Vous êtes sur la page 1sur 20

SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 1/20 SUBSTATION FAULTY UNIT SEPT 25 3019.

S40

Properties

Customer : VUI
Project : SEPAM S40
Switchboard : SUBSTATION
Cubicle : 20KV
Print date : 25/09/19
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 2/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40
Hardware configuration
Application type : Substation S40
Sepam label : SUBSTATIONFAULTYUNIT
Sepam model : MX model (without fixed advanced UMI)
Optional modules
MES (Input / output module) : absent
MET148 (8 temperature sensors module) number 1 : absent
MET148 (8 temperature sensors module) number 2 : absent
MSA141 (1 analog output module) : absent
DSM303 (Front panel UMI module) : present
ACExxx (Communication interface) : absent
Synchronization mode : Network
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 3/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

General characteristics
Network frequency : 50 Hz
Selection of active setting group : Setting group A
Remote setting enabled : No
Sepam working language : UK English (IEC)
Main/feeder : ANSI Main/Feeder - IEC Feeder
Rated secondary current : 5A CT
Number of CTs : Ia,Ib,Ic
Rated primary current (IN) : 630A
Base current (IB) : 630A
Demand Interval : 5min
Residual current : None
Rated primary voltage (VLLp) : 20kV
Rated secondary voltage (VLLs) : 100V
VT connection type : Vab,Vbc
Residual voltage measurement : None
Meter increment Active energy : 0.1kW.h
Meter increment Reactive energy : 0.1kVar.h
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 4/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

Current transformer supervision, CTS


On : No
CTS Time delay : 150ms
Behavior on 46/46BC/51N/32P/32Q : Block
Voltage transformer supervision, VTS
On : No
Use Iinv,Vinv criterion : Yes
Time delay, Iinv Vinv : 1s
Iinv threshold : 5 %IN
Vinv threshold : 10 %VN
Check loss of 3VLn/2VLL : No
Time delay, loss 3VLn/2VLL : 1s
Test current : Yes
Behavior on 27/27D/32P/32Q/47/59/59N/51V : Block
Behavior on 67 : No directional
Behavior on 67N : No directional
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 5/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

Program logic
Circuit breaker control : Yes
Zone selective interlocking : No

Relay output parameters


Used Caracteristics Pulse
O1 Yes normally open
O2 Yes normally closed
O3 Yes normally open
O4 Yes normally closed
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 6/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

50/51 : Phase overcurrent


On Latching Trip C.B. Confirmation
Element 1 X X No confirmation
Element 2 X X No confirmation
Element 3 X X No confirmation
Element 4 X X No confirmation

H2 threshold : 17 %

Group A (Active group)


Tripping curve Current threshold Delay Timer hold curve Timer hold delay H2 Icc min.
1 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA
2 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA
3 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA
4 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA

Group B
Tripping curve Current threshold Delay Timer hold curve Timer hold delay H2 Icc min.
1 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA
2 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA
3 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA
4 Definite time 1.26kA 100ms Definite time 0ms 6.3 kA

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X X
Element 2 X X
Element 3 X
Element 4 X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 7/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

50N/51N : Ground fault


On Latching Trip C.B. Residual current type
Element 1 X X sum 3I
Element 2 X X sum 3I
Element 3 X X sum 3I
Element 4 X X sum 3I

Group A (Active group)


Tripping curve Current threshold Delay Timer hold curve Timer hold delay H2 restraint
1 Definite time 630A 100ms Definite time 0ms
2 Definite time 630A 100ms Definite time 0ms
3 Definite time 630A 100ms Definite time 0ms
4 Definite time 630A 100ms Definite time 0ms

Group B
Tripping curve Current threshold Delay Timer hold curve Timer hold delay H2 restraint
1 Definite time 630A 100ms Definite time 0ms
2 Definite time 630A 100ms Definite time 0ms
3 Definite time 630A 100ms Definite time 0ms
4 Definite time 630A 100ms Definite time 0ms

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X X
Element 2 X X
Element 3 X
Element 4 X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 8/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

50BF : Breaker failure


On Latching Current threshold Delay Use close positionof circuit breaker
Element 1 630A 120ms

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 9/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

46 : Negative sequence current / unbalance


On Latching Trip C.B. Current threshold Tripping curve Delay
Element 1 X X 10% of IB Definite time 100ms
Element 2 X X 10% of IB Definite time 100ms

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 10/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

27/27S : Undervoltage
On Latching Trip C.B. Voltage mode Voltage threshold Delay
Element 1 Phase-to-phase 10%VLLp 100ms
Element 2 Phase-to-phase 10%VLLp 100ms

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 11/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

59 : Overvoltage
On Latching Trip C.B. Voltage mode Voltage threshold Delay
Element 1 Phase-to-phase 110%VLLp 100ms
Element 2 Phase-to-phase 110%VLLp 100ms

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 12/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

59N : Neutral voltage displacement


On Latching Trip C.B. Voltage threshold Delay
Element 1 10%VLLp 100ms
Element 2 10%VLLp 100ms

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 13/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

47 : Negative sequence overvoltage


On Latching Trip C.B. Voltage threshold Delay
Element 1 10%VLLs 100ms

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 14/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

81H : Overfrequency
On Latching Trip C.B. Frequency threshold Delay Min. voltage
Element 1 53Hz 100ms 20%V
Element 2 53Hz 100ms 20%V

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X

81L : Underfrequency
On Latching Trip C.B. Frequency threshold Delay Min. voltage df/dt_restraint Threshold
Element 1 45Hz 100ms 20%V No 5Hz/s
Element 2 45Hz 100ms 20%V No 5Hz/s
Element 3 45Hz 100ms 20%V No 5Hz/s
Element 4 45Hz 100ms 20%V No 5Hz/s

Tripping behavior
O1 O2 O3 O4 L1 L2 L3 L4 L5 L6 L7 L8 L9 Alarm US Alarm Local Rec.
Element 1 X
Element 2 X
Element 3 X
Element 4 X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 15/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

Logical equations

Save variables VL24 to VL31 : yes


SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 16/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

On Latching Trip C.B. O1 O2 O3 O4 Led 1 Led 2 Led 3 Led 4 Led 5 Led 6 Led 7 Led 8 Led 9 UK message US message Rec.
50/51 - 1 X X X X
50/51 - 2 X X X X
50/51 - 3 X X X
50/51 - 4 X X X
50N/51N - 1 X X X X
50N/51N - 2 X X X X
50N/51N - 3 X X X
50N/51N - 4 X X X
50BF - 1
46 - 1 X X X
46 - 2 X X X
27/27S - 1 X
27/27S - 2 X
59 - 1 X
59 - 2 X
59N - 1 X
59N - 2 X
47 - 1 X
81H - 1 X
81H - 2 X
81L - 1 X
81L - 2 X
81L - 3 X
81L - 4 X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 17/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

O1 O2 O3 O4 Led 1 Led 2 Led 3 Led 4 Led 5 Led 6 Led 7 Led 8 Led 9 UK message US message Rec.
Close command by CB control
Tripping by CB control X X
Block closing by CB control X
Pick-up X
Drop-Out
RemCtrl/CB pos. discrepancy
Control circuit fault
Phase reversal
Fault recording blocked
Watchdog X
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 18/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

O1 O2 O3 O4 Led 1 Led 2 Led 3 Led 4 Led 5 Led 6 Led 7 Led 8 Led 9 UK message US message Rec.
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 19/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

O1 O2 O3 O4 Led 1 Led 2 Led 3 Led 4 Led 5 Led 6 Led 7 Led 8 Led 9 UK message US message Rec.
V1
V2
V3
V4
V5
V6
V7
V8
V9
V10
SUBSTATIONFAULTYUNIT (2019/9/25 9:18) page 20/20 SUBSTATION FAULTY UNIT SEPT 25 3019.S40

Function setting

Fault recording
Activity : On

Settings
Memory use : 100%
Number of records : 9
Record length : 2s
Number of cycles before trigger : 36