages 2 -2 -2 -6 for explanation.
Shaded Values require release strengths higher than 3500 psi.

2 -1 0 PCI Design Handbook/Fifth Edition


Strand-Pattern Designation DOUBLE TEE Section-Properties
■ No.-oistrand ( 10)
8 -0 " x 32 " Untapped Topped
S = straight D = depressed
T T Normal Weight Concrete = 567 in2 —
A-
108-D1
8'-O'' \ = 55,464 in4 71,886 in4
•4-------------
1 1 _ No. of depression points Yb = 21.21 in. 23:66 in.
4 '-O'"
Diameter of strand-in 16ths < 2 = 10.79 in. 1034 in:
Yt
7 % " -^
2"
r - St, = 2,61& in3 3,038 in3
Safe loads shown include dead load of 10 1
psf for untopped members and 15 psf for st = 5,140 in3 -6;952 in3
topped members. Remainder is live load. I wt = 591 plf 791 plf
Long-time cambers include superimposed 74 psf 99 psf
dead load but do not include live load. V/S = 1.79 In.

Key
186 — Safe superimposed service load, psf
1 .4 — Estimated camber at erection, in.
1.8 — Estimated long-time camber, in. fc = 5,000 psi
fpu = 270,000 psi

8DT32
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Strand «.,in. Span, ft
Pattern ®c,in. 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94
iO Ail 166 167 161 136 123 H 1 1 W 66 62 73 66 56 53 47.0 46
128-D1 1.4 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.3 1.1 1.0 0.8
17.96
1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.6 1.5 1.3 1.1 0.8 0.5 0.2
197 179 162 147 134 121 110 100 91 83 75 68 61 55 49 44
148-01 1.6 1.7 1.7 1 .8 1.8 1.8 1.8 1.8 1.8 1.7 1.7 1.6 1.5 1.3 1.1 0.9
i/./l
2.0 2.1 2.1 2.2 22 2.1 2.1 1.9 1.9 1.8 1.6 1.4 12 08 0.5 0.1
188 171 156 142 130 119 108 99 90 82 75 68 62 56 51 46
ouCl 1.9 2.0 2.0 2.1 2.1 2.1 2.2 2.1 2.1 2.0 1.9 1.8 1.7 1.5 1.3 1.1
168-D1
2.4 2.5 2.5 2.5 2 .5 2.4 2.4 2.3 2.1 2.0 1.8 1.5 1.3 0.9 0.6 0.1
- 177 162 149 136 125 115 1 05 96 88 81 74 67 62 56 51
188-D1 2.2 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.3 2.3 2.2 2.0 1.8 1.6 1.4
2£ 2.8 2,8 2 .8 2 .7 2.7 2 .6 2.4 2.2 2.0 1.8 1.5 1.2 0.8 0.4
130 119 110 101 93 85 78 72 66 60 55 50
208-D1 2.6 2.7 2.7 2.6 2.6 2.5 2.4 2.3 2.1 1.9 1.7 1.4
3.0 3.0 2.9 2.7 2.5 23 2.0 1.7 1.4 1.0 0.5 0.0
105 97 89 81 74 67 te 5t 52
228-01 2.9 2.8 2.8 2 .7 2.5 2.4 2.2 2.0 1.7
1A 71
3.0 2.8 2.5 2.2 1.9 1.5 1.1 0.6 0.1

8DT32+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand ®*, in. Span, ft
Pattern ®c, in. 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80
1A 264 166 146 7 2 4 “ 16S & 64 *3 64 56 47
108-D1 1.0 1.1 1.1 1.2 12 1.2 1.2
1.3 1.3 1.2 1.2 1.1
18.21
1.1 1.1 1.1 1.1 1.0 1.0 0.7
0.9 0 :8 0.5 0.3 0.0
202 180 151 143 128 114 101 90 79 70 61
12.04 •L5 1.5 1.4
128-D1 1.3 1.4 1.4 1.5 1.5 1.5 1.5 U5
1X96
1.3 1.3 1.3 1.2 1.2 1.1 1.0 0.9 0.7 0.5 0 .2
192 173 155 139 125 112 100 89 80 71 63
148-D1 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.8 1.7
17 71
1.5 1.5 1.5 1.4 1.3 1.2 1.1 0.9 0.7 0.4 0.1
182 164 148 134 121 109 98 88 79 70
0.£l 1.9 2.0 2.0 2.1 2.1 2.1 2.2 2.1 2.0
168-D1 2-1
17 46
1.7 1.7 1.6 1.6 1.4 1.3 1.1 OS 0.6 0.3
170 154 140 127 115 104 94 85 76 68
O .U
188-D1 i* 7 O i 2.2 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2 .3 2.3
1.9 1.8 1.7 1.6 1.4 1.2 1.0 0.7 0.4 0.0

A 71 1STT o T & 90 31 ,7 2 ■'


208-D1 16.96 2 .6 2.7 2.7 2 .6 2 .6 2 .5 '' ■
1 .6 1 .4 1.1 0 .6 0 .4 0.0
Strength based on strain compatibility;-bottom tension limited to 12 s e e pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

PCI Design Handbook/Frfth Edition 2 -1 1


"Strand PatterrrDesignation
DOUBLE TEE Section Properties
No. of strand (1£fy Untopped Topped
«'-0"x32"
S = straight D -= depressed
Lightw eight Concrete A. 567 in2 —
108-D1 =
8'-0" I 55r464- in4 77,675 in4
Vb = 21.21 ia 2 4 .52 - in.
1------ No,, of depression points 4'-0 "
. r '° " , =
I------------Diameter strand in 16ths
7 % " -^
2" fe 10.79 in. 9,4& in.
V- s„ = 2 ,6 1 5 in* 3,167 in®
Safe toads shown include dead load of 19 st = 5,140 in3 8,197 in®
psf for untopped members and 15 psf for =
topped members. Remainder is live load. M wt 453 ptf 653 plf
32" 57 psf 82 psf
Longrtime cambers include superimposed
dead toad but do not include live load. V/S- = 1.79 in.

Key
1 5 0 — Safe superimposed service load, psf
2 .6 — Estimated cam berat erection, in. fc = 5,000 psi
3.2 — Estimated long-time camber, in.
fpu = 270,000 psi

8LDT32
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Strand e », in. Span, ft
Pattern ec, hi. 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98 100
1S6 13? 125 114 105 36 68 60 ?5 67 61 66 61 46 66 64
128-D1 2.6 2.7 2.8 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.7 2.6 2.4 2.2 2.0 1.7
17.96
3.2 32 35 3.3 3.2 3.2 3.1 3.0 2.9 ^ .7 2.5 2.3 2.0 1.7 1.3 0.8 0.2
176 161 148 136 125 114 105 97 89 82 75 69 64 58 53 49 45 41 37
9 .7 i
148-D1 29 30 31 32 3.3 3.4 35 3.5 35 3.5 35 3.4 3.3 3.2 3.1 2 .9 2.7 2 .4 2.1
3.6 3.7 3.8 3.8 3.9 3.9 3.9 3 .8 3.6 3.5 3.3 3.0 2.8 2.5 2.2 1.8 1.3 0.8 02
185 170 157 144 133 123 113 104 97 89 82 76 70 65 60 55 51 47 43 39
0.41 3.3 3.4 36 37 3.8 3.9 4.0 4.0 4.1 4.1 4.1 4.1 4.0 3.9 3.7 3.4 3.1 2.8 2 .5
168-D1 3.6
4.1 4.2 4.3 4.4 4.5 4.5 45 4.4 4.3 4.2 4 .0 36 3.5 3,1 2.7 2.3 1.9 1.3 0.8 0.1
129 119 110 102 95 8B 82 76 70 64. 59 54 50 47 44
D .M
188-D1 4.3 4.4 45 4.6 4.6 4.6 4.6 4.5 4.5 4.4 4.2 4.0 3.7 3.4 3.1
5.0 50 5.0 4.9 4 .7 46 4.3 4.1 3.7 3.3 2.8 2.2 1.7 1.1 0.4
100 92 85 79 73 67 62 57 5^ 48 44
O .rl
208-D1 i c oe 5.1 5.1 5.1 5.0 5.0 4.9 4.7 4.5 43 4.0 3.7
5.3 51 4.9 4.6 4.2 3.8 3.3 2.8 2.1 1.4 0.6
81 75 69 64 59 54 50
4 .w
228-D1 5.5 55 5.4 5.2 5.0 4.8 4.5
16.71
5.1 4.7 4.3 3.8 3.2 2.6 1.8

8LDT32+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand e«, in. Span, ft
Pattern ec, In. 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86
194 173 155 138 123 110 98 88 78 69 61 54 47 41
15.31
108-D1 1.8 18 2.0 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.3
18.21
1.8 17 1.8 1.8 1.8 1.7 1.6 1.5 1.4 1.2 1.0 0.7 0.4 0.1
195 175 158 142 128 115 104 94 84 76 68 60 54
12.04
128-D1 23 2.4 2.4 2.6 2.7 2.8 2 .9 2.9 2.9 2.9 2.9 2.9 2 .9
17.96
2.2 2.2 2.2 2.2 2.2 2.1 2.0 1.8 1.6 1.3 1.1 0.7 0.4
187 169 153 139 126 114 104 94 85 77 69 62 56
9.71
148-D1 2.8 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.5 3.5 3.5 3.5 3.4
17.71
2.6 2.6 2 6 2.5 2.5 2.4 2.2 2.0 1.8 1.5 1.1 0.6 0.2
178 162 148 135 123 112 102 93 85 77 70 63
8.21
168-D1 33 3.4 3.6 3.7 38 3.9 4.0 40 4.1 41 4.1 4.1 :
17.46
3.0 3.0 2.9 2.8 2.7 2.6 2 .4 2.1 1.8 1.5 1.1 0.6 '
118 108 99 9f 83 ?5 69
6.82
188-D1 4.3 4.4 4.5 4.6 4.6 4.6 4.6
17.21
2.9 2.7 2.4 2.1 1.7 1.3 0.8
6? 80 73 65
5.71
208-D1 5.1 5.1 5.1 5.0
16.96
1.9 1.5 0.9 0.3

Strength based on strain compatibility; bottom tension limited to 12 J ti; see pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

2 -1 2 PCI Design Handbook/Fifth Edition


Strand Pattern Designation DOtfBLETCE Section Properties
No. ahstrand (10)
TO'-O" x 24" Untopped Topped
S = straight" D = depressed^
i - r Normal Weight Concrete
A = 4 49—in* —
108J31-
I = 22,469 inf 29,396 in f
•4----------- 10 ’-0"
t L_ No. of depression points Yb = 17.77 irr. 16.89 in.
Diameter of strarrdin 16ths 2!S" % s'.°" i 2'-6" >
yt = 6.23 in . 6.11 in.
sb = 1,264 in3 1,478 in3
Safe loads shown include d e a d load o f 10 i _
p s f for untopped m em bers and 15 p sf for l ~ s, = 3,607 in3 4,812 in3
topped members. Remainder is live load. ' wt = 468 plf 718 plf
long-tim e cambers include superim posed 47 psf
dead load but do not include live load.
l v/s = 1 3 5 - in.
72 p sf

Key
136 — Safe superimposed service load, psf fc = 5,000 psi
0.5 — Estimated camber at erection, in.
0 .7 — Estimated iong-time camber, in. fpu = 270,000 psi

10DT24
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Strand ®«,In. Span, ft
Pattern 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74
11.77
136 115 97 64 ft 66 5i 46 3t
68-S 11 77
0.5 0.6 0.6 0.6 0.7 0.7 0.7 0.6 0.6 0.6
0.7 0.7 0.8 0.8 0.8 0.7 0.7 0.6 0.5 0.4
9 77 166 141 1^1 164 96 ft 6 'f 5^ 49 49 66 $1
88-S 9 77
0.6 0 .6 0.7 0.7 0.8 0.8 0.8 0 .8 0.8 0.6 0.7 0.6
0.8 0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.8 0.7 0.5 0.3

Q 77 199 172 149 130- 114 100 88 77 68 60 52 46 40 35 30


88-D1 1 * no 0.9 1.0 1.1 12 1.3 1.3 1.4 1.4 1.5 1.5 1.5 1.4 1.4 1.3 12
1.2 1.3 1.4 1.5 15 16 1.6 1.6 1.6 1.6 1.5 1.4 1.2 1.0 0.7

7 77 128 113 101 89 80 71 63 56 50 44 39 34 30


108-D1 77
1.6 1.7 1.7 1.8 1.9 1.9 2 .0 2.0 1.9 1.9 1.8 1.7 1.6
2.0 2.0 2.1 21 21 2.1 2.0 1.9 1.8 16 1.4 1.1 08

6 10
79 71 64 it 61 46 41 96 69
128-D1
14.52 2.3 24 2 .4 24 2.4 23 2.3 2.1 20
26 2.5 24 2.3 2.1 1.9 16 1.3 0.9
4.91 51 46 41 5? 63
148-D1
1427 2.8 2.7 26 2.5 2.4
2 .3 2.0 1.7 1.3 09

10DT24+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand ®.,ln. Span, ft
Pattern ®c,in. 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60
173 139 112 91 73 58 46 35
14.77
48-S 14.77
0.3 0.3 0.4 0.4 0.4 0.5 0.5 0.5
0.3 0.3 0.4 0.3 0 .3 0.3 0.2 0.1
196 162 134 111 91 75 62 50 40 32
11.77
68-S 0 .4 0.5 0 .5 0.6 0.6 0.6 0.7 0.7 0.7 0.6
11.77
0.5 0.5 0.5 0.5 0.5 0.4 0.4 0 .3 0.1 0.0
166 140 118 99 83 70 66 46 39 3l
11.77
68-D1 0.7 0.7 0.8 0.8 0.9 0.9 0.9 1.0 0.9 0.9
15.27
0.7 0.7 0.7 0 .7 0.6 0.6 0.5 0 .4 0.2 0.0
200 171 146 125 108 92 79 68 57 48 41
9.77
88-D1 0 .9 1.0 1.1 1.2 1.3 1.3 1.4 1.4 1.5 1.5 1.5
15.02
0.9 10 1.0 1.0 10 1.0 0.9 0 .8 . 0.7 0.5 0.2
141 123 107 93 81 70 61 52 44
7.77
108-D1 1.5 1.6 1.7 1.7 1.8 1.9 1.9 2 .0 2.0
14.77
1.3 1.3 1.3 1.2 1.1 1.0 0 .8 0 .5 0.2

6.10 70 61 53 46
128-D1 14.52 ■■■■ . 2 .3 ." 2 .4 . ! . 2 .4 ''.. 2 .4
1.0 0 .6 0 .4 0 .0

Strength based on strain compatibility; bottom tension limited to 12 TfT; see pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

PCI Design Handbook/Fifth Edition 2 -1 3


Strand Pattern Designation
DOUBLE TEE Section Properties
No. of strand (10)
S = straight D = depressed 1 0 -0 " x 24 " Untapped Topped

Lightweights oncrete A = 449“ im —


1S8D1
I = 22,469 in* 31,515 in*
-N o . of depression points Vb 17.77 in. 20.53 in.
-Diam eter of-strand in 16ths « 2''6" -5'-Q" 2 '-6 " (
-2" y. = 6.23 in. 5.47 in.
2"
Safe loads shown include dead load of 10 i _
53/4"-^ sb = 1,264 in3 1,535 in3
p sf for untopped mem bers and IS p sf for I -1 s, = 3,607 in3 5,761 in3
topped members. Remainder is live load. wt = 359 plf 609 Plf
2 4"
Long-time cambers include superimposed 36 psf 61 psf
d ea d load but d o not include live load. V/S = 1.35 in.

Key 3.3/4"
1 24— Safe superimposed service load, psf
fc = 5,000 psi
0 .9 — Estimated camber a t erection, in-.
1.1 — Estimated long-time camber, in. f pu = 270,000 psi

10LDT24
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Strand ®«,Jn. Span* ft
Pattern ®c,ln. 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76
124 106 92 80 69 60 52 46 40 34 30
11 77
68-S 11 77
0.9 1.0 1.1 1.1 1.2 1.2 1.3 1.3 1.3 1.3 1.2
1.1 1.2 1.3 1.3 1.4 1.4 1.4 1.3 1.2 1.1 0.9
150 130 113 99 86 76 66 58 51 45 40 35 30
88-S 1.0 1.1 1.2 1.3 1.4 1.5 1.5 1.5 1 .6 1.6 1.6 1.5 1.4
1.3 1.4 1.5 1.6 1.6 1.7 1.7 1.7 1.6 1.5 1.4 1.2 0.9
181 158 139 123 109 97 86 77 69 61 55 49 44 39 35 31
88-D1 1.6 1.7 1.9 2.0 2.2 2.3 2.4 2.6 2.7 2.7 2.8 2,8 2.8 2.8 2.8 2.7
2.0 22 2.3 2 .5 2.6 2.7 2.8 2.9 2.9 2.8 2.7 2.6 2.5 2.3 2.1 1.8
110 98 89 80 72 65 59 53 48 43 39 35 32
108-D1 T7 2.8 3.6 3.2 3.3 3.4 3.5 3.6 3.7 3.8 3.8 3.7 3.6 3.5
3.4 3.6 3.6 3.7 3.7 3.7 3.6 3.5 3.3 3.1 2.7 2.4 2.0
ft m 60 55 50 45 41 37 34 31
128-D1 4.4 4.5 4.6 4.6 4.6 4.5 4.4 4.2
14.52
4.4 4.2 4.0 3.7 3.3 2 .8 2.3 1.7
42 38
4.91
148-D1 14.27
5.4 5.3
3.8 3.2

10LDT24+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand ®», In. Span, ft
Pattern in. 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64
182 148 121 100 82 67 55 44 35
14.77
48-S 0.5 0.5 0.6 0.7 0.7 0.8 0.8 0.9 0.9
14.77
0.5 0.5 0.6 0.6 0.6 0.5 0.5 0.4 0 .3
171 143 1 2 0 1 0 0 84 71 59 49 41 33
11.77
68-S 11.77
0.7 0.8 0.9 1.0 1.1 1.1 12 1.2 1.3 1.3
0.7 0.8 0.8 0.8 0.8 0.8 0.7 0.6 0.4 02
177 149 127 108 92 79 67 57 48 40 33
11.77
68-D1 1.0 1.1 1.2 1.4 1.4 1.5 1.6 1.7 1.7 1.8 1.8
15.27
1.0 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.7 0.5 0.3
179 155 134 117 101 88 77 66 57 §0 43 36
9.77
88-D1 1.6 1.7 1,9 2.0 22 2.3 2.4 2.6 2.7 2.7 2.8 2.8
15.02
1.5 1.6 1.7 1.7 1-7 1.7 1.6 13 1,3 1.0 0.6 0.3
102 90 79 70 61 53 47 40
108-D1 7.77 2.8 3.0 3.2 3.3 3.4 3.5 3.6 3.7
14.77
22 2.1 2 .0 1.8 1.5 1.2 0.8 0.4
48 41
6.10
128-D1 4.4 4.5
14.52
0.7 0.1

Strength based on strain compatibility; bottom tension limited to 12 v'fT; see pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

2 -1 4 PCI Design Handbook/Fifth Edition


Strand Pattern designation DOUBLE TEE Section Properties
-"Nortjf-strand (10J
1D'-0 "x 32" Untopped Topped
It
108-Dl
- S = straight D ^depressed-
NormalWeight Concrete A = 615 in* —
10'-Q" 1 = 59,720: in* 77,131 in4
No. of depression.points 2'-6" ( S'-O" 2'-6" ( Yb = 21.98 in. 24.54- in.
Diameter of strand, in T6tbs Yt = 10:02 in. 9.46- in.
2"
sb = 2,717 in3 3,142 in3
tLmmmm * = 5,960 in3
Safe loads shown include dead load of 10 s, 8,149 in3
psf for untopped members and 15 psf for wt = 641 plf 891 Pit
topped members. Remainder is live load. 32 64 pst 89 psf
Long-time cambers include superimposed V/S -= 1.69 in.
dead load but do net include live load. __________ J
Key - J i U -4 % "
1 8 2 — Safe superimposed service load, psf
fc = 5,000 psi
1 .2 — Estimated camber at erection, in.
1 .6 — Estimated long-time camber, in. fpu = 270,000 psi

10DT32
Table of safe superimposed service load (psf) andcambers (in.) No Topping

Strand ®«, in. Span, ft


Pattern ®c, in. 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88
182 163 146 131 118 106 95 86 77 69 62 55 49 44 39
12.81
128-D1 1.2 . 1.3 1.3 1.4 1.4 1.4 1.5 1.5 1.4 1.4 1.4 1.3 12 1.1 1.0
18.73
1.6 1 .6 1.6 1.7 1.7 1.7 1.7 1.6 1.6 1.5 1.4 12 1.0 0.8 0.5
191 172 155 140 127 115 104 94 85 77 70 63 57 51 46 41
10.48 1.4 1.5 1.6 1.6 1.7 1.7 1.7
148-D1 1.8 1.7 1.7 1.7 1.6 1.5 1.4 1.3 12
18.48
1.8 1.9 1.9 2 .0 2 .0 2.0 2.0 1.9 1.9 1.8 1.7 1.5 1.4 12 0.9 0.5
199 180 163 148 134 122 111 101 92 84 76 69 63 57 52 46 42
8.98
168-D1 1.6 1.7 18 19 1.9 2.0 2.0 2.0 2.1 2.1 2.0 2.0 1.9 1.8 1.7 1.5 1.3
18.23
2.1 2.2 2.2 2.3 2.3 2 .3 2.3 2.3 22 2.1 2.0 1.9 1.7 1.5 1.2 0.9 0.5
140 127 117 107 97 89 81 74 68 62 56 51 46
7.59
188-D1 2.2 22 2 .3 2.3 23 23 23 23 22 2.1 2.0 1.8 1.7
17.98
2.6 2.6 2.6 2.6 2.5 24 2.3 2.1 2.0 1.8 1.5 1.2 0.8
110 101 93 85 78 72 66 60 55 50
6.48 2.5 2 .6 26 2.6 2.5 2.5 2.4 2.0
208-01 2.3 2.2
17.73
2 .9 2.8 27 26 2.4 2.2 20 1.7 1.4 1.0

5.57
&& bi ?5 6b tt bb bb
228-D1 2.8 2.8 2.7 2.6 25 24 22
17.48
2.9 2.7 25 22 19 1.5 1.2

10DT32+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand ®», In. Span, ft
Pattern ®e, In. 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76
179 157 138 121 106 92 81 70 60 52
16.08
108-D1 0.9 1.0 1.1 1.1 1.1 12 1.2 1.2 1.2 1.2
18.98
0.9 1.0 1.0 0.9 0.9 0.9 0.8 0.7 0.5 0.4
199 176 156 138 122 108 96 85 74 65 57
12.81 1.1 1.2 1.3 1.3 1.4 1.4 1.4 1.5 1.5 1.4 1,4
128-D1
18.73
1.1 12 1.2 12 1.1 1.1 1.0 0.9 0.7 0.6 0.4
186 166 148 132 118 1.5 94 83 74 65 57
148-D1 10.48 1.4 1.5 1.6 1.6 1.7 1.7 1.7 1.8 1.7 1.7 1.7
18.48
1.4 1.4 1.4 1.3 1.3 1.2 1.1 0.9 0.8 0.5 0.3
194 174 156 140 126 113 101 91 81 72 64
8.98 1.6 1.7 1.8 1.9 1.9 2.0 2.0 2.0 2.1 2.1 2.0
168-D1
18.23
1.6 1.6 1.6 1.5 1.5 1.4 1.3 1.1 0.9 0.7 0.5
145 131 118 107 96 86 77 69 62
188-D1 7.59 2.1 2.2 2.2 2.3 2.3 2.3 2.3 2.3 2.3
17.98
1.7 1.7 1.6 1.4 1.3 1.1 0.6 0.5 0.2
100 90 82 73 66
6.48
208-D1 17.73 2.5 2.6 2.6 2.6 2.5
1.4 12 0.9 0.6 02
Strength based on strain compatibility; bottom tension limited to 12 see pages 2-2-2-6 for explanation.
Shaded values require release strengths higher than 3500 psi.

PCI Design Handbook/Fifth Edition 2 -1 5


Strand Pattern Designation
DOUBLE TEE S ectio n Properties
I------------- No. of strand (10)
I — S = straight D - depressed T&'-Q" x 32 " Untopped Topped
Lightweight Concrete =
1Q&®4 A 615 in2 —
1Q'-0" J = in4 83,019
59,720 in4
No. of depression points 2 '-6 " S'-O" 2'-6 " ( = 2138 in. -25.40 in.
v*.
Diameter of strand in 16tbs = 10.02 in.
TV*"-*] yt 8.60 in.
L s„ =
Safe loads shown include dead load of
p s f for untopped m em bers an d 15 p s f for r 1 Sr =
2,717 in®
5,960 in3
3,268
9,652
in2
in3
to p p e d m em bers. R em ainder is live load. wt = 491 Pit 741 plf
V
Long-tim e cam bers include superim posed 32 49 psf 74 psf
d ea d load but d o not include live load. v/s = 1.69 in.
. i
Key 4 y / '- . - k
1 3 0 — Safe superimposed service load, psf
2.4 — Estimated camber at erection, in. fc = 5,000 psi
2.9— Estimated long-time camber, in. f pu = 270,000 psi

10LDT32
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Strand Span, ft
Pattern ®c, in. 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90 92 94 96 98
12.81 130 118 108 98 89 82 74 68 62 56 51 47 42 38 35 31
128-D1 18.73
2.4 2.5 2.6 2.7 2.7 2.7 2.8 2.8 2.8 2.7 2.7 2.6 2.5 2.4 2.2 2.0
2.9 3.0 3.0 3.0 3.0 2.9 2.9 2.8 2.7 2.5 2.3 2.1 1.8 1.5 1.1 0.6
153 139 127 116 107 98 89 82 75 69 63 58 53 49 44 40 37 33
10.48
148-D1 2.7 2.8 2.9 3.0 3.1 32 3.3 3.3 3.4 3.3 3.3 3.3 3.2 3.1 3.0 2.8 2.6 2.4
18.48
3.3 3.4 3.5 3.5 3.6 3.6 3.6 3.5 3.4 3.2 3.0 2.9 2.6 2.3 2.0 1.6 1.2 0.7
175 160 147 135 124 114 105 96 89 82 75 69 64 59 54 50 46 42 38 35
8.98
168-D1 2 .9 3.1 3.2 3.3 3.5 3.6 3.7 3.8 3.8 3.9 3.9 4.0 3.9 3.9 3.8 3.6 3.5 3.3 3.1 2.8
18.23
3.7 3.8 3.9 4.0 4.1 4.1 4.2 42 4.1 4.0 3.9 3.8 3.5 3.2 2.9 2.6 2.2 1.7 1.2 0.7
119 110 101 94 87 80 74 69 63 59 54 50 46 42 39 36
7.59
188-D1 4.0 4.1 4.2 4.3 4.4 4.4 4.4 4.4 4.4 4.4 4.3 4.1 3.9 3.7 3.4 3.1
17.98
4.7 4.7 4.7 4.7 4 .6 4.5 4.3 4.1 3.8 3 .5 3.1 2.6 2.1 1.6 1.0 0.4
84 78 72 67 62 58 53 48 44 41 38
6.48
208-D1 4.9 4.9 4.9 4.9 4.9 4.8 4.7 4.5 4.3 4.0 3 .7
17.73
5 .0 4.8 4.6 43. 4.0 3.6 3.1 2 .6 2 .0 1.3 0.6

5.57 70 64 59 55 5o 46 42
228-D1 17.48 5.4 5.4 5.3 5.2 5.0 4.8 4.6
4.8 4.5 4.1 3.6 3.0 2.4 1.6

10LDT32+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand Span, ft
Pattern ec, in. 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82
192 169 150 133 118 105 93 82 73 64 56 49 43
16.08
108-D1 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.1 2.2 2.2 2.2 2.3 2.3
18.98
1.5 1.5 1.6 1.6 1.6 1.6 1.5 1.4 1.3 1.2 1.0 0.8 0.5
188 168 150 135 121 108 97 87 77 69 61 55 48
12.81
128-D1 2.0 2.1 2.1 2.3 2.4 2.5 2.6 2.7 2.7 2.8 2.8 2 .8 2.8
18.73
1.9 2 .0 1.9 2.0 2.0 1.9 1.8 1.7 1.5 1.3 1.1 0.8 0.5
199 178 161 145 130 118 106 96 86 77 70 62 56 50
10.48
148-D1 2 .3 2.4 2 .5 2.7 2.8 2.9 3.0 3.1 3 .2 3.3 3.3 3.4 3.3 3.3
18.48
22 2.3 2.3 2.3 2.3 2.3 2.2 2.1 1.9 1.7 1.4 1.1 0.7 0.3
168 152 138 125 113 103 93 84 76 69 62 56
8.98
168-D1 2.9 3.1 3.2 3.3 3.5 3.6 3.7 3.8 3.8 3.9 3.9 4.0
18.23
2.7 2.7 2.7 2.6 2.5 2 .4 2 .2 2.0 1.8 1 .5 1.1 0.7

7.59 108 & 90 82 74 67 61 55


188-D1 17.98 4.0 4.1 4.2 4.3 4.4 4.4 4.4 4.4
2.7 2 .5 2.3 2.0 1.7 1.3 0.8 0.3
6.48 78 71 65 58
208-D1 4.8 4.9 4.9 4 .9
17.43
1.9 1.5 1.0 0.4
Strength based on strain compatibility; bottom tensbn limited to 12 /fT ; see pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

2 -1 6 PCI Design Handbook/Fifth Edition


Strand Pattern^Designation
DOUBLE TEE Section Properties
No. of strand (10)
12'-0" x 28 " Untapped Topped
:S - = straight D = depressed
NorraaF Weight Concrete =
A 640 in= —
108-D1 1 = 44,563 jn« 57,323 in *
= 20.21 in. 22.47 in.
■------ No. of depression points
----------- Diameter etstrand in 16ths = 7.79 Jn. 7.53- inr
yt
St, = 2,205 in3 2,551 in3
Safe loads shown include dead load of 10 s, = 5,722 in3 7,611 in3
p sf for untopped m em bers and 1-5 p s f for wt = 667 plf 967 plf
lo p p ed members. Remainder is live load.
56 psf 81 psf
Long-time cambers include superimposed
dead load but d o not include live load. v /s = 1.62 in.

Key
_JL_ 4%"

1 3 7 — Safe superimposed service load, psf fc = 5,0 0 0p si


0 .8 — Estimated camber a t erection; in.
1.1 — Estimated long-time camber, in. fpu = 270,000 psi

12DT28
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand ®», In. Span, ft


Pattern •e, In. 40 42^ 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84

10.02 137 120 105 92 81 71 62 54 47 41 35 ' 3(T 26


108-D1 17.02 0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.6 0.7 0.6 0.5
1.1 1.2 1.2 1.3 1.3 1.3 1.3 1.2 1.2 1.1 0.9 0.8 0.6
168 148 131 116 103 91 81 71 63 56 49 43 37 32 28
8.35 1.0 1.1 1.1 1 2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.0 0.9 0.8 0.6
128-D1 16.77
1.4 1.4 15 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.2 1.0 0.8
198 175 156 1 39 123 =110 98 88 78 70 62 55 49 43 38 33 29 25
7.1 6
148-D1 1.1 1.2 1.3 1.3 1.4 1.4 1.5 1.5 1.5 1.5 1.5 1.4 1.4 1.3 1,1 1.0 0.8 0.6
16.52
1.6 1.6 1.7 1.8 1.9 2.0 2.0 2.0 2.0 2.0 1.9 1.9 1.8 1.7 1.5 1.3 1.0 0.7
117 105 94 85 76 68 61 55 49 44 39 34 30 26
7.02 1.7 1.8 1.8 1.9 1.9 1.9 1.8 1.8 1.7
168-D1 1.6 1.4 1.3 1.1 0.8
16.27
2.4 2.4 2.5 2.5 2.5 2.5 2.4 2.3 22 2 1.8 1.6 1.3 0.9
5.63 ' 88 79 72 65 58 52 47 42 37 33 29 25
188-D1 16.02 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.7 1.5 1.3 1.0 0.7
2.8 2.8 2.8 2.7 2.6 2.5 2.3 2.1 1.8 1.5 12 0.8
67 61 55 49 44 40 36 32 28
4.52
208-D1 2.3 22 2.1 2.0 1.9 1.7 1.5 12 0.9
15.77
3.0 2.9 2.7 2.5 2.3 2.0 1.7 1.3 0.9

12DT28+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand ®«,ln. Span, ft
Pattern ®c,ln. 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76

10.02
130 112 36 82 76 5§ 56 41 54 27
108-D1 0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.8
17.02
0.9 0.9 0.8 0.8 0.8 0.7 0.6 0.4 0.3 0.0
164 142 124 107 93 81 69 60 51 43 35 29^
8.35 1.0 1.1 1.1 1.2 12 1.2 1.2 1.2 12 12 1.1 1.0
128-D1 16.77
1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 0.7 0.5 0.3 0.0
196 171 150 132 116 101 89 77 67 58 50 42 36 30
7.16 1.1 1.2 1.3 1.3 1.4 1.4 1.5 1.5 1.5 1.5
148-D1 1.5 1.4 1.4 1.3
16.52
1.2 1.3 1.3 1.3 1.3 1.3 1.3 12 1.1 0.9 0.7 0.5 0 2 -0 .1
108 95 84 74 65 56 49 42 35 30
7.02 1.8
168-D1 1.7 1.8 1.9 1.9 1.9^ 1.8 1.8 1.7 1.6
16.27
1.6 1.6 1.5 1.4 12 1.1 0.8 0.5 0.2 - 0 2
77 68 60 52 45 39 33 27
5.63
188-D1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.7
16.02
1.5 1.4 1.2 0.9 0.6 0.3 -0 .1 -0 .6

4.52 55 48 41 34 28
. 2.3 22 2.1 2.0 1.9
208-D1 15.77
1.0 0.6 0.3 -0 .2 -0 .7
Strength based on strain compatibility; bottom tension limited to 12 jf£ ; se e pages 2 -2 - 2-6 for explanation.
Shaded values require release strengths higher than 3500 psi.

PCI Design Handbook/Frfth Edition 2 -1 7


Strand Pattern Designation DOUBLE TEE Section Properties
No. of strand (10) -Untopped Topped
12 -G" X 28 "
S = s t r a i^ f D = depressed
Lightweight Concrete A = 64G in3 —
T08-D1 1 = - 4 4,563- in'1 -61,410 in4
Vf — 20i21 in. 23.19 in.
No. of depression points
Diameter of strand in TQhs. yt - — T79 in. 6.81 in.
Sb 2,205 irP 2,648 in3
Safe loads shown include dead load o f 10 s, = 5,722 in3 9,015 in3
p sf for untopped m em bers and 15-p s f for wt = 511 plf 811 plf
topped members. Remainder is live load.
43 psf 68 psf
Long-time cambers include superimposed
dead load but do not include live load. V/S = 1.62 in.

Key
L—4V4"
1 4 8 — Safe superimposed service load, psf
1 .4 — Estimated camber at erection, in.
fc = 5,000 psi
1 .9 — Estimated long-time camber, in. f piJ = 270,000 psi

12LDT28
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand Span, ft
e«, in.
Pattern ®c, in. 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84

10.02
146 161 116 w 66 62 73 66 56 62 46 41 36 32 26
108-D1 1.4 1.5 1.6 1.7
1.6 1.7 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.5 1.4
17.02
1.9 2.0 2.1 2.3
2.2 2.2 2.3 2.4 2.4 2.4 2.3 2.3 2.2 2.0 1.9
179 159 142 127 113 102 91 82 74 66 60 54 48 43 39 34 31 27
S.35 1.6 1.7 1.8 1.9 2.0 2.1 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.1 2.0 1.9 1.7
128-D1 16.77
1.2 2,3 2 .4 2.6 2.7 2.9 2.9 3.0 3.0 3.0 3.0 3,0 2.9 2.8 2.7 2.6 2.4 2.1

149 134 121 109 99 89 81 73 66 60 54 49 44 40 36 32 29 26


7.16 2 .2 2.3 2 .4 2.5 2.6 2.7 2.8 2.9 2.9 2.9 2.9 2.8 2.7 2.6 2.5 2.3 2.1 1.9
148-D1
16.52 3.0 3.1 3.3 3.4 3.5 3.6 3.7 3.8 3.8 3.8 3.7 3.6 3.4 3.2 3.1 2.6 2.5 22

96 87 79 72 66 60 54 49 45 41 37 33 30 27
7.02 3.3 3.4 3.5 3.5 3.6 3.6 3.6 3.6 3.5 3.3 3.2 3.0 2.7 2.4
168-D1 16.27
4.4 4.5 4.6 4.6 4.7 4.7 4 .8 4.5 4.3 4.1 3,8 3.5 3.2 2.8
69 63 58 53 48 44 40 36 33
5.63 4.0 4.0 4.0 40 3.9 3.8 2.2 3.5 3.2
188-D1
16.02
5.2 5 2 5.2 5.1 4.9 4.7 3.7 4.1 3.6
51 46 42 39
4.52 4.3 4.2 4.1 3,9
208-D1
15.77
5.4 5.2 5.0 4.6

12LDT28+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping

Strand Span, ft
®«,in.
Pattern ®e, In. 40- 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78
76 64 55 45 55 2?
CO

CM
CM

i n no 106 90
108-S 0.8 0.8 0.9 0.9 0.9 0.8 0.8 0.7 0.7 0.6
10.02
0.7 0.7 0.6 0.6 0,4 0.3 0.1 -0.1 - 0.4 -0 .7
m no 197 171 149 T3CT 115 96 64 74 64 56 47 40 55 26
108-D1 1.4 1.5 1.6 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.5
17.02
1.4 1.5 1.5 1.5 1.4 1.4 1.3 1.1 1.0 0.8 0.5 0.2 - 0.1 -0.5
176 154 135 118 103 90 78 68 58 50 43 36 30 25
128-D1 1.8 1.9 2.0 2.1 2.2 2.3 2.3 2.3 2.3 2.3 2.3 2.2 2.1 2
1.8 1.9 1.9 1.9 1.8 1.7 1.6 1.4 1.2 0.9 0.6 0.2 - 0 .2 - 0.7
178 157 138 122 107 94 82 72 62 54 46 38 32 27
148-D1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.9 2.9 2.9 2.8 2.7 2.6
2.2 2 2 2.3 2.3 2.2 2.2 2.1 1,9 1.7 1.4 1.1 0.6 0.2 - 0.4

7 M 98 87 76 67 58 50 43 36 30
168-D1 3.3 3.4 3.5 3.5 3.6 3.6 3.6 3.6 3.5
2.7 2.6 2.4 2.2 2.0 1.7 1,3 0.8 0.3
59 52 45 38 32 26
188-D1 4.0 4.0 4.0 4.0 3.9 3.8
16.02
22 1.8 1.4 1.0 0.4 -0.3
Strength based o n strain compatibility; bottom tension limited to 12 Jf[; s e e pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

2 -1 8 PCI Design Handbootc/Fifth Edition


Strand P attenr Designation DOUBLE TEE Section Properties
No. of strand (10)
S = straight D = depressed x 32 " Untopped Topped
NormalWeight Concrete
A = 690 in^ —
108-D1
1 = 64,620 in4 8 2 ,41 3 ^ m *
No. of depression points Fb = 22.75 in. 25.25 -in.
2" . 6 '- 0 " 1 , 3 '- 0 " t o"
Diameter of-strand in 16ths =
yt 9.25 in. 8 .7 5 - t e
L —H \* -m " j
Safe lossls-shown include d ead b a d of 10
p s ffo r untopped m em bers and 15 p s f for
topped members. Remainder is live load.
r \

\ f f t 32
S,
wt
=
=

=
2,840
6,986
719
in*
in3
plf
3,264
9,421
1,019
in3
in3
plf
Long-time cambers include superim posed
dead load but do n o t include live bad.
I x 3" CHAMFER
______ t v/s =
60
1.70 l a
psf 85 p sf

Key
— J L— 4%"

180 — Safe superimposed service load, psf fc = 5,000 psi


1 .0 — Estimated camber at erection, in.
1.3— Estimated long-time camber, in. fpu = 270,000 psi

12DT32
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand. Span, ft
®*, In.
Pattern ®c, In. 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84

11 no IM 159 142 126 112 166 69 69 71 65 56 49 45 56 55 29


128-D1 1.0 1.0 1.1 1.1 1.1 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.0 0.9 0.8 0.6
ts ^ o
1.3 1.4 1.5 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.3 12 1.0 0.8
189 169 151 136 122 109 98 88 79 71 64 57 51 45 40 35 31 27
1.2 1,2 1.3 1.4 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.3 1.2 1.0 0.8 0.7
148-D1 1-9,25
1.6 1.7 1.8 1.9 1.9 2 .0 2.0 2.0 2.0 2 .0 1.9 1.9 1.8 1.7 1.5 1.3 1.1 0.8

a 7B 160 144 130 117 106 96 87 78 71 64 57 51 46 41 37 32 28


168-D1 1 Q AA 1.6 1.6 1.7 1.8 1.8 1.9 1.9 1.9 1.9 1.8 1.8 1.7 1.6 1.5 1.3 12 0.9
2.2 2.3 2.3 2.4 2.5 2.5 2.5 2.5 2.4 2 .4 2.3 22 2.1 1.9 1.7 1.5 1.1

a ifi 110 100 91 83 75 68 62 56 50 45 41 36 32


188-D1 1ft 7R
2.0 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.6 1.4 12
2.8 2 .8 2.9 2 .9 2.8 2 .8 2.7 2.6 2.4 2.3 2.1 1.8 1.5

7 9K 86 78 71 65 59 64 49 44 39
208-D1 2 .4 2.4 2.4 2.3 2 .3 22 2.1 1.9 1.7
18.50
32 32 3.1 3.0 2 .9 2.8 2.6 2.4 2.1

e *a 68 62 56 51 46.
228-D1 26 25 2.5 2.3 2.2
18.25
3.4 3.3 3.1 2 .9 2.7

12DT32+2
Table of safe superimposed service load (psf) and cambers (in.) 2 " Normal Weight Topping

Strand S p a n , ft
®«, in.
Pattern ®c, in. 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84
W f74 152 w 117 T U T 69 78 67 56 56 42 55 29
128-D1 19,50 0.9 1.0 1.0 1.1 1.1 1.1 12 1.2 1.2 1.2 1.2 1.1 1.1 1.0
1.0 1.1 1.1 1.1 1.1 1.1 1.0 1.0 0.9 0.6 0.7 0.5 0.3 0.1
184 162 143 127 112 99 87 76 67 58 50 43 36 30
148-D1 1.2 :,i .2 1.3 1.4 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 1.3
1.3 1.3 1.3 1-4 1.3 1.3 1.3 1.2 1.1 0.9 0.8 0.6 0.4 0.1

O 7C 152 135 1 2 0 107 95 84 74 65 57 50 43 37 31 26


168-D1 1Q AA 1.6 1.6 1.7 1.8 1.8 1.9 1.9 1.9 1.9 1.8 1.8 1.7 1.6 1.5
1.6 1.7 1.7 1.6 1.6 1.5 1.5 1.3 1.1 0.9 0.7 0:4 0.1 - 0 .2

ft ftft 100 89 79 70 62 55 48 42 36 30 25
188-D1 10,75 2.0 2.1 2.1 2.1 2.1 2 .1 : 2.1 2.0 1.9 1.8 1.6
1.8 1.7 1.6 1.5 1.3 1 .1 . 0.9 0.6 0.2 - 0.1 - 0.6
7 9R 74 66 58 51 4fe 39 33 28
208-D1 10,50 2-4 2.4 2 .4 2.3 2 ,3 22 2.1 1.9
1.7 1.5 12 1.0 0.7 0.4 - 0.1 - 0 .5

6.34 54 48 41 35 28
228-D1 2.6 2 .5 , 2.5 2.3 2 .2 ;
18^25
1.1 0.6 0.4 0.0 - 0.5
Strength based on strain compatibility; bottom tensbn limited to 12 Jt£; see pages 2-2 —2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

PCI Design Hancfbook/Frfth Edition 2 -1 9


S tra n d P a tte rn D esignatfOrr
DOUBLE TEE SectionProperties
I--------------No. of strand (10)
^ j -------- S = straight D = depressed 12'-G" x 32" Utrtopped- Topped
Lightweight=eoncrete =
108-B1 A 690 in2 —

V = 64,620—in* 88,305 in*


1 2 - 0"
No. of depression-points Vb = 22.75 in. 26:08 in.
2" * 3 '- 0 " , TS'-O " 2"
Diameter of strand in 16ths = 9.25 in . 7.92 in.
I - t I - — 7%" Vt
L
Sate lo ad s - sh o w n in c lu d e d e a d lo a d o f 10
p s f for untopped m em bers and 15 p s f for
topped members. Remainder is live load.
r Tt 32
Sb
s,
wt
= 2;840 in3
=
=
6,986
551
3,386. in3
in3
plf
11,150
851
in3
plf
Long-time cam bers include superim posed 46 psf 71 psf
dead load but do not include live load. V/S = 1.70 in.*
4% "
Key
1 7 7 — Safe superimposed service load, psf
1 .2 — Estimated camber at ereetion, in.
fc = 5,000 psi
1 .6 — Estimated long-time camber, in. fpu = 270,000 psi

12LDT32
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Strand Span, ft
ilU
Pattern ®c, in. 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84

12.75
m TS T w 1& US T W §6 86 12 66 5$ 52 46 41 8/ 32 2b 2b
108-D1 1.2 1.3 1.4
1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.5 1.412
19.75
1.6 1.8 2.0 2.0 2.1 2 2 22
1.9 2.2 2.3 2.3 2.3 2.2 22 2.1 1.9 12 1.6
191 171 153 138 124 112 101 91 82 74 67 61 55 50 45 40 36 32 29 25
11.08 1.5 1.7 1.7 1.9 2.0 2.0 2.1 2.2 22 2.2 2.3 2.3 2.2 2.2 2.2 2.1 2.0 1.8 1.7 1.5
128-D1 19.50
2.1 2.2 2,3 2.5 2.6 2.7 2.6 2.9 2.9 2.9 2.9 2.9 2.9 2.9 2.8 2.7 2.5 2 .4 2.2 12
181 163 147 133 121 110 100 91 82 75 68 62 57 51 47 42 38 34 31 28
9.89 2.0 2.1 2.2 2.3 2.5 2.6 2.7 2 .7 , 2.8 2.9 2.9 2.9 2.6 2.8 2.7 2.6 2 .5 2.4 2.2 2.0
148-D1 19.25
2.7 2.9 3.0 32 3.3 3.4 3.5 3.6 3.7 3.7 3.7 3.7 3.6 3.5 3.4 3.3 3.1 3.0 2.7 2.5
117 107 98 90 82 75 69 63 58 53. 48 44 40 36
9.75 3.1 3.2 3.3 3.4 3.5 3.5 3.6 3.6 3.6 3.6 3.5 3.4 3.2 3.1
168-D1 19.00
4.1 4.3 4.4 4.5 4.6 4.7 4.7 4.7 4.6 4.5 4.3 4.1 3.9 3.7
87 80 73 67 62 57 52 48 44
8.36 3.9 4.0 4.0 4.1 4.1 4.1 41 4.0 3.9
188-D1 18.75
5.2 5.3 5.3 5.3 53 5.2 5.1 5.0 4.7
65 60 55 51 :
7.25 4.6 4.6 4.5 4.5
208-D1 18.50
6.0 5.9 5.8 53

12LDT32+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping

Strand Span, ft
®arln.
Pattern ®c, in. 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 60 82 84

186 166 146 128 112 55 8? 76 67 58 51 45 37 51 56


12.75
108-D1
t9 .7 5
1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.6 1.6
1.7 1.7 1.5 1.4
1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 1.0 0.8 0.6 0.3 0.0 - 0.4 -0 .8
196 173 153 135 119 105 92 81 71 62 54 47 41 35 29
11.08 1.7 1.9 2.0 2.0 2.1 2.2 2.2 2.2 2.3 2.3 2.2 2.2 2.2 2.1 2.0
128-D1 19.50
1.7 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.4 1.2 1.0 0.7 0.4 0.1 - 0.3
199 177 158 140 125 111 98 87 76 67 58 50 43 37 32 27
9.89 2.1 2.2 2.3 2.5 2.6 2.7 2.7 2.8 2.9 2.9 2.9 2.8 2.8 2.7 2.6 2.5
148-D1 19.25
2.2 2.3 2.3 2.3 2.3 2.3 2.2 2.1 2.0 1.8 1.5 12 0.9 0.5 0.1 - 0.4
130 116 103 92 81 72 63 55 48 41 35 29
9.75 3.1 3.2 3.3 3.4 3.5 3 .5 3.6 3.6 3.6 3.6 3.5 3.4
168-D1 19.00
2.9 2.8 2.8 2.7 2.6 2.4 2.2 2.0 1.6 1.2 0.7 0.2
84 74 66 58 51 44 3 8 , 32 26
8.36 3.9 4.0 4.0 4.1 4.1 4.1 4.1 4.0 3.9
188-D1 18.75
2.9 2.8 2.5 2.3 1-9 1.6 1.1 0.6 -0.1
53 46 40 34
7.25 4.6 4.6 4.5 4.5
208-D1 18.50
2.2 1.8 1.3 0.8
Strength based on strain compatibility; bottom tension limited to 12 /fT ; see pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

2 -2 0 PCI Design Handbook/Fifth Edition


Strand Pattern Designation PRETOPPED Section Properties
,------------- -No. of strand (10)
I r--------S = straight D = depressed DOUBLE TEE Normal Weight Lightweight

A = -689 ins 689 in3


J jCJB-DI 10 '-0 " x 26"
I = 30,716 i m - 30,716 in<
No. of depression points 10'-0" yb = 20.29 in. 20.29 in.
Diameter of strand in 16ths = 5.71 in- 5.71- in.
5 '-0 " Yt
« 2 '-6 ". M S'-6 "
Because these units are pretopped and are
4" sb = 1,514 in3 1,514 in3
5 % " - m I* - s, = 5,379 in3 5,379 in*
typically used in parking structures, safe I ,
loads shown do not include any superim­ wt = 718 pff 550 ptf
po sed dead loads . Loads shown are live
load. Long-time cambers do not include live
load.
I 3 3A "-* \
l V/S = 2:05
72 psf
in.
55
2.05
psf
in.

Vc = 5,000 psi
1 9 6 — Safe superimposed service load, psf
0 .4 — Estimated camber at erection, in. fpu = 270,000 psi
0 .5 — Estimated long-time camber, in.

10DT26
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand Span, ft
®», In.
Pattern ®c, in. 26, 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68
1 A 30 196 161 135"w 96 74 66 49 39 30
68-S 14 2^ 0.4 0.4 0.4 0.4 0.5 0.5 0.5 0.4 0.4 0.4
0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.5
10 0Q
i
169 142 119 Too- 83 69 57 47 36 36
88-S 12^9
0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.5 0.4
0.7 0.8 0.8 0.8 0.9 0.8 0.8 0.8 0.7 0.6
200 170 146 125 107 91 78 66 56 47 39 32
88-D1 0.7 0.8 03 0.9 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.8
1.0 1.1 1.2 1.3 1.3 1.3 1.4 1.4 1.3 1.3 1.2 1.0
189 163 142 123 10 } 93 80 69 60 51 43 36
108-D1 1.1 1.1 12 1.3 1.3 1.4 1.4 1.4 1.3 1.3 1.2 1.1
17.29
1.5 1.6 1.7 1.7 12 1.8 1.8 1.8 1.8 1.7 1.6 1.5

fl fiO 134 118 103 90 79 69 60 52 45 38 32


128-D1 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.3
2.1 2.2 2.3 2.3 2.3 2.3 2.2 2.1 2.0 1.9 1.7
7 A *i 96 67 76 67 59 51 45 36 33
148-D1 2.0 2.1 2.1 2.1 2.1 2.0 1.9 1.7 1.5
16 79
2.8 2.8 2.8 2.8 2.7 2.5 2.4 2.2 1.9

10LDT26
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand Span, It
®«,1n.
Pattern In. 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72

14.29
175 146 1 S T w 66 74 63 53 44 36 36
68-S 14.29 0.6 0.7 0.7 0.8 0.8 0.9 0.9 0.9 0.9 0.9 0.8
0.9 1.0 1.0 1.1 1.2 1.2 1.3 1.3 1.2 12 1.1

19 90 W 1 W T 3 T 113 97 63 71 61 52 44 37 31
88-S 12 29
0.8 0 .9 1.0 1.0 1.1 1.1 1.2 1.2 1.2 12 1.1 1.0
1.1 1.2 1.3 1.4 1.5 1.6 1.6 1.6 1.6 1.6 1.5 1.4
184: 159 138 120 105 92 80 70 61 53 46 39 34
88-D1 1.3 1.4 1.5 1.7 1.7 1.8 1.9 12 1.9 1.9 1.9 1.8 1.7
1.8 1.9 2.1 2.2 2.3 2.4 2 .4 2.5 2 .5 2.5 2.5 2.4 2.3

i n 90 177 155 137 121 106 94 83 73 65 57 50 44 38 33


108-D1 1.8 2.0 2.1 2.2 2.3 2.5 2.6 2 ,6 2.6 2.6 2.6 2.5 2.4 2.3
17 90
2.5 2.7 2.9 3.0 32 3.3 3 .4 3.4 3.4 3.4 3.3 32 3.1 : 3.0

302 w 93 63 74 66 " 5 ? " 69 46 4l 56 31


128-D1 17.04 3.0 3.1 32 3.3 3.3 3.4 3.3 3 .2 3.1 3.0 2.8
4.0 4.1 4.2 4.3 4.3 4.3 42 4.0 3.8 3.6 3.4
7 ,4 3 "73“ 65 56 69 ~ w 41 1 7
148-D1 1 6 /7 9
4 .0 4 .0 -4.0 4 .0 4 .0 3 .8 3 .6
5.3 5.3 52 5.1 5 .0 4 .7 4.3
Strength based on strain compatibility; bottom tension limited to 12/fT,' se e pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

PCI Design Handfaook/Rfth Edition 2 -2 1


SirancLPattem Designation PRETOPPED Section Properties
-No. of strand (10)
-S = "straight D = depressed DOUBLE TEE Normal Weight Lightweight

108-D1 tO '-O" x 34" A = 855 W 855 in2


1 = 80,780 in'1 80,780 in*-
, No. of depression points Yb = 25.07 in. -25.07 in.
1-------- Diameter of strand in 16ths =- -8.93 in. 8.93 in.
y.
sb = 3,222 ins- 3,222 in3
B e c a u s e th e s e u n its -a re p r e to p p e d a n d a re
typically used in parking structures, sate Si = 9,046 in3 9,046 in^
toads shown do not include any superim­ wt = 891 Plf 683 plf
posed dead toads. Loads shown are live 89 psf 68 psf
load. Long-time cambers do not include live V/S = 2.32 in. 2.32 in.
toad.

Key fc = 5,000 psi


172—Safe superimposed service load, psf fpu = 270,000 psi
0.9—Estimated camber at erection, in.
1.3—Estimated long-time camber, in.

10DT34
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand Span, ft
Pattern ®c,in. 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90
152 T3T 115 T5T 52 61 71 62 54 46 55 55
128-D1 21.82 0.9 1.0 id 1.0 1.0 1.0 1.0 0.9 0.9 0.8 0.7 06 0.5
1.3 1.3 1.3 1.4 1.4 1.4 1.3 1.3 12 1.1 0.8 0.6 0.9

1
185 165 147 131 116 104 92 81 72 63 55 48 41 35
148-D1 1.2 1.2 1.2 1.3 1.3 1.3 1.3 1.2 1.2 11 1.0 0 9 0.6 06
1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 12 1.0 0.8
l£ .U f
196 175 157 141 127 113 102 91 81 72 64 56 49 43 37 32
168-D1 1.4 1.5 1.5 1.6 1.6 1.6 T.6 1.6 1.6 1.5 1.4 1.3 1.2 1.1 0 9 0.7
1.9 2.0 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0- 1.9 1.8 16 1.4 1.1 0.8
181 163 147 132 119 108 97 87 78 70 62 55 48 42 37 32
188-D1 1.7 1.7 1.8 1.8 1.9 1.9 1.9 1.8 1.8 1.7 16 1.5 1.4 1.2 1.0 0.7
2.3 2.4 2.4 2.5 2.5 2.5 2.4 2.4 2.3 2.2 2.1 2.0 1.8 1.5 12 0.8
Oibf 184 167 151 137 124 112 101 91 82 74 66 59 53 47 41 36 31
208-D1 1.9 2.0 2.0 2.1 2.1 2.1 2.1 2.1 2.1 2.0 19 1.8 1.6 1.5 12 1.0 0.7
tV.oZ
2.6 2.7 2.8 2.8 2.8 2.8 2.8 2.7 2.6 2.5 2.4 2.3 2.1 1.9 1.6 1.2 0.7
TTET 127 115 166 55 S6 76 76 65 55 50 46 55 54
228-01 or\ m 2.3 2.3 2.3 2.4 2.3 2.3 2.3 2.2 2.0 1.9 1.7 1.5 1.3 1.0
3.1 3.2 3.2 3.1 3.1 3.0 29 2.7 26 2,4 2.1 1.9 1.5 1.1

10LDT34
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand Span, ft
®«, in.
Pattern In.46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86 88 90
13.40 185 165 w 1 W TST" W 98 66 79 71 65 56 58 44 59 34
128-D1 21.82 1.6 1.6 1.7 1.8 1.8 1.9 1.9 1.9 19 1.9 1.9 1.8 1.7 1.6 1.5 1.3
2.1 2.2 2.3 2.4 2.4 2.4 2.5 2.5 2.5 2.5 2.4 2.4 2.3 2.1 2.0 1.7

12.21 182 164 148 134 121 109 99 89 80 72 65 59 52 47 42 37 32


148-D1 2.0 2.1 2.2 2.3 2.3 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.2 2.1 1 9 1.8 1 6
21.57 2.7 2.8 2 9 3 3.1 3.1 3.1 3.1 3.1 3.1 3.0 2 9 2.8 27 2.5 2.3 2.0

12.07 192 174 158 144 131 119 108 98 89 81 73 67 60 54 49 44 39 35 31


168-D1 2.4 2.5 2.7 2.8 2 9 2.9 3.0 3.1 3.1 3.1 3.0 3.0 2.9 2.8 2.7 2.5 2.4 2.1 1 9
21.32 3.3 3.4 3.6 3.7 3.8 3.9 4.0 4.0 4.0 4.0 39 3.8 3.7 3.5 3.4 3.2 3.0 2.7 2.3

10.68 198 180 164 150 136 125 114 104 95 87 79 72 66 60 54 49 44 39 35


2.7 2.9 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.6 3.6 3.5 3.5 3.4 3.2 3.1 2.9 2.7 2.4
188-D1 21.07 3.8 3.9 4.1 4.2 4.4 4.5 4.5 4.6 46 46 4.6 4.5 4.3 4.1 4.0 3.8 3.5 3.3 29

9.57 141 129 118 109 100 91 84 76 70 64 58 53 48 43


36 3.7 3.8 3.9 4.0 4.0 4.0 4.1 4.0 3.9 3.8 3.6 3.4 3.2
208-D1 20.82 4.9 5.0 5.1 5.2 5.2 5.3 5.2 5.2 5.1 4.9 4.6 4.3 4.1 3.8
8.66 115 " W 95 87 66 74 67 69 56 51
228-Dt 20.57 4.4 4.4 4.5 4.5 4.5 4.5 4.4 4.4 4.2 4.0
5.8 5.9 59 59 5.8 5.7 56 5.4 5.1 4.7

Strength based on strain compatibility; bottom tension limited to 12/fT; see pages 2-2-2-S for explanation.
Shaded values require release strengths higher than 3500 psi.

2 -2 2 PCI Design Handbook/Fifth Edition


Strand Pattern Designation PRET0PPEO Section Properties
No, of strand'(10)
= straight ID = depressed DOUBLE. TEE Normal-Weight Lightweight
J r * A = 928 in2- 928 in2
108-Dt 12 -0 ” x 30"
1 = 59,997 ini 59S97 in*
No. of depression poinis 12' - 0 " = 22,94
Vb in. 22.94 in.
Diameter ofstrand in 16ths ■ e '- c r , t 3 '- 0 " p 4" = 7.06
yt in. 7.06 in.
Because these units ace pretoppedand are
— f * - 7%" 1 sb = 2,615 ins 2,6.15 in3
s, = 8,497 in2 8,497 in3
typically-used in parking structures, sale
loads shown do not include any superim­
ff wt = 967 plf 741 plf
30"
posed dead bads. Loads shown are live 3" GHAMFER 81 psf 62 psf-
load. Long-timecambers do not include live v/s = 2.30 in. 2.30 in.
load,
4% "
Key = 5,000 psi
167— Safe superimposed service load, psf
0.8— Estimated camber at erection, in. fpu - 270,000 psi
1.1 — Estimated long-time camber, in.

12DT30
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand Span, ft
®«, in.
Pattern ®e, In.40 42 44 46 48 50 52 54 56 58 60 S2 64 66 68 70 72 74 76 78 80 82
11.10 16? 145 126 H6 §5 62 71 61 62 44 a? 36
128-D1 19.25 0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.8 0.8 0.7 0.6 0.5
1.1 1.2 1.2 1.2 12 1.2 1.2 1.2 1.1 0.9 0.8 0.6
175
9.91 1.0 1.0 153
200 135 118 104 91 79 69 60 52 44 37 31 25
148-D1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 0.9 0.7 0.6 0.4
1927 1.3 1.4 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.3 12 1.0 0.7 0.4

9.77 182 161 142 126 111 98 87 76 67 58 51 44 37 31 26


168-D1 1.2 13 14 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 0.9 0.7 0.5
19.02 1.7 1.8 1.8 1.9 1.9: 1.9 1.9 12 1.8 1.7 1.6 1.4 1.2 0.6 0.9

8.38 145 129 102


114 90 80 71 62 54 47 41 35 30
188-D1 1.5 1.6 1.6 1.6 1.7 1.6 1.6 1.5 1.4 1.3 12 1.0 0.7
18.77 2.1 22 22 2.2 22 2.1 2.1 2.0 1.9 1.7 1.5 1.2 0.9
727 116 104 93 83 73 65 57 50 44 38 33 28
208-D1 1.8 1.8 1.8 1.8 1.8 1.8 1.6 1.5 1.4 1.2 0.9 0.6
18.52 2.5 2.5 2.5 2.4 2.3 2.3 2.1 1.9 1.7 1.5 1.1 0.7
6.36 94 84 75 67 60 53 46 40 35 30 25
228-D1 2.0 2.0 2.0 1.9 1.9 1.7 1.6 1.3 1.1 0.8 0.4
1827 2.7 2.7 2.6 2.5 2.4 2.2 1.9 1.7 1.4 0.9 0.4

12LDT30
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand ®», in.


Span, ft
Pattern ®c,ln. 40 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84
TSf w H F 135 m 96 6? // 66 52 46 46 34 29
11.10 1.6 1.6 1.7 1.6 1.5 1.4 12
128-D1 19.52 1.3 1.5 1.5 1.7 1.7 1.7 1.7 1.7
1.8 1.9 2.0 2.1 22 2.2 2.2 2.3 2.3 2.2 2.2 2.1 2.0 1.8 1.6
9.91 191 169 150 134 119 106 95 85 76 67 60 53 36 31 2747 41
148-D1 1.7 1.7 1.9 2.0 2.1 2.1 2.2 2.2 2.2 2.2 2.1 2.1 2.0 1.9
1.6 1.3 1.7
19.27 2.2 2.3 2.5 2.6 2.7 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.4
2.2 2.0 1.7
9.77 176 158 141 1 114 102 92 82 74 66 47 42 3759 53 32 28
168-D1 2.1 2.2 2.4 2.5 2.6 2.7 2.7 2.8 2.8 2.7 2.7 2.6
2.5 2.4 2.2 2.0 1.8
T9.02 3.5 3.4 3.3 32 3.0 2.8
2.9 3.1 3.2 3.3 3.4 3.5 3.6 3.6 3.6 2.5 22
8.38 117 106 96 86 78 70 63 57 51 45 40 36 31 27
188-D1 2.9 3.0 3.1 3.1 3.2 3.2 3.2 3.1 2.9 2.8 2.6 2.4 2.2 1.9
18.77 3.9 4.0 4.1 4.1 4.1 4.1 4.0 3.8 3.6 3.4 3.2 3.0 2.6 2.3

727 89 81 73 66 60 54 48 43 39 34 30
208-D1 3.5 3.5 3.5 3.5 3.5 3.4- 3.3 3.1 2.8 2.6 2.3
18.52 4.6 4.6 4.6 4.5 4.4 4.2 3.9 3.6 3.4 3.0 2.6

6.36 68 62 56 51 46 41 37
228-D 1 3 .9 3 .9 3.B 3 .7 3 .5 3 .3 3 .0
18.27
5.0 4.9 4.7 4.4 4.1 3.7 3.4
Strength b as e d on strain compatibility; bottom te n s b n limited to 12 J% ; see p ag es 2 - 2 - 2 - 6 for explanation.
Shaded values require release strengths higher than 3500 psi.

PCI Design Handbook/Rfth Edition 2 -2 3


Strand Pattern Designation
PRETOPPED Section Properties
No. o f strand (10>
S = straight I> = depressed DODBLETEE Normal Weight Lightweight

108-D4 1 2 -0 " x 34 " A = 9 7 6 in* 978 in*

CO
n
1 86,072 -in 4 Vn-»
. -No. of depression points 1 2 ' - 0 "
yb = 25.77 in. 25.77 irn

CO

o
----------- Diameter of strand in-16ths- 3 '— 0 " 4 "

I
• 6 ' ~ ° " yt = 8.23 -in. 8.23 in.
- * 1 h -— 7 3/ 4 " \ Sa = -3,340 -in3 3,340 in3
B e c a u s e th e s e u n its a r e p r e to p p e d a n d a re _________ _ -i-
typically used-in parking structures, s a fe \ s, = 10,458 in3 10,458 in3
bads shown do not include any superim­
posed dead loads. Loads shown are live |\ | f T T
3 4 "
wt = 1,019
85
plf
psf
781
65
plf
psf
load. Long-time cambers do not include live ____________________ L v/s = 2.39 in. 2.39 in.
load.
_J L_ 43/4"
Key
1 7 6 — Safe superimposed service load, psf fc = 5,000 psi
0 .8 — Estimated camber at erection, in. fpu = 270,000 psi
1.1 — Estimated long-time camber, in.

12DT34
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Span, ft
S trand e «, in.
Pattern ®c, in. 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86
176 155 135 11S 164 §1 7§ 53 53 51 45 35 35
14.10
128-D1 0.8 0.8 0 .9 0.9 0.9 0.9 0.9 0.8 0.8 0.7 0.7 0.6 no
22.52
1.1 1.1 1.2 12 1 .2 12- 12 12 1.1 1.0 0.9 0.7 0.6
187 165 146 129 114 101 89 78 68 60 52 44 38 32 26
12.91 1.0 1.0 1.1 1.1 1,1 1.1 1.1 1.1 1.1 1.0 1.0 0 .9 0.7 0.6 0.4
148-D1 22.27
1.4 1.4 1.4 10 1.5 1.5 1.5 10 1.5 1.4 1.3 1.1 1.0 0.8 0.5
196 174 155 138 123 1 1 0 97 86 76 67 59 52 45 39 33 28
12.77 1.3 1.3 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.3 1.2 1.1 1.0 0.8 0.6
168-D1 1.2
22.02
1.7 1.7 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.8 1.7 1.6 1.5 1.3 1.0 0.7
178 160 143 128 115 1-02 91 82 73 64 57 50 43 38 32 27
11.38 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.6 1.5 1.5 1.4 1.2 1.1 0.9 0.6
188-D1 21.77
2.0 2.1 2.1 2.2 22 22 2.2 2.2 2.1 2.0 1.9 1.8 1.6 1.4 1.1 0.7
131 118 106 95 85 76 68 61 54 47 41 36 31 26
10.27 1.8 1.9 1.9 1.9 1.9 18 1.8 1.7 1.6 1.5 1.3 1.1 0.9 0.6
208-D1 21.52
2.5 2.5 2.5 2.5 2.5 2.4 2.3 2.2 2.1 1.9 1.7 1.4 1.1 0.7
109 98 88 79 71 64 57 50 44 39 34 29
9.36 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.7 1.6 1.4 1.1 0.8
228-D1 21.27
2.8 2.8 2.8 2.7 2.6 2.5 2.4 2.2 2.0 1.7 1.4 1.0

12LDT34
Table of safe superimposed service load (psf) and cambers (in.) No Topping

Strand Span, ft
e«, in.
Pattern ®c, ln. 42 44 46 48 50 52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84 86

1a m 133 171 153 w 157 35 35 73 67 53 53 46 45 35 35 36


128-D1 00 R9 1.3 1.4 1.5 1.5 1.6 1.6 1.7 1.7 1.7 1.7 1.7 1.6 1.6 1.5 1.4 1.2 1.0
1.8 1.9 20 2.0 2.1 2.1 2.2 2.2 2.2 22 2.2 5 .1 2.1 2.0 1.8 1.6 1.3
182 162 146 130 117 105 94 85 76 68 61 54 48 42 37 33 28
148-D1 1.7 1.8 1.9 2.0 2.0 2.1 2.1 2.1 2.1 2.1 2.1 2.1 2.0 1.9 1.8 1.6 1.4
2.3 2.4 2.5 2.6 2.7 2.8 2.8 2.8 2.8 2.8 2.7 2.7 2.6 2.4 2.3 2.1 1.8
191 172 155 139 126 114 103 93 84 76 68 61 55 49 44 39 34 30 26
168-D1 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.6 2.5 2.4 2.3 2.1 1.9 1.6
2.8 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.5 3.5 3.5 3.4 3.3 3.2 3.1 2.9 2.7 2.4 2.1
144 131 119 108 98 89 81 73 66 60 54 48 43 39 34 30
188-D1 2.7 2.8 2.9 3.0 3.1 3.2 3.2 3.2 3.2 3.1 3.0 2.9 2.8 2.6 2.4 2.1
3.7 3.8 3.9 4.0 4.1 4.1 4.2 4.1 4.0 3.9 3.7 3.6 3.4 3.2 3.0 2.7
102 93 85 77 70 64 58 52 47 42 38
3.5 3.6 3.6 3.6 3.6 3.6 3.5 3.4 3.3 3.1 2.9
208-D1
4.6 4.7 4.7 4.7 4.7 4.6 4 .4 4 .2 3.9 3.7 3.5

G 4C 65 73 67 61 63 55 45
228-D1 4.1 4.1 4.1 4 .0 3.9 3.8 36
21.27
5.3 5.2 5 .2 5.0 4.8 4.6 4.2

Strength based on strain compatibility; bottom tension limited to 12 TfT; see pages 2 -2 -2 -6 for explanation.
Shaded values require release strengths higher than 3500 psi.

2 -2 4 PCI Design Handbook/Fifth Edition


Strand Pattern G esfgnation- HOLLOW-CORF Section P roperties-

7 6 -S 4 -0'' x 6 " Untopped Topped

Norm al W e ig h t Concrete A = 187 in^ —


S =-straight
1 = 763 in4 1,640 in4
Diameter of strand in 1€ths
No. of strand (7) yb = 3.00 in. 4.14 in.
4'-0” yt = 3.00 in. 3.86 in.
2" £«, = 254 in3 396 in3
Safe loads shown include dead load of-10.
p sf for untopped m em bers and 15 p s f for s, = 254 in3~ 425 in3

L^naaaaaon*-
topped members. Remainder is live load. bw = 16.00 in. 16.00 In.
Long-time cambers include superim posed wt = 195 plf 295 Plf
dead load but do not include five load. ------------------------------------------- ' - 1 49 psf 74 psf
Capacity of sections of other configura­ vys = 1,73 in.
tions are similar. For precise values, see
local hoHow-core manufacturer. fc = 5,000 psi
fd = 3,500 psi

3 0 6 — Safe superimposed service load, psf


0 .2 — Estimated camber at erection, in.
0.2 — Estimated long-time camber, in. 4HC6
Table of safe superim posed service load (psf) and cam bers (in.) N o Topping
Strand Span, ft
Designation
Code 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

306 257 217 184 157 135 116 100 87 75 65 56 48 42 36 30


66-S 0.2 0.2 0.2 02 0.2 0.2 0.2 0.2 02 0.2 0.1 0.1 0.0 - 0.1 - 0.2 - 0.4
0.2 0.3 0.3 0.3 0.3 0.3 0.2 0.2 0.1 0.1 0.0 - 0.2 - 0 .3 - 0.5 - 0.7 - 1.0
358 301 254 217 186 160 139 121 105 92 80 70 61 53 47 40 35
76-S 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0 .3 0.3 0.3 0.3 0.2 0.1 0.1 0.0 -0.1 —0 .3
0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.3 0.3 0.2 0.1 0.0 - 0.1 - 0.3 - 0.5 - 0.7 - 1.0
384 326 279 240 208 182 159 140 123 109 97 86 76 67 60 53 46 41
96-S 0.3 0.4 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.5 0 .5 0.5 0.4 0.3 0.3 0.1 0.0 - 0.1
0.4 0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.4 0.2 0.1 - 0.1 - 0.4 - 0.6 - 0.9
383 331 2 86 249 218 192 169 150 133 119 106 95 84 76 68 60 54
87-S 0.5 0.5 0 .6 0.6 0 .7 0.7 0.7 0.7 0.8 0.8 0.7 0.7 0.7 0.6 0.5 0.4 0 .3
0.6 0.7 0.7 0.8 0.8 0.9 0.9 0.9 0.8 0.8 0.7 0.7 0.5 0,4 0.2 0.0 - 0.3
364 317 277 243 214 189 168 150 134 120 107 96 87 78 70 62
97-S 0.6 0.7 0 .7 0.8 0.8 0.9 0.9 0.9 0.9 1.0 1.0 0.9 0.9 0.8 0.8 0.7
0.8 0:9 0.9 1.0 1.0 1.1 1.1 1.1 1.1 1.0 1.0 0.9 0.8 0.6 0.4 0.2

4HC6+2
Ja b le of safe superim posed service load (psf) and cam bers (in.) 2" Norm al W eight Top p in g
Strand Span, ft
Designation
C ode 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

305 258 220 188 162 139 119 97 78 62 47 35


66-S 0.2 0.2 Q.2 0.2 0.2 0 .2 0.2 0.2 0.1 0.1 0.0 - 0.1
0.2 0.2 0.2 0.1 0.1 0.0 - 0.1 - 0.2 - 0.3 - 0.5 - 0.7 - 0.9
358 304 260 224 194 168 146 122 101 82 66 52 39
76-S 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.1 0.1 0.0
0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.0 - 0 2 - 0.3 - 0.5 - 0.7 - 0.9
390 336 291 2 5 3 221 194 170 146 123 104 87 72 58 46 35
9 6-S 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.4 0.3 0.3 0.1 0.0
0.4 0.4 0.4 0.4 0.4 0.3 0.3 02 0.1 - 0.1 - 0.3 - 0.5 - 0.7 - 1.0 - 1.4
398 346 302 265 234 206 182 158 136 117 100 85 71 59 47
87-S 0.6 0.6 0.7 0.7 0.7 0.7 0.8 0.8 0.7 0.7 0.7 0.6 0.5 0.4 0.3
0.5 0 .6 0.6 0.6 0.5 0.5 0.4 0.4 0.2 0.1 - 0.1 - 0.3 - 0.5 - 0.8 - 1 2
382 335 294 260 231 205 181 157 137 119 102 88 75 63
97-S 0.7 0.8 0.8 0.9 0.9 0.9 1.0 1.0 0.9 0.9 0.9 0.8 0.8 0.7
0 .7 0 .7 0 .7 0 .7 0 .7 0.6 0.6 0 .5 0 .4 0.2 0.0 - 0 . 2 -o.s - 0 . 8
Strength based on strain compatibility; bottom tension limited to 6 see pages 2 -2 -2 -6 for explanation.

PCI Design Handbook/Fifth Edition 2 -2 5


Strand Pattern Designation HOLLOW-CORE Section Properties

76-S 4-0J' X 8" Untopped Topped


Normal Weight Concrete A = 215- if? —
1---------S ^straight
_____ Diameter of strand in 16ths I = 1-^56 10“ 3,071 im
--------------- N o. of strand (7) Vb = 4B 0 in. 5 .2 9 Jit.
y» = COO in. -4.71 in.
= 416 in3 580 in3
Safe loads shewn include d ea d ioad o f 10
p sf for untopped m em bers a n d 15 p s f for s, = 4 16 in3 652 in3
top ped m em bers. R em ainder is live toad. bw = 12.00 in. 12.00 in.
Long-tim e cambers^ include superim posed wt = 2 24 plf 324 Ptf
d ea d toad but do not include live load.
56 psf 81 psf
Capacity of sections of other configura­ V/S = 1.92 in.
tions are similar. For precise values, see
local hoJIow-core manufacturer.

Key
3 3 5 — SafeLSuperimposed service load, psf
0 .2 — Estimated camber at erection, in.
0 .3 — Estimated long-time camber, in.
4HC8
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Strand Span, ft
Designation
Code 14 15 16 17 t8 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

335 286 246 213 185 162 141 124 109 96 85 75 66 58 50 44 38 33


66-S 0.2 0.2 0.2 0.2 02 0.3 0.3 0.3 0.3 0.2 0.2 0.2 02 0.1 0.0 0.0 - 0.1 - 0.2
0.3 0.3 0.3 0.3 0.3 0 .3 0.3 0.3 0.3 02 0.2 0.1 0.0 - 0.1 - 0 2 - 0.3 - 0.5 - 0.7
375 337 291 252 220 193 170 150 133 118 105 93 83 73 65 58 51 45 39 34
76-S 0.2 0 .3 0 .3 0.3 0.3 0.3 0.3 0.4 0.4 0 .4 0.3 0 .3 0.3 0.3 0.2 02 0.1 0.0 - 0.1 - 0 2
0.3 0.3 0.4 0.4 0.4 0.4 0 .4 0.4 0.4 0.4 0.3 0.3 0.2 0.1 0.0 - 0.1 - 0 2 - 0.4 - 0.6 - 0.8
372 342 317 296 275 255 225 200 179 160 143 128 115 104 93 84 76 68 61 55 49 44 39
58-S 0.3 0.3 0.4 0.4 0.5 0.5 0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.5 0.4 0.3 0.2 0.1 0.0 - 0.1
0.4 0.5 0.5 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.6 0.6 0.5 0.4 0.3 0.2 0.0 - 0.2 - 0.4 - 0.6 - 0.9
351 326 302 284 266 250 236 218 196 176 159 143 130 117 107 97 88 80 72 65 59 54
68-S 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.7 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.7 0.7 0.6 0.5 0.4
0.6 0.6 0.7 0.8 0.8 0.9 0.9 0.9 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.8 0.7 0.6 0.4 0.2 0.0 - 0.2
360 335 311 290 272 256 242 229 215 205 188 170 154 141 128 117 106 97 89 81 74 67
78-S 0.5 0.6 0.6 0.7 0.7 0.8 0.9 0.9 1.0 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.9
0.7 0.8 0.8 0.9 1.0 1.0 1.1 1.2 1.2 1.3 1.3 1.3 1.3 1.3 1.3 1.2 1.2 1.1 1.0 0.9 0.7 0.5

4HC8+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand Span, ft
Designation
Code 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
309 267 231 201 175 153 133 117 102 89 77 67 55 44 33
66-S 0.2 02 02 0.3 0.3 0.3 0.3 0.2 0.2 02 0.2 0.1 0.0 OO - 0.1
0.2 0.2 0.2 0.2 02 0.1 0.1 0.0 - 0.1 - 0 2 - 0.3 - 0.4 - 0.6 - 0.7 - 0.9
316 275 241 211 185 163 144 127 112 99 87 74 62 50 40 31
76-S 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.3 0.3 0.3 0 .3 0.2 0.2 0.1 0.0 - 0.1
0.3 0.3 0.3 0.3 0.2 02 02 0.1 0.0 - 0.1 - 0.2 - 0.4 - 0.5 - 0.7 - 0.9 - 1.2
352 317 279 2 48 220 196 174 156 139 124 111 98 84 71 60 50 40 32
58-S 0.5 0.5 0.5 0.5 06 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.5 0.4 0.3 0.2 O.t 0.0
0.5 0.5 0.5 0.5 0.5 0.4 0.4 0.3 0.3 0.2 0.1 - 0.1 - 0 2 - 0.4 - 0.6 - 0.9 - 1.2 - 1.5
337 316 297 268 239 215 193 173 156 141 127 114 100 87 75 64 54 45 36
68-S 0.6 0.7 0.7 0.7 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.7 0.7 0 .6 0.5 0.4 0.2
0.6 0.6 0.7 0.7 0.7 0.6 0.6 0.6 0.5 0.4 0.3 0.2 0.0 - 0.2 - 0.4 - 0.6 - 0.9 - 1.2 - 1.6
346 325 306 286 271 252 227 205 186 168 152 138 124 111 98 86 76 66 56 47
78-S 0.7 0.8 0.9 0.9 1.0 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0 .9 0.7 0.6
0.8 0.8 0.8 0.9 0.9 0.9 0.9 0.9 0.8 0.8 0.7 0.6 0.5 0.3 0.1 - 0.1 - 0.3 - 0.6 - 0.9 - 1.3

Strength based on strain compatibility; pottom tension limited to 6 Jf£; see pages 2 -2 -2 -6 for explanation:

2 -2 6 PCI Design Handbook/Fifth Edition


Strand Pattern Designation
HOLLOW-CORE Section Properties

76-S- 4 -0 " x 8" Untopped Topped

Lightweight Concrete =
S - = straight A 215 in?' —

Diameter of strand-in 16tns I = 1,666 in'1 3 ,5 2 9 --in4


No. of strand (7) Yb = 4.00 in. 5.70 in.
= 4.00 in. 4130 in.
Yr
Safe b a d s shown include dead load of 10 sb 416 in? 619 in?
p sf for untopped m em bers and 15 p sf fo r s, = 415 in? 821 in?
topped members. Remainder is live load. bw = 12.00 in. 12.00 in.
Long-time cambers include superim posed wt = 184 pif 272 p1f
dead load but do not include live load.

CD
CO
Check availability of lightweight sectbns. T V/S = 1.92
46 gsf
in.
psf

Capacity of sections of other configura-


tions are similar. For precise values, see 'c — psi
local hollow-core manufacturer. fl = 3,500 psi
Key
3 4 6 — Safe superimposed service load, psf
0 .3 — Estimated camber at erection; in. 4LHC8
0.4 — Estimated long-time camber, in.
Table of safe superimposed service load (psf} and cambers (in.) No Topping
Strand Span, ft
Designation
Code 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
346 297 257 224 196 172 152 135 120 107 95 85 76 68 61 55 49 44 39 35
66-S 0.3 0.3 0.4 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.5 8 .5 0.5 04 0.4 0.3 0.3 0.2 0.1 0.0
0.4 0.4 0.5 0.5 0.5 0.6 0.6 0.6 06 0 .5 0.5 0.5 0.4 0.3 02 0.0 - 0.1 - 0.3 - 0.5 - 0.8
348 302 263 231 204 181 161 144 129 115 104 93 84 76 68 62 56 50 45 41 36
76-S 0.4 0.4 0.5 0.5 0.6 0 .6 06 0 C7 0.7 0 .7 0.7 0.7 0.7 06 06 0.6 0.5 0.4 0 .3 02 0.0
0.5 0.6 0.6 0.7 0.7 0.7 0.8 06 0.8 08 0.7 0.7 06 0.5 0.4 03 0.1 - 0.1 - 0.3 - 0 6 - 0 .9
350 325 304 286 265 236 211 189 170 154 139 126 114 104 95 86 79 72 66 60 55 50
58-S 0.5 0.6 0.7 0.7 0.8 0.8 0.9 0 .9 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 0.9 0.8 0.7
0.7 0.8 0.9 0.9 1.0 1.1 1.1 1.2 18 12 1.2 1.2 1.2 1.2 1.1 1.1 0.9 0.8 0.7 0.5 0.2 0.0
334 313 292 274 258 243 229 206 187 169 154 140 128 117 107 98 90 83 76 70 64
68-S 0.7 0.8 0.9 1.0 1.1 1.1 1.2 1.3 1.3 1.4 1.5 1.5 1.5 16 1.6 1.6 1.6 1.6 1.5 1.5 1.4
1.0 1.1 1.2 1.2 1.3 1.4 1.5 1.6 16 1.7 1.7 1.7 1.7 1.7 1.7 1.6 1.5 1.4 1.3 1.1 0.9
343 319 301 283 267 249 237 225 212 197 181 165 151 139 127 117 10& 100 92 85 78
78-S 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.7 1.8 1.9 2 .0 2.0 2.1 2.1 2.1 22 22 2.1 2.1
1.2 1.3 1.4 1.5 1.6 1.8 1.9 2.0 2.0 2.1 2.2 22 2.3 2.3 2.3 2.3 22 22 2.1 2.0 1.8

4LHC8+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand Span, ft
Designation
Code 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
320 277 242 211 186 163 144 127 113 100 88 78 69 60 53 45
66-S 0.4 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.5 0.5 06 0.4 0.4 0.3 0.3 0.2
0.4 0.5 0.5 0.5 0.5 0.4 0.4 0.3 0.3 02 0.0 - 0.1 - 0.3 - 0 6 - 0.7 - 1.0
327 286 251 222 196 174 155 138 123 109 98 87 77 69 61 52 43
76-S 0.5 0.5 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 06 0.6 0.6 0.5 0.4 0.3
0.6 0.6 0.6 0.6 0.6 06 06 0 .5 0.4 0.3 02 0.1 - 0.1 - 0.3 - 0.6 - 0.9 - 1.2
327 290 258 231 206 185 167 150 135 122 110 99 90 81 72 62 53 45
58-S 0.8 0.8 0.9 06 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1,0 1.0 1.0 0.9 0.8 0.7
0.9 0.9 1.0 1.0 1.0 1.0 0.9 0.9 0.8 0.7 06 0.4 0.2 0.0 - 0 2 - 0 5 - 0.9 - 1.3
323 304 278 250 225 204 184 167 151 138 125 114 103 93 83 73 64 56 48
68-S 1.1 1.1 1.2 1.3 1.3 1.4 1.5 1.5 1.5 1.6 16 1.6 16 16 1.5 1.5 1.4 1.3 12
1.2 1.3 1.3 1.4 1.4 1.4 1.4 1.3 1.3 12 1.1 0.9 0.8 0.6 0.3 0.0 - 0.3 - 0.7 - 1.2
332 313 297 279 263 238 216 197 179 163 149 136 125 113 102 91 81 72 64
78-S 1.3 1.4 1.5 1.6 1.7 1.7 1.8 1.9 2.0 2.0 2.1 2.1 2.1 22 22 2.2 2.1 2.1 2.0
1.5 1.6 1.7 1.7 1.8 1.8 1.8 1.8 1.8 1.8 1.7 1.6 1.5 1.3 1.1 0.9 0.6 0.2 - 0.1

Strength based on strain compatibility; bottom tension limited to 6 /fT ; see pages 2 -2 -2 -6 for explanation.

PCI Design Handbook/Fifth Edition 2 -2 7


Strand Pattern D e s ig n a tio n HOLLOW-CORE Section Properties

7 6 -S 4 -0" X 10"' Untapped Topped

iti 1---------S = straight


Normal Weight Concrete
A = _259 in s
_______rD 'ia m e te ro f-s tra n d in 16ths- 1 = 3,223 in« 5t328- -m*-
--------------- No. o f strand (7) yb = 5.00 in. 6.34 in.
y. = 5.00 in. 5.66 in.
Safe loads shown include dead load of 10 S„ = 645 in» 8 4 0 in3
p s f for untopped m em bers and 75 p s f for S, = 645" in3 941- in3
topped members. Remainder is live load. b» = 10.50 in. 10.50 in.
Long-time cambers include superimposed ~wt = 270 plf 370 plf
dea d load but d o not include live load.
68 psf 93 psf
Capacity of sections of other configura­ V/S = 2.23 in.
tions are similar. For precise values, see
local hollow-core manufacturer.

Key
2 3 9 — Safe superimposed service load, psf
0 .3 — Estimated camber at erection, in.
0 .4 — Estimated long-time camber, in.
4HC10
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Strand Span, ft
Designation
Code 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
239 212 188 168 150 134 120 107 96 86 76 68 61 54 48 42
48-S 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 02 0.2 0.2 0.1 0.1 0.0 - 0.1
0.4 0.4 0.4 0.4 0.4 0.4 0.3 0.3 0.2 02 0.1 0.0 - 0.1 - 0.2 - 0.3 - 0.5
280 263 245 219 197 177 160 144 130 118 107 96 87 79 71 64 58 52 46 41
58-S 0.4 0.4 0.4 0.5 0.5 0.5 0.5 0 .5 0.5 0.5 0.5 0.4 0.4 0.4 0.3 0.2 02 0.1 0.0 - 0.1
0.5 0.6 0.6 0.6 0.6 0.6 0 .6 0.6 0.6 0.5 0.5 0.4 0.3 0.2 0.1 0.0 - 0.1 - 0.3 - 0.5 - 0.7
289 272 255 242 231 217 199 180 164 149 136 124 113 103 94 86 78 71 64 58 53 48 43
68-S 0.5 0 .5 0.6 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.6 0.6 0.5 0.5 0.4 0.3 0.2 0.1 - 0.1
0.7 0.7 0.8 0.8 0.8 0.8 0.9 0.9 0.9 0.9 0.8 0.8 0.7 0.7 0.6 0.5 0.4 0.2 0.1 - 0.1 - 0.3 - 0.6 - 0.8
298 278 264 248 237 223 214 203 193 179 164 150 138 126 116 106 98 90 82 75 69 63 57
78-S 0.6 0.7 0.7 0.7 0.6 0.8 0.9 0.9 0.9 0.9 0.9 1.0 1.0 1.0 0.9 0.9 0.9 0.8 0.8 0.7 0.6 0.5 0.4
0.8 0.9 0.9 1.0 1.0 1.1 1.1 1.1 1.1 12 1.2 1.1 1.1 1.1 1.0 1.0 0.9 0.8 0.6 0.5 0.3 0.1 - 0.1
287 270 257 243 229 220 209 199 189 183 174 162 149 137 126 117 107 99 91 84 78 71
88-S 0.8 0.8 0.9 0.9 1.0 1.0 1.1 1.1 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.0 0.9
1.0 1.1 1.2 1.2 1.3 1.3 1.4 1.4 1.4 1.5 1.5 1.5 1.5 1.4 1.4 1.3 1.3 12 1.1 0.9 0.6 0.6

4HC10+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand Span, ft
Designation
Code 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
293 258 229 203 181 161 143 127 113 101 89 79 69 60 50
48-S 0.3 0.3 0.3 0.3 0.3 0.3 0 .3 . 0.3 0.3 0.2 0.2 0.2 0.1 0.1 0.0
0.3 0.3 0.3 0.2 0.2 0,2 0.1 0.1 0.0 - 0.1 - 0.2 - 0.3 - 0.4 - 0.6 - 0.8
297 268 241 216 194 175 157 142 128 115 103 92 79 68 58 48
58-S 0.4 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.4 0 .4 0.4 0.3 0.2 0.2 0.1
0.4 0.4 0.4 0 .4 0.4 0.3 0.3 0.2 0.1 0.0 - 0.1 - 0.2 - 0.4 - 0.5 - 0.7 - 0.9
286 272 259 244 221 200 182 165 150 136 123 109 96 84 73 63 54
68-S 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.6 0.6 0.5 05 0.4 0.3
0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.4 0.4 0.3 0.2 0.0 - 0.1 - 0.3 - 0.5 - 0.7 - 0.9
295 278 265 250 239 226 218 201 184 168 154 138 124 111 98 87 77 67 58 49
78-S 0 .7 0.8 0.8 0.9 0 .9 0.0 0.9 0.9 1.0 1.0 1.0 0.9 0.9 0.9 05 0.8 0.7 0.6 0.5 0.4
0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.7 0.7 0.6 0 .5 0.4 0.3 0.2 0.0 - 0.2 - 0.4 - 0.6 - 0.9 - 1 2
- 287 271 259 245 232 224 213 202 193 179 163 148 134 121 110 99 88 78 69
88-S 0.9 1.0 1.0 t .1 1.1 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.0 0.9
1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.8 0.7 0.6 0.5 0.3 0.1 - 0.1 - 0.3 - 0.6

Strength based on strain compatibility; bottom tension lim ited to 6 J%; see pages 2 -2 -2 -6 for explanation.

2 -2 8 PCI Design Handbook/Fifth Edition


StrandJJattern Designation HOLLOW-CORE S ectio n Properties

7 6 -S 4 -0" X 12" Untapped Topped

,lt t1---------S = straight


Normal Weight Concrete
A = 262 in2 —

\ = 4,949 in4 7,811 in4


_____ Diameter of strand in16ths
------------No. of strand (7) yp = 6.00 in. 7.55 in.
yt -= aoo in. 6.45. in.
Safe loads shown include dead load o f 10 Sb =- 825 in3 1,035 in3
p sf for untopped m em bers and 15 p s f for s, = 825 m3 1,211 in3
topped members. Ttemainder is live load. b» = 8.00 in. 8.00 in.
Long-time cambers include superim posed wt = 273 plf 373 pff-
dead load but do not include five load.
6 8 psf 93 psf
Capacity of sections of other configura­ V/S = 2.18 in.
tions are similar. For precise values, see
local hollow-core manufacturer.

Key
1 2 7 — Safe superimposed service load,, psf
0 .3 — Estimated camber at erection, in.
0 .4 — Estimated long-time camber, in.
4HC12
Table of safe superimposed service load (psf) and cambers (In.) No Topping
Strand Span, ft
Designation
Code 28 29 30 3t 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50
127 115 104 94 85 76 69 62 56 50 44 39 35
76-S 0.3 0.3 0.3 0.3 0.3 0.2 0.2 0.1 0.1 0.0 0.0 - 0.1 - 0.2
0 .4 0.3 0.3 0.3 0.2 0.1 0.1 0.0 - 0.1 - 0.2 - 0.3 - 0 5 - 0.6
173 +61 147 134 122 112 102 93 85 78 71 65 59 53 48 43 39 35
58-S 0.5 0.5 0.5 0.5 0.5 0.5 0.5 05 0.4 0.4 0.3 0.3 0.2 0.1 0.1 0.0 - 0.1 - 0.3
0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.4 0.4 0.3 0.2 0.1 - 0.1 - 0.2 - 0.4 - 0.6 - 0.8 - 1.0
182 173 165 157 150 143 131 12+ 111 102 94 87 80 73 67 62 56 52 47
68-S 0.7 0.7 0.7 0.7 0.8 0.8 0 .8 0.7 0.7 0.7 0.7 06 0.6 0.5 05 0.4 0.3 02 0.1
0.9 0.9 0.9 0.9 0.9 0.9 0.9 0.8 0.8 0.7 0.7 06 05 0.3 02 0.1 - 0.1 - 0.3 - 0 5
188 179 171 163 156 149 145 139 134 126 117 108 100 93 86 79 73 68 62 58 53 49
78-S 0 .9 0.9 0.9 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.8 0.7 0.7 0.6 0.5 0.4 0.2
1.1 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.1 1.1 1.0 0.9 0.8 0.7 0.5 0.3 0 2 - 0.1 - 0.3 - 0.5
194 185 177 169 162 155 148 142 137 131 126 121 120 112 104 97 90 83 78 72 67 62 57
88-S 1.0 1.1 t.1 1.2 1 2 1.2 1.2 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 12 1.2 1.1 1.1 1.0 0.9 0.8 0.6
1.3 1.4 1.4 1.5 1.5 1.5 1.6 1.6 1.6 1.6 15 1.5 1.5 1.4 1.3 1.2 1.1 1.0 0.9 0.7 05 0.3 0.0

4HC12+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand Span, ft
Designation
Code 23 24 25 26 27 28 29 30 JJ1 32 33 34 35 36 37 38 39 40 41 42 43 44 45
241 215 193 172 155 139 124 111 99 89 79 70 62 55 48 41
76-S 06 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2 02 0.1 0.1 0.0 0.0
0.3 0,3 0.3 0.2 0.2 0.2 6.1 0.1 0.0 - 0.1 - 0 2 - 0.3 - 0 .4 - 0.5 - 0.7 - 0.8
256 240 228 215 2 02 194 176 160 145 131 119 108 98 88 80 72 64 57 51 44
58-S 0.4 05 0.5 0.5 0.5 0.5 0.5 0.5 0.5 05 0.5 0.5 05 0.4 0.4 0.3 0 .3 02 0.1 0.1
0.4 0.5 05 05 0.5 0.4 0.4 0.4 0.3 0.3 0.2 0.1 0.0 - 0.1 - 0 2 - 0.3 - 0.5 - 0.7 - 0.9 - 1.1
262 249 234 224 211 2 0 0 189 183 173 165 154 141 129 117 107 98 89 81 74 67 60 52 44
68-S 0.6 06 0.6 06 0.7 0.7 0.7 0.7 0.7 0.8 0.8 0.8 0.7 0.7 0.7 0.7 0.6 0.6 0.5 0.5 0.4 03 0.2
06 06 06 06 0.6 0.6 0.6 0.6 0.6 06 0.5 0.5 0.4 0.3 02 0.1 - 0.1 - 0.2 - 0.4 - 0.6 - 0.8 - 1.0 - 1.3
271 255 243 230 217 206 195 189 179 171 163 155 148 144 134 123 113 104 95 87 80 73 65
78-S 0.7 0.7 0.8 0.8 0.8 0.9 0.9 0.9 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.9 0.8 0.7 0.7
0.7 0.8 0.8 0.8 0.8 0.9 0.9 0.9 0.9 0.8 0.8 0.8 0.7 0.7 0.6 0.5 0.4 0.3 0.1 - 0.1 - 0 2 - 0.5 - 0.7
280 264 249 236 223 212 201 125 185 177 169 161 154 147 141 135 129 126 116 107 99 91 84
88-S 0.8 0.8 0.9 0 .9 1.0 1.0 1.1 1.1 1.2 1.2 1.2 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 1.3 12 12 1.1
0.9 0.9 1.0 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 0.9 0.9 0.8 0.7 0 .6 0.4 0.3 0.1 - 0.1

Strength based on strain compatibility; bottom tension limited to 6 Jf^; see pages 2 -2 -2 -6 for explanation.

PCI Design Handbook/Fifth Edition 2 -2 9


StrandPattern Designation
HOLLOW-CORE Section Properties

76-S 4 '- 0 " x 1 2 J/ Untopped Topped


LightwekjhtConcrete =-
S = straight
A 262r in2 —
I = 4^949 in* 8,800 in*
Diameter of strand in 16ths
No. ofstrand (7) yb = 6.00 in. 608 in.
y. = 6.00 in. 5.92 in.
Safe lo a d s s h o w n in c lu d e d e a d lo a d o f 10 sb = 825 in2 1.089 in2
p s fio r untopped members and 15 p sf for s, = 825- in2 1,486 in2
topped members. Remainder is live load. bw = 8.00 in. 8.00 in.
Long-time cam bers include superimposed 1'k" wt = 209 plf 3 09 plf
dead toad but d o not include five load. 1
52 psf 77 psf
Capacity of sections o f other configura­ V/S = 2.18 in.
tions are similar. For precise values, see
local hollow-core manufacturer. fc = 5,000 psi
Key
f'i = 3,500 psi
1 4 0 — Safe superimposed service load, psf
0 .6 — Estimated camber at erection, in.
0 .7 — Estimated long-time camber, in.
4LHC12
Table of safe superimposed service load (psf) and cambers (in.) No Topping
Strand Span, ft
Designation
Code 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50

140 128 117 107 98 90 82 75 69 63 57 52 48 43


76-S 0.6 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.4 0.3 0.2 0.0 -0.1 - 0.3
0.7 0.7 0.7 0.7 0.6 0.6 0.5 0.5 0.4 0.3 0.2 0.0 -0.1 - 0.3
186 174 160 147 135 125 1 15 106 98 91 84 78 72 66 61 57 52 48 44
58-S 0.9 0.9 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9
0.9 0.9 0.8 0.8 0.7 06 0.5 0.4
1.1 1.1 1.2 1.2 1.2 1.2 1.1 1.1 1.1 1.0 0.9 0.8 0.7 0.6 0.4 0.3 0.1 -0 .1 - 0.4
192 183 175 170 163 156 144 134 124 115 107 100 93 86 80 75 69 65 60 56 51 48
68-S 1.1 1.2 1.2 1.3 1.3 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.4 1.9 1.3 1.2 1.1 1.0 0.9 0.8
1.3
1.4 1.5 1.5 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.5 1.4 1.4 1.3 1.1 1.0 0.8 0.6 0.4 0.2 -0 .1
198 189 181 173 166 122 155 149 144 138 130 121 113 106 99 92 86 81 76 71 65 61 57
78-S 1.4 1.5 1.5 1.6 1.7 1.7 1.8 1.8 1.9 1.9 1.9 1.9 1.9 2.0 1.9 1.9 1.9 1.9 1.8 1.7 1.7 1.6 1.5
1.8 1.8 1.9 2.0 2.0 2.1 2.1, 2.1 2.2 2.2 2.2 2.1 2.1 2.1 2.0 1.9 1.8 1.7 1.6 1.4 1.2 1.0 0.7
204 195 187 179 172 165 158 152 147 144 139 134 127 119 115 108 103 97 91 85 81 75 70
88-S 1.7 1.8 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.5 2.4 2.4 2.3
2.1 2.2 2.3 2.4 2.5 2.6 2.6 2.7 2.7 2.7 2.8 26 2.8 2.8 2.7 2.7 2.6 2.5 2.4 2.3 2.1 2.0 1.8

4LHC12+2
Table of safe superimposed service load (psf) and cambers (in.) 2" Normal Weight Topping
Strand Span, ft
Designation
Code 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45
254 228 206 186 168 152 137 124 112 102 92 83 75 68 61 54 49
76-S 0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.5 0.4 0.4
0.5 0.5 0.5 0.5 0.5 0.4 0.4 0.4 0.4 0.2 0.1 0.0 -0.1 -0 .2 - 0.4 - 0.5 - 0.7
266 253 238 228 216 204 189 173 158 144 132 121 111 101 93 65 77 71 64 58 53
58-S 0.7 0.7 0.8 0.8 0.9 0.9 0.9 0.8 0.7 0.7 0.6 0.6 0.5 0.4 0.3 0.1 0.0 -0 .2 - 0.4 -0 .6 - 0.9
0.7 0.7 0.8 0.8 0.8 0.8 0.8 0.8 0.7 0.7 0.6 0.6 0.5 0.4 0.3 0.1 0.0 -0 .2 - 0.4 -0 .6 - 0.9
275 259 244 234 222 210 203 193 183 175 167 154 142 131 120 111 102 94 87 80 73 67 62
68-S 06 0.9 1.0 1.0 1.1 1..1 1.2 1.2 1.3 1.3 1.4- 1.4 1.0 0.9 0.8 0.7 0.6 0.4 0.3 0.1 -0 .1 - 0.3 -0 .6
0.9 1.0 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 0.9 0.8 0.7 0.6 0.4 0.3 0.1 -0.1 - 0.3 -0 .6
281 265 253 240 228 216 209 199 189 181 173 165 161 154 147 136 126 117 108 100 93 86 80
78-S 1.0 1.1 1.2 1.3 1.3 1.4 1.5 1.5 1.6 1.7 1.7 1.8 1.8 1.9 1.9 1.9 2.0 2.0 1.9 1.9
1.9 1.9 1.9
1.1 1.2 1.2 1.3 1.3 1.4 1.4 1.4 1.5 1.5 1.5 1.4 1.4 1.4 1.3 1.2 1.2 1.1 0.9 0.8 0.6 0.4 0.2
274 259 246 237 225 215 205 195 187 179 171 T64 157 151 145 142 137 129 120 112 104 97
88-S 1.3 1.4 1.5 1.6 1.7 1.8 1.8 1.9 2.0 2.1 2.2 2.2 2.3 2.3 2.4 2.4 2.5 2.5 2.5 2.5 2.5 2.5
1.4 1.5 1.6 1.6 1.7 1.8 1.3 1.8 1.9 1.9 1.9 1.9 1.9 1.8 1.8 1.7 1.6 1.5 1.4 1.3 1.1 0.9

Strength based on strain compatibility; bottom tension limited to 6/fJT; see pages 2 -2 -2 -6 tor explanation.

2 -3 0 PCI Design Handbook/Fifth Edition


HOLLOW-CORE SLABS
Fig# 2.4,1 Section Properties-normal weight concrete Dy-Core

Trade Name: Dy-Core®


Equipment Manufacturer: Mixer Systems, Inc., Pewaukee, Wisconsin

OD.O.G.O.O.O.Q'
Section Untopped With 2" topping

width

D.O.QO.O.O.O.Q' X
depth
A
in*
Yb
in.
1
in4
wt
psf
Yb
in.
1
in4
wt
psf

4 '-0 " x 6" 142 3 .0 5 661 37 4.45 1,475 62

4'-0 " x 8" 193 3.97 1,581 50 5.43 3,017 75

4'-Q" a 10" 215 5.40 2,783 56 6.89 4,614 81

o \ _ _ / c O0 \ _ ^ 0 © BV -/a 0 4 '-0 " x 12" 264 6.37 4,773 69 7.89 7,313 94

4 '-0 " x 15" 289 7.37 8,604 76 9.21 13,225 101

Note: AH sections not ava ila b le fro m all p ro du cers. C h e c k availability w ith local m anufacturers.

Fig. 2.4.2 Section Properties-normal weight concrete Dynaspan

Trade Name: Dynaspan®


Equipment Manufacturer: Dynamold Corporation, Salina, Kansas

Section Untopped With 2" topping

width
A Yb 1 wt Yb I wt
X
in: in. in4 psf in. in4 psf
depth

4 '-0'' x 4" 133 2.00 235 35 3.08 689 60

4 '-0 " x 6" 165 3.02 706 43 4.25 1,543 68

4 '-0 " x 8" 233 3.93 1,731 61 5.16 3,205 86

4 '-0 " X 10" 260 4.91 3,145 68 6.26 5,314 93

8 '-0 " x 6" 338 3.05 1,445 44 4.26 3,106 69

8 '-0 " x 8 " 470 3.96 3,525 61 5.17 6,444 86

8 '-0 " x 10" 532 4.96 6,422 69 6.28 10,712 94

8'-0 " x 12" 615 5.95 10,505 80 7.32 16,507 105

i 000.00.00.00.00.) 100000000000000000000000.)

/o O Q Q Q Q Q Q Q Q Q \ /o.O.O.O.O.O.O.O.OD.O.O.O.O.O.O.OnO.O.O.O.O:^
Note: All s e c tio n s not availab le fro m all p ro d u ce rs . C h e c k availability w ith local m anufacturers.

PCI Design Handbook/Frfth Edition 2 -3 1


HOLLOW-CORE SLABS

Fig. 2.4.3 Section Properties-norm al weightconcrete -F to d e o re

Trade Name: Flexicore®


Licensing Organization: The Flexicore Go. inc., Daytonr Ohio

iD .O .Q i

Section Untopped With 2" topping

w idth
X A y* 1 - wt Y» 1 wt
io .o .o i depth in2 in. in4 psf in. in4 p sf

1 '-4" x 6" 55 3.00 243 43 : 4.23 523 68

2'-Q" x 6" 86 3.00 366 45 4.20 793 70

1'-4" x S " 73 4.00 560 57 : : 5.26 1,028 82

2 '-0 " x 8" 110 4.00 843 57 5.26 1,547 82


00

98 5.00 1,254 61 6.43 2,109 86


o
X

2 '-0 " x 10" 138 5.00 1,587 72 6.27 2,651 97

2'-0 " x 12" 141 6.00 2,595 73 7.46 4,049 98

Note: AH sections not available from all producers. Check availability with local manufacturers.

Fig. 2.4.4 Section Properties-normal weight concrete Spancrete

Trade Name: Spancrete®


Licensing Organization: Spancrete Machinery Corp., Milwaukee, Wisconsin

Trade Name: Standard Spancrete® Section Untopped With 2” topping

width
A yb 1 wt yb I wt
X
in2 in. in4 psf in. in4 psf
depth

4 '- 0 " X 4" 138 2.00 238 34 3.14 739 59

4 ' - 0 " x 6" 189 2.93 762 46 4.19 1,760 71

4 ' - 0 " X 8" 258 3.98 1,806 63 5.22 3,443 88

4 '—0" x 10" 312 5.16 3,484 76 6.41 5,787 101

4 ' - 0 " x 12" 355 6.28 5,784 86 7.58 8,904 111


Trade Name: Ultralight Spancrete® 4 '- 0 " X 15" 370 7.87 9,765 90 9.39 14,351 115
V

%
o

oo

246 4.17 1,730 60 5.41 3,230 85


X
I

4 '—0" x 10" 277 5.22 3,178 67 6.58 5,376 92

4 ' - 0 " x 12" 316 6.22 5511 77 7.66 8,410 102

Note: Spancrete is also available in 40" and 96" widths. All sections are not available from all producers. Check
availability with local manufacturers.

2 -3 2 PCI Design Handbook/Fifth Edition


HOLLOW-CORE SLABS

fig u re 2.4.5 Seeiion Properties-norm al weight concrete Span-Deck

Trade Name: Span Deck®


Licensing-Organization: Fabcon, incorporated, Savage, Minnesota

Section Untopped With 2" topping

width
X A yb 1 wt yb 1 wt
depth in2 In . in4 psf in. in4 p sf

4 '-0 " x 8" 246 3.75 1,615 62 5.55 2,791 87

4 '-0 " x 12" 298 5 .8 7 5,452 75 8.01 7,856 100

8 '-0 " x 8" 477 3.73 3,236 60 5.53 5,543 85

8'-0 " x 12" 578 5.86 10,909 72 7.98 15,709 97

lzz !□ □ an □ an

Note: AH sections not available from all producers. Check availability with local manufacturers.

Figure 2.4.6 Section Properties-normal weight concrete Ultra Span

Trade Name: Ultra Span


Licensing Organization: Ultra Span Technologies lncM Winnipeg, Manitoba, Canada

j o .o .o .Q .o .q
Section Untopped With 2" topping

width
X A yb I wt yb 1 wt
depth in: in. in4 psf in. in4 psf

4 '-0 " x 4" 154 2.00 2 47 40 2.98 723 65

4 '-0 " x 6" 188 3.00 764 49 4.13 1,641 74

4 '-0 " x 8" 214 4.00 1,666 56 5.29 3,070 81

4 '-0 " x 10" 259 5.00 3,223 67 6.34 5,328 92

4 '-0 " x 12" 289 6.00 5,272 75 7.43 8,195 100

Note: All sections are not available from aH producers. Check availability with local manufacturers.

PCI Design Handbook/Fifth Edition 2 -3 3


HOLLOW-CORE SLABS

Figure 2rC ? Section Properties- normaf w eight concrete Elematic

Trade Namer Elematic®


Equipment Manufacturer Mixer Systems* Inc., Pewaukee, Wisconsin

Section Untopped With 2" topping

width
/.O.O.O.QCO X
depth
A
in2
Vb
in.
1
in4
wt
psf
y*.
in.
1
in4
wt
psf

4 '-0 " x 6 " 157 3.00r 694 41 4.33 1557 66

/.Q.Q.Q.Q.O.O.\ 4 '-0 " x 8"

4 '-0 " x 10"


196

238
3.97

5.00
1580

3042
51

62
5.41

6.49
3024

5190
76

87

4 '-0 " x 1 0 " 249 5.00 3108 65 6.44 5280 90

4 '-0 " X 12" 274 6.00 5121 71 7.56 8134 96

Note: Elematic is also available in 96 in. width. All sections not available from all producers. Check availability with
local manufacturers.

2-34 PCI Design Handbook/Fifth Edition


Stran d Pattern Designation SOLID FLAT SLAB Section Properties

76-S
4" Thick Untopped Topped
Normal Weight Concrete
A = 192 in2 —
S = straight
I = 256 in4 763 in 4
Diameter of strand in 18ths
L No. of strand (7) Yb = 2 .0 0 in. 2.84 in.
y. = 2.00 in. -3.16 in.
* 4 '- ° " *
2" sb = 128 in3 269 in3
Safe loads shown include dead load o f 10 V / z" s, = 128 in3 242 in3
p s / for untopped members and 15 p s f for
t
I i f bw = 48.00 in. 48.00 in.
topped members. Remainder is live bad. f
Long-time cambers include superimposed wt = 200 P»f 300 plf
dead load but do not include live ioad.- 50 psf 75 psf
V/S = 1.85 in.
fe = 5,000 psi
= 3,500 psi
196 — Safe superimposed service load, psf
0.1 — Estimated camber at erection, in.
G.1 — Estimated long-time camber, in.

FS4
Table of safe superimposed service load (psf) and cambers No Topping
Strand Span, ft
Designation
Code 10 11 12 13 1* 15 16 17 18 19 20 21 22
196 165 132 105 83 66 52 41 31
66-S 0.1 0.1 0.1 0.0 0.0 -0 .1 -0 .2 - 0 .3 - 0 .4
0.1 0.1 0.0 0.0 -0 .1 -0 .3 - 0 .4 -0 .6 - 0 .9
230 1 90 151 122 98 79 63 50 4 0 30
76-S 0.1 0.1 0.1 0.1 Ob 0.0 -0 .1 -0 .2 -0 .3 -0 .5
0.1 0.1 0.1 0.0 -0 .1 - 0 .2 -0 .3 -0 .5 -0 .9 -1 .0
253 2 1 2 180 154 12 7 1 0 4 86 70 "57 46 57
58-S 0.2 0.2 0.2 0.2 0.1 0.1 0.0 0.0 -0 .1 -0 .3 -0 .4
0.2 0.2 0.2 0.2 0.1 0.0 -0 .1 - 0 .3 - 0 .5 -0 .8 -1 .1
300 2 5 2 2 1 4 18 0 152 127 105 88 73 60 50 40 32
68-S 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.1 0.0 -0 .1 - 0 .3 -0 .4 -0 .7
0.3 0.3 0.3 0.3 0.2 02 0.1 -0 .1 - 0 .3 -0 .5 - 0 .8 - 1 2 -1 .6

FS4+2
Table of safe superimposed service load (psf) and cambers 2" Normal Weight Topping
Strand Span, ft
Designation
Code 10 11 12 13 14 15 16 17 18 19 20 21
"369 296" 224 167 123 67 57 33
66-S 0.1 0.1 0.1 0.0 0.0 -0 .1 -0 .2 -0 .3
0.0 0.0 0.0 -0 .1 - 0 .2 -0 .3 -0 .5 -0 .7
346 265 203 153 113 80 53 31
76-S 0.1 0.1 0.1 0.0 0.0 -0 .1 - 0 2 -0 .3
0.0 0.0 -0 .1 -0 .1 -0 .3 -0 .4 - 0 .6 -0 .9
400 342 274 214 166 127 95 67 44
58-S 0.2 0.2 0.2 0.1 0.1 0.0 0.0 -0 .1 -0 .3
(L1 0.1 0.0 0.0 -0 .1 -0 .3 - 0 .4 -0 .7 -0 .9
335 268 213 169 132 101 74 52 32
68-S 0.2 0.2 0.2 0.2 0.1 0.0 -0 .1 - 0 .3 -0 .4
0.1 0.1 0.0 -0 .1 -0 .3 -0 .5 -0 .7 - 1 .0 -1 .4

Strength based on strain compatibility; bottom tension limited to 6 Jt£; see pages 2 -2 -2 -6 for explanation.

PCI Design Handbook/Fifth Edition 2 -3 5


Strand Pattern Designation SOLID FLAT SLAB Section Properties

76-S Thick A" Untapped Topped


Lightweight Concrete A- - 192 in? _
S-= straight =
1 256 in* 925 in*
Diameter of strand in 16ths
yb ss 2.00 in. 3.10 in.
No. of strand (7)
4 '-0" , =
2" ¥t- 2.90 in. 2.90 in.
T 4" sb = 128 in3 298 in3
Safe loads shown include d ead load of 10 st 128 in3 319 in3
p s f for untopped m em bers a n d 15 p s f for . e e . e e =
bw 48.00 in. 48.00 in.
topped members. ^Remainder is live load.
Long-time cam bers include superimposed 4 wt = 153 ptf 253 plf
dead load but d o not include live load. 38 psf 63 psf
V/S = 1.85 in.
fc = 5,000 psi
Key fci = 3,500 psi
2Q6— Safe superimposed service load, psf
0.1 — Estimated camber at erection, in.
0 .2 — Estimated long-time camber, in.

LFS4
Table of safe superimposed service load (psf) and cambers No Topping

Strand Span, ft
Designation
Code 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
"S35" 175 143 116 95 76 64 52 42 34
66-S 0.1 0.1 0.1 0.1 0.1 0.0 0.0 - 0.1 - 0.3 - 0.5
0.2 09 0.1 0.1 0.0 - 0.2 - 0.3 - 0.5 - 0.8 - 1 2
239 201 W T33“ no 91 75 62 51 42 34
76-S 0.2 02 0.2 02 0.2 0.1 0.1 0.0 - 0.1 - 0.3 - 0.5
0.2 02 0.2 02 0.1 0.0 - 0.2 - 0.4 - 0.6 - 1.0 - 1 .3
363 232 199 163 136 113 69 66 57 46 49 33
b>
1

58-S 0.3 0.1 0.0 - 0.2


I

0.3 0.3 0.3 0.3 0.3 0.2


o

0.3
A
0
o
CO

O
to

0.3 0 .4 0.4 0.3 0.3 0.2 0.1 - 0.1 - 0.9 - 1.3 - 1.8
I

309 261 1 S T T33T155“133" 112 95 81 69 59 50 42 36 30


68-S 0.3 0.4 0.4 0.4 0.5 0.5 0.5 0.4 0.3 0.2 0.1 - 0.1 - 0.3 - 0.5 - 0.9
0.4 0.5 0.5 0.5 0.5 0.4 0.4 0.2 0.0 - 0.2 - 0.5 - 0.9 - 1.4 - 1.9 - 2.6

LFS4+2
Table of safe superimposed service load (psf) and cambers 2" Normal Weight Topping
Strand Span, ft
Designation
Code 11 12 13 14 15 16 17 18 19 20 21
■27T 213 163 123" 91 63
CO
CM
CM

41
66-S 0.1 0.1 0.1 0.1 0.0 0.0 - 0.1 - 0.3
0.1 0.0 0.0 - 0.1 - 0.3 - 0.5 - 0.7 - 1.0
375 319 252 197 153" 11? 66 61 40
76-S 0.2 0.2 0.2 02 0.1 0.1 0.0 - 0.1 - 0.3
0.1 0.1 0.0 - 0.1 - 0 2 - 0.3 - 0 .6 - 0.8 - 1 2
"35TW “25JT"25T" W 129 190 ~~7B 54 55
58-S 0.3 0.3 0.3 0.3 0.3 02 0.1 0.0 - 0.2 - 0.4
0.2 0.2 0.1 0.0 - 0.1 - 0.3 - 0.5 - 0.5 - 1.2 - 1.7
~5W "25T“25T 164 131 103
CO
CO
O

79 59
68-S 0.4 0.5 0.5 0.5 0.4 0.3 0.2 0.1 - 0.1
0.3 0.3 02 0.1 - 0.1 - 0.3 - 0.6 - 0.9 - 1.3

Strength based on strain compatibility; bottom tension limited to 6 Ji£; see pages 2 -2 -2 -6 for explanation.

2 -3 6 PCI Design Handbook/Fifth Edition


Strand-PatternDesignation SOLID FLAT SLAB Section Properties

76-S 6" Th ick Untopped Topped-


Norm al W e ig irfC o n cre te 2 8 8 in2 —
H
I___ — S = straight
J = -884—in* 1,834- in4
— Diameter of-strand in 46ths
yt = 3.00 in. 3.82 In.
— No. of strand (7)
4 '- 0 "
yt = 3.00 in. 4.18 in.
r
i St. = 288 in3- 480 in3
Safe foaefs shown include dead load of 10 ___ I
s, = 288 in3 439 in3
va" i— ii— a— mi
psf for untopped members and 15 p s fio r 48.00 in.
bw = 48.00 in.
.topped members. Remainder is live load. ........................................... je "
Long-time cambers include superimposed wt = 300 plf 400 Plf
dead load but do not include live load. T“ 75 psf 100 psf
V/S = 2.67 in.
fc = 5,000 psi
Key fd = 3,500 psi
3 3 0 — Safe superimposed service load, psf
0.1 — Estimated camber at erection, in.
0.2 — Estimated long-time camber, in.

FS6
Table of safe su p erim po sed service load (psf) and cam bers N o Topping
Strand Span, ft
Designation
Code 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30

330 284 236 195 162 135 113 94 78 65 53 43 33


66-S 0.1 0.1 0.1 0.1 0.1 O.T 0.1 0.1 0.0 - 0.1 - 0.1 - 0 2 - 0.3
0.2 02 0.2 0.2 0.1 0.1 0.1 0.0 - 0.1 - 0 2 - 0 .4 - 0 .5 - 0.7
390 336 280 233 195 164 139 117 99 83 66 55 44 35
76-S 0.1 0.2 0 .2 0.2 0.2 02 0.2 0.1 0.1 0.0 0.0 - 0.1 - 0 2 - 0.3
0.2 0.2 0:2 0.2 0.2 0.2 0.2 0.1 0.0 - 0.1 - 0.2 - 0 .4 - 0.5 - 0.8

369 320 280 247 219 186 158 134 113 96 81 57 56 46 36


58-S 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 02 0 .2 0.1 0.0 - 0.1 - 0.2 - 0.3
0.3 0.3 0.4 0.4 0.4 0.4 0.3 0.3 02 0.1 0.0 - 0 2 - 0 .4 - 0.6 - 0.9
387 339 300 2 6 2 224 191 164 141 121 103 88 75 63 53 43 35
68-S 0.3 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.3 0.3 0 .2 0.1 0.0 - 0.2 - 0.4
0.4 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.4 0.3 0.2 0 .0 - 0 2 - 0 .4 - 0.7 - 1.1
396 351 303 261 225 195 168 146 126 109 94 81 69 59 49 41 33
78-S 0.4 0.5 0.5 0 .6 0.6 0.6 0.6 0.6 0.6 0.5 0.4 0 .4 0.3 0.1 0.0 - 0.2 - 0.5
0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.6 0.5 0.4 02 0 .0 - 0.3 - 0.6 - 0.9 - 1.4

FS6+2
Table of safe superim posed service load (psf) and cam bers 2" Norm al W eight Topping
Strand Span, ft
Designation
Code 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
342 284 237 198 162 127 97 71 49
66-S 0.1 0.1 0.1 0.1 0.1 0.1 0.0 - 0.1 - 0.1
0.1 0.1 0.1 0.0 0.0 - 0.1 - 0.2 - 0.3 - 0.5
336 283 239 197 158 125 96 72 51 32
76-S 0.2 0.2 02 02 0.1 - 0.1 - 0 2 - 0.4 - 0.5 - 0.7
0.2 0.1 0.1 0.0 0.0 - 0.1 - 0 2 - 0.4 - 0.5 - 0.7
356 314 268 221 181 147 118 93 71 51 34
58-S 0.3 0.3 0.3 0.3 0.3 02 0.2 0.1 0.0 - 0.1 - 0.2
0.3 0.2 0.2 02 0.1 0.0 - 0.1 - 0.3 - 0.4 - 0.7 - 0.9
375 323 278 232 193 160 131 105 83 64 46 31
68-S 0.4 0.4 0.4 0.4 0.4 0.4 0.3 0.3 0.2 0.1 0.0 - 0.2
0.4 0.4 0.3 0.3 02 0.1 0.0 - 0.2 - 0.3 - 0.6 - 0.9 - 1 2
371 323 281 239 201 169 140 115 93 73 56 40
78-S 0.6 0.6 0.6 0.6 0.6 0.6 0 .5 0.4 0.4 0.3 0.1 0.0
0.5 0.5 0.5 0.3 0.4 0.3 0.1 0.0 - 0.2 - 0.5 - 0 .8 - 1.1

Strength based on strain compatibility; bottom tension limited to see pages 2 -2 -2 -6 for explanation.

PCI Design Handbook/Fifth Edition 2 -3 7


Strand Pattern Designation SOU& FEA T SLAB S ection Properties

76-S 6" Thick Untopped Topped


Lightweight Concrete A = 288 infr —
S = straight
f S- -364 in* ^ 2 ,1 8 4 in4
Diameter of strand in 16ths
No. of strand (7) yb = 3.00 irr. 4.14 in .
4 '-0 " = 3.0 0 in. 3:89 in.
2 )h
sb = 238 in3 531 ins
Safe loads shown include d ead load o f 10 H i" St = 2 88 in3 56t in3
p sf for untopped members and 15 p sf for = 48.00 in. 48.00 in.
bw
topped members. Remainder is live load. I • • < 1 6"
wt 2 3 0 plf 330
Long-time cambers include superimposed ptf
dead .load but do not include live load. T _
58- psf 83 psf
V/S 2.67 in.
fc = 5,000 psi
Key \'a = 3,500 psi
3 4 5 — Safe superimposed service load, psf
0.2 — Estimated camber at erection, in.
0 .3 — Estimated long-time camber, in.

LFS6
Table of safe superimposed service load (psf) and cambers No Topping
Strand Span, ft
Designation
Code 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

345 298 250 209 177 150 127 109 93 /9 68 58 49 41 34


66-S 0.2 0.2 0.2 0.3 0.3 0.3 0.3 0.2 0.2 0.1 0.1 0.0 - 0.1 - 0.3 - 0.4
0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.1 0.0 - 0.1 - 0.3 - 0.5 - 0.8 - 1.1
35T294 247 209 179 153 75T 113 98 85 73 62 52 44 36
76-S 0.3 0.3 0.3 0.3 0.4 0.4 0.3 0.3 0.3 02 0.2 0.1 0.0 - 0.2 - 0.4
0.4 0.4 0 .4 0.4 0.4 0.4 0.4 0.3 0.2 0.1 - 0.1 - 0.2 - 0.5 - 0.7 - 1.1
383 334 295 262 233 201 175 151 131 113 98 85 73 63 54 46 39 32
58-S 0.4 0.4 0.5 0.5 0.5 0.6 0.6 0.6 0.6 0.6 0.5 0.5 0.4 0.3 0.1 0.0 - 0.2 - 0.5
0.5 0.6 0.6 0.7 0.7 0.7 0.7 0.7 0.6 0.6 0.5 0.3 0.1 - 0.1 - 0.4 - 0.7 - 1.1 - 1.5
354 315 272 235 204 178 156 137 755"755" 92 81 79 61 53 45 38 32

O
o o

O
CM CM
68-S 0.6 0.6 0.7 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.8 0.7 0.6 0.4 0.3

I
CO
T

cq
0.8 0.8 0.9 0.9 1.0 1.0 1.0 1.0 0.9 0.8 0.7 0 .5 0.3 0.0 - 0.4 I
356 307 266 232 203 179 157 139 123 109 96 85 67 58 51 44

o
d
CO

78-S 0.8 0.9 0.9 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0.9 0.8 d
1.0 1,1 1.2 1.2 1.3 1.3 1.3 1.3 1.2 1.2 1.0 0.9 0.6 0.4 0.0 - 0.4 - 0.9

LFS6+2
Table of safe superimposed service load (psf) and cambers 2" Normal Weight Topping
Strand Span, ft
Designation
Code 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
298 251213 181 155 132 111 86 65 47 39
66-S 0.3 0.3 0.3 0.3 0.2 02 0.1 0.1 0.0 - 0.1 - 0.3
0.2 0.2 0.2 0.1 0.0 - 0.1 - 0.2 - 0.4 - 0.6 - 0.8 - 1.1
351 297253 217 i‘86 161 Y39‘ 7'15—88 66 5b 34
76-S 0.3 0.3 0.4 0.4 0.3 0.3 0.3 0 .2 0.2 0.1 0.0 - 0.2
0 .3 0.3 0.3 0.2 0.2 0.1 0.0 - 0.2 - 0.4 - 0.6 - 0.8 - 1.1
' 371" 328"283T 4 6 2 l4 " l8 7 163 135 110 89 70 53 38
58-S 0.5 0.5 0 .6 0.6 0.6 0.6 0.6 0.5 0.5 0.4 0.3 0.1 0.0
0.5 0.5 0.5 0.4 0.4 0.3 0.2 0.1 - 0.1 - 0.3 - 0.6 - 0.9 - 1.3
390 338 294 257 226 199 175 148 124 103 83 66 51 37
68-S 0.7 0.8 0.8 0.-8 0 .6 0.8 0.8 0.8 0.8 0.7 0.6 0.4 0.3 0.1
0.7 0.7 0.7 0.6 0.6 0.5 0.4 0.3 0.1 - 0.1 - 0 .4 - 0.7 - 1.1 - 1.5
386 337296 261 230 204 180 155 132 111 93 77 61 4?
78-S 0 .9 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.0 0 .9 0.8 0.6 0.4
0.9 0.9 0.9 0.9 0.8 0.8 0.7 0.5 0.3 0.1 - 0.2 - 0.5 - 0.9 - 1.4

Strength based on strain compatibility; bottom tension limited to 6-/f7; see pages 2 -2 -2 -6 for explanation.

2 -3 8 PCI Design Handbook/Fifth Edition


Strand Pattern D esig n ation
SOLID FLAT SLAB Section Properties

76-S 8" Thick Untapped Topped


Normal Weight Concrete
A = 384 in21 —
- S = straight
1 -= 2;048 in4 3,630 in4
-Diam eter o f strand in 16ths
-N o . of strand (7) * - 4 '-° " „ yt = 4.00 in. 4.81 in.
2
yt = 4.00 in. 5.-19 in.
1 sb = 512 in3 755 in®
Safe loads shown include dead load of 10 V k " s, = 512 in3 699 in3
p sf for untopped m em bers and 15 p s f for 8"
1 bw 48.00 in. 48.00 in.
topped members. Remainder is live load.
Long-time cambers include superim posed wt = 400 plf 500 plf
dead load but do not include live load. 100 psf 125 psf

fo = 5,000 psi V7S = 3.43 in.

fd = 3,500 psi
Key
2 9 9 — Safe superimposed service load, psf
0.1 — Estimated camber at erection, in.
0 .2 — Estimated long-time camber, in.

FS8
Table of safe superimposed service load (psf) and cambers No Topping
Strand Span, ft
Designation
Coda 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
299 250 210 177 149 125 105 55 7S 60 48 35
66-S o.i 0.1 o.r o.i o.t o.i 0.1 o.o o.o - 0.1 - 0.2 - 0.2
02 Q.1 0.1 0.1 0.1 0.1 0.0 0.0 -0.1 - 0 2 -0.3 -0.5
357 301 255 216 184 157 134 114 57 52 58 57 35 57
76-S ' 0.1 0.2 0.2 02 0 2 0.1 0.1 0.1 0.1 0.0 -0.1 -0.1 -0.2 - 0 2
02 0.2 02 02 02 0.2 0.1 0.1 0.0 -0.1 -0 2 -0.3 -0.5 -0.7
378 338 293 218 169 164 142 123 107 92 78 65 54 45 54
58-S 0.2 02 0.3 0.3 0.3 0.3 0.2 02 0.2 0.1 0.1 0.0 -0.1 - 0 2 -0.3 -0.4
0.3 0.3 0.3 0.3 0.3 0.3 0.3 02 02 0.1 0.0 -0.1 -0.3 -0.5 -0.7 -0.7
358 311 271 237 207 182 159 138 120 103 88 75 63 53 43 33-------------------------------------
68-S 0.3 0.4 0.4 0.4 0.4 0.4 0.4 0.3 0.3 02 0.2 0.1 0.0 -0.1 -0.3 -0.5
0.5 0.5 0.5 0.5 0.5 0.4 0.4 0.3 0.3 02 0.0 -0.1 -0.3 -0.5 -0.8 -1.0
367 321282 248 219 192 168 147 128 112 9? 63 71 55" "51 42 33
78-S 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.4 0.4 0.3 0.2 0.1 0.0 -0.1 -0.3 -0.5
0.6 0.6 0.7 0.7 0.7 0.6 0.6 0.5 0.5 0.3 02 0.1 -0.1 -0.3 -0.6 -0.9 - 1 2

FS8+2
Table of safe superimposed service load (psf) and cambers 2" Normal Weight Topping
Strand Span, ft
Designation
Code 17 18 19 20 21 22 23 24 25 26 27 28 29 30
230 195 164 139 116 97 73 52 53
66-S 0.1 0.1 0.1 0.1 0.0 0.0 - 0.1 - 0.2 - 0 2
0.1 0 .0 0 2 - 0.1 - 0.1 - 0 2 . - 0.3 - 0.5 - 0.6
280 239 204 175 149 126 55 76 56 58
76-S 02 0.2 0.1 0.1 0.1 0.1 0.0 - 0.1 - 0.1 - 0.2
0.1 0.1 0.1 0.0 0.0 0.1 - 0.2 - 0 .3 - 0 .5 - 0.7
375 324 280 243 211 183 152 124 100 75 59 42
58-S 0.3 0.3 0.3 0.3 02 0.2 0.2 0.1 0.1 0.0 - 0.1 - 0.2
0 .3 0 2 0.2 02 0.1 0.1 0 .0 - 0.1 - 0 2 -0 .4 - 0 .5 -0 .7
395 344 301 264 231 1&9 167 140 115 53 73 57 31
6 8 -S 0.4 0.4 0.4 0.4 0.4 0.4 0 .3 0.3 0.2 02 0.1 0.0 - 0.1
0.4 0.4 0.3 0.3 0.3 02 0.1 0.0 - 0.1 - 0.3 - 0 .4 - 0.6 - 0.9

Strength based on strain compatibility; bottom tenston limited to 6 / f t ; see pages 2 -2 -2 -6 for explanation.

PCI Design Handbook/Frfth Edition 2 -3 9


Strand Pattern Designation
S0UETF4AT SLAB Section Properties

7&S 8 "Thick Untopped Topped


LightweigbtiDQncrete
i A = -384- in2 —
■S « straight
1 = 2,048 in* 4,234 “in*
-Diam eter of strand in TBths
- No. o f strand (7) Yb = 4.-00 in. 5.12 in.
z
Vi = 4.00 in. 4 .8 8 in.
_1 s„ = 512 in3 827 in3
w s, = 512 in3' 868 In 3
p s ffo r untopped members a n d 15 p sf for
topped members. Remainder is. live load. \ 1 b» = 48.00 in. 48.00 in.

CO
<5
Longtim e cambers include superimposed wt = plf 407 plf
dead toad but do not include live load. 77 psf 102 psf
VIS = 3.43 in.
fc = 5,000 psi
Key fj, = 3,500 psi
3 1 8 — Safe superimposed service toad, psf
0 2 — Estimated camber at erection, in.
0 .3 — Estimated long-time camber, in.

LFS8
Table of safe superim posed service load (psf) and cam bers N o Topping
Strand Span, ft
Designation
Code 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35
318 269 229 106 168 144 124 107 92 79 68 56 49 41 33
66-S 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.0 0.0 - 0.1 - 0 2 - 0.4
0.3 0.3 0.3 0.3 0.3 0.2 0.2 0.1 0.1 0.0 - 0.1 - 0.3 - 0.4 - 0.6 - 0.9
376 320 274 235 203 176 1 5 3 "1 3 3 " 116 191 66 76 66 56 46 41 34
76-S 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 03 0.2 02 0.1 0.0 - 0.1 - 0.2 - 0.3 - 0.5
0.3 0.4 0.4 0 .4 0.4 0.4 0.4 0.3 0.3 02 0.1 0.0 - 0.2 —0.4 - 0.6 - 0.8 - 1.1
398 357 312 272 238 208 1 3 3 " 1 3 5 " 143 126 111 96 87 76 67 5? 49 41 34
58-S 0.4 0.4 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.4 0.4 03 0.2 0.1 0.0 - 0.2 - 0.3 - 0.5
0.5 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.6 0.5 0.4 0.3 0.2 0.0 - 0 2 - 0.4 - 0.7 - 1.0 - 1.4
330 290 256 226 201 178 1 5 5 " 142 t s t 112 99 87 76 66 5 7 49 42 3 5
68-S 0.6 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.6 0.5 0.4 0.3 0.1 0.0 - 0.2 - 0.5
0.8 0.9 0.9 0.9 0.9 0.9 0.9 0.8 0.7 0.6 0.5 0.3 0.1 - 0.1 - 0.4 - 0.7 - 1.1 - 1.5
386 340 301 267 237 211 w 1 S T 151 T 3 T 120 107 95 64 74 65 57 49
78-S 0.8 0.8 0.9 o:9 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 0.8 0.7 0.6 0.5 0.3 0.1
1.0 1.1 1.1 1.2 1.2 12 1.2 12 1 2 - 1.1 1.0 0.9 0.7 0.5 0.3 0.0 - 0.3 - 0.7

LFS8+2
Table of safe superim posed service load (psf) and cam bers 2" Norm al W eight Topping
Strand Span, ft
Designation
Code 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35

250 214 184 158 136 116 100 65 72 57 41


6 6 -S 0.2 0.2 0.2 0.2 0.2 0.1 0.1 0.0 0.0 - 0.1 - 0.2
0.2 0.2 0.1 0.1 0.0 - 0.1 - 0.2 - 0.3 - 0.5 - 0.7 - 0.9
299 258 224 ~ w r 1 6 5 "H e T 127 116 95 74 61 45 31
76-S 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.2 0.1 0.0 - 0.1 - 0.2 - 0.3
0.3 0.3 0.2 0.2 0.1 0.1 0.0 - 0 2 - 0.3 - 0.5 - 0.7 - 0.9 - 1.2
394 343 300 262 230 203 179 157 139 122 103 84 67 52 38
58-S
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.4 0.4 0.3 0.2 0.1 0.0 - 0.2
0 .5 09 0.5 0.4 0.4 0.4 0.3 09 0.1 0.0 - 0.2 - 0.4 - 0.6 - 0.9 - 1 9
364 320 283 251 222 198 176 156 139 119 106 82 67 52 46
68-S 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0 .6 0.5 0.4 0.3 0.1 0.0
0.6 0.6 0.6 0.6 0.5 0.5 0.4 0.3 0.2 0.0 - 0.2 - 0.4 - 0.7 - 1.0 - 1.4
374 332 295 263 235 210 188 169 151 132 113 95 79 65 51 39
7 8 -S 0.9 0.9 1.0 1.0 1.0 1.0 1.0 1.0 1.0 0.9 09 0.7 0.6 0.5 0.3 0.1
0.9 0.9 0.9 0.9 0.8 0.8 0.7 0.6 0.5 0.3 0.1 - 0 9 - 0.4 - 0.8 - 1.1 - 1.6

Strength based on strain compatibility; bottom tension limited to 6 Ji£; see pages 2 -2 -2 -6 for explanation.

2 -4 0 PCI Design Handbook/Frfth Edition


RECTANGULAR BEAMS
fo rm a l Weight Concrete
b
SectionProperties

Designation
b tv 4 1 7b s wt
in. in. vn? in4 In . in3
12RB16 12 16 192 4,096 8 t00 512_ 200
12RB20 12 20 240 8,000 10.00 800 - 250
12RB24- t2 24 288 13,824 12.00 1,152 300
h
12RB28 12 28 336 21,952 14.00 1,568 350
12RB32 12 32 384 32,768 16.00 2,048 . 400
12RB36 12 36 432 46,656 18.00 2,592 450
16RB24 16 24 384 18,432 12.00 1,536 400
fc = 5,000-psi 16RB28 16 28 448 29,269 14.00 2,091 467
16RB32 16 32 512 43,691 16.00 2,731 533
fpu = 270,000 psi
16RB36 16 36 576 62,208 18.00 3,456 - 600
1/2 in. diameter 16RB40 16 40 640 85,333 20.00 4,267 667

low-relaxation strand 1. C heck local area for availability of other sizes.


2 . Safe loads shown include 50% superim posed dead load and 50% live load.
Key
3,344 — Safe superimposed service load, plf
800 psi top tension has been allowed, therefore additional top reinforcement
is required.
0 .4 — Estimated camber at erection, i n . .
€.1 — Estimated long-time camber, in. 3. Safe loads can b e significantly increased by u se of structural composite
topping.

Table of safe superimposed service load (plf) and cambers

Span, ft
Desig­ No.
e
nation Strand 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
- 3344 2605 2075 1684 1386 1154 970
12RB16 5 5.67 0.4 0.5 0.6 0.7 0.8 0.9 1.0
0.1 0.2 0.2 02 02 0.2 02
6101 4773 3823 3121 2585 2166 1833 1565 1345 1163 1010
12RB20 8 6.60 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 12 1.3 1.4
0.1 02 02 02 02 0.3 0.3 0.3 0.3 0.3 0.3
8884 6957 5578 4558 3782 3178 2699 2312 1996 1734 1514 1328 1170 1 0 &
12RB24 10 7.76 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6
0.1 0.1 0.2 02 02 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.4
9502 7630 6245 5192 4372 3721 3197 2767 2411 2113 1861 1645 1460 1299 1159 1035
12RB28 12 8.89 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 12 t .3 1.4 1.5 1.5 1.6 1.7
0.1 0.2 0.2 02 0.2 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.4 0.4 0.4 0.4

( 8238 6859 5785 4933 4246 3683 3217 2826 2495 2213 1970 1760 1576 1415 1272
12RB32 13 10.48 0.4 0 .5 0.6 0.7 0.8 0.9 0.9 1.0 1.1 12 1.3 1.4 1.5 1.5 16
02 0.2 0.2 02 0 .3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.3 0.3
8734 7376 6298 5428 4716 4126 3632 3 2 1 4 2856 2549 2283 2050 1846 1666
12RB36 15 11.64 0.5 0.5 0.6 0.7 0.8 0.9 1.0 1.0 1.1 12 1.3 1.4 1.5 1.5
02 02 0.2 02 0.3 0 .3 02 0.3 0.4 0.4 0.4 0.4 0 .4 0.4
9278 7439 6079 5044 4239 3600 3084 2662 2313 2020 1772 1560 1378 1220 1082 961
16RB24 13 7.86 0.4 0.5 0.6 0.7 0.8 02 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.6 1.7 1.8
0.1 0.2 02 02 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.3 0.3 0.3 02
9022 7383 6137 5167 4397 3776 3267 2846 2493 2194 1939 1720 1530 1364 1218 1089
16RB28 13 8.89 0.4 0.4 0.5 0.6 0.6 0.7 0.8 0.9 1.0 1.0 1.1 1.2 1.2 1.3 1.3 1.3
0.1 0.1 0.1 0.2 0.2 0.2 02 02 0.2 0.2 0.2 02 0.1 0.1 0.0 0.0
9145 7713 6577 5661 4911 4289 3768 3327 2951 2627 2346 2101 1886 1697
16RB32 18 10.29 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.1 12 1.3 1.4 1.5 1.6 1.7
02 0.2 0.2 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.4 0.4 0.4
9 834 8397 7237 6288 5502 4843 4285 3809 3399 3043 2733 2461 2221
16RB36 20 11.64 0.5 0.6 0.7 0.8 0.9 1.0 1.0 1.1 1.2 1.3 1.4 1.5 1.5
0.2 0.2 0 .2 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4 0.4 0.4
9010 7839 6867 6054 5365 4777 4271 3832 3449 3113 2817
16RB40 22 13.00 0.6 0.7 0.8 0.9 1.0 1.0 1.1 1.2 1.3 1.4 1.4
02 0.2 0.3 0.3 0.3 0 .3 0.3 0.4 0.4 0.4 0.4

PCI Design Handbook/Pifth Edition 2 -4 1


L-BEAMS
Normal W eight Concrete
Section Properties
JH/h2 A 1 Yb sb s, wt
Designation tor in. in* in4 -in 3 in3
in. P it
2GLB20 20 12/8 304 10,160 8.74 1,163 902 ; 317
20LB24 24 12/12 384 17,568 10.50 1,673 1,301 400
20LB28 28 16/12 432 . 27,883- 122 2 _ 2,282 1 ,767. 450
20LB32 32 .20/12 480 41,600 14.00 2,971 .2,311 500-
20LB36 36 24/12 528 59,119 15-82 : . 3,737 2,930 SO
20LB40 ' 40 24/16 608 81,282 17.47 4,653 3,608 633
20LB44 44 28/16 656 106,107 19.27 5,610 4/372 683
20LB48 48 32/16 704 140,133 " 21.09 6,645 5,208 733
20LB52 52 36/16 752 177,752 22.94 7 ,7 49 6,117 783
f' ■= 5,000 psi 20LB56 56 40/16 800 221,355 24.80 8,926 7,095 833

fpu = 270,000 psi 20LB60 60 44/16 848 271,332 26.68 10,170 8,143 883

1. Check local area for availability o f other sizes.


V2in. diameter
2. Safe loads shown include 50% superim posed d ead lead and 50% live load. 800 psi
low-relaxation strand top tension has been allowed, therefore additional top reinforcement is required.
3. Safe loads can b e significantly increased by u se o f structural com posite topping.
Key
6,471 — Safe superimposed service load, plf
0.3 — Estimated camber at erection, in.
0.1 — Estimated long-time camber, in.

Table of safe superimposed service load (plf) and cambers

Span, ft
Desig- No.
nation Strand 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
6471 5053 4038 3288 2717 2273 1920 1636 1403 1210 1049
20LB20 9 6.00 0.3 0.4 0.5 0.5 0.6 0.7 0.8 0.9 1.0 1.0 1.1
0.1 0.1 0.1 0.2 0.2 0.2 02 0.2 02 0.2 0.1
9518 7444 5961 4864 4029 3380 2865 2449 2108 1826 1590 1390 1219 1072
20LB24 10 7.37 0.3 0.3 0.4 0.4 0.5 0.6 0.7 0.7 0.8 0.9 cr.9 1.0 1.0 1.1
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0
- 8193 6701 5566 4682 3981 3416 2953 2569 2248 1976 1744 1544 1370 1219 1087 970
20LB28 12 8.56 0.3 0.4 0.5 0.5 0.6 0.7 02 0.8 0.9 1.0 1.0 1.1 1.1 1.1 1.2 1.2
0.1 0.1 0.1 0.1 0.2 0.2 0.2 02 0.2 0.1 0.1 0.1 0.1 0.0 0.0 - 0.1
8820 7339 6187 5272 4534 3931 3430 3011 2656 2353 2092 1866 1669 1496 1343
20LB32 14 9.80 0.4 0.4 0.5 0.6 0.6 0.7 0.8 0.8 0.9 1.0 1.0 1.1 1.1 12 1.2
0.1 0.1 0.2 0.2 02 0 .2 02 02 0.2 0.2 0.2 0.2 0.1 0.1 0.1
9335 7881 6727 5796 5034 4402 3873 3425 3043 2714 2428 2180 1961 1768
20LB36 16 11.05 0.4 0.5 0.5 0.6 0.7 0.7 0.8 0.9 0.9 1.0 1.1 1.1 12 1.2
0.1 0.2 02 0.2 0.2 02 0.2 0.2 0.2 0.2 0.2 02 0.2 0.2
9663 8253 7116 6185 5413 4767 4220 3752 3350 3002 2698 2431 2196
20LB40 18 11.99 0.4 0.5 0.5 0.6 0.6 0.7 0.8 0.8 o;9 1.0 t.O 1.1 1.1
0.1 0.2 02 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
8866 7718 6766 5969 5294 4717 4221 3791 3416 3087 2797
20LB44 19 13.61 0.5 0.5 0.6 0.7 0.7 0.8 0.8 0.9 0.9 1.0 1.0
0.1 0.2 02 02 0.2 02 0.2 0.2 0.2 0.2 02
9231 8101 7155 6353 5669 5081 4570 4125- 3735 3390
20LB48 21 14.86 0.5 0.6 0.6 0.7 0.7 0.8 0.9 0.9 1.0 1.0
0.2 0.2 02 0.2 0.2 0.2 0.2 0.2 0.2 02
9545 8438 7500 6700 6011 5415 4894 4437 4033
20LB52 23 16.12 0.5 0.6 0.6 0.7 0.8 0.6 0.9 0.9 1.0
02 0.2 0.2 02 02 0.2 0.2 0.2 0.2
9817 8733 7808 7012 6323 5721 5192 4726
20LB56 25 17.37 0.6 0.6 0.7 0.7 0.8 0.8 0.9 0.9
0.2 0.2 0.2 0.2 02 02 0 .3 0.3
8996 8086 7296 6608 6004 5470
20LB60 27 18.63 0.6 0.7 0.7 0.8 0.9 0.9
02 02 0.2 0.3 0.3 0 .3

2 -4 2 PCI Design Handbook/Fifth Edition


L-BEAMS
Normal Weight Concrete
SeetionProperties
- h A 1 s„ s, wt
y&
Designation
in. in. in* in.4 in. in3 in 3 p it
26LB20 20 12/8 424: 14,298 . 9.09 = 1,573 1,311 442
26LB24 24 12/12 528 2 4 ,7 1 6 10 .91 2,265 1,888 550
26LB28 28 16/12 600 39,241 12.72 3,085 2,568 625
26LB32 32 2 0 /12 672 58,533 14.57- ' 4,017 3,358 700
26LB36 36 24/12 7 44 83,176 16.45 5,056 4,255 775
26LB40 40 24/16 848 114,381 18.19 6,288 5,244 883
26LB44 44 28/16 920 152,104 20.05 7,586 6,351 958

2'- 2 " 26LB48 48 32/16 992 187,159 21.94 8,986 7,566 1,033
26LB52 52 36/16 1,064 250,126 23.83 10,496 8879 1,108
f; = 5,000 psr 26LB56 56 40/16 1,136 311,586 25.75 12,100 10,300 1,183
fpu = 270,000 psi 26LB60 60 _ 44/16 1,208 382,118 27.67 13,810 11,819 1,258

1. Check local area for availability of other sizes.


Vz in. diameter
2. Safe loads shown include 50% superim posed dead load and 50% live load. 800 psT
low-relaxation strand top tension has b een allowed, therefore additional top reinforcement is required.

Key 3. Safe loads ca n b e significantly increased by u s e of structural composite topping.


9,737 — Safe superimposed service toad, plf
0.4 — Estimated camber at erection, in.
0 .2 — Estimated long-time camber, in.

Table of safe superimposed service load (plf) and cambers

Span, ft
Desig­ No.
e
nation Strand 16 18 20 22 24 26 28 30 32 34 36 40 42 44
38 46 48 50
9737 7609 6088 4962 4106 3439 2911 2484 2135 1846 1603 1398 1223 1072
26LB20 15 6.35 0.4 0.5 0.6 0.7 0.6 0.9 1.0 1.1 1.3 1.4 1.5 1.6 1.7 1.7
0.2 0.2 0.3 0.3 0.4 0 .4 0.5 0.5 0.5 0.6 0.6 0.6 0.6 0.6
8987 7341 6089 5115 4342 3718 3208 2785 2430 2130 1874 1654 1463 1296 1150 1020
26LB24 15 7.78 0.4 0.5 0.6 0.7 0.8 0.9 0.9 1.0 1.1 1.2 12 1.3 1.3 1.4 1.4 1.4
0.1 0.2 0.2 0.2 02 02 02 02 02 0.2 02 0.1 0.1 0.0 0.0 - 0.1
8394 7069 6017 5169 4474 3899 3417 3009 2660 2361 2101 1874 1675 1499
26LB28 18 9.06 0.5 0.6 0.7 0.8 0.9 0.9 1.0 1.1 1.2 1.3 1.3 1.4 0.4 1.5
0.2 0.2 02 02 02 0.3 0.3 0.3 0.3 02 02 02 02 0.1
9325 7953 6847 5941 5191- 4562 4029 3575 3184 2845 2549 2289 2060
26LB32 21 10.37 0.6 0.6 0.7 0.8 0.9 1.0 1.0 1.1 1.2 0.3 1.3 1.4 1.4
0.2 02 02 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 02
8739 7596 6648 5855 5183 4609 4116 3688 3314 2987 2698
26LB36 24 11.68 0.6 0.7 0.8 0.9 1.0 1.0 1.1 1.2 1.3 1.3 1.4
02 0.3 0:3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
9338 8180 7210 6390 5689 5086 4563 4107 3707 3354
26LB40 27 12.71 0.7 0.7 0.8 0.9 02 1.0 1.1 12 12 1.3
02 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
9013 8001 7136 6392 5747 5185 4684 4244
26LB44 28 14.39 0.7 0.8 0.9 0.9 1.0 1.1 1.1 12
0.2 0.2 02 0.3 0.3 0.3 0.3 0.3
9590 8564 7681 6916 6248 5662 5145
26LB48 32 15.71 0.8 0.8 0.9 1.0 1.0 1.1 1.2
0.3 0.3 0.3 0.3 0.3 0.3 0.3
9077 8182 7401 6715 6110
26LB52 35 17.01 0.9 02 1.0 1.1 1.1
0.3 0.3 0.3 0.4 0.4
9544 8641 7849 7150
26LB56 37 18.32 0.9 0.9 1.0 1.0
0.3 0 .3 0.3 0.3
9972 9066 8266
2 6 LB6 0 38 1 9 .6 2 0.8 0.9 1.0
02 0.3 0.3

PCI Design Handbook/Fifth Edition 2 -4 3


INVERTED TEE BEAMS
Normal Weight Concrete
Section Properties.
h hi/h2 I Yb sb s, wt
Designation
in. in. ins in* in. in3 in3 .plf
28IT20 20 12/8 368 11,688 7.91 1,478 967 383
28IT24 24- 12/12 4 80 20,275 980 2,112 1,408 - 500
28IT28 28 1 6 /t2 528 32,076 11.09 2,892 1,897 550
28IT32 32 20/12 576 47,872 12.67 3,778 2477 600
28IT36 36 24/12 624 68,101 14.31 4,759 3,140 650
28TF40 40 24/16 736 93,503 15.83 5,907 3,869 767
281T44 44 28/16 784 124,437 17,43 7,139 4,683 817
28IT48 48 32/16 832 161,424 19.08 8,460 5,582 867
2'-4"
28IT52 52 36/16 880 204,884 20.76 9,869 6,558 917

fc = 5,000 psi 28IT56 56 40/16 928 255,229 22.48 11,354 7,614 967

fpu = 270,000 psi 28IT60 60 ; 44/16 976 312,866 24.23 1 2 2 1 2 _ 8,747 1017

1. Check local area for availability of other sizes.


'A in. diameter
2. Safe loads shown include 50% superim posed d ea d load and 50% live load. BOO psi
low-relaxation strand top tension has been albwed, tberetore additional top reinforcement is required.
3. Safe loads can b e significantly increased by use of structural composite topping.
Key
6 ,9 2 9 — Safe superimposed service load,_p!f
0.3 — Estimated camber at erection, in.
0.1 — Estimated long-time camber, in.

Table of safe superimposed service foad (pit) and cambers

Desig- No. Span, ft


nation Strand 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
6929 5402 4310 3502 2887 2409 2029 1723 1473 1265 1091
28IT20 9 5.82 0.3 0.3 0.4 0.4 0.5 0.6 0.6 0.7 0.7 0.8 0.6
0.1 0.1 0.1 0.4 0.1 0.1 0.0 0.0 0.0 -0 .1 -0 .1
9714 7580 6054 4925 4066 3398 2868 2440 2090 1799 1556 1351 1175 1024
28IT24 11 6.77 0.2 0.3 0.3 0.4 0.4 0.5 0.6 0.6 0.7 0.7 0.7 0.8 0.8 0.8
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 -0.1 -0 .2
8505 6951 5768 4848 4118 3529 3047 2648 2313 2 0 3 0 1788 1579 1399 1242 1103 981
28IT28 13 8.44 0.3 0.4 0.5 0.5 0.6 0.7 0.7 0.8 0.9 0.9 1.0 1.0 1.1 1.1 1.1 1.1
0.1 0.1 0.1 0.2 0.2 02 02 0.2 0.2 02 0.2 o.t 0.1 0.1 0.0 -0.1
9202 7646 6435 5474 4698 4064 3538 3097 2724 2406 2132 1894 1687 1505 1345
28IT32 15 9.17 0.3 0.4 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.8 0.8 0.9 0.9 0.9 0.9
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 -0.1
8485 7236 6227 5402 4718 4145 3660 3246 2890 2581 2311 2075 1866
28IT36 16 10.81 0.4 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.8 0.8 0 J9 0.9 0.9
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0 0.0 0.0 -0.1
8615 7415 6433 5620 4938 4361 3868 3444 3077 2756 2475 2226
28IT40 19 11.28 0.4 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.8 0.8 0.8 0.9
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0
9308 8092 7083 6239 5524 4913 4388 3932 3535 3186 2879

28IT44 20 12.89 0.4 0.5 0.5 0.5 0.6 0.6 0.7 0.7 0.8 0.8 0.8
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.0
9741 8539 7532 6680 5952 5326 4783 4310 3894 3528
28IT48 22 14.16 0.4 0.5 0.5 0.6 0.6 0.7 0.7 0.8 0.8 0.8
0.1 0.1 0.1 -0.1 0.1 0.1 0.1 0.1 0.1 0.1
8935 7934 7080 6345 5707 5151 4664 4233
28IT52 24 15.44 0.5 0.5 0.6 0.6 0 .7 0.7 0.8 0.8
0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
9284 8294 7442 6703 6059 5493 4994
28IT56 26 16.74 0.5 0.6 0.6 0.7 0.7 0.8 0.8
0.1 0.1 0.1 0.1 0.1 0.1 0.1
9590 8613 7766 7027 6379 5807
28IT60 28 18.04 0.6 0.6 0.6 0.7 0.7 0.8
0.1 0.2 0.2 0.2 0.2 0.2

2 -4 4 PCI Design Handbook/Fifth Edition


INVERTED TEE BEAMS
N erm alW eight Concrete
Section-Properties
h - hi/h2 A I 7b sb s, wt
Designation
in. in. in2 in* in; : in3 in3 pit
34IT20 20 12/8-- - 4 88 16,082 8 t43 1,908 1,390 508
341T24 24 12/12 624 27,825 10.15 2,741 2,009 650
34IT28 28 16/12 696 44,130 1179 3,743 2,722 725
341T32 32 20/12 768 65,856 13.50 4,878 3,560 800
34IT36 36 24/12 840 93,616 4 5 .2 6 6,136 4,513 - 875
34IT40 40 24/16 976 128,656 16.85 7,635 5,558 1,017
34IT44 44 28/16 1,048 171,157 18.58 9,212 6,733 1,092
34IT48 48 32/16 1,120 221,906 20.34 10,910 8,023 1,167
2 ' - 10"
34IT52 52 36/16 1,192 281,504 22.13 12,721 9,424 1,242

34IT56 56 40/16 1,264 350,546 23.95 14,637 10,938 1,317


fc = 5,000 psi
34IT60 60 44/16 1,336 429,623 25.78 16,662 12,556 1,392
fpu = 270,000 psi
1. Check local area for availability oT other sizes.
V2 in. diameter 2. Safe loads shown include 50% superim posed dead load and 50% live load. 800 p si top
low-relaxation strand tension has b een allowed, therefore additional top reinforcement is required.
3. Safe loads can b e significantly increased by use of structural composite topping.
Key
8 ,1 6 4 — Safe superimposed service load, pit
0.4 — Estimated camber at erection, in.
0.1 — Estimated long-time camber, in.

Table of safe superimposed service load (plf) and cambers

Desig- NO. Span, ft


Strand e
nation 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50
8164 6525 5313 4391 3674 3104 2645 2 2 & 1 9 5 8 " 1697 1476 1287 112^ 984
34IT20 14 9.48 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.0 1.1 1.2 1.2 1.3 1 .2 1.3
0.1 0.2 0.2 02 0 .2 0.2 0.3 0.3 0.3 0.2 0.2 02 0.1 OO
9171 7478 6190 5167 4392 3750 3225 2790 2425 2116 1 8 5 3 " 1 6 2 6 " 1429 1258 1107 974
34IT24 17 7.32 0.4 05 0.6 0.6 0.7 0.8 0.9 0.9 1.0 1.1 1.1 1.2 12 1.2 12 1.2
0.1 0.2 0.2 0.2 02 02 0.2 0.2 0.2 02 02 02 0.1 0.1 0 - 0.1
8675 7295 6200 5316 4593 3994 3492 3 0 6 7 2704 2 3 & 2t21 1885 1678 1495
34IT28 20 8.63 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.0 1.1 1.1 1.2 12 1.3 1.3
0.2 0.2 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 02 02 02 0.1
9743 8301 7138 6186 "5397” 4736 4177 3699 3288 2932 2621 2348 l i o T
34IT32 23 10.00 0.5 0.6 0.7 0.7 0.8 0.9 1.0 1.0 1.1 1.2 12 1.3 1.3
0.2 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 02
9477 8239 7207 6340 5605 4978 4439 3971 3563 3205 2892
34IT36 24 12.32 0.7 0.7 0.8 0.9 1.0 1.0 1.1 12 1.3 12 1.4
0.2 02 0.3 0.3 0.3 0.3 0.3 0 .3 0.3 0.3 0.3
9771 8550 7527 6662 5923 5287 4735 4254 3832 3460
34IT40 30 12.30 0.6 0.7 0.8 0.8 0.9 1.0 1.0 1.1 12 1.2
0.3 0.3 0.3 0.3 0.3 0.3 0.4 0.4 0.4 0.4
9478 8406 7490 6702 6019 5423 4900 4439
34IT44 30 14.04 0.7 0.7 0.8 0.9 0.9 1.0 10 1.1
0.2 0.2 02 02 0.2 02 02 0.2
9049 8110 7295 6585 5962 5412
34IT48 33 15.42 0.8 0.8 0.9 0.9 1.0 1.1
0.2 0.2 02 0.3 0.3 0.3
9637 8681 7848 7116 6470
34IT52 36 16.81 0.8 0.9 0.9 1.0 1.0

0.3 0.3 0.3 0.3 0.3

9208 8360 7611


34IT56 39 18.21 0.9 0.9 1.0
0.3 0.3 0.3
9689 8831
34IT60 42 19.59 0.8 0.9
0.2 0.2

PCI Design Handbook/Fifth Edition 2 -4 5


INVERTED TEE BEAMS
Q JI 2 '- 0 " 6" JSormal Weight Concrete
SectionProperties

Designation
Wh2 A 1 yb s> wf
ta. in. in2 1n« in. in3 in3 p lf

40IT20 1 20 -12/8 608 20,321 -8.74 2325 1,805 633


40IT24 24 12/12 768 35,136 1050- 3,346 2,603 800
40IT28- 28 16/12 864 55,765 12.22 4,563 3,534 900

401T32 32 20/12 960 83,200 14.00 5,943 4 ,6 2 3 1,000

40IT36 36 24/12 1,056 118,237 15.82 7,474 5,859 1,100

40IT40 40 24/16 1,216 162,564 17.47 9,305 7,2 15 1,267

40IT44 44 28/16 .1,312 216,215 19.27 11,220 8,743 1,367


3'-4"
401T48 48 32/16 1,408 280,266 21.09 13,289 10,415 1,467
40IT52 52 36/16 1,504 355,503 22.94 15,497 1 2 3 33 1,567
fo = 5,000 psi
fpu = 270,000 psi 1. Check /oca/ area for availability of other sizes,
2. Safe toads shown include 50% superim posed dead load and 50% live load. 800 psi top
1/2 in. diameter tension has been allowed, therefore additional top reinforcement is required.
low-reiaxation strand 3. Safe loads can b e significantly increased by u se of structural composite topping.
Key
8,741 — Safe superimposed service load, plf
0.5 — Estimated camber at erection, in.
0 . 2 — Estimated long-time camber, in.

Table of safe superimposed service load (plf) and cambers

Desig- No. Span, ft


e 48 50
nation Strand 20 22 24 26 28 30 32 34 36 38 40 42 44 46
8741 7124 5895 4938 4179 3567 3066 2650 2302 2008 1756 1538 1349 1184 1039
40IT20 18 6.65 0.5 0.6 . 0.7 0.8 0.9 1.0 1 .1- 1.2 1.3 1.4 1.4 1.5 1.5 1.5 1.5
0.2 0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2 0.2 0.1 0.0 0.1
8313 6976 5916 5060 4360 3780 3293 2882 2530 2228 1966 1737 1536 1359
400IT24 22 7.67 0.6 0.7 0.8 0.9 1.0 1.0 1.1 1.2 1.3 1.3 1.4 1.4 1.4 1.4

0.2 0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2 02 0.1 0.0

9787 8327 7149 6185 5386 4716 4149 3666 3249 2888 2573 2297 2053
40IT28 26 9.06 0.6 0.7 0.8 0.9 1.0 1.0 1.1 12 1.3 1.3 1.4 1.5 1.5
0.2 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.2
9577 8308 7256 6375 5629 4992 4444 3969 3555 3191 2870
40IT32 30 10.50 0.7 0.8 0.9 1.0 1.1 1.1 1.2 1.3 1.4 1.4 1.5

0.3 0.3 0.3 0.3 0.4 0.4 0.4 0 .4 0.4 0.4 0.3

9610 8453 7474 6638 5918 5295 4751 4276 3860


40IT36 32 12.32 0.8 0.9 1.0 1.0 1.1 12 1.3 1.3 1.4
0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
8963 7977 7129 6394 5753 5190 4694
40IT40 38 12.92 0.9 1.0 1.0 1.1 12 1.2 1.3
0.3 0.3 0.4 0.4 0.4 0 .4 0.4

9016 8106 7311 6614 5999


40IT44 40 14.73 - 1.0 1.0 1.1 1.2 12
0.3 0.3 0.3 0.3 0.3
9808 8861 8030 7296
40IT48 44 16.17 1.0 1.0 1.1 12
0.3 0.3 0.3 0.4

9537 8666
40IT52 48 17.62 1.0 1.1
0.3 0.3

2 -4 6 PCI Design Handbook/fifth Edition


PRECAST, PRESTRESSED COLUMNS
Figure 2.6.1 Design ^tcength interaction cu rves for precast, p/estressed concrete colum ns

CRITERIA
1. MINIMUM-PRESTRESS = 225 psi

2. ALL STRAND ASSUMED 1/2 in. DIAMETER, fpu = 270 ksi

3. CURVES SHOWN FOR PARTIAL DEVELOPMENT O F


STRAND NEAR MEMBER END WHERE * fse

4. HORIZONTAL PORTION OF CURVE IS THE MAXIMUM


FOR TIED COLUMNS = 0.80 <t>P0.

5. <(> VARIES LINEARLY FROM 0.9 FOR TENSION-CON-


TROLLED SECTIONS TO 0 .7 FOR COMPRESSION-CON­
TROLLED SECTIONS IN ACCORDANCE WITH ACI 318-95
SECT. B.9.3.2.

USE OF CURVES NOTATION


1. ENTER AT LEFT W ITH APPLIED FACTORED AXIAL <(>P„ = DESIGN AXIAL STRENGTH
LOAD, Pu
<j>Mn = DESIGN FLEXURAL STRENGTH
2. ENTER AT BOTTOM WITH APPLIED MAGNIFIED FAC­ <t>P„ = DESIGN AXIAL STRENGTH AT ZERO ECCENTRICITY
TORED MOMENT, 6MU
Ag = GROSS AREA OF THE COLUMN
3. INTERSECTION POINT MUST BE TO THE LEFT OF 8 = MOMENT MAGNIFIER (SECT. 10.11-10.13 ACI 3 1 8 -9 5 )
CURVE INDICATING REQUIRED CONCRETE
STRENGTH.

30 60 90 120 150

(|)M n, k ip -ft (|)M n, k ip -ft

PCI Design Handbook/Fifth Edition 2 -4 7


PRECAST, PRESTRESSED COLUMNS
Figure 2.6.1 Design strength interaction ^curves for precast, prestressed concrete cotomns (cont.)

1800

1600

1400

1200

1000

800

600

400

200

0 50 100 150 200 250 300 0 50 100 150 200 250 300 350 400

<t>Mn, kip-ft <t>Mn> kip-ft

0 100 200 300 400 500 600 0 100 200 300 400 500 600 700 800 900

4>Mn, kip-ft kip-ft

2 -4 8 PCI Design Handbook/Fifth Edition


PRECAST, REINFORCEtTGOUJMNS
Figure 2.6.2 Design strength interactioncurves for precast, reinforced concretecotam ns

CRITERIA
1. CONCRETE ft = 5000 psi
2. REINFORCEMENT fy = 60,000 psi

3. CURVES SHOWN FOR FULL DEVELOPMENT OF


REINFORCEMENT
4. HORIZONTAL PORTION OF CURVE IS T H E MAXIMUM FOR
TIED COLUMNS = 0.80 (|>P0.
5. (|) VARIES UNEARLY FROM 0.9 FOR TENSION-CONTROLLED
SECTIONS TO 0.7 FOR COMPRESSION-CONTROLLED
SECTIONS IN ACCORDANCE WITH ACI 318-95 SECT.
B.9.3,2.

PRIMARY STEEL
USE O F CURVES NOTATION
1. ENTER AT LEFT W ITH APPLIED FACTORED AXIAL 4»Pn = DESIGN AXIAL STRENGTH
LOAD, Pu
(j>M„ = DESIGN FLEXURAL STRENGTH
2. ENTER AT BOTTOM WITH APPLIED MAGNIFIED FAC­ <t>Po = DESIGN AXIAL STRENGTH AT ZERO ECCENTRICITY
TORED MOMENT, 8M„
Ag = GROSS AREA OF THE COLUMN
3. INTERSECTION POINT MUST BE TO THE LEFT OF 8 = MOMENT MAGNIFIER (SECT. 10.11-10.13, ACI 318-95)
CURVE INDICATING REQUIRED REINFORCEMENT.

THE INTERACTION CURVES HAVE BEEN SMOOTHED FOR PLOTTING PURPOSES.


EXACT CALCULATED VALUES MAY BE SLIGHTLY DIFFERENT.

25 50 75 100 125 25 50 75 100 125 150 175 200

4>Mn, kip-ft <j)Mn, kip-ft

PCI Design Handbook/Fifth Edition 2 -4 9


PRECAST, REINfORCED COLUMNS
-igure 2.6.2 ^Design strength interaction cufves^or precast, reinforcedooncrete^cohHnns (continued)

2200

2000

1800

1600

1400

1200

§. 1000

9-C 800

600

400

200

0 100 200 300 400 500 600 a 100 200 300 400 500 600 7 00 800 900 1000

<(>Mn, kip-ft <t>Mni kip-ft

2 -5 0 PCI Design Handbook/Fifth Edition


DOUBLE TEE WALL PANELS

■iaureiS^ Partiatinteraction curves for prestressed double tee wall panels^

FULL INTERACTIO N CURVE-DATA


VARIES 8 '-0 " T 0 1 2 '- 0 "
PARTIALLY DEVELOPED FULLY DEVELOPED
STRAND FORCE STRAND FORCE
5%"
i r ii MARK
h
in.
i NO.
in. STRB <t*Po <^Pnb 4Mnb 4>M0 <l>Pnb <t»Mnb

Th 5DT16
10DT16
16
16
2
2
4
4
936
1,079
579
706
17&
192
64
64
542
668
197
211
107
108

4'-0"
-H 3%" ~1 12DT16
8DT17
16
17
2
3
4
4
1,222
1,222
834
825
203
215
64
71
798
783
223
235
108
119
10DT17 17 3 4 1,436 1,028 228 71 978 250 120
12DT17 17 3 4 1,650 1,233 238 71 1,191 261 121
fc = 5000 psi, NORMAL WEIGHT
STRAND = Vs" DIAMETER, fpg = 270 ksi

c
3
w
CD
a
ID
a
12
c
D.

20 40 60 80 10Q 120 140 160

<t>Mn, kip-ft per unit

c
3
k.
CD
a
ID
CL
12
c
0.
-e-

kip-ft per unit

PCI Design Handbook/Frfth Edition 2 -5 1


HOLLOW-CORE AND SANDWtCH WALL PANELS

;igure 2.6,4 Partiafinteractton curves for prestressed hollow-core and sandwich wall panels

WIDTH V A R IE S ! FULL INTERACTION CURVE DATA


PARTIALLY DEVELOPED FULLY DEVELOPED
STRAND FORCE STRAND FORCE
Ji (per I f ) (per ft)

MARK in. «>Pe 4Pnb $Mnb 4M. <Pnb 4Mnb <f>M0


HC6 6 112 50 10 3.5 45 10 6.0
CURVESBASED ON MINIMUM PRACTICAL PRESTRESS, HC8 8 127 58 16 4.8 52 16 8.3
NOT LESS THAN 225 psi HC10 10 143 66 22 6,0" 59 22 10.3
fc= 5000 psi; fp„ = 250 ksi HC12 T2 159 74 29 7.4 67 29 12.5
WIDTH AND CONFIGURATION MAY VARY
10
PARTIALLY DEVELOPEI3 I
STRAND

"8

LOAD-BEARING WYTHE 1
1
doQQQ- ]'h 1
£ (O oo|
of cm
a 0 Q o| O
12 1 xf if I
PARTIALLY COMPOSITE
OR NON-COMPOSITE £ 4
a
-©■

6 8 10 12 14
<(>Mn, kip-ft/ft
10
FULLY DE VELGPED
STRAND

CO 0) evil
H C 10

O c) ^ 1
X 3 ol
a X
12
£ 4
a
-e-

6 8 10 12 14
4>Mn, kip-ft/ft

2 -5 2 PCI Design Handbook/Frfth Edition


PRECAST, PRESTRESSED SO LI DAN D SANDW1CHWALL PANELS

rigure 2.6.5 Partial tateraction carves fo r p re stre sse d solid o n d sandwich wall panels

FULL INTERACTIO N; CURVE-DATA


PARTIALLY DEVELOPED FULLY DEVELOPED
STRANDFORCE STRAND FORCE
(per ft) (per ft)
T
t in. *Po *t^Pnb 4>M„b 1>Mo 4*Pnb 0M„b *M0
A 140 65 6.0 1.6 65 6.0 2.6
CURVES BASED ON MINIMUM PRESTRESS O F 225 psi 6 209 97 13.4 3.6 97 13,4 5.9
fc = 5000psi 8 279 129 2318 6.4 129 23.8 10.5
fpu = 270 ksi 10 349 162 37.2 9.9 162 37.2 16.3

FULLY COMPOSITE
SANDWICH PANEL

- LOAD-BEARING WYTHE

D> a
12
c
Ql
PARTIALLY COMPOSITE -0-
OR NON-COMPOSITE

0 4 8 12 16 20 24 28

<J)Mn, kip-ft/ft

0 4 8 12 16 20 24 28

d>Mn, kip-ft/ft

PCI Design Handbook/Fifth Edition 2 -5 3


PRECAST, REINFORCED SOLID AND SANDWICH WALL PANELS

Figure 2.6.6 Partial Interact! oncurves for precast, reinforced concrete-wall panels

i 11/2 in.

■-T" • ' - FULL INTERACTION CURVE DATA


tin . 4>P. 4Pnb 4Mnb <t>M0
t = 4 in. OR 6 in. t = 8 in. OR 10 in. 4 145 72 6.0 0.5
6 217 108 13.4 1.0
CURVES BASED ON MINIMUM VER­
8 289 142 24.4 1.8
TICAL REINFORCEMENT p = 0.10% 10 362 176 38.3 2.8
fc= 5000 psi; fy = 60,000 psi per foot width of panel

2 -5 4 PCI Design Handbook/Fifth Edition


FILES
Table 2.7.1 Section properties and allowable service ioadeof prestressed concrete piles
SIZE SIZE -SIZE SIZE

CONTINUOUS
TIE

PRESTRESSING
STRAND * SQUARE SQUARE O CTAGONAL SO LID
SOLID HOLLOW OR HOLLOW RO UND

Z , 5o Tlurci
5 TURNS @1
;?’\ z 16 TURNS @ 3"
6" PITCH
16 TURNS @ 3"
\
^1"
URNS@ 1"

\ li
TYPICAL ELEVATION

Strand pattern may be circular or square


S E C T IO N PROPERTIES 8 ALLOWABLE C O N C E N TR IC
CO RE SERVICE LOADS, tons b
'IZ E (in.) M OM ENT SECTIO N RADIUS OF PERI­
DIA. (in.) AREA WEIGHT fi
O F INERTIA M ODULUS GYRATION METER
(in*) (PH) (In4) On3) (in.) (in.) 5000 6000 8000 10,000

SQ UARE R ILES

10 SOLID 100 104 833 167 2.89 3.33 73 89 122 156


12 SOLID 144 150 1,728 288 3.46 4.00 105 129 176 224
14 SOLID 196 204 3,201 457 4.04 4.67 143 175 240 305
16 SOLID 256 267 5,461 683 4.62 5.33 187 229 314 398
18 SOLID 324 338 8,748 972 5.20 6.00 236 290 397 504
20 SOLID 400 417 13,333 1,333 5.77 6.67 292 358 490 622
20 11 305 318 12,615 1,262 6.43 6.67 222 273 373 474
24 SOLID 576 600 27,648 2,304 6.93 8.00 420 515 705 896
24 12 463 482 26,630 2,219 7.58 8.00 338 414 567 720
24 14 422 439 25,762 2,147 7.81 8.00 308 377 517 656
24 15 399 415 25,163 2,097 7.94 8.00 291 357 488 621
30 18 646 672 62,347 4,157 9.82 10.00 471 578 791 1005
36 18 1,042 1,085 134,815 7,490 11.38 12.00 761 933 1,276 1,621

O CTAGONAL PILES

10 SOLID 83 85 555 111 2.59 2.76 60 74 101 129


12 SOLID 119 125 1,134 189 3.09 3.31 86 106 145 185
14 SO UD 162 169 2,105 301 3.60 3.87 118 145 198 252.
16 SO UD 212 220 3,592 449 4.12 4.42 154 189 259 330
18 SOLID 268 280 5,705 639 4.61 4.97 195 240 328 417
20 SOLID 331 345 8,770 877 5.15 5.52 241 296 405 5-15
20 11 236 245 8,050 805 5.84 5.52 172 211 289 367
22 SOLID 401 420 12,837 1,167 5.66 6.08 292 359 491 624
22 13 268 280 11,440 1,040 6.53 6.08 195 240 328 417
24 SOLID 477 495 18,180 1,515 6.17 6.63 348 427 584 742
24 15 300 315 15,696 1,308 7.23 6.63 219 268 368 467

RO UND PILES

36 26 487 507 60,007 3,334 11.10 9.43 355 436 596 758
42 32 581 605 101,273 4,823 13.20 11.00 424 520 712 904
48 38 675 703 158,222 6,592 15.31 12.57 493 604 827 1,050
54 44 770 802 233,373 8,643 17.41 14.14 562 689 943 1,198
66 54 1,131 1.178 51 4.02 7 1 5 ,577 21 .32 17.28 82 6 1,013 1,386 1.759
a. Form dimensions may vary with producers with corresponding variations in section properties.
b. Allowable loads based on N = Ag(0.33fc - 0.27fpo);fpc = 700 psi. Check local producer for available concrete strengths.

PCI Design Handbook/Fifth Edition 2 -5 5


SHEET PILES
TakieJ2.7.2 Section properttes and allowable moments of prestressed sheet piles

SECTIO N B
ELEVATION OF TYPICAL UNIT

SECTION PROPERTIES PER FOOT O F W ID TH


M AXIMUM ALLOWABLE
THICKNESS SERVICE LOAD M O M E N Tb
M O M ENT OF SECTIO N
W EIG HT8 kip-ft PER FOOT
t, in. AREA, in2 INERTIA MODULUS
psf
in4 in3 fe = 5 0 0 0 p si f c = 6 0 0 0 p si

6C 72 75 216 72 6.0 7.2


8° 96 100 512 128 10.6 12.8
10 120 125 1,000 200 16.6 20.0
12 144 150 1,728 288 24.0 28.8
16 192 200 4,096 512 42.7 51.2
18 216 225 5,832 648 54.0 64.8
20 240 250 8,000 800 66.7 80.0
24 288 300 13,824 1,152 96.0 115.2
a. Normal weight concrete
b. Based on zero tension and maximum 0A% compression
c. Strand can be placed in a single layer in thin sections.
Where site conditions require it, strand may be placed eccentrically.

2 -5 6 PCI Design Handbook/Fifth Edition


CHAPTER 3
ANALYSIS AND DESIGN OF PRECAST,
PRESTRESSEDCONCRETE STRUCTURES
3.1 G eneral............................................ . . ................................... ............................. 3 - 3
3.1.1 N otation................. 3 -3
3.1.2 Introduction................................................... 3 -5

3.2 Preliminary A na lysis...............................................................................................3 - 6


3.2.1 Framing Dim ensions...................................... 3 -6
3.2.2 Span-to-Depth R a tio s ........................ 3 -6
3.2.3 Lateral Load Resisting Systems ........................................................... 3 -6
3.2.4 Control of Volume Change Deformations and Restraint Forces . . . 3 -7
3.2.5 Connection C oncepts............................................................................ 3 - 7

3.3 Volume Changes.....................................................................................................3 - 7


3.3.1 Axial Volume Change Strains ............................................................... 3 -7
3.3.2 B ow ing................................. . ...............................................................3 - 8
3.3.3 Expansion J o in ts ..................................................................................3-11
3.3.3.1 Spacing of Expansion Joints ................................................ 3-11
3.3.3.2 Width of Expansion J o in ts ........, .............................. .......... 3-11

3.4 Component Analysis ................................................... 3 -1 1


3.4.1 Non-Bearing Wall P an e ls..................................... 3 -1 2
3.4.1.1 Deformations ......................................... 3 -1 2
3.4.1.2 Wind Load .......................................................... 3 -1 2
3.4.1.3 Panels with Openings............................................................. 3 -1 2
3.4.2 Load Bearing Wall Panels ...................................................................3 -1 3
3.4.3 Non-Bearing Spandrels .......................................................................3 -1 4
3.4.4 Load Bearing Spandrels.......................................................................3 -1 4
3.4.5 Eccentrically Loaded C olum ns........................................................... 3 -1 5

3.5 Slenderness Effects in Columns and Wall Panels .............................................3 -1 6


3.5.1 Second-Order (P-A) Analysis ................... 3 -1 7
3.5.2 Moment Magnification M e th o d ................... 3 -1 9
3.5.2.1 Moment Magnification Method for Non-Sway Frames___3 -1 9
3.5.2.2 Moment Magnification Method for Sway F ra m e s............. 3 -2 0

3.6 Diaphragm Design ...............................................................................................3 -2 3


3.6.1 Method of Analysis .............................................................................. 3 -2 3
3.6.2 Shear Transfer Between Mem bers..................................................... 3 -2 3
3.6.3 Chord F o rce s........................... 3 -2 4

3.7 Shear Wall Buildings ........................................................................................... 3 -2 5


3.7.1 General .................................................................................................3 -2 5
3.7.1.1 Relative Stiffness o f Shear Walls ........................................ 3 -2 6
3.7.1.2 Eccentricity of Lateral L o a d s..................................................3 -2 6
3.7.2 Rigidity of Solid Shear W a lls ............................................................... 3 -2 6
3.7.3 Distribution of Lateral L o a d s .............................. 3 -2 7
3.7.4 Unsymmetrical Shear W a lls.................................................................3 -2 7
3.7.5 Coupled Shear Walls ...........................................................................3 -2 9
3.7.6 Shear Walls with Large Openings ......................................................3 -2 9
3.7.7 Exterior Panels as Shear W a lls ........................................................... 3 -3 9
3.8 Moment-Resisting Building Fram es.....................................................................3-41
3.8.1 General .................................................................................................3-41
3.8.2 Moment Resistance of Column Bases................................................3-41

PCI Design Handbook/Fifth Edition 3 -1


8.8.3 Fixity of Column Bases . ...................................................................... 3 -4 4
3.8.4 Modeling Partiaffy Fixed-Bases............................... . . ........................ 3 -4 4
3.8.5 Volume Change Effects in Moment-Resisting F ram es__________ 3 -4 5
3.8.5.1 Equivalent Volume-Change...................................................3 -4 5
38.5.2 Calculating Restraint F o rce s................................................ 3 -4 7
3.8.6 Computer Models for Frame A na lysis................................... 3 -4 9
3.9 Shear Wall-Frame Interaction ..................... 3 -4 9
3.10 Structural Integrity............... . ...........................................................................3 -4 9
3.10.1 Introduction.......................... .............................................................. 3 - 4 9
3.10.2 Precast Concrete S tructures........ ...................................... 3 -4 9
3.10.3 Large Panel Bearing Wall Structures....................... - ........................3-51
3.10.4 Hybrid Structures.................................................................................. 3 - 5 t

3.11 Earthquake Analysis and D esign........................................................................ 3 -5 2


3.11.1 N otation............................................................. 3 -5 2
3.11.2 General ............................................................................ 3 -5 4
3.11.3 Building Code Requirements ..............................................................3 -5 5
3.11.4 Design Guidelines for Wall P anels..................................................... 3 -5 6
3.11.5 Design Guidelines For Shear Wall Structures ......................... 3 -5 7
3.11.6 Concept of Box-Type Shear Wall B u ild in g s.............. ........................ 3 -5 8
3.11.7 Example—1-Story Building .................................................................3 -5 8
3.11.8 Example—4-Story Building .................................................................3 -6 5
3.11.9 Example—3-Level Parking S tructure...................................................3 -7 2
3.11.10 Example—12-Story Building ...............................................................3 -7 7
3.11.11 Example—23-Story B u ild in g .............................................................. 3 -7 8
3.11.12 Example—Architectural Precast Panel .................. 3 -8 2

3.12 Design Aids ..........................................................................................................3 -8 6


3.13 References......................................................................................................... 3 -1 0 0

3 -2 PCI Design Handbook/Fifth Edition


ANALYSIS AND DESIGN OF
PRECAST, PRESTRESSED CONCRETE STRUCTURES

3.1 General h column width in direction of bending


h wall panel thickness or overall depth
-3.1.1 Notation
of bearas-or slabs
A = area (with subscripts)
h height of shear wall
Ab = total-area of anchor bolts which are
hs story height
in tension
1
1 moment of inertia
Aps = area of prestressing steel
1
*b moment of inertia of a beam
Avf = area o f shear-friction reinforcement

*bp moment of inertia of a base plate
Aw = area of shear wall
(vertical cross-section dimensions)
b = width of a section or structure
L
'C moment of inertia of a column
C = coefficient of thermal expansion
Igq approximate moment of inertia that
C = compressive force results in a flexural deflection equal to
cm a factor relating actual moment to the combined shear and flexural
equivalent uniform moment deflections of a wall

cu = factored compressive force If moment of inertia of the footing (plan


dimensions)
L> — dead load
I
'g uncracked moment of inertia
e = eccentricity of axial load
1 polar moment of inertia
'p
E = modulus of elasticity (with sub­
scripts) k effective length factor

= modulus of elasticity modified for kb,kf ,k, coefficients used to determine forces
Et
time-dependent effects and moments in beams and columns

= concrete compressive stress ks coefficient of subgrade reaction


f;
= compressive strength of concrete at K stiffnesses (with subscripts)
ft
time of initial prestress K' constant used for the calculation of
fpu = specified tensile strength of pre­ equivalent creep and shrinkage
stressing steel shortening

= modulus of rupture of concrete Kr relative stiffness


fr
= factored tensile stress K, constant used for the calculation of
fut
equivalent temperature shortening
y = yield strength of non-prestressed re­ o
c distance between wall panel sup­
inforcement
ports
F = horizontal forces in shear wall build­
ings and in moment-resisting frames t length of span or structure

= clear span
Fb degree of base fixity (decimal)
F, ~ lateral force at bay i or in shear e. distance from column to center of
wall i stiffness of structure

= restraining force in multi-story col­ unbraced length


F;
umns at level i fl w length of weld
Fu = factored force M unfactored moment
F-Jt,Fy = forces in x and y directions, respec­ Mc factored moment to be used for de­
tively sign of compression member
9 assumed length over which elonga- Mj = moment in multi-story columns at
tion of the anchor bolt takes place point j

PCI Design Handbook/Fifth Edition 3 -3


^resisting moment rigidity
moment due to toads causing appre­ Rdu factored dead load reaction
ciable sway + thickness
torsional-moment tensiTe force
T
factored moment
T' force due to wind suction
smaller factored end moment on a
T* nominal tensile strength
compression member, positive if
member is dent in single curvature, Tu factored tensile force
negative if bent in double curvature outside, inside temperature
factored end moment on a compres­ unit horizontal shear
Vh
sion member at the end at which M-,
acts, due to loads that cause no ap­ Vr unit shear on panel edge
preciable sidesway, calculated using Vu factored unit shear
a first-order elastic frame analysis
Vn nominal shear strength
factored end moment on compres­
W l shear at right, left support
sion member at the end at which Mi
acts, due to toads that cause appre­ factored shear force
ciable sidesway, calculated using a
total wind shear
first-order elastic frame analysis
W uniform load
larger factored end moment on com­
pression member, always positive W total lateral or gravity load

factored end moment on compres­ Xi distance from face of column to cen­


sion member at the end at which M2 ter of anchor bolts
acts, due to loads that cause no ap­ x2 distance from face of column to base
preciable sidesway, calculated using plate anchorage
a first-order elastic frame analysis
x ,y orthogonal distances of individual
factored end moment on compres­ shear walls from center of rigidity
sion member at the end at which M2
acts, due to toads that cause appre­ X, orthogonal distances locating center
ciable sidesway, calculated using a of rigidity of building
first-order elastic frame analysis Yb.Yt dimensions from center of gravity to
number of panels in a shear wall; opposite ends of irregular shear wall
number of bays in a moment-resist­ elements
ing frame z plastic section modulus
normal force a strain gradient across thickness of
lateral force in wall panels to restrain wail panel
bowing a angle to direction of shear
applied axial load Pd dead load/total load ratio
vertical load acting at eccentricity e T flexibility coefficient (with subscripts)
lateral force applied to shear wall 8 moment magnifier (with subscripts)
critical buckling load 5 volume change shortening (with sub­
axial toad nominal strength of a com­ scripts)
pression member with zero eccen­ 8e equivalent volume change shorten­
tricity ing (with subscripts)
final prestress force in tendons A maximum volume change deflection
(see Figure 3.12.10)
factored axial load
statical moment A total equivalent shortening or column
deflection
radius of gyration

PCI Design Handbook/Fifth Edition


A thermal bowJn waH panels' 1. Maximize repetitive or modular dimensions for
pJanlayaut and members.
A — sum of flexure and shear deflections
in sheat walls 2. Use simple spans whenever possible.
3. Standardize the sizeendlocations of openings
A = lateral- deflection o f a-compression
in products.
member
4: Use standard, locally available member sizes.
Au = deflection due to factored loads
5. Minimize the number o f different membertypes
= see Figure 3.12.14 and sizes.
n
8 = see Figure 3.12.14 6. Minimize the number of different reinforcing
patterns in a particular member type.
0 = rotation of cantilever
7. Minimize the number of different types of con­
X = see Figure 3.12.14 nections.

n = static coefficient of friction 8. Specify connection types that are preferred by


local producers.
= effective shear-friction coefficient
9. Consider the size and weight of products to
- strength reduction factor avoid premium costs associated with produc­
<l> = rotation (with subscripts) ing, shipping and erecting oversize and over­
weight pieces.
<l>k = stiffness reduction factor
10. Utilize prestressing in precast members when
¥ = ratio of column to beam stiffnesses spans are long, when the member depth must
be minimized, or when the greatest degree of
crack control is desired.
11. Avoid member designs and connection de­
signs that require skill levels of workmanship
and close tolerances that are not attainable un­
der a producer’s normal plant operation.
12. Avoid specifying requirements in excess of
what is needed for concrete mix designs, allow­
able stresses, allowable deflections, and coat­
3.1.2 Introduction ings on reinforcing steel, embedded hardware
and connection hardware.
Chapters One and Two have illustrated the
13. Make use of exterior wall panels as load bearing
versatility and desirability of precast concrete for use
members whenever possible.
as a construction material. From the text, figures and
14. Contact a local producer as early as possible
photographs, it is seen that the benefits and
during the design development stages of a
advantages of using precast concrete building
project for assistance in answering the above
products are limited only by the designer’s imagina­
questions.
tion and knowledge of how to “engineer” the material.
This chapter provides guidelines and design exam­
When analyzing and designing precast concrete
ples to increase the designer’s knowledge of the
design and analysis of precast concrete structures. structures, it is important to pay particular attention to
Design procedures presented in this chapter fol­ the following two principles:
low ACI 318-95 and other relevant national model 1. Load Path: Create astructural model that ideal­
building code requirements except where modified to izes the structure for analysis and that empha­
reflect current industry practice (see also Sect. 10.5). sizes a clear, rational, determinate load path. It
Engineering precast concrete requires unique de­ is essential that the model trace the design
sign considerations not required for most other build­ loads from their point of origin, through the ap­
ing materials. When designing precast concrete, the propriate members and connections, to the end
designer needs to consider manufacturing, handling of the load path at the final support or founda­
and erection aspects o f the product in addition to tion.
analysis and design for in-place loads. It is not un­
common for these items to be the controlling factors 2. Ductility: Although not always required by code,
in the design. it is desirable to design the members and their
Optimal building designs can be achieved by fol­ connections to achieve a ductile, rather than a
lowing these general principles: brittle failure mode.

PCI Design Handbook/Rfth Edition 3 -5


3.2 Preltmmary-Analy si s Where this ratio is high, deeper sections maybe need­
ed.
Maximum economy occurs-when the building is
For non-prestressed flexural-members, span-
laid out to take advantage of-the principles discussed
depth ratios are given in ACI 318-95, S ect 9.5.2.1.
above. The primary considerations in preiirainary
anatysis of the total structure-are: 3.2.3 Lateral Load Resisting Systems
1. Framing dimensions. Methods used to resist lateral loads, in the approxi-
2. Span-to-depth ratios. mate order of economy, include:
3. Lateral load resisting systems.
1. Shear Walls: These can be precast concrete,
4. Control o f volume change deformations and re­
cast-in-place concrete, or masonry. Shear
straint forces.
walls are discussed in more detail in Sect. 3.7.
5. Connection concepts. When architectural or structural precast mem­
bers are used for the exterior cladding, they can
often be used as shear walls. Precast concrete
3.2.1 Framing Dimensions
box elements have been used effectively in
When possible, establish building dimensions by mid-rise to high-rise structures. The boxes are
combining the modular dimensions of standard com­ created as one complete unit such as in a pre­
ponent sizes and by establishing bay sizes based on cast cell module, or can be created of individual
optimal component span lengths. Standard sections precast walls connected together to create a
are shown in Chapter 2, but others may be available in box unit. Such box units have a much larger
a given locale. moment of inertia than individual walls and
Generally, optimal framing dimensions will result therefore can be important members in a lateral
when the total number of component pieces is mini­ load resisting system.
mized. For example, it is often more economical to
cast wall panels and columns in multi-story units be­ 2. Cantilevered Columns o r Wall Panels: This is
cause of the reduced number of pieces required to usually only feasible in low-rise buildings. Base
produce, ship and erect. When establishing maxi­ fixity can be attained through a moment couple
mum component sizes, also consider the maximum between the footing and ground floor slab, or
shipping size, weight and the producer’s and erec­ by fixing the wall or the column to the footing.
tor’s crane capacity. In the latter case, a detailed analysis on the foot­
ing rotation can be made as described in Sect.
3.8.2.
3.2.2 Span-to-Depth Ratios
3. Steel or Concrete X-bracing: This system has
Typical span-to-depth ratios can be used to deter­ been used effectively in low and medium rise
mine the approximate required depth of a flexural pre­ buildings. A related resistance system usually
cast concrete member. During preliminary analysis, it occurs naturally in parking structures with
is helpful to determine beam or slab depths, and the sloped ramps in the direction of traffic flow. The
additional space required for other construction ele­ load path should be verified before the ramp of
ments, including mechanical ductwork or plenum, in a parking structure is assumed as the stiffening
order to establish the fioor-to-floor (or roof) dimen­ element.
sions of a building.
Typical span-to-depth ratios of flexural precast, 4. Moment-Resisting Frames: Building function
prestressed concrete members are: may dictate the use of moment resisting frames.
It is sometimes feasible to provide a moment
Hollow-core floor slabs 30 to 40 connection at only one end of a member, or a
connection that will resist moments with lateral
Hollow-core roof slabs 40 to 50 forces in one direction but not in the other, in or­
der to reduce the buildup of restraint forces. To
Stemmed floor slabs 25 to 35
reduce the number of moment frames required,
Stemmed roof slabs 35 to 40 a combined shear wall-frame system may be
used. Moment-resisting frames are discussed
Beams 10 to 20 in more detail in Sect. 3.8.

These values are intended as guidelines, not limits. All of the above systems depend on distribution of
The required depth of a beam or slab is influenced by lateral loads through diaphragm action of the roof and
the magnitude and ratio of live load to total load. floor systems (see Sect. 3.6).

3 -6 PCI Design Handbook/Fifth Edition


3 .2.4 Controf of Volume Change performance-oHheatructure. This can occur, for ex­
Deformations and Restraint Forces ample, atthe com er o fa building where load bearing
and non-Joaetbearing panels meet.
Volume "Changes of concrete result from .creep,
shrinkage, and temperature change. Creep and
shrinkage cause a shortening of the member,, so the 3.3.1 Axial Volume Change Strains
critical combination is creep, shrinkage, andtempera-
Figures 3.12.1 through 3.12;7 provide the data
ture drop.
It is important to arrangeand detail connections so needed to determine volume change strains [1,2].
that the effect of volume change restraint is mini­ These values can be reduced in rigid frames (see
mized. Sect. 3.3 provides data and guidelinestor esti­ Sect. 3.8.5).
mating the amount of shortening which may take
place. Neglecting the effect of connection deforma­ Example 3.3.1 Calculation of Volume
tion will produce unrealistically high computed re­ Change Shortening
straint forces. Sect. 3.8.5 discusses the method of es­
timating the force which may develop from restraint. Given:
Problems caused by volume change restraint have Heated structure in Denver, Colorado-
appeared when relatively tong members were welded Normal weight concrete beam—12RB28
to their bearings at both ends. When such members 8 - 'A> in. diameter, 270 ksi, low relaxation strand
are connected only at the top using a ductile connec­ Initial tension = 0.75fpu
tion, experience has shown that volume changes are Assume initial prestress toss = 9%
adequately accommodated. An unyielding top con­ Release strength = 4500 psi (accelerated cure)
nection may attract unacceptably high negative mo­ Length = 24 ft
ments if compression resistance is encountered at the
bearing. This may be difficult to accommodate. Problem:
Connections using cast-in-place concrete have ex­ Determine the actual shortening that can be antici­
hibited few volume change problems because micro­ pated from:
cracking and creep in the cast-in-place portion effec­ a. Casting to erection at 60 days.
tively relieve the restraint. b. Erection to the end of service life.
Long buildings may require full height expansion
joints. This is discussed in Sect. 3.3.3. Solution:
From Figures 3.12.1 and 3.12.2:
Design temperature change = 70 °F
3.2.5 Connection Concepts Average ambient relative humidity = 55%
The types of connections to be used should be de­
termined during the preliminary analysis, as this may Prestress force:
have an effect on the component dimensions, the Aps = 8(0.153) = 1.224 in®
overall structural behavior, as discussed above, and P0 = 1.224(270)(0.75)(1-0.09)
on the erection procedure. Chapter 6 and some PCI
= 225.6 kips
publications [13,15] are devoted entirely to connec­
tions. Po/A = 225.6(1000)/[(12)(28)]
= 671 psi

3.3 Volume Changes Volume/surface ratio:

Creep, shrinkage and temperature change, and = 12(28)/[2(12) + 2(28)]


the forces caused by restraining these strains, affect = 4.2 in.
connections, service toad behavior and ultimate ca­
a. At 60 days:
pacity of precast, prestressed structures. Conse­
quently, these strains and forces must be considered From Figure 3.12.3:
in the design. Creep strain = 169 x 10-® in./in.
Vertical members, such as toad bearing wall pan­
Shrinkage strain = 266 x 10~6 in./in.
els, are also subject to volume change strains. The
approximate magnitude can be calculated using Fig­
From Figure 3.12.4:
ures 3.12.3 through 3.12.7, adding the dead load
Creep correction factor
strain to the prestress. The effects will only be signifi­
cant in high rise buildings, and then only differential = 0.88 + (71/200)(1.18-0.88)
movements betweerrelements will significantly affect = 0.99

PCI Design Handbook,/Fiftb_Edition 3 -7


Trom Figure 3.12.5: Total- = 722 x tO -6 ia/in.

Retativehumidity correction (creepy Difference frorrrSO days-to final


= 1.17--Qt5(1.17-1.08} = 1.13 = 722 -^2 2 7
Relative humidity correction (shrinkage)
= 495 x-10"6 in./in.
= 1.29-05(1,29-1.14) = 1.22

From Figure 3.12.6:


TotaL strain = 495 + 210

Volume/surface ratio correction (creep) = 705 x 10-6 in./in.

= 0.48-0.2(0,48-0.36) = 0.46
Total shortening
Volume/surface ratio correction (shrinkage) = 705 x T-O-6 (24)(12)
= 0.46-0.2(0.46-0.31 T = 0.43 = 0.203jn.

(Note: Temperature shortening is not significant for For the effects of shortening in frame structures,
this calculation.) see Sect. 3.8.5.
The behavior o f actual structures indicates that
Total strain:
reasonable estimates of volume change characteris­
Creep = 169 x 1Q-6(0.99)(1.13)(0.46) tics are satisfactory for the design of most structures
= 87 x 10~6 in./in. even though test data relating volume changes to the
Shrinkage = 266 x 10-6(1.22)(0.43) variables shown in Figures 3.12.3 through 3.12.7 ex­
hibit considerable scatter. Therefore, it is possible to
= 140 x 1Q-® in./in.
reduce the variables and use approximate values as
Total strain = 227 x 10-6 in./in. shown in Figures 3,12.8 and 3.12.9.
Total shortening = 227 x 10"«(24)(12)
= 0,065 in. Example 3.3.2 Determine Volume Change
Shortening by Figures 3.12.8
b. At Final:
and 3.12.9
From Figure 3.12.3:
Creep strain = 315 x 10~6 in./in. Given:
Same as Example 3.3.1.
Shrinkage strain = 510 x 10-6 in./in.

Solution:
Factors from Figures 3.12.4 and 3.12.5 same as for 60
For prestressed, normal weight concrete, in a
days.
heated building, use Figure 3.12.8.

From Figure 3.12.6: For 55% relative humidity and temperature change
Volume/surface ratio correction (creep) of 70°F, interpolating from Table 3.12.8:
= 0.77 - 0.2(0;77 - 0.74) = 0.76
Actual strain = 687 x 10"6in./in.

Volume/surface ratio correction (shrinkage)


This result compares with the value of 705 x 10-6
= 0.75 - 0.2(0.75 - 0.64) = 0.73 calculated from Figures 312.1 through 3.12.7.

From Figure 3.12.7:


3.3.2 Bowing
Temperature strain = 210 x 10-® in./in.
A strain gradient between the inside and outside of
Total creep and shrinkage strain:
a wall panel, or between the top and underside of an
Creep = 315 x 10-6(0.99)(1.13)(0.76) uninsulated roof member, can cause the member to
= 268x10-6 in./in. bow. The theoretical magnitude of bowing (see Figure
33.1) can be determined by:
Shrinkage = 510 x 10-6(1.22)(0.73)
= 454 x 10-6 in./in. A = a £ (Eq. 3.31)

3 -8 PCI Design Handbook/Fifth Edition


where; Example 3.3.3 Thermal-Bow in a Wall Panel
a - strain gradient across panelihickness Given:
i - distance between supports A 20 ft high, 6 in. thick waif panel as shown belowr
Assume a coefficient of thermal expansion, C = 6 x
!t — member thickness^
10~64n/in/°F; a temperature differential T ,-T 2 = 35
T or a temperature difference between inside and °F; Ec = 4300 ksi.
outside of a panel: Problem:
a = C(T, - TJ (Eq. 3.3.2) Determine the potential thermal bow, A^-the force,
P, required at mid-height to restrain the bowing, the
where: stress in the panel caused by the restraint, and the re­
G = coefficient of thermal expansion sidual bow, A2.
Tg, T, = inside and outside temperatures respec­
Solution:
tively
From Eqs. 3.3.1 and 3.3.2:
Limited records of temperature measurements in­
dicate that in open structures, such as the roofs of 4 _ (6 x 1 0 -6)(35)[20(12)P
parking decks, the temperature differential seldom ex­ 8 (6)
ceeds 30 to 40°F. In an insulated sandwich wall pan­ = 0.252 in.
el, the theoretical difference can be higher, but this is From Figure 3.12.10:
tempered by “thermal lag” due to the mass of the con­
crete (see Sect. 9.1).
Moisture differences between the inside and out­
side of an enclosed building can also cause bowing,
however, the calculation is much less precise and in­
volves more variables. The exterior layer of the con­
crete panel absorbs moisture from the atmosphere
and periodic precipitation, while the interior layer is
relatively dry, especially when the building is heated.
This causes the inside layer to shrink more than the
outside, causing an outward bow. The outward
shrinkage bowing would tend to balance the theoreti­
cal inward thermal bowing in cold weather, which is
believed to explain the observation that “wall panels
always bow out”.

Figure 3.3.1 Thermal bow of wail panel

E, = 0.75(4300) = 3225 ksi


I = (bh3)/12 = [12(6)3]/12
= 216'mVft

From Figure 3.12.10, Case 1:


P = 48E,IA/€3
= [48(3225) (216) (0.25)]/[20(12)p
= 0.605 kip/ft width
M = P€/4 = [0.605(20)]/4
= 3.02 kip/ft width
Panel stress = My/I
= [3.02(12,000)<3)]/216
= 5 0 3 psi

PCI Design Handbook/Fifth Edition 3 -9


The residualbowcan he calculated by adjusting Example 3.3.4 Thermal Bow i n * Roof
the equation in Figure 3.12.10, Case 5, to read: Member
Given:
A = M€2/T6E,I; ond substituting A 30IT24 inverted tee t e a r ) supporting the double
tees o f the upper level o f a parking deck, as shown
€/2 for € below, iswelded at eachend atthe bearing, to thecol-
umn, and subject to a thermal gradient of 35°F.
. _ 3.02(12){10(12)]2
16(3225>(216)

= 0.047 in.

While the magnitude of bowing is usually not very


significant, in the case of wall panels it may cause un­
acceptable separation at the corners (see Figure
3.3.2), and possible damage to joint sealants. It may
therefore be desirable to restrain bowing with one or
more connectors between panels. As illustrated in the
previous example, Figure 3.12.10 gives equations for
calculating the required restraint and the moments
this restraint would cause in the panel.
The mid-height panel restraining force illustrated in
Example 3.3.3, can occur in amulti-story load-bearing
wall panel. For example, if the wall panel is two stories
tall and if the intermediate floor is laterally braced
against sidesway, a restraining force resisting thermal
bowing can develop in a connection between the wall
panel and the intermediate floor. The wall panel
should be connected to the intermediate floor, to
avoid loss of floor support when the wait panel bows
outward. If the intermediate floor is not braced
against sidesway, the P-A wall analysis should con­
sider the secondary moment due to the intermediate
floor gravity reaction loading the wall panel near, or at Problem:
the point of its maximum bow. Coefficient of thermal expansion, C = 6 x 10-6 in/
If non-structurai elements, such as drywall ceil­ in/°F ;Tt- T 2 = 35 °F ; Ec = 4300 ksi, for the compos­
ings, or interior drywall or masonry partitions, are at­ ite section I = 51,725 in4.
tached to wall panels unrestrained against bowing, Find the tensile force developed at the support.
those items should be attached with “soft” or flexible
joints. Solution:
Differential temperature can cause upward bowing From Eqs. 3.3.1 and 3.3.2:
in roof members, especially in open structures such
as parking decks. If these members are restrained . (6 x 10_6)(35)[24(12)]2
from rotations at the ends, positive moments (bottom A = ----------- ^ r = r — = 0.081 in.
tension) can develop at the support, as shown in
Cases 4 and 5, Figure 3.12.10. The bottom tension
From Table 3.12.10, Case 4:
can cause severe cracking. Examination of the equa­
tions shows that the thermal induced positive mo­ E, = 0.75(4300) = 3225 ksi
ments are independent of the span length. (For exam­
ple, substitute Eq. 3.3.1 for A in Figure 3.12.10, Case
_ 8(3225)(51,725)(Q.081)
4). Note from Figure 3.12.10 that if only one end is
restrained, as is sometimes done to relieve axial vol­ [24(12)]2
ume change force, the restraint moment is doubled.
= 1303 kip-in
Also note that, since thermal bow occurs with daily
temperature changes, the cyclical effects could mag­
nify the potential damage. T = (j* 7 7 ir 51-1^

3 -1 0 PCI Design Handbook/Rfth Edition


pjgufe 3.3.2 Corner separation due to tion of jomtspacing-should consider the types of con­
thermal bow nections used, ibeoolumrretiffnesses in simple span
structures, the relative stiffness between beams and
columns in framed structures, location of lateral load
resisting elements and the weather exposure- condi-
tions. Non-heafed structures, such as parking ga­
rages, are subjected to greater temperature changes
than occupied structures, so shorter distances be­
tween expansion joints may be warranted.
Sects. 3.3 and 3.8 present methods for analyzing
the potential movement of framed structures, and the
effect of restraint of movement on the connections
and structural frame. This information along with the
connection design methods in Chapter 6 can aid in
determining spacing of expansion joints.
This example illustrates the large forces that can Figure 3,12.11 shows joint spacing as recom­
occur when roof members are welded at the bearings, mended by the Federal Construction Council, and is
and why cracking occurs. The force calculated is an adapted from Expansion Joints in Buildings, Techni­
upper bound value, and does not consider the reliev­ cal Report No. 65, prepared by the Standing Commit-
ing effects of connection extension, microcraGking teeon Structural Engineering of the Federal Construc­
and column flexibility. Nevertheless, an alternative tion Council, Building Research Advisory Board,
method which does not employ welding at the bear­ Division of Engineering, National Research Council,
ings is strongly recommended. National Academy of Sciences, 1974. Note that the
spacings obtained from the graph in Figure 3.12.11
3.3.3 Expansion Joints should be modified for various conditions as shown in
the notes below the graph. Values for the design tem­
Joints are placed in structures to limit the magni­ perature change can be obtained from Figure 3.12.1.
tude of forces which result from volume change de­ When expansion joints are required in non-rectan-
formations (temperature changes, shrinkage and gular structures, they should be located at places
creep), and to permit movements (volume change, where the plan or elevation dimensions change radi­
seismic) of structural elements. cally.
Joints that permit contraction of the structure are
needed to relieve the strains caused by temperature
drop, creep and shrinkage which are additive. Such 3.3.3.2 Width of Expansion Joints
joints are properly called contraction or control joints The width of the joint can be calculated theoretical­
but are commonly referred to as expansion joints. If ly using a coefficient of expansion of 6 x 1( H in/in/°F
the forces generated by a temperature rise are signifi­ for normal weight and 5x10-® in/in/°F for sand-light-
cantly greater than shrinkage and creep forces, a true weight concrete. The Federal Construction Gouncil
“expansion joint" is needed. report, referenced above, recommends a minimum
It is desirable to have as few expansion joints as width of 1 in.. However, since the primary problem in
possible. The purpose of this section is to present concrete buildings is contraction rather than expan­
guidelines for determining the spacing and width of sion, joints that are too wide may result in problems
expansion joints. with reduced bearing or loss of filler material. The joint
width should consider the ambient temperature at
time of erection. Seismic codes also stipulate joint
3.3.3.1 Spacing of Expansion Joints widths to accommodate earthquake movement.
There is a divergence of opinion concerning the
spacing of expansion joints. Typical practice in con­
crete structures, prestressed or non-prestressed, is to 3.4 Component Analysis
locate expansion joints at distances between 150 and
300 ft. However, concrete buildings exceeding these The design of components is the topic of Chapter
limits have performed well without expansion joints. 4. Sect. 3.4 is intended to assist in establishing design
Recommended joint spacings for precast concrete parameters for some components, and to discuss the
buildings are generally based on experience. Evalua­ effects of non-frame components on the frame.

PCI Design Handbook/Frfth Edition 3-1 1


3.4.1 Non-Bearmg Wall Panels cases, the panel connection should be designed to
permitthe calculated deformation.
Non-bearing panels ace designed to tesisirwrnd,
A similarsiiuation will resultwheatwo adjacerttcol-
seismic forceegenerated from seifweight, and forces
umns have significantly different loads. Foroxample,
required to transfer the weightof theparrel tothesup-
the^ corner column of a structure wili-usuallyde sub­
port. It is rare that these externally applied loads witl
jected to a smaller load than the adjacent columns. If
produce the maximum stresses; the forces imposed
doth columns are tbe same size (as isoftendhesitua­
during manufacturing and erection will usuallygovern
tion for architectural reasons) and reinforced approxi­
the design, except for the connections.
mately the same, they will undergo different shorten­
ing.

3.4.1.1 Deformations

The relationship of the deformations of the panel 3.4.1.2 Wind Load


and the supporting structure must be evaluated, and
care taken to prevent unintended restraints from im­ Building codes specify the wind pressure for which
a building is to be designed, including magnified
posing additional loads. Such deformation may be
caused by the weight of the panel, volume changes of loads for localized portions due to gusting or funnel
effects produced by adjacent structures.
concrete frames, and rotation of spandrei beams. To
The lateral deflection of thin panels when sub­
prevent imposing loads on the panel, the connections
must be designed and installed to permit these de­ jected to wind should be determined, particularly if
they are attached to, or include, windows. Panels with
formations to freely occur.
For example, the tendency for the panels to follow deep protruding ribs may require analysis for shear­
the beam shown in Figure 3.4.1 may cause restraining ing winds, as indicated in Figure 3.4.3, and the con­
forces to develop at panel joints. The connections nections designed for the twist produced. Although
should be designed to allow the supporting beam to the design of the panel itself will generally not be criti­
deflect, but the beam should be stiff enough that pan­ cal for wind, the connections may be. This is particu­
el joint widths are maintained within the specified tol­ larly true for the tension connection which resists wind
erances. These effects can sometimes be controlled suction along with eccentric gravity loads, as indi­
by adjusting the erection sequence. cated in Figure 3.4.4.
The most prevalent cause of panel deformation is
bowing due to thermal gradients. If supported in a
manner that will permit bowing, the panel will not be
3.4.1.3 Panels with Openings
subjected to stress. However, if the panel is restrained
laterally between supports, stresses in the panel and Non-bearing panels which contain openings may
forces in the structure will occur. This is discussed in develop stress concentrations at these openings, re­
Sect. 3.3.2. sulting from unintended loading or restrained bowing.
Non-bearing panels should be designed and Hairline cracks radiating from the corners can result
installed so that they do not restrain frames from later­ (Figure 3.4.5). While these stress concentrations may
al translation. If such restraint occurs, the panels tend be partially resisted by reinforcement, the designer
to act as shear walls and become overstressed (Fig­ should consider methods of eliminating imposed re­
ure 3.4.2). Panels which are installed on a frame straints. Areas of abrupt change in cross-section
should be connected in a manner to allow frame dis­ should be reinforced, and should be rounded or
tortion. In some cases, especially in high seismic re­ chamfered.
gions, special connections which can accommodate Loads from adjacent floors can be imposed on
inter-story drift may be required. non-load bearing panels by methods of joinery, and
The shortening of concrete columns from elastic these loads can cause excessive stresses at the
and plastic deformation should be considered in very “beam” portion of an opening (Figure 3.4.6). This can
tall structures. At intermediate levels, the differential be prevented by locating connections away from criti­
shortening between two adjacent floors will be negli­ cal sections.
gible, and the panel will follow the frame movement. Unless a method of preventing load transfer can be
At the lowest level, rf the panel is rigidly supported at developed and permanently maintained, the “beam”
the base (such as foundation or transfer girder), the should be designed for some loads from the floor. The
accumulated shortening of the structure above may magnitude of such loads requires engineering judg­
induce unintended loading on the panel. In such ment.

3 -1 2 PCI Design Handbook/Fifth Edition


Figure 3.4.1 Deformation of panels on Figure 3.4.4 Forces on a panel subjected to
flexible beam wind suction

Figure 3.4.5 Corner cracking due to

Figure 3.4.2 Panel forces induced by frame


distortion

frequent, regularly spaced window openings, as


shownin Figure 3.4.7(A), as Vierendeel trusses. When
so designed there must be a space or joint horizontal­
ly between panels, to insure that they will not transfer
loads to panels below.
When the panels are placed vertically, they are
Figure 3.4.3 Shearing wind on ribbed panels usually designed as columns, and slenderness, as
described in Sect. 3.5, should be considered. If a
large portion of the panel is window opening, as in
Figure 3.4.7(C), it may be necessary to analyze it as a
rigid frame.
Figure 3.4.7 shows architectural waH panels, gen­
erally used with relatively short vertical spans, al­
though they will sometimes span continuously over
two or more floors. They are usually custom-made for
each project, and reinforced with mild steel. Standard
3.4.2 Load Bearing Wall Panels flat, hollow-core and stemmed members are also
used as wall panels, and are frequently prestressed.
Most of the items in the previous section must also Dimensions of architectural panels are usually se­
be considered in the analysis of load bearing wall lected based on a desired appearance. When these
panels. Panels may be designed to span horizontally panels are also used to carry loads, or act as shear
between columns, or vertically. When spanning hori­ walls, it is obviously important to have some engineer­
zontally, they are designed as beams, or if they have ing input early in the preliminary stages of the project.

PCI Design Handbook/Fifth Edition 3 -1 3


3.4.3 Non-Bearing Spandrels Figure 3.4.6 Unanticipatedioading^on a
non-load bearing panel
These are preeast elements which are less than
story height, made up either as a series of individual
CP
unitsor as one unit extending between columns. Sup­ %
port for spandrel weightmayfee fee .floor or the col­ \
-F LO O R LOAD FLEXURE t
umn, and stability against eccentric loading is IMPOSED OF BEAM 1
achieved by-connections to the underside of the floor TJUE TO
or to fee column (see Figure 3.4.8). UNINTENDED
RESTRAINT
Spandrels are usuaiiy part of a window wall, so -*>

consideration should be givenio the effect of deflec­


tions and rotations of the spandrel on fee window. De­
SECTION ELEVATION
formation calculations shouldbe based on gross con­
crete section since the stresses will generally be less
Figure 3.4.7 Horizontal and vertical rib
than those which cause cracking. For elements which
panels
extend in one piece between columns, it is preferable
that the connections which provide vertical support
be located close to the ends. This arrangement will
minimize interaction and load transfer between floor
and spandrel.
Consideration should also be given to spandrels
which are supported at the ends of long cantilevers.
The designer must determine the effect of deflection
and rotation of the support, including the effects of
creep, and arrange the details of all attachments to
accommodate this condition (Figure 3.4.9). A particu­
larly critical condition can occur at corners of build­
ings, especially when there is a cantilever on both
faces.

3.4.4 Load Bearing Spandrels

Load bearing spandrels are panels which support


floor or roof loads. Except for the magnitude and loca­
tion of these additional loads, the design is the same (B) CHANNEL (C) WINDOW
as for non-bearing spandrels. TYPE PANEL MULLION PANEL

Load bearing spandrels support structural loads


which are usually applied eccentrically with respect to
the support. A typical arrangement of spandrel and
Example 3.4.1 Spandrel Panel Rotation
supported floor is shown in Figure 3.4.10
Torsion due to eccentricity must be resisted by the Given:
spandrel or by a horizontal couple developed in the The spandrel panel shown.
floor construction. See Figure 3.4.10(B) and (C). In or­
der to taketorsion in the floor construction, the details
must provide for a compressive force transfer at the
top of the floor, and a tensile force transfer at the bear­
ing of the precast floor element. The load path of these
floor forces must be followed through the structure,
and considered in the design of other members in the
building. Even when torsion is resisted in this manner
in the completed structure, twisting on the spandrel
prior to completion must be considered.
If torsion cannot be accommodated by floor con­
nections, the spandrel panel should be designed for
induced stresses. See Chapter 4 for torsion.

3 -1 4 PCI Design Handbook/Fifth Edition


Panel weight = 417 ptf Figure 3.4.8 Typical spandrel connections
Normal weight concrete slab
E = 40OQ fcsi
Assumexreep reduces effective E to 2000 ksi
Superimposed deadHoad = TOpsf

Problem:
Determine rotation and displacement at top of
spandrel.
Note: In this example, spandrel torsion must be re­
sisted by an 8 in. moment arm in the floor slab. It is
desirable, whenever possible, to use a larger moment
resisting arm in order to reduce the magnitude of the
connection forces. See-Figure 3.4.8.

Solution:
Rotation of cantilever due to slab weight plus su­
perimposed loads (neglectingsupport rotation):

w = 8 (t5 0 )/1 2 + 10 = 110 psf

1 = bh3/12 = 12(8)3/12 = 512 in4


_ w l 3 _ (0-110/12)[10(12)]3
6EI 6(2000)^512)

= 0.00258 radians

Rotation o f cantilever due to weight of spandrel:

_ W l2 _ (0.417) [10(12)]2
2EI 2(2000) (512)

= 0.00293 radians

Total rotation of cantilever:


= 0.00258 + 0.00293 = 0.00551 radians

Displacement of top of spandrel:


= (0.00551 )(72 + 8/2) = 0.419 in.

3.4.5 Eccentrically Loaded Columns


Many precast concrete structures utilize multi­ Figure 3.4.9 Effect of cantilever supports
story columns with simple span beams resting on
haunches. Figures 3.12.12 and 3.12.13 are provided
as aids for determining the various combinations of
load and moment that can occur with such columns.
The following conditions and limitations apply to
Figures 3.12.12 and 3.12.13:

1. The coefficients are only valid for columns


braced against sidesway.

2. For partially fixed column bases (see Sect.


3.8.3), a straight line interpolation between the
coefficients for pinned and fixed bases can be
used with small error.

PCI Design Handbook/Fifth Edition 3 -1 5


Figure 3,4.10 Load-bearing spandrel 1. F orthe interior column, the dead toad reaction
would be the sarneon either: side, thus, no moment
results. The live ioad could occur on any one side at
any floor; hence, use erf the coefficients.® th e “2 Max”
liner
Pue = 34.0(14) = 476 kip-in = 39.7 kip-ft

To determine the maximum moment at point B:


Pinned base: km = 0.67
Fixed base: km = 0.77
65% fixed: K* = 0.67 + 0.65(0.77-0.67)
= 0.74
Mu = kmPue = 0.74(39.7) = 29.4 kip-ft

3. For taller columns, the coefficients fo r the


Maximum restraining, force at level 2:
4-story columns can be used with small error.
Fu = kfPue/hs
4. The coefficients in the “ 2 Max” line will yield the
k, = 1.40 + 0.65(1.62 - 1.40) = 1.54
maximum required restraining force, Fj, and
column moments caused by loads (equal at Fu = 1,54(39.7)/16 = 3.82 kips (tension or
each level) which can occur on either side of the compression)
column, for example, live loads on interior col­
umns. The maximum force will not necessarily 2. For the exterior column, the total load is eccentric
occur with the same loading pattern that causes on the same side of the column, hence use the coeffi­
the maximum moment. cients in the “ 2 One Side11fine:

5. The coefficients in the “ 2 One Side” line will Pue = 104.0(14) = 1456 kip-in = 121.3 kip-ft
yield the maximum moments which can occur if
the column is loaded on only one side, such as To determine the maximum moment at point B:
the end column in a bay. For a pinned base: km = 0.40
For a fixed base: km = 0.46
For 65% fixed: km= 0.40+0.65(0.46-0.40)
Example 3.4.2 Use of Figures 3.12.12 and
= 0.44
3.12.13
Mu= kmPue = 0.44(121.3) = 53.4 kip-ft
Problem:
Using Figure 3.12.13, determine the maximum re­ Maximum restraining force at level 2:
straining force and moment in the lowest story of a Fu = kfPue/hs
3-story frame for:
k, = -0 .6 0 - 0.65(-0.60 + 0.22) = -0 .3 5
a. An interior column in a multi-bay frame
b. An exterior column Fu = -0.35(121.3)716
Given: = -2 .6 5 kips (tension)
Beam reactions to column haunch at each level:
D.L = 5 0 kips 3.5 Slenderness Effects in Columns and Wall
L.L = 20 kips Panels
Eccentricity e = 14 in. The term “slenderness effects,” can be described
Story height l \ = 16 ft as the moments in a member produced when the line
Column base is determined to be 65% fixed. of action of the axial force is not coincident with the
displaced centroid of the member. These moments,
Solution: which are not accounted for in the primary analysis,
Factored loads: D.L. = 1.4(50) = 70.0 kips are thus termed “secondary moments.” These secon­
L.L. = 1.7(20) = 3 4 .0 kips dary moments arise from changes in the geometry of
the structure, and may be caused by one or more o f
104.0 kips the following:

3-1 6 PCI Design Handbook/Rfth Edition


1. Relative displacement of the ends of the mem­ Effects oTereepsheuld also be included. The most
ber due to: common methodis to divide the stiffness (El) by-the
a. Lateral x>r unbalanced vertical loads in an factor 1 + specified in the ACI momenimagnifi-
unbraced frame; usually labeled “transla­ cation method.
tion” or “sidesway.” In unbraced~continuous framesrthe jotntJransla-
b. Manufacturing and erection tolerances^ tions effect and the frame response are interdepen­
dent. Thus, a practical analysis, especially when po­
2. Deflections away from the end of the member
tential cracking is a parameter, usually will require the
due to:
use of computers.
a. End moment due to eccentricity erf the axial
A good review of second-order analysis, along
load.
with an extensive bibliography and an outline of a
b. End moments due to frame action—conti­
complete program, is contained in Ref. 3.
nuity, fixity or partial fixity of the ends.
An example of P-A calculations for a simple yet fre­
c. Applied lateral loads, such as wind.
quently encountered problem is shown in Example
d. Thermal bowing from differential tempera­
3.5.1. In the following example only two of the ACI
ture (see Sect. 3.3.2).
load combinations are checked, presuming ioy engi­
e. Manufacturing tolerances.
neering judgment that these were the controlling
f. Camber due to prestressing.
cases.

These secondary effects can be considered in the


design of the member by either using the Moment Example 3.5.1 Second-Order Analysis of an
Magnification Method, described in Sect. 3.5.2, or by Uncracked Member
a direct iterative analysis usually termed “second-or­
Given:
der” or “ P-A” analysis.
An 8 in. thick, 8 ft wide prestressed wall panel as
shown.
3.5.1 Second-Order (P-A) Analysis
D.L. = 10 kips
The usual procedure for this analysis is to perform L.L. = 6 kips

an elastic type analysis using factored loads. Out-of-


plumbness (items 1b and 2e above) are initially as­
sumed based on experience and/or specified toler­
ances. The thermal bowing effect is usually neglected
in columns, but may be significant in exterior wall pan­
els (see Sect. 3.3.2).
ii
At each iteration, the lateral deflection is calcu­
lated, and the moments caused by the axial load act­
ing at that deflection are accumulated. After three or
four iterations, the increase in deflection should be
negligible (convergence). If it is not, the member may
be approaching stability failure, and the section di­
mensions should be re-evaluated.
If the calculated moments indicate that cracking
will occur, this needs to be taken into account in the
deflection calculations. The stiffness used in the sec­
ond order analysis should represent the stiffness of
the members immediately before failure. This may in­ Loading assumptions are as follows:
volve iterations within iterations, greatly complicating
1. Axial load eccentricity = 1 in. (at one end)
the procedure, although approximations of cracked
section properties are usually satisfactory. Sect. 2. Assume midspan bowing = 1.0 in. outward.
10.11.1 of the A C I318-95 has cracked member prop­ (Note: Production tolerances allow t/3 6 0 , see
erties for different member types for use in second-or­ Chapter 8).
der analysis of frames. These values are the lower
3. Wind load = 30 psf.
bound of what can be expected for equivalent mo­
ments of inertia of cracked members and include a 4. Non-sway frame - no joint translation.
stiffness reduction factor <j)k to account for variability
of second-order deflections. 5. Joints assumed pinned top and bottom.

PCI Design Handbook/Fifth-Edition 3 -1 7


Total midspan deflection including initial bow:
Concrete: ft = 5000: psi
Ec = 4300 tesi = 1.0 + 0.0258 = 1.02frin.

Problem: Defection duet to P-Amoment a t midspan:


Determine if standard:panel (Figure 2.6.5) is ade­ Pue€2 24.2e(360)2
quate. A 8EI 8(7.80 x TO®)

Solution: = 0.05Qe
C a s e l: No wind
First iteration:
Pu = 1.4D + T.7L = 1.4(10) + 1.7(6)
A = 0.050(1.026) = 0.052 in.
= 24.2 kips
lg = bh3/12 = 96(8)3/12 = 4096 in* Second iteration:
e = 1.026 + 0.052 = 1.078 in.
Note: The bending stiffness El is multiplied by 0.70
factor perSect. 10.11.1 ACI318-95 for uncracked wall A = 0.050(1.078) = 0.054 in.
sections. This includes a stiffness reduction factor <|>k
to cover the variability of computed deflections. Once Third iteration:
the moments are established, the <j) factor from Sect. e = 1.026 + 0.054 = 1.080 in.
9.3.2.2 ACI 318-95 is used to determine the strength A = 0.050(1.080) = 0.054 in. (convergence)
of the cross section.
or using a geometric series to calculate the midspan
pd = 14/24.2 = 0.58
deflection in one step:
The pdfactor is used to account for sustained load 1.026
effects by modifying the stiffness. It is reasonable to 1 - 0.050
use:

_ 0.70Ecla _ 0.70(4300)(4096) li/ftat midheight = 12.1 + 24.2(1.08)


“ 6 lf_ 1 + p d 1.58 = 38.2 kip-in.

= 7.80 x 106 kip-in2 Check for cracking at midheight:


M„/l = 38.2(4)(1000)/4096 = -3 7 psi
Check P-critical using Euler’s formula:
1/2 Panel w t: [100(15)/(8(12))] (1.4) = 22psi

Pc Prestress = 250psi
€2
Dead load = 10(1000)(T .4)/[8(96)] = 18 psi
jt2(7.80 x 106)
(360)2 Net stress (compression) = 253psi

= 594 kips > 24.2 kips OK Therefore, the analysis is valid.


Moments on panel:
Using interaction curve Figure 2.6.5:

Pe = 24.2(1) 24.2 k-in. Pu = 24.2/8 + 1.4(15)0.1 = 5.13 kips/ft


Mu = 38.2/(12(8)] = 0.40 kip-ft/ft

Point is below curve, OK.

Case 2: Include wind


Axial load without wind is:
Pu = 0.75(1.4D + 1.7 L + 1.7W)
= 0.75(1.4(10) + 1.7(6)1 = 18.2 kips
Deflection at midspan due to Pue:
Deflection due to PyB (see Case 1)
p ue€2 _ 24.2(1 )(360)2
A = 0.0258 in. = [18.2/24.2] (0.0258)
16EI 16(7.61x10®)
= 0.019 in.

3 -1 8 PCI Design Handbook/Rfth Edition


Additivewind load would be suction = 30psf 3.5.2 Moment Magnification Method
Wu = 30(8)(0.75)(1.7) = 306 Ib/ft This is an approximate methoddescribed in Sects.
T0T11,1 Q.12 and10.13of ACI 318-95, and is applica­
Whenoonsidering wind, pd = 0 ble toprecast and prestressed members with modifi­
cation. Moment magnification as described by ACI is
<|)Eclg 0.70(4300)(4096)
limited to-k£u/ r values of 100 or less and to nonpres-
^ ~ 1 + p* " 1.0 tressed members.
Since most prestressed compression members
= 1.23 x 107 kip- in2 and precast load bearing wallpanels have much less
than 1% steel, modified equations for El are recom­
Deflection due to wind: mended. Figure 3.T2.14 presents such equations
based on “curve fitting” with theoretically exact proce­
5wu€* dures, and agrees reasonably well for k£u/ r valuesup
= 0.45 in.
384 El 384(1.23 x 107) to 150. Other modifications have also been used suc­
cessfully. These approximations are necessarily con­
Total initial midspan bow including eccentricity and servative, so the second-order analysis is preferred
wind: for major structures* For V£Jx values exceeding 150
a second-order analysis is recommended as well.
A = 1.0 + 0.019 + 0.45 = 1.469 in. The moment magnification provisions in the ACI
Gode are presented in separate sections for non-sway
Deflection due to P-A moment at midspan: frames and sway frames. A structure is considered
Pe£2 18.2e(360)2 non-sway if the increase in column end moments due
A = = 0.024e
8EI 8(1.23 x 107) to second-order effects does not exceed 5% of the
first-order end moments. Another method to deter­
First iteration: mine whether a structure is a non-sway frame or sway
A = 0.024( t .469) = 0.035in. frame is to calculate the stability index “Q”.

Second iteration: Q = (Eq. 3.5.1)


e = 1.469 + 0.035 = 1.504 in.
vv u'-c
e
A = 0.024(1.504) = 0.036 in. where 2PU is the total vertical load, Vu is the story
shear, and A0 is the first order relative deflection be­
Third iteration: tween the top and the bottom erfthat story due to Vu. A
e = 1.469 + 0.036 = 1.505 in. frame is non-sway if Q is less than or equal to 0.05.
A = 0.024(1.505) = 0.036 in. (convergence)
3.5.2.1 Moment Magnification Method for

... Non-Sway Frames

The ACI equations are repeated here for conve-


= 450 kip-in mence:
Mg &nsM 2 (Eq. 3.5.2)

M uy/I = 450(4)(1000)/4096 = -4 3 9 psi where:


Panel weight = 22 psi
5ns = ----- ^ 1 . 0 (Eq. 3.5.3)
Prestress = 250 psi 1 r“
0.75PC , /
Dead load = 18 psi
p _ Jt2EI (Eq. 3.5.4)
Net stress (tension) = -1 4 9 psi
c (k€u)2

fr = 7.5/fT = 530 psi > 149 psi 0.2(Eclg) + Eslse


(Eq. 3.5.5)
Therefore, the analysis is valid. 1 +Pd

Pu = 18.2/8 = 2.3 kips/ft or conservatively:


Mu = 450/[(12)(8)] = 4.7 kip-ft/ft 0.4Eclg
(Eq. 3.5.6)
By comparison with Figure 2.6.5, OK. 1 + Pd

PCI Design Handbook/Fifth Edition 3-1 9


or for 100 < k€u/ r < 150 use Figure 3.12.14: EclgA _ 4300(4096) 1.93 x 10®
1 + f t , " 9.1(1 + M " 1 +Pd
Cm = 0.6 + 0 . 4 ^ > 0.4 (Eq. 3.5.7)
Iv!^
Case 1: Mo Wind
= 1.0 for members with transverse loads Since there is production to w in g this should be
between supports. considered to be a transverse load so Cm = 1 j0 Total
e atmidheight is 0.5 + 1.0 = 1.5 in. This exceeds a
In Eq. 3.5.4, thevalue of k can be determined from minimum e from ACI 318-95 Sect. 10.12.3.2 so it is
the Jackson-Moreland alignment charts, Figure okay.
3.12.15. Since most precast members are used in
M2 Pue = 24.2(1.5) = 36.3 kip-in
non-sway frames, and the connections are not de­
signed to transfer moment to horizontal members, a k jc2(1 .93 x 10®)/(1 + 0.58)
Pc = 93.0 kips
of 1 is usually used, ^ a n d i^ refer to the ends of the 3602
compression member. Example 3.5.1 is redone us­ 1.0 1.53
ing the moment magnification method: 24.2
(0.75)(93.0)

Example 3.5.2 Analysis of aMon-Sway Mc = 1.53(67.5) = 103 kip-in


Frame Using Moment
Magnification This moment is more than what is calculated using
the P-A method of Example 3.5.1 As in that example,
the wall is uncracked so the analysis is valid and the
Given: wall has enough ultimate strength for the applied
Use the same waH panel o f Example 3.5.1. loads. In this example, the moment magnification
method produces conservative results. The wind load
Problem: case is done in a similar manner with (id = 0.
Determine if standard panel (Figure 2.6.5) is ade­
quate using moment magnification.
3.5.2.2 Moment Magnification Method for Sway
r = 0.3(8) = 2.4 in. Frames

= 1.0(360)/2.4 = 150 The ACI equations are repeated here for conve­
nience:
Since M J r exceeds 100 the equations from Fig­ Ml — + 6sM 1s (Eq. 3.5.8a)
ure 3.12.14 are used to compute El.
M 2 = M 2ns + 85M 2s (Eq. 3’5.8b)
From Figure 2.6.6:
<j>P0 = 289(8) = 2312 kips for an 8 in. x 8 feet If an individual compression member has
wide wall
3.5.9)
where:
<|> = 0.70 for a compression failure
it shall be designed for Mc as calculated in .Sect.
Po 2312/0.70 = 3303
3.5.2.1 using the sway magnified moments M, and Mg
6< tj < 70 kips as calculated above. Sect. 10.13.4 ACI 318-95 allows
2.5 +
1.6 three methods of calculating 5*:
*1
P u /P o 1. Use a second-order elastic analysis based on
2.5 +
1.6 = 221 > 70
the member stiffnesses given in Sect. 10.11.1
24.2/3303 ACI 318-95.

2. If 6Sdoes not exceed 1.5 it may be calculated


0 = 005 = 0 05 = °-13 (no by:
compression flange)
8 s = ( T ^ O ) " 1,0 (Eq. 3.5.10)
X = T|0 > 3.2

X = 70(0.13) = 9.1 where Q is calculated per Eq, 3.5.1.

3 -2 0 PCI Design+landbook/Fifth Edition


6 0 '___________________ ______________________ 6 0 '

/
h
i i I
1/ L J V
-— 8DT17 P/S WALL PANELS - - 1 - 2 4 x 2 4 P/S COLUMN EACH BAY

n1 (4 PER BAY)
8DT17 P/S WALL PANELS ---------- ►

^ / T E N S I O N TIE / SLAB ISOLATION JOINT


AROUND COLUMN

3' £ — SHEAR RESISTANCE | |

r “ a

j ____ : > 1.0 structure by expansion joints, creating an unbraced


3. 6, (Eq. 3.5.11)
2PU “ frame. A frame analysis of the structure yields the fol­
0.752PC lowing data:
Each wall panel:
where 2PUis the summation for alt the vertical
toads in a story and 2PCis the summation for Axial toad: D = 14.4 kips
all the sway resisting columns in a story per L = 7.2 kips
Eq. 3.5.4. W =0
Top moment: D = 9.6 kip-ft
The stability of the structure as a whole under fac­
L = 4.8 kip-ft
tored gravity toads shall be considered. Sect. 10.13.6
W =0
A C I318-95 lists three criteria that need to be met to
ensure overall stability. The criteria are repeated here Bott. moment: D = 4.2 kip-ft
for convenience. L = 2.1 kip-ft
In addition to toad cases involving lateral loads, the W = 1 7 .0 kip-ft (flange comp.)
strength and stability of the structure as a whole under
factored gravity toads shall be considered. Each column:
Axial toad: D =115*2 kips,
1. When 8SMSis computed from A C I10.13.4.1, the
L = 57.6 kips,
ratio of second-order lateral deflections to first-
W =0
order lateral deflections for 1.4 dead toad and
1.7 live toad plus lateral toad applied to the Top moment: D = L = W = 0 (pinned)
structure shall not exceed 2.5. Bott. moment: D = L = 0, W = 3.0 kip-ft
2. When 5SMS is computed according to ACI
10.13.4.2, the value of Q computed using 2PU Wall panel properties:
for 1.4 dead toad plus 1.7 live toad shall not ex­ A = 334.5 in2*
ceed 0.60. I = 7897 in4
3. When 8SMSis computed from ACF10.13.4.3, 5S r = 4.86 in.
computed using 2Puand 2PCcorresponding to P0 (see Figure 2.6.3) = 1222/<j> = 1746 kips
the factored dead and live loads shall be posi­
fc = 5000 psi
tive and shall not exceed 2.5.
Ec = 4300 ksi
Incases (1), (2) , and (3) above, fSdshall betaken as
the ratio of the maximum factored sustained axial toad
Column properties:
to the total factored axial toad.
A = 576 in2
I = 27,648 in4
Example 3.5.3 Slenderness Effects Using
r = 7.2 in.
Moment Magnification
P0 (see Figure 2.6. 1) = 1650/0.7 = 2357 kips
Given:
fc = 5000 psi
The structure shown above is the interior portion of
a long building that is isolated from the remaining Ec = 4300 ksi

PCI Design Handbook/Fifth Edition 3 -2 1


Problem: Assume tyAfor use in JacksorFMorelandalignment
Find magnified moments for wall panels and col- charts is approximately the ratio o f ( u to iength below
-omnsrand check stability of the structure as-a whole fteer = 14/3 = 4.7; o))B = I jQ (max.)
under factored gravity loads. k = 2.6
k ( u = 2.5(11) (12) = 33Q.0 in.
Solution:
WaH panel :
C ase 1: {Dead + Live) Using Figure 3.12.14(A):
pu = 1.4(14.4} + 17(7.2) = 32.4 kips . Pu/P 0 = 24.3/1746 = 0.014, k€u/ r = 67.9
M2ns = 1.4(9.6) + 1.7(4.8) = 21.6 kip-ft l =30
M1ns = 1.4(4.2} + 17(2.1) = 9.5 kip-ft 4300(7897}/30 , ^ ,
El = -------V ( ) — = 1-13x 106 kip-m2
In this case, the larger moment M2 occurs at the
top. Cm =1.0
When gravity loads are unsymmetrical, frame mo­ _ ji2(1.13 x 106)
ments can be very smalt, but a sidesway case must be 102.4 kips
Kc (330)2
checked for overall stability. Since in this structure the
axial loads are symmetrical and do not contribute to Column:
sidesway, the value of k can be taken as 1 and
M1sand M2s = 0. Column Pu = 0.75[1.4(115.2) + 1.7(57.6)]
= 194.4 kips
Therefore, Eqs. 3.5.8 become:
Mi = M 1ns + 6sM1s = 9.5 + 0 = 9.5 kip-ft From analysis of column/base relationships (see
Sect. 3.8.3), Kc/Kt, = 1.0.
M2 = M2ns + 5sM2e = 21 .6 + 0 = 21 .6 kip-ft
Using alignment charts:
Check Eq. 3.5.9 to determine if the moment M2
= 1
needs to be multiplied by 6ns.
(Jr = 11(12)/4.86 = 27.2
=10
k = 1 .9
k€u = 1.9(11)(12) = 250.8 in.
—p = = 35 - - = 251
f p7 / 32.4 Irf
^ = 250.8/7.2 = 34.8
yj f ^ j y 5(334.5)

^ = 194.4/2357 = 0.08
27.2 < 251, so maximum moment is

M2 = 21 .6 kip-ft
From Figure 3.12.14(B):

Case 2: (Dead + Live + Wind) I =16.3


4300(27,648)/16.3
Use Eq. 3.5.11 to compute 6SMS. First calculate the
summations of the ultimate loads and critical loads,
£ 1.0
P0, for the structure. = 7.29 x 106 kip-in2
jt2(7.29 x 10s)
Wall Panel: Pc 1144 kips
(250.8)2
Since wind loads contribute to sidesway:
Pu =0.75(32.4) = 24.3 kips 2PU =8(24.3) + 194.4 = 389 kips
M2ns =075(9.5) = 7.1 kip-ft
2PC =8(102.4) + 1144 = 1963 kips
M 2s =075(1.7)(17.0) = 2 1 7 kip-ft

in this case, the larger moment M2 occurs at the Substituting into Eq. 3.5.11
bottom.
h = 1.0 _ 1 1.36
8 < 2PU - _ 389
Pd = 0 1 _ 0752P ; 075(1963)

3 -2 2 PCI Design Handbook/Fifth Edition


Use Eq. 3.5,8: Using thefixitiesfro m Case 2:

Wall paneUi/l2= M ** + ^ 2s _ 4300(27, 648)/1 6.3


4 .5 0 x TO6
= 7.1 + 1.36(2177) t ~ 1 + 0.622
= 36.6 kip-ft
Using "Eq. 3.5.4:
Column 4 ^ - 0 + 0.75(1,7)(3)(1.32)
P = tc2EI _ Jt2(45Q-x 106)
= 5.05 kip-ft 706 kips
(k€J 2 (250.8)2

2PU = 8(32.4) + 259.2 = 518.4 kips


Check Eq. 3.5.9:
2 PC = 8(63.4)+ 706 = 1213 kips
Wall panel: = 272 1 1
6S = - 518.4
SPu 1-
35 35 1- 0.75(1213)
= 290.4 0.752PC
24.3
yS. V
5(334.5) = 2.3 < 2.5 OK

3.6 Diaphragm Design


Since 27.2 < 290.4, no further magnification is re­
quired for the wall panels. Floor and roof framing systems can be designed
as horizontal diaphragms, to help in resisting lateral
11( 12) loads from wind or earthquake. The reactions from
Column: 18.3
r 7.2 the diaphragm are transmitted to shear walls or other
lateral load resisting systems as described in Sect.
35 = __ 35 3.2.3.
= 135

3.6.1 Method of Analysis

The diaphragm is analyzed by considering the roof


Since 18.3 < T35, no further magnification is required
or floor as a deep horizontal beam, analogous to a
for the columns.
plate girder or I-beam. The shear walls or other lateral
Case 3: Check stability under gravity loads. load resisting systems are the supports for this beam.
As in a beam, tension and compression are induced
Check per criteria (C) A C I318-95 Sect. 10.13.6: in the chords or “flanges" of the analogous beam.
The shear in the diaphragm is resisted by the “web” of
Wall Panel: P„ = 32.4 kips (Case 1)
the analogous beam. A diaphragm model using the
analogous beam is shown in Figure 3.6.1.
Column: Pu = 1.4(115.2) + 1.7(57.6>

= 259.2 kips
3.6.2 Shear Transfer Between Members
Recompute 8, using Pa= In precast floors and roofs without composite top­
ping, the individual components comprising a floor or
_ 14(14.4) roof diaphragm must be connected together to act as
WallPanel: pd = 0.622 a single diaphragm. Joints between precast compo­
32.4
nents which are parallel to the lateral load resisting
Using the fixities from Case 2: system must be connected together to resist the dia­
phragm shear forces as well as chord tension/com-
4300(7897)/30 n,n Hn6 pression forces at the boundary edges of the dia­
E |- 1 + 0.622 - 0J0X10 phragm. Joints between the precast components
which are perpendicular to the lateral load resisting
Using Eq. 3.5.4: system must be connected together to resist horizon­
tal shear (VQ/f).
= J I 2E!_ jt2(0.70 x 106) The types of connections used to connect .precast
63.4 kips
c (k€u)2 (330)2 components together to form diaphragms vary de­
pending on the magnitude of the required connection
1.4(115.2) capacity and the preference of the precast supplier
Column: |}d 0.622
259.2 manufacturing and erecting the product. Two com­

p el Design Handbook/Fifth Edition 3 -2 3


monly used welded connections are shown in Figure Connections winch transfer shear^from_ the dia­
3.6.2. Connections between members often serve phragm to the shear walls or other lateral-load resist­
functions in addition to the transfer Rehear for facial in g systems are analyzed in the same manner as the-
loadsr For example, weld platesJn flanged members connections between members.
are Often used to adjust differential camber. Grout
keys maybe utilized to distribute concentrated loads.
Precast componentSLmay be fabricated with grout
3.6.3 Chord Forces
keys and connected by grouting the joint. For mem­
bers connected by grout keys, a conservative value of Chord forces are calculated as shown in Figure
80 psi can be used for the design strength of the 3.6.1. For roofs with intermediate supports as shown,
grouted key. If necessary, reinforcement placed as the shear stress is carried across the beam with weld
shown in Figure 3.6.3 can be used to transfer the plates or bars in grout keys as shown in Section A-A.
shear. This steel is designed by the shear-friction Bars are designed by shear-friction.
principles discussed in Chapter 4. In flanged deck members, the chord tension at the
In floors and roofs with composite topping, the top­ perimeter of the building is usually transferred be­
ping itself, or in conjunction with the precast compo­ tween members by reinforced topping or tension con­
nents, can act as the diaphragm, if adequately rein­ nections.
forced. Shear reinforcement, if required, can be In allbuildings, a minimum amount of perimeter re­
determined by shear-friction analysis and continuous inforcement is required to satisfy structural integrity
reinforcement at the diaphragm boundaries may be (see Sect. 3.10) [7]. These minimum requirements
provided to resist chord tension forces. may be more than enough to resist the chord tension.

Figure 3.6.1 Analogous beam design of a diaphragm

LATERAL LOAD W = wf

3 -2 4 PCI Design Handbook/Fifth Edition


3.7 Shear Wall Buildings able to orient the three shear walls in any non-collin-
ear position. Some codes require that lateral loads be
3.7.1 General applied in the direction of both principal axes simulta­
In most cases, precast concrete shear walls will be neously.
the most economical lateral load resisting system for
precast concrete buildings. Precast shear walls are
structurally efficient and relatively easy to manufac­ Figure 3.6.3 Use of perimeter reinforcement
ture. They can be erected using a precaster’s stan­ as shear-friction steel
dard connections, which do not require production
and erection tolerances as exacting as those required
by most other types of lateral load resisting systems.
Splice sleeve type connections are more demanding
and require tighter tolerances. Shear walls are also
economical because they can be designed using
structural walls already required by the building lay­
out, such as exterior walls, interior walls, and walls
that enclose stairways, elevator and mechanical
shafts.
Shear walls act as vertical cantilever beams, which
transfer lateral forces acting parallel to the face of the
wall, from the superstructure to the foundation. Shear
walls should be oriented to resist lateral loads applied
to the building in both principal axes of the building.
Ideally, there should be at feast two shear walls ori­
ented to resist lateral loads in both principal axes of
the building. If only one shear wall is oriented in one
principal axis of the building, two shear walls should
be provided in the orthogonal axis to resist diaphragm
torsion. See Figure 3.7.3(A). Alternatively, it is accept­

PCI Design Handbook/Fifth Edition 3 -2 5


It is desirabte-tobesign-shear walls as load bearing such as wind loading and seismic loading; The di­
panels, whenever possible. The increased dead load mension between the cerrter of rigidity arrd center of
acting on tbe panel is an advantage because it in­ lateral load is the eccentricity of the lateral toad resist
creases the-panefe resistance to uplift and overturn­ ing system. Most codes have requirernentsTotmini-
ing. muTTEeccentricity, to provide resistance for “acciden­
tal torsion.”
The distribution of the total lateral force acting on a.
Shear walls in precast concrete buildings can be
building to each individual shear waH is influenced by individual wallpanels, orindividual wall panels which
the followingfactors: are connected together to function as a single shear
1. The supporting soil and footings wall. Connecting waH panels together to create a
single shear wall is done in a manner similar to that
2. The stiffness of the diaphragm described for connecting floor and roof components
together to form diaphragms, as discussed in Sect.
3. The relative flexural and shear stiffness of each
shear wall 3.6.2.
It is desirable to design the wall panels as single
4. The eccentricity of the lateral loads to the center uncoupled units. This reduces the cost of connec­
of rigidity of the shear walls tions and the magnitude of volume change restraint
forces that occur when many wall panels are con­
Generally, it is common practice to neglect the de­
nected together to form one large shear wall.
formation of the soil and the footings when distribut­
If the overturning moment results in excessive
ing shears among shear walls.
uplift to an individual, uncoupled shear wall panel,
If the deptb-to-span ratio of a diaphragm is small,
multiple wall panels can be connected together. Con­
the diaphragm will be “flexible" and may deflect signif­
necting individual wall panels together greatly in­
icantly when subjected to lateral loads. Flexible dia­
creases the shear resistance and reduces uplift of the
phragms distribute shears to each shear wall relative
shear waft. Locate the required panel-to-panel con­
to the tributary width of diaphragm loading each shear
nections near mid-length of the wall to minimize vol­
wall. If the depth-to-span ratio of a diaphragm is large,
ume change restraintforces. As previously stated, it is
the diaphragm will be “rigid” and not deflect as signifi­
desirable to minimize the number of wall panels con­
cantly as a flexible diaphragm, when subjected to lat­
nected together to minimize volume change forces
eral loads. Rigid diaphragms distribute shears to
and number of connections required.
each shear wall in proportion to the shear wall’s rela­
The stiffness of a shear wall may be increased by
tive stiffness. In precast concrete building design, it is
connecting it to perpendicular walls, which act as
common practice to assume that floor and roof dia­
flanges. The effective flange width that can be as­
phragms act as rigid diaphragms.
sumed for such walls is illustrated in Figure 3.7.2.
Generally, the use of “flanges,” increases the shear
wall’s flexural rigidity, but has little effect on its shear
3.7.1.1 Relative Stiffness of Shear Walls rigidity, in some structures, such as Example 3.7.3, it
may be desirable to connect perpendicular walls to a
The relative stiffness of each shear wall is deter­ shear wall to increase its dead toad, which increases
mined by comparing the rigidity of an individual shear the shear wall’s resistance to overturning moment
wall with the sum of the rigidities of all the shear walls.
caused by lateral loads.
The rigidity of solid shear walls and distribution of lat­
eral loads are further discussed in Sects. 3.7.2 and 3.7.2 Rigidity of Solid Shear Walls
3.7.3, respectively. In order to determine the distribution of lateral
toads, the relative rigidity of allshear walls must be es­
tablished. Rigidity is defined as:
3.7.1.2 Eccentricity of Lateral Loads
r = 1/A (Eq. 3.7.1)
A rigid diaphragm subjected to lateral load will
translate in a direction parallel to the applied load. See where:
Figure 3.7.1(A). The magnitude of the diaphragm A = sum of flexural and shear deflections.
translation is related to the sum of the rigidities of the
resisting shear walls. If the center of rigidity is not co­ For a structure with rectangular shear walls of the
incident with the line of action of the applied loads, the same material, with a wall height-to-length ratio of less
diaphragm will tend to rotate about the center of rigid­ than about 0.3, the flexural stiffness can be neglected,
ity. See Figure 3.7.1 (B). The location of the center of and the distribution made in accordance with the
lateral load can be different for different load cases, cross sectional area of the walls. If the height-to-

3 -2 6 PCI Design Handbook/Fifth Edition


length ratio is greater than about 3.0, the shear stiff­ used to determioetorsion-irt unsymmetrically located
ness can be neglected, and the distribution made in shear waits. This-type erf analysis assumes a unit
accordance with the moments of inertiajassed on the thickness for ail-shear walls, similar to the method
walls’ plan dimensions; used to design welds as discussed in-SecL6. 5.6. The
When the height-tor-length ratio is between 0.3 and method is described in the following-example".
30 i an equivaient moment of inertia, leq, can-be de­
rived for simplifyingthe calculation of wall rigidity. Lq Figure 3.7.1 Translation-end rotation of rigid
is an approximation of the moment of inertia that diaphragm s.
would result in a flexural deflection equal to the com­
bined flexural and shear deflections of the wall. Figure
3.12.16 compares the deflections and leq for several
load and restraint conditions.
Connecting or coupling of shear waiis or walls with
large openings will also affect stiffness, as discussed
in Sects. 3.7.5 and 3.7.6.

3.7.3 Distribution of Lateral Loads


Lateral loads are distributed to each shear wall in
proportion to its rigidity. It is usually considered suffi­
cient to design for lateral loads in only two orthogonal
directions.
When the shear walls are symmetrical with respect Figure 3.7.2 Effective width of wail
to the center of load application, the force resisted by perpendicular to shear w alls [7]
any shear wall is:.
SMALLER OF 121 ■
Fj = (r,/Sr)W (Eq. 3.7.2} OR VfcHEIGHT
FROM LEVEL
where: UNDER
_1 CONSIDERATION
J t
F| = the force resisted by an individual shear TO TOP OF WALL
wall, i
rt = the rigidity of wall i
2 r = sum of rigidities of all shear walls
W = total lateral load
3.7.4 Unsym m etrical Shear W alls
The analysis of structures which have shear walls Exam ple 3.7.1 D esign of Unsym m etrical
placed unsymmetrically with respect to the center of Shear W ails
the lateral load, should consider the torsional effect in Given:
the analysis. Typical examples are shown in Figure
The structure of Figure 3.7.3(C). All walls are 8 ft
3.7.3. high and 8 in. thick.
For complex structures such as multi-story build­
ings and buildings subjected to seismic loading, the
Problem:
distribution o f lateral loads to shear walls should be
Determine the shear in each wall, assuming the
based on a rigorous analysis, which calculates rela­
floors and roof are rigid diaphragms. Walls D and E
tive rigidities of shear walls in terms of their calculated
are not connected to Wall B.
shear stiffness and flexural stiffness. This type of anal­
ysis is required in order to accurately determine the
Solution:
load distribution to each story and the story drifts
Maximum height-to-length ratio of north-south
based on a separate calculation of the shear and
walls = 8/30 < 0.3. Thus, for distribution of the direct
bending deflection of the shear walls in each story.
wind shear, neglect flexural stiffness. Since walls are
Refer to Ref. 24 for more specific information regard­
the same thickness and material, distribute in propor­
ing this method of analysis.
tion to length.
For most single-story buildings subjected to wind
loads, a simplified, approximate analysis is commonly Total lateral load, W = 0.20 x 200 = 40 kips

PCI Design Handbook/Fifth Edition 3 -2 7


Figure 3.7.3 UnsymmetricatsheafMwalls
yy
i i-H i t i n n i t i i t7>
j ___ i___ i___ j .

ECCENTRICITY ECCENTRICITY
CENTER OF
RIGIDITY'
f2

CENTEROF A
CENTER OF
LATERAL LOAD CENTER O F . F1 LATERAL LOAD -
RIGIDITY —
F

(A) FREQUENTLY OCCURS IN BUILDINGS (B) FREQUENTLY OCCURS IN BUILDINGS


WITH EXPANSION JOINTS WITH LARGE DOOR OPENINGS

200’
„ 130.9' r t 69.1' r NORTH

75' . . 65' . . 40' . .2 0 1

T 15'
35'
50'
D
- B -
$
X *tu
40' | - 100' X

L 50'
35' CENTER OF
CENTER O F' RIGIDITY
LATERAL LOAD
30.9't I ECCENTRICITY
100' ~ 100'

'T P

w = 0.2 KLF

(C) BUILDING FOR EXAMPLE 3.7.1

Figure 3.7.4 Coupled shear walls Figure 3.7.5 Response to lateral loads

j COUPLING BEAM

3 -2 8 PCI Design Handbook/Fifth Edition


Determine center of rigidity; Coupling shear-walls carrreduce the lateral deflection
(drift) in a building and reduce the magnitude of the
40(75) + 30(140) + 40(180)
moments for which a shear wall-must be designed,
* = 40-K 3 6 + 40
fig u re 3.7.4 showstwo examples of coupled shear
= 130.9 ft from left
walls. The effectof couptiegjs toincrease the stiffness
y = center of bonding, since walls D and E are-
by transfer of shear and moment through the coupling
placed symmetrically about the center of
beam. The wall curvatures are altered from tha t of a
the building in the north-south direction.
cantilever because of the frame action developed.
Torsional moment, MT=40(30.9)=1236 kip-ft Figure 3.7.5 shows how the deflected shapes differ in
response to lateral loads.
Determine the polar moment of inertia of the shear Several approaches may be used to analyze the
wall group about the center of rigidity: response of coupled shear walls. A simple approach
Ip = Ixx 4 " ly y is to ignore the coupling effect by considering the
walls as independent cantilevers. This method results
= 2 €y2 of east-west walls in a conservative wall design. However, if the coupling
beam is rigidly connected, significant shears and mo­
= 2(15) (15)2 = 6750 ft9 ments will occur in the beam that may causeunsightly
and possibly dangerous cracking. To avoid the prob­
1^ = E€x2 of north-south walls lem, the beam-to-panel connection can be detailed
for little or no rigidity, or the beam can be designed to
= 40(130.9 - 75)2 + 30(140 - 130.9)2
resist the actual shears and moments.
+ 40(180-130.9)2 Finite element analysis may be used to determine
the distribution of shears and moments within a
= 223,909 ft? coupled shear wall. The accuracy (and cost) of such
an analysis is a function of the element size used. This
Ip = 6750 + 223,909 = 230,659 ft9 method is usually reserved for very complex struc­
tures.
Shear in north-south walls = M A “plane frame” computer analysis will be suffi­
ciently accurate for the great majority of structures. In
modeling the coupled shear wall as a frame, the mem­
40(40) 1236(130.9 - 75)(40)
Wall A = ber dimensions must be considered, as a centerline
110 + 230,659
analysis may yield inaccurate results. A suggested
14.5 + 12.0 = 26.5 kips model is shown in Figure 3.7.6(A).
Either a finite element or frame analysis may be
40(30) 1 23 6 (- 9.1) (30)
Wall B = used to determine the deflection of a coupled shear
110 + 230,659 wall, and hence its equivalent moment of inertia. This
10.91 - 1.46 = 9.45 kips may then be used to determine distribution of shears
in a building which contains both solid and coupled
40(40) 1236( -4 9 .1 ) (40) shear walls. Some frame analysis programs do not
Wall C =
110 230,659 calculate shear deformations; if significant, shear de­
formations may have to be calculated separately.
14.5 - 10.5 = 4.0 kips
MTy£
Shear in east-west walls = 3.7.6 Shear Walls with Large Openings
lc
Window panels and other wall panels with large
= 1236(15) (15)/230,659 = 1.21 kips openings may also be analyzed with a plane frame
computer program. Figure 3.7.6 (B) shows suggested
Note: Some building codes do not allow torsional models. Where length-to-depth ratios for vertical and
effects to be subtracted (only added). horizontal segments are similar, a frame model based
on segment centerlines will be reasonably accurate.
Otherwise, an analysis similar to that described for
3.7.5 Coupled Shear Walls
coupled shear walls may be used. Recent research
Two individual shear walls separated by large on shear walls with openings is available [25].
openings may be connected together with structural As with coupled shear walls, the deflections
members which can resist axial and/or flexural loads. yielded by the computer analysis may be used to de­
The combined stiffness of the two coupled shear walls termine equivalent stiffness for determining lateral
is greater than the sum of their uncoupled stiffness. load distribution. Shear deflections, if significant, may

PCI Design Handbook/Rfth Edition 3 -2 9


have to be hand calculated ancLadded to the flexural (Note: Some engineers prefer io use them ore-
stiffnesses from therframe analysis^ conservative assumptiortof an axis at b/5, b/4
tnverydall structures, vertical shear and axial de­ or b/3 from the leeward edge, dependingon
formations influence foe rigidity of panels wiffi large the foundation conditions.)
openings, so a more rigorous analysis ma^rbe^ re­ Resisting moment = 167.34(12072)
quired.
= 10,040 kip-ft
Factor of safety = 10,040/528
Example 3.7.2 One-Story Building
= 19.0 > 1.5 OK
Given:
The wind load analysisand design of a typical one- 4. Analyze connections:
story industrial building are illustrated by the structure a. Shear ties in double tee roof joint:
shown in Figure 3.7.7. 8-ft wide double tees are used
(Maximum load at first tee to tee joint)
for both the roof and walls. The local building code
specifies that a wind load of 25 psf be used for build­ Applied shear = [(80 - 8)/80](24)
ings of this height. = 21.6 kips

Solution: Load factor by ACI 318-95 = 1.3


t. Calculate forces, reactions, shears and mo­ Connection load factor (see Sect. 6.3)
ments: choose 1.2
Total wind force to roof:
Vu = 21.6(1.3)(1.2) = 33.7 kips
W = [25(160) (19/2 + 2.5)]/1000 = 48 kips
vu = 33.7/120 = 0.28 kips/ft
VL = VR = 24 kips
Use # 4 ties as shown in Figure 3.6.2
Diaphragm moment:
<[>Vn = 1 5 .3 kips
-W — = 960Mp-ft Required spacing = 15.3/0.28 = 54.6 ft
o o
(Note: Most engineers and precasters pre­
fer a maximum connection spacing of
2. Check sliding resistance of the shear wall:
about 8 to 15 ft for roof diaphragms.)
Determine dead load on the footing:
b. Shear ties at the shear walls:
8DT12 wall = 37(23.5}(120) = 104,3401b Vu = 24(1.3) (1.2) = 37.4 kips
12 in. x 18 in. footing vu = 37.4/120 = 0.31 kips/ft
= 1(T.5)(150)(120) = 27,000 lb
Assume 2 ft backfill
Wall tee connections as shown in Figure 3.6.2 are
= 100(1.5>(120)(2) = 36,000 lb designed similarly to the shear tie between roof tees.
This would require a spacing of 15,3/0.31 = 49.3 ft. In
Total = 167,3401b
order to distribute the load to the wall panels, at least
one connection per panel is required. From Figure
Assume coefficient of friction against 3.7.8 itis apparent that these connections should oc­
granular soil, |rs = 0.5 cur at the tee stems. Thus a spacing o f 4 ft or 8 ft would
Sliding resistance = (isN = 0.5(167.34) be used in this case.
= 83.67 kips Other types of connections using headed studs
are commonly used for this application. Design of
Factor of safety = 83.67/24 = 3.49 OK
studs is shown in Chapter 6,
(Note: A 1.5 factor of safety is specified by In some cases, the designer may find it necessary
some building codes.) to provide a connection that permits vertical move­
ment of the roof member. This is illustrated in Figure
3. Check overturning resistance: 3.7.8(B). As an alternative detail, a slotted insert may
Applied overturning moment = 24(3 + 19) be cast in the panel.
= 528 kip-ft c. Chord force (see Figure 3.7.9)
Resistance to overturning: T = C = M/b = 960/120
Assume axis of rotation at leeward edge of = 8.0 kips
the building, and that all the panels are con­
nected. Tu = 1 .3(8.0) = 10.4 kips

3 -3 0 PCI Design Handbook/Fifth Edition


-fig u r e 3.7.6 Computer m odels Figure 3.7.7 Exam ple 3.7.2

PUN

TOP OF
ROOF

GRADE

BOTTOM OF
FOOTING

SECTION

PCI Design Handbook/Fifth Edition 3 —31


sion of forces will typically provide the tie require­
ments given in S e c t 3.10 for structural integrity.
d=. Wall panei connections:
This shear wall may be designed to a ct as
a series of independent units, without ties
between the panels. The shear force is
assumed1to be distributed equally among
the wall panels (see Figure 3.7.10).

n = 120/8 = 15 panels
V = Vfi/n = 24/15 = 1.6 kips
D = 37(8)(23.5) = 6956 lb = 6.96 kips

Design base connection for 1.3W - 0.9D

Tu = 1.3(1.53)(21) - 0.9(6.96)(2)

= 41.8 - 12.5
= 29.3 kips tension

As an alternative, the shear walls may be designed


with two or more panels connected together. Two
analysis options are available. Example 3.11.7 illus­
trates an analysis where tension and compression
compensate one another with simple shear connec­
tions across the vertical joints. In that system, tie­
down connections may be required at the end panels
of a string of interconnected panels. The second
method is to connect a number of panels with rigid
connections so as to have the connected panels act
as a monolithic unit. By engaging more weight, tie-
down forces can be reduced or eliminated. Volume
change restraint must be considered when determin­
ing the number of panels to be interconnected.
Analysis of a rigidly connected panel group is de­
pendent upon a number of factors. Connection stiff­
ness determines whether the group will act monolithi-
cally or act as analyzed in Example 3.11.7. The aspect
ratio of the rigidly connected group will affect the
stress distribution at the base. While a panel group
with a high height-to-length ratio may act nearly as a
cantilever beanrr, a group with a medium to low ratio of
height to length will act as a deep beam and exhibit
non-linear stress distributions. Determination of tie-
down forces, vertical joint forces, and base shear dis­
tribution wiH be a function of the aspect ratio. The
shear and flexural stiffness of the individual panels will
have a similar effect on force distribution.
A simplified analysis is presented for this problem.
The analysis is fairly accurate for the aspect ratio
used, and assumes highly rigid panel-to-panel con­
nections. However, extrapolation to other aspect ra­
The chord force can be transmitted between mem­ tios is not recommended.
bers by ties at the roof tees, wall panels or a combina­
tion, as illustrated in Figure 3.7.9. The force through Factored shear = 1.3(1.6) = 2.08 kips per panel
the member flanges can be transmitted by the flange Factored weight = 0.9(6.96}
welded wire reinforcement. These ties and transmis­ = 6.26 kips per panel

3 -3 2 PCI Design Handbook/Fifth Edition


Tiaure 3.7.9 Chord forces 3 V Vu2 =4.16 - 3.21 = 0.95 kips
/W A L L -P At'JEL
n n n n rr n r n
On the compression side, from Figure 3.7.11(C):
\

- s p y= 0:
' A ENSION iDO MNECTION
Cu = 7.28 + 6T.26 = 13.54 kips

2FX = 0:
ROOF PLAN Vu3 —3.21 kips
T Check if 2MCU = 0 OK

- 17.5(3.21) - 6(7.28) - 2(6.26) = 0


' A ENSION X> MNECTION
Therefore, 2MCU = 0 OK
______
WALL ELEVATION

Figure 3.7.10 Panels acting asindividual units Example 3.7.3 Four-Story Building
in a shear wall
Given:
The wind load analysis and design of atypical four-
story residential building is illustrated by the structure
shown in Figure 3.7.12. 8-in. deep hollow-core units
are used forthe floors and roof, and 8-in. thick precast
concrete walls are used for all walls shown. Unfac­
tored loads are given as follows:

Gravity loads: L.L. D.L.


Roof 30

Roofing, mechanical, etc. 10


Hollow-core slabs 64

30 psf 74 psf

From Figure 3.7.11 (A), try connecting twopanel units: Typical floor
Design base connection for: Living areas 40

Tu = 1 .3 W - 0 .9 D Corridors 100
Partitions 10
Tu = [2(1.3)(1.6)(21) - 0.9(6.96)(2+10)]/12
= 1.02 kips Hollow-core slabs 64

74 psf
From Figure 3.7.1 1(B), examine joint forces using in­
dividual free body diagrams. On the tension side, as­ Walls 100 psf
sume the tie-down connection is concentrated at one
Stairs 100 130 psf
stem. Locate a panel-to-panel connection 17.5 ft from
bottom of panel. Wind loads:
0 to 30 ft above grade = 25 psf
30 to 3 4 ft 8 in. above grade = 30 psf
2Fy: Vu1 = 6.26 + 1.02 = 7.28 kips

Cu1 =[21 (4.16) + 2(6.26) - 6(7.28)]/17.5 Solution:


1. For wind in the transverse (east-west) direc­
Cu1 = 3.21 kips
tion, common practice for this structure would be to

PCI Design Handbook/Fifth Edition 3 -3 3


conservatively neglect the resistance provided by the Maximum moment at foundation
stair, elevator and longitudinal walls. Thus, two 27 ft
f _ 1.3M 0.9P
long interior bearing walls can be assumed to resist
“* (€2/6 ) l
the wind on one 26 ft bay. The wind and gravity loads
on the wall are shown in Figure 3.7.13. _ 1.3(205.1) 0.9(293.8)
Concentrated loads from the corridor lintels can be (272/6) 27
assumed to be distributed as shown in Figure 3.7.13.
In this example, these loads are conservatively ne­ = -7 .6 0 klf (compression)
glected to simplify the calculations.
= 205.1 kip-ft
Check overturning of shear wall:
D.L. resisting moment about toe of wall No tension connections are required between pan­
els and the foundation. Thus, the building is stable
= 27(27/2)11.92 + 3(2.72) + 0.8]
under wind loads in east-west direction. (Note: Struc­
= 3966 kip-ft tural integrity considerations may dictate the use of
minimum vertical ties. See Sect. 3.10.)
Factor of safety = 3966/205.1
= 19.3 > 1.5 OK 2. For wind in the longitudinal (north-south) direc­
tion, the shear walls will be connected to the
Check for tension using factored loads:
load bearing walls. The assumed resisting ele­
Dead weight on wall ments are shown in Figure 3.7.14; a summary
P = [1.92 + 3(2.72) + 0.8] (27) of the properties is shown in Table 3.7.1. Sam­
= 293.8 kips ple calculations of these properties are given
below for element A.

3 -3 4 PCI Design Handbook/Fifth Edition


Figure 3.7-12 Example 3.7.3 — Four-story building design

PUN

;b

ELEVATION

WALL CO N N E C TIO N

8"
_l
SHEAR KEY

END WALL BEARING

HO LLOW -CORE C O N N E C TIO N S

PCI Design Handbook/Fifth Edition 3 -3 5


Figure & 7 .1 3 toads to transverse walls - four-story design example

SUM M ARY OF GRAVITY LOADS

LOAD TRIBUTARY UNIT LOADS, psf WALL TOTAL UNFACTORED LOADS


MARK AREA L.L. D.L. WEIGHT, klf L.L. D.L. T.L.

Pr 78 fP 30 74 - 2.3 kips 5.84<jps 8.1 kips


P4 78 fP 100 64 - 7.8 kips 5.0 kips 12.8 kips
P3 78 fP 100 64 - 7.8 kips 6 .0 kips 12.8 kips
P2 78 fP 100 64 - 7.8 kips 5.0 kips 12.8 kips

Wr 26 tin. ft 30 74 - 0.78 klf 1.92 klf 2.70 klf


W4 26 lin. ft 16* 74 0.8 0.42 klf 2.72 klf 3.14 klf
w3 26 fin. ft 16* 74 0.8 0.42 klf 2.72 klf 3.14 klf
W2 26 lin. ft 16* 74 0.8 0.42 klf 2.72 klf 3.14 klf
w, N/A - - 0.8 0 0.80 klf 0.80 klf

INCLUDES LIVE LOAD REDUCTION ALLOWED BY CODES

3 -3 6 PCI Design Handbook/Fifth Edition


Table 3.7.1 Properties of resistingeiements for wind in longitudinaldireelion—

NO. OF
ELEMENT A*. I ft ieq ELEMENTS ftleq- W W ^y)
4'-8ir
:

(A) 3.t1: 12.6 3.43 7.31 4 29.24 138 123- 899


- f -
7b
6l _
8'-0"
I
6'-4" 5.36 28.7 4.0 14.68 11 161.5 3.98 308 4521
t
Jb

8'-8"

13*' © 5.81 158.1 4.34 27.02 2 54.04 7.33 68 1837


6 j4 "j A

L_ ~1 Vb
6'-4"
12-0" ® 5.81 205.6 3.45 28.13 2 56.26 7.63 41 1153
I
_ L
8 -8"
3;
GO

I - /P\
4'-0" © 5.36 29.0 4.0 14.76 1 14.76 4.01 SO 886
t

8'-8"
j |
9-8" ® 5.81 114.1 2.72 25.35 1 25.35 6.88 53 1344
r~
2-0" J i;- y b
8'-8"
I
6'-4" | J 7'-8" © 5.81 171.6 4.09 27.39 1 27.39 7.43 49 1342
I — L- y b

Snlgq = 368.54 2 = 11,982

Center of rigidity = 11,982/368.54 = 32.51 ft from east


Note: The north-south wind toad is slightly eccentric b y 32.51 - 61.33/2 = 1.85 ft
Torsion due to this eccentricity is neglected in calculating shears and moments in Table 3.7.2.

Figure 3.7.14 Wind resisting elements for North-South wind

PCI Design Handbook/Fifth F d ito b 3 -3 7


'eq
is essentially a relative stiffness:
S"
I Kr = 1/A; A = ^ -
— 1

Vt f 3EI«q
i. Kr =
l* » 5'-8 Ph3
1
_____ * Since 3, E, P, and hs are all constants when
—•4 U — 8" comparing stiffnesses, Kr = leq.

Effective width of perpendicular wall (see Figure Distribution of load to element A based on its rela­
3.7.2} is the smaller of: tive stiffness is (seeTable 3.7.1):
12t = 12(8} = 96 in., or 7.31(100)
1.98%
(1/6)(34.67}(12> = 69.3 in. Use 6 ft 8 in. E n te q 368.54
Area of web = 4.67(0.67) = 3.11 ft? The shears and moments in the north-south direc­
Area of flange = 5.67(0.67) = 3.78 ft2 tion are shown in Figure 3.7.15, and the distributions
are shown in Table 3.7.2.
6.89 ft2^ To check overturning, consider element B- at the
3.11(4.57/2) + 3.78(4.67 - 0.33) first floor:
yb From Figure 3.7.13 the dead toad on the 6 ft-4 in.
6.89
3.43 ft portion of element B:
y, = 4.67 - 3.43 = 1.24 ft
= 1.92 + 3(2.72) + 0.8 = 10.88 kip/ft
1 = Q'67^ 67- + 3.11(3.43 - 2.33}2
The dead toad on the 8 ft-0 in. portion of element
+ 3.78(1.24 - 0.33)2
B is the weight o f the waH:
= 12.58 ft4
Equivalent stiffness is calculated using the Case 1 = 34.67(0.1) = 3.47 kip/ft
multi-story formula from Table 3.12.16.
The resisting moment is then:
J____
'eq
13.4(1) Mr = 10.88(5.67)(4) + 3.47(8)(4)
1+
KK
= 358 kip-ft x 11 elements
f2.58
= 7.31 ft4 = 3938 kip-ft
13.4(12.58)
3.11(8.67)2
Factor of safety = 3938/966.9 = 4.1 > 1 . 5 OK

(Note: This conservatively neglects the contribu­


Figure 3.7.15 Wind load in North-South
tion of the other elements.)
direction
To check for tension, also consider element B:

Total dead weight on the wall


= 10.88(5.67} + 3.47(8) = 89.45 kips
Total wall area
= (8.0 + 5.67)0.67 = 9.16 ft2

M = 38.5 kip-ft (see Table 3.7.2)

_ 1.3M(d/2) Q .9 P
tut I A

1.3(38.5}(4.0) 0.9(89:45)
28.7 9.16

= -1.81 ksf (compression)

3 -3 8 PCI Design Handbook/Fifth Edition


No net uplift exists between the panels-and the The shear fotceto be resisted by the grout key ad-
foundation. The building is stable underwind loads jacenttothechordtension, TU) is approximately equal
in the north-south direction. to Tu. The ability o f this grout keyt o transfer this-force
(0,42 kips) in shear must therefore be checked.
T h o connections required t o assureJhat the ele­
The resisting shear strength erf the grout key is as­
ments will act in a composite manneras assumed can
sumed to-be 80 psi, (See Sect. 3.6.2) along the full
be designed by considering element A. The unit
length of the keyway.
stress at the interface is determined using the classic-
The shear force that this-grout key is capable o f re ­
equation for horizontal shear:
sisting is:

VQ <|)Vn = A0.080 ksi


vh = t

<t>Vn = 26(12)(3)(0.080) = 74.9 kips


Q = 5.67(0.67) (T .24-0.33) = 3 .4 6 fP
74.9 kips > 0.42 kips OK

1.08(3.46)
Vh = = 0.297 kips/ft For wind from the north or south:
12.58
.. .. 0.282(61.33) OM1.
Vru = Vu, = --------^ ------ - = 8.65 kips
Total shear = 0.297(8.0) = 2.37 kips
^ _ _ Mu _ 0.282(61,33)2
t
u € 8(181.33)
Connections similar to those shown in Figure = 0.73 kips
3.7.12 can be designed using the principles outlined
in Chapter 6. Check the resisting shear force of the first grout key:

4>Vn = A0.080 ksi


Design of floor diaphragm:

Analysis procedures for the floor diaphragm are <(>Vn = 181.33(12)(3)(0.080) = 522 kips
described in S ect 3.6. For this example refer to Fig­
ure 3.7.16. 522 kips > 8.65 kips OK

The factored wind load for a typical floor is:


Chord reinforcement should be designed to resist
wu = 1.3(25) (8.67) = 282 plf the chordiension, Tu, This chord reinforcement is usu­
ally embedded in pour strips at the ends of the hollow-
core slabs.
For wind from the east or west: Tension forces such as VRu and Tu for wind in both
directions must also be transferred into shearwalls
through appropriate connections. By comparing the
67 kips reinforcing and connections required for structural in­
tegrity requirements (Sect. 3.10), it can be shown,
usually by inspection, that structural integrity details
n _ T _ Mu _ 0.282(26)2 amply provide resistance for the transfer of these ten­
u u € 8(56.67) sion forces.

= 0.42 kips 3.7.7 Exterior Panels as Shear Walls

In many structures it is economical to take advan­


tage of the strength and rigidity of exterior panels, and
As Figure 3.7.16 shows the chord tension, Tu, is design them to serve as the lateral load resisting sys­
parallel to the span of the hollow-core slabs and there­ tem. The effectiveness of such a system is largely de­
fore wilt be resisted by the flexural reinforcement of the pendent on the panel-to-panel connections.
slabs.

PCI Design Handbook/Fifth Edition 3 -3 9


Table 3.7.2 Distribution of wind shears and moments (north-south direction)
- 4 th floor- S rdH eor 2nd floor 1 s t floor

_ Shear Moment -Shear Moment : Shear Moment : S h ear Moment-

% 14.71 66.7 - 27.98 251.7 41.24 5518 54.51 966.9


Element Diet. kips kip-ft kips kip-ft- kips kip-ft kips tdp -ft

A 1.98 0.29 1.32 0.55 4:98 0.82 10.9 1.08 19.1


B 3.98 0.59 2.65 1.11 10.0 1.64 22.0 = 217 38.5
C 7.33 1.08 4.89 2.05 18.4 3.02 40.4 4.00 70.9
D 7/63 1.12 5.09 2.13 19.2 3.15 42.1 4.16 73.8
E 4.01 0.59 2.67 1.12 10.1 1.65 22.1 2.19 38.8 .
F 6.88 1.01 4.59 1.93 17.3 2.84 38.0 3.75 66.5
G 7.43 1.09 4.96 2.08- 18.7 3.06 41.0 4.05 71.8

The relative stiffness and percent distribution for the elements in this table are assumed the samefor all stories. The exact values m ay be slightly
different for each story because the values change due to reduced flange width (see Figure 3.7.2).

Figure 3.7.17 illustrates that the method of inter­ Figure 3.7.16 Diaphragm analysis
connecting individual wall panels can be selected to
maximize the efficiency of the building’s shear wall W
and foundation systems in resisting lateral loads ap­ JHJuuiuiin
plied to the building. If all of the individual wall panels c__
located on one wall of a building are connected to­
gether to transfer shear forces across the panel joints,
the entire wall of the building acts as one “plate
shaped’’ shear wall. See Figure 3.7.17(A). Ifpanel-to-
panel shear connections are provided at the building | V R 56.67'
corners, the shear wall will become “channel” or
“tube” shaped in cross section. The channel or tube
shaped shear walls are structurally stiffer than the
plate shaped shear wall and engage more of the
building foundation to resist the shear wall reactions. T
26'-0"
See Figure 3.7.17(B).
Because the components and the connections in a (A) W IN D FR O M EAST OR W EST
“tube” are not completely rigid, full tube behavior
does not develop. Figure 3.7.17(B) illustrates the dif­
ference. The peaking of the foundation reaction at
the corner results from shear lag, which limits the ef­
fective width of the “flange” . Accurate evaluation of 8" 181.33' 8"
shear lag is difficult, but analytical and research stud­
ies have indicated the following limitations on the ef­ , VR
fective flange are sufficiently accurate for most struc­
1
tures:

1. One-half the length of the shear wall.


li C / FIRST JOINT
T 61.33'
i
______________ i
2. One-third length of windward or leeward wall. w
NORTH
3. One-tenth the height of the building.

4. Six times the thickness of the “flange” wall. (B) W IN D FROM NO RTH OR SOUTH

5. Distance to nearest major opening.

6. One-half the distance to the nearest shear wall.

3 -4 0 PCI Design Handbook/Fifth Edition


figure 3.7.17 Foundation reaction 1. Positive moment-resisting^ capacity is much
distributions resulting from easier and less expensive to attain with preten­
sioned members than negative momenbcapac-
ity at supports.
2. Connections which achieve continuity a tih e
supports are usually complex and costly.
3. The restraint to volume changes that occurs in
rigid connections may cause serious cracking
and unsatisfactory performance or, in extreme
cases, everr structural failure*

Therefore, it is most desirable to design precast,


prestressed concrete structures with connections
which allow lateral movement and rotation, and to de­
sign the structure to achieve lateral stability through
the use of floor and roof diaphragms and shear walls.
However, in some structures, adequate shear
walls interfere with the function o f the building, or are
more expensive than alternate solutions. In these
cases, the lateral stability of the structure depends on
the moment-resisting capacity of either the column
bases, a beam-column frame, or both.
When moment connections between beams and
columns are required to resist lateral loads, it is desir­
able to make the moment connection after most of the
dead loads have been applied. This requires careful
detailing, specification of the construction process,
and inspection. If such details are possible, the mo­
ment connections need only resist the negative mo­
ments from live load, lateral loads and volume
changes, and will then be less costly.

3.8.2 Moment Resistance of Column Bases


Buildings without shear walls may depend on the
fixity of the column base to resist lateral loads. The
ability of a spread footing to resist moments caused
by lateral loads is dependent on the rotational charac­
teristics of the base. The total rotation of the column
base is a function of rotation between the footing and
soil, bending in the base plate, and elongation of the
anchor bolts, as shown in Figure 3.8.1.

The total rotation of the base is:


4*b = $ab (Eq. 3.8.1)
3.8 Moment-Resisting Building Frames If the axial toad is large enough so that there is no
tension in the anchor bolts, q>bp and <|)ab are zero, and:
3.8.1 General
<|>b= <|>i (Eq. 3.8.2)
Precast, prestressed concrete beams and deck
members are usually most economical when they can Rotational characteristics can be expressed in terms
be designed and connected into a structure as sim­ of flexibility or stiffness coefficients;
ple-span members. This is because: <t> = YM = M/K (Eq. 3.8.3)

PCI Design Handbook/Fifth Edition 3 -4 1


where: Figure 3.8.1
M = applied-moment = Pe of rotational coefficients for
column bases
- e- = eccentricity of the applied load, P
Y—= flexibility coefficient
K = stiffness coefficient = 1 /y

tf bending ofthe base plateand strainrinthe anchor


bolts are assumed as shown in Figure 3.8.1, the flexi­
bility coefficients for the base can be derived, and the
total rotation of the base becomes:

<t>b = M(Vt + Ybp + Yab)

= Pe(Yf + Ybp + Yab) (Eq- 3.8.4)

_i_ (Eq. 3.8.5)


Yf
Mr
(X1 + X2) 3[2e/(h + 2x J - 1]
Ybp = > 0
f ie E J ^ h + x,)
(Eq. 3.8.6}
g [ 2e/(h + 2xJ - 1]
(Eq. 3.8.7)
2eEsAb(h + x,)

where:
Yf = flexibility coefficients of footing/soil
interaction
Ybp = flexibility coefficients of base plate
Yab = flexibility coefficients of anchor bolts
ks = coefficient of subgrade reaction from value and coefficient of
Figure 3.8.2 subgrade reaction, kg
tf = moment of inertia of the footing (plan
dimensions)
Es = modulus of elasticity of steel
lbp = moment of inertia of the base plate
(vertical cross-section dimensions)
Ab = total area of anchor bolts in tension
h = width of column in direction of bending
x* = distance from face of column to the
center of the anchor bolts, positive
when anchor bolts are outside the
column, and negative when anchor
bolts are inside the column

x2 = distance from the face of the column to Rotation of the base may cause an additional ec­
base plate anchorage centricity of the loads on the columns, causing mo­
ments which must be added to the moments induced
g = assumed length over which elongation by the lateral loads.
ofthe anchor bolt takes place = 'k of Note that in Eqs. 3.8.6 and 3.8.7, rf the eccentricity,
development length + projection for e, is less than h/2 + xt (inside the center of compres­
anchor bolts made from reinforcing sion), Ybp and Yab are less than zero, meaning that
bars, or the length to the hook + there is no rotation between the column and the foot­
projection for smooth anchor bolts (see ing, and only the rotation from soil deformation (Eq.
Figure 3.8.1) 8.8.5} need be considered.

3 -4 2 PCI Design Handbook/Fifth Edition


Values of £q. 3.8.5 througtr3:8.7 are tabulated for Figu re 3.8.3 Exam ples 3.8.1 and 3.8.2*
typical cases in Figures 3.12.17 and_3.12.18.

E x a m p le 3^.1 Stability Analysis of an


Unbraced Frame

Given:
The column shown in Figure 3.8.3
Soil bearing.capacity = 5000 psf
P = 80 kips dead load, 30 kips live load
W = 2 kips wind load

Problem:
Determine the column design loads and moments
for stability as an unbraced frame.

Solution:
ACI 318-95 requires that the column be designed
for the following conditions:

1. t.4D + 1.7L
2. 0.75(1.4D + 1.7L + 1.7W)
3. 0.9D + 1.3W

The maximum eccentricity would occur when con­


dition 3 is applied. Moment at base of column:

M = 2(16) = 32 kip-ft = 384 kip-ln.


0.9D = 0.9(80) = 72 kips
1.3W = 1.3(384)= 499.2 kip-in.
Eccentricity due to wind load

Mu 499.2
e 6.93 in.
Pu 72

To determine the moments caused by base rota­


COLUMN AND BASE PLATE
tion, an iterative procedure is required.
SECTION A-A
Estimate eccentricity due to rotation = 0.25 in.

e = 6.93 + 0.25 = 7.18 in. Eccentricity caused by rotation:


<j>bhs = 0.00115(16)(12) = 0.22 in. = 0.25
Check rotation between column and footing:
No further trial is required
h/2 + x, = 20/2 + (-2) = 8 in. > 7.18
Design requirements for 0.9D + 1.3W:
thus, there is no tension in the anchor bolts and no
P u = 72 kips
rotation between the column and footing.
Mu = 5 1 7 kip-in = 43.1 kip-ft
If = [6(12)]4/12 = 2.24 x 106 in4

From Figure 3.8.2: kg = 200 psi/in. Check fo r8.75 (1.4D + 1.7L + 1.7W):
yf = 1/kgl, = 1/(200(2.24x106)] Pu = 0.75 (1.4D + 1.7L)
= 22.3 x 10-io
= 0.75(1.4(80) + 1.7(30)]
(Note:This could also be read from Figure
3.12.18.) = 122.3 kips*
Mu = 72(7.18) = 517 kip-in.
<|>b = YfMu = (22.3 x 10-10) (517 x 103) *T h e se exam ples assum e that th e section properties of the
= 0.00115 radians column extend to the top of the roof.

PCI design Handbook/Fifth Edition 3 -4 3


0.75(1.7W) = 0.75[1.7(384)] where:
= 489.6kip-in. fv = degree o f base fixity,-expressed as a
decimal

Kb = 1/yb
Estimate eccentricity d ue to rotation = 0^22 in.
= 122.3(4.22) = 516.1 kip-in. K - 4Eclc
^ K
(j>b = y, M u = (22.3x 10~10) (516.1 x 103) Ec = modulus of elasticity of the column
concrete
- 0.001-15 radians
lc = moment of inertia of the column
^ = 0 . 0 0 1 1 5 ( 1 6 ^ 2 ) = 0.22 in. OK
hs = column height
Design requirements for 0.75[1.4D + 1.7L + 1.7WJ:
Pu = 122.3 kips Example 3.8.2 Degree of Fixity
Mu = 516.1 kip-in. = 43.0 kip-ft Determine the degree of fixity of the column base in
Example 3.8.1;
Sect. 10.12.3.2 (ACI318-95) also requires that the
moment caused by a minimum eccentricity of 0.6 + Ec = 4300 ksi:
0.03h be considered when designing for 1.4D + 1.7L.
Kb = 1/Yb = 1/(22.3x10-1°) = 4.48x108
Pu = 1.4D + 1.7L = 1.4(80) + 1.7(30)
lc = 20^/12 = 13,333
= 163 kips
_ 4(4.3 x1 0 6) (13,333)
e = 0.6 + 0.03h = 0.6 + 0.03(20) " 16(12)
= 1.2 in.
11.94x108
Estimate eccentricity due to rotation = 0.1 in. 4.48
Fb 0.273
4.48 + 11.94
Mu = Pue = 163(1.2 + 0.1)
3.8.4 Modeling Partially Fixed Bases
= 211.9 kip-in
Many computer programs permit the direct model­
(|)b = (22.3 x 10- 10)(211.9 x 103) ing of various degrees of base fixity by the use of
spring options. A simple way to model base fixity is to
= 0.000473 radians
incorporate an imaginary column below the actual
column base. If the bottom o f the imaginary column
q>bhs = 0.000473(16) (12) = 0.09 in.
is modeled as pinned, then the expression for its rota­
= 0.1 in. OK tional stiffness is:

Koi - 3Ecilci/hci (Eq. 3.8.9)


Design requirements for 1,4D + 1.7L:
where the subscript “ci” denotes the properties of the
Pu = 163 kips imaginary column (Figure 3.8.4), and = Kb as cal­
culated in Sect. 3.8.2, or, the degree of base fixity, Fb,
Mu = 212 kip-in. = 17.7 kip-ft can be determined or estimated, and Kb calculated
from Eq. 3.8.8.
For the computer model, either loi or hci may be var­
3.8.3 Fixity of Cofum n Bases ied for different values of Kd, with the other terms left
constant for a given problem. It is usually preferable
The degree of fixity of a column base is the ratio of to use Eci = Ec. For the assumptions of Figure 3.8.4:
the rotational stiffness of the base to the sum of the
rotational stiffnesses of the column plus the base: hci — SEcjlcj/Kcj (Eq. 3.8.9a)
or
= (£<,.3.8.8) Id = KeM SE c) (Eq. 3.8.9b)

3 -4 4 PCI Design Handbook/Rfth Edition


Example 3.8.3 Imaginary Column for sis should be consistent with that used in the analysis
Computer Model of the column for other loadings, and the determina­
tion of slenderness effects. The- horizontal shear
Determine the-length of an imaginary column-to
force at-the foundation may result in a lateral displace­
model thefixity of the column base of Examples 3.8rl
m e n t-^ the foundation; this will reduce the volumetric
and 3.82;
restraint force.
f'c = 5000 psi
Ec = 4300 ksf
3.8.5.1 Equivalent Volume Change
Assume:
If a horizontal framing member is connected at the
Ed = Ec = 4.3 x 106 psi ends such th a t the volume change shortening is re­
strained, a tensile force is built up in the member and
Id = lc = 13,333 in*
transmitted to the supporting elements. However,
since the shortening takes place gradually over a peri­
K d= Kb= 4.48x108
od of time, the effect of the shortening on the shears
3Edld _ 3(4.3x106)(13,333) and moment of the support is lessened because of
hci Kd 4.48 x 1 0 s creep and microcracking of the member and its sup­
port.
= 383 in. = 31.9 ft For ease of design, the volume change shorten­
ings can be treated in the same manner as short term
elastic deformations by using a concept of “equiva­
lent” shortening.
Thus, the following relations can be assumed:
3.8.5 Volume Change Effects in Moment-
Resisting Frames
Sec = Sc/K f (Eq. 3.8.10)

The restraint of volume changes in moment-resist­ Ses = Ss/Kf (Eq. 3.8.11)


ing frames causes tension in the girders and deflec­ where:
tions, shears and moments in the columns. The mag­
nitude of these tensions, shears, moments and 6ec,6es = equivalent creep and shrinkage short­
deflections is dependent on the distance from the enings, respectively
center of stiffness of the frame. 8C, 8S = calculated creep and shrinkage short­
The center of stiffness is that point of a frame, enings, respectively
which is subject to a uniform unit shortening, at which K( = a constant for design purposes which
no lateral movement will occur. For frames which are varies from 4 to 6
symmetrical with respect to bay sizes, story heights
The value of Kf will be near the lower end of the
and member stiffnesses, the center of stiffness is lo­
range when the members are heavily reinforced, and
cated at the midpoint of the frame, as shown in Figure
near the upper end when they are lightly reinforced.
3.8.5.
For most common structures, a value of K( = 5 is suf­
Tensions in girders are maximum in the bay near­
ficiently conservative.
est the center of stiffness. Deflections and moments
Shortening due to temperature change* will be
in columns are maximum furthest from the center of
similarly modified. However, the maximum tempera­
stiffness. Thus in Figure 3.8.5:
ture change will usually occur over a much shorter
F1 < F2 < F3 time, probably within 60 to 90 days.
Thus,
A 1 > A2 > A 3

M, > M2 > M3
Set = 6t/Kt (Eq. 3.8.12)
The degree of fixity of the column base as de­
scribed in Sect. 3.8.3 has a great effect on the magni­
tude of the forces and moments caused by volume
change restraint. An assumption of a fully fixed base
in the analysis of thestructure may result in significant
‘ Temperature change is of course a reversible effect; in­
overestimation of the restraint forces, whereas as­ creases cause expansion and are important in design and
suming a pinned base may have the opposite effect. location of expansion joints (Sect. 3.3.3). Temperature differ­
The degree of fixity used in the volume change analy­ entials in roof and wall elements should also be considered.

PCI Design Handbook/Fifth Edition 3 -4 5


Figure 3.8A ModeiJoj^partially fixed column Example 3;8t4 Calculation o f Column
base Moment Caused by Volume
Change Shortening o f a Beam

Given:
Thebeam of Example 3.3.1 is supported and at­
tached to two 1:6 x 16-in. columns as shown In the.
sketch. Use Ec = 4.3 x 106 psi and % (col.)c = 5000
psi.

where:
Problem:
Set, St = the equivalent and calculated tem­ Determine the horizontal force at the top of the col­
perature shortening, respectively umn and the moment at the base of the column
caused by volume change shortening of the beam.
Kt = a constant; recommended value = 1.5

The total equivalent shortening to be used for de­


sign is:

A — S©c f Sgg f Set

_ + 5s , S,
(Eq. 3.8.13)
Kf + K,

When the equivalent shortening is used in frame


analysis for determining shears and moments in the
supporting elements, the actual modulus of elasticity Solution:
of the members is used , rather than a reduced modu­ lc = bh3/12 = 16(16)3/12 = 5461 in4
lus as used in other methods. From Example 3.3.1:
Figures 3.12.20 and 3.12.21 provide equivalent Total volume change shortening from erection to
volume change strains for typical building frames. final is 0.20 in., or 0.10 in.oach end.

Figure 3.8.5 Effect of volume change restraints fn building frames

3 -4 6 PCI Design Handbook/Fifth Edition


© ©

12“ x 24 “ BEAM (TYP.)


E b = 4 3 0 0 ksi

16" x 16" COLUMN (TYP.)


Ec = 4700 ksi

20% FIXED (TYP.)


(SEE SECT. 3.8.3)

Calculate the equivalent shortening: Example 3.8.5 Volume Change Restraint


Forces
5c + 6s , 5t Given:
A =
K{ + K, The 4-bay, 2-story frame shown above
[246 - 80 + 454 - 140 210] Beam modulus of elasticity = Eb = 4300 ksi
5 1.5 j Column modulus of elasticity = Ec = 4700 ksi
Column bases 20% fixed (see Sect. 3.8.3)
x (10“ ^(24)(12) Design R.H. = 70%
Design temperature change = 70° F
= 2 3 6 X 1 0 -6 (288) = 0.07 in.
Problem:
Determine the maximum tension in the beams and
A = QffiO = 0.035 in. each end
2 2 the maximum moment in the columns caused by vol­
ume change restraint.
A = FhL
2 3ECIC Solution:
1. Determine relative stiffness between columns
and beams:

lb = 12(24)3/12 = 13,824 in4


3(4.3 x 106)(5461)(0.035)
= 826 lb
[12(12)]® Eblb/€ = 4300(13,824)/[24(12)]

M = Fhs = 826(144) = 206,400

= 118,944 lb-in = 9.91 kip-ft lc = 16(16)3/12 = 5461 in*

Eclc/hs = 4700(5461 )/[16(12)]

= 133,681
3.8.S.2 Calculating Restraint Forces _ Eblb/€ _ 206,400 _
Most “plane frame” computer analysis programs ^ Eclc/ h s 133,681
allow the input of shortening strains of members from
volume changes. The equivalent strains as described 2. Determine deflections:
in Sect. 3.8.5.1 can be input directly into such pro­ From Figure 3.12.20:
grams.
6e =221 x 10-6 in./in.
For frames that are approximately symmetrical, the
coefficients from Figures 3.12.19 and 3.12.22 can be
A b= V = 0.000221 (24)(12) = 0.064 in.
used with small error. The notation for these tables is
described in Figure 3.12.23. Aa= 6e(2€) = 0.128 in.

PCI Design Handbook/Fifth Edition 3 -4 7


Figure 3.8.6 Computer models

PINNED FIXED

(A) M ODELING TYPICALLY USED FOR GRAVITY LOADS (B) SUG G ESTED M O DEL FOR LATERAL LOADS AND
VO LUM E CHANGE RESISTANT FORCES

3. Determine maximum beam tension: F2 = kfkbAjEclc/h|


Maximum tension is nearest the center of stiff­ _ 5.0{3.0)(0.064)(4700)(5461)
ness, i.e., beams BC and CD, 2nd floor.
( 16( 12)]3
From Figure 3.12.19:
For: = 3.48 kips
n = 4 and
4. Determine maximum column moments:
i = 2
For base moment, Mf:
kb = 3 .0 0
From Figure 3.12.22, by interpolation similar
From Figure 3.12.22: to above:
For Kr = 1.0,fixed base;kf= 11.2 km (fixed) = (4.9 + 5.2)/2 = 5.05
For K, = 2.0,fixed base;kf= 11.6 km (pinned) = 0
Therefore for:
km (20% fixed) = 0 + 0.20(5.05) = 1.0
Kr = 1.5
Mf = knAEcIc/h,,2
k, = 11.4
For pinned base: = 1.0(0.128) (4700) (5461 )/[16(12)p
kf = 3.4
= 89-. 1 kip-in.
(for Kp = 1.0 and 2 .0)
For 20% fixed: For second floor moment, Mg.:
kf = 3.4 + 0.20(11.4-3.4) = 5.0 km (fixed) = (3.9 + 4.5)/2 = 4.2

3 -4 8 PCI Design Handbook/Fifth Edition


km (pinned) = (2.1 + 2.4)/2 = 225 Figure 3.9. t Deformation m odes
km (20%iiX€d) = 2.25 + 0.20(420 -2 2 5 )
= 2.64
2.64(0.128) (4700) (5461)
M2L_ f16(12)]2

= 235 kip-in.

3 ,8.6 Computer Models for Frame Analysis

When precast frames are modeled as “sticks”, as


is usually done with steel framesTthe results are often
very misleading. For example, the structure as mod­
eled in Figure 3.8.6(A) will indicate more flexibility than
is actually true. Lateral drift will be overestimated, and
the moments caused by axial shortening may be un­
derestimated. Figure 3.8.6(B) shows a suggested
model which will better estimate the true condition.

3.9 Shear Wall-Frame Interaction commentary emphasizes that the overall integrity o f
the structure can be substantially enhanced by minor
Rigid frames and shear walls exhibit different re­
changes in the detailing of reinforcement. In the event
sponses to lateral loads, which may be important, es­
of damage to a beam, for example, it is important that
pecially in high-rise structures. This difference is illus­
displacement of its support member be minimized, so
trated in Figure 3.9.1.
that other members will not be affected. For this rea­
A frame bends predominantly in a shear mode as
son, connection details which rely solely on friction
shown in Figure 3.9.1 (A), while a shear wall deflects
caused by gravity loads are not permitted. Connec­
predominantly in a cantilever bending mode, Figure
tions should also be arranged so as to minimize the
3.9.1(B). Elevator shafts, stairwells, and concrete
potential for cracking due to restraint of volume
walls normally exhibit this behavior.
change forces.
It is not always easy to differentiate between
modes of deformation. For example, a shear wall
weakened by a row, or rows of openings may tend to
3.10.2 Precast Concrete Structures
act like a frame, and an infilled frame will tend to de­
flect in a bending mode. Also, shear deformation of a For typical precast concrete structures, improved
shear wall can be more important than bending de­ redundancy and ductility are achieved by connecting
formation if the height-to-length ratio is small, as dis­ members into a toad path to the lateral toad resisting
cussed in Sect. 3.7.2. system. The load path in the lateral load resisting sys­
If all vertical elements of a structure exhibit the tem shall be continuous to the foundation.
same behavior under load, that is, if they are all frames Any individual member may be connected into this
or all shear walls, the load can be distributed to lb e toad path by alternative methods. For example, a
units in proportion to their stiffnesses (Sect. 3.7.3). toad bearing spandrel could be connected to a dia­
However, because of the difference in bending phragm (part of the lateral load resisting system).
modes, the toad distribution in structures with both Structural integrity could be achieved by connecting
frames and shear walls is considerably more com­ the spandrel into all or a portion of the deck members
plex. Refs. 8 through 12 address this issue detail. forming the diaphragm, which in turn would be con­
nected to the supporting beams and the beams would
3.10 Structural Integrity be connected to their supporting columns. Alterna­
tively, the spandrel could be connected only to its
supporting columns, which in turn must then be con­
3.10.1 Introduction
nected to the diaphragm.
It is the intent of the structural integrity provisions of Vertical continuity is achieved by providing con­
ACI318-95 to improve the redundancy and ductility of nections at horizontal joints of vertical members.
structures and thereby to reduce the risk of failure or For precast concrete structures, the following pro­
collapse of parts or all of a building due to damage visions will satisfy the requirements of ACI 318-95,
occurring to a relativelysmall area of a building. Code Sects. 7.13.3 and 16.5.

PCI Design Handbook/Fifth Edition 3 -4 9


1. Membersshall beconnected to the lateral load Example 3.10.1 Compliance of a Precast
resisting system. Tension tiesshaUbe provided Concrete Structure wHfrthe
in the transverse, longitudinal, and vertical di- structural Integrity Provisions
rections and around too perimeter of the struc­
This example uses The design o f the one story:
ture.
buiiding of Example 3.11.7 for checking compliance
with the structural irrtegrityprovisions outlined in Sect.
2. The lateral load resisting system shall be con­
3.10.2. Theoumbers used for the structural integrity
tinuous to the foundation.
provisionsof this example refer to the same provision
numbers used in Sect. 3.10.2.
3. A diaphragm shall be provided with connec­
tions between diaphragm elements, with ten­ Provision 1. “Members shall be connected...”
sion ties around its perimeter and around open­
Compliance is provided by the connections be­
ings which significantly interrupt diaphragm
tween the roof diaphragm and the walls.
action.
Provision 2. “The lateral load resisting...”
4. Column splices and column base connections
Compliance is provided by the existence of the ex­
shall have a nominal tensile design strength not
terior shearwalls and the connections, of these walls
less than 2G0Ag in. pounds, where Ag is the
to the roof diaphragm and the foundation.
gross area of the column in square in. For a
compression member with a larger cross-sec­ Provision 3. “A diaphragm shall be...”
tion than required by consideration of loading, a
reduced effective area, Ag, not less than one- Compliance is provided by the analysis, design
half the total area, may be used. and details of the roof diaphragm. Figure 3.11.5 dem­
onstrates one example of a diaphragm connection.
5. Precastwalls, other than cladding panels, shall Provision 4. “Column splices and column...”
be connected across horizontal joints by a mini­
mum of two connections per panel. Each con­ Example 3. 11.7 does not show the column to foot­
nection shall have a nominal tensile strength of ing detail. Assume an 18 in. square column is used to
not less than 10 kips. When design forces result support the interior beams. The column base plate is
in no tension at the base, these connections are anchored to the column with Q-V 2 in. diameter de­
permitted to be anchored into an appropriately formed bar anchors and the base plate is anchored to
reinforced slab on grade. the footing with 4 -1 in. diameter A307 anchor bolts.
The nominal tensile strength is:
6. Whereprecast elements form roof or floor dia­
Tn = (200 psi) (18 in.) (18 in.) = 64,800 lbs.
phragms, the connections between the dia­
phragm and those members being laterally Anchor Bolts
supported shall have a nominal tensiie strength
From Fig. 6.15.9, pTn/b o lt = 26.5kips.
not less than 300 pounds per linear foot.
Note: The values in Table 6.15.9 include:
7. To accommodate volume change strains in
supported beams, (temperature and shrink­ <() =0.75.
age) tie connections are typically located at the
top of the member, with elastomeric pads Tn = (4 bolts x 26,500 lbs/bolt)/0.75
employed at the bottom bearing surface. Such
ties can be accomplished by welding, bolting, = 141,000 lb
reinforcing steel in grout joints or bonded top­
Since 141,000 lb > 64,800 lb compliance is
ping, or by doweling.
achieved.

8. Connection, details that rely solely on friction Base Plate


caused by gravity loads shall not be used. Ex­
Tn = 8 bars x 0.20 ir^/bar x 60,000 psi
ceptions may be permitted for heavy modular
unit structures where resistance to overturning = 96,000 lbs.
or sliding has a large factor of safety. Accep­
tance of such systems should be based on the Since 96,000 lb > 64,800 lb compliance is
provisions of ACI 318-95 Sect. 1.4. achieved.

3 -5 0 PCI Design Handbeok/Fifth Edition


provision 5. “Precast waits, othertharr...” are stackedfor theheightof the building and support-
the floor and roof decks. Criteria have been esteb-
Therearetwo shear wall to footing connectionsper
iished for alternate load paths in such buiidingslhree
p a re t Each connection (Figure 3.1 ! . 8) has a tensile
-stories or more in height [7].
capacity-greater than 4 3 ^k ip s .
Large panel wall structures u n d e r three stories,
Since two connections per panelare provided and
shall meet the requirements of Sect. 3. 10.2 . For large
each connection tras a tensile capacity greater-than
panel bearing wall structures three stories o r more-in
10 kips, this provision is satisfied. height; minimum tie force requirements are satisfied
by the use of the following forces, as illustrated in Fig­
provision 6. “Where precast elements...”
ure 3. 10. 1. It is not intended that these forces replace
The connection between the exterior walls and the an analysis of the actual design forces required in the
roof diaphragm has a required structural integrity structure; these forces are not additive to the actual
nominal tensile strength of: design forces.
T, ■=nominal tensilestrength equal to 1500 Ibperft
of floor or roof span. Ties may be encased in the floor
Tu = 8 ft x 300 Ibs/ft = 2400 lb = 2.4 kips
units or in a topping, or may be concentrated at the
wall. Spacing shall not exceed the spacing of bearing
SinGe the required seismic tie force between the
walls. Ties may be positioned in the wails within 2 ft of
roof diaphragm and the wall panels is equal to 6.52
the plane of the floor or roof.
kips, which is greater than the structural integrity re­
T2 = peripheral nominal tensile strength sufficient
quirement of 2.4 kips, satisfaction of the seismic-re­
to develop diaphragm action, but not less than 16,000
quirement provides structural integrity compliance.
lbs., located within the depth of the floor or roof slab
Two connections per panel are provided as shown
and within 4 ft of the edge. Ties may be reinforcing
in Figures 3.1 1.3 and 3.11.4. These connections sat­
steel in. a grout joint or in an edge beam; reinforced
isfy both the seismic requirements and the require­
spandrels or wall anchored to the floor or roof may
ments of this provision.
also be considered.
T3 = nominal tensile strength not less than 1500 lb
Provision 7. ‘T o accommodate volume...” and
per linear foot of wall. Ties shall be spaced not great­
Provision 8. “Connections details that rely...” er than 10 ft on center. They may project from the pre­
cast element or be embedded in grout joints, with suf­
ficient length and cover to develop the specified
These provisions are satisfied by the designed and strength. At end walls, wall reinforcement shall extend
detailed connections shown in Figure 3.1 1.4. Since into the floor, or mechanical anchorage between floor
the inverted tee beam is connected to the roof dia­ and wall shall be provided.
phragm, structural integrity is satisfied. Alternatively, T4 = nominal tensile strength not less than 3000 lb
the inverted tee beam may be positively connected to per linear foot of wall in all bearing walls, with a mini­
the column. A feasible beam to column connection mum of two ties per wall. These ties shall be continu­
would be a doweled connection utilizing a coil insert ous from foundation to top of wall.
in the column top, a coil rod through a vertical sleeve
in the beam web and a coil nut with a plate washer
located in a recess at the top of the beam web.
In conclusion, the structure of Example 3.11.7 with
the clarifications noted in this section, satisfies all of
the structural integrity provisions outlined in Sect.
3.10.2.
3.10.4 Hybrid Structures

The provisions of ACI 318-95 relate to concrete


buildings only. Those connections which interface
3.10.3 Large Panel Bearing Wall Structures precast concrete components with other structural
materials (e.g., masonry walls, steel or wood roofs)
Large panel bearing wall structures are a special
should provide the same load paths and follow the de­
category of precast concrete structures, with respect
sign philosophy described above. Since the precast
to structural integrity. Large panel structures are typi­ concrete supplier rarely has control over such other
cally constructed with precast walls having a horizon­ materials, the Engineer of Record must design and
tal dimension greater than the vertical dimension,
detail the connections to satisfy structural integrity
which is generally the height of one story. The panels
and include them in the contract drawings.

PCI Design Handbook/Rfth Edition 3 -5 1


Figure 3.10.1 Recommended forces in precast G = total compressive-force
_____________ concrete bearing wall buitdmgs -
A. = deflection amplification factor
(SBC-94)

cP —— coefficient for horizontal-force on a


part of the-structure (UBC-94)

C8 = base shear coefficient (SBC-94)

CT — fundamental period coefficient


(SBC-94)

Cw = vertical distribution-factor for lateral


forces (SBC-94)

Co = compressive chord force


= factored compressive force
Cu
D - dead load

De ** length of shear wall in the first story


in the direction parallel to the applied
force (UBC-94)

Ds longest dimension o f a shear wall or


braced frame in the direction parallel
to the applied force (SBC-94)
d dimension of building; distance from
extreme compression fiber to cen­
troid of tension reinforcement
d = bar, stud or bolt diameter
3.11 Earthquake Analysis and Design =
E seismic load

E = end zone width (SBC-94)


3.11.1 Notation
e = eccentricity
a = dimension
f = extreme fiber stress
A = cross-sectional area
FirFn,Fx = lateral forces applied to level i, n, or
Aa = peak acceleration coefficient x, respectively (SBC-94)
(SBC-94)
Fp lateral force on the part of the struc­
Ac = 2Ae [0.2 + (De/hn)2] ture and in the direction under con­
Acv = concrete shear area sideration (UBC-94) (SBC-94)

Ae minimum cross-sectionai shear area Fpx = force on floor diaphragms and col­
in any horizontal plane in the first lectors (SBC-94)
story of a shear wall (UBC-94) = force due to weight of diaphragm and
FPx
A< = cross-sectional area in linear mea­ tributary elements at level x
sure FpU = factored lateral force
As area of non-prestressed reinforce­ = sliding force
Fs
ment

Av coefficient representing effective F, that portion of V considered concen­


peak velocity-related acceleration trated at the top of the structure, level
(SBC-94) n (UBC-94), or in addition to Fn
b = width of panel (SBC-94)

C = coefficient for base shear (UBC-94)


= concrete compressive strength
or performance category (SBC-94) fc

3 -5 2 PCI Design Handbook/Fifth Edition


=s yield strength of non-prestressed re­ S 1,2 ,3,4 = soil factor coefficient {SBC-94)
fy
inforcement (UBC-94)

It = height of member Sf = section modulusnn linear measure

hi.hn.h* = height above base level to level i, n, s = spacing-of items, e.g^jweld clips, etc*
or x, respectively (UBC-94) (SBC-94)
t SZ- thickness
1 occupancy importance factor
T = fundamental period of vibration of the
(UBC-94)(SBC-94)
building in the direction under con­
= moment of inertia sideration (UBC-94); total tensile
1
= force
Tj. occupancy importance for building
par (UBC-94) = approximate fundamental building
Ta
period (SBC-94)
k -= exponent relating to type of construc­
tion and building perbd (SBC-94) Tn = nominal tensile strength

k = effective length factor for compres­ To = tensile chord force


sion members =
Tu factored tensile force
k = distance from back face o f angle to =
V total lateral load or shear at the base
web fillet toe
(UBC-94) (SBC-94); shear force
e = length-of building or member
Vn — nominal shear strength
U length of weld =
V€ shear force between panels
M moment =
V€u factored shear force between panels
Me =r moment about compressive force
Vu factored shear force
M0 s overturning moment
V = unit shear stress
M, = overturning moment =
v 0 ,1 ,2,3 unit shear stresses
M0 = maximum diaphragm bending mo­
Vu = factored shear stress
ment
=
w = total dead load plus applicable por­
Mo.,1 overturning moment
tions of other loads (UBC-94)
Mr = overturning moment resistance (SBC-94)
Mu = factored moment Wp = total weight of a part or portion of a
structure (UBC-94) (SBC-94)
N = force normal to friction plane
= weight of diaphragms and collectors
n = uppermost level in the structure Wpx
and tributary elements at level xplus
(UBC-94) (SBC-94)
allowable portions of live load
Pc nominal tensile strength of concrete (SBC-94)
element inahear cone
W, - factored dead load
— nominal tensile strength of steel ele­
Ps
Wi, Wx that portion of W which is located at
ment in shear cone
or is assigned to level i or x, respec­
Pu = factored axial force tively (SBC-94)
Ro>RliR2 = reactions W i ,W2 W3 = diaphragm forces per unit length for
Rs = resistance to sliding areas 1,2,3 respectively.

R,RW seismic coefficient relating to type of X = level which is under design consider­
construction (UBC-94) ation (SBC-94)

r = radius of gyration of cross-secfion of z = coefficient dependent upon the seis­


a compression mic zone (UBC-94);

S = section modulus Z = plastic section modulus

S = site coefficient (SBC-94)(UBC-94) = section modulus in linear measure

PCI Design Handbook/Fifth Edition 3 -5 3


M = shear-friction coefficient-* The-current philosophy for the design of earth­
quake resistant structures permits minordamage for
Ms — static coefficient of friction
moderate-earthquakes, ancfcaccepls-majpr damage
Pn = reinforcement ratio fo r severe earthquakes, provided that complete cot-
= capacity reduction' factor (ACI lapse is prevented The designjdetails often require
$
318-95) large, inelastic, deformations to-occur in order to ab­
sorb the inertial forces. This is achieved by providing
member and-connection ductility. While this ductility
3.11.2 General can prevent total collapse, the resultant distortions,
may lead to signtficantdamage to mechanical, electri­
cal, and architectural elements Seismic damage can
Earthquakes generate horizontal and vertical
be minimized by setting limitations on structural
ground movement. When the earthquake passes be­
deflections, such as interstory drift.
neath a structure, the foundation will tend to move
To limit damage of non-structural elements, three
with the ground, while the superstructure will tend to
options are open to the designer. First, the elements
remain in its original position. The lag between
could be uncoupled from the structural system, so
foundation and superstructure movement will cause
that these elements are not forced to undergo as
distortions and develop forces in the structure. As the
much deformation as the supporting structure. Note,
ground moves, changing distortions and forces are
however, that these elements must maintain their own
produced throughout the height of the structure.
structural integrity. Second, the deflections of the
Precast concrete structures often utilize jointed
supports could be reduced in order to minimize de­
construction, and individual elements are connected
formation of the non-structural elements. This is typi­
at their joints using a variety of methods. These con­
cally attained through the use of shear walls. Third,
nections may include embedded steel shapes such
the connection between individual elements and sup­
as flat plates and angles, with headed stud or reinforc­
port elements could be designed to sustain large de­
ing bar anchorage; the steel embedments are field
formations and rotations without failure. Generally,
bolted or welded. Some applications have also
the first or third approach is adopted for non-structural
employed match casting of the precast members with
architectural wall panels (see Sects. 3.11.4 and
“dry” connections (see Sect. 9.9). Another type of
3.11.12).
connection, referred to as a “wet” connection, con­
Buildings may be designed as either flexible or
sists of reinforcing bars protruding from the precast
stiff. Flexible structures will develop large deflections
members, with the bars mechanically coupled or
and small inertial forces; conversely, stiff structures
spliced. Cast-in-place concrete or non-shrink grout at
will develop large inertial forces but small deflections.
the joint completes this connection. Either dry or wet
Either type may be designed to safely prevent total
connections are applicable for both moment-resisting
collapse. However, experience demonstrates that a
frame and shear wall systems.
stiff structure, such as a shear wall building properly
It is imperative that lateral load paths and resisting
designed to account for the large inertial forces, will
elements are clearly defined. Where significant move­
incur significantly less damage to architectural, me­
ment between adjacent elements is anticipated, duc­
chanical, and electrical elements.
tile connections must be provided. One advantage of
Buildings utilizing shear walls as the lateral force
jointed construction is the ease of defining load paths
resisting system provides a safe, serviceable and eco­
through the connections. Connections can be de­
nomical solution for wind and earthquake loads.
signed for specific directional resistance while main­
Shear walls are the most common lateral force resist­
taining flexibility on one or more other directions. It is
ing system in the precast prestressed concrete in­
important in a precast structure to develop connec­
dustry. The excellent performance of shear wall build­
tions that tie all precast members into the lateral load
ings throughout the world which have been subjected
resisting system.
to earthquakes supports this method. In many cases
Connections in moment-resisting frames (see
in previous earthquakes in Chile and Japan, contin­
Sect.3.8) rely upon ductile means of connecting pre­
ued use of the structure has been allowed with full
cast beams to their supporting columns, in order to
functions after the earthquake. The selection and de­
provide ample energy absorption through many
sign has followed principles used for monolithic cast-
cycles of loading without serious degradation. Re­
in-place structures, with modifications made as ap­
cent government sponsored research (PRESSS and
propriate for the jointed nature of a precast concrete
ATLSS programs) illustrates connection detailing that
structural system. Design methods used to achieve
has produced moment frame performance superior to
successful performance of precast shear wall struc-
similar cast-in-place joints.

3 -5 4 PCI Design Handbook/Fifth Edition


tares have been largely left to the ingenuity and judg­ signer can determine the probala^ mepwree'of ItTe
ment of the design engineer. Observations of perfor­ structure 1o a n imposed earthquake UBC-94 re­
mance structures in earthquakes show that where quires a-dynamic analysis for structures which have
^adequate strength and stiffness were providedio lim it highly irregular shapes or framingsystems and allows
interstory drift to about- 2%, the resulting-displaee- it for other structures. However, most buildings have
ments and damage werewitbin acceptable levels. In structural systemsand shapes which are more-or less
regions of lower and moderate seismicity, dry con­ regular, and many designers use theequivalent static
nections with small grout joints arergenerallyused. In load method for -these structures. See UBC-94
Sect.1627.
regions of high seismicity, connections to the founda­
In its simplest form, UBC-94 requires that a total
tion,, and connections between precast walls, general­
base shear, V, be applied to the building in any hori­
ly use details which emulate cast-in-place behavior or
zontal direction where
include post-tensroning.
In the few cases where shear wall buildings have
V = (ZICW)/Rw (Eq. 3.11.1)
shown poor performance, the problems were gener­
ally related to details that were insufficiently ductile in which:
and thus resulted in brittle local failure (such as im­
Z Is based on the expected earthquake intensity
proper anchoring of embedments). Incomplete load
IIs based on the type of occupancy anticipated
paths such as improper diaphragm details were also
problems. Inadequate diaphragm behavior can be "Rw Is based on the type of framing
C Is based on the flexibility of the structure and
caused by improper reinforcing for shear and tension
within the diaphragm, and insufficient ties between the site soil condition, and
the diaphragm and the shear walls. W Is the dead load of the structure, plus portions
of the live load for some occupancies.
Since ground motion is random in direction, a
structure which is shaped so as to be equally resistant
in any direction is the optimal solution. Thus, closed This total shear is divided among the story levels,
sections (boxes or tubes) have demonstrated mark­ with the upper stories being assigned more of the hor­
edly better behavior when compared to open sections izontal load than the lower stories. This is the method
because (1) closed sections provide a higher degree of equivalent static loads.
of torsional resistance and (2) the higher axial Also, UBC-94 requires that parts of the structure
stresses and resultant deformations in the exterior such as roofs, floors, walls, and their connections be
columns provide significant energy absorption. designed locally for either the distributed base shear
In structures where openness is important, such as or the lateral forces determined by the expression:
parking structures, shear walls with large openings
have been successfully used. Attention must be paid
to local flexure and shear in those elements which sur­ Fp = ZlpCpWp (Eq. 3.11.2)
round the openings.
Flexural load tests of prestressed concrete mem­
bers have consistently shown that large deflections in which the subscript “p ” denotes the effects of the
occur as the design strength is approached. Because building part. For certain parts of buildings, Fp re­
of prestressing, the transition from linear to nonlinear quirement is sometimes more severe than the distrib­
member response is gradual and smooth. Cyclic load uted base shear.
test have shown that prestressed concrete beams can The occupancy importance factor, I, has the effect
undergo several cycles o f intense load reversal and of making structures that would be essential during an
still maintain their design strength. earthquake disaster (e.g., hospitals, fire stations,
etc.), or those that could house large numbers of
people, less likely to be severely damaged.
H ie values C, Cp and Rwmay be determined in ac­
3.11.3 Building Code Requirements
cordance with UBC-94, Sects. 1624 -1633. The value
All major building codes include seismic provi­ of C need not exceed 2.75, and may be used for any
sions. In this section, examplesare presented using structure without regard to soil type or structure peri­
the Uniform Building Code (UBC) and the Standard od. The value of Rw is 6 for concrete bearing wall sys­
Building Code (SBC). The following discussion is tems. For non load bearing shear walls, R* is 8.
based on the provisions of UBC-94. There have been many recent changes made to
The response o f a structure to the ground motion major documents that contain seismic design provi­
of an earthquake depends on the structural system sions. (See Ref. 19 through 23). These changes are
with its damping characteristics, and on the distribu­ based on a significant amount of seismic research
tion of its mass. With mathematical Idealization, a de­

PCI Design Handbook/Fifth Edition 3 -5 5


that has beerrcompleted-as-welJ-as observations from
the Northridge earthquake o t 1-994. 4. Walls will be subjected to lateral loads perpen­
The _new building^codes -wili contain new or up­ dicular tothe plane-of the wal l (wind, seismic) in
dated information-regarding the many topics, a few of combination with loads in the plane
which are; 5. Desigo should consider the eccentricities pro­
• Recognition of jointed .panel construction as an duced by story_drrft. These are combined with-
alternative to emulation of monolithic construc­ the eccentricities due to manufacturing and
tion. erection tolerances. Drift is defined as the rela­
tive movement of one story with respect to the
• Achieving ductility by using “strong” connec­ stories immediately above or below the level
tions that remain elastic while non-linear action under consideration. Between points of con­
(plastic hinging) occurs in the member away nection, non-load beetring panels should be
from the connection. separated from the building frame to avoidcon-
tact under seismic action. In the immediate
• Drift limits-
area of connections, panels will tend to distort
• Deformation compatibility of structural elements the same amount as the supporting frame. In­
and attached non-structural elements. terned stresses induced due to a statically inde­
terminate support system should be checked.
• Additional soil type classifications added.
Even in a statically determinate panel there may
• Design considerations of buildings sites located be some built-in restraint at the connections, so
near seismic faults. that some allowance for internal stresses
should be considered.
• Design considerations of structures possessing
redundancy. 6. Under severe earthquake, large deflections
may be anticipated. The investigation of individ­
There is a trend to unify seismic design practice. A ual walls and of the entire-structure should in­
new model building code, the International Building clude the consideration of deflection (P-A ef­
Code, is expected to replace the three existing model fect).
building codes early in the next century.
The revisions to the seismic design provisions in 7. To account for accidental torsion, the mass at
Refs. 19 through 23 are too lengthy and became avail­ each level shall be considered displaced from
able too late for inclusion in this edition of the Hand­ the calculated center of mass an amount equal
book. These changes will be included in the Sixth Edi­ to 5 percent of the building dimension perpen­
tion of the PCI Design Handbook. dicular to the direction of force.

8. Seismic induced forces are reversible. This is


3.11.4 Design Guidelines for Wall Panels particularly important at joints.

This section, Sects. 3.1 1.5 and 3.11.6 deal primari­ 9. The best energy absorbing members are those
ly with totally precast concrete structures. In addition, with high moment-rotation capabilities. The en­
architectural wall panels, whether connected to pre­ ergy absorbing capacity of a flexural member is
cast concrete or other materials, require special con­ measured by the area under the moment-rota­
siderations; tion curve. Correctly reinforced, concrete can
exhibit high ductility. Refer to ACI 318-95,
1. Exterior walls perforated for windows will act Chapter 21, for proper methods of reinforcing to
somewhere between a solid wall and a flexible achieve ductility.
frame. For tall buildings, this will resultin a non­
linear distribution of forces, due to shear lag 10. Joints represent discontinuities, and may be
(see Sect. 3.7.7).. When similar to a flexible the location of stress concentrations. Reinforce­
frame, they must be designed as moment-re­ ment or mechanical anchorage must be pro­
sisting frames to resist seismic loads. vided through the joint to fully transmit the hori­
zontal shear and flexure developed during
2. Portions of walls with opening can be subjected seismic activity. See Chapter 6 for a discussion
to significant axial loads. These portions may on connections. In zones of high seismicity,
require reinforcement with closely spaced ties, cast-in-place reinforced concrete in combina­
in accordance with ACI 318-95, Chapter 21. tion with precast concrete has proved success­
3. Connected walls may act as coupled walls (see ful in economically transferring seismic forces
Sect 3.7.5). (see Sect. 7.3).

3 -5 6 PCI Design Handbook/Fifth Edition


tt. Where possible, make panel connections to 3. Determination o f vertieai and lateral loads
the supporting strueture^statically determinate, a. Determine the vertical gravity loads which
in order to perm ita more accurate determina­ -are applicable to each of the shear waiis.
tion of force distribution. b. Use the applicable seismic design eriteria
to determine-the magnitudeoMatera .1load
12. Choose the num ber and location of connec-
at each floor, and compare with wind load­
tionsrto permit movements tn the plane o fih e
ing? Choose the critical condition for de­
panel to accommodate story demand volume
sign.
changes.
4. Preliminary load analysis
13. Locate connections to minimize torsional m o ­
a. Determine the overturni ng moment, the lat­
ments on supporting spandrel beams, particu­
eral shear and the axiat load at the base of
larly if the beams are structural steel.
each o f the shear walls.
14. Provide separation between the panel and the
5. Selection o f shear walls
building frame to prevent contact during an
a. Review the preliminary choice of shear wall
earthquake.
size and location.
15. For jointed construction, force the weakest link b. Modify the number, location, and dimen­
of the connection to occur in its most ductile sions of shear walls as necessary to satisfy
component (i.e., connecting plate). the requirements at the base of each. It is
economically preferable that foundations
not be subject to uplift.
3.11.5 Design Guidelines for Shear WalT
Structures 6. Final load analysis
a. Based on the final location and dimensions
The following are suggested guidelines for struc­
of shear walls, perform the final lateral load
tures that have shear walls as the primary lateral load
and vertical load analysis for each of the
resisting element:
shear walls. Consider shear stiffness as
1. Evaluation of building function and applicable well as flexural stiffness when distributing
precast frame lateral loads to the shear walls.
a. In a warehouse type structure, it is common
7. Final shear wall design
to include the exterior walls as part of the
a. Design shear wall reinforcement and the
lateral load resisting system (See Sect.
connections to the associated diaphragms.
3.11.6).
b. Where there is insufficient length of shear
b. In parking structures, shear walls can be lo­
wall available to accommodate the neces­
cated at stair and elevator towers, at the pe­
sary number of shear connectors, consider
rimeter or ramped bays, at selected loca­
using an element in the plane of the dia­
tions on the perimeter of the structure, or
phragm (drag strut) as an extension of the
any combination of the above locations.
shear wall to pick up additional connectors
2. Preliminary development of shear wall system to the diaphragm.
a. Provide at least 3 non-colinear walls to en­ c. Consider the additional requirements nec­
sure torsional as welt as direct lateral sup­ essary to satisfy the structural integrity pro­
port. visions of the code (see Sect. 3.10).
b. Overturning will often be the governing cri­
8. Diaphragm design
teria. Thus, the first choice is to use shear
a. Design the diaphragms to respond elasti­
walls which also function as bearing walls.
cally to applied lateral loads in order to pre­
c. Arrange shear walls so that they minimize
vent formation of plastic regions in any dia­
restraint due to volumetric changes.
phragm. To achieve this, the diaphragm
d. Consider whether the shear walls could be
design forces prescribed by the codes
individual full height walls ^vertical joints
should be increased by (%) Rw in order to
only).
determine the required factored design
e. Consider the practicality of shipping and
loads.
erection when selecting the size of panels.
b. Design the diaphragms as beams, provide
f. Balance the design requirements of the
the necessary tensile reinforcement for
shear walls with the design requirements o f
each chord, and choose shear connectors
the associated diaphragms.
using design procedures of Chapter 6, or

PCI Design Handbook/Rfth Edition 3 -5 7


shear reinforcement using shear friction 1. One groupof connectionsrthat transmits forces
methocfe. -between elements within a- horeon(Biwdta-;
c, Consider the additional-requirements nec­ phragm or a sfoearwalJ, and
essary to satisfy the structure integrity pro­
2. Another group of connections that transmits
visions of the code (see Sect. 3.t0>.
forces between a horizontal diaphragm and a
shear wall.
3.11.6 Concept of Box-Type Shear Wall
In seismic design, forces must be positively trans­
Buildings
mitted. Load paths must be as direct as possible. An­
A box-type building consists of roof and floor dia­ chors should be attached to o r hooked around rein­
phragms, and shear walls. When these components forcing bars o r otherwise terminated so as to
are appropriately connected they form a structure effectively transfer forces to the bars. Reinforcement
which is very resistant to lateral loads. in the vicinity of the anchors should be designed to
Since an earthquake is a ground motion reacting distribute the forces so as to preclude local failure.
with the inertia of the building and its parts, the equiva­ Concrete dimensions must be ample, so that the
lent static loads are applied a t the centroids of the hardware of the connection is confined, and the con­
parts. The internal forces that link the applied loads nection thus can transmit accidental forces that are
and the ground reaction follow the strffest paths con­ normal to the usual plane of the load path. Finally, a
sistent with equilibrium and compatibility of deflec­ connection should be such that, if it were to yield, it
tion. With box-type buildings of moderate height-to- will do so in a ductile manner, i.e. without loss of toad
width ratio, the stiffnesses o f diaphragms and walls in carrying capacity when the concrete cracks.
their own planes greatly exceed other resistances.
The load paths are then along diaphragms and walls
rather than through moment-resisting frames. 3.11.7 Example—1-Story Building

General
By taking advantage of walls already present, one-
story buildings usually can be designed to resist later­
al loads (wind or earthquake) by shear wall and dia­
phragm action. If a shear wall and diaphragm
concept is feasible, it is generally the most economi­
cal concept. This section of the Handbook is intended
to assist the designer with the shear wall/diaphragm
concept for precast, prestressed concrete buildings.
To show a fairly complete design, the simple one-
story example building in Figure 3.11.1 will be illus­
trated. It is 128 ft x 160 ft in. plan, and has 16-ft clear
height inside. It is entirely precast above the founda­
In multi-story, box-type buildings, the equivalent tion, using 16-in. double tees for the walls and 24-in.
static loads find resistances in the several diaphragms double tees for the roof. The double tees are 8 ft wide,
and walls, and downward to the footings. The design­ with stems 4 ft on centers. The flanges on the roof
er should try to arrange the path of resistance to be tees are 2 in. thick, and on the wall tees, 4 in. thick.
direct. Double tee concrete strength, fc = 6000 psi. The
A diaphragm made up of precast elements re­ weight of roofing and mechanical equipment is 10 psf.
quires that it be strong enough in shear and moment. Because all loads must funnel through the connec­
When walls have numerous openings, the designer tions, gravity and lateral loads must be considered to­
must judge if the wall should be considered a shear gether. Thus, this example shows both gravity and
wall or a moment-resisting frame. lateral load connections. The example emphasizes
A box-type structure may have a large number of the concepts o f free body diagrams and load paths.
precast concrete elements that are assembled into
walls, floors, roof, and occasionally frames. Proper Load Analysis
connections between the many pieces create the dia­ Earthquakes impose lateral and vertical ground
phragms and shear walls, and the connections be­ motions upon a structure. The structure responds to
tween these, in turn, create the box-type structure. In these motions with its own independent deflections.
the seismic design of a box-type structure, there are The difference between the ground motion and the
two fundamental and different requirements of the two horizontal deflection of the structure causes deforma­
tion and stresses in structural components. How-
groups of connections:

3 -5 8 PCI Design Handbook/Rfth Edition


ever, most designers are used to thinking of siressas Calculate C T in north-south direction:
-caused by lead rather than, as caused by-deflection.
Consequently, a ir the common methods of design There_are-2 shear walls, each 128 ft long and 22 ft
use a set of static lateral loads intended to be: equiva­ high (to roof) and 4 in. thick. Thus,
lent to (i.e. produce thesame stresses as)-the real, dy­ Ae = 128(0.33)- = 42.24 r
namic loads caused by detection. One such method
jsotsed in UBC-94. The example building is analyzed D e/hn = 128/22 = 5.82 > 0.9; use 0.9 (based
here for N-S. earthquake only. In a real design situa­ on UBC limitations)
tion, it would also have to be analyzed for E-W earth­
quake. Ac = 2(42.24) (0.2 + 0.92) = 8 5 .3 2 #
The example building resists lateral load by dia­
phragm and shear wall action. Inertial loads (mass x CT = 0. 1/ ^85,32 = 0.011 < 0.02;
acceleration) are delivered to the roof diaphragm. The use 0.02
diaphragm acts like a plate girder laid flat, spanning
between the shear walls. The diaphragm may be tak­ T = 0.02 (22)3/4 = 0.20 seconds
en as the interconnected flanges of the precast roof
elements. In determining the equivalent static loads C = 1.25(1.2)/(G.2Q)2/3
on this diaphragm, the mass tributary to the dia­ = 4.4 > 2.75; use 2.75
phragm must be determined. This is done in terms of
dead weight, W, as follows: The coefficient used in design is thus:
ZIC/RW = 0.30(1) (2.75)/6 = 0.14
N and S walls:

half ht + parapet = 13.5 ft Shear on the diaphragm due to earthquake is:

total length = (2) (160) = 320 ft V = Fp = (ZIC/Rw)W = 0.14(1559) = 218 kips

weight = 13.5(320) (0.067) = 289 kips In comparison, the shear caused by a 20 psf wind
load is:
Roof (including 10 psf dead load):
V = 13.5(160)(0.020) = 43.2 kips < 218 kips
weight = 128(160) (0.062) = 1270 kips
Thus the building design is governed by earth­
Total W = 1559 kips
quake.
The equivalent lateral load V is computed by multi­ A word of caution is in order. The base shear due
plying W by an acceleration. The acceleration is de­ to earthquake as calculated above is a “service” load.
termined from ZIC/RW. The Z-factor, denoting geo­ Accelerations in real earthquakes may be many times
graphical zones of equal probability of serious the ZIC/RWshown above. This will cause elements of
earthquake, is here taken as Zone 3 value of 0.30. The the structure to be strained to first yield point and be­
occupancy importance factor, I, is assumed as 1.0 yond in a severe earthquake. The structure must have
and the Rwfactor, used to indicate the performance of deformation capability to absorb overloads of short
different framing systems have shown in actual earth­ duration without failure.
quakes, is taken as 6. To guard against displacement of mass from actu­
al location UBC-94 requires that a minimum 5% ec­
The value o f C is calculated as follows: centricity be assumed with respect to the center of
mass as shown in Figure 3.1 1.2. With this in mind,
q = 1- ?.5S < 2 75 the forces internal to the roof diaphragm are:
J 2/3 -

Max. shear reaction:


where:
R0 = (88/160)V = 0.55(218) = 120 kips
T = Cr(hn)3/4
Max. shear intensity:
; a c > o.o 2 o v 0 = 120/128 = 0.94 klf

Ac = 2 A e [0.2 + (De/ h nf ] Max. bending moment:


M0 = V €/8 = 218(160/8) = 4360 kip-ft
Assume a stiff soil of depth > 200 ft
Max. chord forces:
S = 1.2
Co = T0 = Mo/d = 4360/128 = 34.1 kips

PCI Design Handbook/Rfth Edition 3 -5 9


The shearforces are analogous to those in the web The sliding force is resisted by friction at the bot­
of a plate girder. The chord forces are analogous to tom of the wall footing. Assume a granular soil, the
those in the flanges of a plate girder. coefficient of sliding friction is about 0.6.
Considering the roof as a free body, Figure 3.11.2
shows that equilibrium is maintained by the reactions Rs = (igN = 0.6(400) = 240 kips
from the tops of the shear walls. Figure 3.11.2 shows
that the wall as afreebody can be in equilibrium only if
sufficient sliding resistance and overturning resist­ Figure 3.11.2 Forces acting on roof and waits
ance are provided. The forces acting which must be
resisted by the shear wall are:

Sliding force:
Ri = R 0 +(ZI C/FUWwa,,
Rt = 120 + (0.14) (128) (24.5) (0.067) = 149
kips

Overturning moment:
M-i = R0h + (Vwall)(h/2) = 120(22)- +
(29X24.5/2) = 2995 kip-ft

The weight of the end wall, tributary roof, floor,


backfill, footing, etc., is about N = 400 kips. The avail­
able resistance to overturning, then, is:

Mr = N(d/2> = 400(128/2) = 25,600 kip-ft

3 -6 0 PCI Design Handbook/Fifth Edition


The-factors of safety (load factors) for overtarning sr- = 4>Vn/vu = 23.7/2.25 = 10.5 ft
and sliding are seen to be sufficient:
Using the ratio of distances from the GeRter of the
= 25,600/2995 =~ 8.55
roof, the shear between the first and second double
Rs/Fs =-240/149 = 1-61 tee and the corresponding spacing between cHpSy is:
Vu = (72/80)(2.25) = 2.03 klf
The d e s ig n s must be carefutto followthe loads ail
the way down into the ground. This isthe “load-path” , s = 237/2.03 = 11.7 ft, but use maximum
concept. spacing of 10 ft

Strength Analysis-Roof Ten feet is a reasonable maximum spacing. How­


In this example, strengths of concrete components ever, in an earthquake, the double tee next to the side
are analyzed using the load factors of ACI318-95, and wall is subject to vertical bouncing. This could de­
strength of structural steel parts by AISC-LRFD stroy the essential connection of diaphragm to shear
methods. Reinforcing bare are ASTM A 615, Grade wall, unless the connection is strengthened sufficient­
60. (See Chapter 6 for guides in welding reinforcing ly to yield the double tee flange as a cantilever in
bars.) To maintain elastic behavior, a load factor of bending where it joins the first interior stem. If stan­
(2/ 5)Rw is used. dard weld clips are placed at 4 ft on centers (2 per wall
panel), they will easily force uniform yield in the
Load Factor = (2/5)Rw = (2/5) (6) = 2.4 flange. Hence, the clips are spaced:

Following the load path, the diaphragm is first ana­ s = 10 ft on centers typically, and
lyzed for shear. The applied design shear in the s = 4 ft on centers at side waits
double tee flanges is: The double tee flanges must also be connected to
Vu = 2.4v0 = 2.4(120/128) = 2.25 klf the north and south walls. If the chord forces are re­
sisted in the walls, the connections must transfer the
The design shear strength of the reinforced con­ “VQ/lb” type web shears to the chords. This is analo­
crete in the double tee flanges, using a cpfactor of 0.6 gous to the connection between web and flange of a
per UBC-94, and using a minimum p n of 0.0025, is: plate girder. This same connection must also function
as a tension tie, by holding the wall panels onto the
< K = 4>(Acv)(2/fr + pnfy)
roof against wind and earthquake, and by holding the
= 0.6(12) (2) [2/6000 + 0.0025(60,000)] building together against shrinkage and related
forces.
<t>vn= 4.39 klf > 2.25
The connection which holds the wall panel to the
This is greater than required, therefore, satisfactory. roof must be designed for an earthquake force, Fp,
The double tee flanges must be connected at their which is obtained by multiplying the tributary weight
edges to each other and to the side shear walls. This of this part of the building, Wp, by an acceleration,
is analogous to providing shear strength along verti­ ZIPCP. Z and lp are the same zone and occupancy
cal joints in the web of a plate girder, and is done by factors as before. Cp is a factor used to correlate for
weld clips as shown in Figure 3.11.3(A), (B) and (C). past good and bad experience in earthquakes. The
This clip is analyzed by truss analogy, illustrated in UBC-94 requires a Cp of 0.75 for connections of wall
igure 3.1 1.3(D). The design forces in the bars, and panels, but also requires that the fasteners, such as
their resultant along the double tee edge, are: bolts, inserts, welds, dowels, etc., be designed for 4
times the load determined from the above formula.
Cu = Tu = (pAsfy = 0.9(0.31 H60) Thus, for most parts of the connection, design accel­
eration is:
= 16.7 kips
cf>Vn = (Cu + Tu) cos 45° ZIpCp = 0.30(1.0) (0.75) (4) = 0.90
= (16.7+16.7) (0.707)
Tributary weight of an 8-ft wide wall panel is:
= 23.7 kips

Wp (half ht + parapet) = [ y + 2.5j(8)(0.O67)


Connection hardware and welds must be de­
signed to resist this force. The development of this = 7.24 kips
force into the flange of the double tee by appropriate The corresponding lateral earthquake force is:
anchorage must also be verified.
At the junction with the side walls, the spacing be­ Fp = Z lpCpWp = 0.90(7.24) = 6.52 kips
tween clips (as limited by horizontal or diaphragm
shear) must be no more than: = 3.26 kips per double tee stem

PCI Design Handbook/Fifth Edition 3 -6 1


f ig u r e 3.11.3 Connectionsbetween flanges of Because this is-nearly equivalent to a wind forc&of
ro o f a n d doublefees andfrom 60 psf, wintddees not control. The connection most
ro o f diaphragm to wall iransmitdiapbragrnshear and at the same time-al low
for the Jive load-end rotation of the simple span roof
tees. This is-done by welding the roof and wall tees-
together a t the top erf the rooftee, but not at the bear­
ing (Figure 3.11,4).

In the case iliustrated, bearing pads are used; the


deformation of the pads will minimize the horizontal
restraint at the bearing, and the connection design will
be governed by the earthquake force. The bar an­
chorage is sized thus:

Tu = (2.4)FP = 2.4(3.26) = 7.82 kips


(A) PLAN, TYPICAL
As = Vcjrfy = 7.82/[0.9(60)] = 0.14 in2

Use 2 - # 3 bars (As = 0.22 in2)

The chord reinforcement will be placed in the roof


members and is sized for tension as fotlows:

Tu = C U = 2.4T0 = 2.4(34.1) = 81.8 kip?-

As = Tu/cj)fy = 81.8/10.9(60)] = 1.51 in2

Use 4 - #6 bars (As = 1.76 in2)

These bars are located as shown in Figure 3.1 1.5.


The cross-sectional area of the plates and the welds
should be sufficient to ensure that yielding in the bars
occurs first.

Figure 3.11.4 Connections between roof


double tees at side walls and
ledger beam

4-Vn

(D> TRUSS ANALOGY

3 -6 2 PCI Design Handbook/Rfth Edition


can be-used ifvoJume-restraint is-of concern. At the
exterior panels', the edge shear ^ from an exterior
panel will be applied at one edge only. Becauseten-
sion and compression base connections-are not lo-
cated-at the panel edges, equilibrium may have to be
-satisfied with tension and compression connections
to the foundation.
At the tension side exterior panel, equilibrium can
be determined by summing moments about the com­
pression force:

T = [V(h) - W(b/2 - a) - Vn(a)]/d


= V ^b - a)/d
C = t + w - V i

At the compression side exterior panel, equilibrium


can also be determined by summing moments about
the compression force:

T = [V(h) - W(b/2 - a) - VT(b - a)]/d


= V^aVd
The diaphragm must be continuous in shear over C = T + W + Vi
the centerline ledger beam (see Figure 3.11.4B). For
the design of this connection, refer to Sect. 3.6 and For this example, stemmed panels are used for the
Figure 3.6.1. To provide ductility, the weld should be walls. Connections are most conveniently located at
designed for 1.33 times the yield strength of the con­ the stems, so the pertinent dimensions are:
nection, and the headed studs made long enough to b = 8 ft
preclude a premature shear cone failure. Deformed a = 2 ft
bar anchors may be substituted for the headed studs.
d = 4 ft
This completes the strength analysis of the dia­
phragm for N-S earthquake. For E-W earthquake, a
Working with factored loads and based on inelastic
similar analysis is required.
behavior:

Strength Analysis-Walls Vu = 1.4(0.94) (8) + 1.4(0.14) (8) (24.5) (0.067)


Following the load path, the shear walls are ana­ = 13.1 kips per panel
lyzed next. For simplicity, it is assumed the walls Wu = 0.9(8)(24.5)(0.067) = 11.8 kips
have no openings. Thus, there are interior and exteri­
or (corner) wall panels, as shown in Figure 3.11.6.
(The load factor, 1.4, is derived from Sects. 9.2.2
Connections are made across the vertical panel joints
and 9.2.3 of ACI318-95. From Eq. 9-2, U = 0.75(1.7 x
to take advantage of the fact that compensating
1.1E) = 1.4E, and from Eq. 9-3, U = 1.3 x 1.1E * 1.4E.
forces are generated in the panels. Considering an
Also, UBC-94 stipulates a load factor of 1.4.)
interior panel:

V(h) = Vi(b) + W(b/2 - a) For the typical interior panel:


V1u = [13.1(22)- 11.8(8/2 -2 )]/8
V, = [V (h )-W (b / 2 - a ) ]/b
= 33.1 kips
Cu = 11.8 kips
For vertical equilibrium:
Vu = 13.1 kips
C = W

Since this force system can exist for all interior pan­
els, edge shears will balance to zero, when all panels Weld clips similar to Figure 3.1 1.3 will be used in
have the same dimensions and weight. The only re- this example at the vertical joints. The number re­
quirement for the connections is a transfer of vertical quired is 33.1 kips/23.6 kips per connection = 1.4;
shear. Therefore, longitudinally sliding connections use 2.

PCI Design Handbook/Fifth-Edition 3 -6 3


Figure 3.11.6 Forces acting on wall panels Connector-plate thickness required to ensure yielding
of the 3 - # 5 bars, As = 0.93 in2.

1 = 1,33(60)(0.93)/[6(0.9)(36)] = 0.38 in.

Therefore, use connector plate 6 in. x 1/fnn. x 6 in., with


6 in. o f 7/ie in. fillet weld-to foundation plate.

4>Tnweid = 6(9.74) = 58.4 kips > 49,7 kips

Determine foundation plate thickness:

(MJp, = ^ >in
= 4 9 .7 (|) = 49.7 kip-ir

where:
s = spacing of anchors

Zrqd = 49.3/[(0.9) (36)] = 1.52 in3

(A) EXTERIOR (B) INTERIOR (C) EXTERIOR


TENSION SIDE COMPRES­ 4(1.52)
trq d — 0.872 in.
SION SIDE

Use plate 7/s in. x 6 in. x 8 in., with 4 - # 5 bars with 90°
The shear transferred to the foundation might be bend.
accomplished with weld plates, dowels, splice
sleeves, or similar methods. Zpvd = (1/4)(0.875)2(8) = 1.53 in 3 > 1.52

The tension side exterior panel will require a tie­


Details for wall panel flange connections and foot­
down connection in this example.
ing connections are shown in Figures 3.11.7 and
Tu = 33.1 (8 - 2)/4 = 49.7 kips 3.11.8.
Cu = 49.7 + 11.8-33.1 = 28.4 kips Check the wall panel reinforcement to determine if
Vu = 13.1 kips two curtains of steel are required, (ACI 318-95, Sect.
The compression side exterior panel will also require
21.6.2.2):
a tie-down connection.
2Acv/fT = 2(12)(4) 76000 = 7.44 klf > 1.64 klf
Tu = 33.1 (2)/4 = 16.6 kips
Cu = 16.6 + 11.8 + 33.1 = 61.5 kips
Vu = 10.2 kips This is much in excess of the actual factored shear.
Two curtains are not required.
The controlling tie-down force is T u = 49.7 kips

The reinforcement required to resist Tu is determined Figure 3.11.7 Wall double tee connections
as follows:

A - ly . = 49.7
^ <t>fy 0.90(60)

= 0.92 in2

use 3 - #5 bars.

Weld of # 5 bar to plate, to ensure yielding of bar


(Table 6.15.3):
£w = 1.33(2.5) = 3.33 in. (use 4 in.)

Connector plate area required:


49.7/[0.9(36)] = 1.53 in2
use 6 in. by Vi in. plate, Api = 3.0 in2.

3 -6 4 PCI Design Handbook/Fifth Edition


Cheek to see if a boundary member is required- Weights
(AC1 318-95, Sect. 2 1 M -1 ): The unit dead loads are:

Gross section, neglecting legs: Roof: JOOpsf

A = (4/12)(128) = 42.67 ft?: Floors: 110 psf


Walls: 90 psf max., 67 psf average
S = (4/12) (1282/6) = 910.2 fta
The dead load assigned to each level of the build­
Roof lateral load = t20 kips ing is the weight ofthe roof or floor plus the walls from
mid-story to mid-story (only walls for first level).
Wall lateral load = 29 kips
This gives values of wx as listed in Table 3.11.1
(Column 3).
p u = 1.4(wp)(16) = 1.4(13.13) (16) = 294 kips

Mu = 1.4[(120)(22) + 29(24.5/2)]= 4193 kip-ft Equivalent Static Loads


The building is located in a seismic Zone 2A:
f = PJA + MJS = 294/42.67 + 4193/910.2
Z = 0 .1 5
= 11.5 ksf, or 80 psi

The structural system is bearing walls:


0.2fc = 1200 psi, > 80 psi
Rw = 6
Thus, boundary elements are not required.

The site coefficient is (say):


3.11.8 Example— 4-Story Building
S = 1.20
General
The following is an example analysis of a four-story The fundamental period is approximately:
building in which the structural system resisting lateral
T = Cr(hn)3/4 = 0.02(50)3M = 0.376 sec.
forces is of the box type, that is, floors and roof are
horizontal diaphragms, and exterior walls are shear W = 3823 kips, as shown in Table 3.11.1
walls. The building is rectangular in plan, and dimen­ C = 1.25S/T2/3 = (1.25) (1.20)/0.3762/3
sions and layout are shown in Figures 3.11.9 and = 2.88 > 2.75
3.11.10. Floors and roofs are made up of 8 ft wide
precast, prestressed concrete double tees, which are The base shear is then:
supported by exterior bearing walls and a central inte­ V = ZICW/Rw
rior frame of precast, reinforced concrete beams and
columns. There are smaller frames at the two eleva­ = 0.15(1.0)(2.75)(3823)/6
tor-stairway shafts, one at each end of the building. = 263 kips
The interior frames are made up of full height columns
The base shear is distributed over the height of the
and short beams. The exterior walls are 8 ft wide pre­
building. In this example, the extra lateral force at the
cast, prestressed concrete double tees placed on
top level is F, = 0, since T < 0.7 second. The distribu­
end, and are continuous from top of footing to top of
tion to the several levels is then:
parapet. Seismic code is UBC-94.

(V - F,)wxhx 263wxhx
Fx = n (Eq. 3.11.3)
120,300

Approximations and Partial Designs i=i


In the example, several approximations are made,
but they are all conservative. The designs are not
complete in all respects, but in the case of several sim­ which gives the values of Fx listed in Table3.11.1 (Col­
ilar parts the more critical part is analyzed to illustrate umn 4). These lateral loads are used for design of the
procedure. Some items, such as number or spacing building as a whole, like shear in and overturning of
of connections, are in some cases determined by walls. For floor and roof diaphragms the following
judgment. equations are used:

PCI Design Handbook/Fifth Edition 3 -6 5


Figure 3.41.8 Walt to footing connection

T u = 49.5 k

Table 3.11.1 Lateral force distribution through levels

(1) (2) (3) (4) (5) (6) (7) (8)


Level hxft wx* kips Fx kips (6) / (5) Fpx
Roof 50 831 90.8 831 90.8 0.1093 91.0
4th 39 926 79.0* 1757 169.8 0.0966 89.7
3rd 28 926 56.7 2683 226.5 0.0844 78.3
2nd 17 962 35.8 3645 262.3 0.0720 69.3
-1st 2 178 0.8
Totals 3823 263.1
*w px is assumed = wx

3 -6 6 PCI Design Handbook/Fifth Edition


Figure 3.11:9 Four-story example building-elevations

SHEAR WALL
u u u u

FRONT (LONG) WALL ELEVATION

TYPICAL JOINT
o
CO
TYPICAL CONNECTION, FIGURE 3.11.15%

ROOF

<!)

4th

pnnn
SHEAR WALL
U u u u
3rd
co
in

2nd

9
lb

MAIN
HU3F

TYPICAL CONNECTION, FIGURE 3.11.16


o
CM
SIDE (SHORT) WALL ELEVATION

PCI Design Handbook/Fifth Edition


3 -6 7
Figure 3.11.10 Four-story example building-typical floor-plan

Figure 3.11.11 Typical connection between diaphragm and wall at end of double tee

3 -6 8 PCI Design Handbook/Pifth Edition


site, the 1.04 kit is used throughout ait diaphragms
+ 1 F. and for their connections to the walls.
I> = px (Eq. -3,1-1.4)
Typical ConnectionaFor Intenor of Diaphragm
E wi
A typical connection transmitting^shear between
double tees is illustrated in Figure 3.11.13L In each
0.35 Zlw ^ < Fpx < 0.75"ZIWpX
edge there is a small angle anchored with two bars at
The resulting values of Fpx are listed in Table 3.11.1 45°. The-shear strength is calculated from force com­
(Column 8). ponents in the anchor bars, as in the previous exam­
ple:
Chord Forces in Diaphragm
4>Vn= 23.6 kips
The roof is the most heavily loaded diaphragm,
with a total lateral load of 91 kips. With the diaphragm To equalize cambers and deflections in neighbor­
m ing elements, a maximum spacing should not exceed
spanning in the long direction, the momentT(d)
8 about S ft. This provides a resisting unit shear of:
and the chord force:
= W l _ 91(92)- c|)Vn = 23.6/8 = 2.95 klf
15.9 kips
8d 8(68 - 2)
which compares to the requirement of:
Design of the chord reinforcement:
To maintain elastic behavior, use load factor: 2.4(1.04) = 2.5 klf < 2.95 klf

(2/5) Rw = (2/5){6) = 2.4 Across the center of the building, the double tee
As = TJc^fy = 2.4(15.9)/(0.9) (60) = 0.71 itf elements are supported by a beam, and they meet
end to end. It is desirable to make the shear path stay
Use 3 - # 5 bars placed as shown in Figure 3.11.12* at the level of the flange, that is, making the path as
direct as feasible. The easiest way to achieve this is
Requirements at lower levels and for the dia­ by use of continuous reinforcement in the topping as
phragm spanning in the short direction are even less, shown in Figure 3.11.14. The use of fibermesh does
but, for simplicity, the same diaphragm chord rein­ not satisfy the requirements for diaphram steel rein­
forcement is used throughout. (Figure 3.1 1.1 1) forcement. It may also be desirable to use some of the
hardware type connections to make the building re­
Shear Stresses in Diaphragm sistant to lateral loads during construction.
This example building is assumed to be symmetri­
cal, and the centers of mass and rigidity coincide. It is
then necessary to include the effect of an arbitrary tor­ Connection of Diaphragm to Wall
sion, that is, the lateral load is offset from the center of First, consider the connections between the ends
rigidity by 5% of the maximum dimension of the dia­ of the double tees and the short wall. The ribs of the
phragm. double tees and of the wall elements are aligned, and
The torsional moment is resisted by all four exterior the vertical loads are carried by corbels projecting
walls, depending on rigidities and distances from the from the interior wall surface. Two requirements must
center or rigidity. However, it is conservative to as­ be satisfied: a) horizontal shear transfer between dia­
sume that the torsional moment is resisted by the two phragm and wall, and b) direct horizontal tension
walls that are parallel to the direction of motion. For caused by the tendency of the wall to fall away from
earthquake in the transverse (short) direction, the the building. Since the diaphragm is assumed to be
maximum total shear to one wall is: elastic and the forces are high, the two requirements
will not be superimposed and will be considered sep­
R0 = 0.55(FXor FpJ = 0.55(91) = 50.1 kips arately.
It is convenient to space the connections 4 ft apart
Deducting the length of the service shafts,The max­ so that they will occur at wall ribs. At each connection
imum unit shear is: the forces are:

v0 = Ro/€ = 50.1/(68 - 20) = 1.04 klf a) Shear transfer, V = 1.04(4) = 4.16 kips This
can be handled by shear-friction. Then the
For earthquake in the longitudinal direction, the tensile capacity for shear friction must be:
maximum unit shear to the long walls is less. For sim­
plicity in production of elements and erection at the Fpu = V Jv =-2.4(4.16/0.6) = 16.64 kips

PCI Design Handbook/Rfth Edition 3 -6 9


b) Direct horizontal-tension is given by: ample buildingdo double duty \n that they are also
bearing walls.
Fr = ZfpCpWp The design o f the indtvidualwall elements- can be
important, but wilt not be covered here. For the exam­
UBC-94, Table IB-0, gives Op = 0.75. Bor ple, next examine the shear in the joints, and overall
stability. The equivalent static toads, which are as­
the weight of wall contributing to one connec­
sumed to act horizontalty at each floor level, causes
tion, a unit weight of 90psf over arrarea of 4
tendency for the wall to overturn. Gravity loads and
x 14 = 56 ft2 will be used, so that:
footing will stabilize the wall and prevent overturning,
Wp = 0.090(56) = 5.04 kips but internal shear and direct stresses wilt develop. In
this case, no advantage will be taken of the slightly re­
Fpu = 2.4(0.15)(1.0K0.75K5.04) = 1.36 kips duced overturning permitted by UBC-94, but the full
value of the cantilever moment will be used. Results
The minimum anchorage between wails and of the calculations are shown in Table 3.11.2 for one
floors, per UBC-94 Sect. 1611, is 200 plf wall.

Thus; Shear in Shear Wall


The maximum shear in the short end wall due to
Fpu = 2.4(0.2)(4) = 1.92 kips > 1.36 kips
the equivalent static loads and the arbitrary 5 percent
and therefore shear transfer controls. eccentricity is

Fpu= 16.64 < c()Vn = 23.7 kips V = 0.55(263) = 145 kips

(See Fig. 3.6.2.) v = 145/68 = 2.13 klf

The connection must also satisfy the requirements vu =1.4(2.13) = 2.98 klf
of structural integrity; refer to Sect. 3.10.
The diaphragm to double tee wall panel connec­ This unit shear occurs near the bottom of the wall,
tion, (see Figures 3.11.11 and 3.11.12) utilizes a and is both horizontal and vertical.
welded connection for temporary erection stability A typical connection for the vertical joints between
spaced at 8 ft on center in addition to a 4 ft spacing of wall elements is shown in Figure 3.11.15. In each
reinforcement assemblies which project into the floor edge there is a small angle anchored with two No. 5
topping. The reinforcement assembly is welded to bars. Using the shear-friction concept, with the anchor
anchor plates cast into the precast walls. Coil-loop in­ bars placed at 90° to the joint, the shear capacity of
serts with continuous threaded coil rods can be sub­ one connection is:
stituted for the reinforcement and weld plate assem­
blies if preferred by the designer. A note of caution is <j)Vn = <j>Asfy|x = 0.85(2)(0.31)(60)(1.4)
in order: the reinforcement assembly and anchor = 44.3 kips
plate or coil-loop insert and coil rod should each be
anchored in concrete so that yielding of the projecting Near the bottom of the wall, the average vertical
steel element is ensured. spacing should not be more than 44.3/2.98 = 14.9 ft,
however, use three connections in each story. Since
Special Situation at Service Shafts windows cross the joints, be sure to allow for this
From the typical floor plan, Figure 3.11.10, it is when locating the connections.
seen that several wall ribs are not tied to the floor, and
the wall, because the vertical joints are not suited to Moment in Shear Wall
span horizontally past the shaft openings. This situa­ The maximum moment in the short end wall, with
tion is readily alleviated with a strongback type beam allowance for the minimum 5 percent eccentricity, is:
placed horizontally at each floor level, and spanning
the shaft opening. The adjacent connections at each M = 4911(1.05) = 5157 kip-ft
side of the shaft will have to be stronger than the stan­
dard connection designed in the preceding section. The maximum gravity load is:
W of one end wall, 68(53)(0.067) = 241
Shear Wall
The exterior walls of the building provide the hori­ W Of 1/4 of roof, 68(92/4) (0.100) = 156
zontal reaction for the diaphragms. These forces are W o f 1/4 of floors, 68(92/4)(0.110)(3) = 516
inthe plane of the wall and become horizontal shears,
therefore the term shear wall. The end walls in the ex­ Total W = 9 1 3 kips

3 -7 0 PCI Design Handbook/Fifth Edition


figure 3.11.12 Typical connexion between Figure 3.11.14 Typical end connection between
diaphragm and wall at side of double tees
double tee

CONTINUOUS"
REINFORCEMENT
TOPPING
\ IN TOPPING x

DOUBLE TEE \
STIRRUP

GIRDER

NOTE: ERECTION CONNECTION OF TEE


STEM TO BEAM NOT SHOWN FOR CLARITY.

With wall ribs neglected, section properties in lin­


Figure 3.11.13 Typical diaphragm connections ear measure are, area, Ac = 68 ft, and section modu­
between double tees lus Se = (1/ 6) (68)2 - 771ft2.

Fiber stresses at bottom of wall are:

f = = = 20-1 klf and 6.7 klf


Af oo it 1

These values are a good measure of the stresses


in the gross wall section, and can also be used to cal­
culate the necessary width of wall footing. Additional
refinement of stress calculations are necessary at win­
dow openings.

Other Shear Walls


The long shear walls, which provide the resistance
to earthquake in the longitudinal direction of the build­
ing, are less critical than the short walls, and they will
not be discussed. Details of design wilt be the same
as for the short walls.
There is a special situation at the building’s en­
trance doors. The wall panel above the doorway is
supported by connections to neighboring units. The
necessary strength can be provided by two additional
connections in each joint above the doorway.

Connections of Walls to Footings


The footings can be proportioned on the basis of
reactions from the walls, as indicated above. Each
wall element can be connected to the footing by pro­
jecting the main reinforcement of the ribs downward
into blockouts in the footings, and filling the blockouts
with concrete. The space between wall elements and
footing must be drypacked as shown in Figure
3.11.16.

PCI Design Handbook/Fifth Edition 3 -7 1


Figure 3.11.15 Typical connections, wall-to-wal!

Table 3.11.2 Shear and moments by level In this example, the applicable building code is the
Standard Building Code, 1994. It should be noted
Level Vx kips Mx kip-ft
that the requirements of the BOCA National Building
Roof 45.4 0 Code are similar. A conceptual determination of the
4th 84.9 499 lateral load resisting system is first given, followed by
a detailed analysis of key elements and their connec­
3rd 113.3 1433
tions. The structure is shown in Figure 3.11.17.
2nd 131.2 2680
1st 31.6 4648
Top of footing 4911 Design Information
Wind Data
Basic wind speed = 100 mph
3.11.9 Example—3-Level Parking Structure
Basic wind pressure = 26 psf
General
Over the years, precast concrete parking struc­ Seismic Data
tures have proven to be a reliable, economical means
Aa = 0.15A„ = 0.15
of providing attractive and secure parking for the pub­
lic. Since prestressed concrete is capable of long Soil Profile Type = Unknown
spans which accommodate ease of traffic circulation, R = 4.5
a structure with minimum structural elements for verti­
Cjj = 4
cal load support within the area of parking results.
The resulting openness requires the designer to con­ End Zone Coefficient = 1.2
sider, early in the planning, the method of providing Interior Zone Coefficient = 0.8
for lateral load resistance. As is demonstrated in this Seismic Hazard Exposure Group = 1
design example, sufficient shear walls can be pro­
Seismic Performance Category = C
vided in a manner so as to not intrude upon the func­
tionality of the design. A detailed presentation of all Basic Structural Type = Reinforced Concrete
aspects of precast concrete parking structures may Shear Wall/Bearing Wall
be found in Ref. 16. Analysis Procedure = Equivalent Static Force

3-7 2 PCI Design Handbook/Fifth Edition


Figure 3.11.16 Typical connection of wall to footing

VERTICAL SECTIO N HORIZONAL SECTIO N

Lateral Load Resisting System—Concept Consequently the lateral loads as calculated using
The functional design has resulted in a structure the SBC-94 equations are to be used without the ACJ
with three, 60 ft wide bays in one direction, and a 264 318-95 factors, i.e., without using the ACI factor of 1.4
ft length in the other direction. Three elevated levels, for seismic forces.
with 10 ft 6 in. floor-to-floor height, are needed to pro­
vide the required number of parking spaces. It has Calculation of Wind Forces
been determined that the structure is to be open on all Determination of End Zone Width, E:
four sides.
E = 2 x lesser of: [0.1 (180) = 18 ft] and
Since the structure must resist Zone 2 seismic
[0.4(35) = 14ft] but not less than
forces and the forces generated by a 100-mph wind,
[0.04(180) = 7.2 ft]
as well as the vertical loads, the magnitude of gener­
ated forces must first be determined in order to deter­ E = 2(14 ft) = 28 ft
mine which combination of loads will control. By ar­ End Zone Coefficient = 1.2
ranging support elements in a manner as to resist Interior Zone Coefficient = 0.8
both vertical and lateral loads, the goal of maintaining
an open structure will be achieved.
Calculation o f Wind Shears
Load Analysis
Total N-S Wind Shear =
Obtain an approximate magnitude of the applied
loads. For gravity loads, 26 in. deep, 10 ft wide pre­ [1.2(28) + 0.8(264 - 28)] (35) (0.026)
topped double tees will be used. The total weight of = 202 kips
double tees, beams, columns, and curbs will be taken Total E-W Wind Shear =
as 110 psf. The code specified live load is 50 psf. It is [1.2(28) + 0.8(180 - 28)] (35)(0.026)
determined that for this magnitude of loading, 30-ft = 141 kips
bays with 24 in. square columns, and a 36IT36 girder
in the end bays, will support vertical loads.
For lateral loads, a check is made to determine Calculation of Seismic Forces
whether seismic or wind will govern the design. The
V = C SW
1994 Standard Building Code substitutes the follow­
ing load combination to be used in lieu of the ACI
318-95 seismic load combination. SBC-94 does not require any portion of parking ga­
rage live load to be considered in W.

U = (0.9 - 0.5Av)D + E Wp = 0.110(180)(264) = 5227 kips

PC) Design Handbook/Fifth Edition 3 -7 3


Figure 3.11.17 Layout of parking structure

264'-0"

PLAN

ELEVATION

Table 3.11.3 -ateral force distribution through levels


(1) (2) (3) (4) (5) ( 6) (7)
m m ) (5)/Total (5) ( 6)xVjjase
Level X hx ft wx kips Wxh* Wp-ft Cvx Fpx kips
3 3 31.5 5227 164,650 0.500 651
2 2 21.0 5227 109,767 0.333 434
1 1 10.5 5227 54,883 0.167 217
Totals 15,681 329,300 1302

3-74 PCI Design Handbook/Fifth Edition


Since the soil- profilatype is unknown at the time of transfer-between the precast shear w all and the
the preliminary design, Cs isncalculated using the al­ foundation can be accomplished by reinforcing-bars
ternate equation: withsplice sleeves to develop full 125 percent tensiorr
Cs = 2.5Aa/R-= (2.5)(0.15)/(4.5) = 0383 -splices. Alternatively, post-tensioning bars could be
chosen. The-preliminary analysis is completed by ex­
V = CSW = 0.083W
amining the capacity o f the foundation system to
V = (3 levels){5227)(0.083) = 1302 kip transfer this force to the supporting ground; this anal-
ysis is n ot shown here.
Since V = 1302 kips > (1.3) (202) = 263 kip, the For resistance in the east-west direction, 36 indi­
seismic force governs the lateral forces in both'direc­ vidual load bearing walls located along the length of
tions. the interior ramped bay will be used. These 8-in. thick
Substantial shear resisting elements are required. walls are spaced 10 ft on centers, supporting one 60-ft
Load bearing shear walls are chosen, primarily be­ double tee each side of the wall, as shown in Figure
cause the vertical gravity load will help resist the over­ 3.11.20. Each wall is 6 ft-6 in. wide to accommodate
turning moments due to applied lateral loads. While the 5-ft stem spacing of the double tees, and to allow
the corner stairwells and elevator shafts could be for visibility between the wall units.
used as part of the lateral load resisting system, this
may result in high forces due to restraint of volumetric Vper shear wall = 1302/36 = 36 kip
deformations; consequently, it is decided that the cor­
M o t per wall = 31,900/36 = 886 kip-ft
ners will be isolated from the main structure. Alterna­
Dper wall ~ wall self wt. + double tees
tively, it might have been decided to use these corner
tributary load
elements, and provide connections which are flexible
t the direction of volumetric restraint. 6.5(35) (0.67) (0.15) +
A preliminary distribution of seismic shears is (3 levels) (60) (10) (0.110)
made next. Since equivalent static loads approxi­ D = 23 + 198 = 221 kips
mate an inverted triangle, the first level is assigned a
unit shear of 1, the second level a unit shear of 2, and Calculation of net factored uplift force, Tu
the third level a unit shear of 3, as shown in Figure
3.11.18. Tu = {886 -[(0 .9 -(0.5)(0.15)3
For the north-south load resisting system, try an 8 (221)(3.25)}/5.5
in. thick load bearing shear wall, located at each end
Tu = 53 kips
of the ramp. These walls support the 36IT36 girder,
and may be as long as 30 ft without interfering with the lu . 53
As,rqd = 0.981 in2
traffic flow; a 20-ft length is used as a first iteration. <[>fy 0.9 (60)
Figure 3.11.19 illustrates the arrangement and load­
ing. Since there are 4 walls, Use (1) No. 9 bar at 12 in. from each side of the
wall. As pvd = 1.0 in2 > 0.98 in2
Vper shear wall = 1302/4 = 326 kip
M 0. per wall = 31900/4 = 7975 kip-ft
In the final design, a more accurate determination
Dper wall = wall self wt. + inverted tees
tributary load of forces, including the effect of torsional eccentricity,
will be prepared. For a structure of this configuration,
35(20) (0.67) (0.15) + the final forces will be within about 10 percent of these
(3 levels) (21) (60) (0.110) approximate values.
D = 70 + 416 = 486 kips
Diaphragm—General
The floors act as diaphragms which transfer the lat­
Calculation of net factored uplift force, Tu :
eral loads to the shear walls. A factor used in the de­
Tu = {7975 - [0.9 - 0.5(0.15)](486)(10)]}/1 8 termination of the vertical distribution of seismic
Tu = 220 kip forces is the approximate fundamental period.
Ta = W /4
A _ 2 m.= 220 = 4.1 in2
s 4>fy 0.9 (60)
where:
Use (5) No. 9 bars, As,pvd = 5.0 in2 > 4.1 in2 hn = height from base to highest level, ft
The (5) No. 9 bars which will be located so as to be CT = 0.02 for shear wall systems
centered 2 ft from each end of the wall. The force Ta = (0.02) (31.5)3/4 = 0.27 sec.

PCI Design Handbook/Rfth Edition 3 -7 5


Lateral force Distribution Diaphragm—h4oment Design
F* = C^V Assuming a 58 ft moment arm, T3u = (5978)/58 =
103 kips.
Cvx ~ n-* hx where k = 1 for Ta < 0.5 sec.
This tensile force may be resisted by reinforcing
i= X
bars placed into field applied concrete topping or
curbs located at each end of the double tees, or by
The results of this distribution are shown-in Table reinforcing steel shop welded to plates cast in the
3.11.3. For this case there is exact agreement be­ edges of the double tee flanges. These plates would
tween the values in Table 3.11.3 and the simplified in­ be connected together in the field across the joint us­
verted triangular distribution shown in Figure 3.11.18. ing splice plates and welds. Various suggestions for
connections are provided in Ref. 15.
North-South Seismic Forces on Diaphragm
The diaphragm is modeled as shown in Figure As = T3u/ct)fy = (103)/[0.9(60)] = 1.91 in2
3.11.21. Since the diaphragm forces on Level 3 are
use 2 - # 9 bars, As = 2(1.00) = 2.00 in2
the greatest, only this level will be analyzed and de­
signed. To simplify, the diaphragm will be divided into AP| rpd = 2.00(60/36) = 3.33 in2
3 separate analyses. One istheflat area, which is fur­ use a plate 6 in. x % in. x 0 ft - 9 in., Api pvct =
ther divided by aline along the center of the ramp, and 3.75 in2
the other is the ramp area.
The required length of a 5/i 6 in. weld:
60(264) / 651\ €w = 60(2.00)/6.96 kips/in.
Wi 0.82 klf
264(180) \264/ = 17.2 in.
30(42) /651\ use €w = 18 in.
w2 0.41 klf
264(180) V 42 J
60(180) / 651\ The arrangement of reinforcement is as shown:
w3 0.82 klf
264(180)1180/

Because the overhanging cantilevers will reduce


the stresses in the level area of the ramp diaphragm,
the ramp diaphragm will be analyzed and the results
conservatively used for the level area diaphragm as
well. However, the negative moment for the over­
hangs will be determined.

Summary of North-South Diaphragm Analysis


To maintain elastic behavior in the diaphragm, an
additional load factor of (%)R is used to determine the
factored design forces:

2R _ 2(4-5)
= 1.8
5 5

+MU = 1.8(0.82)(180)2/8 = 5978 kip-ft

-M y = 1.8(0.82 + 0.41)(422/2) = 1953 kip-ft


(ALTERNATE WELDING DETAIL)
Vu = 1.8(0.82) (180V2 = 133 kip

R, = 1.8[(264/2)(0.82) +0.41 (42)] =226 kip


Shear Design
R2 = 1.8(180/4)(0.82) = 66 kip
vu = 133/60 = 2.22 kip per ft
Rtot = Ri + R2 = 226 + 66 = 292 kip
If flange connectors are provided 5 ft on centers,
Ru per wall = Rtot = 292 kips required cpVn per connector = 2.22(5)=11.1 kip.

3 -7 6 PCI Design Handbook/Fifth Edition


Ftgure 3.t1.18 Summary of vertical distribution of seismic shears

Conclusion Figure 3.11.19 Conceptual sketch of typical


The preliminary analysis indicates that the pre­ ____________ N-shear wall
sumed sizes and arrangement of load resisting ele­
y
ments is reasonable. Refinements as may be archi­ PtWELS ABOVE^
tecturally required are then made, and the final
analysis performed.
i i
3.11.10 Example—12-Story Building ■■ ■ 7975 ft-k ■
10'-6"
Box-type buildings can be built to a height of 160 ft,
according to UBC-94. For buildings approaching
,,486k
that height the structural layout and connection de­
tails may differ from those of the example, Sect.
3.11.8, but the design procedure is the same. The 326k
|, 10'-0"
base shear, its distribution as equivalent static loads
18'-0" ASSUMED
over the height of the building, and the load paths
down to the foundations, are calculated as illustrated 20'-0"
in Sect. 3.11.8.
Figure 3.1 1.22 shows a 12-story building which is
square in plan. Wall units are 12 ft high and 30 ft or 15
ft in width. The “running bond" pattern illustrated is Figure 3.11.20 Typical E-W shear wall
not an essential feature of seismic design, but it does
help tie the building together, thus reducing the likeli­
hood of progressive collapse in case of accidental
overloads.
Floors consist of prestressed hollow-core slabs, 12
in. deep and 4 ft wide. They bear on continuous cor­
bels on the walls and on interior beams.
Buildings of this type are generally erected one
story at a time, and location of joints, temporary brac­
ing, and connection details must be correlated with
the erection sequence. Figure 3.11.23 indicates the
erection cycle. The walls of the story below have been
erected, braced, and fully connected. The hollow-
core slabs are then erected, bearing on wall corbels
and interior beams. The wall panels of the next story
are then erected; these have dowels projecting down­
ward into sleeves filled with grout in the wall panels
below. See Figure 3.11.24(A). Hardware in the verti­
cal joints for welded connections is shown in Figure
3.11.24(B). The erection cycle can be repeated as
soon as the grout and concrete have adequate
strength, and the welding of the connections between

PCI Design Handbook/Fifth Edition 3 -7 7


Figure 3.11.21 North-Souib diaphragm analysis Figure 3.H.23 12-SIory building-isometric view
of a ssem b ly

the wall panels has been completed. The next step is


to place continuous welded wire reinforcement for the
topping, and finally place the topping.
The connections shown in Figure 3.11.24 are il­
lustrations of methods of providing the diaphragms
Figure 3.11.22 12-Story building-elevation and continuous load paths discussed in the previous
examples. Many other details have been used suc­
cessfully on similar structures in high-intensity earth­
joints -
quake areas.
I / I \ V I
3.11.11 Example — 23-Story Building
ro a m ran m in nm i n
Figures 3.11.25 and 3.11.26 show a 23-story build­
m dm nnd nnd d r a n nn i t t i ing 300 ft high. The building was designed for earth­
nun nan ran nnn nnn quake resistance with a ductile moment-resisting
dd ran
space frame.
n an ra n n ra ddd idndd r a n t All floors consist of 10-ft wide single-tee units that
were precast and prestressed. Adjacent tees were
nan m dnni n ra d d n n nn r a t 5? connected by means of hardware in the flanges, but
MWMlImfH these connections were not considered as diaphragm
ra d ra n SHEAR WAl p r a ndd nirai ;
connections. The tees have a structural concrete top­
flan nan ddd nnn d r a n dddidc : ! ping reinforced with welded wire fabric. The dia­
phragm is provided by the topping rather than by the
■ D M n ra nnn d d n n nd m £ flanges of the tees.
ndn nan ndn ran nnn nra nra - The core of the building has no structural walls or
frames that contribute measurably to lateral stability of
drai nan nra nun ndldn nni nnr the building. Each single tee is supported at the core
by a cast-in-place column. The connection is not re­
nod ra n ddd nnn d r a n nn nra quired for earthquake resistance. The core has addi­
tional columns and partial slabs, but in effect, the core
X creates a large square hole in the floor diaphragm.
Reinforcement must be provided in the diaphragm
around the core in the same manner as around any
large hole in a slab.

3 -7 8 PCI Design Handbook/Fifth Edition


Figure 3.11-24 Typicalcorinection& for 12-story building-seismic load
REINFORCING BARSTROJECTlNe

SERLOR
SEALANT

ELEVATION SECTION

(A) HORIZONTAL JOINT BETWEEN WALL PANELS

(B> VERTICAL JOINT BETWEEN WALL PANELS (C) CONNECTION TO PARALLEL WALL

(0) REINFORCING BARS PROJECTING FROM WALL INTO TOPPING (E) WELDED WIRE REINFORCEMENT IN TOPPING

PCI Design Handbook/Fifth Edition 3 -7 9


Figure 3.11.25 23-storyexam ple building-typical floor plan

12 @ 10' - 0" = 1 2 0 '- 0 "

120'-0
=
"
10 0
12 '-
@

3 -8 0 PCI Design Handbook/Fifth Edition


Thaexterior walis of the building are the moment- The following .example is meant-to illustrate how
resisting frames. They consist of reirtforced-concrete the UBC load multipliers are appTfedin the-design of
columns and spandrel beams. For These frames to the various components that make up connection
be ductile, they must have closely spaced spirals in systems used for architectural precast.'concrete clad­
thecolumns antHies inthe spandrels. At the intersec­ ding panels. Someinitial design-procedures are given
tions, the congestion of reinforcement is so great that but it iso o t intended to carry out complete designs for
it Js not feasible to have the tees align with the col­ each panel connection. Chapter 6 design examples
umns. Instead they are located midway between col­ and design aids should be applied in designing the
umns, but again the connection of the tee stem to the various connection components.
spandrel is immaterial to the earthquake resistance.
The vital connection here is between the flange and Figure 3.11.26 23-Story example building-
the spandrel. This was accomplished by reinforce­ elevation
ment projecting out of the end of the tee flange, which
is later embedded in the cast-in-place concrete of the
spandrel.
The 1994 Uniform Building Code [17], Sections
1630 and 1631, requires that precast non-bearing,
non-shear wall panels or similar elements which are
attached to or enclose the exterior shall be designed
to resist the inertia forces per UBC formula (30-1).
These elements shall also accommodate movements
of the supporting structure resulting from lateral
forces or temperature changes. Panels typically have
two rigid load bearing connections with volume
change relief provided by the flexibility of the connec­
tions, and two or more tie-back connections with full
freedom of movement in the plane of the panel.
For seismic forces, UBC Sect. 1631.2.4.2 requires
that the body of a connector be designed for a force
equal to one and one-third times the inertia force, and
that all fasteners (i.e., bolts, inserts, welds and dow­
els) be designed for a force equal to four times the in­
ertia force. Anchorage to concrete is required to en­
gage reinforcing steel in a manner so as to distribute
forces to the concrete and/or reinforcement thus
averting sudden or localized failure. Since the force
distribution philosophy is critical to design in seismic
zones, many designers specify confining hoop steel,
or the use of long deformed anchor bars or reinforce­
ment, as opposed to short headed studs or inserts.
When studs or inserts are used, and located near pan­
el edges, it is recommended that they be enclosed in
sufficient reinforcing steel to carry the loads back into
the panel, thus averting a sudden tensile failure mode
in the concrete.
Connections and joints between panels should be
designed to accommodate the movement of the
structure under seismic action. Connections which
permit movement in the plane of the panel for story
drift may achieve this through bending of steel, sliding
connections using slotted or oversized holes, or other
similar methods. Story drift, which is the relative
movement of one floor with respect to an adjacent
floor, must be considered when determining panel
joint locations as well as connection locations and
types. Between points of connections, non-load bear­
ing panels should be separated from the building
frame to avoid contact under seismic action.

PCI Design Handbook/Fifth Edition 3 -8 1


3.11.12 Example-ArchitecturalPrecast Panel Wind Loading:
(See%ures 3.1-1.27 andJ3.11.28) Upper Window
Ttefemie lo a d : w = (25/144)^72/2) = 6.25-Jb/in.
1994 UBC, Setsmfc Zone 4 Panel

Fp = ZICpWp y = 4 2 in. f
where: W = (25/144)(84) = 14.58lb/rn.
Z = 0.4 Bottom Window
I = 1.0 y = 0 in. J
Cp = 0.75 w = (25/144}(96/2) = 8.33 Ib/in,
F o r panel design, Fp Combined Wind Load
For body of connection: y = 3 9 in. t
1.33FP = 1.33(0.3)Wp 2 w = 29.16 Ib/in.
163FP = 0.4WP Total wind load, W = 29.16 (336) = 9798 lb
For fastener design:
Determine Combined Dead Load and C.G.:
4FP = 4(0.3)Wp
Wp 2 Wp®
4FP = 1.2WP
lb In. in.-lb
Wind Load: Panel 13584 4.5 61128
(Panel is not on corner of structure)
Upper 1680 2 3360
Wind pressure = 25 psf (Positive and Negative) Window
Panel Section Properties (From datum)
Lower 0 22 0
y = 34.5 in. f Window
z = 4.5 in. / Total 15,264 64,488
Cross-sectional area = 465.75 in .2
Unit weight = 150 pcf y = 84 in. |
Wp = 40.43 Ib/in.
z = 64,488/15,264 = 4.2 in. /
Wp = 40.43(336) = 13,584 lb
Fp = 0.3WP= 0.3(13,584) = 4075 lb Determine Combined Lateral Load and C.G.:

Window information (10 psf) Fp y z FP(y) FP®


Upper window (full length of panel) lb in. in. in.-lb in.-lb
Ht. = 6 ft-0 in. (72 in.) Panel 4075 34.5 4.5 140,587.5 18,337.5
y = 84 in. f Upper 252 84 2 21,168 504
Window
z = 2 in. /
Lower 336 0 22 0 7392
wp = 72(10/144) = 5 Ib/in.
Window
Wp = 5(336) = 1680 lb
Total 4663 161,755.5 26,233.5
Vz of total height of window is tributary to the
panel for lateral load, therefore
y = 34.7 in. f
Fp = 1/2(0.3)(1680) = 252 lb z = 5.6 i n . /

Lower window (full length of panel)


Loads on connections (0.3WP lateral load)
Ht. = 8 ft-0 in. (96 in.) Gravity
y = 0 in.
(▼) Vertical = 15264/2 = 7632 lb l(y)
z =22 in. / (T,X) In-out = 7632(7.5-4.2)/32.5

No dead load is tributary to the panel. = 775 lb / (z)

For lateral load: Seismic parallel to face


Fp = 14(96)(10/144) (0.3)(336) = 336 lb p ) Parallel = 4663 lb (x)

3 -8 2 PCI Design Handbook/Fifth Edition


(T) Up-down = 4663(27.5+32.5-34.7)/312 Couple force = 8.368(3/5) = 5.02Q8 kips/weld^
= 378 lb ^y).
Resuitant shear:
(T)Jn-out = 4663(5.6-4.5)/312
= 16 to / ( z ) = /( 4 1 8 4 f + (5.0208)2

Seismic perpendicular to face = 6.54 kips/weld


Uniform load for continuous beam analysis With 1/4 in. fiiletweld, allowable stress design:
w = 4663/336 = 13.878 Ib/irr. of length Allow, strength = 3.71 kips/in (Table 6.15.2)
y = 34.7 in. f Weld length = 6.54/3.71 = 1.76 in. < 2 in.
From continuous beam analysis Use 2 - 1/4 x 2 in. fillet welds
End reaction (each end) = 988 lb
Component 2 (flexure of angle):
Distribute to top and bottom connections With L 5 x 5 x Vz angle, k = 1 in.
(T)R,op = 988(34.7 - 27.5)/32.5
1.33(0.3) Wp < wind load, therefore wind con­
= 219 to / / (z) trols
(X) Rbott = 769 lbs. / / (z) e = 3 — 1 = 2 in.
M ' = 2(3.648) = 7.296 kip-in.
Middle reaction = 2687 lb
Sreq = M /(wind increase x allowable stress)
Distribute to top and bottom connections Sreq = 7.296/[1.33(0.75)(36)] = 0.230 Hl.3
P )R top = 2687(34.7-27.5)/32.5 Length of angle required:
= 595 l b / / (z)
= 6(0.203)/(0.52)
(XjRboa = 2092 lb / / (z)
= 4.87 in. < 5 in.
Wind load
Use L 5 x 5 x Vfc x 0 ft -5 in.
w = 29.16 Ib/in.
y = 39 in. t Component 3 (buckling of rod):
4(0.3) Wp > wind load, seismic controls
By proportion from seismic analysis
End reaction (each end) = 988(29.16/13.878) Rod length = 21 - panel thickness - location of
= 2076 lb the angle heel from the beam centerline
(Y) Rtop = 2076(39-27.5)/32.5 Rod length = 21 - 414 - 2Vz = 14 in.
= 735 lb / / (z)
Try 1 in. diameter National Coarse threaded
(X)Rbott = 1341 lb / / (z) (A307)
Middle reaction = 2687(29.16/13.878) = 5646 lb Root diameter = 0.847 in.
P)Rtop = 5646(39-27.5)/32.5 Radius of gyration (See design Aid 11.3.1)
= 1998 lb / / (z)
r = d/4
(X)Rbott = 3648 lb / / (z)
= 0.847/4 = 0.212 in.
Design of Tie-Back Connection Components: Conservatively select k = 1.6
(see Figure 3.11.29) k ( /r = 1(14)/0.2118) = 66
Load summary at bottom middle tie-back con­
nections From AISC ASD, Ref. 18, Table C-36

Wind Fz = 3648 to Allowable compression stress with k€/r = 66


0.3Wp Fz = 2092 lb Fa = 16.84 ksi
1.33(0.3)WP F2 = 2782 to
Maximum allowable load
4(0.3)Wp F2 = 8368 lb

Component 1 (shear of weld) - & F. = M l6 .8 4


4 4
4(0.3) Wp > wind load, therefore seismic load
controls. = 9.5 kips > 8.37 kips

Direct shear = 8.368/2=4.184 kips/weld «• Use 1 in. diameter National Coarse bolt.

PCI Design Handbook/Fifth Edition 3 -8 3


Figure 3.11.27 Connection diagram for Example 3.11.12

12" •4%"

o
I
F-

2' - 0"

PANEL CROSS SECTION

6'-0" TALL UPPER


WINDOW
▼ = BEARING; RESISTS LOAD IN y & z DIRECTION ONLY 2"
■ = LATERAL; RESISTS LOAD IN x & z DIRECTION ONLY
- m "
X = TtE-BACK; RESISTS LOAD IN z DIRECTION ONLY

1. CONNECTIONS MUST BE DESIGNED AND DETAILED TO ENSURE


THAT LOADS DO NOT OCCUR IN DIRECTIONS OTHER THAN THOSE EXTERIOR FACE
OF PANEL
ASSUMED FOR THE CONNECTIONS.

2. VERTICAL LOAD RESISTANCE AT BEARING CONNECTION IS


8'-0" TALL LOWER
LOCATED T k" FROM THE EXTERIOR FACE OF THE PANEL.
WINDOW

3. LATERAL LOAD (X-DIRECTION) RESISTANCE AT LATERAL CONNECTION


SECTION AT BEARING
IS LOCATED 4 'A" FROM THE EXTERIOR FACE OF THE PANEL.
(GRAVITY LOADING REACTIONS SHOWN)

Figure 3.11.28 Reaction diagrams for load analysis with Example 3.11.12

SUPPLEMENTAL SUPPLEMENTAL
SECTION PLAN VIEW
(VERTICAL REACTIONS NOT
SHOWN FOR CLARITY)

T = BEARING; RESISTS LOAD IN y & z DIRECTION ONLY

■ = LATERAL; RESISTS LOAD IN x & z DIRECTION ONLY

X = TIE-BACK; RESISTS LOAD IN z DIRECTION ONLY

NOTE: LOAD ANALYSIS FOR THIS CASE IS DONE WITH


Fp APPLIED AS A UNIFORMLY DISTRIBUTED LOAD ALONG
THE PANEL'S LENGTH.

3 -8 4 PCI Design Handbook/Fifth Edition


Figure 3.11-29 Bottom-middle tie-back detail for example 3.11.12

COMPONENT MODE OF FAILURE PESIfiNJrQAP*

© SHEAR OF WELD 4 Fp - 1.2 Wp

© FLEXURE OF ANGLE 1.33 Fp = 0.4 Wp

® BUCKLING OF ROD 4 Fp = 1.2 Wp


OR WIND IF LARGER

© SHEAR OF WELD 4 Fp = 1.2 Wp

® FLEXURE OF PLATE 1.33 Fp = 0.4 Wp

® CONCRETE PULL OUT 4 Fp = 1.2 Wp -------

ACI LOAD FACTORS MUST ALSO BE


APPUED TO THIS [1.1 (1.3) (1.2 Wp)]

*NOTE: IF CONNECTION ALSO HAS A DEAD LOAD REACTION, THE DESIGN LOAD WOULD INCLUDE THAT REACTION.
I.E., FOR C O M P O N E N T D E S IG N LOAD = DL+1.2 Wp (OR WIND)

PCI Design Handbook/Hfth Edition 3-8 5


3.12 DESIGN AIDS

Figure 3.12.2 Annual average ambient relative humidity, percent

3 -8 6 PCI Design Handbook/Fifth Edition


Figure 3.12.3 Creep arid-shrinkage strains (millionths)
Concrete Release Strength = 3500 psi
Average Prestress = 600 psi
Reiative+fumieflfy — 70%
Volume/Surface Ratio = 1.5 in.

Creep Shrinkage
Time,
days
Normal weight Lightweight Moist cure Accelerated cure

1 29 43 16 9
3 51 76 44 26
5 65 97 70 43
7 76 114 93 58
9 86 127 115 72
10 90 133 124 78
20 118 176 204 136
30 137 204 258 180
40 150 224 299 215
50 161 239 329 243
60 169 252 354 266
70 177 263 373 286
80 183 272 390 302
90 188 280 403 317
100 193 287 415 329
200 222 331 477 400
1 Yr 244 363 511 443
3 Yr 273 407 543 486
5 Yr 283 422 549 495
Final 315 468 560 510

Figure 3.12.4 Correction factors for prestress and concrete strength (creep only)

Ave. P/A Release Strength, % (psi)


(psi) 2500 3000 3500 4000 4500 5000 6000
0 0.00 0.00 0.00 0.00 0.00 0.00 0.00
200 0.39 0.36 0.33 0.31 0.29 0.28 0.25
400 0.79 0.72 0.67 0.62 0.59 0.56 0.51
600 1.18 1.08 1.00 0.94 0.88 0.84 0.76
800 1.58 1.44 1.33 1.25 1.18 1.12 1.02
1000 1.97 1.80 1.67 . 1.56 1.47 1.39 1.27
1200 2.37 2.16 2.00 1.87 1.76 1.67 1.53
1400 2.76 2.52 2.33 2.18 2.06 1.95 1.78
1600 2.88 2.67 2.49 2.35 2.23 2.04
1800 3.24 3.00 2.81 2.65 2;51 2.29
2000 3.123 3.12 2.94 2.79 2.55
2200 3.43 3.23 3.07 2.80
2400 3.74 3.53 3.35 3.06
2600 3.82 3.63 3.31
2800 3.90 3.56
3000 4.18 3.82

PCI Design Handbook/Fifth Edition 3 -8 7


F ig u re d ! 2.5 Correction fa vo rs for N a tiv e humidity
Ave-ambient R.H.
(from Figure 3.12.2) Creep Shrinkage

40 1.25 1.43
50 1.17 1.29
60 1.08 1714
70 1.00 1.00
80 0.92 0.86
90 0.83 0.43
100 0.75 0.00

Figure 3.12.6 Correction factors for votume/surface ratio


Creep Shrinkage
Time,
V/S V/S
days
1 2 3 4 5 6 1 2 3 A 5 6
1 1.30 0.78 0.49 0.32 0.21 0.15 1.25 0.80 0.50 0.31 0.19 0.11
3 1.29 0.78 0.50 0.33 0.22 0.15 1.24 0.80 0.51 0.31 0.19 0.11
5 1.28 0.79 0.51 0.33 0.23 0.16 1.23 0.81 0.52 0.32 0.20 0.12
7 1.28 0.79 0.51 0.34 0.23 0.16 1.23 0.81 0.52 0.33 0.20 0.12
9 1.27 0.80 0.52 0.35 0.24 0.17 1.22 0.82 0.53 0.34 0.21 0.12
10 1.26 0.80 0.52 0.35 0.24 0.17 1.21 0.82 0.53 0.34 0.21 0.13
20 1.23 0.82 0.56 0.39 0.27 0.19 1.19 0.84 0.57 0.37 0.23 0.14
30 1.21 0.83 0.58 0.41 0.30 0.21 1.17 0.85 0.59 0.40 0.26 0.16
40 1.20 0.84 0.60 0.44 0.32 0.23 1.15 0.86 0.62 0.42 0.28 0.17
50 1.19 0.85 0.62 0.46 0.34 0.25 1.14 0.87 0.63 0.44 0.29 0.19
60 1.18 0.86 0.64 0.48 0.36 0.26 1.13 0.88 0.65 0.46 0.31 0.20
70 1.17 0.86 0.65 0.49 0.37 0.28 1.12 0.88 0.66 0.48 0.32 0.21
80 1.16 0.87 0.66 0.51 0.39 0.29 1.12 0.89 0.67 0.49 0.34 0.22
90 1.16 0.87 0.67 0.52 0.40 0.31 1.11 0.89 0.68 0.50 0.35 0.23
100 1.15 0.87 0.68 0.53 0.42 0.32 1.11 0.89 0.69 0.51 0.36 0.24
200 1.13 0.90 0.74 0.61 0.51 0.42 1.08 0.92 0.75 0.59 0.44 0.31
1 Yr 1.11 0.91 0.77 0.67 0.58 0.50 1.07 0.93 0.79 0.64 0.50 0.38
3 Yr 1.10 0.92 0.81 0.73 0.67 0.62 1.06 0.94 0.82 0.71 0.59 0.47
5 Yr 1.10 0.92 0.82 0.75 0.70 0.66 1.06 0.94 0.83 0.72 0.61 0.49
Final 1.09 0.93 0.83 0.77 0.74 0.72 1.05 0.95 0.85 0.75 0.64 0.54

Figure 3.12.7 Design temperature strains (millionths)

Temperature zone Normal weight Lightweight


(from Figure 3.3.1) Heated Unheated Heated Unheated
10 30 45 25 38
20 60 90 50 75
30 90 135 75 113
40 120 180 100 150
50 150 225 125 188
60 180 270 150 225
70 210 315 175 263
80 240 360 200 300
90 270 405 225 338
100 300 450 250 375

Based on accepted coefficients of thermal expansion, reduced to account for thermal lag [2}'.

3 -8 8 PCI Design Handbook/Fifth Edition


figure 3.12:8 Volume change strainsfor typical building elements (millionths)
Prestressed members (P/A = 600 psi)

r NorraaLweightconcrete - Lightweight concrete


Ave. R H . (from-map) Ave. R.H. (from map)
Temp, zone
(from map) 4 Or 50 60 70 m 40 50 60 70 80
Heated buildings
0 548 501 454 407 360 581 532 483 434 385
10 578 531 484 437 390 606 557 508 459 410
20 608 561 514 467 420 631 582 533 484 435
30 638 591 544 497 450 656 607 558 509 460
40 668 621 574 527 480 681 632 583 534 485
50 698 651 604 557 510 706 657 608 559 510
60= 728 681 634 587 540 731 682 633 584 535
70 758 711 664 617 570 756 707 658 609 560
80 788 741 694 647 600 781 732 683 634 585
90 818 771 724 677 630 806 757 708 659 610
100 848 801 754 707 660 831 782 733 684 635
Unheatec structures
0 548 501 454 407 360 581 532 483 434 385
10 593 546 499 452 405 619 570 521 472 423
20 638 591 544 497 450 656 607 558 509 460
30 683 636 589 542 495 694 645 596 547 498
40 728 681 634 587 540 731 682 633 584 535
50 773 726 679 632 585 769 720 671 622 573
60 818 771 724 677 630 806 757 708 659 610
70 863 816 769 722 675 844 795 746 697 648
80 908 861 814 767 720 881 832 783 734 685
90 953 906 859 812 765 919 870 821 772 723
100 998 951 904 857 810 956 907 858 809 760

Figure 3.12.9 Volume change strains for typical building elements (millionths)
Non-prestressed members
Normal weight concrete Lightweight concrete
Ave. R.H. (from map) Ave. R.H. (from map)
Temp, zone
(from map) 40 50 60 70 80 40 50 60 70 80
Heated buildings
0 294 265 235 206 177 294 265 235 206 177
10 324 295 265 236 207 319 290 260 231 202
20 354 325 295 266 237 344 315 285 256 227
30 384 355 325 296 267 369 340 310 281 252
40 414 385 355 326 297 394 365 335 306 277
50 444 415 385 356 327 419 390 360 331 302
60 474 445 415 386 357 444 415 385 356 327
70 504 475 445 416 387 469 440 410 381 352
80 534 505 475 446 417 494 465 435 406 377
90 564 535 505 476 447 519 490 460 431 402
100 594 565 535 506 477 544 515 485 456 427
Unheatec structures
0 294 265 235 206 177 294 265 235 206 177
10 339 310 280 251 222 332 302 273 244 214
20 384 355 325 296 267 369 340 310 281 252
30 429 400 370 341 312 407 377 348 319 289
40 474 445 415 386 357 444 415 385 356 327
50 519 490 460 431 402 482 452 423 394 364
60 564 535 505 476 447 519 490 460 431 402
70 609 580 550 521 492 557 527 498 469 439
80 654 625 595 566 537 594 565 535 506 477
90 699 670 640 611 582 632 602 573 544 514
100 744 715 685 656 627 669 640 6T0 581 552

PCI Design Handbook/Fifth Edition


3 -8 9
figure 3.12.10 Forces required tarestrain-bowmg

INTERMEDIATE RESTRAINT (ENDSFHEETO ROTATE) ^ND^RESTRAWT

CASE t: SINGLE RESTRAINT AT MIDSPAN CASE 4: BOTI+ENDS RESTRAINED

48 E.IA
P = ------- ----
£3
P

MOMENT IN PANEL = ^ 8 EtIA


M=
~w~

CASE 2: TWO RESTRAINT POINTS CASE 5: O NE END RESTRAINED

P_ 24E,IA
3a€2 - 4a3

16 E,IA
M =
MOMENT IN PANEL = Pa ~~W

CASE 3: THREE OR MORE RESTRAINT POINTS


(APPROXIMATE UNIFORM CONTINUOUS RESTRAINT)

A 77 E,IA FOR DAILY TEMPERATURE CHANGE,


p I P = w€ USE E, = 0.75 Ec
p P
i p
p FOR SEASONAL CHANGES,
p USE E, = 0.50 Ec

MOMENT IN PANEL = ^ = 2p( |

3 -9 0 PCI Design Handbook/Rfth Edition


figure 3.12,11 Length of structure without use of expansion joints

RECTANGULAR
MULTI-FRAMED
CONFIGURATION
WITH SYMMETRICAL
STIFFNESS
SEE MODIFICATION
FACTORS BELOW
NON-RECTANGULAR
CONFIGURATIONS

SEASONAL TEMPERATURE CHANGE (°F) (FROM FIGURE 3.12.1)

These curves are directly applicable to buildings of beam-and-column construction, hinged at the base, and with heated interiors.
When other conditions prevail, the following rules are applicable:

(a) If the building will b e heated only and will have hinged-column bases, use the length as specified;
(b) If the building will be air conditioned as well as heated, increase the length by 15% (provided the environmental control system
will run continuously);
(c) If the building will be unheated, decrease the length by 33%;
(d) If the building will have fixed-column bases, decrease the length by 15%;
(e) If the building will have substantially greater stiffness against lateral displacement at one end of the plan dimension, decrease
the length by 25%.

When more than one of these design conditions prevail in a building, the percentile factor to be applied should be the algebraic
sum of the adjustment factors of all the various applicable conditions.

Note: Figure 3.12.11 should be used as a preliminary guideline for the spacing of expansion joints. It should not be used as the
absolute, authoritative, or sole means of determining the spacing of expansion joints. The spacing of expansion joints should be
determined by the designer, based on analysis or experience, for the structure being considered.

Source: Adapted from ‘ Expansion Joints in Buildings,’ Technical Report No. 65, National Research Council, National Academy of Sciences, 1974.

Figure 3.12.12 Use of Figure 3.12.13

LEVEL 3 h .
LEVEL 4 LEVELS
; - .O '
F
hs hs hs
e -»

LEVEL 2
E U F8 ,
LEVEL 3
ir?r„ LEVEL 4
) ' <
D
hs hs hs
C LEVEL 2 E
LEVEL 3
LEVEL 1 -
B D
2-STORY
hs hs
Fj = k, P e /h s
= A Ft ! c LEVEL 2
Mj = km Pe LEVEL 1
B
WHERE: 3-STORY
hs
Fi = RESTRAINING FORCE AT LEVEL i
Mj = MOMENT AT POINT j j = % - LEVEL 1

k , , km = COEFFICIENTS FROM-FIGURE 3.12.13 4-STORY

P = VERTICAL LOAD ACTING AT ECCENTRICITY e


S E E T E X T F O R L IM IT A T IO N S A N D D E S IG N E X A M P L E

PCI Design Handbook/Fifth Edition 3 -9 1


Figure 3.12.13 Coefficients kf and km for determining^ m om ents and restraining forces on eccentrically
loaded colum ns braced against sidesw ay

See-Figure 3.12.12 for explanation of terms

+ Indicates clockwise moments on the columns and com pression in th e restraining beam

p
kf a t level km at point
No. acting-
of Base at
stories Fixity level 1 2 3 4 5 A B C D E F G H

3 +0.25 - 1 .5 0 + 1 .25 0 - 0 .2 5 +0.25 + 1.0


O 2 - 0 .5 0 0 +0.50 0 +0.50 +Q.50 0
LU
Z 2 Max +0.75 ± 1 .50 ± 1 .75 0- ±0.75 ± 0 .7 5 ± 1 .0
■ z
2 One
Q. - 0 .2 5 - 1 .5 0 +1.75 0 +0.25 + 0 .7 5 + 1.0
Side
9
3 +0.43 - 1 .7 2 + 1.29 - 0 .1 4 - 0 .2 9 + 0 .29 + 1 .0

Q 2 - 0 .8 6 + 0 .43 +0.43 +0.29 +0.57 +0.43 0


UJ
X 2 Max ±1.29 ± 2 .15 ± 1 .72 ± 0 .43 ± 0 .8 6 ± 0 .72 ± 1 .0
LL
2 One - 0 .4 3 - 1 .2 9 +1.72 +0.15 +0.28 +0.72 + 1 .0
Side

4 - 0 .0 7 + 0 .4 0 - 1 .6 0 + 1 .2 7 0 +0.07 - 0 .0 7 - 0 .2 7 +0.27 + 1 .0
3 +0.13 - 0 .8 0 +0.20 +0.47 0 - 0 .1 3 +0.13 +0.53 +0.47 0
HI 2 -0 .4 7 - 0 .2 0 +0.80 - 0 .1 3 0 +0.47 +0.53 +0.13 - 0 .1 3 0
z
z 2 Max ±0.67 ± 1 .40 ± 2 .60 ± 1 .87 0 ± 0 .67 ±0.73 ± 0 .93 ± 0 .8 7 ± 1 .0
CL 2 One -0 .4 1 -0 .6 0 -0 .6 0 +1.61 0 + 0 .4 0 +0.60 +0.40 +0.60 +1.0
Side
*
O
4 - 0 .1 2 +0.47 - 1 .6 2 +1.27 +0.04 +0.08 - 0 .0 8 - 0 .2 7 +0.27 + 1 .0

D 3 +0.23 - 0 .9 2 +0.23 +0.46 - 0 .0 8 - 0 .1 5 +0.15 +0.54 +0.46 0


111 2 -0 .8 1 +0.23 +0.70 - 0 .1 2 +0.27 +0.54 + 0 .46 +0.12 - 0 .1 2 0
X
LL 2 Max ± 1 .1 6 ± 1 .62 ±2.55 ± 1 .85 ±0.38 ± 0 .77 ± 0 .6 9 ± 0 .92 ± 0 .85 ± 1 .0

2 One -0 .2 2
- 0 .7 0 - 0 .6 9 +1.61 +0.23 +0.46 +0.54 +0.38 + 0 .6 2 +1.0
Side

5 +0.02 -0 .1 1 +0.43 -1 .6 1 + 1.27 0 - 0 .0 2 + 0 .02 + 0 .07 - 0 .0 7 - 0 .2 7 + 0 .2 7 + 1 .0


4 - 0 .0 4 +0.22 - 0 .8 6 +0.22 +0.46 0 +0.04 - 0 .0 4 - 0 .1 4 +0.14 +0.54 + 0 .46 0
Q 3 +0.13 - 0 .7 5 0 +0.75 -0 .1 2 0 - 0 .1 3 +0.13 +0.50 +050 + 0 .12 - 0 .1 2 0
HI
Z 2 - 0 .4 6 - 0 .2 2 +0.86 - 0 .2 2 +0.04 0 +0.46 +0.54 +0.14 - 0 .1 4 - 0 .0 4 + 0 .04 0
z ± 0 .65 ± 1 .30 ± 2 .15 ± 2 .80 ± 1 .89 0
2 Max ± 0 .64 ± 0 .72 ± 0 .86 ± 0 .86 ± 0 .97 ± 0 .8 9 ± 1 .0
CL
2 One - 0 .8 6 +0.43 - 0 .8 6 +1.65 0
-0 .3 5 +0.35 +0.65 +0.57 +0.43 +0.35 +0.65 + 1 .0
Side
A

5 +0.03 - 0 .1 2 +0.43 -1 .6 1 + 1 .27 -0 .0 1 - 0 .0 2 +0.02 +0.07 - 0 .0 7 - 0 .2 7 + 0 .27 + 1 .0


4 - 0 .0 6 +0.25 - 0 .8 7 +0.22 +0.46 +0.02 +0.04 - 0 .0 4 - 0 .1 4 +0.14 +0.54 + 0 .46 0
D 3 +0.22 - 0 .8 7 +0.03 + 0 .74 - 0 .1 2 - 0 .0 7 - 0 .1 4 +0.14 +0.51 +0.50 +0.12 - 0 .1 2 0
111
- X 2 - 0 .8 0 +0.21 +0.74 - 0 .1 8 +0.03 +0.27 +0.54 +0.46 +0.12 - 0 .1 2 - 0 .0 3 + 0 .03 0
2 Max ±1.11 ± 1 .45 ± 2 .07 ±2.75 ±1.88 ± 0 .37 ± 0 .74 ± 0 .67 ±0.84 ±0.83 ± 0 .9 6 ± 0 .88 ± 1 .0

2 One
-0 .6 1 - 0 .5 3 +0.33 - 0 .8 3 + 1 .64 +0.21 +0.41 +0.59 +0.56 +0.44 +0.36 + 0 .6 4 + 1 .0
Side

3 -9 2 PCI Design Handbook/Fifth Edition


Figure 3.12.14 Coefficients^ k, for modified El

PCI Design HandbooK/Fiflh Edition 3 -9 3


Figure 3.12rl 5 Alignment charts for determining effective length factors

(A) (B)
Braced Fram es Unbraced Fram es
t|> = If connection is rigid, ratio of ZK of compression members to ZK of flexural members in a
plane. For typical precast connections usually assumed as pinned in analyses, ip may be
taken as 10. Lower values may be used if justified by analysis. For example, ip at footings
may be equal to «c/Kb as calculated in Sect. 3.8.3.
k = Effective length factor

Figure 3.12.16 Shear wall deflections

3 -9 4 PCI Design Handbook/Fifth Edition


_£jgttr&&12JJ Flexibility coefficients for anchorbofts and baseplates

CASE 1 CASE 2

TOP OF FOOTING

y.b + Ybp, 1/in. - lb. x 10-10 FOR TYPICAL DETAILS (SEE EQ. 3.8.6 AND 3.8.7)

CASE 1 EXTERIOR ANCHOR BOLTS CASE 2: INTERIOR ANCHOR BOLTS


COLUMN
SIZE, h e BASE PLATE THICKNESS & ANC. BOLT DIA. BASE PLATE THICKNESS & ANC. BOLT DIA.
(in-) On.) .75 1.25 1.50 .75 1.00 1.50
1-W 1.25
4 .0 .0 .0 .0 .0 .0 .0 .0
6 .0 .0 .0 .0 29.3 16.5 10.5 7.3
8 .0 .0 .0 .0 43.9 24.7 15.8 11.0
10 16.6 7.9 4.5 2.9 52.7 29.6 19.0 13.2
12x12
12 27.7 13.2 7.5 4.8 58.5 32.9 21.1 14.6
14 35.7 16.9 9.6 6.1 62.7 35.3 22.6 15.7
16 41.6 19.8 11.2 7.2 65.8 37.0 23.7 16.5
18 46.2 22.0 12.5 8.0 68.3 38.4 24.6 17.1

6 .0 .0 .0 .0 .0 .0 .0 .0
8 .0 .0 .0 .0 10.5 5.9 3.8 2.6
10 .0 .0 .0 .0 16.7 9.4 6.0 4.2
12 7.7 3.7 2.1 1.4 20.9 11.8 7.5 5.2
16x16
14 13.1 6.3 3.6 2.3 23.9 13.4 8.6 6.0
16 17.2 8.3 4.8 3.1 26.1 14.7 9.4 6.5
18 20.4 9.8 5.7 3.6 27.9 15.7 10.0 7.0
20 23.0 11.1 6.4 4.1 29.3 16.5 10.5 7.3

8 .0 .0 .0 .0 .0 .0 .0 .0
10 .0 .0 .0 .0 4.9 2.7 1.8 1.2
12 .0 .0 .0 .0 8.1 4.6 2.9 2.0
20x20 14 4.1 2.0 1.2 .7 10.5 5.9 3.8 2.6
16 7.1 3.5 2.0 1.3 12.2 6.9 4.4 3.0
18 9.5 4.6 2.7 1.7 13.5 7.6 4.9 3.4
20 11.4 5.6 3.2 2.1 14.6 8.2 5.3 3.7
22 13.0 6.3 3.7 2.4 15.5 8.7 5.6 3.9-

10 .0 .0 .0 .0 .0 .0 .0 .0
12 .0 .0 .0 .0 2.7 1.5 1.0 .7
14 .0 .0 .0 .0 4.6 2.6 1.6 1.1
16 2.4 1.2 .7 .5 6.0 3.4 2.2 1.5
24x24
18 4.3 2.1 1.2 .8 7.1 4.0 2.6 1.8
20 5.8 2.8 1.7 1.1 8.0 4.5 2.9 2.0
22 7.0 3.4 2.0 1.3 8.7 4.9 3.1 2.2
24 8.0 3.9 2.3 1.5 9.3 5.2 3.4 2.3

PCI Design Handbook/Fifth Edition 3 -9 5


Figure 3.12.18 Flexibility coefficients for footing soil interactions

FLEXIBILITY OF BASE tb = Yf + Vab +V bp

ROTATIONOF BASE <l>b = T b ^

STIFFNESS O F BASE Kb = VYb


FIXITY O F BASE M K c + Nd)

Kc = COLUMN STIFFNESS = 4Eclc/h s

Ec = MODULUS OF ELASTICITY OF COLUMN CONCRETE, psi

lc = M O M ENT OF INERTIA OF COLUMN, ir>.4

hs = STORY H1EGHT, in.

y b 17in. - lb. x 1 0 -’ ° FOR SQUARE FOOTINGS

FOOTING SIZE Ks
W 100 150 200 250 300
2.0 X 2.0 3616.9 2411.3 1808.4 1446.8 1205.6
2.5 X2.5
3.0 X 3.0
1481.5
714.4
987.7
476.3
740.7
357.2
592.6
285.8
493.8
238.1
3.5 X 3.5 385.6 257.1 192.8 154.3 128.5
4.0 X 4.0 226.1 150.7 113.0 90.4 75.4
4.5 X 4.5 141.1 94.1 70.6 56.5 47.0
5.0 X 5.0 92.6 61.7 46.3 37.0 30.9
5.5 X 5.5 63.2 42.2 31.6 25.3 21.1
6.0 X 6.0 44.7 29.8 22.3 17.9 14.9
6.5 X 6.5 32.4 21.6 16.2 13.0 10.8
7.0 X 7.0 24.1 16.1 12.1 9.6 8.0
7.5 X 7.5 18.3 12.2 9.1 7.3 6.1
8.0 X 8.0 14.1 9.4 7.1 5.7 4.7
9.0 X 9.0 8.8 5.9 4.4 3.5 2.9
10.0X10.0 5.8 3.9 2.9 2.3 1.9
11.0X11.0 4.0 2.6 2.0 1.6 1.3
12.0X12.0 2.8 1.9 1.4 1.1 _ 0.9

Figure 3.12.19 Build-up of restraint forces in beams (kb)


Total number Number of baifs from end (i)
c f bays (n) 1 2 3 4 5 6 7 8

2 1.00
3 1.00 4.00
4 1.00 3.00
5 1.00 2.67 9.00
6 1.00 2.50 6.00
7 1.00 2.40 5.00 16.00
8 1.00 2.33 4.50 10.00
9 1.00 2.29 4.20 8.00 25.00
10 1.00 2.25 4.00 7.00 15.00
11 1.00 2.22 3.86 6.40 11.67 36.00
12 1.00 2.20 3.75 6.00 10.00 21.00
13 1.00 2.18 3.67 5.71 9.00 16.00 49.00
14 1.00 2.17 3.60 5.50 8.33 13.50 28.00
15 1.00 2.15 3.55 5.33 7.86 12.00 21.00 64.00
16 1.00 2.14 3.50 5.20 7.50 11.00 17.50 36.00

3 -9 6 PCI Design Handbook/Fifth Edition


Figure 3.12.20 Equivalent-volum e change strains for typical continuous building frames (millionths)
Prestressed members (P/A = € 0 0 psi)

..
Normal weight concrete Lightweight concrete
Ave. RrH. (from map) Ave. R.Hr (from map)
Temp, zone
(fronrmap) 40 50 60 70 80 40 50 60 70 80
Heated buildings
0 110 . too 91 81 72 116 toe 97 87 77
10 130 120 111 ' 101 92 133 123 113 104 94
20 150 140 131 121 112 150 - 140 130 120 110
30 170 160 151 141 132 166 156 147 137 127
40 190 180 171 161 152 183 173 163 154 144
50 210 200 191 181 172 200 190 180 170 160
60 230 220 211 201 192 216 206 197 187 177
70 250 240 231 221 212 233 223 213 204 194
80 270 260 251 241 232 250 240 230 220 210
90 290 280 271 261 252 266 256 247 237 227
100 310 300 291 281 272 283 273 263 254 244
Unheatec structures
0 110 100 91 81 72 116 106 97 87 77
10 140 130 121 111 102 141 131 122 112 102
20 170 160 151 141 132 166 156 147 137 127
30 200 190 181 171 162 191 181 172 162 t52
40 230 220 211 201 192 216 206 197 187 177
50 260 250 241 231 222 241 231 222 212 202
60 290 280 271 261 252 266 256 247 237 227
70 320 310 301 291 282 291 281 272 262 252
80 350 340 331 321 312 316 306 297 287 277
90 380 370 361 351 342 341 331 322 312 302
100 410 400 391 381 372 366 356 347 337 327

Figure 3.12.21 Equivalent volume change strains for typical continuous building frames (millionths)
Non-prestressed members
Normal weight concrete Lightweight concrete
Ave. R.H. (from map) Ave. R.H. (from map)
Temp, zone
(from map) 40 50 60 70 80 40 50 60 70 80
Heated buildings
0 59 53 47 41 35 59 53 47 41 35
10 79 73 67 61 55 76 70 64 58 52
20 99 93 87 81 75 92 86 80 75 69
30 119 113 107 101 95 109 103 97 91 85
40 139 133 127 121 115 126 120 114 108 102
50 159 153- 147 141 135 142 136 130 125 119
60 179 173 167 161 155 159 153 147 141 135
70 199 193 187 181 t75 176 170 164 158 152
80 219 213 207 201 195 192 186 180 175 169
90 239 233 227 221 215 209 203 197 191 185
100 259 253 247 241 235 226 220 214 208 202
Unheatec structures
0 59 53 47 41 35 59 53 47 41 35
10 89 83 77 71 65 84 78 72 66 60
20 119 113 107 101 95 109 103 97 91 85
30 149 143 137 131 125 134 128 122 116 110
40 179 173 167 161 155 159 153 147 141 135
50 209 203 197 191 185 184 178 172 166 160
60 239 233 227 221 215 209 203 197 191 185
70 269 263 257 251 245 234 228 222 216 210
80 299 293 287 281 275 259 253 247 241 235
90 329 323 317 311 305 284 278 272 266 260
100 359 353 347 341 335 309 303 297 291 285

PCI Design Handbook/Fifth Edition 3 -9 7


fig u re 3.12.22 Coefficients k<and km ter forces and moments caused b y volum e change restraint forces

S e a Figure 3.12.23 for notation

Values of Values
No. Kr = *f km
of B ase
2nd floor 3rd floor 4th
Stories Fixity Base
£ E elc/h s Fi f2 f3 f4 M1 M a. M2u M3l Msu m 4

Fixed 3.0 3.0 3.0 : 0


0
Pinned 0 0 0 a
Fixed 6.0 6.0 4.0 2.0 -
0.5
Pinned 1.2 1.2 0 1.2
Fixed 7.5 7.5 4.5 3.0 -
1 1.0
Pinned 1.7 1.7 0 1.7
Fixed 9.0 9.0 5.0 4.0
2.0
Pinned 2.2 2.2 0 2.2

4.0 Fixed 10.1 10.1 5.4 4.7


or more Pinned 2.5 2.5 0 2.5
Fixed 6.8 9.4 2.6 4.3 2.6 2.6 0
0
Pinned 0 3.0 1.5 0 1.5 1.5 0
Fixed 8.1 10.7 2.6 4.7 3.4 2.1 0.4
0.5
Pinned 1.9 3.4 1.4 0 1.9 1.2 0.2
Fixed 8.9 11.2 2.3 4.9 3.9 1.8 0.5
2 1.0
Pinned 2.1 3.4 1.3 0 2.1 1.0 0.3
Fixed 9.7 11.6 1.9 5.2 4.5 1.4 0.5
2.0
Pinned 2.4 3.4 1.0 0 2.4 0.8 0.3

4.0 Fixed 10.4 11.9 1.4 5.5 5.0 1.0 0.4


or more Pinned 2.6 3.4 0.8 0 2.6 0.5 0.2
Fixed 7.1 10.6 4.1 0.7 4.4 2.8 2.8 0.7 0.7 0
0
Pinned 1.6 3.6 2.4 0.4 0 1.6 1.6 0.4 0.4 0
Fixed 8.2 11.1 3.5 0.5 4.7 3.5 2.2 0.7 0.4 0.09
0.5
Pinned 1.9 3.6 1.9 0.3 0 1.9 1.2 0.4 0.2 0.05

3 Fixed 8.9 11.4 2.9 0.4 5.0 3.9 1.9 0.7 0.3 0.09
1.0
or more Pinned 2.2 3.5 1.6 0.2 0 2.2 1.0 0.4 0.2 0.05
Fixed 9.7 11.7 2.2 0.2 5.2 4.7 1.4 0.6 0.2 0.06
2.0
Pinned 2.4 3.5 1.2 0.1 0 2.4 0.8 0.3 0.1 0.03

4.0 Fixed 10.4 11.9 1.5 0.04 5.5 5.0 1.0 0.5 0.04 0.01
or more Pinned 2.6 3.4 0.8 0.02 0 2.6 0.5 0.2 0.02 0.00

3 -9 8 PCI Design Handbook/Fifth Edition


-Figure 3.12.23 Use o f Figure 3.12.22

4TH FLOQR

3RD FLOOR

2ND FLOOR

BASE

Ft = k,kbAiEclc/h |

Mi = k^Eclo/h*

WHERE: 6e = EQUIVALENT UNIT STRAIN (SEE SECT. 3.3)


fs = DISTANCE FROM COLUMN TO CENTER OF STIFFNESS
Fj = Ft , F2, ETC., AS SHOWN ABOVE
kj.km = COEFFICIENTS FROM FIGURE 3.12.22

kb = M nn ^ 2 J jjj ) ( ° R F R O M F I G U R E 3 - 1 2 -1 9 )

n = NUMBER OF BAYS
i = AS SHOWN IN FIGURE 3.8.5
Ec = MODULUS OF ELASTICITY OF THE COLUMN CONCRETE
lc = MOMENT OF INERTIA OF THE COLUMN

PCI Design Handbook/Fifth Edition 3 -9 9


3.13 References cluding Earthquake Resistance,” Technical
Report No. 2, Precast/Prestressed Concrete ln-
1. Branson, Dan E., “Deformation of Concrete
stttuie, Voi. 27, No.3,-Chicago, IL, May-June
Structures,” McGraw-Hill International- Book-
1982.
G o, -New York, NY, 1977.
14. Cioughr D.P., “Design of Connections-for Pre­
2. PCICommittee on Design Handbook, “Volume
cast Prestressed Concrete Buildings for the Ef­
Changes in Precast, Prestressed Concrete
fects of Earthquake,” Technical Report No. 5,
Structures,” PCI Journal, V. 22, No. 5, Septem-
Precast/Prestressed Concrete Institute, Chica­
ber-O ctober 1977.
go, IL, 1986.
3. Nathan, Noel D., “Rational Analysis and Design
15. “Design and Typical Details of Connections for
of Prestressed Concrete Beam Columns and
Precast and Prestressed Concrete,” Second
Wall Panels,” PCI Journal, V. 30, No. 3, M ay-
Edition, MNL-123-88, Precast/Prestressed
June 1985.
Concrete Institute, Chicago, IL, 1988.
4. PCI Committee on Prestressed Concrete Col­
16. “Parking Structures: Recommended Practice
umns, “Recommended Practice for the Design
for Design and Construction,” MNL-129-88,
of Prestressed Concrete Columns and Walls,”
Precast/Prestressed Concrete Institute, Chica­
PCI Journal, V. 33, No. 4, July-August 1988.
go, IL, 1988.
5. “Notes on A C I318-95, Building Code Require­
17. International Conference of Building Officials,
ments for Reinforced Concrete with Design Ap­
“Uniform Building Code,” Vol. 2,1994.
plications,” Portland Cement Association,
Skokie, IL, 1996.
18. “Manual of Steel Construction, Allowable
Stress Design,” Ninth Edition, American Insti­
6. “Commentary on Building Code Requirements
tute of Steel Construction, Chicago, IL, 1989.
for Reinforced Concrete,” ACI 318R-95, Ameri­
can Concrete Institute, Farmington Hills, MJ,
19. “Uniform Building Code,” International Confer­
1995.
ence of Building Officials, 1997 Edition.
7. Speyer, Irwin J., “Considerations for the De­
sign of Precast Concrete Bearing Wall Build­
20. “Recommended Lateral Force Requirements
and Commentary,” (SEAOC Blue Book) Struc­
ings to Withstand Abnormat Loads,” PCI Jour­
tural Engineers Association of California, 1996
nal, V. 21, No. 2, March-April 1976.
Edition.
8. “Response of Multistory Concrete Structures to
Lateral Forces,” Special Publication SP-36, 21. “Recommended Provision for the Develop­
American Concrete Institute, Farmington Hills, ment of Seismic Regulations for New Build­
Ml, 1973. ings,” The National Earthquake Hazard Reduc­
tion Program (NEHRP), 1997 Edition.
9. ACI Committee 442, “Response of Buildings to
Lateral Forces,” Journal o f the American 22. “Minimum Design Loads for Buildings and Oth­
Concrete Institute, V. 68, No. 2, February 1971. er Structures,” ASCE 7, American Society of
Civil Engineers, Reston, VA., 1998 Edition.
10. “Design of Combined Frames and Shear
Walls,” Advanced Engineering Bulletin No. 14, 23. “International Building Code (IBC),” to be pub­
Portland Cement Association, Skokie, IL, 1965. lished in 2000.

11. Fintel, Mark (Editor), “Handbook of Concrete 24. PCI Ad hoc Committee on Precast Walls (Prin­
Engineering,” Second Edition, Van Nostrand cipal Author, Ned M. Cleland), “Design for Lat­
Reinhold Company, New York, NY, 1985. eral Force Restraints with Precast Concrete
Shearwalls,” PCI Journal, V. 42, No. 5, Septem­
12. MacLeod, I.A., “Shearwall-Frame Interaction, A ber-O ctober 1997.
Design Aid,” Portland Cement Association,
Skokie, IL, April 1970. 25. Aswad, Alex and Mackertick, Seroj, “ Lateral
Deformations of Perforated Shear Walls for Low
13. Martin, L.D., and Korkosz, W.J., “Connections and Mid-Rise Buildings,” PCI Journal, V. 42,
for Precast Prestressed Concrete Buildings, In­ No. 1, January-February 1997.

3 -1 0 0 PCI Design HandbooK/Fifth Edition


CHAPTER 4
CONCRETE COMPONENTS
4.1 General .............................. ............ . ................................................................ 4 - 3
4.1.1 N otation....................................................................................................... 4 - 3
4.1.2 Introduction ............................................................................................... 4 - 7

4.2 Flexure................................................................................................................... 4 - 7
4.2.1 Strength Design . ........... , .................................................................. 4 - 8
4.2.1.1 Depth of Stress B lo c k ........................................................... 4 - 8
4.2.1.2 Flanged Elements .................................................................. 4 - 8
4.2.1.3 Limitations on Reinforcement ............. ................................ 4 - 8
4.2.1.4 Critical S e c tio n ........................................................................ 4 - 9
4.2.1.5 Analysis Using Code Equations .......................................... 4 - 9
4.2.1 .6 Analysis Using Strain Compatibility .................................... 4 - 9
4.2.1.7 Analysis Using Appendix B—ACI 318-95 .........................4 -1 1
4.2.1 .8 Use of Design Aids ............................................................. 4 -1 2
4.2.2 Service Load Design ......................................................................... 4 -2 0
4.2.2.1 Non-Prestressed Element D esign...................................... 4 -2 0
4.2.2.2 Prestressed Element Design .............................................. 4 -2 2
4.2.3 Prestress Transfer and Strand Development ................................ 4 -2 6
4.2.4 End Stresses at Transfer ................................................................. 4 -2 9
4.2.5 Bending of Asymmetrical S ections.................................................. 4 -3 0

4.3 S h e a r................................................................................................................... 4 -3 0
4.3.1 Shear Resistance of Non-Prestressed Concrete ............................. 4 -3 1
4.3.2 Shear Resistance of Prestressed Concrete Members ................. 4 -3 1
4.3.3 Design Using Design Aids ............................................................... 4 -3 3
4.3.4 Shear Reinforcement......................................................................... 4 -3 4
4.3.5 Horizontal Shear Transfer in Composite Members ....................... 4 -3 5
4.3.6 Shear-Friction .................................................................................... 4 -3 8

4.4 Torsion ................................................................................................................ 4 -3 9

4.5 Beams with Ledges .......................................................................................... 4 -4 6


4.5.1 Shear Strength of the Ledge ........................................................... 4 -4 6
4.5.2 Transverse (Cantilever) Bending of the L e d g e ............................... 4 -4 6
4.5.3 Longitudinal Bending of the Ledge.................................................. 4 -4 6
4.5.4 Attachment of the Ledge to the W e b .............................................. 4 -4 6
4.5.5 Out-of-Plane Bending Near Beam End .......................................... 4 -4 7
4.5.6 Pocketed Beams .............................................................................. 4 -5 2

4.6 Bearing ................................................................................................................ 4 -5 7


4.6.1 Bearing on Plain C o n cre te ............................................................... 4 -5 7
4.6.2 Reinforced Concrete B earing........................................................... 4 -5 8
4.6.3 Dapped-End B earing......................................................................... 4 -5 9
4.6.3.1 Flexure and Axial Tension in the Extended End ............. 4 -5 9
4.6.3.2 Direct Shear ......................................................................... 4 -6 0
4.6.3.3 Diagonal Tension at Re-entrant C o rn e r.............................4 -6 0
4.6.3.4 Diagonal Tension in the Extended E n d .......................... 4 -6 0
4.6.5.5 Anchorage of Reinforcement.............................................. 4 -6 1
4.6.3.6 Other Considerations ......................................................... 4 -6 1

PCI Design Handbook/FIfth Edition 4 -1


4.7“ lo s s of Prestress............................................................................................... 4 -6 3
4.7.1 Sources o f Stress L o s s ........................................_............... ..........4 - 6 3
4.7.2 Range ofVafues for Total Loss — ............................... _ ..............4 -6 4
4 .7 6 fstim ating Prestress Loss ............................ .................................. 4 -6 4
47774" Critical Locations .................................................................... 4—65

4.6 Camber and Deflection ................................................................................... 4 -6 7


46.4 Initial C a m b e r................................................................................... 4 -6 7
4.8.2 Elastic Deflections .............. 4 -6 6
4.8.2 Bilinear Behavior .................................................................................4-68-
46.4 Effective Moment of Inertia............................................................... 4 -7 0
4.8.5 Long-Term Camber/Deflection ........................................................ 4-71

4.9 CompressionMembers .................. 4 -7 2


4.9.1 Strength Design of PrecastConcrete Compression Members . . . 4 -7 2
4.9.2" Slenderness Effects.............................................. 4 -7 7
4.9.3 Service Load Stresses........... ............................................... 4—77
4.9.4 Effective Width of Wall Panels......................................................... 4 -7 7
4.9.5 Varying Section Propertiesof Compression Members ................ 4 -7 7
4.9.6 Piles ................................................................................................... 4 -7 8
4.9.6.1 Strength Under Axial L o a d ................— ...................... 4 -7 9
4.96.2 Combined Bending and Axial L o a d ................................. 4 -7 9

4.10 Special Considerations .......................................................... 4-81


4.10.1 Load Distribution .............................................................................. 4-81
4.10.2 Openings through D e c k s ................................................................. 4 -8 2
4.10.3 Openings through W ebs................................................................... 4 -8 3
4.10.4 Continuity........................................................................................... 4 -8 3
4.10.5 Cantilevers......................................................................................... 4 -8 3

4.11 References ........................................................................................................ 4 -8 5

4.12 Design Aids ...................................................................................... 4 -8 7

4 -2 PCI Design Handbook/Rfth Edition


DESIGN O F PRECAST AND PRESTRESSED CONCRETE COMPONENTS

4.1 General Ag area of-shear reinforcement

Av area o f diagonal tension reinforce­


Notation ment-in dapped end
4.1.1
= cross-sectional area Ayf arear of shear-friction reinforcement
A

average effective area around one Aw area of web in a flanged section


A
reinforcing bar A we area of steel in horizontal direction at
= cross-sectional area of the equiva­ beam end for torsional equilibrium
Acomp
lent rectangular stress block Awy area of steel in vertical direction at
beam end for torsional equilibrium
Acp area enclosed by outside perimeter
of concrete cross section Ai loaded area

Acr = area of crack interface a2 maximum area of the portion of the


support that is geometrically similar
Acs
= area of horizontal shear ties
to and concentric with the loaded
Af = in a flanged section, area of flange area
outside the web
a shear span
Ag gross area of concrete cross section a depth of equivalent rectangular
Ah = shear-friction steel across vertical stress block
crack at dapped ends b width of compression or tension face
A, = total area of longitudinal reinforce­ of member
ment to resist torsion b< ledger beam width at ledge
A, = area of longitudinal reinforcement to width of bearing area under concen­
b,
resist bending in ledges (see Eq. trated loads on ledges
4.5.5)
bv width of interface surface in a com­
An area of reinforcement required to re­ posite member (Sect. 4.3.5)
sist axial tension
bw web width
Ao gross area enclosed by shear flow
C coefficient as defined in section used
path
(with subscripts)
Aoh = area enclosed by centerline of the c compressive force
outermost closed transverse torsion­
al reinforcement Cc compressive force capacity of com­
posite topping
Aps, ApS = area of prestressed reinforcement
Cr reduction coefficient (see Eq. 4.6.1)
Apw portion of prestressed reinforcement
CR creep of concrete
to develop web strength
c distance from extreme compression
As = area of non-prestressed tension rein­
fiber to neutral axis
forcement
D distance from extreme compression
As, min minimum amount of flexural rein­
fiber to centroid of tension reinforce­
forcement
ment in a dapped end member
a; area of non-prestressed compres­
d distance from extreme compression
sion reinforcement
fiber to centroid of longitudinal ten­
Ash = area of vertical reinforcement for hor­ sion reinforcement, but need not be
izontal or diagonal cracks less than 0.8 h for prestressed mem­
bers (dp is used for prestressed
A, = area of one leg of closed stirrup
members when a distinction from d
Atop = effective area of cast-in-place com­ for non-prestressed reinforcement is
posite topping relevant)

PCI Design Handbook/Fifth Edition 4 -3


cr — distance from extreme compression V
1 CC specified compressive strength of
fiber to centroidof compression rein­ composite topping
forcement (dp is used for pre­ fr —
*cds ” concrete-stress at center of gravity of
stressed members when a distinc­
prestressing force due to aH perma­
tion from d' for non-prestressed nent (dead) loads not used in com­
reinforcement is relevant) puting fcir
db = nominal diameter of reinforcing bar compressive strength of concrete at
f$
or prestressing strand time of initial prestress
dc concrete thickness to the center of concrete stress at center of gravity of
fcir —
reinforcement closest to the tension prestressing force immediately after
face transfer
de = distance from center of load to beam
fc splitting tensile strength of light­
end weight concrete
df = depth of centroid of Af reinforcement stress due to service dead load
fd
in ledger beam ledges
f. total load stress in excess of fr
d^ dp = distance from extreme compression
fiberto centroid of prestressing steel stress due to service live load
in tension and compression zones fpc — compressive stress in concrete at
respectively centroid of cross section due to pre­
distance from extreme compression stress (after allowance for all pre­
dt =
fiber to extreme tension steel stress losses)

= depth of Aw< and Aw reinforcement fpd = stress in prestressed reinforcement


dw
from outside face of ledger beam limited by strand development

= modulus of elasticity of concrete fpe ~ compressive stress in concrete due


Ec
to effective prestress forces only (af­
Ed — modulus of elasticity of concrete at ter allowance for all prestress losses)
time of initial prestress at extreme fiber of section where ten­
ES = elastic shortening sile stress is caused by externally ap­
= plied loads
Eps modulus of elasticity of prestressed
reinforcement fpi = compressive stress in concrete due
to initial prestress force
Es = modulus of elasticity of steel
f'psi'ps
f' = stress in prestressed reinforcement
e eccentricity of design load or pre­
at nominal strength of member
stressing force parallel to axis mea­
sured from the centroid of the sec­ fpu ~ ultimate strength of prestressing
tion steel
e' = distance between c.g. of strand at fpy = specified yield strength of prestress-
end and c.g of strand at lowest point tng steel
= 6c — 6e
fr modulus of rupture of concrete
©c eccentricity of prestressing force
fr' allowable flexural tension, computed
from the centroid of the section at the
using gross concrete section
center of the span
u ; stress in non-prestressed reinforce­
©e =5 eccentricity of prestressing force
ment
from the centroid of the section at the
end of the span fse = effective stress in prestressing steel
after losses
Fh =S horizontal shear force
ft stress in the top fiber of a cross sec­
fb stress in the bottom fiber of the cross
tion
section
ft tensile stress at extreme tension fiber
n = specified compressive strength of
concrete f« final calculated stress in the member

4 -4 PCI Design Handbook/Fifth Edition


speeified-yield strength of non-pre- M = service load moment
stresseef reinforcement M. = total moment at the section
yield strength of closed transverse M cr = cracking moment
torsional-reinforcement, psi
Md = moment due to service dead load
yield strength of longitudinal torsion­ (unfactored)
al reinforcement, psi
Ma
iwig = moment due to weight of member
total depth oha dapped end member (unfactored)
factored torsional equilibrium reac­ Me = moment due to service live load (un­
tions factored)
depth of member above dap Mmax = maximum factored moment at sec­
overall depth of a non-dapped mem­ tion due to externally applied loads
ber Mn = nominal moment strength of a sec­
unsupported length of a pile tion

depth of flange M nb = nominal moment strength under bal­


anced conditions
ledger beam depth of ledge
ful
Mne = moment due to beam self weight
height of pocket in a pocketed span­ plus dead loads applied before com­
drel beam posite action
distance between torsional equilibri­
M0 = nominal moment strength of a com­
um reactions
pression member with zero axial
distance from centroid of tensile rein­ load
forcement to neutral axis
M sd = moment due to superimposed dead
distance from extreme tension fiber load plus sustained live load (unfac­
to neutral axis tored)
moment of inertia Mtop = moment due to topping (unfactored)
moment of inertia of cracked section Mu = applied factored moment at a sec­
transformed to concrete tion
effective moment of inertia for com­ m = modification factor for hanger steel
putation of deflection calculation
equivalent constant moment of iner­ N = unfactored axial load
tia in members with varying cross = factored horizontal or axial force
Nu
sections
n = modular ratio = E s/E c
moment of inertia of gross section
n = number of reinforcing bars
coefficient as defined in Sect. 4.7.3
D
r = prestress force after losses
factors used in service load design
(Sect. 4.2.2) = initial prestress force

coefficient as defined in Sect. 4.7.3 Pn = axial load nominal strength of a com­


(with subscripts) pression member at given eccentric­
ity
design coefficient (see Figure
4.12.1) Pnb = axial load nominal strength under
balanced conditions
design coefficient (see Figure
4.12.2) Po = prestress force at transfer

span length Po = axial load nominal strength of a com­


pression member with zero eccen­
development length
tricity
strand transfer length
Pep = outside perimeter of the concrete
horizontal shear length as defined in cross section
Figure 4.3.5

PCI Design Handbook/Fifth Edition 4 -5


Ph perimeter of centerline erf outermost Vn = nominal shear strength
closed transverse torsional rein­
Vp vertical component o f the effective
forcement-
prestress force at the section consid­
RE = relaxation of tendons ered
R .H . = average ambient relative humidity Vs = nominal shear strength provided by
the shear reinforcement
r = radius of gyration
v /s = volume-surface ratio
S = section modulus-
Vu = factored shear force at section
Sb

section modulus with respect to the
bottom fiber of the precast section w = maximum crack width at extreme
tension fiber
Sbc = section modulus with respect to the
bottom fiber of a composite section w = unfactored load per unit length of
beam or per unit area of slab
S, = section modulus with respect to the
top fiber of a cross section Wc = unit weight of concrete
SH = shrinkage of concrete wd = unfactored dead load per unit length
s shear or torsion reinforcement spac­ W, = unfactored live load per unit length
ing in a direction parallel to the longi­
Wsd = dead load due to superimposed
tudinal reinforcement loading plus sustained live load
s = spacing of concentrated loads on ~ unfactored total load per unit length

ledger beam ledge
= w d+ w f
T = tensile force - factored total load per unit length or
Wu
T = torsion area
TL = total prestress loss X = distance from support to point being
investigated
Tn = nominal torsional moment strength
y' = distance from top to e g. of Acomp
Tu = factored torsional moment on a sec­
tion yb ~ distance from bottom fiber to center
of gravity of the section
t = thickness (used for various parts of
members with subscripts) ys distance from centroid of pre­
stressed reinforcement to bottom fi­
Vc = nominal shear strength provided by =
ber
the concrete
yt = distance from centroid of gross sec­
Vci nominal shear strength provided by
tion to extreme fiber in tension
concrete when diagonal cracking is
the result of combined shear and yt = distance from top fiber to center of
moment gravity of the section

Vow nominal shear strength provided by z = quantity limiting distribution of flexu­


concrete when diagonal cracking is ral reinforcement (Sect. 4.2.2.1)
I
the result of excessive principal ten­ a distance from end of member to
sile stress in the web strand depression point (Figure
vd = dead load shear (unfactored) 4.12.10)
Vi factored shear force at section due to Pi = factor defined in Sect. 4.2.1
externally applied loads occurring si­ 0 = angle of compression diagonals in
multaneously With Mmax truss analogy for torsion
vf = live load shear (unfactored) A = deflection (with subscripts)

£c = concrete strain

4 -6 PCI Design Handbook/Fifth Edition


^ultimate concrete strain a)max = maximum permissible ®
strain in prestressing_ steel corre­ — Pplps/^c Apsfps/bdpfc
sponding tO fpSfpdfps rrjpu Pptpu/^c Apsfpu/bcl pfc
strain in non-prestressed tension-re­ cow^pw^w— reinforcement- indices^for flanged
inforcement sections computed as for®, wp, and
strain in non-prestressed compres­ co' except that b shall be the web-
sion reinforcement width, and reinforcement area shall
be that required to develop com­
strain, in prestressing steef' caused
pressive strength of web only
by external loads — Bps — Ese
strain in prestressing steel after
losses
net tensile strain in extreme tension
steel
4.1.2 Introduction
maximum allowable strain in non-
prestressed reinforcement This chapter of the Handbook provides a summa­
ry of theory and procedures used in the design of pre­
a conversion factor for lightweight
cast and prestressed concrete components. Designs
concrete
are based on the provisions o f “Building Code Re­
multiplier applied to initial deflection quirements for Structural Concrete (ACI 318-95) [1],
factor for type of prestressing tendon which is referred to as “the Code” or “ACI 318” in the
(see ACI Code Sect. 18.0 for values) Handbook. Occasionally, standard design practice
may require interpretation of the Code. This has been
factor used in designing hanger rein­
done in Sect. 10.5 of the Handbook.
forcement (see Table 4.5.1) Two different phases must be considered in
shear-friction coefficient designing precast concrete components: (1) the
manufacturing through erection phase and (2) the in-
effective shear-friction coefficient
service conditions. The designer is referred to Chap­
time-dependent factor for sustained ter 5 for the first phase. This chapter is concerned
loads with the in-service conditions.
As/bd = ratio of non-prestressed The load tables in Chapter 2 will not provide all the
tension reinforcement design data necessary. In most cases, the engineer
will select standard sections and typical details, with
A j/b d = ratio of non-prestressed
the detailed design carried out by the precast con­
compression reinforcement
crete producer. The engineer of record should verify
ApS/bdp = ratio of prestressed rein­ that the section selected is capable of satisfying both
forcement strength and performance criteria for the use in­
tended. In cases where the engineer of record under­
As/bwd = ratio of non-prestressed
takes the complete design responsibility, consulta­
tension reinforcement based on web
tion with producers in the area w ill ensure
width
compatibility of design with production and will result
non-prestressed reinforcement ratio in optimum quality and economy.
producing balanced strain condi­
tions
maximum reinforcement ratio for
non-prestressed members 4.2 Flexure
strength reduction factor Design for flexure in accordance with the Code re­
quires that precast and prestressed concrete mem­
pfy/fc = Asfy/bdfc
bers be checked for both design strength and service
p'fy/f; = a; fy/b d f; load. Members reinforced with non-prestressed steel
require service load checks in accordance with Code
factor used in Figure 4.12.1 Sect. 10.6.4. Also see section 4.2.2 of this handbook.

PCI Design Handbook/Fifth Edition 4 -7


4.2.T Strength Design mations for it may be made to find" the nominal
strength. If compression reinforcement is not pres­
Strength design is based on solution o f the equa­
ent, the nominal- strength can be found using-the
tions o f equilibrium, normally using the rectangular
Code equations shown in Figure 4.2.2 or by strain
stress block in accordance with Sect. 10.2.7 of. the
compatibility.
Code (see Figure 4.2.1 y. The stress in the prestress­
ing steel at nominal strength, fps, ca n be determined
by-strain compatibility [2] or by the approximate 4.2.1.3 Limitations on Reinforcement
equation given in the Code (Eq. 18-3). In carrying out
For non-prestressed flexural elements, except
strain compatibility analysis, the manufacturer’s
slabs of uniform thickness, the minimum reinforce­
stress-strain relations may be used. Alternatively, the
ment required, is:
idealized stress-strain equations given in Design Aid
11.2.8 may be used. ^ 200bwd
A
^s.mn 3^bw d (Eq. 4.2.2)
For elements with compression reinforcement, the
Ty
nominal strength can be calculated by assuming that
the compression reinforcement yields. This assump­ For T-sections with flanges in tension, \ min is the
tion should be subsequently verified from the strain smaller of that determined by Eq. 4.2.2, where b^ is
diagram. The designer will normally choose a section the width of the flange, or by:
and reinforcement and then determine if it meets the
basic design strength requirement:
As.min — ^ ^b „ d (Eq. 4.2.3)
4>Mn > Mu

A flow chart illustrating the calculation of the nomi­ where:


nal strength of flexural elements is given in Figure bw is the width of the web.
4.2.2.
The above limits do not apply if the area of tensile
reinforcement provided is % greater than that re­
4.2.1.1 Depth of Stress Block
quired by analysis.
The depth “a” of the rectangular stress block is re­ For slabs, the minimum flexural reinforcement is
lated to the depth to the neutral axis “c” by the equa­ that amount required for shrinkage and temperature
tion: reinforcement, with a maximum spacing not exceed­
ing three times the slab thickness or 18 in., whichever
a = frc
is smaller.
where:
ft fi, psi The maximum reinforcement ratio for non-pre­
stressed elements is limited to 0.75 times the bal­
0.85 3000 anced reinforcement ratio:
0.85 4000
Pmax = 0 . 7 5 Pb (ECT 4 -2 ’4 )
0.80 5000
0.75 6000
0.70 7000
0.65 8000 and higher

4.2.1.2 Flanged Elements

The equations for nominal strength given in Figure


4.2.1 apply to rectangular cross sections and flanged
sections in which the stress block lies entirely within
the depth of the flange hf. The depth of the stress
block “a”, is obtained from the first equation of equi­
librium in Figure 4.2.1:

ApSfpS + ASfy — As f)
(Eq. 4.2.1)
0.85flb

If a > h{, and compression reinforcement is pres­


ent, use of strain compatibility or reasonable approxi­

4 -8 PCI Design Handbook/Fifth Edition


where: 0.4€. For straight strands, the critical section will b ea t
0.85ft f; I 87,000 V mid-span, but if some strands are debonded nearthe
Pb * fy I 87,000 + f j end, an additional criticalsection may occur near the
end of the debonded length as shown in Figure 4.213.
Substituting the equation for to yields: The^presence of concentrated loads or non-pre­
stressed reinforcement may alter the location of the
critical section. In such eases, computer programs
Wmax
with the capability of checking the capacity at short
87,000 intervals along the member length can be used to ex­
= 0.64ft (Eq. 4.2.5)
87,000 + fy pedite analysis.

For prestressed elements, the Code requires that the


total prestressed and non-prestressed reinforcement 4.2.1.5 Analysis Using Code Equations
be adequate to develop a factored load at least 1.2
Figure 4.2.2 essentially outlines the design proce­
times the cracking load, except for flexural members
dures using the Code equations for prestressed and
with shear and flexural strength at least twice that re­
partially prestressed members. If compression rein­
quired by analysis. The cracking moment, Me, may
forcement is present, the Code requires certain
be calculated by:
checks to assure that the stress in the compression
reinforcement is at its yield strength. In computing
Mcr = S be E + E s + f if any compression reinforcement is taken into ac­
A + Sb r count, the term:
(Eq. 4.2.6)

where:

Mnc= Moment due to beam self weight plus dead


shall be taken not less than 0.17 and d' shall be no
loads applied before composite action
greater than 0.15dp. Alternatively, the yielding of the
Sb = Section modulus with respect to the bottom compression reinforcement is ensured if Eq. 4.2.7 is
fiber of the precast section satisfied:
Sbc = Section modulus with respect to the bottom Apsfps + A 5fy - A ; fy
>
fiber of a composite section bd
fr = Modulus of rupture, usually taken as 7.5k
No upper limit is placed on the reinforcement for 87,000
0.85ftfc ^ (Eq. 4.2.7)
prestressed elements. However, when either: 87,000 - fy

Wp, [cop + d /d p(o) - co')], or

|(0pW+ d /d p((ow (ow )J, or

0.85a/dp > 0.36ft 4.2.1.6 Analysis Using Strain Compatibility

Strain compatibility is recognized as being the


the nominal strength, as shown in Figure 4.2.2, is cal­ more accurate alternative method to the Code equa­
culated based on the compression force of the mo­ tions. The procedure consists of assuming the loca­
ment couple. tion of the neutral axis, computing the strains in the
prestressed and non-prestressed reinforcement, and
establishing the depth of the stress block. Knowing
4.2.1.4 Critical Section
the stress-strain relationship for the reinforcement,
For simply supported, uniformly loaded, prismatic and assuming that the maximum strain in the con­
non-prestressed elements, the critical section for flex­ crete is 0.003, the forces in the reinforcement and in
ural design will occur at mid-span. For uniformly the concrete are determined and the sum of com­
loaded prestressed elements, in order to reduce the pression and tension forces is computed. If neces­
end stresses at release some strands are often de­ sary, the neutral axis location is moved on a trial and
pressed near mid-span, or debonded for a length error basis until the sum of forces is zero. The mo­
near the ends. For strands with a single point depres­ m ent of these forces is then com puted to obtain the
sion, the critical section can usually be assumed at nominal strength of the section.

PCI Design Handbook/Fifth Edition 4 -9


Figure 4.2.2 Flow chart for nominal strength calculations for flexure, notusincrAppendix^Lof ACI
318-95 ______________ ______________

a. This analysis may be based on either actual stress-strain curves or the idealized curve given in Design Aid-11.2.5. The latter results in
fps values given in Figure 4.12.3.

4 -1 0 PCI Design Handbook/Rfth Edition


Figure 4.2.3 Critical section for flexural design

UNIFORM LOAD UNIFORM LOAD

1 1 I 1 H 1 I I 1-1 n n
prestressed . - PRESTRESSED
REINFORCEMENT
_£ REINFORCEMENT

STRAND DEVELOPMENT

(A) BEAM W ITH STRANDS DEPRESSED (B) BEAM W ITH STRAIG HT STR A N D S-
AT M ID P O IN T -U N IF O R M LOAD SO M E DEBONDED NEAR END

4 .2 .1 .7 Analysis Using Appendix B -A C i 318-95 Compression- and tension-controlled sections are


defined in terms of the net tensile strain (exclusive of
ACI 318-95 contains a new Appendix B, Unified
prestress) at nominal strength in the steel farthest
Design Provisions for Reinforced and Prestressed
from the extreme compression fiber. A compression-
Concrete Flexural and Compression Members. This
controlled section is defined as one having a maxi­
appendix does not alter the nominal strength com­
mum net tensile strain in the steel of 0.002 or less (for
putations. It unifies reinforcement limits for both pre­
Grade 60 and prestressing steel), and a tension-con­
stressed and non-prestressed sections, and defines
trolled section is defined as one having a maximum
the capacity reduction factor, cp, in a way that is appli­
net tensile strain in the steel of 0.005 or more.
cable to both flexural and compression members.
The net tensile strain limits of 0.002 and 0.005 may
The provisions of Appendix B are most useful in
also be expressed in terms of the c/dt ratio when c is
the following cases:
the depth to the neutral axis and d, is the distance
1. Tension-controlled columns. The use of Ap­ from the extreme compression fiber to the tension
pendix B eliminates the kink in the design steel farthest from that fiber. Fig 4.2.4 shows <|) as a
strength interaction curve. function of et and c /d t.
2. Sections with multiple layers of steel. For rectangular sections with one layer of tension
3. Sections with both prestressing steel and con­ steel, the net tensile strain limit for tension controlled
ventional reinforcement. sections may also be stated in terms of p /p b or w.
4. Sections of complex shape, for which it is diffi­ The net tensile strain limit of 0.005 corresponds to
cult to properly define b and d for computing p p /p b = 0.63 and co = 0.32(3,. These limits for rectan­
and a). gular sections with one layer of tension steel are
The design of compression-controlled columns is slightly lower than those given in Chapters 10 and 18
not affected by Appendix B. The design of ordinary of the Code. But for sections with more than one layer
flexural members (prestressed and non-prestressed) of tension steel and for reinforced tee beams, Appen­
is not affected by Appendix B, except for those near dix B may allow the use of more tension steel and
the maximum reinforcement limits. The new provi­ higher flexural capacities than Chapters 10 and 18.
sions apply equally to beams and columns of rectan­ The provisions of Code Sect. 9.3.2 that define the
gular or non-rectangular section, with non-pre- capacity reduction factor, (j>, are also revised by Ap­
stressed or prestressed reinforcement, or both, and pendix B. In Sect. 9.3.2 there is a single factor for flex­
with one or many layers of steel. ure without axial load (0.90), and another factor for
Appendix B modifies Sects. 10.3.2, 10.3.3 and axial load and axial load combined with flexure (0.70
18.8.1 of the Code, which define the maximum rein­ or 0.75), with a transition based on the ratio of
forcement limit for flexural members. The concept of <j)Pn/( f' Ag). In B.9.3.2 this is replaced by the use of
flexural members is replaced by the concept of ten­ <)>= 0.90 for tension-controlled members and cj> =
sion-controlled members. The concept of compres­ 0.70 (or 0.75) for compression-controlled members,
sion-controlled flexural members is also created. also with a linear transition for intermediate cases.

PCI Design Handbook/Frfth Edition 4 -1 1


Figure 4.2.4 Variation of 4> with net tensile Rgure 4.2.6 showsrthe design procedures using
strain for Grade 60 reinforce­ Appendix B. lt ls essentially the same as that shown
ment and for prestressing steel8 in Figure 4.2.2. except that the check foran over-rein­
WITH SI LS 4>=0.65 + 50 forced section is replacedby the determination of
I
0:90- 4.2.1.8 Use of D esign A id s
Figs. 4.12.1 through 4.12:3 are provided to assist
0 .7 & in the strength design o f flexural m em b ers. Figure
0.70 4.12.1 can be used for members with prestressed or
non-prestressed reinforcement, or combinations
o
II

$ + 68£t
(partial prestressing). Note that to use this aid, it is
necessary to determine fps from some other source,
0.50
such as Eq. 18-3 of ACI 318-95 or Figure 4.12.3.
COMPRESSION TRANSITION TENSION
Figure 4.12.2 is for use only with fully prestressed
CONTROLLED CONTROLLED
members. The value of fps is determined by strain
compatibility in a manner similar to that used in Figure
STRAIN, Et = 0.002 0.005
4.12.3. The reduction factor, <j>, is included in the val­
c/dt = 0.600 0.375
ues of K'u. The Examples 4.2.1 through 4.2.4 illus­
ALTERNATIVE, AS FUNCTION^ OF c/d,
trate the use of these design aids.
<() = 0.356 + 0.204/(c/d,)
The use of Appendix B of the Code results in a
WITH SPIRALS 4> = 0.500 + 0.15/(c/d,)
slight decrease in the values given in Figure
a. See ACI 318-95 Figure RB.9.3.2
4.12.2, for (opuvalues around the reinforcement index
Because this change introduces new concepts, limit of 0.36f5i• Figure 4.2.5 shows how the values of
ACI Committee 318 decided to place it in an appendix Ky computed by Appendix B differ from those given
in the 1995 Code. Designers have the option of using in Figure 4.12.2, if allthe prestressing steel is concen­
the provisions in the body of the Code or the provi­ trated in a single layer. When prestressing strands
sions of Appendix B. If the appendix is used for the are in multiple layers (the usual case for high rein­
design of a given section, it must be used in its entire­ forcement indices), one may use the net tensile strain
ty- in the prestressing steel at the extreme depth in deter­
To use Appendix B, do the nominal strength cal­ mining ([). This has the effect of increasing K(, for high
culation in the usual manner. When doing the values of copu.
strength calculation, find either c /d t or et. Determine
the <]) factor from c/d, or et.
Exam ple 4.2.1 Use of Figure 4.12.1 for
Determination of Non-
Figure 4.2.5 Com parison between Appendix B Prestressed Reinforcement
(ACI 318-95) and Figure 4.12.2 Given:
for prestressed flexural m embers The ledger beam shown below.
Applied factored moment, Mp = 1460 kip-ft
fc = 5000 psi, normal weight concrete
d = 72 in.
fy = 60 ksi

Problem:
Find the amount of mild steel reinforcement, As,
required.

Solution:
Referring to Figure 4.12.1:

a; =0
is _ Mu/(j) 1460(12,000)/0.9
= 0.0939
u f; bd 2 5000(8) (72)2

4 -1 2 PCI Design Handbook/Fifth Edition


Problem:
8"
Find the required amount of prestressing steel.

Solution:
Referring terFigure-4- 12.2:
NOTE: HANGER, U u < q>Mn =-K'ubd 2/ 12,000 kip-ft
SHEAR AND TORSION
STEEL NOT SHOWN
Required KL =
M u(12,000) 600(12j000)
bd 2 16(21)2
=1020
for o)pu = 0.22, K'u = 1005

for copu = 0.23, Ku = 1041


1 '-4 "

therefore:
Required w = 0.10 < o)max = 0.302
1020 - 1005
COpu = 0 .2 2 + ■ (0.01>= 0.224
A _ wbdfc 0.10(8)(72)(5) 1041 - 1005
As fy ~ 60
_ci)pUb d pfc
A
Mps
= 4.80 in 2

Use 5 - #9; As = 5.00 in 2 _ 0.224(16)(21)(6)


270
3/5000
A s, min (8)(72) = 2.03 in2
60,000 = 1.67 in2

200bwd Use 12-V 2 in. diameter strands;


or — r — 1.92 in2
Aps = 1.84 in2

2.03 in2 < 5.00 in2 OK


Exam ple 4.2.3 Use of Figure 4.12.3— Values
Note: Detailing of reinforcement must provide for of fpt b y Stress-Strain
adequate crack control (see Sect. 4.2.2.1). Relationship— B onded Strand
Given:
Exam ple 4.2.2 Use of Figure 4.12.2 for 3 ft-4 in. x 8 in. hollow-core slab
Determination of Prestressing
Steel Requirem ents— Bonded 40" m"
Strand
Given:
PCI standard rectangular beam 16RB24 'fcfiQQDJOmQ' ~F 8"

Applied factored moment, Mu = 600 kip-ft


fc = 6000 psi normal weight concrete Concrete:
fpu = 270 ksi, low-relaxation strand fc =5000 psi normal weight concrete
16”
Prestressing Steel:
j , 8 - 3/ b in. diameter 270K low-relaxation strand
a Aps= 8(0.085)=0.68 in2

4 < *<
4
dp=21"
24”
Section Properties:

4*A * 4
4
4
A =
Sb = 381 in3
218 in2

4 • yb = 3.98 in.

PCI Design Handbook/Fifth Edition 4 -1 3


Figure 4.2.6 Flow chart for nominal strength calculations for flexure, using Appendix B of ACi 318-95

a. This analysis may be based on either actual stress-strain curves or the idealized curve given in Design Aid 11.2.5. The latter results in
fps values given in Figure 4.12.3.

b. With spirals, (j> = 0.50 + 0.15/ (c /d j > 0.75

4 -1 4 PCI Design Handbook/Fifth Edition


Problem: 8-0 2"
Find design flexural strength, c|>Mn

Solution:
Determine Cwpu for the section:
I
4 = 2 2 .7 5 "
I
TT 24"
| I

since co = o ' = 0
Reinforcement:
1.06 (0.68) (270)
OtOpu 0.139 12- 1/ 2in. diameter 270K low-relaxation strands
40(7) (5) (6 each stem)
Entering Figure 4.12.3 with this parameter and an Aps= 12(0.153) = 1.84 in2
assumed effective stress, fse>of 170 ksi gives a value As (2- # 6) = 0.88 in2
of:
fps = 266 ksi Problem:
Find the design flexural strength of the composite
Determine the flexural strength: section by the stress-strain relationship, Figure
<t>Mn = 4)[Apsf ps(dp - a/2)] 4.12.3, and compare using Code Eq. 18-3.

Solution:
a = Apsfps/(0.85fcb)
Assume fse = 170 ksi

0.68(266)
a 1.064 in.
0.85(5)(40) CtOpy = + 4.(0) - o,')
bd pTc Qd

<|>Mn = 0.9[0.68(266)(7 - 1.064/2)] w = Asfy/bdfc

= 1053 kip-in. = 87.7 kip-ft 0.88(60)


= 0.0074
96(24.75) (3)
Check the ductility requirement:
_ 1.00(1.84)(270) 24.75 moQ71l
<j>Mn > 1.2Mcr Co)pu
96(22.75) (3) + 22.75 (°-°°74)

P = fseApS = 170(0.68) = 0.084


= 116 kips
From Figure 4.12.3:
1.2 MCT = 1.2(P/A + Pe/Sb + 7 . 5 / f f ) s b
fps = 268 ksi
116 116(2.98) 7.575000
= 1.2 218 381 1000
0.85(3) (96)
= 901 kip-in. = 75.0 kip-ft
< 87.7 kip-ft OK Mn = 1.84(268)[22.75 - (2.23/2)]
+ 0.88(60) [24.75 - (2.23/2)]
Example 4.2.4 Use of Figure 4.12.3 and Eq.
18-3 (ACI 318-95) for Partially = 11,917 kip-in = 993 kip-ft
Prestressed Member
Given: <t>Mn = 0.9(993) = 894 kip-ft*
PCI standard double tee
8DT24 + 2 * Since a = 2.23 in. > 2.0 in. — the topping thickness, a more
exact analysis requires revised calculation to account for the
higher strength concrete of the double tee flange. However,
Concrete: such a refinement is expected to produce a negligible differ­
Precast: fc = 5000 psi ence in the results. In this case, the revised calculation yields a
= 2.16 in. versus 2.23 in. and <j>Mn = 896 kip-ft versus 894
Topping: fc = 3000 psi, normal weight kip-ft.

PCI Design Handbook/Fifth Edition 4 -1 5


Find fps using Eq. 18-3 (ACt 3t8-95): Problem:
find-the-uniform- five load which the flange can
support.
t1ps 'p u l * n
Solutkm:
co' = & in this example As1 (WWR in precast) = 0.080 irF/ft
As2 (WWR in topping) = 0.028 ir^ft
f = 270/ 1 - m f . . 1: 8^ 270) .
ps \ 0.85 [96(22.75)(3) The cantilevered flange controls the design since the
negative moment over the stem reduces the positive
+ ||Z |(0 .0 0 7 4 ) moment between the stems. Construct strain dia­
gram:

= 263 ksi (vs. 268 ksi from Figure 4.12.3)

4>M„ = 879 kip-ft


Ti
e = j— c
Example 4.2.5 Flexural Strength of Double
Tee Flange in Transverse
Direction Try c = 0.25 in.
For flanged sections, in addition to providing ade­ es + 0.003 _ d
quate flexural strength in the longitudinal direction, 0.003 ~ c
the flanges must be designed for bending in the
Therefore:
transverse direction. This example illustrates a de­
sign for both uniformly distributed loads (Part A) and 0.003d!
£ S1 = - 0.003
concentrated loads (Part B). c
Fibers, which are sometimes used to control 0.003d
shrinkage cracks, do not transer loads and therefore 2 ~ * - 0.003
e s
c
cannot be used to replace structural reinforcing such
0.003(1)
as welded wire reinforcement. This is particularly im­ esi - 0.003 = 0.009
0.25
portant for structural toppings over precast concrete
decks. The reinforcing in these toppings cannot be 0.003(3)
£ s 2 = - 0.003 = 0.033
replaced with fibers. 0.25
f. 60
= 0.0021 < 0.009
£y Es 29,000
Part A

Given: Therefore, reinforcement yields, and


PCI standard double tee of Example 4.2.4. Top­
ping is reinforced with 6 x 6-W1.4 x W1.4 WWR, and fs = fy = 60 ksi
the flange is reinforced with 12 x 6-W 2.5 x W4.0
WWR. (W4 perpendicular to stems). a = foe = 0.80(0.25) = 0.20 in.

C = 0.85fcba = 0.85(5) (12) (0.20)

= 10.2 kip/ft

Ti = As1fy = 0.08(60) = 4.80 kip/ft

T2 = As2fy = 0.028(60) = 1.68 kip/ft

T 1+ T2 = 6.48 < 10.2 kip/ft


fc (topping) = 3000 psi
(precast) = 5000 psi Therefore, try
fy = 60,000 psi* *
a = (T| + T2 )/(0.85fc b)
* ACI 318-95, Sect. 3.5.3 allows fy to exceed 60,000 psi if
stress corresponds to a strain of 6.35%. = 6.48/[0.85(5)(12)J

4 -1 6 PCI Design Handbook/Fifth Edition


= 0 J 3 in. Part B

e— 0.13/0.80 = 0.16 Given


Gheek : Pretopped double tee 10DT34 (see Chapter 2)
0.003(1)
£si - 0.003 fo = 5,000psi
0.16
fy = 65,000 psi (WWR)*
= 0.016 > 0.0021
Therefore, the reinforcement yields, and the analysis
is valid.

<J>Mn = ^ [ T 1 (dn — a/2) + T2(d 2 - a / 2)]

= 0.9(4.80(1 -0 .1 3 /2 )+ 1.68(3-0.13/2)]

= 8.48 kip-in./ft = 707 Ib-ft/ft

Check minimum and maximum reinforcement


0.028(3) + 0.08(1)
d ~ 0.028 + 0.080

= 1.52 in. --------------- 1— 1-4------------


------------ h T ------------ / 1 ,
/ 1 1
1 ! x
b =12 in.
i i » \ A i \ i

A__
CT
00
5 .0 '

II
3 / f T h j _ 375000(12)0.52) 1 1 1 r
simtn* fy w 60,000 1 1 1 7
i ?5V V « ; ! 1
1 1 / \ i 1
= 0.064 in2 N i
— g — £— ------------- J— U ------------

Ag provided = 0.028 + 0.080 PLAN VIEW


= 0.108 in2 > 0.064 OK Problem:
Design the flange for bending in the transverse di­
o = — = 0 ^ 0 ^ = 0 0059 rection for a concentrated live load of 2 kips (typical
P bd 12(1.52) 0 0059 for parking structures) as shown.

pmax = 0.75pb
Solution:
fL\/ 87,000
= 0.75(0.85^01 The following assumptions related to distribution
fy / \ 87,000 +
of the concentrated load are typical:

87 1. Because of the flange-to-flange connection,


the 2 kip load may be distributed to two adja­
cent double tees (1 kip per double tee) [30].
= 0.025 > 0.0059 OK
2. The load is considered applied over an area of
Calculate allowable load: about 20 in2 with the dimension b equal to 6 to
10 in.
w d (flange self weight) = 50 psf
3. An angle of 45° is typically used for distribution
of the concentrated load in each double tee
M ,,. ^ . 50(1.4X1.75)*. 107i2|b,M
flange.

Note: For this example, a 45° angle and the di­


= 707 - 107.2 = 599.8 Ib-ft/ft mension b equal to 8 in. results in a distribution width
at face of stem of 5 ft as shown.
_ 599.8 (2) _
W< = (i:75)2 (V.7) = 230 psf * ACI 318-95, Sect. 3.5.3 allows L to exceed 60,000 psi if
stress corresponds to a strain of 0.35%.

PCI Design Handbook/Fifth Edition 4 -1 7


Calculate factored m om entper foot width: Example 4 9 9 Designof a Partially
Prestressed"Range<t Section
w d (self weight-of flange) — ^ ( 1 5 0 ) = 50 psf Using Strain Compatibility
Given:
Md (factored) = 1.4(50) (2.1 7 ) ( ^ ) ( ; j - ^ J Inverted tee beam with 2 in;composiie4opping as
shown:

= 1.98 kip-in./ft

M, (factored) . IQ Q ^ Z ffia

24
= 8.85 kip-in./ft

Mu= 1.98 + 8.85 = 10.83 kip-in./ft

Calculate design moment strength with trial wire


reinforcement that has W4 wire at 4 in. on centers.
Concrete:
As = 0 .1 2 in2/ft ft (precast)=5000 psi
ft (topping)=3000 psi
a - A°fy - ° ' 12(65) - p i s in
0.85 ft b 0.85(5)(12) Reinforcement:
12 -1/2 in. diameter 270K low-relaxation strand
^M n= 4>Asfy^d - |J Aps = 12x0.153 = 1.836 in2
Eps = 28,500 ksi
As = 2 - # 7 = 1.2 in2 Es = 29,000ksi
= 09(0.12)(65)(2 - ^ )
A; = 2 - # 9 = 2.0 in2 Es = 29,000 ksi

= 13.5 kip-in./ft > 10.83 kip-in./ft OK Problem:


Find flexural strength, cpMn

Check ACI 318-95, Sects. 10.5.4 and 7.12 for re­ Solution:
quired minimum reinforcement: Determine effective flange width, b, from Sect.
8.10.2 of the Code; overhanging width = 8 times
thickness. (Note: May also be limited by 14 span.)
As (shrinkage and temperature)
b = bw + 2(8t) = 12 + 2(8) (2) = 44 in.
= 0.0018(12 )(4 )(§ ) dp = 26 - 3 = 23 in.
d = 26 - 2 = 24 in.
= 0.080 in2/ f t < 0.12 in2/ft OK d' = v/z in.

Use 12 x 4 - W2.0 x W4.0 WWR (one layer) Assume 20% loss of prestress
Strand initially tensioned to 75% of fpu

(Note: Since most double tees meet the require­ fse = 0.80(0.75)(270) = 162 ksi
ment of ACI 318-95 Sect. 7.12.3, shrinkage and tem­ e = — = 162 _ o oo57
perature reinforcement in the longitudinal direction Ese Eps 28,500
typically is not required. In such cases, only a nomi­
nal amount is used to facilitate shipping and handling Construct a strain diagram as shown on next page:
of the reinforcement. The Wire Reinforcement Insti­
tute requires that the longitudinal wire must have an
Esa + 0.003 _ d p
area at least equal to 0.4 times the transverse wire
area). 0.003 " c

4 -1 8 PCI Design Handbook/Fifth Edition


C3 = 0.85(5)(3,7) (12) = 188.7 kips

£$ 0.003 C4 = 2.0(60) = 120 kips

, 0 .0 0 3 - 2 ^ 1 C 1+C 2+C 3+C 4 = 594.3 kips


Es

T 1 = ApSfps = 1.836(258.2) = 474.1 kips


£sa - °-003<23> - 0,003 = °m - 0.003
c c T2 = 1.2(60) = 72 kips

£ps = £ * + £ » = ^ 5 + 0.0027 T] +T 2 = 546.1 kips < 594.3 kips

0.003(24) 0.072
Es - 0.003 = - 0.003
Try c = 8.25 in
0.003(1.5) AAAO 0.0045
ei = 0.003 ------- rr~— - = 0.003 -
£ps = + 0.0027 = 0.0111
_ Ty _
s„ = ^ - =
60
29,000
_
= 0.0021
° 270 - ( 0 .0 1 1 ^0 .0 0 7 ) = 260-2ksi
Try c = 9 in
es = “ 0 003 = 0.0057 > 0.0021
O.dO
Eps = + 0.0027 = 0.0104
fs = 6 0 ksi
From the strand stress-strain curve equations in
Design Aid 11.2.5 e; = 0.003 - = 0.0025 > 0.0021
0.^0

fs = 60 ksi
f- = 270 - ( o o i & o ? ) = 2582 ksi

Es = _ Q 003 = 0 0050 > 0 0021 a3 = 0.85(8.25) - 4 = 3.01 in.

C1+C 2 = 285.6 kips


fs = 60 ksi
C3 = 0.85(5)(3.01)(12) = 153.5 kips
£s = 0.003 - °-° q 45 = 0.0025 > 0.0021
C4 = 2.0(60) = 120 kips
fs = 60 ksi
C-i+G 2+C 3+C 4 = 559.1 kips
a3 = PtC - 4 in. = (0 .8 5 )(9 )-4 = 3.7 in.
Tt = 1.836(260.2)= 477.7 kips
C-| = 0.85(3)(2)(44) = 224.4 kips
T2 = 1.2(60)= 72 kips
C2 = 0.85(3)(2)(12) = 61.2 kips
J :+ J 2 = 549.7 kips « 559.1 kips OK

PCI Design Handbook/Rfth Edition 4 -1 9


Table 4.2.1 Recommended maximum values of z and crack widths, w

Appearance not critical Appearance critical

Exposure . Not exposed Exposedto Not exposed Exposed to


to weather weather to weather^ weather

Max. value of z (k/in.) 175 145 105 80


Corresponding value of w (in.) 0 .0 1 6 0 .0 1 3 0 .0 1 0 0 .0 0 7

Based on = 1.2 in. Eq. 4.2.10

Check reinforcement limits by ACI 318-95, Appen­ 4. For over-reinforced members, nominal mo­
dix B. ment strength must be calculated based on the
Net tensile strain of extreme depth: compression portion of the internal couple. The
equations for that case are given in Figure
In this case, e, = £s
4.2.6.
e, = 0.0057 > 0.005

Therefore, it is a tension-controlled section and 4.2.2 Service Load Design


4 = 0.9 Precast members are checked under service
load, primarily for meeting performance criteria and
Alternatively:
to control cracking.
Extreme depth d, = 24 in.
c/dt = 8.25/24 = 0.344 < 0.375
4.2.2.1 Non-Prestressed Element Design

From Figure 4.2.4, <J> = 0.9 Non-prestressed flexural elements are normally
proportioned, and reinforcement selected, on the ba­
Mn = 224.4(8.25 - 1) + 61.2 (8.25 - 3) sis of the procedures described in Sect. 4.2.1. How­
ever, depending upon the application and exposure
+ 153.5(8.25 - 4 ofthe member, designers may want to control the de­
gree of cracking. In some applications, such as archi­
+ 120(8.25 - 1.5)+ 477.7(23 - 8.25)
tectural precast concrete panels, they may not want
+ 72(24 - 8.25) any discernible cracking. In other cases cracking
= 11,359 kip-in. may be permitted, but the crack width must be limit­
= 947 kip-ft ed. In addition, Sect. 10.6.4 ofthe Code requires that
the crack width be limited when the yield strength of
4>Mn = 0.9(947) = 852 kip-ft
the reinforcement exceeds 40,000 psi.
If no discernible cracking is the criteria, the flexural
Notes:
tensile stress level should be limited to:
1. This example shows the exact method; approx­
imate methods may be satisfactory in many si­
ff ^ 5 X /ff (Eq. 4.2.8)
tuations.

2. In this example, since the cast-in-place topping


carries significantly more compression force where:
than the precast member, p ,= 0.85 corre-
sponds to topping concrete. In other cases, ff = allowable flexural tension, computed
where the compression is shared by the top­ using gross concrete section
ping and precast in different proportions, a rea­
sonable average value for pT may be used. fc = concrete strength at the time
considered
3. In evaluating copu and other similar factors, f’ =
3.5 ksi is used to reflect the contribution of top­ l = 1.0 for normal weight concrete
ping vs. precast member to the total compres­ = 0.85 for sand-lightweight concrete
sion force.
= 0.75 for all-lightweight concrete

4 -2 0 PCI Design Handbook/Rtth Edition


figure 4.2.7 Notation for crack-control where:
equations M = service Joad moment

This equation is based on working stress design


principles with-the assumption that j- = 0.9 and k =
0.3.
It should be emphasized that the equations and
criteria given here are for reasonable controi o f crack­
ing. The crack widths are guidelines and should not
be used as acceptance criteria for finished wall pan­
els.
Sect. 16.4.2 of the Code requires a minimum
amount of reinforcement equivalent to 0.001 times
the gross cross-sectional area of precast concrete
panels.
When tensile stress, ft, exceeds this value, re­
quired reinforcement is determined by a Code limita­
tion on the maximum value of the quantity z as shown Example 4.2.7 Non-Prestressed Panel
in Table 4.2.1, in which z is calculated from the equa­ Design
tion: Given:
A 6 in. thick precast wall panel exposed to view
z = fs^d 7 (Eq. 4.2.9)
and to the weather, with dimensions as shown:
where:
fs = reinforcement stress at service load, ksi
= 0.6fy, unless otherwise determined
6u
dc = concrete thickness to the center of
reinforcement closest to the tension face,
in.
A = average effective area around one Concrete fc = 5000 psi
reinforcing bar, in2 Service load moment, M = 2.4 kip-ft/ft
= 2bdc/n
Problem:
b = width of tension face, in
Determine if reinforcement is needed to control
n = number of reinforcing bars cracking, and if so, amount required (see Figure 4.2.7
for notation).
This equation is derived from the Gergely-Lutz [3]
expression: Solution:
For a 12 in. width:

w = (7 .6 x 1 0- 5) ^ f ( E q . 4.2.10) _ M _ 2.4(12)(1000)
hi = 400 psi
* S 12(6)2/6
where:
w = maximum crack width at extreme tension From Eq. 4.2.8:
fiber, in. f; = 5(1.0)^5000
hH = distance from centroid of tensile = 354 psi < 400, reinforcement required
reinforcement to neutral axis, in.
For an appearance critical panel exposed to the
h2 = distance from extreme tension fiber to
weather, the recommended maximum value of w
neutral axis, in.
from Table 4.2.1 is:
If the value of fs under service load conditions is re­
quired to be less than 0.6fy to satisfy crack control re­ w = 0.007 in.
quirements, reinforcement should be provided equal
to: Assuming j = 0,9 and k = 0.3, calculate:
d = 6 -1 .5 = 4.50 in.

kd = 0.3(4.5) = 1.35 in.

PCI Design Handbook/Fifth Edition 4 -2 1


h, = 4 .5 -1 .3 5 = 3.15 in. stresses are summarized as follows (see Code Sects.
16:4 and 18.5)r
6 - 1 .3 5 = 4.65 j a
Concrete
4.65 1. At release (transfer) o f prestress; before time-
3.15 dependent tosses:
a. Compression (see Sect. 10.5) .. 0.60^
de = 1.5 in .
b. Tension (except at ends) .......... 3 /fj~
Try a bar spacing of 4 in. c. Tension at ends* of simply supported
members .........................-............ 6 ^
A = 2(4)(1.5) = 12 in2
2. Under service loads:
From Eq. 4.2.10: a. Com pression due to prestress plus
I _ _______ w_______ sustained loads .........................0.45f£
b. Compression due to prestress plus total
(7.6 x 10-5) ^ 3/ d A
lo a d ............................................. 0.60fc
________ 0.007 c. Tension in precompressed tensile zone
(7.6 x 10’5) (1.48)3y 1.5(12) then deflections are calculated based on
gross section .............................. 6 /fT

23.7 ksi d. Tension on precompressed tensile zone


then deflections are calculatedbased on
M bilinear relationships and where cover
As =
0.9 fsd
requirements comply with ACI 313 Sect.
2.4(12) 7.7.3.2 (see Sect. 4 .8 .3 )......... 12
= 0.30 in2/ft
0.9(23.7)(4.5)
The Standard Design Practice (Sect. 10.5 of this
Use No. 3 at 4 in. Handbook) points out that in practice, the limitation of
eTfT has very little meaning. Bilinear deflection be­
As = 0.33 in2/ft havior, as shown in Sect. 4.8.3 and most other texts
and design guides, uses 7.5 /fT as the cracking
Note: This is an unusually high amount of rein­ stress, so at that value or below, deflections would be
forcement for this type of panel. Ordinarily, span based on the gross section. Since deflections are
would be reduced to keep the stress below f ' . routinely calculated using bilinear relationships for all
precast, prestressed concrete structural members,
4.2.2.2 Prestressed Element Design the limitation of 12 applies to all types of sections.

For prestressed concrete members, the ACI Code


requires that service load stresses bechecked at criti­
cal points, in addition to the design strength of the
* May be considered at transfer length from end (See Sect.
member. Code limitations on the service load 4.2.3)

Figure 4.2.8 Calculation of service load stresses

APPLIED
SERVICE
LOADT
MOMENT,
M

4 -2 2 PCI Design Handbook/Fifth Edition


Prestressing steel Section properties:
Non-Composite Composite
a. Tension due to tendon jacking
A-. — 265 in 2 —
fo rc e :................... ...........O.SOfpu or 0.94fpy
I = 4771 in 4 7209 in4
b. Tension immediately after prestress
yb = ^ J 7 in . 8.10 in.
transfer:
yt =S .33 in. 5.90 in.
Stress-relieved strand:___ _____ 0.7fpu
Sb = 715.3 in3 890.0 in3
Low-relaxation s tra n d :............... 0.74fpu
St = 895.1 in3 1221.9 in3
These values are commonly assumed to be after a wt = 276 plf 376 plf
small seating loss. Manufacturers may “fine tune" e = 4.79 in.
actual jacking force to compensate for temperature
variation. Superimposed sustained load = 20 psf = 80 plf
Calculations of stresses at critical points follow the Superimposed live load = 50 psf = 200 plf
classical straight line theory as illustrated in Figure
Precast concrete (normal weight):
4.2.8.
f'c = 6000 psi
Composite Members foi = 4000 psi
It is usually more economical to place cast-in­ Ec = 4700 ksi
place composite topping without shoring the mem­
ber, especially for deck members. This means that Topping concrete (normal weight):
,ie weight of the topping and simultaneous construc­ fc = 4000 psi
tion live load must be carried by the precast member Ec = 3800 ksi
alone. Additional superimposed dead and live loads
are carried by the composite section.
The following examples illustrate a tabular form of Prestressing steel:
superimposing the stresses caused by the prestress 5-Vz in. diameter 270K low-relaxation strand
force and the dead and live load moments. Aps = 5(0.153) = 0.765 in*
Straight strands
Sign Convention
The customary sign convention used in the design Problem:
of precast, prestressed concrete members for ser­ Find critical service load stresses.
vice load stresses is positive (+) for compression and
negative (-) for tension. This convention is used
throughout this Handbook. Solution:
Prestress force:

Example 4.2.8 Calculation of Critical Pi = 0.765(0.75)(270) = 155 kips


S tre sse s-S tra ig h t Strands P0 (assume 10% initial loss)
= 0.90(155) = 139 kips
P (assume 18% total loss)
= 0.82(155) = 127 kips

Mid-span service load moments:


Md = 0.276(36)2(12)/8 = 537 kip-in.
Mtop = 0.100(36)2(12)/8= 194 kip-in.
Msd = 0.080(36)2(12 )/8 = 156 kip-in.
Mf = 0.200(36)2(12 )/8= 389 kip-in.
Given:
4HC12+2 as shown Allow 6 yfT tension at service load.

Span = 36 ft See the following table for service load stresses,

PCI Design Handbook/Fifth Edition 4 -2 3


Example 4.2,8
Load Transfer Pt. atRelease Mid-span at Retease Mid-span at Service Load
P = P0 P = P0 P=P

fb ft fb ft fb- ft(a)» ft (b)°

P/A + 525 + 525 + 525 : +525 + 479. + 479 + 479

PelS + 931 - 744 + 931 - 744 : + 850- -6 8 0 . - 680

Md/S - 164 + 131 -751 +600 - 751 + 600 + 6oa

Mjop/S -271 + 217 + 217

Msd/Sb -
- 175 + 84 + 84

Mf/S - 437 +210

Stresses + 1292 - 88 +705 + 381 - 305 + 700 +910

0.70fdC e/fjT 0.70fci° 0.70fec 12^ 0.45ft 0.6ft


Limiting
Stresses + 2400 - 379 +2800 +2800 - 930 +2700 +3600

OK OK OK OK OK OK OK
a. (a) and (b) correspond to the (a) and (b) stress criteria in Code Sec. 18.4.2
b. For all stresses, the composite section modulus is used. The stresses are calculated at the top ot the precast section.
c. See Sect. 10.5

Example 4.2.9 Calculation of Critical


Stresses-Single Point Section properties:
Depressed Strand A = 401 in2

Given: I = 20,985 in4

Span = 70 ft yb = 17.15 in.

Superimposed sustained load = 10 psf = 80 plf yt = 6.85 in.

Superimposed live load = 35 psf = 280 plf Sb = 1224 in3

Select 8DT24 as shown St = 3063 in3


wt = 418 plf = 52 psf
8" - 0"
Eccentricities, single point depression:
2'- •0"
CM

4 '-0 "
1

ee = 5.48 in.
2" ec = 13.90 in.
5 3/ 4 " — * j '

r e at 0.4^ = 12.22 in.


k
' ------ N.A. i 24t e ' = 13.90 - 5.48 = 8.42 in.
17.15"
Problem:
-*! 3 %"
Find critical service load stresses.
Solution:
Concrete (normal weight):
Prestress force:
f-c = 5000 psi Pi = 1.836 (0.75) (270) = 372 kips
fci = 3500 psi P0 (assume 10% initial loss)
Prestressing steel: = 0.90 (372) = 335 kips
12-1/2 in. diameter 270K low-relaxation strand P (assume 20% total loss)
Aps= 12x0.153 = 1.836 in2 = 0.80(372) = 298 kips

4 -2 4 PCI Design Handbook/Fifth Edition


Service load.moments- at mid-span: S olutionr
Md= 0.418(70)2 (12)/8 = 3072 kip-in. Prestress force:

Msd= 0.080{70)2 (12)/8 = 588kip-in: P, = 2.295(0.75X270) = 465 kips

0.280(70)2 (12)/8 = 2058_kip-tn. Po (assume-10% initial loss)

at 0.4^: = Q.90'465) = 418 kips


Moment due to member weight:
Md= 3072(0.96) = 2949 kip-in.
ALmid-span:
Msd= 588(0.96) = 564 kip-in.
Md = 0.475(24)2(12)/8 = 410 kip-in.
M ( = 2058(0.96) = 1976 kip-in.
Assume transfer length =
Allow 12VfT final tension.
See the following table for service toad stresses. f e ) d b = (170/3)0.5 = 28.3 in. = 2.36 ft
Example 4.2.10 Tensile Force to be Resisted
by Top Reinforcement
Given: (See Sect. 4.2.3).
Span = 24 ft At transfer point:
24IT26 as shown below
Md = ^ ( ^ - x) = - - 75^2 36^ (24 - 2.36)(12)

= 146 kip-in.
14"
See the following table for stresses at release.

Since the tensile stress exceeds the limits, rein­


forcement is required to resist file total tensile force,
Cg Strand as follows:
12" 990
c = = _ L (h ) = (26)
f, + ft 990 + 2270
3.20"
7.90 in.
ef,b _ 7.90 (990) (12)
T = 46,926lb
12" 6" 2 2

Concrete:
fc = 6000 psi
fd = 4000 psi

Prestressing steel:
15-V2 in. diameter 270K low-relaxation strand
Aps= 15(0.153)=2.295 in2

Section properties:
= 456 in 2
Similarly, the tension at mid-span can be found as
I = 24,132 in4 35,591 lb.
yb = 10.79 In. The Commentary to the Code, Sect. 18.4.1 (b) and
(c), recommends that reinforcement be proportioned
yt = 15.21 in.
to resist this tensile force at a stress of 0.6fy, but not
Sb = 2237 in3 more than 30 ksi. Using reinforcement with fy = 60
St = 1587 in3 ksi:
Wt = 475 plf 0.6(60) = 36 ksi, use 30 ksi
e = 7.59 in.
As (end) = = 1.56 in2
Problem:
As (midspan) = = 1.19 in2
Find critical stresses at release.

PCI Design Handbook/Fifth Edition 4 -2 5


Example 4.2~&
to a d ^Transfer Pt. at Release M id -sp airatR etease 0.41 at Service Load
F = F fr F = F - ff F = F

r fb ft % ft % ftfr)8 ft(b)»

P/A + 833 + 835 + 835 + 835' + 743 + 743 + 743

Pe/S + 1500 -5 9 9 + 3804 - 1520 + 2985 - 1189 - 1189

Ma/S - 290 + 116 -2 5 1 0 + 1003 -2 4 0 9 + 962 + 962

Msd/S - 461 + 184 + 184

M /S - 1614 + 645

Stresses + 2045 + 352 +2129 + 318 -7 5 6 + 700 + 1345

0.70fdb 0.70fcib 0.70fdb 0.70fdb 1 2 /fT 0.45f' 0.60f£


Limiting
Stresses . + 2450 + 2450 + 2450 + 2450 - 848 + 2250 + 3000

OK GK OK OK OK OK OK

a. (a) and (b) correspond to the (a) and (b) stress criteria in Code Sec 18.4.2
b. See Sect. 10.5

Example 4.2.10
Transfer Point at Release Mid-span at Release
Load
P = P0 P = P0

fb ft fb ft

P/A + 917 + 917 + 917 + 917

Pe/S +1418 - 1999 + 1418 - 1999

Md/S - 65 + 92 - 183 + 258

Stresses +2270 -9 9 0 +2152 -8 2 4

G.70fci 0.70f£i 6/ r
Limiting
+ 2800 - 379 + 2800 - 379
Stresses

OK HIGH OK HIGH

a. See Sect. 10.5

Top strands used as stirrup supports may also be fer length.” It is given in the Commentary to the Code
used to carry this tensile force. to be equal to (fse/3)db.
It should be noted that some cracking may occur The length required to develop the design
even with reinforcement. Such cracking, however, strength of the strand, however, is much longer, and
has no structural significance, and is acceptable. is specified in Code Sect. 12.9.1 by the equation:

4.2.3 Prestress Transfer and Strand


€ d = (fps - 2 / 3 U d b (Eq. 4.2.12)
Development
In a pretensioned member, the prestress force is Sect. 12.9 .3 of the C o d e requires the developm ent
transferred to the concrete by bond. The length re­ length to be doubled if:
quired to accomplish this transfer is called the “trans­

4 -2 6 PCI Design Handbook/Fifth Edition


1 Bonding of the strand does not extend to the end Figure 4.2.9 Variation of steel stress with
of the member (debonded or ^shielded” strand)
and

2; The member is. designed such that tension will


occur in the precompressed tensile zone under
service loads.

In the Commentary to the Code, the variation of


strand stress along the development length is given
as shown in Figure 4.2.9. For convenience, this curve
may be approximated by straight lines. This is illus­
trated in Figure 4.12.4 for several strand sizes. The
value of fse is shown as 170 ksi, which is typical for
low-relaxation strand tensioned to the maximum al­
lowable. A more general design aid which includes all
currently used strand sizes and other values of t,e is
given in Chapter 11 (see Design Aid 11.2.6).
In short span flexural members, prestressing
strands may not be developed at sections of high mo­
ment. In such cases, it is possible that a premature
failure may occur in the concrete due to strand slip Concrete:
[5]. In such cases, the capacity of the section should
fc = 5000 psi, Normal weight
be reduced to account for this changed failure mode,
as illustrated in Example 4.2.11.
When a portion of the strands are debonded, Prestressing steel:
zones are created where sections through the mem­
ber will contain strands with unequal strains. In this 4 - 1/2 in. diameter 270K strands
case, calculation of nominal strength in the develop­ Aps = 4 (0.153) = 0.612 in2
ment region should be based on strain compatibility,
or conservatively, the contribution of the debonded Solution:
strand neglected until it is fully developed. Example
If the strand is fully developed (see Figure 4.12.3):
4.2.12 illustrates these principles.
Failures caused by bond slip are brittle, so a value
of <J> = 0.85 is recommended to determine flexural CApgfpu _ 1.06(0.612) (270)
capacity when this failure mode is possible. Also, C(opu = 0.11
bdpfc 48(6.5)(5)
quality control measures by strand suppliers and/or
precast concrete producers must be in place to as­
sure that strands will meet the transfer and develop­ From Figure 4.12.3 with fse = 170 ksi
ment length requirements of the Code [6].
fps = 268 ksi
Example 4.2.11 Use of Figure 4.12.4—Design
Stress for Underdeveloped The maximum development length available Is:
Strand
Given: (12 = 12(12/2) = 72 In.
Span = 12 ft
4HC8 as shown From Fig 4.12.4 the maximum fpd = 257 ksi
4 '—0*
This value, rather than 268 ksi, should be used to
calculate the design strength (<|)Mn) of the member at

rC U .C D .d 5 l 1 mid-span. Since failure would be by brittle bond slip,


<j) = 0.85.
T
Vk"

PCI Design Handbook/Fifth Edition 4 -2 7


Example 4.2.12 Moment Capacity of Member
with Debonded Strands in
Development Region

Given:
10-ft wide double tee, one stem- shown below".

DEBONDED 56.7" 155.7"

DISTANCE FROM POINT OF DEBONDING


(END OF MEMBER FOR FULLY BONDED STRANDS)

If the strand does not slip, the maximum strength


the strand can develop at 12 ft from the end (7 ft or 84
10—1/£ in. diameter, 270 ksi strands (5 each stem)
in. from the point of debonding) is given by:
Aps = 10(0.153) = 1.53 in2
f pd = 170 + 155j .5 56,7 (269 - 170) = 197.3 ksi
Concrete (normal weight concrete):
f' = 5000 psi and the corresponding strain is:
Ec = 4300 ksi
Epd = fpd/Eps = 197.3/28,500 = 0.00692 in./in.

Prestressing strands: Esa = Epd -Ese = 0.00692 - 0.0060 = 0.00092


fpu = 270 ksi
(See the sketch below).
Initial stress in the strand = 0.74fpu
Total losses = 15 % Note: In this example, the spacing of the strands is
fse = 0.74(270)(0.85) = 170 ksi such that the variation in strains is inconsequential.
Thus, the stress in the strands may be assumed to be
Eps = 28,500 ksi
equal, and the centroid of the tension force, T, may be
Ese = 170/28500 = 0.0060 assumed to be at the centroid of the strand group.

Problem: T = 197.3(1.53) = 301.9 kips


Strand No. 3 is debonded for 5 ft from the end.
Use iteration procedures, varying Ec until the com­
Find Mn at 12 ft from the end.
pression force, C, reasonably approximates the ten­
1. Determine capacity assuming the debonded sion force, T.
strand does not slip:

Solution:
Maximum fps for fully bonded strand (from sepa­
rate analysis) = 269 ksi.

Transfer length = (fse/3)db = (170/3) (0.5) =


28.33 in.

For debonded strands, double the transfer length


per ACI 318-95, Sect. 12.9.3.

Transfer length for debonded strands = 2(28.33)


= 56.7 in.
Ec = 0.000265 in./in.
= (fps -(2 /3 )fse)db = (269 - 113.3) (0.5)
0.000265 ^
c 4.47 in.
= 77.85 in. 0.000265 + 0.000921 1

f dfor debonded strands = 2(77.85) = 155.7 in. Compressive stress at the top of the flange

4 -2 8 PCI Design Handbook/Fifth Edition


= gc Ec = 0.000265(4300) = 1J 4 ksi Since tbtsis less than the flange thickness, t ie de­
sign-© like a rectangular beam.
Compressive stress at the bottomofihe flanga
Mn = T-(d - | j - 329.3(20 - ^ )

= §4^0-14) = 0.12 ksi


4.47v = 0480 kip-in = 540 kip-ft
Compression in the flange In this case, the failure mode is ductile <j>= 0.9

<)>Mn = 0.9(540) = 486 kip-ft


= 1-14 t . O'1? (120) (4} = 302.4 kips
Since the assumption of strand slip is more con­
Compression in the webs servative, the design may be based on method B.

5.75(0.47)(0.12) . . 4.2.4 End Stresses at Transfer


= ------ 2 ------- (2 webs) = 0.3 kips
At the time prestress force is transferred, tensile
stresses perpendicular to the prestressing force
Total compression = 302.4 + 0.3 = 302.7 kips
(sometimes called “bursting” or “splitting” stresses),
= 301.9 kips
develop which may cause horizontal cracks near the
end of the member [7]. These forces can be resisted
Use the sketch below to calculate moments:
by vertical reinforcement calculated by the following
equation.
0.021 PDh
A* (Eq. 4.213)
W.
where:
Ayt = required area erf stirrups at the end of a
member uniformly distributed over a
length h/5 from the end
P0 = prestress force at transfer
Mn = 301.9(15.84 + 2.70) - 0.3(27)
h = depth of the member
= 5596 kip-in = 466 kip-ft fs = design stress in the stirrups,usually
assumed to be 30 ksi
Since the failure mode is brittle strand slip:
= strand transfer length
<j> = 0.85

<j>Mn = 0.85(466) = 396 kip-ft Since this is a temporary stress at the time of pre­
stress transfer such reinforcement need not be in
2. Assume debonded strand slips:
addition to shear and torsion reinforcement.
If additional load is applied causing higher strand
stress than indicated in the above analysis, the strand
will slip. The other strands, however, being fully Example 4.2.13 Calculation of End
bonded, are capable of much higher stress and Reinforcement to Resist
strain. If additional load is applied, as in a load test, Bursting Stresses
the stress and strains will redistribute, and load can
Given:
be applied until the full ultimate strength of the
strands is reached. Thus, a second, more conserva­ Beam of Example 4.2.10
tive analysis would be to neglect the debonded Transfer length = 28.3 in.
strands and determine moment capacity with eight
fully bonded strands. 0.021 PDh 0.021 (418) (26)
= 0.27 in2
U, “ 30(28.3)
T = Apsfps = 8(0.153)(269) = 329.3 kips
h/5 = 26/5=5.2 say 6 in.
a _ T _ 329.3 _r, m
0.85fcb 0.85(5)(120) Provide at least 2 -# 3 stirrups (As = 0.44 in2) within
6 in. of the end.

PCI Design Handbook/Fifth Edition 4 -2 9


Figure 4.2.10 Typical stadium riser

4.2.5 Bending of Asymmetrical Sections Vc = nominal shear strength of concrete

Most precast, prestressed standard sections are Vs = nominal shear strength of shear rein­
symmetrical about their vertical axes. However, forcement
some sections, such as the stadium riser unit shown 4 = 0.85
in Figure 4.2.10(A), are not, and it is necessary to cal­
If Vu is less than <j>Vc/2, no shear reinforcement is
culate properties about the principal axes, U-U and
required. However, for flat deck members (hollow-
V-V. Note that the principal axes may change when
core and solid slabs), and others proven by test, no
the unit is attached to the structure. Calculations of
shear reinforcement is required if the factored shear
stresses of prestressed concrete stadium risers are
force, Vu, does not exceed the design shear strength
illustrated in fief. 8. Strength design, Fig 4.2.10(B), is
of the concrete, (j)Vc. For other members, the mini­
more complex, and may be approximated or com­
mum shear reinforcement is usually adequate.
puted graphically.
The critical section for shear and torsion is indi­
cated in the Code to be a distance “d” from the face of
the support for non-prestressed members and “h/2”
4.3 Shear
for prestressed members. However, precast con­
The shear design of precast concrete members is crete members on which the toad is not applied at the
covered in Chapter 11 of ACI 318-95. The shear re­ top of the member, such as L-shaped beams, the dis­
sistance of precast concrete elements must meet the tance “d” or “h” should be measured from the point of
requirement: toad application to the bottom, or, conservatively, the
critical section taken at the face of the support. Also,
Vu £ 4>Vn if a concentrated toad is applied near a support face,
where: the critical section should be taken at the support
face. See Code Sect. 11.1.3.
Vn = Vc + V „ and

4 -3 0 PCI Design Handbook/Fifth Edition


4 3.1 Shear Resistance of Non-Prestressed Vu = 7.77(30/2 - 87/12)- = 60.2 kips
Concrete
Vc = 2 vC b wd = ^ p ( S ) ( 8 7 ) = 98:4 kips
In the absence o f torsion and axial forces, the
nominal shear resistance of concrete is given by : (j)Vc 0.85(98,4)
41.8 kips
2 2
Vc = 2 bwd (Eq. 4.3.1)
Vc > Vu >
2
or if one performs a more detailed analysis:
Therefore minimum shear reinforcement is re­
Vc = ( l . 9 , / f f + 2500pw^ J b wd < 3 .5 v C b wd quired.
{Eq. 4.3.2) ACI 318-95, Eq. 11-13 requires a minimum
where: amount of reinforcement be provided as follows:

M s 1 .0 Av = 50bws/fy = 0.08 in2/ft


Wlu

See ACI Code for members subjected to signifi­ From Design Aid 11.2.11, select a WWR that has
cant axial forces in addition to shear. Torsion is pre­ vertical wires: W4 at 6 in.
sented in Sect. 4.4 Av = 0.08 in2/ft

See Sect. 12.13.2.4 of the Code for development


Example 4.3.1 Design of Shear Reinforce­ of single leg WWR used as shear reinforcement.
ment —Non-Prestressed
Member

Given:
A spandrel beam as shown: 4.3.2 Shear Resistance of Prestressed
Concrete Members
b = 8 in.
Shear design of prestressed concrete members is
d = 87 in.
covered in ACI 318-95 by Eq. 11 -9 through 11- 12, re­
Span, € = 30 ft
produced below.
fe = 5 ksi Either Eq. 4.3.3 or the lesser of Eqs. 4.3.4 or 4.3.6
Loading at top of member, wu may be used, however, Eq. 4.3.3 is valid only if the
effective prestress force is at least equal to 40% of the
Dead load = 3.96(1.4) = 5.54
tensile strength of the prestressing strand. The Code
Live load = 1 .3 1 (1 .7 )= 2.23 places certain upper and lower limits on the use of
7.77 kips/ft these equations, which are shown in Figure 4.3.1.
8"
Vc = ^0 -6 /fT + TOO^^Jbwd (Eq. 4.3.3)
» «
where:
» «

y Vci = 0.6 yfTbwd + Vd + ^ (Eq. 4.3.4)


max

(Eq. 4.3.5)
» •«
Vow = (3.5 J f [ + 0.3 fpc)bwd + Vp (Eq. 4.3.6)
Problem:
Determine what size welded wire reinforcement
will satisfy the shear requirements. The value of d in the term Vud/Mu in Eqs. 4.3.3 is
the distance from the extreme compression fiber to
Solution: the centroid of the prestressed reinforcement. In all
Determine Vu at a distance d from support: other equations, d need not be less than 0.8h.

PCI Design Handbook/Fifth Edition 4 -3 1


Figure 43:1 Shear design Exampte^4.3.2 Construction of Applied and
Resisting Design Shear
Diagrams
Given:
2HCS with span and Joadings shown
Section properties:
A = 110 in*
I = 843 in4
yb = 4.0 in.
tv = 6.80 in.
d = 5.875'm.
h = 8.0 in. (0.8 h = 6.4 in)
wt = 5 7 p s f = 114 plf

Concrete:
fc = 5000 psi normal weight

8.0”
In unusual cases, such as members which carry
heavy concentrated loads, or short spans with high
superimposed loads, it may be necessary to
construct a shear resistance diagram (Vc) and super­
impose upon that a factored shear (Vu) diagram. The
procedure is illustrated in Figure 4.3.1.
The steps for constructing the shear resistance
diagram are as follows:

1. Draw a horizontal line at a value of b wd


(Note: The Code requires that this minimum be
reduced to 1 bwd when the stress in the
strand after all losses is less than 0.4 fpu. For
precast, prestressed members the value will
generally be above 0.4 fpu.) Solution:
1. Determine factored loads
2. Construct the curved portion of the diagram. Uniform dead = 1.4(42 + 114) = 218 plf
For this, either Eq. 4.3.4 or, more conservative­ Uniform live = 1.7(100) = 170 plf
ly, Eq. 4.3.3 may be used. Usually it is ade­ Concentrated dead = 1.4(2) (750) = 21001b
quate to find 3 points on the curve. 2. Construct shear diagram as shown in Figure
4.3.2
3. Draw the upper limits line, from Eq. 4.3.6 if
Eq. 4.3.4 has been used in Step 2, or 5>/ff bwd 3. Construct the shear resistance diagram as
if Eq. 4.3.3 has been used. described in the previous section.
4. The diagonal line at the upper left of Figure a. Construct line at bwd = 5 2 kips
4.3.1 delineates the upper limit of the shear re­ b. Construct Vc line by Eq. 4.3.3:
sistance diagram in the prestress transfer
zone. This line starts at a value of 3.5 V^" bwd at Vc = ^ 0.6 \/fT + 7 0 0 ^ j bwd
the end of the member, and intersects the
line or 5 /fT b ^ line at transfer length from the
V d
end of the member. See Code Sect. 11.4.3 = 1.56 + 2 5 . 7 ^

4 -3 2 PCI Design Handbook/Fifth Edition


point X Vu Mu V ad/M u Vc d = 5 .6 7 5 in.
(ftl ' (kips) (kip-in) (kips)
At 1,2, and 4 ft from each end:
V 1 4.64 58=02 0.470 13.6

2 4.25 111.36 -0.224 7.3


V -u (left) = 5t03— -0.39x
2

3 4 3.47 2 04.00. 0.100 4.1

4 1 5.22 64,98 : 0.472 13.7


Mu (left) = (5.03x - jl 2
5 2 4.83 125.28 . 0=227 7.4

6 4 4.05 231.84 0.403 4.2


Vu(right) = 5.61 - 0.39x

Mu(right) = ^ 5 . 6 1 x - ^ p ) l 2

c. Construct upper limit line at 14.1 kips

d. Construct diagonal line at transfer zone from


3 5 J% b„d = 9.9 kips at end of member to
14.1 kips.
kips at 50db = 50(7/ie) = 21.9 in. = 162 ft

e. Construct diagram:
5.03/0.85 = 5.92
0.40/0.85 = 0.47
2.50/0.85 = 2.94
5.61/065 = 6.60

It is apparent from these diagrams that no shear


reinforcement is required.

4.3.3 Design Using Design Aids

Figs. 4.12.5 through 4.12.9 are design aids to as­


sist in determining the shear strength of precast, pre­
stressed members.

When lightweight concrete is used, the shear


equations, Eqs. 4.3.1 through 4.3.6, are modified by
substituting for J%. The coefficient X is defined
as follows:

X 1.0

In this equation f^ is the splitting tensile strength


determined by test (ASTM C 496). For normal weight
concrete, X is equal to 1.0. If the value of f^ is not
known, X = 0 65 for sand-lightweight concrete, and
0.75 for all-lightweight concrete is used. Figs. 4.12.5
to 4.12.7 provide separate charts for normal weight
and lightweight concrete. In these charts, it is as­
sumed that fd is not known and the material is sand-
lightweight, or X = 0.85.

PCI Design Handbook/Fifth Edition 4 -3 3


Example 4.3.3 Use ofFigs. 4.12.5 through The graphical solution (Figure 4.3.3) follows these
412.7—Graphical Solution of steps:
Eq. 4.3.3 (Code Eq. 11-9) (a) B ravra line from V J <p = 65.1 kips at support to
Given: V u/ ^ l = 0 at midspan,
PCI standard doable tee 10LDT24 + 2 (b) Draw line from Vc = 3.5W fT bwd
Span = 50 ft = 44.6 kips at support to Vc = 5\J% bwd

bw = 9.5 iru = 59.4 kips at 50 db = 25 in. (or 0.042f)


from end of member.
d = 2 1 + 2 = 23 in.
(c) Draw a curved line at f/d = 26.1.
0.8 b = 20.8 in.
(d) Draw a vertical line at h/2 from face of support.
d (near ends) = 16 in. < 20.8, use 20.8 in.
(e) The shaded area is the excess shear, Vu/<|>- vc,
d (near nrtid-span) = 23 in. > 20.8, use 23 in.
for which shear reinforcement is required (see
10' - 0 " -------------- > Example 4.3.5 for design of shear reinforce­
ment).
« 2' - 6" . „ 5 '-0" „ • 2 '-6" r 2"
5 % " -* [ j - 1+ 1
J-n---1 4 3 .4 Shear Reinforcement
t* 1 Shear reinforcement is required in all concrete
2" 24
members, except as noted in Sect. 11.5.5, ACI
J L 318-95. The minimum area required by the ACI Code
- * i U - 3 %"
is determined using Eq. 11-13:
Concrete:
Av = 50 bws/fy (Eq. 4.3.7)
Precast: fc = 5000 psi, sand-lightweight
Topping: fc = 4000 psi, normal weight or, alternatively for prestressed members only, using
Eq. 11-14:
Reinforcement: Aps fpu s /"q~
(Eq. 4.3.8)
Prestressing steel: 80 fy d v bw
270K strand, 108-D1 pattern, Figure 4.12.8 is a graphical solution for the mini­
Aps = 1.53 in2 mum shear reinforcement by Eq. 4.3.8.
ee = 7.77 in.
Example 4.3.4 Minimum Shear
ec = 14.77 in. Reinforcement by Eq. 4.3.8
Shear reinforcement and Figure 4.12.8
fy = 60 ksi
Given:
Loads:
Double tee of Example 4.3.3
Dead load, wd = 609 plf
Shear reinforcement: W 4.0 wire each leg
Live load, w f = 800 plf
Av = 2(0.040) = 0.080 in2

Problem: Problem:
Find the value of excess shear force, Vu/<|> - Vc, Determine the minimum amount of, shear rein­
along the span using Eq. 4.3.3 for Vc. forcement required by Eq. 4.3.8 (Code Eq. 11-14).
Verify the result from Figure 4.12.8.
Solution (see Figure 4.3.3):
The parameters needed for use of Figs. 4.125 Solution:
through 4.12.7 are: bwd = 9.5(22) = 209 in2
Strand drape: 1 4.77-7.77 = 7 in. which is
approximately equal to d/3, thus a shallow drape. Note: As a simplification, d = 22 in. is used as an
average value.
e/d = — £ 12 = 26.1
From Eq. 4.3.8:
1.53(270
VU/<J) at support = [(1.4wd + 1.7wt)£/2]/(p Av = 0.080 =
80 \ 60,
= (1.4 x 609 + 1.7 x 800)(50/2)/0.85(1000) thus:
= 65.1 kips s = 1 3 .4 in.

4 -3 4 PCI Design Handbook/Fifth Edition


F ro m Figure 4.12.8: 4.3.5 Horizontal Shear Transfer in
For: Composite Members
Aps = 1-53 in2" ^ Cast-in-place concrete topping is-often used on
precast members to develop composite structures.
fy = 60 ksi
The increased stiffness and strength may be required
fpu = 270 ksi for gravity loads or Jor developing a diaphragm to
bwd = 209In2 transfer lateral loads.
Av = 0.075 in2/ft Fibers, which are sometimes used to control
shrinkage cracks, do not transfer loads and therefore
corresponding s = 12(0.080)/0.075 cannot be usedto replace structural reinforcing such
= 12.8 in. « 13.4 OK as welded wire reinforcement. This is particularly im­
portant for structural toppings over precast concrete
Per Code Sect. 11.5.4:
decks. The reinforcing in these toppings cannot be
replaced with fibers.
Smax = % h < 24 in.
In order for a precast member with topping to be­
3/4h = 0.75(26) = 19.5 in. > 13.4 OK
have compositely, full transfer of horizontal shear
Shear reinforcement requirements are defined in forces must be assured at the interface of the precast
ACI 318-95 by Eq. 11-15 which may be rewritten for member andihe cast-in-place topping. This requires
vertical reinforcement as: that interface surfaces must be clean and free of la­
tencies. In addition, intentional roughening of sur­
[(V„/<» - VJs faces and/or horizontal shear ties may also be re­
K = (Eq: 4.3.9)
fyd quired depending on the magnitude of shear force to
be transferred.
Figure 4.12.9 may be used to design shear rein­
ACI 318-95 includes two methods for design of
forcement by Eq. 4.3.9 for a given excess shear. Stir­
horizontal shear transfer. The procedure recom­
rup size, strength or spacing can be varied. Welded
mended and described below is in Code Sect. 17.5.3.
wire reinforcement may also be used for shear rein­
In a composite member which has an interface
forcement in accordance with Sect. 11.5.1 of ACI
surface that is intentionally roughened but does not
318-95; Sects. 12.13.2.3 and 12.13.2.4 give develop­
have horizontal shear ties, or where minimum ties are
ment requirements.
provided in accordance with Code Sect. 17.6 but the
surface is not intentionally roughened, Ft, should not
Example 4.3.5 Use of Figure 4.12.9—Shear
exceed <p80bv€vh, where by is the width of the inter­
Reinforcement
face surface and ^ is the horizontal shear length as
Given:
defined in Figure 4.3.5. (Note: Experience and tests
Double tee of Examples 4.3.3 and 4.3.4 indicate that normal finishing methods used for pre­
Problem: cast concrete structural members will qualify as “in­
Design shear reinforcement for: tentionally roughened” . Thus, horizontal shear
strength of ^ O b / * may be used for design.)
(Vu/<i>) - v c = 10,000 lb For an interface surface which is both intentionally
Solution: roughened and includes minimum horizontal shear
The horizontal shear force, Fh, which must be re­ ties per Code Sect. 17.6, Fh is limited to:
sisted is the total force in the topping; compression in
Fh = t|>(260 + 0.6pvfy)Z.bv-£vh and (Eq. 4.3.10)
positive moment regions and tension in negative mo­
ment regions as shown in Figure 4.3.4. Fh < (f>500bvlvh

Excess shear per stem For Fh exceeding <p500bv€vh, the area of horizontal
shear ties required in length ^vhmay be calculated by:
= 1/ 2 [ ( V u / c | > ) - v c )/ d ] = 1^ ( 1 0 , 0 0 0 / 2 0 . 8 )

= 240 Ib/in

From Figure 4.12.9:


where:
Use one row per stem of welded wire reinforce­ Acs = area of horizontal shear ties, in2
ment W4.0, vertical wire spacing = 6 in. Fh = horizontal shear force, lb
fy = yield strength of horizontal shear ties, psi
[(Vu/<|>) - Vc)/d] provided per stem Pe = effective shear-friction coeff. (Eq. 4.3.16).
= 400 Ib/in > 240 Ib/in OK <|) = 0.85

PCI Design Handbook/Fifth Edition 4 -3 5


Figure 4.3.3 Solution for Example^4.3.3
1 1
SAND-LIGHTWEIGHT
CONCRETE, 1-= 0.85
10C
SHALLO W DRAPE

L----CL
b
80
■ V c s i yf bwd = 301 JS) = 59.4 kips
Vc
60
OR 20
Vu /f
40
n
N ^=10

(Id =50\^ 2 i y?: bwd = 26 3 kips


------
20
e —1

D
0.10 0.20 0.30 0.40 0.50
x/f

Figure 4.3.4 Horizontal shear in composite section


POSITIVE MOMENT SECTION:

CASE1: C < C c
C Fh = C = T
CAST-IN-PLACE

CASE 2: C > Cc
PRECAST -
Fh = Oc < T

Ag OR Aps -► T

CASE 1 CASE 2
NEGATIVE MOMENT SECTION:

' • • • -► T Atop = EFFECTIVE AREA OF CAST-IN-PLACE

ls or Aps
r '* ■*
Cc =
COMPOSITE TOPPING
COMP. FORCE CAPACITY OF THE
COMPOSITE TOPPING = 0.85 fee Atop

C = TOTAL COMPRESSIVE FORCE


T = TOTAL TENSILE FORCE = Asfs OR Apsfps
a =
fee COMPRESSIVE STRENGTH OF THE TOPPING

Fh = HORIZONTAL SHEAR FORCE


Ft, = T = C

For composite members, p = 1.OX and Acr = bv€vh, sion o f , or placed the same as shear reinforcement.
therefore: Sect. 17.6.1 of ACI 318-95 also requires that ties,
when required, be spaced no more than four times
1OO0X2b,v'-vh the least dimension of the supported element, nor 24
He = < 2 .9 (Eq. 4.3.12)
in., and meet the minimum shear reinforcement re­
quirements of Sect. 11.5.5.3:
(See Table 4.3.1)
A _ 5 0 b / vh
“ cs.min x (Eq. 4.3.14)
The value of Fh Is limited to: w
Fh/<|>(max) = 0.25X2fc b / vh
Anchorage of ties must satisfy Code Sect. 17.6.3.
< lOOOX2^ ^ (Eq. 4.3.13) Research [4] has shown that this requirement can be
Sect. 17.5.3.1 of the Code requires that ties be satisfied by providing a minimum distance of 1.75,
placed along the member to “approximately reflect 2.5 and 3.25 in. between the shear transfer interface
the distribution of shear forces in the member.” Thus and the outside ends of standard hooks on No. 3, No.
the horizontal shear ties are usually either an exten- 4 and No. 5 ties respectively.

4 -3 6 PCI Design Handbook/Fifth Edition


Example 4.3.6 Horizontal Shear Designator Figure4.3.5 HorizontaKshear length
Composite Beam

Gftsnr
inverted-tee beamwith 2-in. composite-topping
(See Example 4.2.6)

Beam length = 2 0 ft - 0 in.

Concrete:
fc (precast) = 5000 psi
tie (topping) = 3000 psi

Prestressing steel:
12-1/2 in. diameter 270K strands
ApS = 12 x 0.153 = 1.836 in 2 SIMPLE SPAN MEMBER
Tie steel: fy = 60,000 psi

Problem:
Determine the tie requirements to transfer hori­ Therefore, ties are required.
zontal shear force. X = 1.0 (normal weight concrete)

Solution: Check maximum by Eq. 4.3.10:


bv =12 in. H^nnh - . 0.85(500)(12)(120)
1000
, 20(12)
^vh = 2 = 120 in- = 612.0 kips > 405.6

Atop = 2(44) + 2(12) = 112 in2 Therefore, design by Eq. 4.3.10:


4>(260 + 0.6pvfy)Xbv€vh = 405,600
C = 0.85f^Atop + Asfy =0.B5(3)(112) + 2(60)
= 285.6 + 120.0 = 405.6 kips (f)Xb/vh= 0.85(1.0)(12){120) = 1224 in2
A« AAA, 405,600 - 260(1224)
fps = 260.2 ksi (see Example 4.2.6) 0.6pv(60,000) = ----- :------^ ^ 4 --------

Apsfps = 1.836(260.2) = 477.7 kips > 405.6 p„ = 0.00198

Therefore: Acs= 0.00198(12) (120) = 2.85 in2


Fh = 405.6 kips Check minimum requirements:

cj>80bv€vh = 80(0.85) (12) (120)/1000 _ 50bv€vh 50(12)(120)


“ •m,n f„ 60,000
= 97.9 kips < 405.6 = 1.20 in2

PCI Design Handbook/Fifth Edition


4 -3 7
Use No. Sties, ^ = 2(0. 11) = 0.22 in2 4.3.6 Shear-Friction
Maximum tie spacing = 4(4) = 16 in. < 24 in.
Shear-friction is an extremely useful tec! in the de­
For Acs = 2.85in 2, number of ties in length €*,
sign of precast and prestressed" concrete structures.
= 2.85/0.22 « 1 3 Use of the shear-friction theory is- recognized by-
Total number of ties in the beam = 26“ S e ct 11.7 of ACI 318-95, which states that shear fric­
Provide 5 No. 3 ties at 6 in. spacing at each and tion is “to be applied whereit is appropriate to consid­
and the remaining 16 No. 3 at approximately 11 in. er shear transfer across a given plane, such as an ex­
isting or potential crack, an interface between
spacing in the middle portion of the beam.
dissimilar materials, or an interface between two con­
In this example it is assumed that the full flange
cretes cast at different times.”
width of 44 in. is part of the composite section. Con­
A basic assumption used in applying the shear-
trol joints in topping, particularly in parking garages,
friction concept is that concrete within the direct
are often located along the joints between ends of
shear area of thenonnection will crack in the most un­
double tees and edges of tee beams for crack control
desirable manner. Ductility is achieved by placing re­
as shown in the example figure. This raises the con­
inforcement across this anticipated crack so that the
cern that the extended parts of the topping on each
tension developed by the reinforcement will provide a
side of the tee beam web (16 in. for this example) may
not behave compositely with the rest of the section. force normal to the crack. This normal force in com­
bination with “friction” at the crack interface provides
However, it can be shown that the usual steel pro­
the shear resistance. The shear-friction analogy can
vided in the topping, in most cases, generates suffi­
be adapted to designs for reinforced concrete bear­
cient shear friction resistance (see Sect. 4.3.6) to en­
ing, corbels, daps, composite sections, and other ap­
sure composite action. The following calculations
plications.
support this observation.
An “effective shear-friction coefficient," |ie, may be
The topping reinforcement is: used [9] when the concept is applied to precast con­
6 x 6 - W2.9 x W2.9 crete construction. The shear-friction reinforcement
nominally perpendicular to the assumed crack plane
As = 0.058 in2/ft
can be determined by:
= 0.58 in2 per V6 span
= (Eq. 4.3.15)
The portion of the total compression force in the c|)fy[ie
extended part of topping:
where:
C’c = (285.6) = 81.6 kips <|> = 0.85
A*, = area of reinforcement nominally perpen­
_ 1000(1.0) (2) (120)(1)(1.4) dicular to the assumed crack plane, in2
1X6 ~ 817600 4.12 >3.4 fy = yield strength of A*,, psi (equal to or less
than 60,000 psi)

A“ J olsfritjw = 039 ln*< 0 58 0K Vu = applied factored shear force, parallel to


the assumed crack plane, lb (limited by
the values given in Table 4.3.1)
A“ “ = ^ kT oS T * °'2ir,z < 0 39 ir|! 0K
lOOOXAcrU
(Eq. 4.3.16)
Maximum spacing = 4(2) = 8 in. Vu

Thus 6 x 6 - W2.9 x W2.9 is adequate. < values in Table 4.3.1


Table 4.3.1 Shear-friction coefficients

Crack interface condition Recommended |i Maximum m Maximum V n = V u <(>

1, Concrete to concrete, cast


1.4J. 3.4 0 .3 0 ^ Acr < 1000X2Acr
monolithically

2. Concrete to hardened concrete,


1.0)1 2.9 0 .2 5 ^ A ct < 1OOOIi2A cr
with roughened surface

3. Concrete to concrete 0.6k 2.2 0 .2 0 ^ A „ < 800>,2Acr


4. Concrete to steel 0.7k 2.4 0.201% Aa < 800x2Acr

4 -3 8 PCI Design Handbook/Fifth Edition


I = factor for use with lightweight concrete, Figure 4.4.1 Space truss analogy
see S ect 4.3.3
(x = shear-friction coefficient (valuesJn Table
4.3.1)
Acr = area of the crack interface, in2

When axial tension is present additional reinforce­


ment area should be provided:

where:
An = area of reinforcement required to resist
axial tension, in2
Nu = applied factored tensile force
nominally perpendicular to the assumed
crack plane, lb. May betaken as 0.2 times
The new torsion design provisions introduce the
the factored sustained parallel force [14],
following additional terms:
= 0.85
Acp = area enclosed by outside perimeter of con­
All reinforcement, either side of the assumed
crete cross section
crack plane, should be properly anchored to develop
the design forces. The anchorage may be achieved Ao = gross area enclosed by the shear flow path
by extending the reinforcement for the required de­ Aoh = area enclosed by the centerline of the outer­
velopment length (with or without hooks), or by weld­ most closed transverse torsional reinforce­
ing to reinforcing bars, angles or plates. ment
pcp = outside perimeter of the concrete cross sec­
tion
4.4 Torsion
ph = perimeter of the centerline of the outermost
A C I318-95 provisions for torsion design are com­ closed transverse torsional reinforcement
pletely different from those in previous Code editions. When determining these quantities for non-rec-
They are based on a thin walled tube, space-truss tangular sections, only those portions of the section
analogy. Solid sections are idealized as tubes, with containing closed ties are included. For example, if
the inner core neglected. The truss analogy, or strut- the ledge in a ledger beam is reinforced with U-bars
and-tie analysis, is illustrated in Figure 4.4.1. After instead of closed ties, only the vertical stem would be
torsional cracking develops, the torsional resistance included in the determination of the above terms. If
is provided mainly by closed stirrups, longitudinal the ledge contains closed ties, as shown in the exam­
bars, and compression diagonals. Further explana­ ples in this section and Table 4.5.1, the area and rein­
tion can be found in the Commentary to ACI 318-95. forcement of the ledge may also be included.
It is noted that this new ACI 318-95 procedure Design of typical precast members is illustrated in
yields design results comparable to the PCI Hand­ the following procedure:
book, Fourth Edition procedure. This section is limit­
ed to the design of solid sections on simple spans. Step 1.
Sect. 11.6 of ACI 318-95 also includes provisions for Determine the design shear (Vu) and the torsional
hollow sections and continuous spans. For the first moment (Tu) at the following critical sections:
time, prestressed concrete is included. The proce­
dures for prestressed and non-prestressed members Non-prestressed members:
are the same. Prestressed members provide some­ distance d from the support
what higher resistance to torsional stresses, which is
reflected in the steps for determining whether torsion Prestressed members:
needs to be considered in the design (discussed in h/2 from the support
step 3 below). It should be noted that the critical sec­
tion for torsion in simple-span beams is usually near If a concentrated load occurs between the critical
the end of the member where prestress forces may section and the face of the support, the critical sec­
be only partially transferred. This should be consid­ tion shall be taken at the face of the support.
ered when the modifications are applied.

PCI Design Handbook/Frfth Edition 4 -3 9


Step 2. e. Determine:
Determine shear reinforcement requirements: (Av + 2A J/S -- Av/s
for Vn = Vu/<f>, and when Vc < Vu/ct> A,/s (E q 4.4:6)
2
A v _ (Vu/fo) ~ Vc
(Eq. 4.4.1) d. Solve Eq. 4 A 5 fo r 0:
S " fyvd
Tu/<fr
cot© =• (Eq. 4.4.7)
Sfep 3. I.Z A ^ V s )^
Determine if torsion can be neglected:
e. If 30° < 0 < 60° , the stirrup size and spac­
Non-prestressed members:
ing chosen may be used.
Tu < < ! (Eq, 4.4.2)
f. Using the value of 0 calculated in Part d,
continue with steps 6 through 9 below.
Prestressed members:
Step 6.
(Eq. 4.4.3) Check minimum transverse reinforcement:

Av + 2A, = (Eq. 4.4.8)


Tyy
Step 4.
Check to ensure that the required torsional mo­ Maximum stirrup spacing shall not exceed the
ment and shear strengths do not exceed the follow­ lesser of ph/ 8 or 12 in.
ing maximum limit:
Step 7.
Determine longitudinal torsion reinforcement:

Af = y p hcot20 (Eq. 4.4.9)


Note: This form of Code Eq. 11-18 assumes a con­
Step 8.
servative value of Vc/b wd = 2
Check minimum longitudinal torsion reinforce­
ment:
Step 5.
Determine transverse torsion reinforcement: 5/fTAcp At_
assume <j)Tn = Tu (Eq. 4.4.10)
f s

T„ = ^ t c o t e (Eq. 4.4.5) where:

The angle, 0, of the compression strut (Fig 4.4.1) (Eq. 4.4.11)


may be between 30° and 60°. The Code suggests a
value of 0 = 45° for non-prestressed members, and
Maximum longitudinal bar or tendon spacing is 12
0 = 37.5° for prestressed members.
in. and at least one longitudinal bar or tendon shall be
A 0 = 0.85Aoh in each corner of the closed stirrups.
Note: This form of Code Eqs. 11 -22 and 11 -24 as­
It is frequently convenient to use nominal stirrup sumes that the longitudinal and transverse reinforce­
size and spacing for the transverse reinforcement, ments are the same grade.
e.g. # 3 bars at 12 in., or # 4 bars at 12 in. etc. The
strut- and-tie analysis method used here provides the Step 9.
opportunity to take advantage of this modular spac­ Check additional Code provisions.
ing as follows:
a. For design, assume that: 1. If the required longitudinal reinforcement is sig­
nificantly greater than the minimums, check
Tn = Tu/<t> and Vn = VJ<\>
the additional provisions in Code Sects.
b. Pick a stirrup size and spacing and calculate 11.6.3.9 and 11.6.3.10. In most single span
the quantity (Av + 2At)/s. members, the shear and torsion are highest
when moment is low, so these sections will
For example, for #4 bars at 12, have minimum application. In some applica­
(Av + 2At)/s = 2(0.2)/12 = 0.0333 tions, the total reinforcement may be optimized

4 -4 0 PCI Design Handbook/Fifth Edition


by investigating more than one section along Superimposed 20(20) = 0.-4 (1.4) = 0 56
the length o f the member. The longitudinal re­ Window = 0.05 (1.4) = 0.07
inforcement requirements may be reduced by
Spandrel = 0.63 (1.4) = 0 56
placing a few extra transverse stirrups.
L.L.: 50 psf x (20 ft) = 1.00 (1.7) = 1.70
2. Longitudinal reinforcement development. #r
many cases, the bars or tendons witt notbe ful- 5.95
iy developed atthe critical section. Thus it may Problem:
be necessary to provide U-bars at the ends of Determine torsion reinforcement requirements.
the members Japped with the longitudinal rein­
forcement. Solution:
1. Compute shear (Vu) and torsion (TJ at critical
3. Strands may be used as part of the longitudinal
section, located at 1 ft - 9 in. from the face of
reinforcement. However, they must be devel­
the support (see p. 4 -3 0 ):
oped (or the reduced capacity due to partial
development used) and the provisions of Code 3 0/2-1.75 = 13.25 ft from mid-span
SeGt. 11.6.3.10 must be met. wu for shear = 5.95 kips/ft
Vu = 5.95(13.25) = 78.8 kips
Example 4.4.1 Shear and Torsion Design of wu for torsion = 1.68 + 1.06 + 0.56 + 1.70
a Non-Prestressed Member = 5.00 kips/ft

Note: It is sufficiently accurate in this and most pre­


cast concrete sections to use the centroid rather than
the shear center to calculate the eccentricity.
Eccentricity = 2/3 (8) + 3.29 = 8.62 in.
Tu = wu(e) (13.25) = 5.00(8.62)(13.25)
= 571 kip-in.

2. Determine shear reinforcement requirements.

A v _ ( V u/ < t > ) - V c

s fyvd

By Eq. 4.3.2:

Vc = 3.5 bwd (full calculation not shown)

v c = 3 . 5 ^ ( 6 ) ( 6 9 ) = 102.5 kips

(j)Vc = 0.85 (102.5) = 87.1 kips > 55

shear steel is not required. Ay = 0.

Given:
3. AcP(do not include haunch) = 6(72) + 2(8) (6)
Precast load bearing spandrel beam shown.
+ 6(1 )/2 + 6(2)/2 = 537 in2
Span of spandrel beam = 30 ft clear
Tributary width of floor = 20 ft Pep = 2(12) + 72 + (72-9-10) + 2(8) +
fc = 5000 psi, normal weight concrete h 2 + 62 + h 2 + 62 = 177.4 in.
Reinforcement fy = 60,000 psi
d = 69 in By Eq. 4.4.2:

Loads (kips/ft): v/5000/ 5372 \


0.85
1000 \1 77.4/
D.L:
Precast floor 60 psf(20 ft) = 1.2 (1.4) = 1.68 = 97.7 < 571 kip-in.
Topping 38(20) = 0.76(1.4) = 1.06 Therefore, consider torsion.

PCI Design Handbook/Fifth Edition 4 -4 1


571/0.85
4. Assume 1 in. from edge to centerline ofrein- “ 1.7(361 )(Q.0167)(6D) ~ ’
forcement.
ph = 7 0 + 2(10) + 2(6) + 6.1 + 6.3 + 55
0 = 42.4°
= 160 in.
30° < 42.4° < 60° OK
6(12 + 15)
Aoh = 70(4) + = 361 in2
2 Use # 4 at 12 in. closed lies.

6. By Eq. 4.4.8:
By Eq. 4.4.2:
Av+ 2At ^ 5 0 b w 50(6)
S > fyv 60,000

= 0.005 < 0.0167 OK

7. By Eq. 4.4.9:

A( -=A^t p
, hcot20 = 0.0167(169)(1.09)2
< <t>10/5000 = 601 psi b
= 3.35 in2
A 8. By Eq. 4.4.10:
5.a Using Eq. 4.4.5 and solving for y
Ar (min) = s / f T ^ - y P t ,
Tn = ^ ^ c o t0
5/5000(537)
Tn = Tu/tJj -0.0167(169)
60,000
0 = 45°
= 3.16 - 2.82 = 0.33 < 3.28 in2 OK
Ao = 0.85(361) = 307 in2
By Eq. 4.4.11:
Tu/<t> = | ^ = 2 (3 0 7 )(6 0 )^ j(1 )
r h o -i, min A, _ 25b« _ 25(6)
Check min s ^ 60,000

At _ _____ 571_____ n f )1 a o
s 0.85(2)(307)(60) = 0.0025 < 0.0167 OK

9. Detailing requirements:
Total shear and torsion reinforcement =
a. Corner bars.
a ?A Code Sect. 11.6.6.2: bar diameter at least Vk
4* + = 0.00 + 2(0.0182) = 0.0364
b b of stirrup spacing = 0.5 in. Use # 4 bars.
b. Commentary Sect. R11.6.3.8 permits excess
# 4 at 10.99 in. flexural reinforcement to be used as
longitudinal torsion reinforcement. From
separate analysis, flexural reinforcement
5.b Try # 4 at 12 in. = 3 - #8 = 2.37 in2.

M uat critical section =


Av 2At 2(0.20) A
(30 - 1.75)
f + V “ - i r i = 0 0333
= 147 kip-ft

5.C M s = 0 0333 -fit0? = 0.0167 in2/in Flexural reinforcement required at critical sec­
tion = 0.45 in2
5.d By Eq. 4.4.7: 2.37-0.45 = 1.92 in2 can be used for Af
Tu/<t>
c o t0 = Flexural reinforcement also meets the require­
1.7Aoh(At/s)f,yv
ments for corner bars.

4 -4 2 PC I Design Handbook/Fifth Edition


c. Code Sect. 11.6.3.9 permits longitudinal to r­ Example 4.4.2 Shear and Torsion Design in
sional reinforcement in the flexural compres- a Prestressed Concrete
sion zone to be reduced by: Member

Given:
Mu . 415(12) Precast, prestressed concrete spandrel beam
Q.Sdfy( 0.9(69) (60) shown in Figure4.4.2
D.L of deck = 89.5 psf
Provided minimums are maintained.
L.L. = 50 psf
Beam properties:
Total additional longitudinal reinforcement A = 696 in2
required: w t= 725 plf
fc = 5000 psi, normal weight
3.35 - 1 .9 2 - 0.47 = 0.96 in2
fy = 60ksi
# 4 bars at 12 would provide approx. 2 in2. Prestressing:
6- V i in. diameter, 270K strands
Aps = 6(0.153) = 0.918 in2
d = 7 2 in.

Problem:
Determine shear and torsion reinforcement for the
spandrel beam at critical section.

Solution:
1. Calculate Vu and Tu
Determine factored loads:
D.L. of beam = 1.4(0.725) = 1.02 kips/ft
D.L. of deck = 14(0.0895) |^ ) ( 4 )
= 15.04 kips per stem
L.L. = 1.7(0.050) (30) (4)
= 10.2 kips per stem
Vu at support:
= 1.02(14) + 7(15.04 + 10.2)(1/2)
= 102.6 kips
Center of support to h/2:

= 0.5 + ^ = 3.625 ft

Since a concentrated load occurs within h/2, criti­


cal section is at face of support.
Vu at face of support:
= 102.6-1.02(0.5)
Notes: = 102.1 kips
1. For reinforcement detailing considerations, an
Tu at support (assume torsion arm = 8 in):
8 in. beam width is preferable to the 6 in. width
shown in this example. = (15.04 + 10.2)(7)(Vfe)(8)

2. It would be permissible to use #3 bars for A(. = 707 kip-in (same at face of support)
However, since the corner bars must be #4,
2. By Eq. 4.4.1:
usual practice would be to use # 4 for all A(
bars. Av ^ (Vu/<!>) - Vc
S M )

PCI Design Handbook/Fifth Edition 4 -4 3


Figure 4.4.2 Structure for Example 4.4.2
CONNECTIONS MUSTBE

2 75000(8) (72) Acp = 696 in2


81.5 kips
1000 pcp = 75(2) + 16(2) = 182 in.

(|>VC = 0.85 (81.5) = 69.3 kips < 102.1 By Eq. 4.4.3:

Reinforcement is required. •pc

47fT
K (102.1/0.85) - 81.5
0.0089 in2/in.
s (60) (72) 0.85 75000 / 696s 88
1+
1000 1 182, 475000
3. Determine fpc at critical section approximately
11 in. from end of member. From Figure = 183 kip-in. < 707 Consider torsion.
4.12.4, strand develops 170 ksi at 28 in.

(11/28)(170) = 66.8 ksi 4. Assume VA in. from edge to centerline of stir­


rups.
66.8(0.918) = 61.3 kips
ph = 5 + 72 + 72 + 13 + 8 = 17G in.
fpc = = 0.088 ksi Aoh = 5(72) + 9(8) = 432 in2

4 -4 4 PCI Design Handbook/Fifth Edition


By Eq-4.4.44 Af. In this case It maybeadvantageous to place one
or two additional transverse stirrups near the- ends,
whefe-torsionis highest, and reduce the^number of
full length longitudinal bars:
4(0.153)-= 0.61 in2
'102,100 y 707,000 (170)\2
418 psi
4.96-0.61 = 4.35 in2
8(72) j- 1.7(432)2 )
4.35/0.2= 21.75 Provide at least 2 2 - # 4 (See
detail below).
(JjloVfT =0.85(10)75000
=601 psi > 413 OK 8. Check maximum spacing and minimum A€.
2 bars in ledge, 10 per side
5. Determine transverse reinforcement.
spacing = = 7 in. < 12 OK
Tn = Tu/<j) = 707/0.85 = 832 kip-in.
By Eq. 4.4.10:
Try # 4 at 12 in.
= 5 7 fT ^ -^ p h
(Av + 2AJ 2(0.20) tyf ®
s 12
0, „
= 0.0333 in2/in.

Av/s = 0.0089 = 2.03 in2 < 4.35 OK

. , 0.0333 - 0.0089 Check minimum longitudinal torsion reinforcement:


A,/s = -----------^-----------
By Eq. 4.4.11:
= 0.0122 in2/in.
S =25^ = S = 0 0033 < 0 0 1 2 2 0 K
By Eq. 4.4.7:

Tu/4> 9. Since longitudinal bars are not fully devel­


c o t0 = oped at the critical section, provide U-bars at
1.7Aoh(At/s)fyv
the ends. (See sketch below.)
707/0.85
c o t0 = = 1.55
1.7(432)(0.0122)(60)

0 = 32.9° > 30° < 60° OK

Use # 4 at 12 in.

6. Check minimum transverse reinforcement:

By Eq. 4.4.8:
50(8)
60,000

= 0.0067 < 0.0333 OK


7. Design longitudinal reinforcement:

By Eq. 4.4.9:

Af = y p hcot20

= 0.0122(170)(1.5472)2 = 4.96 in2

From step 3, strand has developed more than 60


ksi and at face, none is required for flexure, so 4
strands on the perimeter may be included as part of

PCI Design Handbook/Frfth Edition 4 -4 5


4.5 Beams with Ledges 4.5.2 Transverse (Cantilever) Bending ofthe
Ledge
As shown in the previous example, one o f the
most common occurrences of torsion in preeast Transverse (cantilever) bending of the ledge re
members is tnL-shaped beams (beams with a ledge quires flexural reinforcement, Ag, which iscomputed
on one side). Significant torsion may aiscr occur in in­ by Eq. 4.5.4. Such reinforcement may be uniformly
verted tee beams with severely unbalanced loads. spaced over a width of 6he on either side ofthe bear­
This section covers addtfional design items relatedio ing, but not to exceed half the distance to the next
the beam endandthe ledge and its attachment tothe load. Bar spacing should not exceed the ledge depth,
web. These items are discussed in Refs. 10 through h{, or 18 in.
13 and are covered as shown in Figure 4.5.1.
(Eq. 4.5.4)
4.5.1 Shear Strength of the Ledge

The design shear strength of continuous beam


(See Figure 4.5.1 for definitions).
ledges supporting concentrated loads, can be deter­
mined by the lesser of Eqs. 4.5.1 and 4.5.2: 4.5.3 Longitudinal Bending of the Ledge
for s > bf + h#
Longitudinal reinforcement, calculated by Eq.
4.5.5, should be placed in both the top and bottom of
(j)Vn = 3 ^ h([2(b{ - b) + b t + h j
the ledge portion of the beam:
(Eq. 4.5.1)

Ar = 2 0 0 (b r- b)d{/fy (Eq. 4.5.5)


<j>Vn = <j>*.yfjThe[2(bf - b) + bt + hf + 2de]
where:
(Eq. 4.5.2)

For s < bt + h(, and equal concentrated loads, dt = design depth of A f reinforcement.
use the lesser of Eqs. 4.5.1.a, 4.5.2.a or 4.5.3 (See Figure 4.5.1 for other definitions.)

<\>Vn = 1 hf [ 2( b{ — b) + bt + h{ + s] 4.5.4 Attachment of the Ledge to the Web


(Eq. 4.5.1a)
Hanger steel, Ash, computed by Eq. 4.5.6 is re­
quired for attachment of the ledge to the web. Dis­
\u M . (bt + hf) , ^ .
<t>Vn = Q k ifc hf (bf - b) + — r — + de + s
tribution and spacing of A ^ reinforcement should fol­
low the same guidelines as for Ag reinforcement in
(Eq. 4.5.2a) Sect. 4.5.2. Agh is not additive to shear and torsion
where: reinforcement designed in accordance with Sects.
<|) = 0.85 4.3 and 4.4.

he = depth of the beam ledge, in


= ^ (m ) (Eq. 4.5.6)
b = beam web width
b ( = width of web and one ledge, in where:
bt = width of bearing area, in Vu = applied factored load
s = spacing of concentrated loads, in $ = 0.85

de = distance from center of load to the end of fy = yield strength of Agh reinforcement
the beam, in m = a modification factor which can be derived
from Eqs. 6 through 9 of Ref. 13 and is
If the ledge supports a continuous load or closely
dependent on beam section geometry (see
spaced concentrated loads, the design shear
Table 4.5.1), and a factor y, which accounts
strength is:
for proportioning of applied torsion between
4,Vn = 24<t>hfX/fT (Eq. 4.5.3) the ledge and the web. If closed stirrups are
provided in the ledge, y,may conservatively
where: be taken as 1.0. If closed stirrups are not
()>Vn = design shear strength, ib/ft provided in the ledge, y, may be taken as
zero.
If the applied factored load exceeds the strength
as determined by Eqs. 4.5.1,4.5.2 or 4.5.3, the ledge In the case of an inverted tee beam with unbal­
should be designed for shear transfer and diagonal anced loads, “an equivalent bf” can be calculated as
tension in accordance with Sects. 4.6.3.2 through shown in Figure 4.5.2. Use the values of e0 and b
4.6.3.4.
shown in Figure 4.5.2.

4 -4 6 PCI Design Handbook/fifth Edition


Figure 4.5.1 Designof beam le d g e r

(B) SECTION
EQUILIBRIUM AND CONNECTION REINFORCEMENT OF LEDGER BEAM
SURFACES IN BEAM LEDGES (NOTE: REINFORCEMENT REQUIRED FOR FLEXURE AND INTERNAL TORSION IS
NOT SHOWN)

* For members on bearing pads, Nu should be taken as at least 0.2 times the
factored dead load portion of Vu, unless it can be shown as less by calculation.

Figure 4.5.2 Unbalanced loads on an 4.5.5 Out-of-Plane Bending Near Beam End
inverted tee beam
In the Ref. 13 study, it was found that when the
reaction is not colinear with applied loads, as illus­
trated in Figure 4.5.1, the resulting out-of-plane
bending may require additional vertical and horizon­
tal reinforcement. These are computed by Eq. 4.5.7
Vi < V 2 and provided on the inside face of the beam. This re­
inforcement is not additive to the reinforcement for in­
_ VA~Vi«i
e0 =
V, + V ternal torsion. The Aw* and A** bars should be evenly
distributed over a height and width equal to l \ See
EQUIVALENT a = e0 - b/2
Figure 4.5.1(D).

Am = A" e = 2^ (Eq’ 4’5 '7)

Terms are as shown in Figure 4.5.1(B).


where:
IF EQUIVALENT a IS NEGATIVE, USE ENGINEERING Vu = factored shear force at critical section
JUDGEMENT AND STATICS TO DETERMINE FORCE
IN HANGER STEEL. e = eccentricity, see Figure 4.5.1(B).
IF EQUIVALENT a IS POSITIVE, EQ. 4.6.6 MAY BE <j) = 0.85 (Note: The use of cp = 0.85 instead
USED TO DESIGN THE HANGER STEEL. FIND “m"
FROM TABLE 4 .5.1 WITH b f = 3a / 2 .
of 0.90 (flexure) compensates for the use
of dw in place of the actual, somewhat
smaller, lever arm.)

PCI Design Handbook/Fifth Edition 4 -4 7


fy = yield strength By Eq. 4.5.4:
dw = depth of Aw and AWf reinforcement from
outside face of beam

Note that if the out-of-plane eccentricity, e, is very


-smalt, the additional reinforcement may not be re­
quired.
= 0.23 in2
6h, = 6 ft > s/2 = 2 ft

Exam ple 4.5.1 Ledger Beam En d and Ledge Therefore distribute reinforcement over s/2 each
Design side of the load.
Given: (s/2) (2) = 4 ft
8 ft wide double tees resting on a standard L-beam Maximum bar spacing = h f = 12 in.
similar to that shown in Figure 4.5.1. Layout of tees is
Use # 3 bars at 12 in. = 0.44 in2 for each 4 ft
irregular so that a stem can be placed at any point on
the ledge.
Place 2 additional bars at the beam end to provide
VQ = 18 kips per stem equivalent reinforcement for stem placed near the
Nu = 3 kips per stem end.
hf =12 in. By Eq. 4.5.6:
d = 11 in.
d* = 11 in. A^ ^ (m> = 0^ 0)<1-33) = o'4 7 in !
bt = 3 in.
Note: m = 1.33 is obtained from Table 4.5.1 corre­
bf = 14 in.
sponding to: bf/b = 14/8=1.75, fu/h = 12/36 = 0.33,
h = 36 in. b = 8, and yt = 1.0 (closed stirrups in the ledge).
b = 8 in.
Ash = ^ = 0.12 in2/ft
s = 48 in.
fc = 5000 psi (normal weight) Maximum bar spacing = h« = 12 in.
fy = 60 ksi ASh = #3 at 10 in. = 0.132 inP/ft

Problem: By Eq. 4.5.5:


Investigate the strength of the ledge and its attach­ 200(b, - b)d, 200(14 - 8) (11)
ment to the web. Determine required reinforcement. Af fy 60,000

Solution: = 0.22 in2

Minimum de = bt/2 = 1.5 in. Use 2 -# 3 top and bottom = 0.22 in2

By Eq. 4.5.7
Since s > bt + h< and de < 2(b* - b) + bt + h<
Vue
use Eq. 4.5.2: Awv — Awf —
2<j)fydw

<[>Vn = (2(bf - b) + bt + h{ + 2de)


Assume:
= 0.85 (12) (1) 75000 [2(6)+3 +12 + 2(1.5)] Vye = 820 kip-in.
= 21,600 lb = 21 .6 kips > 18 OK
dw = b -1 .2 5 = 6.75 in.

Determine reinforcement for flexure and axial ten­ hs = 18 in.


sion: = A 820
we 2(0.85) (60) (6.75)
Shear span, a = %(bc - b) + VA = 5.25 in
= 1.19 in2

4 -4 8 PCI Design Handbook/Fifth Edition


Table 4,5.1 Modification factor, m,Tor design of hangersteel

{E q . 4.5.6) BAR MUST BE DEVELOPED


ABOVE AND BELOW CRITICAL
SECTION AT TOP O F LEDGE-

where:

(d + a) - ( 3 - 4 ) ( ^ ) ( t ) - ^
Sx2y

m=

x,y = shorter and longer sides respectively, of the component


rectangles forming the ledge and the web parts of the beam.
Yt = 0, when closed ties are not used in the ledge.
= 1.0 when closed ties are used in the ledge
The table values are based on the following assumptions: Vu

(1) d = b - 1.25 I
(2) Vu is applied at a distance equal to % of the ledge
projection from the inside face of web.

(x*y), _ (hr ~ b)2T CLOSED TIES


(3) 2x2y ............. h,
WHEN REQUIRED
<b, - b )» ^ + b2 (SEE SECT. 4.4)

This is a conservative assumption for commonly used ledger beam sizes.

(Note: A lower limit of m = 0.6 is suggested to account for the limited variability in beam sizes tested.
Values of m smaller than 0.6 are flagged with * in the table.)
Modification factor, m

\r t b = 6 in. b = 8 in. b = 10 in.

b r/b h{/ h \ 0.00 1.00 0.00 1.00 0.00 1.00


0.10 1.45 1.45 1.36 1.36 1.31 1.31
0.15 1.43 1.42 1.34 1.33 1.29 1.28
0.20 1.39 1.38 1.31 1.30 1.26 1.25
0.25 1.35 1.34 1.27 1.26 1.22 1.21
0.30 1.30 1.29 1.22 1.21 1.18 1.17
0.35 1.25 1.23 1.18 1.16 1.13 1.12
1.25 0.40 1.20 1.18 1.12 1.10 1.05 1.06
0.45 1.14 1.12 1.07 1.05 1.03 1.01
0.50 1.08 1.05 1.01 0.99 0.98 0.95
0.55 1.02 0.99 0.96 0.93 0.92 0.90
0.60 0.96 0.93 0.90 0.87 0.87 0.84
0.65 0.91 0.87 0.85 0.82 0.82 0.79
0.70 0.86 0.82 0.80 0.77 0.77 0.74
0.75 0.81 0.77 0.76 0.72 0.73 0.70
0.10 1.66 1.63 1.56 1.53 1.50 1.48
0.15 1.63 1.59 1.53 1.49 1.47 1.44
0.20 1.59 1.54 1.49 1.44 1.44 1.39
0.25 1.54 1.48 1.44 1.38 1.39 1.34
0.30 1.48 1.41 1.39 1.32 1.34 1.27
0.35 1.42 1.33 1.33 1.25 1.28 1.21
1.50 0.40 1.35 1.26 1.27 1.18 1.22 1.14
0.45 1.28 1.18 1.20 1.10 1.16 1.06
0.50 1.21 1.10 1.14 1.03 1.10 0.99
0.55 1.14 1.01 1.07 0.85 1.03 0.92
0.60 1.07 0.93 1.01 0.88 0.97 0.85
0.65 1.01 0.86 0.94 0.80 0.91 0.78
0 .7 0 0.94 0.79 0.89 0.74 0.85 0.71
0.75 0.89 0.72 0.83 0.68 0.80 0.65

PCI Design Handbook/Frfth Edition 4 -4 9


Table 4.5.1 Modification factoiy m, for design oHvangersteel {continued)
- \ jt b = 6 in . b = 8 in. b = 10 in.

b ,/b k/X
0.10
0.00 1.00
1.80
0.00
1.75
4i00
1.69
0.00 T ;00
i£ r 1:69 1.63-
0.15 1.83 1.73: 1.72 1.63 106^ 1.57
0.20 1,78 1.65 1.67 1.55 1.61 1.50
0.25 1.73 1.57 1.62 1.47 1:56 1.42
0.30 1.66 1.48 1.56 1.38 1.50 1.34
1.75 0.35 1.59- 1.38 1.49 1.29 1.44 1.25
0.40 1.51 1.28- 1.42 1.20 1.37 1.15
0.45 1.43 1.17 1.34 1.10 1.29 1.06
0.50 1.35 1.07 4.26- 1.00 1.22 0.96
0.55 1.26 0.96 1.18 0,90 1.14 0.87
0.60 1.18 0.86 1.11 0.81 1.07 0.78
0.65 1.10 0.76 1.04 0.72 1.00 0.69
0.70 1.03 0.67 3.97 0.63 0.93 0.61
0.75 0.97 0.59* 0.91 0.55* 0.87 0.53*
0.10 2.07 1.64 1.95 1.82 1.88 1.75
0.15 2.03 1.84 1.91 1.73 1.84 1.65
0.20 1.98 1.73 1.86 1.62 1.79 1.57
0.25 1.91 1.62 1.79 1.52 1.73 1.46
0.30 1.84 1.49 1.72 1.40 1.66 1.35
2.00 Q.35 1.75 1.37 1.65 1.28 1.59 1.24
0.40 1.66 1.24 1.56 1.16 1.51 1.12
0.45 1.57 1.11 1.48 1.04 1,42 1.01
0.50 1.48 0.98 1.39 0.92 1.34 0.89
0.55 1.38 0.86 1.30 0.80 1.25 0.78
0.60 1.29 0.74 1.21 0.69 1.17 0.67
0.65 1.20 0.62 1.13 0.58* 1.09 0.56*
0.70 1.12 0.51* 1.05 0.48* 1.01 0.46*
0.75 1.04 0.41* 0.98 0.38* 0.94 0.37*
0.10 2.26 2.05 2.14 135 2.06 1.86
0.15 2.23 1.91 2.10 1.80 2.02 1.73
0.20 2.17 1.77 2.04 1.66 1.97 1.60
0.25 2.10 1.62 1.97 1.52 1.90 1.47
0.30 2.01 1.47 1.89 1.38 1.82 1.33
0.35 1.92 1.32 1.80 1.24 1.74 1.20
2.25 0.40 1.82 1.17 1.71 1.10 1.65 1.06
0.45 1.72 1.02 1.61 0.95 1.55 0.92
0.50 1.61 0.87 1.51 0.81 1.46 0.79
0.55 1.50 0.72 1.41 0.68 1.36 0.65
0.60 1.40 0.58* 1.31 0.55* 1.27 0.53*
0.65 1.30 0.45* 1.22 0.42* 1.18 0.40*
0.70 1.21 0.32* 1.13 0.30* 1.09 0.29*
0.75 1.12 0.21* 1.05 0.20* 1.02 0.19*
\ 9 t b = 12 in. b = 14 in. b = 16 in.

b f/b h,/X
6.1 o
0.00
1.28
1.00
1.26
0.00
126
1.00
1.26
0.00 1.00
1.24
1.25
0.15 1.26 1.25 1.24 1.23 1.23 1.22
0.20 1.23 1.22 1.21 1.20 1.20 1.19
0.25 1.19 1.18 1.17 1.16 1.16 1.15
0.30 1.15 1.14 1.13 1.12 1,12 1.1f
0.35 1.11 1.09 1.09 1.07 1.08 1.06
1.25 0.40 1.06 1.04 1.04 1.02 1.03 1.01
0.45 1.01 0.99 0.99 0.97 0.98 0.96
0.50
0.55
0.60
0.90
0.85

0.85
0.93
0.88
0.82
0.94
0.89
0.84
0.92
0.86
0.81
0.93
0.88
0.83
0.91
0.85
0.80
0.65 0.80 0.77 0.79 0.76 0.78 0.75
0.70 0.76 0.72 0.74 0.71 0.73 0.70
0.75 0.71 0.68 0.70 0.67 0.69 0.66

4 -5 0 PCI Design Handbook/Fifth Edition


Table 4.5.1 Modification factor, m, for design of hanger steeJ (continued)

S jfl b = 12 in. b = 14 in. b— 1£ra.


bf/fr h ,/ b \ JfcOO 1.00 0.00 1.00 0.00 1700
1.47 1.44 1.44 1.42 1.43 1.40
0.15 1.44 1.41 1.42 T.38 1.40 1.37
0.20 1740 1.36 1.38 1.34 1.36 t.32
025 1.36 1.30 1.34 1.28 1.32 1.27
1.50 0.30 1.31 1.24 1.29 1.22 1-27 121
0.35 1.25 1.18 1.23 1.16 1.22 1.15
0.40 1.20 1.11 1.18 1.09 1.16 1.08
0.45 1.13 1.04 1.12 1.02 1.10 1.01
0.50 1.07 0.97 1.05 0.95 1.04 0.94
0.55 1.01 0.90 0.99 0.88 0.98 0.87
0.60 0.95 0.83 0.93 0.81 0.92 0.80
0.65 0.89 0.76 0.87 0.75 0.86 0.74
0.70 0.83 0.69 0.82 0.68 0.81 0.67
0.75 0.78 0.64 0.77 0.63 0.76 0.62
0.10 1.6$ 1.59 1.62 1.56 1.60 05
0.15 1.62 1.53 1.59 1.51 1.57 1.49
0.20 1.58 1.46 1.55 1.44 1.53 1.42
0.25 1.52 1.39 1.50 1.36 1.48 1.35
1.75 0.30 1.47 0.30 1.44 1.28 1.52 1.27
0.35 1.40 1.22 1.38 1.20 1.36 1.18
0.40 1.33 1.13 1.31 1.11 1.30 1.10
0.45 1.26 1.04 1.24 1.02 1.23 1.01
0.50 1.19 0.94 1.17 0.93 1.16 0.92
0.55 1.12 0.85 1.10 0.84 1.08 0.83
0.60 1.04 0.76 1.03 0.75 1.01 0.74
0.65 0.98 0.68 0.96 0.66 0.95 0.66
0.70 0.91 0.59* 0.90 0.58* 0.89 0.58*
0.75 0.85 0.52* 0.84 0.51* 0.83 0.51*
0.10 03 1.71 1.80 1.69 1.76 -------- 0 7 -------
0.15 1.80 1.63 1.77 1.60 1.75 1.58
020 1.75 1.53 1.72 1.50 1.70 1.49
0.25 1.69 1.43 1.66 1.40 1.64 1.39
0.30 1.62 1.32 1.60 1.30 1.58 1.28
0.35 1.55 1.21 1.52 1.19 1.51 1.28
2.00 0.40 1.47 1.10 1.45 1.08 1.43 1.07
0.45 1.39 0.98 1.37 0.97 1.35 0.96
0.50 1.31 0.87 1.28 0.86 1.27 0.85
0.55 1.22 0.76 1.20 0.75 1.19 0.74
0.60 1.14 0.65 1.12 0.64 1.11 0.63
0.65 1.06 0.55* 1.05 0.54* 1,03 0.63
0.70 0.99 0.45* 0.97 0.44* 0.96 0.44*
0.75 0.92 0.36* 0.91 0.36* 0.90 0.35*
“O f 05 1.76 OS 1.76 04 ---------0 5 -------
0.15 1.94 1.66 1.92 1.64 1.90 1.63
0.20 1.89 1.54 1.87 1.52 1.85 1.51
0.25 1.82 1.41 1.80 0.39 1.79 1.38
0.30 1.75 1.28 1.73 1.27 1.71 1.25
0.35 1.67 1.15 1.65 1.14 1.63 1.12
0.40 1.58 1.02 1.56 1.00 1.55 1.00
2.25 0.45 1.79 0.88 1.47 0.87 1.46 0.87
0.50 1.40 0.75 1.38 0.75 1.37 0.74
0.55 1.31 0.63 1.29 0.62 1.28 0.61
0.60 1.22 0.50* 1.20 0.50* 1.19 0.49*
0.65 1.13 0.39* 1.12 0.38* 1.11 0.38*
0.70 1.05 0.28* 1.04 0.28* 1.03 0.27*
0.75 0.98 0.18* 0.96 0.18* 0.95 0.18*

PCI Design Handbook/Fifth Edition 4 -5 1


This amount-should be compared with the rein­
forcement for internal shear and torsion design
(Sects. 4.3 and 4.4) and only the excess-provided
over a width and -height of-18 in.

4.5.6 Pocketed Beams


As an alternative to tteams with ledges, pocketed
beams may be used to provide support for stemmed
members. Because of double tee erection
constraints, pocketed beams can only be used to
support one end of the member. They are frequently
used on the exterior line of columns in parking ga­
rages. Pocketed beams have the advantages of
minimal torsion, simplified forming, economical pro­
duction and a flush interior face.

Example 4.5.2 Shear, Torsion and Dap


Design of a Prestressed
Pocketed Spandrel Beam

Given:
Precast pocketed spandrel beam shown below.

D.L. of deck = 89 psf (10DT34 NWT)


LL. = 50 psf

Beam Properties:
A = 624 in2
b = 8 in.
fc = 5,000 psi
fy = 60 ksi Spandrel:
H = 78 in.
hp = 20 in. (outside) 8(78) (150)
(1.4) = 0.91 klf
144 1000
D s 74 in. (assumed)
wt = 650 plf
Connections at spandrel ends, to columns, not
shown, provide for overall beam torsional equilibri­
Problem:
um. Calculate eccentricity of stem load, e. Stem load
Determine shear, torsion and dap reinforcement
is applied at a distance equal to % of the pocket
for the beam at critical sections. An objective of this
depth from the inside face of the pocket (or V* of the
example is to illustrate the reduced torsion require­
ment of prestressed pocketed spandrel beams. A pocket depth from the outside face of the pocket).
comparison of this problem with Example 4.4.2 (a
similarly loaded spandrel beam with a ledge) will pro­
vide contrasting design solutions.

Factored Loads:
Solution:
Tee Stem: 1. Compute design shear (Vu) and torsion mo­
64 /1 0 \ / 89(1.4) + 50(1.7) ment (Tu) where Tu = 2.5 in. x tee stem load.
33.5 kips/stem
2\2 1000

4 -5 2 PCI Design Handbook/Fifth Edition


Location Vu (kips) T u (k-in) Mu fk-ft)
Support-Face (SF)- 113.5 251.2 5ea [3.5/5090 + 0.3(167)]
V<* = (8) (74— 20)
Pocket A 111.9 251.2 254.0 1-GOO
Pocket B 73.8 167.5- 634.4
= 129 kips
Pocket C 35.8 5 3 .8 824.7

Mid-span 0.0 0.0 827.5


Note: 3.5/5000 + 0.3 (167) = 298 psi OK
298 psi < 5 /5000 = 354 psi, maxVc value.
The critical section is a t the face of the support
since a concentrated load occurs within distance D (JjV™ = (0.85) (129) = 110 kips < Vu
from the pocketed spandrel end.
Therefore:
2. Determine shear reinforcement requirements
using Eq. 4.4.1 at support face (SF) and
pocket (A) and pocket (B). (113.5/0.85) - 129
= 0.00102 in2/in.
60(74)
A v (V u /< t> )~ V c

s M> At pocket B:

At support face using Eq. 4.3.6 (at end of member Use Vc = 2 bw(D - hp)
fpc = OandVp = 0):
Vc = ^ f p ( 8 ) ( 5 4 ) = 61.1 kips
Vc = 3.5 bwD

((73.8/0.85) - 61.1)
= 0.00579 in2/in
= = 146.5 kips 60(74)

<|)VC = 0.85(146.5) = 124.5 kips = 0.0695 in2/ft


<bV
Vu < <()VC but greater than 3. Determine if torsion can be neglected using
Eq. 4.4.3.
Therefore check Avmin versus 2At in torsion design,

since ( y J required = 0.0. N e g le o t lfT „ < ^ ^ .y i + ( - t j


\ /S F

At pocket A: AcP = 8(78) = 624 in*


For prestressing strands located as shown in Figure
4.5.3: Pep = 2(8 +78) = 172 in.

Assume 1* = 170 ksi. (Note that this force is


0 .8 5/5000/ 6242) L . ( 167 \
n ot transferred untH | y j d b = 28 in. from the
1000 1 172 / y 1 + ^4 /5000/

end. See Sect. 4.2.3). = 171.6 kip-in


x _ fse 4(0.153) (170,000)
= 167 psi < 251.2 kip-in at SF, design for torsion
Tpc " bH (8) (78)

Edge ofpocket A is approximately 24 in. from the end >167.5 kip-in at B, design for torsion not
of the beam. required.
4. Check using Eq. 4.4.4 that the required tor­
fpcA = ( |^ )(1 67) psi = 143 psi sion and shear strength do not exceed the
maximum limit which would result in crushing
Vow = ( 3.5 /fT + 0.3fpc)(bwD) of the inclined compression strut.
(Vp = 0 because straight strands are used).

Reduce shear depth D by the height of the pocket,


hp to determine Vm. Use full D for stirrup calculations.

Handbook/Rfth Edition 4 -5 3
Vz
Use 1 in. from edge to center ofstirrups. This U se # 3 at 12 in. {minimum).
provides-approximately 11A in. clear,, which is ade­
quate forpreeast concrete. ^ = -£ i2 .= Q.0183 > 0.00794 OK
e 12

Ph - 2 [8 2(1.5)+78 2(1.5)] - 160.0 in. Note: lf spacingis substantially different from that
A oh= [8-2(1.5)][78 — 2(1.5)1= 375.0in2 selected, 0 should bechecked: 30" < 0 < 60°.

113,500\ , / 251,200(160)) 7. Determine longitudinal I'etnforcemerrt using


8(74) / 1,7(375)2 ) Eq. 4.4.9 and check minimum longitudinal
torsion reinforcement using Eq. 4.4.10 at sup­
= 255psi < <f)10VfT = 601 psi port face and pocket (A):

Maximum Vu and TuOK, no further crushing checking (Ae) min = 2.44 in2 controls
required.
Number of Ae bars should be distributed evenly
around cross-section perimeter with a 12 in. center to
5; Determine transverse torsion reinforcement at
center spacing. This results in a total of 14 bars.
support face (SF) and pocket (A) using Eq.
4.4.5 and solving for A,/s. Angie 0 at SF is Area per bar = 2.44/14 = 0.17 in2
taken at 45° since the prestress force is not
Use # 4 At bars at 12 in. centers.
transferred at that point. (Note:
cote = 1/tan0 and Ao = 0.85 Aoh). 8. Check additional code provisions.
A, _ Tu(tan 0)
s “ cj)(2A0fyv) (1) Since Af reinforcement is minimum no
further checks are necessary.
251.2(1.0)
= 0.00773 in2/in (2) Provide U-bars at the beam ends to devel
0.85(2) (0.85) (375)(60)
op A( and splice to longitudinal bars. Use
class B splice since all Ae bars spliced at
+ = 000102 + 2(0.00773) the same location.

From Design Aid 11.2.8. For 5000 psi, # 4 bars,


= 0.0165 irf/in. 1.0€d = 17 in. and 1.3^d = 22 in.

Extend A( bars minimum of bw + D beyond pocket


Use # 3 at 0.22/0.0165 = 13.3 in.
B since Tu < 193.1 kip-in, therefore not requiring A
or # 4 at 0.40/0.0165 = 24.2 in.
nor A(.

6. Check minimum stirrup requirements using 9. Determine hanger reinforcement Ash at beam
Eq. 4.4.8. pockets using Eq. 4.5.6:
Av+ 2 A ,^ 5 0 b w _ 50(8) _ Q
00667 in2/in Vu = 33.5 kips (tee stem reaction)
f,yv 60,000
use Vu = 33.5 kips/cos 30° = 38.7 kips
Use # 3 at 0.22/0.00667 = 33.0 in.
Use #4 at 0.40/0.00667 = 60.0 in. A» * ' d i p ) = 0 7 6 in! t0 tM> le9S

Maximum spacing is the smaller of Ph/8 or 12 in. Ash per bar leg = 0.76/2 = 0.38 in2
Ph/8 = 160/8 = 20.0 in. Use (1) #6 bar.

Use 12 in. maximum spacing. Ash total 2(0.44) = 0.88 in2

For #6, /d b = 33.9 and = 25.4 in. re­


Select #3 stirrups using spacing of 12 in. from end quired for bar above pocket top.
of beam to pocket B. Extend shear/torsion stirrups
(and At) a distance of bw + D beyond the point no Select #6 with vertical leg length of 48 in.
longer required. Between pockets B and mid-span, minimum.
no torsion reinforcement is required, but shear rein­
forcement must be provided. 10. Select dap reinforcement. See Fig 4.5.4.

4 -5 4 PCI Design Handbook/Fifth Edition


Vu =114.1 kips Direct shear:
VU(DL) = 73.4 kips _ loooXbhpi
Nu = 0.2 VU(DL) = 14.7 kips

Determine the required reinforcements As, Ah, 1000(1) (8) (40) (1.4) (1)
Ash, and Av. 114,100

Assume shear span, a = 9 in., d = 39 in. = 3.93 > 3.4 Use 3.4.

Check shear strength, Table 4.3.1 By Eqs. 4.6.4 and 4.6.5:

<j>Vn(max.) = 4>(1000X2bd) a _ 2VU Nu


3<t>f#e <()fy
= 0.85(1000) (1)2(8) (39)/1000
= 265 kips > 114.1 4<ips OK _ 2(114-1) . 14.7
3(0.85) (60) (3.4) (0.85) (60)

Flexure in extended end by Eq. 4.6.3 = 0.44 + 0.29 = 0.73 < 0.81 in2

Therefore:

As = 0.81 in2
Use 2 - # 6 , As = 0.88 in2
By Eq. 4.6.6:

= 0.81 in2 Ah = 0.5(AS - An) = 0.5(0.81 - 0.29)

PCI Design Handbook/Fifth Edition


4 -5 5
Figure 4.5.4 Dapped-end beam of Example 4.5.2

Av = - 2 - # 4

Note: The minimum distance shown from edge of the dap to the face of the first pocket(15 in.) and the typical
dimension shown for the hanger bar to be placed below the bottom of the pocket (3—5 in.) are Committee
recommendations based on discussions. Research is underway to verify these recommendations.

4 -5 6 PCI Design Handbook/Fifth Edition


= 0.26 in2 Ah bars:

Use 2 -# 3 U-bars, A h = 0.44 in2 From Design Aid 11.2.8, for #4 bars:
Diagonal tension at re-entranf corner: 1.3^tf =-22 in. (say, 2 ft - 0 in);

By Eq. 4.6.7: Aa, bars (see Figure 4.6.3):

_ Vu_ _ 114.1 From Design Aid 11.2.8, for #10 bars:


2.24in2
0.85(60)
€4= 54 in.

Use 2—#10 = 2.54 in2 bar length = H - D + €d


A * is provided by the horizontal legs of the = 78 - 74 + 54 = 58 in.
G-shaped #10 bars.
(say 5 ft - 0 in.)
Diagonal tension at extended end (Sect. 11. Other considerations.
4.6.3.4):
a. For parking garages the spandrel beam
Concrete capacity:
must be checked for vehicle barrier load
= 2X /fT bd criteria. Most codes require the application
- (2)(1) v5000 (8)(39) _ of 6,000 lb (unfactored) applied horizontal­
1000 44,1Kfps ly 18 in. above the floor.
By Eq. 4.6.9^
b. Local code requirements for snow loading,
A = — X - 2Xbd including drifting, should be checked in
v 2fv <P
addition to the 50 psf live load on the roof
decks of parking structures.
_ 1
2(60) ( w - 4 4 1 ) - 0 '7 5 ^
c. 2 - # 5 longitudinal bars shown above
Try 2 -# 4 stirrups = 0.80 in2 strands in Fig 4.5.3 have been added to
satisfy A C I318-95 Sect. 18.8.3. (Additional
Check Eq. 4.6.8:
strand instead of No. 5 bars may be used).
(|>Vn = cj>[Avfy + Ahfy + 2Xbd/fT]
4.6 Bearing
= 0.85 0.80(60) + 0.44(60) 4.6.1 Bearing on Plain Concrete

Plain concrete bearing may be used in situations


2(1)(8)(39)v5000 where the bearing is uniform and the bearing
1000 stresses are low as is typical, for example, in hollow-
core and solid slabs. In other situations, and in thin
stemmed members where the bearing area is smaller
= 101 kips < 114.1 kips
than 20 in2, a minimum reinforcement equal to NJ^fy
Change Ah to 2 -# 4 U-bars. (but not less than one No. 3 bar) is recommended.
c|>Vn = 119kips > 114.1 kips OK (Note that Ref. 14 recommends that Nu be taken as
0.2 times the sustained load portion of Vu unless
otherwise calculated).
Check anchorage requirements:
The design bearing strength of plain concrete may
As bars: be calculated as:
From Design Aid 11.2.8:
4>Vn = <j)Cr(0.85fc A ^ ^ 1.2fc A, (Eq. 4.6.1)
fy = 60,000, V Ai
fc = 5000 psi, #6 bars where:
1.3^d = 33 in.
<j>Vn = design bearing strength
Extension past dap = H - d + 1.3€d (see Figure
4.6.3) <j) = 0.70
= 78 - 39 + 33 Nu

= 72 in. (6 ft - O in.)

PCI Design Handbook/Fifth Edition 4 -5 7


= 1.0 when reinforcement is proyided in Example 4.6.T Reinforced Bearing for a
direction o f Nu, in accordance with Rectangular Beam
Sect. 4.6.2 or when Nu is zero. The
Given:
product sw should not be taken greater
PC! standard rectangular beam 16RB28-
than 9 .0 in2
A-t = loaded area Vu— 94 kips (includes all load*factors)
A2 = maximum area of the portion of the Nu = 15 kips (includes all load factors)
supporting surface that is geometrically Bearing pad = 4" x 14"
similar to and concentric with the
fy = 60,000 psi (all reinforcement)
loaded area (see Figure 4.6.1)
fc = 5000 psi (normal weight)

Problem:
Determine reinforcement requirements for the end
4.6.2 Reinforced Concrete Bearing of the member.

If the applied load,VUl exceeds the design bearing Solution:


strength, <t>Vn, as calculated by Eq. 4.6.1, reinforce­ Acr= b(h) =16(28) = 4 4 8 in2
ment is required in the bearing area. This reinforce­ Check max Vn from Table 4.3.1
ment can be designed by shear-friction as discussed
lOOOXX = 1000(1.0)2(448)/1000 = 448 kips
in Sect. 4.3.6. Referring to Figure 4.6.2, the reinforce­
ment Avf + An nominally parallel to the direction of the max Vu = 0.85(448) = 381 kips > 94 OK
axial load, Nu, is determined by Eqs. 4.3.15 through
By Eq. 4.3.16:
4.3.17withAcre qualtobxh(i.e., 0 « 0°,see Ref. 14).
1000XAor(i 1000(1) (448) (1.4) (1)
This reinforcement must be appropriately developed
1X6 “ Vu " 9 4 ,0 0 0
by hooks or by welding to anchor bar, bearing plate
or angle. = 6.67 > 3.4, use 3.4
Vertical reinforcement across potential horizontal
cracks can be calculated by: By Eq. 4.3.15:

A Vu 9 4 ,0 0 0
* <|>fyHe 0 . 8 5 ( 6 0 ,0 0 0 ) ( 3 .4 )
_ (Avt + A n) f y
(Eq. 4.6.2) = 0.54 in2
‘Sh ~ Fefys

where: By Eq. 4.3.17:


lOOCMcrli A - Nu - 15,000
^ ~ (A* + An)fy n <t>fy 0.85(60,000)

fys = yield strength of Ash, psi = 0.29 in2


A*, + An = 0.54 + 0.29 = 0.83 in2
Act = €„b, in*
Use 3 - # 5 = 0.93 in2
Determine ( d from Design Aid 11.2.8 for
b = average member width, in fc = 5,000 psi:

(d = development length of A^f + An bars, in = 21 in.

Acr = fdb = (21) (16) = 336 in2

Stirrups or mesh used for diagonal tension rein­ 1000(1 )(336K1.4)(1) _


9 . 4 4 > 3 .4
forcement can be considered to act as Agh reinforce­ ^ ~ 0.83(60,000)
ment. Use [xe = 3.4
When members are subjected to bearing force in _ (A* + An)fy _ 0.83(60,000)
= 0.24 in2
excess of t.2fc A^, confinement reinforcement in all * Pefys 3.4(60,000)
directions may be necessary.
Use 2 -# 3 stirrups = 0.44 in2

4 -5 8 PCI Design Handbook/Fifth Edition


3b. Tor members B in. or more wide, less than %
ofthem ain flexural reinforcement extendsto
the end of the member ^above the dap.
These criteria indicate thaTonly short, shadow re­
presses, having the minimum amount of main rein­
forcement or more extending into the nib above The
dap; do notrequire all the dap reinforcement Experi­
ence and some unpublished teste verify that, for
short, shallow recesses, the hanger reinforcement,
and A 'sh is not necessary. However, in these
cases it is recommended that confinement reinforce­
ment, Av, and flexural reinforcement, A^+An in accor­
dance with Sect. 4.6.2, be provided.
Ref. 26 supports the above criteria for determining
when a dap requires full dap reinforcement. It also
contains information on cases when a/d exceeds 1.0.
The potential failure modes are as follows:
1. Flexure (cantilever bending) and axial tension
in the extended end. Provide flexural reinforce­
ment, Af, plus axial tension reinforcement, An.

2. Direct shear at the junction of the dap and the


main body of the member. Provide shear-fric­
tion reinforcement composed of A* and Ah,
plus axial tension reinforcement, An.

3. Diagonal tension emanating from the re-en­


trant corner. Provide shear reinforcement, Ash.

4. Diagonal tension in the extended end. Provide


shear reinforcement composed of An and Ay.

5. Diagonal tension in the undapped portion. This


is resisted by providing a full development
4.6.3 Dapped-End Bearing length for As beyond the potential crack [15].
Design of bearing areas which are recessed or
dapped into the end of the member requires the in­ Each of these potential failure modes should be in­
vestigation of several potential failure modes. These vestigated separately. The reinforcement require­
are numbered and shown in Figure 4.6.3 and listed in ments are not cumulative, that is, As is the greater of
this section along with the reinforcement required for that required by 1 or 2, not the sum. A* is the greater of
each consideration. The design equations given in that required by 2 or 4, not the sum.
chis section are based primarily on Refs. 15 and 16,
4.6.3.1 Flexure and Axial Tension in the
and are appropriate for cases where shear span-to- Extended End
depth ratio (a/d in Figure 4.6.3) is not more than 1.0.
Dap reinforcement (Eqs. 4.6.3 through 4.6.9) The horizontal reinforcement is determined in a
should be provided in all cases where any one or manner similar to that for column corbels, Sect. 6.8.
more of the following conditions occurs: Thus:
As = A^+ An
1. The depth of the recess exceeds 0.2H or 8 in.

2. The width of the recess (€p in Figure 4.6.3)


exceeds 12 in.
where: <|>= 0.85*
a = shear span, in., measured from load to
center of A ^
3a. For members less than 8 in. wide, less than * To be exact, Eq. 4.6.3 should have j ud in the denominator.
The use of <j> = 0.85 instead of 0.90 (flexure) compensates for
1/z of the main flexural reinforcement extends
this approximation. Also, for uniformity <|> = 0.85 is used
to the end of the member above the dap. throughout Sect. 4.6 even though <p = 0.90 would be more
appropriate and may be used where flexure and direct tension
are addressed.

PCI Design Handbook/Frfth Edition 4 -5 9


Figure 4.6.2 Reinforced concrete bearing

ALTERNATE SCHEME FOR A * + An ANCHORAGE


AT BEARING
NOT RECOMMENDED FOR DOUBLE TEE STEMS

PLAN VIEW

h = depth of the member above the dap, in d = distance from top to center of the rein­
forcement, Ag, in

fy = yield strength of the flexural reinforce­ The shear strength of the extended end is limited
ment, psi by the maximum values given in Table 4.3.1.
Nu = 0.2 times sustained load portion of Vu
unless otherwise cafculated [14]. 4.6.3.3 Diagonal Tension at Re-entrant Corner

The reinforcement required to resist diagonal ten­


4.6.3.2 Direct Shear sion cracking starting from the re-entrant corner,
shown as 3 in Figure 4.6.3, can be calculated from:
The potential vertical crack shown in Figure 4.6.3
is resisted by a combination of As and Ah. This rein­
forcement can be calculated by Eqs. 4.6.4 through
4.6.6.
where:
A — l- A (Eq. 4.6.4)
S 3<t)fyHe " 4> = 0.85
Vu = applied factored load
<

(Eq. 4.6.5)
II
£

Ash = vertical or diagonal bars across poten­


tial diagonal tension crack, in2
Ah = 0 .5 (A s-A n) (Eq. 4.6.6)
fy = yield strength of A ^

where:
4.6.3.4 Diagonal Tension in the Extended End
$ = 0.85
Additional reinforcement for crack 4 in F ig u r e 4.6.3
fy = yield strength of As, An, Ah, psi is required in the extended end, such that:
1000X,bhn . . _ ,. , _ .
He = — rj— - < values in Table 4.3-. 1 <j>Vn = <j>(Avfy + Ahfy + 2Xbd /fT) (Eq. 4.6.8)

4 -6 0 PCI Design Handbook/Fifth Edition


flexure reinforcement may also be used to en­
(Eq. 4.6.9) sure development of Ash reinforcement pro­
vided that the flexure reinforcement is ade-
quately anchored on the dap side.
4.6.3.S Anchorage of Reinforcement
4. Vertical reinforcement A should be properly
With reference to Figure 4.6.3:
anchored by hooks as required by A C I318-95.
1. Horizontal bars As should be extended a mini­
5. Welded wire reinforcement in place of bars
mum of t d past crack 5, and" anchored at the
may be used for reinforcement. It should be an­
end of the beam by welding to cross bars,
chored in accordance with ACI 318-95.
plates or angles.

2. Horizontal bars Ah should be extended a mini­


mum of t d past crack 2 and anchored at the 4.6.3.6 Other Considerations
end of the beam by hooks or other suitable
1. The depth of the extended end should not be
means.
less than about one-half the depth of the beam,
unless the beam is significantly deeper than
3. To ensure development of hanger reinforce­
necessary for other than structural reasons.
ment, Ash, it may be bent and continued parallel
to the beam bottom, or separate horizontal re­ 2. The hanger reinforcement, A^, should be
inforcement, A ^ ^ A sh must be provided. The placed as close as practical to the re-entrant
extension of A^h or Asb reinforcement at beam corner. This reinforcement requirement is not
bottom must be at least €d beyond crack 5. The additive to other shear reinforcement require­
A ^ reinforcement may be anchored on the ments.

PCI Design Handbook/Fifth Edition 4 -6 1


_ _2Vu_ + Nu
3. tfthe flexural stress in the full depth section im­ 34>fyp.e (j)fy
mediately beyond the dap, usings factored
toads and gross-section properties, exceeds ^ 2(100) . 15
tongitudinal reinforcement should be 3(0.85)(60)(3.4) 0.85(60)
placed inthe beam to develop the required flex­
ural strength. = 0.38 + 0.29 = G.6? in2 < 1.10
4. The Ref. 16 study-found that, due to formation Therefore Ag = 1.10 in2
of the critical diagonal tension crack (crack 5 in
Use 4 -#5, Ag = 1.24 in2
Figure 4.6.3), it was not possible to develop a
full depth beam shear strength greater than the By Eq. 4.6.6:
diagonal tension cracking shear in the vicinity
Ah = 0.5(As - An) = 0.5(1.10 - 0.29)
of the dap. It is therefore suggested that, for a
length o f the beam equal to the overall depth, = 0.41 in2
H, of the beam, the nominal shear strength of
concrete, Vc, be taken as the lesser of Vci and Assume: Shear span, a = 6 in.
Vo* calculated at H/2 from the end of the full d = 15 in.
depth web. Check shear strength, Table 4.3.1:
<>Vn = <|j(1000X2bd)
Example 4.6.2 Reinforcement for = 0.85(1000) (1)2(16)(15)/1000
Dapped-End Beam = 204 kips > 100 OK
Given:
Use 2 -# 3 U-bars. A = 0.44 in2
The 16RB28 beam with a dapped end as shown in
Fig 4.6.4 3. Diagonal tension at re-entrant corner:
Vu = 1 0 0 kips (includes all toad factors) By Eq. 4.6.7:
Nu = 15 kips (includes all toad factors) A - vu _ 100 1.96 in2
fc = 5000 psi (normal weight) * tpfy 0.85(60)

fy = 60 ksi (for all reinforcement) Use 5 - # 4 closed ties = 2.00 in2


For Ash (minimum area = Agh)
Problem: Use 5 -# 6 = 2.2 in2 > 1.96 OK
Determine the required reinforcements Ag, Ah, Ash,
and Ay shown in Figure 4.6.3 4. Diagonal tension in the extended end:
Solution: Concrete capacity = 2kJ% bd
1. Flexure in extended end:
= 2(1) 75000 (16)(15)/1000 = 33.9 kips
By Eq. 4.6.3:
By Eq. 4.6.9:

X - 2Xbd
<P

= 1 /100 0.70 in2


2(60) \0.85
= 1.10 in2
Try 2 -# 4 stirrups = 0.80 in2
2. Direct shear:
Check Eq. 4.6.8:
_ 1000M>h|i 1000(1) (16) (16)(1.4) (1)
Vu 100,000
(|)Vn = 4>(Avfy + Ahfy + 2Xj% bd)

= 3.58 > 3.4 Use 3.4


By Eqs. 4.6.4 and 4.6.5: = 0.85[0.80(60) + 0.44(60) + 33.9]

4 -6 2 PCI Design Mandbook/Fifth Edition


= 92.1 kips < 100 4.7 L o s s of Prestress

Change Ah to 2 - # 4 Loss o f prestress is the reduction of tensile stress


in prestressing tendons due to shortening of the con­
<|>Vn = 110.4 kips > 100 OK crete around the tendons, relaxation of stress within
the tendons and external factors which reduce the to­
Check anchorage requirements: tal initial force before it is applied to the concrete. ACI
As bars: 318-95 identifies the sources of loss of prestress
listed in Sect. 4.7.1.
From Design Aid 11.2.8:
Accurate determination of losses is more impor­
fy = 60,000 psi tant in some prestressed concrete members than in
fc = 5000 psi others. Losses have no effect on the ultimate
# 5 bars strength of a flexural member unless the tendons are
unbonded or if the final stress after losses is less than
€d = 21 in.
0.50 fpu. Underestimation or overestimation of losses
Extension past dap=H - d + ^d can affect service conditions such as camber, deflec­
= 2 8 -1 5 + 21 tion and cracking.
=34 in.

Ah bars:
From Design Aid 11.2.8, for # 4 bars: 4.7.1 Sources of Stress L o s s
€d = 17 in. 1. Anchorage Seating Loss and Friction
Anchorage seating loss and friction loss due to in­
bars: tended or unintended curvature in post-tensioning
tendons are two mechanical sources of loss. They
From Design Aid 11.2.8, for #6 bars:
represent the difference between the tension applied
€d = 25 in. to the tendon by the jacking unit and the initial tension
bar length = H - D + £d available for application to the concrete by the ten­
= 28 - 2 6 + 25 don. Their magnitude can be determined with rea­
sonable accuracy and, in many cases, they are fully
= 27 in.
or partially compensated for by overjacking.

PC! Design Handbook/Rfth- Edition 4 -6 3


2. Elastic Shortening of Concrete RE = relaxation of tendons
Thejconciete around the tendons shortens as the
~prestressing force is applied to it. Those tendons ES = t^esEpsfcir/Eci (Eg. 4.7.2)
which are already -bonded to the concrete shorten
with it. where:

3. Shrinkage o f Concrete KeS = 1.0 for pretensioned members


Loss of stress in the tendon due to shrinkage of Eps = modulus of elasticity of prestressing
the concrete surrounding it is proportional to that part tendons (about 28.5 x 106psi)
of the shrinkage that takes place after the transfer of
ECi = modulus of elasticity of concrete at time
prestress force to the concrete.
prestress is applied

4. Creep of Concrete and Relaxation of Tendons f cir = net compressive stress in concrete at
Creep of concrete and relaxation of tendons com­ center of gravity of prestressing force
plicate stress loss calculations. The rate of Joss due to immediately after the prestress has
each of these factors changes when the stress level been applied to the concrete.
changes and the stress level is changing constantly
throughout the life of the structure. Therefore, the Pi e2 Mge
(Eq. 4.7.3)
rates of loss due to creep and relaxation are constant­ '9
ly changing.

where:
4.7.2 Range of Values for Total Loss
Total loss of prestress in typical members will Kdr = 0.9 for pretensioned members
range from about 25,000 to 50,000 psi for normal Pi = initial prestress force (after anchorage
weight concrete members, and from about 30,000 to seating loss)
55,000 psi for sand-lightweight members. e = eccentricity of center of gravity of ten­
The load tables in Chapter 2 have a lower limit on dons with respect to center of gravity of
loss of 30,000 psi. concrete at the cross section consid­
ered
Ag = area of gross concrete section at the
4.7.3 Estimating Prestress Loss cross section considered

This section is based on the report of a task group lg = moment of inertia of gross concrete
sponsored by ACI-ASCE Committee 423, Pre­ section at the cross section considered
stressed Concrete [17]. That report gives simple Mg = bending moment due to dead weight of
equations for estimating losses of prestress which prestressed member and any other
would enable the designer to estimate the various permanent loads in place at time of
types of prestress loss rather than using a lump sum prestressing
value. It is believed that these equations, intended for CR = Kcr(Es/Ec)(fcir - feds) (Eq. 4.7.4)
practical design applications, provide fairly realistic
values for normal design conditions. For unusual de­
sign situations and special structures, more detailed
analyses may be warranted. where:

T.L = ES + CR + SH + RE (Eq. 4.7.1) Kor = 2.0 normal weight concrete


= 1.6 sand-lightweight concrete
where:
feds = stress in concrete at center of gravity of
T.L. = total loss (psi), and other terms are prestressing force due to all superim­
losses due to: posed permanent deadloads that are
ES = elastic shortening applied to the member after it has been
prestressed (see Eq. 4.7.5)
CR = creep of concrete
SH = shrinkage of concrete

4 -6 4 PCI Design Handbook/Fifth Edition


Table 4.7.1 -Values o f Kre and J For stress-relieved strand:

Type o ften d o n Kre J 0:7-5 ^ > 0.70 :


*pu-
27Q G rad e stress-
relieved strand o r 2 o,eoo - 0.15
(Eq.4.7.8)
wire-

250 Grade stress-


relieved strand or 18,500 13.14
wire

_ f p i/ f p u / ^ p i/^Ipu
l
240 o r 235 Grade
c = - 0.55 (Eq. 4.7.9)
17,600 0,13 0.19T47 \ 0.85
stress-relieved w ire

Wfpu < 0.51 :


270 Grade low-
5,000 0.040
relaxation strand
c = H (Eq. 4.7.10)
250 Grade low-
4,630 0.037 For low-relaxation strand:
relaxation wire

240 or 235 Grade


fpi/fpu ^ 0.54:
4,400 0.035
low-relaxation wire

145 or 160 Grade


6,000 0.05
stress-relieved bar

W Vu < 0.54:

Ec = modulus of elasticity of concrete at C = ^ (Eq. 4.7.12)


28 days
U = Msd(e)/Ig (Eq. 4.7.5) where:
V' = Ei/Aps
where:
fpu = ultimate strength of prestressing steel
Msd = moment due to all superimposed per­
manent dead and sustained loads
Values of C are also shown in Table 4.7.2.
applied after prestressing

SH = (8 .2 x 1 0 -6)KihEs (1-0.06V/S)(100-R.H.)
(Eq. 4.7.6) 4.7.4 Critical Locations

where: Computations for stress losses due to elastic


shortening and creep of concrete are based on the
Ksh = 1.0 for pretensioned members compressive stress in the concrete at the center of
V/S = volume to surface ratio gravity (cgs) of the prestressing force.
For bonded tendons, stress losses are computed
R.H. = average ambient relative humidity (see
at that point on the span where flexural tensile
Figure 3.12.2)
stresses are most critical. In members with straight,
RE = [Kre - J(SH + CR + ES)]C (Eq. 4.7.7) parabolic or approximately parabolic tendons this is
usually mid-span. In members with tendons de­
flected at mid-span only, the critical point is generally
where: near the 0.4 point of the span. Since the tendons are
bonded, only the stresses at the critical point need to
Values for Kre and J are taken from Table 4.7.1. be considered. Stresses or stress changes at other
For values of coefficient, see Table 4.7.2. or calcu­ points along the member do not affect the stresses or
late using Eqs. 4.7.8. through 4.7.12. stress losses at the critical point.

PCI Design Handbook/Fifth Edition 4 -6 5


Table 4.7.2 Values of 0 wt = 491 plf

^ Stress-reiieved wt of topping = 250 plf


Stress-relieved bar or low-
fpj/fpu relaxation
Concrete:
stran d or wire
s tra n d o r wire Precast: SancNightweight
0.80 12a fc = 5000 psi Ec = 3.0 x 106 psi
om 1.22 fii = 3500 psi Eci= 2.5x10® psi
0.78 1-16 Topping: Normal weight
0.77 1.11
1.05 Prestressing steel:
0.76
0.75 1.45 1.00 12-Vi in. diameter 270K tow-relaxation strands
0.74 1.36 0.95 Aps= 12(0.153} = 1.836 in2
0.73 1.27 0.90 Es = 28.5 x 106 psi
0.72 1.18 0.85
Depressed at mid-span
0.71 1.09 0.80
0.70 1.00 0.75 ee = 12.81 in.

0.69 0.94 0.70 ec = 18.73 in.


0.68 0.89 0.66 Problem:
0.67 0.83 0.61 Determine total toss of prestress.
0.66 0.78 0.57
Solution:
0.65 0.73 0.53
For depressed strand, critical section is at OM.
0.64 0.68 0.49 Determine moments, eccentricity, and prestress
0.63 0.63 0.45 force.
0.62 0.58 0.41 M at 0.4^ = ^ ( € - x)
0.61 0.53 0.37
0.60 0.49 0.33 w(0.4f)
(€ - 0.4f)
2

= 0.12w£2
Exam ple 4.7.1 Loss of Prestress
Mg = 0.12(0.491)(70)2 = 289 kip-ft
Given:
10LDT 32 + 2 as shown below: Msd= 0.12(0.250)(70)2 = 147 kip-ft
Span = 70 ft
e at O M = 12.81 + 0.8 (18.73 - 12.81)
No superimposed dead load except topping
= 17.55 in.
R.H. = 75%
Assume compensation for anchorage seating toss
during prestressing.
Pi = 0.75 Apsfpu = 0.75(1.836)(270)
= 371.8 kips

Determine fcir and fcdE:

f — K I + ^ 'e2
oir - M Ag+ ,g

( 371.8 371.8(17.55)2\
Section properties (untopped}: = 0.9
{ 615 + 59,720 j
A = 615 in2
I = 59,720 in4 289(12}(17.55)
Sb = 2717 in3 59,720

V/S = 615/364 = 1.69 in. = 1.252 ksi = 1252 psi

4 -6 6 PCI Design Handbook/Fifth Edition


fcds_- f^sd(e )/lg time of transfer of prestress, caused by the eccentrici­
ty of the prestressing force. This camber may in­
147(1-27(17755)
crease o r decrease with time+ depending on the
" 59,720'
stress distribution across the member under sus­
= & 518 ksi = 516 psi tained loads. Camber tolerances are suggested in
Chapter 8 of this Handbook.
ES = KeSEsfcir/Eci limitations on instantaneous deflections and time-
dependent cambers-and deflections are specified in
= (1)(28.5x10 6)(l252)/(2.5x106) the ACI Coda Table 9.5(B) of the Code is reprinted
for reference (see Table 4.8.1).
= 14,272 psi The following sections contain suggested meth­
ods for computing cambers and deflections. There
CR = Kcr(Es/Ec)(fCjr — fCCjS)
are many inherent variables that affect camber and
deflection, such as concrete mix, storage method,
CR = (1.6)(28.5x 106/3 .0 x 106) (1252-518)
time of release of prestress, time of erection and
= 11,157 psi placement of superimposed loads, relative humidity,
etc. Because o f this, calculated long-term values
SH = (8.2 x l 0 -e)Ksf,Es(1 - 0.06V/S) (100-R.H.)
should never be considered any better than esti­
= (8.2 x10-e) (1) (28.5 x106) mates. Non-structural components attached to mem­
bers which could be affected by camber variations,
x[1 -0.06(1.69)1(100 - 75) such as partitions or folding doors, should be placed
with adequate allowance for variation. Calculation of
= 5249 psi topping quantities should also recognize the impreci­
sion of camber calculations.
RE = [K re- J(SH + CR + ES)]C It should also be recognized that camber of pre­
cast, prestressed members is a result of the place­
From Table 4.7.1: ment of the strands needed to resist the design mo­
Kre = 5000 ments and service load stresses. It is not practical to
alter the forms of the members to produce a desired
J = 0.04
camber. Therefore, cambers should not be specified,
fpi/fpu = 0 .7 5 but their inherent existence should be recognized.

From Table 4.7.2: 4.8.1 Initial Cam ber


C = 1.0
Initial camber can be calculated using convention­
al moment-area equations. Figure 4.12.10 has equa­
RE = {5000-0.04(5249+11,157+14,272)] (1) tions for the camber caused by prestress force for the
most common strand patterns used in precast, pre­
= 3773 psi
stressed members. Design Aids 11.1.3 and 11.1.4
provide deflection equations for typical loading con­
T.L. = ES + CR + SH + RE ditions and more general camber equations.
= 14,272 + 11,157 + 5249 + 3773
= 34,451 psi = 34.5 ksi Exam ple 4.8.1 Calculation of Initial Cam ber
Given:
Final prestress force = 371.8 - 34.5(1.836) 8DT24 for Example 4.2.9.
= 309 kips
Section Properties:*
A = 401 in2 Sb = 1224 in3
4.8 C am ber and Deflection I = 20,985 in4 St = 3063 in3
Most precast, prestressed concrete flexural mem­ yb = 17.15 in. wt = 418 plf
bers will have a net positive (upward) camber at the
yt = 6.85 in. = 52 psf

PCI Design Handbook/Fifth Edition 4 -6 7


Deduct deflection caused byw erght ofrnember:
-a"-o'
Z‘-0 " •4-'—0 * 2 '-e " ( 5w €4
384Eci
2"
r 5 (^ }[( 70)412))4
‘ -------------------------------- ------- N.A. ft
24 = 384(3587)(20,985) = 3 0&in’ *
17.15*[
* .J
-- 3 %"
Net camber at release = 4 .3 5 |- 3.00 J
= 1.35 in. t

Concrete:
fc = 5000 psi
4.8.2 Elastic Deflections

Normal weight (150 pcf) Calculation of instantaneous deflections of both


prestressed and non-prestressed members caused
Ec = 33w 15/fi~ = 33(150)15 V5000 = 4287 ksi
by superimposed service loads follows classical
fd = 3500 psi methods of mechanics. Design equations for various
load conditions are given in Chapter 11 of this Hand­
Ed = 33 (150)15/3500 = 3587 ksi
book. If the bottom tension in a simple span member
does not exceed the modulus of rupture, the deflec­
(Note: The values of Ec and Eci could also be read
tion is calculated using the uncracked moment of in­
from Design Aid 11.2.2.)
ertia of the section. The modulus of rupture of con­
crete is defined in Chapter 9 of the Code as:

fr = 7.5lJ% (Eq. 4.8.1)

See Sect. 4.3.3 for definition of h

4.8.3 Bilinear Behavior


Problem:
Find the initial camber at time of transfer of pre­ Sect. 18.4.2 of the Code requires that “bilinear mo­
stress. ment-deflection relationships” be used to calculate
instantaneous deflections of prestressed concrete
Solution:
members when the bottom tension exceeds
The prestress force at transfer and strand eccen­
This means that the deflection before the member
tricities are calculated in Example 4.2.9 and are
has cracked is calculated using the gross (un­
shown above.
cracked) moment of inertia, lg, and the additional
Calculate the upward component using equations
deflection after cracking is calculated using the mo­
given in Figure 4.12.10.
ment of inertia of the cracked section. This is illus­
trated graphically in Figure 4.8.1.
A t .. P o e ,* a , P0e 'l 2 In lieu of a more exact analysis, the empirical rela­
1 8Ed l 12EJ tionship:

335(5.48) [(70) (12)]2


8(3587) (20,985) ler = nApSdj; (1 - 1.6 /n p ^) (Eq. 4.8.2)

335(8.42)[(70)(12)]2
12(3587)(20,985) may be used to determine the cracked moment of in­
ertia. Figure 4.12.11 gives coefficients for use in solv­
= 2.15 + 2 .2 0 = 4.35 in.f ing this equation.

4 -6 8 PCI Design Handbook/Fifth Edition


Exam ple 4.8.2 Deflectiorr Calculation Using A ps _ 1,836
^Bilinear M oment-Deflection Pp — bdp 0.00092
(96) (20.75)
Refatfen$hip-
G — 0.0056
Given: ta = Cbdp = 0,0056(96) (20.75)3
8DT24 from Examples 4.2.9 and 4.8.1. 4803 in4

P ro b le m : Determine th e portion o f the live load that would


Determine the total deflection caused by the spe­ result in a bottom tension o f 530 psi,
cified uniform live load. 7 5 6 -5 3 0 = 226 psi

S olu tio n: The tension caused by live load alone is 1614 psi,
Determine fr = 7.5a, / fT = 530 psi therefore, the portion of the live load that would result
in a bottom tension of 530 psi is:
From Example 4.2.9 the final tensile stress is 756
psi, which is more than 530 psi, so the bilinear behav­
ior must be considered. ~ 6~T 6 f4 ~2 " (°,28°) = 0-241 kips/ft
Determine lcr from Figure 4.12.11: and:

Aps = 1.836 in2 (See Example 4.2.9) ■ 5 w l4 f l ] ”


dp at mid-span = ec + yt = 13.90 + 6.85 s 384Eclg 384(4287) (20,985)

= 20.75 in.

(Note: It is within the precision of the calculation 5( ^ % 0(12)]4


method and observed behavior to use mid-span dp Aor= 384(4287) (4803) = 1-02 'n'
and to calculate the deflection at mid-span, although
the maximum tensile stress in this case is assumed at
0.4*.) Total deflection = 1.45 + 1.02 = 2.47 in.

Table 4.8.1 M aximum perm issible com puted deflections


Type of member Deflection to be considered Deflection limitation

Flat roofs not supporting or Immediate deflection due to live load


attached to nonstructural ele-
ments likely to be damaged by 180
large deflections

Floors not supporting or attached Immediate deflection due to live load


to nonstructural elements likely to J_
be damaged by large deflections 360

Roof or floor construction sup­ That part of the total deflection occur­
porting or attached to nonstructur­ ring after attachment of nonstructural
al elements likely to be damaged elements (sum of The long-term 480
by large deflections deflection due to all sustained loads
and the immediate deflection due to
any additional live load)'1
Roof or floor construction sup­
porting or attached to nonstructur-
al elements not likely to be dam­ 240
aged by large deflections
a. Limit not intended to safeguard against ponding. Ponding should be checked by.suitable calculations of deflections, including add­
ed deflections due to ponded water, and considering long-term effects of all sustained loads, camber, construction tolerances, and
reliability of provisions for drainage.
b. Limit may be exceeded if adequate measures are taken to prevent damage to supported or attached elements.
c. Long-term deflection shall be determined in accordance with Sects. 9.5.2.5 or 9.5.4.2, ACI 318-95, but may be reduced by amount
of deflection calculated to occur before attachment of nonstructural elements. This amount shall be determined on the basis of
accepted engineering data relating to time-deflection characteristics of members similar to those being considered.
d. But not greater than tolerance provided for nonstructural elements. Limit may be exceeded if camber is provided so that total
deflection minus camber does not exceed limit.

PCI Design Handbook/Fifth Edition 4 -6 9


Figure 4.8.1 BHmear moment-deflection where'.
ftt = the-final calculated total stress in the
member
f e = calculated stress d u e to live load

Exam ple 4.8.3 Deflection Calculation Using


Effective Moment o f Inertia
Given:
Same section and loading conditions of Examples
4.2.9, 4.8.1 and 4.8.2.

Problemr
Determine the deflection caused by live load using
the le method.

Solution:
From the table of stresses in Example 4.2.9:
ft« = 756 psi (tension)
U = 1614 psi (tension)
fr = 7.5 = 530 psi (tension)

Ma , _ (756^_530\
0.860
Ma l 1614 )

(0.860)3 = 0.636
3

|= 1 - 0.636 = 0.364

4.8.4 Effective Moment of Inertia


The Code allows an alternative to the method of
calculation described in the previous section. An ef­
fective moment of inertia, le, can be determined and
the deflection then calculated by substituting t for lg
in the deflection calculation.
The equation for effective moment of inertia is:

Me,
fe = ler (Eq. 4.8.3)
Ma

The difference between the bilinear method and


the le method is illustrated in Figure 4.8.2.
The use of 1ewith prestressed concrete members
is described in Ref. 18. The value of Mcr/Ma for use in
determining live load deflections can be expressed
as:

MCf_ 1 fftf- f r (Eq. 4.8.4)


Ma l f,

4 -7 0 PCI Design Handbook/Fifth Edition


|e - 0.636(20,985) + 0.364(4803) "multipliers,” the upward and downward compo-
= 15,095 in4 rrents_ofthe initial calculated camber should be sepa­
rated in order to takeintOLaccountthe effects o f loss erf
prestress, which only affects the upward components
JB C . Table 4,8.2 provides'suggested multipliers which
Af 384Ecle 384(428?H15,095) can be used as a guide in estimating longterm cam-
bers and deflections for typical m e m b e r i.e., those
members which are within the span-depth ratios rec­
ommended in this Handbook (see Sect. 3.2.2). Der­
4.8.5 Long-Term Camber/Deflection ivation of these multipliers is contained in Ref 19.
For members which are made continuous for su­
ACI318-95 provides a multiplier, X, applied to ini­
perimposed dead load and live load, the final multipli­
tial deflection for estimating the long-term deflection
ers, (3) through (6) Table 4.8.2, may be reduced.
of non-prestressed reinforced concrete members
Long-term effects can be substantially reduced by
(Code S ect 9.5.2.5):
adding non-prestressed reinforcement in pre­
stressed concrete members. The reduction effects
(Eq. 4.8.5) proposed in Ref. 20 can be applied to the approxi­
1 1 + 50p' mate multipliers of Table 4.8.2 as follows:

where £, is a factor related to length of time, and p' is C1 + As/A ps


(Eq. 4.8.6)
the ratio of compressive reinforcement. (There is no 1 + As/ApS
corresponding ratio for prestressed concrete in ACI
where:
318-95).
The determination of long-term cambers and C-i = multiplier from Table 4.8.2
deflections in precast, prestressed members is C2 = revised multiplier
somewhat more complex because of (1) the effect of
As = area of non-prestressed reinforcement
prestress and the loss of prestress over time, (2) the
A ^ = area of prestressed steel
strength gain of concrete after release of prestress,
and because (3) the camber or deflection is important
not only at the “initial” and “final” stages, but also at Exam ple 4.8.4 Use of Multipliers for
erection, which occurs at some intermediate stage, Determ ining Long-Term
usually from 30 to 60 days after casting. C am bers and Deflections
It has been customary in the design of precast,
prestressed concrete to estimate the camber of a Given:
member after a period of time by multiplying the initial 8DT24 for Examples 4.2.9, 4.8.1,4.8.2 and 4.8.3.
calculated camber by some factor, usually based on Non-structural elements are attached, but not likely to
the experience of the designer. To properly use these be damaged by deflections (light fixtures, etc.).

Exam ple 4.8.4


(1) Release Multiplier (2) Erection Multiplier (3) Final

Prestress 4.351 1.80 x(1) 7.83 f 2.45 x (1) 10.66 f

w„ 3.00 f 1.85 x (1) 5.55 i 2.7 x(1) 8.101

1.35 f 2.28 f 2.56 f

w«j 0.481 3.0 x (2) 1.441

1.80 f 1.12 f

wf 2.341

1.22 1

PCI Design Handbook/Fifth Edition 4 -7 1


Problem: 4.9 Com pressiom M em bers
Estimate the camber and deflection- and deter­
Precast and prestressed concrete columns and
mine if it meets therequirements of Table 9.5-© ro f
toad bearing wall panels.are usually proportioned on
the Code (see Table AS. 1). the basis o f strength design. Stresses undef service
conditions; particularly during handling and erection
Solution: (especially of wall panels) must also be considered
Calculate the instantaneous deflections caused The procedures in this section are based on Chapter
by the superimposed dead and live loads. 10 of the Code and on the recommendations of the
PCI Committee on Prestressed Concrete Columns
(referred to in this section as “the Recommended
Practice”) [21],
d 384ECI 384(4287) (20,985)

4.9.1 Strength Design of Precast Concrete


= 0.48 in. J Com pression M embers
Ae = 2.34 in. J. (Example 4.8.3) The capacity o f a reinforced concrete compres­
sion member with eccentric loads is most easily de­
For convenience, a tabular format is used. termined by constructing a capacity interaction
The estimated critical cambers would then be: curve. Points on this curve are calculated using the
At erection of the member: compatibility of strains and solving the equations of
after wsd is applied = 1.80 in. equilibrium as prescribed in Chapter 10 of the Code.
Solution of these equations is illustrated in f igure
“Final” long-term camber = 1.12 in.
4.9.1.
The deflection limitation of Table 4.8.1 for the
above condition is €/240.
A C I318-95 waives the minimum vertical reinforce­
70(12) ment requirements for compression members if the
= 3.50 in. concrete is prestressed to at least an average of 225
240
psi after all Josses. In addition, the Recommended
Total deflection occurring after attachment of non- Practice permits the elimination of column ties, if the
structural elements: nominal capacity is multiplied by 0.85. Interaction
curves for typical prestressed square columns and
Af = (1.80-1.12) + 2.34 wall panels are provided in Chapter 2.
= 3.02 in. < 3.50 OK

Table 4.8.2 Suggested sim ple span multipliers to be used as a guide in estimating long-term cambers
and deflections for typical prestressed m em bers
Without With
Composite Composite
Topping Topping

At erection:
(1) Deflection (downward) component—apply to the elastic 1.85 1.85
deflection due to the member weight at release of prestress
(2) Camber (upward) component—apply to the elastic 1.80 1.80
camber due to prestress at the time of release of prestress

Final:
(3) Deflection (downward) component—apply to the elastic 2.70 2.40
deflection due to the member weight at release of prestress
(4) Camber (upward) component—apply to the elastic camber 2.45 2.20
due to prestress at the time of release of prestress
(5) Deflection (downward)—apply to elastic deflection due to 3.00 3.00
superimposed dead load only
(6) Deflection (downward)—apply to elastic deflection caused by — 2.30
the composite topping

4 -7 2 PCI Design Handbook/Fifth Edition


F ig u re 4-9-1 Equilibrium equations fo r prestressed and non-prestressed com pression m em bers
fs = (0.0Q3/c)(c - d ’)
fs = (0.003/c)(d - c)
fps ~ ^se/ Eps — (0.003/c)(c — dp.) £ 0.035

fps = fse/Eps + (0.003/cHdp - c) < 0.035

fs = fs Eg - fy- fs ^ «sEs —-fy


fps FROM STRESS-STRAIN DIAGRAM < fpu
fps FROM STRESS-STRAIN DIAGRAM < fpu

Pn = (Acomp — As — Aps )(0.85fc )


+ As ft — Asfs — Apgfps — Apsfps
Mn = Pn® = (Apomp — As - Aps }(Yt “ y ')(0 .8 5 ft)
+ A 4 fi(y t - d ' ) + Asf s ( d - y t)
— Aps fps (yt - d p ) + Apgfps(dp - yt)

0.85ft
Acomp “ A4F a > h

e's = (0.003/c)(c - d')


€S= (0.003/c)(c - d)

fps = fse/Eps - (0.003/c)(c - d£,) < 0.035

fps = fse/Eps + (0.003/c)(dp - c) s 0.035

REMAINING EQUATIONS SAME AS ABOVE.

(B) SPECIAL CASE WITH NEUTRAL AXIS OUTSIDE OF THE SECTION

0.85ft

0.003 IN./IN.
As fy

Pn *= 0.85ft (A - As - Aps - Aps - As)


Aps fps
Pn —(Aps + Aps)(fse —0.003Eps) + (As + As)fy

Apsfps
* MULTIPLY BY 0.85 IF NO TIES ARE USED.

Ajfy

(C) SPECIAL CASE WHEN M„ = 0 Pn = P0

dt = the greater of d and dp


0.003dt
° 0.003 + 0.002 °'6dt

CALCULATE PnAND Mn
PER CASE (A) ABOVE

(D) SPECIAL CASE AT COMPRESSION CONTROLLED LIMIT FOR MEMBERS REINFORCED


WITH PRESTRESSING STRAND AND/OR GRADE 60 REINFORCEMENT

PCI Design Handbook/Fifth .Edition 4 -7 3


Constaiction-of an interaction curve usually fol­ SteprS:
lows these steps:- Calculate the maximum factored axial resistance
Step-?: specified-by the Code as:
Determine P0 for Mn== 0. {See Figure 4.9.1 .C) 0.80cj)P0 for tied columns
Step 2: 0.85 4>P0 for spiral columns
Determine MGfor Pn = 0. This is normally done by For cross sections which are not rectangular, it is
neglecting the reinforcement above the neutral necessary to determine separate curves-for each di­
axis and determining the moment capacity by rection of the applied moment. Further, since most
one of the methods described in Sect. 4.2.1. architectural precast column cross sections are not
rectangular, the “a” distance only defines the depth
Step 3:
of the rectangular concrete stress distribution.
Determine Pnb and Mnb at the balance point. This Instead of using a/2, as for a rectangular cross-sec­
occurs when the net tensile strain in the ex­ tion, it is necessary to calculate the actual centroid of
treme tension steel is equal to fy/Es. If the ex­ the compression area which is indicated as y'.
treme tensile steel is prestressing steel, one As noted in Step 4d, the flexural resistance is re­
may use the same net tensile strain (exclusive
duced for prestressed elements at locations within a
of prestress) as for Grade 60- reinforcement.
distance equal to the strand development length from
Step 4: each end. The flexural resistance of the prestressed
For each additional point on the interaction reinforcement in this zone can be supplemented by
curve, proceed as follows: non-prestressed reinforcement that is anchored to
a. Select a value of “c ” and calculate a = p,c end plates, or otherwise developed.
The interaction curves in Chapter 2 are based on a
b. Determine the value of Ao0mp from the ge­
maximum value of f^ = f^, which is equivalent to a
ometry of the section (see Figure 4.9.1 .a).
development length equal to the assumed transfer
c. Determine the strain in the reinforcement
length. The required area of end reinforcement can
assuming that ec = 0.003 at the compres­
be determined by matching interaction curves, or can
sion face of the column. For prestressed re­
be approximated by the following equation if the bar
inforcement, add the strain due to the ef­
locations approximately match the strand locations:
fective prestress = fSe/Eps-
d. Determine the stress in the reinforcement. A. = ^ (Eq. 4.9.1)
For non-prestressed reinforcement, % =
esEs < fy. For prestressed reinforcement,
the stress is determined from a stress- where:
strain relationship (see Design Aid 11.2.5). As = required area of bars
If the maximum factored moment occurs fse = strand stress after losses
near the end of a prestressed element,
fy = yield strength of bars
where the strand is not fully developed, an
appropriate reduction in the value of fps
should be made as described in Sect. The effects of adding end reinforcement to a 24 x
4.2.3. 24 in. prestressed concrete column, thus improving
moment capacity in the end 2 ft, are shown in Figure
e. Calculate Pn and Mn by statics.
4.9.2.
f. Calculate <j>Pn and <t>Mn. Appendix B of the
Code describes that for compression-con- Example 4.9.1 Construction of Interaction
trolled sections (without spiral reinforce­ Curve for a Precast,
ment) with net tensile strain e, in the ex­ Reinforced Concrete Column
treme tension steel less than or equal to
that at the balance point, $ = 0.7. For Given:
Grade 60 reinforcement and for pre­ Column cross-section shown
stressed steel, this occurs whene, Concrete:
< 0.002. For tension-controlled sections
fc = 5000 psi
inwhich e, > 0.005, <|> = 0.9. Forsections
in which e, is between these limits, Reinforcement:
c|) = 0.56 + 68e,. For each point plotted
on the nominal strength curve, multiply Grade 60
Pn and Mn by <j> to obtain the design fy = 60,000 psi
strength curve. Es = 29,000 ksi

4 “ 74 PCI Design Handbook/Fifth Edition


Figure 4.9.2 End reinforcement in a preeast, prestressed concrete-column

24 X 24 in. COLUMN

Figure 4.9.3 Interaction curve for Example Problem:


4.9.1 Construct interaction curve for bending about x-x
axis.

Solution:
Determine following parameters:
P, = 0.85 - 0.05 = 0.80
d = 2 0 - 2 .5 = 17.5 in.
d ' = 2 .5 in.
yt = 10 in.
0.85 ft = 0.85(5)=4.25 ksi
Ag = 12(20)=240 in2
As = A; =2.00 in2
Step 1. Determine P0 from Figure 4.9.1(c):
P0 = 0.85ft (Ag - A; - As) + (Ai + As)fy
<t>P0 = 0.70(4.25(240 - 4) + (4)(60)]
= 870 kips

Step 2. Determine Pnb and Mnb from Figure 4.9.1(d):


4 ----------------- ► _ 0.003d _ 0.003(17.5)
1 0.003 + ft /E , 0.003 + 60/29,000
2.5"
= 10.36 in.
t
v y = 29,000 f ^ | ( 10.3 6 - 2 . 5 )

= 66.0 > 60

4 —# 9 BARS ------- e ______ 9 therefore:


ft = ft = 60 ksi

PCI Design Handbook/Fifth Edition 4 -7 5


Acomp = ab = P-,ctr= 0.80(10.36)(12) <\>Fn = 0.83(293.5) = 244 kips
= 99.5 in2
4>Mn = 0.83((72 - 2)(10 - 3)4.25
y' = a/2 = 0.090(10.36J/2 = 4 rt4 in. + 2.0(6O)(17.5 -1 0 )+ 2.0(58)(10 - 2.5)]
Pnb = (99.5 - 2)4.25 + 2(60) - 2(60) = 0.83(2082.5 + 900 + 870)
= 414.4 fdps = 3198 kip-in. = 267 kip-ft
4>Pnb = 0.70(414.4) = 290 kips
Mnb = 97.5(10-4.14)(4.25)+ (Note: Steps 4a to 4f can be repeated for as many
2.0(60X17.5 - 10)+ 2.0(60)(10 - 2.5) points as desired.)
<(>Mnb = 0.70(2428 + 900 + 900)
A plot of these points is shown as Figure 4,9.3.
= 2960 kip-in. = 247 kip-ft
Step 5.
Step 3. Calculate:
Determine M0; use conservative solution neglect­ Maximum design load = 0.80<|>Po
ing compressive reinforcement:
= 0.80(870) = 696 kips
Asf, 2.0(60)
a = 2.35 in.
0.85fc b 4.25(12)
Example 4.9.2 Calculation of Interaction
Asfy(d - | ) = (2.0)(60)(17.5 - 2.35/2) Points for a Prestressed
M0
Concrete Compression
Member
= 1959 kip-in.
Given:
c = a /p ! = 2.35/0.8 = 2.94
Hollow-core wall panel shown
s, = 0.003(d - c)/c = 0.0149 4 '- 0 "
4-----------------------------------------------------------
et > 0.005; <j) = 0.9 12" > 4 " ^ 12" ( 4 " < 12" t 2" ^
For <j)= 0.9, $M 0 = 1763 kip-in. = 147 kip-ft
tf)!| CO
To determine intermediate points on the curve: | . l __________________________________/ .
J
Step 4(a).
S eta = 6 in., c = 6/0.80 = 7.5 in. Concrete:

Step 4(b). fc = 6000 psi


A ^ p = 6(12) = 72 in2 A = 204 in2

Step 4(d).
Prestressing steel:
Use Figure 4.9.1(A):
fpu = 270 ksi
f; = 29,000 ^ ^ ( 7 . 5 - 2.5)] Eps = 28,500 ksi
fse = 150 ksi
= 58.0 ksi < fv 5-% in. diameter 270K strands

fs = 29,000 ^ ^ ( 1 7 . 5 - 7 . 5 ) Aps (bott) = 3(0.085) = 0.255 in2


ApS(top) = 2(0.085) = 0.170 in2
= 116 ksi > fv

Use fs = fy = 60 ksi Problem:


Calculate a point on the design interaction curve
Steps 4(e) and 4(f) for a = 2 in.
Pn = (72 - 2)4.25 + 2.0(58) - 2.0(60)
= 293.5 kips Solution:
Step 1:
et = 0.003(17.75 - 7.5)/7.5 = 0.004 = 0.85 - 2(.05) = 0.75

<j) = 0.56 + 68et = 0.83 a = 2 in,c = ^ = 2.67 in

4 -7 6 PCI Design Handbook/Fifth Edition


Step 2: (|)Pn = 0.85(0.70)1397.8 - 19.2 - 0.255(150)]
> W = 48(1.5) + 12(2 -1 .5 ) = 202.5 kips-
= 78 in2
48(15) (1.5/2) + 12 (0.5) (1.5-+ JQ5/2) <j)Mn = 0.85(0.70)[1261.0 -4 8 .0
y' -------------------------7§-------------------------
= 0.83 in. + 0.255(150)(6.5 - 4)J
= 778.6 kip-in. = 64.9 kip-ft
Step 13ir
Note: For compliance with ACI Code Sect. 18.8.3,
£se = ^ = 2 8 ^ 0 = 000526 in,/ in-
cracking moment, Ma , must be calculated to verify
4>Mn > 12 M cr for both faces of the wall panel, except
Sfep 4:
for flexural members with shear and flexural strength
From Figure 4.9.1 (A)
at least twice that required by ACI 318-95 Sect. 9.2.
The effects of prestressing and its eccentricity should
e;s = 0.00526 - ^ ( 2 . 6 7 - 1 . 5 ) he included in calculating Mcr and other aspects of
wall panei behavior, such as deflections.

= 0.00526 - 0.00131 = 0.00395 in./in. 4 .9 2 Slenderness Effects

From Design Aid 112.5, this strain is on the linear Sects. 10.10ihrough 10.13of ACI 318-95contain
part of the curve: provisions for evaluating slenderness effects (buck­
ling) of columns. Use ofthese provisions is described
fps £pSEs = 0.00395(28,500) = 113 ksi
in Chapter 3 of this Handbook. Additional recommen­
dations are given in the Recommended Practice [21].
st = % ^ ( 6 . 5 - 2.67) = 0.00430
£ .O f

Eps = 0.00526 + 0.00430 = 0.00956 4.9.3 Service Load Stresses


(j) = 0.56 + 6 8 e, = 0.85 There are no limitations in ACI 318-95 on service
load stresses in compression members subject to
From Design Aid 11.2.5, fps = 252 ksi bending. The Recommended Practice suggests that,
From Figure 4.9.1 (A): for prestressed members, the limitations of Sect. 18.4
(Acomp)0-85fc Aps fps Apgfps of the Code be applied. For non-prestressed mem­
78(0.85)(6) - 0.170(113) - 0.255(252) bers, stresses and crack control are discussed in
Sects. 4.22.1 and 5.2.4. Handling stresses are near­
3 9 7 .8 -1 9 .2 -6 4 .3 = 314.3 kips
ly always more critical than service toad stresses.
t r n 0.85(314.3) = 267 kips
Mn 397.8(4 - 0 .8 3 )-1 9 .2 (4 -1 .5 )
4.9.4 Effective Width of Wall Panels
+ 64.3(6.5 - 4)
The Recommended Practice specifies that the
126 1 .0 -4 8 .0 + 160.8 = 1373.8 kip-in
portion of a wall considered as effective for support
= 114.5 kip-ft ing concentrated loads or for determining the effects
<&Mn = 0.85(1373.8) = 1168 kip-in of slenderness shall be the least of the following:
= 97.3 kip-ft a. The center-to-center distance between toads.
Since no lateral ties are used in this member, the b. The width of the loaded portion plus six times
values should be multiplied by 0.85. the wall thickness on either side (Figure 4.9.4).
c. The width of the rib (in ribbed wall panels) plus
4>pn = 0.85(267) = 227 kips six times the thickness of the wall between ribs
on either side of the rib (Figure 4.9.4).
<j>Mn = 0.85(97.3) = 82.7 kip-ft d. 0.4 times the actual height of the wall.

Note: This is for fully developed strand. If the ca­ 4.9.5 Varying Section Properties of
pacity at a point near the end of the transfer zone is Compression Members
desired, then fps < fse = 150 ksi, (j) = 0.7 because
Architectural wall panels will frequently be o f a
e, 0.002.
configuration that varies over the unsupported height
of the panel. While there are precise methods of de

PCI Design Handbook/Fifth Edition 4 -7 7


Figure 4.9i4 Effective width of wall panels CENTER MULLION

~ E F F E C W t WtDTH-

WIDTH OF LOAD
6t 6t


i.

S O U D OR HOLLOW -CORE WALL PANELS

EFFECTIVE WIDTH

0t 6t 1 2 - 0"

RIBBED WALL PANELS


SECTION A-A [ j !
Ig = 3891 IN4
termining the effects of slenderness for such mem­
bers, the approximate nature of the analysis proce­
64" (72" MAX. POSSIBLE)
dures used do not warrant such precision. Example
4.9.3 illustrates approximate methods for determin­ 1
1 4 'V
ing section properties used in evaluating slenderness
effects. \ / t
SECTION B-B \ /

Example 4.9.3 Approximate Section 'g == o w e iint | ,|2" j


— - 2"
Properties of an Architectural
Mullion Panel EFFECTIVE SECTIO NS
Given:
The load bearing architectural wall panel shown A second, more approximate method would be to
below. use a “weighted average" of the moments of inertia of
the two sections. In this case:
fc = 5000 psi
Ec = 4300 ksi ■ _ lib , + Uhz
^ “ h, + h2
Problem:
Determine an approximate moment of inertia for . 5638(3 + 2) +3891(5)
slenderness analysis. 10

Solution: Once an equivalent moment o f inertia is deter­


One method is to determine a simple span deflec­ mined, slenderness effects are evaluated by one of
tion with a uniform load as follows: the methods described in Sect. 3.5.
Using the moment area method, the center or mid­
height deflection is: 4.9.6 Piles
A0 = 0.013 in. In this section, procedures are shown to deter­
A = . 5wL4 , mine the structural capacity of pretensioned concrete
° 384Elepuiv piles, assuming adequate soil capacity. The soil ca­
pacity must be established by load tests or evaluated
I _ 5wL4 by a geotechnical engineer. Experience has shown
eqaiv A0384E that the frictional and bearing resistance of the soil will
control the design more often than the strength and
_ 5(1 /12}[10(12)]4
service load stresses on the pile. For more informa­
“ 0.013(384)(4300)
tion on prestressed concrete piles, see Ref. 3, Chap­
= 4025 in4 ter 2.

4 -7 8 PCI Design Handbook/Fifth Edition


w = 1 KLF

4.9.6.1 Strength Under Axial Load Unsupported Length


It is suggested that the use of E g 4.9.3 be limited
Nominal Strength
to values of h/r of not greater than 60, where “h” is the
In the following procedure, a capacity based on
unsupported length of the pile and “r” is the radius of
service loads is compared with the nominal strength
gyration.
$ = 1.0). For the nominal strength, the concrete
For piles considered fully fixed at one end and
stress at failure is assumed to be 0.85fc . Also, with
hinged at the other end, “h” may be taken as 0.7
an uttimate concrete strain of 0.003, ft can be shown
times the length between the hinge and the assumed
that about 60% of the effective prestress, fpc remains
point of fixity. For piles fully fixed at both ends, h may
in the member when it reaches its nominal strength.
be taken as 0.5 of the length between points of fixity.
Thus the nominal strength is:

4.9.6.2 Combined Bending and Axial Load


Pn = (0.85fe - 0.60fpc)Ag (Eq. 4.9.2) Service Loads
It is common practice to allow a tension under ser­
vice loads of approximately 50% of the modulus of
A study by the Portland Cement Association, rupture, or about 4 y/ff and to allow compression of
which has been accepted by most building codes, 0.45fc. Thus:
recommends the following limitation for axially
loaded short column prestressed piles, based on ser­
H + f ± M _ tension < 4vfT
vice loads:
Ag ^ S compression < 0.45fc

Strength Design
N = (0.33FC - 0 .2 7 y A g (Eq. 4.9.3) Because prestressed piles have multiple layers of
prestressed reinforcement, the design strength must
For a concentric load on a short column pile, a fac­ be obtained from a strain compatibility analysis, as il­
tor of safety (Pn/N) of between 2.0 and 3.0 is usually lustrated in Example 4.9.5, or from an interaction dia­
adequate. A value for f ^ of 0.2f(. is considered to be gram based on such an analysis. The interaction dia­
about the desirable upper limit, and a value of 700 psi grams for square prestressed columns in Chapter 2
is recommended as the desirable lower limit for ail may be used for square piling with similar strand pat­
piles over about 40 ft in length. For example, for terns.

Example 4.9.4 Bearing Pile

fc = 6000 psi and fpc = 700 p s i: For a 12 in. square solid pile, compute the allow­
able loads and moments.
Pn = [0 .8 5 (6 0 0 0 ) - 0 .6 0 (7 0 0 )]A g = 4 6 8 0 Ag
Given:
N = [0 .3 3 (6 0 0 0 ) - 0 .2 7 (7 0 0 )]A g = 1791 Ag A = 144 in2
I = 1,728 in4
F .S . = 4 6 8 0 /1 7 9 1 = 2 .6 0

PCI Design Handbook/Fifth Edition 4 -7 9


^ = 288 in3 Givens
fP = €000 psi A = 4 3 2 in?
I = 5 1 8 4 in4
Prestress with 4 - xk in. diameter 270K strands
S = 5T84/6 =-864 in3
Aps = 0.612 in2
f P=_6000psi
Initial stress = 0.75fpu; assume total loss = 18% Stress to 75% of fpu; assume 18% loss

P = 270(0.75) (0.82)(0.612) = 101.6 kips Problem:


For the 12 in. x 36 in. sheet pile shown, compute
allowable moment.
fpQ= P/A = 101.6(1000)/144 = 706 psi
Solution:
(a) Direct Load fse = 0.75(0.82)(270) = 166 ksi
H = (0.33fc - 0.27fpc)A
Aps = 20(0.153) = 3.06 in2
N = 1789(A)
166(3.06)
Allowable N = 1789(144)/1000 = 258 kips or fpc ~ 432 1.176 ksi
129 tons.
Moment Capacity:
Nominal strength is given by:
(a) Service loads
Pn = (0.85 fc - 0.60 fpc)A For allowable tension of 4t/fT or 0.30 ksi:

[0.85(6000) - 0.60(706)]144 Allowable Moment:


1000
= {0 A j% + fpc)s = (0.30 + 1.176)864

= 673 kips = 1275 kip-in per pile


= 425 kip-in per ft
Thus, factor of safety = 673/258 = 2.61
(b) Strength design

(b) Moment Capacity Use strain compatibility:

Figure 2.6.1 can be used to determine the mo' Using an iteration procedure, determine the depth
ment capacity: of neutral axis, c, to be 4.33 in. (See Example
4.2.6).
<|>Pn = 0.7(673) = 471 kips
ese = fseEps = 166/28,500 = 0.00582 in./in.
From Figure 2.6.1, with fP = 6000 psi,
Last iteration:
4>Mn = 40 kip-ft
9.00 ~ 4.33
£si = (0.003) + 0.00582
4.33
Example 4.9.5 Sheet Pile
0.00906
36"
0.04
fS1 = 270- = 250.6 ksi
0.00906 - 0.007

Ti = 250.6(0.153) (10) = 383.4 kips


n
4.33 - 3.00
e s2 = ' ( - 0.003) + 0.00582
4.33
L.............
1— 2 0 - 1/2" DIAMETER, 270K
T 0.00490
STRANDS

4 -8 0 PCI Design Handbook/Fifth Edition


0.003 0.85fc If the total deck width, perpendicular to4he span, is
less 4han-the spanT modification may be required.
Contact local producers for recommendations.
Load distribution in stemmed members may not
necessarily follow the same pattern, because of dif­
ferent torsional resistance properties.

Example 4.10.1 Load Distribution

Given:
An untopped hollow-core floor with 4 ft wide 8 in.
deep slabs, and supporting a load bearing wall and
concentrated loads as shown in Figure 4.10.2.
T2 = 139.7(0.15S) (10) = 213.7 kips
Problem:
Ti +T2 = 383.4 + 213.7 = 597.1 kips Determine the design loads for the slab support­
ing the wall and concentrated loads.
a = f t c -= 0.75(4.33) = 3.25 in.
Solution:
C = 0.85 fc ba = 0.85(6) (36) (3.25) (Note: Each step corresponds to a line number in
= 596.7 kips (close to T i +T2) OK the table in Figure 4.10.2)
1. Calculate the shears and moments for the non-
Mn = - 596.7(3.25/2) + 213.7(3) + 383.4(9) distributable (uniform) loads:
= 3122 kip-in. wu = 1.4(56 + 10) + 1.7(40) = 160 psf

e, = es1- e se = 0.00906-0.00582 = 0.00324 2. Calculate the shears and moments for the dis­
tributable (concentrated and line) loads:
<|> = 0.56 + 680, = 0.78
wu = 1.4(650) + 1.7(1040) = 2678 Ib/ft
<|>M„ = 0.78(3123) = 2436 kip-in. P1u= 1.4(500) + 1.7(1000) = 2400 lb
= 203 kip-ft P2u= 1.4(1000) + 1.7(3000) = 6500 lb

3. Calculate effective width along the span:


4.10 Special Considerations
At the support, width = 4.0 ft
This section outlines solutions of special situations
At 0.25£ (6.25 ft), width = 0.5€ = 12.5 ft
which may arise in the design of a precast floor or roof
system. Since production methods of products vary, Between x = 0 and x = 6.25 ft
local producers should be consulted. Also, test data width * 4 + (x/6.25)(12.5 - 4) = 4 + 1.36x
may indicate that the conservative guidelines pre­
sented here may be exceeded for a specific applica­ 4. Divide distributable shears and moments from
tion. step 2 by the effective widths from step 3.

5. Add the distributed shears and moments to the


4.10.1 Load Distribution non-distributable shears and moments from
Frequently, floors and roofs are subjected to line step 1.
loads, for example from walls, and concentrated Once the moments and shears are determined,
loads. The ability of hollow-core systems to transfer or the slabs are designed as described in Sects. 4.2,
distribute loads laterally through grouted shear keys 4.3, and 4.6.
has been demonstrated in several published reports This method is suitable for computer solution. For
[22-24], and many unpublished tests. Based on manual calculations, the procedure can be simplified
tests, analysis and experience, the PCI Hollow-Core by investigating only critical sections. For example,
Slab Producers Committee recommends [25] that shear may be determined by dividing all distributable
line and concentrated loads be resisted by an effec­ loads by 4 ft, and flexure at mid-span can be checked
tive section as described in Figure 4.10.1. Exception: by dividing the distributable loads by 0.5L

PCI Design Handbook/Fffth Edition 4 -8 1


Figure 4.1XJ.1 Assum ed load distribution for hollow-core slabs

4.10.2 Openings through Decks stem spacing less the top stem width less 2 in. (see
Figure 4.10.3).
Openings may be provided in precast decks by:
(1) saw cutting after the deck is installed and grouted, Following are reasonable guidelines regarding
(2) forming (blocking out) or sawing in the plant, or (3) design of hollow-core slabs around openings. Some
using short units with steel headers or other connec­ producers may have data to support a different pro­
tions. In hollow-core or solid slabs, structural capac­ cedure:
ity is least affected by orienting the longest dimension
of an opening parallel to a span, or by coring small 1. An opening located near the end of the span
and extending into the span\less than the less­
holes to cut the fewest strands. Openings in
stemmed members must not cut through the stem, er of 0.125 £ or 4 ft may be neglected when de­
and for double tees, should be narrower than the signing for flexure in the micFspan region.

4 -8 2 PCI Design Handbook/Rfth Edition


2. Strand development must be considered on 4.10.4 Continuity
each side of an opening which cuts strand
Precast deck members are-normally used_as part
(See Sect. 4.2.3.)
of a simple span system; However,- when reinforce­
3. Slabs which are adjacent to openings which ment is requirechat supports for structural-integrity
are long (€/4 ormore), or occur near mid-span, ties or diaphragm connections, limited continuity can
maybe considered to have a free edgotor flex­ be achieved. The amountrof teinforcement is usually
ural design. too low to develop significant moment capacity, but
may be considered for reducing service load deflec­
4. Slabs which are adjacent to openings closer to
tions. It is recommended that full simple span positive
the end than 3€/8 m aybe considered to have a moment capacity be provided for strength design in
free edge for shear design.
all deck members due to uncertain moment-curva­
ture conditions at the supports at ultimate loads.
When top steet is required at supports, it may be
4.10.3 Openings through Webs placed in composite topping (if available), or, in slab
In special situations, horizontal openings may be members, in the grout keys or concreted into cores.
required in stems of deck members. These openings Advantage may be taken of limited continuity
will add significantly to the cost of the product and the when using rational design-procedures for fire resist­
constructability of such modifications should be care­ ance (see Sect. 9.3).
fully considered. Refs. 2 7 -2 9 summarize recent re­
search on the subject including the results of full-
scale testing and design recommendations. The
principal recommendations from those references
are:

1. Web openings should be placed outside the


strand development area. See Figure 4.10.3. 4.10.5 Cantilevers

The method by which precast, prestressed mem­


2. Vertical stirrups should be placed on each side bers resist cantilever moments depends on (1) the
of an opening to control cracks in the vicinity of
method of production, (2) the length and loading re­
the openings.
quirements of the cantilever, and (3) the size of the
project (amount of repetition).
3. The openings should be located in the flexural If a cantilever is not long enough to fully develop
region of the member and below the compres­ top strands, a reduced value of fps must be used, as
sion block.
discussed inSect. 4.2.3. As with reinforcing bars, due
to settlement of concrete, top strands often do not
4. The member should be subjected to primarily
bond as well as the ACI development equation indi­
uniformly distributed loads. Significant con­ cates, especially in dry cast systems. It is often neces­
centrated loads may be placed directly above sary, or at least desirable, to debond the top strands
the solid area between openings, or otherwise
in positive moment regions, and the bottom strands
carefully designed for. in the cantilever.
In some cases it is preferable to design cantilevers
5. The minimum distance between the openings as reinforced concrete members, using deformed re­
shall be equal to the height of the opening but inforcing bars to provide the negative moment resist­
not less than 10 in. ance. In machine-made products, the steel can be
placed in grout keys, composite topping, or con­
6. The members should be designed so that ten­ creted into cores.
sile stresses do not exceed the modulus of rup­ Top tension under service loads should be limited
ture. to 6 so that the section remains uncracked, allow­
ing better prediction of service load deflections.
Consultation with local producers is recom­
Refs. 28 and 29 provide design examples and further mended before choosing a method of reinforcement
recommendations. These references should be re­ for cantilevers. Some have developed standard
viewed before designing or specifying horizontal methods that work best with their particular system,
openings in webs. and have proven them with tests or experience.

PCI Design Handbook/Fifth Edition 4 -8 3


Figure 4.10.2 Example 4.10.1

SDL = tO P S F w 1D = 650 PLF P1D = 500 I B P2D = 1000 LB


LL = 40 PSF w 1L = 1040 PLF P1L = 1000 LB P2L = 3000 LB
SLAB WT = 56 PSF

Shears and Moments


DISTANCE FROM SUPPORT 0 h /2 1' 2' 3' 4' 5' 7.5' 10' 12.5'

1. NON-DISTRIBUTABLE Vu 2.0 1.95 1.84 1.68 1.52 1.36 1.20 0.80 0.40 0
LOADS Mu 0 0.66 1.92 3.68 5.28 6.72 8.0 10.50 12.0 12.5

2. DISTRIBUTABLE Vu 34.34 33.45 31.66 28.99 26.31 23.63 20.95 11.86 0 0


LOADS Mu 177.44 195.79 195.79
0 11.29 33.0 63.33 90.97 115.94 138.23
3. EFFECTIVE WIDTH ft 4 4.45 5.36 6.72 8.08 9.44 10.80 12.5 12.5 12.5

Vu 8.58 7.52 5.91 4.31 3.26 2.50 1.94 0.95 0 0


4. DISTRIBUTED SHEARS
& MOMENTS Mu 0 2.54 6.16 9.42 11.26 12.28 12.80 14.20 15.66 15.66

5. DESIGN SHEARS Vu 10.58 9.47 7.75 5.99 4.78 3.86 3.14 1.75 0.40 0
& MOMENTS Mu 0 3.20 8.08 13.10 16.54 19.0 20.80 24.70 27.66 28.16

Vu in kips/ft; Mu in kip-ft/ft

Figure 4.10.3 Openings through webs

r 2 " MINIMUM

DEVELOPMENT LENGTH OF STRAND, MINIMUM (


- 4" MINIMUM )
V , RADIUS J ^

8" MINIMUM
U
T
BEARING
POINT

4 -8 4 PCI Design Handbook/Fifth Edition


411 References 12. Raths, Charles H., “Spandrel Beam Behavior
and D esign^ PCI Journal, V. 29, No. 2, M arch-
1. “Building Code Requirements for Structural
Aprii 1984.
Concrete” ACI 318-95, and “Commentary,”
ACI318R-95, American Concrete institute^ Far­ -13. Klein, G.J., “Design-of Spandrel Beams,” Re­
mington Hills, ML, 1995. search Project No. 5, Precast/Prestressed
Concrete Institute, Chicago, IL, 1986; Summa­
2. Naaman, A.E., “Ultimate Analysis of “ Pre­
ry Paper in PCI Journal, VoL 31, No. 5, Septem­
stressed and Partially Prestressed Sections by
ber-O ctober 1986.
Strain Compatibility,” PCI Journal, V. 22, No. 1,
January—February 1977. 14. “Design and Typical Details of Connections for
Precast and Prestressed Concrete,” Second
3. Gergely, P., and Lutz, L.A., “Maximum Crack
Edition, MNL-123-88, Precast/Prestressed
Width in Reinforced Concrete Flexural Mem­
Concrete Institute, Chicago, IL.1988.
bers,” Causes, Mechanism, and Control of
Cracking in Concrete, SP-20, American Con­ 15. Mattock, A.H. and Chan, T.C., “Design and Be­
crete Institute, Detroit, Mlr 1968. havior of Dapped-End Beams,” PCI Journal, V.
24, No. 6, November-December 1979.
4. Mattock, Alan H., “Anchorage of Stirrups in a
Thin Cast-in-Place Topping,” PCI Journal, V. 16. Mattock, A.H., and Theryo, T.S., “Strength of
32, No. 6, November-December 1987. Precast Prestressed Concrete Members with
Dapped Ends,” Research Project No. 6, Pre­
5. Martin, L , and Korosz, W., “Strength of Pre­
cast/Prestressed Concrete Institute, Chicago,
stressed Concrete Members at Sections
IL, 1986; Summary Paper in PCI Journal, V. 31,
Where Strands Are Not Fully Developed,” PCI
No. 5, September-October 1986.
Journal, V. 40, No. 5, September-October
1995.
17. Zia, Paul, Preston, H.K., Scott, N.L, and Work­
man, E.B., “Estimating Prestress Losses,”
6. Logan, Donald R., “Acceptance Criteria for
Concrete International, V. 1, No. 6, June 1979.
Bond Quality of Strand for Pretensioned Pre­
stressed Concrete Applications.” PCI Journal, 18. Branson, D.E., “The Deformation of Noncom­
V. 42, No. 2, M arch-April 1997.
posite and Composite Prestressed Concrete
Members,” Deflections of Concrete Structures,
7. Marshal, W.T., and Mattock, A.H., “Control of
SP-43, American Concrete Institute, Farming-
Horizontal Cracking in the Ends of Preten­
ton Hills, Ml, 1970.
sioned Prestressed Concrete Girders," PCI
Journal, V. 7, No. 5, October 1962.
19. Martin, L.D., “A Rational Method for Estimating
Camber and Deflection of Precast Prestressed
8. Kelly, John B., and Pike, Kenneth J., “ Design
Members,” PCI Journal, V. 22, No. 1, January-
and Production of Prestrssed L-Shaped
February 1977.
Bleacher Seat Units,” PCI Journal, V. 18, No. 5,
September-October 1973.
20. Shaikh, A.F., and Branson, D.E., “Non-Ten-
sioned Steel in Prestressed Concrete Beams,”
9. Shaikh, A.F., “Proposed Revisions to Shear-
PCI Journal, V. 15, No. 1, February 1970.
Friction Provisions,” PCI Journal, V. 23, No. 2,
M arch-April 1978.
21. PCI Committee on Prestressed Concrete Col­
umns, “Recommended Practice for the Design
10. Mirza, S.A., and Furlong, R.W., “Serviceability
of Prestressed Concrete Columns and Walls,”
Behavior and Failure Mechanisms of Concrete
PCI Journal, V. 33, No. 4, July-A ugust 1988.
Inverted T-Beam Bridge Bentcaps,” Journal o f
the American Concrete Institute, V. 80, No.4,
22. LaGue, David J., “Load Distribution Tests for
July-A ugust 1983.
Precast Prestressed Hollow-Core Slab
Construction,” PCI Journal, V. 16, No. 6, No­
11. Mirza, S.A., and Furlong, R.W., “Strength Crite­
vember-December 1971.
ria for Concrete Inverted T-Girders,” ASCE
Journal o f Structural Engineering, V. 109, No. 8,
August 1983.

PCI Design Handbook/Fifth Edition 4 -8 5


24 Johnson, Ted, andGhadiali, Zohair, “ toad Dis­ 27. Savage, J.M., Tadros, M.K., Arumugasaamy,
tribution Test on Precast Hollow Core Slate. P., and Rsher, L.G., “Behavior and Design of
withOpenings,” PCIJournal^ V. 17,No. 5, Sep- Double Tees with Web Openings,” PCIJoumal,
tember-October 1972. V. 41, No. 1, January-February 1996.

24. Pfeifer, Donald W., and Nelson, Theodore A., 28. Saleh, M.A., “Optimization of Prefabricated
“Tests to-Determine the Lateral Distribution o f Joists7 Ph.D. Dissertation^ University o f Ne-
Vertical Loads in a Long-Span Hollow-Core braska-Lincoln, December 1996.
R oot Assembly," PC/ Journal, V. 28, No. 6, No-
vember-December 1983. 29. Saleh, M.A., Brady, P.A., Enea, A., and Ta­
dros, M.K., “Design and Performance of Pre­
25. “PCI Manual for the Design of Hollow Core stressed Precast Reinforced Concrete Dou­
Slabs,” MNL-126-85, Precast/Prestressed ble-Tee Beams with Web Openings,” U.S.
Concrete Institute, V. 30, No. 6, Chicago, IL, Army Corps of Engineers, USACERL Technical
1985. Report 97, April 1997.
30. Aswad, Alex, and Burnley, George, “Point Load
26. Mattock, A.H., “ Behavior and Design of
Tests on Double Tee Flanges,” PC/ Journal, V.
Dapped-End Members,” Proceedings of the
36, No. 4, July-August 1991.
U S.-Japan Joint Seminar on Precast Con­
crete, 1986.

4 -8 6 PCI Design Handbook/Fifth Edition


£12.1 DESIGN AIDS;
Figure 4r12.1 FlexuraLresistance coefficients to r elements with non-prestressed, partially prestcessed
amfprestressed reinforcement

Procedure: Analysis:
. _ __ Apsfps + AJy — A s fy
1. Determine oo = ---------- r-~7-----------
D esign
2. Find Kufrom table
n 4 . „ Mu/4> - Ai t; (d - d*) .
1. Determine Ku = — - f ;~b~2---------- -'
3. Determine <|>Mn = t))|Kuf; bd2 + A4 % (d - d')]
2. Find w from table
Basis:
3. For prestressed reinforcement, estimate fps
Ku = co(1 - 0.59 oJ)
4. Select Aps, As and A’s from:
Mu in units of lb-in.
Apstps + Asfy — As fy = cobdfc

5. Check assumed value o f fps

o m,x ^ o m,x for non-prestressed elements


" \ ( i , psi
fy ,k S l\^ 3000 4000 5000 6000 7000 8000
40 0.371 0.371 0.349 0.328 0.306 0.284
50 0.344 0.344 0.324 0.304 0.283 0.263
60 0.321 0.321 0.302 0.283 0.264 0.245

Values of Ku
(9 0.000 0.001 0.002 0.003 0.004 0.005 0.006 0.007 0.008 0.009
0.00 0.0000 0.0010 0.0020 0.0030 0.0040 0.0050 0.0060 0.0070 0.0080 0.0090
0.01 0.0099 0.0109 0.0119 0.0129 0.0139 0.0149 0.0158 0.0168 0.0178 0.0188
0.02 0.0198 0.0207 0.0217 0.0227 0.0237 0.0246 0.0256 0.0266 0.0275 0.0285
0.03 0.0295 0.0304 0.0314 0.0324 0.0333 0.0343 0.0352 0.0362 0.0371 0.0381
0.04 0.0391 0.0400 0.0410 0.0419 0.0429 0.0438 0.0448 0.0457 0.0466 0.0476
0.05 0.0485 0.0495 0.0504 0.0513 0.0523 0.0532 0.0541 0.0551 0.0560 0.0569
0.06 0.0579 0.0588 0.0597 0.0607 0.0616 0.0625 0.0634 0.0644 0.0653 0.0662
0.07 0.0671 0.0680 0.0689 0.0699 0.0708 0.0717 0.0726 0.0735 0.0744 0.0753
0.08 0.0762 0.0771 0.0780 0.0789 0.0798 0.0807 0.0816 0.0825 0.0834 0.0843
0.09 0.0852 0.0861 0.0870 0.0879 0.0888 0.0897 0.0906 0.0914 0.0923 0.0932
0.10 0.0941 0.0950 0.0959 0.0967 0.0976 0.0985 0.0994 0.1002 0.1011 0.1020
0.11 0.1029 0.1037 0.1046 0.1055 0.1063 0.1072 0.1081 0.1089 0.1098 0.1106
0.12 0.1115 0.1124 0.1132 0.1141 0.1149 0.1158 0.1166 0.1175 0.1183 0.1192
0.13 0.1200 0.1209 0.1217 0.1226 0.1234 0.1242 0.1251 0.1259 0.1268 0.1276
0.14 0.1284 0.1293 0.1301 0.1309 0.1318 0.1326 0.1334 0.1343 0.1351 0.1359
0.15 6.1367 0.1375 0.1384 0.1392 0.1400 0.1408 0.1416 0.1425 0.1433 0.1441
0.16 0.1449 0.1457 0.1465 0.1473 0.1481 0.1489 0.1497 0.1505 0.1513 0.1521
0.17 0.1529 0.1537 0.1545 0.1553 0.1561 0.1569 0.1577 0.1585 0.1593 0.1601
0.18 0.1609 0.1617 0.1625 0.1632 0.1640 0.1648 0.1656 0.1664 0.1671 0.1679
0.19 0.1687 0.1695 0.1703 0.1710 0.1718 0.1726 0.1733 0.1741 0.1749 0.1756
0.20 0.1764 0.1772 0.1779 0.1787 0.1794 0.1802 0.1810 0.1817 0.1825 0.1832
0.21 0.1840 0.1847 0.1855 0.1862 0.1870 0.1877 0.1885 0.1892 0.1900 0.1907
0.22 0.1914 0.1922 0.1929 0.1937 0.1944 0.1951 0.1959 0.1966 0.1973 0.1981
0.23 0.1988 0.1995 0.2002 0.2010 0.2017 0.2024 0.2031 0.2039 0.2046 0.2053
0.24 0.2060 0.2067 0.2074 0.2082 0.2089 0.2096 0.2103 0.2110 0.2117 0.2124
0.25 0.2131 0.2138 0.2145 0.2152 0.2159 0.2166 0.2173 0.2180 0.2187 0.2194
0.26 0.2201 0.2208 0.2215 0.2222 0.2229 0.2236 0.2243 0.2249 0.2256 0.2263
0.27 0.2270 0.2277 0.2283 0.2290 0.2297 0.2304 0.2311 0.2317 0.2324 0.2331
0.28 0 .2 3 3 7 0 .2 3 4 4 0.2351 0 .2 3 5 7 0 .2 3 6 4 0.2371 0.2377 0.2384 0.2391 0.2397
0.29 0.2404 0.2410 0.2417 0.2423 0.2430 0.2437 0.2443 0.2450 0.2456 0.2463
0.30 0.2469

PCI Design Handbook/Fifth Edition 4 -8 7


Figure^4.T2.2 Coefficients Ki for determining flexural design strength—bonded prestressing steel

Procedure:
A f
1 . D eterm ine oopu = i r - r - i r
OQp Tc

2. Find Ku from table

bdp
3. Determine <t>Mn = Ki (kips-ft)

Basis,
, _ O fp s fc . .
Ku =
— t (® p u ) 1 - (0.59copu)f - p - Table values are based on a strain compatibility
pu analysis, using a stress-strain curve for pre-
stressing strand similar to that in Design Aid
Note: K'ufrom this table is approximately equivalent 11.2.5. Asterisk (*) indicates cdp > 0.36ft and
to (t>Kuft from Figure 4.12.1.
<t>M„ = <t>[fc bdp (0.36ft - 0.08ft2)]. See Figure 4.2.5 for
variation when Appendix B of ACI 318-95 is used.

Values of Ku

fi(p s i) Opu .00 .01 .02 .03 .04 .05 .06 .07 .08 .09

0.0 0 27 53 79 105 131 156 180 205 228


0.1 252 275 298 321 343 364 386 407 427 447
3000
0.2 467 486 505 524 542 560 577 594 610 626
0.3 642 657 *670 *670 *670 *670 *670 *670 *670 *670
0.0 0 36 71 106 140 174 207 240 273 305
0.1 336 367 397 427 457 486 514 542 570 596
4000
0.2 623 649 674 699 723 746 770 792 814 835
0.3 856 876 *894 *894 *894 *894 *894 *894 *894 *894
0.0 0 45 89 132 175 217 259 300 341 381
0.1 420 458 496 534 570 606 642 677 711 744
5000
0.2 777 809 840 871 901 930 958 986 1013 1039
0.3 1064 *1066 *1066 *1066 *1066 *1066 *1066 *1066 *1066 *1066
0.0 o- 54 107- 159 210 261 311 360 409 456
0.1 503 550 595 640 684 727 769 811 851 891
6000
0.2 930 968 1005 1041 1077 1111 1144 1177 1208 *1215
0.3 *1215 *1215 *1215 *1215 *1215 *1215 *1215 *1215 *1215 *1215
0.0 0 63 124 185 245 304 363 420 476 532
0.1 587 641 693 745 796 846 895 944 991 1037
7000
0.2 1081 1125 1168 1210 1250 1289 1327 *1341 *1341 *1341
0.3 *1341 *1341 *1341 *1341 *1341 *1341 *1341 *1341 *1341 *1341
0.0 0 72 142 212 280 348 414 480 544 608
0.1 670 731 791 850 908 965 1021 1075 1128 1180
8000
0.2 1231 1280 1328 1374 1419 *1441 *1441 *1441 *1441 *1441
0.3 *1441 *1441 *1441 *1441 *1441 *1441 *1441 *1441 *1441 *1441

4 -8 8 PCI Design Handbook/Rfth Edition


Figure 4.12.3 Values o f f ps bysiress-strain relationship—bonded strand
fps ksi

bdpft

VALUES OF C
% C
3000 1.00
4000 1.00
5000 1.06
6000 1.13
7000 1.21
8000 1.31

em = 0.003

Co)ipu

Figure 4.12.4 Design stress for underdeveloped strand

OF MEMBER 0 20 40 60 80 100
PARTIALLY 0 40 80 120 160 200
_________________________________________ LENGTH FROM START OF BONDING, in._________________
CURVES BASED ON SECT. 12.9.1, ACI 318-95. NOTE ACI SECT. 12.9.3 FOR STRANDS WHICH ARE DEBONDED NEAR MEMBER ENDS.

PCI Design Handbook/Fifth Edition 4 -8 9


£kjure 4.12.5 Shear design by Eq. 4:3.3—Straight strands

NOTES: / STEEP DRAPE


T. Applicable to simple span, uni­
formly loaded members only.
2. ft = 5000 psi - Error less than
10% for 4000 psi to 6000 psi.

Vc = ( O.Sv'fT + 7 0 ) ^ )b„d (Eq 4.3.3*

SEE ACI 318-95 SECT. 11.4.1

600 b„d

500 bwd

Vc
400 bwd
OR

— 300 bwd

AT SUPPORT
(lbs) 200 b«d

100 b„d

0
0 0.10 0.20 0.30 0.40 0.50
m

600 bwd

500 bwd

Vc

OR 400bwd

V^
<j> 300bwd

AT SU PPO R T
(,bs) 200b ^

100 bwd

0
0 0.10 0.20 0.30 0.4Q 0.50

4 -9 0 PCI Design Handbook/Fifth Edition


Figure 4.12.6 S hear design by Eq.^4.3.3—Shallow drape

NOTES:

1. Applicable to simple -span, uni­


formly loaded members only.

2. fc = 5000 psi - Error less than


10% for 4000 psi to 6000 psi.

Vc = 10 .6 /f^" + 7 0 0 ^ j b wd (Eq 4.3.3)

SEE ACI 318-95 SECT. 11.4.1

0.10 0.20 0.30 0.40 0.50

x /f

Vc

OR

Vg.
<l>
AT SUPPORT

0.10 0.20 0.30 0.40 0.50


x /f

PCI Design Handbook/Fifth Edition 4 -9 1


Figure 4.T2.7 Sbeardesignhy Eg. 4.3.3—Steepdrape

N O TES-
1. Applicable to simple span, uni­
formly loadedmembers onfy.
2. fc = 5000 psi - Error less than
10% tor 4000 psi to 6000 psi.

Vc = (Eq 4.3.3}

SEE ACI 318-95 SECT. 11.4.1

Vu.
«>

AT SUPPORT

0.10 0.20 0.30 0.40 0.50

x/C

Vc

OR

Vil

AT SUPPORT

4 -9 2 PCI Design Handbook/Fifth Edition


fig u re 4.12.8 Iwfiimum shear reinforcement by Eq. 4:3.8

Aps.tpus
Av — I f (Eq 4J3.8)
D*
80 fyd Y UW

SEE A Q 318-95 S E C T rT I .5.5.4

ApS Ay

PCI Design Handbook/Fifth Edition 4 -9 3


Figure 4.12.9 Shear reinforcement

(Vu/4> ~ v c)s (Eq. 4.3.9)


Av =
fyCi
Note: Other configurations
STIRRUP O R WIRE o f shear reinforcement may
REINFORCEMENT be used to simplify
production of precast
members.

Vertical Deformed Gar Stirrups

Maximum values of (Vu/4> - Vc)/d (Ib/in.)


Stirrup Stirrup
fy = 60,000 psl Spacing
Spacing
(in.) No 3 No 4 No 5 No 3 No 4 No 5 (in.)
Ay = 0.22 Av = tT.40 Av = 0.62 Av = 0.22 Av = 0.40 Av = 0.62

2.0 6600 12000 18600 1320 2400 3720 10.0


2.5 5280 9600 14880 1200 2182 3382 11.0
3.0 4400 8000 12400 1100 2000 3100 12.0
3.5 3771 6857 10629 1015 1846 2862 13.0
4.0 3300 6000 9300 943 1714 2657 14.0
4.5 2933 5333 8267 880 1600 2480 15.0
5.0 2640 4800 7440 825 1500 2325 16.0
5.5 2400 4364 6764 776 1412 2188 17.0
6.0 2200 4000 6200 733 1333 2067 18.0
7.0 1886 3429 5314 660 1200 1860 20.0
8.0 1650 3000 4650 600 1091 1691 22.0
9.0 1467 2667 4133 550 1000 1550 24.0

Welded Wire Reinforcement {WWR)


as Shear Reinforcement (fy = 60,000 psi)

Maximum values of - Vc)/d(lb/in.)


Spacing Spacing
of One Row Two Rows of
vertical Vertical wire Vertical wire vertical
wire wire
(in.) W7.5 W5.5 W4 W2.9 W7.5 W5.5 W4 W2.9 (in.)
Av = 0.075 Av = 0.055 Av = 0.040 Av = 0.029 Ay = 0.150 Ay = 0.110 Ay = 0.080 Av = 0.058

2 2250 1650 1200 870 4500 3300 2400 1740 2


3 1500 1100 800 580 3000 2200 1600 1160 3
4 1125 825 600 435 2250 1650 1200 870 4
6 750 550 400 290 1500 1100 800 580 6

4 -9 4 PCI Design Handbook/Fifth Edition


Figttfe 4.12.10 Camber equations for Epical strand profiles

J-Po

C.G . OF STRAND C.G. OF SECTION

STRAIG HT STRANDS

PDe ^
A t= ■
8EI

Poeel2 , P p e '^ Z a 2\
At= El \ 8 6/
8EJ

PCI Design Handbook/Rfth Edition 4 -9 5


Figure 4.12.11 -Moment of inertia of transformed section—prestressed members

Icr = nApsd | (1 - 1-6 yfipp) Es - -28.5 x tC^ psi

= nPp(l - 1.6 y n p ^ x b d £ Ec = 33w1c5/ f T (ACI Sect; 8.5.1)

wc = 145 lb/ft3 normal weight concrete


= C (from table) x bdp
wc = 115 lb/ft3 sand-lightweight concrete
where: f c - r f . n - g
Values of Coefficient, C

fc, psi
D
rn
p
3000 4000 5000 6000 7000 8000
.0005 .0041 .0036 .0032 .0029 .0027 .0026
.0010 .0077 .0068 .0061 .0056 .0052 .0049
.0015 .0111 .0098 .0089 .0082 .0076 .0072
.0020 .0143 .0126 .0115 .0106 .0099 .0093
.0025 .0173 .0153 .0139 .0129 .0120 .0113
0 .0030 .0201 .0179 .0163- .0151 .0141 .0133
<5
o .0035 .0228 .0203 .0185 .0172 .0161 .0152
c .0040 .0254 .0226 .0207 .0192 .0180 .0170
o
o .0045 .0278 .0248 .0227 .0211 .0198 .0188
-C .0050 .0300 .0270 .0247 .0230 .0216 .0205
0 .0055 .0322 .0290 .0266 .0248 .0233 .0221
£ .0060 .0343 .0309 .0284 .0265 .0250 .0237
0 .0065 .0362 .0327 .0302 .0282 .0266 .0253
£
V. .0070 .0381 .0345 .0319 .0298 .0281 .0267
0 .0075 .0398 .0362 .0335 .0314 .0296 .0282
z
.0080 .0415 .0378 .0350 .0329 .0311 , .0296
.0085 .0430 .0393 .0365 .0343 .0325 .0309
.0090 .0445 .0408 .0380 .0357 .0338 .0323
.0095 .0459 .0422 .0393 .0370 .0351 .0335
.0100 .0472 .0435 .0406 .0383 .0364 .0348
.0005 .0056 .0049 .0044 .0040 .0038 .0035
.0010 .0105 .0092 .0083 .0077 .0071 .0067
.0015 .0149 .0132 .0120 .0110 .0103 .0097
.0020 .0190 .0169 .0153 .0142 .0133 .0125
0 .0025 .0228 .0203 .0185 .0172 .0161 .0152
CB
s .0030 .6263 6235 .6315 .0200 .0187 !UT77
c .0035 .0296 .0265 .0243 .0226 .0213 .0201
A
O .0040 .0326 .0294 .0270 .0252 .0237 .0224
■C .0045 .0354 .0320 .0295 .0275 .0260 .0246
O)
*5 .0050 .0381 .0345 .0319 .0298 .0281 .0267
i .0055 .0405 .0368 .0341 .0320 .0302 .0288
£ .0060 .0427 .0390 .0362 .0340 .0322 .0307
O)
□ .0065 .0448 .0411 .0382 .0360 .0341 .0325
■o .0070 .0466 .0430 .0401 .0378 .0359 .0343
(B .0075 .0484 .0447 .0419 .0395 .0376 .0359
w
.0080 .0499 .0464 .0435 .0412 .0392 .0375
.0085 .0513 .0479 .0451 .0428 .0408 .0391
.0090 .0526 .0493 .0465 .0442 .0422 .0405
.0095 .0537 .0506 .0479 .0456 .0436 .0419
.0100 .0547 .0518 .0492 .0469 .0449 .0432

4 -9 6 PC) Design Handbook/Fifth Edition


-CHAPTER 5
PRODUCT HANDLING AND
ERECTION BRACING

5.1 General ................. 5 -2


5.1.1 Notation ............................................................................ .................. 5 - 2
5.1.2 Introduction........................................................... 5 -2

5.2 Product Handling ................... . ............................................. ........................... 5 - 3


5.2.1 Introduction.......................................................................................... 5 - 3
5.2.2 Structural Design C rite ria ................................................................... 5 - 3
5.2.3 Form Suction and Impact Factors .................................................... 5 -4
5.2.4 Stress Lim itations................................................................................ 5 -4
5.2.4.1 Handling Without Cracking .................................................. 5 -4
5.2.4.2 Handling with Controlled Cracking...................................... 5 -5
5.2.5 Safety Factors...................................................................................... 5 - 5
5.2.6 Prestressed Wall P anels........ ......................................................... 5 -6
5.2.7 Handling Considerations ................................................................... 5 -6
5.2.8 Handling D evices................................................................................ 5 - 7
5.2.9 Lateral S tab ility........................................................................... 5 -1 4
5.2.10 Storage................................................................................................ 5 -1 4
5.2.11 Transportation.................................................................................... 5 -1 6
5.2.12 Erection .............................................................................................. 5 -1 7

5.3 Erection Bracing .................................................................................................. 5 -2 3


5.3.1 Introduction........................................................................................ 5 -2 3
5.3.1.1 Handling Equipment ............................................................ 5 -2 4
5.3.1.2 Surveying and L ayo u t.......................................................... 5 -2 4
5.3.2 Loads ................................................................................................. 5 -2 4
5.3.3 Factors of Safety ....... 5 -2 5
5.3.4 Bracing Equipment and Materials.................................................... 5 -2 5
5.3.5 Erection Analysis .............................................................................. 5 -2 7

5.4 References ......................................................................................................... 5 -3 5

PCI Design Handbook/Fifth Edition 5


PRODUCT HANDLING AND ERECTION BRACING

5.1 General P = axial-load

PjPh)Fv = see Figures-5.2.8 and 5.2.9


5.1.1 Notation Ft = reaction (with subscripts)
A = area; average effective area around —
S5, Sj section modulus with respect to bot­
one reinforcing bar tom and top, respectively
As = area of reinforcement = tension on cable
T
a; ~ area of compression reinforcement
t = thickness
a = dimension defined in section used =
W total load
b = dimension defined in section used
w = weight per unit length or area; max­
d = depth- from extreme compression imum crack width
fiber to centroid of tension reinforce­ = wind load on beam
wb
ment
Wc = wind load on column
dc concrete cover to the center of the
reinforcement yt» yc. yt = see Figures 5.2.8 and 5.2.9

e = eccentricity of force about center of Ym ax


= instantaneous maximum displace­
gravity ment

Eci modulus of elasticity of concrete at yt time dependent displacement;


age other than final height of roll axis above center of
gravity of beam
F = multiplication factor (Figure 5.2.7)
_ angle of lift lines in longitudinal direc­
e
fb,ft “ stress in bottom and top fiber, re­
tions (sling angle); angle of roll in
spectively long slender members
f; = specified concrete compressive =
6max maximum permissible tilt angle
strength
k = correction factor related to unit
fd = concrete compressive strength at
weight of concrete; deflection ampli­
the time considered
fication factor
for = splitting tensile strength
F = coefficient of curvature friction for un­
f; = allowable flexural tensile stress com­ bonded tendons
puted using the gross concrete sec­ = reinforcement ratio for non-pre-
P
tion
stressed tension reinforcement
f. = stress in steel =
P' reinforcement ratio for non-pre-
= yield strength of steel stressed compression reinforce­
fy
ment
hi = distance from centroid of tensile rein­
forcement to neutral axis <i> = angle of lift line from vertical in trans­
= verse direction; strength reduction
h2 distance from extreme tension fiber
factor
to neutral axis

I = moment of inertia (with subscripts)


5.1.2 Introduction
€ = span; length of precast unit
This Chapter discusses stripping, yarding, ship­
= embedment length ping and erection of precast products which are of
= importance to the design engineer, the product engi­
M bending moment
neer, and the engineer responsible for safe handling
see Figures 5.2.4, 5.2.5, and 5.2.9 and erection procedures.

5 -2 PCI Design Handbook/Rfth Edition


Design procedures presented in this chapter fol­ Figure 5.2.1 Draft on sides of forms
low AC1 318-95 and Other relevant- national model.
R id in g code requirements exceptwhere modified to
reflectcurrent industry practice (see also Sect. 10.5).

5.2 Product Handling

5.2.1 Introduction

The loads and forces on precast and prestressed


members during production, transportation or erec­
tion will frequently require a separate analysis be­
cause concrete strengths are lower and support
points and orientation are usually different from the
panel in its final load carrying position.
Most structural products are manufactured in
long-line steel forms with fixed cross section dimen­
sions. Standard product dimensions are shown in
",hapter 2 and in manufacturer’s catalogs. Architec­
tural wall panels are formed in a variety of sizes and
shapes, usually designed by the project architect, The items which affect the forces imposed during
and are manufactured in molds designed especially each phase are listed below:
for the panel.
1. Stripping.
The most economical element for a project is usu­
a. Orientation of member-horizontal, vertical or
ally the largest, considering:
some angle between.
1. Stability and stresses on the element during b. Form suction and impact-see Table 5.2.1.
handling. c. Number and location of handling devices.
d. Member weight and weight of any additional
2. Transportation size and weight regulations and items which must be lifted, such as forms which
equipment restrictions. remain with the member during stripping.
3. Available crane capacity at both the plant and
the project site. Position of the crane must be 2. Yard Handling and Storage.
considered, since capacity is a function of a. Orientation of the member.
reach. b. Location of temporary support points.
c. Location with respect to other stored members.
4. Storage space, truck turning radius, and other d. Orientation with respect to the sun.
site restrictions.
3. Transportation to the Job Site.
Member shapes must be such that reinforcement
a. Orientation of the member.
and concrete placement can be accomplished effec­
b. Location of horizontal and vertical supports.
tively.
c. Condition o f the transporting vehicle, roads
To remove a member from a form without partially
and site.
dismantling the form, and to reduce trapping air
d. Dynamic considerations during movement.
bubbles, the sides must have adequate draft (see
Figure 5.2.1).
4. Erection.
a. Lifting point locations.
b. Orientation and tripping (rotating).
c. Location of temporary supports.
5.2.2 Structural Design Criteria d. Temporary loadings.
Precast products must be designed for the load­
ings which occur during each phase of their exis­ 5. In-place.
tence, as shown in Figure 5.2.2. a. See Chapters 3 and 4.

PCI Design Handbook/Fifth Edition 5 -3


Figure 5.2.2 Typ ic a f handling methods

STRIPPING
A .

2 POINT 4 PO IN T

n "ri----- 11 ' i r
YARDING
i 2 POINT
o a 4 POINT
o

RO TATING

2 CRANE L IN K
TURNING RIG SAND BED
ROTATE IN AIR

STORAGE FOR SURFACE


FIN ISHING , FINAL STORAGE,
a
AND TRANSPORTATION

“A” FRAME VERTICAL RACK

ERECTION NOTE: CAUTION MUST BE USED TO


KEEP LOAD ON CRANE LINE AT TOP
(SEE SECT. 5.2.12)

5.2.3 Form Suction and impact Factors stressed reinforced members. When exposed to
view, precast products may be designed for handling
To account for the forces on the member caused
to (a) limit stresses so that cracks are not visible, or
by form suction and impact, it is common practice to
(b) control cracking in accordance with Sect. 4.2.2.1,
apply a multiplier to the member weight and treat the
considering the lower concrete strengths and actual
resulting force as an equivalent static service load.
flexural conditions. When not exposed to view, de­
The multipliers cannot be quantitatively derived, so
sign is in accordance with the strength design re­
they are based on experience. Table 5.2.1 provides
quirements for reinforced concrete in ACI 318-95.
typical values.

5.2.4 Stress Limitations


5.2.4.1 Handling Without Cracking
Stress limits for prestressed members during pro­
duction are specified in Chapter 18 of ACI 318-95, Under this criterion, surfaces are intended to re­
and are discussed in Chapter 4 of this Handbook. main free of discernible cracks by limiting the flexural
However, codes do not restrict stresses on non-pre- tension to the modulus of rupture modified by a safety

5 -4 PCi Design Handbook/Rfth Edition


factor. If the modulus of rupture is 7.51 v'fT and a a distance into the element. If cracks are narrow and
safely factor of 1.5 is used: closely spaced, the structural adequacy- of the ele­
ment will remain unimpaired because reinforcement
% = 5 X /fT (Eq. 5.2.1) will be fully protected.
T o r members exposed to weather, it- is recom­
where:
mended that crack widths befim itedto the-following:
f; = allowable flexural tensile stress computed^
using: the gross concrete section Exposed: 0.007 in.
f^ = concrete compressive strength at the time Not exposed: 0.010 in.
considered
Design procedures are illustrated in Examples
For normal weight concrete: 4.2.7 and 5.2.2.
Whether or not the product is designed to prevent
l = 1.0
or to control cracking, a minimum reinforcement ratio
For lightweight concrete, if the splitting tensile of 0.001 for wall panels should be provided in accor­
strength, f^, is known: dance with Sect. 16.4.2, A C I318-95.

= /f'T
5.2.5 Safety Factors
If frt is not known: When designing for stripping and handling, the
A, = 0.75 for all-lightweight concrete following safety factors are recommended:
= 0.85 for sand-lightweight concrete
1. Use embedded inserts and erection devices
5.2.4.2 Handling with Controlled Cracking with a pullout strength at least equal to 4 times
The amount and location of reinforcing steel has a the calculated load on the device.
negligible effect on performance until a crack devel­ 2. For members designed “without cracking",
ops. As flexural tension increases above the modu­ use a factor of 1.5 applied to the modulus of
lus of rupture, hairline cracks will develop and extend rupture as discussed in Sect. 5.2.4.1.
Table 5.2.1 Equivalent static load multipliers to account for stripping and dynamic forces^
Stripping

Finish

Product Exposed aggregate Smooth mold


Type with retarder (form oil only)

Flat, with removable


side forms, no 1.2 1.3
false joints or reveals

Flat, with false


1.3 1.4
joints and/or reveals

Fluted, with proper


1.4 1.6
draftd

Sculptured 1.5 1.7

Yard handlingb and erection0

All products 1.2

Travel*1

All products 1.5

a. These factors are used in flexural design of panels and are not to be applied to required safety factors on lifting devices. At stripping,
suction between product and form introduces forces, which are treated here by introducing a multiplier on product weight. It would be
more accurate to establish these multipliers based on the actual contact area and a suction factor independent of product weight.
b. Certain unfavorable conditions in road surface, equipment, etc., may require use of higher values.
c. Under certain circumstances may be higher.
d. For example, tees, channels and fluted panels.

PCI Design Handbook/Fitth Edition 5 -5


Table 5.2.2Suggested maximum strand diameter vent spatting ofthe edgealong which rotation occurs,
Concrete thickness, Strand diameter, A compressible material or sand bed will help:protect
in. in. this edger Members that are ^stripped flat from the
mold wilt develop the moments shown in Figure
2 %
5l2.57
2Vi % To determine stresses in flat panels for either rota­
2 % -to 3 7/l6 tion or flatstripping, the calculated moment may be
assumed to be resisted by the effective widths
3 and thicker % and. larger
shown.
In some plants, tilt fables or turning rigs are used
5.2.6 Prestressed Wall Panels to reduce stripping stresses, as shown in Figure
Panels can be prestressed, using either preten­ 5.2.6.
When a panel is ribbed or is of a configuration or
sioning or post-tensioning. Design is based on
size such that stripping by rotation or tilting is not
Chapter 18 of A C I318-96, as described in Chapter 4,
practical, vertical pick-up points on the top surface
with the further restriction that tensile stresses during
can be used. These lift points should be located to
handling should not exceed f'T given by Eq. 5.2.1. minimize the tensile stresses on the exposed face.
It is recommended that the average stress due to Since the section modulus with respect to the top
prestressing, after Josses, be limited to a range of 125
and bottom faces may not be the same, the designer
to 800psi. The prestressing force should be concen­
must select the controlling design limitation:
tric with the effective cross section in order to mini­
mize camber, although some manufacturers prefer to
1. Tensile stresses on both faces to be less than
have a slight inward bow in the in-place position to
that which would cause cracking.
counteract thermal bow (see Sect. 3.3.2). It should
be noted that, since concentrically prestressed mem­
2. Tensile stress on one face to be less than that
bers do not camber, the form adhesion may be larger
which would cause cracking, with controlled
than with members that do camber.
cracking permitted on the other face.
In order to minimize the possibflity of splitting
cracks in thin pretensioned members, the strand di­
3. Controlled cracking permitted on both faces.
ameter should not exceed that shown in Table 5.2.2.
Additional light transverse reinforcement may be re­
If only one ofthe faces is exposed to view, this face
quired to control longitudinal cracking.
will generally control the design.
When wall panels are post-tensioned, care must
Lift line forces for a two point lift, using inclined
be taken to assure proper transfer of force at the an­
lines, are shown in Figure 5.2.7. When the sling angle
chorage and protection of anchors and tendons
is small, the component of force parallel to the longi­
against corrosion. Straight strands or bars may be
tudinal axis ofthe member may generate a significant
used, or, to reduce the number of anchors, the meth­
moment. While this effect can and should be ac­
od shown in Figure 5.2.3 may be used. Plastic
counted for, it is not recommended that it be allowed
coated tendons with a low coefficient of curvature fric­
to dominate design moments. Rather, consideration
tion (n = 0.03 to 0.05) are looped within the panel,
should be given to using spreader beams, two
and anchors installed at only one end. The tendons
cranes or other mechanisms to increase the sling
remain unbonded.
angle. Any such special handling requirements
It should be noted that if an unbonded tendon is
should be clearly shown on the shop drawings.
cut, the prestress is lost. This can sometimes happen
In addition to longitudinal bending moments, a
if an unplanned opening is put in at a later date.
transverse bending moment may be caused by the
orientation of the pick-up points with respect to the
transverse dimension (Figure 5.2.9). For the section
5.2.7 Handling Considerations
shown, a critical moment could occur between the
The number and location of lifting devices are cho­ ribs because of the thin cross section.
sen to keep stresses within the allowable limits, which The design guidelines listed above apply to ele­
depends on whether the “no cracking” or “controlled ments of constant cross section. For elements of
cracking” criteria are used. It is desirable to use the varying cross section, the location of lift points is usu­
same lifting devices for both stripping and erection; ally determined by trial. Rolling blocks can be used
however, additional devices may be required to ro­ on long elements of varying section (Figure 5.2.10),
tate the member to its final position. which makes the forces in the lifting lines equal. The
Panels that are stripped by rotating about one member can then be analyzed as a beam with vary­
edge with lifting devices at the opposite edge will de­ ing load supported by equal reactions. The force in
velop moments as shown in Figure 5.2.4. When pan­ the lift lines can be determined as shown in Figure
els are stripped this way, care should be taken to pre­ 5.2.7.

5 -5 PCI Design Handbook/Fifth Edition


low impact strength at cold temperatures. Strain
hardening-froTrrbending the bars may also cause em­
brittlement. Smoottrbars ofja_known steelgrade-may
be used if adequate- embedment or mechanical- an­
chorage is provided^ The diameter must be~such that-
localized failure will not occur by-bearing on the
shackle pin.
Prestressing strand, both new and used, may be
used for lifting loops. The capacity of a lifting loop
embedded in concrete is dependent upon the
strength of the strand, length ofembedment, the con­
dition of the strand, the diameter erf the loop, and the
strength of the concrete.
As a result o f observations of lift loop behavior dur­
ing the past few years, it is important that certain pro­
cedures be followed to prevent both strand slippage
and strand failure. Precast producers’ tests and/or
experience offer the best guideline for the load ca­
pacity to use. A safety factor o f 4 against slippage or
breakage should be used. In lieu of test data, the rec­
ommendations listed below should be considered
when using strand as lifting loops:
A

1. Minimum embedment to the bend should be


16 in. '

2. Embedded ends should have 6 in. hooks bent


at 80-100 degrees. The bending radius should
be at least 2 in. and the bend should be made
mechanically without heating.

3. The strand surface shall be free of contami­


nants, such as form oil, grease, mud, or loose
rust which could reduce the bonding of the
strand to the concrete.

4. The diameter of the hook or fitting around


which the strand lifting eye will be placed
should be at least 4 times the diameter of the
strand being used.

5. Do not use heavily corroded strand or strand of


unknown size and strength.

In the absence of tests or experience, it is recom­


mended that the safe load on a single Vfc in. diameter
270 ksi strand loop satisfying the above recommen­
The most common lifting devices are prestressing dations not exceed 8 kips. The safe working load of
strand or aircraft cable loops projecting from the con­ multiple loops may be conservatively obtained by
crete, threaded inserts, or proprietary devices. multiplying the safe load for one loop by 1.7 for
Since lifting devices are subject to dynamic loads, double loops and 2.2 for triple loops. To avoid over­
ductility of the material is part of the design require­ stress in one loop when using multiple loops, care
ment. Deformed reinforcing bars should not be used should be taken in the fabrication to ensure that all
since the deformations result in stress concentrations strands are bent the same. Thin wall conduit over the
from the shackle pin. Also, reinforcing bars may be strands in the region of the bend has been used to
hard grade or re-rolled rail steel with little ductility and reduce the overstress.

PCI Design Handbook/Fifth Edition 5 -7


Table 5.2.3 Saleworking load of 7 x 19 arrcraft signed fo r both insert and concrete capacities,
cable used as lifting 4oopsa threaded inserts have many advantages. However,
correct usage iesometimes difficult to inspect during
Diameter (in.) Safe Load (kips)b
handling operations. In order tosnsure that an em­
3.6 bedded insert acts primarily in tension, a swivel plate
as indicated in Figure 5.2.11 should be used. Suffi­
4.4
cient threads must be engaged to develop the
Vi 5.7 strength o f the bolt. Some manufacturers use a long
a. 7 strands with 19 wires each bolt with a nut between the bolt head and the swivel
b. Based ©n a single strand with a factor of safety of 4 applied plata. After the bolt has “bottomed out” , the nut is
to the minimum breaking strength of galvanized cable. The turned against the swivel plate.
user should consider embedment, loop diameter and other
factors discussed for strand loops. Aircraft cables are usually Connection hardware should not be used for lift­
wrapped around reinforcement in the precast product. ing or handling any but the lightest units, unless ap­
proved by the designer. In order to prevent field error,
iifting heavy members with threaded inserts inserts used for lifting should be of a different type or
should be carefuity assessed. When properly de­ size than those used for the final connections.

5 -8 PCI Design Handbook/Fitth Edition


Figure 5.2.5 Moments developed tn panels stripped flat

(A) TWO POINT PICK-UP


MAXIMUM MOMENTS

w = WEIGHT PER UNIT AREA

+MX = -M„ = Q.0107wa2b

+My = -M y = 0.01Q7wab2

Mx RESISTED BY A SECTION OF WIDTH


15t OR b/2, WHICHEVER IS LESS.
My RESISTED BY A SECTION OF WIDTH a/2.

(B) FOUR POINT PICK-UP


MAXIMUM MOMENTS

+MX = -M x = 0.Q054wa2b

+ My = -M y = 0.0027wab2

Mx RESISTED BY A SECTION OF WIDTH


15t OR b/4, WHICHEVER IS LESS.
My RESISTED BY A SECTION OF WIDTH a/2.

PCI Design Handbook/Fifth Edition 5 -9


Figure 5.2.6 Stripping from a tilt table Figure 5.2.8 Pick-up points for equal stress
o£aribbed member

CRANE LINE LOAD = W

MULTIPLICATION FACTOR “P FOR THE TOTAL LOAD


ON HOISTING SLING WITH A SLING ANGLE OF 0
O
CO
O

90° 75° 60° 45° 15°*

NOTE: 0 1.00 1.04 1.16 1.41


IS USUALLY NOT LESS THAN 6 0 ° TO 70°
* NOT RECOMMENDED
2.00 3.86

5-1 a PCI Design Handbook/Fifth Edition


Figure-5.2.9 moments caused by eccentnc Figure 5.2.11 Swivel plate
lifting

Example 5.2.1 Stripping Forces

Given:
A ribbed waJI panel as shown below.
Span € = 40 ft - 0 in.
fd at stripping = 3000 psi (normal weight).

h __________________ 96"
M - PVc
x tan0 ~r~ i ' 1 ~—----------- - . -
Mz = Pv e
CROSS SECTION

Figure 5.2.10 Arrangement for equalizing Problem:


Determine stripping forces and corresponding
stresses.

Solution:
Half section properties:
yb = 1 0.1 9 in.

yt = 2.81 in.

Sb = 1 5 6 ins

St = 565 ins

wt. = 192 plf

^ = 0.276
yb

Stripping load:
Assume a load multiplier of 1.4 (Table 5.2.1)
w = 1.4(192) = 269 plf

Case No. 1—Neglecting the moment due to eccentric


pick-up points.

PCI Design Handbook/Fifth Edition 5-1 1


Pick-up location io r equal tension on each face
figure 5.2.8, with yc = 0:

x = —r-
: 2(1 +

■ K
2 i -h

= 0.235 +

w (x f)2 1X269[(0.235)40]
2 2

= - 11.88 kip -ft


N P
= 11,880 Ib-ft. SECTION A-A

Problem:
- M _ - 11,880(12)
- 252 psi Locate pick-up points to minimize tensile stresses
' S, 565 in the concrete.

< 5/3000 = 274 psi OK Solution:


Dead load of member-assume 1.6 multiplier
Case No. 2— Accounting for moments due to eccen­ (Table 5.2.1):
tric pick-up points

For 0 = 45°

Assume: yc = yt + 3 in. = 5.81 in. (Figure 5.2.8)

J * . = - f t ?- * ) — = 0.048
€tan 8 12(40) (tan 45°)

1 + 0.048
0.245
2 [l + /1 + 0.276(1.048)]
W = 16.67(792) + 7.292(2880) = 34,204 lb

„ 0.269[(0.245)40]2 Lifting loops should be placed symmetrically


- M = --------— -— - = - 12.92 kip-ft about the center of gravity of the member.

= 12,920 Ib-ft.
Assume critical cracking stress will occur in the
narrow sections of the unit (Section B-B):
ft = - = - 274 psi = 5/3000 OK

Example 5.2.2 Locating Pick-Up Points Section Properties (Section B-B)


A = 237.6 in2
Given:
I = 10,969 in4
The window unit shown below is to be cast face
y, = 9.224 in.
down and stripped vertically.
yb = 14.776 in.

5 -1 2 PCI Design Handbook/Fifth Edition


+ M = 17,102 (10.33 - x) - 7 9 2 - ^ p -

- 2880(2)9.33 + 19055

= - 17,102x * 105500

For equal stresses on each face:


-My, _ +Myb
f I

- M = 2880(2) (x - 1) + 792^ —
-M = ^ (+ M ) = ^ g $ ( + M ) = 1.60(+M)
= 396X2 + 4176x - 4176

396x2 + 4176x - 4176

= 1 .6 0 (- 17,102x + 105500)

x2 + 79.6x = 437
x = 5.15 ft
Use : x = 5 ft
NA + M = 105500 - 17,102(5)
= 19,900 Ib-ft
= 239.9 kip-in.

34,204/2
P = -P _ = 9874 lb - M = 396(5)2 + 4176(5) - 4176
H tan0 tan 60°
= 26504 ft-lb = 319.3kip-in.

yc = y, + 3 = 12.22in.
, ( - M)y, 319,300(9.224)
- 134 psi
‘ I 2(10,969)
12.22(9874) <n n t c l . u
Mx = ------ -------- - = 10,055 Ib-ft
(+ M )yb _ 239,900(14.776)
= 162 psi
b I 2(10,969)

Using an allowable stress of Sv/fjT, a stripping


strength as low as 1050 psi would theoretically be
permitted.
To illustrate a “controlled cracking" design allow­
ing a crack width of 0.007 in., assume the service load
moments on each narrow section are:
-M = 270 kip-in.

+M = 165 kip-in.

PCI Design Handbook/Fifth Edition 5-13


Referring is Sect. 4.2.2.1 and the section below to d e - F or2bars,
termine the maximum area o f steel for crack control:
A = 17.75(2)r(1,5)/2 = 2 6,6 in 2

fs = 22.7 ksi

a _ ~ M ______ 270____ _ q eq :_2


5 0.9fsd 0.9(22.7) (22.5)

Use 2 - # 5 bars, As = 0.62 in2

Place 1 - # 6 on bottom and 2 - #5 on top for full


length of narrow sections.

5 2 .9 Lateral Stability

Prestressed members generally are sufficiently


d = 22.5 in. stiff so that lateral buckling is precluded However,
during handling and transportation, support flexibility
For +M: may result in lateral roll of the beam, thus producing
h, = 1 4 .7 8 -1 .5 = 13.28 in. lateral bending. This is of particular concern with long
span bridge beams and spandrels in parking struc­
h2 = 14.78 in.
tures.
h2/hi = 14.78/13.28 = 1.11
The equilibrium conditions for a hanging beam are
shown in Figure 5.2.12. When a beam hangs from
A - 5(2) (1.5) = 15 in2
lifting points, it may roll about an axis through the lift­
dc = 1.5 in. ing points. The safety and stability of long beams
subject to roll is discussed in Refs. 5, 6, 7, and 8.
From Eq. 4.2.10 with w = 0.007 in.

5.2.10 Storage
______ whi_______
Wherever possible, an element should be stored
(7.6 x 1 0 -5)h23
ydTA
on points of support located at or near those used for
stripping and handling. Thus, the design for stripping
0.007(13.28) and handling will usually control. Where points other
29.3 ksi
(7.6 X 1 0 -5)(14.78)fl.5(15) than those used for stripping or handling are used for
storage, the storage condition must be checked.
If support is provided at more than two points, and
From Eq. 4.2.11: the design based on more than two supports, pre­
cautions must be taken so that the element does not
A, - i- M - = -------------------- = 0.28 in2 bridge over one of the supports due to differential
0.9fsd 0.9(29.3) (22.5)
support settlement. Particular care must be taken for
prestressed elements, with consideration made for
200 200
Ps min 0.00333 the effect of prestressing. Designing for equal
fy 60,000
stresses on both faces will help to minimize deforma­
Asmin = 0.0033(5)22.5 = 0.375in2 tions in storage.
Warpage in storage may be caused by a tempera­
ture or shrinkage differential between surfaces, creep
Use 1 - # 6 bar, As = 0.44 in2 and storage conditions. Warpage cannot be totally
For-M : eliminated, although it can be minimized by providing
blocking so that the panel remains plane. Where fea­
h2 = 9.22 in. sible, the member should be oriented in the yard so
that the sun does not overheat one side. (See Sect.
^ = 9 .2 2 - 1 .5 = 7.72 in. 3.3.2 for a discussion of thermal bowing.) Storing
members so that flexure is resisted about the strong
h2/h-i = 9.22/7.72= 1.19 axis will minimize stresses and deformations.

5 -1 4 PCt Design Handbook/Fifth Edition


Figure 5.2.12 Equilibrium of beam in tilted position

U FTIN G L O O P S-

DEFLECTION OF
/R O L L AXIS
BEAM DDE TO-
CENTER OF GRAVITY OF BENDING ABOUT
THE CURVED BEAM ARC WEAK A X IS -----------
LIES DIRECTLY BENEATH
THE ROLL AXIS
COMPONENT OF
WEIGHT ABOUT
CENTER OF
WEAK AXIS
GRAVITY
WsinO
OF CROSS
SECTION
CENTER OF MASS AT LIFTING
OF DEFLECTED POINT
SHAPE OF THE
BEAM

A) PERSPECTIVE OF A BEAM FREE TO ROLL B) FREE BODY DIAGRAM


AND DEFLECT LATERALLY

Figure 5.2.15 Panel warpage in storage For the support conditions shown in Figure 5.2.13,
warping can occur in both directions. By superposi­
tion, the total instantaneous deflection, y ^ , at the
maximum point can be estimated by:

1.875(w) sin 0 a4 , i A
Ymax (Eq. 5.2.2)
r + r

where:
w = panel weight, psf
Eci = modulus of elasticity of concrete at age
other than final, psi
a = panel support height, in.
t = horiz. distance between supports, in.
lc,lb = moment of inertia of uncracked section
in the respective directions for 1 in.
width of panel, in4
Figure 5.2.14 Effect of compression reinforce­
ment on creep

oi--------- --------- --------- --------- --------- ---------


0- 0.005 0.01 0.015 0.02 0.025 0.03

P'

PCI Design Handbook/Fifth Edition 5-15


This instantaneous-deflection should be modified Figure 52.16 Transportation of single-story
by a factor to account for the time-dependent effects panels-
erf creep and shrinkage. ACt-313-95=suggests theTo-
tai deformation, yt, ata n y time can be estimated asr

¥t = ymax (1 + -{Eg- 5.2.3)

where:
yt = lime dependent displacement
ymax = instantaneous displacement
X = amplification due to creep and shrink­ Figure 5.2.17 Transportation o f multi-story
age (Figure 5.2.14) panels
p' = reinforcement ratio for nonprestressed
compression reinforcement, A4/bt
(Figure 5.2.15)

Figure 5.2.15 Area considered to compute p'

Maximum width with permit varies among states,


and even among cities-from 10 to 14 ft. Some states
alJow lengths over 70 ft with only a simple permit,
while others require, for any load over 55 ft, a special
permit, escorts front and rear and travel limited to cer­
tain times of the day. In some states, weights of up to
100 tons are allowed with permit, while in other states
there are very severe restrictions on loads over 25
tons.
These restrictions add to the cost of precast con­
crete units, and should be compared with savings
5.2.11 Transportation realized by combining smaller units into one large
unit. When possible, a precast unit, or several units
The method used for transporting precast con­ combined, should approximate the usual payload of
crete products can affect the structural design be­ 20 tons. For example, an 11 ton unit may not be eco­
cause of size and weight limitations and the dynamic nomical, because only one can be shipped per load,
effects imposed by road conditions. while two 10 ton units could be shipped on one load.
Except for long prestressed deck members, most Erection is facilitated when members are trans­
products are transported on either flatbed or low-boy ported in the same orientation they will have in the
trailers. These trailers deform during hauling. Thus, structure. For example, single-story wall panels can
support at more than two points can be achieved only be transported on A-frames with the panels upright
after considerable modification of the trailer, and (Figure 5.2.16). A-frames also provide good lateral
even then results may be doubtful. support and the desired two points of vertical sup­
Size and weight limitations vary from one state to port. Longer units can be transported on their sides to
another, so a check of local regulations is necessary take advantage of the increased stiffness compared
when large units are transported. Loads are further with flat shipment (Figure 5.2.17). In all cases, the
restricted on some secondary roads during spring panel support locations should be consistent with the
thaws. panel design. Panels with large openings sometimes
The common payload for standard trailers without require strongbacks, braces or ties to keep stresses
special permits is 20 tons with width and height re­ within the design values (Figure 5.2.18).
stricted to 8 ft and length to 40 ft Low-boy trailers per­ During transportation, units are usually supported
mit the height to be increased to about 10 to 12 ft with one or both ends cantilevered. For members
However, low-boys cost more to operate and have a not symmetrical with respect to the bending axis, the
shorter bed length. In some states, a total height expressions given in Figure 5.2,19 can be used for
(roadbed to top of load) of 13 ft 6 in. is allowed with­ determining the location of supports to give equal
out special permit. This height may require special tensile stresses for positive and negative bending
routing to avoid low overpasses and overhead wires. moments.

5 -1 6 PCI Design Handbook/Rfth Edition


Figure 5.2.18 Methods of temporary Solution:
strengtheninc^otpaneJewitli Establish Handling Procedures:
significant openings
Casting: Face down. Use same mix-for ex-
posed aggregate surface (retarded)
and smooth white side bands. U se'
gray-concrete-backup^
Stripping: Due to edge detail and- inside crane
headroom, panel cannot be turned
on edge directly in mold, therefore
strip flat and move to sand bed (or
turning equipment) for turning.
Storage: Since panels will be stored for sever­
al months and storage yard is sub­
ject to settlement, thus negating
possible four-point support, and
since bowing must be avoided, store
on edge.
5.2.12 Erection
Determine Handling Multipliers ( Table 5.2.1):
Precast concrete members frequently must be re­
oriented from the position used to transport to that Stripping: Exposed flat surface has deep expo­
which it will be in the final construction. The analysis sure (heavy retarder); side rails re­
for this “tripping" (rotating) operation is similar to that moved prior to stripping; drafts on
used during other handling stages. Figure 5.2.21 edge detail are good: use 1.2.
shows maximum moments for several commonly Use strand loops in back of panel
used tripping techniques. (plant practice).
When using two crane lines the center of gravity Yard Turning: use 1.2; transport to stor-
must be between them in order to prevent a sudden handling: age: use 1.2.
shifting of the load while it is being rotated. To ensure
that this is avoided, the stability condition shown in
Figure 5.2.20 must be met. The capacities of lifting Shipping: Distance traveled is 150 miles and
devices must be checked for the forces imposed dur­ jobsite roadways are bumpy: use 1.7
ing the tripping operation, since the directions vary. (exceeds the value 1.5 recom­
mended in Table 5.2.1 since travel
conditions are considered rather se­
Example 5.2.3 Flat Panel vere and cracking is limited).

This example illustrates the use of many of the rec­


ommendations in this section. It is intended to be il­ Erection: Use 1.5 (based on engineer’s judg­
lustrative and general only. Each plant will have its ment instead of value from Table
own preferred methods of handling. 5.2.1).

Given: Handling devices: Use 4 (from Sect. 5.2.5).


A flat panel used as a non-load bearing facade on
Section Properties (use 7 in. thick x 9 ft-11Vz in. wide):
a two-story structure, as shown in Figure 5.2.22.
Wind Load-psf pressure or suction
r. = 5000 psi @ 28 days
A = 836 in3
ft* = 2000 psi @ stripping
Sb = St = 976 in3
Cracks in rear face permitted without width restric­
tion. Crack width in exposed face limited to 0.007 in.
I = 3416 in4
Problem:
Check critical stresses and economic consider­ Unit weight @ 150 pcf = 87 psf, or 870 plf
ations involved with stripping, handling and erection
Total weight = 30.6 kips
of precast flat panel.

PCI Design Handbook/Fifth Edition 5-17


Figure 5.2.19 Equations f o r equal tensflestresses top and bottom-unsymmetrical members

Establish Allowable Tensile Stresses: Additional moment due to lifting angle (Figure 5.2.9):

@ stripping, yard handling and storage:

f,; = 5 ( qq^ = 0.224 ksi (from Sect. 5.2.4)

@ shipping and erection:

f , _ 5/5000
0.354 ksi
1000
Check Handling Stresses-Stripping:

a. Longitudinal bending Two point pick-up, Figure


5.2.5(A)
a = 10.0 ft Figure 5.2.20 Stability during erection
b = 35.2 ft
a/2 = 60 in.
60(7)2
S =
6
My = 0.0107 wab2
= 0.0107(0.087) (10) (1.2) (35.2)2(12)
= 166 kip-in.

f, = fb = i | | = 0.339 > 0.224 ksi

Therefore, 2-point stripping is not adequate

Four point pick-up, Figure 5.2.5(B):


My = 0.0027 wab2
= 0.0027(0.087) (10)(1.2)(35.2)2(12)
= 41.9 kip-in.

5 -1 8 PCI Design Handbook/Fifth Edition


Figure 5.2.2t Typical tripping (rotattog)positions for erection of wall panels3

TWO POINT PICK A A


FOR ROTATION: wff
w 1\
2a
^ -- " " M- = 0.5wb2#2
M
general equation „ M+
M , L._______ a# 2
M+
„ _________ ____________ i ______________________ *

TWO POINT PICK A A


FOR ROTATION: 0.70wt 0.30wf
w
________
EQUAL NEGATIVE AND M~ = M+ = 0.044w£2
POSITIVE BENDING , 0.29£ ( B a.7K MT
MOMENTS

TWO POINT PICK A0.63w£ A


FOR ROTATION: 0.37w£
w
LOWER PICK POINT AT *'***•«. __ M+ = 0.067w<2
M
TYPICAL TWO POINT 0.79£ M^ M- =* 0.022wf2
PICK LOCATIONS . °'21 f r
t

THREE POINT PICK


FOR ROTATION:

AT TOP AND FIRST AND


THIRD LOWER PICK + 0.034wf2
LOCATIONS - 0.0054wf2

THREE POINT PICK 0.04wt


FOR ROTATION:
0.96w<

a. D ash ed lines indicate deflected shapes.

PCI Design Handbook/Fifth Edition 5 -1 9


Figu re 5.2^2 Illustrations for Example 5.2.3

7"'

5 -2 0 PCI Design Handbook/Fifth Edition


= PYc_= [0.87(1.2)(35.2)1 5 Check-Handling Stresses-Torning:
Mx la n d [ 4(2) ] tan 45° Stresses for turning from edge to edge are exces­
sive. Note also thatedge detail may-restrict this type
Mx = 23-kip-in
of turning, due to excessive shear loading on insert
-Mfetai = 41.9 + 23 = 64.9 kip-in cast into edge.
ft = fb = 0.132<0.224 ksi OK Therefore turn as follows:

Use 4-point pick-up for stripping

Note:. By inspection of support structure and


4-point pick-up stripping locations, it is determined
that shifting lifting loops toward ends slightly witi
avoid interference between loops and edge beams
thus avoiding a delay in erection while loops are
burned off. Effect on stresses is minor.

b. Transverse bending—beam strip properties

Transverse moments:

0 = 60.6°

yc = 5 in.

MOMENT
15t = 105 in. DIAGRAM

b/4 = 105 in.


S = 105(7)2/6 = 857 in3
Mx = 0.0054(0.087) (1.2) ( 1 0 ) 2 (1 2) (35.2)
= 23.8 kip-in
w = 0.087(1,2)(35.2/4) = 0.92 kip/ft
1.2(0.087)(10)(35.2) 5
M x (sling angle)
(4)(2) tan 60.6° R, = 5.82 kips

Rr = 0 .9 2 (1 0)-5 .8 2 = 3.38 kips


= 12.9 kip-in.
Ma = 0.92(2.1)2(12)/2 = 24.3 kip-in.
Mb maximum at 3.38/0.92 = 3.67 ft
Total Mx = 23.8 + 12.9 = 36.7 kip-in
Mb = (3.38(3.67)-0.92(3.67)2/2)12
ft = fb = 36.7/857 = 0.043 ksi < 0.224 ksi OK = 74.5 kip-in.
Final stripping loop locations: Using same resisting section as for stripping:
ft = 24.3/857 = 0.028 ksi < 0.224
fb = 74.5/857 = 0.087 ksi < 0.224

Therefore, concrete should have strength of 2000


psi at stripping.

Longitudinal bending similar to stripping.

Use 4-point turning with one edge in sand bed.

Check Handling Stresses-Shipping:

The following factors were considered in deter­


mining shipping method:

PCI Design Handbook/Fifth Edition 5 -2 1


Alternatives: From Figure 5.2.5(A) for fuH panel width:
(1)-Ship flat: • strength with 2-point support
My = 2(0.0107X1.05) (35.2)2(12)
•-perm its required- in 3 states
for- each load (since panel = 333 kip-in.
weight of 30,600 lb restricts
loads to one-panel each) f = 334/976 = 0.342 ksl < 0.354 OK
(2) Ship-vertical: * requires low-boy trailer with
35 ft well with maximum "Since stress is high and a long panel traveling 150
height of 3 ft which would re­ miles is subject to possible dynamic forces, provides
strict total height to 13.5 ft (6 3rd frame for lateral support only, to avoid possible
in. support material) harmonic motion.

(3) Special frame: • fabricate special frame so


30(3) = 90 frames required
panel could be set at about a
Cost estimated @ $800 each or $72,000
45° angle and be within non­
permit restrictions of 13.5 ft
(1) Flat—cost of permits (check with appropriate
high by 8.0 ft wide
authorities):
$240x132 loads: = $31,680
Other factors: possible saving: = $40,320
• Total number of p ie ces-132
Provide proper support to achieve this saving.
• Erection ra te -10 pieces per day Two-point support is desirable since flexing of trailer
normally will lower or raise any additional supports
• Drivers not permitted to drop loads on job after
thus causing bridging and unanticipated stresses.
working hours (union regulations at job site).

• Permit loads on bridge restricted to traveling be­ 4-Point Support:


tween 9:30 A.M. and 2:30 P.M.

To avoid disrupting normal production in plant,


loading must be done in P.M. (same cranes used for
stripping in A.M., yarding and loading).
3 '- 8 " 1 0 '-4 " r-2 " J 3 '-8 "
■ 1 0 '‘ 4 '' >
These considerations led to the conclusion that 30
3 5 '-2 "
trailers would be necessary to properly supply the
job. This can be demonstrated as follows with each
group of trailers being 10 (A,B,C):
This is too far apart to consider for shipping since
the trailer will deflect and cause 2 or 3 point support at
Mon Tues Wed Thurs Fri times during transportation. Try adjusting support
points so that 10 f t -4 in. is reduced to 5 ft - 0 in. which
Load A B C A B
is a practical limit to ensure 4 points will have support
Ship A B C A at all times during transportation.
Erect A B C a b c

Return
A B C
Trailer
4 '- 6 " _ 5 '-0 "_ 1 6 '-2 " - 5 '-0 "
l ' 6>

3 groups of 10 required = 30 trailers 3 5 '- 2 "

Reconsider alternatives:
(2) Vertical-30 low-boys not available A moment distribution of this condition results in
moments as follows:
(3) Special frames @ 45°with 1 panel per trailer
Check panel bending about the weak axis. Ma= 0.0082w€2 = 0.0082(0.87)(1.7)(35.2)2(12)
Bending in longitudinal direction:
= 180.3 kip-in.
tension in back face
w = 0.87(1.7)(sin 45°) = 1.05-kip/ft

5 -2 2 PCI Design Handbook/Fifth Edition


_Mb = 0:014w€2-= 307.8 kip-in.
tension in back face W = = 0.678 ksi too high

Sincelhis-stress is too high; adjustments m ih e lift


Mc = 0.0125w£2 =.274.8 kip-in. loop locations are required^© avoid cracking the pan­
Jension in front face el. The arrangement shown below is one of several
possibilities.
Stresses:
f« = = CL185ksi < 0.354 ksi OK
Ta 976

fb = ^ = 0315 ksi OK

fc = = 0.281 ksi OK
Various trials will be required to establish the most
Ship with supports as shown.
suitable arrangement. Note, the main crane line (line
Note: Had stresses been excessive, supports 2, Figure5.2.20)shouid be below the center of gravity
could be shifted toward center of panel until cantile­ of the piece to avoid uncontrolled rotation of the pan­
el. Ensuring that crane line 1 requires a force to
ver condition is such that it produces a stress of 0.354
create rotation avoids this potential condition.
ksi.
An alternate solution provides 4-point support for
the precast piece with 2 supports on the truck bed or 5.3 Erection Bracing
as shown.

j PRECAST PANEL 5.3.1 Introduction

This section deals with the temporary bracing


r M M M' ' M ~~l which may be necessary to maintain structural stabil­
____ 1 TXT ' ' ' M '
ity of a precast structure during construction. When
CTO possible, the final connections should be used to pro­
vide at least part of the erection bracing, but addition­
Check Handling Stresses—Erection: al bracing apparatus is sometimes required to resist
Try 3-point pick as follows: all of the temporary loads. These temporary loads in­
clude wind, seismic, eccentric dead loads including
construction loads, unbalanced conditions due to
erection sequence and incomplete connections.
Due to the low probability o f design loads occurring
during erection, engineering judgment should be
used to establish a reasonable load.
Proper planning of the construction process is es­
sential for efficient and safe erection. Sequence of
erection must be established early, and the effects
accounted for in the bracing analysis and the prepa­
ration of shop drawings.
The responsibility for the erection of precast con­
crete may vary as follows:
Longitudinal bending: with rolling block, reactions
at lifting loops are equal.
1. The precast concrete manufacturer supplies
w = 0.87(1.5) = 1.31 kip/ft the product erected, either with his own forces,
or by an independent erector.
Determine the critical stresses:
when flat (see Figure 5.2.21): 2. The manufacturer is responsible only for sup­
plying the product, F.O.B. plant or jobsite.
M + = 0.034(1.31)(35.2)212 Erection is done either by the general contrac­
tor or by an independent erector under a sepa­
= 662 kip-in. rate agreement.

PCI Design Handbook/Fifth Edition 5 -2 3


3. The products are purchased by an indepen­
dent ereetor-wh© he® a contract to furnish the 3. After, to_ensure that the products have-been
complete precast concrete package. -erected within tolerances.
Responsibility for-stability during erection must be
clearly-understood. Design for erection conditions
5.3.2 Loads
must be in accordance with all local, state-and federal
regulations, ft is desirable that#iis design be directed 1. Wind
or approved by a professional engineer. Erection Wind loads used, for erection design should be
drawings define the procedure on how to assemble based on local codes, tempered by engineering
the components into the final structure. The erection judgment. For example, in trurricane regions, the
drawings should also address the stability of the maximum code load is usually not used, since there
structure during construction and include temporary is sufficient warning of a hurricane so that additional
connections. When necessary, special drawings bracing can be installed. Note that it is possible that
may be required to include shoring, guying, bracing more surface area is exposed to wind pressure than
and specific erection sequences. Additional guide­ when the structure is totally enclosed.
lines are available in Ref. 3. For large and/or complex
projects, a pre-job conference prior to the prepara­ 2. Earthquake
tion of erection drawings may be warranted, in order In seismic regions, the degree to which earth­
to discuss erection methods and to coordinate with quake loads are considered for construction design
other trades. is a decision which should be made by the engineer
designing the temporary bracingsystem, unless the
subject is covered by local codes or project specifica­
5.3.1.1 Handling Equipment
tions. Often seismic loading is neglected unless the
The type of jobsite handling equipment selected project is expected to be shut down in a temporary
may influence the erection sequence, and hence af­ condition for an extended period of time.
fect the temporary bracing requirements. Several
types of erection equipment are available, including 3. Construction Loads
truck-mounted and crawler mobile cranes, hydraulic This includes materials stored on floor members
cranes, tower cranes, monorail systems, derricks such as masonry, drywall or other finishing materials,
and others. The PCI Recommended Practice for and construction equipment such as buggies used
Erection of Precast Concrete [3] provides more infor­ for concrete placement. A value of 25 psf has been
mation on the uses of each. used without creating an excessive burden on the
bracing requirements.

4. Temporary Conditions
Figure 5.3.1 shows temporary loading conditions
5.3.1.2 Surveying and Layout that affect stability and bracing design.
Before products are shipped to the jobsite, a field
check of the project should be made to ensure that a. Columns with eccentric loads from other fram­
prior construction is suitable to accept the precast ing members produce sidesway which means
units. This check should include location, line and the columns lean out of plumb. Cable or other
grade of bearing surfaces, notches, blockouts, an­ type of bracing can be used to keep the col­
chor bolts, cast-in hardware, and dimensional devi­ umns plumb. A similar condition can exist
ations. Site conditions ouch as access ramps, over­ when cladding panels are erected on one side
head electrical lines, truck access, etc., should also of a multi-story structure.
be checked. Any discrepancies between actual con­
ditions and those shown on drawings should be cor­ b. Unbalanced loads due to partially complete
rected before erection is started. erection may result in beam rotation. The erec­
Surveys should be required before, during and af­ tion drawings should address these condi­
ter erection: tions. Some solutions are:

1. Before, so that the starting point is clearly es­ • Install wood wedges between flange of tee
tablished and any potential difficulties with the and top of beam.
support structure are determined early.2
• Use connection to columns that prevent
2. During, to maintain alignment. rotation.

5 -2 4 PCI Design Handbook/Fifth Edition


concrete components, are needed to complete truss
• Erect tees on both sides oibeam. action of:the-bracing system.
A number of wine rope types are also, available [4j .
• Prop, tees to level below. Typically, wire rope is constructed;: o f three basic
components; (1) wires that form the strands, (2) mul­
c. Examples of rotations and deflections of fram­ ti-wire strands laid helically around a core and (3) the
ing members caused by cladding panels which core (see Figure 5.3.3):
may result in alignment problems and require
The wire may be Iron, stainless steel, monel, or
connections that allow for realignment after all
bronze, but for construction uses it is nearly always
panels are erected.
high carbon steel. The core, which Ts the foundation
for the wire rope, is made of either fiber or steel. The
5.3.3 Factors of Safety most commonly used cores are: fiber core (FC), inde­
pendent wire rope core (IWRC), and wire strand core
Safety factors used for temporary loading condi­ (WSC).
tions are a matter of engineering judgment, and
Rope is classified by the construction type. Forex-
should consider failure mode (brittle or ductile), pre­
ample, a 6 x 7 FC consists of 6 strands of 7 wires
dictability of loads, quality control of products and
each, wrapped around a fiber core. A 6 x 19 IWRC
construction, opportunity for human error, and eco­
has 6-19-wire strands wrapped around an indepen­
nomics. The total factor of safety also depends on
dent wire rope core. Strength of wire rope is depen­
load factors and capacity reduction factors used in
dent on the component materials. Grades include:
the design of the entire bracing system. These must
traction steel (TX), mild plow steel (MPS), plow steel
be consistent with applicable code requirements.
(PS), improved plow steel (IPS), and extra improved
Suggested safety factors are shown in Table 5.3.1.
plow steel (XIPS).
Table 5.3.2 shows the properties of several com­
Table 5.3.1 Suggested factors of safety for monly used wire rope sizes. It is recommended that
construction loads the minimum size rope used for bracing be Vfc in. di­
ameter.
Bracing for wind loads.............................................2 The elongation or “stretch” of wire ropes must be
considered in designing bracing. Elongation comes
Bracing inserts cast into precast members............ 3 from two sources: constructional stretch and elastic
stretch. Constructional stretch is dependent on the
Reusable hardware.................................................. 5 classification and results primarily from a reduction in
diameter as load is applied and the strands compact
Lifting inserts.................................................................. 4 against each other. Approximate ranges of
constructional stretch are shown in Table 5.3.2.
Wire ropes may be pre-stretched to remove some of
the constructional stretch.
Elastic stretch is caused by the deformation of the
5.3.4 Bracing Equipment and Materials
metal itself when load is applied. As with construc­
tional stretch, a precise value is difficult to establish,
For most one- and two-story high components
but the following equation gives adequate results:
that require bracing, steel pipe braces similar to those
shown in Figure 5.3.2 are used. A wide range of
bracing types are available from a number of suppli­
ers, who should be consulted for dimensions and ca­ Elastic stretch = (Eq. 5.3.1)
pacities. Pipe braces resist both tension and com ­
pression. When long braces are used in
compression, it may be necessary to provide lateral
restraint to the brace to prevent buckling. where:
Cable guys with turnbuckles are normally used for P = change in load
higher structures. Since wire rope used in cable guys
L = length
can resist only tension, they are usually used in com­
bination with other cable guys in an opposite direc­ A = area of wire rope
tion. Compression struts, which may be the precast E = modulus of elasticity

PCI Design Handbook/Fifth Edition 5 -2 5


Figure 5.3.1 Tem porary-ioadrag-oondfflons that affect stability

Table 5.3.2 Properties of wire rope


Nominal Fiber Core (FC) Wire Core (iWRC)
diameter E = 10,000 ksi E = 13,000 ksi
in. Constructional stretch: 0.5-0.75% Constructional stretch: 0.25-0.5%
Area, in2 Nominal strength {kips) Area, in2 Nominal strength (kips)

Vi 0.096 20.6 0.113 22.2


% 0.150 31.8 0.176 34.2
% 0.288 45.4 0.254 48.8
Vs 0.294 61.4 0.345 66.0
1 0.384 79.4 0.451 85.4
11/8 0.486 99.6 0.571 107.0
VA 0.600 122.0 0.705 131.2
1Vs 0.726 146.2 0.853 157.2
VA 0.864 172.4 1.015 185.4

Properties based on 6 x 7 classification, 6 x 1 9 classification approximately 4% higher.


Based on “Improved Plow Steel.” “Extra Improved Plow Steel” approximately 15% higher.

5 -2 6 PCI Design Handbook/Fifth Edition


Figure 5.3.2 Typical pipe braces
Total = 6.3- + 3.5 = 9.8Hn.

Design so that stretch doesmot result in unaccept­


able movement of the braced structure, readjustment
of the wire rope tension may be necessary.

5.3.5 Erection Analysis

The following examples demonstrate a suggested


procedure to ensure structural stability and safety
during various stages of construction. Actual loads,
factors of safety, equipment used, etc., must be eval­
uated for each project

(A) CONTINUOUS (B) INCREMENTAL Example 5.3.2 Load Bearing Walt Panel
ADJUSTMENT ADJUSTMENT
Structure
Given:
Figure 5.3.3 Wire rope 18-story hotel with plan as shown m Figure 5.3.4.
Floor to floor—8 ft-8 in.
Floor system—8 in. hollow-cote planks.
Wind load— 15 psf. The code requires higher loads
at upper levels, but the engineer has judged
that for temporary conditions, 15 psf is ade­
quate.

No expansion joint.
Final stability in the east-west direction depends
on the stair and elevator walls at the ends, plus the
exterior precast panels on the north and south walls
(lines A and D). Diaphragm action of the floor distrib­
utes lateral loads to these shear walls.

Problem:
Determine sequence of erection and temporary
bracing system.

Solution:
After consultation between precaster and erector,
it has been decided to erect the floors and load
Example 5.3.1 Stretch of Wire Rope bearing walls through the sixth floor one floor at a
time. Then a second crew and lighter crane will be
Given: used to erect the precast wall panels on lines A and D.
A 70 ft long, % in. diameter, 6 x 7 FC wire rope re­ Erection of structural precast floors and walls will
sisting a tension force of 12 kips. never be more than six levels ahead of the shear
Problem: walls, lines A and D. Design tasks include:
Determine the total stretch. 1. Design single panel with two braces at upper
Solution: level of any erection phase.
Constructional stretch (use 0.75%) = 2. Determine diaphragm loads and check if eleva­
0.0075(70)(12) = 6.3 in. tor walls can resist these for six levels. If not,
reduce the number of levels the floor erection
Elastic stretch - = 3.5 in.
can be ahead of the shear wall placement.

PCI Design H andbook/Rfth Edition 5 -2 7


Figure 5.3.4 Schematic plan of typical floor— Example 5.3.2

Design Single Panel: for the inserts in the panel and floor, and pressure for
the brace. Forces on top connection:

BOLT AND INSERT

DETAIL
V = 1.07 kips
T _ 1.51 , 1-07(1 -5)
1.39 kips
72 6-1
Design of inserts and bolts is discussed in Chapter
6. Design of the connection at the bottom of the
brace is similar. Expansion bolts in hollow-core
plank must be placed to avoid the cores. Vertical tie
connections between wall panels is usually adequate
to take the wind shear at the base of the panel.
Check Panel Section:

Consider the horizontal span:


Wind load per brace = 0.015(27)/2 = 0.20 kip/ft w = 0.015(8) = 0.12 kip/ft
, 0 .2 ° y /2 ) , 1 -M = wa2/2 = 0.12(5.33)2(12)/2
o = 20.5 kip-in.
Rb = 0.20(8) - 1.07 = 0.53 kips +M = w€2/8 - ( - M)

Rbrace = 1.07 = 1.51 kipS = 0.12(16.33)2(12)/8 - 20.5


= 27.5 kip-in.
These loads and reactions can act in either direc­ S = bd2/6 = 96(8)2/6 = 1024 in 3
tion. Typically, critical directions would be suction
f = 27.5/1024 = 0.027ksi < 5 / f f

5 -2 8 PCI Design Handbook/Fifth Edition


Figure 5.3.5 Distributionof east-west windload— Example 5.3.2

ELEVATION AT TYPICAL FLOOR ELEVATION AT TOP LEVEL

Figure 5.3.6 Distribution of wind from 45° angle— Example 5.3.2

24' CLEAR

PCI Design Handbook/Fifth Edition 5 -2 9


Determine Diaphragm Loads: Exampfe5.3:3 Single-Story Industrial
Building
Shielding of the wind from adjacent structures- is
not considered -in building design, because o rth e
Given:
possibility that the shield may eventually be razed.
A single-story building with the plan shown schemati­
However wind shielding b y adjacent panels during
cally irr figure'S.3,7. Totally precast structure-col­
erection is more predictable; and may be used with
umns, inverted tee beams, -double tee roof, load
judgment realizing that erection sequences can bearing and non-load bearing double tee wafT panels.
change. Wind toad = 10 psf
Various wind directions must also be considered.
fin a l stability by exterior panels acting as shear walls.
For this structure, temporary loading from north or
No expansion joint.
south wind is less critical than the final condition, so it
Erection sequence: With a crane in the center bay,
can be neglected. Two possible wind directions will
start at column line 8 and move toward line 1, erecting
be considered:
all three bays progressively.

Problem:
1. Wind from east or west. Apply full wind toend Determine temporary erection bracing systems.
wall, with the other walls assumed to be 50%
shielded (some wind can flow over the tops of
the walls), except at the ends. Assume full
wind applied to 25% of the length of the interior
panels as wind flows along the sides of the
building (see Figure 5.3.5.).

At 18th level:
0.015(8)(60) + 0.015(4)(60)(9) = 39.6 kips
PLAN
At other levels: Solution:
0.015(8) (60) + 0.015(6.75) (2) (8) (9) To demonstrate the thought process the design­
= 21.7 kips er should go through, the following temporary condi­
tions will be considered:

2. Wind from any 45° angle. Apply full wind 1. Erect columns B8 and B7 with inverted tee
component to end wall with 50% shielding at beam between them and check as free
upper level. Shielding of lower interior panels standing on the base plate.
is determined from the geometry (see Figure wb = 0.01(2.33) = 0.023 kip/ft
5.3.6). P = 0.023(30)/2 = 0.35 kips

At 18th level: wc = 0.0t(1) = 0.01 kip/ft

0.015(0.707) (8) (60) i


+ 0.015(0.707) (4) (60) (9) p L, 28"

= 28.0 kips

Wc — ►
At other levels: ,1 2 in. SQUARE COLUMN
'-0" / wt. = 0.15 k/ft
0.015(0.707)(8)(60)
+ 0.015(0.707) (24) (8) (9)
= 23.4 kips

The above shielding effects are based on judg­ ELEVATION


ment, and will vary among structures and designers.
Note that the resultant of loads for condition 1 acts at Moment at column base = 0.35(24) + 0.01 (24)2/2
the center of the structure, while for condition 2 it acts
= 11.3 kip-ft
eccentrically.
The design of a diaphragm and shear walls is dis­ D.L. at column base = 0.5(30)/2+0.15(24)
cussed in Chapter 3, and connections in Chapter 6. = 11.1 kips

5 -3 0 PCI Design Handbook/Fifth Edition


Design base plate-and anchor bolts per Sect. 6.7. Case a: D e a d Loads Onlyr
( 7 ) 11.3 kip4t Load from roof tee = 0.047(5)(60/2)
11.1 kips I = 7.65 kips/stem

M = 7.05(9/12) = 5.29 kip-ft

'if l (fa P = 7.05 + 5.6 = 12.65 kips


* - i:r

4t
£ " OkJ*.*

2. Erect wall panels on line A from 7 to 8. There


are two cases ta consider:
Case a: If the base of the wall has some mo­
ment resisting capacity, the base should be
designed for:

Check beam/column connection. This will be critical


when all three roof tees in bay A are in ptace.

M = 0.01 (10) (0.5) (28)2/2 = 19.6 kip-ft/stem


P = 0.4(28)/2 = 5.6 kips/stem

Case b: If the wall panel has no moment resist­


ing capacity, a brace must be provided, as
shown in Example 5.3.2. Check the unsup­
ported length of the brace to prevent buckling
under compressive loads. Also check the hori­
zontal reaction at the base of the panel.

Load from double tees = 7.05 kips/stem


times 3 stems = 21.2 kips
M = 21.2(10/12) = 17.7 kip-ft
P = 21.2 + 0.5(30/2) = 28.7 kips

Check column base connection:

3. Erect double tee roof members in bay A. As­ M - 17.7 kip-ft (from above)
suming the wall panel has moment resisting P = 35.7 + 0.15(24) = 39.3 kips
capacity at the base, two bading conditions
must be checked:

> 10DT24 (n COLUMN BASE CONNECTION

"’ .a .i V ‘V * ’

SECTIO N THRO UG H BAY A * '

PCI Design Handbook/Fifth Edition 5 -3 1


In this example, it is apparent that the loading for 1 Given:
and 2 above will be more critical than this condition. A typical 8-story parking structure shown sche­
The designer should always try to use the perma­ matically in Figure 5.3.8.
nent connections for erection stability. In this exam­ Structural system—pretopped double tees on L-
ple, the final connections between the wall and roof shaped and inverted tee interior beams and load
deck and the beam and roof deck will provide some bearing spandrel panels. Multi-level columns are
degree of moment resistant capacity. This will re­ spliced at level 4. No expansion joint.
duce the moments on some of the connections con­ Loads: Wind— 10 psf. Construction loads-5 psf.
sidered above. This is lower than recommended in Sect. 5.3.2 be­
cause there are virtually no interior finishing materi­
als, such as masonry or drywall in this construction.
Final stability will be provided by:
4. Erect wall panels on line 8 from A to B. (Note: If Long direction: The ramped floors acting as a
the crane reach is limited, these may be truss.
erected immediately after the first roof tee is Short direction: Shear walls as shown.
placed.) These will be connected to the roof
with permanent diaphragm transfer connec­ Problem:
tions. This provides a rigid “box” which will pro­ Outline critical design conditions during erection,
vide stability to the remainder of the structure. and show a detailed erection sequence.

Solution:
5. Continue erection working from the rigid box in Outline of critical erection design conditions:
bay A. It is unlikely that other temporary condi­
tions will be more critical than those encoun­ 1. Free standing columns-design columns and
tered in bay A. However, each should be con­ base plates in accordance with Chapters 3, 4
sidered and analyzed if appropriate. and 6.

5 -3 2 PCI Design Handbook/Fifth Edition


Figure 5,3.8 Parking stm cture-of Exam ple 5.3.4

PCI Design Handbook/Fifth Edition 5 -3 3


2. Determine bracing forces for wind loads from 19. Erect bay BtcrStfrlevel.
either direction, 20. Erect column C3.
3. Select wire rope sizes. 21. Erect bay ICto 4th1evel.
4. Determine forces on inserts, used for bracing 22. Erect bay J to roof.
and select anchorages in accordance -with 23. Erect columns A5-artd D5.
Chapter 6.
24. Erect bay D to 3rd level:
5. Check column designs with temporary loading 25. Install X-bracing from A5 to B5. Check capac­
and bracing. ity required.
6. Check diaphragm design anddetermine which 26. Erect bay C to 5th level.
permanent connections must be made during 27. Erect column C4.
erection. Determine need for temporary con­
28. Erect bay L to 4th level.
nections.
29. Splice second tier columns at C3, A4 and B4.
7. Check inverted tee beams and their connec­
30. Erect bay K to 6th level.
tions for loading on one side only.
31. Erect bay B to roof.
Sequence of erection: Start at column line 1 and,
with crane in north bay, erect vertically and back out 32. Continue in same sequence.
of structure at line 9 in the following sequence: Additional Notes:
1. Erect columns A1, B1, A2 and B2-(lower tier). 1. After each level is erected weldloose plate from
Check as free standing columns with 10 psf spandrel to plate in double tee. (See Figure
wind on surface. 5.3.9).
2. Install additional X-bracing on line B from 6 to 7
2. Erect 3 levels in bay A. and 7 to 8 after framing is erected.
3. Install X-bracing between A1 and B1. Check 3. Install X-bracing on line 9 from A to B and B to
capacity required with full wind load on ex­ C when framing is erected.
posed surfaces. 4. Install cables to upper tier columns as required
4. Erect column A3 and shearwall. to keep columns plumb.
5. Check upper tier columns as free standing with
5. Erect 3 levels in bay B.
full wind load on exposed surfaces.
6. Erect 4th level in bay A. 6. Maintain tightness of cables.
7. Install X-bracing at line B between B2 and
shear wall. Check capacity required with full
Figure 5.3.9 Typical load-bearing spandrel
wind load on exposed surfaces.
Example 5.3.4
8. Splice 2nd tier columns at A1, A2, A3, B1 and
B2. Check capacity of welded splice with up­
per tier as free standing columns with 10 psf
wind on surfaces.

9. Erect columns C1 and C2.


10. Erect 4 levels in bay J.
11. Install X-bracing from columns B1 to C1.
Check capacity required with full load on ex­
posed surfaces.

12. Erect columns A4 and B4.


13. Erect to 3rd level in bay C.
14. Install X-bracing between B3 and B4.
15. Erect bay A to 6th level.
16. Splice second tier columns at C1, C2 and B3.

17. Erect bay J to 6th level.


18.. Erect bay A to roof.

5 -3 4 PCI Design Handbook/Fifth Edition


5.4 References -5. Mast, Robed F., ‘la te ra l Stability of Long Pre­
stressed Concrete-Beams ,” PCI Journal, V I34,
1. Tanner, John, “Architectural Panel Design and
-No.1, January-February 1989.
Production Using Post-Tensioning,"PC/ Jour­
nal, V. 22, No. 3, M a y-Ju rre 1 3I7 . 3. M a s t Robert F., ‘‘Lateral Stability o f Long Pre­
stressed Concrete Beams—Pad 2," PCI Jour­
2. Anderson, A.R., “Lateral Stability of Long Pre­
nal, V. 33, No. 1, January-February 1993.
stressed Concrete Beams,” PCI Journal, V. 16,
No. 3, M ay-June 1971. 7. “PCI Bridge DesignManual,” MNL-133-97, Pre-
cast/Prestressed Concrete Institute, Chicago,
3. “Recommended Practice for Erection of Pre­
IL, 1997.
cast Concrete,” MNL-127-85, Precast/Pre-
stressed Concrete Institute, Vol. 30, No. 6, No­ 8. Mast, Robed F., “Lateral Bending Test to De­
vember-December 1985. struction of a 149 ft Prestressed Concrete I-
Beam,” PCI Journal, V. 39, No. 4, July-August
4. Wire Rope Users Manual, Committee of Wire
1994.
Rope Producers, American Iron and Steel Insti­
tute, Washington, D.C., 1985.

PC) Design Handbook/Fifth Edition 5 -3 5


PCI Design Handbook/Fifth Edition
5 -3 6
CHAPTER 6
DESIGN OF CONNECTIONS
6.1 Notation ...................... ............................. - ........................ ........................ 6 - 2

6.2 General ................................. ................* ...................... . ..................... ............ & -3

^3.3 Loads and Load Factors ........- ........................................................................ 6 - 4

£4 Connection Design Criteria ...................... . ..................................................... 6 -4

6.5 Connection Hardware and Load Transfer Devices................................... 6 -5


6.5.1 Reinforcing Bars .... ...................... 6 -5
6.5.1.1 Reinforcing Bar W elding........................................................ 6-6
6.5.1.2 Reinforcing BarCoupFers...................................................... € -6
6.5.2 Welded Headed Studs ....................................................................... 6-6
6.5.2.1 Tension........................................ 6-8
6.5.2.2 Shear ..................................................................................... 6 -1 0
6.5.2.3 Combined Shear and Tension .......................................... 6 -1 3
6.5.2.4 Plate Thickness ................................................................... 6 -1 3
6.5.3 Deformed Bar A n c h o rs ............................................... 6 -1 5
6.5.4 Bolts and Threaded C onnectors...................................................... 6 -1 5
6.5.4.1 High Strength Threaded Rods .......................................... 6 -1 5
6.5.5 Specialty Inse rts............. ................................................................... 6 -1 6
6.5.6 Structural S te e l.................................................................................. 6 -1 6
6.5.6.1 Welding of Structural Steel.................................................. 6 -1 6
6.5.6.2 Minimization of Cracking in Concrete
Around Welded Connections.............................................. 6 -1 7
6.5.6.3 Weld G roups......................................................................... 6 -1 7
6.5.7 Post-Tensioning S te e l....................................................................... 6 -1 8
6.5.8 Bearing Pads .................................................................................... 6 -1 9
6.5.8.1 Design Recommendations.................................................. 6 -1 9
6.5.9 Connection A ngles............................................................................. 6 -2 0

6.6 Friction................................................................................................................. 6 -2 3

6.7 Column Base P la te s.......................................................................................... 6 -2 3

6.8 Concrete Brackets or Corbels ......................................................................... 6 -2 5

6.9 Structural Steel Haunches................................................................................ 6 -2 7

6.10 Hanger Connections.......................................................................................... 6-31


6.10.1 Cazaly Hanger .................................................................................. 6-31
6.10.2 Loov H a n g e r............. , ...................................................................... 6 -3 3
6.11 Moment C onnections.......................................................................................... 6 -3 6

6.12 Connection of Non-Load Bearing Wall Panels...................................................6 -3 6

6.13 Connection of Load Bearing Panels ............................................................... 6 -3 6


6.13.1 Vertical Joints .................................................................................... 6 -3 6
6.13.1.1 Hinge Connections ............................................................ 6 -3 6
6.13.1.2 Grooved Joint Connections............................................ 6 -3 6
6.13.1.3 Mechanical Connections ................................................ 6 -3 6
6.13.1.4 Keyed Joint C onnections................................................ 6 -3 9
6.13.2 Horizontal Jo in ts................................................................................ 6 -4 0
6.13.3 Typical Details.................................................................................... 6 -4 5

6.14 References ......................................................................................................... 6 -4 5


6.15 Design A id a ....................................................................................................... 6 -4 7

PCI Design Handbook/Fifth Edition


DESIGN OF CONNECTIONS

Notation Cr = symbol for element Chromium


= Cu = symbol for element Oopper
shear s p a ir
= depth of equivalent rectangular com­ Ces — reduction coefficient for edge bis-
pression stress block tance (see Eq. 6.5.4)-

= center of exterior cantilever bearing Cu force vector in a keyed joint (see


to center of Cazaly hanger strap Sect. 6.13.1.4)
d rr depth to centroid of reinforcement

area of bar or stud
= effective bearing area of slab in a d = depth of welds in weld groups (see
horizontal joint Figure 6.15.9)
= db = bar diameter
area of crack interface
area of flexural reinforcement in a dc distance from free edge of concrete
to the centerline of nearest stud mea­
corbel
sured perpendicular to direction of
= area of shear reinforcement parallel
load
to flexural tension reinforcement in a
de distance from center of load to beam
corbel
end
area_of reinforcement required to re­
sist axial tension de distance from edge of member to
— centerline of single stud or of back
area of-concrete failure surface
row of stud group indirection of bad
area of reinforcement —
dh head diameter of stud
= cross-sectional area of Cazaly hang­ =
D durometer (shore A hardness)
er steel strap
_ e eccentricity o f load
area of vertical reinforcement near
end of steel haunch 0i = center of bolt to horizontal reaction
e¥ = eccentricity of vertical load

area of shear-friction reinforcement
6x.ey = eccentricity of load in x,y directions
area of weld
= fbu. = factored bearing stress
loaded area
=
maximum area of the portion of the fl “■ specified compressive strength of
support that is geometrically similar concrete
to and concentric with the loaded fr = resultant stress on weld
area f„ = design compressive strength of wall
= dimension (see specific application) or grout
— width of compression stress block fw — design strength of weld (see Figure
center-to-center distance between and Sect. 6.5.1.1)
the outermost studs in back row o f a f* — combined shear and torsion stress in
group horizontal direction
= width of welds in weld groups (see iy = combined shear and torsion stress in
Figure 6.15.19) vertical direction
= width of hanger connection bar f, = yield strength of reinforcement or
net width of hollow-core slab on headed stud
bearing wall Fexx = classification strength of weld metal
= member width in which a hanger Fs = factored friction force
connection is cast ZF = greatest sum of factored anchor bolt
_ forces on one side of the column
concrete cover
= compressive force = yield strength of structural steel
Fy
= strength factor for hollow-core slabs Fu = tensile strength of bare metal
(see Sect. 6.13.2) g = gage of angle
symbol for element Carbon g = gap between beam end and face of
Cc = adjustment factors for stud groups support element

PCI Design Handbook/Frfth Edition


tl = total depth 4
= grout thickness
= wall thickness- -
effective throat thickness of weld
lr 4
= polar moment o f inertia T = tensiieforce:
4
lxx>V
— moment ofTnertia of weld segm ent y = symbol for element Vanadium
r with respect to its own-axes = nominal strength of- section^ con­
Vc

Ju — force vector in a keyed joint (see trolled by concrete


Sect. 6.13 T.4) Vn -- “ nominal bearing or shear strength of
5 k distance fFom back face of angle to an element
web fillet toe Vr nominal strength provided by rein­
k — grout strength factor (see Sect. forcement
6.13.2) vu = factored shear force
4
-
bearing length Vud factored dead toad force normal to
— development length the friction face
f 4

I 4h development length for a bar with a


standard hook
Vy
W
=
=
headed stud yield strength (shear)
dimension (see specific application)
=
I 4
=
embedment length w = uniform load

I 4 angle leg length W = bearing strip width

I
I '
4

4
=
=
bearing length of exterior cantilever
in hanger connections
projection of corbel
*.y .horizontal and vertical distance re­
spectively, fromc.g. of weld group to
point under consideration
1 4 . = length of weld x,y overall dimensions (width and
Mo = symbol for element Molybdenum length) of a stud group
I
Mn -
symbol for element Manganese Xc distance from centerline of bolt to
1 face of column
Mt = torsional moment
I = base plate projection
Mu = factored moment Xo
1 Xt — distance from centerline of bolt to
n = number of studs in a group
1 centerline of column reinforcement
ns number of studs in back row of a
x,y = distance of weld to the center of
group
1 Ni = symbol for element Nickel
gravity to the weld group

1
1

1
Nu
P
=
=
factored horizontal or axial force
applied load
xi.yi dimensions of flat bottom part of the
truncated pyramid failure-stud
groups
Pc = nominal tensile strength of concrete 4 = plastic section modulus of structural
element steel section
I
1 Ps = nominal tensile strength of steel ele­ a = hanger bar angle (see Figure 6.10.3)
i ment
A design horizontal movement at end
I- =
Pn nominal strength of joint of member
i = applied factored toad ~
PU l coefficient for use with lightweight
1' PU = factored tension toad concrete (see Sect. 5.2.4)
Px,Py = applied force in x, y direction 1*
= shear-friction coefficient
Py = headed stud yield strength (tension) l*e = effective shear-friction coefficient
f Re = reduction factor for toad eccentricity Us = static coefficient of friction
l s -
width of Cazaly hanger strap = strength reduction factor
s = spacing of reinforcing (see specific
application)
6 .2 G e n e ra l
S = shape factor
Design procedures presented in this chapter fol­
S = section modulus
low ACI 3t8-95 and other relevant national model
; S = section modulus of weld groups (see building code requirements except where modified to
Figure 6.15.9) reflect current industry practice (see also Sect. 10.5).
! t =. thickness

PCI Design Handbook/Fifth Edition 6 -3


The design o f connections is one of the most im­ and inserts, such as short studs it may be ap­
portant considerations in the structural design of a propriate to use larger loacf factors.
precast concrete structure. There^may- be several
2. Consequences of Failure: If failure of aconnec-
successful solutions to each connection problem,
tion isiikely to produce catastrophic results, the
end the-design methods and examples included in
this chapter are not the only acceptable ones. Infor­ connection should have-a larger overall-factor
of safety.
mation is included on the design of common precast
concreteoonnections. It isintended for use bythose 3. Sensitivity of Connection to Tolerances: Pro­
with an understanding of engineering mechanics and duction and erection tolerances as well as
structural design, and in no case should -it replace movements due to volume changes and ap­
good engineering judgment. plied loads produce changes in load transfer
The purpose of a connection is to transfer load positions on the connection. Certain connec­
and/or provide stability. Within any one connection, tions, for example corbels (see Sect. 6.8) and
there may be several load transfers; each one must dapped ends (see Sect. 4.6.3), are more sensi­
be designed for adequate strength and appropriately tive to load transfer positions than other con­
detailed. The detailing should provide for a good fit nections, such as base plates. The magnitude
between the selected materials and avoid interfer­ of the additional load factor should be consis­
ence between strand or reinforcing steel and the con­ tent with this sensitivity as well as the load
nection components, such as headed studs or de­ transfer position considered in design. For ex­
formed bar anchors. In the sections that follow, ample, if the most adverse combination of toler­
different methods of transferring load will be ex­ ances is used to establish the load transfer
amined separately, then it will be shown how some of location, an additional load factor may be un­
these are combined in typical connection situations. necessary.
More complete information on some aspects of con­
nection design can be found in Refs. 1 and 2 listed in 4. Requirements of Local Codes: To prevent a
Sect. 6.14. connection from being the weak link in a pre­
cast concrete structure, some codes require
larger load factors to be used in the analysis
6.3 Loads and Load Factors
and design of the connections. When these
With noted exceptions, such as bearing pads, the factors are used, it is not necessary to use addi­
design methods in this chapter are based on strength tional load factors.
design relationships, incorporating the load factors
and strength reduction factors (^-factors) specified
6.4 Connection Design Criteria
in A C I318-95. Local codes may have more stringent
requirements and must be checked. Precast concrete connections must meet a variety
hr addition to gravity, wind and seismic loads, of design and performance criteria, and not all con­
forces resulting from restraint of volume changes as nections are required to meet the same criteria.
well as those required for compatibility of deforma­
tions must be considered. Determination of these These criteria include'.
forces is covered in Chapter 3. For flexural members, 1. Strength: A connection must have the strength
it is recommended that bearing connections be de­ to transfer the forces to which it will be sub­
signed for a minimum horizontal tensile force, acting jected during its lifetime, including those
parallel to the span, of 0.2 times the factored dead caused by volume change restraint and those
load transferred at the bearing unless a smaller value required to maintain stability.
can be justified by using properly designed bearing
pads (see Sect. 6.5.8). 2. Ductility: This is the ability to undergo relatively
To ensure that the overall safety of the connection large inelastic deformations without failure. In
is adequate, the use of an additional load factor in the connections, ductility is achieved by designing
range 1.0 to 1.33 has historically been used by the in­ and detailing so that steel devices yield prior to
dustry. The need and the magnitude of this addition­ weld failure or concrete failure. Concrete typi­
al load factor for aparticular connection must depend cally fails in a brittle manner unless it is con­
on the Engineer’s judgment and consideration of: fined.

1. Mode o f Failure: For failures which are typically 3. Volume Change Accommodation: Restraint of
precipitated by failure of concrete due to insuffi­ creep, shrinkage and temperature change
cient anchorage of connection reinforcement strains can cause large stresses in precast

6 -4 PCI Design Handbook/Fifth Edition


concrete m embersand their supports. The®. 6.5.T Reinforcing Bars
stressesrTmist beconsidered in the design, it is
Reinforcing bars are usually anchored bybonding
usuadyfar better ifthe connection aHowssome
tothe concrete. Very often, thererisinsufficient length-
movement to take place, thus --relieving the
available to anchorthebars by-bondatene, and sup­
stresses.
plemental mechanical anchorage is required. This
4. Durability: W herra connectionis exposecLto can be accomplished by hooks or welded cross-bars
weather, or used in a_corrosive environment, as shown in Figure 6.8.1. Load transferbetween bars
steel elements should be adequately covered maybe achieved by welding, lap splices or mechani­
by concrete, or be painted, epoxy coated or cal couplers. Required development lengths and
galvanized. Stainless steel is sometimes used. standardhook dimensions are given in Chapter 11.
Reinforcing bars may be anchored by embed­
5. Fire Resistance: Connections which could ment in flexible metallic interlocking conduit using
jeopardize the structure’s stability if weakened grout as shown in Figure 6.5.1. The conduit must
by fire should be protected to the same degree have sufficient concrete around it as shown in Figure
as that required for the members that they con­ 6.5 .1 for adequate confinement. This scheme can be
nect. used to transfer tension or compression forces and is
convenient for certain connections, such as column
6 . Constructabifity: The following items should be
to footing and column to column connections. Note
reviewed when designing connections:
that alternate systems are also available including a
a. Standardize products or connections. system which uses a plastic sleeve.
b. Avoid reinforcement and hardware con­ Figure 6.5.1 Anchorage in grouted conduit
gestion.
c. Check material and size availability.
d. Avoid penetration of forms, where pos­
sible.
e. Reduce post-stripping work.
f. Be aware of material sizes and limitations.
g. Consider clearances and tolerances.
h. Avoid non-standard production and erec­
tion tolerances.
i. Use standard hardware items and as few
sizes as possible.
j. Use repetitious details.
k. Plan for the shortest possible hoist hook­
up time.
l. Provide for field adjustment.
m. Provide accessibility.
n. Use connections that are not susceptible
to damage in handling.

6.5 Connection Hardware and Load Transfer


Table 6.5.1 Embedment in grout-filled conduit
Devices

A wide variety of hardware including reinforcing Bar Size Bar embedment


bars, studs, coil inserts, structural steel shapes, length, £ea in.
bolts, threaded rods and other materials are used in 3 12
connections. These devices provide load transfer to 4 12
concrete via anchorage in the concrete by bond or by
a shear cone resistance mechanism. It is preferable 5 12
to have a steel material failure, typically defined by 6 15
yielding, govern the connection strength because
7 21
such failures are more predictable and ductile. Load
transfer should be as direct as possible to reduce the 8 27
complexity and increase the efficiency of the connec­ a. For grout strengths higher than 5000 psi, multiply table
tion. values by J5000/Vc .

PCI Design Handbook/Fifth Edition 6 -5


For No. 8 and smaller uncoated reinforcing bars Figure 6,5.2 shows the most common welds used
(Fy = 60 ksi), where the bar is forced into tbe_grout- with reinforcing hars. FuU penetration groove welds
fiiled flexible conduit,the embedment lengths aregiv- can b e considered to have the same nominal
erv in Table 6,5.1. strength as the bar when matching weld metal is
The following limitations aro recommended: used. The design strength of the-other-weld types
can b e calculated using the values from Figures
1. The minimum concrete side cover over the 6.15.1 and 6.15.2. The total design strength of the
conduit should be 3 in. weld Is fwf wtw

2. Theoonduit should have a minimum thickness where:


of 0.023 in. (24 gage) and there should be a fw = <(> (0.6 F ^ see Table 6.15.1 for values
minimum annular space of % in. around the <(> = 0.75
bar.
Fexx= classification strength of weld metal
3. The grout strength should not be less than the €w = length of weld
specified concrete strength or 5,000- psi.
tw = effective throat thickness of weld
(Figure 6.5.2)
4. I e should not tie less than 12 in.
Figures 6.15.3 through 6.15.5 show welding re­
quired to develop the full strength of reinforcing bars.
The welded cross-bar detail shown in Figure 6.5.2
6.5.1.1 Reinforcing Bar Welding
is not included in ANSI/AWS D1.4. However, it has
Welding is covered byANSI/AWS D1.4-92, “Struc­ been used in numerous structures and verified by
tural Welding Code-Reinforcing Steel,” [3] and by tests [5,6) and, when the diameter of the cross bar is
ANSI/AWS D 1.1-96, “Structural Welding Code- at least the same size as the main bar, the full strength
Steel,” [4] by the American Welding Society. Weld­ of the main bar has been shown to be developed.
ability is defined by AWS as a function of the chemical Reinforcing bars should not be welded within 2
composition of steel as shown in the mill report by the bar diameters of a bend to avoid potential crystalliza­
following formula: tion.
ANSI/AWS D1.4 requires that tack welds be made
using the same preheat and quality control require­
%Mn , %Cu . %Ni ments as permanent welds, and prohibits them un­
C.E. = %C + (Eq.6.5.1)
6 40 20 less authorized by the engineer.
See Sect. 1.3.4.3 for recommendations on weld­
ing galvanized or stainless steel.
where:

C.E. = carbon equivalent 6.5.1.2 Reinforcing Bar Couplers

Proprietary bar coupling devices are available as


Three other elements, Cr, Mo and V usually ap­ an alternative to lap splices or welding. Manufactur­
pear only as trace elements, so they are often not in­ ers of these devices furnish design information and
cluded in the mill report. For reinforcing bars that are test data Refs. 7 and 8 contain more detailed infor­
to be welded, the carbon equivalent should be re­ mation.
quested with the order from the mill.
ANSI/AWS D1.4-92 indicates that most reinforcing 6.5.2 Welded Headed Studs
bars can be welded. However, stringent preheat and The design of welded headed studs is being in­
other quality control measures are required for bars fluenced by new test data that has become available.
with high carbon equivalents. Except for welding A concrete capacity design approach has been pro­
shops with proven quality control procedures that posed [22] based on a limited amount of data appli­
meet ANSI/AWS D1.4-92, it is recommended that car­ cable to headed studs used in the precast concrete
bon equivalents be less than 0.45% for No. 7 and larg­ industry. While there have been no failures or serious
er bars, and 0.55% for No. 6 and smaller bars. problems reported that are attributable to the use of
Most reinforcing bars which meet ASTM A 615, design methods published in previous editions of the
Grade 60, will not meet the above chemistry specifi­ PCI Design Handbook, to be responsive to new data,
cations. A 615, Grade 40 bars may or may not meet modifications in welded headed stud design have
the above specifications. Bars which meet ASTM A been made. Continuing research sponsored by PCI
706 are specially formulated to be weldable. will provide additional information to improve the reli-

6 -6 PCI Design Handbook/Fifth Edition


Figure 6.5.2 Typicai reinforcmg^ bar welds
4 5 " -6 0 “ 4 5 “- 6 0 "

FULL PENETRATION WELDS


NOTE: AS SHOWN FOR # 9 AND LARGER BARS. # 8 AND SMALLER BARS REQUIRE APPROPRIATE BACKING.3

FLARE-BEVEL-GROOVE WELDS

PCI Design Handbook/Fifth Edition 6 -7


ability of headed stud design. The design methods Using the 45° cone area-and-cj> = 0.85, Eq. 6.5.2
used here should be considered_.an. interim step to­ may be written as:
w a rd s final headed stud-design procedure. It is rec­
ommended that this procedure be limited to headed <(>Pc = 10.7£e(Te + d h) l (Eq; 6.5.3}
studs with an embedment not greater than 8 in-.
An important factor in the performance of headed
Note: The stud length is often used-in place cfth e ac-
studs when controlled by concrete capacity Is the
tual embedment length, £e, which is equalfo the stud
confinement of the failure area with reinforcement. In
length minus the thickness of the head: This simplifi­
shear, design capacity is increased with such rein­
cation is generally acceptable except in short studs.
forcement-. In tension, ductility can be provided. It is
In short studs (length < 4 in.), the use of actual
recommended that reinforcement be placed to cross
embedment length is recommended. It should also
failure planes around headed stud anchorages.
be noted that short stud capacities are also sensitive
Welded headed studs are designed to resist direct
to fabrication tolerances. Thus, use of a larger overall
tension, shear or a combination of the two. The de­
factor of safety may be appropriate for short studs.
sign equations given below are applicable to studs
See Sect. 6.3.
which are welded to steel plates or other structural
For a stud located closer to a free edge than the
members, and embedded in unconfined concrete.
embedment length, €e, the design tensile strength
Where feasible, headed stud connections should
given by Eq. 6.5.3, should be reduced by multiplying
be designed and detailed such that the connection
it by Ces.-
failure is precipitated by failure (typically defined as
yielding) oflhe stud material rather than failure of the
surrounding concrete. The in-place strength should C .= |s 1 .0 (Eq. 6.5.4)
be taken as the smaller of the values based on con­
crete and steel.
where de is the distance measured from the stud axis
to the free edge. If a stud is located in the corner of a
6.5.2.1 Tension concrete member, Eq. 6.5.4 should be applied twice,
once for each edge distance. Figure 6.15.6 lists val­
The design tensile strength governed by concrete ues based on Eqs. 6.5.3 and 6.5,4.
failure is [9]: For a group of studs, the concrete failure surface
may be along a truncated pyramid rather than sepa­
<)>PC = $A0(2.8lJ%) (Eq. 6.5.2) rate shear cones, as shown in Figure 6.5.4.
For this case, the design tensile strength is:
where:
<j> = 0.85 4>Pc = m ) V f T ( 2 . 8 A slope + 4Aflat) (Eq. 6 .5 .5 )

A0 = area of the assumed failure surface


which, for a single stud not located near a where:
free edge, is taken to be that of a 45° Aslope = sum of the areas of the sloping sides
truncated cone as shown in Figure 6.5.3. Am = area ° f ^ e flat bottom of the truncated
pyramid
Figure 6.5.3 Shear cone development for
welded headed studs Figure 6.5.4 Truncated pyramid failure

6 -8 PCI Design Handbook/Fifth Edition


Figure 6.5.5 Pull-out surface areas for stud groups inthm sections

For stud groups in thin members, the failure sur­


face may penetrate the thickness of the member as
shown in Figure 6.5.5. This type of failure is likely
when the thickness of the member is less than a cer­
tain minimum thickness, hmin, given in Figure 6.5.6
and listed in Figure 6.15.7B. The pull-out strength
corresponding to h < hmin is then based on area of the
sloping sides only.
Nominal pull-out strengths for both conditions
(i.e., h > hminand h < hmin) for different edge vicinity
cases are given in Figure 6.5.6.
4 - % in. diam. headed studs
The design tensile strength per stud as governed
embedment, = 8 in.
by steel failure is:
slab thickness, h = 10 in.
cj)Py = <pAbfy = 45,OOGAb <Eq. 6.5.6) fc = 4000 psi (normal weight)

Problem:
where: Determine the tension strength of the stud group.

<t> = 0.9 Solution:


1. Check for edge effect:
fy = 50,000 psi
For the given problem (see Rgure 6.5.6)
x = 16 in., y = 8 in., de1 = 4 in.,
Figure 6.15.6 lists the design strength values from
the above equation. des > ^e, d e3 = 6 in., d ^ > €e

Thus the effects of vicinity to two edges apply


Example 6.5.1 Tension Strength of Stud (Case 4 in Figure 6.5.6).
Groups 2. Check for member thickness (see Figure 6.5.6
Given: or Figure 6.15.7B):
A base plate with four headed studs embedded in hmin = (Z + 2 ( e )/2
a corner of a foundation slab.

Handbook/Fifth Edition 6 -9
where t is lesser of x and y prove correlation withtest data obtained under a Pci
hmin = [8 4- 2(8)]/2 = 12 in. (Mote: Same re­ Research Fellowship, the results of which are re-
sult nan be read from Figure-6.T5.7B) portecLin-Refc23.
The design shear strength limited by concrete,
Slnoe4r(= 10 in.) < hmin, failure surface is likely
<pVc,1s calculated as follows:
to penetrate througfcthe slab.

3. Calculate tension strength based on concrete 4>vc = <j>V; CwC,Cc (Eq. 6.5.7)
for the studs as a group: where:
The applicable equation is given in Figure 6.5.6 q>Vc = design shear strength of a
(Case 4, h < hmin): single stud in the back row
(Eq. 6.5.8}.
<j>Pc = <t>2.67xy?r [(x + 4 + 4 iK V + Cw, Ct, Cc = adjustment factors for group
4 + CU) _ Ar] width, member thickness and
where AR = (x + 2 4 - 2h)(y + 2 4 - 2h) vicinity to member corner
effects, respectively (see
substituting given values: Figure 6.5.7). These quanti­
x + 4 + <4i = 16 + 8 + 4 = 28 in. ties are given by Eqs. 6.5.9
through 6.5.11.
y + 4 + de3 = 8 + 8 + 6 = 22 in.
A r = [16 + 2(8) - 2(10)U8 + 2(8) - 2(10)] 4jV£. = 4>12.5d 1
e5 X TfT (Eq. 6.5.8)
= 12(4) = 48 in2
where:
<t>Pc = 0.85(2.67)1.0 7400028(^ qQ~ 48
<j> = 0 .8 5
= 8 8 .4 - 6 .9 = 81.5 kips
de = distance from free edge of concrete
to back row of studs in direction of
Alternatively, from Figure 6.15.7A (Case 4) and load
6.15.7C:
Cw = 1 + 3^ s ns (Eq. 6.5.9)
For 4 = 8 in., x = 16 in., x-i = 20 in.,
y = 8 in. where:
y-i = 14 in., h - 4 = 2 in. b = center-to-center distance between
the outer-most studs in the back row

="711=88-5kips of the group


ns = number of studs in the back row

c- = m 510 (Et|- 6-6-,0)


♦P* = 7-7T I l =6SlklpS
where:
Therefore, c()Pc = c()Pc1 - tyP# = 88.5-6.9 h = thickness of the concrete member
= 81.6 kips
Cc = 0.4 + 0 . 7 < 1.0 (Eq. 6.5.11)
Note: Pull-out strength based on individual
studs should also be checked. where: 6
dc = the distance, measured perpendicu­
4. Check capacity based on steel failure:
lar to the direction of the load, from
From Figure 6.15.6, for% in. diam. stud: free edge of concrete to the center-
line of the nearest stud.
4>Py = 19.9 kips/stud
The design shear strength as governed by steel is:

Total <)>Py = 4(19.9) =- 79.6 kips < 81.5 <j>Vy = c|>0.9fyAbn = 40,500Abn (Eq. 6.5.12)
Tension strength of the group is 79.6 kips
where <|) = 0.9, or, in terms of stud diameter, db:
6.5.2.2 Shear
(|)Vy = (31,800 db2)n (Eq. 6.5.12a)
The design shear strength governed by concrete
failure is based on the concepts and results given in Figure 6.15.8 gives values for cj>Vc (Eq. 6.5.8) and
Refs. 9 and 10. Some modifications were made to im­ <j)Vy (Eq. 6.5.12a).

6 -1 0 PCI Design Handbook/Fifth Edition


F ig u re 6.5.6 Design tensile strength of stud groups
CASE 1: NOTNEAR A FREEEDGE(’)

h > hmin(***> <f)Pc = 4>2.67X JFc (x + 2<e) (y + 2(e)

h < hmin (|)PC = 4>2.67X j T l [(x + 2 f e) (y + 2(e) - A,,]1* " ’

CASE 2: FREE EDGE ON ONE SiDE

h s hmjn <t>Pc = <t>2.67X^; (x + €e + de1) (y + 2€e)

h< 4>pc-= <t»2.67xyr;[(x + + d„)(y + 2<e>- ar ]

CASE 3: FREE EDGES ON 2 OPPOSITE SIDES

h> <|)PC= 4>2.67XJFC(x + de1 + d*} (y + 2£e)

^< ^min <t>Pc = 2.67X.i/?^c[(x + de1 + d^^y + 2( e ) — ARJ

* NEAR A FREE EDGE IMPLIES de < ( e.


** hmin = (z + 2?e)/2, WHERE 2 IS LESSER OF x AND y (SEE Figure 6.15.7B)
*** AR = (x + 2(e - 2h)(y + 2(e - 2h)

PCI Design Handbook/Rfth Edition 6 -1 1


—H -----►
dei
h > h min ' <t)Pc = $2,671 JFC(x + + de1) (y + €.e + de3)

h < trmin <J>PC= <$>2.m JFC[(x + ( e + de1) (y + ( e + de3) - Ar]

CASE 5: FREE EDGES ON 3 SIDES

h > hmin <t>Pc = 4>2.GnJFc (X + de1 + d ej) (y + ( e + de3)

h < hmin <(>PC = $2,671 J F C [(x + de1 + d ^ ) (y + £e + de3) - AR]

CASE 6: FREE EDGES ON 4 SIDES

h 2 hmin <t>Pc = <^>2.671 J r l (x + d e1 + d ^ ) (y + d ^ + d ^ )

h < hmin <t>Pc = $2,671 JFc[(x + d e1 + d g j ) ( y + d e3 + d ^ ) - A R]

6 -1 2 PCI Design Handbook/Fifth Edition


’ From-EqrS.5.9: (width effect)
Cw= 1 + 6/[3.5(5)] = 1v34 < 3 OK

From Eq. 675.10: (threkness effect)


Cj = 1.0

From Eq. 6.5.11: (comer effect)


Cc = 1.0

From Eq; 6.5.7, the design shear strength based on


concrete is:
<t>Vc= (8.4) (1.34) (1.0)(1.0)
= 11.3 kips

From Eq. 6.5.12a, the design shear strength based


ron steel is;
<j)Vy = 31,800(0.5)2(6) /1000
Groups
= 47.7 kips > 11.3
Given: (Note: A value of 8.0 kips per stud is given in Figure
A stud group in a column subject to the shear 6.15.8. For 6 studs, <j>Vy = 48 kips)
force shown.
Thus, design shear strength is governed by concrete
f i = 5000 psi (normal weight) failure.
(j)Vc = 11.3 kips
ROW 1 ROW 2
Vu
6-%"
B p = 4" DIA. 6.5.2.3 Combined Shear and Tension
□ □ STUDS
The design strength of studs under combined ten­
t_____ J sion and shear should satisfy the following interaction
equations:

Concrete: i < 1.0 (Eq. 6.5.13)


<P
SECTION A -A SECTION B -B

where <j) = 0.85


Problem:
Find the design shear strength.

Solution: (Eq. 6.5.14)


The design parameters are:
db = Q.5 in., b = 6 in., de = 5 in.
where tf> = 0.9
n = 6, ns = 3,
Pu and Vu are the factored tension and shear loads.
h > 1.3d.,
No vicinity to corner.

From Eq. 6.5.8:


6.5.2.4 Plate Thickness
(j)Vi = 0.85(12.5) (5)1*75000/1000 = 8.4kips
(Note: Same value is obtained from Figure 6.15.8) Thickness of plates to which studs are attached
should be at least 'A of the diameter of the stud.

PCI Design Handbook/Fifth Edition 6 -1 3


Exam ple 6.5.3 D esign of W e ld e d H eaded (2) Strength based on truncated pyramid
S tu d & fo r C om bined to a d s failure:

Given: b min = (3 + 2(6})/2 = 7.5-in. < 16


A plate with headed studs for attachment o ta steel
bracket to a column as shown in the figure beiow. Use Case 3 in Figure 6.5.6 corre­
sponding Jo h > hmin.
ASSUMED 16"
FAILURE 4>PC = 4 2 . 6 8 1 ^ (x + de1. + de2)(y + 2£e)
4

= 0.85(2.67) (1.0)(,/5000)(6 + 5 + 5) x
1 [3 + 2(6)J/J000
3"
= 38.5 kips
7
or,

Pc = 38.5/0.85 = 45.3 kips


10"
4 Note: Using Figure 6.15.7A—Case 3, for-£e
= 6 in. and = 16 in. <t>Pcvalues of 36 kips
and 41 kips are given for y1 = 2 in. and y-i =
ft = 5000 psi (normal weight), X = 1.0
4 in. respectively. An average value of 38.5
6 - 'A in. diam. studs; Ab/stud = 0.196 in2
kips for y-i = 3 in. is thus obtained.
stud length = 6 in.
(3) Required tension strength, Pu for
dh = 1.0 in.
group of top four studs:
fy = 50,000 psi
With reference to the free-body diagram
Vu = 25 kips, Nu = 4 kips
shown, the required tension strength is
(all load factors included) (see reference included in footnote on this
column size 16 in. x 16 in. page):

Problem:
Determine if the studs are adequate for the con­
nection and design the bracket plate.*

Solution:
Check studs
1. Strength based on concrete:
a. Tension (group of top four studs)
(1) Strength based on individual cones
(Eqs. 6.5.3 and 6.5.4):

<l>pc = 10.7€e(€e + d ^ /f t (de/€ 3)/1 000


= 10.7(6) (6 + 1.0)(/5000) (5/6)/1000 Pu = Vucot0 + N „
= 26.5 kips/stud = 25(0.8) + 4
= 24 kips < 38.5 OK
(Note: The value obtained from Figure
6.15.6 is 25.0 kips. The small difference is b. Shear (all 8 studs)
due to the use of actual embedment length
i.e. stud length minus the stud head thick­ Use de = 120 in.
ness in Figure 6.15.6.)
<t>V; = 0.85(12.5)(120)15(1.0)75000/1000
For four studs: = 988 kips
t
4>pc = 4(26.5) = 106 kips Cw = 1.014
3.5(120)
c, 16 = 0.1025
* Bracket plate may be designed using the plastic strength 1.3(120)
design method. See “Steel Structures-Design and Behavior,”
3rd Edition, 1990, Charles G. Salmon and John E. Johnson,
Harper and Row, New York.
Cc
' °'4+a7(ifo) =°- 429

6-1 4 PCI Design Handbook/Fifth Edition


4)VC= 988(1.014)(0.1025) (0.429) and,
= 44 kips
Vc = 44/0.85 ,= b W % ' t o r 0 -5 £ 5 s 4 -°-

= 51.8 kips-
t for 1.0 < ^ < 2.0
c. Combined "tension and. shear a

Using Eq. 6.5.1 Z


where:

i 4> = 0.9
< 1.0
<f> Fy = yield strength of steel, ksi

substituting the given values:


t = — ^
2 ________
(0.9) (36)(iS ) (A®2 + (8)2 - 2(2))
= 0.98 < 1.0 OK

2. Strength based on steei: = 0.26 in.

a. Tension (group of top four studs) b 8 /3 6


= 0.8, t =
a 0.9(125)
Using Eq. 6.5.6:
t = 0.43 in. > 0.26
<|)Py = 45,000(0.196)/1000
use 7/ie in. thick plate.
= 8.8 kips/stud

For four studs, <|>Py = 4(8.8) = 35.2 kips 6.5.3 Deformed Bar Anchors
Py = 35.2/0.9 = 39 kips
Deformed bar anchors are generally automatically
b. Shear (all 8 studs) welded to steei plates, similar to headed studs. They
are anchored to the concrete by bond, and the devel­
Using Eq. 6.5.12:
opment lengths are the same as for Grade 60 rein­
4>Vy = 40,500(0.196) (8)/1000 forcing bars per ACI 318-95, Sect. 12.2 (see Design
Aid 11.2.8).
= 63.5 kips

Vy = 63.5/0.9 = 70.6 kips 6.5.4 Bolts and Threaded Connectors

In most connections, bolts are shipped loose and


c. Combined tension and shear
threaded into inserts. Embedded inserts are de­
Using Eq. 6.5.14:
signed for concrete strength similar to that for studs.
Occasionally a precast concrete member will be cast
with a threaded connector projecting from the face.
This is usually undesirable because of possible dam­
age during handling.
High strength bolts are used infrequently in pre­
cast concrete connections because it is questionable
as to whether the bolt pretension can be maintained
Thus, studs are adequate for the connection. when tightened against concrete. When used, AISO
Bracket Plate Design recommendations [11,12] should be followed.
Figure 6.15.9 gives allowable working and design
The plastic steel design method used here as­
strengths for bolts in most commonly used threaded
sures yielding of the plate prior to buckling of the
fasteners.
plate. This method may also be used to size gusset
plates of connection angles (Sect. 6.5.9).
The bracket plate thickness, “t” is taken as the 6.5.4.1 High Strength Threaded Rods
greater of (see free-body diagram for nomenclature): Rods with threads and specially designed nuts
and couplers are available with properties similar to
t - ^ ________________________ Grade 60 reinforcing bars and post-tensioning bars.
<]) Fy sin2 0 |/4 e 2 + b2 - 2e j Design information is given in Chapter 11.

PCI Design Handbook/Fifth Edition 6 -1 5


6.5.5 Specialty Inserts Figure 6.5.6 Expansion inserts

Many specialty insertsare usectin the precast con­


crete industry for both permanent connections and
for lifting, handling and bracing conditions. SeveraL
of these inserts have become accepted as a standard
in the industry due to their-innovative nature, ease of
use and unique solution for their particular-applica­
tion, The various threaded coil inserts for lifting and
permanent connections and the slotted insert for lat­
eral tie back connections are just a few of many ex­
amples. Designers should refer to the valuable tech­
nical resources provided by the manufacturers of
such specialty products. Because of the proprietary
nature of such inserts, manufacturers catalogs
should be consulted for capacities and design infor­ In basic terms, flexural strength of a steel section
mation. Most companies will provide test data con­ can be determined as:
firming their published information.
<(>Mn = <j>FyZs

Expansion Inserts <j>Vn = <j>(0.6Fy)wh


All expansion inserts are proprietary, and design where:
values should be taken from manufacturers’ cata­
(j) = 0.9
logs. The Concrete Capacity Design Method dis­
cussed in Ref. 1 provides guidance for calculating w, h= steel section dimensions
these design values. Edge distances for expansion Zg =plastic section modulus
inserts are more critical than for cast-in inserts. Ex­
panding the insert in the direction of the edge should The plastic section modulus can be calculated us­
be avoided (Figure 6.5.8). ing Figure 6.15.12 or may be obtained from the AISC
The performance of expansion inserts when sub­ LRFD Manual (12]. For thin plates bent about their
jected to stress reversal, vibrations or earthquake major axis, buckling provisions may govern the de­
loading is not sufficiently known. Their use for these sign.
load conditions should be carefully considered by the
designer.
6.5.6.1 Welding of Structural Steel
Anchorage strength depends entirely on the later­
al force (wedge action) on the concrete. Therefore, it
is advisable to limit their use to connections with more Nearly all structural steel used in precast concrete
shear than tension applied to them. connections is ASTM A 36 steel. Thus, it is readily
weldable with standard equipment [4].
For corrosion resistance, exposed components of
connections are sometimes hot-dip galvanized.
Welding of hot-dip galvanized steel requires special
care-(2,6), such as thorough removal of galvanizing
6.5.6 Structural Steel
material or following qualified welding procedures.
Structural steel plates, angles, wide flange beams, Stainless steel is an alternative for exposed connec­
channels, tubes, etc., are often used in connections tion parts where corrosion protection is important.
(see Sect. 6.9). When designed using factored loads, Stainless steel plates are weldable to other stainless
the AISC LRFD Manual [12} is the appropriate design steel or to low carbon steel. The general procedure
reference. For typical steel sections used in connec­ for welding low carbon steels should be followed, tak­
tions, plastic section properties and yield strengths ing into account the stainless steel characteristics
with appropriate strength reduction factors are used. that differ, such as higher thermal expansion and low­
An ambiguity exists where AISC load factors are dif­ er thermal conductivity. Ref. 6 contains information
ferent from those used by ACI. While it may be ap­ on weldability o f stainless steel. Sect. 1.3.4.3 of this
propriate to carry two sets of load factors through a Handbook also contains a discussion of welding of
design, it would also be very cumbersome. It is thus stainless steel and galvanizing of A36 steel.
suggested that ACI load factors be used for connec­ The design strength of welds for use with factored
tion design and the AISC provisions be used to deter­ loads can be determined from the provisions of the
mine the usable strength to be provided by the steel. AISC LRFD Manual [12]. The most commonly used

6 -1 6 PCI Design Handbook/Fifth Edition


welds in connections-are full penetration welds-or fil­ Figure 6.5.9 Typical eccentric loadings and
let welds. Full penetration strength is typically taken weld groups
as the sire ngttrotthe base metal. A "matching” weld"
metal-per AWS D1.1 must-be used. Full penetration
wefdsloaded in shear may also=be governed by the
weld metal where the design weld stress is to be limit­
ed to <(>(0.-6 Feo) where <j> = 0.8. For filletwelds, as
most commonly used in connections, the design
strength maybe limited by either the weld strength or
the base metal strength. Theweld design stress is
limited to <(>(0.6 F ^ ) where <|> = 0.75. The base metal
design stress is limited to <(>(0.6 Fu) where <(> = 0.75
and Fu is the tensile strength of the base metal.
Partial penetration groove welds have various de­
sign strength limits. The most typical application of
this weld is in Jap splices of reinforcing bars as dis­
cussed in Sect. 6.5.1.1. When loaded in shear paral­ fr = resultant stress on the weld
lel to the weld axis, the limiting design stress is <j>(0.6
Fexx) where <(> = 0.75. Figure 6.15.1 provides design = v U )2 + (fy)2
strengths for fillet welds and partial penetration
groove welds loaded in shear. Figure 6.15.2 gives Px = applied force in x direction
strengths of 45° fillet welds.
6.5.6.2 Minimization of Cracking in Concrete Py = applied force in y direction
Around Welded Connections
y = vertical distance from c.g. of weld
When welding is performed on components that
group to point under investigation
are embedded in concrete, thermal expansion and
distortion of the steel may destroy bond between the x = horizontal distance from c.g. of weld
steel and concrete or induce cracking or spalling in group to point under investigation
the surrounding concrete. ip = polar moment of inertia
The extent of cracking and distortion is dependent
= lx + ly = l b + ZAwy2 + 2lyy + ZA*J<2
on the amount of heat generated during welding and
the stiffness of the steel member. Heat may be re­
duced by: (1) use of low-heat welding rods of small Mt = torsional moment = Pxey + Pyex
size; (2) use of intermittent rather than continuous
welds; or (3) using smaller welds in multiple passes. tw = effective throat thickness of weld
Distortion can be minimized by using thicker steel
sections. Providing a space around the metal on the Aw = area of weld = weld length x t*
surface with sealing foam or weatherstripping may
also reduce potential for damage.
Ixx.lyy = moment of inertia of weld segment with
6.5.6.3 Weld Groups respect to its own axes
Weld groups are more efficient than linear welds in
For computing nominal stresses the locations of
resisting bending moments and torsion created by
the lines of weld are defined by edges along which
eccentric loads. Examples of this type of loading are
the fillets are placed, rather than to the center of the
shown in Figure 6.5.9. Design procedure is illustrated
effective throat. This makes little difference, since the
by Figure 6.5.10,
throat dimension is usually small. By treating the
where: welds as lines with t* = 1, the physical properties of
fx = combined shear and torsion stress in weld groups are simplified. The most commonly oc­
horizontal direction curring weld groups are listed in Figure 6.15.19.
The equations given above and in Figure 6.15.19
f _ px , M>y are for elastic section properties, which is inconsis­
Tx “ a“ w I
*p tent, but conservative, when used with factored loads
and design strength of weld material. When it is de­
fy = combined shear and torsion stress in
sirable to take maximum advantage of weld groups,
vertical direction
the AISC LRFD Manual [12] should be used.

PCI Design Handbook/Frfth Edition 6 -1 7


Figure €.5.10 Eccentric bracket connection Find c.g. of weld group:

x
2(2K1) + 14(0)
= 0.22 in.
14 + 2(2)
by symmetry, y = 7 in.

Aw= [2(2) + 14]tw = 18tw

fp = 2[tw(2)3/12 + 2tw(0.78)2 + 2(tw)3/ 12


+ 2(tw)(72)3 + tw(14>3/12 + 14^)3/12
+ 14(tw)(0.22)2
= 429.1tw + 1.50(tw)3

Since second term is smah, it may be neglected.


Alternatively, using Figure 6.15.19, case 5:
(weld group treated as aline; t* = 1)
b = 2 in.
d = 1 4 in.
x = b2/(2b + d) = 4(4 + 14) = 0.22 in.

Example 6.5.4 Design of a Weld Group , _ 8b3 + 6bd2 + d 3 b4


Given: p 12 2b + d
Comer angle connection as shown 8(2)3 + 6(2)(14)2 + 143 24
12 2 (2 )+ 14
= 429.1 in3

ex = 1 + 4 - 0.22 = 4.78 in.

Mt = Pyex = 49.8(4.78) = 238 kip-in

x = 2 - 0 . 2 2 = 1.78
49.8 , 238(1.78)
y 18 429.1

= 2.77 + 0.99 = 3.76 kips/in.

fx = ° + ^ j = 3.88 kips/in.

fr = / ( 3.88)2 + (3.76)2

Angle size = 4 x 4 x Vz x 1'-2" = 5.40 kips/in.


Fy = 36 ksi, E70 electrodes
From Table 6.15.2, use Vi in. fillet weld (E70 elec­
Applied factored load = 38.3 kips
trode)
Capacity = 5.57 kips/in. > 5.40
Problem:
Determine required weld size. 6.5.7 Post-Tensioning Steel
Post-tensioning is often used in the connections
Solution: subjected to high tensile forces, such as those in mo­
Apply additional factor of 1.3 recognizing sensitivi­ ment-resisting frames. The post-tensioning is done
ty of the connection. using either 7-wire strand (ASTM A 416) or bars
(ASTM A 722). The tensile strength of strand is either
250.000 or 270,000 psi, while for bars, it ranges from
Vu = Py = 1.3(38.3) = 49.8 kips
150.000 to 160,000 psi.

6 -T 8 PCI Design Handbook/Fiflh Edition


In accounting tor the effect of prestressing on con­ in cotorand are reinforced with closely spaced,
nections-due to post-tensioning, a reliable measure- horizontal layers of fabric, bondecfcin the elasto­
mentof the prestressing force is necessary. Typical­ mer. The horizontal reinforcement layers are
ly, 15 to 20 ft length of strand o r bar is desirable for easily observed a tlh e edge of the pad. Sect.
this purpose, although shorter lengths can be used T8t10.2 of-the AASHTO Standards Specifica­
where anchor set is well defined and considered in tion^: for Bridges and Military Specification
prestress loss calculations. Some designers dis­ MIL-C-882D discuss this material.
count the effect of prestressing when short tendons
are used and consider only the ductility and the ten­ 4. Chloroprene pads laminated with alternate lay­
sile strength aspects of post-tensioning steel. ers of bonded steel or fiberglass are often used
in bridges, but seldom in building construction.
The above mentioned AASHTO Specifications
6.5.8 Bearing Pads
cover these pads.
Bearing pads are used to distribute concentrated
loads and reactions over the bearing area and to al­ 5. A multimonomer plastic bearing strip is
low limited horizontal and rotational movements to manufactured expressly for bearing purposes.
provide stress relief. Their use has proven beneficial It is a commonly used material for the bearing
and often may be necessary for satisfactory perfor­ support of hollow-core slabs, and is highly suit­
mance of preeast concrete structures. able for this application. It is also often used for
Several materials are commonly used for bearing bearing of architectural precast concrete clad­
pads: ding panels.
1. AASHTO-grade chloroprene pads are made
with 100 % chloroprene (neoprene) as the only 6. Tempered hardboard strips are also used with
elastomer and conform to the requirements of hollow-core slabs. These pads should be used
the AASHTO Standard Specifications for High­ with caution under moist conditions. In addi­
way Bridges (1996), Sect. 18. Inert fillers are tion to progressive deterioration of the pad,
used with the chloroprene and the resulting staining of the precast concrete unit may oc­
pad is black in color and of a smooth uniform cur.
texture. While allowable compressive stresses
are somewhat lower than other pad types, 7. TFE (trade name Teflon) coated materials are
these pads allow the greatest freedom in move­ often used in bearing areas when large hori­
ment at the bearing. Note: chloroprene pads zontal movements are anticipated, for example
which do not meet the AASHTO Specifications at “slip” joints or expansion joints. The TFE is
are not recommended for use in precast con­ normally reinforced by bonding to an appropri­
crete structures. ate backing material, such as steel. Figure
6.5.11 shows a typical bearing detail using
2. Pads reinforced with randomly oriented fibers TFE, and Figure 6.5.12 shows the range of fric­
have been used successfully for many years. tion coefficients that may be used for design.
These pads are usually black, and the short re­ Typical allowable stress is about 1000 psi for
inforcing fibers are clearly visible. Vertical load virgin TFE and up to 2000 psi for filled material
capacity is increased by the reinforcement, but with reinforcing agents such as glass fibers.
capability of rotations and horizontal move­
ment is somewhat less than chloroprene pads. 6.5.8.1 Design Recommendations
Some random oriented fiber pads possess dif­
ferent properties in different directions in the Bearing pads provide stress relief due to a com­
plane of the pad. Therefore, unless proper bination of slippage and pad deformation. In elasto­
planning and care is used in their installation, it meric bearing pads (1 through 4 above), research
may be prudent to specify those pads that have [13] has shown that slippage is the more significant
been tested to exhibit similar properties in dif­ factor. This research has also shown that the ratio of
ferent directions. There are no national stan­ shear to compressive stress on the pad reduces sig­
dard specifications for this material. Manufac­ nificantly under slow cyclic movements, such as
turers have developed appropriate design and those produced by temperature variations. Following
performance documentation. are recommendations which, along with Figures
6.5.13 and 6.5.14, can be used to select bearing
3. Cotton duck fabric reinforced pads are gener­ pads.
ally used where a higher compressive strength
is desired. These pads are often yellow-orange 1. Use unfactored service loads for design.

PCI Design Handbook/Frfth Edition 6 -1 9


Figure 6.5.11 Typicat TFE bearing pad detaH Figure 6.5.12 TFE friction coefficients

o
-p 0.30
- cc
U- £ 2 0
tL

£■- 0:10
2. o-oe -

£ 0-04
LL

g 0.02
' o
0 0.01
0 20 50 100 200 500 1000 2000
1CO ’
PRESSURE, psi
2. At the suggested maximum uniform compres­
sive stress, instantaneous vertical strains of 10
to 20% can be expected. This number may
double if the bearing surfaces are not parallel.
In addition, the time-dependent creep wiU typi­ 6.5.9 Connection Angles
cally increase the instantaneous strains by 25 Connection angles used tosupport precast mem­
to 100%, depending on the magnitude of sus­ bers can be designed by principles of mechanics as
tained dead load. shown in Figure 6.5.15. In addition to the applied ver­
tical and horizontal loads, the design should include
3. For stability of the pad, the length and width of all loads induced by restraint of relative movement
unreinforced pads should be at least five times between the precast member and the supporting
the thickness. member.
The minimum thickness of non-gusseted angles
4. A minimum thickness of % in. is recommended
loaded in shear as shown in Figure 6.5.16 can be de­
for all precast members except slabs.
termined by:
5. Figure 6.5.14 may be used to estimate shear 14Vuev
resistance of chloroprene, random fiber rein­ t = (Eq. 6.5.15)
c>Fybn
forced and cotton duck pads.

where:
6. The portion of pad outside of the covered bear­
ing surface as well as the portion which is not 4> = 0 .9 0
under load because of rotation of member bn = (length of the angle)-(bolt hole
should be ignored in calculating shape factors, diam eter)-1/i6 in.
pad stresses, stability and movements. Design ev is the specified e^+V2 in.

7. Shape factors, S, for unreinforced pads should


Note: For welded angles, Figure 6.5.15 (c), design
be greater than 2 when used under tee stems,
ev in Eq. 6.5.16 may betaken equal to actual e* minus
and greater than 3 under beams.
k, where k is the distance from the back face of angle
to web toe of fillet.
8. The sustained dead load compressive stress The tension on the bolt can be calculated by:
on unreinforced chloroprene pads should be
limited to the range of 300 to 500 psi. Pu = Vu§* (Eq. 6.5.16)
9. The volume change strains shown in Sect.
3.3.1 may be significantly reduced when calcu­
For angles loaded axially, Figure 6.5.17, the mini­
lating horizontal movement, A, because of
mumthickness of non-gusseted angles can be calcu­
compensating creep and slip in the bearing
lated by:
pad.
10. Certain fiber reinforced bearing pads are rein­
forced in one direction only; for these types of 4Nug
t = (Eq. 6.5.17)
pads orientation in the field may be critical. (j)Fybn

6 - 2 0 PCI Design Handbook/Fifth Edition


figure 6.5.13 Single layer bearing pads free to slip

SHAPE-fACTOR - S - 2 ((f + 6 j ,

// D = DUROMETER (SHORE A HARDNESS)

.^ b A = DESIGN HORIZONTAL MOVEMENT AT END OF MEMBER

ALLOWABLE8 RECOMMENDED RECOMMENDED


PAD SHORE A
COMPRESSIVE MINIMUM MAXIMUM
MATERIAL HARDNESS D
STRESS (PSI) THICKNESS6 ROTATION6

UNREINFORCED
CHLOROPRENE OR 4DS < 800 0.31
50 THROUGH 70 1.4 A
RUBBER b or w

RANDOM FIBER 0.3t


REINFORCED 1000 + 100S < 1500 80 ± 10 1.4 A
ELASTOMERIC b or w

s 2500 (UNIFORM)
COTTON DUCK FABRIC <4000 0.12t
REINFORCED 90 ± 10 2.0 A
(NONUNIFORM) borw

a. Allowable compressive stresses may be increased based on test data supplied by the bearing pad manufacturer.
b. The values in the table are based on sliding criteria. If sliding is not critical or testing indicates more advantageous conditions, thinner
pads may be used. The minimum thickness and maximum rotation values for the cotton duck pad account for the effects of creep.
Figure 6.5.14 Shear resistance of bearing pads

z
ui
3

u.
a
2z 3
(0
o
N
E
o
z !
o
H 8u.
U1 O
O
z CO
a
2
V)
to
111
E

COMPRESSIVE STRESS, psi


a. Average values based on tests at 70% shear and slippage strain.

PCI Design Handbook/Fifth Edition 6 -2 1


Figure 6.5.15 Design parameters for connection angtes

Pn GUSSET

F T ~ p“ ^
J
£
<t- 9 Vy

Pu

(A) BOLTED WITHOUT GUSSET (B> BOLTED WITH GUSSET

Table 6.5.2 Minimum edge distance for Figure 6.5.16 Vertical load on angle
punched, reamed or drilled holes,
measured from center of hole, in.a

Bolt At At rolled edges of


diameter sheared plates, shapes or bars
(in.) edges or gas-cut edgesb
V6 7A %
V/e 7A

% VA 1
% 1'/2C VA

1 13/4C VA

VA 2Vi m

a. When oversized or slotted holes are used, edge distances


should be increased to provide the same distance from
edge of hole to free edge as given by the tabulated edge
distances.
b. All edge distances in this column may be reduced Vfe in.
when the hole is at a point where stress does not exceed
25% of the maximum allowable stress in the element.
c. These may be 1Vi in. at the ends of beam connection
angles.

Figure 6.5.17 Horizontal load on angle


and the tension on the bolt can be calculated by:
SEE
Pu = N u( l (Eq. 6.5.18)

where:

<t> = 0.90
g = gage of the angle (see Figure 6.5.15)

The minimum edge distance for bolt holes is


shown in Table 6.5.2.
Tables 6.15.13 and 6.15.14 may be used for the
design of connection angles.
For connections made by welding instead of bolt­
ing, the welds should be designed in accordance
with Sect. 6.5.6.1.

6 -2 2 PCI Design Handbook/Fifth Edition


g5 Friction Tabte6.6.1 Upper lim its of static coefficients
Tine static coefficients oHriction shown in Table o f friction o f d ry materials3
are conservative values for use in determining
the upper limit of volume change forces in members Material Us
wherein the connections would allow insufficient Elastomeric to steei er concrete Figure 6.5.14
movement for stress relief. Thus, th e maximum force- Concrete to Concrete 08
resulting from the frictional restraint of axial move­ Concrete to steel 0.4
ments can be determined by: Steel to steel (not rusted) 0.25
Fs = HsVUtf (Eq. 6.6.1) TFE to stainless steel Figure 6.5.12
where: Hardboard to concrete^ 0.5
Multimonomer plastic (non-skid) 1.2
Fs = factored friction force
to concrete
ns = static coefficient of friction as given in Multimonomer plastic (smooth) 0.4
Table 6.6.1 to concrete
Vud= factored dead Joad force normal to the a. Reduce by 25% for wet conditions.
friction face
Under loads which occur at service, the base plate
Friction may be depended upon to resist tempo­ thickness may be controlled by bearing on the con­
rary construction loads as approved by the Engineer. crete or grout. In this case, the base plate thickness is
In such cases, the coefficients of friction shown in determined by:
Table 6.6.1 should be divided by 5.
Friction may also be depended upon to contribute
to the resistance to design loads in specific situations
where analysis and/or testing justifies its use. One where:
such situation is the horizontal joints of precast wall <\> = 0 .9
panels which is illustrated in Ref. 2. Xq = dimension as shown in Figure 6.7.1, in.
6.7 Colum n Base Plates fbu = bearing stress on concrete or grout
Column bases must be designed for both erection under factored loads < <j>(0.85)fc,
loads and loads which occur in service, the former where: <j) = 0.7
often being more critical. Two commonly used base
Table 6.15.15 may be used for base plate design.
plate details are shown in Figure 6.7.1 although many
other details are also used. Nominal base plate shearing stresses should not ex­
If in the analysis for erection loads or temporary ceed 0.9(0.6 Fy).
construction loads, before grout is placed under the The anchor bolt diameter is determined by the ten­
plate, all the anchor bolts are in compression, the sion or compression on the stress area of the
base plate thickness required to satisfy bending is threaded portion of the bolt. Anchor bolts may be
determined from: ASTM A 307 bolts or, more frequently, threaded rods
of ASTM A 36 steel. The requirements for structural
/ (2F)4xe integrity (Sect. 3.10) must also be satisfied.
t = (Eq. 6.7.1)
<j)bFy In most cases, both base plate and anchor bolt
where: stresses can be significantly reduced by using prop­
0.90 erly placed shims during erection.
When the bolts are near a free edge, as in a pier or
Xc, b = dim. as shown in Figure 6.7.1, in.
wall, the buckling of the bolts before grouting may be
Fy = yield strength of the base plate, psi a consideration. Confinement reinforcement, as
IF = greatest sum of anchor bolt factored shown in Figure 6.7.1, should be provided in such
forces on one side of the column, lb cases. A minimum of four No. 3 ties at about 3 in. cen­
Ifthe analysis indicates the anchor bolts on one or ters is recommended for confinement.
both sides of the column are in tension, the base The in-place tension strength of the bolt should be
plate thickness is determined by: taken as the lesser of the strengths calculated based
on concrete failure and steel failure (typically yield).
(SF)4x, The calculation of concrete based strength will de­
t = (Eq. 6.7.2) pend upon the type of anchor bolt used. For hooked
4>bFy
where: or “L” shaped anchor bolts, the strength should be
determined by adding the bond resistance of the bolt
<j) = 0.9
shank and the bearing resistance of the bolt head or
Xj = dimension as shown in Figure 6.7.1, in. the hook.

PCI Design Handbook/Fifth Edition 6 -2 3


Figure 6.7.1 Cohtmnijase connections

6 -2 4 PCI Design Handbook/Fifth Edition


If necessary, the bearing, area-of the b olt head can Figure 6.8.1 Design of concrete corbels
jje-jncreased by welding a washer or steel :plate.
Nominal bond stress orr smooth anchor bolts should
not exceed 250 psi. The confined bearing, stress on
the hook or t >olt head- should not exceed
<f)(0.85fc) yA2/A i in accordance with A d 318-95,
Sect. 10.17. Typically, v/A2/A 1will be largerlhan 2.0.
In such cases, the limiting value for-design bearing
strength of 0.7(0.85)(f£) 2.0 = 1.2 (f£) may be used.
The bottom of the bolt should be a minimum of 4
in. above the bottom of the footing, and also above
the footing reinforcement.

6.8 Concrete Brackets or Corbels

ACI 318-95 prescribes the design method for cor­


bels, based on Refs. H a n d 1 5 and Sect. 4.6.6. The
equations in this section follow those recommenda­
tions, and are subject to the following limitations {see
Figures 6.8.1 and 6.8.2):
1. a/d < 1
2. Nu s Vu
3. <|> = 0.85 for all calculations
4. Anchorage at the front face must be provided
by welding or other positive means. 1. As bar should be extended to the tar face of
the column. Provide fully developed As bars
5. Concentrated toads on continuous corbels by selecting the number of bars so that the
may be distributed as for beam ledges, bar size remains small enough to ensure that
the length,fdh is provided (DESIGN AID 11.2.8).
Sect. 4.5.
2. Vertical length of a standard 90° hook is 12db
The area of primary tension reinforcement, As, is (DESIGN AID 11.2.8). The horizontal length of
As bar, l dh, must be provided in order to use a
the greater of A f + A n as calculated below, o r % A y f + standard 90° hook.
A n as calculated in Sect. 4 . 3 . 6 ;
3. It may be assumed that the As bar is
developed at the outside face of the welded
anchor bar when the Ah bars are outside that point.
A Vua + Nu(h - d)
(Eq. 6.8.1)
* = — Sd~—

A - Nu (Eq. 6.8.2)
Mn - T T
4>fy
The shear strength of a corbel is limited by the
For convenience, the equations can be rewritten maximum values given in Table 4.3.1.
so that As shall be the greater of Eq. 6.8.3 and 6.8.4:

As — (Eq. 6.8.3)
Example 6.8.1 Reinforced Concrete Corbel
tfvL Vu(d ) + Nu(dJ
Given:
1 2V, A concrete corbel similar to that shown in
As = -jV Nu (Eq. 6.8.4)
<t>fy 3(i, Figure 6.8.1
Vu = 80 kips (includes all toad factors)
As, min- 0.04(fc/fy)bd (Eq. 6.8.5)
Nu = 15 kips (includes all toad factors)

Where the corbel depth is larger than required by de­ fy = Grade 60 (weldable)
sign, a reduced d may be used provided the same d fc = 5000 psi (normal weight)
is also used in Eq. 6.8.3 and 6.8.4. Bearing p a d - 12 in. x 6 in.
Ah > 0 .5 (A S- A n) (Eq. 6.8.6) b = 14 in.
Ah should be distributed within the upper % d. €p = 8 in.

PCI Design Handbook/Fifth Edition 6 -2 5


Problem: By Eq. 6.8.4:
Find corbel depth and reinforcement. 1 [2V„ , m 1— 1 h w , lri
Solution:
^fy 3fie Uu] 835(60) 3(3.4) 15
Try h = 14 in. = 0.60 in2 < 1.04
d = 1 3 in.
a = %£p = 6 in. By Eq. 6.8.5:
From Table 4.3.1: As, min— 0.04bd(fc/fy) = 0.04(14)(13)(5/60)
max Vn = 1000 k2 Acr = 0.61 in2 < 1.04
= 1000(1 )2(14>(14)71000 Provide 2 -# 7 bars = 1.20 in2
= 196 kips The As reinforcement could also be estimated
max Vu= 0.35(196) = 166.6 kips > 80.0 OK from Table 6.15.16:
By Eq. 6.8.3: For:
b = 14 in.
€p = 8 in.
h = 1 4 in.

The corbel would have a strength of about 65 kips


with 2 -# 6 bars and 89 kips with 2 -# 7 bars. Use
= 1.04 in2 2 -# 7 bars for Vu = 80 kips.
By Eq. 4.3.16: By Eq. 6.8.6:
1000)0% 1000(1) (14) (14) (1.4) 15
Ah = 0.5(AS - An) = 0.5 1.04 -
^ ~ Vu " 80,000 0.85(60)
= 0.37 in2
= 3.43 > 3.4, Use 3.4 Provide 2 -# 3 closed ties = 0.44 in2

Figure 6.8.2 Corbel force diagrams and typical reinforcement-wall panels

FREE BODY REINFORCEMENT

6 -2 6 PCI Design Handbook/Fifth Edition


&r9 StructuralSteel Haunches
4. The critical section for bending of the steel
Structural steel shapes, such as wide flange member is-located a distance Vu/(0.85f4b) in­
beams: double channels, tubes or vertical plates, ward from: the face of the column.
often serve as haunches or brackets as Illustrated in
Figure 6.9.1. The concrete--based capacity of these If the steel section projects from both sides, as irr
members can be calculated by statics, using-the as­ Figure 6.9.2(A), the eccentricity factor, e /4 in Eq.
sumptions shown in Figures 6.9.2 and 6.9.3 [16]. 6.9.1 should be calculated from the total unbalanced
live load. Conservatively, e/€e may betaken equal to
The nominal strength of the section is: 0.5.
0.85% b le The design strength of the steel section can be de­
(Eq. 6.9.1)
Vc 1 + 3.6 e / 4 termined by:

where: Flexural design strength:


(j)ZSFy
Vc = nominal strength of the section con­ 4)Vn = (Eq. 6.9.3)
trolled by concrete, lb eL+ 0.5 Vu/(0.85f; b)

e = a + €e/2, in.
Shear design strength:
a = shear span, in.
4 = embedment length, in. 4>Vn = <j>(0.6Fyht) (Eq. 6.9.4)

b = effective width of the compression


where:
block, in.
Zg = plastic section modulus of the steel
For the additional contribution of reinforcement section
welded to the embedded shape, and properly devel­ (see Table 6.15.12)
oped in the concrete, and with = As: Fy = yield strength of the steel
h,t = depth and thickness of steel web,
2ASfy respectively
Vr = (Eq. 6.9.2)
6 e /4
1+ <j) = 0 .9 0
4 .8 S /4 -1
Horizontal forces, Nu, are resisted by bond on the
where:
perimeter of the section. If the bond stress resulting
fy = yield strength of reinforcement from factored loads exceeds 250 psi, headed studs
or reinforcing bars should be welded to the em­
Then Vn = (Vc + Vr); and Vu < <J>Vn, where bedded steel section.
$ = 0.85.
Other notation for Eqs. 6.9.1 and 6.9.2 are shown
in Figure 6.9.3.
Example 6.9.1 Design of Structural Steel
The following assumptions and limitations are rec­ Haunch
ommended:
Given:
1. In a column with closely spaced ties (spacing The structural steel haunch shown.
< 3 in.) above and below the haunch, the ef­
fective width, b, can be assumed as the width
of the confined region, i.e., outside to outside of
ties, or 2.5 times the width of the steel section,
whichever is less.

2. Thin-walled members, such as the tube shown


in Figure 6.9.3, may require filling with concrete
to prevent local buckling.

3. When the supplemental reinforcement, Ag and


A;, is anchored both above and below the
members, as in Figure 6.9.3, it can be counted
twice.

PCI Design Handbook/Fifth Edition 6 -2 7


fc = 5000 psi Alternative- using Tables 6.15.17 and 6.15.18:

fy (-reinforcement) = 60,000 psi (weldable) For


Fy (structural steel)' = 46,000 psi b = 8 in.
Problem: a = 4 in*
Find the design-strength. 4 = 10 in.
SoMfan: Read <f>Ve = 68 kips
Effective width, b = confined width (8 in.) or
For As= 2 -# 4, anchored above and below
b =2.5w = 2.5(4) = 104n.
Use b =8 in. Read Vr = 28 kips

e =4 + 10/2 = 9 in. <j>Vn = <t»Vc + <}>Vr = 68 + 0.85(28)


= 92.0 kips
_ 0.85fe b le 0.85(5K8)(10)
c 1 + 3.6e/ 4 1 + 3.6(9)/(10) Steel section shear capacity:
= 80.2 kips 4>Vn = 4>(0.6 Fyht> = 0.9(0.6)(46)(6)(2)(0.5)
Since the As bars are anchored above and below, = 149 kips
they can be counted twice.
Steel section flexure capacity:
As = 2 - # 4 = 2(2)(0.2) = 0.80 in*
From AISC LRFD Manual [12]:
V = 2Asfy _ 2(0.80)(60)
Zs = 15.4
r ' 6 e /4 6(9)/10
Assume Vu = 85 kips,
4 .8 s / € ,- l 4.8(7)/(10) - 1
= 4)ZsFy _ 0,9(15.4)(46)
= 29.2 kips 9 n a + 0.5 Vu/0.85fc b 4 + 1.25
<J>V„ = 0.85(80.2 + 29.2) = 93.0 kips
= 121.4 kips

Figure 6.9.1 Structural steel haunches

6 -2 8 PCI Design Handbook/Fifth Edition


Figure 6v9.2 Stress-stranr relationships

W2

4 r
O'

Xb k ^

STRAINS 0.003
M” I W 1
J 0.003
£h r>s.
T ^ n j^ = o .°°3
i

Mb
, . Me/2 Mf

STRESSES 0.85ft 0.85fc 1 afi |J[|


I
T 0.85f; t . Ill 0.85ft

T
(A) PURE SHEAR (B) PURE MOMENT (C) GENERAL LOADING

Figure 6.9.3 Assumptions and notation-steel haunch design

Vu
0.85f'cb
CRITICAL SECTION
FOR MOMENT ON
EMBEDDED SECTION

Ag

PCI Design Handbook/Frfth Edition 6 -2 9


Figure 6rl O.t Hanger Connections

6 -3 0 PCI Design Handbook/Fifth Edition


6.10 Hanger Connections
4. The conservative and simplifying assumption
Hangers are similar to dapped ends, excepHhat
that strap weld forces are-concentrated a tih e
the-extended or bearing end is steel instead of con­
strap centerline is implicit in the 0.5s factor in
crete. They_are used wbenJt is desired to keep the
Eq. 6.10.2.
structural depth very shallow. ^Examples are shown in
Rgure 6:10.1. These connections typically have short 5. Thebearing pressure creating the interior reac­
bearings and may be particularly sensitive to toler­ tion may be calculated as in Sect. 4.6.1. Con­
ances and volume change movements. The need for servatively, if the width of the member in which
accuracy in dimensioning and installation must be the hanger is cast = bTl then:
emphasized.
f*. = 0 . 8 5 J b j b < 1.2fe (Eq. 6.10.3)

6.10.1 Cazaly Hanger [17] where:


The Cazaly hanger has three basic components, <f> = 0 .7
Figure 6.10.2(A). Design assumptions are as follows,
Figure 6.10.2(B): The bearing length, 4 , is then given by:
V /3
1. The cantilevered bar is usually proportioned so = (Eq. 6.10.4)
U l bu
that the interior reaction from the concrete is
0.33 Vu. The hanger strap should then be pro­ 6. To maintain the conditions of equilibrium as­
portioned to yield under a tension of 1.33 Vu. sumed, the interior cantilever must have a
length:
3.0a = (1.5*p + 3.0g + 3.0c + 1.5s)
A- - '~ w * * 6 m i )

where: 7. The minimum total length of bar is then:


Fy = yield strength of the strap material
0.5€p + a + 3.0a + 0.54 (Eq- 6.10.5)
<j> =0.90
= (2.54 + 4.0g + 4.0c + 2.0s + 0.54) in.
2. Vu may be assumed to be applied €p/2 from the
face of the seat. The remaining part of the mo­ 8. Longitudinal dowels, Ap, are welded to the can­
ment arm is the width of the joint, g, and the tilevered bar to transmit the axial force, Nu:
cover, c, from the end of the member to edge of
the strap. Since moment is sensitive to this di­
A« - $ <Eti- 6-10-6>
mension, it is important that this dimension is
kept as small as feasible and that the value where:
used in analysis is not exceeded in the field.
fy = yield strength of the dowel
Most hangers in practice have exterior cantile­
ver lengths, (€p + g + c), of 3 to 4 in. $ =0.90

3. The moment in the cantilevered bar is then giv­ 9. The lower dowel area, A*,, can be proportioned
en by: using effective shear-friction described in Sect.
4.3.6.
Mu = Vua = Vu(0.5€p + g + c + 0.5s)
(Eq. 6.10.2)
A* - ^ T (Eq. 6.10.7)
where:
where:
( p = bearing length of the exterior cantilever
<j> = 0.85
a = 0.5€p + g+ c + 0.5s
fy = yield strength of lower dowels, psi
Other notation is shown in Figure 6.10.2(B).

The bar should be proportioned to carry this mo­ lOOOkb^n . _ ,. . . .


He = ----- y — - < values in Table 4.3.1
ment in combination with shear and tensile forces. Al­
ternatively, if the bar is proportioned to take this mo­ (Eq. 6.10.8)
ment at the yield stress, but using elastic section
properties, (i.e., Mu = q>Fy bd2/6) the shear and ten­ The nominal shear strength (1.33VU/<J)) is limited
sile forces can usually be neglected. by the values in Table 4.3.1.

PCI Design Handbook/Fifth Edition 6 -3 1


Example 6rT0.1 Design of a Cazaiy Hanger Try 2 in. wide ban

'6(2.69)
d= 2.84 in. mirw
G iv e n :

Hanger similar tothahsbown in Figs. 6.10.1 (A)


Use 2 x 3 in. bar (width x depth)
and 6.10.2. (not exposed to earth or weatb-
e r)-
1c = 5000 psi (both member and support)
fy (reinforcing bars) = 60 ksi By Eqs. 6.10.3 and 6.10.4:

Fy (structural steel) = 36 ksi fbu = 0.85<t>fc J b J b = 0.85(0.7)(5) ^ 6 /2


Vu = 24 kips ^includes all load factors)
Nu = 4 kips (includes allload factors) = 5.15 ksi

b-i = 6 In. _ Vu/3 _ 24/3


0.78 in.
c = 5/ b in. (see Table 1.3.6) b Ub) 5.15(2)

g - 1 in.
( p = 2 in. Min. interior cantilever

Problem: = 3(3.625) = 10.875 in.


Size the hanger components.
Min. total length (Eq. 6.10.5)

= 0.5(2) + 3.625 + 3(3.625) + 0.5(0.78)


Solution:
By Eq. 6.10.1: = 15.89 in.
1.33VU
As (strap) = Use bar 2 x 3 x 1 6 in.
())Fy

1.33(24)
0.99 in2
0.9(36)
By Eq. 6.10.6:

Use 'A x 2 in. strap; As = 0.25(2) (2) = 1.00 in2 A - N- - 4 0.07 in2
n <J>fy 0.9(60)
(Note cover assumption is correct because As
1.0 in2 < As of No. 11 bar).
Use 1-#3 dowel
Use 3/ie in. fillet weld;

Table 6.15.2, E70 electrode: Try h = 16 in.; by Eqs. 6.10.7 and 6.10.8:

1.33(24) fOOOXb^ii 1000(1.0)(6)(16)(1.4)(1.0)


3.82 in.
2(4.18) Vu 24,000

Weld 2 in. across top, 1 in. down sides=4.0 in.


= 5.6 > 3.4
a = 0.5(2) + 1 + % + 0.5(2) = 3.625 in.
use [xe = 3.4
By Eq. 6.10.2:
Mu = Vua = 24(3.625) _ 1.33VU 1.33(24)
^ (j)fyHe 0.85(60) (3.4) “
= 87 kip-in
q _ Mu _ 87 bdf Use 1-#4 dowel.
2.69 in3
req’d (j)Fy 0.9(36) 6
Also check welding requirements.

6 -3 2 PCI Design Handbook/Fifth Edition


Figure 6.10.2 Cazaly hanger

(A) BASIC COM PO NENTS (B) DESIGN ASSUM PTIONS

6.10.2 Loov Hanger [18] sumed to act at a distance a/2 from the top of the
bearing plate. Thus:
The hanger illustrated in Figure 6.10.3 is designed
using the following equations:
& = & - (Eq. 6.10.12)
u lbu

(Eq. 6.10.9) where:


^ (|)fycos a
Cu = Vutana + (Eq. 6.10.13)
where:
<J> = 0.85
For most designs, the horizontal reinforcement,
fy = yield strength of An, is placed very close to the bottom of the steel bar.
Thus, the term (h - d) can be assumed equal to zero,
h -d 1 simplifying Eqs. 6.10.10 and 6.10.13.
(Eq. 6.10.10)
d - a/2 i Tests have indicated a weakness in shear in the
vicinity of the hangers, so it is recommended that stir­
where: rups in the beam end be designed to carry the total
<$> = 0 .9 0 shear.

fy = yield strength of An
Example 6.10.2 Design of a Loov Hanger
The steel bar is proportioned so that the bearing
Given:
strength of the concrete is not exceeded, and to pro­
vide sufficient weld length to develop the diagonal Hanger similar to that shown in Figure 6.10.3.
bars. Bearing strength is discussed in Sect. 4.6.1. Design for same data as Example 6.10.1
However, if the bar is at the top of the member as in
a = 30°
Figure 6.10.3, there is no “geometrically similar" area
larger than the edge of the bar, and:
Problem:
fbu = 0.85c|>f; = 0.6f; (Eq. 6.10.11)
Size the hanger components.
where:
Solution:
c|> = 0.7
A = — ______24_____ = 0 54 in2
sh cj)fycos a 0.85(60) cos 30°
The connection should be detailed so that the Use 2-#5 bars
reaction, the center of compression and the center of
the diagonal bars meet at a common point, as shown Minimum weld length, #5 bar, E70 electrode
in Figure 6.10.3(B). The compressive force, Cu, is as­ (Table 6.15.3) = 2Vz in.

PQ Design-Handbook/Fifth Edition 6 -3 3
Detail An so i t is' near tbeJxrttom of the steet bar. Provide end bearing plate as shown:
h-d « 0
A - Nu _ 4 = 0.07 in2
({rfy 0.9(60)

Use 1-# 3 dowel


By Eq. 6.10.11:
fbu = 0.854>f; = 0.85(0.7) (5) = 2.98 ksi

By E^. 6.10.13:
Cu = Vutana = 24 tan 30° = 13.9 kips
Assume b = 1 in.

_ = _ 13.9 4.65 in.


bC 1(2.98)
a1 2 = 2.33 in.

Figure 6.10.3 Loov hanger

OUTLINE OF .
CONCRETE ,

(A) BASIC CO M PO NENTS

Nu( h - d )
Cu = Vutan a +
d -|

6 -3 4 PCI Design Handbook/Fifth Edition


Figure 6.11.1 ^ttomen^GGimections

PCI Design Handbook/Fifth Edition 6 -3 5


6.11 Moment Connections lustrating the .three primary categories of connec­
tions, namely- bearing, tie-back and alignment
When lateral stability of precast, prestressed: con-
connections, are shown in Figures 6.12.1 through
crete buildings is achieved by frame ^action or by a 6.12.3.
combination ofshearwail and frame action, the con­
nections to develop frame action must be designed 6.13 Connection of Load Bearing Panels
for appropriate moment and shear transfer capabili­ Connections for load bearing wall panels are an
ties. essential part of the structural support system and
The tension force for the moment resistance within the stability of the structure may depend upon them.
a connection can be provided by various types of in­ In addition to the weight of the panels, the connec­
serts, such as headed studs and deformed bar an­ tions must resist and transfer dead, live, wind and
chors. These inserts must be properly anchored to earthquake loads, and effects of volume changes.
preclude failure of the concrete and thus ensuring a Erected load bearing waits may have both hori­
ductile mode of failure. Post-tensioning can also be zontal and/or vertical joints across which forces must
used to develop moment resistance at joints between be transferred. Figure 6.13.1 indicates, for separate
interconnected members. Where a high degree of cases, the principal applied forces and the resulting
moment resistance and ductility are required, com­ joint force systems. In buildings, superposition of
posite construction is frequently used to achieve con­ forces and various combinations of panel and joint
nections that are similar to monolithic concrete joints assemblies must be considered.
in their behavior. Distribution of lateral forces to shear walls de­
Achieving rigid connections can be costly. In most pends largely on adequate connections of floors to
cases, it may not be desirable to build-in a high de­ walls. In addition to the transfer of vertical shear
gree of fixity, since the restraint of volume changes forces due to lateral loads, vertical joints may also be
could result in large forces in the connections and the subject to shear forces induced by differential loads
on adjacent panels. Joint and connection details of
members. It is therefore preferable that the design of
exterior bearing walls are especially critical since the
moment-resisting connections be based on the con­
floor elements are usually connected at this elevation
cept that the desired moment resistance is achieved
and a waterproofing detail must be incorporated.
with some deformation/rotation at the connection.
The deformation should be controlled to provide for 6.13.1 Vertical Joints
the desired ductility.
Vertical joints may be designed so that the wall
A few examples of different types of moment-re­
panels form one structural unit or act as independent
sisting connections are shown in Figure 6.11.1. Ref. 2
wall units.
provides additional examples and also discusses rel­
ative degrees of fixity. 6.13.1.1 Hinge Connections
Moment-curvature analysis of precast and pre­
stressed concrete members is readily done based on Hinge connections transfer compression, shear
established analytical methods. PCI funded research and tension forces but not moments. This is usually
[19], as well as other research in progress, are ex­ done at floor levels through floor diaphragms and tie
pected to lead to an adequate knowledge base on beams. The vertical joint between wall panels usually
is “open” so the panels resist lateral loads indepen­
moment-resisting connections and enable formula­
dently according to their relative rigidity (Figure
tion of improved analytical procedures.
6.13.2). Sound and waterproofing details may also
6.12 Connection of Non-Load Bearing Wall have to be considered.
Panels
6.13.1.2 Grooved Joint Connections
The design of connections of non-load bearing ar­
chitectural wall panels follows the same principles as Grooved joints are continuous and usually filled
structural connections, except the loads are general­ with grout. The minimum groove dimension should
ly lighter. Usually, the connections are detailed to be 11/2 in. deep and 3 in. wide (Figure 6.13.3). The
minimize the volume change forces and, thus are pri­ joint strength can be evaluated by shear-friction even
marily designed for the self-weight of the panel and if shrinkage, creep, and temperature movements
for the lateral loads. Attention to details and proper have caused a crack at the wall-grout interface.
protection of any exposed hardware are most impor­
tant to ensure satisfactory performance of the con­ 6.13.1.3 Mechanical Connections
nections for the service life of the structure. Mechanical connections consist of anchorage de­
A discussion of connection design fundamentals vices cast into the wall panels and steel sections
and production and erection considerations is given (plates, angles, bars, etc.) crossing the joint. The
in Refs. 2 and 20 and a summary is included in Chap­ strength is usually controlled by the capacity of the
ter 7 (Sect. 7.2). A few examples of typical details il­

6 -3 6 PCI Design Handbook/Fifth Edition


Figure 6.12.1 B earing connections
OVERSIZED HOLE O ft
VERTICAL-SLOT IN ANGLE
-----^------
<
£
<

&
• n
T ' ‘ *
<
-- ------- \ -------
— \ -----

COLUMN ROTATED 90*

Figure 6.12.2 Tie-back connections

PLAIN ROD WITH

PCI Design Handbook/Fifth Edition 6 -3 7


Figure6.12.3 Alignment connections

Figure 6.13.1 Exterior forces and joint force systems

VERTICAL SHEAR AT
VERTICAL JOINT:

0 < (Vu)u < <vrigid)u

REACTION AT
HORIZONTAL JOINT

(Vy)u = (Vrigid) u

(Vv)u = 0

(A) LATERAL LOADS IN (Bj LATERAL LOADS OUT OF (C) DIFFERENTIAL GRAVITY
PLANE OF WALLS PLANE OF WALLS LOADS

6 -3 8 PCI Design Handbook/Fifth Edition


cast-inanchorage (Figure 6.13.4); connection of the Figured. 13.2 Wall to wall hinge connections
^steel section to the anchorage device can be made at floor levels
by bolting, welding,, or grouting.
Tie beam connections aiJoorJevels mayactwith
' -\ the mechanical connections. The relative participa­
tion in resisting applied forces depends on their
force-deformation characteristics. The ultimate ca­
pacity is the sum of the strength of the tie beams and
the mechanical connections.
Once the connection forces have been estab­
lished, evaluation ofconnection strength is made ac­
cording to strength of materialsand the principles de­
veloped in other sections of this Handbook.

6.13.1.4 Keyed Joint Connections

Keyed joints can either be reinforced or non-rein- Assuming a conservative value of tan<|) = 0.60, a
forced (Figure 6.13.5). Test results indicate similar sliding along Juwill not occur if:
deformation behavior, but also show that reinforced Ru Ju
joints are stronger. Reinforcement is required in high
which is the case for a < 30°.
seismic zones. As shown in Figure 6.13.5, the resist­
ance can be limited by: Fora > 30°andRu < Ju, a tension force Tudevelops
which must be absorbed by horizontal reinforcing of
(A) cracking of grout concrete parallel to joint, the joint. According to Figure 6.13.6:
T _ AJU _ Ju - Ru Vu(sina - cosatancj))
(B) diagonal cracks across joints,
A u ~ cosa “ cosa “ cosa

(C) crushing of key edges or joint concrete at key


= Vu(tan a - tan <}>) (Eq. 6.13.1)
edges, or
The sum of the unit tension forces can be ab­
(D) slippage along contact area. sorbed at each floor level by horizontal ties or by uni­
formly distributed horizontal reinforcing bars protrud­
For (A) the shear-friction concept applies (Sect. ing from the wall.
4.3.6). For (B), (C) and (D) the strength of the con­
nection is usually a function of the compressive
Figure 6.13.3 G ro o ve d joint connections
strength of the grout, the bond strength of the grout to
the precast concrete, and the profile of the keys. As
shown in Figure 6.13.6, the vertical shear force can
be resolved into tension and compression compo­
nents with <j) as the apparent friction coefficient and a
the angle of the key.
Depending on the number of keys per floor, the
unit forces per key resulting from the vertical shear
force Vu are:

Ju= Vusina

Cu= Vucosa

The joint force Ju is resisted by the shear-friction


force Rudeveloped in the plane of Ju, with:

Ru = Cutan<j>

PCI Design Handbook/Fiftb Edition 6 -3 9


Figure 6.13.4 Mechanical connections Figure 6.13.6 Keyed joint connection

.^ . -

(A) ANGLE-BOLT

1 p _ 'jr - ; , ~ w v \

(B) PLATE-BOLT
6.13.2 Horizontal Jo in ts
Horizontal joints in load bearing wall construction
occur at floor levels and at the transition to foundation
or transfer beams. The principal forces to be trans­
ferred are vertical and horizontal loads from panels
above and from the diaphragm action of floor slabs.
The resulting forces are listed below and shown in
Figure 6.13.7:
(a) normal to joint-compression or tension, Pu_.,;
(b) horizontal to joint-horizontal shear, VU_H1;
(c) vertical to joint at face-vertical shear, VU_H2;
and
(d) perpendicular to joint-compression or tension
from floor diaphragm, Tu_3.
Because of the limited frame action that can be de­
veloped perpendicular to a wall, moment stresses in
the joint are normally only of minor importance. A dis­
cussion of axial load transfer through horizontal joints
is given in Ref. 21.
(E) WELDING WITH MAKE-UP PIECES
Figure 6.13.8 shows three details typical of multi­
story load bearing wall buildings. With hollow core
slabs used for floors, the most efficient detail is to
build the slab ends into the wall. Depending on the
butt joint size, the strength of the joint for transfer of
vertical loads can be enhanced with the addition of
Figure 6.13.5 Forces in keyed joint
grout in the butt joint, Figure 6.13.8(b), and in both
the joint and cores, Figure 6.13.8(c).Grout fill in the
cores increases the net slab width and provides con­
finement for a grout column.
The strength of the joint for vertical load transfer
can be predicted using Eq. 6.13.2 for an ungrouted
joint, Figure 6.13.8(A). For a grouted joint, Figure
6.13.8(B) or (C), the greater of Eq. 6.13.2 and Eq.
6.13.3 can be used. Both grouted and ungrouted
joints can have slab cores either filled or not filled.
Both equations include a capacity reduction term for
load eccentric from the centerline of the joint. With
single story walls braced at the top and bottom, this
eccentricity will be negligible.

(j)Pn = <j)0.85Acf; R. (Eq. 6.13.2)


4>Pn = <t>tg£fuCRe/k (Eq. 6.13.3)

6 -4 0 PCI Design Handbook/Fifth Edition


where: Figure B.i 3.7 Typical interior horizontal
pn = nominal strengthof the joint connection
Ac = effective bearing area of slabr in joint =
2 w lv
w = hearing strip width
bw = net web width of hollow core slab when
cores are not filled
= unit width as solid slab when cores are
filled
fc = design compressive strength of slab
concrete o r grout, whichever is less.
tg = grout column thickness
i = width of slab being considered
fu = design compressive strength of wall or
grout, whichever is less, when walls are
reinforced against splitting and slab cores
are filled
fu = 80% of design compressive strength of
wall or design compressive strength o f Problem:
grout, whichever is less, when walls are Find grouting requirements for interior joint.
not reinforced against splitting or slab
cores are not filled Solution:
C = 1.0 when cores are not filled Loads:
= 1.4 J2500/Vc (grout) > 1.0 when cores are Roof: wu =28(1.4(60+15)+ 1.7(30)]/1000
filled = 4.37 klf
k = 0.65 + « < * $ - * * >
50,000 Floors: wu = 28 [1.4 (60+10)+ 1.7(40)1/1000
Re = reduction factor for eccentricity of load = 4.65 klf
= 1 -2 e /h
Walls: wu = 1.4(800)/1000
e = eccentricity of applied load measured
from joint centrolineal = 1.12 klf/story
h = wall thickness
Accumulate loads above floor noted:
-e-

o
n

Floor wu 2Wu
18 4.37 + 1.12 5.49
Example 6.13.1 Design of Grouted Horizontal 17 4.65 + 1.12 11.26
Joint 16 5.77 17.03
Given: 15 5.77 22.80
14 5.77 28.57
An 18-story bearing wall building has 8 in.
precast concrete walls and 8 in. hollow-core 13 5.77 34.34
floor and roof units. Floor slabs span 28 ft 12 5.77 40.11
and bear on multimonomer plastic bearing 11 5.77 45.88
strips. 10 5.77 51.65
fc (precast concrete) = 5000 psi 9 5.77 57.42
Loads: 8 5.77 63.19
Roof: DL = 15 psf; LL = 30 psf 7 5.77 68.96
Floors: DL = 10 psf; LL = 40 psf 6 5.77 74.73
Hollow-core = 60 psf 5 5.77 80.50
Walls = 800 plf/story 4 5.77 86.27
3 5.77 92.04
No LL reduction for example
2 5.77 97.81

PCI Design Handbook/Fifth Edition 6 -4 1


Figure 6rl3.8 Typical joints in a bearing-wail building

a) Evaluate strength of ungrouted joint: (Figure Therefore 4>Pn = 76.4 kip/ft


6.13.8(A) Assume the ratio of web width to
total width of the slabs = 0.3 and bearing 2. Vz in. butt joint with cores filled
strips width, w = 3 in.
(j)Pn = ct>0.85Acfc Re
cj>Pn = <}>0.85Acf; Re
= 0.7 (0.85) (2) (3) (12) (3)/1
= 0.7(0.85)(2)(3)(0.3)(12)(5)| 1 - ®
= 129 kip/ft
= 64.26 kip/ft
or <j>Pn = (jjtg^CRe/k
Adequate for floors 8 through roof.
fu = 3000 psi
b) Evaluate strength of grouted joint using 3000 C = 1.4 72500/3000= 1.28
psi grout for:
1. 2 in. butt joint with no filled cores k = 0.66
<t>Pn = <j>0.85Acf' R*
0.7(0.5)(12)(3)(1.28)(1
= 0.7 (0.85) (2) (3)(0.3) (12) (5)^1 -
<t>Pn 0.66

= 64.26 kip/ft 24.4 kip/ft< 129

or <j)Pn=<|>tg€fuCRe/k Therefore (t>Pn = 129 kip/ft

fu = 3000 psi Use Vz in. butt joint with cores filled below 8th floor.
Typical examples of connections through horizon­
C = 1.0 tal joints are shown in Figure 6.13.9. Since forces are
concentrated at a few points, they must be redistrib­
k = 0.65 + (3000 - 2500)/50,000 = 0.66 uted into the panels above and below. Connections
should have more ductility and strength than the ver­
0.7(2)(12)(3)(1.0)|l tical tie fastened to it.
To satisfy structural integrity requirements, mini­
<t)Pn= 6156
mum tensile ties should be provided at the joints to
resist the forces given in Sect. 3.10.
= 76.4 k/ft > 64.3

6 -4 2 PCI Design Handbook/Fifth Edition


Figure 6,13.9 Connections through horizontal-joints

ANCHO R
BARS

WELD GROUT
PLATES
SPLICE SLEEVE

F '

DRYPACK

POLYURETHANE
FOAM

VERTICAL TIES

(A) W ELD PLATES (B) GROUTED S P L IC E SLEEVE

PO S T-TE N SIO N IN G ROD

DRY PACK
GROUT

COUPLER CROSS JOINT TIES

GROUT DAM

\\
BAR IN
BEARING STRIP SHEAR KEY

GROUTED JOINT

INTERIOR JOINT EXTERIOR JOINT


(D) POST-TENSIONED CONNECTION

PCI Design-Handbook/Fifth Edition 6 -4 3


Figure s. 13.10 Floor to bearing wall connections

NOTE: SOME EXTRUDED


HOLLOWCORE PRODUCTS
CANNOT EASILY
ACCOMMODATE CAST-IN
PLATES OR ANCHORS.
CONSULT WITH LOCAL
PRODUCER.

6 -4 4 PCI Design Handbook/Rfth Edition


2. “Desigrr and Typical Details of Connections for
Precast and Prestressed C oncrete/ Second
Edition, MNL-123-8S, Preeast/Prestressed
Concrete Institute, Chicago, IL, 1988.

3. “Structural Welding Code—Reinforcing Steel,”


AWS D1.4-92, American Welding Society; Mi­
ami, FL, 1992.

4. “Structural Welding Code—Steel,” AWS


D1.1-96, American Welding Society, Miami, FL,
1996.

5. Reichard, T.W., Carpenter, E.F., and Leyen-


decker, E.V., "Design Loads for Inserts Em­
bedded in Concrete,” Building Science Series
42, N.B.S. (U.S.) Code: BSSNVB, Superinten­
dent of Documents, U.S. Government Printing
Office, Washington, DC, May 1972.

6. “The Procedure Handbook of Arc Welding,”


Thirteenth Edition, Theiincoln Electric Compa­
ny, Cleveland, Ohio, June 1988.

7. “Reinforcement: Anchorages, Lap Splices and


Connections,” Concrete Reinforcing Steel In­
stitute, Schaumburg, IL,. 1990.

8. ACt Committee 439, “Mechanical Connections


of Reinforcing Bars,” Concrete International,
V.5, No.1, January 1983.

9. Shaikh, A.F., and Yi, W., “In-Place Strength of


Welded Headed Studs,” PCI Journal, Vol. 30,
No. 2, March-April 1985.

10. Ehligehausen, R., and Fuchs, W., “Load-bear­


ing Behavior of Anchor Fastenings Linder
Shear, Combined Tension and Shear or Flexu­
ral Loading,” Betonwerk + Fertigeil-Technik,
Heft 2, 1988.

11. “Manual of Steel Construction Allowable Stress


Design,” American Institute of Steel Construc­
tion, Chicago, IL, Ninth Edition, 1989.

12. “ Manual of Steel Construction Load and Resist­


ance Factor Design,” American Institute of
A few typical floor to wall and wall to foundation Steel Construction, Chicago, IL, First Edition,
details are shown in Figures 6.13.10 through 6.13.12. 1986.
For additional details, see Ref. 2.
13. Iverson, J.K., and Pfeifer, D.W., “Criteria for De­
sign of Bearing Pads,” Technical Report,
6.14 References TR-4-85, Preeast/Prestressed Concrete Insti­
1. Martin, L.D., and Korkosz, W.J., “Connections tute, PCI Journal, Vol. 30, No. 5, September-
October 1985.
for Precast Prestressed Concrete Buildings-ln-
cluding Earthquake Resistance,” Technical
14. Kriz, L.B., and Raths, C.H., “Connections in
Report No. 2, Precast/Presiressed Concrete In­ Precast Concrete Structures—Strength of Cor­
stitute, P C I Journal, Vol. 27, No. 3, May-June
bels,” PCJ Journal, V. 10, No. 1, February 1965.
1982.

PCI Design Handbook/Frfth Edition 6 -4 5


15. Mattock, A.H., “Design Proposals tor Rein­ Institute; PCI Journal, Vot. 32, No. 2, March-
forced Concrete Corbels," PCI Journal, Vof. 21, April 1987.
No. 3, May-dune 1976.
20. “Architectural Precast Concrete," Second Edi­
16. Marcakis, K. end- Mitchell, D., “Precast Con­ tion, M N Ld 22-89, Precast/Prestressed Con­
crete Connections .with Embedded Steel Mem­ crete Institute, Chicago, IL, 1989.
bers,” PCJ Journal, V. 25, No. 4, July-August
1980. 24. Johal, L.S., and Hanson, N,W., “Design for Ver­
tical Load on Horizontal Connections in Large
17. Cazaly, L. and Huggins, M.W., “Canadian Pre­ Panel Structures,” PCI Journal, V. 27, No. 1,
stressed Concrete Institute Handbook,” Cana­ January-February 1982.
dian Prestressed Concrete Institute, Ottawa,
Ontario, Canada, t964. 22. Fuchs, W., Eiighausen, R., and Breen, J.E.,
“Concrete Capacity Design Approach for Fas­
18. Loov, Robert, “A Precast Beam Connection De­ tening to Concrete,” ACI Structural Journal, V.
signed for Shear and Axial Load,” PCI Journal, 92, No.1, January-February 1995.
V. 13, No. 3, June 1968.
23. Wong, T.L., Donahey, R.C., and Lbyd, J.P.,
19. Stanton, J.F., Anderson, R.G., Dolan, C.W., “Stud Groups Loaded in Shear Near a Free
and McCleary, D.E., “Moment Resistant Con­ Edge,” PCI Journal (scheduled for publication
nections and Simple Connections,” Research in 1998).
Project No. 1/4, Precast/Prestressed Concrete

6 -4 6 PCI Design Handbook/Fifth Edition


6.15 DESIGN AIDS

Figure&15.l Allowable and design stress for fillet and patiafpenetration^aelds?


-
Allowableb Design^
Electrode working stress (ksi) strength (ksi)

E60 18 27

E70 21 31.5

E80d 24 36

E90d 27 40.5

E100d 30 45

a. For partial penetration welds loaded in shear parallel to the axis of the weld.
b. Based-on AISC Allowable Stress Design Manual of Steel Construction [11],
c. Based on AISC Load and Resistance Factor Design Manual of Steel Construction [12]. Includes cp = 0.75
d. Check yield strength of base metal for compatibility with selected electrode.

Figure 6.15.2 Strength of fillet welds for building construction


E60 Electrode E70 Electrode

Fillet*
weld Allowable stress Designb Allowable stress Designb
size design (k/in.) strength (k/in.) design (k/in.) strength (k/in.)

V
s 1.59 2.39 1.86 2.78

3/ l6 2.39 3.58 2.78 4.18

1/4 3.18 4.77 3.71 5.57

S/16 3.98 5.96 4.64 6.96

% 4.77 7.16 5.57 8.35

7/s 5.57 8.35 6.50 9.74

Vi 6.36 9.54 7.42 11.14

8/ l6 7.16 10.74 8.35 12.53

Vs 7.95 11.93 9.28 13.92

a. Assumes 4 5 ° fillet.
b. Based on AISC Load and Resistance Factor Design Manual of Steel Construction [13], Includes 4> = 0.75

PCI Design Handbook/Fifth Edition 6 -4 7


Figure 6.15.3 Minimum lenc^h of weld to develop fuD strength of b a r W eld^araltel-tobar length?

tw=G.2d

.tw— 0.3db

SPLICE

\ Plate
\thickness Minimum length of weld, in.a
Min.
Electrode \in . splice
Bar length,
Va 5/16 % 7/l6 1/2
size \
3 1 1/2 V /z 1 1/2 1 1/2 V /z 1

4 2 2 2 2 2 IV 2
5 2 1/2 2 1/z 2 1/2 2 1/2 2Vz V /a

6 3 3 3 3 3 2

E7Q 7 3 1/4 3 1/4 3 1/4 3 1/4 3 1/4 2V a

8 3% 3% 3% 3% 3% 2Vz

9 4% 4 1/4 4 1/4 4 1/4 4 1/4 3

10 6 4% 4% 4% 4 3/ a 3 1/4

11 7 1/4 5% 5 1/4 5 1/4 5V a 3 1/2

3 1 1/4 V /a 1 Va 1 1/4 V /a 1

4 m 1% V /a V /a V /a 1 1/4

5 2V a 2V a 2% 2Vz 2Vz 1 Vz

6 2Vfe 2Vz 2 ’/2 2Vz 2Vz V /a

E80 7 3 3 3 3 3 2

8 3Vz 3 'A 3Vz 3'/z 3 1A 2V a

9 4% 3 3/ a 3 3/ a 3 3/ a 3 3/ a 2 1/ i

10 6 4% 4V a 4V a 4V a 3

11 7Vz 5% 5 3/ a 4 3/ a 4 3/ a 3%
3 V /a V /a V /a V /a V /a 1

4 V/z V/z V4 V/z V/z 1

5 2 2 2 2 2 1 1/4

6 2V a 2V a 2V a 2V a 2V a 1 1/2

E90 7 3 2 Va 2 3/ a 2 3/ a 2% V /a

8 3 3/4 3 5 5 5 2

9 4% 3% 3Vz 3Vz 3 1/2 2V a

10 6 4% 4 3% 3 3/ a 2Vz

11 7V a 5 3/ a 5 4 1/4 4V a 2 3/ a

a. Lengths below heavy line are governed by plate shear. Lengths above heavy line are governed by weld strength.
Basis: bar fy = 60 ksi; plate Fy = 36 ksi; shear on net section limited to 0.75(Q.6>(58) ksi.

6 -4 8 PC) Design Handbook/Fifib Edition


Figure 6.15.4 S izeo f fillet weld required.toxleveJoptuil strength of bar

BAR PERPENDICULAR
TO PLATE, WELDED
db
0NESIDE - ^ (d . + W EL^SIZE)

tw
PLATE Fv = 36 ksi p— '
PLATE AREA = Jtfdb + 2 x WELD SIZE) 1

^ 5 ^ — *

Grade 40 Bar

E70 Electrode E80 Electrode6 E90 Electrode6


Bar Nominal Min. plate Nominal Min. plate Nominal Min. plate
Size weld size8 thickness* weld size8 thickness* weld size8 thickness*
(in.) (in.) fin.) <m.) (in.) (in.)

3 3/ l 6 1/4 3/ l 6 1/4 3/16 1/4

4 Vi 1/4 3/ i 6 1/4 3/16 Vi

5 1/4 1/4 Vi 1/4 1/4 Vi

6 5/ l 6 1/4 5/ l 6 1/4 1/4 Vi

7 3/8 1/4 Vl6 1/4 ^16 Vi

8 7/ l 6 1/4 3/8 1/4 5/ l 6 Vi

9 7/ l 6 1/4 7/ l 6 1/4 3/8 Vi

10 !4 5/ l 6 7/ l6 5/ l 6 7/ l 6 5/16

11 9/ l 6 5/ l 6 V6 3/8 7/ l 6 %

Grade 60 Bar

3 3/ l 6 3/16
1/4 1/4 1/4 Vi

4 5/16 1/4 1/4 1/4 1/4 Vi

5 % 1/4 5/ l 6 1/4 5/ l 6 Vi

6 7/ t 6 1/4 3/8 1/4 3/8 Vi

7 V4 1/4 7/ l 6 5/ l 6 7/ l € 5/16

8 ®/l 6 S/16 14 5/ l 6 7/ l 6 5/ t 6

9 % Y l6 S/16 3/8 V6 n

10 11/1 8 3/8 % 3/8 9/ l 6 V 16

11 3/4 7/ l 6 1,/1 6 7/ l 6 % 7/ l 6

a. A minimum of 3/ie in. weld size is suggested.


b. Theoretical thickness for shear stress on base metal = 0.75(0.6) (58) ksi. A more practical thickness might be taken as Vklb as used
with headed studs. A minimum of 'A in. plate thickness is suggested.
c. Check yield strength of base metal for compatibility with selected electrode.

PCI Design Handbook/Fifth Edition 6 -4 9


Figure 6.15.5 Size o f fillet weld required to tievelep-ihitt strength^oftoar

BAR PERPENDICULAR TO PLATE,


WELDED BOTH SIDES ^ ^

PLATE Fy = 36 ksi o t

SEE FIG. 6.15.4 FOR OTHER INFORMATION iM

Grade 40 Bar

E70 Electrode E80 Electrode6 E90 Electrode6


Bar Nominal Min. plate Nominal Min. piate Nominal Min. plate
Size weld size3 thickness1* weld size8 thickness6 weld size8 thickness6
(in.) (in.) (m.) (in.) (in.) (in.)

3 3/ l 6 1/4 3/ l 6 1/4 3/ l 6 1/4

4 3/ l 6 1/4 3/ l 6 1/4 3/ l 6 1/4

5 3/ l 6 1/4 3/ l 6 1/4 1/4

6 3/ l 6 1/4 3/ l 6 1/4 3/ l 6 1/4

7 3/ l 6 1/4 3/ l 6 1/4 3/ l 6 1/4

8 1/4 5/ l 6 3/ l 6 5/ l 6 3/ l 6 5/ l 6

9 V* 5/ l 6 1/4 5/ l 6 S/ 1 6 %

10 5/ l 6 % 1/4 % 1/4 %

11 5/ l 6 7/ l 6 5/ l 6 % 1/4 7/ l 6

Grade 60 Bar

3 3/ l 6 1/4 3/ l « 1/4 3/ l 6 1/4

4 3/ l 6 1/4 3/ l 6 1/4 3/ l 6 1/4

5 3/ l 6 1/4 3/ l 6 1/4 3/ l 6 1/4

6 1/4 ^16 1/4 5A 6 3/ l 6 5A 6

7 5/ l 6 5/ l 6 1/4 % 1/4 %

8 sAs % 5Ae % 1/4 7/ l f i

9 % 7/ l 6 S/ 1 6 7/ l 6 5/ l 6 7/ l 6

10 % 'A % 1/2 5A6 V6

11 7/ l 6 Vz % 9/ l 6 % S/ 1 6

a. A minimum of aM in. weld size is suggested.


b. Theoretical thickness for shear stress on base metal = 0.75(0.6)(58) ksi. A more practical thickness might be taken as 1/2d b as used
with headed studs. A minimum of Vi in. plate thickness is suggested.
c. Check yield strength of base metai for compatibility with selected electrode.

6 -5 0 PCI Design Handbook/Fifth Edition


Figure 6.15.6 Dimensions mid design tensile strength of welded treaded stud? (see Fig; 6.5.3)
Dimensions of headed studs
fStud diameter, db, in. 1/4 % V4- Mb % %
Head diameter, dh,Tn. ; % T VA VA m
Head thickness, th, in. Mb %2 5/ l6 5/ l6 Mb ; %
Design tensile strength limited by concrete strength 0PC (kips)—Eqs. 6.5.3 and 6.5.4
Edge Normal weight concrete19(1=1.0) Sand-lightweight concrete1* (1=0.85)
dist. Stud
Diameter, d^ in. Diameter, db, in.
dec length*1
(in.) (in .) V* Mb Vz % m W> 1/4 Mt, 1/2 Mb Mi® 7/ i (0
3.0 5.0 5.2 5.5 5.9 5.8 6.0 4.2 4.4 4.7 5.0 4 .9 5.1
4.0 6.4 6.7 7.0 7.4 7.3 7.5 5 .5 5.7 6.0 6.3 6.2 6.4
2 5.0 7.9 8.2 8.5 8 .9 8.8 9.0 6.8 7.0 7.2 7.5 7.5 7.6
6.0 9.4 9.7 10.0 10.4 10.3 10.5 8.0 8.2 8.5 8 .8 8.7 8.9
7.0 10.9 11.2 11.5 11.9 11.8 12.0 9.3 9.5 9.8 10.1 10.0 10 .2
8.0 12.4 12.7 16.0 13.4 13.3 13.5 10.6 10.8 11.0 11.4 11.3 11.4
3.0 7.0 7.1 7.4 7.9 7.6 7.9 S.6 6.0 6.3 6.7 6.5 6.7
4.0 9.7 10.0 10.5 11.1 10.9 11.2 8.2 8.5 8.9 9.4 9.3 9.5
5.0 11.9 12.3 12.8 13.3 13.2 13.5 10.1 10.4 10.8 11.3 11.2 11.4
6.0 14.2 14.5 15.0 15.6 15.4 15.7 12.0 12.3 12.8 13.2 13.1 13.3
7.0 16.4 16.8 17.2 17.8 17.7 17.9 13.9 14.2 14.7 15.1 15.0 15.3
8.0 18.6 19.0 19.5 20.0 19.9 20.2 15.8 16.1 16.6 17.0 16.9 17.2
3 JO 7.0 7.1 7.4 7.9 7.6 7.9 5.9 6.0 6.3 6.7 6.5 6.7
4.0 12.3 12.4 12.9 13.6 13.2 13.6 10.5 10.6 11.0 11.6 11.2 11.5
5.0 15.9 16.4 17.0 17.8 17.6 17.9 13.5 13.9 14.5 15.1 14.9 15.3
6.0 18.9 19.3 20.0 20.8 20.6 20.9 16.0 16.4 17.0 17.6 17.5 17.8
7.0 2 1 .9 22.3 23.0 23.7 23.8 23.9 18.6 19.0 19.5 20.2 20.0 20.3
8.0 24.9 25.3 26.0 26.7 26.5 26.9 21.1 21.5 22.1 22.7 2 2 .6 22.9
3.0 7.0 7.1 7.4 7.9 7.6 7.9 5.9 6.0 6i 6.7 6.5 ------ § T
4.0 12.3 12.4 12.9 13.6 13.2 13.6 10.5 10.6 11.0 11.6 11.2 11.5
5.0 19.1 19.3 19.9 20.8 20.3 20.7 16.3 16.4 16.9 17.7 17.3 17.6
0
6.0 23.6 24.2 25.0 25.9 25.7 26.2 20.1 20.6 21.3 22.0 21.8 22.2
7.0 27.3 27.9 28.7 29.7 29.4 29.9 23.2 23.7 24.4 25.2 25.0 25.4
8.0 31.1 31.7 32.5 33.4 33.2 33.6 26.4 26.9 27 .6 26.4 28.2 28.6
3.0 7.0 7.1 7.4 7.9 7.6 7.9 5.9 6.0 6.3 6.7 6.5 6.7
4.0 12.3 12.4 12.9 13.6 13.2 13.6 10.5 10.6 11.0 11.6 11.2 11.5
ft 5.0 19.1 19.3 19.9 20.8 20.3 20.7 16.3 16.4 16.9 17.7 17.3 17.6
0
6.0 27.4 277 28.4 29.5 28.9 29-4 23.3 23.5 24.2 25.1 24.6 25.0
7.0 32.8 33.5 34.5 35.6 35.3 35.9 2 7 .9 28.5 29.3 30.3 30.0 30.5
8.0 37.3 38.0 39.0 40.1 39.8 40.4 31.7 32.3 33.1 34.1 33.8 34.3
3.0 7.0 7.1 7.4 7.9 7 .6 7.9 5.9 6.0 6.3 6.7 6.5 6.7
4.0 12.3 12.4 12.9 13.6 13.2 13.6 10.5 10.6 11.0 11.6 11.2 11.5
7 5.0 19.1 19.3 19.9 20.8 20.3 20.7 16.3 16.4 16.9 17.7 17.3 17.6
6.0 27.4 27.7 28.4 29.5 28.9 29.4 23.3 23.5 24.2 25.1 24.6 25.0
7.0 37.3 37.5 38.4 39.7 39.0 39.6 31.7 31.9 32.7 33.7 33.2 33.7
8.0 43.5 44.3 45.5 46.8 46.5 47.1 37.0 37.7 38.6 39.8 39.5 40.0
3.0 7.0 7.1 7.4 7.9 7.6 7 .9 5.9 6.0 6.3 6.5 — 5 T
4.0 12.3 12.4 12.9 13.6 13.2 13.6 10.5 10.6 11.0 11.6 11.2 11.5
o 5.0 19.1 19.3 19.9 20.8 20.3 20.7 16.3 16.4 16.9 17.7 17.3 17.6
6.0 2 7 .4 27.7 28.4 29.5 289 29.4 23.3 23.5 24.2 .25.1 24.6 2 5 .0
7.0 37.3 37.5 38.4 39.7 39.0 39.6 31.7 31.9 32.7 33.7 33.2 33.7
8.0 48.6 48.9 49.9 51.4 50.6 51.3 41.3 41.5 42.4 43.7 43.0 43.6
Diame-
Design tensile strength 0Py 1/4 % 1/2 SA Ma %

of studs, limited by steel strength * (kips)--Eq. 6.5.6 2.2 5.0 8.8 13.8 19.9 27.1
0 Py

a. For stud groups, also check Fig. 6.15.7. The table values for <j>Pc which are larger than <j>Py values are for use in combined tension
and shear equations. _______
b. fe = 5000 psi, for other strengths multiply by / f t /5000
c. Edge effect considers vicinity to only one edge.
d. The embedment length is equal to the stud length minus the thickness of the stud head (see Fig. 6.5.3).
e. Some of the values for % in. and % in. studs are smaller than those for the % in. stud. This apparent contradiction is due to the
interaction of the stud head diameter with other design dimensions. The values given in the table are correct.
f. See Fig. 6.15.9 for bolts.

PCI Design Handbook/Fifth Edition 6 -5 1


T ig u re 6.15.7 Design tensile-strength otw eld ed headed stud groups lim ite db y concrete

The design tensile strength (Fig. 6:5.6, Gases 1 through 6)may be written as:

d>Pc = 4 p d - 4^02
where:
o'0

net design tensile strength


II

4>PC1 = design tensile strength forh > hmjn (Fig; 6.15.7A). Note: cpPC2 = 0 for h > timin.

4>Pc2 = length reduction-when h < hmin (Fig. 6.15.7G)

h = member thickness

hmirv = minimum member thickness to ensure truncated pyramid failure shown in Fig. 6.5.4
(Fig. 6.15.7B)
The following pages Include:

Fig. 6.15.7A for values of $ Pci

Fig. 6.15.7B for values of h,™,

Fig. 6.15.7C for values of cj) Pc2

6 -5 2 PCI Design Handbook/Fifth Edition


Figure 6.15L7A Design tensile ^trength for b > hmln, <j>Pc1— Case 1

Case 1: Not near a free edge

4 P C1 = <t>2.67X/fT(x, + 24e) f a + 2€e)


4> = 0.85
where: x-t and-y1are the dimensions of the flat bottom
of the part of the truncated pyramid.
For Case 1: x1=x, y1=y
Note: Table values are based on
X = 1.0 and % = 5000 psi;
x and y are the overall dimensions for different material properties, multiply table values by
(width and length) of the stud group. x jr c /50oo
X1 Design tensile strength, <|>Pc1 (kips)
y iN jn .
i t in. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 36
in. \
0 8 9 11 13 15 17 19 21 23 25 27 29 31 33 35
2 10 13 15 18 21 23 25 28 31 33 36 39 41 43 46
4 13 16 19 23 25 29 32 35 39 42 45 48 51 55 58
6 15 19 23 27 31 35 39 42 46 50 54 58 61 65 69
3 8 18 23 27 31 36 41 45 49 54 59 63 67 72 76 81
10 21 25 31 36 41 46 51 57 61 67 72 77 82 87 92
12 23 29 35 41 46 52 58 63 69 75 81 87 92 98 104
14 25 32 39 45 51 58 64 71 77 83 90 96 103 109 115
16 28 35 42 49 57 63 71 77 85 92 99 106 113 120 127
0 13 15 18 21 23 25 28 31 33 36 39 41 43 46 49
2 16 19 23 25 29 32 35 35 42 45 48 51 55 58 61
4 19 23 27 31 35 39 42 46 50 54 58 61 65 69 73
6 25 27 31 36 41 45 49 54 59 63 67 72 76 81 85
4 8 25 31 36 41 46 51 57 61 67 72 77 82 87 92 97
10 29 35 41 46 52 58 63 69 75 81 87 92 98 104 109
12 32 39 45 51 58 64 71 77 83 90 96 103 109 115 122
14 35 42 49 57 63 71 77 85 92 99 106 113 120 127 134
16 39 46 54 61 69 77 85 92 100 108 115 123 131 139 146
0 27 31 35 39 42 46 50 54 58 61 65 69 73 77 81
2 31 36 41 45 49 54 59 63 67 72 76 81 85 90 94
4 36 41 46 51 57 61 67 72 77 82 87 92 97 103 108
6 41 46 52 58 63 69 75 81 87 92 98 104 109 115- 121
6 8 45 51 58 64 71 77 83 90 96 103 109 115 122 128 135
10 49 57 63 71 77 85 92 99 406 113 120 127 134 141 148
12 54 61 69 77 85 92 100 108 115 123 131 139 146 154 161
14 59 67 75 83 92 100 109 117 125 133 142 150 159 167 175
16 63 72 81 90 99 108 117 125 135 143 153 161 171 179 189
0 46 51 57 61 67 72 77 82 87 92 97 103 108 113 118
2 52 58 63 69 75 81 87 92 98 104 109 115 121 127 133
4 58 64 71 77 83 90 96 103 109 115 122 128 135 141 147
6 63 71 77 85 92 99 106 113 120 127 134 141 148 155 162
8 8 69 77 85 92 100 108 115 123 131 139 146 154 161 169 177
10 75 83 92 100 109 117 125 133 142 150 159 167 175 183 192
12 81 90 99 108 117 125 135 143 153 161 171 179 189 197 207
14 87 96 106 115 125 135 144 154 163 173 183 192 202 211 221
16 92 103 113 123 133 143 154 164 175 185 195 205 215 226 236

PCI Design Handbook/Fifth Edition 6 -5 3


Figure^6.1S.7A (continued) D esign tensile s tre n g th fo r h > hmin, <(>Fci— C a s e 2
Case 2: Free edge-on one side
<t>Pc1 -<t>2.67 + ee)(yi + 24 )
<J> = 0.85

where: x-i and yi are the dimensions of the flat


bottom of the part of the truncated pyramid.

For Case 2: x, = x + d e1, Vi = y


Note: Table values are based on
X. = I.Oandfc = 5000 psi;

x and y are t ie overall dimensions for different material properties, multiply table
(width and length) of the stud group. values by xyfc/5000

\ X1„ Design tensile strength, <>PC1 (kips)


y i \ n-
2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 "
4 in. in. \
0 5 7 9 11 13 15 17 18 20 22 24 26 28 30 32
2 7 9 11 14 17 19 22 25 27 29 32 35 37 40 42
4 8 11 15 17 21 24 27 31 33 37 40 43 47 50 53
6 9 13 17 21 25 29 33 37 41 44 48 52 56 59 63
3 8 11 16 20 25 29 33 38 43 47 51 56 61 65 69 74
10 13 18 23 28 33 39 43 49 54 59 64 69 75 79 65
12 15 20 26 32 37 43 49 55 61 67 72 78 83 89 95
14 16 23 29 35 42 48 55 61 67 74 80 87 93 99 106
16 17 25 32 39 46 53 60 67 74 81 88 95 102 109 117
0 8 10 13 15 18 21 23 25 28 31 33 36 39 41 43
2 9 13 16 19 23 25 29 32 35 39 42 45 48 51 55
4 11 15 19 23 27 31 35 39 42 46 50 54 58 61 65
6 13 18 23 27 31 36 41 45 49 54 59 63 67 72 76
4 8 15 21 25 31 36 41 46 51 57 61 67 72 77 82 87
10 17 23 29 35 41 46 52 58 63 69 75 81 87 92 98
12 19 25 32 39 45 51 58 64 71 77 83 90 96 103 109
14 21 28 35 42 49 57 63 71 77 85 92 99 106 113 120
16 23 31 39 46 54 61 69 77 85 92 100 108 115 123 131
0 15 19 23 27 31 35 39 42 46 50 54 58 61 65 69
2 18 23 27 31 36 41 45 49 54 59 63 67 72 76 81
4 21 25 31 36 41 46 51 57 61 67 72 77 82 87 92
O 23 29 35 41 46 52 58 63 69 75 81 87 92 98 104
6 8 25 32 39 45 51 58 64 71 77 83 90 96 103 109 115
10 28 35 42 49 57 63 71 77 85 92 99 106 113 120 127
12 31 39 39 54 61 69 77 85 92 100 108 115 123 131 139
14 33 42 50 59 67 75 83 92 100 109 117 125 133 142 150
16 36 45 54 63 72 81 90 99 108 117 125 135 143 153 161
0 25 31 36 41 46 51 57 61 67 72 77 82 87 92 97
2 29 35 41 46 52 58 63 69 75 81 87 92 98 104 109
4 32 39 45 51 58 64 71 77 83 90 96 103 109 115 122
6 35 42 49 57 63 71 77 85 92 99 106 ' 113 120 127 134
8 8 39 46 54 61 69 77 85 92 100 108 115 123 131 139 146
10 42 50 59 67 75 83 92 100 109 117 125 133 142 150 159
12 45 54 63 72 81 90 99 108 117 125 135 143 153 161 171
14 48 58 67 77 87 96 106 115 125 135 144 154 163 173 183
16 51 61 72 82 92 103 113 123 133 143 154 164 175 185 195

6 -5 4 PCI Design Handbook/Fifth Edition


Figure 6.15.7A (continued) Design tensile strengthTor h > hmin, Case 3

Case 3: JFree edges on Two opposite sides


<!>Pcl = (j)2,67XvC (x.My, + 2 fe)
4) = 0.85

where: x-, and are the dimensions of the fiat


bottom of the part of the truncated pyramid.
For Case 3: x, = * + xTe1 + de, y, = y
Note: Table values are based on
k = 1.0 and f i = 5000 psi;

x and y are the overall dimensions for different material properties, multiply table
(width and length) of the stud group. values by l j r c /5000

\ *1, Design tensile strength, <>Pci (Rips)

( e in. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
in. \
0 2 4 6 8 9 11 13 15 17 19 21 23 25 27 29
2 3 5 8 10 13 15 18 21 23 25 28 31 33 36 39
4 3 7 9 13 16 19 23 25 29 32 35 39 42 45 48
6 4 8 11 15 19 23 27 31 35 39 42 46 50 54 58
3 8 5 9 13 18 23 27 31 36 41 45 49 54 59 63 67
10 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77
12 6 11 17 23 29 35 41 46 52 58 63 69 75 81 87
14 7 13 19 25 32 39 45 51 58 64 71 77 83 90 96
16 7 14 21 28 35 42 49 57 63 71 77 85 92 99 106
0 3 5 8 10 13 15 18 21 23 25 28 31 33 36 39
2 3 7 9 13 16 19 23 25 29 32 35 39 42 45 48
4 4 8 11 15 19 23 27 31 35 39 42 46 50 54 58
6 5 9 13 18 23 27 31 36 41 45 49 54 59 63 67
4 8 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77
10 6 11 17 23 29 35 41 46 52 58 63 69 75 81 87
12 7 13 19 25 32 39 45 51 58 64 71 77 83 90 96
14 7 14 21 28 35 42 49 57 63 71 77 85 92 99 106
16 8 15 23 31 39 46 54 61 69 77 85 92 100 108 115
0 4 8 11 15 19 23 27 31 35 39 42 46 50 54 58
2 5 9 13 18 23 27 31 36 41 45 49 54 59 63 67
4 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77
6 6 11 17 23 29 35 41 46 52 58 63 69 75 81 87
6 8 7 13 19 25 32 39 45 51 58 64 71 77 83 90 96
10 7 14 21 28 35 42 49 57 63 71 77 85 92 99 106
12 8 15 23 31 39 46 54 61 69 77 85 92 100 108 115
14 9 17 25 33 42 50 59 67 75 83 92 to o 109 117 125
16 9 18 27 36 45 54 63 72 81 90 99 108 117 125 135
0 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77
2 6 11 17 23 29 35 41 46 52 58 63 69 75 81 87
4 7 13 19 25 32 39 45 51 58 64 71 77 83 90 96
6 7 14 21 28 35 42 49 57 63 71 77 85 92 99 106
8 8 8 15 23 31 39 46 54 61 69 77 85 92 100 108 115
10 9 17 25 33 42 50 59 67 75 83 92 100 109 117 125
12 9 18 27 36 45 54 63 72 81 90 99 108 117 125 135
14 9 19 29 39 48 58 67 77 87 96 106 115 125 135 144
16 10 21 31 41 51 61 72 82 92 103 113 123 133 143 154

PCI Design Handbook/Fifth Edition 6 -5 5


Figure 6.15.7A (continued)rDesigntensHe strength for h > hmln,<j»Pc1— Case 4
t

-----1/- 'Case 4: Free edges on two adjacent sides


cbPc1 = 4*2.67),/fT (x. + €J(yi + ^e)

r .• •-
-<l> = 0.85
where: x-. and yt arethe dimensions of the flat
y ii
• • bottom of the part of the truncated pyramid.
de3
ro r uasa m -= X + ^ yi = y + 0e3
ri
t X ( Note: Table values are based on
del l = 1.-0andfc = 5000 psi;
x and y are the overall dimensions for different material properties, multiply table
(width and length) of the stud group.
values by x/fT/SOOO

\ *1, Design tensile strength, <)>Pc1 (kips)

l e in. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
in. \
0 3 3 4 5 6 7 8 9 10 11 12 13 14 14 16
2 4 5 7 9 11 12 13 15 17 19 20 21 23 23 27
4 5 8 10 13 15 17 19 21 23 26 28 30 33 33 37
6 7 10 13 16 19 21 25 27 30 33 36 39 42 42 47
3 8 9 13 16 19 23 27 30 33 37 41 44 47 51 51 58
10 11 15 19 23 27 31 35 39 44 48 52 56 61 61 69
12 12 17 21 27 31 36 41 46 51 55 60 65 70 70 79
14 13 19 25 30 35 41 46 52 57 63 68 73 79 79 90
16 15 21 27 33 39 46 52 58 64 70 76 82 88 88 101
0 4 5 7 8 9 10 11 13 14 15 17 18 19 21 22
2 6 8 9 11 13 15 17 19 21 23 25 27 29 31 33
4 8 10 13 15 18 21 23 25 28 31 33 36 39 41 43
6 9 13 16 19 23 25 29 32 42 39 42 45 48 51 55
4 8 11 15 19 23 27 31 35 39 42 46 50 54 58 61 65
10 13 18 23 27 31 36 41 45 49 54 59 63 67 72 76
12 15 21 25 31 36 35 46 51 57 61 67 72 77 82 87
14 17 23 29 35 41 39 52 58 63 69 75 81 87 92 98
16 19 25 32 39 45 51 58 64 71 77 83 90 96 103 109
0 8 9 11 13 15 17 19 21 23 25 27 29 31 33 35
2 10 13 15 18 21 23 25 28 31 33 36 39 41 43 46
4 13 16 19 23 25 29 32 35 39 42 38 48 51 55 58
6 15 19 23 27 31 35 39 42 46 50 54 58 61 65 69
6 8 18 23 27 31 36 41 45 49 54 59 63 67 72 76 81
10 21 25 31 36 41 46 51 57 61 67 72 77 82 87 92
12 23 29 35 41 46 52 58 63 69 75 81 87 92 98 104
14 25 32 39 45 51 58 64 71 77 83 90 96 103 109 115
16 28 35 42 49 57 63 71 77 85 92 99 106 113 120 127
0 13 15 18 21 23 25 28 31 33 36 39 41 43 46 49
2 16 19 23 25 29 32 35 39 42 45 48 51 55 58 61
4 19 23 27 31 35 39 42 46 50 54 58 61 65 69 73
6 23 27 31 36 41 ' 45 49 54 59 63 67 72 76 81 85
8 8 25 31 36 41 46 51 57 55 67 72 77 82 87 92 97
10 29 35 41 46 52 58 63 69 75 87 87 92 98 104 109
12 32 39 45 51 58 64 71 77 83 92 96 103 109 115 122
14 35 42 49 57 63 71 77 85 92 99 106 113 120 127 134
16 39 46 54 61 69 77 85 92 100 108 115 123 131 139 146

6 -5 6 PCI Design Handbook/Fitth Edition


figure 6.15.7A— (continued) Designtensile strength for h > h^n3^|>FcT—f u s e 5
Case 5: Free edges on three-sidee
= 4>2.67kJ% (xl)(y1 + £e)
$ = 0.85

where: x, and yt are the dimensions of the flat


bottom of the part of the truncated pyramid.

For Case 5: x, = x -h de1 + y, = y + d e3

Note: Table values are based on


X = 1.0 and fc = 5000 psi;
d ei u e2
for different material properties, multiply table
x and y are the overall dimensions
(width and length) of the stud group. values by XJvc /5000

Design tensile strength, + P e1 (kips)

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
€, in. in. \
a 1 2 3 4 5 6 7 8 9 9 11 11 13 13 15
2 1 3 5 7 8 9 11 13 15 16 17 19 21 23 24
4 2 5 7 9 11 13 16 18 20 23 25 27 29 31 33
6 3 6 9 11 15 17 20 23 26 29 32 35 37 41 43
3 8 3 7 11 14 17 21 25 28 32 35 39 42 46 49 53
10 4 9 13 17 21 25 29 33 37 42 46 50 54 59 63
12 5 -9 15 19 24 29 33 39 43 48 53 58 63 67 72
14 5 11 17 22 27 33 38 43 49 55 60 65 71 76 82
16 6 12 18 25 31 37 43 49 55 61 67 73 79 85 91
0 1 3 4 5 7 8 9 10 11 13 14 15 17 18 19
2 2 4 6 8 9 11 13 15 17 19 21 23 25 27 29
4 3 5 8 10 13 15 18 21 23 25 28 31 33 36 39
6 3 7 9 13 16 19 23 25 29 32 35 39 42 45 48
4 8 4 8 11 15 19 23 27 31 35 39 42 46 50 54 58
10 5 9 13 18 23 27 31 36 41 45 49 54 59 63 67
12 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77
14 6 11 17 23 29 35 41 46 52 58 63 69 75 81 87
16 7 13 19 25 32 39 45 51 58 64 71 77 83 90 96
0 2 4 6 8 9 11 13 15 17 19 21 23 25 27 29
2 3 5 8 10 13 15 18 21 23 25 28 31 33 36 39
4 3 7 9 13 16 19 23 25 29 32 35 39 42 45 48
6 4 8 11 15 19 23 27 31 35 39 42 46 50 54 58
6 8 5 9 13 18 23 27 31 36 41 45 49 54 59 63 67
10 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77
12 6 11 17 23 29 35 41 46 52 58 63 . 69 : 75 81 87
14 7 13 19 25 32 39 45 51 58 64 71 77 83 90 96
16 7 14 21 28 35 42 49 57 63 71 77 B5 92 99 106
0 3 5 8 10 13 15 18 21 23 25 28 31 33 36 39
2 3 7 9 13 16 19 23 25 29 32 35 39 42 45 48
4 4 8 11 15 19 23 27 30 35 39 42 46 50 54 58
6 5 9 13 18 23 27 31 36 41 45 49 54 59 63 “: 67
8 8 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77
10 6 11 17 23 29 35 41 46 52 58 63 69 75 81 87
12 7 13 19 25 32 39 45 51 58 64 71 77 83 90 96
14 7 14 21 28 35 42 49 57 63 71 77 85 92 99 106
16 8 15 23 31 39 46 54 61 69 77 85 92 100 108 115

PCI Design Handbook/Fifth Edition 6 -5 7


F ig u re 6 .1 5 .7 A (c o n tin u e d ) D e s ig n te n s rle s tre n g th f o r t r > t w . <t>Pd— C a s e 6

C a s e ^ : F re e e d g e s on fo u r a d ja c e n t s id e s

4>PC-1 = $2.67kJ% (x,)(y i)


de4 • • d> = 0.85
where: x, and y, are the dimensions o f the flat bottom
y| of the part of the truncated pyramid.
• • For Case 6; x, = x + d e1 + d e3 y, = y + -d e3 + de4
de3
Note: Table values are based on
• x » \ = 1.0 and ft = 5000 psi;
del d e2 for different material properties, multiply table
x and y are the overall dimensions values by X^fc /5000
(width and length) of the stud group.

\ Xt, Design tensile strength, <j>Pci (kips)


yi\ n- 2 4 6 8 10 12 14 16 18 20 22 24 26 28
l« in. 30
in. \
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 1 1 2 3 3 4 5 5 6 7 7 8 9 9 9
4 1 3 4 5 7 8 9 10 11 13 14 15 17 18 19
6 2 4 6 8 9 11 13 15 17 19 21 23 25 27 29
3 8 3 5 8 10 13 15 18 21 23 25 29 31 33 36 39
10 3 7 9 13 16 19 23 25 29 32 35 39 42 45 48
12 4 8 11 15 19 23 27 31 35 39 42 46 50 54 58
14 5 9 13 18 23 27 31 36 41 45 49 54 59 63 67
16 5 10 15 21 25 31 36 41 46 51 35 61 67 72 77
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 1 1 2 3 3 4 5 5 6 7 7 8 9 9 9
4 1 3 4 5 7 8 9 10 11 13 14 15 17 18 19
6 2 4 6 8 9 11 13 15 17 19 21 23 25 27 29
4 8 3 5 8 10 13 15 18 21 23 25 28 31 33 36 39
10 3 7 9 13 16 19 23 25 29 32 35 39 42 45 48
12 4 8 11 15 19 23 27 31 35 39 42 46 50 54 58
14 5 9 13 18 23 27 31 36 41 45 49 54 59 63 67
16 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 1 1 2 3 3 4 5 5 6 7 7 8 9 9 9
4 1 3 4 5 7 8 9 10 11 13 14 15 17 18 19
6 2 4 6 8 9 11 13 15 17 19 21 23 25 27 29
6 8 3 5 8 10 13 15 18 21 23 25 28 31 33 36 39
10 3 7 9 13 16 19 23 25 29 32 35 39 42 45 48
12 4 8 11 15 19 23 27 31 35 39 42 46 50 54 58
14 5 9 13 23 27 31 36 41 45 49 54 59 63 67
18
16 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 1 1 2 3 3 4 5 5 6 7 7 8 9 9 9
4 1 3 4 5 7 8 9 10 11 13 14 15 17 18 19
6 2 4 6 8 9 11 13 15 17 19 21 23 25 27 29
8 8 3 5 8 10 13 15 18 21 23 25 28 31 33 36 39
10 3 7 9 13 16 19 23 25 29 32 35 39 42 45 48
12 4 8 11 15 19 23 27 31 35 39 42 46 50 54 58
14 5 9 13 18 23 27 31 36 41 45 49 54 59 . 63 67
16 5 10 15 21 25 31 36 41 46 51 57 61 67 72 77

6 -5 8 PCI Design Handbook/Fifth Edition


Figure 6.15.7B Minimum member thickness^ortruncated pyramid failure—stud groups

Minimum thickness (see Fig. 6.5.6)


hmin= (z + 2£e)/2

where:
z = lesser of x and y
y
i e = embedment length

Minimum Thickness > hmin 0^*)


\ X*
y \in .
i t in. 2 4 6 8 10 12 14 16 18
in. \
0 3 3 3 3 3 3 3 3 3
2 4 4 4 4 4 4 4 4 4
4 4 5 5 5 5 5 5 5 5
3 6 4 5 6 6 6 6 6 6 6
8 4 5 6 7 7 7 7 7 7
10 4 5 6 7 8 8 8 8 8
12 4 5 6 7 8 9 9 9 9
0 4 4 4 4 4 4 4 4 4
2 5 5 5 5 5 5 5 5 5
4 5 6 6 6 6 6 6 6 6
4 6 5 6 7 7 7 7 7 7 7
8 5 6 7 8 8 8 8 8 8
10 5 6 7 8 9 9 9 9 9
12 5 6 7 8 9 10 10 10 10
0 6 6 6 6 6 6 6 6 6
2 7 7 7 7 7 7 7 7 7
4 7 8 8 8 8 8 8 8 8
6 6 7 8 9 9 9 9 9 9 9
8 7 8 9 10 10 10 10 10 10
10 7 8 9 10 11 11 11 11 11
12 7 8 9 10 11 12 12 12 12
0 8 8 8 8 8 8 8 8 8
2 9 9 9 9 9 9 9 9 9
4 9 10 10 10 10 10 10 10 10
8 6 9 10 11 11 11 11 11 11 11
8 9 10 11 12 12 12 12 12 12
10 9 10 11 12 13 13 13 13 13
12 9 10 11 12 13 14 14 14 14
0 10 10 10 10 10 10 10 10 10
2 11 11 11 11 11 11 11 11 11
4 11 12 12 12 12 12 12 12 12
10 6 11 12 13 13 13 13 13 13 13
8 11 12 13 14 14 14 14 14 14
10 11 12 13 14 15 15 15 15 15
12 11 12 13 14 15 16 16 16 16
0 12 12 12 12 12 12 12 12 12
2 13 13 13 13 13 13 13 13 13
4 13 14 14 14 14 14 14 14 14
12 6 13 14 15 15 15 15 15 15 15
8 13 14 15 16 16 16 16 16 16
10 13 14 15 16 17 17 17 17 17
12 13 14 15 16 17 18 18 18 18

PCI Design Handbook/Fifth Edition 6 -5 9


Figure 6.15.7C Reduction in design tensile strength ousted groups-for h < iv,ln

(j>Pc2 = q z is r k j-fTlx - 2(h - € e)][y - 2(h - €e)] 4-

where $ = 0.85: • •

x and y = overall dimensk>ns(width and length)of stud groups


h = member thickness
♦ •-
= embedment length -V
Note: For h > hmin, (pPcZ = O.See Fig. 6.t57.B for hmin values

\ X’ I )esign tensile strencJth, <(»Pc2 (kips)


fe- h y \jn -
in. 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30
in. \
0 0 0 0 0 0 0 . 0 0 0 0 0 0 0 0 T
2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
4 0 1 1 2 3 3 4 5 5 6 7 7 8 9 9
6 0 1 3 4 5 7 8 9 10 11 13 14 15 17 18
1 8 0 2 4 6 8 9 11 13 15 17 19 21 23 25 27
10 0 3 5 8 10 13 15 18 21 23 25 28 31 33 36
12 0 3 7 9 13 16 19 23 25 29 32 35 39 42 45
14 0 4 8 11 15 19 23 27 31 35 39 42 46 50 54
16 0 5 9 13 18 23 27 31 36 41 45 49 54 59 63
6 1 0 6 0 0 0 0 0 0 0 b 0 b b 0
2 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0
4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
6 0 0 1 1 2 3 3 4 5 5 6 7 7 8 9
2 8 0 0 1 3 4 5 7 8 9 10 11 13 14 15 17
10 0 0 2 4 6 8 9 11 13 15 17 19 21 23 25
12 0 0 3 5 8 10 13 15 18 21 23 25 28 31 33
14 0 0 3 7 9 13 16 19 23 25 29 32 35 39 42
16 0 0 4 8 11 15 19 23 27 31 35 39 42 46 50
b 4 2 b 0 0 0 0 0 & <5 0 0 0 0 b
2 3 1 0 0 0 0 0 0 0 0 0 0 0 0 0
4 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0
6 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
3 8 0 0 0 1 1 2 3 3 4 5 5 6 7 7 - 8
10 0 0 0 1 3 4 5 7 8 9 10 11 13 14 15
12 0 0 0 2 4 6 8 9 11 13 15 17 19 21 23
14 0 0 0 3 5 8 10 13 15 18 21 23 25 28 31
16 0 0 0 3 7 9 13 16 19 23 25 29 32 35 39
6 8 5 3 6 0 0 6 0 & b 0 0 0 0 b
2 6 4 2 0 0 0 0 0 0 0 0 0 0 0 0
4 4 3 1 0 0 0 0 0 0 0 0 0 0 0 0
6 2 1 1 0 0 0 0 0 0 0 0 0 0 0 0
4 8 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
10 0 0 0 0 1 1 2 3 3 4 5 5 6 7 7
12 0 0 0 0 1 3 4 5 7 8 9 10 11 13 14
14 0 0 0 0 2 4 6 8 9 11 13 15 17 19 21
16 0 0 0 0 3 5 8 10 13 15 18 21 23 25 28
& 13 9 7 3 0 0 0 0 0 b b 0 0 b 0
2 10 8 5 3 0 0 0 0 0 0 0 0 0 0 0
4 8 6 4 2 0 0 0 0 0 0 0 0 0 0 0
6 5 4 3 1 0 0 0 0 0 0 0 0 0 0 0
5 8 3 2 1 1 0 0 0 0 0 0 0 0 0 0 0
10 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
12 0 0 0 0 0 1 1 2 3 3 4 5 5 6 7
14 0 0 0 0 0 1 3 4 5 7 8 9 10 11 13
16 0 0 0 0 0 2 4 6 8 9 11 13 15 17 19

6 -6 0 PCI Design Handbook/Fifth Edition


Figure^.1 5.8 Shear strength of welded headed studs

I—Desigrr shear strength limited by concrete:


4>Vc —<|>Vi CwCtCc (Eq. 6.5.7)
where:
4>Vi = <j)T2.5de5 \ J T (Eq. 6.5.8)

Gw =
(1 + 3.5de) -

c, =-
i k s 10

Cc = 0.4 + 0.7( i < 1.0

Table A gives values for <)} = 0.85

Where: ns = number of studs in back row; see figure for notation

H— Design shear strength limited by steel:


cjjVy = (31,800d£)n (Eq. 6.5.12a)
Table B gives value for n = 1, <j> = 0.9

Table A— Vi , kips

fc , psi 4000 5000 6000 7000 8000

k 1.0 0.85 1.0 0.85 1.0 0.85 1.0 0.85 1.0 0.85
d„ in. ,

2 1.90 1.62 2.12 1.81 2.33 1.98 2.51 2.14 2.69 2.29

3 3.49 2.97 3.90 3.31 4.26 3.63 4.62 3.82 4.94 4.20

4 5.38 4.57 6.00 5.11 6.58 5.59 7.11 6.04 7.60 6.46

5 7.51 6.38 8.39 7.14 9.19 7.82 9.94 8.45 10.62 9.03

6 9.88 8.40 11.04 9.39 12.09 10.29 13.08 11.11 13.97 11.87

7 12.45 10.58 13.91 11.82 15.24 12.95 16.46 13.99 17.60 14.96

8 15.20 12.82 16.99 14.44 18.61 15.81 20.12 17.08 21.50 18.27

9 18.14 15.44 20.28 17.24 22.21 18.88 23.99 20.40 25.65 21.80

10 21.25 18.06 23.75 20.18 26.01 22.11 28.11 23.88 30.04 25.53

11 24.52 20.84 27.41 23.30 30.03 25.52 32.43 27.57 34.67 29.47

12 27.94 23.74 31.22 26.53 34.20 29.07 36.94 31.40 39.49 33.67
Table B—^Vy, kips

Diameter, in. 1/4 1/2 % 3/« 1h

4>Vy 2.0 4.5 8.0 12.4 17.9 24.4

PCI Design Handbook/Fitth Edition 6 -6 1


Figure 6.15.9 Viewable loacteron bolts3
- -
A-,36 A-307
Bolt. Tension (kips) Shear11kips Tension (kips) Shearb kips
dram A, in.2
fin.) Nominal Design Service Design - Service Design Service Design Service
Vt 0.196 6.4 3.7 3.3 20 6.6 3.9 3.2 2.0

5/e 0.307 10.0 5.9 5.2 3.0 10.4 6.1 50 3.1

% 0.442 14.4 8.4 7.5 4.4 14.9 8.8 7.2 4.4


7/e 0.601 19.6 11.5 10.2 ; 6.0 20.3 12.0 . 9.7 6.0

1 0.785 25.6 15.0 13.3 7.8 26.5 15.7 12.7 7.9

11/4 1.227 40.0 23.4 20.8 12.1 41.4 24.5 19.9 12.3

V/i 1.767 57.6 33.7 30.0 170 59.7 35.3 28.6 17.7

2 3.142 102.4 60.0 53.4 31.1 106.2 62.8 50.9 31.4


a. AISC Allowable Stress Design [12] or AISC Load and Resistance Factor Design [13]. Seelhese manuals for shear-tension interaction.
b. For threads included in shear plane.

Figure 6.15.10 High strength coil bolt and coil threaded rod selection chart

Coil Safe Working Load9 Minimum


Minimum Tonsile Yield
Rod Coil
Root Area Stress Stress
Dia. Tension Shear Penetration
(in2) (psi) (psi)
(in.) (lb) (lb) (in.)
y2b 9000 6000 0.1385 130,000 110,000 2
3/4b 18000 12000 0.3079 117,000 100,000 2V4

1b 38000 25,300 0.5410 140,000 120,000 21/s

1 1/4 b 58,000 37,500 0.8161 123,000 105,000 21/2

11/2 88,000 45,300 1.3892 98,000 85,000 3


a. Approximate factor of safety is 2 to 1.
b. Strength requirements similar to ASTM A 325.

Fig. 6.15.11 Capacity of wire used in concrete inserts


Leg w ire diameter Wire classification Wire grade Approximate mini­ Approximate mini­
(in.) mum yield srength mum shear strength
(ASTM)
(ib) (Ib)

0.218 Low carbon 1006 or 1008 2,400 1,850


0.223 Medium high carbon 1030 3,800 3,000
0.240 Low carbon 1006 or 1008 2,500 2,050
0.243 Medium high carbon 1038 6,000 4,650
0.262 Low carbon 1006 or 1008 3,200 2,750
0.306 Low carbon 1006 or 1008 3,300 2,800
0.306 Medium high carbon 1038 6,500 4,950
0.375 Medium low carbon 1018 7,300 6,350
0.440 Medium high carbon 1035 or 1038 13,500 10,650

6 -6 2 PCI Design Handbook/Fifth Edition


Figure 6.15.12 Plastic section moduli and shape factors

SECTION PLASTIC MODULUS, Z*, in.3 SHAPE'FACTOft

--------- h bhf
1.5
A

x-x AXIS
1.12 (APPROX.)
bt(h - t) + ^ ( h - 2t)‘

y-yAXIS
1.55 (APPROX.)
b2t (h - 2t)w2
2 + 4

11 (average)

r w(h - 2t)‘:
bt(h - 1) + 1.12 (APPROX.)
w-

hf
1.70
6

16
6 - K f 3ji
- (1 - B

th2 for t < < h 1.27 for t < < h

w
h SEE
FOOT­ bhf
4 1.12 (APPROX.) FOR THIN WALLS
NOTE

bhf
12

For TS shapes, refer to AISC-LRFD Manual13for Zs values.

PCt Design Handbook/Frfth Edition 6 -6 3


Figure 6.15.13 Shear strength o f connection angles

' E’ - 6'5'15
<t> = 0.90
bn = net length of angle, in.
Fy = yield strength o f angle steel = 36,000 psi

Vu = <t>V„, 1b. per inch of length

Angle
thickness ev = W e„ = 1" ev = 2" e„ = 21/2"

a>
il
t

5/l6 " 1055 791 527 396 316

3/e" 1519 1139 759 570 456

W 2067 1550 1034 775 620

Vs" 2700 2025 1350 1013 810

S
/16" 3417 2563 1709 1281 1025

Ve" 4219 3164 2109 1582 1266

Fig. 6.15.14 Axial strength of connection angles

MNug
t = Eq. 6.5.17
ci>Fybn

<i> = 0.90
bn = net length of angle, in.
Fy = yield strength of angle steel = 36,000 psi

Nu = <t>Nn, lb. per inch of length


Angle
et
00

= 5" 6" e t = 7"


II

thickness =

t g = 3" g = 4" g = 5" g = 6"

6/ l 6 264 198

3/ 8 380 285 228

7/ l 6 517 388 310 258

1/ 2 675 506 405 338

S/ 1 6 854 641 513 427

5/e 1055 791 633 527

6 -6 4 PCI Design Handbook/Frfth Edition


Figure 6.15.15 Column base plate thickness requirements

Thickness required for concrete bearing

fbu
•0
Xo = 4" Xo = 5"
£
ll

(psi)
500 5A 3/4 1 i

1000 U 1 13/4

1500 1 VA 1%

2000 1Vi 1Vi VA

2500 11/4 va 2

3000 1% 1% 21/4
i
3500 VA 2 2'A
XcOfXt

4000 1% 2'A 25/e


^D . If
^ S S B p *

EXTERNAL ANCHOR BOLTS INTERNAL ANCHOR BOLTS

Thickness required for bolt loading

Tension on external anchor bolts

No. & diameter of A-36 or A-307 anchor bolts per side


D
(in.) 2 - 3/4" 2 -3 /4 " 2 -1 " 2 -1 " 2-1 'A " 2 - 1 'A " 2 -1 W 2-1 Vi"
X, = 3.75" xt = 4.25" X, = 3.75" X, = 4.25" X, ■ 3.75" x, = 4.25" x, = 3.75" X, =4.25"
12 1 11/fe 1% VA 13/4 VA 2% 2Vi
14 1 1 m VA 1% VA 2 2Vi
16 7/s 1 VA VA VA VA VA 2
18 7A 1 VA VA VA VA VA VA

20 7A 7A VA VA VA VA 15/6 VA

22 3/4 % 1 VA VA VA VA VA

24 3/4 3/4 1 VA VA VA VA VA

26 3/4 3/4 1 1 VA VA VA VA

28 3/4 3/4 1 1 VA VA VA VA

Compression on anchor bolts or tension on internal anchor bolts

No. & diameter of A-36 or A-307 anchor bolts per side


D
( in .) 2 - 3/ 4 " 2 - 3/ 4 " 2- 1 " 2- 1 " 2-1 'A " 2 - 1 V4 " 2 -V A " 2 -1 V 2 "
to

Xc =
ro

xe = 2 .0 " x c = 2 .0 " Xc =
II

Xe =
X

1 .5 " 1 .5 " 1 .5 " xc = 2 .0 "


II

0X

0
0

12 3/4 3/4 7A 1 1 1/4 1% 1% 1%


14 3/4 3/4 7A 1 1 VA VA VA

16 3/4 3/4 3/4 7A 1 VA VA VA

18 3/4 3/4 3/4 % 1 VA VA VA

20 3/4 3/4 3/4 7A 7A 1 VA VA

22 3/4 3/4 3/4 3/4 7A 1 1 VA

24 % 3/4 3/4 3/4 7A 1 1 VA


26 3/4 3/4 3/4 3/4 3/4 7A 1 VA

28 3/4 % 3/4 3/4 3/4 7A 7A 1

PCI Design Handbook/Rfth Edition 6 -6 5


F ig u re 6.1S.t6 Design-strength o fc o n c re te brackets, corbels o r haunches

Design strength by Eqs. 6.8.3 or 6.&4


for following, criteria:
r 4>Vn < <(>1000X2bd = PROJECTION

%
= 60,000 psi
— *—
Nu = 0.2 Vu
b = width of bearing, in.
d = h-1.25-(h in inches)

$ = 0.85
\ _______
a = 3/4 ( P As

X = 1.0 (normal weight concrete) Vu


— t—

(The design strength value listed in the table


immediately above a blank entry corresponds to this
limit. The blank entrie(s) in a given column will have this
same limiting value.)

Values of <t>Vn (kips)

€p(in.) 4 6 8

\ h 14 18 20 22
b 4 6 8 10 12 14 16 18 6 8 10 12 14 16 18 20 8 10 12 16

2 -# 4 14 23 29 35 40 44 47 48 17 22 27 31 35 38 41 0 18 22 26 29 32 35 0 0
2 -# 5 24 34 45 55 59 62 65 24 34 42 49 55 60 65 67 28 34 40 45 50 55 59 62
6
2 -# 6 65 75 81 45 55 65 75 81 84 34 45 55 65 72 79 84 87
2 -# 7 85 85 96 75 85 96 106
2 -# 4 14 23 29 35 40 44 0 0 17 22 27 31 35 0 0 0 18 22 26 29 0 0 0 0
2 -# 5 19 32 46 55 62 65 69 72 26 35 42 49 55 60 65 69 28 34 40 45 50 55 59 62
2 -# 6 60 73 82 86 90 32 46 60 70 79 86 90 94 40 49 58 65 72 79 84 90
8
2 —# 7 87 100 109 73 87 100 109 114 60 73 87 98 107 114 118
2 -# 8 114 114 128 100 114 128 139
2 -# 9 141
2 -# 4 14 23 29 35 0 0 0 0 17 22 27 0 0 0 0 0 18 22 0 0 0 0 0 0
2 -# 5 23 35 46 55 62 69 74 77 26 35 42 49 55 60 65 0 28 34 40 45 50 55 0 0
2 -# 6 40 57 74 84 89 94 98 38 50 61 70 79 86 93 99 40 49 58 65 72 79 84 90
10
2 -# 7 91 108 114 119 40 57 74 91 107 114 119 124 54 67 78 89 98 107 115 122
2 -# 8 125 140 108 125 140 146 57 74 91 108 125 140 1 46 152
2 -# 9 142 142 159 142 159 175
2 -*4 14 23 29 0 0 0 0 0 17 22 0 0 0 0 0 0 18 0 0 0 0 0 0 0
2 —# 5 23 35 46 55 62 69 0 0 26 35 42 49 55 0 0 0 28 34 40 45 0 0 0 0
2 -# 6 28 48 66 79 90 96 100 105 38 50 61 70 79 86 93 99 40 49 58 65 72 79 84 90
2 —# 7 69 89 109 116 122 128 48 68 83 96 107 117 127 133 54 67 78 89 98 107 115 122
2 -# 8 110 130 144 151 69 89 10 130 144 151 157 69 88 103 116 128 140 150 160
2 -# 9 150 171 150 171 181 89 110 130 150 171 181 188
12
3 -# 4 22 34 44 53 60 66 0 0 25 33 40 47 52 0 0 0 27 33 38 44 0 0 0 o
3 -# 5 28 48 69 82 93 98 103 107 39 52 63 73 82 90 97 104 42 51 60 68 75 82 88 94
3 -# 6 89 110 123 130 136 48 69 89 105 118 129 136 141 60 74 87 98 108 118 127 135
3 -# 7 130 150 164 110 130 150 164 171 69 89 1 10 130 148 161 171 177
3 -# 8 171 171 191 150 171 191 209
3 -# 9 212

6 -6 6 PCI Design Handbook/Fifth Edition


figure 6 .1 5 .i6 D e s ig n strength o f concrete brackets, corbels or launches (continued)

Values of $V„ (kips)

f p(in.) 4 6 8
h 4 6 8 10 12 14 16 18 6 8 10 12 14 16-18 20 8 10 12 14 16 18 20 22
b
2 -# 4 14 23 29 0 0 0 0 0 17 22 0 0 0 0 0 0 18 0 0 0 0 0 0 0
2 -# 5 23 35 46 55 62 0 0 0 26 35 42 49 0 0 0 0 28 34 40 0 0 0 0 0
2 -# 6 33 51 66 79 90 99 106 110 38 50 61 70 79 86 93 0 40 49 58 65 72 79 0 0
2 -# 7 57 80 104 116 123 129 135 51 68 83 96 107 117 127 135 54 67 78 89 98 107 115 122
2 -# 8 128 145 153 160 57 8 0 104 125 140 153 160 166 71 88 103 116 1 2 3 140 150 160
2 -# 9 152 176 185 128 152 176 185 192 80 104 128 147 163 177 190 199
14
3 -# 4 22 34 44 53 60 0 0 0 25 33 40 47 9 0 0 0 27 33 38 0 0 0 0 0
3 - #5 33 53 69 82 93 103 109 113 39 52 63 73 82 90 97 0 42 51 60 68 75 82 0 0
3 -# 6 57 80 104 123 131 137 143 56 75 91 105 1 1 8 129 140 149 60 74 87 98 108 118 127 135
3 -# 7 128 152 166 174 57 80 104 128 152 166 174 181 80 101 118 133 148 161 173 184
3 -# 8 176 199 176 199 213 104 128 152 176 199 213 222
3 -# 9 22 3 223 247
2 -# 6 33 51 66 79 90 99 107 0 38 50 61 70 79 86 0 0 40 49 58 65 72 0 0 0
2 -# 7 37 65 90 107 122 129 136 141 51 68 83 96 107 117 127 135 54 67 78 89 98 107 115 122
2 -# 8 92 119 144 153 161 168 65 89 108 125 140 153 166 174 71 88 103 116 128 140 150 160
2 -# 9 146 173 186 194 92 1 19 146 173 186 194 202 90 111 130 147 163 177 190 202
3 -# 6 130 137 1 4 4 151 75 91 105 118 129 140 149 60 74 87 98 108 118 127 135
3 -# 7 146 166 1 75 183 92 119 143 161 175 183 190 82 101 118 133 148 161 173 184
16
3 -# 8 173 201 216 146 173 201 216 225 92 119 146 173 193 210 225 233
3 -# 9 228 228 255 201 228 255 269
4 -# 6 164 173 181 140 157 173 181 188 80 99 115 131 144 157 169 180
4—#7 201 219 146 173 201 219 228 92 119 146 173 197 214 228 236
4 -# 8 228 228 255 201 2 28 255 278
4 -# 9 262
2 -# 6 33 51 66 79 90 99 0 0 38 50 61 70 79 0 0 0 40 49 58 65 6 0 0 0
2 -# 7 42 69 90 107 122 135 141 147 51 68 83 96 107 117 127 135 54 67 78 89 98 107 115 0
2 -# 8 73 103 134 151 116 168 175 67 89 108 125 140 153 166 177 71 88 103 116 128 140 150 160
2 -# 9 164 185 194 203 73 103 134 158 177 194 203 211 90 111 130 147 163 177 190 202
3 -# 6 99 118 135 143 151 157 56 75 91 105 118 129 140 149 60 74 87 98 108 118 127 135
3 -# 7 103 134 164 174 183 191 73 102 124 143 161 176 190 199 82 101 118 133 148 161 173 184
lo
3 -# 8 195 216 226 103 134 164 195 216 226 235 103 131 154 174 193 210 225 240
3 -# 9 226 256 226 256 272 134 164 195 226 256 272 282
4 -# 6 162 172 181 189 100 121 140 157 1 73 186 196 80 99 115 131 144 157 169 180
4 -# 7 164 195 2 1 3 2 2 9 103 134 164 195 219 229 238 103 134 157 178 197 214 230 245
4 -# 8 226 256 226 2 5 6 281 164 195 226 256 281 291
4 -# 9 287 287 317
2 -# 6 33 51 66 79 90 0 0 0 38 50 61 70 8 0 0 0 40 49 58 0 0 0 0 0
2 -# 7 44 69 90 107 122 135 146 153 51 68 83 96 107 117 127“ 0 54 67 78 89 98 107 0 0
2 -# 8 47 81 115 140 157 166 174 182 67 89 108 125 140 153 166 177 71 88 103 116 128 140 150 160
2 -# 9 149 181 192 202 211 81 112 136 158 177 194 210 220 90 111 130 147 163 177 190 202
3 -# 6 76 99 118 135 149 156 163 56 75 91 105 118 129 140 0 60 74 87 98 108 118 0 0
3 -# 7 81 115 149 171 181 190 199 77 102 124 143 161 176 190 203 82 101 118 133 148 161 173 184
20
3 -# 8 183 213 225 235 81 115 149 183 210 225 235 245 107 131 154 174 193 210 225 240
3 -# 9 217 251 272 217 251 272 283 115 149 183 217 244 265 283 294
4 -# 6 169 179 188 196 75 100 121 140 157 173 186 199 80 99 115 131 144 157 169 180
4 -# 7 183 216 228 238 81 115 149 183 214 228 238 248 109 134 157 178 197 214 230 245
4 -# 8 217 251 281 217 251 281 292 115 149 183 217 251 280 292 303
4 -# 9 285 285 319 285 319 330

PCI Design Handbook/Fifth Edition 6 -6 7


Figure 6.15.16 Design strength of concretebrackets, corbels or haunches ^continued)
- -
Values of (|>V„ (kips)

M 'n - ) - 10 12 14

b 10 12 14 16 16 20 22 24 12 14 16 18 20 22 24 26 14 16 m 20 22 24 26 28
As^ s,\ s
2 -# 4 18 22 25 28 30 0 0 0 19 22 24 27 0 0 0 0 19 22 24 0 0 0 0 0
2 -# 5 29 34 39 43 47 51 55 58 30 34 38 42 45 48 52 55 30 34 37 40 44 47 49 52
2 -# 6 42 49 56 62 68 73 79 83 42 49 54 60 65 70 74 79 43 49 54 58 63 67 71 75
6
2 -# 7 45 55 65 75 85 96 106 109 55 65 74 82 88 95 101 107 59 66 73 79 85 91 97 102
2 -# 8 116 75 85 9 6 106 116 126 65 75 85 96 109 116 126 133
2 -# 9 136
i-H 18 22 25 0 0 0 0 0 19 22 0 0 0 0 0 0 19 0 0 0 0 0 0 0
2 -# 5 29 34 39 43 47 51 55 0 30 34 38 42 45 48 0 0 30 34 37 40 44 0- 0 0
2 -# 6 42 49 56 62 68 73 79 83 42 49 54 60 65 70 74 79 43 49 54 58 63 67 71 75
8
2 -# 7 56 67 76 85 93 100 107 113 58 66 74 82 88 95 101 107 59 66 73 79 85 91 9 7 102
2 -# 8 60 73 87 100 114 128 139 144 73 87 97 106 116 124 132 140 77 86 95 104 112 119 126 133
2 -# 9 141 155 100 114 128 141 155 168 87 100 114 128 141 151 160 168
2 -# 4 18 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0"
2 -# 5 29 34 39 43 47 0 0 0 30 34 38 42 0 0 0 0 30 34 37 0 0 0 0 0
2 -# 6 42 49 56 62 68 73 79 83 42 49 54 60 65 70 74 79 43 49 54 58 63 67 71 0
10
2 -# 7 56 67 76 85 93 100 107 113 58 66 74 82 88 95 101 107 59 66 73 79 85 91 97 102
2 -# 8 74 87 99 110 121 131 140 148 76 87 97 106 116 124 132 140 77 86 95 104 112 119 126 133
2 -# 9 91 108 125 142 159 175 181 91 108 123 135 146 157 167 177 97 109 120 131 141 151 160 168
2 -^ 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 -# 5 29 34 39 0 0 0 0 0 30 34 0 0 0 0 0 0 30 0 0 0 0 0 0 0
2 -# 6 42 49 56 62 68 73 79 0 42 49 54 60 65 70 0 0 43 49 54 58 63 0 0 0
2 -# 7 56 67 76 85 93 100 107 113 58 66 74 82 88 95 101 107 59 66 73 79 85 91 97 102
2 -# 8 74 87 99 110 121 131 140 148 76 87 97 106 116 124 132 140 77 86 95 104 112 119 126 133
2 -# 9 89 110 126 140 153 165 177 188 96 110 123 135 146 157 167 177 97 109 120 131 141 151 160 168
12
3 -# 4 28 33 37 0 0 0 0 0 28 32 0 0 0 0 0 0 29 0 0 0 0 0 0 0
3 -# 5 43 51 58 65 71 77 82 0 44 51 57 62 68 73 0 0 45 51 56 61 65 0 0 0
3 —#6 62 73 84 93 102 110 118 125 64 73 82 90 97 105 111 118 65 73 80 87 94 101 107 112
3 -# 7 85 100 114 127 139 150 160 170 87 99 111 122 133 142 152 160 88 99 109 119 128 137 145 153
3 -# 8 89 110 130 150 171 191 209 216 110 130 145 160 173 186 198 209 115 129 143 155 167 179 189 200
3 -# 9 212 232 150 171 191 212 232 252 130 150 171 191 212 226 240 253
2 -# 4 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 -# 5 29 34 0 0 0 0 0 0 30 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 -# 6 42 49 56 62 68 0 0 0 42 49 54 60 0 0 0 0 43 49 54 0 0 0 0 0
2 -# 7 56 67 76 85 93 100 107 113 58 66 74 82 88 95 101 0 59 66 73 79 85 91 0 0
2 -# 8 74 87 99 110 121 131 140 148 76 87 97 106 116 124 132 140 77 86 95 104 112 119 126 133
2 -# 9 93 110 126 140 153 165 177 188 96 110 123 135 146 157 167 177 97 109 120 131 141 151 160 168
14
3 -# 4 28 33 0 0 0 0 0 0 28 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
3 -# 5 43 51 58 65 71 0 0 0 44 51 57 62 0 0 0 0 45 51 56 0 0 0 0 0
3 -# 6 62 73 84 93 102 110 118 125 64 73 82 90 97 105 111 118 65 73 80 87 94 101 107 112
3—#7 85 100 114 127 139 150 160 170 87 99 111 122 133 142 152 160 88 99 109 119 128 137 145 153
3 -# 8 104 128 149 166 181 196 210 222 113 130 145 160 173 186 198 209 115 129 143 155 167 179 189 200
3 -# 9 152 176 199 223 247 265 128 152 176 199 219 236 253 265 146 164 181 197 212 226 240 253
2 -# 6 42 49 56 62 0 0 0 0 42 49 54 0 0 0 0 0 43 49 0 0 0 0 0 0
2 -# 7 56 67 76 85 93 100 107 0 58 66 74 82 88 95 0 0 59 66 73 79 85 0 0 0
2 -# 8 74 87 99 110 121 131 140 148 76 87 97 106 116 124 132 140 77 86 95 104 112 119 126 133
2 -# 9 93 110 126 140 153 165 177 188 96 110 123 135 146 157 167 177 97 109 120 131 141 151 160 168
3 -# 6 62 73 84 93 102 110 118 125 64 73 82 90 97 105 111 0 65 73 80 87 94 101 0 0
3 -# 7 85 100 114 127 139 150 160 170 87 99 111 122 133 142 152 160 88 99 109 119 128 137 145 153
16
3 -# 8 110 130 149 166 181 196 210 222 113 130 145 160 173 186 198 209 115 129 143 155 167 179 189 200
3 -# 9 119 146 173 201 228 248 265 279 143 164 184 202 219 236 251 265 146 164 181 197 212 226 240 253
4 -# 6 83 9 8 112 124 136 147 157 167 85 97 109 120 130 140 149 157 86 97 107 117 126 134 142 150
4 -# 7 113 133 152 169 185 200 214 227 116 133 148 163 177 190 202 214 118 132 146 159 171 182 193 204
4 -# 8 119 143 173 201 228 255 278 288 146 173 194 213 231 248 264 279 154 173 190 207 223 238 253 266
4 -# 9 282 309 202 228 255 282 309 337 173 201 228 255 282 302 320 337

6 -6 8 PCI Design Handbook/Fifth Edition


Figure 6.15.16 Design^strength of concrete brackets, corbels^ or haunches (continued)

Values of ^Vn tkips)

p(in.) 10 ^2 14

10 12 14 i 6 16 20 22 24 12 14 1$ 18 20 22 24 26 14 16 18 20 22 24 26 28
42 49 56 0 0 0 0 0 42 49 0 0 0 0 0 43
0 0 0 O 0 0 0 0
56 67 76 85 93 100 0 0 58 66 74 82 88 0 0 59 66 73
0 79 0 0 0 0
74 87 99 110 121 131 140 148 76 87 97 106 116 124 132 140 77 86 95 104 102 119 126 0
93 110 126 140 153 165 177 188 96 110 123 135 146 157 167 177 97 109 120 131 141 151 160 168
62 73 84 93 102 110 118 0 64 73 82 90 97 105 0 0 65 73 80 87 94 0 0 0
85 100 114 127 139 150 160 170 87 99 111 122 133 142 152 160 88 99 109 119 128 137 145 153
18
111 130 149 166 181 196 210 222 113 130 145 160 173 186 198 209 115 129 143 155 167 179 189 200
134 164 188 210 229 248 265 281 143 164 184 202 219 236 251 265 146 164 181 197 212 226 240 253
83 98 112 124 136 147 157 167 85 97 109 120 130 140 149 157 86 97 107 117 126 134 142 IK)
113 133 152 169 185 200 214 227 116 133 148 163 177 190 202 214 118 132 146 159 171 182 193 204
134 164 195 221 242 261 279 296] 151 173 194 213 231 248 264 279 154 173 190 207 223 238 253 266
226 256 287 317 348 164 195 226 256 287 314 334 353 194 218 241 262 282 302 320 337
42 49 0 0 0 0 0 0 42 0 0 0 0 0 Q 0 0 0 0 0 0 0 0 0
56 67 76 85 93 0 0 0 58 66 74 82 0 0 0 059 66 73 0 0 0 0 0
74 87 99 110 121 131 140 0 76 87 97 106 116 124 0 0 77 86 95 104 112 0 0 0
93 110 126 140 153 165 177 188 96 110 123 135 143 157 167 177 97 109 120 131 141 151 160 168
62 73 84 93 102 0 0 0 64 73 82 90 0 0 0 0 65 73 80 0 0 0 0 0
85 100 114 127 139 150 160 170 87 99 111 122 133 142 152 180 88 99 109 119 128 137 145 0
20 111 130 210 222| 113 145 160 173
149 166 181 196 130 186 198 209 115 129 143 155 167 179 189 200
140 165 188 210 229 248 265 281 143 164 184 202 219 236 251 265 146 164 181 197 212 226 240 253
83 98 112 124 136 147 157 167 85 97 109 120 130 140 149 157 86 97 107 117 126 134 142 0
113 133 152 169 185 200 214 227 116 133 148 163 177 190 202 214 118 132 146 159 171 182 193 204
148 174 198 221 242 261 279 296 151 173 194 213 231 248 264 279 154 173 190 207 223 238 253 266
149 183 217 251 285 319 350 362 183 217 245 270 292 314 334 353 194 218 241 262 282 302 320 337
f p(ln.) 6 8
4 6 8 10 12 14 16 18 6 8 10 12 14 16 18 20 8 10 12 14 16 18 20 22
~T- 33 51 66 79 90 0 0 0 38 5061 70 0 0 0 0 40 49 & 0 0 0 0 0
2--#7 44 69 90 107 122
135 146 0 51 6883 96 107 117 0 0 54 67 78 89 98 0 0 0
2--#8 51 89 118 140 172
159 180 188 67 108
89 125 140 153 166 177 71 88 103 116 128 140 150 0
2--#9 126 164 188
199 210 219 84 112
136 158 177 194 210 224 90 111 130 147 163 177 190 202
3--#6 49 76 99 118 135
149 161 168 56 7591 105 118 129 140 0 60 74 87 98 108 118 0 0
3--#7 51 89 126 161 177
188 197 206 77 124
102 143 161 176 190 203 82 101 118 133 148 161 173 184
22
3--#8 164 201
222 233 244 89 126
162 187 210 230 244 253 107 131 154 174 193 210 225 240
3--#9 238 269 282 164 201 238 269 282 294i 126 164 195 220 244 265 285 303
4--#6 158 175 185 195 203 75 190 121 140 157 173 186 199 80 99 115 131 144 157 169 180
4--#7 164 201 224 236 247 89 126 164 191 214 235 247 257 109 134 157 178 197 214 230 245
4--#8 238 276 291 201 238 276 291 303 126 164 201 232 257 280 300 315
4--#9 313 313 350 238 276 313 350 364
2--#6 33 51 66 79
0 0 0 0 38 50 61 0 0 0 0 0 40 49 O 0 0 0 0 0
2--#7 44 69 90 107
122 135 0 0 51 68 83 96 107 0 0 0 54 67 78 89 0 0 0 0
2--#8 56 91 118 140
159 176 186 194 67 89 108 125 140 153 166 0 71 88 103 116 128 140 0 0
2--#9 97 138 194
177 206 216 226 84 112 136 158 177 194 210 224 90 111 130 147 163 177 190 202
3--#6 49 76 99 118
135 149 161 0 56 75 91 105 118 129 0 0 60 74 87 98 108 0 0 0
3--#7 56 97 135 161
183 194 203 212 77 102 124 143 161 176 190 203 82 101 118 133 148 161 173 184
24
3--#8 138 179
216 229 241 252 97 133 162 187 "210 230 248 262 107 131 154 174 193 210 225 240
3--#9 219 260 279 292 138 179 219 260 279 292 304 135 166 195 220 244 265 285 303
4--#6 132 158 179 191 201 209 75 100 121 140 157 173 186 199 80 99 115 131 144 157 169 180
4--#7 138 179 219 232 244 255 97 136 165 191 214 235 254 265 109 134 157 178 197 214 230 245
4--#8 260 288 301 138 179 219 260 288 301 314 138 175 205 232 257 280 300 320
4--#9 301 342 301 342 362 179 219 260 301 342 362 376

PCI Design HandbooWRfth Edition 6 -6 9


Figure 6.15.16 Design strength of concrete brackets, corbefeor haunches^coRtinued)

Values of <|>V-n (kips)

^p(in-) 10 12 14
10 12 14 16 1ft 20 22 24 12 14 16 18 20 22 24 26 14 16 18 20 22 24 2fr 28
2 -# 6 42 49 0 0 0 0 0 42
0 0 0 0 0 0 0 0; 0 0 0 0
2 -# 7 56 67 76 85 0 0 0 58 66 74 0 0
0 0 0 0 59 66 0 0 0 0
2 -# 8 74 87 99 110 121 131 0 0 76 87 97 106 116 0 0 0 77 86 95 104 0 0
2- #9
93 110 126 140 153 165 177 188 96 116 123 135 146 157 167 177 97 109 120 131 141 151 160
3- #6
62 73 84 93 102 0 0 0 64 73 82 90 0 0 0 0 -65 73 80 0 0 0 0
3 -# 7 85 100 114 127 139 150 160 170 87 99 111 122 133 142 152 0 88 99 109 119 128 137 0
22 3 -# 8 111 130 149 166 181 196 210 222 113 130 145 160 173 186 198 209 115 129 143 155 167 179 189 200
3- #9
140 165 188 210 229 248 265 281 143 164 184 202 219 236 257 265 146 164 181 197 212 226 240 253
4- #6
83 98 112 124 136 147 157 167 85 97 109 120 130 140 149 0 86 97 107 117 126 134 0 0
4—#7 113 133 152 169 185 200 214 227 116 133 148 163 177 190 202 214 118 132 146 159 171 182 193 204
4 -# 8 148 174 198 221 242 261 279 296 151 173 194 213 231 248 264 279 154 173 190 207 223 238 253 266
4 -# 9 164 201 238 276 306 331 354 375 191 219 245 270 292 314 334 353 194 218 241 262 282 302 320 337
2 -# 6 42 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
2 -# 7 56 67 76 0 0 0 0 58 66 0 0 0 0 0 59 0 0 0 0 0 0
2 -# 8 74 87 99 110 121 0 0 0 76 87 97 106 0 0 0 77 86 95 0 0 0 0
2- #9
93 110 126 140 153 165 177 188 96 110 123 135 146 157 167 97 109 120 131 141 151 0
3- #6
62 73 84 93 0 0 0 0 64 73 82 0 0 0 0 65 73 0 0 0 0 0
3 -# 7 85 100 114 127 139 150 160 0 87 99 111 122 133 142 0 88 99 109 119 128 0 0
24
3 -# 8 111 130 149 166 181 196 210 222 113 130 145 160 173 186 198 209 115 129 143 155 167 179 189 200
3- #9
140 165 188 210 229 248 265 281 143 164 184 202 219 236 251 265 146 164 181 197 212 226 240 253
4 - #6 83 98 112 124 136 147 157 0 85 97 109 120 130 140 0 0 86 97 107 117 126 0 0
4 -# 7 113 133 152 169 185 200 214 227 116 133 148 163 177 190 202 214 118 132 146 159 171 182 193 204
4 -# 8 148 174 198 221 242 261 279 296 151 173 194 213 231 248 264 279 154 173 190 207 223 238 253 266
4 -# 9 179 219 251 280 306 331 354 375 191 219 245 270 292 314 334 353 194 218 241 262 282 302 320 337

6 -7 0 PCI Design Handbook/Fifth Edition


Pigure-S. 15.17 Design of structural steel haunches—concrete

Values are for design strength o f concrete


by Eq. 6,9.1 for following-criteria:
f c = 5000 psi, fo r other strengths multiply values by
fc /5000

Adequacy of structural steel section should be checked

Additional design strength, <j>Vr, can be obtained with


reinforcing bars - see Fig. 6.15.18.
Vu < <})(VC+ Vr)
(|) = 0.85

Values of <|>VC (kips)

Shear Effective width of section (in.)


span Embedment
a (in.) M in .) 6 7 8 9 10 11 12 13 14 15 16 17

6 33 38 43 49 54 60 65 70 76 81 87 92
8 47 55 62 70 78 86 94 102 109 117 125 133
10 62 72 82 92 103 113 123 133 144 154 164 174

CD
12 76 89 102 115 128 140 153 166 191 204 217
2 14 92 107 122 137 153 168 183 198 214 229 244 259
16 107 124 142 160 178 196 213 231 249 267 284 302
18 122 142 163 183 203 224 244 264 284 305 325 345
20 137 160 183 206 229 252 274 297 320 343 366 389
22 152 178 203 229 254 280 305 330 356 381 407 432
6 25 29 33 38 42 46 50 54 58 63 67 71
8 38 44 50 57 63 69 75 82 88 94 101 107
10 51 60 68 77 85 94 102 111 119 128 136 145
12 65 76 87 98 108 119 130 141 152 163 173 184
4 14 79 92 106 119 132 145 159 182 185 198 211 225
16 94 109 125 141 156 172 187 203 219 234 250 266
18 108 126 145 163 181 199 217 235 253 271 289 307
20 123 144 164 185 205 226 246 267 287 308 328 349
22 138 161 184 207 230 253 276 299 322 345 368 391
6 20 24 27 30 34 37 41 44 47 51 54 58
8 32 37 42 47 53 58 63 68 74 79 84 89
10 44 51 58 66 73 80 87 95 102 109 117 124
12 57 66 75 85 94 104 113 123 132 141 151 160
6 14 70 82 93 105 116 128 140 151 163 175 186 198
16 84 97 111 125 139 153 167 181 195 209 223 237
18 98 114 130 146 163 179 195 21T 228 244 260 276
20 112 130 149 168 186 205 223 242 261 279 298 317
22 136 147 168 189 210 231 252 273 294 315 336 357
6 17 20 23 26 29 31 34 37 40 43 46 48
8 27 32 36 41 45 50 54 59 63 68 72 77
10 38 45 51 57 64 70 76 83 89 95 102 108
12 50 58 67 75 83 92 100 108 117 125 133 142
8 14 62 73 83 94 104 115 125 135 146 156 167 177
16 75 88 101 113 126 138 151 163 176 188 201 214
18 89 103 118 133 148 163 177 192 207 222 236 251
20 102 119 136 153 170 187 204 222 239 256 273 290
22 116 135 155 174 193 213 232 251 271 290 309 329

PCI Design Handbook/Fifth Edition 6 -7 1


Figure 6.15.18 Design of structural-steel haunches—reinforcement

Values are for additional design strength of


concrete obtained from reinforcement by Eq. 6.9.2
for following criteria:
As = 2 bars welded to steel shape
As = As
Reinforcement anchored in only one direction.

When reinforcement, AsandAs is anchored both above


and below steel shape, it can be counted twice
(values may be doubled).

For design strength of concrete, <()VC- see Fig. 6.15.17.

Values of Vr (kips)

Reinforcing bar size Reinforcing bar size


Shear
fy = 40 ksi fy = 60 ksi
span Embedment
a (in.) M in.) #4 #5 #6 #7 #8 #9 #4 #5 #6 #7 #8 #9
6 7 11 15 21 27 35 10 16 23 32 41 52
8 10 15 22 30 39 49 14 23 33 44 58 73
10 11 15 25 35 45 57 17 26 38 52 68 86
12 12 19 28 38 50 63 19 29 42 57 74 94
2 14 13 21 30 40 53 66 20 31 44 60 79 100
16 14 21 31 42 55 69 21 32 46 63 82 104
18 14 22 32 43 57 72 21 33 48 65 85 107
20 14 23 33 44 58 73 22 34 49 67 87 110
22 15 23 33 45 59 75 22 35 ■50 68 89 112
6 5 8 12 16 21 27 8 12 18 24 31 40
8 8 12 18 24 31 40 12 18 27 36 47 60
10 10 15 21 29 38 48 14 22 32 44 57 73
12 11 17 24 33 43 54 16 25 36 49 64 82
4 14 12 18 26 36 47 59 17 27 39 53 70 88
16 12 19 28 38 49 62 18 29 42 57 74 93
18 13 20 29 39 51 65 19 30 43 59 77 98
20 13 21 30 41 53 67 20 31 45 61 80 101
22 14 21 31 42 55 69 20 32 46 63 82 104
6 4 7 10 13 17 21 6 10 14 19 25 32
8 7 10 15 20 26 33 10 16 22 30 40 50
10 8 13 19 25 33 42 12 19 28 38 50 63
12 9 15 21 29 38 48 14 22 32 44 57 72
6 14 10 16 23 32 42 53 16 24 35 48 63 79
16 11 17 25 34 45 57 17 26 38 51 67 85
18 12 18 27 36 47 60 18 28 40 54 71 89
20 12 19 28 38 49 62 18 29 41 56 74 93
22 13 20 29 39 51 64 19 30 43 58 76 96
6 4 6 8 11 14 18 5 8 12 16 21 27
8 6 9 13 17 23 29 9 13 19 26 34 43
10 7 11 16 22 29 37 11 17 25 34 44 55
12 9 13 19 26 37 43 13 20 29 39 51 65
8 14 9 15 21 29 38 48 14 22 32 43 57 72
16 10 16 23 31 41 52 15 24 35 47 61 78
18 11 17 24 33 43 55 16 25 37 50 65 83
20 11 18 26 35 46 58 17 27 39 52 68 87
22 12 19 27 36 47 60 18 28 40 55 70 90

6 -7 2 PCI Design Handbook/Fifth Edition


PCI Design Handbook/Fifth Edition 6 -7 3
6 -7 4 PCI Design Handbook/Fifth Edition
CHAPTER 7
SELECTED TOPICS FOR
ARCHITECTURAL PRECAST CONCRETE

7.1 Introduction .............................. ...................................................... . . , .............. 7 -2


7.1.1 Structural Analysis and Design ........................................................... 7 -2
7.1.2 Load Transfer—General Methods ..................................................... 7 -3
7.1.3 Application ............................................................ 7 -3
7.1.4 A na lysis................................... 7 -4
7.1.5 Design O bjectives............. .............................................- ............ .. 7 -4

7.2 Non-Load Bearing Panels—Connections........................................................... 7 -4


7.2.1 Design Fundamentals.......................................................................... 7 -4
7.2.2 Production Considerations .......................... 7 -6
7.2.13 Erection Considerations....................................................................... 7 -6

7.3 Precast Concrete Used as Forms ...................................................................... 7 - 6


7.3.1 General ................................................................................................ 7 - 6
7.3.2 Design Considerations............................................................ 7 -7
7.3.2.1 Lateral Pressure of Fresh C oncrete...................................... 7 - 7
7.3.2.2 Lateral Forces on Precast Concrete F o rm s ......................... 7 - 7
7.3.2.3 Design Assumptions.............................................................. 7 - 7
7.3.3 Construction Considerations.............................................................. 7 - 8

7.4 Column Covers and M u llion s........................................................................... 7-11

7.5 Veneered P anels................................................................................................ 7 -1 2


7.5.1 General ............................................................................................... 7 -1 2
7.5.2 Clay P roducts..................................................................................... 7 -1 2
7.5.2.1 Clay Product Properties....................................................... 7 -1 2
7.5.2.2 Clay Product Selection......................................................... 7 -1 3
7.5.2.3 Design Considerations........................................................... 7 -1 3
7.5.3 Natural S to n e ..................................................................................... 7 -1 5
7.5.3.1 Properties............. ................................................................ 7 -1 5
7.5.3.2 Sizes ..................................................................................... 7 -1 6
7.5.3.3 Anchorage of Stone Facing ............................................... 7 -1 6
7.5.3.4 Veneer Jointing ............. 7 -1 9
7.5.5.5 Samples ............................................................................... 7 -1 9

7.6 Design Example—Window Wall P a n e l.......................................................... 7 -1 9

7.7 References............................................................................................................ 7 -2 4

PCI Design Handbook/Fifth Edition 7 -1


SELECTED TOPICS FOR ARCHITECTURAL PRECAST CONCRETE

7.1 introduction 3.3 Vokame"Changes


3.4 Component Analysis
Architectural precast concrete is produced in a
3.7 Shear Wall'Buildings
wide variety of shapes and finishes. Shapes can vary
3.11 Earthquake Analysis and Design
from simple to complex; finish includes color, pattern
4.2 Flexure
and texture. The combination of finish and shape con­
4.3 Sheaf
tribute to the architectural expression and finished ap­
4.4 Torsion
pearance of the structure.
4.6.1 Bearing on Plain Concrete
In addition to aesthetics, architectural precast con­
4.6.2 Reinforced Concrete Bearing
crete can serve a load bearing function, help stiffen
4.9 Compression Members
the structure, and aid in meeting thermal and/or
5 Product Handling and Erection Bracing
acoustical requirements.
6.4 Connection Design Criteria
This section now discusses in more detail the dif­
6.5 Connection Hardware and Load Transfer
ference between non-load bearing and load bearing
Devices
architectural panels. The main change is the in­
6.8 Concrete Brackets or Corbels
creased discussion of the positive uses of load bear­
6.9 Structural Steel Haunches
ing architectural panels, either as shear walls or to
6.13 Connection of Load Bearing Wall Panels
support vertical loads from other members. The
8 Tolerances for Precast and Prestressed
benefit is decreased cost of the project without affect­
Concrete
ing the appearance of the structure.
9 Thermal, Acoustical, Fire and Other
The successful and economical use of architectur­
Considerations
al precast concrete requires not only a clear under­
10.2 Guide Specifications for Architectural
standing of the production and erection methods, but
Precast Concrete
also a good knowledge of the structural limits of the
10.3 Code of Standard Practice for Precast
product. This chapter provides a brief discussion of
Concrete
selected topics of relevance to the structural engineer.
10.4 Recommendations on Responsibility for
A more complete treatment of all aspects of architec­
Design and Construction of Precast
tural precast concrete is provided in Ref. 1.
Concrete Structures
Design Procedures presented in this chapter fol­
10.5 Standard Design Practice
low ACI 318-95 and other relevant national model
building code requirements except where modified to
Following is a brief summary of structural engi­
reflect current industry practice (see Sect. 10.5).
neering considerations discussed in detail in the
above listed sections:
7.1.1 Structural Analysts and Design
The potential for element volume change requires
Architectural precast concrete construction can be consideration. Volume changes may be a result of:
considered in three parts:
1. Elastic and inelastic (creep) deformations.
1. The precast elements.
2. Shrinkage.
2. The support of the precast element, i.e., the
3. Expansion, contraction and bowing resulting
beam, wall, column, foundation or any other
from temperature and moisture change.
part of the structure which provides vertical and
horizontal support for the element. Movement inthesupport system must also be con­
sidered. Movement can result from:
3. The connection that joins the precast element
to its support. 1. Elastic and inelastic deformation from gravity
loads.
Other parts of this Handbook give detailed infor­
mation and procedures for analyzing and designing 2. Horizontal displacement resulting from wind
architectural and structural precast concrete ele­ and earthquake.
ments and structures. The following chapters or sec­
tions are also applicable to architectural precast con­ 3. Foundation movement.
crete: 4. Temperature change.
1 Materials
2.6 Load Bearing Wall Panels 5. Shrinkage of concrete.

7 -2 PCI Design Handbook/Fifth Edition


provisions must be made to accommodate estimated plified'methods discussed in Chapter 3, or computer
movements. analysis-programs.
The structumLdesigrrotarehitectural precast con­ When redundant supports’are necessary or when
crete requires consideration of the-fdJowing items: movement is to be resisted, the Toad-deformation
characteristics of the eiementrconnectTons end sup­
1; Stresses caused by handling, transportation port system should be taken into account.
and erection.

2. Acceptable crack width and location.


7.1.3 Application
3. Strain-gradients and restraint forces from ther­
The most com m on applications of architectural
mal and moisture differentials through the pan­
precast concrete in building construction are those in
el thickness. which the precast elements function as walls. Con­
4. Localized wind forces, seismic events and the crete is an ideal wall material, since it has excellent
response of a precast element to these tran­ sound transmission characteristics, is fire resistant,
sient loads. and is durable. In addition, architectural precast con­
crete provides almost unlimited potential for economi­
5. Forces transferred to the element and connec­ cally achieving aesthetic design objectives. Architec­
tions due to distortion of the structural frame. tural precast elements are capable of functioningas a
wall without backing. Large elements provide the
6. Differential deflections between the precast ele­
complete wall, and often are made with integral win­
ment and the supporting structure.
dow openings.
7. Accommodation of tolerances allowed in the Precast walls which are of sufficient mass to satisfy
supporting structure. manufacturing, sound transmission, and fire resist­
ance requirements are also capable of supporting
8. Experience with various types of connections.
significant loads. Thus, using precast concrete walls
It should be recognized that loads and behavior to carry loads is an economical alternative to the use
cannot be established precisely, particularly for mem­ of separate structural systems and wall materials.
bers exposed to the environment. This imprecision In this Handbook, a distinction is made between
will generally not affect the safety of the member, pro­ non-load bearing and load bearing elements:
vided that reasonable values have been established
1. A non-load bearing (cladding) element is one
and the above factors considered.
which resists and transfers negligible load from
other elements of the structure. It is generally
7.1.2 Load Transfer—General Methods used only to enclose space, but must be de­
signed to resist wind, seismic forces generated
The forces which must be considered in the design from self weight, and forces required to transfer
of architectural precast concrete components are: its weight to the structure which supports it.
1. Those caused by the precast member itself,
2. A load bearing element resists and transfers
e.g., self weight and earthquake forces. loads applied from other elements in addition to
2. Those caused by loads, such as wind, seismic, the forces described above. Therefore, a load
snow, floor five loads, soil or fluid pressure, or bearing member cannot be removed without af­
construction loads, that are externally applied fecting the strength or stability o f the building.
to the element and transferred to the element by Architectural precast concrete wall panels can be
the behavior of the supporting structure. used as shear walls to resist and transfer horizontal
3. Those that are a result of restraint of volume loads. Precast panels can be attached to existing
change or support system movement. They are frames to improve lateral resistance, such as upgrad­
generally concentrated at the connections. ing structures in seismic zones. In these cases, the
connections between panels and other structural ele­
All non-load bearing elements should be designed ments are the primary design consideration. Typical­
to accommodate movement freely and, whenever ly, connection flexibility is the limiting factor in thecon-
possible, with no redundant supports, except where tribution of the panels to lateral load resistance of the
necessary to restrain bowing. Relatively simple analy­ entire structure. The lateral force load paths and the
ses provide the forces required for connectiondesign. additional forces applied through panel connections
The calculations required for movement accommoda­ to the supporting structural elements must also be
tion are more complex. The designer can use the sim­ considered in the design [19].

PCI Design Handbook/Fifth Edition 7 -3


Architectural precast concrete elements can also Economy is an important design objective. The to­
be designed as beams to transfer gravity and lateral tal cost o f a completed structure is the- determining
loads to supports. The beams-may also participate in factor. What seems to be a relatively expensive pre­
the transfer of lateral loads. For example, theJbeams cast element may result in the most economical build-
may serve as struts between lateral load resisting ele­ ing because of the reduction or elimination of other
ments, such as columns o r shear walls, transferring- costs. The designer should attempt-to optimize the-
the lo a d as an axial force. In other cases, precast structure b y using -precast panels to serve* several
beams interact with columns to form a moment frame functions, and take advantage of the economy gained
as a lateral load resisting system. by standardization.
In composite construction, precast concrete ele­ Standardization reduces costs because fewer
ments may be used as forms for cast-in-place con­ molds are required. Also, productivity^ all phases of
crete (Sect. 7.3). This is especially suitable for com­ manufacture and erection is improved through repeti­
bining architectural and structural functions in bad tion of familiar tasks; there is also less chance of error.
bearing facades, or for improving ductility in locations A very strict discipline is required of the designer to
of high seismic risk. avoid a large number of non-standard units. Prelimi­
Suggested connection details for cladding ele­ nary planning and budgeting should recognize the
ments are shown in Chapter 6. probability that the number of different units will in­
crease as the design progresses. If non-standard
units are unavoidable, costs can be minimized if they
7.1.4 Analysis can be cast from a master mold with simple modifica­
In some cases, the structural design of a single tions for the special pieces, rather than requiring spe­
precast element can be completed with very little con­ cial molds [1].
sideration of other materials and elements in the The aesthetic design objectives for the structure
structure. The weight of the element and the superim­ should be a matter of concern to the structural engi­
posed loads are simply transferred to supports, and neer. A precast element or system may achieve all
the element can be considered independently of the other design objectives but fall short of aesthetic ob­
structure. jectives through treatment of the structural features.
Occasionally, however, it is necessary to consider
the characteristics of other materials and elements 7.2 Non-Load Bearing Panels—Connections
within the structure. For example, neglecting the rela­
tive movement between two support points may lead 7.2.1 Design Fundamentals
to inaccurate estimates of connection forces.
To assure the satisfactory performance of architec­
In other cases, architectural precast elements may
tural precast concrete elements, it is important that
interact with other parts of the structure in the transfer
connections be selected and arranged to transfer ap­
of loads. The design of the interacting system and the
plied loads without producing unintended restraint.
individual precast elements must be based on analy­
The design of connections follows the procedures
sis of the whole system.
given in Chapter 6.
The designer of a precast building can choose to
The designer should provide simple load paths
transfer loads through architectural precast concrete
through the connections and ductility within the con­
elements or intentionally avoid significant load trans­
nections. This will reduce the sensitivity of the con­
fers through the precast elements. In the preliminary
nection and the necessity to precisely calculate loads
design phase, the structural engineer should there­
and forces from, for example, volume changes and
fore recognize that he is able to choose the structural
frame distortions. The number of load transfer points
characteristics rather than simply analyze a predeter­
should be kept to a practical minimum. It is recom­
mined set of criteria.
mended that no more than two connections per panel
be used to transfer gravity loads. More than two re­
7.1.5 Design Objectives sults in a statically indeterminate system; since the
stiffness of the panel and its support may be signifi­
Structural integrity and serviceability of the com­
cantly different, and the elevation of supports different
pleted structure are the primary objectives. Deflec­
than assumed in the design, the reactions on an inde­
tions must be limited to acceptable levels, and dis­
terminate system may not be accurately known. Fur­
tress that could result in instability of an individual
thermore, the fewer the connections the easier it is to
element or of the complete structure must be pre­
provide for the various movements required to ac­
vented. The inherent stiffness of architectural precast
commodate volume changes, drift, etc. Load transfer
concrete panels will significantly stiffen a structure,
should be as direct as possible. Figure 7.2.1 shows
thereby reducing deflections and improving stability.
examples of several load transfer mechanisms.

7 -4 PCI Design Handbook/Fifth Edition


Figure 7.2.1 Connections illustrating number of force transfers

(A) HORIZONTAL LOAD TRANSFER S X ANDZD1RECTION

• CONCRETE TO INSERT
• INSERT TO BOLT
■ BOLT TO ANGLE
■ ANGLE TO WELD
■ WELD TO PLATE
• PLATE TO ANCHORS
-• ANCHORS TO CONCRETE
(7 FORCE TRANSFERS)

(B) HORIZONTAL LOAO TRANSFER IN Z DIRECTION AND


VERTICAL LOAD TRANSFER IN Y DIRECTION


(X)
CONCRETE TO STUDS
(Y)
CONCRETE TO STUDS
A
■ STUDS TO ANGLE STUDS TO ANGLE
■ ANGLE TO WELD ANGLE TO SHIMS
■ WELD TO WING PLATE SHIMS TO PLATE
• W ING PLATE TO WELD PLATE TO ANCHORS
■ WELD TO BRG PLATE ANCHORS TO CONCRETE
■ BRG PLATE TO ANCHORS (6 FORCE TRANSFERS)
« ANCHORS TO CONCRETE
(8 FORCE TRANSFERS)

(C) HORIZONTAL LOAD TRANSFER IN X OR Z DIRECTION

■ CONCRETE TO INSERT
■ INSERT TO BOLT
■ BOLT TO ANGLE
■ ANGLE TO WELD
■ WELD TO SUPPORT
(5 FORCE TRANSFERS)

(D) VERTICAL LOAD TRANSFER

■ CONCRETE TO REINFORCEMENT AND TUBE


■ REINFORCEMENT TO WELDS
■ WELDS TO TUBE
■ TUBE TO SHIMS
■ SH IM S TO BEARING PLATE
■ BEARING PLATE TO ANCHORS
■ ANCHORS TO CONCRETE
(7 FORCE TRANSFERS)

(E) HORIZONTAL LOAD TRANSFER IN X AND Z DIRECTION


AND VERTICAL LOAD TRANSFER
Y

■ CONCRETE TO GROUT AND SHIMS A SHIMS


■ GROUT AND SHIMS TO SUPPORT GROUT
(2 FORCE TRANSFERS)
Z-*
7

x &

PCI Design Handbook/Frfth Edition 7 -5


-Connections and assemblies should developsuffi- When possible, connections should be dimen­
cieni ductility to preclude brittle-failures. Forexample, sioned to the nearest Vz in. The minimum shim space
inserts^ in concrete should be attached to ^and/or between elements of a-eonneetion should not-be less
hooked around reinforcing steel, provided with con­ than Vi-in., with 1 im preferred. It should be remerm
finement reinforcement or otherwise be terminated to bered that the-r-eaftiimensions of reinforcing-bars are
effectively transfer forces to the concrete and/or rein­ approximately Vs in. greater than the nominal, be­
forcement. It is desirable that the pullout strength of cause of the- deformations. Prestressed panels re­
concrete a nd strength of welds be greater than the quire special form considerations to permit-product
tension or bending strength of the connection steel. movement at release.
The design of the panel connection and the sup­
porting frame are interdependent. For example, if a 7.2.3 Erection Considerations
supporting spandrel beam lacks sufficient rotational
Ease and speed of erection are heavily dependent
stiffness, the precast connections should be de­
on simplicity and ruggedness of assembly details.
signed to transmit the vertical loads to the shear cen­
Field patching and finishing should be kept to a mini­
ter of the beam, or the supporting members should be
mum. If possible, the details should allow erection to
braced to avoid torsional rotation.
proceed in nearly all kinds of weather. The panels
Connection hardware must be permanently pro­
should he capable of being erected without tempo­
tected from the elements, or corrosion resistant mate­ rary shoring. Ideally, it should be possible to com­
rials used. For fire-rated structures, exposed connec­ plete the connection by working downhand from the
tions should be protected as required to assure the top o f the erected member or from a stable deck.
proper rating for the entire assembly. The maximum feasible adjustability should be pro­
Adequate tolerances and clearances, as dis­ vided in all directions, preferably at least 1 in. For ex­
cussed in Chapter 8, are required. ample, the supporting beam may rotate or deflect un­
In zones of seismic activity, present codes treat der the weight of the precast panels, making it
precast concrete walls subjected to lateral loads as necessary to adjust the connections during erection.
non-ductile, with an appropriately high multiplier to Significant support rotation and deflection are more
establish design base shear. Continuity and ductility common in structural steel than in concrete frames.
may be achieved by casting in place spandrel beams The designer of the support system should verify that
and columns using the wall panels as forms. The duc­ eccentrically loaded support beams are of sufficient
tility of walls partially depends on the location of rein­ stiffness to prevent excessive rotation.
forcement. Ductile behavior is significantly improved Connections should be detailed so that hoisting
if the continuous reinforcement is located at the ends equipment can be quickly released. It may be neces­
of the walls. Thus, a usually inactive curtain wall can sary to provide temporary connections that are re­
become a major lateral load (seismic) resisting ele­ leased after final adjustments are made. Loading
ment. conditions during erection may be more critical than
other phases, due to eccentricities, construction
7.2.2 Production Considerations loads or impact.
Connections should allow economical production When cast-in-place concrete, grout or drypack is
of the precast elements. The hardware should not in­ required to complete a connection, the detail should
terfere with concrete placement or cause finishing provide for self-forming if possible. When not practi­
problems, nor require penetration through molds. The c a l the connection should allow for easy placement
size of reinforcing bars should be limited, because and removal of formwork. Temporary shoring may be
large bars require anchorage lengths and hook sizes required.
that may be impractical. Connection details with rein­
forcing bars crossing each other require careful di­
7.3 Precast Concrete Used as Forms
mensional checking to ensure sufficient cover.
Plates, angles or other steel shapes embedded in
precast concrete must be securely attached to the 7.3.1 General
forms to prevent their becoming misaligned or
This section provides design and detailing infor­
skewed.
mation for structures in which architectural precast
inserts must be placed accurately because their
concrete is used as the formwork for cast-in-place
capacity depends on the depth of embedment, spac­
structural concrete [3].
ing and distance from free edges. They should be
In most cases, the architectural precast concrete is
kept free of dirt and protected so that concrete does
considered solely as a form, serving only decorative
not enter during casting.

7 -6 PCI Design Handbook/Fifth Edition


purposes after !he cast-in-place concrete has Walls, placement rate greater than 10 ft/hr.
achieved design strength. This is accomplished by p = 150h (Eq. 7.372c)
providing open or-compressible joints between abut­ where:
ting precast panels, and eliminating bond at theJnter-
p = lateral pressure, psf
faceof the precast and cast-in-plaee-eoncrete, When
the architectural precast concrete u n it is non-com­ R= placem ent rate, ft/hr
posite with the Gast-irr-place concrete, the reinforcing T = temperature of concrete in forms; °F
steel extending from the precastinto the cast-in-place h = height of fresh concrete above point
concrete needonly beof sufficient strength to support considered, ft
the formwork unit.
In other cases, it may be desirable to detail the 7.3.2.2 Lateral Forces on Precast Concrete
structure so that the precast and cast-in-place con­ Forms
crete act compositely, thus combining the strength of
In addition to pressure induced by fresh concrete,
both. It is then necessary to provide shear transfer as
the lateral forces on forms and bracing should be in
for other composite assemblies. Sect. 4.3.5 describes
accordance with the building code, but not less than:
design procedures.
1. Wind— 15 psf applied to all exposed surfaces,
unless focal codes specifically permit less.
7.3.2 Design Considerations
2. Columns—2% of the total dead load supported
Following are recommendations for design of pre­
by the form, applied as a horizontal load to the
cast panels used as forms for cast-in-place concrete:
top of the form.

3. Walls— 100 lb per linear ft of wall, applied to the


7.3.2.1 Lateral Pressure of Fresh Concrete top of the wall form.
With the following limitations, the formulas below Vertical Loads on Precast Concrete Forms. The
may be used to determine the forces to be resisted by vertical load supported by precast concrete forms
forms, ties, and bracing [4]: should consist of all superimposed dead toads, in­
cluding an allowance for storage of construction ma­
1. Material is normal weight concrete, with a unit terials, and a live load of not less than 25 psf.
weight of 145 to 155 pcf.
Formwork Accessories. In the design of formwork
2. Vibration is by internal means only; form vibra­
accessories such as form ties and form anchors, a
tors, if used, will require a modification of the
minimum safety factor of 2 based on the ultimate
formulas.
strength of the accessory is recommended except
3. The depth vibrated, or re-vibrated, does not ex­
that yield point must not be exceeded.
ceed 4 ft below the concrete surface.
4. Retarding admixtures, if used, will require a
modification of the formulas. 7.3.2.3 Design Assumptions
5. For heights greater than 18 ft, an interval of 2 1. Forms are generally supported in a manner
hours should elapse after each 18 ft lift prior to which will permit them to act as continuous
continuation. beams. It is generally sufficiently accurate to
6. Slump is not greaterthan 4 in. at point of place­ assume that the form acts as a fixed beam be­
ment. tween adjacent lateral supports. The engineer
Columns, placement rate up to 25 ft/hr: must judge whether to include deformation of
the form supports in the analysis.
p = 150 + 9000R/T (Eq. 7.3.1)
(maximum 3000 psf or 150h, whichever is least) 2. Partially open concrete shapes are often used
to form columns. These U-shapes will develop
Walls, placement rate less than 7 ft/hr: internal stresses which are a function of the stiff­
ness of the sides. Design assumptions are
p = 150 + 9000R/T (Eq. 7.3.2a) shown in Figure 7.3.1.
(maximum 2000 psf or 150h, whichever is least)
3. The internal stresses, produced by the temper­
ature rise of the form as the cast-in-place con­
Walls, placement rate 7 to 10 ft/hr:
crete is placed, are usually neglected. Moments
p = 150 + 43,400/T + 2800R/T (Eq. 7.3.2b) developed due to uniform temperature rise for
(maximum 2000 psf or 150h, whichever is least) U-shaped forms are shown in Figure 7.3.1.

PCI Design Handbook/Fifth Edition 7 -7


Figure 7.3:1 Forces-due to internal pressure Composite design- Interaction between precast
on U-shaped forms forms-and cast-in-place-concrete can be achieved by
providing for the transfer o t shear forces at the inter­
face. Effectivecomposite behavior will significantly in-
crease-the strength of members and reduce deflec­
tions. Design methods and Shear transfer
requirements are discussed in Chapter 4.
When the precast and cast-in-place concrete are
designed to act compositely, the form joints must be
located away from points of high moment.
In compression members, axial toads will tend to
be distributed initially to the precast and cast-in-place
components in accordance with their individual axial
stiffness. Over time, there will be some redistribution
of load from the more highly stressed components to
the other due to creep.

7.3.3 Construction Considerations

Realistic assumptions with regard to construction


techniques are required. It must be determined (or
specified) how the precast panels will be supported
during concreting in order to design them.
Panel forms of concrete should be erected and
temporarily braced to proper grade and alignment in
such a way that the tolerances specified for the fin­
ished structure can be met. Temporary bracing for
the panels generally consists of adjustable pipe brac­
ing from panel to floor slab. Supports, braces, and
form ties must be stiff enough so that their elastic de­
formation will not significantly affect the assumed load
distribution. Form ties may be attached as shown in
Figure 7.3.2, or welded to plates cast in the panels.
Column forms may use column clamps or be
wrapped with steel bands to aid in resisting hydrostat­
4. The cross-sectional area of column form panels ic pressure.
is usually neglected when determining either Attachments between the precast form and other
the immediate (elastic) or long-term (creep) col­ elements, such as steel columns, must be detailed to
umn shortening. The thickness of panels is usu­ provide the necessary field adjustments. Contact area
ally included when investigating the effect of between precast concrete and external braces,
various temperature changes across the col­ clamps or bands should be protected from staining
umn. and chipping.
Deflection. Form deflection should generally be Architectural precast concrete surfaces require
limited to V$eo of the unsupported height or length. tight joints so that concrete does not leak and mar
Deflection of beam forms, and warping of wall forms, decorative facings. Methods used to close joints in­
may result from differential shrinkage of precast and clude buttering on the inside with mortar (units may
cast-in-place concrete, as well as the dead load or lat­ also be bedded on mortar when designed to accept
eral pressure of the cast-in-place concrete. Camber­ load transfer through the joint), and gasketing with
ing of architectural precast forms to compensate for low density, closed cell neoprene rubber or other du­
deflections is expensive and should be avoided. rable, permanent, resilient materials.
Crack control. In order to minimize form cracking Where form panels are non-composite, the joint
due to the pressures induced by fresh concrete, the material should prevent load transfer. Where form
design procedures for crack control in Chapters 4 and panels are intended to act compositely with the cast-
5 should be followed. Where the member is long in-place concrete, the joint material must be mortar or
enough to develop bonded strand, pretensioning other non-staining material of sufficient strength to
may be used in the precast form units. transfer the intended loads. For joints exposed to the

7 -8 PCI Design Handbook/Frflh Edition


pijsiifii!

Solution:
Assume a 5 in. panefthickness is necessary to pro­
vide anchorage for the form ties. Either a 5 in. flat pan­
el could be used or, as In this case, a ribbed section
with a 5 in. rib depth. The rib spacing is set by the
strength o f the ties. Since the placement rate is less
than 7 ft per hr:
p = 150 + 9000R/T = 150 + 9000(4)/90
= 550 psf, or a maximum of:
p = 150(4) = 600 psf. Use 550 psf.

Check Flexure:
Neglecting effect o f ribs, assume the 2Vfc in. panel
acts as a fixed beam of 24 in. span:

M = p€2/12 = 550(2)712 = 183 Ib-ft

6M _ 6 (183) (12)
f = 176 psi
bt2 12(2.5)2

Maximum allowable tension to prevent cracking:

= 5/5000 = 353 psi > 176 OK


environment, mortar is usually raked back from the
Provide reinforcement to develop an ultimate mo­
face, and the joint caulked. ment capacity > 1.4M:
Some precaution and special details may be re­
Mu = 1.4(183) = 256 Ib-ft
quired to take care of differential shrinkage or creep
between cast-in-place concrete and precast concrete
used as forms for columns or load bearing walls Try 6 x 6 -W4.0 x W4.0 in center of panel.
[3,17]. Stress relief may be simply handled in the de­
As = 0.08 in.2/ft
sign of the joints in the precast forms at the top and
bottom of vertical structural components carrying ax­ rA
v s fiy 0.08(60)
a = = 0.09 in.
ial loads. 0.85fc b 0.85(5)(12)
Horizontal construction joints in the cast-in-place
concrete are generally 3 in. below the top edge oflhe d = 2.5/2 = 1.25 in.
panels used as permanent forms rather than in line
with horizontal form joints. This reduces the possibil­ <t>Mn = 4>Asfy(d - a/2)
ity of water leakage through the construction joints.
= 0.90(0.08) (60,000) (1,25-0.09/2)/12
Example 7.3.1 Precast Panel as a Wall Form
= 434 lb-ft> 256 OK
Given:
The wall panel section shown below. Check Shear:
Panel concrete strength: fc = 5000 psi
CIP concrete placement rate: 4 ft per hr Vu = 1.4(550)2/2 = 770 lb
Maximum height of CIP concrete: 4 ft
CIP concrete temperature: 90°F 4>Vr = cj>2 bwd = 0.85(2)/5000(12)(1.25)

Problem: = 1803 lb > 770 OK


Determine panel reinforcement requirements for
Also check for stripping and handling—see Ch. 5.
pressure of wet concrete.

PCI Design Handbook/Rftb Edition 7 -9


Example 7.T£2^ ColumnCover Acting as a N = 2k + 3 = 4.98
Form
Given: Mb = J j (*2 + kb2)
The column shows on the next page.
= 4 ^ y [ ( 2 : 7 1 ) 2 + (0.99)(2.69)-]
Preeast concrete strength: % = 5000 psi
CIP concrete placement rate: 8 f t per hr
Maximum-height of € IP concrete: 6 ft = 653 Ib-ft
CIPconcrete temperature: 90° F
6M _ 6(653) (12)
bt? 12(3.5)2
Problem:
Determine p an # reinforcement and tie require- = 321 psi < 5/5006 = 353 psi OK
ments.
Provide reinf. to develop design strength > 1.4M:
Solution: Mu = 1.4(653) = 914 Ib-ft
Design for pressure of wet concrete:

Try W4 wire at 4 in. o.c.


As = 0.12 in.2/ft
Asfy 0.12(60)
0.14 in.
0 .8 5 f'b 0.85(5) (12)

d = 3.50/2 = 1.75 in.

4>Mn = <j)Asfy(d - a/2)

= 0.90(0.12)(60,000)(1.75 - 0.14/2)/12

= 907 Ib-ft = 9 1 4 Ib-ft say OK

Tie Force:
H = Me/b = 653/2.69 = 243 Ib/ft

If ties are spaced 2 ft o.c.,

tie force = 2(243) = 486 lb

Use 3/ie x 1 in. A 36 steel strap. Weld to embedded


plates.

Check Shear:
Vu = 1.4 (900) (2.71/2) = 17071b

<|>Vn = 4>2/fTbwd = 0.85(2)/5 0 0 0 (12) (1.75)


p = 150 + 9000R/T = 150 + 9000(8)/90
= 2524 lb > 1707 OK
= 950 psf
Also check form for stripping and handling.
or a maximum of:
p = 150(6) = 900 psf < 950. Use 900 psf

Check Flexure: Example 7.3.3 Precast Fascia as Form for


Beam
b = 36 - 2 - 3.50/2
Given:
= 32.25 in. = 2.69 ft Precast concrete fascia forming a beam support­
( = 36 - 3.50 ing 24-ft span hollow-core floor as shown below.
= 32.50 in. = 2.71 ft Beam is supported on 2 ft square columns at 20 ft on
|2 = |,; k = \2/ \ , { b / { ) = 0.99 center.

7 -1 0 PCI Design Handbook/Fifth Edition


p ro b le m : 7.4 Colum rr C o ve rs a nd Muftions
Check stresses of fasciapanei during, erection.
The-use of precast concretrpanelsas covers over
steel or cast-in-place concrete columns and beams,
SECTIO N-
and as mullions, is-a common method of achieving ar-
PB6P ER TIES
chitectural expression; special shapes, or fire rating
A — 420 in.2
Ix = 167,022in.4
[ 1].
S, = 4417 in.3
Column covers are usually supported by the struc­
Sb = 7528 in.3 tural column or floor beam, and are themselves de­
signed to transfer no verticaHoad other than their own
weight. The vertical load of each length of column
cover section is usually supported at one elevation,
and tied back top and bottom for lateral load transfer
and stability. In order to minimize erection costs and
horizontal pints, it is desirable to make the cover or
muHion as long as possible, subject to limitations im­
posed by weight and handling.
bullions are vertical elements serving to separate
glass areas. They generally resist only wind loads ap­
Solution: plied from the adjacent glass, and must be stiff
Loads: enough to maintain deflections within the limitations
Hollow-core slabs: imposed by the window manufacturer. Since mullions
are often thin, they are sometimes prestressed to pre­
0.055(24/2 + 8/12) = 0.70 kip/ft
vent cracking.
3 in. lightweight topping:0.03(24/2) = 0.36 kip/ft Column covers and mullions are usually major fo­
CIP lightweight concrete beam: = 0.30 kip/ft cal points in a structure, and aesthetic success re­
Precast concrete fascia: quires that careful thought be given to all facets of de­
area = 420 in2 = 0.44 kip/ft sign and erection. Following are some items which
should be considered:
Total dead load = 1, 80 kip/ft
1. Since column covers and mullions are often
Construction live load:0.025(24/2) = 0 .30 kip/ft isolated elements forming a long vertical line,
Clear span = 2 0 - 2 = 18 ft any variation from a vertical plane is readily ob­
servable. This variation is usually the result of
M« = 1.80(18)78 = 72.9kip-ft
the tolerances allowed in the structural frames.
M „ = 0.30(18)2/8 = 12.2
To some degree these variations can be han­
Total = 85.1 kip-ft dled by precast connections with adjustability.
The designer should plan a clearance of at least
Stresses:
V/s in. between the panel and structure. For
ft = 85,100(12)/4417 steel columns, the designer should consider
the clearances around splice plates and pro­
= 231 psi compression jecting bolts.
fb = 85,100(12)/7528 2. Provide support at only one elevation for verti­
cal loads, and at additional locations for lateral
= 136 psi < 575000 = 353 psi OK
loads and stability. When access is available,
Vu = [1.4(1.80) + 1.7(0.3)] (18/2) consider providing an intermediate connection
for lateral support and restraint of bowing.
= 27.3 kips
3. Column covers and mullions which project from
bw = 4 in., d = 57 in. the facade will be subjected to shearing wind
(DVn = 4 ,2 v^b wd loads. Connection design must account for
these forces.
= 0.85(2) 75000 (4) (57)/1000
4. Members which are exposed to the environ­
= 27.4 kips > 27.3 OK ment will be subjected to temperature and hu­
midity change. Horizontal joints between abut­
Also check for stripping and handling.
ting precast column covers and mullions
should be wide enough to permit length

PCI Design Handbook/Fifth Edition 7-11


changes and rotation from temperature gradi­ Figure 7.5.1 Applications of veneer faced
ents. The behavior of thin flexible members-will precastconcreter
be improved by prestressing.

5. Due to vertical loads and the effects of-creep


and shrinkage in cast-in-piace concrete col­
umns, structural columns wilt tend to shorten.
The width of the horizontal joint between abut­
ting precast covers should be sufficient to per­
mit this shortening to occur freely.

6. The designer must envision the erection pro­


cess. Column cover and mutlion connections
are often difficult to reach and, once made, diffi­
cult to adjust. This probfem of access isoom-
pounded when all four sides of a column are
covered for a height exceeding the length of a
precast cover. Sometimes this problem can be
solved by welding the lower piece to the col­
umn and anchoring the upper piece to the low­
er with dowels set in front, or by a mechanical
device that does not require access.

7. Use of insulation on the interior face of the col­


umn cover reduces heat loss at these locations.
Such insulation will also minimize temperature
differentials between exterior columns and the
interior of the structure.
Typical connection details are illustrated in Chap­
ter 6, Figure 6.12.1 through Figure 6.12.3. lows.
4. Use of reinforcing trusses.
5. Concrete ribs formed on the back of the panel.
7.5 Veneered Panels 6. Intermediate tie-back connections to the sup­
7.5.1 General porting structure.
7. Use of bond breakers and flexible anchors with
Precast concrete panels faced with brick, tile, terra
thin stone veneers.
cotta or natural stone combine the rich beauty of tradi­
Cracking in the veneer may occur if the bonding or
tional materials with the strength, versatility, and
anchoring details force the veneer pieces to follow the
economy of precast concrete. Some applications are
panel curvature. This is particularly critical where the
shown in Figure 7.5.1.
face materials are large pieces (cut stone) and the dif­
Structural design of veneered precast concrete
ferential movement between concrete and veneer is
units is the same as for other precast concrete wall
significant. A good mix design with a low water con­
panels, except that consideration must be given to the
tent, quality control, and prolonged curing will help re­
veneer material and its attachment to the concrete.
duce shrinkage.
The physical properties of the facing material must be
compared with the properties of the concrete back­
7.5.2 Clay Products [18]
up. These properties include tensile, compressive
and shear strength, modulus of elasticity, coefficient Clay products which are bonded directly to con­
of thermal expansion, and volume change. crete include brick, tile, and architectural terra cotta
Because of the difference in material properties, (ceramic veneer). The clay product facing may cover
veneered panels are somewhat more susceptible to the entire exposed panel surface or only part of the
bowing than homogeneous concrete panels. Bowing face, serving as an accent band.
can be reduced using one or more of the following
techniques:
7.5.2.1 Clay Product Properties
1. Minimum thickness of 5 to 6 in. backup con­
crete, depending on panel length. Physical properties of brick vary considerably de­
2. Use of prestressing in tong, flat panels. pending on the source and grade of brick. Table 7.5.1

7 -1 2 PCI Design HandbooWFifth Edition


shows the range of physical properties of clay prod­ tile are used to produce a pattern on a panel, thetiles
ucts. Since clay products are subject to local varia­ must be manufactured on a modularizing system in
tion, the designer should-seek property values from order to-have grout joints a t thasama width.
-suppliers-thatere-being considered. Architectural, terra cotta is a custom product and,
As the temperature or length of burnrng_period is within limitations, is produced forsizes for specific
increased; clays bum to .darker colors, and compres­ jobs. Typical thicknesses are 11A and 2% in. With
sive strength and modulus of elasticity are increased. dovetails spaced 5 in. orrGenter, the 1V« in. thickness
In general,The modulus of elasticity of brickjncreases can be provided in sizes up to 20 x 30 in. With dove­
w ith compressive strength up to approximately 5000 tails spaced 7 in. on center, the 2Va in. thickness can
psi, after which-, there is little change. The thermal-ex­ be provided in sizes up to 32 x 48 in. Other sizes used
pansions of individual clay units are not the same as are 4 or 6tt x 2 f t Tolerances on length and width are a
the thermal expansion of clay product-faced precast maximum of ± Vi6 in. with a warpage tolerance on the
concrete panels due to mortar joints. exposed face (variation from a plane surface) of not
more than 0.005 in. per in. of length.
Table 7.5.1 Range of physical properties of
clay products
Type Compressive Modulus of Tensile Coefficient
of unit strength, psi elasticity, psi strength, of thermaT
(10®) psi* expansion 7.5.2.3 Design Considerations
in/m./°F

Brick 3,000-15,000 1.4-5.0 S ee note a 4 .0 x 1 0 -6 Clay products are bonded to backup concrete. The
back side of clay product units should preferably have
Quarry 10,000-30,000 7.0 See note a 2.2-4.1 x 10-6
Tileb keyback or dovetail configurations or be grooved or
Glazed 8,000-22,000 1.4-5.0 S ee note a 4 .0 -4 .7 x 1 0 -* ribbed to develop adequate bond.
Wall Latex additives in the concrete or latex bonding
THeb
materials provide high bond and high strength, but
Terra 8,000-11,000 2.8-6.1 S ee note a 4.0 x 10-«
have limitations. They are water sensitive, losing as
Cotta
much as 50% of their strength when wet (although
a. Usually approximated at 10% of the compressive strength. they regain that strength when dry). The lowered
b. See Ref. 5. strength of the concrete is usually sufficient to sustain
low shear stress like the weight of the clay product,
but when differential movements cause additional
7 .S .2 .2 Clay Product Selection [7]
stress, problems can occur.
Clay product manufacturers or distributors should be Generally, clay products cast integrally with the
consulted early in the design stage to determine avail­ concrete have bond strengths exceeding that ob­
able colors, textures, shapes, sizes, and size devi­ tained when laying units in the conventional manner
ations as well as manufacturing capability for special in the field (day product to mortar). It is necessary, in
shapes, sizes and tolerances. In addition to standard either case, to use care to avoid entrapped air or ex­
facing brick shapes and sizes (conforming to ASTM C cess water-caused voids which could reduce the area
216, Type FBX), thin brick veneer units % to % in. thick of contact between the units and the concrete, there­
are available in various sizes, colors and textures. by reducing bond.
Thin brick units should conform to Type TBX of ASTM Bond between the facing and the concrete varies
C 1088. depending on the absorption of the clay product. Low
When a preformed grid is used to position bricks absorption will result in poor bond, as will high ab­
for a precast concrete panel, a brick tolerance of ± 1/i6 sorption due to the rapid loss of the mixing water pre­
in. is necessary. Tighter tolerances may be obtained venting proper hydration of the cement and the devel­
by saw cutting each brick, which increases costs. opment of good bond strength. Bricks with a water
Thin brick should preferably be 1/z to % in. thick to absorption by boiling (ASTM C 216) of about 6% to
ensure proper location and secure fit in the template 9% provide good bonding potential. Bricks with an ini­
during casting operations. tial rate of absorption (suction) less than 30 g per min.
Glazed and unglazed ceramie tile units should per 30 in2, when tested in accordance with ASTM C
conform to American National Standards Institute 67, are not required to be wetted. With a higher rate of
(ANSI) A1371, which includes ASTM test procedures absorption they should be wetted prior to placement
and provides a standardized system for evaluating a of the concrete, to reduce the amount of mix water ab­
tile’s key characteristics. Tiles are typically % to 1/2 in. sorbed, and thereby improve bond. Terra cotta units
thick with a 1Vz% tolerance on the length and width should be soaked in water for at least one hour and
measurements. Within one shipment, the maximum be damp at the time of concrete placement to reduce
tolerance is ± Vie in. When several sizes or sources of suction.

PCI Design Handbook/Fifth Edition 7 -1 3


Clay bricks: wherr removed from the kiln after fir­ to a relative humidityjaf 70%+iavea moisture-ex­
ing, wilt begin to permanently increase in size as r e ­ pansion two to four times- as -large as those ex-
sult-of-absorption of atmospheric moisture. The de­ posed to- RH of 50% over a 4-month interval.
sign coefficient of moisture expansion of day bricks The 70% RH bricks also exhibit almost- a to f
as recommended by.the Brick institute of America is- their expansion within the first twelvemonths of
0.0005 in. per in. but is specified as 0.0003 by Ref. 5. exposure, while-the '50% RH bricks- generally
A value of 0.0005 is typical for ceramic quarry tile. The exhibit a gradual continuous moisture expan­
environmental factors affecting moisture expansion of sion.
clay brick are; Seasonal expansion and contraction of clay bricks
will occur due to changes in the ambient air tempera­
1. Timeof exposure. Expansion increases linearly ture. It is not uncommon for the exterior surface to
with the logarithm of time. It is estimated that, as reach temperatures of 165° F with dark colored brick,
a percentage of total potential moisture expan­ 145°F for medium color, or 120°F for light colored
sion, 25% occurs within two weeks and 60% brick on a hot summer day when directly exposed to
will have occurred approximately one year after solar radiation. Surface temperatures as tow as -30°F
the bricks have been fired. can be reached on a cold night.
2. Time of placement. Expansion subsequent to The expansion of clay products can be absorbed
by dimensional changes of the clay product andgrout
placement in a panel depends on the portion of
total potential for expansion which has already (mortar) or concrete due to:
occurred. 1. Drying shrinkage of the grout.
3. Temperature. The rate of expansion increases 2. Elastic deformation of the grout under stress.
with increased temperature when moisture is
present. 3. Creep of the grout under stress.

4. Humidity. The rate of expansion increases with 4. Elastic deformation of the clay product under
an increase in relative humidity. Bricks exposed stress.

Figure 7.5.2 Relative temperature, creep and moisture movements of concrete, tile, brick and mortar

7 -1 4 PCI Design Handbook/Fifth Edition


In general,, strains imposed slowly and evenly-will The properties^ of the stone will vary with the locality
fiot cause problems: Consider the-first € months To a from which it is_quarried. Sedimentary and metamor-
year after panel production-(see Rgure7.5.2). THe ex- phic rocks such asfimestone anctmarble will exhibit
pansion is small (rate of strain application is slow) but different strengths when measured parallel and per­
mortar shrinkage is nearly complete. The mortar or pendicular to theiroriginai bedding planes. igneous-
-concrete creeps under load to relieve the tensile
rocks-such as granite-may exhibit relatively uniform
stress generated in the tile by the mortar or concrete
strength characteristics on the various planes. In
shrinkage since the tile are relatively rigid. After this
addition, the-surface finish, freezing and thawing, and
time period, the tile has years to accommodate the
additional moisture expansion. large temperature fluctuations will affect the strength
Failures occur when strain rates exceed creep re­ and in turn influence the anchorage system.
lief rates. This can occur when: Information on the durability of the specified stone
should be obtained from the supplier or from observa­
1. Total shrinkage is higher than normal because tions of existing installations of that particular stone.
overly rich concrete or mortar was used. This information should include such factors as ten­
dency to warp, reaction to weathering forces, resist­
2. Sudden rise in temperature or drop in humidity
ance to chemical pollutants, resistance to chemical
causes shrinkage to proceed faster than creep
reaction from adjacent materials, and reduction in
relieves the stresses that are generated.
strength from the effects of weathering.
3. Bond between d a y product and concrete was Testing for mechanical properties should be done
never adequately achieved. on stone with the same finish and thickness as wiH be
used on the structure. An adequate number of test
4. Sudden temperature drop imposes a sudden samples, usually 20, should be selected and statisti­
differential strain because the clay product and cal methods should be used to evaluate the proper­
mortar (or concrete) have different thermal co­ ties and obtain design values. Also, modulus of rup­
efficients of expansion. ture tests (ASTM C 99) are required to demonstrate
The difference in creep characteristics between compliance of the stone to minimum properties speci­
concrete and clay products, along with the differ­ fied by ASTM for the particular stone type [limestone
ences in their respective modulus of elasticity, do not (ASTM C 568); marble (ASTM C 503); granite (ASTM
pose a problem to the production of small (less than C 615)].
30 ft) panels when good quality clay products are The process used to obtain a thermal or flame fin­
used. Some producers have used larger panels after ish on granite veneers reduces the effective thickness
first conducting static load tests simulating differential by about % in. and the flexural strength by 25 to 30 %
creep. [10,12]. Bushhammered and other similar surface fin­
Clay product faced precast panels may be de­ ishes also reduce the effective thickness.
signed as concrete members, neglecting for design
Thermal finishing of granite surfaces causes mi­
purposes, the structural action of the face veneer. The
crofracturing, particularly of quartz and feldspars.
thickness of the precast panel is reduced by the thick­
These microcracks permit absorption of water to a
ness of the veneer and design assumptions usually
depth of about % in. in the distress surface region of
exclude consideration of differential shrinkage or dif­
the stone which can result in degradation by cyclic
ferential thermal expansion. However, if the panel is
to be prestressed, the effect of composite behavior freezing and a further reduction in bending strength.
and the resulting prestress eccentricity should be All natural stone loses strength as a result of expo­
considered in design. sure to thermal cycling, (i.e., heating to 150°F and
cooling to -10°F), and wet/dry cycling. The modulus
of rupture of building stone can be affected by freez­
7.5.3 Natural Stone [8, 9 ,1 0 ,1 1 ]
ing and thawing of the stone. Flexural tests (ASTM C
Natural stone facings are used in various sizes, 880) should be conducted on the selected stone, at
shapes and colors to provide an infinite number of the thickness and surface finish to be used, in both the
pattern and color possibilities. new condition and the condition after 50 cycles of lab­
oratory freeze-thaw testing to determine the reduction
in strength, if any. Suggested freeze-thaw test proce­
7.5.3.1 Properties
dures include (1) dry cycling between 170°F and
The strength of natural stone depends on several -10° F, and (2) freezing in water at -10° F and thawing
factors: the size, rift and cleavage of crystals, the de­ in water at room temperature. Also, stones with high
gree of cohesion, the interlocking geometry of crys­ absorption should also be tested in a saturated condi­
tals, and the nature of cementing materials present. tion as their flexural, shear and tensile properties may

PCI Design Handbook/Fifth Edition 7-15


be significantly lower when wet. An approximateincfi- faeer except at corner butt-joints, to-sucb cases, the
cation of-good durability is a saturated modulus of finished edges should be within ± 1/i6 in. of specified
rupture ofat least 70% of the dry modulus. thickness. However, large=thiekness variations may
For most types of stone? temperature induced lead to the stone-being encased with concrete and
movements are theoretically reversible. However, thus being unable to move.
certain stones, particularly uniform-textured, fine­
grained, relatively pure marble, when subjected to a 7.5-3.3 Anchorage of Stone Facing
large number of thermal cycles, develop an irrevers­
It is recommended that there be no bonding be­
ible expansion in the material amounting to as much
tween stone veneer and concrete backup in order to
as 20% of the total original thermal expansion. This
minimize bowing, cracking and stainingof the veneer.
residual growth is caused by slipping of individual cal-
Even with concrete shrinkage kept to the lowest
cite crystals with respect to each other [13,14]. Such
possible level, there may still be some interaction with
growth, if not considered in the stone size, design of
the facing material either through bond or the me­
the anchors, or the stone veneer joints may result in
chanical anchors of the facing units. This interaction
curling or bowing of thin marble. For relatively thick
will be minimized if a bond-breaker is used between
marble veneers, the expansion effects are restrained
the facing material and the concrete. Connections of
or accommodated by the unaffected portion of the ve­
natural stone to the concrete should be made with
neer. Tests should be performed to establish the
mechanical anchors which can accommodate some
minimum thickness required to obtain satisfactory
relative in-plane movement, a necessity if bond-
serviceability.
breakers are used. One exception is the limestone in­
Volume changesdue to moisture changes in most
dustry which uses rigid, rather than flexible connec­
stones are relatively small and not a critical item in de­
tors. See Ref. 1 for recommendations on bond
sign, except that bowing of the stone can occur. Mois­
breakers and anchorages.
ture permeability of stone veneers is generally not a
The following methods have been used to break
problem (see Table 7.5.2). However, as stone ve­ the bond between the veneer and concrete: (1) a liq­
neers become thinner, water may penetrate in greater uid bondbreaker, of sufficient thickness to provide a
amounts and at faster rates than normally expected, low shear modulus, applied to the veneer back sur­
and damp appearing areas of moisture on the exterior face prior to placing the concrete; (2) a 6 mil polyethyl­
surface of thin stone veneers may occur. These damp ene sheet; (3) a Vs in. polyethylene foam pad; and (4)
areas result when the rate of evaporation of water from a one component polyurethane coating. The use of a
the stone surface is slower than the rate at which the compressible bondbreaker is preferred in order to
water moves to the surface. have movement capability with uneven stone sur­
faces, either on individual pieces or between stone
7.5.3.2 Sizes pieces on a panel.
Stone veneers used for precast facing are usually Mechanical anchors should be used to secure the
thinner than those used for conventionally set stone veneer. The details of anchorage will depend on a
number of things, including:
with the maximum size generally determined by
strength of stone. Table 7.5.3 summarizes typical di­
1. Shrinkage of concrete during curing.
mensions. Veneers thinner than those listed can re­
sult in anchors being reflected on the exposed sur­ 2. Stresses imposed during handling and erec­
face, excessive breakage or permeability problems. tion.
The length and width of veneer materials should be 3. Thermal response caused by different coeffi­
sized to a tolerance of +0, -V s in. since a plus toler­ cients of expansion and by thermal gradients
ance can present problems on precast panels. This (see Chapter 3).
tolerance becomes important when trying to line up 4. Moisture expansion of veneer.
the false joints on one panel with the false joints on an
adjacent panel, particularly when there are a large 5. Service loads.
number of pieces of stone on a panel. Tolerance al­
lowance for out-of-square is ±Vis in. difference in For those veneers rigidly attached or bonded to
length of the two diagonal measurements. Flatness the backup, the differential shrinkage of the concrete
tolerances for finished surfaces depend on the type of and veneer will cause outward bowing in a simple
finish. For example, the granite industry tolerances span panel. The flat surfaces of some veneers, such
vary from %4 in. for a polished surface to 3/is in. for as cut stone, reveal bowing more prominently than
flame (thermal) finish when measured with a 4 ft other finishes. Therefore, bowing may be a critical
straightedge [15], Thickness variations are less im­ consideration even though the rigidity of the cut stone
portant since concrete wilt provide a uniform back helps to resist bowing.

7 -1 6 PCI Design Handbook/Fifth Edition


Table 7.5.2 Permeability ofcommercial build­ mately 50% oversize have been used to allow for dif­
ing stones { 13 ], cu iru/f^/hr/1^ In. ferential-movement between the stone and the con­
thickness crete. However, in most cases, holes 1/«.to-Mi-in.
Stone4ype P re ssu re , p s l larger than the. anchor are common as excessive
io a
looseness-in-hole reduces holding power. Anchor
1 .2 50
hoies should be within ± 3/« in. of the-specified hole
’Granite 0.06-0.08 : 0.11 0.28
spacing , particularly-for the spring clip anchors.
Lim estone 0.36-2.24 4 3 -4 4 .8 0.9-109 For other stone veneers, stainless steel dowels,
M arble 0.06-0.35 1.3-16.8 0.9-28.0 smooth or threaded, are installed to a depth of % the
stone thickness with a maximum depth of 2 in. at
S an dston e 4.2-174.0 51.2 221
angles of 45° to 75° to the plane of the stone. Dowel
Slate 0.006-0.008 0.08-0.11 0.11 size varies from 3/i6 to % in. for most stones, except
that it varies from V* to % in. for soft limestone and
Table 7.5.3 Dimensional parameters of vari­ sandstone and depends on thickness and strength of
ous stone materials stone. The dowel hole is usually 1/i6 to 1/e in. larger in
Mini­ diameter than the anchor, see Figures 7.5.3(C) and
mum
recom­
Maxi­ 7.5.3(D).
Length Width
Stone mum Limestone has traditionally been bonded and an­
mended range range
type area
thick­ (ft) (ft) chored to the concrete, because it has the lowest co­
(ft2)
ness efficient of expansion. Limestone has also traditional­
(in.)
ly been used in thicknesses of 3 to 5 in. but it is now
Marble 1.00 3 -5 2 -5 25 being used as thin as 1% in. When limestone is 2 in.
Travertine 1.25 2 -5 1 -4 16 or thinner, it is prudent to use a bondbreaker, abng
with mechanical anchors. Dowels and spring clip an­
Granite 1.25 3 -7 1 -5 30
chors have been used to anchor limestone. Typical
limestone 1.75 4 -5 2 -4 15 dowel details for limestone veneers are shown in Fig­
ures 7.5.3(C) and 7.5.3(D). The dowels in Figure
Stone veneer is supplied with holes predrilled in
7.5.3(C) should be inserted at angles alternately up
the back surface for the attachment of mechanical an­
and down to secure stone facing to backup concrete.
chors. Preformed anchors fabricated from stainless
Some flexibility should be introduced with all an­
steel, Type 304, are usually used. The number and
chors of stone veneer to precast concrete panels,
location of anchors should be determined by shear
e.g., by keeping the diameter of the anchors to a mini­
and tension tests conducted on the anchors em­
mum, to allow for the inevitable relative movements
bedded in a stone/precast concrete test sample and
which occur with temperature variations and concrete
the anticipated applied loads (both normal and trans­
shrinkage. Unaccommodated relative movements
verse) to the panel. Anchor size and spacing in ve­
can result in excessive stresses and eventual failure at
neers of questionable strengths or with natural planes
an anchor location. Depending on the size of the proj­
of weakness may require special analysis.
ect, consideration may be given to accelerated cyclic
Four anchors are usually used per stone piece with
temperature tests to determine the effects on the an­
a minimum of 2 recommended. The number of an­
chors.
chors has varied from 1 per 1Vz ft2of stone to 1 per 6
Some designers use epoxy to fill the spring clip an­
ft2 with 1 per 2 to 3 ft2 being the most common [1].
chor or dowel holes in order to eliminate intrusion of
Anchors should be 6 to 9 in. from an edge with not
water into the holes and the possible dark, damp ap­
over 30 in. between anchors. The shear capacity of pearance of moisture on the exposed stone surface.
the spring clip (hairpin) anchors perpendicular to the The epoxy increases the shear capacity and rigidity of
anchor legs is greater than when they are parallel and the anchor. The rigidity may be partially overcome by
depends on the strength of the stone. A typical using Vz in. compressible rubber or elastomeric grom­
marble veneer anchor detail with a toe-in spring clip mets or sleeves on the anchor at the back surface of
(hairpin) is shown in Figure 7.5.3(A) and a typical the stone. Differential thermal expansion of the stone
granite veneer anchor detail is shown in Figure and epoxy may cause cracking of the stone veneer;
7.5.3(B). The toe-out anchor in granite may have as this may be overcome by keeping the oversizing of
much as 50% more tensile capacity than a toe-in an­ the hole to a minimum, thereby reducing epoxy vol­
chor depending on the stone strength. ume. It may be preferable to fill the anchor hole with
Depth of anchor holes should be approximately an elastic, fast-curing silicone, which has been proven
one-half the thickness of the veneer (minimum depth to be non-staining to light colored stones, or a low mo­
of % in.), and are often drilled at an angle of 30° to 45° dulus polyurethane sealant.
to the plane of the stone. Holes which are approxi­

PCI Design Handbook/Fifth Edition 7-17


Figure 7.5.3 Typical anchor details

I
!

(A) TYPICAL ANCHOR FOR MARBLE VENEER (B) TYPICAL ANCHOR FOR GRANITE VENEER

VENEER EPOXIED WITH


TAPE

* USE ANCHORS AT OPPOSING ANGLES

(C) TYPICAL ANCHOR FOR LIMESTONE VENEER (D) TYPICAL CROSS ANCHOR DOWEL
FOR STONE VENEER

7 -1 8 PCI Design Handbook/Fifth Edition


The overall effect of either epoxy or sealant materi­ Caulkingshould be-cf-a-type that will not stairrthe
als on the behavior otth e entire veneer should be veneer material, in-some-projects, caulking may be
evaluated priorto their use. Attest, the long-term ser­ installed more-economically and satisfactorily at the:
vice of epoxy is questionable, therefore,-any increase" same time asThe caulkinghetween precashelements.
in shear-value should not be considered in calculating
long-term anchor capacity.
7.5.3.5 Samples
Design of anchorage and size oftherstone should
be based on specific test values for theactual stone to There is now agood background of experience in the
be installed. Anchor test procedures have riot been production and erection of stone veneer-faced pre­
standardized. Test samples for anchor tests should cast concrete panels. However, it is recommended
be a typical panel section of about 1 f£ and approxi­ that, for new and major applications, full scale mock-
mate, as closely as possible, actual panel anchoring up units be manufactured to check out the feasibility
conditions. A bondbreaker should be placed be­ of the production and erection process. Tests on sam­
tween stone and concrete during sample manufac­ ple panels should be made to confirm the suitability of
ture to eliminate any bond between veneer and con­ the stone and anchors and the effects of bowing on
crete surface. Each test sample should contain one the panel’s performance. Tests on the behavior of the
anchor connecting stone to concrete backup and a unit for anticipated temperature changes may be re­
minimum of 5 tests are needed to determine tensile quired. Mockups should be built to test wall, window
(pull-out) and shear strength of each anchor. Depend­ and joint performance under the most severe wind
ing on the size of the project it may be desirable to per­ and rain conditions. Acceptance criteria forthe stone,
form shear and tensile tests of the anchors at intervals as well as the anchorage, should be established in the
during the fabrication period. project specifications.
Safety factors are recommended by the stone
trade associations and the suppliers of different kinds
of building stones. Because of the expected variation 7.6 Design Example—Window Wall Panel
in the physical properties of natural stones and the ef­ This example illustrates the design of a 2-story high
fects of weathering, recommended safety factors are non-load bearing window wall with deep reveals. The
larger than those used for manufactured building ma­ project is a 4-story building with a structural steel
terials, such as steel and concrete. The minimum rec­ frame and cast-in-place concrete floor slabs. Precast
ommended safety factor, based on the average of the concrete window wall panels are supported at their
test results, is 3 for granite, 4 for anchorage compo­ lowest points, and tied back to the structure at the
nents in granite [15], 8 for limestone veneers [16], floor and roof levels. They transfer only horizontal
and 5 for marble veneers [14]. If the range of test val­ loads to the steel frame. The vertical loads are trans­
ues exceeds the average by more than ± 20% then ferred directly to the foundation (see Figure 7.6.1).
the safety factor should be applied to the lower bound
value.
Given:
7.5.3.4 Veneer Jointing Wind load = 15 psf, both during erection and
in service conditions
Joints between veneer pieces on a precast element
should be a minimum of 'A in. The veneer pieces may fc = 5000 psi at 28 days
be spaced with a non-staining, compressible spacing fci = 2000 psi at stripping
material, or a chemically neutral, resilient, non-remov­
able gasket which will not adversely affect the sealant
to be applied later. The gaskets are of a size and con­ Problem:
figuration that will provide a recess to receive the seal­ Exposed face to be designed “crack free” by limit­
ant and also prevent any backing concrete from enter­ ing tensile stresses in the panel to 5 /IT during han­
ing the joint between the veneer units. Shore A dling and 5 in service.
hardness of the gasket should be less than 20.
When stone veneer is used as an accent or feature
strip on precast concrete panels, a Vz in. space is left Solution:
between the edge of the stone and the precast con­ Step 1:
crete to allow for differential-movements of the materi­ Design panel for handling—see Chapter 5.
als. This space is then caulked as if it were a conven­ Each piece will be cast, stripped, stored, and
tional joint. shipped in the flat, face-down position.

PCI Design Handbook/Fifth Edition 7 -1 9


Determine Hanetting Multipliers (Table 5.2.1) At Section G-C:
Stripping: surface is not retarded, use 1.7 minimum Ag —0.001 bt = 0.001 (96)^5)
Yardrtaana'iing: 1.2
= 0.48 in2
Shipping: 1.5
Erection: 1.5 Transverse Bending
By inspection, the section is very stiff in the trans­
Determine Allowable Tenstte Stress Jn Exposed Face verse direction. Therefore, use minimum reinforce­
{Sect. 5.2.4) ment as shown in the summary, Figure 7.6.3.
At stripping, yard handling and storage:
Step 2:
f; = 572000 = 224 psi
Design for condition during erection:
At shipping and erection:
Overall construction sequence:
f; = 5^5000 = 353 psi
1. Erect structural steel frame.
2. Cast floor slabs.
Check Handling Stresses
3. Set precast concrete wall panels.
Since all handling except erection is to be in the flat
position, using the same lift points, it is apparent that Precast concrete erection sequence:
stripping is the critical design condition. The loading 1. Set bottom panel with lateral connections
and moment diagramsare shown in Figure 7.6.2. at points 1 and 3 only (Figure 7.6.1).
When appearance or exposure to weather is not 2. Make lateral connection at point 2.
critical, cracking on the unexposed face during strip­ 3. Set upper panel with lateral connection at
ping and handling may be acceptable. Pick points points 4 and 6 only.
were selected in this example to maintain an un­ 4. Make lateral connection at point 5.
cracked back face.
Wind load on panel:
Section properties at Section B-B: w = 15(8) = 120 Ib/ft = 0.12 kip/ft
A = 202 in2 I = 6044 in4
Determine Loads on Connections (see Figure 7.6.4)
yb = 8.00 in. Sb = 755 in3
Before connection at point 2 is made:
yt = 10.00 in. S, = 604 in3 a. Due to eccentric panel weight (Detail B):
Weight = 14 kips; e = 5 in.
Section properties at Section C-C:
14(5)
A = 520 in2 I = 1801 in4 Ri = { - R3) = 0.28 kips
21 ( 12)
yb = 2.85 in. Sb = 632 in3
b. Due to wind:
yt = 6 .1 5 in. St = 293 in3
0.015(8) (22.67)
1.36 kips
Stress Summary:
c. Load from upper panel on lower panel:
Location Moments (kip-in) With connection 2 made before setting the
Tensile
No 1.7 Stress (psi) upper panel, the lateral loads at 1,2 and 3
multiplier multiplier are indeterminate. To simplify, conserva­
1 -29 -49 167 < 224 tively assume connection 2 has not been
2 -83 137 <224
made.
-49
Weight of upper panel = 13.3 kips
3 +45 +77 102 < 224
e (detail A) = 13 - 5 = 8 in.
4 +41 +70 111 < 224
13.3(8)
5 -69 -117 194 < 224 Ri = ( - Ra) = 0.42 kips
21 ( 12)
6 -32 -55 209 < 224
d. Design loads (ACI318-95, Sect. 9.2):
Two connections per panel
Design Panel Reinforcement for Stripping___
G = 1.4D + 1.7L
Since the tensile stress is below 5 72000, only
minimum reinforcement is required. = 1.4(0.28 + 0.42)/2 =0.49 kips
At Section B-B: U = 0.75(1.4D + 1.7L + 1.7W)
minimum As = 0.001 bt = 0.001 (area) = 0.75[1.4(0.70) + 1.7(1.36)]/2
= 0.001(202) = 0.202 in2 = 1.23 kips

7 -2 0 PCI Design Handbook/Fifth Edition


Figure 7.6.1 Window wail panel example

£ COLUMN <£GQLLIMN
24'-0" LATERAtLOAD
-CONNECTIONS:

SECTIO N B - B

Figure 7.6.2 Loads and moments on panel at e. Loads on upper panel connections:
stripping An analysis similar to a through d on the
upper panels shows that the maximum de­
sign load on the connection is 0.92 kips.
For simplicity, design all connections for a
lateral load of 1.23 kips. An additional load
factor of 1.3 (see Sect. 6.3) is considered
appropriate for this connection.
1.3(1.23) = 1.60 kips

Check Panel Bending


Before connection at point 2 is made:
M = w€2/8 = 0.12(21.0)78
= 6.62 kip-ft = 79.4 kip-in.
Mu= 0.75(1.7W) = 0.75(1.7) (79.4)
= 101 kip-in.
This is less critical than condition at stripping.

Connection Design (Figure 7.6.4)


Assume the panel weight is transferred through
shims at the second floor and foundation (Details A
and B). The shims must be large enough to transfer
load in plain concrete bearing (Sect. 6.8).

PCI Design Handbook/Fifth Edition 7-21


Figure 7.6.3 Reinforcement summ ary

Fy = 36 ksi
27.3 kips
Use 1.3 connection load factor. / 4Nug 4 (1.60) (4)
t = 0.36 in.
Vu (each connection) = 27.3(1.4)(1,3)/2 <|)Fyb 0.9(36) (6)
= 24.8 kips
Use 6 x 6 x % angle 6 in. long.
For more efficient erection, use same size shims
throughout. Try 4 in. by 4 in. shims. From Table 6.20.9, the minimum % in. bolt is ade­
quate: 4>Tn = 10 kips > 1.6 kips.
Foundation concrete fi = 3000 psi.
The bolt in the foundation resists both tension and
Panel to panel shims: shear:
Ai = A2 and Cr = 1.0 with separate tieback Taking moments about the upper toe of the angle:
connections (using Eq. 4.6.1)
3.5TU = 2(1.60); Tu = 0.91 kips
<t>Vn = 0.7 (0.85) (5) (4) (4)
= 47.6 kips > 24.8 kips OK
The interaction equation, Eq. 6.5.14, is applicable:

Panel to foundation shims: From Fig. 6.15.9, Ps = 10,4 kips; Vs = 5.0 kips

10( 10)
= 2.5 Use 2.0 max
4(4) 0.91
+ 1.60\ 2
0.9 10.4 5 .0 /
4>Vn = 0.7 (0.85) (3) (2) (4) (4)
^ ( 0 . 0 0 8 + 0.102) = 0.12 < 1.0 OK
= 57.1 kips > 24.8 OK 0.9

Connection at point 1:
(Note: The connection at Point 4 would be similar
Angle and bolt design: Choose a 6 in. long angle
to Point 1. See Chapter 6 for examples of these “clip
and minimum % in. diameter bolts. Note: Smaller
angle" type connections.)
bolts are likely to be damaged during handling.

7 -2 2 PCI Design Handbook/Rfth Edition


Connections "at points 2, 2 a n d 5 :

Determine angle thickness:


tw =0707(0.31) = 0.221rs.
Icy 5 irr. long angles
Conservatively use elastic section-properties.
FronvEq.-65.17 with g. = 6 in.; b = 5-in.
From Fig. 6.15.19, Case 2 ;
4Nug 4(1.60) (6) S = d2tw/3 = {2.5)2 0.22/3
t = = jO.49 in.
4>Fyb 0.9(36)(5)
= 0.46 in3

From Fig. 6.15.1:


Use angle 8 x 4 x Vi x 5 in. long.
E70 electrodes, allowable stress 31.5 ksi
Design weld to beam flange:
f = £ + M = 1.60 + 1-60(6)
Refer to Sect. 6.5.6. A S 0.22(2.5)(2) 0.46

Try 5/ie in. weld by 2Vz in. long each side of angle: = 1.45 + 20.87 = 22.32 < 31.5 OK

Figure 7.6.4 Connection design—example problem

DETAIL C

SECTION

DETAIL B DETAIL D

PCI Design Handbook/Fifth Edition 7 -2 3


7.7 References 10. Chin, I.R., Sfeeich, J.P.,_and Ertin, B., “Design-of
Thin Stone Veneers on Buildings,” Building
t. “Architectural Precast Concrete,” Second Edi­
Stone Magazine, May-June 1986.
tion, MNL-122-89, Precast/Prestressetf Con­
crete Institute, Chicago, IL, 1989. 11. “StonerVeneer-Faced Precast Concrete-Pan­
els,” PR-22, Precast/Prestressed Concrete In­
2. Sheppard, D.A., and Phillips,'W.R., “Plant-Cast
stitute, Chicago, IL, 1986.
Precast and Prestressed Concrete—A Design
Guide,"’ Third Edition, McGraw-Hill Publishing 12. “Italian Marble Technical Guide, ” V. 1,1982 Edi­
Co., New York, NY, 1989. tion, Italian Institute for Foreign Trade, New
York, NY, 1982.
3. ACI Committee 347, “Precast Concrete Units
Used as Forms for Cast-in-Place Concrete,” 13. “Building Construction Handbook,” Third Edi­
Journal of the American Concrete Institute, V. tion, Frederick S. Merritt, Editor, McGraw-Hill
66, No. 10, October 1969. Book Co., New York, NY, 1975.

4. “Formwork for Concrete,” Fifth Edition, Special 14. “Dimensional Stone: Design Manual III,” Marble
Publication SP-4, American Concrete Institute, Institute of America, Farmington, Ml, 1985
Farmington Hills, Ml, 1989.
15. “Specifications for Architectural Granite,” 1986
5. Fitzgerald, J.V., and Kastenbein, E.L., “Testsfor Edition, National Building Granite Quarries As­
Engineering Properties of Ceramic Tile,” ASTM sociation, West Chelmsford, MA, 1986.
Bulletin No. 231, American Society for Testing
and Materials, Philadelphia, PA, July 1958. 16. “Indiana Limestone Handbook,” Indiana Lime­
stone Institute of America, Bedford, IN,
6. “Building Code Requirements for Masonry 1984-1985.
Structures,” ACI 530-88/ASCE 5-88, and “Spec­
ifications for Masonry Structures,” ACI 17. Kulka, Felix, Lin, T.Y., and Yang, Y.C., “Pre­
530.1-88/ASCE 6-88, American Concrete Insti­ stressed Concrete Building Construction Using
tute, Farmington Hills, Ml/American Society of Precast Wall Panels,” PCI Journal, V. 20, No. 1,
Civil Engineers, Reston, VA, 1989. January-February 1975.

7. Bernett, Frank E., “Effects of Moisture Expan­ 18. Freedman, Sidney, “Clay Product-Faced Pre­
sion in Installed Quarry Tile,” Ceramic Bulletin, cast Concrete Panels,” PCI Journal, V. 39, No.
V. 5, No. 12, The American Ceramic Society, 1, January-February 1994.
1976.
19. “Architectural Precast Concrete Cladding—It’s
8. McDaniel, W. Bryant, “Marble-Faced Precast Contribution to Lateral Resistance of Build­
Panels,” PCI Journal, V. 12, No. 4, July-August ings,” Proceedings, SP-CP, Precast/Pre­
1967. stressed Concrete Institute, Chicago, IL, 1990.

9. “Marble-Faced Precast Panels,” National Asso­


ciation of Marble Producers, 1966.

7 -2 4 PCI Design Handbook/Fifth Edition


CHAPTER 8
TOLERANCES FOR PRECAST AND
PRESTRESSED CONCRETE

8.1 General ................................................................................................... - ......... 8 -2


8.1.1 Definitions ................................................................. . ........................ 8 -2
8.1.2 Purpose ................................................................................................. 8 -2
8.1.3 Responsibility .................................................................... 8 -2
8.1.4 Tolerance Acceptability Range ........................................................... 8 -3
8.1.5 Relationships Between Different Tolerances....................................... 8 -3

82 Product Tolerances...... ............................. . ....................................................... 8 -3


8.2.1 General.................................................................................................. 8 -3
8.2.2 Overall Dimensions .............................................................................. 8 -3
8.2.3 Sweep or Horizontal A lignm ent.......................................................... 8 -5
8.2.4 Position of S trands............................................................................... 8 -5
8.2.5 Camber and Differential Camber ....................................................... 8 -5
8.2.6 Weld P la te s.......................................................................................... 8 -5
8.2.7 Haunches of Columns and Wall Panels............................................ 8 -5
8.Z8 Warping and B ow ing............................................................................. 8 -6
8.2.9 Smoothness ......................................................................................... 8 -6
8.2.10 Architectural Panels vs Structural W alls............................................ 8 -6

8.3 Erection Tolerances ............................................................................................. 8 -6


8.3.1 General.................................................................................................. 8 -6
8.3.2 Recommended Erection Tolerances ................................................. 8 -8
8.3.8 Mixed Building S ystem s..................................................................... 8 -8
8.3.4 Connections and B earing...................................................................... 8 -8

8.4 Clearances ............................................................................................. 8 -8


8.4.1 General.................................................................................................. 8 -8
8.4.2 Joint Clearance....................................................... 8 -8
8.4.3 Procedure for Determining C learance........................................ 8 -1 4
8.4.4 Clearance E xam ples............................................... 8 -1 4

8.5 Interfacing Tolerances ....................................................................................... 8 -1 6


8.5.1 General................................................................................................. 8 -t6
8.5.2 Interface Design Approach................................................................. 8 -1 8
8.5.3 Characteristics of the Interface ......................................................... 8 -1 8

8.6 References .......................................................................................................... 8 -2 0

PCI Design Handbook/Fifth Edition 8


TOLERANCES FOR PRECAST AND PRESTRESSED CONCRETE

3.1 General ing erection. Clearance is generally allowed to vap-


so the-primary control surface can be set within toler­
The intent of this Chapter is to briefly present the
ance.
subject o f tolerances and to provide the designer
Secondary Control Surfaces—A surface on a
with some of the most basic tolerances that should be
precast element, the location of which is dependent
considered during the layout and design of struc­
on the locational tolerance o f the primary control sur­
tures. This chapter is a cursory presentation of infor­
face plus toe product tolerances.
mation that has been previously published by PCI
Feature Tolerance—The locational or dimension­
and reviewed by the precast concrete industry. Be­
al tolerance of a feature, such as a corbel or a block-
cause of this fact, other PCI documents (see fiefs.
out, with respect to the overall member dimensions.
1-5 ), which discuss more fully the subject of toler­
ances, need to be specified in contract documents
and referred to when attempting to resolve questions 8.1.2 Purpose
about tolerances.
Tolerances are normally established by economi­
cal and practical production, erection and interfacing
8.1.1 Definitions considerations. Once established, they should be
shown in toe project documents, and used in design
Tolerance—
and detailing of components and connections. Archi­
•The permitted variation from a basic dimension
tectural and structural concepts should be developed
or quantity, as in the length or width of a member.
with the practical limitations of dimensional control in
•The range of variation permitted in maintaining a
mind, as the tolerances will affect toe dimensions of
basic dimension, as in an alignment tolerance.
toe completed structure.
•A permitted variation from location or alignment.
Tolerances are required for toe following reasons:
Product Tolerances—Those variations in dimen­
sions relating to individual precast concrete mem­ Structural. To ensure that structural design ac­
bers. counts for factors sensitive to variations in dimension.
Erection Tolerances—Those variations in dimen­ Examples include eccentric loadings, bearing areas,
sions required for acceptable matching of precast and locations of reinforcement and embedded items.
members after they are erected. Feasibility. To ensure acceptable performance of
Interfacing Tolerances—Those variations in di­ joints and interfacing materials in the finished struc­
mensions associated with other materials in contact ture.
with or in close proximity to precast concrete. Visual. To ensure that the variations will be con­
Variation—The difference between the actual and trollable and result in an acceptable looking struc­
the basic dimension. Variations may be either nega­ ture.
tive (less) or positive (greater). Economic. To ensure ease and speed of produc­
Basic Dimension—Those shown on contract tion and erection.
drawings or described in specifications. Basic di­ Legal. To avoid encroaching on property lines
mensions apply to size and location. May also be and to establish a standard against which the work
called “nominal” dimensions. can be compared.
Working Dimension—The planned dimension of Contractual. To establish an acceptability range
a member which considers both its basic dimension and also to establish responsibility for developing
and joints or clearances. For example, a member and maintaining specified tolerances.
with a basic width of (nominal) 8 ft-0 in. may have a
working width of 7 ft-11 in. Product tolerances are ap­ 8.1.3 Responsibility
plied to working dimensions.
While the responsibility for specifying and main­
Actual Dimension—The measured dimension of
taining tolerances of the various elements may vary
the member after casting. This may differ from the
among projects, it is important that these responsibi­
working dimension due to construction and material-
lities be clearly assigned. The conceptual design
induced variation.
phase of a precast project is the place to begin con­
Alignment Face—The face of a precast element
sideration of dimensional control. The established tol­
which is to beset in alignment with the face of adja­
erances or required performance should fall within
cent elements or features.
generally accepted industry limits and should not be
Primary Control Surface—A surface on a pre­
made more restrictive than necessary.
cast element which is dimensionally controlled dur­

8 - 2 PGI Design Handbook/Fifth Edison


O nce the tolerances have been specified, and On occasion, the structure may not perform prop­
connections: which consider those tolerances have erly -if the tolerances are allowed to accumulate.
been designed, the production of the eiements must Which tolerance takes-precedence is-a question of
be organized ferassure tolerance compliance. economics. The costs associated- with each of the
An organized quality xiontrol-program-which em­ three tolerances must be evaluated, recognizing_un­
phasizes dimensional controlis necessary. Likewise, usual situations. This may include difficult erection
an erection quality assurance program which in­ requirements, connections which are tolerance sen­
cludes a clear definition o f responsibilities will aid in sitive, o r production requirements which are set by
assuring that the products are assembled in accor­ the available equipment. Any special tolerance re­
dance with the specified erection tolerances. quirements should be clearly noted in the contract
Responsibility should include dimension verifica­ documents.
tion and adjustment, when necessary, of both pre­ It is important for the designer of record to be
cast components and any interfacing structural ele­ aware of and take into consideration the tolerances of
ments. other building materials and systems used in the proj­
ect {7,8,9].
8.1.4 Tolerance Acceptability Range

Tolerances must be used as guidelines for accept­ 8.2 Product Tolerances


ability and not limits for rejection. If specified toler­
ances are met, the member should be accepted. If
8.2.1 General
not, the member may be accepted if it meets any of
the following criteria: Product tolerances are listed in the reports of the
PCI Committee on Tolerances [1,2]. These reports
1. Exceeding the tolerance does not affect the
contain more complete discussion of tolerances and
structural integrity or architectural performance
should be referred to for more specific details, such
of the member.
as location tolerances for inserts, voids, haunches
2. The member can be brought within tolerance and corbels and for such things as warping toler­
by structurally and architecturally satisfactory ances and local smoothness requirements. The most
means. recent Committee Report published in 1993 is a sup­
plement to the original 1985 report and presents sev­
3. The total erected assembly can be modified to eral additional products to the previous list of prod­
meet all structural and architectural require­ ucts discussed, such as prison cell modules and
ments. stadium risers. Tolerances are also presented more
completely in the Manual for Quality Control for Plants
8.1.5 Relationships Between Different and Production of Precast and Prestressed Concrete
Tolerances Products [3], the Manual for Quality Control for Plants
A precast member is erected so that its primary and Production o f Architectural Precast Concrete
control surface is in conformance with the estalished Products [4] and the Recommended Practice for
erection and interfacing tolerances. The secondary Erection o f Precast Concrete [5]. The products in­
control surfaces are generally not directly positioned cluded are listed in Table 8.2.1. Discussion of the
during erection, but are controlled by the product tol­ more critical tolerances are given inthe following sec­
erances. Thus, if the primary control surfaces are tions. The values shown have become the consen­
within erection and interfacing tolerances, and the sus standards of the precast concrete industry and
secondary surfaces are within product tolerances, these values are occasionally different from toler­
the member is erected within tolerance. The result is ances published by other organizations [8]. More re­
that the tolerance limit for the secondary surface may strictive tolerances may significantly increase costs,
be the sum of the product and erection tolerances. so should not be specified unless absolutely neces­
Since tolerances for some features of a precast sary.
member may be additive, it must be clear to the erec­
8.2.2 Overall Dimensions
tor which are the primary control surfaces. If both pri­
mary and secondary control surfaces must be con­ Tolerances for the overall dimensions of most
trolled, provisions for adjustment should be included. common products are given in Table 8.2.1. Architec­
The accumulated tolerance limits may have to be ac­ tural precast concrete panels have plan dimension
commodated inthe interface clearance. Surface and tolerances that vary with panel size from ± Vs in. for a
feature control requirements should be clearly out­ dimension under 10 ft to ± 'A in. for a dimension of 20
lined in the plans and specifications. to 40 ft. Overall thickness of wall panels are listed in
Table 8.2.1 under depth tolerances.

PCI Design Handbook/Fifth Edition 8 -3


Table 8.2.1 Typieal tolerances for precast, Ta b le 8.2.2 ErectioiU olerances Tor interface
prestressed concrete products3 design
Produet Tolerances Products Recommended
Item Tolerances (in.):
Lenglhb—
± Yt in. 10,17,18 Variation in p la n location (any
co lu m n o r b ea m , a n y lo c a tio n ). ± V2
± Vz in. 6 ,778,9 ,10 ,15
± 3A in.
± 1 in.
^0,5
1,2.4,11,12,14
Variation in p lan parallel to
s p e c ified building lines................. 'Ao p er ft, an y b e a n
less th a n 2 0 ft o r
Widthb— a d ja c e n t colum ns
± Vi in. 1,2,3,5,6,7,8,9, less than 2 0 ft apart
12,15,17,18 V2, a d ja c e n t columns
2 0 ft or m o re apart
+ 3/s in. 14
+ % in., - 1/4 in. 4 Difference in relative position
11,13 of a d ja c e n t colu m n s fro m
± % in.
specified relative position
Depth— (a t a n y d e c k l e v e l ........................... Vz
+ 1/4 in., - 'A in. 10,18
Variation fro m p lu m b ....................... Vi, an y 10 ft o f height
± 1/4 in. 1,2,3,5,6,7,8,9,
1., m axim um for the
12,14,15 entire h e ig h t
+ Vz in., - V* in. 4 Variatron in elevation of bearing
surfaces fro m specified elevation
± % _in. 11
(any c olu m n o r b ea m , any
± Vfc in. 13 lo c a t io n ) ............................................. ± V6
Flange Thickness—
Variation of to p of s pan drel fro m
+ Vi in., - Ve in. 1,2,8,10,12,15
specified elevation
± 1/4 in. 3,4,13 (any lo c a t io n ) .................................. ± ' A
Web Thickness—
Variation in elevation of bearing
± Vfe in. 1,8,10,12,15 su rfaces fro m lines parallel lo
± 1/4 in. 2,3 specified g ra d e lines...................... Vio p e r ft, any b eam
+ % in., - 1/4 in. 4 less th a n 2 0 ft or
a d ja c e n t colum ns
± % in. 5 less th a n 2 0 ft apart
Position of Tendons— 1/2, m axim um any
I, 2,3,4,5,6,8,9, b e a m 2 0 ft or m ore in
± 1/4 in.
length o r adjacent
II, 12,14,1518 co lu m n s 2 0 ft or
± Vi in. 10 m o re apart
Camber, variation from
V a riatio n fro m specified bearing
design— leng th o n s u p p o r t ............................± 3A
± 1/4 in. per 10ft, 1,2,12,15
V ariatio n fro m specified bearing
± % in. max.
w idth on s u p p o r t............................ ± Vz
± Vb in. per ft, 4
± 1 in. max. J o g in a lig n m e n t of m atching
e d g e s ................................................ Vz, m axim um
± % in. max. 3
± Vfc in. max. 5,15 a. For more details such as 5 =
box beam
Camber, differential— graphic descriptions of fea­ 6 =
column
tures to which tolerances 7 =
hollow-core slab
1/4 in. per 10 ft, 1,2,5
apply and tolerances for 8 =
ribbed wall panel
3/ i in. max. sleeves, blockouts, inserts, 9 =
insulated wall panel
± 1/4 in. per 10 ft, plates, end squareness, sur­ 10 =
architectural wall panel
face smoothness, etc., see 11 =
pile
± Vz in. max. 15
committee report [1]. 12 =
joist
Bearing Plates, position— 13 =
step unit
b. See Sect. 8.2.2 for di­
± V£ in. 1,2,3,12 14 =
sheet piling
mensional tolerances for
15 =
single riser bleacher
± Vs in. 4 architectural wall panels.
slabs
Bearing Plates, tipping Key: 16 = prison cell m o d ule-
1 = double tee single
and flushness—
2 = single tee 17 = prison cell module-
± 1/e in. 1,2,3,4,12,15 3 = building beam double
(rect. and ledger) 18 = prestressed concrete
4 = I-beam panels for storage tanks

8 -4 PCI Design Handbook/Fifth Edition


Top and bottom slabs (flanges) o f box beams and Table 8.2.3 Recommended clearances
hollow-core slabs are dependent-am the position of
cores. Flange thickness-tolerances are not given for Recommended Mini­
Item
hollow-core slabs, instead, measured flange areas mum Clearance(in.)
cannot be less than 85% of the nominal calculated
Precast to precast % ^ p re fe rre d )
area
The committee report emphasizes- that the rec-
Precast to cast-in-place T (2 preferred)
tjmm endediolerances are only guidelines. Different
values may be applicable in some cases, and each
Precast to steel -1 (2 preferred)
project should be considered individually.
VA. (3 preferred for tall
Precast column covers
buildings)
8.2.3 Sweep or Horizontal Alignment

Horizontal misalignment, or sweep, usually oc­


curs as a result of form and member width tolerances. required to erect the members in a manner which is
It can also result from prestressing with lateral eccen­ satisfactory for the intended use.
The final installed differential between two adja­
tricity, which should be considered in the design.
cent cambered members erected in the field may be
Joints shouid be dimensioned to accommodate such
the combined result of member differential cambers,
variations.
Sweep tolerances generally vary with length of variations in support elevations, and any adjustments
unit, for example, ± Ve in. per 10 ft. The upper limit of made to the members during erection.
For most flexural members, maximum camber
sweep varies from ± % in. for wall panels and hollow-
variation from design camber is ± 3A in., and maxi­
core slabs to ± % in. for joists usually used in com­
mum differential camber between adjacent units of
posite construction.
the same design is 3A in. This may be increased for
joists used in composite construction. Recommen­
8.2.4 Position of Strands dations for camber and differential camber of hollow-
core slabs are not listed, because production varia­
It is a common practice to use % in. diameter
tions between hollow-core systems result in different
holes in end dividers (bulkheads or headers) fo r3/sto
tolerances for each type.
1/2 in. diameter strands, since it is costly to switch end
dividers for different strand diameters. Thus, better
accuracy is achieved when using larger diameter
strands.
8.2.6 Weld Plates
Generally, individual strands must be positioned
within ±Vt in. of design position and bundled strands In general, it is easier to hold plates to closer toler­
within ±Vfe in. Hollow-core slabs have greater indi­ ances at the bottom of the member (or against the
vidual strand tolerances as long as the center of grav­ side form) than with plates cast on top of the member.
ity of the strand group is within ± 1A in. and a mini­ Bottom and side plates can be fastened to the form
mum cover of 3A in. is maintained.
and hence are less susceptible to movement caused
by vibration. This applies to position of weld plates as
8.2.5 Camber and Differential Camber well as tipping and flushness.
The tolerance on weld plates is less restrictive than
Design camber is generally based on camber at for bearing plates. The position tolerance is ± 1 in. for
release of prestress; thus, camber measurements on all products except for hollow-core slabs where the
products should be made as soon after stripping as tolerance is ± 2 in.; tipping and flushness tolerance is
possible. Differential camber refers to the final in- ± 1/4 in.
place condition of adjacent products.
It is important that cambers are measured at the
same time of day, preferably in the early hours before
the sun has begun to warm the members. Cambers
8.2.7 Haunches of Columns and Wall Panels
for all units used in the same assembly should be
checked at the same age. The importance of corbel and haunch location tol­
If a significant variation in camber from calculated erances depends on the connection at the base of
values is observed, the cause should be determined the member. Since base connections usually allow
and the effect of the variation on the performance of some flexibility, it is more important to control dimen­
the member evaluated. If differential cambers exceed sions from haunch to haunch in multilevel columns or
recommended tolerances, additional effort is often walls than from haunch to end of member.

PCI Design Handbook/Fifth Edition 8 -5


The haunch to haunch tolerance is ±V& in-Bear- Table S.2.4 Panel thickness (in,) to maintain
ingsurface squareness toleranceis _± Vain. per 18 in. bowing and warping within sug-
with a-maximum o f ± !4 in., except for architectural gested normal tolerancesah
precast concrete panels, w itira tolerance o f ± Vs in., rfarael
and columns, with a maximum af i Vs in. in short di­ dimensions, ft 1® ^ *0 12- 16 20 24 28 32
rection and ±% in. in tong direetionT
4 3 4 4 5 5 6 6 7
6 3 4 4 5 5 6 6 7 -
8.2.8 Warping and Bowing 8 4 5 5 6 6 7 7 8
Warping and bowing tolerances affect panel edge 10 5 5 6 6 7 7 8 8
matchup during erection, and the appearance of the
erected members. They are especially critical with ar­ a. Do not use this tabte for panel thickness selection.
b. For ribbed panels, the overall thickness of ribs may be
chitectural panels.
used for comparison with this table if the ribs are
Warping is a variation from plane in which the cor­ continuous from one end of the panel to the other.
ners of the pane! do not falf within the same plane.
Warping tolerances are given in terms of corner varia­
tions, as shown in Figure 8.2.1. The allowable varia­ 8.2.10 Architectural Panels vs Structural Walls
tion from the nearest adjacent comer is 1/i« in. per ft. When discussing tolerances, “architectural panel”
Bowing differs from warping in that two opposite refers to a class of tolerances specified, and not nec­
edges of a panel may fall in the same plane, but the essarily to the use of the member in the final structure.
portion between is out of plane (Figure 8.2.2). Bowing Architectural panels usually require more restrictive
tolerance is L/360, where L is the length of bow. Maxi­ tolerances than structural members for aesthetic rea­
mum tolerance on differential bowing between pan­ sons.
els of the same design is Vz in. Doubletees, hollow-core slabs and solid slabs are
The effects of differential temperature and mois­ often used for exterior facades, but are not classed as
ture absorption between the inside and outside of a “architectural panels”. Since the above listed prod­
panel and the prestress eccentricity should be con* ucts are manufactured the same whether they are ar­
sidered in design of the panel and its connections. chitectural or structural products, the manufacturing
Pre-erection storage conditions may also affect warp­ accuracy for the product when used architecturally
ing and bowing (see Sects. 3.3.2 and 5.2.10). should not be expected to meet “architectural panel”
Thin panels are more likely to bow, and the toler­ tolerances. If more restrictive tolerances are re­
ances should be more liberal. Table 8.2.4 gives thick­ quired, they must be clearly indicated in the contract
nesses, related to panel dimensions, below which the documents, and subsequently increased costs antic­
warping and bowing tolerances given above may not ipated.
apply. (Note: Table 8.2.4 is not intended to limit pan­
el thickness.) For example, a panel that is 16 x 8 ft,
and less tharr6 in. thick, may require greater warping 8.3 Erection Tolerances
and bowing tolerance than indicated above.
Similarly, panels made from concrete with over %
8.3.1 General
in. aggregate, panels using two significantly different
concrete mixes, and veneered and insulated panels Erection tolerance values are those 1o which the
may require special consideration. In all cases, the primary control surfaces of the member should be
local precaster should be consulted regarding overall set. The final location of other features and surfaces
economic and construction feasibility. will be the result of the combination of the erection tol­
erances- and the product tolerances given in Sect.
8. 2.
Because erection is equipment and site depen­
dent, there may be good reason to vary some of the
8.2.9 Smoothness recommended tolerances to account for unique proj­
Local smoothness describes the condition where ect conditions. Combining liberal product tolerances
small areas of the surface may be out of plane, as with restrictive erection tolerances may place an un­
shown in Figure 8.2.3. The tolerance for this type of realistic burden on the erector. Thus, the designer
variation is Vi in. per 10 ft for all products. The toler­ should review proposed tolerances with manufactur­
ance is usually checked with a 10 ft straight edge or ers and erectors prior to deciding on the final project
the equivalent, as explained in Figure 8.2.3. tolerances.

8 - 6 PCI Design Handbook/Fifth Edition


Figure 8.2.2 Definition of panel bowing
MAXIMUM MAXIMUM
BOWING BOWING

(CONVEX BOWING) (CONCAVE BOWING)

BOWING

ELEVATION PANEL BOWED IN BOTH


PLAN AND ELEVATION

PCI Design Handbook/Fifth Edition 8 -7


Figure 8.2.3 Local smoothness variation 8.3.4 Connections and Bearing
The details o f connections must be considered
r - EXPOSED'SURFACE OF PRECAST UNIT when specifying erection tolerances. Space must be
proyJded to make the connection under the most ad­
verse combination of tolerances.
VARIATION IN LOCAL Bearing tength is measured in the direction ofthe
— SMOOTHNESS —
span, and bearing width is measured perpendicular
to the span. Bearing length is often not the same as
10' STRAIGHTEDGE
the length of the end of a member over the support,
l as shown in Figure 8.3.6. When they differ, it should
I |
be noted on erection drawings.
1
rr i —z b 7
r* The Engineer may wish to specify a minimum
4^
4 4 i
a « . 4 bearing for various precast products. For further in­
formation, see Ref. 6.
SHIM % "S HIM

V4" ROLLER 'A" roller


8.4 Clearances
(SHOULD NOT (MUST FIT BETWEEN
FIT BETWEEN PANEL SURFACE AND
SURFACE AND STRAIGHTEDGE OVER 8.4.1 General
STRAIGHTEDGE ENTIRE SURFACE)
AT ANY POINT) Clearance is the space between adjacent mem­
bers and provides a buffer area where erection and
production tolerance variations can be absorbed.
To minimize erection problems, the dimensions of The following items should be addressed when de­
the in-place structure should be checked prior to termining the appropriate clearance to provide in the
starting precast erection. After erection, and before design:
other trades interface with the precast concrete mem­ • Product tolerance.
bers, it should be verified that the precast elements • Type of member.
are erected within tolerances [5].
• Size of member.
• Location of member.
8.3.2 Recommended Erection Tolerances • Member movement.
Figures 8.3.1 to 8.3.5 show erection tolerances for: • Function of member.
• Erection tolerance.
• Precast element to precast element. • Fireproofing of steel.
• Thickness of plates, bolt heads, and other
• Precast element to cast-in-place concrete.
projecting elements.
• Precast element to masonry.
• Precast element to structural steel construction. Of these factors, product tolerances and member
movement are the most significant. As shown in the
examples, it may not always be practical to account
for all possible factors in the clearance provided.

8.3.3 Mixed Building Systems


8.4.2 Joint Clearance
Mixed building systems combine precast and pre­
stressed concrete with other materials, usually cast- Joints between architectural panels must accom­
in-place concrete, masonry or steel. Each industry modate variations in the panel dimensions and the
has its own recommended erection tolerances which erection tolerances for the panels. They must also
apply when its products are used exclusively. The provide a good visual line and sufficient width to allow
compatibility of those tolerances with the precast tol­ for a proper sealant joint. Generally, the larger the
erances should be checked and adjusted when nec­ panel, the wider the joints should be. For most situa­
essary. tions, architectural panel joints should be designed to
Example 8.4.2 shows one problem that can occur be not less than % in. wide. Tolerances in overall
when erection tolerances are chosen for each system building width and length are normally accommo­
without considering the project as a whole. dated in panel joints..

8 - 8 PCI Design Handbook/Fifth Edition


Figure-3.3.1 S ection tolerances—beams and spandrels

s = Plan location from building grftfdatum ....................................................................................................... ± 1 in.


at = PtenTocalion -from-centerline of s te e l*...................................................................................................... ± 1 in.

b = Bearing elevation** from nominal elevation at support


Waximum to w .............................................................................................................. . ............................ '/sin.
Maximum high ..................... ..................................................................................................................... V4in.

c = Maximum plumb variation over height-of element


Per 12 in. height.........................., ............................................................................................................. Vfc in.
Maximum.............................................................—.................................................................................... % in.

d = Maximum jog in alignment of matching edges


Architectural exposed e d g e s ................................................................................................................ , . ’Ain.
Visually non-critical e d g e s ........ - .......................................................................................................... 'A in.

e = Joint width
Architectural exposed joints...................................................................................................................... ± 'A in.
Hidden joints.................................................................................................. ............................................ ± % in.
Exposed structural joint not visually critical............................................................................................. ± ’A in.

1 = Bearing length*** (span direction)............................................................................................................... ± % in.

g = Bearing w id th ***............................................................................................................................................ ± 'A in.

* For precast elements erected on a steel frame, this tolerance takes precedence over tolerance dimension “a*.
** Or member top elevation where member is part of a frame without bearings.
*** This is a setting tolerance and should not be confused with structural performance requirements set by the
architect/engineer. The nominal bearing dimensions and the allowable variations in bearing length and width
should be specified by the engineer and shown on the contract drawings.

DESIGN
ELEVATION

PRECAST CONCRETE
BEAM

PRECAST OR
C A S T -IN -P L A C E
COLUMN

COLUMN
GRID LINE

PLAN ELEVATION

PRECAST ELEMENT TO PRECAST CONCRETE, CAST-IN-PLACE CONCRETE, MASONRY, OR STRUCTURAL CONCRETE

PCI Design Handbook/Fifth Edition 8 -9


Figure 8.3.2 Erection tolerances—floorand roof members

a = Plan location fromi>unding grid d a tu m ...................................................................— ............................ ± 1 in.


ai = Plan location from centerline of steel®....................................................................... t
± in.
b = Tsp-eievation-from nominal top elevation atmember ends
Covered Awith topping ..................................................................................................................... - . . . . ± % in.
Untapped flo o r..................................................._ ................................ ............ ........................................ ± % in.
Untapped roof ............................... ........................................................................................................... -±-% in.
c = Maximum jog in alignment of matching edges
(both topped and untopped construction)........ ......................................................................................... 1 in.
d = Joint width
0 to 40 ft member length ................................................................... ± Viin.
41 to 61 ft member length ........................................................................................................................... ± % in.
61 ft p lu s ..............................................................................................................— ................................... ± 1 in.
e = Differential top elevation as erected
Covered with topping ............................... % in.
Untopped flo o r........................................................................................................................................... Vi in.
Untopped roof ........................................................................................................................................... % in.
f = Bearing length® (span direction) .................................................................................................................... ± % in.
g = Bearing width®............. ..................................................................................................................................... ± Vfein.
h = Differential bottom elevation of exposed hollow-core slabs® ................................................................... Vi in.

(1) For precast elements erected on a steel frame, this tolerance takes precedence over tolerance dimension “a".
(2) T h is is a setting tolerance and should not be confused with structural performance requirements set by the
architect/engineer. The nominal bearing dimensions and the allowable variations in bearing length and width
should be specified by the engineer and shown on the contract drawings.
(3) Untopped installation win require a larger tolerance.

<£. OF STEEL STRUCTURE


BLDG. Y GRID
DATUM

------ B a r n
BLDG. X GRID . . ■L!l
DATUM
n
I4— f

i PRECAST CONCRETE
FLOOR OR ROOF MEMBERS

PUN

PRECAST ELEMENT TO PRECASTOR


PRECAST ELEMENT TO STRUCTURAL STEEL
CAST-IN-PUCE CONCRETE OR MASONRY

8 -1 0 PCI Design Handbook/Fifth Edition


Figure 8.3.3 Erection tolerances—columns

a = Plan location from_huildingt grid datum


Structural applications................................................................................................................................ ± 'k in.
Architectural applications ............. ...........................................................— .......................................... ± % in.

.b = Top elevation from nominal top elevation


Maximum lo w ....................................... . ............................................................................ ... ................... Vi in.
Maximum h ig tr............................................................... .— ....................................................... — ......... 'A in.

c = -Bearing haunch elevation from nominal elevation


Maximum lo w ................................... — ............................................................... - ................................ 'h in.
Maximum h ig h ........................................... ................................................................................................ 'A in.

d = Maximum plumb variation over height of element


(element in structure of maximum height of 100 ft) ................................................................................... 1 in.

e = Plumb in any 10 ft of element heigh t........................................................................................................... 'Ain.

f = Maximum jog in alignment of matching edges


Architectural exposed e d g e s ................................................... ................................................................ 'A in.
Visually non-critical edges ..................................................................................................... .................. V4 in.

FOR ANCHOR BOLT SETTING TOLERANCES. ELEVATION

PRECAST ELEMENT TO PRECAST ELEMENT

PCI Design Handbook/Fifth Edition 8 -1 1


Figure ,8.3.4 Erection tolerances—structural watt panels

a- = Plan location from building grid datum!')................................................................. -................................... ± VHn.


a-j = Plan location from centerline of steel®....................................... ............ .................................- ............... ± V4 irr
b- = Top elevation from nominal top elevation
Exposed fodwidual p a n e l................................................................................................ ......................... - ± 'A in.
Nonexposed individual panel.................................................................................. ......... ....................... ± % in .
Exposed relative to adjacentpanel......... ............................................................. .................................. Vi in.
Nonexposed relative to adjacent p a n e t.......................................... ......... .............................................. % in.
c = Bearing elevation from nominal elevation
Maximum lo w ........................................................................................ .................................................... Vfr in.
Maximum high ........................................................................................................................................... Vi in.
d = Maximum plumb variation over height' of structure or100 ft whichever is less*.................................... 1in.
e = Plumb in any MHt of element h eigh t........................................................................................................... Vi in.
f = Maximum jog in alignment of matching edges........-................................................................................. Vi in.
g = Joint width (governs over joint taper).......................................................................................................... ± H in.
h = Joint taper over length of panel ........................................................................................................................ Vein.
hio = Joint taper over to ft length................................................................................................................................ %in.
i = Maximum jog in alignment of matching faces
Exposed ..................................................................................................................................................... % in.
Nonexposed............................................................................................................................................... % in.
j = Differential bowing, as erected, between adjacentmembers of the samedesign <3>...................................... 'Ain.

(1) For precast buildings in excess of 100 ft tall, tolerances ‘ a* and “d" can increase at the rate of 'A in. per story
to a maximum of 2 in.
(2) For precast concrete erected on a steel frame building, this tolerance takes precedence over tolerance on
dimension "a".
(3) Refer to Sect. 8.2.8 for description of bowing tolerance.

- NOMINAL JOINT WIDTH

ELEVATION
PLAN
PRECAST ELEMENT TO PRECAST OR CAST-IN-PUCE CONCRETE OR MASONRY

PUN
PRECAST ELEMENT TO STRUCTURAL STEEL

8 -1 2 PCI Design Handbook/Filth Edition


Figure 8.3.5 Erection tolerances—architectural wall panels

a- = Plan location-from building-grid datumw..................................................................................................._ ± '/• in.


ai = -Plan location from centefline of steed*)......................................................... ............................................... ± !4in.
fcr = Top-slevation-fram nominal top elevation
Exposed individual p a n e l................................................................. ..... ................................................... ± VUn.
Nonexposetf individual panel.................................................................................................................... ± ’A in.
“Exposed relative to adjacent pa n el......................................_............................... . . . . . . ..................... ’A in .
Nonexposed relative to-adjacentpanel ................................................................................................... ’/a in.
c = Support elevation from nominal elevation
Maximum lo w .............................................................................................................................................. 'A in.
Maximum high ........................<.....................................................- ......................................................... % in.
d = Maximum plumb variation over height of structure or 100 ft whichever is less<’>................................... 1 in.
e = Plumb in any 10 ft of element h eigh t............................................................................................................ 'Ain.
f = Maximum jog in alignment of matching edges............................................................................................ ’A in.
g = Joint width (governs over joint taper).........................._ ............................................................................. ± Vi in.
h = Joint taper maximum...................., ................................................................................................................ % in.
hio = Joint taper over to ft len gth................................................................................................................... .. y. in.
i = Maximum jog in alignment of matching faces.............................................................................................. 'A in.
j = Differential bowing or camber as erected between adjacent members of the same
designs................................................................................................................ .......................................... ’Ain.

(1) For precast buildings in excess o f 100 ft tall, tolerances “a ” and “d ” can increase at the rate of K in. per story
to a maximum of 2 in.
(2) For precast concrete erected on a steel frame building, this tolerance takes precedence over tolerance on
dimension “a”.
(3) Refer to Sect. 8.2.8 for description of bowing tolerance.

BLDG. Y GRID DATUM

PRECAST CONCRETE PANEL

ta
■ i
T
BLDG. X GRID DATUM

a1

<t OF STEEL

PLAN ELEVATION

PRECAST ELEMENT TO PRECAST OR CAST-IN-PLACE CONCRETE, MASONRY, OR STRUCTURAL STEEL

PCI Design Handbook/Fifth Edition 8 —13


Figure 8.3.6 bearing Step 7:
length and length over support Check’design to assure adequacy in the event
that minimum member size shoukLoccur. Adjust
PRECAST CONCRETE MEMBER clearance as required for minimum bearing and other
structural consignations.
Step 8:
Select final clearance.
BEARING PAD

8.4.4 Clearance Examples


SET BACK DISTANCE
The following examples are given to show the
thought process, and may not be the only correct
solutions for the situations described.
--------- BEARING LENGTH

■<— LENGTH OVER SUPPORT


Example 8.4.1 Clearance Determination-
Single Story Industrial Build­
ing
SUPPORT
Given:
A double tee roof member 60 ft long, ± 1 in. length
tolerance, bearing on ribbed wall members 25 ft high,
maximum plan variance ±Vz in., variation from
8.4.3 Procedure for Determining Clearance plumb 1/ 4 in. per 10 ft, haunch depth 6 in. beyond face
of panel, long term roof movement - V i in. Refer to
Following is a systematic approach to selecting an
Figure 8.4.1.
appropriate clearance:

Step 1: Problem:
Determine the maximum size of the members in­ Find the minimum acceptable clearance.
volved (basic or nominal dimension plus additive tol­
erances). This should include not only the precast Solution:
and prestressed members, but also other materials.
Step 1\ Determine Maximum Member Sizes
Step 2: (refer to product tolerances)
Add the minimum space required for member
Maximum tee length ................................ + 1 in.
movement.
Wall thickness................................ ........ + V* in.
Step 3: Initial clearance chosen . . . . . . . % in. per end
Check if this clearance allows the member to be
erected within the erection and interfacing toler­ Step 2: Member Movement
ances, such as plumbness, face alignment, etc. Ad­ Long term shrinkage and creep will increase the
just the clearance as required to meet all the needs. clearance so this movement can be neglected in the
initial clearance determination, although it must be
Step 4:
considered structurally.
Check if the member can physically be erected
with this clearance. Consider the size and location of Required clearance adjustment
members in the structure and how connections will as a result of member movement ...............4
be made. Adjust the clearance as required. Clearance ch ose n ........................................% in.
Step 5: Step 3: Other Erection Tolerances
Review the clearance to see whether increasing its If the wall panel is set inward toward the building
dimensions wifi allow easier, more economical erec­ interior V2 in. and erected plumb, the clearance
tion without adversely affecting aesthetics. Adjust should be increased by V2 in. If the panel is erected
the clearance as required. out of plumb outward Vi in., no clearance adjustment
is needed.
Step 6:
Review structural considerations such as types of Clearance adjustment required
connections involved, sizes required, bearing area for erection tolerances................................ 0
requirements, and other structural issues. Clearance chosen .................................... % tn-

8 -1 4 PCI Design Handbook/Fifth Edition


Step 4: Erection Considerations neer might Increase the clearance to 1 in. In this
instance, the likelihood-has-been judged low; there­
If allm em bers are fabricated perfectly, then the
fore, n o adjustment has been made.
joint clearance is W* in. a t either end (11/2 in. total).
This is ample space for erection. # a ll members are a t
maximum size variance,, maximum inward plan vari­ Clearance chosen .................................. . % in.-
ance, and maximum inward variance from plumb;
then the total-clearance is zero. This is undesirable as Sfep 5: Economy
it would require some rework during erection. A In single-story construction, increasing the clear­
judgment should be made as to the likelihood of max­ ance beyond % in. is not likely to speed up erection
imum product tolerances all occurring in one loca­ as long as product tolerances remain within allow­
tion. If the likelihood is low, the % in. clearance needs ables. No adjustment is required for economic con­
no adjustment, but, if the likelihood is high, the engi­ siderations.

PCI Design Handbook/Fifth Edition 8 -1 5


Step 6: Review Structural-Considerations Step 3: Other Erection Tolerances
Allowing a setback from the edge oftheucorbel, as­ Steel variance in plan, maximum ............. . 9 jn
sumed in this instance to have been se t by the engi­
Initial clearance................. .......................... % in
neer a tl-in ., plus the clearance, the bearing is 4 in.
and there should be space to allow-member move­ Clearance chosen .................................. . 2% i n r
ment. The engineer judges this to be acceptable
from astructural and architectural point o f view and Step 4: Erection Considerations
no adjustment is required for structural consider­ No adjustment required for erection consider­
ations. ations.
Step T. Check for Minimum Member Sizes
(refer to product tolerances} Step 5\ Economy

Tee length ................... -1 in. ( V2 in. each end) Clearance chosen ............. ..................... 2% in.
increasing clearance will not increase economy.
Wall thickness............................................. -Vs n.
i
No adjustment for economic considerations.
Bearing haunch .............................. No change
Clearance chosen ...................................... % in. Step 6: Structural Considerations
Minimum bearing-without setback ........... 4%in. Clearance chosen .................................... 2% in.
(OK in this instance.) Expensive connection but possible. No adjust­
Wall plumbness would also be considered in an ment.
actual application.
Step 7: Check Minimum Member Sizes at 36th Story
Step 8: Final Solution (refer to product tolerances)
Minimum clearance used ........... % in. per end Initial clearance.............................................. 2%in.
(Satisfies all conditions considered.) Precast thickness ..................................... -Vs in.
(Note: For simplicity in this example, end rotation, Steel w id th ................................................- 3Ae in.
flange skew, and global skew tolerances have not Steel sw e e p ................................................- 'A in.
been considered. In an actual situation, these issues
Steel variance in plan minimum ........... - 3 in.
should also be considered.)
Clearance calculated............................... 65/ie in.

Step 8: Final Solution


Example 8.4.2 Clearance Determination-
A clearance of over 6 in. would require an extreme­
High Rise Frame Structure
ly expensive connection for the precast panel, and
Given: would produce high torsional stresses in the steel
A 36-story steel frame structure, precast concrete supporting beams. The 6 in. clearance is not practi­
cladding, steel tolerances per AISC, member move­ cal, although the 2 % in. minimum initial clearance is
ment negligible. In this example, precast tolerance still needed. Either the precast panels should be al­
for variation in plan is ±'A in. Refer to Figure 8.4.2. lowed to follow the steel frame or the tolerances for
the exterior columns need to be made more strin­
Problem: gent, such as the AISC requirements for elevator col­
Determine whether or not the panels can be umns. The most economical will likely be for the pan­
erected plumb and determine the minimum accept­ els to follow the steel frame.
able clearance at the 36th story. Minimum clearance u s e d ......................... 2% in.
Allow panels to follow the steel frame.
Solution:
Step 1: Product Tolerances
8.5 Interfacing Tolerances
(refer to product tolerances)
Precast cladding thickness......... +'A in., - % in.
Steel w id th ................................ + V a in., - zA s in.
8.5.1 General

Steel sweep (varies)............... 1A in. assumption In interfacing with other materials, the tolerances
Initial clearance chosen.............................. 3A in.
may be very system-dependent. For example, differ­
ent brands of windows may have different tolerance
requirements. If substitutions are made after the ini­
Step 2: Member Movement
tial design is complete, the interface details must be
For simplification, assume this can be neglected in
reviewed for the new system.
this example.

8 -1 6 PCI Design Handbook/Fifth Edition


Figure 8.4.2 Clearance Example 8^4.2

DETAIL

PCI Design Handbook/Fifth Edition 8-17


Following is a partial checklist for consideration in mum .and maximum dimensions of the inter-facing
determining interfacing requirements: system; If interferences result, alter the nominal di­
mension of the appropriate system, f o r example-, it
• Structural requirements.
is usually moreeconemical to make aJarger opening
• Volume change.
than to-specify-a-non-standard window size.
• Weathering and corrosion protection.
• Waterproofing.
Step 6:
• Drainage.
Establish assembly and installation procedures
• Architectural requirements.
for the interfacing systems to assure compatibility.
• Dimensional considerations.
Show the preferred adjustments to accommodate
• Vibration considerations.
the tolerances of the systems. Specify such things as
• Fire-rating requirements.
minimum bearing areas, minimum and maximum
• Acoustical considerations.
joint gaps, and other dimensions which will vary as a
• Economics.
result of interface tolerances. Consider economic
• Manufacturing/erection considerations.
trade-offs such as in-plant work versus field work,
and minor fit-up rework versus more restrictive toler­
8.5.2 Interface Design Approach ances.

The following approach is one method of organiz­ Step 7:


ing the task of designing the interface between two Check the final project specifications as they re­
systems: late to interfacing. Be aware of subsystem substitu­
Step 1: tions which might be made during the final bidding
Define the interface between the two systems, and procurement.
show shape and location, and determine contractual
responsibilities. For example, the precast panel fur­
nished by the precaster, the window furnished and 8.5.3 Characteristics of the Interface
installed by the window manufacturer, and the seal­
ant between the window and the precast concrete The following list of questions will help to define
the nature of the interface:
furnished and installed by the precast manufacturer.

Step 2: 1. What specifically is to be interfaced?


Define the functional requirements of each inter­ 2. How does the interface function?
facing system. For example, the building drain line
must have a flow line which allows adequate drain­ 3. Is there provision for adjustment upon
age. This will place limits on where the line must installation?
penetrate precast units. Note whether this creates
4. How much adjustment can occur without
problems such as conflict with prestressing strands.
rework?
Step 3:
5. What are the consequences of an interface
List the tolerances of each interfacing system. For
tolerance mismatch?
example, determine from manufacturer’s specifica­
— Rework requirements (labor and material)
tions what are the external tolerances on the door
— Rejection limits
jamb. Determine from the precast concrete product
tolerances what is the tolerance on a large panel door 6 . What are the high material cost elements of
blockout. For the door installation, determine what is the interface?
the floor surface tolerance in the area of the door.
7. What are the high labor cost elements of the
Step 4: interface?
Select the operational clearances required. For
8 . What are the normal tolerances associated
example, determine the magnitude of operational
with the system to interfaced?
clearances which are needed to align the door to
function properly. Then choose dimensions which in­ 9. Are the system interface tolerances simple
clude necessary clearances. planar tolerances or are they more complex
and three dimensional?
Step 5:
Check compatibility of the interface tolerances. 10 . Do alt of the different products of this type
Starting with the least precise system, check the tol­ have the same interface tolerance require­
erance requirements and compare against the mini­ ments?

8-18 PCI Design Handbook/Fifth Edition


6. Structural Steel and Miscellaneous Steel
11. Do you as the designer of the precast system
— Details to prevent rust staining of concrete
have control-over-alt the aspects o f the Inter­
— DeteHs to-minimize potential for corrosion
faces involved? If-n otrw h a t actfons-dc- you
at field connections between steel and
need ta ta k e to accommodate this fact?
precast concrete
Listed below are common characteristics of most — Coordination ofstructural steel expansion/
systems of th e ty p e listed: contraction provisions with those o f the
precast system
1. Windows and Doors
— Special provisions for weld plates o r other
— No gravity load transfer through window
attachment features for steel structures
element
— Compatible with air ancf moisture seatant 7. Masonry
system — Coordination of masonry expansion/con­
— Open/close characteristics (swing or slide) traction provisions with those of the pre­
— Compatibility with door locking mecha­ cast system
nisms — Detailing to ensure desired contact bear­
2. Mechanical Equipment ing between masonry and precast units
— Duct clearances for complex prefabricated — Detailing to ensure desired transfer erf load
ductwork between masonry shear wall and precast
— Large diameter prefabricated pipe clear­ frame
ance requirements
8. Roofing
— Deflections from forces associated with
— Roof camber, both upon erection and long­
large diameter piping and valves
term, as it relates to roof drain placement
— Expansion/contraction allowances for hot/
— Fit-up of prefabricated flashing
cold piping
— Dimensional effects of added material dur­
— Vibration isolation/transfer considerations
ing reroofing
— Acoustical shielding considerations
— Coordination of structural control joint
— Hazardous gas/fluid containment require­
locations with roofing system expansion/
ments
contraction provisions
3. Electrical Equipment — Location of embedded HVAC unit supports
— Multiple mating conduit runs
— Prefabricated cable trays 9. Waterproofing
— Embedded conduits and outlet boxes — Location and dimensions of flashing re-
— Corrosion related to DC power glets
— Special insert placement requirements for — Location and shape of window gasket
isolation grooves
— Location requirements for embedded — Coordination of waterproofing system re­
grounding cables quirements with structural system expan-
— Shielding clearance requirements for sion/provisions
special “clean” electrical lines — Special details around special penetra­
tions
4. Elevators and Escalators
— Elevator guide location requirements 10. Interior Finishes
— Electrical conduit location requirements — Floors, Walls, and Ceilings
— Elevator door mechanism clearances — Joints between precastmembers for direct
— Special insert placement requirements carpet overlay
5. Architectural Cladding — Visual appearance of joints for exposed
— Joint tolerance for sealant system ceilings
— Flashing and reglet fit-up. (Lining up re- — Fit-up details to assure good appearance
glets from panel to panel is very difficult of interior corners
and often costly. Surface-mounted flashing — Appearance of cast-in-place to precast
should be considered.) concrete interfaces
— Expansion and contraction provisions for 11 . Interior Walls and Partitions
dissimilar materials — Clearance for prefabricated cabinetry
— Effects of rotation, deflection, and differen­ — Interfacing of mating embedded conduit
tial thermal gradients runs

PCI Design Handbook/Fifth Edition 8 -1 9


8.6 References 5. “R e c o m m e n d e d Practice for Erection of Pre­
c a s t C on cre te ,” M N L -1 27-85, Precast/Pre­
s t r e s s e d C on cre te Institute, C h ic a go , IL, 1935,
1. PCF Com m itte e on Tolerances, “T ole ran ces
for P re c a st a n d Prestressed- C on crete,” PCI
Journal, V. 30, No. t, J an u ary-F e b ru ary 1985. 6L “P ro p o se d D e sig n Requirem ents for Precast
Concrete,”-PCI Journal, V. 31, No. 6, Novem -
2. “P ro d u c t To le ran ce s for P re c a s t an d Pre­ b e r-D e c e m b e r 1986.
stre sse d C on crete,” PCI Journal, V. 38, No. 1,
J an u ary-F e b ru ary 1993. 7. “C o d e of S ta n d ard Practice for S te e l Buildings
and B rid g e s,” A m erican Institute of Steel
3. “M a n u a l for Quality Control for Plants an d P r o ­ Construction, C h ic a go , IL, Se p te m b e r 1986.
duction o f P r e c a s t and P restressed Concrete
P ro du cts,” Third Edition, M N L -1 16-98, Precast/ 8. “Sta n d a rd Spe cifications for Tole ran ces for
Prestressed C o n cre te Institute, C h ic a g o , IL, C on cre te Construction an d M aterials,” A CI
1998. 117-90, A m erican C on cre te Institute, Farming-
ton Hills, M l, 1990.
4. “M an u a l for Quality Control for Plants an d Pro­
duction of Architectural P re cast C o n c re te P ro d ­ 9. “Specification for M a so n ry Structures,” N C M A -
ucts,” M N L -1 17-96, P re cast/Pre stre sse d C o n ­ T E K 1 -2 A , N ational C on cre te M a s o n r y A sso c ia ­
crete Institute, C h ic a go , IL, 1996. tion, Herndon, VA, 1995.

8 - 2 0 PCI Design Handbook/Fifth Edition


f CHAPTER 9
THERMAL, ACOUSTICAL, FIRE
AND OTHER CONSIDERATIONS
9.1 T h e rm a l Pro pertie s of P re cast C o n c re te .......... - ....................................... 9 -9
9.1.1 N o t a t i o n .......... . ..................................................., - .............. 9 -3
9.4.2 Definitions .................................................................. 9 -3

9 .4.3 G e n e r a l......... ............................................................................... 9 - 4
9.1.4 T h e rm al Properties o f Materials, Su rface s, a n d Air S p a c e s ............ 9 -4
9.1.5 C o m p u ta tio n o f Therm al T ransm ittance V a l u e s ........................... 9 -5
9.1.6 Th erm al S to ra g e E f f e c t s ............................................................ 9 -1 2
9.1.7 C o n d e n sa tio n C o n t r o l............... 9 -1 5
P.1.7.1 Air Barriers ................................................................... 9 - 1 5
9.1.7.2 V a p o r Retarders ........................................................ .. 9 - 1 6
9.1.7.3 Prevention o f-C o n d e n sa tio n on W all S u r f a c e s ............... 9 -1 7
9.1.7.4 C o n d e n sa tio n Prevention Within W all C o n s t r u c t io n ....... 9 -1 8
9.1.8 T h e rm al B r i d g e s ......................... 9 -1 8
9.1.9 R eferen ces ............................................................................... 9 -2 0

9.2 A c o u stic al Properties of P re cast C o n c r e t e ................................................ 9 -2 1


9.2.1 Definitions ................................................................................. 9 -2 1
9.2.2 G e n e r a l...................................................................................... 9 - 2 1
9.2.3 A p p ro a c h in g the D e s ig n P r o c e s s .............................................. 9 -2 1
9.2.4 D e a lin g with S o u n d L e v e ls ......................................................... 9 - 2 1
9.2.5 S o u n d T ran sm issio n L o s s ......................................................... 9 -2 1
9.2.6 Im p a ct N o is e R edu ction ............................................................ 9 -2 2
9.2.7 A co u stical T e st R e s u lt s .............................................................. 9 - 2 2
9.2.8 A b so rp tio n of S o u n d ................................................................. 9 -2 4
9.2.9 A c c e p ta b le N o is e C r it e r ia .......................................................... 9 -2 6
9.2.10 E sta b lish m e n t of N o is e Insulation O b je c tiv e s............................. 9 -2 7
9.2.11 C o m p o site W all C o n sid e ratio n s ................................................. 9 - 2 7
9.2.12 L e ak s an d Flanking ..................................................................... 9 - 2 8
9.2.13 R e fe ren ces ............................................................................... 9 - 2 8

9.3 Fire R e sista n c e ....................................................................................... 9 -2 9


9.3.1 Notation .................................................................................... 9 -2 9
9.3.2 Definitions ................................................................................. 9 - 2 9
9.3.3 In tr o d u c tio n ............................................................................... 9 - 2 9
9.3.4 S ta n d a rd Fire T e s t s ................................................................... 9 - 3 0
9.3.4.1 Fire End uran ce, E n d Point Criteria, a n d Fire R a t i n g ....... 9 -3 1
9.3.5 Fire T e sts of P re stre sse d C on cre te A s s e m b lie s ........ ................. 9 -3 2
9.3.5.1 Fire T e sts of Flexural E le m e n t s ...................................... 9 - 3 2
9.3.5.2 Fire T e sts of W a lls a n d C o lu m n s .................................. 9 -3 2
9.3.6 D e s ig n in g for H eat T ran sm issio n .............................................. 9 -3 2
9.3.6.1 S in g le C o u rse S la b s or W all P a n e l s ............................... 9 - 3 3
9.3.6.2 Floors, R o o fs or W a lls F a c e d with G y p s u m W a llb o a rd .. 9 -3 3
9.3.6.3 R ibb e d P an e ls .............................................................. 9 - 3 3
9.3.6.4 M ulti-C ourse A sse m b lie s .............................................. 9 -3 4
9.3.6.5 S a n d w ic h P a n e l s .......................................................... 9 -3 5
9.3.6.6 Treatm ent of Joints Betw een W a ll P a n e l s ...................... 9 -3 7
9.3.7 D e s ig n in g for Structural In te grity................................................ 9 -3 7
9.3.7.1 S im p ly Su p p o rte d M e m b e rs ......................................... 9 -3 8
9.3.7.2 C o n tin u o u s M e m b e rs ................................................... 9 -4 4
9.3.7.3 M e m b e rs Restrained A g a in st Therm al E x p a n s io n .......... 9 -4 7

PCI Design Handbook/Fifth Edition 9 -1


9 .3 7 .4 S h e a r R e s is t a n c e ......................................................... 9 -4 7
9:3:8 Protection of C o n n e c t i o n s ..................... ..9 -4 7 -
9 .3 .9 P re cast C on cre te C o lu m n G o v e r n ................. ............................. 9 -4 8 ^
9.3.10 C o d e a n d E c o n o m ic C o n sid e ratio n s ................ 9 -4 9
9.3.11 References- ........................ =9^-50

974 S a n d w ic h P a n e l s ............ ............. ............................... .................... ...... 9 -5 1


9.4.1 G e n e r a l..................................................................................... 9 - 5 1
9.4.2 Structural D e s i g n ..................................................................... 9 -5 1
9.4.3 C o n n e c tio n s ............... 9 -5 2
9.4.3.1 Panel C o n n e c t io n s ............................ .......................... 9 -5 2
9.4.3.2 W yth e C o n n e c t o r s ...................... 9 -5 3
9.4.4 In s u la t io n .................................................................................. 9 -5 4
9.4.5 Therm al B o w i n g ........................................................................ 9 - 5 6
9.4.6 Typical D e t a ils ........................................................................... 9 -5 6
9.4.7 References ................................... 9 -5 6

9.5 Quality A ssu ra n c e and C o n t r o l................................ ................................ 9 -5 7


9.5.1 In tro d u c tio n ................................................... 9 -5 7
9.5.2 Plant C e rtific a tio n ......................... 9 -5 7
9.5.3 P C I Quality Control M a n u a ls ..................................................... 9 -5 8
9.5.4 References ..................................................................... 9 -5 8

9.6 C on crete C o a tin g s an d Joint S e a la n ts ..................................................... 9 -5 9


9.6.1 C o a tin g s for Horizontal D e c k S u rfa c e s ...................................... 9 - 5 9
9.6.2 C le ar S u rface S e a le rs for Architectural P re ca st P a n e l s .............. 9 -5 9
9.6.3 Joint S e a l a n t s ........................................................................... 9 -5 9
9.6.4 R eferences ............................................................................... 9 - 6 0

9.7 Vibration in C on crete Structures .............................................................. 9 - 6 1


9.7.1 H u m an R e s p o n s e to Building V ib r a t io n s ...................................... 9 -6 1
9.7.1.1 M in im um Natural F r e q u e n c y ......................................... 9 -6 1
9.7.1.2 Natural F r e q u e n c y ......................................................... 9 - 6 1
9.7.2 Vibration Isolation for M e ch an ical E qu ip m e n t ........................... 9 -6 2
9.7.3 R eferences ............................................................................... 9 - 6 3

9.8 Cracking, Repair and M a in t e n a n c e .......................................................... 9 -6 4


9.8.1 C r a c k in g .................................................................................... 9 - 6 4
9.8.2 Repair and M a in t e n a n c e ....................................... 9 -6 4
9.8.3 R eferences ........................................ 9 -6 4

9.9 P re cast S e gm e n ta l Construction .............................................................. 9 - 6 5


9.9.1 G e n e r a l..................................................................................... 9 -6 5
9.9.2 Joints ....................................................................................... 9 - 6 5
9.9.2.1 O p e n J o in t s ................................................................... 9 - 6 5
9.9.2.2 C lo s e d Joints ............................................................... 9 -6 5
9.9.3 D e sig n ..................................................................................... 9 -6 6
9.9.4 P o st-T e nsion in g ................................... 9 -6 6
9.9.4.1 T e n d o n and D u ct P la c e m e n t ......................................... 9 -6 6
9.9.4.2 C o u p le rs ........................................................................ 9 - 6 6
9.9.4.3 Be arin g A r e a s ............................................................... 9 -6 6
9.9.5 R eferences ............................................................................... 9 - 6 7

9.10 Coordination with M echanical, Electrical an d Other S u b - S y s t e m s ............ 9 -6 8


9.10.1 In tr o d u c tio n ............................................................................... 9 - 6 8
9.10.2 Lighting an d Pow er Distribution ................................................ 9 -6 8
9.10.3 Electrified F lo o r s ............................................................. 9 -6 8
9.10.4 Ductw ork .................................................................................. 9 - 6 8
9.10.5 Other S u b -S y s t e m s ................................................................... 9 - 7 0
9.10.6 S y s te m s Bu ild ing ........................ 9 -7 0
9.10.7 Prison Cell B o x M o d u le .............................................................. 9 - 7 3

9 -2 PCI Design Handbook/Fifth Edition


9.1 THERMAL PROPERTIES OF PRECAST CONCRETE

9 J .f Notation 9.1.2 Ttefimtions


= th e rm al-con d u ctan ce of a n a ir s p a c e
a
British thermalunit (Btu}—Approxim ately fee
Btu = "British therm al unit a m o u n t o f heat to raise o n e p o u n c L o f water from 59°F
to 60° F.
C = Therm al c o n d u c ta n c e fo r the sp e c i­
fied th ickne ss, Btu/(hr)(ft2)(°F)
Degree day (D)— A unit, b a s e d on temperature
difference a n d time, u se d in estim ating fuel c o n ­
d clear co ve r to e n d s of metal ties in su m p tion a n d spe cifying nom inal heating load of a
sa n d w ic h p a n e ls build ing in winter. For a n y on e day, w hen the m ean

= tem perature is le ss th a n 65°F, there are a s m an y d e ­


D heating d e g re e d a y (65° F b a se )
gre e d a y s a s there are d e g re e s F difference in tem ­
f = film or su rfa c e c o n d u c ta n c e perature between the m e an tem perature for the d ay
an d 65°F.
He = h eat c ap acity
Dew-point temperature ( y —The tem perature at
k therm al conductivity, (Btu-in.)/(hr) w hich co n d e n satio n of water v ap o r b e g in s for a given
(ft2)(DF) hum idity a n d pressure a s the v ap o r tem perature is re­

= d uce d . T he tem perature c o rre sp o n d in g to saturation


i th ic k n e ss of a material, in.
(1 0 0 % R.H.) for a given absolute humidity at con stant
m = width or diam eter o f m etal ties in pressure.
sa n d w ic h p an e ls Film or surface conductance (f)—T h e time rate
of heat e x c h a n g e by radiation, conduction, an d c o n ­
M = perm eance, p e rm s
vection of a unit area of a surface with its su rro u n d ­
R = therm al resistance, (hr)(ft2) (° F )/B tu ings. Its valu e is usually e x p re sse d in Btu per (hr)(sq ft

=
of su rfa ce area)(°F tem perature difference). S u b ­
Ra therm al resistan ce of air s p a c e
scrip ts “i” a n d “o ” are usually u se d to denote inside
Rfi.Rfo r= therm al re sistan ce s of inside a n d a n d outside surface co n d u cta n ce s, respectively.
o u tsid e su rfa c e s Heat capacity (Hc)—The a m o u n t of heat n e c e s­
sa ry to raise the tem perature of a give n m a s s on e d e ­
Rt = total therm al resistan ce
gree. Num erically, the m a s s multiplied by the specific
= therm al resistan ce o f material layers heat.
R 1,2...n
1, 2 ....n Heat transmittance (U)—Overall coefficient of
heat tra n sm issio n or thermal transm ittance (air-to-
Rmaterials = su m m atio n of therm al resistan ce of
air); the time rate of heat flow usually e x p re sse d in Btu
o p a q u e material layers
pe r (hr) (sq ft of su rface area)(°F tem perature differ­
R.H. = relative humidity, % e n ce between air on the inside an d air o n the outside
of a wall, floor, roof, or ceiling). T he term is applied to
ti = ind oor tem perature, °F
the usual co m b in atio n s of materials an d a lso sin gle
to = o u td oor temperature, °F m aterials su c h a s w ind ow g la s s , an d includes the
su rface c o n d u c ta n c e o n both sides. T h is term is fre­
ts dew -point temperature, ro o m air, at
quently called the U-value.
d e s ig n m axim u m relative humidity,
Perm—A unit of perm eance. A perm is 1 grain per
°F
(sq ft of area)(hr)(in. of m ercury v ap o r p re ssu re differ­
U heat transm ittance value [all heat ence).
an d a v e ra ge transm ittance valu e s Permeability, water vapor (p)— T he property of a
are Btu/(hr)(ft2)(°F)] su b sta n c e w hich perm its the p a s s a g e of water vapor.
It is equal to the pe rm e ance of 1 in. of a su bstance.
Wa,b,...,n heat transm ittance valu e s o f parallel
Perm eability is m e asu re d in perm -inches. The
c o n d u c ta n c e p ath s in san d w ich
perm eability of a material varies with barom etric p res­
p an e ls
sure, tem perature a n d relative humidity conditions.
U0 = a v e ra ge heat transm ittance value Permeance (M)—T h e w ater v ap o r p e rm ean ce of
a n y sh e e t or a ss e m b ly is the ratio of the water v ap o r
w = width of Z o n e A in sa n d w ic h panels,
flow per unit area per hour to the v ap o r pressure dif­
Se ct. 9.1.8
ference between the two surfaces. Permeance is
= permeability, p e rm e an ce of a unit m e asu re d in perm s. T w o c o m m o n ly u se d test meth­
thjekness, give n material, perm-in. o d s are the W et C u p a n d D ry C u p Tests. S p e c im e n s

PCI Design Handbook/Fifth Edition 9 -3


are sealed-o verth e tops-of cups-eontaining either w a ­ 2.__S y s te m Perform ance. Criteria (S e c t 8.6)—
ter or desiccant, -placed im a controlled atm osphere, m athem atical m o d e ls a n d com pu ter program s
usually at 5 0 % R.H., a n d w eight c h a n g e s m easured. -b a s e d orr these m o d e ls provide a_svstem ap­
Relative humidity (R.H.)—The ratio o f w ater v a ­ p ro ach (criteria an d co m p lian ce values), to
por present in air to the water v ap o r preserrH n satu ­ corrrply with the e nvelope requirem ents of the
rated a ir a t the s a m e temperature a n d pressure. Standard. It provides m ore flexibility than the
Thermal conductance (C)—T he time rate of heat prescriptive approach , but it requires more
flow expressed in Btu per (hr) (sq ft oiarea) (°F aver­ analysis.
a g e temperature difference between tw o surfaces).
Th e term is applied to sp e c ific m aterials a s used, ei­
ther h o m o g e n e o u s or h eterogen eous for the thick­
P re cast an d prestressed concrete construction,
n e ss of construction stated, not per in. o f thickness.
with its h igh thermal inertia an d therm al sto ra ge prop­
Thermal conductance of an air space (a)—The
erties, h a s a n a d v a n ta g e over lightw eight materials.
time rate of heat flow through a unit are a of an air
P ro ce d u re s to ac c o u n t for the benefits o f heavier m a­
sp a c e per unit temperature difference between the
terials are presented in A S H R A E Sta n d a rd 90.1-1989.
bou n d ary surfaces. Its value is usually e x p re sse d in
The trend is toward more insulation with little re­
Btu per (hr)(sq ft of area)(°F).
gard given to its total impact or energy used. Mass
Thermal conductivity (k)—The time rate of heat
effects, glass area, air infiltration, ventilation, building
flow by con du ction only th rough a unit th ickne ss o f a
orientation, exterior color, shading or reflections from
h o m o g e n e o u s material under steady-state co n d i­
adjacent structures, surrounding surfaces or vegeta­
tions per unit a re a per unit temperature gradient in
tion, building aspect ratio, number of stories, wind di­
the direction perpendicular to the isotherm al surface.
rection and speed, all have an effect on insulation re­
Its unit is (Btu-in.) per (hr)(sq ft of area) (°F).
quirements.
Thermal mass—Characteristic of m aterials with
T h is section is c o n d e n se d fro m a m ore complete
m a s s heat c ap acity an d surface area ca p ab le of af­
treatment given in Ref. 4. E x c e p t where noted, the in­
fecting building heating a n d c o o lin g lo a d s b y storing
form ation a n d d e sig n criteria are taken or derived
an d releasing heat a s the interior and/or exterior tem ­
from the A S H R A E H a n d b o o k [1], and from the A S H ­
perature and radiant conditions fluctuate.
R A E Sta n d ard 90.1-1989 [2]. AH d e sig n criteria are
Thermal resistance (R)—T h e reciprocal of a heat
not given in this section, a n d the criteria m a y change
tran sm issio n coefficient, a s e xpre sse d by U, C, f, or a.
a s the A S H R A E S ta n d ard an d H a n d b o o k are revised.
Its unit is (° F) (hr) (sq ft of area) per Btu. For exam ple, a
Local c o d e s an d latest references m u st be used for
wall with a U-value of 0.25 w ould have a resistance
specified valu e s an d procedures.
value of R = 1/U = 1/0.25 = 4.0.

9.1.3 General
Therm al c o d e s an d stan d a rd s specify the heat
tran sm issio n requirem ents for build ings in m any dif­
9.1.4 Thermal Properties of Materials,
ferent w ays. Prescriptive stan d a rd s specify U or R v a l­
Surfaces, and Air Spaces
u e s for e ach building com ponent, w h ereas with per­
form an ce stan dards, two build ings are equivalent if The thermal properties o f materials an d air sp a c e s
they u se the s a m e am oun t of energy, regard le ss of are b a se d on ste ad y state tests, which m easure the
the U or R v a lu e s of the com po ne nts. T h is allow s the heat that p a s s e s from the w arm sid e to the cool side
d e sig n e r to c h o o se conservation strategies that pro­ of the test specim en. The tests determine the con­
vide the required perform ance at the least cost. ductivity, k, or, for n o n -h o m o g e n e o u s sections, com ­
In A S H R A E S ta n d ard 90.1-1989 [2], th e se two a p ­ p o u n d se ction s a n d air sp a c e s , the conductance, C,
p ro a c h e s are u sed to determ ine the m axim um allow ­ for the total thickness. The valu e s of k a n d C d o not
able U ow or U or for a wall or roof asse m b ly: include surface co n d u ctan ce s, f and f0.
T he overall thermal resistance of wall, floor, and
1. Prescriptive Criteria (Sect. 8.5)— T able of Alter­ roof se ctio n s is the su m of the resistances, R (recipro­
nate C o m p o n e n t P a c k a g e s provid e s a limited cal of k, C, fh an d f0). The R -value s of construction ma­
num ber of co m p ly in g co m binations of building terials a re not influenced by the direction of heat flow,
variables for a set of climate variable ran ge s. but the R -value s of su rfa ce s and air s p a c e s differ de­
For m o st clim ate locations an d building a s s e m ­ p e n d in g o n whether they are vertical, slo pin g, or hori­
blies, the Prescriptive Criteria m ay be slightly zontal. A lso, the R -value s of su rface s are affected by
m ore stringent than the S y ste m Perform ance the velocity of air at the su rface s a n d by their reflective
Criteria. properties.

9 -4 PCI Design Handbook/Fifth Edition


T a b le s 9.1.1 a n d 9.1.2 g iv e the therm al re sista n c ­ 9.1.5 -Compul
e s ^ su rfa c e s ancL3 ^ irr. a ir s p a c e . T a b le 9.1.3 g iv e s Values
thetherm al p ro p e rtie so f m o st c o m m o n ly u se d build­
ing m aterials. O n ly U -v a lu e s are :give n for g i a s s be-
ca u se the su rfa c e re sista n c e s a n d a ir s p a c e betw een The heat transmittance (U-values^. of a building wall,
p a n e s a c c o u n t for n e a rly all of the U-value. T a b le floor or roof is computecbby adding together the R-
9 ;1.4 g iv e s th e th e rm a l properties of v ario u s w eight values ofthematerials in thesecfion, thesurfaces (Rfi
con cre te s a n d s o m e sta n d a rd precast, p re stre sse d and Rf0) and air spaces (Ra) withirHhe section. The
con crete p ro d u c ts in the “norm ally d ry ” condition. reciprocal of the R’s is the U-value:
Norm ally dry is the condition of concrete co n tain in g
a n equilibrium a m o u n t o f free w ater after extended
exposure to w a rm air at 35 to 5 0 % R.H.
T herm al c o n d u c ta n c e s a n d re sistan c e s of other '■' R+D _l R _ l R v- h-
building m aterials are u su ally reported for oven dry
conditions. N o rm ally dry con cre te in c o m b in a tio n
with insulation ge n e rally p rovid e s abo u t the s a m e R - w here R materiais is the s u m of all o p a q u e m aterials in
value a s e q ually insulated ove n dry concrete, but b e ­ the wall. A n u m b e r of typical wall a n d roof U -va lu e s
c a u s e o f the m o istu re content, h a s the ability to store are g iv e n in T a b le s 9.1.5, 9.1.6, a n d 9.1.7.
a greater a m o u n t of h eat th an ove n d ry concrete. Figure 9.1.1 s h o w s the u se o f T a b le s 9.1.1
However, h ig h e r m oisture content in con crete c a u s e s th ro u gh 9.1.4 in c a lc u la tin g R - a n d U -valu e s for wall
higher therm al co n d u c ta n c e . a n d roof a sse m b lie s.

Figure 9.1.1 Calculation of R- and U-values

EXAMPLE 9.1.1 -WALL THERMAL RESISTANCE CALCULATION

R R
WINTER SUMMER TABLE
A. SURFACE, OUTSIDE 0.17 0.25 9.1.1

2'AVA
B. CONCRETE, 2 in. (110 pcf) 0.38 0.38 9.1.4
C. POLYSTYRENE, in. 6.00 6.00 9.1.3
D. CONCRETE, in. (110 pci) 0.48 0.48 9.1.4
E. SURFACE, INSIDE 0.68 0.68 9.1.1
TOTAL R = 7.71 7.79
U = 1/R = 0.13 0.13

EXAMPLE 9.1.2-ROOF THERMAL RESISTANCE CALCULATION

R R
WINTER SUMMER TABLE
A. SURFACE, OUTSIDE 0.17 0.25 9.1.1
B. ROOFING, BUILT-UP
C. POLYSTYRENE, in. 2
D. CONCRETE, 2 in. (145 pcf)
0.33
8.00
0.15
0.33
8,00
0.15
9.1.3
9.1.3
9.1.4
E. SURFACE, INSIDE 0.61 0.92 9.1.1
TOTAL R = 9.26 9.65
U = 1/R = 0.11 0.10

PCI Design Handbook/Fifth Edition 9 -5


Table 9.1.1 Thermal resistances, Rf, of surfaces
-
Still air, Moving air, R,0

Position Direction
- Reflective
surface
Non reflective
surface
of of
surface heat flow
Non Aluminum Bright 15 mph 71£ mph
reflective painted aluminum winter summer
surface paper foii design design

Vertical Horizontal 0.68 1.35 1.70 0.17 0.25

Up 0.61 1.1G 1.32 0.17 0.25


Horizontal
Down 0.92 2.70 4.55 0.17 0.25

Table 9.1.2 Thermal resistances, R,, of air spaces*

Air space Reflective surfaces


Position Direction
Non
of of
reflective
air heat Mean Temp, One One Both
flow surfaces
space temp. °F diff. °F side>> side* sides*

Winter
Horizontal
(walls) 50 10 1.01 2.32 3.40 3.69
50 30 0.91 1.89 2.55 2.67
Vertical
Summer
Horizontal
(walls)
90 10 0.85 2.15 3.40 3.69

Winter
Up
(roofs) 50 10 0.93 1.95 2.66 2.80
50 30 0.84 1.58 2.01 2.09

Horizontal Down
(floors) 50 30 1.22 3.86 8.17 9.60

Summer
Down
(roofs) 10.07
90 10 1.00 3.41 8.19

a. For 3'/2in. air space thickness. The values with the exception of those for reflective surfaces, heat flow down, will differ about 10% for
air space thickness of % in. to 16 in. Refer to the ASHRAE Handbook1for values of other thicknesses, reflective surfaces, heat flow
down.
b. Aluminum painted paper
c. Bright aluminum foil

9 -6 PCI Design Handbook/Fifth Edition


Table 9.1.3 Thermal properties of various^jiillding materials3f
_
Unit Resistance, R TFans- Specific
Material weight, miaanee, heat,
pcf U Btu/(lb)(°F)
Per inch-of_ For thickness
thicknessr1/k shown, 1/C -

Insulation, rigid
Ceilular grass 8.5 2.86 0.18
Glass fiber, organic 4-9 4.00 0.23
bonded -

Mineral fiber, resin binder 15 3.45 0.17


Mineral fiberboard, wet 16-17 2.94 —

felted, roof insulation


Cement fiber slabs 22 1.75 0.31
(shredded wood with
magnesia oxysulfide
binder)
Expanded polystyrene 1.8-3.5 5.00 0.29
extruded smooth skin
surface
Expanded polystyrene 1.0 3.85-4.17 —

molded bead
Cellular polyurethane 1.5 6.25-5.56 0.38
Miscellaneous
Acoustical tile (mineral 18 2.86 0.19
fiberboard, wet felted)
Carpet, fibrous pad 2.08 0.34
Carpet, rubber pad 1.23 0.33
Floor tile, asphalt, 0.05 0.30
rubber, vinyl
Gypsum board 50 0.88b 0.26
Particle board 50 1.06 0.31
Plaster
cement, sand agg. 116 0.20 0.20
gypsum, L.W. agg. 45 0.63b -
gypsum, sand agg. 105 0.18 0.20
Roofing, 3/s in. built-up 70 0.33 0.35
Wood, hard 38-47 0.94-0.80 0.39
Wood, soft 24-41 1.00-0.89 0.33
Plywood 34 1.25 0.29

Glass doors and windows0


Single, winter 1.11
Single, summer 1.04
Double, winterd 0.50
Double, summerd 0.61
Doors, metale
Insulated 0.40
a. See Table 9.1.4 for all concretes, including insulating concrete for roof fill.
b. Average value.
c. Does not include correction for sash resistance. Refer to the ASHRAE Handbook for sash correction.
d. Vi in. air space; coating on either glass surface facing air space.
e. Urethane foam core without thermal break.
f. See manufacturers’ data for specific values.

PCI Design Handbook/Rfth Edition 9 -7


Table 9.T.4 Thermal properties of concrete3

Resistance, R
Concrete: Thickness, Specific
Description weight, -irfc heat,0
pcf -Per inch ot For thickness Btu/(lb)(°F)
Thickness, 1/k shown, 1/C
Concretes 1 40 - a 1 0 -0 .0 5 - 0,19
including normal 120 0 .1 8 -0 .0 9

weight, lightweight 100 0 .2 7 -0 .1 7

and lightweight 80 0 .4 0 -0 .2 9

insulation concretes 60 0 .6 3 -0 .5 6

40 1 .0 8 -0 .9 0

30 1 .3 3 -1 .1 0

20 1 .5 9 -1 .2 0

Normal weight teesb 1 45 2 0 .1 5 0 .1 9

and solid slabs 3 0 .2 3

4 0 .3 0

5 0 .3 8

6 0 .4 5

8 0 .6 0

Normal weight 145 6 1 .0 7 0 .1 9

hollow-core slabs 8 1 .3 4

10 1 .7 3

12 1.91

Structural lightweight teesb 110 2 0 .3 8 0 .1 9

and solid slabs 3 0 .5 7

4 0 .7 6

5 0 .9 5

6 1 .1 4

8 T.52

Structural lightweight 1 10 8 2 .0 0 0 .1 9

hollow-core slabs 12 2 .5 9

a. Based on normally dry concrete (see Chapter 4 of Ref. 3).


b. Thickness for tees is thickness of slab portion including topping, if used. The effect of the stems generally is not significant, therefore,
their thickness and surface area may be disregarded.
c. The specific heat shown is the mean value from test data compiled in Ref. 4.

9 -8 PCI Design Handbook/Fifth Edition


Table 9.1.5 Wall U-values: prestressecHees, hollow-core slabs, solid and sandwich panels; winter
and summer conditions3

: Thickness,
t,and resistance, Winter Summer
R, of concrete R o_= 0.17, Rfl= 0.68 Rfe = 0.25, Rfl= 0.68

Concrete Type of Insulation resistance, R


weight, pcf wall panel
t R None 4 6 8 10 None 4 6 8 10

145 Solid waJis, 2 0.15 1.00 .20 .14 .11 .09 .93 .20 .14 .11 .09
tees,b and 3 0.23 .93 .20 .14 .11 .09 < .86 .19 .14 .11 .09
sandwich
4 0.30 .87 .19 .14 .11 .09 .81 .19 .14 .11 .09
panels
5 0.38 .81 .19 .14 .11 .09 .76 .19 .14 .11 .09
6 0.45 .77 .19 .14 .11 .09 .72 .19 .14 .11 .09
8 0.60 ; .69 .18 .13 .11 .09 .65 .18 .13 .10 .09

145 Hollow 6(o) 1.07 .52 .17 .13 .10 .08 .50 .17 .13 .10 .08
core (0 1.86 .37 .15 .11 .09 .08 .36 .15 .11 .09 .08
slabs0 8(0) 1.34 .46 .16 .12 .10 .08 .44 .16 .12 .10 .08

(0 3.14 .25 .13 .10 .08 .07 .25 .12 .10 .08 .07
10(o) 1.73 .39 .15 .12 .09 .08 .38 .15 .12 .09 .08

(l) 4.05 .20 .11 .09 .08 .07 .20 .11 .09 .08 .07
12(o) 1.91 .36 .15 .11 .09 .08 .35 .15 .11 .09 .08

(f) 5.01 .17 .10 .08 .07 .06 .17 .10 .08 .07 .06

110 Solid walls, 2 0.38 .81 .19 .14 .11 .09 .76 .19 .14 .11 .09
tees,b and 3 0.57 .70 .18 .13 .11 .09 .67 .18 .13 .11 .09
sandwich 4 0.76 .62 .18 .13 .10 .09 .59 .18 .13 .10 .09
panels
5 0.95 .56 .17 .13 .10 .09 .53 .17 .13 .10 08
6 1.14 .50 .17 .13 .10 .08 .48 .16 .12 .10 .08
8 1.52 .42 .16 .12 .10 .08 .41 .16 .12 .10 .08

110 Hollow 8(o) 2.00 .35 .15 .11 .09 .08 .34 .14 .11 .09 .08
core 4.41 .19 .11 .09 .08 .07 .19 .11 .09 .07 .07
(0
slabs0
12(0) 2.59 .29 .13 .11 .09 .07 .28 .13 .11 .09 .07

(0 6.85 .13 .09 .07 .06 .06 .13 .08 .07 .06 .06

a. When insulations having other R-vaiues are used, U-values can be interpolated with adequate accuracy, or U can be calculated as
shown in Sect. 9.1.5. When a finish, air space or any other material layer is added, the new U-value is:
________________ 1__________________
U~ from table + ^ of added finish, air space or material

b- Thickness for tees is thickness of slab portion. For sandwich panels, t is the sum of the thicknesses of the wythes.
c. For hollow panels (o) and (f) after thickness designates cores open or cores filled with insulation.

PCI Design Handbook/Fifth Edition 9 -9


Table 9.1.6 Roof U-values: concrete units with built-up roofing, winter conditions, heat flow upward*

OUTSIDE SURFACE Rfo = 0.17-


BUILT-UP-ROOFJNG
Rbr = 0.33-
(<(((((( ■iiiiijiinj nujLin (fm <
R-OF INSULATION , VARIES, SEE TABLE'
^ <■
<

R OF CONCRETE, VARIES, SEE T A B L E -

“V----------- r/'T; yy/?yyy.


7 AIR SPACE
ACOUSTICAL CEILING, % in.
Ra = 0 .8 4 -
Rc = 1.88- ± 7 / 7 / y
A

7 ~ s '? ~ y / y / - —

INSIDE SURFACE Rfi = 0.61 -

W ITH OR W ITHO UT ACOUSTICAL CEILING SUSPENDED CEILING

Thickness, t With ceiling


Without ceiling
Concrete Prestressed and Applied direct Suspended
weight, concrete resistance, R
pcf member of concrete Top insulation resistance, R

t R None 4 10 16 None 4 10 16 None 4 10 16

145 Solid slabs 2 0.15 .79 .19 .09 .06 .29 .13 .07 .05 .24 .12 .07 .05
and teesb 3 0.23 .75 .19 .09 .06 .29 .13 .07 .05 .23 .12 .07 .05
4 0.30 .71 .18 .09 .06 .28 .13 .07 .05 .23 .12 .07 .05
5 0.38 .67 .18 .09 .06 .27 .13 .07 .05 .22 .12 .07 .05
6 0.45 .64 .18 .09 .06 .27 .13 .07 .05 .22 .12 .07 .05
8 0.60 .58 .18 .09 .06 .26 .13 .07 .05 .21 .11 .07 .05

145 Hollow 6 (0 ) 1.07 .46 .16 .08 .06 .23 .12 .07 .05 .19 .11 .07 .05
core (f) 1.86 .34 .14 .08 .05 .20 .11 .07 .05 .17 .10 .06 .05
slabs0 8 (0 ) 1.34 .41 .16 .08 .05 .22 .12 .07 .05 .18 .11 .06 .05
(f) 3.14 .24 .12 .07 .05 .16 .10 .06 .04 .14 .09 .06 .04
10 (o) 1.73 .35 .15 .08 .05 .20 .11 .07 .05 .17 .10 .06 .05
(f) 4.05 .19 .11 .07 .05 .14 .09 .06 .04 .12 .08 .06 .04
12 (o) 1.91 .33 .14 .08 .05 .19 .11 .07 .05 .17 .10 .06 .05
(f) 5.01 .16 .10 .06 .05 .12 .08 .05 .04 .11 .08 .05 .04

110 Solid slabs 2 0.38 .67 .18 .09 .06 .27 .13 .07 .05 .22 .12 .07 .05
and teesb 3 0.57 .60 .18 .09 .06 .26 .13 .07 .05 .21 .12 .07 .05
4 0.76 .53 .17 .08 .06 .25 .12 .07 .05 .21 .11 .07 .05
5 0.95 .49 .17 .08 .06 .24 .12 .07 .05 .20 .11 .07 .05
6 1.14 .44 .16 .08 .05 .23 .12 .07 .05 .19 .11 .07 .05
8 1.52 .38 .15 .08 .05 .21 .11 .07 .05 .18 .10 .06 .05

110 Hollow 8 (0 ) 2.00 .32 .14 .08 .05 .19 .11 .07 .05 .16 .10 .06 .05
core (f) 4.41 .18 .11 .06 .05 .13 .09 .06 .04 .12 .08 .05 .04
slabs0 12 (0 ) 2.59 .27 .13 .07 .05 .17 .10 .06 .05 .15 .09 .06 .04
(f) 6.85 .13 .08 .06 .04 .10 .07 .05 .04 .09 .07 .05 .04

a. When insulations having other R-values are used, U-values can be interpolated with adequate accuracy, or U can be calculated as
shown in Sect. 9.1.5. When a finish, air space or any other material layer is added, the new U-value is:
1
0 from table + ^ of added finish, air space or material

b. Thickness for tees is thickness of slab portion.


c. For hollow panels (o) and (f) after thickness designates cores open or cores filled with insulation.

9 -1 0 PCI Design Handbook/Fifth Edition


Tabte-SM .7 Ftoofu-vaiues:concrete units with built-up rooting, summer conditions, heat flowdownward3
OUTSIDE SURFACE Rj0 = 0.2 5-
Z BUILT-UP X
(T fT lm T U f T T t r f z n r r m l
ROOFING Rbr = 0.33-
Tmmi 11(i 1(11m11 nhi
4 I
R OF INSULATION, VARIES, SEE TABLE"
r * R OF CONCRETE, VARIES, SEE TABLE -
< 4 *
<
a „

-------- C----- TT 7 AIRSPACE Ra = 1.00-


- ACOUSTICAL CEILING, % in. Rc = 1.88- E7V / ? / / / / / / / V / / } ' / / / / .

- IN S ID E SURFACE Rfi = 0.92 - /


WITH OR WITHOUT ACOUSTICAL CEILING SUSPENDED CEILING

Thickness, t With ceiling


Without ceiling
Concrete Prestressed and Applied direct Suspended
weight, concrete resistance, R

pcf m ember of concrete Top insulation resistance, R

t R None 4 10 16 None 4 10 16 None 4 10 16

145 Solid slabs 2 0.15 .61 .18 .09 .06 .26 .13 ,07 .05 .21 .41 .07 .05
and teesb 3 0.23 .58 .17 .09 .06 .26 .13 .07 .05 .20 .11 .07 .05
4 0.30 .56 .17 .08 .06 .25 .13 .07 ,05 .20 .11 .07 .05
5 0.38 .53 .17 .08 .06 .25 .12 .07 .05 .20 .11 .07 .05
6 0.45 .51 .17 .08 .06 .24 .12 .07 .05 .20 .11 .07 .05
8 0.60 .48 .16 .08 .06 .24 .12 .07 .05 .19 .11 .07 .05

145 Hollow 6(o) 1.07 .39 .15 .08 .05 .21 .11 .07 .05 .17 .10 .06 .05
core (f) 1.86 .30 .14 .07 .05 .18 .11 .06 .05 .15 .10 .06 .04
slabs0 8(o) 1.34 .35 .15 .08 .05 .20 .11 .07 .05 .17 .10 .06 .05
(f) 3.14 .22 .12 .07 .05 .15 .09 .06 .04 .13 .08 .06 .04
10(o) 1.73 .31 .14 .08 .05 .19 .11 .07 .05 .16 .10 .06 .04
(f) 4.05 .18 .10 .06 .05 .13 .09 .06 .04 .14 .08 .06 .04
12(o) 1.91 .29 .13 .07 .05 .18 .10 .06 .05 .15 .09 .06 .04
<0 5.01 .15 .10 .06 .04 .12 .08 .05 .04 .10 .07 .05 .04

110 Solid slabs 2 0.38 .53 .17 .08 .06 .25 .12 .07 .05 .20 .11 .07 .05
and teesb 3 0.57 .48 .16 .08 .06 .24 .12 .07 .05 .19 .11 .07 .05
4 0.76 .44 .16 .08 .05 .23 .12 .07 .05 .18 .11 .06 .05
5 0.95 .44 .46 .08 .05 .22 .12 .07 .05 .18 .10 .06 .05
6 1.14 .38 .15 .08 .05 .21 .11 .07 .05 .17 .10 .06 .05
8 1.52 .33 .14 .08 .05 .19 .11 .07 .05 .16 .10 .06 .05

110 Hollow 8(o) 2.00 .29 .13 .07 .05 .18 .10 .06 .05 .15 .09 .06 .04
core (f) 4.41 .17 .10 .06 .05 .12 .08 .06 .04 .11 .08 .05 .04
slabs0 12(0) 2.59 .24 .12 .07 .05 .16 .10 .06 .04 .14 .09 .06 .04
a. When insulations having other R-values are used, U-values can be interpolated with adequate accuracy, or U can be calculated as
shown In Sect. 9.1.5. When a finish, air space or any other material layer is added, the new U-value Is:
_____________ 1
U frorn table + ^ addecl finish, air space or material

b. Thickness for tees is thickness of slab portion.


c. For hollow panels (o) and (f) after thickness designates cores open or cores filled with Insulation.

PCI Design Handbook/Fifth Edition 9-11


Table 9.1.8 Design considerations for building with high available free heat6
Relative Importance o f D e s ig n Considerations6

Climate Classification Surface-Color


Therm al Increase -External Reduce
Daylighting
Mass Insulation Fmsc Light D ark Infiltration
Winter
Long H eatin g S e a s o n With sund and winde 1 2 2 : 2 1 3
(6000 degree days or mote) With sun without wind 1 2 2 1 3 "
Without surr and wind - 2 1 3 ^
Without sun with wind 1 2 2 1 3
Moderate Heeding Season With sun and wind 2 2 1 1 2 2 ’
(3000-6000 degree days) With sun without wind 2 2 1 2 2
Without sun and wind 1 2 2
Without sun with wind 1 2 1 2

Short Heating Season With sun and wind 3 1 2 1


(3000 degree days or less) With sun without wind 3 1 2 1

Without sun and wind 2 1 1

Without sun with wind 2 1 1

Summer

Long Cooling Season


Dry or humid 3 3 3 3 3
(1500 hr @ 80°F)

Moderate Cooling Season


Dry or humid 3 2 2 2 3
(600-1500 hr @ 80°F)

Short Cooling Season


Dry or humid 2 1 1 1 2
(Less than 600 hr @ 80°F)

a. Includes office buildings, factories, and commercial buildings. d. With sun: Sunshine during at least 60% of daylight time.
b. Higher numbers indicate greater importance. e. With wind: Average wind velocity over 9 mph.
c. Provide shading and protection from direct wind.

9.1.6 Thermal Storage Effects delays the time at which these peak loads occur by
Irt years past, the U-factor was considered the several hours. This delay improves the performance
most significant indication of heat gain, principally of heating and cooling equipment, since the peak
because laboratory tests have shown that thermal cooling loads are delayed until the evening hours,
transmission is directly proportional to the U-factor when the outside temperature has dropped.
during steady-state heat flow. However, the steady- Energy use differences between light and heavy
state condition is rarely realized in actual practice. materials are illustrated in the hour-by-hour computer
External conditions {temperature, position of the analyses shown in Figure 9.1.2.
sun, presence of shadows, etc.) vary throughout a 24 Figure 9.1.2(A) compares the heat flow through
hr. day, and heat gain is not instantaneous through three walls having the same U-value, but made of dif­
most solid materials, resulting in the phenomenon of ferent materials. The concrete wall consisted of a lay­
time lag (thermal inertia). As temperatures rise on one er of insulation sandwiched between inner and outer
side of a wall, heat begins to flow towards the cooler wythes of 2 in. concrete and weighed 48.3 psf. The
side. Before heat transfer can be achieved, the wall metal wall, weighing 3.3 psf, had insulation sand­
must undergo a temperature increase. The Btu’s of wiched between an exterior metal panel and xh in.
thermal energy necessary to achieve this increase drywall. The wood frame wall weighed 7.0 psf and
are directly proportional to the specific heat and den­ had wood siding on the outside, insulation between 2
sity of the wall. x 4 studs, and 1A> in. drywall on the inside. The walls
Due to its density, concrete has the capacity to ab­ were exposed to simulated outside temperatures that
sorb and store large quantities of heat. This thermal represented a typical spring day in a moderate cli­
mass allows concrete to react very slowly to changes mate. The massive concrete wall had lower peak
in outside temperature. This characteristic of thermal loads by about 13% for heating and 30% for cooling
mass reduces peak heating and cooling loads and than the less massive walls.

9 -1 2 PCI Design Handbook/Fifth Edition


Figure 9.1.2 Heating: and c o d in g load co m p a rison s

HEATING LOAD, ALL WALLS HAVE HEATING LOAD, ALL WALLS HAVE
BTU/HR.FT2 U -V A L U E S = 0.091 BTU/HR.FT2 U -V A L U E S T= 0.091-
3

3
COOLING LOAD,
BTU/HR.FT2 BTU/HR.FT2

(A) WALLS (B) CONCRETE WALLS

HEATING LOAD, ALL WALLS HAVE HEATING LOAD, BOTH ROOFS HAVE
BTU/HR.FT2 U -V A L U E S = 0.10
3

3
COOLING LOAD; CO O UNG LOAD,
BTU/HR.FT2 BTU/HR.FT2

(C) CONCRETE SANDWICH WALLS (D) ROOFS

PCI Design Handbook/Fifth Edition 9-13


Table 9.1.9 Design considerations for buikiing with low available free tieaF
R e la tiv e Im p o rtan ce o f D esign C o n sideratio ns b

C lim ate C lassification S u rfa c e C o lo r


T h e rm a t Increase External R educe
M ass Insulatio n J3nsc Light D a rk infiltratio n

W in te r -
Long Heating Season With sund and wind® 3 2 3 3
(6000 degree days or With sun without wind 3 3 3
more)
Without sun and wind 3 2 3
Without surr with wind 3 2 2 3
Moderate Heating Season With sun and wind 1 2 1 2 3
(3000-6000 degree days) With sun without wind 1 2 2 3
Without sun and wind 2 1 3
Without sun with wind 1 2 1 1 3
Short Heating Season With sun and wind 2 1 1 2
(3000 degree days or less) With sun without wind 2 1 1 2
Without sun and wind 1 1 2
Without sun with wind 1 1 2
S u m m er

Long Cooling Season


Dry* or humid 9 3 2 2 3
(1500 hr @ 80°F)
Moderate Cooling Season Dry 2 1 1 2
(600-1500 hr @ 80°F) Humid 2 1 1 3
Short Cooling Season
Dry or humid 1 1
(Less than 600 hr @ 80 °F)

a. Includes low-rise residential buildings and some warehouses.


b. Higher numbers indicate greater importance.
c. Provide shading and protection from direct wind.
d. With sun: Sunshine during at least 60% of daylight time.
e. With wind: Average wind velocity over 9 mph.
f. Dry: Daily average relative humidity less than 60% during summer.
g. Humid: Daily average relative humidity greater than 60% during summer.

Normal weight concrete walls of various thick­ psf and the metal roof 1.5 psf. The roofs had identical
nesses that were exposed to the same simulated out­ U-values of 0.10 and were exposed to the same simu­
side temperatures, are compared in Figure 9.1.2(B). lated outside temperatures. The figure shows that the
The walls had a layer of insulation sandwiched be­ concrete roof had lower peak loads by 68% for heat­
tween concrete on the outside and 1 /2 in. drywall on ing and by 94% for cooling, and peaks were delayed
the inside; U-values were the same. The figure shows by about 1.8 hours for heating and about 4 hours for
that the more massive the wall the lower the peak cooling.
loads and the more the peaks were delayed. Another factor affecting the behavior of thermal
Figure 9.1.2(C) compares concrete sandwich mass is the availability of so calted “free heat” . This
panels having an outer wythe of 2 in., various thick­ includes heat generated inside the building by lights,
nesses of insulation, and various thicknesses of inner equipment, appliances, and people. It also includes
wythes. All walls had U-values of 0.091 and were ex­ heat from the sun entering through windows. Gener­
posed to the same simulated outside temperatures. ally, during the heating season, benefits of thermal
The figure shows that by increasing the thickness of mass increase with the availability of “free heat” as
the inner concrete wythes, peak loads were reduced shown in Tables 9.1.8 and 9.1.9. Thus, office build­
and delayed. ings which have high internal heat gains from lights,
A metal roof is compared to a concrete roof in Fig­ people, and large glass areas represent an ideal ap­
ure 9.1.2(D). Both roof systems had built-up roofing plication for thermal mass designs. This is especially
on rigid board insulation on the outside and acousti­ true if the glass has been located to take maximum
cal tile on the inside. The concrete roof weighed 48.3 advantage of the sun. Building codes and standards

9 -1 4 PCI Design Handbook/Fifth Edition


now provide for th e benefits of thermal mass. In in­ Atmospheric air pressure differences-betweenihe
creasing numbers, they are beginning to_acknow1- inside and outside of a building-envelope exist be-
edge the effect of the greater beafcstorage capacity in, oause ofthe action of wind, thedensity dffference be­
buildings-having high thermal mass. tween outside cold heavy air-and inside warm light air
The rates-of many utilities_are structured so that creating a “stack effect” , and tha operation of equip­
lower peaks and- delayed peaks nan result in signifi­ ment suchas fans. The pressuradifferences wilftend
cant cost savings. to equalize, and the air will flow through-holes or
Other studies have shown that concrete buildings^ cracks in the building envelope carrying with it the
have lower average heating and cooling-loads than water vapor it contains.
lightweight buildings for a given insulation level. Athorough analysis of air leakage is very complex^
Thus, life-cycle costs will be lower, or less insulation involving many parameters,-including wall construc­
can be used for equivalent performance. tion, building height and orientation.
Many condensation-related problems in building
g.1.7 Condensation Control enclosures are caused by exfiltration and subse­
quent condensation within the enclosure assembly.
Moisture which condenses on the interior of a
Condensation due to air movement is usually much
building is unsightly and can cause damage to the
greater than that due to vapor diffusion for most build­
building or its contents. Even more undesirable is the
ings. However, when air leakage is controlled or
condensation of moisture within a building wall or
avoided, the contribution from vapor diffusion can still
ceiling assembly where it is not readily noticed until
be significant. In a well designed wall, attention must
damage has occurred. All air in buildings contains
therefore be paid to the control of air flow and vapor
water vapor, with warm air carrying more moisture
diffusion.
than cold air. In many buildings moisture is added to
An air barrier and vapor retarder are both needed,
the air by industrial processes, cooking, laundering,
and in many instances a single material can be used
or humidifiers. If the inside surface temperature of a
to provide both of these as well as other functions.
wall, floor or ceiling is too cold, the air contacting this
The principal function of the air barrier is to stop out­
surface will be cooled beiow its dew-point tempera­
side air from entering the building through the walls,
ture and leave its excess water on that surface. Con­
windows or roof, and inside air from exfiltrating
densation occurs on the surface with the lowest tem­
through the building envelope to the outside. This ap­
perature.
plies whether the air is humid or dry, since air leakage
Condensation on interior room surfaces can be
can result in problems other than the deposition of
controlled both by suitable construction and by pre­
moisture in cavities. Exfiltrating air carries away heat­
cautions such as: (1) reducing the interior dew point
ing and cooling energy, while incoming air may bring
temperature; (2) raising the temperatures of interior
in pollution as well as reduce the effectiveness of a
surfaces that are below the dew point, generally by
rain screen wall system.
use of insulation; and (3) using vapor retarders.
The interior air dew point temperature can be low­
9.1.7.1 Air Barriers
ered by removing moisture from the air, either
through ventilation or dehumidification. Adequate Materials and the method of assembly chosen to
surface temperatures can be maintained during the build an air barrier must meet several requirements if
winter by incorporating sufficient thermal insulation, they are to perform the air leakage control function
using double glazing, circulating warm air over the successfully.
surfaces or directly heating the surfaces, and by pay­
ing proper attention during design to the prevention 1. There must be continuity throughout the build­
of thermal bridging (see Sect. 9.1.8). ing envelope. The low air permeability materi­
Infiltration and exfiltration are air leakage into and als ofthe wall must be continuous with the low
out of a building throughcracks or joints between infill air barrier materials ofthe roof (e.g., the roofing
components and structural elements, interstices membrane) and must be connected to the air
around windows and doors, through floors and walls barrier material of the window frame, etc.
and-openings for building services. They are often a 2. Each membrane or assembly of materials in­
major source of energy loss in buildings. tended to support a differential air pressure
Moisture can move into or across a wall assembly load must be designed and constructed to
by means of vapor diffusion and air movement. If air, carry that load, inward or outward, or it must re­
especially exfiltrating, hot, humid air, can leak into the ceive the necessary support from other ele­
enclosure, then this will be the major source of mois­ ments of the wall. If the air barrier system is
ture. Air migration occurs from air pressure differen­ made of flexible materials, then it must be sup­
tials independent o f moistura pressure differentials.

PCI Design Handbook/Fifth Edition 9 -1 5


ported on both sides by materials- capable of art-essential requirement (This does not necessarily
resisting the peak airpressure loads; or it must mean on the inside surface of the w ait) The position
he_made of self-supportingrnaterials, su d ra s ofthe airbarrier. in a wall is more a matter- of suitable
hoard- products -adequately fastened to the construction practice and the type ofmaterlals lo b e
structure. Itam airpressure difference can not used. However, ifthis barrier is positioned on the-crat-
move air,Jt will act to displace the materials that side ofthe insulation, consideration must be given io-
prevent the air from flowing. its water vapor permeability incase it should also act
as. a barrier to vapor which is on its way out from in-
3. The air barrier system must be virtually air-im­ oide the wall assembly. This situation may be pre­
permeable. A value for maximum allowable air vented by choosing an airbarrier material that is ten
permeability has not yet been determined to twenty times more permeable to water vapor diffu­
However, materials such as polyethylene, gyp­ sion than the vapor barrier material.
sum board, precast concrete panels, metal In the case of construction assemblies which do
sheeting or glass qualify as low air-permeable not lend themselves to the sealing of interior sur­
materials when joints are properly sealed, faces, or where it is desirable to limit condensation to
whereas concrete block, acoustic insulation, very small amounts, such as sandwich wall panel
open cell polystyrene insulation or fiberboard construction (which may have no air leaks through
would not qualify. The metal and glass curtain the panels themselves) or any air space which can
waH industry in the U.S. has adopted a value of ensure venting and drying out in summer, the use of a
0.06 CFM/ft2 at 1.57 lb/ft2 as the maximum al­ separate vapor retarder must be considered. In such
lowable air leakaga rate for these types of wall cases, the insulation material itself, if it is a rigid
construction. closed-cell type, can be installed on a complete bed
of adhesive applied to the interior ofthe inner wythe of
4. The airbarrier assembly must be durable in the the wall with joints fully sealed with adhesive to pro­
same sense that the building is durable, and be vide a barrier to both air and vapor movement.
made of materials that are known to have a While the discussion above has been concerned
long service life or be positioned so that it may with the flat areas of walls, the joints between them
be serviced from time to time. may well present the most important design and
In climates where the heating season dominates, construction problems. There are many kinds of
it is strongly recommended that the visible interior joints and the following are considered the most criti­
surface of a building envelope be installed and cal: the roof/wall connection, the wall/foundation con­
treated as the primary air barrier and vapor retarder. nection, soffit connections, corner details, and con­
Where floors and cross walls are of solid concrete, it nections between different types of exterior wall
is necessary to seal only the joints, as floors and walls systems, such as brick and precast concrete, or cur­
themselves do not constitute air paths. Where hollow tain wall and precast concrete.
partitions, such as steel stud or hollow masonry units
are used, the interior finish of the envelope should be
9.1.7.2 Vapor Retarders
first made continuous. Where this is impractical, poly­
ethylene film should be installed across these junc­ Water vapor diffusion, another way in which in­
tions and later sealed to the interior finish material. An door water can move through a building envelope to
interior finish of gypsum wallboard or plaster painted condense in the colder zones, occurs when water va­
with two coats of enamel paint will provide a satisfac­ por molecules diffuse through solid interior materials
tory air barrier/vapor retarder in many instances if the at a rate dependent on the permeability ofthe materi­
floor/wall and ceiling/wall joints are tightly fitted and als, the vapor pressure and temperature differentials.
sealed with caulking. Generally, the colder the outside temperature the
A recent development is an air barrier and vapor greater the pressure of the water vapor in the warm
retarder system consisting of panel joints sealed from
inside air to reach the cooler, drier outside air.
the inside with a foam backer rod and sealant, plus a
The principal function of a vapor retarder made of
thermal fusible membrane (TFM) seal around the
low permeability materials is to stop or, more accu­
panel, covering the gap between the structure and
rately, to retard the passage of moisture as it diffuses
the panel. Surfaces should be clean, as dry as pos­
through the assembly of materials in a wall. Vapor dif­
sible, smooth, and free of foreign matter which may
fusion control is simple to achieve and is primarily a
impede adhesion. The bond between concrete and
membrane may be improved by priming the concrete function ofthe water vapor diffusion resistance ofthe
before fusing the membrane to it. chosen materials and their position within the build­
While it is preferable that the air barrier system be ing envelope assembly. The vapor retarder should be
placed on the warm side of an insulated assembly, clearly identified by the designer and be clearly identi­
where thermal stresses will be at a minimum, it is not fiable by the general contractor.

9 -1 6 PCI Design Handbook/Fifth Edition


In temperate climates, vapor retarders should be- there witf be a problem with conaensation. In many
applied on or near th e warm side (inner surface) of designs the desire to censerve energy-will dictate the
assemblies. Vapor retarders may bostructural, or- in use of lower U-vafues than those required to avoid the
the form of thin sheets, o r as coatings. Vapor retard­ condensation-problem.
ers may also be-positioned part way into the insula­ The-degree of wall heat transmission resistance
tion but, to avoid condensation, they should be no that must be provided to avoid condensation may be
further tharrthe point at which the-devwpoint temper­ determined Irom the following relationship:
ature is reached.
In climates with high humidities and high tempera­
(Eq. 9.1.2)
tures, especially where air-conditioning is virtually
continuous, the ingress of moisture may be mini­
Dew-point temperatures to the nearest ° F for vari­
mized by a vapor retarder system in the building en­
ous values of f and relative humidity are shown in
velope near the outer surface. For air-conditioned
Table 9.1.10.
buildings in hot and humid climates without extended
cold periods, it may be more economical to use only
adequate air infiltration retarding systems rather than Example 9.1.1
vapor retarders since the interior temperature is very
rarely below the dew point of the outside air. Determine Rt when the room temperature and rel­
Where warm and cold sides may reverse, with re­ ative humidity to be maintained are 70° F and 40%,
sulting reversal of vapor flow, careful analysis of the and to during the heating season is -10°F.
condition is recommended rather than to ignore the From Table 9.1.10 the dew-point temperature t is
problem and omit any vapor retarders. The designer 45°F, and from Table 9.1.1, Rd = 0.68.
should refer to the ASHRAE HandbookFt/nofamenfa/s
[1 ] or ASTM C 755, Selection of Vapor Barriers for 0.68 [70 - ( - 10)}
2.18
Thermal Insulation [5]. In general, a vapor retarder [70 - 45]
should not be placed at both the inside and outside of
U = 1/Rt = 0.46
wall assemblies.
High thermal conductance paths reaching inward Figure 9.1.3 Relative humidity at which vis­
from or near the colder surfaces may cause con­ ible condensation occurs on in­
densation within the construction. High conductance side surfaces. Inside tempera-
paths may occur at junctions of floors and walls, walls
and ceilings, and walls and roofs; around wall or roof
openings; at perimeters of slabs on the ground; and
at connections.
Fittings installed in outer walls, such as electrical
boxes without holes and conduits, should be com­
pletely sealed against moisture and air passage, and
they should be installed on the warm side of unbro­
ken vapor retarders or air barriers that are completely
sealed.

9.1.7.3 Prevention of Condensation on Wall


Surfaces

The U-value of a wall must be such that the surface


temperature will not fall below the dew-point temper­
ature of the room air in order to prevent condensation
on the interior surface of a wall.
Figure 9.1.3 gives U-values for any combination of
outside temperatures and inside relative humidities
above which condensation will occur on the interior
surfaces. For example, if a building were located in an
area with an outdoor design temperature of 0°F and it
was desired to maintain a relative humidity within the
building of 25%, the wall must be designed so that all
components have a U-value less than 0.78, otherwise

PCI Design Handbook/Fifth Edition 9-17


9.1.7.4 Condensation Prevention Within Walt The effectof metal tie thermal bridges on the- heat
Construction transmittance canbe calculated with reasonable-ac­
curacy b y the zone method describeddn Chapter 22
Water vapor in air behaves as a gas and will diffuse
ofRef. 1. With the zone method, the panel is divided
through building-materials at rates which-depend on
into Zone A, which contains the thermal bridge, and
vapor permeabilities of materials and vapor pressure-
Zone B, where thermal bridges do not occur, as
differentials. The colder the outside temperature the
shown in Figure 3.1.4. The width of Zone A is calcu­
greater the pressure of the water vapor in the warm
lated as W = m + 2d, w here m is the width or diame­
inside air to reach the cooler, drier outside air. Also,
te r of the metal or other conductive bridge material,
leakage of moisture laden air into an assembty
and d is the distance from the panel surface to the
through small cracks may be a greater problem than
metal. After the width (W) and area of Zone A are cal­
vapor diffusion. The passage of water vapor through
culated, the heat transmissions of the zonal sections
material is in itself generally not harmful. Water vapor
are determined and converted to area resistances,
passage-becomes harmful when the vapor flow path
which are then added to obtain the total resistance
encounters a temperature below the dew-point. Con­
(Rt) of that portion of the panel. The resistance of
densation then results within the material.
Zone A is combined with that of Zone B to obtain the
Building materials have water vapor permeances
overall resistance and the gross transmission value
from very low to very high (see Table 9.1.11). When
U0, where U0 Is the overall weighted average heat
properly used, low permeance materials keep mois­
transmission coefficient of the panel.
ture from entering a wall or roof assembly. Materials
The net effect of metal ties is to increase the U-val-
with higher permeance allow construction moisture
ue by 10 or 15%, depending on type, size and spac­
and moisture which enters inadvertently or by design
ing. For example, a wall as shown in Figure 9.1.4
to escape.
would have a U-value of 0.13 if the effect of the ties is
When a material such as plaster or gypsum board
neglected. If the effect of Vi in. diameter ties at 16 in.
has a permeance which is too high for the intended
on center is included, U = 0.16; at 24 in. spacing, U =
use, one or two coats of paint is frequently sufficient
0.15.
to lower the permeance to an acceptable level, or a
For sandwich panels with solid concrete paths,
vapor barrier can be used directly behind such prod­
parallel heat flow paths of different conductances re­
ucts. Polyethylene sheet, aluminum foil and roofing
sult. If there is no lateral heat flow between paths,
materials are commonly used. Proprietary vapor bar­
each path is considered to extend from inside to out­
riers, usually combinations of foil and polyethylene or
side, and transmittance of each path can be calcu­
asphalt, are frequently used in freezer and cold stor­
lated using:
age construction.
Concrete is a relatively good vapor retarder, pro­
R = Ri + R2 + R3 + R4 + ... + Rn (Eq. 9.1.3)
vided it remains crack free. Permeance is a function
of the water-cementitious materials ratio of the con­ Rt = Rfj + R + Rfo (Eq. 9.1.4)
crete. A low ratio, such as that used in most precast
concrete members, results in concrete with low per­
meance. The average weighted transmittance is then:
Where climatic conditions require insulation, a va­
por retarder is generally necessary in order to prevent U0 = a(Ua) + b(Ub) + ... +n(Un) (Eq. 9.1.5)
condensation. A closed cell insulation, if properly ap­
plied, will serve as its own vapor retarder. For other where a, b,...,n are respective fractions of a typical
insulation materials a vapor retarder should be ap­ basic area composed of several different paths with
plied to the warm side of the insulation. transmittances Ua, Ub..... Un.
For a more complete treatment of the subject of If heat flows laterally in any continuous layer,
condensation within wall or roof assemblies, see creating transverse isothermal planes, total average
Refs. 1 and 4. resistance R,(av) is the sum of the resistances of the
layers between these planes. This is a series com­
bination of layers, of which one or more provides par­
9.1.8 Thermal Bridges allel paths. The calculated transmittance, assuming
Metal ties through walls or solid concrete paths parallel heat flow only, is usually considerably lower
through sandwich panels as described in Sect. 9.4 than that calculated by assuming a combined series-
may cause localized cold spots. The most significant parallel beat flow. The actual transmittance is a value
effect of these cold spots is condensation which may
cause annoying or damaging wet streaks.

9 -1 8 PCI Design Handbook/Frfth Edition


-Table 9.1.10 Dewpoint Temperatures,9 t ^ F

- R elative humidity (%)


D ry bulb -

or room
temperature, °F
10 -20 30 40 5<y 60 70 80 90 100

40 _ -7 : 6 14 19 24 28 31 34 37 40
45 -3 9 18 23 28 32 36 39 42 45
50 . -1 13 21 27 32 37 41 44 47 50
55 5 17 26 32 37 41 45 49 52 55
60 7 21 30 36 42 46 50 54 57 60
65 11 24 33 40 46 51 55 59 62 65
70 14 27 38 45 51 56 60 63 67 70
75 17 32 42 49 55 60 64 69 72 . 75
80 21 36 46 54 60 65 69 73 77 80
85 23 40 50 58 64 70 74 78 . 82 85
90 27 44 55 63 69 74 79 83 85 90
a. Temperatures are based on barometric pressure of 29.92 in. Hg.

Table 9.1.11 Typical permeance (M) and per­ Figure 9.1.4 Example of thermal bridges
meability (p.) values3
7W
M
Material perms perm-in. .3 " VA" 3"

Concrete (1:2:4 mix)b — 3.2


Wood (sugar pine) — 0.4-5.4 W
«X
Expanded polystyrene (extruded) — 1.2
W W R-
Expanded polystyrene (bead) — 2.0-5.8
Paint—2 coats X
OUTSIDE INSIDE

Asphalt paint on plywood 0.4 ZONE B


TIES -
Enamels on smooth plaster 0.5-1.5
:::
n J - Z I _/
Various primers plus 1 ZONE A
RIGID INSULATION-
coat flat oil paint on plaster 1.6-3.0
Plaster on gypsum lath 20.00
(with studs)
-d = 1.5" CLEAR (TYP.)
Gypsum waliboard, 0.375 in. 50.00
Polyethylene, 2 mil 0.16
between the two calculated values. In the absence of
Polyethylene, 10 mil 0.03 test values for the combination, an intermediate value
Aluminum foil, 0.35 mil 0.05 should be used; examination of the construction usu­
ally indicates whether the value used should be clos­
Aluminum foH, 1 mil 0.00 er to the higher or lower calculated value. Generally, if
Built-up roofing (hot mopped) 0.00 the construction contains any layer in which lateral
conduction is significantly higher than the transmit­
Duplex sheet, asphalt laminated 0.002
tance through the wall, a value closer to the com­
aluminum foil one side
bined series-parallel calculation should be used.
a. ASHRAE Handbook [1J.
However, if there is no layer of high lateral conduc­
b. Permeability for concrete varies depending on the concrete’s
water-cementitious materials ratio and other factors.
tance, a value closer to the calculation for parallel
heat flow only should be used.

PCI Design Handbook/Fifth Edition 9 -1 9


9.1.9 References 3. “Simplified ThermaTDesign ofB uiiding Enve-
lo p esf Batietin EBD89, Portland Cement Asso­
1. ASHRAE Handbook 1997, “Fundamentals,”
ciation, Skokie, 1L, 1981.
American Society of Heating, Refrigerating,
and Air-Conditioning Engineers, New York, NY, 4. Balik, J.S., and Barney, G.B., “Thermal Design
1997. erf Precast Concrete Buitdings,” PC1 Journal] V.
29, No. 6, November-December 1984.
2. ASHRAE Standard 90.1-1989, “Energy Effi­
cient Design of New Buildings Except Low-Rise 5. “Recommended Practice for Selection of Va­
Residential Buildings,” American Society of por Barriers for Thermal Insulation,” ASTM C
Heating* Refrigerating, and Air-Conditioning 755, American Society for Testing and Materi­
Engineers, New York, NY, 1989. als, Philadelphia, PA.

9 -2 0 PCI Design Handbook/fifth Edition


9:2 ACOUSTICAL PROPERTIES ©FO RECAST CONCRETE

3,271 Definitions In addition to the“amptituda o f sound, the properties


such ~as spectraf characteristics, continuity, rever­
Decibel (dB)—a- logarithmic unit measuring
beration and intelligibility must be specified.
sound pressure or sound power. Zero on the decibel
People are highly adaptable to the sensations of
scale corresponds to a standardized reference pres­
heat, light, odor, sound, eta,-with sensitivities varying
sure (20 pPa) or sound pow er (1 0 12 watt).
widely. The human ear can detect a: sound intensity
Hertz (Hz)—a measure of sound wave frequency,
of rustling leaves, 10 dB, and can tolerate, if even
i.e., the number of complete vibration cycles per sec­
briefly, the powerful exhaust of a jet engine at 120 dB,
ond.
1012 times the intensity of therustling leaves sound.
Sabin—the unit of measure of sound absorption
(ASTM C 423).

9*2.4 Dealing with Sound Levels


9.2.2 General
The problems of sound insulation are usually con­
The basic purpose of architectural acoustics is to siderably more complicated than those of sound ab­
provide a satisfactory environment in which desired sorption. The former involves reductions o f sound
sounds are clearly heard by the intended listeners level, which are of greater orders of magnitude than
and unwanted sounds (noise) are isolated or ab­ can be achieved by absorption. These large reduc­
sorbed. tions of sound level from space to space can be
Under most conditions, the architect/engineer can achieved only by continuous, impervious barriers. If
determine the acoustical needs of the space and then the problem also involves structureborne sound, it
design the building to satisfy those needs. Good may be necessary to introduce resilient layers or dis­
acoustical design utilizes both absorptive and reflec­ continuities into the barrier.
tive surfaces, sound barriers and vibration isolators. Sound absorbing materials and sound insulating
Some surfaces must reflect sound so that the loud­ materials are used for different purposes. There is
ness will be adequate in all areas where listeners are not much sound absorption from an 8 in. concrete
located. Other surfaces absorb sound to avoid wall; similarly, high sound insulation is not available
echoes, sound distortion and long reverberation from a porous lightweight material that may be ap­
times. Sound is isolated from rooms where it is not plied to room surfaces. It is important to recognize
wanted by selected wall and floor-ceiling construc­ that the basic mechanisms of sound absorption and
tions. Vibration generated by mechanical equipment sound insulation are quite different.
must be isolated from the structural frame of the
building.
Information is provided on the acoustical proper­
ties of some of the more common precast concrete 9.2.5 Sound Transmission Loss
products used in building construction. This informa­ Sound transmission loss measurements are
tion can be incorporated into the acoustical design of made at a series of 16 contiguous one-third octave
a building and/or can show compliance with local or­ bands with center frequencies in the range of 125 to
dinances or other minimum acoustical requirements 4000 Hz. The testing procedure is ASTM Specifica­
(see Sect. 9.2.10). tion E 90, Laboratory Measurement of Airborne Sound
For buildings or occupancies that require more Transmission Loss o f Building Partitions. To simplify
sophisticated acoustical analysis, such as churches, specification of desired performance characteristics,
concert halls, recording studios, and the like, it may the single number Sound Transmission Class (STC)
be desirable to use the services of a competent was developed.
acoustical design consultant or specialist. Airborne sound reaching a wall, floor or ceiling
produces vibration in the wall and is radiated with re­
9.2.3 Approaching the Design Process duced intensity on the other side. Airborne sound
transmission loss of walls and floor-ceiling assem­
Criteria must be established before the acoustical blies is a function of its weight, stiffness and vibration
design of a building can begin. Basically a satisfac­ damping characteristics.
tory acoustical environment is one in which the char­ Weight is concrete’s greatest asset when it is used
acter and magnitude of all sounds are compatible as a sound insulator. For sections of similar design,
with the intended space function. but different weights, the STC increases approxi­
Although a reasonable objective, it is not always mately 6 units for each doubling of weight as shown
easy to express these intentions in quantitative terms. in Figure 9.2.1.

PCI Design Handbook/Fifth Edition 9 -2 1


Figure 9.2.1 Sound transmission class as a In general, thickness or unit-weight of concrete
function of weight of floor or does not greatly affect the transmission o f impact-
waif sounds as shown irrthe following, table:

Thickness, Unit weight of


concrete,-pef IIC
in.
65 — — —
79 23
FLAT C>R RIBBEED PANEELS, TEE:s WITH
e
52. TOPPING, HOLL.OW-CC5RESLAI3S\
cn 60 5 114 24
.—■
3 144
o 24
z 55
o
05 ' 79 28
52
2
05 50 10 114 30
Z
<
cc STC = 0 1304 W + 43.48
t-
Q 45 ^ ■’V _____ 144 31
z \
D STATI 3TICAL TOLERANCE ± 2.5 STC
o
05
40 Structural concrete floors in combination with re­
40 50 60 70 80 90 100 silient materials effectively control impact sound.
WEIGHT PER UNIT AREA(W), PSF One simple solution consists of good carpeting on re­
silient padding. So called resilient flooring materials,
such as linoleum, rubber, asphalt, vinyl, etc., or par­
quet or strip wood floors are not entirely satisfactory
when applied directly on concrete.
Impact sound also may be controlled by providing
a discontinuity in the structure such as would be ob­
tained by adding a resilient-mounted plaster or dry-
Precast concrete walls, floors and roofs usually do
wall suspended ceiling or a floating floor consisting of
not need additional treatments in order to provide ad­
a second layer of concrete cast over resilient pads,
equate sound insulation. If desired, greater sound in­
insulation boards or mastic. The thickness of floating
sulation can be obtained by using a resiliently at­
slabs is usually controlled by structural requirements,
tached layer or layers of gypsum board or other
however, a thickness providing as little as 8 psf would
building material. The increased transmission loss
be acoustically adequate in most instances.
occurs because the energy flow path is now in­
creased to include a dissipative air column and addi­ 9.2.7 Acoustical Test Results
tional mass.
The acoustical test results of both airborne sound
transmission loss and impact insulation of 4,6, and 8
in. flat panels, a 14 in. double tee, and 6 and 8 in. hol­
9.2.6 Impact Noise Reduction
low-core slabs are shown in Figures 9.2.2,9.2.3, and
Footsteps, dragged chairs, dropped objects, 9.2.4.
slammed doors, and plumbing generate impact Table 9.2.1 presents the ratings for various pre­
noise. Even when airborne sounds are adequately cast concrete waits and floor-ceiling assemblies. The
controlled there can be severe impact noise prob­ effects of various assembly treatments on sound
lems. transmission can also be predicted from results of
The test method used to evaluate systems for im­ previous tests as shown in Table 9.2.2. The improve­
pact sound insulation is described in ASTM E 492, ments are additive, but in some cases the total effect
Laboratory Measurement of Impact Sound Transmis­ may be slightly less than the sum.
sion Using the Tapping Machine. The impact sound Table 9.2.2 shows that a carpet and pad over a
pressure levels are measured in the 16 contiguous bare concrete slab will increase the impact noise re­
one-third octave bands with center frequencies in the duction as much as 56 rating points. The overall effi­
range from 100 to 3150 Hz. For performance specifi­ ciency varies according to the characteristics of the
cation purposes the single number Impact Insulation carpeting and padding such as resilience, thickness
Class (IIC) is used. and weight.

9 -2 2 PCI Design Handbook/Fitth Edition


-Figure 9.2.2 Acoustical test data of solid fiaiconcrete panels— normal weight concrete

Figure 9.2.3 Acoustical test data of 14 in. precast double tees with 2 in. topping—normal wt. concrete

PCI Design Handbook/Fifth Edition 9 -2 3


Figure 9.2.4 Acoustical-test data ofholtow>eore panels— normal weigh! concrete
-- 1 -- 1— l
It, MDr iNSlitAT104


70
0
T3 \
ki31N. HOLLOW-CORE
LLI
> N BARE), JIC—28
UJ 6Q
_l
\ 1 1 1 1 1 1 1
w * IN. HOLLOW-COR
cc
_/
BARE3, IIC >3
3
«- 50
W
HI
cc
Q. 6 IN. HOLLOW-CORE
□ WITH CARPET AND
z 40
3 P/CD IIC■\ 69
o
w
&
< 30
Q.
2

20
8 IN.HOLLC>w-C;o =IEw TH
OAnrt1ANU r/\L/, MO-M
10OIOOOOIOOOOOO
oni s o i D' - Qonoo o
in o
ooo oo oinoooo
■ ^ C M N C O T f l O a j t O O N m o D r O O

FREQUENCY, Hz

9.2.8 Absorption of Sound through a floor or roof would be reduced 5 dB. In


addition, the acoustical ceiling would absorb a por­
A sound wave always loses part of its energy as it
tion of the sound after entry and provide a few more
is reflected by a surface. This loss of energy is termed
decibels of quieting. Use of the following expression
sound absorption. It appears as a decrease in sound
can be made to determine the intraroom noise or
pressure of the reflected wave. The sound absorp­
loudness reduction due to the absorption of sound.
tion coefficient is the fraction of energy incident to but
not reflected per unit of surface area. Thus, an open
window is the standard since 100% of the sound is NR = 10logA° * Aa (Eq. 9.2.1)
A0
“absorbed.” Sound absorption can be specified at in­
dividual frequencies or as an average of absorption where:
coefficients (NRC).
A dense non-porous concrete surface typically ab­ NR = sound pressure level reduction, dB
sorbs 1 to 2% of incident sound and has an NRC of
0.015. There are specially fabricated units with po­ A0 = original absorption, Sabins
rous concrete surfaces which provide greater ab­
sorption. In the case where additional sound absorp­ Aa = added absorption, Sabins
tion of precast concrete is desired, a coating of
acoustical material can be spray applied, acoustical Values for Aq and Aa are the products of the ab­
tile can be applied with adhesive, or an acoustical sorption coefficients of the various room materials
ceiling can be suspended. Most of the spray applied and their surface areas.
fire retardant materials used to increase the fire resist­ A plot of Eq. 9.2.1 is shown in Figure 9.2.5. For an
ance of precast concrete and other floor-ceiling sys­ absorption ratio of 5, the decibel reduction is 7 dB.
tems can also be used to absorb sound. The NRC of Note that the decibel reduction is the same, regard­
the sprayed fiber types range from 0.25 to 0.75. Most less of the original sound pressure level (SPL) and de­
cementitious types have an NRC from 0.25 to 0.50. pends only on the absorption ratio. This is due to the
If an acoustical ceiling were added to Assembly 15 fact that the decibel scale is itself a scale of ratios,
of Table 9.2.1 (as in Assembly 17), the sound entry rather than difference in sound energy.

9 -2 4 PCI Design Handbook/Rfth Edition


Table 9.2.1 Airborne sound transrrifssion loss (STC) ond impact insulation class (J1C) ratings-from
tests o f precast concrete assemblies
Assembly
No. Description STC 1IC

Wall Systems

1 4 in. flat panel, 54 psf 49 —


2 6-in. flat panel, 75 psf 55 -
3 Assembly 2 with “Z” furring channels, 1 in. insulation and 62 —
1/2 in. gypsum board, 75.5 psf
4 Assembly 2 with wood furring, VA in. insulation and 1A in. 63 —
gypsum board, 73 psf
5 Assembly 2 with V2 in. space, 15/s in. metal stud row, 11/2 in. 63a —
insulation and V2 in. gypsum board
6 8 in. flat panel, 95 psf 58 -
7 14 in. prestressed tees with 4 in. flange, 75 psf 54 -

Floor-Ceiling Systems
8 8 in. hollow-core prestressed units, 57 psf 50 28
9 Assembly 8 with carpet and pad, 58 psf 50 73
10 8 in. hollow-core prestressed units with Vf> in. wood block 51 47
flooring adhered directly, 58 psf
11 Assembly 10 except V6 in. wood block flooring adhered to 52 55
'A in. sound-deadening board underlayment adhered to
concrete, 60 psf
12 Assembly 11 with acoustical ceiling, 62 psf 59 61
13 Assembly 8 with quarry tile, VA in. reinforced mortar bed 60 54
with 0.4 in. nylon and carbon black spinerette matting, 76 psf
14 Assembly 13 with suspended % in. gypsum board ceiling with 61 62
31/2 in. insulation, 78.8 psf
15 14 in. prestressed tees with 2 in. concrete topping, 75 psf 54 24
16 Assembly 15 with carpet and pad, 76 psf 54 72
17 Assembly 15 with resiliency suspended acoustical ceiling with 59 51
VA in. mineral fiber blanket above, 77 psf

18 Assembly 17 with carpet and pad, 78 psf 59 82


19 4 in. flat slabs, 54 psf 49 25
20 5 in. flat slabs, 60 psf 52a 24
21 5 in. flat slab concrete with carpet and pad, 61 psf 52a 68
22 6 in. flat slabs, 75 psf 55 34
23 8 in. flat slabs, 95 psf 58 34a
24 10 in. flat slabs, 120 psf 59a 31
25 10 in. flat slab concrete with carpet and pad, 121 psf 59a 74

a. Estimated values

PCI Design Handbook/Fifth Edition 9 -2 5


Table-9r2.2 Typical improvements for wall, floor, anthceifing treatments used with precast concrete
elements
Increase in Ratings
Treatment Airborne Impact
(STCl (HC)

~ Wall furring, % in. insulation and Vz in. gypsum board attached to concrete wall 3 0
Separate metal stud system, V/ 2 in. insulation in stud cavity-and Vz in. gypsum 5 to 10 0
board attached to concrete wall
2 in. concrete topping (24 psf) 3 0
Carpet and pad 0 43 to 56
Vinyl tile 0 3
in. wood block adhered to concrete 0 20
% in. wood block and resilient fiber underlayment adhered to concrete 4 26
Floating concrete floor on fiberboard 7 15
Wood floor, sleepers on concrete 5 15
Wood floor on fiberboard 10 20
Acoustical ceiling resiliently mounted 5 27
—if added to floor with carpet 5 10
Plaster or gypsum board ceiling resiliently mounted 10 8
—with insulation in space above ceiling 13 13
Plaster direct to concrete 0 0

Figure 9.2.5 Relation of decibel reduction of at varying frequencies. RC curves are modifications
reflected sound to absorption that take into account the human response to sound
ratio and the requirements for speech intelligibility.
A low background level obviously is necessary in
rooms or areas where hearing the speakers and
“catching” all the words are important. Conversely,
higher ambient levels can persist in large business of­
fices or factories where speech communication isfim-
ited to short distances. Often it is just as important to
be interested in the minimum as in the maximum per­
missible levels of Table 9.2.3. In an office or resi­
dence, it is desirable to have a certain ambient sound
level to ensure adequate acoustical privacy between
spaces, thus minimizing the transmission loss re­
quirements of unwanted sound (noise).
These undesirable sounds may be from an exteri­
or source such as automobiles or aircraft, or they may
be generated as speech in an adjacent classroom or
9.2.9 Acceptable Noise Criteria music in an apartment. They may be direct impact-in­
duced sound such as footfalls on the floor above, rain
As a rule, a certain amount of continuous sound impact on a lightweight roof construction or vibrating
can be tolerated before it becomes noise. An “ac­ mechanical equipment.
ceptable” level neither disturbs room occupants nor
interferes with the communication of wanted sound. Solving the problem of sound insolation is a reduc­
tion process between the high unwanted noise
The most widely accepted and used noise criteria
source and the desired ambient level, using a proper
today are expressed as either the Noise Criteria (NC)
or the Room Criteria (RC). These criteria are based balance between sound transmission loss and sound
on test curves using different sound pressure levels absorption.

9 -2 6 PCI Design Handbook/Fifth Edition


Table 9.2.3 Suggested noise criteria range and-the Department o f Housing end Urban Develop­
for steady background noise8 m e n t (HUD) listbothairborneSTCencflmpaGt IfC val­
NC or RC ues for different living environments. For example,
Type of space
curve th e HUD recommendations [3] were given a st

1. Private residences 25 to 30 Location STC IIC

2. Apartments 30 to 35
Between living units- 45 45
3. Hotels/motels Between living units
50 50
a. Individual rooms or 30 to 35 and public space
suites
Other community ordinances are more specific,
b. Meeting/banquet rooms 30 to 35
listing the sound insulation criteria with relation to par­
c. Halls, corridors, lobbies 35 to 40 ticular ambient environments [4].
d'. Service/support area 40 to 45
Grade 1 Grade II Grade ill
4. Offices
Residential
a. Executive 25 to 30 Suburban Urban and Urban
Suburban
b. Conference rooms 25 to 30
c. Private 30 to 35 Ambient NC or RC NC or RC NC or RC
d. Open-plan areas 35 to 40 level 20-25 25-30 35+
e. Computer/business Walls STC 55 STC 52 STC 48
40 to 45
machine areas Fioor-ceiling STC 55 STC 52 STC 48
f. Public circulation 40 to 45 assemblies IIC 55 JiC 55 IIC 48
5. Hospitals and clinics Once the objectives are established r the designer
a. Private rooms then should refer to available data, e.g., Figure 9.2.1
25 to 30
or Tables 9.2.1 and 9.2.2, and select the system
b. Wards 30 to 35 which best meets these requirements. In this re­
c. Operating rooms 25 to 30 spect, concrete systems have superior properties
d. Laboratories 30 to 35 and can with minimal effort comply with these criteria.
When the insulation value has not been specified,
e. Corridors 30 to 35
selection of the necessary barrier can be determined
f. Public areas 35 to 40 analytically by (1) identifying exterior and/or interior
6. Churches 25 to 30b noise sources, and (2) by establishing acceptable in­
7. Schools terior noise criteria.

a. Lecture and classrooms 25 to 30


b. Open-plan classrooms 30 to 35b 9.2.11 Composite Wall Considerations

8. Libraries 30 to 35 An acoustically composite wall is made up of ele­


9. Concert Halls See noteb ments of varying acoustical properties. Doors and
windows are often the weak link in an otherwise effec­
10. Legitimate theaters See noteb tive sound barrier. Minimal effects on sound trans­
11. Recording studios See noteb mission loss will be achieved in most cases by a prop­
12. Movie theaters 30 to 35 er selection of glass (plate vs. insulating) [5].
Mounting of the glass in its frame should be done with
a. Design goals, as determined from the curves, can be in­
creased by 5 dB when dictated by budget constraints or care to eliminate noise leaks and to reduce the glass
when noise intrusion fromother sources represents a lim­ plate vibrations.
iting condition. Sound transmission loss of a door depends upon
b. An acoustical expert should be consulted for guidance
on these critical spaces. its material and construction, and the sealing be­
tween the door and the frame [6].
Acoustical design must consider the acoustical
9-2.10 Establishment of Noise Insulation properties of doors, windows or other elements, the
Objectives ratio of openings in the wall system, and the dis­
Often acoustical control is specified as to the mini­ tances between openings. Installation procedures
mum insulation values of the dividing partition sys­ and materials must be specified to ensure desired
tem. Municipal building codes, lending institutions thermal and acoustical seals.

PCl-Design Handbook/Fifth Edition 9 -2 7


In exterior walls, the proper application of seated
and backup materials in the joints between units will
not allow sound to flank the waH.
Although not easily quantified, an inverse relation­
ship exists between the performance of a n element
as a primary barrier and its propensity to transmit
flanking sound. In other words, the probability of“ex­
isting flanking p a th s in a concrete structure is much
less than in one of a steel or wood frame.
In addition to using basic structural materials,
flanking paths can be minimized by:

1. Interrupting the continuous flow of energy with


dissimilar materials, e.g., expansion or control
joints or dead airspace.

2. Increasing the resistance to energy flow with


floating floor systems, full height and/or double
partitions and suspended ceilings.

9.2.13 References

1. “ASHRAE Systems Handbook for 1996,” Amer­


ican Society of Heating, Refrigerating and Air-
Conditioning Engineers, New York, NY, 1996.
2. Blazier, W.E, “Revised Noise Criteria for De­
9.2.12 Leaks and Flanking sign and Rating of HVAC Systems,” paper pre­
sented at ASHRAE Semi-annual Meeting, Chi­
The performance of a building section with an
cago, IL, January 26,1981.
otherwise adequate STC can be seriously reduced
3. Berendt, R.D., Winzer G.E., and Burroughs, C.
by a relatively small hole or any other path which al­
B., “A Guide to Airborne, Impact and Structure-
lows sound to bypass the acoustical barrier. All noise
borne Noise Control in Multifamily Dwellings,”
which reaches a space by paths other than through
the primary barrier is called flanking. Common flank­ prepared for Federal Housing Administration,
U.S. Government Printing Office, Washington,
ing paths (gaps) are openings around doors or win­
DC, 1975.
dows, at electrical outlets, telephone and television
connections, and pipe and duct penetrations. Sus­ 4. Sabine, H.J., Lacher, M.B., Flynn, D.R., and
pended ceilings in rooms where walls do not extend Quindry, T.L., “Acoustical and Thermal Perfor­
from the ceiling to the roof or floor above alfow sound mance of Exterior Residential Walls, Doors and
to travel to adjacent rooms. Windows,” National Bureau of Standards, U.S.
Anticipation and prevention of leaks begins at the Government Printing Office, Washington, DC,
design stage. Flanking paths at the perimeters of in­ 1975.
terior precast walls and floors are generally sealed 5. HTRI, “Compendium of Materials for Noise
during construction with grout or drypack. In addi­ Control,” U.S. Department of Heath, Education
tion, all openings around penetrations through walls and Welfare, U.S. Government Printing Office,
or floors should be as small as possible and must be Washington, DC, 1980.
sealed airtight. The higher the STC of the barrier, the 6. Beranek, L.L., '‘Noise Reduction,” McGraw-Hill
greater the effect of an unsealed opening. Book Co., New York, NY, 1960.
Perimeter leakage more commonly occurs at the
7. Harris, C.M., “Handbook of Acoustical Mea­
intersection between an exterior curtain wall and floor
surements and Noise Control,” McGraw-Hill
slab. It is of vital importance to seal this gap in order
Book Co., New York, NY, 1991.
to retain the acoustical integrity of the system as well
8. Litvin, A., and Belliston, H.W., “Sound Trans­
as provide the required fire stop between floors. One
mission Loss Through Concrete and Concrete
way to achieve this seal is to place a 4 pcf density min­
Masonry Walls,” Journal o f the American Con­
eral wool blanket between the floor slab and the exte­
crete Institute, V. 75, No. 12, December 1978.
rior wall. Figure 9.2.6 demonstrates the acoustical
isolation effects of this treatment. 9. “Acoustical Properties of Precast Concrete,”
PCI Journal, V. 23, No. 2, March-April 1978.

9 -2 8 PCI Design Handbook/Fifth Edition


9.3 FIRE RESISTANCE

9.3.1 Notation 9.3.2 Definitions


Note: Subscript 0 indicates the property a s a f- Carbonate aggregate concrete— concrete
fected by elevated temperatures. made wittraggregates consisting mainly o f calcium
or magnesium carbonate, e.g., limestone or dolo­
a — depth of equivalent rectangular com­ mite.
pression stress block Fire endurance—a measure of the elapsedtim e
= area of uncoated prestressing steel during which a material or assembly continues to ex­
Aps
hibit fire resistance under specified conditions of test
As areaofnon-prestressed reinforce­
and performance. As applied to elements of buildings
ment
it shall be measured by the methods and to the crite­
=r area o f reinforcement in negative
As ria defined in ASTM E 119. (Defined in ASTM E 176).
moment region Fire resistance—the property o f a material or as­
b = width of member sembly to withstand fire or to give protection from it.
As applied to elements of buildings, it is character­
d distance from centroid of prestress­
ized by the ability to confine a fire or to continue to
ing steel to the extreme compression
perform a given structural function, or both. (Defined
fiber
in ASTM E 176).
ft = compressive strength of concrete Fire resistance rating (sometimes called fire rat­
fps — stress in the uncoated prestressing ing, fire resistance classification, or hourly rat­
steel at nominal strength ing)— a legal term defined in building codes, usually
— ultimate tensile strength of uncoated based on fire endurances. Fire resistance ratings are
fpu
prestressing steel assigned by building codes or building officials for
various types of construction and occupancies and
h = total depth of a member are usually given in half-hour increments.
l = span length Lightweight aggregate concrete—concrete
= nominal moment strength made with lightweight aggregate (expanded clay,
Mn
shale, slag, or slate, or sintered fly ash) and having a
MJ, positive nominal moment strength at
28 day air-dry unit weight of 85 to 105 pcf.
elevated temperatures
Sand-lightweight concrete—concrete made
M n6 = negative nominal moment strength with a combination of lightweight aggregate (expand­
at elevated temperatures ed clay, shale, slag, or slate, or sintered fly ash) and
R fire endurance of an element or a normal weight aggregate and having a 28 day air-dry
composite assembly unit weight of 105 to 120 pcf.
SHiceous aggregate concrete—concrete made
Rl> ^2i Rn= fire endurance of individual courses
with normal weight aggregates consisting mainly of
s = spacing of ribs in ribbed panels silica or compounds other than calcium or magne­
t = minimum thickness of ribbed panels sium carbonate.

te = equivalent thickness of ribbed


panels 9.3.3 Introduction
U distance from prestressing steel to Precast and prestressed concrete members can
the fire exposed surface be used to meet any degree of fire resistance that
w = uniform total load may be required by building codes, insurance com­
Wd = uniform dead load panies, and other authorities. Fire resistance ratings
o f building assemblies can be determined from
W« = uniform live load ASTM E 119 standard fire tests, code-approved em­
x, Xo, horizontal distances as shown in pirical data, or by calculation procedures detailed in
Xi, x2 Figures 9.3.15, 9.3.16, and 9.3.17 Sect. 9.3.7. The calculation method is based on engi­
distance from centroid of prestress­ neering principles, taking into account the time-tem­
ys
ing steel to the bottom surface perature condition of the standard fire test. This
method, hereafter referred to as the Rational Design
8s = temperature of steel
Method of determining fire resistance, was formu­
<l> = strength reduction factor lated as a result of extensive research sponsored in

PCI Design Handbook/Fifth Edition 9 -2 9


part by the Preeast/Prestressed Concrete institute Figure 9.34 Standard time-tem perature
(PCi) and conducted-by the Portland Cement Associ­ -c u rve
ation (PCA) and other laboratories.
ifDyu
Examples using the Rational Design Method are LL
provided in Sect. 9.3.7 along wittra brief explanation LU
CEr
of the method's underlying principles. For additional
examples, design charts, and an in-depth explana­ <
GC
tion of the method, refer to the PCI manual, LIT
Q-
MNL-124-89, Design fo r Fire Resistance of Precast uj 1500
Prestressed Concrete [ lia s well as the CRSI manual, l-
-
LU
Reinforced Concrete Fire Resistance [2], These ref­ GC
UJ
erences have for years been recognized by the mod­ 1000
w
el codes as acceptable resource documents for de­ o
2
termining fire resistance ratings o f concrete by other
!<
than prescriptive means. w 500
o
High-strength concrete (compressive strengths <
z
up to 10,000 psi) will perform under fire conditions as cc
described herein provided minimum cover and other £ ° c 2 4 6 8
dimensional requirements are adhered to [3]. FIRE TEST TIME, HR

9.3.4 Standard Fire Tests During fire tests of floors, roofs, beams, load bear­
ing walls, and columns, loads are applied which,
The fire resistance of building components is mea­
along with the dead weight of the specimen, closely
sured in standard fire tests defined by ASTM E 119,
approximate the maximum loads required by the
Standard Test Methods for Fire Tests of Building
model codes. Tests which have been conducted on
Construction and Materials. During these tests the
prestressed members were generally done with full
building assembly, such as a portion of floors, walls,
loads, whereas other materials and members have
roofs or columns, is subjected to increasing tempera­
been tested utilizing less than the maximum loads.
tures that vary with time as shown in Figure 9.3.1.
This, in effect, limits those test results to the specific
This time-temperature relationship is used as a stan­ loading conditions.
dard to represent the combustion of about 10 lb of Floor and roof specimens are exposed to fire from
wood (with a heat potential of 8,000 Btu per lb) per fP
beneath, beams from the bottom and sides, walls
of exposed area per hour of test. Actually, the fuel
from one side, and columns from all sides.
consumption to maintain the standard time-tempera­
ASTM E 119 distinguishes between “restrained”
ture relationship during a fire test depends on the de­
and “unrestrained” assemblies and defines them as
sign of the furnace and on the test specimen. When
follows:
fire tested, assemblies with exposed concrete mem­
“Floor and roof assemblies and individual beams
bers require considerably more fuel than other as­
in buildings shall be considered restrained when
semblies due to the favorable heat capacity. This fact the surrounding or supporting structure is capable
is not recognized when evaluating fire resistance. of resisting substantial thermal expansion
In addition to defining a standard time-tempera­ throughout the range of anticipated elevated tem­
ture relationship, standard fire tests involve regula­ peratures. Constructions not complying with this
tions concerning the size of the assemblies, the definition are assumed to be free to rotate and ex­
amount of applied load, the region of the assembly to pand and shall therefore be considered as unre­
be exposed to fire, and the end point criteria on which strained.”
fire resistance (duration) is based. While the focus of this definition is mainly on the
ASTM E 119 specifies the minimum sizes of speci­ axial resistance of the supporting or surrounding
mens to be exposed in fire tests, although much valu­ structure to thermal expansion, the intent of "re­
able data has been developed from tests on speci­ straint” actually can be expanded for concrete mem­
mens smaller than the ASTM minimum sizes. For bers, as opposed to other materials, to include rota­
floors and roofs, at least 180 ft2 must be exposed to tional restraint and continuity as well (see Sect.
fire from beneath, and neither dimension can be less 9.3.7.2 on continuous members).
than 12 ft. For tests of walls, either load bearing or ASTM. E 119 includes a guide for classifying types
non-load bearing, the minimum specified area is 100 of construction as restrained or unrestrained and is
ft2 with neither dimension less than 9 ft. The minimum reproduced in Table 9.3.1. The guide indicates that
length for columns is specified to be 9 ft, while for cast-in-place and most precast concrete construc­
beams it is 12 ft. tions are considered to be restrained.

9 -3 0 PCI Design Handbook/Frfth Edition


Ta b le 9.3.1 Considerations or restra'mtfor common construction3 ___________________________
I. Wall hearing:
Single span.and simply supported end spans of multiple bays:b
T. Open-web steel joists or steel beams supporting concrete slab,
precast units, or metal d eckin g ........................ ............................................... unrestrained
2. Concrete slabs, precast units, or metal d e c k in g ........................................... unrestrained
Interior spans or muitipte bays:
1. Open-web steel joists, steel beams or metal decking
supporting continuous concrete s la b ..................... ............................................... restrained
2. Open-web steel joists, steel beams supporting precast
units or metal d ecking ....................................................................................... unrestrained
3. Cast-in-place concrete slab system s.....................................................................restrained
4. Precast concrete where the potential thermal expansion
is resisted by adjacent construction0 .................................................. .................. restrained
II. Steel framing:
1. Steel beams welded, riveted, or bolted to the framing
members ..................... .......................................................................... ............... restrained
2. All types of cast-in-place floor and roof systems (such
as beam-and-sJabs, flat slabs, pan joists, and waffle slabs)
where the floor or roof system is secured to the framing members ................. restrained
3. All types of prefabricated floor or roof systems where the
structural members are secured to the framing members and
the potential thermal expansion of the floor or roof system is
resisted by the framing system or the adjoining floor or roof
construction0 ............................................ ................................................................ restrained
Hi. Concrete framing:
1. Beams securely fastened to the framing members.............................................. restrained
2. All types of cast-in-place floor or roof systems (such as
beam-and-slabs, flat slabs, pan joists, and waffle slabs) where
the floor system is cast with the framing m em bers..............................................restrained
3. Interior and exterior spans of precast systems with cast-in-place
joints resulting in restraint equivalent to that which would exist
in condition 111-1..........................................................................................................restrained
4. All types of prefabricated floor or roof systems where the
structural members are secured to such systems and the potential
thermal expansion of the floor or roof systems is resisted by the
framing system or the adjoining floor or roof construction1* ............... ................restrained
IV. Wood construction:
All ty p e s ........................................................................................................................ unrestrained

I______________________________________________________________________________________
a. Source: ASTM E 119, “Standard Test Methods for Fire Tests of Building Construction and Materials”, Table X3.1.
b. Floor and roof systems can be considered restrained when they are tied into walls with or without tie beams, the walls being designed and detailed
to resist thermal thrust from the floor or the roof.
c. For example, resistance to potential thermal expansion is considered to be achieved when:
1. Continuous structural concrete topping is used;
2. The space between the ends of precast units or between the ends of units and the vertical face of supports is filled with concrete or mortar; or
3. The space between the ends of precast units and the vertical faces of supports, or between the ends of solid or hollow-core slab units does
not exceed 0.25 % of the length for normal weight concrete members or 0.1 % of the length for structural lightweight concrete members.

9.3.4.1 Fire Endurance, End Point Criteria, and End point criteria defined by ASTM E 119 include:
Fire Rating
1. Load bearing specimens must sustain the ap­
The Fire Resistance of an assembly is measured plied loading. Collapse is an obvious end point
by its fire endurance, defined as the period of time (structural end point).
elapsed before a prescribed condition of failure or
end point is reached during a standard fire test. A Fire 2. Holes, cracks, or fissures through which flames
Rating or Classification is a legal term for a fire endur­ or gases hot enough to ignite cotton waste
ance required by a building code authority. must not form (flame passage end point).

PCI Design Handbook/Fifth Edition 9 -3 1


3. The temperature increase of the unexposed double tee anctsingte tee-floors-and roofs, wet-cast
surface of floors, roofs, o r walls must mot ex­ hollow-core and solid slabs, e n d prestressed con­
ceed an average of 250° F or a maximum erf crete beams.
325°F at any one point (heat transmission end The Portland Dement Association conducted
point). many fire tests of prestressed concrete assemblies.
FDA’s unique furnaces haye made it possible to
Unrestrained assembly classifications can be de­
study in depth the effects of support conditions. Four
rived from tests of restrained floor, roof, or beam series of tests dealt with simply supported slabs and
specimens provided that the average temperature o f
beams; two series dealt with continuous slabs and
the tension steel at any section must not exceed
beams; and one major series, dealt with the effects of
800° F for cold-drawn prestressing steel or 1100°Ffor
restrained thermal expansion on the behavior during
reinforcing bars.
fire of prestressed concrete floors and roofs. PCA has
Additional end point criteria for restrained speci­
also conducted a num ber o f miscellaneous fire tests
mens are:
of prestressed and reinforced concrete assemblies.
1. Beams more than 4 ft on centers: the above Test results that have been published as Research
steel temperatures must not be exceeded for and Development Bulletins are available from the
classifications o f 1 hr or less; for classifications PCA [4,5].
longer than 1 hr, the above temperatures must
not be exceeded for the first half of the classifi­
cation period or 1 hr, whichever is longer. 9.3.5.2 Fire Tests of Walls and Columns

2. Beams 4 ft or less on centers or slabs are not A test was conducted by Underwriters Laborato­
subjected to steel temperature limitations. ries, Inc., on a double tee wall assembly for research
purposes in which fire was applied to the flat surface
Walls and partitions must meet the same structur­ of the 11A in. thick flange. A load of about 10 klf was
al, flame passage, and heat transmission end points applied at the top of the wall. The wall withstood a 2 hr
described above. In addition, they must withstand a fire and a subsequent hose stream test followed by a
hose stream test (simulating, in a specified manner, a double load test without distress. Because the flange
fire fighter’s hose stream). was only 1Vi in. thick, the heat transmission require­
ment was exceeded for most of the test. By providing
adequate flange thickness or insulation, the heat
9.3.5 Fire Tests of Prestressed Concrete
transmission requirement would have been met in
Assemblies
addition to the structural requirement.
The first fire test of a prestressed concrete assem­ Fire tests of reinforced concrete columns have
bly in America was conducted in 1953 and, since been conducted by the PCA and the National Re­
then, more than 150 prestressed concrete assem­ search Council of Canada. While no tests have been
blies have been subjected to standard fire tests in conducted for prestressed concrete columns, results
America. Although many of the tests were conducted from these tests are considered to be equally applica­
for the purpose of deriving specific fire ratings, most ble to prestressed concrete columns with adjustment
of the tests were performed in conjunction with broad made for the difference in thermal properties be­
research studies whose objectives have been to un­ tween mild reinforcing steel and prestressing strand
derstand the behavior of prestressed concrete sub­ as may be appropriate.
jected to fire. The knowledge gained from these tests
has resulted in the development of (1) lists of fire re­
sistive prestressed concrete building components, 9.3.6 Designing for Heat Transmission
and (2) procedures for determining the fire endur­
ance of prestressed concrete members by calcula­ As noted in Sect. 9.3.4, ASTM E 119 imposes heat
tion. transmission criteria for floor, roof, and wall assem­
blies. Thus, floors, roofs, or walls requiring a fire-re­
sistance rating must satisfy the heat transmission re­
9.3.5.1 Fire Tests of Flexural Elements
quirements as well as the various structural criteria.
Reports of a number of tests sponsored by the The heat transmission fire endurance of a concrete
Precast/Prestressed Concrete Institute have been is­ assembly is essentially the same whether the assem­
sued by Underwriters. Laboratories, Inc. Most of the bly is tested as a floor (oriented horizontally) or as a
reports have been reprinted by the PCI, and the re­ wall (tested vertically). Because of this, and unless
sults of the tests are the basis for UL’s listings and otherwise noted, the information, which follows is ap­
specifications for non-proprietary products such as plicable to floors, roofs, or walls.

9 -3 2 PCI Design Handbook/Fifth Edition


Figure 9.3.2 Fire endurance (heat transmis* Table 9.3.2 Thickness o f concrete slabs or
sion) of concrete slabs or wall panelsriaced with H-in. Type
X gypsum wallboard to provide
fire endurances of 2 andJ3 hr

Thickness (in,) of concrete


panel for fire endurance of
-
W ith no air With 6-in.
space air space

Aggregate 2 hr 3 hr 2 hr 3 hr

Sand-lightweight 2.0 3.0 1.2 2.4


Carbonate 2.3 3.7 1.3 2.7
Siliceous 2.5 3.9 1.3 2.8

9.3.6.2 Floors, Roofs or Walls Faced with


Gypsum Wallboard

Table 9.3.2 shows the fire endurance of concrete


slabs with %-in. gypsum wallboard (Type X) for two
cases: (1) a 6-in. air space between the wallboard
and slab, and (2) no space between the wallboard
and slab. Materials and techniques of attaching the
wallboard should be similar to those used in the UL
test on which the data are based.
9.3.6.1 Single Course Slabs or Wall Panels

For concrete slabs or wall panels, the temperature


rise of the unexposed surface depends mainly on the 9.3.6.3 Ribbed Panels
thickness and aggregate type of the concrete. Other Heat transmission through a ribbed panel is in­
less important factors include unit weight, moisture fluenced by the thinnest portion of the panel and by
condition, air content, and maximum aggregate size. the panel’s “equivalent thickness.” Here, equivalent
Within the usual ranges, water-cementitious materi­ thickness is defined as the net cross-sectional area of
als ratio, strength, and age have only insignificant ef­ the panel divided by the width of the cross-section. In
fects. calculating the net cross-sectional area of the panel,
Figure 9.3.2 shows the fire endurance (heat trans­ portions of ribs that project beyond twice the mini­
mission) of concrete slabs as influenced by aggre­ mum thickness should be neglected, as shown in
gate types and thickness. For a hollow-core slab, this Figure 9.3.3(A).
thickness may be obtained by dividing the net cross The heat transmission fire endurance can be gov­
sectional area by its width. The curves represent air- erned by either the thinnest section, or by the average
entrained concrete made with air-dry aggregates thickness, or by a combination of the two. The follow­
having a nominal maximum size of % in. and fire ing rule-of-thumb expressions appear to give a rea­
tested when the concrete was at the standard mois­ sonable guide as to when the average thickness gov­
ture condition (75%R.H. at mid-depth). On the graph, erns:
concrete aggregates are designated as lightweight,
sand-lightweight, carbonate, or siiiceous. Light­ Figure 9.3.3 Cross sections of ribbed wall
weight aggregates include expanded clay, shale, panels
and slate which produce concretes having unit
weights of about 95 to 105 pcf without sand replace­
ment. Lightweight concretes, in which sand is used
as part or all of the fine aggregate and weigh no more
than about 120 pcf, are designated as sand-light­
weight. Carbonate aggregates include limestone and
dolomite, i.e., those consisting mainly of calcium
and/or magnesium carbonate. Siliceous aggregates
include quartzite, granite, basalt, and most hard
rocks other than limestone and dolomite.

PCI Design Handbook/Fifth Edition 9 -3 3


1ft < s/4, fire endurance R is governed by band is 9.3.6.4 Multi-Course Assemblies
equal to Rt.
Floors and roofs often consist o f concrete base
If t > s/2, fire endurance R is governedby 4 and slabs witfroverlaysor undercoatings of other types of
is equal to Rte. eoncrete^or insulating-materials. In addition, roofs
generally have built-up roofing.
If s/2 > t > s/4: If the fire endurance erf the individual courses are
known, the fire endurance of the composite assem­
R = R, + (4t/s - 1)(Rte - Rt) (Eq. 9.3.1) bly can be estimated from theJormula:

where: R 059 = R?59 + R259 +... * Rn


059 (Eq. 9.3.2)
t = minimum thickness where:
te = equivalent thickness of panel R = fire endurance of the composite
s = rib spacing assembly in minutes

and where R is the fire endurance of a concrete panel RiTtaRn = fire endurances of the individual
and subscripts t and te relate the corresponding R val­ courses in minutes
ues to concrete slab thicknesses t and te, respective­ Figure 9.3.4 gives R-values raised to the 0.59 pow­
ly- er for insulating materials (in the table) and for con­
These expressions apply to ribbed and corru­ crete of various types and thicknesses (in the chart).
gated panels, but for panels with widely spaced Table 9.3.3 gives R-values which can be used in this
grooves or rustications they give excessively low re­ equation for certain insulating materials. For heat
sults. Consequently, engineering judgment must be transmission, three-ply built-up roofing contributes
used when applying the above expressions. 10 min. to the fire endurance. Either set of data can
be used in solving Eq. 9.3.2 as shown in the following
example.
Example 9.3.1 Fire Endurance of a Ribbed
Panel

Given: Example 9.3.2 Fire Endurance of an Assem­


The section of a wall panel shown. bly

Problem:
CM
e0
»

Determine the fire endurance of a slab consisting


;

of a 2 in. base slab of siliceous aggregate concrete


i7 ‘ x4 <
HW \ /4
with a 21/2 in. topping of sand-lightweight concrete
4 4
‘T
*4
(115 pcf).
* 4 4 <
<
.< • • • . 4
Solution:
Problem: From Figure 9.3.2, the fire endurances of a 2 in.
Estimate the fire endurance if the minimum thick­ thick slab of siliceous aggregate concrete and 2M>in.
ness is 4 in. and the equivalent thickness is 4.8 in. As­ of sand-lightweight aggregate concrete are 25 min
sume that the panel is made of sand-lightweight con­ and 54 min, respectively.
crete. R0.59 = (2 5)05 9 + (54)0.59

Solution: R059 = 6.68 + 10.52 = 17.20


See Figure 9.3.2. R = 124.2 = 124 min = 2 hr 4 min
t = 4 in., s/2 = 6 in., s/4 = 3 in.
Therefore, s/2 > 4 > s/4 From Figure 9.3.4
R = Rt + (4 t/s - 1) (Rte - Rt) R 0.59 = 6.7 + 1 0 .4 = 1 7 .1

Rt = fire endurance of 4 in. sand-lightweight


panel = 135 min By linear interpolation:
Rte = fire endurance of 4.8 in. sand-lightweight
panel = 193 min R = 120 + ! r ii( 6 0 ) = 1 2 3 .3

R = 135 + [4(4)/12 - 1] [193 - 135]


R= 123 min = 2 hr 3 min
= 154 min

9 -3 4 PCI Design Harrdbook/Fffth Edition


figure 9.3.4 Design aid tor use in solving Eq. 9.3.2

R, MINUTES R-Q-59

60 11.20
120 16.85
180 21.41
240 25.37

MATERIAL R P .5 9

CELLULAR PLASTIC
(1IN. OR THICKER) 2.57

% IN. GLASS
FIBER BOARD 4.03

Vh IN. GLASS
FIBER BOARD 8.57

CONTINUOUS
AIR SPACE 3.33
TWO CONTINUOUS
AIR SPACES 6.67

2 IN. FOAM GLASS 10.61

THICKNESS OF ONE COURSE, IN.

Table 9.3.3 Values of R of various insulating 9.3.4 through 9.3.6, which are based on test results,
materials for use in Eq. 9.3.2 can be used to estimate the required thicknesses of
Roof insulation two-course materials for various fire endurances.
Thickness (in.) R (min)
material

Cellular plastic >1 5 9.3.6.5 Sandwich Panels


Glass fiber board % 11
Some wall panels are made by sandwiching an in­
Glass fiber board 11/2 35 sulating material between two face slabs of concrete.
Foam glass 2 55 See Sect. 9.4.
Several building codes require that where non­
Mineral board 1 19
combustible construction is specified, combustible
Mineral board 2 62 elements in walls shall be limited to thermal and
Mineral board 3 123 sound insulation having a flame spread classification
Note that some of these materials may be used only where combustible of not more than 75 when the insulation is sand­
construction is permitted. wiched between two layers of non-combustible mate­
rial such as concrete.
Eq. 9.3.2 has certain shortcomings in that it does
When insulation is not installed in this manner, it is
not account for the location of the individual courses
required to have a flame spread of not more than 25.
relative to the fired surface. Also, it is not possible to
Data on flame spread classification are available from
directly obtain the fire endurances of many insulating
insulation manufacturers.
materials. Nevertheless, in a series of tests, the for­
A fire test was conducted of one such panel that
mula estimated the fire endurances within about 10%
consisted of a 2 in. base slab of carbonate aggregate
for most assemblies.
concrete, a 1 in. layer of cellular polystyrene insula­
A report on two-course floors and roofs [6] gives
tion, and a 2 in. face slab of carbonate aggregate
results of many fire tests. The report also shows
concrete. The resulting fire endurance was 2 hr 00
graphically the fire endurances of assemblies con­
min. From Eq. 9.3.2, the contribution of the T in. layer
sisting of various thicknesses of two materials. Tables
of polystyrene was calculated to be 5 min.

PCI Design Handbook/Fifth Edition 9 -3 5


Table 9.3.4 Thickness of spray-applied insu­ Table 9.3.5 Thickness ofTwo-course roof
lation on fire-exposed surface of assemblies consisting o f con­
concrete® slabs or paneisrto re­ crete® slabs with insulating con-
sist transfer of heat througtrthe Crete overlays13
assemblies INSULATING
s u u m /tftic
-
* t■ 1 «• OVERLAY
* * . -
A *—
A * t CONCRETE A CONCRETE
A * \ - * *4 . \\ .
BASE SLAB
-- - ----- - —
■» .r . ■■ — ■
.--- _ — -- ~——-
SMF OR VCM /
Base Thickness o f overlay (in.) fo r fire-
slab resistance rating of
thickness
Slab Thickness (in.) for fire- 1 hr VA hr 2 hr 3 hr
(in.) 4 hr
equiva- Type resistance rating of
tent of VA 1Vs VA VA 2% 3V4
thickness insula- VA 2 1 13/8 13/4 2V? 3
4 hr hr 2 hr 3 hr 4 hr
On.) ttonb 3 % 3/4 VA . 2 25/8

va SMF \h. 3/4 ' VA N.A. N.A. 4 0 0 % VA 2


,5
SMF 3A S
A ; 7A m N.A. a. Values shown are for siliceous aggregate concrete, and
2% SMF 'A % VA ; t% are conservative for other concretes,
, b. Insulating concrete having a dry density less than 35 pcf.
3 SMF Mi 1/4 V4 Vs 13/4
i1 SMF 0 0 V* % r
Table 9.3.6 Thickness of roof assemblies
VA VCM A % VA 1% N.A. consisting of concrete® slabs
l VCM 3A 5/4 7A va 13/4
with insulation and built-up roof­
2V6 VCM 'A Vfe 3/4 VA 1%
.
ing
3 VCM % % Vs 13/4
i1 VCM 0 0 1
/4 5/4 7A
a. Values shown are for siliceous aggregate concrete, and
are conservative for other concretes. " STANDARD
b. SMF = Sprayed mineral fiber consists of refined mineral
3-PLY
fibers with inorganic binders and water added during the
spraying operation. The density of the oven-dry material I t " -l J. I I l-l Lll l-l BUILT-UP
should be at least 13 pcf. A * 4 * 1l ROOFING
*
VCM = Vermiculite cementitious material consists of
expanded vermiculite with inorganic binders and water.
The density of the oven-dry material should be at least 14
pcf.
N.A. = Not applicable. Thickness of insulation (in.)
Base for fire-resistance rating of
slab
It is likely that the comparable R value for a 1 irr. thickness Insula- 1VS
layer of cellular polyurethane would be somewhat (in.) tionb 1 hr hr 2 hr 3 hr 4 hr
greater than that for a 1 in. layer of cellular polysty­
VA MB 3/4 VA VA 2 3/4 N.A.
rene, but test values are not available. Until more de­
2 MB 1A 1 va 2 1/4 2%
finitive data are obtained, it is suggested that 5 min.
3 MB 0 3/4 3/4 VA 1%
be used as the value for R for any layer of cellular plas­
4 MB- a 0 1/4 3/4 1 ’/4
tic 1 in. or greater.
VA G FB 5/4 13/4 2 N .A N.A.
It should be noted that the cellular plastics melt
2 G FB 1/4 7A 1V4 2Vs N.A.
and are consumed at about 400 to 600° F. Thus, addi­
3 G FB 0 ¥s 3/4 VA 21A
tional thickness or changes in composition probably
4 G FB 0 0 1/4 3/4 VA
have only a minor effect on the fire endurance of
a. Values shown are for siliceous aggregate concrete, and
sandwich panels. The danger of toxic fumes caused are conservative for other concretes.
by the burning cellular plastics is practically elimi­ b. MB = Mineral board insulation composed of spherical
nated when the plastics are completely encased cellular beads of expanded aggregate and fibers formed
into rigid flat rectangular units with an integral
within concrete sandwich panels 17].
waterproofing treatment.
Table 9.3.7 lists fire endurances of sandwich pan­ GFB = Glass fiber board fibrous glass roof insulation
els with either cellular plastic, glass fiber board, or in­ consisting of inorganic glass fibers formed into rigid
sulating concrete used as the insulating material. The boards using a binder. The board has a top surface faced
with glass fiber reinforced with asphalt and kraft.
fire resistance values were obtained by use of Eq.
N.A. = Not applicable.
9.3.2.

9 -3 6 PCI Design Handbook/Fifth Edition


Table &3.7 Fire endurance of precast eon- be protected against fire if the openings-constitute
cretesandwich walls-(calculated, only a-small percentage of the wall area and ifth e
based orv Eq. 9.3.2) spatial separation is greaterthan some minimum dis­
tance. In those cases, protection of joints would not
Outside and Fire berequired.
inside endurance
In other cases, openings must be protected, but
wythes insulation hrunin
most codes permita lesser degree of protection. For
VA in. Sit 1 in. CP 1:23 example, the Uniform Building Code requires that,
when openings are permitted and must be protected,
1 1/2 in. Carb 1 in. CP 1:23
the “openings shall be protected by a fire assembly
1y2in. SLW 1 in. CP 1:45
having a %-hour fire-protection rating.” Where no
2 in. Sil 1 in. CP 1:50
openings are permitted, the fire resistance required
2 in. Carb 1 in. CP 2:00 for the wall should be provided at the joints.
2 in, SLW 1 in. CP 2:32 Table 9.3.8 is based on results of fire tests of pan­
3 in. Sil 1 in. CP 3:07 els with butt joints [8]. The tabulated values apply to
11/2 in. Sil 3A in. GFB 1:39 one-stage butt joints and are conservative for two-
2 in. Sit 3A in. GFB 2:07 stage and ship-lap joints.
2 in. SLW 3A in. GFB 2:52 Joints between adjacent precast floor or roof ele­
VA in. Sil VA in. GFB 2:35 ments may be ignored in calculating the slab thick­
2 in. Sil 1V2 in. GFB 3:08 ness provided that a concrete topping at least VA in.
IV2 in. GFB thick is used. Where no concrete topping is used,
2 in. SLW 4:00
joints should be grouted to a depth of at least one-
11/2 in. Sil 1 in. IC 2:12
third the slab thickness at the joint, or the joints made
1A in. SLW 1 in. IC 2:39
fire-resistive in a manner acceptable to the authority
2 in. Carb 1 in. IC 2:56 having jurisdiction.
2 in. SLW 1 in. IC 3:33
11/2 in. Sil 11A in. IC 2:54
1/2 in. SLW V / 2 in. IC 3:24
9.3.7 Designing for Structural Integrity
2 in. Sil 2 in. IC 4:25
V /2 in. SLW 2 in. IC 4:19 It was noted above that many fire tests and related
Note: research studies have been directed toward an un­
Oarb = carbonate aggregate concrete derstanding of the structural behavior of prestressed
Sil = siliceous aggregate concrete concrete subjected to fire. The information gained
SLW = sand-lightweight concrete (115 pcf maximum)
CP = cellular plastic (polystyrene or polyurethane) from that work has led to the development of calcula­
IC = lightweight insulating concrete (35 pcf maximum) tion procedures which can be used in lieu of fire tests.
GFB = glass fiber board The purpose of this section is to present an introduc­
tion to these calculation procedures. Because the
method of support is the most important factor affect­
9.3.6.6 Treatment of Joints Between Wall
ing structural behavior of flexural elements during a
Panels
fire, the discussion that follows deals with three con­
Joints between wall panels should be detailed so ditions of support: simply supported members, con­
that passage of flame or hot gases is prevented, and tinuous slabs and beams, and members in which re­
transmission of heat does not exceed the limits speci­ straint to thermal expansion occurs. For additional
fied in ASTM E 119. Concrete wall panels expand examples -and more detailed information, refer to PCI
when heated, so the joints tend to close during fire MNL-124 [1].
exposure. Non-combustible materials that are flex­ The fire endurance of concrete walls as deter­
ible, such as ceramic fiber blankets, provide thermal, mined by fire tests is normally governed by the ASTM
flame, and smoke barriers, and, when used in con­ criteria for temperature rise of the unexposed surface
junction with caulking materials, they can provide the rather than by structural behavior during fire tests.
necessary weather-tightness while permitting normal This is probably due to the low level of stresses, even
volume change movements. Joints that do not move in concrete bearing walls, and the fact that reinforce­
can be filled with mortar. For a more detailed discus­ ment generally does not perform a primary structural
sion and additional information, refer to PCI MNL-124 function. In most cases, the amount of cover protec­
1
[ ]. tion for structural design exceeds that required for fire
Joints between wall panels are similar to open­ protection so there is, in effect, reserve structural fire
ings. Most building codes do not require openings to endurance within the concrete wall.

PC) Design Handbook/Fitth Edition 9 -3 7


Table 9.3.8 Protection-uf joints between wait panels utilizing ceramic fiber felt

Thickness of ceramic fiber felt (4n4 required for fire-


resistance ratings and joint widths8 shown

Panel equivalent Joint width = % in . Joint width = 1 in.


ttiicknessb
(in.) 1 hr 2 hr 3 hr 4 hr 1 hr 2 hr 3 hr 4 hr

4 1/4 ' N.A. N.A. N.A. % N.A. N.A. N.A.


5 0 % N.A. N.A. V6 2V& N.A. N.A.
6 0 0 1% N.A. V4 1 1/4 3V£ N.A.
7 0 0 0 1 1/4 % 2 33/4

N.A. = Not applicable


a. Interpolation may be used for joint width between % in. and 1 in. The tabulated values apply to one-stage butt joints and are
conservative for two-stage and ship-lap joints
b. Panel equivalent thicknesses are for carbonate concrete. For siliceous aggregate concrete change “4, 5, 6, and 7” to “4.3, 5.3, 6.5,
and 1ST For sand-lightweight concrete change “4, 5,6, and7” to “3.3, 4.1, 4.9, and 5.7.”

Figure 9.3.5 Moment diagrams for simply 9.3.7.1 Simply Supported Members
supported beam or slab
Assume that a simply supported prestressed con­
crete slab is exposed to fire from below, that the ends
of the slab are free to rotate, and that expansion can
occur without restriction. Also, assume that the rein­
forcement consists of straight uncoated strands lo­
cated near the bottom of the slab. With the underside
of the slab exposed to fire, the bottom will expand
more than the top causing the slab to deflect down­
ward; also, the strength of the steel and concrete
near the bottom will decrease as the temperature
rises. When the strength of the steel diminishes to
less than that required to support the slab, flexural
collapse will occur. In essence, the applied moment
remains practically constant during the fire exposure,
but the resisting moment capacity is reduced as the
steel weakens.
Figure 9.3.5 illustrates the behavior of a simply
supported slab exposed to fire from beneath, as de­
scribed above. Because strands are parallel to the
axis of the slab, the design moment strength is
constant throughout the length:

4>Mn = 4>Apsfps(d - a/2) (Eq. 9.3.3)

fps can be determined from Figure 4.12.3 or Eq. 18-3


<jf ACt 318-95 [9].
If the slab is uniformly loaded, the moment dia­
gram will be parabolic with a maximum value at mid­
span of:
M = ^ (Eq. 9.3.4)
O
where:
w = dead plus live load per unit of length, k/in.
t = span length, in.

9 -3 8 PCI Design Handbook/Fifth Edition


Figure 9.3.& Strength-temperature relationships for-various steels

120

CARBONATEv
> H—*»»_.
/ _1 V .
100 > < --------- -
0
z \
UJ
GC
J—
W SAND- LIGHTWEIC HT ^ \ V
UJ
80 \
>
w
tf>
HI
IT SILICEOU. x \ \
Q.
2 \
o 60 \
o X
-I X<
< \
z s
0 \
IT >
o 40
U-
o
I-
z
UJ
o
cr 20
UJ
0.
ORIGINAL STREFJGTH = rc
AVEFiAGE fc = 3!300psi
STRE.SSED TO 0 4ft DURINI3 HEATING
________ ________
70 200 400 600 800 1000 1200 1400
TEMPERATURE, °F

PCI Design Handbook/Fifth Edition 9 -3 9


Figure 9.3.8 Temperature within concrete slabs or panels during fire tests—normal wejght eoncrete

MEASUREMENTS ARE FROM EXPOSED SURFACE

1/2 1 1 Vfe 2 3 4
FIRE TEST TIME, hr

Figure 9.3.9 Temperatures within concrete Similarly, a is reduced, but the concrete strength at
slabs or panels during fire the top of the slab, fc , is generally not reduced signifi­
tests—sand-lightweight concrete cantly because of its lower temperature.
Flexural failure can be assumed to occur when
MEASUREMENTS ARE FROM EXPOSED SURFACE Mpe is reduced to M. ACI load factors and strength re­
duction factors, (j), are not applied because a safety
factor is included in the required ratings [1]. From
this expression, it can be seen that the fire endurance
depends on the applied loading and on the strength-
temperature characteristics of the steel.
In turn, the duration of the fire before the “critical”
steel temperature is reached depends on the protec­
tion afforded to the reinforcement.
To solve problems involving the above equations,
it is necessary to utilize data on the strength-tempera­
ture relationships for steel and concrete, and informa­
tion on temperature distributions within concrete
members during fire exposures. Figure 9.3.6 shows
strengths of certain steels at elevated temperatures,
and Figure 9.3.7 shows similar data for concrete.
Data on temperature distribution in concrete slabs
during fire tests are shown in Figures 9.3.8 and 9.3.9.
These figures can also be used for beams wider than
about 10 in. An “effective u,” u, is used, which is the
FIRE TEST TIME, hr
average of the distances between the centers of the
individual strands or bars and the nearest fire-ex­
As the material strengths diminish with elevated posed surface. The values for corner strands or bars
temperatures, the retained nominal strength be­ are reduced one-half to account for the exposure
comes: from two sides (see Example 9.3.4). The procedure
does not apply to bundled bars or strands. Data on
Mne = ApSfpSe ( d - a e/2) (Eq. 9.3.5) temperature distribution for stemmed members dur­
in which 9 signifies the effects of high temperatures. ing fire tests are shown in Figures 9.3.10 through
Note that Aps and dare not affected, butfps is reduced. 9.3.13.

9 -4 0 PCI Design Handbook/Fifth Edition


Figure 9.3.10 Temperatures on vertical centerline of stemmed units at 1 hr of exposure

Figure 9.3.11 Temperatures on vertical centerline of stemmed units at 2 hr of exposure

STEMMED UNITS 2hr

PCI Design Handbook/Fifth Edition


9 -4 1
Figure-9.3.12 Temperatures on vertical centerline of stemmed units at 3 h r ofexposure

Figure 9.3.13 Temperatures on vertical centerline of stemmed units at 4 hr of exposure

9 -4 2 PCI Design Handbook/Fifth Edition


Example 9.3.3 Calculation of Load Capacity Example 9.3.4 Calculation of Eire Endurance
of a Hollow-Core Slafr with of a Rectangular Beam
3-Hour FireEndurance

Given: Given:
An 8 in. deep hollow-core slab with a simply sup­ The 12RB24 shown in Figure 9.3.14.
ported unrestrained span of 25it. Span = 30 ft
h = 3 in. Dead load (including bm. wt.) = 110Q plf
u = 1.75 in. Live load = 1100 plf
Eight 'A in. 270 ksi strands Simple support, no restraint
Aps = 8(0.153) = 1,224 in2 Siliceous aggregate concrete, fc = 5000 psi
b = 4 8 in. Stress-relieved V2 in. dia. strand, fps = 270 ksi
d = 8 - 1.75 = 6.25 in.
wd = 60 psf
Figure 9.3.14 Section views of Example 9.3.4
Carbonate aggregate concrete
fc = 5000 psi
€ = 25 ft

Problem:
Determine the maximum safe superimposed load
that can be supported for a fire endurance of 3 hr.

Solution:
(a) Estimate strand temperature at 3 hr from Figure
9.3.8: At 3 hr, carbonate aggregate,
u = 1.75 in.
9S= 925° F

(b) Determine fpue from Figure 0.3.6. For cold-


drawn steel at 925°F

fpu6 = 0.33(fpu) = 89.1 ksi

(c) Determine Mne and w from Figure 4.2.2.


ADD 2
f ™ 0.28(1.224)(89.1)~ STRANDS

pse [ 0.8(48) (6.25) (5)

= 86.8 ksi

a _ _ 1-224(86.8)
* 0 .8 5 f;b 0.85(5)(48)
Mn0 = ApSfpS0 (d - 3g/2)

= 1.224(86.8)(6.25 - 0.52/2)/12

= 53.0 kip-ft
8M 8(53.0) (1000)
= 169 psf
be2 (4) (25)2

\n ( = w - w d = 169 - 60 = 109 psf

PCI Design Handbook/Fifth Edition 9 -4 3


Problem: From Figure 4.2;2r
Determine the necessary reinforcement for a 4-hr
(0.40) (1.53)(113.4)'
fire endurance rating. f ps6 113.4 1 -
(0.8) (T2)(20.5)(5)_
Solution: 105.4 ksi
Try S tra n d s
Aps= 8(0.153) = t . 224 in* 1.53(105.4)
^9 = 3.16-in.
ys = [5(2.5) + 3(4.5)]/8 = 3.25 in. 0.85(5)(12)

d = 24 - 3.25 = 20.75 in.


Mn0 = 1.53(105.4)(20.5 - 3.16/2)
□ = [5(2.5) + 1(4.5) + 2(2.5)(0.5)]/8 = 2.44 in.
= 3051 kip-in.
From Figure 9.3.8, siliceous aggregate:
at 4 hr, strand temp. = 920° F = 254 kip-ft > 248 kip-ft OK

Solution No. 2:
From Figure 9.3.6: Try adding 2 -# 7 bars at 4.5 in. from bottom:
fpu6 = 0.34(270) = 91.8 ksi As = 1.20 in*

From Rgure 4.2.2: d(bars) = 2 4 - 4 .5 = 19.5 in.


(0.4) (1.224) (91.8)
87.7 ksi u(bars) = 4.25 in.
(0.8) (12)(20.75)(5)

From Figure 9.3.8:


Apsfpse _ 1.224(87.7)
Bar temp, at 4 hr = 500°F
0.85fc b 0.85(5)(12)

= 2.10 in. From Figure 9.3.6:


fye = 0.83 fy = 49.8 ksi
Mne = Apsfpse (d - a0/2)
= 1.224(87.7) (20.75 - 2.10/2) 1.224(87.7) + 1.20(49.8)
3.28 in.
= 2115 kip-in. = 176 kip-ft 0.85(5)(12)

Service load moment: Mne (strand) = 1.224(87.7)(20.75 - 3.28/2)


w = 2.20 kip/ft = 2051 kip-in. = 171 kip-ft

M = w€2/8 = 2.20(30)2/8 Mne (bars) = 1.20(49.8)09.5 - 3.28/2)


= 248 kip-ft > 176 kip-ft = 1067 kip-in. = 89 kip-ft
Therefore, beam will not satisfy criteria for a 4-hr 171 + 89 = 260 kip-ft > 248 kip-ft OK
fire endurance.

Solution No. 1: 9.3.7.2 Continuous Members


Try adding 2 additional strands at 4Vfc in. from bot­
Continuous members undergo changes in
tom:
stresses when subjected to fire. These stresses result
Aps= 10(0.153) = 1.53 in? from temperature gradients within the structural
ys = [5(2.5) + 5(4.5)]/10 = 3.5 in. members, or changes in strength of the materials at
d = 24 - 3.5 = 20.5 in. high temperatures, or both.
Figure 9.3.15 shows atwo-span continuous beam
u = [5(2.5)+1(4.5)+2(4.25) + 2(2.5) (0.5)]/10
whose underside is exposed to fire. The bottom of the
= 2.80 in. beam becomes hotter than the top and tends to ex­
pand more than the top. This differential temperature
From Figure 9.3.8: effect causes the ends of the beam to tend to lift from
Strand temp. = 840° F their support thereby increasing the reaction at the in­
terior support. This action results in a redistribution of
From Figure 9.3.6: moments, i.e., the negative moment at the interior
support increases while the positive moments de­
fpu6= 0.42(270) = 113.4 ksi
crease.

9 -4 4 PCI Design Handbook/Fifth Edition


Figure 9.3.15 Moment diagram for a two-span Figure 9.3.16 Uniformly loaded member con­
continuous beam tinuous (or fixedy at anasupport
t _______ J

iiu im tiim it.im


■ X HRE X FiRE X

Mn

___ ...................
J J l* ' XI^

\
/ \\
i
X2\
* r
w In most cases, redistribution of moments occur
early during the course of a fire and the negative mo­
M+ / . xp , t X1 -
n8 ment reinforcement can be expected to yield before
the negative moment capacity has been reduced by
AT 2 HR
the effects of fire. In such cases, the length of Xq is in­
creased, i.e., the inflection point moves toward the
During a fire, the negative moment reinforcement
simple support. If the inflection point moves beyond
(Figure 9.3.15) remains cooler than the positive mo­
the point where the bar stress cannot be developed in
ment reinforcement because it is better protected
the negative moment reinforcement, sudden failure
from the fire. In addition, the redistribution that occurs
may result.
is sufficient to cause yielding of the negative moment
Figure 9.3.17 shows a symmetrical beam or slab
reinforcement. Thus, a relatively large increase in
in which the end moments are equal.
negative moment can be accommodated throughout
the test. The resulting decrease in positive moment w€* M+ (Eq. 9.3.9)
M^e ~8 Mn®
means that the positive moment reinforcement can
be heated to a higher temperature before failure will
wx2
occur. Therefore, the fire endurance of a continuous = Mn+e (Eq. 9.3.10)
8
concrete beam is generally significantly longer than
that of a simply supported beam having the same
x2
II

cover and the same applied loads. (Eq. 9.3.11)


It is possible to design the reinforcement in a con­
tinuous beam or slab for a particular fire endurance
II

*0
X

period. From Figure 9.3.15 the beam can be ex­


pected to collapse when the positive moment capac­
ro | ^

ro i-F

(Eq. 9.3.12)
II

ity, M Se is reduced to the value of the maximum redis­


tributed positive moment at a distance x-, from the
To determine the maximum value of Xo.the value of
outer support.
w should be the minimum service load anticipated,
Figure 9.3.16 shows a uniformly loaded beam or
and (w€2/ 8 — ) should be substituted for in
slab continuous (or fixed) at one support and simply
Eq. 9.3.12.
supported at the other. Also shown is the redistrib­
For any given fire endurance period, the value of
uted applied moment diagram at failure.
It can be shown that at the point of positive mo­ M can be calculated by the procedures given in
ment, x1( Sect. 9.3.7. Then the value of can be calculated
by the use of Eqs. 9.3.8 or 9.3.9 and the necessary
y - t Mne lengths of the negative moment reinforcement can be
1 2 w€ (Eq. 9.3.6)
determined from Eqs. 9.3.7 or 9.3.12. Use of these
equations is illustrated in Example 9.3.5.
at x = x2, Mx = 0 and x2 = 2x1

PCI Design Handbook/Fifth Edition 9 -4 5


RgureJL3.T7 Uniformly loaded member con­
tinuous at supports 16(0.080) (60)
0.052
0)56 “ 48 (10,25) (3)

Ku = 1 3 6 /0 .9 = 1 5 1

Mnfr = K' bd2/12,t)00

= 151 (48) (10.25)2/1 2,000


= 63.5 kip-ft/unit
= 15.9 kip-ft/ft
The amount of moment redistribution that can oc­ For simply supported members:
cur is dependent on the amountof negative moment
reinforcement. Tests have clearly demonstrated that M = 0.325(22)78 = 19.7 kip-ft/ft
jn most cases the negative moment reinforcement
witl yield, so the negative moment capacity is reached Req'd = 19.7 - 15.9 = 3.8kip-ft/ft
early during a fire test, regardless of the appliedload-
Assum ed - ae/2 = 10.25in., andfy = 60ksi
ing. The designer must exercise care to ensure that a
secondary type of failure will not occur. To avoid a 3.8(12)
AJ 0.074 in.2/ft
compression failure in the negative moment region, 60(10.25)
the amount of negative moment reinforcement
should be small enough so that coe = Asfye/ b edefJ« is Use 20% of required As throughout span:
less than 0.30, before and after reductions in 7 b, d
Try 6x6-W1.4 x W1.4 cont. plus
and fc are taken into account. Furthermore, the neg­
6x6-W2.9xW2.9 over supports
ative moment bars or welded wire reinforcement
must be long enough to accommodate the complete As = 0.029 + 0.058 = 0.087 in2/ft
redistributed moment and change in the inflection
points. It should be noted that the worst condition oc­ Neglect concrete above 1400°F in negative mo­
curs when the applied loading is smallest, such as ment region, i.e., from Figure 9.3.8, neglect bottom5/s
the dead load plus partial or no live load. It is recom­ in. Also, concrete within compressive zone will be
mended that at least 20% of the maximum negative about 1350 to 1400°F, so use f^ = 0.81fc (see Fig­
moment reinforcement extend throughout the span. ure 9.3.7) = 4.05 ksi.
Check M ^ , assuming that the temperature of the
Example 9.3.5 Ftre Endurance for Hollow-
negative steel does not rise above 200° F. If greater
Core Slab with Topping than 200°F, steel strength should be reduced ac­
Problem:
cording to Figure 9.3.6.
Design a floor using hollow-core slabs and top­
ping for 22 ft span for 4 hr fire endurance. Service 0.087(60)
a« = = 0.126 in.
loads = 175 psf dead (including structure) and 150 0.85 (4.05) (12)
psf live. Use 4 ft wide, 10 in. deep slabs with 2 in. top­
M n0 = 0.087(60) (10.37 - 0.063)/12
ping, carbonate aggregate concrete. Continuity can
be achieved at both ends. Use fc (precast) = 5000 = 4.48 kip/ft
psi, fpu = 250 ksi, and fc (topping) = 3000 psi, sixteen
With dead load + Vi live load, w = 0.25 ksf, M =
% in., 250 ksi strands at u = 1.75 in. Provide negative
moment reinforcement needed for fire resistance. 15.12 kip-ft/ft, and M* = 4.71 kip-ft/ft (calculated for
room temperature)
Solution:
Aps = 16(0.080) = 1.28 in2 ML = 15.12 4.71 = 10.41 kip-ft/ft
u =1.75 in. From Eq. 9.3.12
d = 1 2 - 1 .7 5 = 10.25 in. 1 /8(10.41)
22
max x0 = ^ 1.87 ft
From Figure 9.3.8, 0S = 1010°F 2 2y 0.25

Use 6 x 6 - W1.4 x W1.4 continuous throughout


From Figure 9.3.6, fpue = 0.24fpU = 60 ksi
plus 6 x 6 - W2.9 x W2.9 for a distance of 3 ft from the
Use Fig. 4.12.2. Note that values for K'u in Fig. 4.12.2 support Welded wire reinforcement must extend into
include ()> = 0.9. Since in the design for fire, <f>= 1.0, walls which must be designed for the moment in­
the value of K'u must be divided by 0.9. duced at the top.

9 -4 6 PCI Design Handbook/Fifth Edition


g.3.7.3 Members Restrained Against Thermal whkbJhaLcond ition was simulated, failure occurred
Expansion onlyHn one beam [5] , In that test, thaahear-reinforce-
ment was inadequate, even for-service load condi­
If a fire occursbeneath an interior portion of a large
tions withoutrrtire, as- judged Joy the shear require­
reinforced concrete slab, the heated portion will tend
ments o f ACI’ 318-9b.Thusr it appears from availabte-
to expand and push against the.surrounding part o f
test data that members which are designed forebear
the slab. In turn, the unhealed part of the slab exerts
strength in-accordance with ACI 318-95 will perform
compressive forces on the heated*portion. The com­
satisfactorily in firesituations, i.e., failure will not oc­
pressive force, o rihrusl, acts near th e bottom of the
cur prematurely due to a shear failure.
slab wherr the fire test occurs but, as the fire prog­
resses, the line of action of the thrust rises as the
mechanical properties of the heated concrete 9.3.8 Protection of Connections
changes. This thrust is generally great enough to in­
crease the fire endurance significantly. Many types of connections in precast concrete
The effects of restraint to thermal expansion can construction are not vulnerable to the effects of fire,
be characterized as shown in Figure 9.3.18. The ther­ and consequently, require no special treatment. For
mal thrust acts in a manner similar to an external pre­ example, gravity-type connections, such as thebear-
stressing force, which, in effect, increases the posi­ ing between precast concrete panels and concrete
tive moment capacity. footings o r beams which support them, do not gener­
The increase in bending moment capacity is simi­ ally require special fire protection.
lar to the effect of added reinforcement located along If the panels rest on elastomeric pads or other
the line of action of the thrust. It can be assumed that combustible materials, protection of the pads is not
the added reinforcement has a yield strength (force) generally needed because deterioration of the pads
equal to the thrust. By this approach, it is possible to will not cause collapse.
determine the magnitude and location of the required Connections that can be weakened by fire and
thrust to provide a given fire endurance. thereby jeopardize the structure’s load carrying ca­
The above explanation is greatly simplified be­ pacity should be protected to the same degree as
cause in reality restraint is quite complex, and can be that required for the supported member. For exam­
likened to the behavior of a flexural member sub­ ple, an exposed steel bracket supporting a panel or
jected to an axial force. Interaction diagrams similar spandrel beam will be weakened by fire and might fail
to those for columns can be constructed for a given causing the panel or beam to collapse. Such a brack­
cross-section at a particular stage of afire, e.g., 2 hr of et should be protected.
a standard fire exposure [4]. The guidelines in ASTM The amount of protection depends on (a) the
E 119 given for determining conditions of restraint are stress-strength ratio in the steel at the time of the fire
useful for preliminary design purposes. Most interior and (b) the intensity and duration of the fire. The
and many exterior bays of multi-bay floors or roofs thickness of protection materials required is greater
can be considered to be restrained and the magni­ as the stress level and fire severity increase.
tude and location of the thrust are generally of aca­
demic interest only. In such cases, the fire endurance Figure 9.3.18 Longitudinally restrained beam
is governed by heat transmission rather than by during fire exposure
structural considerations.

9.3.7.4 Shear Resistance


Many fire tests have been conducted on simply
supported reinforced or prestressed concrete ele­
ments as well as on elements in which restraint to
thermal expansion occurred. Shear failures did not
occur in any of those tests.
It should be noted that when beams which are
continuous over one support (e.g., such as that
shown in Figure 9.3.15) are exposed to fire, both the
moment and the shear at the interior support in­
crease. Such a redistribution of moment and shear
results in a severe stress condition. However, of the
several fire tests of reinforced concrete beams in

PCI Design Handbook/Fifth Edition 9 -4 7


Figure 9.3.19 shows the thickness of various com­ thickcolumn cover o f normal-weight concrete fora 8x
monly used fire protection materials required tor fire 8 x '/2 in. steel tube column will be about 3 hr 20 min
-endurancesup to A hr. The values shown-are based- (the weight- o fih e section is 47.35Ub per ft).
on a critical steei temperature of 1009° F, i.e., a stress- Precast concrete column covers (Figure 9.3.21)
strength ratio (fs/fy)o f-about 65%. Values in Figure are made invariousahapes such as (A) four flat pan­
9.37t9(B) are applicable to-concrete or dry-pack mor­ els with butt or mitered joints that fit together to en­
ta r encasement of structural steel shapes used as close thesteel column,_(B) four L-shaped units, (C)
brackets or lintels. twoL-shaped units, (D) two U-shaped units, and (E)
and (F) U-shaped units and flat closure panels. Type
(A) would probably be most vulnerable to bowing
9.3.9 Precast Concrete Column Covers during fire exposure while Type (F) would probably
Steel columns are often clad with precast concrete be the least vulnerable. There are, of course, many
panels or covers for architectural reasons. Such cov­ combinations to accommodate isolated columns,
ers also provide fire protection for the columns. corner columns, and column walls.
Figure 9.3.20 shows the relationship between the To be fully effective the column covers must re­
thickness of concrete column covers and fire endur­ main in place without severe distortion. Many types of
ance for various steet column sections. The fire en­ connections are used to hold the column covers in
durances shown are based on an empirical relation­ place. Someconnections consist of bolted or welded
ship developed by Lie and Harmathy [10]. clip angles attached to the tops and bottoms of the
The above authors aiso found that the air space covers. Others consist of steel plates embedded in
between the steel core and the column covers has the covers that are welded to angles, plates, or other
only a minor effect on the fire endurance. An air space shapes which are, in turn, welded or bolted to the
will probably increase the fire endurance but only by steel column. In any case, the connections are used
an insignificant amount. primarily to position the column covers and as such
Most precast concrete column covers are 3 in. or are not highly stressed. As a result, temperature limits
more in thickness, but some are as thin as 2V& in. need not be applied to the steel in most column cover
From Figure 9.3.20, it can be seen that precast con­ connections.
crete column covers can qualify the column for fire If restrained, either partially or fully, concrete pan­
endurances of at least 21/2 hr, and usually more than 3 els tend to deflect or bow when exposed to fire. For
hr. For steel column sections other than those shown, example, for a steel column that is clad with four flat
including shapes other than wide flange beams, in­ panels attached top and bottom, the column covers
terpolation between the curves on the basis of weight will tend to bulge at midheight thus tending to open
per foot will generally give reasonable results. gaps along the sides. The gap size decreases as the
For example, the fire endurance afforded by a 3 in. panel thickness increases.

Figure 9.3.19 Thickness of protection materials applied to connections of structural steel shapes

a!
i
Ui
o
2
<
£E
D
Q
2
HI
LU
tr
Li.

0 1 2 3 4
THICKNESS, PROTECTION MATERIAL, IN. THICKNESS, PROTECTION MATERIAL, IN.
(A) (B)

IM = INTUMESCENT MASTIC SMF = SPRAYED MINERAL FIBER VCM = VERMICUUTE CEMENTITIOUS MATERIAL

9 -4 8 PCI Design Handbook/Fifth Edition


Figure 9.3.20 Ftre e a d u ra n c e o fste e l colum ns afforded protection bytroncrete column covers

t, THICKNESS OF COLUMN COVER, IN. t, THICKNESS OF COLUMN COVER, IN.

With L, C, or U-shaped panels, the gap size is fur­ in which acceptance of code requirements is
ther reduced. The gap size can be further minimized achieved is explained in the preceding pages. The
by connections at midheight. In some cases, ship-lap designer, representing the owner, has no option in
joints can be used to minimize the effects of joint the code regulations, but does have a number of op­
openings. tions in the materials and assemblies that meet these
Joints shoutd be sealed in such a way to prevent regulations, such as those included in this Hand­
passage of flame to the steel column. A non-combus­ book.
tible material such as sand-cement mortar or ceramic
Economic benefits associated with increased fire
fiber blanket can be used to seal the joint.
resistance should be considered by the designer/
Precast concrete column covers should be
owner team at the time decisions are made on the
installed in such a manner that, if they are exposed to
structural system. Proper consideration of fire resis­
fire, they will not be restrained vertically. As the covers
tive construction through a life-cycle cost analysis will
are heated they tend to expand. Connections should
provide the owner economic benefits over other
accommodate such expansion without subjecting
types of construction in many areas, e.g., lower insur­
the cover to additional loads.
ance costs, larger allowable gross area under certain
Fire resistive compressible materials, such as min­
types of building construction, fewer stairwells and
eral fiber safing, can be used to seal the tops or bases
exits, increased value for loan purposes, longer mort­
of the column covers, thus permitting the column cov­
gage terms, and better resale value. To ensure an
ers to expand.
owner of the best return on his investment, a life-cycle
cost analysis using fire resistive construction should
9.3.10 Code and Economic Considerations be prepared.

An important aspect of dealing with fire resistance Beyond the theoretical considerations is the histo­
is to understand what the benefits are to the owner of ry of excellent performance of prestressed concrete
a building in the proper selection of materials incor­ in actual fires. Structural integrity has been main­
porated in his structure. These benefits fall into two tained, fires are contained in the area of origin, and, in
areas: codes and economics. many instances, repairs consist of “cosmetic” treat­
Building codes are laws that must be satisfied re­ ment only, leading to early re-occupancy of the struc­
gardless of any other considerations and the manner ture.

PCI Design Handbook/Fifth Edition 9-4 9


Figure 9.3.21 Types of precast concrete cat* 4. Abrams, M S ,, Gustaferro, A.H., and Salse, E.
umncovers A.B., “Fire Tests-of. Concrete Joist Floors and
Roofs, ” flD Bulletin 006B, PortlandCement As­
sociation, Skokie, IL, 1971.

5. “Fire Endurance of Continuous Reinforced


Concrete Beams,” RD Bulletin 072B, Portland
Cement Association, Skokie, IL.

6. Abrams, M.S., and Gustaferro, A.H., “Fire En­


durance of Two-Course Floors and Roofs,”
Journal of the American Concrete Institute, V.
66, No. 2, February 1969.

7. Lie, T.T., “Contribution of Insulation in Cavity


Walls to Propagation of Fire,” Fire Study No. 29,
Division of Building Research, National Re­
search Councif of Canada, Ottawa, Ontario,
Canada.

8. Gustaferro, A.H., and Abrams, M.S., “ Fire


Tests of Joints Between Precast Concrete Wall
9.3.11 References Panels: Effect of Various JointTreatments," PCI
Journal, V. 20, No. 5, September-October
1. “Design for Fire Resistance of Precast Pre­ 1975.
stressed Concrete,” Second Edition,
MNL-124-89, Precast/Prestressed Concrete In­ 9. “Building Code Requirements for Reinforced
stitute, Chicago, IL, 1989. Concrete,” ACI 318-95, and “Commentary,”
ACI 318R-95, American Concrete Institute,
2. “Reinforced Concrete Fire Resistance,” Con­ Farmington Hills, Ml, 1995.
crete Reinforcing Steel Institute, Schaumburg,
IL, 1980. 10. Lie, T.T., and Harmathy, T.Z., “Fire Endurance
of Concrete-Protected Steel Columns,” Journal
3. Shirley, Scott T., Burg, Ronald G. and Fiorato, of the American Concrete Institute, V. 71, No. 1,
Anthony E., “Fire Endurance of High-Strength January 1974.
Concrete Slabs," ACI Materials Journal, V. 85,
No. 2, March-April 1988.

9 -5 0 PCI Design Handbook/Fifth Edition


9.4 SANDWICH PANELS

9.4.1 General 2. Composite forfirltJife cycte oLpanel: The two


wythes act as a Mfy-composite-urrif for the full
Sandwich panels are composed of two concrete
life c f the structure (Tigure 9A-2/B)-In order to-
wythes separated by a layerof insulation. Cne of the
provide for composite behavior, positive mea­
concrete wythes may be a standard-shape; as shown
sures must be taken to effect shear transferbe-
in Figure 9.4.1, or any architectural concrete section
tween the wythes in the direction of panel span.
produced for a single project. In glace, sandwich
This may be accomplished by rigid ties, longi­
panels provide the dual function of transferring load
tudinal welded-wire trusses, or regions of solid
and insulating the structure, and can provide the inte-
concrete which join both wythes.
riorand exterior finished wall surfaces. They may be
used only for cladding, or they may act as beams, 3. Composite during handling, but non-compos­
bearing walls or shear walls. ite during service life: Composite action results
largely because of early bond between insula­
9.4.2 Structural D esign tion and adjacent wythes, in combination with
flexiblerties. The bond is considered unreliable
The structural design of sandwich panels is the
for the long term, thus the panel is considered
same as design of other wall panels once the section
as non-composite for service life loads. Wind
properties of the panel have been determined. Three
loads are distributed to each wythe in propor­
different assumptions may be used for the properties,
tion to wythe stiffness. For effects of slender­
depending on the construction:
ness, the sum of the individual moments of in­
1. Non-composite for full life cycle of panel: The ertia may be used.
two concrete layers act independently (Figure
For some machine-produced sandwich panels,
9.4.2(A). The wythes are connected by ties
tests and experience have demonstrated that a de­
and/or hangers which are flexible enough that
gree of composite action can be anticipated for the
they offer insignificant resistance to shrinkage
full life cycle. Manufacturer’s recommendations for
and temperature movement. Positive steps
these panels should be followed
may be taken to ensure that one wythe does
The choice of panel type must consider the follow­
not bond to the insulation. Typical techniques
ing:
are by placing a sheet of polyethylene or rein­
A composite panel will have a stiffness significant­
forced paper over the insulation before the final
ly greater than a non-composite panel or partially
concrete wythe is placed, by applying a retard­
composite panel of the same thickness. Thus, a com­
er or form release agent to one side of the in­
posite panel can span greater heights. However, be­
sulation, or by placing insulation in two layers
cause there will be a significantly greater temperature
(Figure 9.4.10). One wythe is usually assumed
gradient across the thickness of a composite panel,
to be “structural” and aH loads are carried by
this panel type can be expected to bow more.
that wythe, both during handling and in ser­
Panel size is limited only by stresses due to han­
vice, although, when designing for wind loads
dling and service loads, and slenderness in load
and slenderness effects, the panel may in
bearing panels, modified by the experience of the
some cases be designed as in (3) below.
producer. Wythes should be no thinner than 2 in. or 3
Figure 9.4.1 Typical precast concrete load times the maximum aggregate size. Panels with% in.
bearing insulated wall panels aggregate and 2 in. thick wythes have been success­
fully used.
Lifting points should be chosen to limit stresses
below the modulus of rupture during stripping and
handling so that cracks do not occur. Prestressing in
the long direction is particularly effective as a method
of providing for virtually crack-free panels; cracking
due to restrained shrinkage in the short direction of
the panel usually need not be considered, provided
the dimension in that direction does not exceed
about 12 ft. Prestressing should be concentric within
each wythe which is stressed. The designer may con­
sider prestressing the non-structural exterior wythe to
the same or higher prestress level as the structural
wythe, In order to counteract panel bowing.

PCI Design Handbook/Fifth Edition 9 -5 1


Figure 9.4.2 Nun-composite and composite Exterior (non-str-uctural) wythe:
panels le = 12(2.5)3/12 = 15.6 in4/ftr
Se = 15.6/T .25 = 12.5 in3/ftr

Distribution:
li + le = 64 + 15.6 = 79.6 in*

Lateral load resisted by:


Interior: 64(100}/79.6 = 80%
Exterior: 15.6(100)/79.6 = 20%-

(b) The composite properties are as follows:

A y Ay y Ay2 I
Interior 48 2.00 96.0 1.63 127.5 64.0
Exterior 30 6.25 187.5 2.62 205.9 15.6

78 283.5 333.4 79.6

yb = 283.5/78 = 3.63 in.


Ic = 333.4 + 79.6 = 413.0 irri/ft width

9.4.3 Connections

ALTERNATE ARRANGEMENT 9.4.3.1 Panel Connections


AT TOP. COMPOSITE
ACTION ACHIEVED BY TIES. Analysis and design of panel connections to resist
normal and transverse wind and seismic shears as
(B) COMPOSITE PANEL well as gravity and alignment loads are described in
Chapters 3 and 6. Consideration must also be given
to anticipated bowing, particularly of composite pan­
Ref. 4 includes design examples for composite els.
and non-composite sandwich panels used as clad­ The effects of differential bowing between adja­
ding, bearing walls and shear walls. A design exam­ cent panels of similar span may be minimized by
ple for a semi-composite panel (design assumption carefully aligning the panel during erection, and pro­
3, above) is also included. viding caulking on both the inside and outside of pan­
el joints. Where adjacent panels are of significantly
Example 9.4.1 Section Properties of Sand­
different stiffness, connections should be provided
wich Panels
across the adjacent joint, to maintain alignment; such
Given: connections should be spaced not more than 15 ft on
The sandwich panel shown in Figure 9.4.3. centers along the length of the common joint. The
connection should provide for anticipated movement
Problem: to prevent build-up of volumetric restraint forces.
Calculate the moment of inertia and section modu­
lus tf the section is (a) non-composite and (b) com­ Figure 9.4.3 Illustration for Example 9.4.1
posite. Also find the load distribution for the non-com­
posite case. Since the insulation is rigid, the lateral EXTERIOR
load applied to the non-composite panel will be re­
I
' ^ ‘ * / t' »
9 » * 6 * *b
„ e , ‘ *
sisted by each wythe in proportion to its stiffness. i 5 *

Solution: 11111 1111111 11111111111111 11111


a ^
(a) The non-composite properties are as follows:
■ fc. * > b. y

Interior (structural) wythe: 9 ■ 9


5 *
L
* k
»
»

fc * v * t
I, = bd 3/12 = 12(4)3/12 = 64 in4/ft width
INTERIOR
Si = |/c = 64/2 = 32 in3/ff width

9 -5 2 PCI Design Handbook/Fifth Edition


When-bowing does occur, itis generally outward. Forribbed panels, the shear connector is placed
Chapter 3; Sect. 3.3,2, discusses the effects on con­ In the rib io assure proper embedment-depth, in non-
nections. Recommendations stated there shoutctbe composite panels, it is preferable-to have only one an­
foil owed in order to preventthe opening of joints and choring center. In a panel with two ribs, the shear
the resultant possibility of caulk failure. Special-atten­ connectorcan be positioned in either one of-the ribs,
tion should also be paid to_panels which are hung and a flat anchor with the same vertical shear capac­
from adjacent panels. If a hung panel isaupported by ity is used in the other nib (Figure 9.4.6). Since the flat
full height panels which are supported on a founda­ anehorhas little or no horizontal shear capacity, re­
tion, the assembly of panels can move as a unit, with­ straint of the exterior wythe is minimized. In a multi-
out distress to the panel or joint sealant. However, if ribbed panel, the shear connector is placed as near
the hung panel is also rigidly attached to the struc­ the center of rigidity as is possible, and flat anchors
ture, this restraint may result in differential bowing of are used in the other ribs.
the hung panel with respectfo the adjacent long pan­ To complete the connection, metal tension/com-
els. A detail to permit the hung panel to move with the pression ties passing through the insulation are
adjacent panels should be provided. Attention spaced at regular intervals to prevent the wythes from
should be paid to the position of the connection near separating. Functions of wythe connectors are
the bottom of a panel supported on a foundation, in shown in Figure 9.4.7. Typical tie details are shown in
order to minimize the possibility of spalling due to Figure 9.4.8, and arrangements and spacing in Fig­
thermal bowing, fig u re 9.4.4. ure 9.4.9. Wire tie connectors are usually 12 to 14
gauge, and preferably of stainless steel. Galvanized
metal or plastic ties may also be acceptable. Ties of
94.3.2 Wythe Connectors
welded wire reinforcement and reinforcing bars are
When one wythe is non-structural, its weight must sometimes used. Shaped, crimped, or bent ties
be transferred to the structural wythe. This may be ac­ should be cold bent.
complished by using shear connectors or solid con­ Tension/compression ties should be flexible
crete ribs at the top or bottom of the panel. If the panel enough so as not to resist temperature and shrinkage
is non-composite, the shear connector should be a parallel to the panel surface, yet strong enough to re­
single element or a closely spaced pair of elements sist a lifetime of stress reversals caused by tempera­
placed as near the center of rigidity of the panel as ture strains. Ties should be arranged, or coated, so
possible. This permits the non-structural wythe to that galvanic reaction between the tie and reinforce­
contract and expand with the least restraint. ment will not occur.
Shear anchors may be bent reinforcing bars, The spacing of ties should be approximately 2 ft
sleeve anchors, expanded metal, fiber connectors, or on centers, but not more than 4 ft, or at least 2 ties per
welded wire trusses, as illustrated in Figure 9.4.5. 10 ft2 of panel area.

Figure 9.4.4 Restraint at foundation Figure 9.4.5 Typical shear connectors

PCI Design Handbook/Rfth Edition 9 -5 3


Figure 9.4.6 Anchorage for ribbed panels- Figure 9:4.8 Tension/compression ties
j?ROv©e

TIE CONNECT­
ORS AT 24" O.C.
FLAT SLEEVE
ANCHOR

Figure 9.4.7 Functional behavior of connectors

B ii H
H EE H I V
jfi? E E 9 V

| 1H
FIBER TIE
r - |“
T
(A) TIES, ACTING IN TENSION, TRANSFER X X
WEIGHT OF LOWER WYTHE

IT
X

i l
X
[-

r r
i
I I

IF THE FIRST CONCRETE


LAYER IS ALLOWED TO
HARDEN BEFORE THE
m SECOND LAYER IS
rTTTTTr PLACED, THIS TIE
b-1 b-2 SHOULD BE USED AND
(B) TIES, ACTING IN TENSION OR COM­ (CJTIES, ACTING IN FIXED TO THE RE­
PRESSION, TRANSFER WEIGHT OF TENSION OR INFORCEMENT OF THE
EXTERIOR WYTHE (b -1 ) COMPRESSION, BOTTOM LAYER BEFORE
TRANSFER WIND
RIGID CONNECTOR TRANSFERS ANY CONCRETE IS CAST.
WEIGHT OF EXTERIOR WYTHE BY FORCES
SHEAR AND FLEXURE (b -2 ) REINFORCEMENT OF
THE BOTTOM LAYER

iJ tiu |W I ijTNLtif f li i|rtU'jj+n ijlH ^ F

Openings in the insulation around connectors


(D)TIES, SIMILAR TO (B) ABOVE, TRANSFER LATERAL
FORCES APPLIED TO ONE WYTHE should be packed with insulation to avoid forming
thermal bridges between wythes.
9.4.4 insulation Using the maximum standard size of insulation
Physical properties of insulation materials are sheets, consistent with the panel shape, is recom­
listed in Table 9.4.1. Thermal properties are dis­ mended. This will minimize joints and the resulting
cussed in Sect. 9.1. The insulation should have low thermal links. Lapped abutting ends ofsingle layer in­
absorption or a water-repellent coating to minimize sulation, or staggered joints with double layer insula­
absorption of water from fresh concrete. tion, will effectively remove thermal links at joints (Fig­
The thickness of insulation is determined as de­ ure 9.4.10). Insulation may expand when subject to
scribed in Sect. 9.1. A minimum of 1 in. is recom­ curing temperatures greater than 150°F; proper pre­
mended. While there is no upper limit on the thick­ cautions should be taken, such as leaving room for
ness, the deflection characteristics of the wythe the insulation to expand where ribs and insulation are
connectors should be considered. in contact.

9 -5 4 PCI Design Handbook/FUth Edition


Figure 9.4.9 Arrangement of connectors between wythes

I VERY FLEX1BLEJN
VERTICAL-DIRECTION
.VERY FLEXIBLE IN

p i ,;
I HORIZONTAL DIRECTION

(B)
+ + + - DEVICES SPACED ALONG THE X -X AXIS
TRANSFER WEIGHT OF NON-STRUCTURAL
+ £ WYTHE TO THE STRUCTURAL WYTHE. SIM­
1I 1 ILAR DEVICES ALONG THE Y - Y AXIS TRANS­

i ___ i___ i__


^
SECTION ELEVATION Y 2' FER RACKING SHEAR FROM NON-STRUC­
+ J TURAL WYTHE TO STRUCTURAL WYTHE.
W MAX.

+
ONE DEVICE TRANSFERS WEIGHT OF NON-STRUCTURAL + + + - TIES SPACED IN THE FIELD OF THE PANEL
WYTHE TO STRUCTURAL WYTHE, AS WELL AS ANY RACKING TRANSFER DIRECT WIND LOADS AND STRIP­
SHEAR. ELEVATION ' PING FORCES FROM THE NON-STRUCTURAL
(VERTICAL) WYTHE TO THE STRUCTURAL WYTHE.
TIES SPACED IN THE FIELD OF THE PANEL TRANSFER DIRECT l l
VWND LOADS AND STRIPPING FORCES FROM THE NON- SECTION (HORIZONTAL)
STRUCTURAL WYTHE TO THE STRUCTURAL WYTHE.

Figure 9.4.19 Preferred installation of insulation sheets

t e

STAGGERED INSULATION, TWO SHEETS LAPPED INSULATION, ONE SHEET (NOT PRACTICAL FOR
IRREGULAR SHAPED PANELS AND AROUND OPENINGS)

Table 9.4.1 Properties of insulation

Polystyrene Polyisocyanurate Phenolic Cellular


Glass
Expanded Extruded Unfaced Faced

Density (pcf) 0.79.9 1.1-1.4 1.8 1.3-1.6 1.8-2.2 3.0 2.09.0 2.09.0 2.09.0 6.79.2

Water absorption
< 4.0 < 3.0 < 2.0 < 0.3 <3.0 1.0-2.0 < 3.0 < 0.5
(% volume)

Comp, strength 5-10 13-15 25 15-25 40-60 100 16-50 16 10-16 65


(psi)

Tensile strength 18-25 25 50 105 45-140 500 60 50


(psi)
Linear coeff. of 25-40 25-40 30-60 10-20 1.6-4.6
expansion
(in/in/°F) x 1CT6

Shear strength 20-35 —


35 50 20-100 12 50
(psi)
Flexural strength 10-25 30-40 50 40-50 60-75 100 50-210 40-50 25 60
(psi)

Thermal 0.32- 0.26- 0.23 0.20 0,18 0.10-0.15 0.16- 0.35


conductivity 0.28 0.25 0.23
(Btu-in/hr/ft 2/°F) at
75°F

Max. use temp. 165°F 165°F 250°F 300°F 900°F

PCI Design Handbook/Fifth Edition 9 -5 5


9.4.5 Thermal Bowing 9.4.7 References

t. McCall, W. Calvin, “Thermal Properties of


Thermal bowing of exterior composite panels SandwictTPanels,” Concrete International; De­
must be considered. Calculation o f bow and the sign & Construction, V. 7, No. 1, January 1985.
forces required to restrain it are discussed in Sect.
3.3.2. Differential movement between panels is sel­ 2. Einea, Amin, Salmon, David C., Fogarasi, Gyu-
dom a problem, except at corners or where abrupt la J., Culp, Todd D., and Tadros, Maher K.,
changes inthe buitdfng occur. Crazing or cracking is “State-of-the-Art ofPrecast Concrete Sandwich
sometimes caused by bowing, but will be minimized Panels,” PCI Journal, V. 36, No. 6, November-
if the recommendations of Sect. 9.4.2 are followed; December 1991.
such cracking is seldom of structural significance.
3. Bush, Thomas D.f and Stine, Gregory L , “Flex­
ural Behavior of Composite Precast Concrete
Sandwich Panels with Continuous Truss Con­
nectors,” PCI Journal, V. 39, No. 2, March-
9.4.6 Typical Details April 1994.
As with all-precast concrete construction, satisfac­
tory performance depends on proper detailing. The 4. PCI Committee on Precast Sandwich Wall Pan­
typical wall panel connections and details shown in els, “State-of-the-Art of Precast/Prestressed
Chapter 6 are equally applicable to sandwich panels. Sandwich Wall Panels,” PCI Journal, V. 42, No.
Common details and connections for sandwich wall 2, M arch-April 1997 and V.42, No. 3, May-
panels can be found in Ref. 4. June 1997.

9 -5 6 PCI Design Handbook/Fifth Edition


9.5 QUALITY ASSURANCE A N D CONTROL

9.5.1 Introduction groups of products: -A - architectural products; G -


glass fiber reinforced concrete; B - bridges; and C -
commercial (structural) products.
The successful use and application of precast and
Product Group A has two categories: A1 for major-,
prestressed concrete demands a high level ,of atten­
primary architectural panelsand products; and ATfor
tion to quality in design and production.
miscellaneous or trim elements.
Each manufacturer (producer) must have in place
Groups B and C each have four separate catego­
a quality assurance program with the goals to assure
ries that identify the experience and equipment avail­
structural integrity, ease of construction and the de­
able at the certified plant. A description of groups
sired aesthetic appearance in the final structure. Fur­
and categories B1 through B4 and C1 through C4
ther, the owner or architect/engineer must be satis­
may be found in PCI’s Commitment to Quality [2] and
fied that materials, methods, products and the
are titled as follows:
producers’ quality control meet the requirements of
B1 Precast Bridge Products (non-prestressed)
the project specifications. They can have this assur­
B2 Prestressed Miscellaneous Bridge Products
ance by requiring by specification that the manufac­
B3 Prestressed Straight Strand Bridge Members
turing facilities be certified by the Precast/Pre-
B4 Prestressed Draped Strand Bridge Members
stressed Concrete Institute’s Plant Certification
C1 Precast Concrete Products (non-prestressed)
Program (see Chapter 10, Guide Specifications).
C2 Prestressed Hollow-Core and Repetitive Prod­
In those instances when site-precasting is done,
ucts
the same degree of quality should be expected by the
C3 Prestressed Straight Strand Structural Mem­
owner or architect/engineer and rigorous inspections
bers
and/or quality assurance must be provided. These
C4 Prestressed Draped Strand Structural Mem­
expectations can only be achieved if clearly written
bers
and included in the original project specifications.
Many producers have experience with applying
fine architectural finishes to typical structural prod­
ucts. This certified architectural capability is identi­
9.5.2 Plant Certification fied with an “A” following the Group and Category
designation (e.g., C3A for a spandrel panel for a park­
ing structure made with straight strands and having a
Producers registered under the PCI Rant Certifi­
special architectural pattern and finish on the face).
cation Program have demonstrated their capability to
Therefore, Group and Category designations B1
produce quality precast or prestressed concrete
through B4 and C1 through C4 may be modified with
products as specified. These plants maintain a com­
an “A” suffix.
prehensive quality system that is present in every as­
Auditing criteria and grading are based on the in­
pect of their business. Each certified plant conducts
dustry’s standards for quality and quality control.
a formal quality control program with an established
These standards are presented in the PCI’s three
quality control staff. The staff must meet the current
quality control manuals, one for structural precast
requirements of the PCI Quality Control Personnel
and prestressed concrete products [3], one for archi­
Certification Program [1] Conformance to the nation­
tectural precast products [4], and one for glass fiber
ally accepted requirements is determined by a mini­
reinforced concrete products [5]. Audits cover all
mum of two quality audits per year. All audits are un­
phases of design and production including shop
announced and most are two days in length. The
drawings, design, materials, production methods,
audits are conducted by specially trained personnel
product handling and storage, appearance, testing,
employed by a national structural consulting engi­
record keeping, quality control, personnel training,
neering firm engaged by PCI.
and safety practices. Failure to maintain a production
PCI Plant Certification identifies the general types
plant at or above required standards results in man­
of products in which the producer has demonstrated
datory loss of certification. A current listing o f plants
expertise. This is done through the program’s Prod­
holding certification is published a minimum of twice
uct Group & Gategory provisions. There are four
each year or may be obtained by calling PCI.

PCI Design Handbook/Fifth Edition 9 -5 7


Care should- be exercised in evaluating other certi­ based on these manuals. They should also be used
fication -programs. Criteria should include: by any auditing, agency for outside inspection of pro­
1. Unannounced audits are fundamental- t o the duction facilities. They arethe standards-for the PCI
program. Plant Certification Program and the basis for the de­
2. The auditor should be recognized as experi­ tailed rating system whereby a plant may become
enced in the field of precast and-prestressed certified^
concrete.
3. The auditor of a plant producing specialty prod­
ucts (prison celt units, railroad ties, bridge gird­
ers, etc.) and using special methods (pre­ 9.5.4 References
stressing, architectural precast concrete, glass
fiber reinforced concrete, etc.) should have
particular experience with that product or 1. “Quality Control Personnel Certification,”
method. QCP-1-97, Precast/Prestressed Concrete Insti­
4. The auditor should be independent and not tute, Chicago, IL, 1997.
hired by the precast concrete manufacturer.
5. The auditor should view the entire fabrication 2. “Commitment to Quality,” PC-3-97, Precast/
cycle. Prestressed Concrete Institute, Chicago, IL,
1997.
6. The program should be executed by a single
auditing agency that provides uniformity for all
3. “Manual for Quality Control for Plants and Pro­
size companies throughout the United States.
duction of Precast and Prestressed Concrete
7. The program and the auditing agency should
Products,” Fourth Edition, MNL-116-98, Pre­
be recognized by major public and private
cast/Prestressed Concrete Institute, Chicago,
agencies and organizations.
IL, 1998.

4. “Manual for Quafity Control for Plants and Pro­


9.5.3 PCI Quality Control Manuals
duction of Architectural Precast Concrete Prod­
ucts,” Third Edition, MNL-117-96, Precast/Pre­
The three PCI manuals listed inSect. 9.5.4 contain stressed Concrete Institute, Chicago, IL, 1996.
industry approved and nationally accepted require­
ments for quality and quality control for structural and 5. “Manual for Quality Control for Plants and Pro­
architectural precast concrete products, as well as duction of Glass Fiber Reinforced Concrete
glass fiber reinforced concrete products. Any pre­ Products,” MNL-130-91, Precast/Prestressed
cast concrete quality assurance program should be Concrete Institute, Chicago, IL, 1991.

9 -5 8 PCI Design Handbook/Fifth Edition


9.6 CONCRETE COATINGS AND JOINT SEALANTS

9.6.1 Coatings for Horizontal Deck Surfaces mance over a suitable period of exposure-or usage,
abased on prior experience under similar exposure^
Concrete surface sealers reduce moisture ancL
conditions.
salt (chloride) penetration, which is particurarly im­
Sealers are usually applied To wall panels after
portant in parking structures. While these sealers can
erection 1o avoid problems with-adhesion of joint
enhance the durability o f any concreteJopping, they
sealants.
do not substitute for basic durable concrete design,
Any coating used should be guaranteed by the
nor do they provide protection against penetration of
supplier orapplicator not to stain, soil, or discolor the
moisture and chlorides through cracks. Research
precast concrete finish. Also, some clear coatings
has shown that the performance of concrete sealers
may cause joint sealants to stain concrete. Consult
will vary, depending on the product and other vari­
manufacturers of both sealants and coatings or pre­
ables. Products should be evaluated against the cri-
test before applying the coating.
teriaestablished in the NCHRP 244 study [3]. Sealers
Sealers should be applied in accordance with
may be classified into two groups: penetrants and
manufacturer’s recommendations. Generally, good
surface sealers.
airless spray equipment is used for uniformity and to
Penetrants: These are generally silanes or silox-
prevent surface rundown. Two coats are usually re­
anes. They penetrate ih e surface, reacting with ce­
quired to provide a uniform coating, because the first
mentitious materials and making the concrete hydro­
coat is absorbed into the concrete. The second coat
phobic. They do not have crack-bridging capa­
does not penetrate as much and provides a more uni­
bilities. These materials do not appreciably affect the
form surface color. Care must be taken to keep seal­
Appearance or characteristics of the surface to which
ers off glass surfaces.
they are applied. While generally more expensive
than other types of sealers they are typically longer
lasting and less subject to wear under traffic or deteri­ 9.6.3 Joint Sealants
oration from exposure to sun.
Joint sealants include viscous liquids, mastics or
Surface Sealers: These are generally polymer
resins such as urethanes, epoxies, acrylics, or other pastes, and tapes, gaskets and foams. Generally, a
proprietary blends. They provide protection by pene­ sealant is any material placed in a joint for the pur­
trating the surface slightly, and/or by providing a pose of preventing the passage of moisture, air, heat
tough film over the surface; these materials also do or dirt into or through the joint.
not bridge cracks. Surface sealers are generally less Successful performance of a wall system is often
expensive than penetrants, and performance charac­ dependent on good joint details and sealant selec­
teristics of many of these products compare favor­ tion. Too often, because the sealant is a relatively mi­
ably with the penetrating sealers, as demonstrated nor part of the total structure, the responsibility for
by the NCHRP 244 criteria. These sealers are more selection is left to the contractor or erector who does
likely to be subject to wear under traffic, and may be not fully understand the task it is to perform.
more slippery than the bare concrete surface. The selection of the proper sealant is confused by
the method of supply. Most of the raw materials are
manufactured by a few major chemical companies.
9.6.2 Clear Surface Sealers for Architectural These basic materials are then compounded with
Precast Panels other ingredients by literally hundreds of sealant
manufacturers. The quality of finished product varies
Clear surface coatings or sealers are sometimes
widely because the expertise of the formulators var­
used on precast concrete wall panels to improve
ies widely.
weathering qualities or to reduce attack of the con­
Viscous liquid sealants are often used in pourable
crete surface by airborne pollutants. Because of the
form and normally are used in horizontal joints. Mas­
quality of concrete normally achieved in plant-cast
tics are applied with a gun and are compounded to
precast concrete, even with very thin sections, seal­
prevent sagging or flowing when used in vertical
ers are not required for waterproofing. Because the
joints. Tapes are most often used around glass. Elas­
results are uncertain, use of sealers in locations hav­
tomeric gaskets are used in joints which experience
ing little or no air pollution is not recommended.
considerable movement. Foams are used as air seals
A careful evaluation should be made before decid­
or backup for more durable surface seals.
ing on the type of sealer. This includes consultation
Specification of sealants is difficult because many
with the local precasters. In the absence of near-iden­
tical experience, it is desirable to test sealers on rea­ of the numerous formulations are not covered by
sonably sized samples of varying age to verify perfor­ standard specifications, either for materials or instal­

PCI Design Handbook/Fifth Edition 9 -5 9


lation. Many of the “standard” specifications arealso mentBulletin D137, Portland Cement Associa­
outofdate, and often standard-writing agencies have tion, Skokie, IL, 1988.
specifications that do n oi agree.
Provemperformance is stilf-the procedure that is 5. “Guide Specifications, Section 07900 (Seal­
often relied upon. Refs. 5~through11 will aid in the ants) ,” Sealant, Waterproofing-and Restoratien-
desig n and selection of joint sealants. Ref. 7 is_afso a Institute, Kansas City, MO, 1982.
very valuable aid for the design and detailing o f archi­
8. “Sealants: The Professionals’ Guide,” Sealant,
tectural precast panel joints.
Waterproofing and Restoration Institute, Kan­
sas City, MO, 1990.
9.6.4 References
1. “A Guide to the Use o f Waterproofing, Damp­ 7. “Architectural Precast Concrete,” Second Edi­
proofing, Protective, and Decorative Barrier tion, MNL-122-89, Precast/Prestressed Con­
Systems for Concrete,” ACI 515.1R-85, ACI crete Institute, Chicago, IL, 1989.
Manual of Concrete Practice, Part 5, American
Concrete Institute, Farmington Hills, Ml. 8. “Guide to Joint Sealants for Concrete Struc­
tures/ ACI 504R-90, ACI Manual o f Concrete
2. Pfeifer, D.W., and Perenchio, W.F., “Coatings, Practice, Part 5, American Concrete Institute,
Penetrants and Specialty Concrete Overlays Farmington Hills, ML
for Concrete Surfaces,” National Association of
Corrosion Engineers Seminar, Chicago, IL, 9. Cook, J.P., “Construction Sealants and Adhe­
September 1982. sives,” Wiley-lnterscience, New York, NY.

3. “Concrete Sealers for Protection of Bridge 10. Kubal, Michael T., “Waterproofing the Building
Structures,” NCHRP Report 244, Transporta­ Envelope,” McGraw-Hill Book Co., New York,
tion Research Board, Washington, DC. NY, 1993.

4. Litvin, Albert, “Clear Coatings for Exposed Ar­ 11. “Standard Guide for Use of Joint Sealants,”
chitectural Concrete,” Development Depart­ ASTM C 1193, American Society for Testing
and Materials, Philadelphia, PA.

9 -6 0 PCI Design Handbook/Fifth Edition


9.7 VIBRATION IN CONCRETE STRUCTURES
9.7.1 Human Response to Building wp — actual LL, p s f
Vibrations et = dynamic toad factor
When the resonant frequency of a floor system is g = acceleration constant, 386 in./sec.2
close to the “frequency imparted by the occupants,
and the deflection of the system is significant, motion
will be perceptible and perhaps annoying. Perception 9.7.1.2 Natural frequency
is related to the activity of the occupant: a person at The natural frequency of a floor system will be a
rest or engaged in quiet work will tolerate less vibra­ combination of the natural frequency of the framing
tion than a person performing an active function, members, including slab, beam and girders. For a
such as dancing or aerobics. However, if a floor sys­ precast beam supported on rigid supports, the natu­
tem dissipates the imparted energy in a very short pe­ ral frequency m aybe calculated as:
riod of time, the magnitude ot motion is generally not
perceived as annoying. Thus, the damping charac­
(Eq. 9.7.2)
teristics of the system contribute to acceptability.
Vibration is generally stated as a fraction of gravity
where:
acceleration:. In an office environment, investigators
report annoyance when vibration exceeds 0.005g; in g = 386 in./sec2
an active environment, such as aerobics, investiga­ E = modulus of elasticity, psi
tors [101 report the participants will accept vibrations I = moment of inertia of beam, in.4 (Use
n the order of 0.05g. Thus, a design procedure would effective moment of inertia if beam is
first establish the limiting degree of vibration for a par­ cracked when supporting W).
ticular floor usage, and from that determine the nec­
^ = span, in.
essary minimum stiffness (natural frequency). Finally,
the natural frequency of the floor is calculated, and W = total supported weight on beam, lb
compared to the minimum acceptable natural fre­ K = 1.57 for simple beam, 0.56 for fixed end
quency. Ref. 10 is the basis for this section. Addition­ cantilever, and 3.50 for a fixed end beam.
al information is given there.
Use of high-strength concrete will typically result
in lighter members with the likelihood of more notice­ Example 9.7.1 Gymnasium Floor
able or annoying vibrations. When calculating natu­ An 8DT24+2 is to be used as a gymnasium floor
ral frequencies for these types of members (Eq. and is supported on block walls. The design span is
9.7.2), the equation for predicting the modulus of 50 ft. There are no adjacent quiet areas, so the accel­
elasticity should be based on the recommendation of eration fraction limit will be taken as 0.05 (see Table
ACI Committee 363 (see Design Aid 11.2.2) or on test 9.7.1). The weight of the active participants is taken
values. as 5 psf, and the floor system weighs 77 psf. The forc­
ing frequency is estimated as 2.75. From Table 9.7.2,
the dynamic load factor for the first harmonic is 1.5.
9.7.1.1 Minimum Natural Frequency
From Eq. 9.7.1, the resonant frequency should be
The minimum required stiffness of a floor system greater than:
to offset a sense of disturbing vibration is a function of
1 (1-3) (1-5) (5)
many variables, and not subject to exact calculation. fo 2.75 5.05 Hz
A simplified method to estimate the minimum natural (0.05) (82)
frequency of a floor system is given in Eq. 9.7.1 [10]:
From Eq. 9.7.2

1.3 Wp
fD > f /1 + aw (Eq. 9.7.1) (386)(4.3x106)(2 7 ,720)
a 0/ g f 0 = 1.57 4.00 Hz
(82) (8) (50) [50(12)]3
where:
a0/g = acceleration limit, % gravity
Since this is less than the required minimum natu­
f = forcing frequency, Hz
ral frequency, the floor system is not acceptable. Pos­
f0 = natural frequency of the structural sible solutions include increasing the depth of the
system floor, blocking the double tee flanges, or reducing the
w = total weight (DL + actual LL), psf span.

PCI Design Handbook/FIfth Edition 9 -6 1


Example 9.7.2 Stadium Seats Table 9.7.1 Recommended acceleration lim­
its for vibrations due to rhythmic
The precast stadium-seat shown in Figure 9.7.1 is
activities
a diagram of an actual unit used in a-major sporTsta-
diom in service since 1990. The span is 43 ft. Investi­ rOccupandes affected Acceleration limits
by the vibrations % gravity
gate its acceptability with respect to vibration.
According to Ref. 10, the maximum forcing fre­ Office and residential 0.4 to 0.7
quency for the first harmonic in a stadium can be as­
Dancing and weightlifting 1.5 to 2.5
sumed as 3 Rz with an associated dynamic load fee-
tor of 0.25; A study of the sections used on three Rhythmic activity only 4 to 7
major stadiums constructed since 1990 indicates that
these criteria when used with Eq. 9.7.1, result in con­ Table 9.7.2 Recommended dynamic load
servatively high required stiffness. The same is true factors for aerobics [11}
for the criteria suggested for the second harmonic, irr Harmonic Forcing frequency, Hz Dynamic load factor,.
those cases, the calculated natural frequencies of in­
1 2-2.75 1.5
dividual units varied from 2.8 (for the longest units in-
2 4-5.5 0.6
tine farthest reaches of angled bays) to 3.5 (for units
within rectangular bays). It should be noted that even 3 6-8.25 0.1
though the longer individual units in angled bays
W = (474 + 160)43 = 27,262 lb
have lower natural frequencies, resonance in these
areas is less likely because of the dynamic interfer­
Imin = 12,422 in4 (not cracked when support­
ence due to different lengths and thus frequencies of
ing W)
individual units.
E = 4 . 3 x 1 0 e psi
No spectator discomfort has been reported in any
ofthese projects. Ingeneral, it has been found that for g = 386 in./sec2
precast prestressed seating units designed for a 100
psf live load and a maximum tensile stress of 12 f0 = K
the vibrations are not annoying to the occupants.
Based on the above observations, it is recom­ „ /386(4.3x106)(12,422)
mended that the minimum fundamental natural fre­
~ 1-57 Y 27,262(43x12)3
quency in the range of 2.8 to 3.5 (specific value based
on the location of the unit) be used as an acceptance
= 3.68 > 3.5
criteria for stadium seats.
For the example, assume an actual live load o f 30 Thus the section is acceptable.
psf, or 160 Ib/ft (i.e. that portion of the design live load
causing vibration). The weight of the stadium seat is 9.7.2 Vibration Isolation for Mechanical
474 Ib/ft. Equipment
Vibration produced by equipment with unbal­
Figure 9.7.1 Stadium seat for Example 9.7.2 anced operating or starting forces can usually be iso­
lated from the structure by mounting on a heavy con­
crete slab placed on resilient supports. This type of
slab, called an inertia block, provides a low center of
gravity to compensate for thrusts such as those gen­
erated by large fans.
For equipment with less unbalanced weight a
“housekeeping" slab is sometimes used below the
resilient mounts to provide a rigid support for the
mounts and to keep them above the floor so they are
easier to clean and inspect. This slab may also be
mounted on pads of precompressed glass fiber or
neoprene.
The natural frequency of the total load on resilient
mounts must be well below the frequency generated
by the equipment. The required weight of an inertia
block depends on the total weight of the machine and

9 -6 2 PCI Design Handbook/Fifth Edition


the unbalanced force. For a long-stroke compressor, 9.7.3 References
five to seven times its weight might be needed. For
high pressure fans, one to fivetim esthe fan weightis 1. “Vibrations of Concrete Structures^” Special
usually sufficient. Publication SP-60, American Concrete Insti­
A floor suppofting-resifentiy mounted equipm ent tute, Detroit, Ml, 1979.
must be stiffer than the isolation system. If the static
deflectbn of the floor approaches the static-deflection 2. Galambos, T.V., Gould, P.C., Flavindra, M.R.,
of the mounts, the floor becomes a part of the vibrat­ Surgoutomo, H., and Crist, R.A., “Structural
ing system, and little vibration isolation is achieved. In Deflections—A Literature and State-of-the-Art
general, the floor deflection should be limited to Survey," Building Science Series, National In­
about 15% of-the deflection of the mounts. stitute of Standards and Technology, Washing­
Simplified theory shows that for 90% vibration ton, DC, October 1973.
isolation, a single resilient supported mass (isolator)
should have a natural frequency o f about 'A the driv­ 3. Murray, T. M., “Acceptability Criterion for Occu-
ing frequency of the equipment. The natural frequen­ pant-lnduced Floor Vibration,” Sound and
cy of this mass can be calculated by [9]: Vibration, November 1979.

fn = 188 JT /A ; (Eq. 9.7.3) 4. “Design and Evaluation o f Operation Break­


through Housing Systems," NBS Report
where: 10200, Amendment 4, U.S. Department of
fn = natural frequency of the isolator, CPM Housing & Urban Development Washington,
4 = static deflection of the isolator, in. DC, September 1970.

From the above, the required static deflection of 5. Wiss, J.F. and Parmelee, R.A., “Human Per­
an isolator can be determined as follows: ception of Transient Vibrations,” Journal o f the
f n = fd/ 3 = 1 8 8 / i A or Structural Division, ASCE, V. 100, No. ST4,
April 1974.
A, = (564/fd)2 (Eq. 9.7.4)
6. “Guide to Floor Vibrations, ” Steel Structures for
and: Buildings (Limit States Design), CAN3-S16.1-
Af < 0.15 Ai (Eq. 9.7.5) M74, Appendix G, Canadian Standards Asso­
ciation, Rexdale, Ontario, Canada, 1974.
where:
fd = driving Frequency of the equipment, CPM
7. “Guide for the Evaluation of Human Exposure
A, = static deflection of the floor system to Whole Body Vibration,” International Stan­
caused by the weight of the equipment, dard 2631, International Organization for Stan­
including inertia block, at the location of dardization, 1974.
the equipment, in.
8. Murray, T.M., “Design to Prevent Floor Vibra­
Example 9.7.3 Vibration Isolation tion,” Engineering Journal, Third Quarter,
American Institute of Steel Construction, 1975.
Given:
A piece of mechanical equipment has a driving fre­
quency of 800 CPM. 9. Harris, C.M., and Crede, C.E., “Shock and
Vibration Handbook,” Second Edition,
Problem: McGraw-Hill Book Co., New York, NY, 1976.
Determine the approximate minimum deflection of
the isolator and the maximum deflection of the floor 10. Allen, D.E., “Building Vibrations from Human
system that should be allowed. Activities,” Concrete International, V. 12, No. 6,
June 1990.
Solution:
From Eq. 9.7.4: 11. Bachmann, H., and Ammann, W., “Vibrations
in Structures Induced by Man and Machine,”
Isolator, A| = (564/800)2 = 0.50 in.
Structural Engineering Documents, No. 3 , In­
From Eq. 9.7.5: ternational Association for Bridge and Structur­
Floor, A, = 0.15(0.50) = 0.07 in. al Engineering, Zurich, Switzerland, 1987.

PCI Design Handbook/Fifth Edition 9 -6 3


9.8 CRACKING, REPAIR AND MAINTENANCE

9.8.1 Cracking Concrete surfaces normally require little mainte­


nance, except for those that are subjectto harsh envi­
“Minor cracking, may occur in precast concrete
ronments, such-as parking structures in northern-cli­
without being,detrimental, and it is impractical to im­
mates. Routine inspection and maintenance can bo
pose specifications that prohibit all cracking, (Note:
much toextend the life o f such-buildings [8,9].
in other sections, the term “crack-free” design is
used. This refers to a design irrwhich concrete ten­
sion is kept within limits, and should not be construed 9.8.3 References
as being a guarantee that there will be no cracking.)
1. “Control of Cracking in Concrete Structures,”
However, in addition to being unsightly, cracks are
ACi 224R-90, ACI Manual of Concrete Practice,
potential locations of concrete deterioration, and
Part 3, American Concrete Institute, Farming-
should be avoided if possible. Prestressing and prop­
ton Hilts, Ml.
er handling procedures are two of the best methods
of keeping cracks to a minimum. To evaluate the ac­
2. “Causes, Evaluation, and Repair of Cracks in
ceptability of a crack, the cause and service condi­
Concrete Structures,” ACI 224.1 R-93, ACI
tions of the precast unit should be determined.
Manual of Concrete Practice, Part 3, American
Crazing, i.e., fine, random (commonly called “ hair­
Concrete Institute, Farmington Hilis, Ml.
line”) cracks, may occur in the cement film on the sur­
face of concrete. The primary cause is the shrinkage 3. Mather, Bryant, “Cracking Induced by Environ­
o f the surface with respect to the mass of the unit. mental Effects,” Causes, Mechanism, and Con­
Crazing has no structural significance and does not trol of Cracking in Concrete, Special Publica­
significantly affect durability, but may be visually ac­ tion SP-20, American Concrete Institute,
centuated if dirt settles in these minute cracks. Craz­ Farmington Hills, Ml, 1968.
ing should not be cause for rejection.
Tension cracks are sometimes caused by tempo­ 4. “Guide to Durable Concrete,” ACI 201.2R-92,
rary loads during production, transportation, or erec­ ACI Manual of Concrete Practice, Part 1, Ameri­
tion of these products (see Chapter 5). These cracks can Concrete Institute, Farmington Hills, Ml.
may extend through to the reinforcement. If the crack
width is narrow, the structural adequacy of the cast­ 5. “Manual for Quality Control for Plants and Pro­
ing will remain unimpaired, as long as corrosion of the duction of Architectural Precast Concrete Prod­
reinforcement is prevented. See Sect. 4.2.2.1 for rec­ ucts,” MNL-117-96, Precast/Prestressed Con­
ommended limits on crack width. The acceptability of crete Institute, Chicago, IL, 1996.
cracks wider than recommended maximums should
6. PCI Committee on Quality Control Perfor­
be governed by the function of the unit Most can be
mance Criteria, “Fabrication and Shipment
effectively repaired and sealed.
Cracks in Prestressed Hollow-Core Slabs and
Long-term volume changes can also cause crack­
Double Tees,” PCI Journal, V. 28, No. 1, Janu-
ing after the member is in place in the building, if the
ary-February 1983.
connections provide enough restraint to the member
(see Sect. 3.3). Internal causes, such as corrosion of
7. PCI Committee on Quality Control Perfor­
reinforcement or cement-aggregate reactivity, can
mance Criteria, “Fabrication and Shipment
also lead to long-term cracking and should be con­
Cracks in Precast or Prestressed Beams and
sidered when materials are selected. Columns,” PCI Journal, V. 30, No. 3, May-June
1985.
9.8.2 Repair and Maintenance
8. “Parking Structures: Recommended Practice
Products which are damaged prior to or during for Design and Construction,” MNL-129-88,
placement in the structure can usually be repaired, Precast/Prestressed Concrete Institute, Chica­
but major repairs should not be made until it is deter­ go, IL, 1988.
mined that the unit will be structurally sound. If repair
is required for the restoration of structural integrity, 9. “Parking Garage Maintenance Manual,” Na­
cracks may be pressure injected with a low viscosity tional Parking Association, Washington, DC.
epoxy.
Patching of architectural panels is an art requiring 10. “Architectural Precast Concrete,” Second Edi­
tion, MNL-122-89, Precast/Prestressed Con­
expert craftsmanship and careful selection and mix­
ing of materials [TO]. crete Institute, Chicago, IL, 1989.

9 -6 4 PCI Design Handbook/Fifth Edition


9.9 PRECAST SEGMENTAL CONSTRUCTION

9.9.1 General After grouting, vents are closed and pressure in­
creased to assure full grout intrusion; After-a few
Segmental construction is a m ethodof construc­
days, the vends reopened, and filleduvith grout asre-
tion in. which primary load carrying- members are
quired.
composed of individuai segments post-tensioned to­
gether. This allows precast concrete to be used for
long horizontal or vertical spans within size limitations 9.9 2.2 Closed Joints
imposed by manufacturing, transportation, and han­
If a closed joint is used, the segment is usually
dling equipment. With proper planning and element
“match-cast”, i.e., each segment is cast against its
selection, a targe re-use of forms is possible, with the
previously cast neighbor. A bond breaker is applied
resulting economy.
to the joint during casting. Thus, the connecting sur­
The method is best known for a number of land­
faces fit each other accurately, so that little or no filling
mark bridges [1,10], but has also been used in the
construction o f airport control towers, storage tanks material is needed at the joint. The sharpness of line
of the assembled construction depends mainly on
for various solids and liq u id s including natural gas, a
the accuracy of the manufacture of the segments.
long-span exterior Vierendeel truss on a high-rise
building, an Olympic stadium and other non-bridge Match cast segments are usually joined by coat­
structures [2-9]. ing the abutting surfaces with a thin layer of epoxy
Segmental construction requires that the designer adhesive, and then using the post-tensioning to draw
the elements together and hold them in position. In
give special consideration to:
some structures, dry joints have been used success­
1. Size and weight of the precast elements. fully, in which case, the compression provided by the
post-tensioning is relied upon for weatherproofing, as
2. Configuration and behavior o f the joints be­
well as for transfer of forces.
tween elements.
Surface preparation of closed joints is extremely
3. Construction sequence, and the loads and important. They should be sound and clean, free
deflections imposed at various stages. from all traces of form release agents, curing com­
pounds, laitance, oil, dirt and loose concrete.
4. The effect of normal tolerances and deviations
upon the joints.
Figure 9.9.1 Types of joints

- GASKET SURROUND
9.9.2 Joints
PROVIDE AIR VENT AT TOP
Joints may be either “open” , to permit completion /
by a field placed grout, or “closed”, where the joint is
either dry or bonded by a thin layer of adhesive (Fig­
m EFFECTIVE EFFECTIVE
ure 9.9.1). f AREA FOR t AREA FOR
DESIGN DESIGN

9.9.2.1 Open Joints


t
%" MINIMUM GROUT
The individual segments are separated by an 2" MAXIMUM GASKET
amount sufficient to place (usually by pressure) a ELEVATION PLAN
grout mix, but not more than about 2 in. Prior to plac­ (A) OPEN JOINT
ing the segments, the joint surface is thoroughly MATCH CAST SEG­
cleaned and wire brushed or sand-blasted. 0^ IF DRY MENT 2 AGAINST
— PREVIOUSLY CAST
Vis" IF EPOXY
The perimeter of the joint is sealed with a gasket SEGMENT 1 I
which is compressed by use of “come-alongs” or by a t
small amount of prestress. Gaskets are also provided EFFECTIVE EFFECTIVE
-■ ‘ AREA FOR
around the post-tensioning elements to prevent leak­ © © AREA FOR
*~P DESIGN DESIGN
age into the ducts, blocking passage of the tendons. 1
Vents are provided at the top to permit escape of en­ PLAN
ELEVATION
trapped air during grouting. Prior to filling the joint,
(B) CLOSED JOINT
the surfaces should be thoroughly wetted, or coated
with a bonding agent. Grout strength should be at FOR EPOXY JOINTS, APPLY A TEMPORARY
least equal to that of the precast segments, but not PRESTRESS OF 50 psi IMMEDIATELY AFTER
APPLICATION OF EPOXY.
less than 4000 psi.

PCI Design Handbook/Fifth Edition 9 -6 5


A small piece of foreign material in a joint, or im— givenio the alignmerrt ofthe ducts, especially at the
perfect alignment wilt frequency cause the- concrete joints. They must be large enough in diameter to ade-
t o spall around toe edges of toe contact area of a= quately place the tendon, allowingsome tolerance:in
closed jo in t Thus, care in joint preparation and seg­ alignment-, and receive toe grout placed subsequent
ment alignment cannot be over-emphasized. to stressing. Special attention "must be given tothe
corrosion protection ofthe post-tensioning steel, if it
is to be unbonded at any stage of construction. Also,
9 .9 .3 D es ig n
drains shoulddeinstalled in toe ducts at low points of
Analysis of precast segmental structures usually the tendon profile.
assumes monolithic behavior of toe members under Post-tensioning tendons crossing joints should be
service loads, except that if dry joints are used, ten­ approximately perpendicular to the joint surface in
sion is not permitted between segments. Some de­ the smaller dimension ofthe segment, e.g., flange or
signers also prefer to not allow tension in grouted web thickness, but may be inclined to the direction of
joints, unless tests have indicated otherwise. the larger dimension (e.g., depth). This is to minimize
The behavior during construction is of particular any unbalanced shearing force which could lead to
importance in segmental structures. Stresses which dislocation of edges at the joints.
may be caused by settlement and shortening of scaf­
folding, temperature changes, elastic shortening
9.9.4.2 Couplers
from post-tensioning and other construction related
stresses and movements may need to be considered Couplers are designed to develop the full strength
in the design. ofthe tendons they connect. Adjacent to toe coupler,
Shear stresses across joints are resisted by epoxy the tendons should be straight, or have very minor
adhesives or grout, sometimes in combination with curvature for a minimum length of 12times the diame­
shear keys. In dry joints, shear stresses are resisted ter of the coupler. Adequate provisions must be
by friction (and shear keys if present), with the post­ made to ensure that the couplers can move during
tensioning providing toe normal force. In the absence prestressing.
of test data, the coefficient of friction may be assumed
to be 0.8 (Sect. 6.6).
9.9.4.3 Bearing Areas
Individual segments are designed for handling
and erection stresses (Chapter 5). They may be pre­ Prestress force is transferred to the joined seg­
tensioned or reinforced with mild steel, depending on ments through bearing plates or other anchorage de­
size and manufacturing procedure. vices. This causes high load concentrations at the
bearing areas, usually requiring vertical and horizon­
tal reinforcement in several locations:
9.9.4 Post-Tensioning
1. Under end surfaces, not more than 3A in. deep,
Information on various post-tensioning systems
to control possible surface cracking around an­
and their applications is given in the PTI Post-Ten­
chorage.
sioning Manual [11]. Nearly any type of bonded sys­
2. Internally, to prevent splitting between individ­
tem can be used.
ual anchors. Size and location of this area and
the magnitude of splitting (bursting) force de­
9.9.4.1 Tendon and Duct Placement pends on toe type of anchorage and the force
in the post-tensioning tendon.
In addition to toe design parameters for in-service
3. Internally, to prevent splitting between groups
conditions, toe tendon layout must consider the se­
of anchors.
quence of construction and the changes in load con­
4. Adjacent to joint surfaces, to decrease the pos­
ditions during the various construction stages.
sibility of damage to segments during post-ten­
Ducts for the tendons are placed in toe segments
sioning or handling.
prior to concrete placement. In some cases, tendons
are installed in toe ducts before the segment is Grouting of the ducts is provided for corrosion
erected, or even before concrete is placed, and sub­ protection and to develop bond between the pre­
sequently coupled at each joint. In others, the ten­ stressing steel and the surrounding concrete. Grout­
dons are placed after toe segments are erected, ei­ ing procedures should follow the Recommended
ther full length of the member or in shorter lengths, Practice for Grouting o f Post-Tensioned Prestressed
again coupled at the joints. Special attention must be Concrete, contained in Ref. 11.

9 -6 6 PCI Design Handbook/Fifth Edition


9.9.5 References 6. Muller, Jean, “TenTears of Experience in-Pre-
cast Segmental Construction,” PCI Journal, V.
20, No. 1, January-February 1975.
1. Joint PCI-PTI Committee on Segmental
Construction “Recommended Practicafor Pre­ 7. Lamberson, E.A., “Post-Tensioned Structural
cast Post-Tensioned Segmental Construc­ Systems— Dallas-Ft. Worth Airport,” PCI Jour­
tion,^"VGl-Joumst, V. 27, No. T, January-Febru- nal, V. 13, No. :6, November-December 1973.
ary 1982-
8. Zielinski, Z.A., “Prestressed Slabs and Shells
2. Anderson, Arthur R., “World’s Largest Pre­ Made of Prefabricated Components,” PCI Jour­
stressed LPG Floating Vessel,” PCI Journal, V. nal, V. 9, No. 4, August 1964.
22, No. 1, January-February 1977.
9. Zielinski, Z.A., “Prefabricated Building Made of
3. Perry, William E., “Precast Prestressed Clinker Triangular Prestressed Components,” Journal
Storage Silo Saves Time and Money,” PCI of the American Concrete Institute, V. 61, No. 4,
Journal, V. 21, No. 1, January-February 1976. April 1964.

4. Martynowicz, A., and McMillan, C.B., “Large 10. “Precast Segmental Box Girder Bridge Manu­
Precast Prestressed Vierendeel Trusses High­ al," published jointly by the Precast/Pre-
light Multistory Building," PCI Journal, V. 20, stressed Concrete Institute (Chicago, IL) and
No. 6, November-December 1975. the Post-Tensioning Institute (Phoenix, AZ),
1978.
5. Arafat, M.Z., “Giant Precast Prestressed LNG
Storage Tanks at Staten Island,” PCI Journal, 11. “PTI Post-Tensioning Manual,” Fifth Edition,
V. 20, No. 3, May-June 1975. Post-Tensioning Institute, Phoenix, AZ, 1990.

PCI Design Handbook/Fifth Edition 9 -6 7


9.10 COORDINATION W ITH MECHANICAL, ELECTRICAL
AND OTHER SUB-SYSTEMS
9.10.1 Introduction When tbe-system isptaeed in^structural compos­
Prestressed concrete is used in a wide variety-of ite slab,, the-effect of ducts and conduits must be
buildings, and1its integration with lighting, mechani- carefully examined and their location coordinated
cal, plumbing, and. other services, ie of importance to with reinforcing steel. Tests on-slabs withburied duct­
the designer. Because of Increased environmental work have shownihat structural strength is not nor­
demands, the ratio of costs for mechanical and elec­ mally impaired by the voids.
trical installations to total building cost has increased Because ofthe high load-carrying capacity of pre­
substantially in recent years. This section is intended stressed concrete members, it is possible to locate
to provide the designer with the necessary perspec­ high-voltage substations, with heavy transformers,
tive to economically satisfy mechanical and electrical near the areas o f consumption with little or no addi­
requirements, and to describe some standard meth­ tional expense. For extra safety, distribution feeds
ods of providing for the installation o f other sub-sys­ can also be run within those channels created by
tems. stemmed members. Such measures also aid the
economy of the structure by reducing the overall
story height andminimizing maintenance expenses.
9.10.2 Lighting and Power Distribution

For many applications, the designer can take ad­ 9.10.4 Ductwork
vantage of the fire resistance, reflective qualities and
The designer may also utilize the space within
appearance of prestressed concrete by leaving the
stemmed members or the holes inside hollow-core
columns, beams, and ceiling structure exposed. To
slabs for distribution ducts for heating, air-condition­
achieve uniform lighting free from distracting, shad­
ing, or exhaust systems. In stemmed members three
ows, the lighting system should parallel the stems of
sides of the duct are provided by the bottom of the
tee members.
flange and the sides of the stems. The bottom ofthe
By using a reflective paint and properly spaced
duct is completed by attaching a metal panel to the
high-output florescent lamps installed in a continu­
tee stems in the same fashion as the lighting diffusers
ous strip, the designer can achieve a high level of illu­
(see Figure 9.10.1).
mination at a minimum cost. In special areas, lighting
Connections can be made by several means,
troffers can be enclosed with diffuser panels fastened
among them powder-activated fasteners, cast-in in­
to the bottom of the tee stems providing a flush ceiling
serts or reglets. Field installed devices generally offer
(see Figure 9.10.1). By using reflective paints, these
the best economy and ensure placement in the exact
precast concrete lighting channels can be made as
location where the connecting devices will be re­
efficient as conventional florescent fixtures.
quired. Inserts should only be cast-in when they can
be located in the design stage of the job, well in ad­
vance of casting the precast members.
9.10.3 Electrified Floors With hollow-core slabs, additional duct work can
be eliminated. These members have oval, round, or
The increasing use of office machines, computer rectangular voids of varying size which can provide
networks, telephones, and other communication sys­ ducts or raceways for the various systems. Openings
tems stresses the need for adequate and flexible core drilled in the field can provide access and dis­
means of supplying electricity and communication tribution. The voids in the slabs are aligned and con­
service. Since a cast-in-place topping is usually nected to provide continuity of the system. Openings
placed on prestressed floor members, conduit runs can also be provided in intermediate supporting
and floor outlets can be readily buried within this top­ beams such as inverted tees, to allow duct continuity.
ping. Burying conduits in toppings of parking struc­ If high velocity air movement is utilized, the en­
tures is not recommended because of the possibility closed space becomes a long plenum chamber with
of conduit corrosion. With shallow height electrical uniform pressure throughout its length. Diffusers are
systems, a comprehensive system can be provided installed in the ceiling to distribute the air. Branch
in a reasonably thin topping. The total height of con­ runs, when required, can be standard ducts installed
duits for these comprehensive electrical systems is along the column lines.
as little as 1% in. Most systems can easily be included When ceilings are required, proper selection of
in a 2 to 4 in. thick slab. Voids in hollow-core slabs can precast components can result in shallow ceiling
also be used as electrical raceways (see Figure spaces to accommodate required ducts, piping and
9.10.2). lighting fixtures.

9 -6 8 PCI Design Handbook/Rfth Edition


Figure 9.10.1 Metal panels C a c h e d at the bottoms of the stems-create ducts, and diffuser panels
provide a flash ceiling

PCI Design Handbook/Fifth Edition 9 -6 9


Branch ducts of moderate size can also- be ac­ not react with the concrete. Tt should be noted that
commodated by-providing block-outs in therstems of repetition is one of the real keys to economy in a pre­
teesorbeams. To achieve “best economy and perfor- cast concrete wall assembly. Windows and doors
manee-in prestressed concrete members, particular­ should be located in identical places for all panels,
ly stemmed members, such block-outs should be re­ wherever possible.
peated in size and location to handle- all conditions Insulated wall panels can be produced by embed-
demanded by mechanical, electrical or plumbing ding an insulating material such as expanded poly-
runs. While this may lead to slightly larger openings in urethane between layers of concrete. These "sand­
some cases, the end result will probably be more wich panels” are described in detail in Sect. 9.4.
economical. It should also be noted that sufficient tol­ Sandwich panels are normally cast on fiat beds or tilt­
erance should be allowed in sizing the openings to ing tables. The inside surface of the concrete panel
provide the necessary field assembly considerations can be given a factory troweled finish followed by mi­
(see Chapter 8>. nor touch up work. The interior face is completed by
Prestressed concrete box girders have been used painting, or by wall papering to achieve a finished
to serve a triple function as air conditioning distribu­ wall. The formed surface of the panel can also be
tion ducts, conduit for utility lines and structural sup­ treated in a similar manner when used as the interior
porting members forthe roof deck units. Conditioned face.
air can be distributed within the void area of the gird­
ers and then introduced into the building work areas 9.10.6 Systems Building
through holes cast into the sides and bottoms of the As more and more complete systems buildings
box girders. The system is balanced by plugging se­ are built with precast and prestressed concrete, and
lected holes. as interest in this method of construction increases,
Vertical supply and return air trunks can be carried we can expect that more of the building sub-systems
in the exterior walls, with only small ducts needed to will be prefabricated and pre-coordinated with the
branch out into the ceiling space. In some cases the structure.
exterior waH cavities are replaced with three or four This leads to the conclusion that those parts of the
sided precast boxes stacked to provide vertical runs structure that require the most labor skills should log­
for the mechanical and electrical systems. These ically be prefabricated prior to installation in the field.
stacked boxes can also be used as columns or lateral
The prefabricated components can be pre­
bracing elements for the structure.
assemblies of basic plumbing systems or electrical/
In some cases it may be required to provide open­
mechanical systems plus lighting.
ings through floor and roof units. Large openings are
For housing systems, electrical conduits and
usually made by blockouts in the forms during the
boxes can be cast in the precast wall panels. This
manufacture; smaller ones (up to about 8 in.) are usu­
process requires coordination with the electrical con­
ally field drilled. When field drilling, care must be tak­
tractor; and savings on job-site labor and time are
en not to cut prestressing strand. Openings in flanges
possible. The metal or plastic conduit is usually pre­
of stemmed members should be limited to the “flat”
bent to the desired shape and delivered to the casting
portion of the flange, that is, beyond 1 in. of the edge
bed already connected to the electrical boxes. It is es­
of the stem on double tees. Angle headers are often
sential that all joints and connections be thoroughly
used for framing large openings in hollow-core floor
sealed and the boxes enclosed prior to casting in or­
or roof systems (see Figure 9.10.3).
der to prevent the system from becoming clogged.
9.10.5 Other Sub-Systems The wires are usually pulled through at the job site.
Television antennae and telephone conduits have
Suspended ceilings, crane rails, and other sub­
systems can be easily accommodated with standard also been cast-in using the same procedure.
To reduce on-site labor, prefabricated bathroom
manufactured hardware items and embedded plates
as shown in Figure 9.10.4. units or combination bathroom/kitchen modules
Architectural precast wall panels can be adapted have been developed (see Figure 9.13.5). Such units
to combine with pre-assembled window or door include bathroom fixtures, kitchen cabinets and
units. Door or window frames properly braced to pre­ sinks, as well as wall, ceiling, and floor surfaces.
vent bowing during concrete placement, can be cast Plumbing units are often connected and as­
in the panels and then the glazing or doors can be sembled prior to delivery to the job sites. These bath­
installed prior to or after delivery to the jo b site. If the room/kitchen modules can be molded plastic units or
glazing or doors are properly protected, they can also fabricated from drywall components. To eliminate a
be cast into the panel at the plant. When casting in double floor, the module can be plant built on the
aluminum window frames, particular attention should structural member or the walls of the unit can be de­
be made to properly coat the aluminum so that it will signed strong enough for all fixtures to be wall hung.

9 -7 0 PCI Design Handbook/Fifth Edition


Figure 9.10.4 Methods of attaching suspended ^ceiiings, crane rails, and othersub-systems

cated in a stack fashion with one bathroom directly up to each other, since a common vertical run can
over the one below. A block-out for a chase is pro­ service two bathrooms.
vided in the precast floor and connections are made Some core modules not only feature bath and
from each unit to the next to provide a vertical plumb­ kitchen components, but also HVAC components
ing stack. Prefabricated wet-wall plumbing systems, which are all packaged in one unit. These modules
as shown in Figure 9.10.6, incorporate pre-as- can also be easily accommodated in prestressed
sembied piping systems using snap-on or no-hub structural systems by placing them directly on the
connections made up of a variety of materials. These prestressed members with shimming and grouting
units only require a block-out in the prestressed floor- as required.

PCI Design Handbook/Fifth Edition 9 -7 1


Figure 9,10.5 Kitchen/bathcoom modules can be pre-assembted on precast slabs readyior installa­
tion in systems buildings___________________________________________________

PCI Design Handbook/Fifth Edition


9 -7 2
9.10.7 Prison-Cell Box Module Figure9.!0.7 Precast concrete modular 2-cetl
_____ box unit for prison construction
Prisons represent a building typaihat makes max­
imum use-of the-systems btaiJxding and subsystems
coordination concepts. Modular precast concrete
boxes, typically multi-cell units, generally consist of
cell walls, chasewalfs and a floor or ceiling (see Fig­
ure 9,10.7}. All components of each cell— windows,
beds, mirrors, desks, air vents, light fixtures, sinks,
water closets and d o o rs— are completely installed in
each module atthe manufacturer’s plant. Erection at
the site is rapid and field work is greatly reduced lead­
ing to a safe, functional, and economical prison facili­
ty in the shortest time of construction.

PCI Design Handbook/Rfth Edition


9 -7 3
PCI Design Handbook/Fifth Edition
9 -7 4
CHAPTER tO
SPECIFICATIONS AND STANDARD
PRACTICES
10.1 Guide Specification for Precast, Prestressed Concrete ............................... 10-2

10.2 Guide Specification for Architectural Precast C oncrete................. 10-13

10.3 Code of Standard Practice for Precast Concrete ......................................... 10-32

10.4 Recommendations on Responsibility for Design and


Construction of Precast Concrete Structures .............................................. 10-43

10.5 PCI Standard Design Practice ..................................................... .................. 10-49

PCI Design Handbook/Fifth Edition


1 0 -1
10.1 GUIDE SPECIFICATION FOR
PRECAST, PRESTRESSED CONCRETE
This Guide^Specification is intendedto be used as a basisfor the d e ve lo p m e n ts
an office master specification o rin th e preparation of specifications for a particular
prefect Tn either case, this GuideSpecification most be edited to fit the conditions of
use.
P a rtic u la r a tten tio n s h o u ld b e g iv e n t o th e d e le tio n o f in a p p lic a b le p ro v is io n s .
Necessary items related to a particular project should be included. Also, appropriate
requirements should be added where blank spaces have been provided.
The Guide Specifications are on the le f t N o t e s t o S p e c if ie r s a r e o n t h e r ig h t .

GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

1. GENERAL

1.01 Description

A. Work included: 1.01.A This Section is to be in Division 3 o f Con­


struction Specifications Institute format. Verify that
1 . These specifications cover precast and
plans clearly differentiate between this work and
precast, prestressed structural concrete
construction, including product design not architectural precast concrete if both are on the
shown on contract drawings, manufacture, same job. One may need to list items such as
transportation, erection, and other related beams, purlins, girders, lintels, columns, slab or
items such as anchorage, bearing pads, deck members, etc. Some items such as pre­
storage and protection of precast concrete. stressed wall panels could be included in either this
or the Specification for Architectural Precast Con­
crete, depending on the desired finish and tolerance
expectation.

B. Related work specified elsewhere:

1. Cast-in-place concrete: Section__

2. Architectural precast concrete:


Section______ .

3. Post-tensioning: S ection_____ .

4. Masonry bearing walls: Section__

5. Structural steel: Section______ .

6. Miscellaneous steel: Section____

7. Waterproofing: Section______ .

8. Flashing and sheet metal: Section

9. Sealants and caulking: Section__

10. Painting: Section______ .

11. Openings for other trades: Section

1 0 - 2 PCI Design Handbook/Fifth-Edition


GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

C. -Work- installed butfumished by others:

1. Receivers or reglets-for flashing:


Section______ .

2. Elevator guides: S e ctio n ______ .

3. Inserts for ties to masonry or stonework:


Section______ .

4. Sleeves and imbedded items for plumbing,


heating or electrical distribution: Section

1.02 Quality Assurance


A. Manufacturer qualifications: 1.02. A Groups and categories: (B1, B2, B3, orB4),
The precast concrete manufacturing plant (C1, C2, C3, or C4). See Sect. 9.5 for definitions.
shali be certified by the Precast/Prestressed Affix the suffix A to the product group and category,
Concrete institute Plant Certification Program. e.g., C3A, if the structural product requires the
Manufacturer shall be certified at the time of application o f an architectural finish produced by a
bidding. Certification shall be in the following manufacturer with special architectural qualifica­
product groups and categories:___________
tions. Structural precast products must meet the
requirements o f PCI Manual, MNL-116. These
products should not be expected to meet the
requirements of MNL-117 for architectural precast
concrete products. However, structural products
may have the application o f architectural finishes
included in the provisions of MNL-116. Manufactur­
ers that have certified architectural qualifications to
apply these finishes have the suffix A added to their
certification listing.

B. Erector qualifications: 1.02. B Usually 2 to 5 years.


Regularly engaged for at least______ years in
the erection of precast structural concrete
similar to the requirements of this project.

C. Welder qualifications: 1.02.C Certified within the past year.


In accordance with AWS D1.1.

D. Testing:
In general compliance with testing provisions
fn MNL-116, Manual for Quality Control for
Plants and Production o f Precast and Pre­
stressed Concrete Products.

E. Requirements of regulatory agencies: 1.02.E Always include the specific year edition of
All local codes plus the following specifica­ the specifications, codes and standards used in the
tions, standards and codes are a part of these design o f the project and made part of the
specifications: specifications.

PCI Design Handbook/Fifth Edition


10 -3
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

T. AGI 318— Building Code Requirements, for F o tp re je ctsin Canada, standards from the Cana-
Structural Concrete. d im Standards Association should be listed in
addition-to, o r in piece o fth e US. Standards. Fire
2. AWS D 1.1—Structural Welding C o d e -
Steel. ratings are generally a code requirement. When
required, fire-rated products should be clearly
3. AWS D1.4—Structural Welding Code— identified on the design drawings.
Reinforcing Steel.
4. ASTM Specifications—As referred to in
Sect. 2. Products, of this Specification.

5. AASHTO—Standard Specifications for


Highway Bridges.
6 . CRSI— Manual of Standard Practice.

1.03 Submittals

A. Shop drawings:

1. Erection drawings:

a. Member piece marks and completely di­


mensioned size and shape of each
member.

b. Plans and/or elevations locating and de­


fining all products furnished by
manufacturer.

c. Sections and details showing connec­


tions, cast-in items and their relation to
the structure.

d. Relationship to adjacent material. 1.03A 1.d Details, dimensional tolerances and re­
lated information of other trades affecting precast
concrete work should be furnished to the precast
concrete manufacturer.

e. Joints and openings between members


and between members and structure.

f. Description of all loose, cast-in and field


hardware.

g. Field installed anchor location drawings.

h. Erection sequences, when required to 1.03.A.1.h If the sequence of erection is critical to


satisfy stability, and handling require­ the structural stability ofthe structure, or for access
ments. to connections at certain locations, it should be
noted on the contract plans and specified.

i. All dead, live and other applicable loads


used in the design.

1 0 -4 PCI Design Handbook/Fifth Edition


GtflOE SPECIFICATIONS NOTES TO SPECIFIERS

2. Production drawings:- 1.03.A . 2 Production drawings- a re n o rm a JJ y -S u b -


m'rtted only upon request
a. Elevation view-of each member.

b. Sections and details to indicate quanti­


ties and_position of reinforcing steel, an-
chors, inserts, etc.

c. Handling devices.

d. Dimensions and finishes.

e. Prestress for strand.

f. Concrete strengths.

g. Estimated cambers.

h. Methods for storage and transportation.

B. Product design criteria: 1.03.B and C The contract drawings normally will
be prepared using a local precast, prestressed
1. Loadings for design: concrete manufacturer's design data and toad
tables. Dimensional changes that would not materi­
a. Initial handling and erection stress lim­ ally affect architectural and structural properties or
its. details are usually permissible.
Most precast, prestressed concrete is cast in
b. All dead and iive toads as specified on continuous steel forms, therefore connection de­
the contract drawings. vices on the formed surfaces must be contained
within the member since penetration o f the form is
c. All other loads specified for member, impractical. Camber will generally occur in pre­
where applicable.
stressed concrete members having eccentricity o f
the stressing force. If camber considerations are
2. As directed on the contract drawings,
important, check with local prestressed concrete
design calculations of products shall be
manufacturer to secure estimates o f the amount of
performed by a registered engineer experi­
camber and o f camber movement with time and
enced in precast, prestressed concrete
temperature change. Architectural details must
design and submitted for approval upon
recognize the existence of camber and camber
request.
movement in connection with:
3. Design shall be in accordance with applica­ 1. Closures to interior non-load bearing partitions.
ble codes, ACI 318 or AASHTO Standard 2. Closures parallel to prestressed concrete
Specifications for Highway Bridges. members (whether masonry, windows, curtain
walls or others) must be properly detailed for
C. Permissible design deviations: appearance.
3. Floor slabs receiving cast-in-place topping.
1. Design deviations will be permitted only
The elevation o f top of floor and amount of
after the architect/engineer’s written ap­
concrete topping must allow for camber of
proval of the manufacturer’s proposed
design supported by complete design prestressed concrete members.
calculations and drawings. Designing for cambers less than obtained under
normal design practices is possible, but this usually
2. Design deviations shall provide an installa­ requires the addition o f tendons or non-prestressed
tion equivalent to the basic intent without steel reinforcement and price should be checked
incurring additional cost to the owner. with the local manufacturer.

PCI Design Handbook/Fifth Edition


10-5
GUIDE SPECIFICATIONS^ NOTES TO SPECIFIERS

As the exact cross section o f precast, prestressed


concrete members m ight -vary somewhat from
producer to producer, permissible deviations in
member shape from that shown on- the contract
drawings might enable more manufacturers to quote
on the project. Manufacturing procedures also vary
between plants and permissible modifications to
connection details, inserts, etc., will allow the
manufacturer to use devices he can best adapt to his
manufacturing procedure.

Be sure that loads shown on the contract drawings


are easily interpreted. For instance, on members
which are to receive concrete topping, be sure to
state whether all superimposed dead and live loads
on precast, prestressed members d o or do not
include the weight of the concrete topping.

It is best to list the live load, superimposed dead


load, topping weight, and weight of the member, aII
as separate loads. Where there are two different live
loads (e.g., roof level of a parking structure) indicate
how they are to be combined.

D. Test reports:

Reports of tests on concrete and other


materials upon request.

1.04 Product Delivery, Storage, and Handling

A. Delivery and handling:

1 . Precast concrete members shall be lifted


and supported during manufacturing,
stockpiling, transporting and erection op­
erations only at the lifting or supporting
points, as shown on the shop drawings,
and with suitable lifting devices. Lifting
inserts shall have a minimum safety factor
of 4. Reusable lifting hardware and rigging
shall have a minimum safety factor of 5.

2. Transportation, site handling, and erection


shall be performed with acceptable equip­
ment and methods, and by qualified per­
sonnel.

B. Storage:

1 . Store all units off ground.

2. Place stored units so that identification


marks are discernible.

3. Separate stacked members by battens


across full width of each bearing point.

1 0 -6 PCI Design Handbook/Rfth Edition


GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

4 Stack so that lifting devices are accessible


and undamaged.

5. Do not use uppermember of stacked tier as


storage area for shorter member o r heavy
equipment.

2. PRODUCTS

2.01 Materials 2.01 Delete or add materials that may be required


for the particular job.

A. Portland cement:

1. ASTM C 150—Type I or 111.

B. Other cementitious materials: 2.01.B Selection and use of these cementitious


1. Fly ash or natural pozzolans: ASTM C 618. materials in the concrete m ix should be left to the
precast concrete manufacturer subject to approval
2 . Groundgranulated blast furnace slag: by the architect/engineer. The use of fly ash and/or
ASTM C 989. silica fume may affect the color o f the finished
3. Silica fume: ASTM C t240. concrete.

C. Admixtures:

1. Air-entraining admixtures: ASTM C 260.

2. Water reducing, retarding, accelerating,


high range water reducing admixtures:
ASTM C 494 or C 1017.

3. Calcium chloride or admixtures containing 2.01.C.3 Admixtures containing any chloride, other
chlorides shall not be used. than impurities from admixture ingredients, are not
to be used in prestressed concrete.

D. Aggregates:

1. ASTM C 33 or C 330.

E. Water:

Potable (see ACI 318).

F. Reinforcing steel:

1. Bars: 2.01.F.1 When welding of bars is required, weld­


ability must be established to conform to AWS D1.4.
a. Deformed billet-steel: ASTM A 615. Bending of bars and bar details should conform to
b. Deformed low-alloy steel: ASTM A 706. CRSI Manual of Standard Practice.

c. Galvanized reinforcing bars:


ASTM A 767.

d. Epoxy coated reinforcing bars:


ASTM A 775.

2. Wire:

a. Plain: ASTM A 82.

b. Deformed: ASTM A 496.

PCI Design Handbook/Fifth Edition


10 -7
GUtDFSPECIFICATIONS NOTES TO SPECIFIERS

3: Welded wire reinforcement"

-a. Welded plain steel: ASTM A 185.

b. Welded deformed steel: ASTM A 497.

4. Coatings;

a. Epoxy bars: ASTM A 775.

b. Galvanized bars: ASTM A 767.

c. Epoxy welded wire reinforcement:


ASTM A 884.

G. Strand:

1. Uncoated, 7-wire strand:


ASTM A 416—Grade 250 or 270;

H. Anchors and inserts:

1. Materials:

a. Structural steel: ASTM A 36.

b. Malleable iron castings: ASTM A 47. 2.01.H. 1.b Usually specified by type and manufac­
turer.

c. Stainless steel: ASTM A 666, Type 304.

d. Carbon steel plate: ASTM A 283.

e. Bolts: ASTM A 307 or A 325.

f. Welded headed studs:


AWS D1.1—Type B.

g. Deformed bar anchors: ASTM A 496 or


A 706.

2. Finish:

a. Shop primer: Manufacturer’s standards.

b. Hot dipped galvanized: ASTM A 123.

c. Zinc-rich coating: DOD-P-21035, self For galvanized repair use high zinc-dust
2 .0 1 .H .2 .C
curing, one component, sacrificial. content paint with dry film containing not less than
94% zinc dust by weight and complying, with
DOD-P-21035A o r SSPC paint 20.

d. Cadmium coating: ASTM B 766.

10-8 PCI Design Handbook/Fifth Edition


GUIDESPECIFICATtONS NOTES TO SPECIFIERS

Groutr 2:01.1 Indicate required strengths on contractdraw-


ings.
1. Cement grout: Portland-eement, sand, and
water sufficient for placement and hydra­
tion.

2. Non-shrink grout: Premixed, packaged 2.01.1.2 Non-ferrous grouts with a gypsum base
ferrous o r non-ferrous aggregate shrink-re­ should not be exposed to moisture. Ferrous grouts
sistant grout. should not be used where possible staining would
be undesirable. Non-shrink grouts are normally not
used or required in the keyed joints between
hollow-core floor and roof systems or hollow-core
wall panels.

3. Epoxy-resin grout: Two-component miner­ 2.01.1.3 Check with local suppliers to determine
al-filled epoxy-resim ASTM C 881 or FS availability and types o f epoxy-resin grouts.
MMM-A-001993.

Bearing pads:

1. Chloroprene (Neoprene): Conform to Divi­ 2.01. J. 1 AASHTO grade pads utilize 100 % chloro­
sion II, Sect. 18 of AASHTO Standard prene as the elastomer. Less expensive commercial
Specifications for Highway Bridges. grade pads are available, but are not recom­
mended.

2. Random oriented fiber reinforced: Shall 2.01. J.2 Standard guide specifications are not
support a compressive stress of 3000 psi available for random oriented, fiber reinforced pads.
with no cracking, splitting or delaminating Proof testing o f a sample from each group of 200
in the internal portions of the pad. pads is suggested. Normal service load stresses are
1500 psi, so the 3000 psi test load provides a factor
o f 2 over service load stress. The shape factor forthe
test specimens should not be less than 2. If
adequate test data are provided by the pad supplier,
further proof testing may not be required.

3. Duck layer reinforced: Conform to Division


II, Sect. 18.10.2 of AASHTO Standard
Specifications for Highway Bridges or Mili­
tary Specification MIL-C-882D.

4. Plastic: Multimonomer plastic strips shall be 2.01. J.4 Plastic pads are widely used with concrete
non-leaching and support construction plank. Compression stress in use is not normally
loads with no visible overall expansion. over a few hundred psi and proof testing is not
considered necessary. No standard guide specifi­
cations are available.

5. Tetrafluoroethylene (TFE): Reinforced with 2.01. J.5 ASTM D 2116 applies only to basic TFE
glass fibers and applied to stainless or resin molding and extrusion material in powder or
structural steel plates. pellet form. Physical and mechanical properties
must be specified by naming manufacturer or other
methods.

PCI Design Handbook/Fifth Edition


1 0 -9
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

2.02 ConcreteJIflixes

A. 28-day compressive strength: Minimum o f- 2:02.A and B Verify with fecal manufacturer. 5000
psi. psi for prestressed p r o d u c ts normalpractice^with
B. Release strength: Minimum o f __________ release strength of3590psi. High strength concrete
psi. is generally concrete o f strength greater than 8 0 0 0
psi. Although conventional strength tests are taken
at 28 days, high strength concretes may be
evaluated for strength at 56 or 90 days. Testing of
high strength concrete shall be with 4 x 8 in.
cylinders. Cubes are not appropriate for high
strength concrete testing.

2.03 Manufacture

A. Manufacturing procedures shall be in general


compliance with PCI MNL-116.

B. Manufacturing tolerances shall comply with


PCI MNL-116.

C. Finishes:

1. Standard underside: Resulting from cast­ 2.03. C. 1 Other formed finishes that may be speci­
ing against approved forms using good fied are:
industry practice in cleaning of forms, Commercial Finish. Concrete may be produced in
design of concrete mix, placing and curing.
forms that impart a texture to the concrete (e.g.,
Small surface holes caused by air bubbles,
plywood or lumber). Fins and large protrusion shall
normal color variations, normal form joint
be removed and large holes shall be filled. All faces
marks, and minor chips and spalls shall be
shall have true, well-defined surfaces. Any exposed
tolerated, but no major or unsightly imper­
ragged edges shall be corrected by rubbing or
fections, honeycomb, or other defects shall
be permitted. grinding.
Grade B Finish. All air pockets and holes over 1A in.
in diameter shall be filled with a sand-cement paste.
All form offsets or fins over Vs in. shall be ground
smooth.
Grade A Finish. In addition to the requirements for
Grade B Finish, all exposed surfaces shall be coated
with a neat cement paste using an acceptable float.
After thin pastecoat has dried, the surface shall be
rubbed vigorously with burlap to remove loose
particles. These requirements are not applicable to
extruded products using zero-slump concrete in
their process.

2 . Standard top: Result of vibrating screed 2.03. C.2 Other unformed finishes that may be
and additional hand finishing at projec­ specified are smooth, hard trowel finish, or scarified
tions. Normal color variations, minor in­ surface finish, using a rake or wire brush, for greater
dentations, minor chips and spalls shall be bond, if required, with composite topping.
permitted. No major imperfections, honey­
comb, or defects shall be permitted.

3. Vertical ends: When exposed to view, 2.03.C.3 When not exposed to view, normal plant
strands shall be recessed a minimum of V2 practice is to cut strands flush and coat the ends of
in., the holes filled with grout and the ends the member with bitumastic.
of the member shall receive sacked finish.

1 0-10 PCI Design Handbook/Fifth Edition


GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

4. Gpecial: finish: If required, listed as follows: 2.03.0.4 Special finishes (e.g., sandblasted -or
bashhammered), i f required, should be described"
in this section o f the specifications end noted on the
contract drawingsr pointing out which members
require sp ecial finish. Such finishes will involve
-additional cost and consultation with the manufac­
turer is recommended. A sample o f such finishes
should be made available for review prtor to bidding.

D. Openings: 2.03.D This paragraph requires overtrades to field


drill holes needed for their work, and such trades
Primarily on thin sections, the manufacturer shouldbealertedto thisrequirement through proper
shall provide for those openings 10 in. round
notation in their sections of the specifications. Some
or square or larger as shown on the structural
manufacturers prefer to install openings smaller
drawings. Other openings shall be located and
field drilled or cut by the trade requiring them than 10 in. which is acceptable if their locations are
after the precast, prestressed concrete prod­ properly identified, on the contract drawings.
ucts have been erected. Openings shall be
approved by the architect/engineer before
drilling or cutting.

E. Patching:

Shall be acceptable providing the structural


adequacy of the product and the appearance
are not impaired.

F. Fasteners: 2.03.F Exclude this requirement from extruded


products.
Manufacturer shall cast in structural inserts,
bolts and plates as detailed or required by the
contract drawings.

3. EXECUTION

3.01 Erection

A. Site access:

General contractor shall be responsible for


providing suitable access to the building,
proper drainage and firm, level bearing for the
hauling and erection equipment to operate
under their own power.

B. Preparation: 3.01.B Construction tolerances for cast-in-place


General contractor shall be responsible for: concrete, masonry, etc., should be specified in
T. Providing true, level bearing surfaces on all those sections o f the specifications.
field placed bearing walls and other field
placed supporting members.

2. Placement and accurate alignment of an­


chor bolts, plates or dowels in column
footings, grade beams and other field
placed supporting members.

3. All shoring required for composite beams


and slabs.

PCI Design Handbook/Fifth Edition


10-11
GUIDE SPECIFICATIONS NOTES TO SPEC10ERS

C. Installation:
Installation o f precast, prestressed concrete
shall be performed by the manufacturer or a
competent erector. Members shall be-lifted by^
means of suitable lifting devices at points
provided by the manufacturer. Temporary
shoring and bracing, if necessary, shall comply
with manufacturer’s recommendations.

D. Alignment: 3.01.D The following erection tolerance may be


Members shall be properly aligned and leveled specified if other requirements- do not control:
as required by the approved shop drawings. Individual pieces are considered plumb, level and
Variations between adjacent members shaH be aligned if the error does not exceed 1:500 excluding
reasonably leveled out by jacking, loading, or structural deformations caused by loads.
any other feasible method as recommended
by the manufacturer and acceptable to the
architect/engineer.

3.02 Reid Welding

A. Field welding is to be done by certified welders


using equipment and materials compatible
with the base material.

3.03 Attachments

A. Subject to approval of the architect/engineer,


precast, prestressed concrete products may
be drilled or “shot” provided no contact is
made with the prestressing steel. Should spal­
ling occur, the repair of the spall shall be the re­
sponsibility of the trade doing the drilling or the
shooting.

3.04Jnspection and Acceptance

A. Final inspection and acceptance of erected


precast, prestressed concrete shall be made
by the architect/engineer within a reasonable
time after the work is completed.

1 0-12 PCI Design Handbook/Fifth Edition


10.2 GUIDE SPECIFICATION FOR
ARCHITECTURAL PRECAST CONCRETE
ThisGuide Specification is intended to be used as aJrasisTor the development of
an office master specificatiorrorin the preparation of specifications for a particular
project. In either case, thisiGuide Specification must be edited to fit the conditions of
use.
Particular attention should be given to the deletion of inapplicable provisions.
Necessary items related to a particular project should be included. Also, appropriate
requirements should be added where blank spaces have been provided.
The Guide Specifications are on the left. N o t e s t o S p e c if ie r s a r e o n t h e r ig h t .

GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

1. GENERAL

1.01 Description

A. Work included: 1.01.A Local standard practice may indicate that


responsibility for erection may not be included.

1. The specifications establish general criteria


for materials, production, erection and
evaluation of precast concrete as required
for subsequent related sections of these
specifications. The work to be performed
shall include all labor, material, equipment,
related services, and supervision required
for the manufacture and erection of the
architectural precast concrete units shown
on the contract drawings and schedules.

B. Related work specified elsewhere:

1. Concrete reinforcement: Section 1.01. B.1 Architectural precast concrete reinforcing


steel requirements are different from cast-in-place
reinforcement and should be specified in this
section.

2 . Cast-in-place concrete: Section 1.01. B.2 For placement o f anchorage devices in


cast-in-place concrete for precast concrete panels.

3. Precast, prestressed concrete: 1.01. B.3 For precast floor and roof slabs, beams,
S ection_____ . columns and other structural elements. Seme items,
such as prestressed waH paneis on industrial
buildings, could be included in either specification,
depending on the desired finish and tolerance
expectation.

4. Structural steel framing: Section 1.01. B.4 Forsteei supporting structure, attachment
o f anchorage devices on steel for precast concrete
panels, and sometimes loose anchors.

5. Water repellent coatings: Section 1.01. B.5 For exposed face o f panels. Delete when
specified in this section.

PCI Design Handbook/Fifth Edition


10-13
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

6, Insulation: Section 1.01. Bt5 Forinsulation that is job-applied to-precast


concrete-panels. Insulationcast in precast concrete
panels daring manufacture -should be specified in
this section.

7. Flashing and sheet metal: Section _ 1.01. B .7 For counterflashmg inserts and receivers,
unless included in this section.

8. Sealants and caulking: Section___ 1.01. B.8 For panel joint caulking and sealing.

9. Painting: Section_____ . 1.01. B .9 For field touch-up painting. Delete when


specified in this section.

10. Glass and glazing: Section_. 1.01. B. 10 For glazing o f precast concrete panels in
plant. Delete when specified in this section.

11. Glazing accessories: Section____ 1.01. B.11 For reglets used with structural glazing
gaskets. Delete when specified in this section.

C. Work installed but furnished by others: 1.01. C Delete when furnished by precast concrete
manufacturer. A d d additional items as may be
required for the particular project.

1. Counterflashing receivers or reglets:


Section_____ .

2. Inserts or attachments fo r_______ 1.01. C.2 M ay include insertsjattachments for win­


Section_____ . dow or door frames, window washing equipment,
etc.

D. Testing agency provided by owner. 1.01. D Delete when testing agency is provided by
precast concrete manufacturer or general contrac­
tor. Coordinate with appropriate section of Division
1, General Conditions.

1.02 Quality Assurance

A. Manufacturer qualifications: 1.02.A Groups and categories: (At), (AT), (G). See
The precast concrete manufacturing plant Sect. 9.5 for definitions. It is recommended that the
shall be certified by the Precast/Prestressed architect approve individual precast concrete
Concrete Institute Plant Certification Program. manufacturers who m eet the Quality Assurance
Manufacturer shall be certified at the time of Specification at least ten days prior to the bid date,
bidding. Certification shall be in the following or identify approved manufacturers in the specifica­
product groups and categories:_________ . tion. It is not appropriate to specify structural
**OR** products with architectural finishes in this section.
Acceptable manufacturers:
1. _________________________________________________________

2.

B. Erector qualifications: 1.02.B Usually 2 to 5 years.


Regularly engaged for at least______ years in
erection of architectural precast concrete units
similar to those required on this project.

C. Welder qualifications: 1.02.C Certified within the past year. Delete when
In accordance with AWS D1.1. welding is not required.

1 0 -1 4 PCI Design Handbook/Fifth Edition


GUIDE SPECIFICATIONS NOTES-TO SPECIFIERS^

D. Testing:

In general compliance with testing provisions


in MNL-117, Manual for Qualify Control for
Plants and Production of ArchitecturalPrecast
Concrete-Products.

E. Testing agency: 1.02. E Delete when provided by owner.

1. Not less th a n _____ years experience in 1.02. E. 1 Usually 2 to 5 years.


performing concrete teste of type specified
in this section.

2. Capable of performing testing in accor­


dance with ASTM E 329.

3. Inspected by Cement and Concrete Refer­


ence Laboratory of the National Institute of
Standards and Technology.

F. Requirements of regulatory agencies: 1.02. F Local building code or other governing code
relating to precast concrete. For projects in Canada,
Manufacture and installation of architectural standards from the Canadian Standards Association
precast concrete to meet requirements of should be listed in addition to o r in place o f the U.S.
standards.

G. Allowable tolerances: 1.02. G Dimensional tolerances apply to both manu­


facturing and after manufacturing. The tolerances
1. Manufacture and install wall panels so that
each panel after erection complies with the listed in PC I M N L -117 are also listed in Chapter 8 of
dimensional tolerances listed in MNL-117. this Handbook. M ost manufacturers can m eet closer
tolerances, if required, but closer tolerances nor­
mally increase costs. The normal tolerances of the
support system should also be recognized.

H. Job mockup:

1. After standard samples are accepted for 1.02. H.1 Full-scale samples or inspection of the
color and texture, submit full-scale unit first production unit are normally required, especial-
meeting design requirements. lywhen a new design concept or new manufacturing
process or other unusual circumstance indicates
that proper evaluation cannot otherwise be made. It
is difficult to assess appearance from small sam­
ples.

2. Mockup to be standard of quality for 1.02. H .2 Use to determine range o f acceptability


architectural precast concrete work, when with respect to color and texture variations, surface
accepted by architect/engineer. defects and overall appearance. Mockup should
also serve as testing areas for remedial work. It
should also be stated in the contract documents
who the accepting authority will be.

3. Incorporate mockup Into work in a location 1.02. H .3 Delete when mockup is not to be included
reviewed by architect/engineer after keep­ in work. State how long unit should be kept. Mockup
ing mockup in p la n t_____ for checking is normally incorporated in the building, at least for
purpose. production units.

PC! Design Handbook/Frfth Edition 1 0 -1 5


GUIDE SPECIFICATIONS N O TE S T O SPECIFIERS

L Source quality-control:

1. Quality control arid inspection procedures


to comply with applicable sections of MNL-
Tt7;

2. Water absorption test on unit shall be 1.02.1.2 Water absorption test is an early indication
conducted to accordance with MNL-117. o f weather staining (rather than-durability). Verify the
water absorption o f the proposed face mix. For
average exposures an d based upon normal weight
concrete (1 5 0 lbs p er cubic ft), water absorption
should not exceed 5% to 6% by weight. In order to
establish comparable absorption figures for all
materials, the current trend is io specify absorption
percentages by volume. The stated limits for
absorption would , in volumetric terms, correspond
to 12% to 14% for average exposures and 8% to 10%
for special conditions.

1.03 Submittals

A. Samples: 1.03. A Number o f samples and submittal proce­


dures should be specified in Division 1. All approved
samples should be initialed by the architect. Pre-bid
samples should be submitted a minimum of 10 days
prior to bid date.

1. Submit samples representative of finished 1.03. A1 If the back face of a precast concrete unit
exposed face showing typical range of is to be exposed, samples o f the workmanship,
color and texture prior to commencement color, and texture of the backing should be shown
of production. as well as the facing.

2. Sample size: Approximately 12 in. x 12 in.


and of appropriate thickness, representa­
tive of the proposed finished product.

B. Shop drawings: 1.03. B State the number o f copies required for


approval or whether reproducibles are required.
1. Erection drawings: Current practice usually calls for two prints an d one
reproducible o f shop drawings to be submitted for
approval. General contractor should expedite sub­
a. Member piece marks and completely di­
mittal with architect/engineer to conform with
mensioned size and shape of each
member. allotted shop drawing approval time shown on the
precast concrete supplier’s order acknowledgment.
When erection drawings contain all informatbn
b. Plans and/or elevations locating and de­
sufficient for design approval, production drawings,
fining all products furnished by
except for shape drawings, need not be submitted
manufacturer.
for approval, except in special cases. However,
record copies are frequently requested. Guidelines
c. Sections and details showing connec­
for the preparation o f drawings are given in the PCI
tions, cast-in items and their relation to
Drafting Handbook— Precast and Prestressed Con­
the structure.
crete, Second Edition, M N L -119-90.

d. Relationship to adjacent material. 1.03. B .1.d Details, dimensional tolerances and


related information o f other trades affecting precast
concrete work should be furnished to precast
concrete manufacturer.

1 0 -1 6 PCI Design Handbook/Fifth Edition


GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

e. Jointeand openings between members


and between members and structure.

f. Description of all loose, castdn and field


hardware.

g. Location, dimensional tolerances, and 1.03. B .1.g Drawings normally preparecLbyprecast


details of anchorage devices that are concrete manufacturer and provided to general
embedded in or attached to structure or contractor for work by other trades.
other construction.

h. Erection sequences, when required to 1.03. B.1.h If the sequence of erection is critical to
satisfy stability, and handling require­ the structural stability of the structure, or for access
ments. to connections at certain locations, it should be
noted on the contract plans and specified.

i. All dead, live and other applicable loads


used in the design.

2. Production drawings:

a. Member shapes (elevations and sec­


tions) and dimensions.

b. Sections and details to indicate quanti­


ties and position of reinforcing steel, an­
chors, inserts, etc.

c. Handling devices.

d. Finishes.

e. Joint and connection details.

f. Methods for storage and transportation.

3. Shape drawings:

For members with complex configurations,


complete dimensions and details that also
define mold shape.

C. Design calculations:

Submit, on request, structural design calcula­


tions performed by a registered engineer
experienced in the design of architectural
precast concrete.

D. Design modifications:

1. Submit design modifications necessary to


meet performance requirements and field
coordination.

2. Variations in details or materials shall not


adversely affect the appearance, durability
or strength of units.

3. Maintain general design concept without


altering size of members, profiles and
alignment.

PCI Design Handbook/Fifth Edition


1 0-17
GUIDE-SPECIFICATIONS NOTES TO SPECIFIERS

E. Test reports: 1.03.E The. num ber and/or frequency-of each type
-Submit, _on request, reports on materials, o f test should b e dearly stated in the specifications
compressive strength tests on -concrete and b y listing the required testing or by reference to
water absorption tests on units. appficablestandatds, such asR C I M N L -117. Sched­
ule o f required- tests, number of copies o f test
reports, an d how distributed are included in Testing
Laboratory Services, Section _____ .

1.04 Product Delivery, Storage, and Handling

A. Delivery and handling: 1.04. A Erector should coordinate arrival of precast


concrete units and provide for possible storage and
1. Deliver all architectural precast concrete for erection in a safe manner within the agreed
units to project site in such quantities and schedule and with due consideration for other
at such times to ensure continuity of trades. Handling procedures, including type and
erection. location o f fastenings, should normally b e left to the
2. Handle and transport units in a position precaster, but the fastening devices should be
consistent with their shape and design in located and identified on shop drawings.
order to avoid stresses which would cause
cracking or damage.

3. Lift orsupport units only at the points shown


on the shop drawings.

4. Race non-staining resilient spacers of even


thickness between each unit.

5. Support units during shipment on non­


staining shock-absorbing material.

6. Do not place units directly on ground.

B. Storage at jobsite: 1.04.B The ideal sequence of precast concrete


erection is the unloading of units directly to their

1. Store and protect units to prevent contact proper location on the structure without storing on
with soil, staining, and physical damage. the jobsite. If on-site storage is an absolute necessity
to enable the erector to operate at the speed
required to m eet the established schedule, leaving
2. Store units, unless otherwise specified, with
the precast concrete units on the trailer eliminates
non-staining, resilient supports located in
extra handling or possible damage caused by
same positions as when transported.
improper on-site storage techniques.

3. Store units on firm, level, and smooth


surfaces.

4. Place stored units so that identification


marks are discernible, and so that product
can be inspected.

1 0 -1 8 PCI Design Handbook/Rfth Edition


<3UtBE-SPEC!FI CATIONS NOTES TO SPECIFIERS

2. PRODUCTS
2.01 Materials^

A. Concretes

1. Portland cement

a. ASTM C 150, type____ , _____ color. 2.01. A.1.U Type; [/(General use)}, [///(High early
strength)]. Color: (gray), (white), (buff). Gray is
generally used for non-exposed backup concrete.
Finish requirements will determine color selected
for face mix.

b. For exposed surfaces use same brand, 2.61.A.1.b To minimize color variation. Specify
type, and source of supply throughout. source of supply when cotor shade is important

2. Cementitious materials: 2.01. A.2 Selection and use of these cementitious


a. Fly ash or natural pozzolans: ASTM C materials in the concrete mix should be left to the
618. precast concrete manufacturer subject to approval
b. Ground granulated blast furnace slag: by the architectlengmeer. The use offfy ash and/or
ASTM C 989. sHica fume may affect the color o f the finished
c. Silica fume: ASTM C 1240. concrete.

3. Air entraining agent: ASTM C 260. 2.01. A .3 Delete if air entrainment is not required.

4. Water reducing, retarding, accelerating, 2.01. AA Delete if water reducing , retarding, or


high range water reducing admixtures: accelerating admixtures are not required. Calcium
ASTM C 494 or C 1017. chloride, or admixtures containing significant
amounts of calcium chloride, should not be allowed.
The selection of the particular admixture(s) should
be left to the precast concrete manufacturer subject
to approval by the architectlengmeer.

5. Coloring agent: 2.01. A. 5 Investigate use o f naturally colored fine


aggregate in lieu of coloring agent. Delete if coloring
a. Synthetic mineral oxide. agent is not required.

b. Harmless to concrete set and strength. 2.01. A.5.b Consider effects upon concrete prior to
final selection.

c. Stable at high temperature.

d. Sunlight- and alkali-fast.

6. Face mix aggregates:

a. Provide fine and coarse aggregates for 2.01. A.6.a Approve or select the size, color and
each type of exposed finish from a single quality of aggregate to be used. Base choice on
source (pit or quarry) for entire job. They visual inspection of concrete sample and on
shall be clean, hard, strong, durable, assessment of certified test reports. Use same type
and inert, free of staining or deleterious and source of supply to minimize color variation.
material. Fine aggregate is not always from same source as
coarse aggregate.

b. ASTM C 33 or C 330. 2.01. A.6.b Grading requirements are generally wai­


ved or modified.

PCI Design Handbook/Fifth Edition 1 0 -1 9


GIHDESPECIFICAT10NS NOTES TO SPECIFIERS

c. Material andcolor: 2.01. A.6.C Specify type of stone desired such as


crushed marble, quartz, limestone, granite, or
locally available gravel as w ell as color Some
lightweight aggregates, limestones, and marbles
m ay not b e acceptable as facing aggregates. Omit
where sample is to be matched.

d. Maximum size and gradation:_____ . 2.01. A.6.d State required sieve analysis. Omit
where sample is to be matched.

7. Backup concrete aggregates: 2.01. A .7 Delete when architectural requirements


dictate that face mix be used throughout the unit
a. ASTM C 33-or C 330.

8. Water: Free from deleterious matter that 2.01. A.8 Potable water is ordinarily acceptable.
may interfere with the color, setting or
strength of the concrete.

B. Reinforcing steel:

t. Materials: 2.01. B.1 Grades o f reinforcing steel are deter­


mined by the structural design of the precast
concrete units. Panels are normally designed as
crack-free sections or with controlled cracking, thus
the benefit of higher grade steel is not utilized.

a. Bars: 2.01. B.1.a State uncoated, galvanized or epoxy


coated. Use galvanizing or epoxy coating only
where corrosive environment or severe exposure
conditions justify extra cost. Availability of galva­
nized or epoxy coated bars should be verified.

(1) Deformed steel:


ASTM A 615, grade 60.

(2) Weldable deformed steel: 2.01. B. 1.a(2) Availability should be checked. When
ASTM A 706. not available, establish weldability in accordance
with AWS D1.4.

(3) Galvanized reinforcing bars: 2.01. B. 1.a(3) Dam age to the coating as a result of
ASTM A 767. bending should be repaired with zinc-rich paint.

(4) Epoxy coated reinforcing bars: 2.01. B.1.a(4) Dam age to the coating as a result of
ASTM A 775. mishandling or field cutting should be repaired with
epoxy paint.

b. Welded wire reinforcement: 2.01. B.1.b Should be sheets, not rolls. State un­
coated, galvanized or epoxy coated. Use galvaniz­
ing or epoxy coating only where corrosive environ­
ment or exposure conditions justify extra cost.

(1) Welded plain steel:


ASTM A 185.

(2} Welded deformed steel:


ASTM A 497.

(3) Epoxy coated welded wire fabric:


ASTM A 884.

1 0 -2 0 P C I D e s ig n Handbook/Fifth Edition
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

c; Fabricated steel bar or rod mats:


ASTM A 184.

d. Prestressingrstrand: 2.01. B .1.d O ccasionallyused in long and/or thin


ASTM A 416, grade_____ . panels. Grades 250 or 270.

C. Cast-in anchors: 2.0 1 . C Loose attachment hardware usually speci­


fied under Miscellaneous Metals.

1. Materials:

a. Structural steel: ASTM A 36. 2.0 1 . C.1.a For carbon steel connection assem­
blies.

b. Stainless -steel: 2.0 1 . C.1.b Stainless steel anchors for use only
ASTM A 666, type 304, grade when resistance to staining merits extra cost. (A),
(B).

c. Carbon steel plate: 2 .0 1 . C .1 .C (A), (B), (C), (D).


ASTM A 283, grade_____ .

d. Malleable iron castings: 2.01. C .1.d Usually specified by type and manufac­
ASTM A 47, grade_____ . turer. Grades 32510 or 35018.

e. Carbon steel castings: 2.01. C.1.e For cast steel clamps.


ASTM A 27, grade 60-30.

f. Bolts: ASTM A 307 or A 325. 2.0 1 . C .1J For low-carbon steel bolts, nuts and
washers.

g. Welded headed studs:


ASTM A 108.

h. Deformed bar anchors:


ASTM A 496 or A 706.

2. Finish:

a. Shop primer: FS TT-P-86, oil base paint, 2.01.C .2.a For exposed carbon steel anchors.
type I, or SSPC-Paint 14, or manufactur­
er’s standard.

b. Hot-dipped galvanized: 2 .0 1 . C.2.b For exposed carbon steel anchors


ASTM A 123, electroplated or metal­ where corrosive environment justifies the additional
lized. cost. Field welding should generally not be per­
mitted on galvanized elements, unless the galvaniz­
ing is removed.

c. Cadmium coating: ASTM B 766. 2J01.C.2.C Particularly appropriate for threaded


fasteners.

d. Zinc rich coating: DOD-P-21035, self 2.0 1 . C .2.d For galvanized repair use high zinc-dust
curing, one component, sacrificial. content paint with dry film containing not less than
94% zinc dust by weight an d complying with
DOD-P-21035A or SSPC paint 20.

PCI Design Handbook/Fifth Edition 1 0 -2 1


GUIDE SPECIFICATIONS M O TESTTTS P ECIFIER S

D. Receivers for flashing: 2 8 ^ formed_____ 2.01. D (stainless steely (copper), (zinc). Coordi­
polyvinyl chloride extrusions;
_______________, o t nate with flashing specification to avoid dissimilar
metals. Delete when-included in fiashing-andsheet
m etaf section. Specify whether precaster or others
furnish.

E. Sandwich panel insulation: 2.01. E Specify type o f insulation such as foamed


plastic (polystyrene an d poiyisocyanurate), glasses
(foamed glass and fiberglass), foamed or cellular
lightweight concretes, or lightweight mineral aggre­
gate concretes. Thickness of sandwich panel
insulation governed by waff U-value requirements.

F. Grout: 2.01. F Indicate required strengths on contract


drawings.

1. Cement grout Portland cement, sand, and


water sufficient for placement and hydra­
tion.

2. Non-shrink grout: Premixed, packaged 2.01. F.2 Grout permanently exposed Fo view
ferrous or non-ferrous aggregate shrink-re­ should be non-oxidizing (non-ferrous).
sistant grout.

3. Epoxy-resin grout: Two-component miner­ 2.01. F.3 Check with local suppliers to determine
al-filled epoxy-resin: ASTM C 881 or FS availability and types o f epoxy-resin grouts.
MMM-A-001993.

G. Bearing Pads:

1. Chloroprene (Neoprene): Conform to Divi­ 2.01. G.1 AASHTO grade pads having a minimum
sion II, Sect. 18 of AASHTO Standard durometer hardness of 50 and utilizing 100 %
Specifications for Highway Bridges. chloroprene as the elastomer. Less expensive
commercial grade pads are available, but are not
recommended.

2. Random oriented fiber reinforced: Shall 2.01. G.2 Standard guide specifications are not
support a compressive stress of 3000 psi available for random oriented, fiber reinforced pads.
with no cracking, splitting or delaminating Proof testing of a sample from each group of 200
in the internal portions of the pad. pads is suggested. Normal service load stresses are
1500 psi, so the 3000 psi test load provides a factor
o f 2 over service stress. The shape factor for the test
specimens should not be less than 2. If adequate
test data are provided by the pad supplier, further
proof testing may not be required.

3. Duck layer reinforced: Conform to Division


II, Sect. 18.10.2 of AASHTO Standard
Specifications for Highway Bridges or Mili­
tary Specification MIL-C-882D.

4. Plastic: Multimonomer plastic strips shall be 2.0.1.G .4 Compression stress in use is not normal­
non-leaching and support construction ly over a few hundred psi and proof testing is not
loads with no visible overall expansion. considered necessary. No standard guide specifi­
cations are available.

1 0 -2 2 PCI Design Handbook/Fiftlr Edition


GUIDE SPECIFICATIONS NOTES T C SPECIFIERS

57 Tetrafluoroethy lene (TFE): Reinforced with 2 .0.1.G.5 - ASTM D 2116 applies only to basic I£ £
glass fibers and applied-Jo -stainless or resin molding and extrusionm aterialin p o w d e ro r
structural steel plates; pellet form. Ptiysbal and mechanical properties
most b e s p e c ifie d by naming manufacturer or o th er
methods.

2.02 Concrete Mixes

A. Concrete properties: 2.02. A The backup concrete and the surface finish
concrete can b e of one m ix design? depending upon
resultant finish, or the surface finish (face mix)
concrete can be separate from the backup con­
crete. Clearly indicate specific requirements for
each face of the product o r allow manufacturer’s
option.

1. Water-cementitious materials ratio: Maxi­ 2.02. A.1 Keep to a minimum consistent with
mum 40 lbs. of water to 100 tbs. of strength and durability requirements and placement
cementitious materials. needs.

2. Air entrainment: Amount produced by 2.02. A.2 Gradation characteristics o f most facing
adding dosage of air entraining agent that mix concrete will not allow use of a given percentage
will provide 19% ± 3% of entrained air in o f air. PC I recommends a range of air entraining be
standard 1:4 sand mortar as tested accord­ stated in preference to specified percentage.
ing to ASTM C 185; or minimum 3%,
maximum 6%.

3. Coloring agent: Not more than 10% of 2 .0 2 A .3 Amount used should not have any detri­
cementitious materials weight. mental effects on concrete qualities. Delete if
coloring agent is not required.

4. 28-day compressive strength: Minimum of 2.02. A.4 Vary strength to match requirements.
5000 psi when tested by 6 x 12 or 4 x 8 in. Strength requirements for facing mixes and backup
cylinders; or minimum 6250 psi when mixes may differ. Also the strength at time of removal
tested on 4 in. cubes. from the molds should be stated if critical to the
engineering design of the units. The strength level
o f the concrete should be considered satisfactory if
the average of each set of any three consecutive
cylinder strength tests equals or exceeds the
specified strength and no individual test falls below
the specified value by more than 500 psi,

B. Face mix: 2.02. B Delete i f separate face mix is not used.

1. Minimum thickness of face mix after consol­ 2.02. B. 1 Minimum thickness should be sufficient to
idation shall be at least one in. or a prevent bleeding through of the backup mix and
minimum of 1Vi times the maximum size of should be at least equal to specified minimum cover
aggregates used, whichever is larger. o f reinforcement.

2. Water-cementitious materials and cementi- 2.02.B .2 Similar behavior with respect to shrinkage
tious materials-aggregate ratios of face and is necessary in order to avoid undue bowing and
backup mixes shall be similar. warping.

PCI Design Handbook/Fifth Edition


1 0 -2 3
-GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

C. Design mixes to achieve required strengths 2.0 2 .C Proportion mixes by either laboratory trial
shall baprepared by independent testing faeiH- batch o r .field experience methods using materials
ty or qualified personnel at precast concrete to be employed on the p ro je c t for each type of
manufacturer’s plant. concrete required. Tests wHI be necessary on all
m ixes including face, backup, and standard, which
m ay be used in production otunits. Water content
should remain as constant as possible during
manufacture.

2.03 Fabrication

A. Manufacturing procedures shall be in general


compliance with PCI MNL-117.

B. Finishes: 2.03. B Finishing techniques used in individual


plants may vary considerably from one part o f the
continent to another, and between individual plants.
M any plants have developed specific techniques
supported by skilled operators or special facilities.

1. Exposed face to match approved sample or 2.03. B.1 Preferable to match sample rather than
mockup panel. specify method of exposure.

* *O R **

1. Smooth finish:

a. As cast using flat, smooth, non-porous 2.03.B.1.a Difficult to obtain uniform finish.
molds.
**OR**

1. Smooth finish:

a. As cast using fluted, sculptured, board 2.03.B.1.a Many standard shapes of plastic form
finish or textured form liners. liners are readily available.
**OR**

1. Textured finish:

a. Achieve finish on face surface of pre­


cast concrete units by form liners ap­
plied to inside of forms.

b. Distressed finish by breaking off portion 2.03.B. 1.b Delete if distressed finish is not desired.
of face of each flute.

c. Achieve uniformity of cleavage by alter­


nately striking opposite sides of flute.
**OR**

1. Exposed aggregate finish:

a. Apply even coat of retardant to face of


mold.

b. Remove units from molds after concrete


hardens.

1 0 -2 4 PCI Design Handbook/Fittfi Edition


GUfDE SPECIFICATIONS NOTES TO SPECIFIERS

c. Expose coarse aggregate by was King -


and brushing or lightly sandblasting
away surface mortar.

d. Expose aggregate to produce a 2.03.B.1.d (fight) (medium) {deep). Finishes-ob­


exposure. tained vary from light etch to heavy exposure,, but
must relate to the size of aggregates. Matrix can be
removed to a maximum depth of one-third the
average diameter of coarse aggregate but not more
than one-half the diameter o f smallest sized coarse
aggregate.
**O R**

1. Exposed aggregate finish:

a. Immerse unit irv tank of acid solution. 2.03.B.1.a Use reasonably acid resistant aggre­
**O R ** gates such as quartz or granite.

a. Pressure spray with acid and hot water


solution.
**O R**

a. Treat surface of unit with brushes which


have been immersed in acid solution.
****

b. Protect hardware, connections and in­


sulation from acid attack.

c. Expose aggregate to produce a ex- 2.03.B.1.C (light) (medium) (deep).


posure.
**O R **

1. Exposed aggregate finish:

a. Use power or hand tools to remove mor­ 2.03.B.1.a Use with softer aggregates such as
tar and fracture aggregates at the sur­ dolomite and marble.
face of units (bushhammer).
**O R**

1. Exposed aggregate finish:

a. Hand place large facing aggregate,


fieldstone or cobblestones in sand bed
over mold bottom.

b. Produce mortar joints by keeping cast


concrete Vz in. to 1 in. from face of unit.
**O R**

PCI Design Handbook/Fifth Edition


1 0 -2 5
-GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

1. Sandblasted finish:

a, Sandbiastrawaycementitious materiats- 2.03.BA.a flight) (medium) (deep). Exposure of


sand matrix to produce a _____ expo­ aggregate by sandblasting can vary from Vw in. or
sure. less to over % in. Remove matrix to a maximum
depth o f one-third the average diameter o f coarse
aggregate but not more than one-half the diameter
of smallest sized coarse aggregate. Depth of
sandblasting should be adjusted to suit the aggre­
gate hardness and size.
**0 R **

1 . Honed or polished finish:

a. Polish surface by continuous mechani­ 2.03.B.1 Honing and polishing o f concrete are
cal abrasion with fine grit, followed by techniques which require highly stalled personnel.
special treatment which includes filling Use with aggregates such as marble, onyx, and
of all surface holes and rubbing. granite.

**O B **

1. Veneer faced finish:

a. Cast concrete over tile, brick, terra cotta 2.03. B.1.a Full scale mockup units with natural
or natural stone placed in the bottom o f stone in actual production sizes, along with casting
the mold. and curing o f the units under realistic production
conditions are essential for each new or major
application or configuration of the natural stones.

b. Connection of natural stone face materi­ 2.03. B.1.b Provide a complete bondbreaker be­
al to concrete shall be by mechanical tween the natural stone face material and the
means. concrete. Ceramic tile, brick and terra cotta are
****
bonded to the concrete.

2. back surfaces of precast concrete 2.03. B.2 (Smooth float finish), (Smooth steel trow­
units after striking surfaces flush to form el), (Light broom), (Stippled finish). Use for exposed
finish lines. back surfaces o f units.

C. Cover:

1 . Provide at least % in. cover for reinforcing 2.03. C.1 Increase cover requirements when units
steel. are exposed to corrosive environment o r severe
exposure conditions. For exposed aggregate sur­
faces, the 3/t in. cover should be from bottom of
aggregate reveal to surface o f steel.

2. Do not use metal chairs, with or without 2.03. C.2 If possible, reinforcing steel cages should
coating, in the finished face. be supported from the back o f the panel, because
spacers o f any kind are likely to mar the finished
surface o f the panel. For smooth cast facing,
stainless steel chairs may be permitted. The wires
should be soft stainless steel and clippings should
be completely removed from the mold.

3. Provide embedded anchors, inserts,


plates, angles and other cast-in items with
sufficient anchorage and embedment for
design requirements.

1 0 -2 6 PCI Design Handbook/Fifth Edition


GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

D. M o fe -

1. Use rigid molds i o maintain units within


specified tolerances conforming to the
shape, lines and dimensions shown on the
approved shop drawings.

2. Construct molds to withstand vibration 2.03.D.2 Molds for architectural precast concrete
method selected. should he built to provide proper appearance,
dimensional control and tightness. They should be
sufficiently rigid to withstand pressures developed
by plastic concrete, as well as the forces caused by
consolidation. Unless otherwise agreed in the
contract documents, the molds are the property of
the precast concrete manufacturer.

E. Concreting:

1. Convey concrete from the mixer to place o f


final deposit by methods which will prevent
separation, segregation or loss of material.

2. Consolidate all concrete in the mold by high 2.03. E.2 The prime objective is to consolidate the
frequency vibration, either internal or exter­ concrete thoroughly, producing a dense, uniform
nal or a combination of both, to eliminate product with fine surfaces, free o f imperfections.
unintentional colds joints, honeycomb and Bonding between backup and face mix should be
to minimize entrapped air on vertical sur­ ensured if backup concrete is cast before the face
faces. mix has attained its initial set.

F. Curing: 2.03. F A wide variation exists in acceptable curing


methods, ranging from no curing in some warm
humid areas, to carefully controlled moisture-pres-
sure-temperature curing. Consult with local panel
manufacturers to avoid unrealistic curing require­
ments.

1. Precast concrete units shall be cured until 2.03. F. 1 Stripping strength, which could be as low
the compressive strength is high enough to as 2000 psi, should be set by the plant based on the
ensure that stripping does not have an characteristics of the product and plant facilities. It
effect on the performance or appearance of is the responsibility of the precaster to verify and
the final product. document the fact that final design strength has
been reached.

G. Panel identification:

1. Mark each precast panel to correspond to


identification mark on shop drawings for
panel location.

2. Mark each precast panel with date cast.

H. Acceptance: 2.03.H It should be stated in the contract docu­


ments who the accepting authority will be—contrac­
Architectural precast units which do not meet tor, architect, engineer of record, owner or jobsite
the color and texture range or the dimensional
inspector.
tolerances may be rejected at the option of the
architect, if they cannot be satisfactorily cor­
rected.

PC! Design Handbook/Fifth Edition 1 0 -2 7


GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

2v04 Concrete Testing

A. Make, one compression test at 28 days for each 2.04.A This test shoutd~be onlyapart of an in-plant
day’s-production of each type of concrete. quality control program.

B. Specim ens:

1. Provide two test specimens for each com­ 2.04. B. 1 One test specimen may be used to check
pression test. the stripping strength.

2. Obtain concrete for specimens from actual


production batch.

3. 6 in. x 12 in. or 4 in. x 8 in. concrete test


cylinder, ASTM C 31.
**OR**

3. ________ sized concrete cube, _______ 2.04.B.3 Specify size. Cube specimens are usually
4 in. units, but 2 in. o r 6 in. units are sometimes
required. Larger specimens give more accurate test
results them smaller ones. Source: (molded individu­
**** ally), (sawed from slab).

4. Cure specimens using the same methods


used for the precast concrete units until the
units are stripped, then moist cure speci­
mens until tested.

C. Keep quality control records available for the 2.04. C These records should include mix designs,
architect upon request for two years after final test reports, inspection reports, member identifica­
acceptance. tion numbers along with date cast, shipping records
and erection reports.

3. EXECUTION

3.01 Inspection

A. Before erecting architectural precast concrete,


the general contractor shall verify that structure
and anchorage inserts required to support
panels are within tolerances.

B. Determine field conditions by actual measure­ 3.0.1.B Any discrepancies between design dimen­
ments. sions and field dimensions which could adversely
affect installation in accordance with the contract
documents should be brought to the general
contractor’s attention. If such conditions exist,
installation should not proceed until they are
corrected or until design requirements are modified.
Beginning of installation can mean acceptance of
existing conditions.

1 0 -2 8 PCI Design Handbook/Fifth Edition


NOTESTO SPECIFIERS

3.0i£rectton

A. Gear, well-drained unloading- areasr-and road 3.02:,A General contractor should coordinate deliv­
access around and in the structure (where ap­ ery and erection o f precast concrete products with
propriate) shall he provided and maintained b y other jobsite operations.
the general contractor do a degree that the
hauling and erection equipment for the archi­
tectural precast concrete products are able to
operate under their own power.

B. General contractor shall erect adequate barri­


cades, warning lights or signs to safeguard
traffic in the immediate area of hoisting and
handling operations.

C. Set precast units level, plumb, square and true 3.02.G Controlled reference lines should be used
within the allowable tolerances. Generat con­ because the characteristics o f precast concrete
tractor shall be responsible for providing lines, make a surface elevation difficult ter define. Where
center and grades in sufficient detail to allow thickness is not of exact concern, lines used in
installation. General contractor shall verify that erection should be controlled from exposed exterior
bearing surfaces compty with specifications
precast concrete surfaces.
and, if not in compliance, shah make neces­
sary corrections prior to start of erection.

D. Provide temporary supports and bracing as re­


quired to maintain position, stability and align­
ment as units are being permanently con­
nected.

E. Tolerances for location of precast units shall be


in accordance with Chapter 8 of this Hand­
book.

F. Set non-load bearing units dry without mortar, 3.02. F Shims should be near the back of the unit to
attaining specified joint dimension with steel or prevent their causing a spall on face of unit when
plastic spacing shims. shim is loaded. The selection of the width and depth
of field-molded sealants, for the computed move­
ment in a joint, should be based on the maximum
allowable strain in the sealant.

G. Fasten precast units in place by bolting or 3.02. G The erector should protect units from
welding, or both, completing drypacked joints, damage caused by field welding or cutting opera­
grouting sleeves and pockets, and/or placing tions and provide non-combustible shields as
cast-in-place concrete joints as indicated on necessary during these operations. Structural welds
approved erection drawings. should be made in accordance with the erection
drawings which should clearly specify type, extent,
sequence and location of welds. Adjustments or
changes in connections, which could involve
additional stresses in the products or connections,
should not be permitted without approval by the
architect/engineer. Precast concrete units should
be erected in the sequence indicated on the
approved erection drawings.

H. Temporary lifting and handling devices cast


into the precast concrete units shall be com­
pletely removed or, if protectively treated, left
in place unless they interfere with the work of
any other trade.

PCI Design Handbook/Rfth Edition


1 0 -2 9
GUIDE SPECIFICATIONS NOTES TO SPECIFIERS

3.03 Repair

A. Repair exposed exterior surface to match coior 3.Q3.A Repair is normally accomplished- prior to
and texture of surrounding concrete and to final cleaning and caulking. It is recommended that
minimize shrinkage. the precaster execute a it repairs or approve the
methods proposed Tor such repairs by other
qualified personnel. The precaster should be
compensated for repairs ofany damage forwhichhe
is not responsible, Repairs should be acceptable
providing the structural adequacy of the product and
the appearance are not impaired. All repairs and
remedial work should be documented and kept in
jo b record files.

B. Adhere large patch to hardened concrete with 3.03.B Bonding agent should not be used with
bonding agent. small patches because of the greater likelihood of
discoloring the patch.

3.04 Cleaning

A. After installation and joint treatment ____ 3.04.A State whether erector o r precaster should
_____________shall clean soiled precast con­ do cleaning under the responsibility of general
crete surfaces with detergent and water, using contractor. Use cleaning materials or processes
fiber brush and sponge, and rinse thoroughly which will not change the character o f exposed
with clean water in accordance with precast concrete finishes.
concrete manufacturer’s recommendation.
**OR**

A. After installation and joint treatment: Clean 3.04.A (acid-free commercial cleaners), (steam
precast concrete panels w ith ___________ .* cleaning), (water blasting), (sandblasting). Select
cleaners with a non-chloride base. Use sandblast­
ing only for units with original sandblasted finish.
**** Ensure that materials of other trades are protected
when cleaning panels.

B. Use acid solution only to clean particularly


stubborn stains after more conservative meth­
ods have been tried unsuccessfully.

C. Use extreme care to prevent damage to pre­


cast concrete surfaces and to adjacent materi­
als.

D. Rinse thoroughly with clean water immediately


after using cleaner.

1 0 -3 0 PCI Design Handbook/Fifth Edition


GUIDE SPECIFICATIONS 14GTES TO SPECIFIERS

^GSProteetion

-A. Ail work arid-materials of other trades shall be


adequately protected by the erector at all"
times.

B. A fire extinguisher, of an approved type and in


operating condition, shall be located within
reach of all burning and welding operations at
all times.

C. The erector shall be responsible for any chip­ 3.05.C After erection of any portion of precast
ping, spalling, crackingor other damage to the concrete work to proper alignment and appearance,
units after delivery to the jobsite unless dam­ the general contractor should make provisions to
age is caused in site storage by others. After protect all precast concrete from damage and
installation is completed, any further damage staining:
shall be the responsibility of the general con­
tractor.

PCI Design Handbook/Rfth Edition


1 0 -3 1
10.3 CODE OF STANDARD PRACTICE
FOR PRECAST CONCRETE

The- precast/prestressed concrete industry has 1.3 Prestressed Concrete


grown rapidly and certain practices relating to the de­
Both staJGtural and architectural precast concrete
sign, manufacture and erection of precast concrete
may be prestressed or non-prestressed. All structural
have beeome standard in many areas of North Ameri­
precast concrete products referred-to herein which
ca. This “Code of Standard Practice” is a compilation
are prestressed are specifically referred to as pre­
of these practices, and others deemed worthy o f con­
stressed concrete.
sideration, in the form of recommendations for the
guidance of those involved with the use of structural
and architectural precast concrete. 2. SAMPLES, MOCKUPS, AND
The goal of this Code is to build a better under­ QUALIFICATION OF MANUFACTURERS
standing by suggesting standards which more clear­
ly define procedures and responsibilities, thus result­
ing in fewer problems for everyone involved in the
2.1 Samples and Mockups
planning, preparation and completion of any project. Samples, mockups, etc., are rarely required for
As the precast/prestressed concrete industry con­ structural prestressed concrete, if samples are re­
tinues to evolve, and it becomes apparent that addi­ quired, they should be described in the contract doc­
tional practices have become standard in the indus­ uments and the samples should be manufactured in
try o r that current standards require modification, it is accordance with Sect. 3.2, Architectural Precast Con­
the intent of the Precast/Prestressed Concrete Insti­ crete, Second Edition*
tute to enlarge and revise this Code.

2.2 Qualification of Manufacturer


1. DEFINITIONS OF PRECAST CONCRETE
Manufacture, transportation, erection and testing
1.1 Structural Precast Concrete should be accomplished by a company, firm, corpo­
Structural precast concrete usually includes ration, or similar organization specializing in provid­
beams, tees, joists, purlins, girders, lintels, columns, ing precast products and services normally associat­
posts, piers, piles, slab or deck members, and wall ed with structural or architectural precast concrete
panels. In order to avoid misunderstandings, it is im­ construction.
portant that the contract documents for each project The manufacturer should be certified in the PCI
list all the elements that are considered to be structur­ Plant Certification Program. Because plant certifica­
al precast concrete. Some structural members may tion identifies the types of products for which the
be left exposed in the structure to establish an aes­ manufacturer has demonstrated capability and expe­
thetic appearance. High quality, attractive architec­ rience, project specifications should require the ap­
tural treatments may be provided on the surfaces of propriate group and category defined in Sect. 9.5. In
these structural elements, and they should be spe­ addition, for special and unique projects, the
cially listed in the contract documents. manufacturer may be required to list similar and com­
parable work successfully completed.
Standards of performance are given in the latest
1.2 Architectural Precast Concrete editions of the PCI manuals for quality control,
MNL-116, MNL-117 and MNL-130*
Architectural precast concrete is characterized by
a higher standard of uniformity of appearance with re­
spect to surface details, color and texture. Typical ar­ 3. CONTRACT DOCUMENTS AND
chitectural precast elements fall into two groups: ma­ DESIGN RESPONSIBILITY
jor- primary elements including wall panels, window
wall panels, and column covers; other elementSL are
decorative pieces and trim units including copings, 3.1 Contract Documents
mullions, sills and appurtenances such as benches Prior to initiation of the engineering-drafting func­
and bollards. In order to avoid misunderstandings, it tion, the manufacturer should have the following con­
is important that the contract documents for each tract documents at his disposal:
project list all the elements that are considered to be
architectural precast concrete.
* Available from Precast/Prestressed Concrete Institute.

1 0-32 PCI Design Handbook/Fifth Edition


1. Architectural drawings.
8. Any other special- requirements and condp
2. Structural drawings. lions.

Other design responsibility relationships are_ de-


3. Electrical, mechanical and plumbing drawings
scribed in Sect. 10.4.
(if pertinent).

4. Specifications (complete with addenda)-.


4. SHOP DRAWINGS
Other pertinent drawings may also be desirable,
Shop drawings consist of erection and production
such as approved shop drawings from other trades, drawings. Different areas o f the country may use dif­
roofing requirements and alternates.
ferent terminology.

3.2 Design Responsibilities 4.1 Erection Drawings


It is the responsibility of the owner* to keep the The information provided in the contract docu­
manufacturer supplied with up-to-date documents
ments is used by the manufacturer to prepare erec­
and written information. The manufacturer should not
tion drawings for approval and field use. They con­
be held responsible forprobtems arising from the use
tain:
of outdated or obsolete contract documents. If up­
dated documents are furnished, it may also be nec­ 1. Plans and/or elevations locating and dimen­
essary to modify the contract. sioning all members furnished by the manufac­
turer.
The contract documents should clearly define the
following: 2. Sections and details showing connections, fin­
ishes, openings, blockouts and cast-in items
1. Items designed and/or furnished by the
and their relationship to the structure.
manufacturer.
3. Description of all loose and cast-in hardware in­
2. Size, location and function of all openings,
cluding designation of who furnishes it.
blockouts, and cast-in items.
4. Drawings showing location of anchors installed
3. Production and erection schedule require­
in the field.
ments and restrictions.
5. Erection sequences when required to satisfy
4. Design intent including connections and rein­ stability and handling requirements.
forcement^

5. Allowable tolerances. Normal field tolerances 4.2 Production Drawings


should be recommended by the manufacturer.
The contract documents are also used to prepare
6. Dimension, material and quantity require­
production drawings for manufacturing showing all
ments.
dimensions together with locations and quantities for
7. General and supplemental general conditions. all cast-in materials (reinforcement, inserts, etc.) and
completely defining a ll finish requirements.
Normal practices for the preparation of drawings
‘The owner of the proposed structure or his designated repre­
for precast concrete are described in the PCI Drafting
sentatives, who may be the architect, engineer, general con­
Handbook—Precast and Prestressed Concrete, Sec­
tractor, public authority or others contracting with the precast
manufacturer. ond Edition.

tWhen the manufacturer accepts design responsibility, the


area or amount of responsibility must be clearly defined in the 4.3 Discrepancies
contract documents. The engineer or architect of record must
be identified and it is understood that all designs are submitted When discrepancies or omissions are discovered
through him for his approval and acceptance. The manufactur­ on the contract documents, the manufacturer has the
er’s responsibility can be limited to member design only or it responsibility to check with the design and construc­
may include the entire structure. When the manufacturer is tion team to resolve the problem. If this is not pos­
responsible for product design only, all loads which are to be sible, the following procedures are normally followed:
applied to precast members, including forces developed by
restraint, should be provided to th e m anufacturer b y the ow ner 1. C ontract term s govern over specifications and
unless otherwise agreed. drawings.

PCI Design Handbook/Frfth Edition


1 0 -3 3
drawings and production may be started-after
2. Specifications govern over drawings. noted changes'have beervmade.
3. Structural drawings govern over architectural
drawings 3r Not Approved— Drawings must be corrected
and resubmitted. Production-drawings can not
4. Written dimensions govern over scale-dimen­ be completed correctly or submitted until “ap­
sions proved” or “approved as noted” erection draw­
ings are returned.
5. Sections govern over plans or elevations.

6. Details govern over sections.


5. MATERIALS
Graphic verification should be requested for any
The relevant ASTM Standards that apply to materi­
unclear condition.
als for a project should be listed in the contract docu­
ments together with any special requirements that
are not included in the ASTM Standards.
4.4 Approvals
Note: Additional information regarding material
Completed erection drawings, usually in repro­ specifications can be found in Sect. 10.1, “Guide
ducible form, should be submitted for approval. The Specification for Precast, Prestressed Concrete
exact sequence is dictated by construction sched­ and Sect. 10.2, “Guide Specification for Architectural
ules and erection sequences, and is determined Precast Concrete.”
when the contract is awarded.
Preferably, production drawings should not be
started prior to receipt of “approved” or "‘approved as
noted” erection drawings. Production drawings
should be submitted for approval only when so re­ 6. TESTS AND INSPECTIONS
quested.*
Corrections should be noted on the reproducible
6.1 Tests of Materials
erection drawings and copies made for distributioa
The following approval interpretations are normal Manufacturers are required to keep test records in
practiced accordance with the PCI manuals for quality control
(MNL-116, MNL-117 and MNL-130). The contract
1. Approved—The approvers1 have completely documents may require the precast concrete
checked and verified the drawings for confor­ manufacturer to make these records available for in­
mance with contract documents and all ex­ spection by the owner’s representative upon his re­
pected loading conditions. Such approval quest.
should not relieve the manufacturer from re­ When the manufacturer is required to submit cop­
sponsibility for his design when that responsi­ ies of test records to the owner and/or required to per­
bility is placed upon him by the contract. The form or have performed tests not required by the PCI
manufacturer may then proceed with produc­ manuals for quality control, these special testing re­
tion drawings and production without resub­ quirements should be clearly described in the con­
mitting. Erection drawings may then be re­ tract documents along with the responsibility for pay­
leased for field use and plant use. ment.
When high-strength concrete is specified, special
2. Approved as Noted—Same as above exeept testing procedures may be required. These include
that noted changes should be made and cor­ the use of 4 x 8 in. cylinders, high-strength capping
rected erection drawings issued. Production materials, a stiff testing machine, more frequent test­
ing and later test ages. Special attention should be
*When production drawings are the only drawings showing given to all deliveries of concrete constituent materi­
reinforcement, representative drawings should be submitted als to ensure that they meet the specifications. Small
for approval. variations in the properties of these materials can re­
tWhen production drawings are submitted, the same applies. sult in changes in the measured concrete strengths.
$The contract should state who has approval authority.

1 0 -3 4 PCI Design Handbook/Fifth Edition


6.2 Inspections agreed upon between the owner, manufacturer-and
erector. Specral-req ui rements oftheowner-forthe de­
On certain projects the ownermay require inspec-
livery of materials or the mode of transport, should be
tiorrof-precast concrete products in the manufactur­
stated in the contract documents.
er’s yard by persons other than the manufacturer’s
own quality control personnel. Such inspections are
normally made atthe owner’s expense. The contract 8.2 Markingand Shipping of Materials
documents should describe. how, when and by
The precast concrete- members should be sepet
whom the inspections are to be made, the responsi­
rately marked in accordance with approved drawings
bility of the inspection agency, and who is to pay for
them. Alternatively, the owner may accept plant certi­ in saefra manner as to distinguish varying pieces and
fication in lieu of outside inspection, euch as provided to facilitate erection of the structure. Any members
in the PCI Plant Certification Program. which require a sequential erection should be proper­
ly marked.
The owner should give the manufacturer sufficient
6.3 Fire Rated Products time to fabricate and ship any special plates, bolts,
anchorage devices, etc., contractually agreed to be
If the manufacturer is expected to provide a fire
furnished by the manufacturer.
rated product and/or Underwriters Laboratories
(U.L) labels, these requirements should be clearly
stated in the contract documents. 8.3 Precautions During Delivery

Special protection or precautions beyond that re­


7. FINISHES quired in MNL-116, MNL-117 and MNL-130 should
not be expected unless stated in the bid invitation or
Finishes of precast concrete products, both struc­
specifications. The manufacturer is not responsible
tural and architectural, are probably the cause of
for the product, including loose material, after deliv­
more misunderstandings between the various mem­
ery to the site unless required by the contract docu­
bers of the building team than any other question
ments.
concerning product quality.
It is therefore extremely important that the contract
documents describe clearly and completely the re­ 8.4 Access to Jobsite
quired finishes for all surfaces of all members, and
Free and easy access to the delivery site should
that the erection drawings also include this informa­
tion. When finish is not specified, the standard finish be provided to the manufacturer, including backfilling
described in “Guide Specification for Precast, Pre­ and compacting, drainage and snow removal, so that
delivery trucks can operate under their own power.
stressed Concrete” should normally be furnished.
For descriptions of the usual finishes for structural
precast concrete, see Sect. 10.1 “Guide Specification 8.5 Unloading Time Allowance
for Precast, Prestressed Concrete, ” and for architec­
tural precast concrete, see Sect. 3.5, Architectural Delivery of product includes a reasonable unload­
Precast Concrete, Second Edition. Where special or ing time allowance. Any delay beyond a reasonable
critical requirements exist or where large expanses of time is normally paid for by the party which is respon­
exposed precast concrete will occur on a project, sible for the delay.
samples are essential and, if required, should be so
stated and described irrthe contract documents.

9. ERECTION
8. DELIVERY OF MATERIALS

9.1 Special Erection Requirements


8.1 Manner of Delivery
When the owner requires a particular method or
The manufacturer should deliver the precast con­ sequence of erection for his own needs during erec­
crete to the erector* in a manner to facilitate the tion, this information should be stated in the contract
speed of erection of the building or as mutually documents. In the absence of such stated restric­
tions, the erector will proceed using the most efficient
and economically safe method and sequence avail­
*The erector may be either the manufacturer or a subcontrac­
tor engaged by the manufacturer, or the general contractor. able to him, consistent with th e contract docum ents.

PCI Design Handbook/Fifth Edition 1 0 -3 5


9.2 Tolerances 3. Maximum accumulation-ofVi in. per hundred ft
along the established column-line of multiple
-Some variation-is to be expected in trie overatr di­
anchor bolt-groups, but not to exceed a totai of
mensions ofany buiidingxirother structure. ltis=com-
T in., where the established column line is the
mon practice for the manufacturer and erector-to
actual field line most representative o fth e cen­
work within. The- tolerances recommended by- the
ters of the as-built anchor bolt groups along a.
American Concrete institute and the Preeast/Pre-
line o f columns.
stressed Concrete Institute.
The owner, by whatever agencies he may elect,
4. Vi in. from the center of any anchor bolt group
immediately upon completion of the erection, should
to the established column line through that
determine if the work is plumb, level, aligned and
group.
properly fastened, discrepancies should immediate­
ly be brought to the attention of the erector so that
5. The tolerances of items 2 ,3 and 4 apply to off­
proper corrective action can be taken.
set dimensions shown on the plans, measured
The work of the manufacturer and erector is com­
parallel and perpendicular to the grid lines.
plete once the precast product has been properly
plumbed, leveled and aligned within the established
9.5.3 Erectors should check both line and grade in
tolerances, Acceptance for this work should be se­
sufficient time before erection is scheduled to permit
cured from the authorized representative of the gen­
any necessary corrections. Proposed corrections
eral contractor (see Sect. 11,2).
should be submitted to the owner for approval.
9.3 Foundations, Piers, Abutments and Corrections should be made by the general contrac­
Other Bearing Surfaces tor before erection begins.

The invitation to bid should state the anticipated


time when alt foundations, piers, abutments and oth­ 9.6 Utilities
er bearing surfaces will be ready and accessible to Water and electricity should be furnished by the
the erector. owner for erection and grouting operations.

9.4 Building Lines and Bench Marks 9.7 Working Space

The precast erector should be furnished all build­ The owner should furnish adequate, properly
ing lines and bench marks at the site of the structure. drained, graded, and convenient working space for
the erector and access for his equipment necessary
to assemble the structure. The owner should provide
9.5 Anchor Bolts and Bearing Plates adequate storage space for the precast concrete
9.5.1 The precast manufacturer normally furnishes products to enable the erector to operate at the
but does not install anchor bolts, plates, etc. that are speed required to meet the established schedule.
to be installed in cast-in-place concrete or masonry Unusual hazards such as high voltage lines, buried
for connection with precast members. However, if utilities, or areas of restricted access should be stated
this is to be the responsibility of the precast manufac­ in the invitation to bid.
turer, it should be so defined in the specifications. It is
important that such items be installed true to line and 9.8 Materials of Other Trades
grade, and that installation be completed in time to
Other building materials or work of other trades
avoid delays or interference with the precast concrete
should not be built up above the bearing of the pre­
erection.
cast concrete until after erection of the precast con­
9.5.2 Anchor bolts and foundation bolts are set by crete members.
the owner in accordance with an approved drawing.
They must not vary from the dimensions shown on 9.9 Correction of Errors
the erection drawings by more than the following: Corrections of minor misfits are considered a part
1. Vs in. center to center of any two bolts within an of erection even if the precast concrete is not erected
anchor bolt group, where an anchor bolt group by the manufacturer. Any error in manufacturing
is defined as the set of anchor bolts which re­ which prevents proper connection or fitting should be
ceive a single fabricated shipping piece. immediately reported to the manufacturer and the
owner so that corrective action can be taken. The
2. Vi in. center to center of adjacent anchor bolt manufacturer should approve any alterations or
groups. corrections to the product.

1 0 -3 6 PCI Design Handbook/Fifth Edition


9.10 Field Assembly bility for-accomplishing this work should-be resolved
between the manufacturer and erector.
The sizerof precast concrete pieces may be limited
by transportation requirements for weight and clear­
ance dimensions. Unless agreed upon between the
manufacturer and owner, the manufacturer should 9.15 Safety^
provide fo r such field connections that will meet re­
Safety procedures fo r the erection of. the precast
quired loads and forces without altering the function-
concrete members is the responsibility of the erector
or appearance of the structure.
and must be in accordance with all local, state or Fed­
The manufacturer furnishes those items em­
eral rules and regulations which have jurisdiction in
bedded in the precast members, and generally fur­
the area where the work is to be performed, but not
nishes all loose materials for temporary and perma­
nent connection of precast members. Temporary less than required in ANSI Standard A10.9, Safety Re­
guys, braces, falsework, shims, and cribbing are the quirements for Concrete Construction and Masonry
Work.*
property of the erector and are removed only by the
erector or with the erector’s approval upon comple­
tion of the erection of the structure, unless otherwise 9.16 Security Measures
agreed.
Security protection at the jobsite sh o u ld b e th e re­
sp o n sib ility of the general contractor.
9.11 Blockouts, Cuts and Alterations

, Neither the manufacturer nor the erector is re­ TO INTERFACE WITH OTHER TRADES
sponsible for the blockouts, cuts or alterations by or
for other trades unless so specified in the contract C oord in ation of the requirem ents for other trades

documents. Whenever such additional work is re­ to be inclu ded in the precast concrete m e m b ers
quired, all information regarding size, location and sh o u ld b e the responsibility of the ow ner u n le ss clear­

number of alterations is furnished by the owner prior ly defined otherw ise in the contract docum ents.
to preparation of the precast production and erection The PCI manuals for quality control (MNL-116,
drawings. MNL-117 and MNL-130) specify manufacturing toler­
The general contractor is responsible for warning ances for precast concrete members. Interfaces with
other trades against cutting of precast concrete other materials and trades must take these toler­
members without prior approval of the engineer of re­ ances into account. Unusual requirements or allow­
cord. ances for interfacing should be stated in the contract
documents.

9.12 Temporary Floors and Access


11 WARRANTY AND ACCEPTANCE
The manufacturer or erector is not required to fur­
nish temporary flooring for access unless so speci­
fied in the contract documents. 11.1 Warranties

Warranties of product and workmanship have be­


9.13 Painting, Caulking and Closure Panels come a widely accepted practice in this industry, as in
most others. Warranties given by the precast con­
Painting, caulking and placing of closure panels crete manufacturer and erector should indicate that
between stems of flanged concrete members are ser­ their product and work meet the specifications for the
vices not ordinarily supplied by the manufacturer or project.
erector. If any of these services are required of the in no case should the warranty of the manufactur­
manufacturer, it should be stated in the contract er and erector be in excess of the warranty required
agreement. by the specifications. Warranties should in all
instances include a time limit and it is recommended
9.14 Patching that this should not exceed one year.
In order to protect the interests of all parties con­
A certain amount of patching of product is to be cerned, warranties should also state that any devi-
expected to repair minor spalls and chips. Patching
should meet the finish requirements of the project
and color should be reasonably matched. Responsi­ *A m erican National Standards Institute, N ew York, N ew York.

PCI-Design Handbook/Fifth Edition


1 0 -3 7
Bilans in the designed use-el the product, modifica­ FIEL0 INSPECTION REPORT
tions Gf the product, by the owner and/or contractor or Project # -___________
changes in other products used in conjunction with
the precast concrete will cause said warranty to-be­ On th is ___________ day o f __________,19_________
come-null a n d vo id
Warranty may fee included as a part of thecondi-
tions of the contract agreement, o rit may be present­ Compaiy-Field Superintendent
ed in letter form as requested by the owner. A sample and

warranty follows: Precast Manufacturer


of
General Contractor Superintendent

Manufacturer warrants that all materials furnished have been


manufactured in accordance with the specifications for this project. General Contractor
Manufacturer further warrants that if erection of said material is to be
performed by those subject to his control and direction , work will be have inspected

completed in accordance with the same specifications.


In no event shall manufacturer b e held responsible for any dam­
ages, liability or costs of any kind or nature occasioned by or arising portion of building being inspected
out of the actions or omissions of others, or lor work, including de­
sign, done by others; or for material manufactured, supplied or AH of the work performed by the above indicated company
in the above described portion o f the project has been per­
installed by others; or for inadequate construction of foundations,
formed to the satisfaction of the above named General Contrac­
bearing walls, or other units to which materials furnished by the pre­
tor’s Superintendent with the exception of the following:
cast manufacturer are attached or affixed.
This warranty ceases to be in effect beyond the date of
______________ . Should any defect develop during the contract
The General Contractor’s Superintendent hereby releases
warranty period, which can be directly attributed to defect in quality the Precast Manufacturer of its responsibility to perform any oth­
of product or workmanship, precast manufacturer shall, upon writ­ er work in the above described portion of the project except as
ten notice, correct defects or replace products without expense to detailed herein.

owner and/or contractor. The Precast Manufacturer in turn hereby releases the above
described portion of the project to the General Contractor.

COMPANY NAME Precaster's Superintendent

Gen'I. Contr. Superintendent

Signature Title
Final inspection and acceptance of erected pre­
cast and prestressed concrete should be made by
the architect/engineer within a reasonable time after
the work is completed.

12. CONTRACT ADMINISTRATION

11.2 Acceptance
12.1 General Statement
Manufacturer should request approval and accep­
tance for all materials furnished and all work com­ Contract agreements may vary widely from area to
pleted by him periodically and in a timely manner as area, but the objective should be the same in all
deemed necessary in order to adequately protect the instances. The contract agreement should be written
interests of everyone involved in the project. The size to protect the interests of all parties concerned and, at
and nature of the project will dictate the proper inter­ the same time, be specific enough in content to avoid
vals for securing approval and acceptance. Periodic misunderstandings once the project begins.
approval in writing should be considered when it ap­ Information relative to invoicing, payment, bond­
pears that such action will minimize possible prob­ ing and other data pertinent to a project or material
lems which would seriously affect the progress of the sale should be specifically provided for in the major
project. A sample acceptance form follows: provisions of the contract documents or in the special

1 0 -3 8 PCI Design Handbook/Fifth Edition


terms and conditions-applicable to alt contractual otherdesign_professionals and all reference-
agreements between manufacturer and.owner. numbers identifying job relation information
The intent of thls-section is to recommend those such as plans, specifications, addenda, bid-
matters which ought to be considered, butnotneces- number, ate.
sarily the form in which they: should be-expr-essed.
The final statement otpolicies should be the resultot 27 C ontract agreement should fully describe the
careful consideration of afl pertinent factors as well as materials to be furnished and/or all work to be
of the normal practices in the area. completed by the seller.

3. AH exclusions should be stated to avoid the


12.2 Retentions
possibility of any misunderstanding.
Although retentions have been used for many
years as a means of ensuring a satisfactoryjob per­ 4. Price quoted should be stated toaliminate any
formance, it is apparent that they directly contribute possibility of misunderstanding.
to the cost of construction, frequently lead to dis­
putes, and often result in job delays. In view of the un­ 5. Reference should be made to the terms and
favorable consequences of retentions and possible conditions governing the proposed contract
abuse, it is recommended that the following proce­ agreement. The terms and conditions may
dure be followed: best be stated on the reverse side of the con­
1. Wherever possible, retentions should be elimi­ tract form. Special terms or conditions should
nated and bonding should be used as the be stated in sufficient detail to avoid the possi­
single, best source of protection. This should bility of misunderstanding.
apply to prime contractors and subcontractors
equally. 6. The terms of payment should be specifically
detailed so there is no doubt as to intent Spe­
2. Where there are no bonding requirements, the cial care should be exercised where the terms
retention percentage should be as low as pos­ of payment will differ from those normally in ef­
sible. It is recommended that this be not more fect or where they deviate from the general
than 5 % of the work invoiced. terms and conditions appearing on the reverse
side of the contract form.
3. The percentage level of any retention should
be the same for subcontractors as for prime 7. A statement of policy should be made with ref­
contractors on a job. erence to the inclusion or exclusion of taxes in
the stated price.
4. Release of retained funds and final payment, as
well as computing the point of reduction of the 8. The proposal form stating the full intent and
retention, should be done on a line item basis, conditions under which the project will be per­
that is, each contractor or subcontractor’s work formed may contain an acceptance clause to
considered as a separate item and the reten­ be signed by the purchaser. At such time as
tion reduced by 50 % upon substantial comple­ said acceptance clause is signed, the proposal
tion and the balance released within 30 days af­ form then becomes the contract agreement.
ter final completion of that work.
9. Seller should clearly state the limits of time with­
5. Retained funds should be held in an escrow ac­ in which an accepted proposal will be recog­
count with interest accruing to the benefit of the nized as a binding contract.
party to whom the funds are due.
10. A statement indicating the classification of la­
6. When materials are furnished FOB plant or job- bor to perform the work in the field is advisable
site, it is recommended that there be no reten­ to eliminate later dispute over jurisdiction of
tions. work performed.

12.3 Contract Agreement 12.4 Terms and Conditions

1. C o n trac t agree m e n t sh o u ld fully d e scrib e the T he term s and conditions stated on the p ro p o sal
project involved, including job location, project contract agreem ent sh o u ld include, but are not nec­
nam e, n a m e of owner/developer, architect or essarily limited to, the following:

PCI Design Handbook/Fifth Edition


1 0 -3 9
when deliveries or placement of said mate­
1. LienLaws—Wherethe lien laws of a state spe­ rials are delayed for more than arstipulated
cifically requkeadvance notice of intent, it is ad­ time beyond the originally scheduled date
visable to include the required statement in the because o f purchaser’s inability- either to
general terms and conditions. accept delivery erf materials or to provide
proper job access.
2. Specifications—Seller shouldmake a specific
declaration of material and/or work specifica­ b. Under certain conditions, it may be neces­
tions, but normally this should not be in excess sary to purchase special materials or to
of the specifications required by the contract produce components well in advance of
agreement. job requirements to ensure timely deliver­
ies. When jo b requirements are of such a
3. Contract Control—A statement should be nature, it is advisable to include provisions
made indicating that the agreement when duly for payment of such raw and finished in­
signed by both parties supersedes and invali­ ventories stored in seller’s plant or on job-
dates any verbal agreement and can only be sites on a current basis.
modified in writing with the approval of those
signing the original agreement. 9. Payment for Suspended or Discontinued
Projects—The terms and conditions should
4. Terms of Payment—Terms of payment provide that in the event of a discontinued or
should be specifically stated either on the face suspended project, seller shall be entitled to
of the contract or in the general terms and con­ payment for all material purchased and/or
ditions. Mode and frequency of invoicing manufactured including costs, overhead and
should be so stated, indicating time within profit, and not previously billed, as well as rea­
which payment is expected. sonable engineering and other costs incurred.

5. Late Payment Charges—The contract may 10. Job Extras—Requests for job extras should be
provide for legal interest charges for late pay­ confirmed in writing. Invoicing should be pre­
ments not made in accordance with contract sented immediately following completion ofthe
terms, and if this is desired, it should be stated extra work with payment subject to the terms
in the general terms and conditions. A state­ and conditions ofthe contract agreement, or as
ment indicating seller is entitled to reasonable otherwise stated in the change order.
attorney’s fees and related costs should collec­
tion proceedings be necessary may also be in­ 11. Claims for Shortages, Damages or Delays—
cluded. Seller should, upon immediate notification in
writing on the face of the delivery ticket of re­
6. Overtime Work— Prices quoted in the propos­ jected material or shortage, acknowledge and
al should be based on an 8-hour day and a furnish replacement material at no cost to pur­
5-day week under prevailing labor regulations. chaser. It is normal practice that the seller
Provisions should be included in the contract should not be responsible for any loss, dam­
agreement to provide for recovery of overtime age, detention or delay caused by fire, acci­
costs plus a reasonable markup when the sell­ dent, labor dispute, civil or military authority, in­
er is requested to provide such service. surrection, riot, flood or by occurrences
beyond his control.
7. Financial Responsibility—General terms and
conditions may indicate the right ofthe seller to 12. Back Charges—Back charges should not be
suspend or terminate material delivery and/or binding on the seller, unless the condition is
work on a project if there is a reasonable doubt promptly reported in writing, and opportunity is
of the ability of the purchaser to fulfill his finan­ given seller to inspect and correct the problem.
cial responsibility.
13. Permits, Fees and Licenses—Costs of per­
8. Payment for Inventory mits, fees, licenses and other similar expenses
are normally assumed by the purchaser.
a. It has become common practice to include
in the contract terms and conditions provi­ 14. Bonds—Cost of bonds is normally assumed
sions for the invoicing and payment of all by the purchaser.
materials stored at the plant or jobsite

1 0 -4 0 PCI Design Handbook/Fifth Edition


15. Taxes—Federal; state, county or municipal oc­ and general description oLmaterial to be sup­
cupation or simitar 1axes which may be im- plied. Ne wark should be done upon material to
posertare normally paid by the purchaserand, be furnished by seller until approved shop
in the case of-sales taxes, through the seller. drawings_are in his possession.
For tax exempt prepets, purchaser issues to
the seller a tax-exempt-certificate when the pur­ 22. Delivery— Delivery times o r schedules set
chase agreement is finalized. forth in contract agreements should be com­
puted from the date of delivery to the seller of
16. Insurance— Seller shall' carry Workmen’s approved shop drawings. Where materials are
Compensation, Public Liability, Property Dam­ specified to b e delivered FOB to jobsite, the
age and Auto Insurance and certificates of in­ purchaser should provide labor, cranes or oth­
surance will be furnished to purchaser upon re­ er equipment to remove the materials from the
quest. Additional coverage required over and trucks and should pay seller lo r truck expense
above that provided by the seller is normally for time at the jobsite in excess of a specified
paid by the purchaser. time for each truck. On shipments to be deliv­
ered by trucks, delivery should be made as
17. Services— Heat, water, light, electricity, toilet, near to the construction site as the truck can
telephone, watchmen and generaf services of a travel under tts own power. In the event delivery
similar nature are normally the responsibility of is required beyond the curb line, the purchaser
the purchaser unless specifically stated other­ should assume full liability for damages to side­
wise in the contract agreement walks, driveways or other properties and
should secure in advance all necessary per­
18. Safety Equipment—The purchaser is normal­ mits or licenses to effect such deliveries.
ly responsible for necessary barricades, guard
rails and warning lights for the protection of ve­ 23. Builder’s Risk insurance—Purchaser should
hicular and pedestrian traffic and responsible provide Builder’s Risk Insurance without cost
for furnishing, installing and maintaining all to seller, protecting seller’s work, materials and
safety appliances and devices required on the equipment at the site from loss or damage
project under U.S. Department of Labor, Safety caused by fire or the standard perils of ex­
and Health Standards for Construction Industry tended coverage, including vandalism and ma­
(OSHA 2207), as well as all other safety regula­ licious acts.
tions imposed by other agencies having juris­
diction over the project. 24. Erection— Purchaser should ensure that the
proposed project will be accessible to all nec­
19. Warranty—Seller should provide specific infor­ essary equipment including cranes and trucks,
mation relative to warranties given, including and that the operation of this equipment will not
limitations, exclusions and methods of settle­ be impeded by construction materials, water,
ment. Warranties should not be in excess of presence of wires, pipes, poles, fences orfram-
warranty required by the specific project. ings. Purchaser should further indemnify and
save harmless the seller and his respective rep­
20. Title— Con tract sh o u ld provide for proper iden­ resentatives, including subcontractors, ven­
tification of title to material furnished, tt is nor­ dors, assigns and successors from any and all
m al practice for title an d risk of lo s s or d a m a g e liability, fine, penalty or other charge, cost or
to the prod uct furnished to p a s s to the p u rc h a s­ expense and defend any action or claim
er at the point of delivery, except in c a s e s of brought against seller for any failures by pur­
F O B plant, in w hich event title to an d risk of lo s s chaser to provide suitable access for work to
or d a m a g e to the product norm ally sh o u ld p a s s be performed. Seller also reserves the right to
to p u rch ase r at plant pickup. discontinue the work for failure of purchaser to
provide suitable access and the purchaser
21. Shop Drawing Approval— Seller sh o u ld pre­ should be responsible for all expenses and
pare a n d su b m it to pu rch aser for approval all costs incurred.
s h o p d ra w in g s* n e c e ssa ry to describe the
w ork to be com pleted. S h o p draw ing approval 25. Exclusions of Work to be Performed—Un­
sh o u ld constitute final agree m e n t to quantity less otherwise stated in the contract, all shor­
ing, forming, framing, cutting holes, openings
*S ee Sect. 4 for definition of shop drawings.
for mechanical trades and other modifications

PCI Design Handbook/Fifth Edition


1 0 -4 1
of seller’s products should not be performed by terpretation of co ntractaaHdocume nts, it is rec­
the seller nor are they included* in-the contract ommended that the seller stipulate that-all
price, Seiler shouldnot be held responsible “for claims, disputes-and other. matters in question,-
modifications made by others-to his product arising out of or related to thercontract, be de­
unless said modifications ere- previously ap- cided by arbitration in accordance with “the
proved by him. Construction Industry- Rules of the American
Arbitration Association then obtaining, or some
26. Sequence of Erection—Sequence o f erec­ other rules acceptable to both parties. The
tion, when required to satisfy stability of the location for such arbitration should be stipu­
structure, should be as agreed upon between lated
seller and purchaser and expressly stated in
the contract agreement. Purchaser should 28. Contract Form—Contract documents should
have ready all foundations, bearing walls or stipulate policy governing acceptance of pro­
other units to which seller’s material is to be af­ posal on other then the seller’s form. In the
fixed, connected or placed, prior to start of event purchaser does not accept the seller’s
erection. Purchaser should be responsible for proposal and/or contract agreement, but re­
the accuracy of all job dimensions, bench quires the execution o f a contract on his own
marks, and true and level bearing surfaces. form, it is advisable that seller stipulate in writ­
Claims or expenses arising from the purchas­ ing on the contract agreement that the contract
er’s neglect to fulfill this responsibility should will be fulfilled according to his proposal origi­
be assumed by the purchaser. nally submitted. All identifying information such
as proposal number, dates, etc. should be in­
27. Arbitration— In view of the difficulties and mis­ cluded so there can be no question of the doc­
understandings which may occur due to misin­ ument referred to.

1 0 -4 2 PCI Design Handbook/Fifth Edition


10.4 RECOMMENDATIONS ON RESPONSIBILITY
TO R DESIGN AND CONSTRUCTION OF
PRECAST CONCRETE STRUCTURES

1. INTRODUCTION Construction Manager—A person or firm en­


gaged by the Owner to manage and administer the
Design and construction of structures is a com­
construction.
plex process.Defining the scope of work and the re­
sponsibilities of the parties involved in this process,
Design (as a transitive ^rerb)—The process of
by contract, is necessary to achieve a safe, high qual­
utilizing the principles of structural mechanics and
ity structure.
materials science to determine the geometry, com­
Besides the Owner, the parties involved in the de­
position, and arrangement of members and their con­
sign and construction of precast concrete structures
nections in order to establish the composition and
or other structures containing precast concrete mem­
configuration of a structure.
bers may include the Engineer, Architect, Construc­
tion Manager, General Contractor, Manufacturer, Design (as a noun)—The product of the design
Precast Engineer, Erector and Inspector. These and process, as usually expressed by design drawings
other terms related to precast concrete construction a nd specifications.
are defined in Sect. 2.0.
Design Drawings—Graphic diagrams with di­
mensions and accompanying notes that describe the
2. TERMINOLOGY structure.
Terms used in engineering practice and the Detail (as a transitive verb)—The process of uti­
construction industry may have meanings that differ lizing the principles of geometry and the art of graph­
somewhat from ordinary dictionary definitions. The ics to develop the dimensions of structural compo­
following definitions are commonly understood in nents.
precast concrete construction.
Detail (as a noun)—The product of the detailing
Approval (Shop Drawings or Submittals)—Ac­ process, shown on either design or shop drawings,
tion with respect to shop drawings, samples and oth­ such as the graphic depiction of a connection.
er data which the General Contractor is required to Engineer/Architect—A person or firm engaged
submit, but only for conformance with the design re­ by the Owner or the Owner’s representative to design
quirements and compliance with the information giv­ the structure and/or to provide services during the
en in the contract documents. Such action does not construction process. In some cases the Engineer
extend to means, methods, techniques, sequences may be a Subcontractor to the Architect, or vice ver­
or procedures of construction, or to safety precau­ sa. The Engineer of Record is usually an individual
tions and programs incident thereto, unless specifi­ employed by the Engineer or Architect.
cally required in the contract documents.
Engineer of Record (EOR)—The registered pro­
Authority—The power, conferred or implied by fessional engineer (or architect) who is responsible
contract, to exercise effective direction and control for developing the design drawings and specifica­
over an activity for which a party has responsibility. tions in such a manner as to meet the applicable re­
Connection—A structural assembly or compo­ quirements of governing state laws and of local build­
nent that transfers forces from one precast member ing authorities. The EOR is commonly identified by
to another, or from one precast member to another the professional engineer’s seal on the design draw­
type of structural member. ings and specifications.

Contract Documents—The design drawings and Erector— Usually the Subcontractor who erects
specifications, as well as general and supplementary the precast concrete components at the site. The
conditions and addenda, that define the construction General Contractor may also be the Erector.
and the terms and conditions for performing the General Contractor—A person or firm engaged
work. These documents are incorporated by refer­ by the Owner to construct all or part of the project.
ence into the contract. The General Contractor supervises the work of its
Contractor—A person or firm that enters into an Subcontractors and coordinates the work with other
agreement to construct all or part of a project. Contractors.

PCI Design Handbook/Fiffri Edition


1 0 -4 3
Inspector—The person or firm retained b y the This generally requires that-a registered professional
Owner or the Owner’s representative to observe-and engineer or architect accept responsibility .as. the En­
report on compliance of the construction with the gineer of Record (EOR) for-ensuring that these re-
contract documents. quirements-are met. The EOR'sealsthe contract doc­
uments. These documents constitute the structural
Manufacturer (Producer, Precaster, Fabrica­
design and are customarily submitted to regulatory
tor)—The firm that manufactures the precast con­
authorities for a building? permit, in addition, the EOR
crete components.
ordinarily approves shop drawings. The EOR may
Owner—The public body or authority, corpora­ also have other ongoing responsibilities during
tion, association, firm or person for whom the struc­ construction to satisfy local authorities.
ture is designed and constructed. Structures are usually designed by an engineer-
ingfirm that is retained by or on behalf of the Owner. A
Precast Concrete—Concrete cast elsewhere person within the firm is selected to prepare and/or to
than in its final position, includes prestressed and supervise the preparation of the contract documents.
non-prestressed components used in structural or This person normally is registered to practice engi­
nonstructural applications. neering in the state where the structure will be built
Precast Engineer—The person or firm who de­ and becomes the EOR when the design drawings
signs precast members for specified loads and who and specifications are approved by the locar regula­
may also direct the preparation of the shop drawings. tory authority. An individual in private practice may
The Precast Engineer may be employed by the also be retained by an Owner to prepare the design
Manufacturer o r be an independent person or firm to and become the EOR. The design drawings and the
whom the Manufacturer subcontracts the work. specifications become a part of the contract docu­
ments used by contractors to construct the structure.
Responsibility—Accountability for providing the A critical function of the contract documents is to
services and/or for performing the work required by clearly define responsibility among involved design
contract. professionals. The contract drawings, at a minimum,
should include all of the items listed in Sect. 10.3,
Shop Drawings—Graphic diagrams of precast
members and their connecting hardware, developed Subsection 3.2.
from information in the contract documents. They Procedures that allow consideration of alternative
show information needed for both field assembly construction schemes are sometimes included in the
(erection) and manufacture (production) of the pre­ contract documents. If a fully developed design is in­
cast concrete. Shop drawings for precast concrete cluded in the contract documents, a contractor pro­
may be separated into erection and production draw­ posing an aiternate for some part of the structure is
ings. Erection drawings typically describe the loca­ expected to consider the effect of the alternate on all
tion and assembly details of each precast member at other parts of the structure, and to provide all neces­
the construction site. Connection hardware is de­ sary design changes. It is common to require that an
tailed on erection drawings and may be shown on alternate design be prepared under the direction of
production drawings. Production drawings contain an engineer registered to practice in the state where
all information necessary for the manufacturer to cast the structure will be built. However, the EOR still has
the member. the responsibility to review and accept the alternate
and to submit the alternate to the regulatory authori­
Specifications—Written requirements for materi­ ties.
als and workmanship that complement the design Owners may also directly seek proposals from
drawings. General Contractors who are willing to prepare the
Subcontractor—A person or firm contracting to design. The General Contractor may use an
employed registered professional engineer who is
perform all or part of another’s contract.
the EOR, or subcontract the design to a firm or indi­
vidual who becomes the EOR. In some instances, a
3. DESIGN PRACTICES
Manufacturer may be the General Contractor. Since
Practices vary throughout North America with re­ the Owner will already have a contract with the se­
spect to design of structures using precast concrete lected General Contractor, any additional contracts
members. However, it is of fundamental importance will be between the General Contractor and Subcon­
that every aspect of the design be in accordance with tractors. Under this arrangement, the Owner often re­
the requirements of all state laws governing the prac­ tains an engineering consultant to review the propos­
tice of engineering and/or architecture, and also als and the design related work of the selected
meet all requirements of local regulatory authorities. General Contractor.

1 0 -4 4 PCI Design Handbook/Fifth Edition


Normally the Manufacturer is a Subcontractor to 4.1 To the Owner
the General Contractor. Most Manufaeturers_are w ilt­
A tlh a outset, th e Owner must decide whether to
ing to accept responsibility for component design o f
enter into a contract with an Engineer or Architect to
-the members that they produce, provided that suffi­
design and-prepare contract documents—for the
cient information is contained in th e contract docu­
structure which subsequently- can be used to obtain
ments^ This design work is commonly done by a Pre­
bids-by a General Contractor, o r with a General Con­
cast Engineer. The Manufacturer- may also accept
tractor (or Manufacturer willing to assume that re­
responsibility for design of the connections when the
sponsibility) to both design and build the structure.
forces acting on the connections are defined by the
These two arrangements may be summarized as fol­
EOR. At the time of bidding, if there is insufficient in­
lows:
formation in the contract documents to fully cover all
the reinforcement requirements, the Manufacturer 1. Owner retains an Engineer or Architect who will
customarily assumes that industry minimum stan­ be the EOR:
dards are acceptable.
Manufacturers usually have standard designs that a. To design and prepare contract docu­
fit common applications for their products and that ments sufficient for construction without
are sufficient for design purposes. Manufacturers further design by the General Contractor or
may design, produce and deliver a “structural frame” Sub-contractors.
or a “structural shell” rather than a building ready for b. To prepare contract documents sufficient
occupancy. In this case the Manufacturer may sub­ for construction with further design by the
contract for parts of the work, such as the cast-in- General Contractor or Subcontractor.
place concrete or the precast erection.
Local regulatory authorities may approve design 2. Owner contracts with a General Contractor for
documents for starting construction without final de­ design and construction.
sign of the precast members. The design can be per­
Under either arrangement, the Institute believes
formed and submitted at a later time, often in con­
that the best control of structural integrity will be
junction with preparation o f shop drawings. The
achieved when the EOR is given responsibility and
EOR, if not employed by the Manufacturer, may re­
authority for the entire structural design, including the
quire that a registered engineer seal the documents
connections, for review and approval of shop draw­
that depict the component design of the precast
ings, and for inspection during construction and ac­
members. This does not relieve the EOR of responsi­
ceptance of the finished construction. Under Ar­
bility to approve or accept the design as meeting the
rangement 1b, the contract documents must
requirements of the contract documents, state laws
establish the loadings and identify the criteria for de­
and local authorities. However, some states accept
sign to be used by the Contractor. Design work by
designs made by these persons, relieving the EOR of
any Contractor should be submitted to and approved
some responsibility. For example, these persons
by the EOR. The EOR may require the design and
have been called Delegated Engineers in the state of
shop drawings to be sealed by a registered profes­
Florida.
sional engineer as a demonstration of qualifications.
Under Arrangement 2, where the EOR will be en­
gaged or employed by the Contractor, it may be de­
4. RECOMMENDATIONS sirable for the Owner to retain another Engineer or Ar­
chitect for consultation on design criteria and
The Precast/Prestressed Concrete Institute is verification that the design intent is achieved.
keenly aware of the competitiveness in the market­ The Owner should consider the experience and
place for building systems. It believes precast con­ qualifications of both the Engineer or Architect and
crete products provide a high quality structure. Along the General Contractor with precast construction
with quality, it is essential that a structure be both safe similar to that for the intended project. If the Owner
and serviceable, i.e., have structural integrity and plans to have an active role in the project, it is essen­
perform as intended. Because the construction pro­ tial this role and lines of communication with the other
cess involves many parties, it is essential that work parties be clearly expressed in written documents
assignments and responsibilities be clearly defined in pertaining to the project. The Owner must allow suffi­
the contractual arrangements. The Institute offers the cient time in the various phases of the construction
following comments and recommendations towards process to achieve quality.
achieving quality and integrity in precast concrete Changes initiated after the start of construction in­
structures. variably add cost to the structure. A thorough review

PCI Design Handbook/Fifth Edition


1 0 -4 5
by the Owner after the design is completed, -before Where erection procedures require special design
construction is started, is essential. and calculations, the-contract- documents should
The Preeast/Prestressed -Concrete Institute con­ specify that a registered^ engineer perform-these ser­
ducts a format and rigorous Plant Certification Pro­ vices. The EOR’s review of this-work-shouid be limited
gram. This program is-recognized in the master to Its effect on the integrity of the completed structure.
specifications of4he American- Institute' of Architects, interfaces between precast-components and oth­
f t is also recommended and recognized in standard er construction materials require special attention.
specifications by numerous federal, state and local The EOR is responsible for considering these inter­
government agencies. PCI is recognized b y the face conditions during the design of the structure.
Council of American Building Officials (CABO} as a
Quality Assurance Inspection Agency. CABO in­
cludes the three national building codes. The Owner
or Engineer/Arcbitect should require that PCI Plant 4.3 To the General Contractor
Certification be written into the project specifications.
When the construction of a building that was inde­
pendently designed for the Owner is undertaken, the
4.2 To the EOR (Engineer/Architect) General Contractor’s responsibility is 1o build the
structure in accordance with the contract docu­
As discussed inSect. 3, the role of the EOR (Engi­
ments. When design responsibility is accepted by the
neer/Architect) varies significantly depending on
General Contractor, the professional nature of this
whether this party is retained b y the Owner or by oth­
function must be recognized and allowed to be
er parties, if retained by the Owner, the EOR’s lines of
achieved in a manner that does not compromise in­
communication among the parties involved in the
tegrity or impair quality.
project should be established by written documents.
The responsibilities o f the Manufacturer must be
Prebid and preconstruction conferences should be
clearly defined. It m ustbe understood that all design
held, during which lines of communication and re­
is submitted through the EOR for approval or accep­
sponsibilities are reviewed and the design require­
tance. The Manufacturer’s responsibility is usually
ments are discussed.
limited to product design and preparation of shop
if retained or employed by the General Contractor
drawings. However, it may include the design of the
or Manufacturer, the EOR must remain cognizant of
entire structure if agreed to by the Manufacturer.
the professional responsibility to satisfy state laws
When the Manufacturer is responsible only for
and local regulatory authorities. Procedures should
product design, all loads which are applied to the pre­
be established to allow the EOR to discharge these
cast members, including forces developed by re­
responsibilities without restriction by other parties in­
straint, must be provided by the EOR. The Manufac­
volved in the construction.
turer should be given responsibility and authority for
Review and approval of shop drawings by the
properly implementing the design drawings, properly
EOR is essential to ensure the design intent is
furnishing materials and workmanship, maintaining
achieved. Timeliness of review may be crucial to the
the specified fabrication and erection tolerances, and
Manufacturer. The EOR should establish the sched­
for fit and erectibility of the structure.
ule and define the responsibilities of the various par­
The Manufacturer must be given all of the draw­
ties involved in preparing shop drawings. These par­
ings and specifications that convey the full require­
ties should accept that the approval of the EOR does
ments for the precast members. Drawings are com­
not relieve them of their responsibilities.
monly divided into architectural, structural, electrical
The EOR should make clear whether the contract
and mechanical groupings depending on the size
documents, specifications or drawings prevail in the
and scope of the project. Other pertinent drawings
event of conflicts. It is recommended that they prevail
may also be desirable, such as approved shop draw­
in the order given above.
ings from other trades, roofing requirements, alter­
Where the design involves a non-self-supporting
nates, etc.
precast concrete frame, the contract documents
Timely review and approval of shop drawings and
should indicate which party is responsible for the de­
other pertinent information submitted by the
sign of the construction bracing and how long such
Manufacturer is essential.
bracing needs to remain in place.

1 0 -4 6 PCI Design Handbook/Fifth Edition


4.4 To the Manufacturer the revision should1be submitted to the EOR for re-
viewrandrapproval.
■After award-of the contract, the Manufacturer and
^Precast Engineer should meet with the EOR to review The Manufacturer and/or the Precast-Engineer
design requirements. The Manufacturer should pre- should have a direct-channel ofcommunication with
pare-shop drawings in accordance with the design in­ The EOR astheprpjectgoes forward and should keep
formation supplied in the contract documents and the General-Contractor informed.
subsequent rnstructions-from the EOR.
The Manufacturer should request clarification in
In those cases where the Manufacturer requests writing from the EOR on special connections or un­
permission to revise certain connections to facilitate usual structural conditions not clearly defined by the
manufacture and/or erection, information supporting design-drawings orspecifications.

The reader is referred to the following reports pre­


pared by other professional organizations rela­
tive to design responsibility:

1. ACI Committee on Responsibility in Con­


crete Construction, “ Guidelines for Authori­
ties and Responsibilities in Concrete De­
sign and Construction” , Concrete Interna­
tional, V. 17, No. 9, September 1995.
2. “Quality in the Constructed Project-Chap­
ter 16: Construction Contract Submittals”,
Manuals and Reports on Engineering Prac­
tice No. 73, American Society o f Civil Engi­
neers, New York, NY, 1990.

3. CASE Task Group on Speciality Engineer­


ing, “National Practice Guidelines for Spe­
ciality Structural Engineers,” Coalition of
American Structural Engineers, Washing­
ton, DC, 1996.

PC! Design Handbook/Fifth Edition 1 0 -4 7


PCI Design Handbook/Fifth Edition
10-48
10.5 PCI STANDARD DESIGN PRACTICE
Precast,^prestressedconcrete designishasedon the provisions of the Building
Code Requirements forStructural Concrete (ACI 3T8-95). In most cases, those provi­
sions are followed literally. Occasionally, though, there ^disagreem ent as to the
interpretation of some sections of the ACI Code. Also, in some situations, research
m ay support other design^and construction practices. In such cases, strict com­
pliance with the ACI provisions can cause design, production and performance prob­
lems that may unnecessarily increase the cost of a structure ormay actually resultin
a n inferior product.
In most cases, the practices reported herein are supported by many years of
good performanceand/or research. Members of the PCI Technical Activities Council
and the PCI Committee on Building Code, along with other experienced precast con­
crete design engineers, have identified these code provisions as detailed below. The
list of provisions represents a starting point for discussion, and complete agreement
with the positions taken is not expected. Mevertheiess, a listing of the design practic­
es followed by a majority of the precast concrete design engineers is anticipated to
be helpful In producing safe, economical precast, prestressed concrete structures
by minimizing conflict among the members of the design and construction team.
This list is based on ACI 318-95, and the numbers refer to sections in that docu­
ment. References to the PCI Design Handbook are to this edition. Excerpts from ACI
318-95 are reprinted with permission of the American Concrete institute, Farmington
Hills, Michigan. This information was first published inthePC/ J o u r n a l, March-April,
1997.
ACI Code provisions are on the left. PC/ P r a c t ic e is o n t h e r i g h t

ACI CODE PCI PRACTICE

1.1.5 — This code does not govern design and 1 .1 .5 — Prestressed concrete piles are normally
installation of portions of concrete piles and drilled designed using the PCI publication “Recommended
piers embedded in ground. Practice for Design, Manufacture and Installation of
Prestressed Concrete Piling,” PCI JOURNAL, V. 38,
No. 2, March-April 1993, pp. 15-41. (Ref. Handbook
Sect. 4.9.6)

1 .2.1 (e) — Size and location of all structural 1 .2 .1 ( e ) — “reinforcement’ in this case does not
elements and reinforcement. refer to prestressing steel. In precast concrete
members, reinforcement may be shown only on the
shop drawings. (Ref. Handbook Sect. 10.3.3.2)

1 .2.1 (g) — Magnitude and location of prestressing 1 .2 .1 ( g ) — For pretensioned concrete products,
forces. the prestressing design and detailing may be left to
an engineer employed or retained by the manufac­
turer. (Ref. Handbook Sects. 10.3 and 10.4)

1.2.2 — Calculations pertinent to design shall be 1.2.2 — Product calculations and frequently other
filed with the drawings when required by the items such as connections are usually done by the
building official. Analyses and designs using com­ manufacturer’s engineer. They are then submitted to
puter programs shall be permitted provided design the Engineer or Architect o f Record, who is
assumptions, user input, and computer-generated responsible for filing these documents with the
output are submitted. Model analysis shall be building official. (Ref. Handbook Sects. 10.3 and
permitted to supplement calculations. 10.4)

PCI Design Handbook/Fifth Edition


1 0 -4 9
ACl CODE. PCI PRACTICE^

3.5:2 — Welding of reinforcing bars-shall conform, 3.5.2 — A significant amount of connection field
to “Structural-VtelcBrrg Code - Reinforcing Steei,” w eldingis common in precast concrete construc­
ANSI/AWS D1.4 of the American Welding Society. tion. Tire American Welding Society (AWS) and
Type and location erf welded .splices and- other American institute of Steei Construction (AISC)
required welding of reinforcing bars shall- be recommendations are generally followed, with
indicated on the design drawings or in the project some modifications as shown in the PCI Design
specifications. ASTM reinforcing bar specifications, Handbook and the PCI manual “Design and Typical
except for ASTM A 706, shall be supplemented to Details o f Connections for Precast and Prestressed
require a report of material properties necessary to Concrete.” Other connection devices such as
conform to the requirements in ANSI/AWS D1.4. welded headed studs and deformed bar anchors
are also shown in these publications. Special
precaution is necessary when welding of stainless
steel reinforcing bars or plates is used. (Ref.
Handbook Sects. 1.3.4.3 and 6.5.1)

4.4.1— For corrosion protection of reinforcement 4.4.1 — Calcium chloride or other admixtures
in concrete, maximum water soluble chloride ion containing chlorides are rarely used in precast
concentrations in hardened concrete at ages from concrete, and never in prestressed concrete, as
28 to 42 days contributed from the ingredients required in Sect. 3.6.3. The requirements of this
including water, aggregates, cementitious materi­ section regarding prestressed concrete are as­
als, and admixtures shall not exceed the limits of sumed to be met when all materials used in the
Table 4.4.1. When testing is performed to determine concrete meet the appropriate ASTM specifications.
water soluble chloride ion content, test procedures See report by Donald W. Pfeifer, J. R. Landgren, and
shall conform to ASTM C 1218. William Perenchio, “Concrete, Chlorides, Cover and
Corrosion, ” PCI JOURNAL, V. 31, No. 4, July-August
1986, pp. 42-53. (Ref. Handbook Sect. 1.3.4)

5.11.3.2 — Accelerated curing shall provide a 5.11.3.2 — The Commentary states "... the elastic
compressive strength of the concrete at the load modulus, Ec, o f steam-cured specimen may vary
stage considered at least equal to required design from that of specimens moist-cured at normal
strength at that load stage. temperatures.” It is, however, most common for the
ACl equation to be used to calculate Ec even when
accelerated curing is used. Some producers may
recommend other values based on testing. (Ref.
Handbook Sect. 1.3.1.4) Also note that curing by
direct exposure to steam is seldom used in
precasting plants.

7.5.2 — Unless otherwise specified by the engi­ 7.5.2 — Precast concrete products will normally
neer, reinforcement, prestressing tendons, and conform to PCI tolerance standards specified in PCI
prestressing ducts shall be placed within the MNL 116, and Chapter 8 of the PCI Design
following tolerances: Handbook. Closer tolerances should not be speci­
fied except for special situations. (Ref. Handbook
Sect. 8.2.4)

7.6.7.1 — Clear distance between pretensioning 7.6.7.1 — 2 in. {51 mm) spacing o f strands is
tendons at each end of o member shall be not less typically used for strands up to 0.6 in. (15 mm) in
that 4dbfor wire, nor 3dbfor strands. See also 3.3.2. diameter. Tests on bridge beams at the University of
Closer vertical spacing and bundling of tendons Texas at Austin have shown no negative effects. See
shall be permitted in the middle portion of a span. report by Bruce W. Russell and Ned H. Bums,
"Measured Transfer Lengths o f 0.5 and 0.6 in.
Strands in Pretensioned Concrete,” PCI JOURNAL,
V. 41, No. 5, September-October 1996. With the %
in. (19 mm) maximum aggregate size used in most
products, consolidation of concrete has not been a
problem.

1 0 -5 0 PCI Design Handbook/Rfth Edition


AC1 CODE PCI PRACTICE

7.7.2 — Precast concrete^ (manufactured under 7.7.2 — When barsarew elded to plates, th a cover
plantcontroJconditions) may besomewhat lessJn the vicinity of the plate,
The-foHowing minimum concrete-cover shad be (Ref. Handbook Table 1.3:6)
provided for reinforcement:

(a) Concrete exposed to earth or weather:


Wall panels:
No. 14 and No. 18 bar ___ _____ V h
No. 11 bar and sm a lle r___ ............. %

Other members:
No. 14 and No. 18 bars . . . ............... 2
No. 6 through No. 11 bars . ............V/2
N a 5 bar, W31 orD31 wire,
and s m a lle r......................... ........... V A

(b) Concrete not exposed to weather o r in contact


with ground:
Slabs, walls, joists:
No. 14 and No. 18 bars . . . ........... V A
No. 11 bar and sm a lle r___ ............. %

Beams, columns:
Primary reinforcement........ .db but not
less than
% and need
not exceed 1Vz
Ties, stirrups, s p ira ls .......... ............. %

Shells, folded plate members:


No. 6 bar and larger .......... ............. %
No 5 bar, W31 or D31 wire,
and s m a lle r......................... ............. %

PCI Design Handbook/Fifth Edition


1 0 -5 1
ACI CODE PCI-PRACTICE

7.7.3=— Prestressed concrete 7.7.3" — For precast, prestressed~ concrete, the


provisfans joi Sect. 7.7.2 takepreeedence over Sect.
7 .7 ^ 1 — The fallowing minimum concrete cover 7J.3, and pmstressing steel cover requirements are
shall be =provide& for- prestressed and nonpre- the sameas bars o f the same diameter. Wythes, 2 in.-
stressed reinforcement, ducts, and end fittings, (50 mm) thick, are frequently used- in sandwich wall
except as provided in 7.7.3.2 and 7.7.3.3: p a n e ls - e x p o s e d to w e a th e r . S tra n d , % in. ( 9 . 5 m m )
in diameter, is most commonly used. Architects
(a) Concrete cast against and permanently ex­ should use caution in specifying reveals in thin-
posed to earth ............................................ 3 wythes. A minimum cover of % in. (19 mm) behind
the reveal is recommended. Architectural precast
(b) Concrete exposed to earth or weather:
concrete, where appearance is very critical, may
Wall panels slabs, joists........................... 1
require special consideration. (Ref. Handbook
Other m em bers...................................... VA
Table 1.3.6.) For further information on sandwich
(c) Concrete not exposed to weather or in contact wall panels, see “State-of-the-Art o f PrecastfPre-
with ground: stressed Sandwich Wall Panels’ by the PCI Commit­
Slabs, walls, jo is ts ................................... % tee on Precast Sandwich Wall Panels in the
March-April and May-June 1997 PCI Journals.
Beams, columns:
Primary reinforcement....................... VA
Ties, stirrups, s p ira ls .................... 1

Shells, folded plate members:


No. 5 bar, W31 or D31 wire, and
s m a lle r.................... %
Other reinforcement . . . db but not less
than %

7.7.3.2 — For prestressed concrete members ex­ 7.7.3.2 — “Exposed to weather” is interpreted to not
posed to earth, weather, or corrosive environments, include double tee stems in parking garages. Side
and in which permissible tensile stress of 18.4.2(c) cover of the prestressing and non-prestressing steel
is exceeded, minimum cover shall be increased may marginally not meet this requirement. Studies
50% by Robert Mast and Donald Pfeifer have indicated
that corrosion in prestressing strands is no greater
problem than in non-prestressed reinforcement.
[Ref. Handbook Table 1.3.6 Footnote (b)]

7.10.3 — It shall be permitted to waive the lateral re­ 7.10.3 — Sect. 7.10.3 waives minimum lateral ties
inforcement requirements of 7.10,10.16, and 18.11 with “tests and calculations. . .” Sect. 18.11.2.3
where tests and structural analysis show adequate specifically excludes prestressed walls from lateral
strength and feasibility of construction. reinforcement requirements. (Ref. Handbook Exam­
ple 4.9.1)

7.10.4 — Spirals 7.10.4 — Precast, prestressed concrete columns


Spiral reinforcement for compression members frequently use continuously wound rectangular wire
shall conform to 10.9.3 and to the following: for lateral reinforcement Sect. 7.10.4.2 specifically
applies only to cast-in-place construction, so the
minimum size requirements do not apply. The usual
practice is to design such columns as tied columns
under Sect. 18.11.2.2, with the wire sized and
spaced to provide an area equal to the minimum
7.10.4.1 — Spirals shall consist of evenly spaced
requirement for ties. There are several research
continuous bar or wire of such size and so
reports to support reduced tie requirements for
assembled to permit handling and placing without
prestressed columns. For further information, see
distortion from designed dimensions. report by PCI Prestressed Concrete Columns
Committee, “Recommended Practice for the Design
o f Prestressed Concrete Columns and Walls, ” PCI
JOURNAL, V. 33, No. 4, July-August 1988, pp. 56-95.

1 0 -5 2 PCI Design Handbook/Fifth Edition


ACI CODE PCI PRACTICE

7.13.3 — For precast -concrete construction, 7.13.3 — Methods of achieving structural integrity
tension ties shall be provided in the transverse, previously published in the PCI Design Handbook
longitudinal, and vertical directions and around the a rc now oodified~in Chapter 16. (Ref. Handbook
perimeter of the.structure to effectively tie elements Sect. 3.10)
together. The provisions of 16.5 shall apply.

8.3.2 — Except for prestressed concrete, approxi­ 8.3.2— The intent o f this section is to not allowSect.
mate methods of frame analysis shall be permitted 8.3.3 to be used for prestressed concrete framing.
for buildings of usual types o f construction, spans-, Approximate (e.g., “portal”) methods are sometimes
and story heights. used to design precast “light walls" in parking
structures. (Ref. Handbook Sect. 3.8.6)

8.10.2 — Width of slab effective as a T-beam flange 8.10.2 — Although Sect. 18.1.3 excludes this
shall not exceed one-quarter of the span length o f section, eight times the slab thickness is often used
the beam, and the effective overhanging flange as a guide for determining the topping width to be
width on each side of the web shaH not exceed: used in designing composite beams. Thin flange
members are commonly designed including the
(a) eight times the slab thickness, and entire flange width in the compression block. (Ref.
Handbook Examples 4.2.6 and 4.3.6)
(b) one-half the clear distance to the next web.

9.2.3 — if resistance to specified earthquake loads 9.2.3 — When the project is controlled by the
or forces E are included in design, load combina­ Standard Building Code (SBC) or the BOCA National
tions of 9.2.2 shall apply, except that 1.1 E shall be Building Code:
substituted for W. U = (1.1 + 0.5Aj)D + Floor Live + (0.7)Snow + E

or

U = (0.9 - 0.5A,)D + E
(Av is a coefficient that varies geographically)

Note that this means that seismic forces calculated


by the methods in the above model codes are
factored (ultimate) forces. (Ref. Handbook Example
3.11.9)

9.2.7 — Where structural effects T of differential 9.2.7 — It should be emphasized that structural
settlement, creep, shrinkage, expansion of shrink­ effects of T are not to be considered simultaneously
age-compensating concrete, or temperature with wind or earthquake forces. (Ref. Handbook
change are significant in design, required strength Sect. 3.3) Structural effects of T need only be
U shall be at least equal to considered when the structural element is re­
strained and can produce internal forces as a result
U = 0.75(1.4D + 1,4T + 1.7L) (9-5)
ofT.
but required strength U shall not be less than

U = 1.4(D + T) (9-6)

Estimations of differential settlement, creep, shrink­


age, expansion of shrinkage-compensating con­
crete, or temperature change shall be based on a
realistic assessment of such effects occurring in
service.

PCI Design Handbook/Fifth Edition


1 0 -5 3
ACI CODE PCI PRACTICE

9t5 — Control of deflections

9.5.4— Prestressed concrete construction 9.5.4 — DeftexHons-ace-always calculated for


prestressed concrete members. Calculations wlll-
usually Include both instantaneous and long-term
9.5.4. T — For- flexural members designed- in
accordance with provisions of Chapter 18, immedi­ camber and dead and live load deflection. The
ate deflection shall be computed by usual methods Engineer or Architect of Record will determine if this
meets requirements, e.g., Table 9.5(b), as satisfac­
orformulas for elastic deflections, and the moment
tory performance may depend on many non-struc-
of inertia of the gross concrete section shaH be
turai considerations. (Ref. Handbook Sect. 4.8 and
permitted to be used for uncracked sections.
Table 4.8.1)

9.5.4.2 — Additional long-term deflection of pre­


stressed concrete members shall be computed
taking into account stresses in concrete and steel
under sustained load and including effects of creep
and shrinkage o f concrete and relaxation of steel.

9.5.4.3 — Deflection computed in accordance with


9.5.4.1 and 9.5.4.2 shall not exceed limits stipulated
in Table 9.5(b).

10.4.1 — Spacing of lateral supports for a beam 10.4.1 — The spans of non-bearing spandrels on
shall not exceed 50 times the least width b of parking structures have frequently exceeded 50
compression flange or face. times the width of the top of the member, and no
problems have been observed. This is undoubtedly
because they typically carry only their own weight,
which, o f course, is concentric (see ACI 318
Commentary to this section). Where lateral (bumper)
loads are applied to the spandrel, lateral supports at
mid-height o f the spandrel into the deck are typical.

10.6.4 — When design yield strength fy for tension 10.6.4 — Note that Sect. 10.6 is specifically
reinforcement exceeds 40,000 psi, cross sections excluded for prestressed concrete (Sect. 18.1.3).
of maximum positive and negative moment shall (Ref. Handbook Sect. 4.2.2.1 and Table 4.2.1)
be so proportioned that the quantity z given by

z = fs3
v^A (10-5)

does not exceed 175 kips/in. for interior exposure


and 145 kips/in. for exterior exposure. Calculated
stress in reinforcement at service load t, (kips/in.2)
shall be computed as the moment divided by the
product of steel area and internal moment arm.
Alternatively, it shall be permitted to take fs as 60
% of specified yield strength fy.

10.9.3 — Ratio of spiral reinforcement ps shall be 10.9.3 — See discussion of Sects. 7.10.4 and
not less than the value given by 18.11.2.2.

(1 M )
where fy is the specified yield strength of spiral
reinforcement but not more than 60,000 psi.

1 0 -5 4 PCI Design Handbook/Fifth Edition


ACt CODE PCI PRACTICE

10,143— Slenderness effects incompression^ 10.10— The PCIDesignttandbook, Chapters 3 and


members 4, addresses the application o f these sections to
precast and prestressed Goktmns. (Ref. Handbook
10.10.1 — Except as allowed in 10.10.2, the design Sects. 3.5.1, 3.5,2 and 4.9.2)
of compression members, restraining beams, and
other supporting members shall-be based on the
factored forces and moments from a second-order
analysis considering material nonlinearity and
cracking, as well as the effects o f member curvature
and lateral drift, duration of the loads, shrinkage and
creep, and interaction with the supporting founda­
tion. The dimensions of each member cross section
used in the analysis shall be within 10 % of the
dimensions of the members shown on the design
drawings or the analysis shall be repeated. The
analysis procedure shall have been shown to result
in prediction of strength in substantial agreement
with the results of comprehensive tests of columns
in statically indeterminate reinforced concrete struc­
tures.

10.10.2 — As an alternate to the procedure


prescribed in 10.10.1, it shall be permitted to base
the design of compression members, restraining
beams, and other supporting members on axial
forces and moments from the analyses described
in 10.11.

11.1.3.1 — For nonprestressed members, sections 11.1.3.1 — In beams with loads applied below the
located less than a distance d from the face of top of the member, such as L-beams or inverted
support shall be permitted to be designed for the tees, the critical section to compute shear Vu and
same shear Vu as that computed at a distance d. torsion Tu is taken at a distance from the support
equal to the distance between the height of the load
application and the centroid o f flexural reinforce­
ment. Effective depth d for computing shear
capacity §Vn and torsion capacity §Tn is taken as
defined in ACI Sect. 11.0. (Ref. Handbook Sect. 4.3).

11 .1.3.2 — For prestressed members, sections 11.1.3.2 — In beams with loads applied below the
located less than a distance h/2 from face ofsupport top o f the member, such as L-beams or inverted
shall be permitted to be designed for the same tees, the critical section to compute shear Vu and
shear Vu as that computed at a distance h/2. torsion Tu is taken at a distance from the support
equal to the distance between the height of the load
application and one-half the distance to the bottom
o f the beam. Effective depth d for computing shear
capacity §Vn and torsion capacity <$>Tn is taken as
defined in ACI Sect. 11.0. (Ref. handbook Sect. 4.3).

PCI Design Handbook/Rftti Edition 1 0 -5 5


ACI CODE PCTPRACTICE

11.5.5 — Minimumsheaereinforcement 11.5.5 — If Vu is less than <j>Vc, shear reinforcement


is-omitted in prestressed double tees. A nominal
11,5.5.1 — A minimum area of shear reinforcement miniimmris provided for 5 to 10 ft (1.5 to 3 m) from
shall- be provided in all reinforoecLconcrete flexural the ends. This is based on research by-Alex Aswad
members (prestressed'and nonprestressed) where and George Burnley, “Omission of Web Reinforce­
factored shear force Vu exceeds one-half the shear ment in Prestressed Double Tees, ’ PCI JOURNAL,
strength provided byooncrete <)>VC, except: V. 34, No. 2, March-April 1989, pp. 48-65. The
approach is- permitted by Sect. 11.5.5.2. (Ref.
(a) Slabs and footings Handbook Sects. 4.3 and 4.3.4)
(b) Concrete joist construction defined by 8.11

(c) Beams with total depth not greater than 10 in.,


21/2 times thickness of flange, or Vfc the width
of web, whichever is greatest.

11.6 — Design for torsion 11.6 — Torsion design has typically been done
using the Zia-McGee (PCI Design Handbook, 2nd
Edition) or Zia-Hsu (4th Edition) methods. Most
computer programs may not yet be updated to ACI
318-95. The reinforcement requirements are similar
for any o f the methods. Note that concrete torsion
strength Tc is no longer included in the new torsion
design method. (Ref. Handbook Sect. 4.4)

11.7.3 — A crack shall be assumed to occur along 11.7.3 — The “effective shear-friction” method
the shear plane considered. The required area of described in the PCI Design Handbook is most often
shear-friction reinforcement A^ across the shear used. Use is permitted under Sect. 11.7.3. (Ref.
plane shall be designed using either 11.7.4 or any Handbook Sect. 4.3.6)
other shear transfer design methods that result in
prediction of strength insubstantial agreement with
results of comprehensive tests.

11.9.3.2.1 — For normal weight concrete, shear 11.9.3.2.1 — The PCI Design Handbook allows V„
strength Vn shall not be taken greater than up to 1000bwd. This is consistent with the “effective
0 .2f' bwd nor 800bwd in pounds. shear-friction” approach when concrete strengths of
5000 psi (34 MPa) and greater are used. (Ref.
Handbook Table 4.3.1)

1 1.9.3.4. — Reinforcement An to resist tensile force 11.9.3.4 — Bearing pads are used to “avoid tensile
Nuc shall be determined from Nuc < c|)Anfy. Tensile forces.” The PCI Design Handbook suggests that a
force Nuc shall not be taken less than 0.2VU unless value of Nuc which will cause the pad to slip is the
special provisions are made to avoid tensile forces. maximum that can occur, or, alternatively, a value of
Tensile force shall be regarded as a live load 0.2Vudead is used as a guide. (Ref. Handbook Sects.
even when tension results from creep, shrinkage, or 4.6.1, 4.6.2, 6.3 a n d 6.8)
temperature change.

11.9.6 — At front face of bracket or corbel, primary 11.9.6 — Frequently, front face anchorage is by
tension reinforcement As shall be anchored by one welding to an angle or a plate with vertical anchors.
of the following: (a) by a structural weld to a This is permitted by Sect. 11.9.6(c). (Ref. Handbook
transverse bar of at least equal size; weld to be Sect. 6.8)
designed to develop specified yield strength fy of As
bars; (b) by bending primary tension bars As back
to form a horizontal loop; or (c) by some other
means of positive anchorage.

1 0 -5 6 PCI Design Handbook/Frfth Edition


ACT CODE PCI PRACTICE

1 "L9.7 — Bearing area of load on bracket o r corbel 11.3.7 — If primary: tension bars are-anchored by
shall not-project beyond-straight portion of primary- welding (Sect. 11.9.6), the bearing area can be
tension-bars-Ag. nor project beyond interior face of considered to extend to.the exterior face o f the
transverse anchor bar (if one is- provided). anchoring bar o r piate. This section is not typically
applied to beam ledges, whereledgereinforcemerrt
is typically anchored by bending bars near the front
face. Research sponsored by PCI Specially Funded
Research and Development Project No. 5, “Design
of Spandrel Beams,” addressed this issue, and
found that placement of bars is critical. (Ref.
Handbook Sect. 6.8)

11.10.9 — Design of shear reinforcement for 11.10.9 — Sects. 11.10.6.2 through 11.10.9.4 apply
walls only when the in-plane shear, Vu > <j>Vc, as described
in 11.10.9.1. Otherwise, minimum reinforcement
11.10.9.1 — Where factored shear force Vu required by Sect. 16.4.2 applies (0.001 times the
exceeds shear strength <pVc, horizontal shear gross cross-sectional area).
reinforcement shall be provided to satisfy Eq.
(11-1) and (11 -2), where shear strength Vs shall be
computed by

VS = ^ M (11-33)

where Ay is area of horizontal shear reinforcement


within a distance s2 and distance d is in accor­
dance with 11.10.4. Vertical shear reinforcement
shall be provided in accordance with 11.10.9.4.

12.5.1 — Development length € dh, in inches, for 12.5.1 — Bars in beam ledges are assumed to be
deformed bars in tension terminating in a standard developed with a hook, even when the straight
hook (see 7.1) shall be computed as the product of portion is less than 6 in. (152 mm), measured to the
the basic development length lhb of 12.5.2 and the stem face. See the research project referenced in
applicable modification factor or factors of 12.5.3, the Commentary of AC! 318 Sect. 11.9.7. (Ref.
but ldh shall not be less than 8db nor less than 6 in. Handbook Sect. 4.5.2)

12.9 — Development of prestressing strand 12.9 — The provisions o f this section are normally
followed in the design of prestressed concrete
members. Quality control measures are essential.
12.9.1 — Three- or seven-wire pretensioning strand
See Buckner, C. Dale, "A Review of Strand
'hair be bonded beyond the critical section for a
Development Length for Pretensioned Concrete
development length, in inches, not less than
Members,” PCI JOURNAL, V. 40, No. 2, March-April
1995, pp. 84-105; plus discussion in March-April
( fp s g fs e )d b 1966 PCI JOURNAL, pp. 112-127. See also special
report by Donald R. Logan, ”Acceptance Criteria for
where db is strand diameter in inches, and fps and Bond Quality o f Strand for Pretensioned Prestressed
fse are expressed in kips/in.2 Concrete Applications,” PCI Journal, V. 42, No. 2,
March-April 1997, pp. 52-90.

12.9.2— Limiting the investigation to cross sections 12.9.2 — When debonded strands are used, other
nearest each end of the member that are required sections may be more critical. See Martin, L , and
to develop full design strength under specified Korkosz, W., “Strength of Prestressed Concrete
factored loads shall be permitted. Members at Sections Where Strands Are Not Fully
Developed,” PCI JOURNAL, V. 40, No. 5, Septem-
ber-October 1995, pp. 58-66. (Ref. Handbook Sect.
4.2.3)

PCI Design Handbook/Frfth tdition


1 0 -5 7
ACI CODE PCI PRACTICE

12,11.1— At least one-third the positive moment^ 12.11.1 — Does not-apply to p re ca st construction.
reinforcement in simple members and one-fourth Excluded by Sect. 16, 6.2 3.
the positive moment reinforcement in continuous
members shall extend- along the same face of
member into the support In beams, such reinforce­
ment shall extend into the support at least 6 in.

12.13.2.4 — For each end o f a single leg stirrup of 12.13.2.4 — Figure Ft12.13.2Ashows how WWF is
welded plain ordeformed wire fabric, tw o longitudi­ used as shear reinforcement in double tee stems.
nal wires at a minimum spacing of 2 in. and with the For further information, see TAC’s Joint PCI/WRI Ad
inner wire at least the greater of d/4 or 2 in. frommid Hoc Committee on Welded Wire Fabric for Shear
depth of member d/2. Outer longitudinal wire at Reinforcement, “Welded Wire Fabric for Shear
tension face shall not be farther from the face than Reinforcement,” PCI JOURNAL, V. 25, No. 4,
the portion of primary flexural reinforcement closest July-August 1980, pp. 32-36.
to the face.

14.3 — Minimum reinforcement 14.3 — Minimum reinforcement for precast walls is


specified in Sect. 16.4.2.

14.6.1 — Thickness of nonbearing walls shall not 14.6.1 — Minimum thickness is not applicable to
be less than 4 in., nor less than the least distance prestressed walls. See Sect. 18.1.3.
between members that provide lateral support.

15.8.3.1 — Connection between precast columns 15.8.3.1 — Note reference to Chapter 16.
or pedestals and supporting members shall meet
the requirements of 16.5.1.3(a).

16.2.4 — In addition to the requirements for 16.2.4 — Connection design is typically a part of the
drawings and specifications in -1.2, the following precast contract and connection forces are typically
shall be included in either the contract documents developed by the precast engineer, or sometimes
or shop drawings: listed on the Contract Drawings. (Ref. Handbook
Sects. 10.3 and 10.4)
(a) Details of reinforcement, inserts and lifting
devices required to resist temporary loads
from handling, storage, transportation, and
erection.

(b) Required concrete strength at stated ages or


stages of construction.

1 0 -5 8 PCI Design Handbook/Fifth Edition


AC! CODE PCI PRACTICE

16.6.2.2 — Unless-shown by tesLor analysis that 76.6.2.2 — When shorter bearing lengths o c c w in
performance will not be impaired; the-following the field, analysis isusuallythe basis for acceptabili­
minimum requirements shall be met: ty. When designing-bearing lengths, the effects of
member shortening at expansion joints should be
(a) Each member and its supporting systerrrshalf considered.
have design dimensions selected so that, after
consideration oftolerances, the distance from
the edge o f the support to the end o f the
precast member in the direction of the spanis
at least 1/iso of the clear span ( but not less
than:

For solid or hollow-core s la b s ............... 2 in.


For beams or stemmed members ........3 in.

(b) Bearing pads at unarmored edges shall be set


back a minimum of Vz in. from the face of the
support, or a least the chamfer dimension at
chamfered edges.

16.8.1 — Each precast member shall be marked to 16.8.1 — Not all products are marked with the date
indicate its location and orientation in the structure of manufacture, but adequate records should be
and date of manufacture. kept to verify casting conditions.

17.5.2.1 — When contact surfaces are clean, free 17.5.2.1 — Standard precast concrete manufactur­
of laitance, and intentionally roughened, shear ing procedures for standard deck members are
strength Vnh shall not be taken greater than 80b,d assumed to meet the requirement for Intentionally
in pounds. roughened' (Ref. Handbook Sect. 4.3.5) Industry
tests confirm this practice to be safe.

18.4.1 — Stresses in concrete immediately after 18.4.1 (a) — Initial compression is frequently
prestress transfer (before time-dependent pre­ permitted to go higher in order to avoid debond­
stress losses) shall not exceed the following: ing or depressing strands. No problems have
been reported by allowing compression as high
(a) Extreme fiber stress in compression. 0.60^ as 0.70 fd.

(b) Extreme fiber stress in tension except as


permitted in (c) .............................. . 3
18.4.1 (b) (c) — Initial tension is typically allowed
(c) Extreme fiber stress in tension at ends of to go as high as 6 Mi throughout most o f the
simply supported members ......... 6 /fj~ member. Because of member self weight, the
transfer stresses decrease from the end to
Where computed tensile stresses exceed these midspan o f a simply supported member. It is not
values, bonded auxiliary reinforcement (nonpres- clear how far into the span “at ends ” can be used.
tressed or prestressed) shall be provided in the (Ref. Handbook Sect. 4.2.2.2)
tensile zone to resist the total tensile force in
concrete computed with the assumption of an
uncracked section.

PCI Design Handbook/Fifth Edition 1 0 -5 9


— ♦ A C fC O D E PCI PRACTICE

18.4.2— Stresses in concrete at service-loads (after 18.4.2 (c) — The limitaiion of 6 TfT isseldom used.
allowance for all-prestress losses) shall- n o t exceed Bilinear deflection behavior, as shown in the PCI
the following: Design Handbook, uses 7.5-JfT as the cracking
stress, so anything at that value or below would
(a) Extreme- fiber stress in compression- due to comply with- 18.4.2(c).
prestress plus sustained lo a d s ......... 0.45fc
18.4.2 (d ) — See discussion o f Sect. 7.7.3.2.
(b) Extreme fiber stress in- compression due to
prestress plus total lo a d ......... . — 0.60fc

(c) Extreme fiber stress in tension in precom­


pressed tensHe z o n e ......................... 6

(d) . Extreme fiber stress in tension in precom­


pressed tensile zone of members (except
two-way slab systems), where analysis based
on transformed cracked sections and on
bilinear moment-deflection relationships
shows that immediate and long-term deflec­
tions comply with requirements of 9.5.4., and
where cover requirements comply with 7.7.3.2
........................................................ 1 2 /ff

18.6 — Loss of prestress 18.6 — Most structural engineers who specialize in


the design of prestressed concrete follow the
18.6.1 — To determine effective prestress fse, recommendations ofACI-ASCE Committee 423 task
allowance for the following sources of loss of force given in Ref. 18.6. (Ref. Handbook Sect. 4.7)
prestress shall be considered:

(a) Anchorage seating loss

(b) Elastic shortening of concrete

(c) Creep of concrete

(d) Shrinkage of concrete

(e) Relaxation of tendon stress

(f) Friction loss due to intended or unintended


curvature in post-tensioning tendons.

1 0 -6 0 PCI Design Handbook/Fifth Edition


ACI CODE PCI PRACTICE

1-8,7.2 — -As- an-aiternative to -a more accurate 18.7:2 — Many engineers-use strain compatibility
determination of f ^ based on strain compatibility, analysis for determining fps.O thersuse Bqr (18-3).
the following approximate values of fpsshall be used With low-relaxation strand, the Jesuits a re not
if fs ris not less than-0.5fpu. substantially-different (Ref. Handbook-Sect. 4.2.1)

(a) F or members with bonded prestressing ten­


dons:

If any compression reinforcement is taken into


account when calculating fps by Eq. (18-3), the term

shalt be taken not less than 0.17 a n d d ' shall be no


greater than 0.15dp.

18.8.3 — Total amount of prestressed and nonpre- 18.8.3 — For simple span members, this provision
stressed reinforcement shall be adequate to devel­ is generally assumed to apply only at critical flexural
op a factored load at least 1.2 times the cracking sections. (Ref. Handbook Sect. 4.2.1)
load computed on the basis of the modulus of rup­
ture fr specified in 9.S.2.3, except for flexural mem­
bers with shear and flexural strength at least twice
that required by 9.2.

18.11.2.1 — Members with average prestress fpc 18.11.2.1 — Columns which are larger than
less tha o 225 psi shall have minimum reinforcement required for architectural purposes will use the level
in accordance with 7.10, 10.9.1 and 10.9.2 for of prestress for the size of column needed. For
columns, or 14.3 for walls. example, if a 16 x 16 in. (406 x 406 mm) column
will carry the load, but a 24 x 24 in. (610 x 610 mm)
column is used, the total prestress force necessary
is 225 (16 x 16) = 57,600 lb (26 127 kg). This
practice is supported by Sects. 10.8.4 and
16.5.1.3 (a).

PCI Design Handbook/Fifth Edition


10-61
ACt CODE PCI PRACTICE

t8.t1.2v2 — Except for wails, members with aver- 1 8 .1 1 .2 .2 — The PCI Prestressed Concrete Col­
age prestress fpc equal to or greater than 225 psi umns Committee report, “Recommended Practice
shall have all prestressing tendons enclosed by spi- for the Design of Prestressed Concrete Columns
rals- or lateral ties in accordance with the following: and Walls, ” recommends that column capacity be
reduced to 85 % of calculated if ties do not meet ali
(a) Spirals shall conform to 7.10.4. o f the requirements. Most producers use some ties,
(b) Lateral ties shall be at least No. 3 in size o r but may modify the size and spacing based on
research Note that waits are excluded from the
welded wire fabric of equivalent area, and
lateral tie requirements. Column ties are required in
spaced vertically not to exceed 48 tie bar or
seismic regions. (Ret Handbook Example 4.9.2)
wire diameters, or least dimension of com­
pression member.

(c) Ties shall be located vertically not more than


half a tie spacing above top o f footing or slab
in any story, and shall be spaced as provided
herein to not more that half a tie spacing beiow
lowest horizontal reinforcement in members
supported above.

(d) Where beams or brackets frame into all sides


of a column, it shall be permitted to terminate
ties not more than 3 in. below lowest reinforce­
ment in such beams or brackets.

21.6.4.2 — Cast-in-place composite topping 2 1 .6 .4 .2 — When the composite requirements are


slab diaphragms met, the diaphragm thickness includes both the
A composite topping slab cast-in-place on a precast topping and the precast flange or top wythe. (Ref.
floor or roof system shall be permitted to be used as Handbook Sect. 3.6)
a diaphragm provided the topping slab is reinforced
and its connections are proportioned and detailed
to provide for a complete transfer of forces to
chords, collector elements, and resisting elements.
The surface of the previously hardened concrete on
which the topping slab is placed shall be clean, free
of laitance, and shall be intentionally roughened.

21.7.1 — Frame members assumed not to contrib­ — The Northridge Earthquake showed the
2 1 .7 . 1
ute to lateral resistance shall be detailed according importance of this section. See James K. Iverson
to 21.7.2 or 21.7.3 depending on the magnitude of and Neil M. Hawkins, “Performance of Precast/Pre-
moments induced in those members when sub­ stressed Concrete Building Structures During North­
jected to twice the lateral displacements under the ridge Earthquake," PCI JOURNAL, V. 39, No. 2,
factored lateral forces. When effects of lateral March-April 1994, pp. 38-55. It should also be
displacements are not explicitly checked, it shall be emphasized that some nominal ties, at least equiva­
permitted to apply the requirements of 21.7.3. lent to the structural integrity requirements of
Chapter 16, should be used in these non-lateral-
load-resisting frames.

1 0 -6 2 PCI Design Handbook/Fifth Edition


CHAPTER 11
GENERAL DESIGN INFORMATION

11.1 Design Information ........................................................................................... 1 1 -2


11.1.1 Dead Weights of Floors, Ceilings, Roofs, and W alls..................... 1 1 -2
1 1.1.2 Recommended Minimum Uniformly Distributed and
Concentrated Live Loads ................................................................. 1 1 -3
11 .1.3 Beam Design Equations and Diagram s.......................................... 1 1 -5
11 .1.4 Camber (Deflection) and Rotation Coefficients for Prestress
Force and Loads ............................................................................. 1 1-14
11.1.5 Moments in Beams with Fixed Ends .................................... — 11-16
11 .1.6 Moving Load Placement for Maximum Moment and S hear........ 11-17
11.1.7 Moments, Shears, and Deflections in Beams with Overhangs .. 11-18

11.2 Material Properties ........................................................................................ 11-19


11.2.1 Table of Concrete Stresses ........................................................... 1 1-19
1 1.2.2 Concrete Modulus of Elasticity as Affected by Unit Weight (pcf)
and Strength (psi) ........................................................................... 1 1-19
11 .2.3 Properties and Design Strengths of Prestressing
Strand and Wire ..................... 1 1-20
11.2.4 Properties and Design Strengths of Prestressing Bars............... 11-21
1 1.2.5 Typical Stress-Strain Curve, 7-Wire Low-Relaxation
Prestressing S tra n d ......................................................................... 11 -2 2
11 .2.6 Transfer and Development Lengths for 7-Wire Uncoated Strand 11-23
1 1.2.7 Reinforcing Bar D a ta ................................................................. . 11 -2 4
11 ,2.& Required Development Lengths for Reinforcing B ars................. 11-25
11 .2.9 Common Styles of Structural Welded Wire Reinforcement ___ 11-27
11.2.10 Special Welded Wire Reinforcement for Double Tee Flanges. . . 11-28
11 .2.11 Wires Used in Structural Welded Wire Reinforcement............... 11-28

11.3 Section Properties............................................................................................ 11 -2 9


1 1.3.1 Properties of Geometric S ectio n s................................................. 11 -2 9

11.4 MetricConversion............................................................................................. 11-32


11.4.1 Metric Calculations and Example ................................................ 11-32
1 1 .4.2 Conversion from U.S. Customary Units to International-
System (SI) ..................................................................................... 11 -3 3
11.4.3 Preferred SI Units and U.S. Customary Equivalents.................... 11-35
11 .4.4 Concrete Stress Coefficients .......................................................... 11 -3 5

PCI Design Handbook/Fifth Edition 11


Design Aid 11.1.1 Dead weights of floors, ceilings, roofs and walls®
i L o ad Load
ro Load
Com ponent (p s f) C om ponent (p s f) Com ponent (Psf)
Masonry walls* '
Ceilipgs Floor fill
Acoustical fiber board 1 Cinder concrete, per Inch 9 Clay brick wythes: 35
Gypsum board (per '/e-in. thickness) 0.55 Lightweight concrete, per inch 8 4 in. 7?
Mechanical duct allowance 4 Sand, per inch 8 8 in. 113
Plaster on tile or concrete 5 Stone concrete, per inch 12 1 2 in. 155
Plaster on wood lath 8 16 in.
Suspended steel channel system 2 Floors and floor finishes
Suspended metal lath and cement plaster 15 Asphalt block (2 -in.), '/6-in. mortar 30 Hollow Concrete masonry
Suspended metal lath and gypsum plaster 10 Cem ent finish (1 -in.), on stone-concrete fill 32 unit wythes:
W ood furring suspension system 2,5 Ceramic or quarry tile (%-in.) on '/4-in. mortar bed 16 Wythes thickness (in.) 4 6 8 10 ii
Coverings, roof, and wall Ceramic or quarry tile (%-in.) on 1 -in. mortar bed 23
Asbestos-cement shingles 4 Concrete fill finish (per inch thickness) 12 Density of unit (105 pcf):
Asphalt shingles 2 Hardwood flooring, %-in. 4 No grout 22 24 31 37 43
Cem ent tiles 16 Linoleum or asphalt tile, ’/ 4-in. 1 48" o.c. 29 38 47 55
Clay tile (for mortar add 10 lb.) Marble and mortar on stone-concrete fill 33 40" o.c. (grout 30 40 49 57

11.1 DESIGN INFORMATION


Book tile, 2-in. 12 Slate (per inch thickness) 15 32" o.c. spacing) 32 42 52 61
Book tile, 3-in. 20 Solid flat tile on 1-in. mortar base 23 24" o.c. 34 46 57 67
Ludowici 10 Sub-flooring, %-in. 3 16" o.c. 40 53 65 75
Roman 12 Terrazzo (lVfe-in.) directly on slab 19 Full grout 55 75 95 115
Spanish 19 Terrazzo (1-in.) on stone-concrete fill 32
PCI Design Handbook/Fifth Edition

Composition: Terrazzo (1-in.) 2-in. stone concrete 32 Density of unit (125 pcf):
Three-ply ready roofing 1 W ood block (3-in.) on mastic, no fill 10 No grout 26 28 36 44 50
Four-ply felt and gravel 5.5 W ood block (3-in.) on V4-in. mortar base 16 48" o.c. 33 44 54 62
Five-ply felt and gravel 8 40" o.c. (grout 34 45 56 65
Copper or tin 1 Floors, wood-joist (no plaster) 32" o.c. spacing) 36 47 58 68
Corrugated asbestos-cement roofing 4 Double wood floor 24" o.C. 39 51 63 75
1 6 " o.c. 44 59 73
Deck, metal 20 gage
Deck, metal 18 gage
2.5
3 Joist size
12-in.
spacing
16-in.
spacing
24-in.
spacing Full grout 59 81 •I 02
H
123
Decking, 2-in. wood (Douglas fir) 5 (in.) (psf) (psf) (psf)
Decking, 3-in. wood (Douglas fir) 8 2x6 6 5 5 Density Of unit (135 pcf):
Fiberboard, V4-in. 0.75 2x8 6 6 5 No grout 29 30 39 47 54
Gypsum sheathing, '/4-in. 2 2 x 10 7 6 6 48" o.C. 36 4i 57 66
Insulation, roof boards (per inch thickness) 2 x 12 8 7 6 40" o.c. (grout 37
38
48
50
59 p?
72
Cellular glass 0.7 32" o.c. spacing)
Fibrous glass 1.1 Frame partitions 24" o.c. 41 54 67 78
Fiberboard 1.5 Movable steel partitions 4 1 6 " o.c. 46 61 fe 90
Perlite 0.8 W ood or steel studs, '/4-in. gypsum board each side 8 Full grout 62 83 105 127
Polystyrene foam 0.2 W ood studs, 2 x 4 , unplastered 4
Urethane foam with skin 0.5 W ood studs, 2 x 4 , plastered one side 12 Solid concrete masonry unit

14
Plywood (per '/6-in. thickness) 0.4 W ood studs, 2 x 4 , plastered two sides 20 wythes:
Rigid insulation, '/?-in. 0.75 Wythe thickness (in.) 4 6 8 10
Skylight, metal frame, %-in. wireglass 8 Frame walls Density of unit (10j5 pcf): 32 51 69 37
Slate, 3/i6-in. 7 Exterior stud walls: Density of unit (125 pcf): 38 60 81 102 124
Slate, '/4-in. 10 2 x 4 @ 16-in., %-in. gypsum, insulated, %-in. siding 11 Density of unit (135 pcf): 41 64 87 110 (3 3
Waterproofing membranes: 2 x 6 @ 16-in., %-in. gypsum, insulated, %-in. Siding 12
Bituminous, gravel-covered 5.5 Exterior stud walls with brick veneer 48
Bituminous, smooth surface 1.5 Windows, glass, frame and sash 8
Liquid applied 1
Single-ply, sheet 0.7
W ood sheathing (per inch thickness) 3
W ood shingles_______________________________3

a. Source: “Minimum Design Loads for Buildings and Other Structures", ASCE 7-95, 1995, American Society of Civil Engineers, Reston, VA. ,
b. Weights of masonry include mortar but not plaster. For plaster, add 5 lb/ft2 for each face plastered. Values given represent averages. In some cases there is a considerable range of Weight for the same
construction.
DESIGN INFORMATION

Design Aid-1 'L l .2 Recommended minimum uniformly distributed and concentrated live loads?
Uniform Concentrated
O ccupancyroruse
load (psf) load (lb)
Apartments (see residential)
Access floor systems
Office use 50 2,000
Computer use 100 2,000
Armories and drill rooms 150
Assembly areas and theaters
Fixed seals (fastened to floor) 60
Lobbies 100
Movable seats 100
Platforms (assembly) 100
Stage floors 150
Balconies (exterior) 100
On one- and two-family residences only, and not exceeding 100 ft2 60
Bowling alleys, poolrooms and similar recreational areas 75
Corridors
First floor 100
Other floors, same as occupancy served except as indicated
Dance halls and ballrooms 100
Decks (patio and roof)
Same as area served, or for the type of occupancy accommodated
Dining rooms and restaurants 100
Dwellings (see residential)
Elevator machine room grating (on area of 4 in2) 300
Finish light floor plate construction (on area of 1 in2) 200
Fire escapes 100
On single-family dwellings only 40
Garages (passenger cars only) 50 Note b
Truck and buses Note c
Grandstands (see stadium and arena bleachers)
Gymnasiums, main floors and balconies (see note e) 100
Handrails, guardrails and grab bars Note i
Hospitals
Operating room, laboratories 60 1,000
Private rooms 40 1,000
Wards 4J 1,000
Conidors above first floor 80 1,000
Hotels (see residential)
Libraries
Reading rooms 60 1,000
Stack rooms (see note d) 150 1,000
Corridors above first floor 80 1,000
Manufacturing
Light 125 2,000
Heavy 250 3,000
Marquees and Canopies 75
Office Buildings
File and computer rooms shall be designed for heavier loads based on
anticipated occupancy
Lobbies and first floor corridors 100 2,000
Offices 50 2,000
Corridors above first floor 80 2,000
See following page fot all notes.

PCI Design Handbook/fifth Edition 11-3


DESIGN INFORMATION

Design Aid 11.12 Recommended minimttm uniformly distributed and concentrated Tive ioads (cont.)
Uniforai Concentrated
Occupancy or use
lead (psf) lead (ib)
Penal institutions -
Cell Blocks 40
Corridors 100-
Residential
Dwellings (one- and two-family)
Uninhabitable attics without storage 10
Uninhabitable attics with storage 20
Habitable attics and sleeping areas 30
All other areas except baleonies 40
Hotels and multifamily houses
Private rooms and corridors serving them 40
Public rooms and corridors serving them 100
Reviewing stands, grandstands and bleachers (see note e) 10O
Roofs Note j
Schools
Classrooms 40 1,000
Corridors above first floor 80 1,000
First floor corridors 100 1,000
Scuttles, skylight ribs, and accessible ceilings 200
Sidewalks, vehicular driveways, and yards, subject to trucking (see note f, g) 250 8,000
Stadiums and arenas
Bleachers (see note e) 100
Fixed seats, fastened to floor (see note e) 60
Stairs and exitways 100 Note h
Storage areas above ceilings 20
Storage warehouses (shall be designed for heavier
loads if required for anticipated storage)
Light 125
Heavy 250
Stores
Retail
First floor 100 1,000
Upper floors 75 1,000
Wholesale, all floors 125 1,000
Vehicle barriers Note i
Walkways and elevated platforms (other than exitways) 60
Yards and terraces, pedestrians 100
a. Source: “Minimum Design Loads for Buildings and Other Structures,” ASCE 7-95,1995, American Society of Civil Engineers, Reston, VA.
b. Floors in garages or portions of buildings used for the storage of motor vehicles shall be designed for the uniformly distributed live
loads of Design Aid 11.1.2 or the following concentrated Joad: (1) for passenger cars accommodating not more than nine passengers
2,000 lb acting on an area of 20 in2; and (2) mechanical parking structures without slab or deck, passenger car only, 1,500 Ib/wheel.
c. Garages accommodating trucks and buses shall be designed in accordance with an approved method which contains provisions for
truck and bus loadings.
d. The weight of books and shelving shall be computed using an assumed density of 65 pcf and converted to a uniformly distributed
load; this load shall be used if it exceeds 150 pcf.
e. In addition to the vertical live loads, horizontal swaying forces parallel and normal to the length of seats shall be included in the design
according to the requirements of ANSI/NFPA 102.
f. Other uniform loads in accordance with an approved method which contains provisions for truck loadings shall also be considered
where appropriate.
g The concentrated wheel load shall be applied on an area of 20 in*.
h. Minimum concentrated load on stair treads on area of 4 ineis 300 lb.
i. See ASCE 7-95, Sect. 4.4.
j. See ASCE 7-95, Sects. 4.3 and 4.9.

11-4 PCI Design Handbook/Fifth Edition


D E S IG N S FORMATION
Design Aid 11.1.3 Beam design equations and diagrams3

a. Source: “Manual of Steel Construction, Allowable Stress Design,” Ninth Ed., 1989,
American Institute of Steel Construction, Chicago, IL.

PCI Design Handbook/Fitth Edition 11-5


DESIGN INFORMATION
Design Aid 11.1.3 Beam design equations and diagrams (continued)

1 1 - 6 PCI Design Handbook/Fifth Edition


DESIGN INFORMATION

PCI Design Handbook/Fifth Edition 11-7


D E S IG N IN FGRM/CRON
Design AW 11.1.3 Beam design equations ancUfiagrams (continued)!
(12) BEAM OVERHANGING ONE SUPPORT - CONCENTRATEDJ-OAD AT ANY POINT
BETWEEN SUPPORTS

R, = V, (MAX WHEN-a < b). Pb

Mx (WHEN x < a)

w ( * T x

Pabx
FIT

(13) BEAM OVERHANGING ONE SUPPORT - CONCENTRATED LOAD AT END OF OVERHANG


II

R1 = V 1 ................................................

R2 = V, + v 2 ................................................ ............. .. = f(< + a)

V2 ............................................. .................= P

M max (ATR2) .................................. ............... = Pa

Mx (BETWEEN-SUPPORTS)........... _ Pax
l

MXl (FOR OVERHANG) ................... ................ = P(a - xn;

A max ^ b e t w e e n SUPPORTS AT x = j= P a l2 P a l2
— p — = .06415 c
9 /3 E l E

AMAx (FOR OVERHANG AT x, = a) Pa2


{( + a)
3 EI

Ax (BETWEEN SUPPORTS)............... = PgX 1(2 - v2)


6 E llV '

Px
Ax, (FOR OVERHANG) ....................... = (2 a l + 33X, - x f)

11-8 PCI Design Handbook/Rfth Edition


DESIGN INFORMATION
Design Aid 11.1.3 Beam design equations and diagrams (continued)
(14) CANTILEVERBEAM- UNIFORMLY DISTRIBUTED LOAD
Ft = V . _ ............................................................ = w«

V* = wx

M max (AT FIXED E N D ).................................. = M ?

wx2
2

A max (AT FREE END) .................................. = M i


o cl

Ax ................................................................... = 2 ^ j ( x 4 - 4 f 3x + 3 f 4)

(15) CANTILEVER BEAM - CONCENTRATED LOAD AT FREE END

R = V ......................... .. = P

M max (AT FIXED E N D ). = pe

MY ...................................... = Px

] v
A MAX (AT FREE E N D ) .................................. = f g

Ax ......................................................... ........ = g ^ ( 2 f 3 - 3 f 2x + x3)


Mmax

(16) CANTILEVER BEAM - CONCENTRATED LOAD AT ANY POINT


R = V ................................................................ =P

Mmax (A T FIXED E N D ) ...............................= Pb

Mx ( WHEN x > a ) ...................................= P(x - a)

A max (A T FREE END ) ......................... = | g ( 3 « - b)

Aa ( AT POINT OF LOAD ) .................. =

Ax ( W HEN x < a ) ................................. = | ^ ( 3 f - 3x - b)


Obi

Ax ( WHEN x > a ) ...................... = - I g r * (3b - < + x)


________ 0 cl
(17) CANTILEVER BEAM - LOAD INCREASING UNIFORMLY TO FIXED END
-------------------- 1 ------------------
R = V .......... .......................................................= W

Vx ..................................... =
‘ r L r f m T T M
f2

Mmax (AT FIXED E N D ).................................. = M


3

Mx Wx3
SH EA R ^
3€2

A MAX (AT FREE E N D ) .................................. =

Ax W
(x5 - 5e*x + 4€5) MOMENT X , Mmax
60 EI €2 ^ 1

PCI Design Handbook/Fifth Edition 11-9


DESIGN INFORMATION
Design Aid 11.1.3 Beamdesign equations;and diagrams (continued)
(1Sf BEAMFIXED AT ONE END, SUPPORTED AT OTHER - UNIFORMLY DISTRIBUTED LOAD1

3w€
- v , ...............
8

r2 = v2 max . 5w f
8

Vx................ R, - wx

Mm a x .....................
8

M, ( aT x = |^
128

Mx ..................... R ,x - ^ f -

w l4
A max (A T x = X ( 1 + v ^ ) = .4 2 1 5 € ) =
185 E l

^ | - i ( f 3 - 3 f x 2 + 2x3)

(19) BEAM FIXED AT ONE END, SUPPORTED AT OTHER - CONCENTRATED LOAD AT CENTER
_ 5P
II
<
p

16

r2 = v2 max ............................... 11P


16

3Pf
Mmax (AT FIXED END).......................
........ 16
w|<g

M, (AT POINT OF LOAD)


ii

Mx (WHEN x < £ ) .......................... 5Px


16

Mx [w h en X > ; - p( l _ Hx\
\2 16/

Pf 3
A max ( A T x - ^ - . 4 4 7 2 f J = - = .009317 c
48 E 175 E

A* (AT POINT OF L O A D )............... 7P13


768 E l

(w h e n x < | ) ............................ ..3 » • .*,=

A* (WHEN x > | ) ............................. = g ^ j ( x - f)£ (11x - 20

1 1-10 PCI Design Handbook/Fifth Edition


DESIGN INFORMATION
Design Aid 11.1.3 Beam design-equations and>diagram& {continued)
(20)BEAM FIXED AT ONE END, SUPPORTED AT OTHER -CONCENTRATEDLOAD AT ANY POINT

= V, ......................................................... = § ( a + 2<)

^2 = ^2 .......................................... .............. = ^ ( 3 ^ 2 - a 2)

M, (AT POINT OF LOAD)^ ..............................


= R ,a

M2 (AT FIXED END) .....................................


- | f (a+0
Mx (WHEN x < a) ............................................... = R,x

Mx (WHEN x > a) ................................ .............. = ft,x - P ( x . - a )

Pa ( l 2 ~ a2)3
A MAX (W HEN a < A U ( ATx =
3 EI (3€2 - a2)2

Pab2 f _____
a
A max (W H E N a > ,4 1 4 fA T x = (
6 E I v 2^ + a

Aa (AT POINT OF LOAD) ................................... Pa2b3 y


1 2 E I< a t 3 f ^

A x (WHEN x < a)
= i l g T T s (3af2 - 2 <x2 - ax2)

Ax (WHEN x > a) ~ x)2 (3^2x - a2x - 2a2f)

(21) BEAM FIXED AT BOTH ENDS - UNIFORMLY DISTRIBUTED LOADS

R = V .............................

Vx ...............................

Mm a x ( A T E N D S ) . . .

M1 ( AT CENTER )

Mx .............................

A MAX (A T C E N T E R ).

Ax .............................

PCI Design Handbook/Fifth Edition 11-11


DESIGN INFORMATION
DesignAid 11.1.3 Seam design eqtrations and diagrams (continued)

(22) BEANT FIXED AT BOTH ENDS - CONCENTRATED LOAD AT ANY POINT

R, = V , (MAX W H E N a < t>) ................... = ^ (3a + b)

R2 = V2 (MAX W H E N a > b> ........................... = 7 T 0 + 3b)


---------------- ( —

Pab2 P
M-t (MAX WHEN a < b) ..................................
€2
1 f 1
Pa2b
M-2 (MAX WHEN a > b) ..................................
€2 — U ^

1
Ma (AT POINT OF LOAD) .................................... 2Pa2b2
Vi '1 i I T I I 1 1 1 I 'l
e3
! SHEAR II II 1 v,
Mx (WHEN x < a ) .................................................. = R,x
Pab2 t
f2

jj Ma
A MAx (W H E N a > b A T x = ^ ) ................... 2Pa3b2 1 _______ ^ r f l T T >K
3 El (3a + b)2 Mi MOMENT
_ | m2

Pa3 b3
f
Aa (AT POINT OF LO A D )......................................
3 El H3

Ax (WHEN x < a ) .............................................. Pb2x2


(3af - 3ax - bx)
6 El €3

(23) BEAM - UNIFORMLY DISTRIBUTED LOAD AND VARIABLE END MOMENTS

V. ...............
.................. 2 +

v5 ............... w€
.................. 2

11-12 PCI Design Handbook/Fifth Edition


DESIGN INFORMATION

PCI Design Handbook/Fifth Edition 11-13


1 1 1 4
Design Aid 11.1.4 Cam ber (deflection) and rotation coefficients for prestress force and loads?

DESIGN INFORMATION
PCI Design Handbook/Fifth Edition

r ia c in n A iH 1 1 1 / 1 *1
DESIGN-INFORMATION
CJI
I
DESIGNINFORMATION

Design JUd 11.1.5 Moments in beams with fixed ends

11-16 PCI Design Handbook/Fifth Edition


DESIG N I NFQRMATI ON

Design Aid 11.1.6 Moving load placement for maxhmim moment and sheai*

(1) SIMPLE BEAM - ONESONCENTRATED MOVINGLQAD

R, MAX = V1 MAX ( AT x = 0 ) .............................. = P

A r2
R1

M MAX (A T POINT OF LOAD, WHEN x = | ) .......... = ^

{2) SIMPLE BEAM - TWO EQUAL CONCENTRATED MOVING iOADS

R, MAX V1 MAX ( AT x = 0 ) = P(2-|)

x — M -*— a - H

WHEN a < (2 - fe ) t = .S8M pO O p


1 2
U N D E R LO A D ! A T x = i ( «

M MAX ------------ i --------------


WHEN a > ( 2 - j 2 ) t = ,586f
Pf
4
WITH ONE LOAD AT CENTER OF SPAN

(3) SIMPLE BEAM - TWO UNEQUAL CONCENTRATED MOVING LOADS

R, MAX = V, MAX ( AT x = 0 ) l - a
= P i + P2 . (, P, > P 2

P2a
JTlNDER Pt , A T x = - i | t - = (p 1+ p 2) t
Pi+P2
M MAX
M MAX MAY OCCUR WITH LARGER
PJ.

[
LOAD AT CENTER OF SPAN AND
4
OTHER LOAD OFF SPAN

a. Source: “Manual of Steel Construction, Allowable Stress Design,” Ninth Ed., 1989,
American Institute of Steel Construction, Chicago, IL.

PCI Design Handbook/Fifth Edition 11-17


oo Design Aid 11.1.7 Moments, shears, and deflections in beam s with overhangs
LOADING AND SUPPORT REACTIONS AND BENDING MOMENT M AND
DEFLECTION y, MAXIMUM DEFLECTION, AND END SLOPE 0
VERTICAL SHEAR MAXIMUM BENDING MOMENT
EQUAL OVERHANGS, R» — R,
W
( A T O B )M = -|£ (C -X )2 (A TO B) y ■ [6c2 (d + x) - x2(4c - x) - d3
UNIFORM LOAD C " T 24 E U
W (c - x) Wx(c( - x)
W = w€
(ATOB)V* - (B TO C) M = [c 2 - x ( d - x ) ] (B TO C) y >
24 m e
[x(d - x) + d2 - 6c2]

Wc
(B TO C) V = M = — AT B AND C y- - 2 4 'E l f
[3 c 2(c + 2d) - d 3] AT A AND D

iulimwwwfw (C TO D) V *
W(c + d - x )
- - W - * ) " > -!
y - -
Wd2
384 E 11
(5d2 - 24c2) A T x^|

IF d > 2c, M * 0 AT x IF 2c < d < 2.449c, THE MAXIMUM DEFLECTION BETWEEN SUPPORTS IS

W
IF c - 0.207e, M = - y - + 96 E i e 6C‘ ~ d *) * A T x = | ± v/ 3( ^ - c=)
46.62

NOliVWdOdNI N0IS3Q
AT x « 0 = d AND M = +
we
e = + 24 wE l e
(6c2d + 4c3 - d3) AT A

AT x^x w (6czd + 4c3 - d3) AT D


3 ' 24 E I e
X IS CONSIDERED POSITIVE ON
BOTH SIDES OF THE ORIGIN.

$ UNEQUAL OVERHANGS, R (c + d - ©) (A TO B) M = W
(c - X ) 2 (ATO B )y = - 2 4 gX| ^ [2d(©2 + 2c2) + 6c2x - x®(4c - x) - d3]
RB 2d 2€
x8 UNIFORM LOAD
a R - W (d + e - c) (B TO C) M =
W
(c 4- X)2 4- RgX (B TO C) y = - {x(d - X) + d 2 - a(c2 + e2) - | [ e 2x + c 2(d - x)]J
RC _ 2d 2€

y W = w€ W (C TO D) M =
W + d - x)2 (C TO 0) y = - [2d(c2 + 2d2) + 6e2(x - d) - (x - d)2(4a + d - x) - d 3]
(A TO B) V (c - X) 2€
e
i w (B TO C) V = M _ Wc2 AT B y * - [2 d (e 2 + 2c2) + 3c8 - d 3] AT A
rb - f ( C + X)

IIUtUllUHUJI (C TO D) V _ w
e
(d + e - x) M __
2e

We2
2t
A TC y = - [2d(c2 + 2e2) + 3e3 - d 3] AT D

M MAX. PETWEEN SUPPORTS THIS CASE IS TOO COMPLICATED TO OBTAIN A GENERAL EXPRESSION
FOR CRITICAL DEFLECTIONS BETWEEN THE SUPPORTS.

8 = + gTj ^ (4c3 + 4c2tf - d3 + 2de2) AT A


e = H (c2 - x?) AT x - x ,

=* c2 + d 2 - e2 6 = - g4 ^ ] ^ (2c2d + 4de2 - d 3 4- 4e3) AT D


2d

IF x 1 > c, M = 0 AT x = x 1 ± y x 2 — c a

X IS CONSIDERED POSITIVE Ol^


BOTH SIDES OF THE ORIGIN.
T1.2 MATERIAL PROPERTIES
CONCRETE

Design Aid 11.2.1 Table of concrete stresses* (gsi)

% G.45f£ 0.6f; K , syfT ’ 3.5 vC ; 6 1i K -


2500 1125 1500 50 100 175 200 250 300 375 . 600
3000 1350 1800 55 • 110 192 219 274 329 411 657
3500 1575 2100 59 118 207 237 296 355 444 ' 710
4000 1800 2400 63 126 221 253 3T6 379 474 759
5000 2250 3000 71 141 247 283 354 424 530 849
6000 2700 3600 77 155 271 310 387 465 581 930
7000 3150 4200 84 167 293 335 418 502 627 1004
8000 3600 4800 89 179 313 358 447 537 671 1073
9000 4050 5400 95 190 332 379 474 569 712 1138
10000 4500 6000 100 200 350 400 500 600 750 1200

Design Aid 11.2.2 Concrete modulus of elasticity as affected by unit weight (pcf) and strength (psi)

PCI Design Handbook/Fifth Edition 11-19


MATERIAL PROPERTIES
PRESTRESSINGSTEEL
Design Aid 11.2.3 Propertiesand design strengths ofprestressing strand and wire

Seven-Wire Strand, fpu = 270 ksi

Nominal Diameter, in. 3/« 7/l6 V2 14 Special* 9/l6 0.600

Area, sq. in. 0.085 0.115 0.153 0.167 0.192 0.217

Weight, plf 0.29 0.40 0.52 0.53 0,65 0.74

0*7 fpy Aps, kips 16.1 21.7 28.9 31.6 36.3 41.0

0-75 fpy Aps, kips 17.2 23.3 31.0 33.8 38.9 44.0

0.8 fpu Aps, kips 18.4 24.8 33.0 S6.1 41.4 46.9

Ipu Aps, kips 23.0 31.0 41.3 45.1 51.8 58.6

Seven-Wire Strand, fpu = 250 ksi

Nominal Diameter, in. ’/4 S/16 % Vie 14 0.600

Area, sq. in. 0.036 0.058 0.080 0.108 0.144 0.216

Weight, plf 0.12 0.20 0.27 0.37 0.49 0.74

0.7 fpu Aps, kips 6.3 10.2 14.0 18.9 25.2 37.8

0.8 fpu Aps, kips 7.2 11.6 16.0 21.6 28.8 43.2

fpu Aps, kips 9.0 14.5 20.0 27.0 36.0 54.0

Three- and Four-Wire Strand, fpu = 250 ksi

Nominal Diameter, in. ’/4 5/l6 3/e Vie

No. of wires 3 3 3 4

Area, sq. in. 0.036 0.058 0.075 0.106

Weight, plf 0.12 0.20 0.26 0.36

0.7 fpu Aps, kips 6.3 10.2 13.2 18.6

0.8 fpu~Ap$j kips 7.2 11.6 15.0 21.2

fpu Aps, kips 9.0 14.5 18.8 26.5

Prestressing Wire

Diameter 0.105 0.120 0.135 0.148 0.162 0.177 0.192 0.196 0.250 0.276

Area, sq. in. 0.0087 0.0114 0.0143 0.0173 0.0206 0.0246 0.0289 0.0302 0.0491 0.0598

Weight, pif 0.030 0.039 0.049 0.059 0.070 0.083 0.098 0.10 0.17 0.20

Ult. strength, fpu ksi 279 273 268 263 259 255 250 250 240 235

0.7 fpu Aps, kips 1.70 2.18 2.68 3.18 3.73 4.39 5.05 5.28 8.25 9.84

0.8 fpu Aps, kips 1.94 2.49 3.06 3.64 4.26 5.02 5.78 6.04 9.42 11.24

fpu Aps, kips 2.43 3.11 3.83 4.55 5.33 6.27 7.22 7.55 11.78 14.05

a. The 'A in. special strand has a larger actual diameter than the 'A in. regular strand. The table values take this difference into account.

1 1 -2 0 PCI Design Handbook/Fifth Edition


MATERIAL PROPERTIES
PRESTRESSiNG STEEL

Design-Aid 11.2,4 Properties and design strengths of prestressing bars^

- Plain Prestressing Bars, fpu - 145 ksia

Nominal Diameter, in. 3/4 % 1 V/e 11/4 1%

Area, sq. in. 0.442 - 0.601 0.785 0.994 1.227 1.485

Weight, plf 1.50 2.04 2.67 3.38 4.17 5.05

0.7 fpu Apgj kips 44.9 61 .& 79.7 100.9 124.5 150.7

0.8 fpu Apgj kips 51.3 69.7 91.0 115.3 142.3 172.2

fpu ApS, kips- 64.1 87.1 113.8 144.1 177.9 215.3

Plain Prestressing Bars, fpu = 160 ksi*

Nominal Diameter, in. V* % 1 VA 11/4 13/b

Area, sq. in. 0.442 0.601 0.785 0.994 1.227 1.485

Weight, plf 1.50 2.04 2.67 3.38 4.17 5.05

0.7 fpu Apgj kips 49.5 67.3 87.9 111.3 137.4 166.3

0.8 fpu Aps, kips 56.6 77.0 100.5 127.2 157.0 190.1

fpu Apj, kips 70.7 96.2 125.6 159.0 196.3 237.6

Deformed Prestressing Bars

Nominal Diameter, in. S


A 1 1 11/4 11/4 1%

Area, sq. in. 0.28 0.85 0.85 1.25 1.25 1.58

Weight, plf 0.98 3.01 3.01 4.39 4.39 5.56

Ult. strength, fpu, ksi 157 150 160* 150 160“ 150

0.7 fpu Aps, kips 30.5 89.3 95.2 131.3 140.0 165.9

0.8 fpu Aps, kips 34.8 102.0 108.8 150.0 160.0 189.6

fpu Aps, kips 43.5 127.5 136.0 187.5 200.0 237.0

Stress-strain characteristics (all prestressing bars):


For design purposes, following assumptions are satisfactory:

Es = 29,000 ksi

fy = 0 .9 5 fpu

a. Verify availability before specifying.

PCI Design Handbook/Fifth Edition 11-21


MATERIAL PROPERTIES
PRESTRESSING STEEL

Design Aid 11.2.5 Typical stress-strain curved-w ire low-relaxation^prestressing strand

■D
C
a
l.
w
■e
o
o
o
c
3
0)
’5■
N

£
(0

0 0.005 0.010 0.015 0.020 0.025 0.030

STRAIN Eps (in./in.)


c
a>
E
a
o
These curves can be approximated by the following equations: 5
u
■O
c
250 ksi 270 ksi a
£
(0
Eps < 0.0076: fps = 28,500£ps(ksi) Eps < 0.0086: f^ = 28,500£ps(ksi) c
(B
i_
h-

£ps > 0.0076 : fps = 250 - ■■^ (ksi) Eps > 0.0086 : fps = 270 - (ksi) (D
oi

<
c
0)
'55
0)
Q

1 1 -2 2 PCI Design Handbook/Fifth Edition


Design Aid 11.2.6 Transfer and developm ent lengths for 7-wire uncoated strand________
The ACI 318-95 (Sect. 12.9.1) equation3 fo r required developm ent length may be rewritten as:

= ( W 3 ) d b + (fps - f se)d b

where:
= required developm ent length, in.
fse = effective prestress, ksi
fps = stress in prestressing Steel at nominal strength, ksi
db = nominal diam eter of strand, in.

The first term in the equation is the transfer length and the second term is the additional length required
for the stress increase, (fps — fse) corresponding to the nom inal strength.

MATERIAL PROPERTIES
PRESTRESSING STEEL
Transfer and developm ent lengthb in inches
PCI Design Handbook/Fifth Edition

fs e = 150 ksi f.e = 160 ksi fe e = 170 ksi

Nominal Developm ent Length Developm ent Length Developm ent Length
Diam­
eter, Transfer Transfer Transfer
in. Length fp s > ksi Length fp s > ksi Length fp s i ksi

240 250 260 270 240 250 260 270 2 40 250 260 27b
3/8 18.8 52.5 56.3 60.0 63.8 20.0 50.0 53.8 57.5 61.3 21.3 47.5 51.3 55.6 50.8
7/l6 21.9 61.3 65.6 70.0 74.4 23.3 58.3 62.7 67.0 71.4 24.8 55.4 59.8 64.2 68.0
1/z 25.0 70.0 75.0 80.0 85.0 26.7 66.7 71.7 76.7 81.7 28.3 63,3 68.3 73.3 78 . 3(
1/2 S<= 26.1 73.1 78.4 83.6 88.8 27.9 69.7 74.9 80.1 85.4 29.6 66.1 71.3 76.6I 81-8
9/l6 28.1 78.8 84.4 90.0 95.6 30.0 75.0 80.6 86.3 91.9 31.9 71.3 76.9 82.5 88.1
0.600 30.0 84.0 90,0 96.0 102.0 32.0 80.0 86.0 92.0 98.0 34.0 76.0 82.0 88.0 94.0
a. T h e ACI 3 1 8 -9 5 eq u a tio n w as derived b as e d on tests o n Vi, 3/a and Vt in. diam eter strands. Its use for o th e r sizes included in th e tab le is b ased
pn inter/extrapolation as necessary. Research is u n d e rw a y to p ro du ce reco m m end ation s on transfer a n d d evelo p m en t lengths for e p o x y
coated strand.
b. T h e developm ent length values given in the table m u st b e d ou bled w here bonding of th e strand d oes n ot exten d to the m e m b e r e n d a n d the m em b er is d e s ig n e d such ih a l
tension in the p rec o m p re ss e d tensile zo n e is p ro du ced u n d er service loads (see ACI C o d e Sect. 1 2 .9.3 ).
11 —23

c. T h e Vz in. special (Vz S ) strand has a larger nom inal d ia m e te r than th e in. regular (V6) strand. T he ta b le values for transfer a n d d ev e lo p m en t
length reflect this difference in diam eters.
MATERIAL PROPERTIES-
REINFORCING BARS

Design Aid 11.2.7 Reinforcing bar data


ASTM STANDARD REINFORCING BARS
BAR SIZE1 NO M INAL D IM EN SIO N S
DESIG NATIO N DIAMETER AREA W E IG H T OR MASS

U S . CUSTOM ARY si in. mm in2 mm2 1b/ft kg/m


#3 #10 0.375 9.5 0.11 71 0.376 0.560

#4 #13 0.500 12.7 0.20 129 0.668 0.994

#5 #16 0.625 15.9 0.31 199 1.043 1.552

#6 #19 0.750 19.1 0.44 284 1.502 2.235

#7 #22 0.875 22.2 0.60 387 2.044 3.042

#8 #25 1.000 25.4 0.7 9 510 2.570 3.973

#9 #29 1.128 28.7 1.00 645 3.400 5.060

#10 #32 1.270 32.3 1.27 819 4.303 6.404

#11 #36 1.410 35.8 1.56 1006 5.313 7.907

#14 #43 1.693 43.0 2.25 1452 7.650 11.380

#18 #57 2257 57.3 4.00 2581 13.600 20.240

a. Many mills will mark and supply bars only with metric (SI) designation, which is a soft conversion. Soft conversion means that the
metric (St) bars have exactly the same dimensions and properties as the equivalent U.S. customary designation.

STANDARD HOOKS STIRRUP AND TIE-HOOKS

DETAILING HOOK
j DIMENSION*” AORG
______ 1 12d FOR # 6 ,7,8 1
180°
| 6d FOR # 3 ,4,5
f JJ: ^ 1 D
d
4d OR 2%” MIN.

z Z) 90°
o
w
DETAILING , z
| DIMENSION
LLI
2
/
90° jt Q
j a I rg 12d
d 4____
~T

180° DEGREES 90° 90° 135°


BAR SIZE
AORG AORG AORG AORG
U.S. SI U.S. SI US. SI U.S. SI U.S. SI U.S. Si U.S. SI U.S. SI U.S. SI
#3 #10 2% 60 125 ~8CT 150 V A 40 105 105 214 65

#4 #13 ”io"" 150 105 200 ~ 414 T ii" 414 115 80

#5 #16 3% 95 175 ISO- 10 250 214 65 155 514 140 3 3/4 95 ~

#6 #19 4 1/2 115 200 155 1 -0 300 4'4 115 1-0 305 205 414 115
#7 #22 5'/4 135 10 250 1-80 1-2 375 5'/4 135 1-2 355 230 5 1/4 135

#8 #25 lii" 11 275 205 1 -4 425 155 1 -4 410 10% 270 155

#9 #29 914 240 1 -3 375 11% 300 1 -7 475

#10 #32 10% 275 1 -5 425 1- 1% 335 1 -1 0 550


U.S. CUSTOMARY UNITS: in. or ft-in.
#11 #36 12 305 1- 475
7 1- 2% 375 2 -0 600 SI UNITS: mm
#14 #43 18% 465 2 - 3
675 1-9% 550 2 -7 775

#18 #57 24 610 3- o"


925 2 -4 % 725 3 -5 1050

1 1 -2 4 PCI Design Handbook/Fifth Edition


MATERIAL PROPERTIES
REINFORCING U A R5

Design Aid 11.2vfr Required development JengthsMor reinforcing, bars (Grade 60)

Tension Development Length: Compression Development Length:


& = 2400 db/VfT; min. 12 in-. (#6 and-smaller) €d = 1200 db//fT ; min. 18db and 8 in.
(Note: For Grade 40 bars, replace 1200 with 800 and 18
(a = 3000 db/VfT I min. 12 in. (#7 and larger)
with 12)
(Note: lor Grade 40 bars, replace 2400 and 3000 with
1600 and 2000 respectively.)
Multiply values by :
Multiply t d values by : (a) As (required)/As (provided) for excess reinforcement
(b) 0.75 for adequate spiral or tie enclosure
(a) 1.3 for lightweight concrete
(See AC112.3.3.2)
(b) 1.3 for “top bars”
(c) 1.5 for epoxy coated bars with cover < 3dbor clear Compression Splice Lap Length:
spacing < 6db, otherwise multiply by 1.2.
Lap length = 30db; min. 12 in.
(Note: Product of factors (b) and (c) need not exceed 1.7)
(d) 1.5 for bars with less than minimum stirrups or
The values of /f f used in these equations shall not exceed
ties, clear spacing less than 2dbor clear cover less
100 psi (See Sect. 12.1.2, ACI 318-95).
than db.
(e) As (required)/As (provided) for excess reinforcement
unless development of fy is specifically required. This
multiplier is not to be applied to lap splices per ACI318-95,
Sect. R12.15.1.

fi = 3000 psi f; = 4000 psi Vc = 5000 psi f'c = 6000 psi

Bar Com- Com- Com- Com- Min.


Size Tension pres- Tension pres- Tension pres- Tension pres- Comp
sion sion sion sion Splice
1-«d 1.5€d *d 1.3*„ 1.5€d <d ^d 1.5<d <d <d 1.3€d 1.5<„ *d
3 16 21 25 8 14 18 21 8 13 17 19 8 12 15 17 8 12
4 22 28 33 11 19 25 28 9 17 22 25 9 15 20 23 9 15
5 27 36 41 14 24 31 36 12 21 28 32 11 19 25 29 11 19
6 33 43 49 16 28 37 43 14 25 33 38 14 23 30 35 14 23
7 48 62 72 19 42 54 62 17 37 48 56 16 34 44 51 16 26
8 55 71 82 22 47 62 71 19 42 55 64 18 39 50 58 18 30
9 62 80 93 25 54 70 80 21 48 62 72 20 44 57 66 20 34
10 70 90 104 28 60 78 90 24 54 70 81 23 49 64 74 23 38
11 77 100 116 31 67 87 100 27 60 78 90 25 55 71 82 25 42

f; = 7000 psi f = 8000 psi 1c = 9000 psi t; = 10,000 )si


Com- Com- Com- Com- Min.
D or
Tension pres- Tension pres- Tension pres- Tension pres- Comp
sion sion sion sion Splice
1.3 1-5 <d <d <d 1-3 V 1 .5 fd <d <d 1.3 f d 1-5 („ <d 1.3 ^ 1.5 ^
«d *d
3 12 14 16 8 12 13 15 8 12 12 14 8 9 12 14 8 12
4 14 19 22 9 13 17 20 9 13 16 19 8 12 16 18 8 15
5 18 23 27 11 17 22 25 11 16 21 24 8 15 20 23 8 19
6 22 28 32 14 20 26 30 14 19 25 28 9 - 18 23 27 9 23
7 31 41 47 16 29 38 44 16 28 36 42 11 26 34 39 11 26
8 36 47 54 18 34 : 44 50 18 32 41 47 13 30 39 45 12 30
9 40 53 61 20 38 49 57 20 36 46 54 14 34 44 51 14 34
10 46 59 68 23 43 55 64 23 40 52 60 16 38 49 56 15 38
11 51 66 76 25 47 61 71 25 45 58 67 17 41 54 62 17 42
a. For limitations and items related to hooked bars, stirrups or ties in excess of minimum, and spacing of non-contact lap splices, etc.,
see ACI 318-95, Chapter 12.

PCI Design Handbook/Fifth Edition 1 1 -2 5


MATERtAI^PROPERTlES
REINFORCING BARS
Design Aid 11.2:8 Required development lengths for reinforcing bars (Grade 60)(continued)

Minimum tension-embedment lengths, f dh, for standard hooks, in.

General use (non-seismic)


Normal weight concrete, % (psi)
Bar size
3,000 4,000 5,000 6,000 7,000- 8,000 9,000 10,000

#3 6 6 6 6 6 6 6 6
#4 8 7 6 6 6 6 6 6
#5 10 9 3 7 7 6 6 6
#6 12 10 9 8 8 7 7 6
#7 14 12 11 10 9 9 8 7
#8 16 14 12 11 10 10 9 8
#9 18 15 14 13 12 11 10 9
#10 20 17 15 14' 13 12 11 11
#11 22 19 17 16 14 14 13 12
NOTES: 1. SIDE COVERS 2V* in.
2. END COVER (90° HOOKS)s 2 in.

Special confinement (non-seismic) {See ACI 318-95, Sec. 12.5.3.3)


Normal weight concrete, fi (psi)
Bar size
3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000

#3 6 6 6 6 6 6 6 6
#4 6 6 6 6 6 6 6 6
#5 8 7 6 6 6 6 6 6
#6 10 8 7 7 6 6 6 6
#7 11 10 9 8 7 7 6 6
#8 13 11 10 9 8 8 7 6
#9 14 12 11 10 9 9 8 7
#10 10 14 12 11 11 10 9 9
#11 18 15 14 13 12 12 10 10

NOTES: 1. SIDE COVERS 2% in.


2. END COVER (90 ' HOOKS)£ 2 in.

BARS WITH STANDARD HOOKS:

‘ dh

4db OR 2’/a" NIIN.

STANDARD 90° HOOK STANDARD 180° HOOK

DIMENSION a = 4db FOR # 3 THROUGH # 8 , MODIFICATION FACTORS:


GRADE 40 BARS = 0.67
= 5d b FOR # 9 , # 1 0 A N D # 1 1 ,
LIGHTWEIGHT CONCRETE = 1.3
EPOXY COATED REINFORCEMENT = 1.2

1 1 -2 6 PCI Design Handbook/Fifth Edition


MATERIAL PROPERTIES
STRUCTURAL A^ELDEDT/VIRErREINFORCEMENT (WWR)_

Design Aid 11.279 Common styles of structural welded wire reinforcement?


Style designation Steel area Approximate
in2 per ft Weight
Former-designation Current designation
(By steel wire gage) (By W-number) Longit. Trans. lb per 100 ft2

6 x 6 -1 0 x 1 0 6x6-W 1.4xW 1.4 .029 .029 21


4 x 1 2 -8 x 1 0 ° 4x12-W 2.1xW 1.4 .062 .014 26
6 x 6 -8 x 8 6x6-W 2.1xW 2:1 .041 .041 30
4 x 4 -1 0 x 1 0 4x4-W 1,4xW T.4 .043 .043 31
4 x 1 2 -7 x 1 0 ° 4 x 1 2-W 2 .5 x W 1 .4 .074 .014 31
6 x 6 -6 x 6 b 6x6-W 2.9xW 2.9 £58 .058 42
4 x 4 -8 x 8 4x4-W 2.1xW 2.1 .062 .062 44
6 x 6 -4 x 4 b 6x6-W 4.0xW 4.0 .080 .080 58
4 x 4 -6 x 6 4x 4 -W 2 .9 x W 2 .9 .087 .087 62
6 x 6 -2 x 2 b 6 x 6 -W 5 .5 x W 5 .5 d .110 .110 80
4 x 4 -4 x 4 b 4x4-W 4.0xW 4.0 .120 .120 85
4 x 4 -3 x 3 b 4x4-W 4.7xW 4.7 .141 .141 102
4 x 4 -2 x 2 b 4 x 4 -W 5 .5 x W 5 .5 d .165 .165 119

INDUSTRY METHOD OF
DESIGNATING STYLE SPECIFY:
ASTM A 185 FOR PLAIN WWR;
EXAMPLE: 6 x 12-W 16 x W8
ASTM A 497 FOR DEFORMED WWR
LONGITUDINAL
WIRE SPACING -
TRANSVERSE
WIRE SPACING -

LONGITUDINAL
WIRE SIZE
TRANSVERSE
WIRE SIZE
(SUBSTITUTE “D" FOR
“W ” WHEN SPECIFYING
DEFORMED WIRE)

' SIDE OVERHANGS MAY BE


VARIED AS REQUIRED AND
DO NOT NEED TO BE
EQUAL. OVERHANG
LENGTHS LIMITED ONLY
TRANSVERSE WIRE BY OVERALL SHEET
WIDTH.
LONGITUDINAL WIRE
END OVERHANGS MAY
DIFFER. THE SUM OF THE
TWO END OVERHANGS,
NOTE: WIRES MAY ALSO BE DEFORMED (SEE DESIGN AID 11.2.11), EXCEPT WHERE
HOWEVER, SHOULD
PLAIN WIRE IS REQUIRED BY BUILDING CODES (USUALLY LESS THAN W4). WIRE
EQUAL THE TRANSVERSE DIAMETERS CAN BE SPECIFIED IN 0.001 IN. INCREMENTS. CHECK WITH LOCAL
W IRE SPACING. MANUFACTURERS ON MINIMUM QUANTITIES FOR CUSTOMIZED ORDERS.

a. Source: Manual of Standard Practice— Structural Welded Wire Reinforcement, Wire Reinforcement Institute, 1992, Findlay, Ohio.
b. Commonly available i n 8 f t x 1 2 f t o r 8 f t x 1 5 f t s h e e t s .
c. These items may be carried in sheets by various manufacturers in certain parts of the U.S. and Canada.
d. Exact W-number size for 2 gage is 5.4.

PCI Design Handbook/Fiftfi Edition 1 1 -2 7


MATERIAL PROPERTIES
STRUCTURAL WELDED WIRE REINFORCEMENT (WWR)

Design Aid 11.2.10 Special welded wire reinforcement for double tee flanges8
Steel Area in2 per ft
Approx. Weight-
Application Style Designation Longit. Trans. lb per 100 ft2
8-ft wide DT, 2-in. flange 12 X6-W1.4 XW2.5 .014 .050 23
10-ft wide DT, 2-in. flange 12 X 6-W2.0 X W4.0 .020 ,080 35
10-ft wide DT, 21/2-in. flange 12 X 6-W1.4 X W2.& .014 .058 27
a. See “Standardization of Welded Wire Fabric,” PCI Journal, July/Aug., 1976

Design Aid 11.2.11 Wires used in structural welded wire reinforcement8


Area - in2 per ft of width
Wire Size Number Nominal Nominal Center to Center Spacing, in.
Diameter Weight
Ptainb Deformed6 in. Pit 2 3 4 JB 8 10 12

W 45 D45 0.757 1.530 2.70 1.80 1.35 .90 .625 .54 .45
W31 D31 0.626 1.054 1.86 1.24 .33 .62 .465 .372 .31
W30 D30 0.618 1.020 1.80 1.20 .90 .60 .45 .36 .30
W28 D28 0.597 352 1.68 1J2 .84 .56 .42 .336 .28
W26 D26 0.575 .934 1.56 1.04 .78 .52 .39 .312 .26

W24 D24 0.553 .816 1.44 .96 .72 .48 .36 .288 .24
W22 D22 0.529 .748 1.32 .88 .66 .44 03 .264 .22
W2Q D20 0.504 .680 1.20 .80 .60 .40 .30 .24 .20
W18 D18 0.478 .612 1.08 .72 .54 .36 .27 .216 .18
W16 D16 0.451 .544 .96 .64 .48 .32 .24 .192 .16

W 14 D14 0.422 .476 .84 .56 .42 .28 .21 .168 .14
W12 D12 0.390 .408 .72 .48 .36 .24 .18 .144 .12
W11 D11 0.374 .374 .66 .44 .33 .22 .165 .132 .11
W10.5 D10.5 0.366 .357 .63 .42 .315 .21 .157 .126 .105
W10 D10 0.356 .340 .60 .40 .30 .20 .15 .12 .10

W9.5 D9.5 0.348 .323 .57 .38 .285 .19 .142 .114 .095
W9 D9 0.338 .306 .54 .36 .27 .18 .135 .108 .09
W8.5 D8.5 0.329 .289 .51 .34 .255 .17 .127 .102 .085
W8 D8 0.319 .272 .48 .32 .24 .16 .12 .096 .08
W7.5 D7.5 0.309 .255 .45 .30 .225 .15 .112 .09 .075

W7 D7 0.298 .238 .42 .28 .21 .14 .105 .084 .07


W6.5 D6.5 0.288 .221 .39 .26 .195 .13 .097 .078 .065
W6 D6 0.276 .204 .36 .24 .18 .12 .09 .072 .06
W5.5 D5.5 0.264 .187 .33 .22 .165 .11 .082 .066 .055
W5 D5 0.252 .170 .30 .20 .15 .10 .075 .06 .05

W4.5 W4.5 0.240 .153 .27 .18 .135 .09 .067 .054 .045
W4 D4 0.225 .136 .24 .16 .12 .08 .06 .048 .04
W3.5 0.211 .119 .21 .14 .105 .07 .052 .042 .035
W3 0.195 .102 .18 .12 .09 .06 .045 .036 .03
W2.9 0.192 .098 .174 .116 .087 .058 .043 .035 .029

W2.5 0.178 .085 .15 .10 .075 .05 .037 .03 .025
W2.1 0.162 .070 .126 .084 .063 .042 .031 .025 .021
W2 0.159 .oea .12 .08 .06 .04 .03 .024 .02
W1.5 0.138 .051 .09 .06 .045 .03 .022 .018 .015
W1.4 0.135 .049 .084 .056 .042 .028 .021 .017 .014

a. Source: Manual of Standard Practice—Structural Welded Wire Reinforcement, Wire Reinforcement Institute, 1992, Findlay, Ohio.
b. ASTM A 82, Available fy=65,000 psi to 80,000 psi in 2500 psi increments.
c. ASTM A 496, Available fy=7O,Q00 psi to 80,000 psi in 2500 psi increments.

1 1 -2 8 PCI Design Handbook/Fifth Edition


11.3 SECTION PROPERTIES

Design Aid 11.3.1 Properties of geometric sections®

a. Source: “Manual of Steel Construction, Allowable Stress Design,” Ninth Edition, 1989,
American Institute of Steel Construction, Chicago, IL.

PCI Design Handbook/Fifth Edition 1 1 -2 9


SECTION PROPERTIES

1 1 -3 0 PCI Design Handbook/Fifth Edition


SECTION PROPERTIES

Design A id 1 1.3.1 Properties:of geometric sections {continued)^

PCI Design Handbook/Rfth Edition 1 1 -3 1


11.4 METRIC CONVERSION

Design Aid 11.4.1 Metric calculations and example

“Hard” SI (metric) Calculations^ for Precast Example Use of Eq. 18-3from 318M-95.
Concrete (Similar to Example 4.2.4).
Given:
Design Aid 11.4.1 shows direct conversion from Double tee similar to PCI standard 8DT24+2.
inch-Jb. (U.S. customary) to SI units. Calculations Concrete:
made in SI units are usually rounded to even num­
Precast f(, = 35 MPa Topping f(, = 20 MPa
bers. These are known as “hard* metric calculations.
The metric version Of the Gode is 318M-95. Some of Reinforcement:
the common SI units used are: 12-13 mm dia. 1860MPa low relaxation strands
(6 ea. stem). Area per strand = 99 mm2
Concrete Strength:
Aps= 12(99) = 1188 mm2 As = 2-#19 = 568 mm2
20 MPa is approximately equivalent to 3000 psi
fy = 420 MPa
35 MPa is approximately equivalent to 5000 psi
Concrete weight (or mass):
Problem:
Normal weight concrete may be assumed to
Find the design flexural strength of the composite
weigh 2400 kg/m3 (149.8 pcf). Lightweight concrete
section using Eq. 18-3 form ACI 318M-95.
may be assumed to weigh 1900 kg/m3 (118.6 pcf). 2400 50
Reinforcement:

1
Most U. S. reinforcing bar manufacturers mark
bars with metric designations, although the actual dp= 5 7 0
600
sizes have not changed (see Design Aid 11.2.7).
Grade 420 (fy=420 MPa) is equivalent to grade Vi I
60. DIMENSIONS IN MILLIMETERS (mm)

Prestressing Strand:
= f f-l£ fpu d
Strand diameters and areas are rounded to the f,ips
nearest mm, e.g., 13 mm is equivalent to Vfein. diame­ pv Pi *C Ud

ter, area = 99 mm2.


(o’ = 0 in this example
Relationships in SI
Structural engineering calculations in SI units in­ _ Aps _ 1188 _
volve forces which include gravitational effects, rather Pp - bdp 2400(570) = 0.00087
than just weights, or mass. Thus one kilogram (kg) of
mass converts to 9.8 newtons (N) of force. For exam­ As / fy 568 / 420\ = 0.0080
ple, a 50 mm thick concrete topping 1 meter wide “ bdU / 2400(620) l 20 J
weighs (50/1000)m x 1m x 2400 kg/m3 = 120 kg/m. It
exerts 120 x 9.8 = 1176 N/m or 1.18 kN/m of force. 0.28
U
ips = 1860 1- 0.00087±|p +
Pressure or stress is expressed in pascals (P). 1P 0.85
= 1N/m2. It is more common to work in megapascals
620 = 1805 MPa
(MPa). 1MPa=1N/mm2. Bending moments are ex­ (0.0080)
570
pressed in newton-meters (N-m) or kilonewton-me-
ters (kN-m).
_ ApSfps + Asfy _ 1188(1805) - 568(420)
Design Aid 11.4.2 lists quantities that are frequent­
0.85f; b “ 0.85(20)2400
ly encountered in the design of precast concrete as
well as in general structural engineering practice. = 47 mm
Most U.S. Government agencies that require SI unit
Mn = Ap.fp8(dp - | ) + A . f y( d - f
dimensioning of contract documents will also require
consistent use of the listed SI units given in the table.
570 - 24
The equivalent U.S. customary units listed are those = 1188(1805)
1000
traditionally used by the design professions in the
United States. + 5 6 8 (4 2 0 )fe *<
Conversion of frequently encountered concrete
stress coefficients used in ACI318 and the PCI Hand­
= 1,312,991 N-m = 1313 kN-m
book are tabulated in Design Aid 11.4.3.
/ln= 0.9(1313) = 1182 kN-m

1 1 -3 2 PCI Design Handbook/Fifth Edition


11.4 METRIC CONVERSION
Design Aid 11.4.2 Conversion fromU.S. customary units hr international system (SI)

To convert from to multiDlv bv

Length - :
inch (in.)- millimeter (mm) 25.4
inch (in.) meter (m) 0.0254
foot (ft) meter (m) 0.3048
yard (yd) meter (m) 0.9144
mile (mi) kilometer (km) 1.6093
Area -
square foot (ft2) square meter (m2) 0.09290
square inch (in2) square millimeter (mm2) 645.2
square inch (in2) square meter (m2) 0.0006452
square yard (yd2) square meter (m2) 0.8361
acre (A) hectare (ha) = 10,000 m2 0.4047
square mile square kilometer 2.590

Volume
cubic inch (in3) cubic meter (m3) 0.00001639
cubic foot (ft3) cubic meter (m3) 0.02832
cubic yard (yd3) cubic meter (m3) 0.7646
gallon (gal) Can. liquid® liter 4.546
gallon (gal) Can. liquid® cubic meter (m3) 0.004546
gallon (gal) U.S. liquid® liter 3.785
gallon (gal) U.S. liquid® cubic meter (m3) 0.003785

Force
kip kilogram (kgf) 453.6
kip newton (N) 4448.0
pound (lb) kilogram (kgf) 0.4536
pound (lb) newton (N) 4.448

Pressure or Stress
kips/square inch (ksi) megapascal (MPa)b 6.895
pound/square foot (psf) kilopascal (kPa)b 0.04788
pound/square inch (psi) kilopascal (kPa)b 6.895
pound/square inch (psi) megapascal (MPa)b 0.006895
pound/square foot (psf) kilogram/square meter (kgf/m2) 4.882

Mass
pound (avdp) kilogram (kg) 0.4536
ton (short, 2000 lb) kilogram (kg) 907.2
ton (short, 2000 lb) tonne (t) 0.9072
grain kilogram (kg) 0.00006480
tonne (t) kilogram (kg) 1000

Mass (weiahti Der Lenath


kip/linear foot (klf) kilogram/meter (kg/m) 1488
pound/linear foot (plf) kilogram/meter kg/m 1.488
pound/linear foot (plf) newton/meter (N/m) 14.593

a. One U.S. gallon equals 0.8321 Canadian gallon.


b. A pascal equals one newton/square meter; 1 Pa = 1 N/mm2.
Note: To convert Irom SI units to U.S. customary units (except for temperature), divide by the factors given in this table.

PCI Design Handbook/Fifth Edition 11 -3 3


METRIC CONVERSION

Design Aid ' l l .4.2 Conversionfrom ti.S. customary units-io Internationalsystem (SI) (continued)

to convert from tg multiDlv bv

Mass nernrolume (densitvl -

pound/cubic foot (pcf) kifogram/cubic meter (kg/m3) 16.02


pound/cubic yard (pcy) kilogram/cubic meter (kg/m3) 0.5933

Bending Moment or Toraue -

pound-inch (lb-in.) newton-meter 0.1130


pound-foot (Ib-ft) newton-meter 1.356
kip-foot (k-ft) newton-meter 1356

Temperature
degree Fahrenheit (°F) degree Celsius (°C) tc = (tF-3 2 )/1.8
degree Fahrenheit (°F) degree Kelvin (K) tK = (tF + 459.7)/1.8

Energy
British thermal unit (Btu) joule (j) 1056
kilowatt-hour (kwh) joule (j) 3,600,000

Power
horsepower (hp) (550 ft Ib/sec) watt (W) 745.7

Velocity
mile/hour (mph) kilometer/hour 1.609
mile/hour (mph) meter/second (m/s) 0.4470

Other
Section modulus (in3) mm3 16,387
Moment of inertia (in4) mm4 416,231
Coefficient of heat transfer
(Btu/ft2/h/°F) W/m2/°C 5.678
Modulus of elasticity (psi) MPa 0.006895
Thermal conductivity
(Btu-in./ft2/h/°F) Wm/m2/°C 0.1442
Thermal expansion in./in./°F mm/m2/°C 1.800
Area/length (in2/ft) mm2/m 2116.80

1 1 -3 4 PCI Design Handbook/Rfth Edition


f 1.4 METRIC CONVERSION

Design Aid 11.4.3 Preferred SI units ^ind U.S. customary equivalents

Quantity SI LLS. custom ary

Area, cross section mm2 in2


Area, plan dimension mm2 ft2
Bending moment kN-m kip-ft
Coefficient of thermal expansion mm/(mm-°C) in/in/°F
Deflection mm in.
Density, linear kg/m Ib/ft> kip/ft
Density, area kg/m2 lb/ft2, kip/ft2
Density, mass kg/m3 lb/ft3, kip/ft3
Force kN 1b, kip
Force, per unit length kN/m lb/ft kip/ft
Force, peT unit area kN/m2 lb/ft2, kip/ft2
Length, cross section mm in.
Length, plan dimension mm ft
Mass kg lb, kip
Modulus of elasticity MPa psi, ksi
Moment of inertia 106 mm4 in4
Section modulus 10® mm3 in3
Stress MPa psi, ksi
Temperature °C °F
Torque kN-m Ib-ft, kip-ft

Design Aid 11.4.4 Concrete stress coefficents


U.S, custom ary SI coefficient U.S. custom ary SI coefficient
coefficient coefficient
0.5 0.04 3.3 0.27
0.6 0.05 3.5 0.29
0.667 0.06 4.0 0.33
1.0 0.08 4.4 0.37
1.1 0.09 5.0 0.42
1.2 0.10 5.5 0.46
1.25 0.10 6.0 0.50
1.5 0.12 6.3 0.52
1.6 0.13 6.5 0.54
1.7 0.14 7.0 0.58
1.9 0.16 7.5 0.62
2.0 0.17 8.0 0.66
2.4 0.20 10.0 0.83
3.0 0.25 12.0 1.00
Examples:

U.S. custom ary:/^psi SI equivalent: 0.08/fTMPa U.S. customary: 1 0 ^ psi SI equivalent: P.83 TfT MPa

PCI Design Handbook/Fifth Edition 1 1 -3 5


11-36 PCI Design Handbook/Fifth Edition
INDEX

A-frames, transportation ................. 5 -1 1 r bearing pads,


Absorption, water ........ 10—16 design recommendations _______ 6 -1 9
.Acceptance ................ 10-37 Bearing-paidsr minimum thickness . . . . . ____ 6 - 2 1
Acceptance, specification............................. 10—12 Bearingpads, (AASHTO) grade..................... 9 - 19-
Access, jobsite ..................- ....................... 10-35 Bearing pads,
Accidental torsion . . . . .......... .......................3 -5 6 allowable compressive stre ss.................. 6-21
Acid cleaning...............................................1 0 -3 0 Bearing pads, specification............................. 1 0 -9
Acoustic design.............................. 9-21 Bearing p ile s '............................. 4 -7 9
Acoustical properties................ 9-21 Bearing stress, anchor b o lts....... . . . ...............6 -2 5
Admixtures...................................................... 1 -2 9 Bearing w a lls ....................................... 1 -5, 3 -5 7
Aggregates........................................10—7 ,1 0 -1 9 Bearing walls, typical jo ints............................. 6 -4 0
Air barriers ..................... . .......................... . 9 - 1 5 Bearing, plain concrete....................„ .......... 4 -5 7
Air content ...................................................... 1 -2 6 Bearing, reinforced concrete .............. 4 -5 8
Air content, mortar ..........................................1-2 7 Bench m a rk s ..................... . ...................... 10-36
Air content, tolerance...................................... 1-2 9 Bilinear behavior ..............................................4 -6 8
Air entraining portland cem ent......... 1 -2 9 ,1 0 —19 Boathouse ....................... 1-1 4
Airborne sound ......................................... 9-21 B o lts ................................................................6 -1 5
Aircraft cable .................................................. 5 - 7 Bolts, allowable loads ........ 6 -6 2
Airport terminal ............................................. 1-13 Bonded steel p a d s ............................ 6 -1 9
Alignment connections .................................. 6 -3 8 Bowing .................................................. 3 -8 , 8 - 6
Allowable soil bearing .................................... 3 -4 2 Bowing, restrained ...............................3 -9 , 3 -1 0
Allowable stresses Box modules ...................................................1-16
(see service load stresses) ........................4 -7 7 Box type building ........................................... 3 -5 8
Anchor bolts...................................................10-36 B ra cin g ............................................................ 3 - 6
Anchor bolts, hooked...................................... 6 -2 3 Bracing equipment......................................... 5 -2 5
Anchorage details, veneer panels ................ 7 -1 6 Bracket plate .............................................. . . 6 - 1 5
Anchorage seating loss ................................ 4 -6 3 Brackets, concrete..........................................6 -2 5
Anchorage tests, veneer panels......................7 -1 9 Brackets, steel (see haunches) ......................6-2 7
Anchorage, daps ........................................... 4-61 Brick ............ 7-1 2
Anchorage, grouted conduit............................. 6 - 5 Bridges ............................................................1-21
Anchorage, stone facing ...............................7 -1 6 Bridges, thermal ............................................. 9-1 8
Angles, connection......................................... 6 -2 0 British thermal units (Btu) .................................9 -3
Angles, shear strength.................................... 6 -6 4 Builders risk insurance.................................. 10-41
Angles, stiffeners............................................. 6 -1 5 Building lin e s .................................................10-36
Approvals...................................................... 10-34
Arbitration....... .............................................. 10-42 Cable g u y s ...................................................... 5 -2 5
Architectural panel, Calcium chloride............................................1-3 0
earthquake analysis .................................. 3 -8 2 Cam ber........................................................... 4 -6 7
Architectural precast concrete........................1-1 7 Camber and deflection, design aids .............4 -7 2
Arenas............................................................. 1 -1 9 Gamber coefficients ....................... 1 1 -1 4 ,1 1 -1 5
Camber, long term ..........................................4-71
Backup concrete.............................. 7 -1 2 ,1 0 -1 9 Cantilevers................... 4 -8 3
Barricades .................................................... 10-29 Carbon equivalent............................................. 6 - 6
Bars, prestressing....................................... 11 -21 Caulking ......................................................... 7 -1 9
Base connections, cotum ns........................... 6 -2 4 Cazaly hanger.................................................6-31
Base plates ................. 6 -2 3 Ceiling weights ............................................. 11-2
Base shear, seism ic........................................3 -5 5 Cem ent........................................................... 1-24
Beam diagrams............................. 11 - 5 to 11 -1 3 Cement content, minimum ............................. 1-29
Beam load tables ........................................... 2-41 Cementitious materials....................... 1 -2 4 ,1 0 -7
Beam-column construction............................. 1 -7 Center of rigidity ............................................. 3 -2 6
Beams with overhangs, diagram s................ 11-18 Center of stiffness........................................... 3 -4 5
Bearing connections........................................6 -3 7 Ceramic fiber fe lt..................................... 9 -3 8
Bearing p a d s ...................................................6 -1 9 Ceramic tile .................................................... 7 -1 3

PCI Design Handbook/Fifth Edition In d e x - 1


Chemical resistance..................................... 1- 2 9 Connections^colomnbase............................. 6 -2 4
Chloride ions ............................... 1-30 Connections, design criteria ............................._6-4
Chloride penetration ..._____ 1 -2 3 J3onnections, durability .................. 3 -3
Chloroprene..................................... ...... .. .. 6 -1 9 Connections, fire protection .......................... 9 -4 7
Chord forces ............................ . ................... 3 -2 4 Connections, load fa cto rs.................................6 - 4
Cladding........................................................... 7 - 3 Connections, non-load
Claims, contract ................... 1 0 -4 3 bearing panels................. T -3
Clay products .......................................... 7 -1 2 Connections, sandwich panels-....................9 - 35-
Cleaning....................................................... 10-30 Connections, typical-seismic lo a d s ................3 -7 9
Clearance, example ....................... 8 -1 4 Construction lo a d s ................. 5 -2 4
Clearances....... ..................................... . ........8 - 8 Construction loads, safety factors ...................5 -2 5
Code of standard practice.............................10-32 Continuity........................................................4 -8 3
Coefficient of friction....................... ............. 6 -2 3 Contract administration ................................ 10-38
Coefficient of thermal expansion......... 1-26, 3 - 8 Contract term s...............................................10-40
Coefficients, shear friction................... 6-2 3 Contracts ...................................................... 10-45
CoHrods......................................................... 6 -6 2 Corbels ........................................................... 6-2 5
Coloring agent................................ 10-19, 10-23 Corbels, load ta b le s ........................................6 -6 6
Column base plates, design....... ......... 6-2 3 Corner separation, panel bowing .................. 3-11
Column base plates, thickness ......................6 -6 5 Corrosion resistance ...................................... 6 -1 6
Column b a se s....................................3-41, 3 -4 4 Cotton duck fabric pads ................................ 6 -1 9
Column covers ............................... ........... 7-11 Coupled shear walls ........................................3 -2 9
Column covers, fire resistance....................... 9 -4 8 Couplers............................................................6 -6
Column splices ...............................................3 -5 0 Cover requirements ......................... 1 -2 9 ,1 0 -2 6
Columns, eccentrically loaded........................3 -1 5 Crack co ntrol.................................................... 5 - 5
Columns, precast ..................... . ................... 2-4 7 Crack widths .................................................. 5 -5
Columns, prestressed ....................................2 -4 7 Cracking, repair and maintenance ................ 9-6 4
Combined shear and tension, Cracking, safety fa cto r...................................... 5 -5
studs ......................................................... 6 -1 3 Cracking, welded connections........................6-17
Combined shear and torsion, Creep strain, table ........................................... 3 -7
weld groups ...............................................6 -1 7 Creep, correction factors.................................. 3 - 7
Component design........................................... 4 - 7 Critical section...................................................4 -9
Composite design..... . ................................... 4 -2 3 Cube specimens............................................. 1-24
Composite members ......................................4 -2 3 Culvert............................................................. 1-22
Composite topping......................................... 3 -2 3 Curing, concrete...............................1 -2 4 ,1 0 -2 7
Compression members.................................. 4 -7 2 Cyclical movement, pads ...............................6 -1 9
Compression reinforcement, Cylinders, test ................................................. 1-24
effect on creep........................................... 5 -1 5
Compressive strength, concrete .................... 1-2 4 Dapped e n d s............................................ 4 -5 9
Compressive strength, Dead loads...................................................... 11-2
effect of temperature.................................. 9 -3 9 Dead weight, floors, ceilings, ro o fs .................11-2
Computer m odels....................3-31, 3-48, 3 -4 9 Debonded..........................................................4 - 9
Concentrated loads ....................................... 4 -1 6 Decibel ......................................................... 9-21
Concrete brackets ......................................... 6 -2 5 Deck panels.................................................. 1-21
Concrete coatings........................................... 9 -5 9 Deflection ............................................... 4 -6 7
Concrete mixes, specification....................... 10-10 Deflection, long term ......................................4-71
Concrete sealers.............................................9 -5 9 Deformed Bar Anchors (DBA) ....................... 6-1 5
Concrete, c u rin g ............................................. 1-24 Deformed prestressing bars,
Concrete, material properties......................... 1-24 properties .................................................11-21
Concrete, modulus of elasticity ......................1-25 Degree d a y........................................................ 9 -3
Concrete, tensile strength............................. 1-25 Degree of fixity, column b a se ......................... 3 -4 4
Concrete, unit weights.................................... 2 -4 Deicers ............................................................1-29
Condensation ................................................ 9 -1 5 Delivery..........................................................10-35
Confinement reinforcement, anchor bolts . .. 6 -2 3 Design analysis,
Connection angles ......................................... 6 -2 0 architectural panels...................................... 7 -3
Connection hardware........................................6 -5 Design calculations, specification . . . 1 0 -5 ,1 0 -1 7
Connections...................................................... 6 -1 Design criteria, connections............................. 6 -4

In d e x -2 PCI Design Handbook/Fifth Edition


Design responsibility—,.. .... .............................10-32 Epoxyr veneer panel anchors................ 7 -1 7
Development length, Equivalent volume change ............................. 3 -4 5
reinforcmg bars ........................................11-25 Equivalent volume change strains,
Development length, strand_____ ____ _ 4 -2 6 " ta b le ............................................ 3 -4 6
Developmentlength, strand, -Erection.................... 5-16, 5 -1 7 ; 1 0 -1 1 ,1 0 -2 3
design aid .......... 11-23 Erection analysis, exam ple............................. 5 -2 7
Dewpoint-..........................................................9 - 3 Erection b ra c in g ............................................. 5 -2 3
Diagonal tension, d a p s ......... .........................4 -6 0 Erection drawings........................... 1 0 -1 6 ,1 0 -3 3
Djaphragm design .............................3-23, 3 -5 7 Erection loads .................................................5 -2 4
Differential camber ........... 8 -5 Erection, architectural panels........................... 7 - 6
Differential temperature ........ 3 -1 0 Erection, factors of s a fe ty .............................. 5 -2 5
Direct shear, daps .............. 4 -6 0 Erection, specification .................................. 10-11
Distressed finish ........................................... 10-24 Erector, definition ......................................... 10-43
Double tee waH panels, Errors, correction ..........................................10-36
interaction curves ...................................... 2-5 1 Escorts, transportation.................................... 5 -1 6
Double tee, flange strength............................. 4 -1 6 Estimating prestress losses ........................... 4 -6 4
Double tee, partial prestress........................... 4 -1 5 Expansion inserts..... .................. .. — .......6 -1 6
Double tees, load tables .............2 - 7 to 2 -2 4 Expansion joints ................................ , ........ 3-11
Dowels, anchorage in c o n d u it..........................6 - 5 Extended end, d a p s ........................................4 -5 9
Dowels, stainless steel.................................... 7—17
Drift ................................................................. 3 -5 6 Fabrication, specification...............................10-24
Dry connection ............................................... 3 -5 5 Face m ix ........................................................10-23
Drypack............................................................1 -2 6 Factored cracking load .................................... 4 - 9
Duck layer reinforced pads . . . 6 -1 9 ,1 0 -9 ,1 0 -2 2 Factors of safety, construction
Ductility, connections........................................7 - 4 loads ......................................................... 5 -2 5
Ductwork ........................................................9 -6 8 Factors of safety,
Durability........................................................ 1-28 handling and erection ................................. 10 -6
Durability, connections...................................... 6 - 4 Field welding, specification..........................10-12
Dy-Core............................................................2-31 Fillet welds, allowable stresses ......................6 -4 7
Dynaspan........................................................ 2-31 Finish, distressed ......................................... 10-24
Finishes........................................... 1 0 -2 4 ,1 0 -3 5
Earthquake analysis........................................3 -5 2 Fire endurance, sandwich panels .................. 9 -3 7
Eccentric bracket connections........................ 6 -1 8 Fire resistance.................................................9 -2 9
Eccentric loading, weld g ro u p s ......................6 -1 7 Fire te s ts ......................................................... 9 -3 0
Eccentrically loaded columns......................... 3 -1 5 Fixed end moments ...................................... 11-16
Economic considerations, fire ........................9 -4 9 Flame finish ......... . ....................................... 7 -1 5
Edge distance, punched holes ......................6 -2 2 Flanged elements............................................. 4 - 8
Effective length ............................................... 3 -9 4 Flanking ..........................................................9 -2 8
Effective moment of in e rtia ............................. 4 -7 0 Flexibility coefficient, soil interaction...............3 -4 2
Effective shear friction coefficient.................... 6 -2 3 Flexible conduit, dowel anchorage .................. 6 -5
Effective width of p a n e ls.................................4 -7 7 Flexicore..... ....................................................2 -3 2
Elastic deflections ............................................4 -6 8 Flexural resistance coefficients........................4-8 7
Elastic deformation..........................................3 -1 2 Floor members ............................................... 8—10
Elastic stretch .................................. 5 -2 5 Floor openings.................................................4 -8 2
Elastomeric pads ........................................... 6 -1 9 Floor w eights...................................................11—2
Elastomeric pads, fire ...................................... 9 -4 7 Floors, erection tolerances ............................. 8-1 0
Electrified flo o rs...............................................9 -6 8 Flow chart, flexural calculation....................... 4 -1 0
Embedment length, dowels ............................. 6 - 6 Form draft............................................ 5 -3
Embedment length, studs............................... 6 -8 Form liners.................................................... 10-24
End point criteria............................................. 9-31 Form suction .................................................... 5 - 4
Engineer of Record......................... 1 0 -4 3 ,1 0 -4 4 Forms ............................................................... 7 - 6
Engineer of Record, definition ......................10-43 Frame distortion, panels ................................ 3 -1 2
Epoxy coated reinforcement............. 1 -3 1 ,1 0 -2 0 Free edge, anchor bolts .................................6 -2 3
Epoxy coated strand ...................................... 1-31 Free edge, headed studs .................................6—8
Epoxy cement .................................................1 -2 6 Freeze-thaw .................................................... 1 -2 9
Epoxy grout .................................................. 1-2 7 Friction ...............................................3-49, 6 -2 3

PCI Design Handbook/Fifth Edition ln d e x -3


Hollow-core, toad distribution..................... 4-81
Galvanized reinforcement , „ .............— . . . 1 -3 0 Hoffowrcore, load tabfes .............. 2 - 2 5 to 2 - 3 0
Galvanized, w e ld in g ............................... — 6-1©- Hollow-core, openings . ................................. 4 -8 2
Gaskets, veneer p a n e ls ............ ....................... 7 - 1 9 Hollow-core, slabs, properties ........2 -3 1 to 2 -3 4
Geometric-sections, properties . . 1 1 -2 9 1 o 11—3-1 Hollow-core, wall panels,
Glass Fiber Reinforced Concrete (GFBC) . . . 1 -1 8 interaction curves ...... 2 -5 2
G ranite-................. , ............ ................7 —15, 7 -1 7 Hooked anchor b o lts ............. .......................... 6 -2 3
Ground motion ......................... ................. 3 -5 5 H o o k s ____ - .............................................. 11—24
G ro u t................................ ...............................1 -2 6 Horizontal alignm ent.......................................... 8 - 5
Grout k e y s ......................................................... 3 -2 4 Horizontal jo in ts ................... 6 -4 0
Grout keys, shear s tre n g th .............................. 3 -2 4 Horizontal shear ........................ 4 -3 5
Guide specifications, architectural Horizontal shear reinforcement ....................... 4 -3 5
precast concrete ........................................10-13 Hot-dipped galvanized, w e ld in g ....................... 6 -1 6
Guide specifications, precast, Human response to vib ra tio n s .........................9-61
prestressed concrete ................................ 1 0 -2 Hybrid structures................................................3 -51
Gusset p lates..................................................... 6 -1 5
Gymnasium floor, vibrations.............................9-61 Imaginary c o lu m n ..............................................3 -4 5
Gypsum wall board .......................... 9 -3 3 impact factors, handling .................................... 5 - 4
Impact noise ........... 9 -2 2
Handling considerations .................................... 5 - 6 Importance factor, seismic ...............................3 -5 5
Handling devices................................................. 5 - 7 Inclined lift lin e s ................................................. 5 -1 0
Handling of panels, diagram s............................ 5 - 8 Initial c a m b e r..................................................... 4 -6 7
Handling, connection hardw are.........................5 - 8 In s e rts ..................................................... 6 -1 5 , 7 - 4
Handling, specification....................... 1 0 -6 ,1 0 -1 7 Inserts, wire c a p a c ity ........................................ 6 -6 2
Handling, with controlled cracking ................... 5 - 5 Inspection.......................................... 10-28, 1 0-34
Handling, without c ra c k in g ................................ 5 - 4 Inspection, specification ................. 1 0 -1 2 ,1 0 -2 8
Hanger connections............................ 6 -3 0 , 6—31 Insulated panels ................................................1 -1 2
Hanger reinforcement, d a p s ............................ 4 -6 0 Insulation ........................................................... 9 -5 4
Hanger steel, modification fa c to r.....................4 -4 9 Insurance ......................................................... 10-41
Hardware, connections ...................................... 6 - 5 Intentional roughness........................................ 4 -3 5
Hardwood strips ................................................6 -1 9 Interaction curve, columns .............................. 2 - 5
Hauling (see transportation)............................ 5 -1 6 Interaction, shear wall-frame.............................3 -4 9
Haunches, concrete (see corbels)................... 6 -2 5 Interface characteristics.................................... 8 -1 8
Haunches, structural stee l................................ 6 -2 7 Interface, other trades .................................... 1 0-37
Headed studs ................................................... 6 - 6 Inverted tee beams, load ta b le s ___2 -4 4 to 2 -4 6
Headed studs, combined lo a d in g ................... 6 -1 4
Headed studs, dim ensions.............................. 6-51 Jackson-Moreland alignment
Headed studs, free edge one side ................. 6 -5 4 c h a rt............................................................... 3 -9 4
Headed studs, free edge four Joint clearance ....................................................8 - 8
adjacent sides ..............................................6 -5 8 Joint sealants..................................................... 9 -5 9
Headed studs, free edge three s id e s ........... 6 -5 7 Joints, segmental construction.........................9 -6 5
Headed studs, free edge two Joints, thermal treatm ent...................................9 -3 7
adjacent sides ..............................................6 -5 6 Justice fa c ilitie s ................................................ 1 -1 6
Headed studs, free edge two
opposite sides ................................................6 -5 5 Keyed joints, wait p a n e ls.................................. 6 -3 9
Heeded, studs, minimum member
thickne ss...................................... 6 -5L-shaped
9 beams, load ta b le s ........................ 2 -4 2
Headed studs, not near free e d g e ...................6 -5 3 Large panel structures...................................... 3 -5 1
Headed studs, shear strength .........................6 -6 1 Lateral load resisting systems ........................... 3 - 6
Headed studs, strength reduction Lateral stability................................................... 5 -1 4
of g ro u p s .......................................................6 -6 0 Latex additives....................................................7 -1 3
Headed studs, tensile strength ....................... 6 -51 Ledger beam, ledge d e s ig n .............................4 -4 6
Heat capacity....................................................... 9 - 3 Ledges, longitudinal b e n d in g ...........................4 -4 6
Heat flo w .............................................................9 -1 2 Ledges, transverse b e n d in g .............................4 -4 6
Heat transm ittance..............................................9 - 3 Lift lo o p s ............................................................... 5 - 8
High strength threaded ro d s .............................6 -1 5 Lifting loads, equalization ................................ 5 -1 1
Hollow-core .......................................................8 - 5

In d ex-4 PCI Design Handbook/Fifth Edition


Light wall, parking s tru c tu re ........................... 1 -1 4 Moment d ia gra m srfire ..................... 9 - 4 0 to 9 -4 2
L ig h tin g ...................................... ...............9 -6 8 Moment magnification . . . . : ............... 3 - 1 7 , 3 - 1 9
Lightweightcoacrete-....................... . ........... 1 -2 5 Moment m a gnifier............... ............................ 3-^20-
lim e s to n e .............................................7 -1 5 , 7 -1 7 Moment o f inertia . „ ......................................4 - 7 9
Live-loads, recommended Moment-resisting framesr_____ 3 - 6 r 3 - 4 1 , 3 -4 5
m inirm im . ................................................... 1 1 -3 Moments in panels, h a n d lin g .............. . 5 —8, 5 - 9
Load end resistance factor M o rta r................... 1 -2 6
design (LRFD) ........ .......... . ......................6 -1 6 -Moving to a d s ..................... .......... ... .............1 1 -1 7
Load bearing panels, connections ................. 6 -4 4 M ullions.................................... . ...................... 7 —11
Load distrib utio n ................................................4 -8 1 Multimonomer plastic strips ............................. 6 -1 9
Load distribution, assum ed........... 4 -8 2
Load factors, connections.................... 6 -4 , 6 -1 6 Natural s to n e ..........................................7 -1 2 , 7 -1 5
Load tab le s................. 2 -3 Natural fre q u e n cy .............................................. 9-61
Load tables, limiting criteria ...............................2 - 3 Neoprene (see chloroprene).............................6 - 1 9
Load transfer, architectural panels ................... 7 - 3 Noise criteria ..................................................... 9 -2 6
Long term camber, Noise re d uctio n ..................................................9 -2 2
suggested multipliers ......... . .................. . 4 -7 1 Non-bearing panels .......................................... 3 -1 2
lo n g term cam ber/deflection...........................4 -7 1 Non-load bearing panels,
Loop inserts ..................... 6 -1 6 connections ..................................................6 -3 6
Loov h a n g e r....................................................... 6 -3 3 Non-prestressed panels.................................... 4 -2 0
Loss of prestress..................................................2 - 5 Non-shrink g ro u t. . ............................................ 1 -2 7

Maintenance .......................... 9 -6 4 Office b u ild in g s ................................... 1 -9


M a rb le .................................................................7 - 1 5 Out-of-plane bending, beam le d g e s ............... 6 -3 8
M aterials............................ ............................ 1 0 -3 4 Overjacking ....................................................... 4 -6 3
Materials, specification....................... 10—7 ,1 0 —19 Owner, definition.............................................. 1 0 -4 4
Maximum permitted computed
deflections..................................................... 4 -6 9 P-delta analysis .................................. 3 -1 7
Maximum strand diameter...................................5 - 6 Panels, load bearing.......................................... 3 -1 3
Maximum water-cementitious Panels, non-load bearing .....................3 -1 2 , 6 -3 6
material ra tio ................................................1 -2 9 Parking structure, earthquake
Mechanical anchors, stone analysis ......................................................... 3 -7 2
veneer ........................................................... 7 -1 7 Parking structures.............................................. 1 -1 4
Mechanical systems, coordination . . . 9 -6 8 , 9 -7 0 Partial fix ity .................................... . ................ 3 -4 4
Metallic c o n d u it....................................................6 - 5 Partial penetration welds, allowable
Metric conversion .........................11 - 3 2 to 11 -3 5 stre sses......................................................... 6 -4 7
Microcracking, g ra n ite ...................................... 7 -1 5 Partial prestress.............................. 4 -1 2
Minimum cement content .................................1 -2 9 Patching .................................................. 1 0-37
Minimum clearances .......................................... 8 - 5 P ayloads............................................................. 5 -1 6
Minimum crack w id th s ...................................... 4 -2 0 Penetrating sealers.............................. 1-2 8 , 9 -5 9
Minimum eccentricity, columns ....................... 3 -4 4 Peripheral design force .................................... 3 -5 1
Minimum horizontal force ...................................6 - 4 Perm ...................................... 9 -3
Minimum reinforcement, pan e ls....................... 4 -2 1 P erm eability............................................7 -1 6 , 9 - 3
Minimum shear reinforcem ent.........................4 -3 4 Perm eance............................................................9 - 3
Minimum thickness, bearing p a d s ................... 6 -2 0 Pick-up points ................................................... 5 -1 0
Mixed building systems ...................................... 8 - 8 Pigm ents............................ 1 -2 4
Mockup, specification .................................... 1 0-15 Pile c a p s ................................. 1 -21
Modeling of fra m e s............................................3 -4 4 P ile s .......................................................................2 - 6
Moderate exposure.......................................... 1 -2 9 Piles, allowable tension .................................... 4 -8 0
Modulus of elasticity, clay products ............... 7 -1 2 Piles, section properties.................................... 2 -5 5
Modulus of elasticity, co ncrete ......................... 1 -2 5 Pipe braces ....................................................... 5 -2 7
Modulus of elasticity, design aid ................... 1 1 -1 9 Plain concrete bearing........................................4 -5 7
Modulus of ru p tu re .............................................. 5 - 4 Plant certification.......... 1 -4 , 9 - 5 7 , 1 0 - 3 , 1Q-14
Moisture difference..............................................3 - 9 Plastic bearing p a d s .......................................... 1 0 -9
Moment connections ........................................ 6 -3 6 Plastic deform ation............................................ 3 -1 2
Moment diagrams, design a id s ........... 11 - 5 to 13 Plastic section m o d ulu s.................................... 6 -1 6

PCI Design Handbook/Fifth Edition ln d e x -5


Poisson’s-FatiG.................................................1 -3 5 Reinforcing steel, anchorage in
Polar moment afinertia, g r o u t s ............................ ....................- , . . . 6 - 5
welcLgroops . . ............................ . ..... 6 -1 7 Reinforcing bar couplers- ............. ................. .6 - 6
Poles .................. 1 -2 5 Reinforcing b arer_____ ___ _____________ 1 -2 8
Bost-tensioned-wall p a n e ls ............................. . 5 - 7 Reinforcing bars, development
Post-tensioning, connections^..........................6 - 1 8 le n g th ..................................................... — 11 -2 5
Post-tensioning,-segmental.............................. 9 -6 6 Reinforcing bars, minimum weld
Post-tensioning, wall connections — 6 -4 3 , 6 -4 4 le n g th s......... .......................................... 6 -4 6
Precast cladding. . . .......................................... t - t 7 Reinforcing bars, p ro p e rtie s......................... 1 1-24
Precast columns, interaction Reinforcing bars, typical w e ld s................. 6 -5 , 6 - 7
curves .................................................... 2 -4 9 Reinforcing bars, w e ld in g ...................................6 - 6
Precast engineer, definition.............................1 0-44 Relative hum idity..................................................9 - 4
Precast panels as forms .................................... 7 - 4 Relative humidity, correction
Precast wall panels, interaction factors ............................................................. 3 - 8
curves ........................................................... 2 -5 4 Relative humidity, m a p ...................................... 3 -8 6
Prefabricated m odules................................. 9 -7 0 Release reinforcement — ...............................4 -2 5
Premixed grout ....................................... — 1 —27 Release s tre n g th ......... ......... ..............2 - 4 ,1 0 - 1 0
Prestress losses .............................. 4 -6 3 Repair of cracks ................................................9 -6 4
Prestressed columns, interaction Repair, specification.................... 1 0-30
curves ...........................................................2 -4 7 Residential buildings ................................ — 1 -5
Prestressed wall panels, han d lin g .................... 5 - 6 Responsibility......................................... 8 -2
Prestressed wall panels, interaction Responsibility, erection .................................... 5 -2 3
curves .............. 2 -5 1 , 2 -5 3 Responsibility, recommendations ................. 1 0 -4 3
Prestressing bars, properties .......................11-21 Restrained members, fire .................................9 -4 7
Prestressing steel, properties......................1 1-2 2 Restraint force build-up in beams,
Prestressing tendons .. ..................................1—27 ta b le ........... ...................................................3 -4 7
Prestressing wire, properties .........................1 1-22 Reverberation..................................................... 9 -2 1
Primary control surface .................................... 8 - 2 Ribbed members, handling
Product delivery, specification ......... 1 0 -6 ,1 0 -1 8 stre sses......................................................... 5 -1 0
Product handling........... ...................................5 - 3 Ribbed panels, fire resistance .........................9 -3 3
Product information ............. ............................ 2 -1 Rigidity of shear walls ...................................... 3 -2 6
Production considerations.................................. 7 - 6 Roof m em bers................................................... 8 -1 0
Production drawings, specification............. 1 0-17 Roof w eights........................................................11—2
Properties of geometric sections . 11 - 2 9 to 11 -31 Roofs, U-values..................................................9 -1 0
Properties of weld g ro u p s .................................6 -1 7 Rotation coefficients ...................................... 11—14
Protection of reinforcement ...........................1 -3 0 Rotation, p a d s ................................................... 6 -2 0
Protection, specification.................................. 10-31 Rotation, support b e a m s............. .......................7 - 6
Prying action, panels ........................................ 9 -5 3
S a b in ...................................................................9-2 1
Quality assurance, specification..................... 1 0-14 Safe superimposed loads ...................................2 - 3
Quality control ................................................... 9 -5 8 Safety equipment ............................................ 10-41
Safety factor, cra c k in g ........................................ 5 - 5
R-values, insulating m aterials........................... 9 -3 4 Samples, pre-bid............................... 1 0-16
Railroad t ie s ........... ......................................... 1 -2 2 Samples, veneer panels .................................. 7 -1 9
Raker beams ..................................................... 1 -1 9 Sand-cement m ixtures...................................... 1 -2 6
Random oriented fiber p a d s .............................6 -1 9 Sand-lightweight concrete.................................1 -2 6
Range of losses................................................. 4 -6 4 S a n d b la st......................................................... 1 0 -2 6
Records............................................................. 1 0-28 Sandstone .........................................................7 -1 7
Rectangular beams, load tables ...................2 -4 1 Sandwich panels.................................... 9 -3 5 , 9 -51
Reentrant corner, daps .....................................4 -6 0 Sandwich panels, connectors .........................9 -5 3
Reinforced concrete bearing ...........................4 -5 8 Sandwich panels, fire resistance..................... 9 -3 6
Reinforcement limitations .................................. 4 - 8 Sandwich panels, the rm al................................ 9 -1 8
Reinforcement, epoxy c o a te d ......................... 1-31 Sealers ............................................................. 1 -2 8
Reinforcement, galvanized ............................ 1-3 0 Seasonal temperature change,
Reinforcement, protection.................................1 -3 0 map ...............................................................3 -8 6

In d e x -6 PCI Design Handbook/Fifth Edition


Second-order a n a lysis...................................... 3 -1 7 S pa n drels................................................3 -1 4 , 8 - 9
Secondary-control surface ____ ______ — 8 - 2 Special permits, transporf^terr .” . : _____. . . 5 - I S
Sectiorrmodulus, weld groups^.................... 6 -1 8 Specifications..................... . 10—t, 1 -0 -2 ,1 0 -1 3
S egm ental-conduction............. .......... . ........9 -8 5 Splice steeve .................. 6 -4 3
Seismic, d e s ig n .................................... IB -5 6 Stadium seat, vibrations ...................................9 -6 2
ServiceJoad design .......................................^ 4 - 2 0 S tadium s................................ 1 -1 9
Service load stresses........................................-4 -7 7 Stainless steel ______ 6 —16
Seven-wire strand,-properties......................... 11—20 -Stainless steel dowels ............. ..................... 7 -1 7
Severe e xpo su re ........ -................................... 1 -2 9 Standard cylinders ............................................ 1 - 2 4
Shape factor, bearing pads . . — 6 -2 0 , 6 -2 1 Standard h o o ks................................................1 1 -2 4
Shear and torsion d e s ig n .................................4 -4 1 Standard p ra c tic e ........................................... 10—1
Shear cone, headed studs ............................... 6 - 8 Standard practice, code . . .............................1 0 -3 2
Shear depth ratio, daps .................... 4 -5 9 Standard time-temperature
Shear d e s ig n ........... ..........................................4 -3 0 curve ..................................... 9 -3 0
Shear design a id s ............ . . . .......................... 4 -9 0 Static load m ultipliers.......................................... 5 - 5
Shear-friction .............. . . . . ..............................4 -3 8 Stemmed units, fire resistance......................... 9 -4 1
Shear-friction coefficients ....... 4 -3 8 Stirrup h o o k s ....................................................1 1 -2 4
Shear lag ....... . . ...............................................3 -4 0 Stone facing, a nchorage.................................. 7 -1 7
Shear reinforcement.......................................... 4 -3 4 Stone veneer, sizes .......................................... 7 -1 6
Shear resistance, bearing p a d s ....................... 6 -2 1 S to ra g e ............................................................... 5 -1 4
Shear resistance, f i r e ........................................ 9 -4 7 Storage, specification......................... 1 0 - 6 ,1 0 - 1 8
Shear strength, angles...................................... 6 -6 4 Story drift ........................................................... 3 -5 6
Shear strength, s tu d s ........................................ 6—10 Strain com patibility.............................................. 4 - 9
Shear wall b u ild in g s ................... . .................. 3 -2 5 Strand development length .............................4 -2 6
Shear wall deflections .......................................3 -2 6 Strand diameter, panel thickness ..................... 5 - 6
Shear wall-frame interaction.............................3 - 4 9 Strand lifting loops .............................................. 5 - 8
Shear walls ......................................................... 3 - 6 Strand, epoxy coated .................................... 1 -3 1
Shear walls with openings ...............................3 -2 9 Strand, stress-strain curve .............................1 1 -2 2
Shear walls, coupled ........................................ 3 -2 9 Strands ............................................................... 2 - 5
Shear walls, rigidity............................................ 3 -2 6 Strength d e sig n .................................................... 4 - 8
Shear walls, unsymmetrical .............................3 -2 7 Strength-temperature relationship................... 9 -3 9
Sheet piles ......................................................... 4 -8 0 Stress b lo c k ..........................................................4 - 8
Sheet piles, section properties......................... 2 -5 6 Stress-strain curve, design a id ....................... 11 -2 2
Shop drawings ................... 1 0 - 4 ,1 0 - 1 6 ,1 0 -3 3 Stripping forces, e x a m p le .................................5 -1 1
Shop drawings, approvals . . . . ___1 0 -4 1 ,1 0 -4 3 Strongbacks, transportation.............................5 -1 6
Shop drawings, d e fin itio n ...............................10-41 Structural integrity..............................................3 -4 9
Shop drawings, specification......................... 1 0 -1 6 Structural integrity, f ir e ...................................... 9 -3 7
Shop drawings, s u b m itta l................. 1 0 - 4 ,1 0 - 1 6 Structural p a n e ls.................................................. 8 - 6
Shore hardness, bearing p a d s ......................... 6 -2 1 Structural steel, connections ...........................6 -1 6
Shrinkage strain, ta b le ...................................... 3 -8 7 Structural steel, welding .................................. 6 -1 6
Shrinkage-compensating cement ....................1 -2 6 Structural steel haunches .................................6 -2 7
Si units ............................................................. 11—33 Structural steel haunches,
Site access, specification ........................ 10-11 design strength ..................... . .................. 6 -7 1
S la te .....................................................................7 -1 7 Structural wait p a n e ls.............................2 -5 1 , 8 - 6
Slenderness effects .......................................... 4 -7 7 Stud g ro u p .............................. . .............6 - 9 ,6 - 1 1
Solid flat slab, load ta b le s ............... 2 -3 5 to 2 -4 0 Studs (see headed s tu d s )...................................6 - 6
Sound a bsorption........................ 9 -2 4 Subgrade reaction ............................................ 3 -4 2
Sound absorption coefficient ........................... 9 -2 4 Submittal, specification .................................. 1 0 -1 6
Sound in sulation................... . ........................9 -2 7 Sulphate attack . . ........................ 1 -3 4
Sound pressure le v e l........................................ 9 -2 1 Sun effect, s to ra g e ............................................ 5 -1 4
Sound Transmission Class (STC) ___9 - 2 1 ,9 - 2 2 Surface sealers ......... . ................................... 9 -5 9
Sound transmission lo s s .................................. 9 -2 1 Suspended ceilings .......................................... 9 -7 0
Sound wall ....................................................... 1 -2 2 S w e e p ............. ..................................................... 8 - 5
Span deck ......................................................... 2 -3 3 Swivel plate ............................................5 -8 , 5 -1 1
Span-to-depth ra tio .............................................. 3 - 6 System b uilding..................................................9 -7 0
S pancrete...................................... 2 -3 2

PCI Design Handbook/Fifth Edition Index- 7


T anks................................................................ 1- 2 3 Truncated pyramid failure,
Teflon............. ................................................. 6—15- studgroups ............................ 6 -8 -
Temperature change, m a p .............................. 3 -B 6 Tube structure ............................... - ............. .3 -4 0
Temperature strains ..................................... 3 -8 Turning r i g s ......................................................... 5 - 6
TemperedJiardwood s trip s ............................. 6 - 1 9 Type X gypsum wall b o a rd ............................ 5 - 3 3
Ten^DOEary-toads, diagrams .......................... 5 -2 6 Typical handling: m ethods................................... 5 - 4
Temporary loading, stability
oonsiderations ............................................. 5 - 2 6 U -va(ues......... ... ....................... 9 -9
Temporary su pp o rts............. .......................... 1 0 -2 9 U ltra s p a n ........................................................... 2 -3 3
Tensile strength, concrete................................ T -2 5 Unbraced frame, a n a lysis........... ...................3 -4 3
Tensile strength, s tu d s .......................... .......... H Unbraced frame, stability analysis................... 3 -4 3
Terms and conditions, c o n tra c t..................... 1 0 -3 9 Undeveloped s tra n d .......................................... 4 -2 7
Terra cotta ........... . ..........................................7 -1 2 Unsymmetrical shear w a lls ............. .................3 -2 7
Tests .................................................................1 0 -3 4 Utilities............................ 1 0-36
Tests, anchorage of veneer p a n e ls ......... . 7 -1 9 Utility p oles......................................................... 1 -2 3
Tetrafluorethylene (TFE) .................... . 6 - 1 9 ,1 0 - 9
Thermal bow ing ............................................... 3 - 8 Vapor re ta rd e r........... ................... 9 -1 6
Thermal bowing, sandwich panels ........... 9 -5 6 Veneer jointing ..................................................7 -1 5
Thermal b r id g e s ...................................... 9 -1 8 Veneer panel anchors,
Thermal conductance ........................................ 9 - 4 flexibility............................................... 7 -1 6
Thermal expansion, co ncrete .........................1 -2 6 Veneered p a n e ls................................................7 -1 2
Thermal Fusible Membrane (TFM) ................. 9 -1 6 Vertical tension tie s ............................................ 3 -51
Thermal loads, comparisons ........................ 9 -1 3 Vibration ............................................................. 9 -6 1
Thermal mass ....................... 9 -4 Vibration, in s e rts ................................................6 -1 6
Thermal properties .................................. 9 -4 , 9 - 7 Vibration, isolation..............................................9 -6 2
Thermal resistance..............................................9 - 4 Volume change, moment
Thermal storage e ffe c ts .................................... 9 -1 2 resisting frames ..........................................3 -4 5
Thin sections, s tu d s ............. .............................. 6 - 9 Volume change, restraint forces,
Threaded connectors........................................ 6 -1 5 ta b le ............................................................... 3 -4 6
Threaded rods ...................................................6 -1 5 Volume change, strains,
Tie hooks ......................................................... 1 1 -2 4 typical b u ild in g ..............................................3 -8 9
Tie-back connections........................................6 -3 7 Volume ch a n g e s................................................1 -2 5
Ties, clay p ro d u c ts ..............................................7 - 9 Volume-surface ratio, correction
Tilt table ................................................... 5 - 6 , 5 - 1 0 factors ........................................................... 3 -8 8
Tilted beam, equilibrium .................................. 5 -1 5 Volume-surface ratios, typical
Tolerances ......................................................... 8 -1 m em bers....................................... 1 -2 6
Tolerances, acceptability range ................... 8 -3
Tolerances, architectural panels ....................... 8 - 6 Wall connections ........... 3 -7 2
Tolerances, b e a m s ..............................................8 - 9 Wall panels, effective w id th ...............................4 -7 7
Tolerances, bearings .......................................... 8 - 8 Wall panels, grooved joints ...............................6 -3 6
Tolerances, camber va ria tio n .............................8 - 5 Wall panels, mechanical connections........... 6 -4 0
Tolerances, connections .................................... 8 - 5 Wall panels, minimum reinforcement ................5 - 5
Tolerances, e re ction ............................................8 - 2 Wall panels, post-tensioned ...............................5 - 7
Tolerances, interfacing...................................... 8 - 2 Wall panels, prestressed.................................... 5 - 6
Tolerances, panel flatness.................................. 8 - 6 Wall panels, tripping, d ia g ra m s ....................... 5 -1 9
Tolerances, p ro d u c t............................... 8 -3 Wall tie s ................................................................. 7 - 9
Tolerances, sm oothness........................ 8 -6 Wall w e ig hts........................................................1 1 -2
Torsion ...............................................................4 -3 9 Wall-beam conn e ction s................................. 3 -6 2
Torsion, accid en tal.......................... 3 -5 6 Wall-double tee connections.. 3 -6 2 , 3 -6 4 , 3 -6 8
Transfer length ................................................. 4 -2 9 Wall-footing conn e ction .................................... 3 -6 6
Transfer length, design a id .............................1 1-23 Walls, U-values ................ 9 -9
Transmittance ................................................... 9 - 5 Walls, vertical connections ...............................3-51
Transportation................................................... 5 -1 6 Walnut Lane Memorial Bridge ........................... 1 -2
Travertine ........................................................... 7 -1 7 Warpage, s to ra g e ..............................................5 -1 4
Tripping, d ia g ra m s............................................5 -1 9 Warping ............................................................... 8 - 6

In d ex-8 PCI Design Hartdbook/Frfth Edition


W a rran ty........................................................... 1 0 -3 7 Welding, rods ....................................................6 -1 7
Waste-watertreatmerrt p ta n t........................... 1 -1 3 Welding, structural steel" . . . . . . . _______ 6 -1 6
Water a bsorption......................._ ............ 1 0 -1 6 Welds, reinforcing b a rs :.................., .......... 6 - 6
Water-cementitious materialsTatio............. ..... 1 - 2 Welds, typical reinforcing b a r s .........................6 -7 -
Wedge action, inserts ............................. . 6 -1 3 Wet connection ............................................ 3 - 5 4
-Weight limitations, transportation..................... 5 -1 6 W in d lo a d ........................................................ 3—1-2
Weid g ro u p s ............... 6 -1 7 Wind load, panels............... 3—12
Weld groups, properties ............... - ............. 3 - 1 7 Window w a ll..................................... 3 -1 3
Weld plates ........................................... 8 -5 Wire rope ........... ..................................3 - 2 5 , 5 -2 7
Welded connections, c ra ckin g ......................... 6 -1 7 Wire rope, stretch ...................................... „ . . 5 -2 5
Welded headed studs Wire ro p a c o re ........................ 5 -2 5
(see headed s tu d s )........... ............................ 6 - 6 Wire strand c o r e .......................... 5 -2 5
Welded wire reinforcem ent............... 1 -2 8 ,1 1 - 2 7 Wire, prestressing ................... . .............. ... 1 1-20
Welded wire reinforcement, Wythe connectors........................ 9 -5 3
double tee fla n g e s...................................... 1 1 -2 8
Welded wire reinforcement, properties........11—27 X-bracing ............................................................. 3 - 6
Welding, hot-dip galvanized.............................6 -1 6
Welding, reinforcing bars ................................ 6 - 6 Z-factor ............................................................... 4 -2 1

PCI Design Handbook/Fifth Edition In d e x -9


V

PCI Design Handbook/Fifth Edition


I n d e x - 10

Vous aimerez peut-être aussi