Académique Documents
Professionnel Documents
Culture Documents
MINISTRY OF RAILWAYS
Handbook on
Troubleshooting
of
DIGITAL AXLE COUNTERS
I hope that this handbook will help the signal maintenance personal in efficiently
rectifying the failures of Digital Axle Counters. Any suggestions for further improvement
are welcome.
It is clarified that this handbook does not supersede any existing provisions laid
down in Signal Engineering Manual, Railway Board publications and RDSO
publications. This handbook is not statutory and instructions given in it are for the
purpose of guidance only.
Since technological upgradation and learning is a continuous process, you may feel
the need for some addition/modification in this handbook. If so, please feel free to give
your comments on email address dirsntcamtech@gmail.com or write to us at Indian
Railways Centre for Advanced Maintenance Technology, In front of Adityaz Hotel,
Airport Road, Maharajpur, Gwalior (M.P.) 474005.
Foreword IV
Preface VI
Contents VIII
Correction Slip X
Disclaimer XII
The correction slips to be issued in future for this handbook will be numbered as follows:
Where “XX” is the serial number of the concerned correction slip (starting from 01 onwards).
It is clarified that the information given in this handbook does not supersede any
existing provisions laid down in the Signal Engineering Manual, Railway Board and
RDSO publications. This document is not statuary and instructions given are for
the purpose of guidance only. If at any point contradiction is observed, then SEM,
Railway Board/RDSO guidelines may be referred or prevalent Zonal Railways
instructions may be followed.
----------------------------------------------------------------------------------------------------
OUR OBJECTIVE
To upgrade Maintenance Technologies and Methodologies and achieve improvement in Productivity
and Performance of all Railway assets and manpower which inter-alia would cover Reliability,
Availability and Utilisation.
If you have any suggestion & any specific comments, please write to us:
Email : dirsntcamtech@gmail.com
Troubleshooting of
Eldyne AzLS
Single Section Digital Axle Counter
1.1 Introduction 1
Section I
Troubleshooting
Az LS
Eldyne Single Section Digital Axle Counter
1.1 Introduction
Troubleshooting in AzLS can be done with the help of LEDs provided on the Analog and
Evaluator/Digital cards of the Trackside Electronic Unit (EAK) which indicate the status
of the system. Diagnostics LED indications conforming to AzLS version V1.1 are given
in the following paragraphs.
Fig. 1.1 : LED indications on Analog card (As viewed from top)
1.3 Sequence of LED indications on Analog card with wheel movement over
Sk1 & Sk2
(i)
→ LED ON (Steady)
☼ ☼ → LED ON (Blinking)
Ο Ο → LED OFF (Blank)
Fig. 1.2(a) : Sequence of LED indications on Analog board with wheel movement over
Sk1 & Sk2
Section I: Troubleshooting Eldyne AzLS September 2013
(ii)
(iii)
(iv)
(v)
(vi)
Fig. 1.2(b) : Sequence of LED indications on Analog board with wheel movement over
Sk1 & Sk2
Section I: Troubleshooting Eldyne AzLS September 2013
(vii)
(viii)
(ix)
Fig. 1.2(c) : Sequence of LED indications on Analog board with wheel movement over
Sk1 & Sk2
^ Disturbance indicates an error in the system due to any problem in communication medium
and/or power. System is re-settable after rectifying the problem and without putting the power
off.
* Defect indicates an error in the system due to any problem in analog card and/or digital card
and/or motherboard. Power to be made OFF and then ON for resetting the system after
rectifying the problem.
→ LED ON (Steady)
☼ ☼ → LED ON (Blinking)
Ο Ο → LED OFF (Blank)
Fig.1.4 (ii) Pattern of lit LEDs on Digital Card during various stages of track section
If the AzLS system experiences frequent loss of telegram (due to fault in communication
media or power supply), the system performs a safe act by halting the CPUs on the
Digital Card. If the Digital card halts, the EAK is to be powered OFF and then ON to
make it functional.
To prevent the occurrence of Digital Card halt phenomena, the possibility of
electromagnetic induction in the communication media is to be reduced. Following
preventive measures are to be taken to arrest EMC/EMI problem and ensure trouble-free
operation of the system:
The cross pair conductors in quad cable (used for axle counter communication)
when exposed from the protective jacket of the quad cable, must be twisted to the
points of termination of the conductors.
Unused quad pairs inside location box must be earthed.
All cable segments to be earthed at one end only.
The ripple content of the power supply must be less than 20 mV AC.
A free wheeling diode (IN4007) must be connected across the coil of each Vital
and Reset relay.
LED indication Digital Card in halt state:
Go to index Go to Chapter index
2.1 Introduction 1
Section II
Troubleshooting
Az LM
Eldyne Multi Section Digital Axle Counter
2.1 Introduction
Troubleshooting in AzLM can be done with the help of LED indications provided on the
Analog and Evaluator/Digital cards of the Trackside Electronic Unit (EAK) as well as on
the front panel of boards in Axle Counter Evaluator (ACE). A Diagnostic Interface
Software is also provided as an additional tool which interrogates the system to determine
its status.
Note: The Sequence of LED indications on Analog Board with wheel movement over Sk1 &
Sk2 is same as that of AzLS.
1. Ethernet interface
2. Reset Button
3. LED 1…4
LED1: The flashing LED shows the communication
on the Ethernet interface.
LED2 & 3: Flashing LEDs show the communication
between the processors. In normal condition, both
LEDs flash.
LED4: Not used.
4. Alphanumeric display
The display shows a rotating bar if the CPU is
operational
5. Diagnostic interface
The serial interface socket to which the serial
interface of the diagnostic PC is connected.
The alphanumeric display on the CPU Card shows the following indications:
Start up:
Initially the display is illuminated for a short while, then the screen goes blank for a short
period. After that a ’_’ sign appers and stays for approximately 2.5 minutes. Then the normal
operation begins.
Axle counter application and diagnostic stopped: Standing bar in any orientation
LED 1 The flashing LED shows the communication on the Ethernet interface
LED 2 & 3 The flashing LEDs show the communication between the processors. In
normal operation both LEDs flash.
LED 4 Not used
The serial I/O interface consists of two independent ISDN transmission paths and one I/O
board is used for maximum two detection points.
LED ISDN-link channel 1
LED ISDN-link channel 2
• ON for link state “connected”(if the ISDN link to the associated
detection point is operational)
• otherwise OFF
LED ISDN-telegram channel 2
LED ISDN-telegram channel 1
• flashes while receiving an ISDN-telegram(if a valid ISDN telegram
was received from the associated detection point)
• otherwise OFF
●●
is OK working;
computer halted
Loss of
Detection Point
communication
computer not
between
working;
Detection Point
computer halted
and ACE
The element status indicates the momentary status of the following elements
Sections
Detection points
Interfaces
Computers
Software Versions
System diagnostics for AzLM can be done with the help of a PC loaded with diagnostic
software. The diagnostic PC must be a Pentium PC having a serial interface RS-232
(19200 bps) port with Windows operating system. The serial interface has to be
connected to the serial interface port on the CPU Card 1 of ACE by a Null-modem cable
having female DB9 connector at both ends. After running the diagnostic software, the
system data (viz. Elements current data and Historical data) can be downloaded and
analyzed on the PC.
The elements data includes status of section, detection point, interfaces, versions etc. The
status of elements is displayed on the PC screen in a coded message format with date &
time of occurrence.
Note:
The null-modem cable should always be kept connected at the CPU card end as well at
the diagnostic PC end. In case the null-modem cable needs to get disconnected, it should
be disconnected from both ends.
Diagnostic Messages
The following format of diagnostic messages is used in the history files and element data
files generated by the diagnostic tool.
Where
RNr - CPU number from where the diagnostic messages are read out.
Replica
0 - Message from all running CPUs
1 - Message from CPU1 (that is, CPU Card on left side of ACE subrack)
2 - Message from CPU2 (that is, CPU Card on right side of ACE subrack)
3 - Message from CPU1 and CPU2
Date/Time
Date and time of occurrence of diagnostic event.
Element Type
There are several element types, e.g., section, detection point, parallel I/O card, serial I/O
card etc.
Element Number
Each element has its own number (e.g., n = 1, 2, …) which is specified in the site specific
data. These element numbers are listed in the element window of the diagnostic tool together
with the names which are used in the layout plan.
Diagnostic Event
There are five types of diagnostic events, namely, operational name, site specific data, state,
version and axles.
Parameter
Information about different events.
Following is the example of display of a diagnostic message on the PC screen
Some coded messages and there interpretations useful for diagnostic purposes are given
below:
1. DP information WLP ZPR 1+0+1 Wheel pulse longer than 3 seconds detected at
DP n.
2. DP information VERSTAZI(1) Counting fault in DP n.
3. DP information STA 01 011 Self test of analog circuits failed in DP n
message received from SK1
4. DP information DRW AS11,1 Drift warning from DP n. CPU1 & 2 send a
GDI Menu
Save ACE data in the Diagnostic PC. The name of the data file should be as same as the
name of project site so that the data file can be easily identified later.
When an ACE is opened for the first time, it takes some time to get opened. Later the same
ACE can be opened much faster.
Left side CPU – connector for Right side CPU – connector for
serial interface of diagnostic PC Ethernet interface of diagnostic PC
Never connect the diagnostic PC to the serial interface as well as Ethernet interface in the
ACE at same time.
Never connect the diagnostic PC to more than one ACE at same time.
If the AzLM system experiences frequent loss of telegram (due to fault in communication
media or power supply), the system performs a safe act by halting the CPUs on the Digital
Card. If the Digital card halts, the EAK is to be powered OFF and then ON to make it
functional.
To prevent the occurrence of Digital Card halt phenomena, the possibility of electromagnetic
induction in the communication media is to be reduced. Following preventive measures are
to be taken to arrest EMC/EMI problem and ensure trouble-free operation of the system:
The cross pair conductors in quad cable (used for axle counter communication) when
exposed from the protective jacket of the quad cable, must be twisted to the points of
termination of the conductors.
Unused quad pairs inside location box must be earthed.
All cable segments to be earthed at one end only.
The ripple content of the power supply must be less than 20 mV AC.
A free wheeling diode (IN4007) must be connected across the coil of each Vital and
Reset relay.
Troubleshooting
of
Siemens Az S 350 U
Multi Section Digital Axle Counter
CAMTECH/S/PROJ/2013-14/HB- DAC(T)
September 2013
3.1 Introduction 1
Section III
Troubleshooting
Az S 350 U
SIEMENS MULTI SECTION DIGITAL AXLE COUNTER
3.1 Introduction
Az S 350 U consists of two main components:
Outdoor equipment
Indoor equipment
Power Supply
Following power supplies are required for functioning of the Axle Counter equipment:
5 V DC for internal operation
70 V DC for external operation of max. five counting heads
Fig. 3.2: (i) ZP 43 V Wheel Detection Equipment with Probe Adapter Board (ii) Front
panel of the Probe Adapter Board
Fig. 3.3 : Front view of Az S 350 U Evaluation computer (including slot numbers)
Transmitter frequency fs
Fault: Transmitter frequency is out of the tolerance range. Frequency
adjustment is not possible.
Cause of fault Measure
Generator defective Replace generator board
Lightning protection elements defective Replace lightning protection board
Frequency tuning board defective Replace mounting frame
Double wheel detector (transmitter) Replace double wheel detector
defective (transmitter)
The SVK2150 board is ready for operation when voltage is applied to the switching
input. This is indicated by the yellow LED "Vin". When the switch on the front panel is
set to "I", the yellow LEDs "5 V" and "70 V" ("12 V" is not used) indicate the presence
of the voltages.
In case of under-voltage, the output voltage is switched off. When the output voltage is
missing, the control-circuit fuse (fuse 0.2 A; fast) on the front panel blows. The unit
cannot go back into operation until this fuse has been replaced.
If there is no voltage at all, the input fuse on the printed circuit board (fuse 8 A; slow-
acting) has to be checked.
VAU board
Indication Description
VGL(Yellow LED) Comparator
SPW (Red LED) Voltage Controller
PAB (Red LED) Program-controlled shutdown
ANL (Red LED) Start-up
Red button System reset
Note
The meaning of LED 4
(reset restriction) is
only applicable to the
AzGrT mode. In the
vAzGrT mode LED 4
is permanently off.
If the fault could not be eliminated by means of an axle count reset operation by
the authorized person press the AzGrH button on one channel in order to activate
the statistics functions and record and evaluate the statistical data.
If the signal frequencies f1, f2 and the voltages V1, V2 are within the admissible
tolerance range, the cause of fault is most probably to be found in the evaluation
computer.
Before checking the outdoor equipment, check whether the fuse on the VESBA
board (0.2 A) in the evaluation computer is fault-free and if there is WDE supply
voltage present in the indoor equipment. The tests are carried out with the test
adapter board for ZP 43 WDE in conjunction with a multi-meter and by
comparison with the values given in the table on page. Faulty boards must be
replaced.
Only the boards of a failed computer channel may be replaced with spare boards.
It is not allowed to insert boards of intact computer channels into a faulty
computer channel. If a board of the evaluation computer has failed, the cause of
the fault may be the failure of a peripheral board.
If one of the LEDs is permanently on, there is probably a wheel at the position where the
wheel detector is mounted. If this is not the case, a fault can be assumed.
The LEDs light up if no counting head is connected or if the voltage supply for the
counting head is not present, interchanged or maladjusted (V < 1.3 V or counting head
connected incorrectly).
Approx. 60/70 V DC must be measured at the terminals for the counting heads. If no
voltage is measured, the fuses must be checked. The counting heads are protected via
fuse Si 1, which is mounted directly on the front panel, and another fuse on the printed
circuit board.
Fault: Yellow LED of the VESBA card is continuously lit (i.e. no wheel on the
detection point)
Procedure
Set the switch of the failed power supply board to "0".
Replace the fuse(s) if faulty, or replace the failed power supply board with a spare board.
Ensure that the power supply board is replaced with a board of the same type.
Set the switches of the power supply boards to "I".
On the front panel of the SVK2150 board, the LEDs "5 V" (computer supply voltage) and
"70 V" (WDE supply voltage) must be on.
Set the switch of the power supply board to "I" and check LEDs "5 V" and "70 V" again.
If the LEDs are still not on, also replace the remaining boards of the channel with spare
boards. If this is not successful, then notify the firm.
If LED "70 V" is not on:
Check the WDE cable (for short circuits).
Check the WDE connection (wrong polarity).
If power supply was faulty, continue maintenance work as described in Section 3.12
"Restarting an Evaluation Computer" on page 16.
The SVK2150 board is ready for operation when voltage is applied to the switching
input. This is indicated by the yellow LED "Vin". When the switch on the front panel is
set to "I", the yellow LEDs "5 V" and "70 V" ("12 V" is not used) indicate the presence
of the voltages.
In case of under-voltage, the output voltage is switched off. When the output voltage is
missing, the control-circuit fuse (fuse 0.2 A; fast) on the front panel blows. The unit
cannot go back into operation until this fuse has been replaced.
If there is no voltage at all, the input fuse on the printed circuit board (fuse 8 A; slow-
acting) has to be checked.
Fig. 3.9 : Front view of STEU board, display for emergency shutdown (TVDS 1 to 4)
A lit LED 4 or LED 10 of the STEU board indicates the RR for the TVDS affected.
Remedy - Restart the evaluation computer. (Refer section 3.12 on page 16).
Reset restriction
Depending on the configuration, the reset restriction is set according to different
parameters. There might be a reset restriction, if one of the following is true:
Pulse detection by a counting head belonging to the TVDS:
There is an axle on or oscillating over the double wheel detector.
The power supply of the counting heads is faulty.
The double wheel detector or double wheel detector cable connections are faulty.
Counting heads of the TVDS have been traversed within the last six seconds.
The last test of switching capability (internal software test – SOPP) of the data
channels on the VAU board has not been successful.
The axle last recorded by the evaluation computer in a track vacancy detection
section is an axle counted in.
Note
After AzGrH operation, the authorized person can, after verifying that track section is
clear actuate the AzGrT button for an axle count reset. No train movements should be
carried out during this operation.
3.10 Switching the Evaluation Computer On and Off
Switching ON
Restarting an evaluation computer means switching on all computer channels either
for the first time or after a fault.
Set the switches of the power supply boards to "I".
Simultaneously press the red buttons (system reset) on both VAU boards of both
computer channels for approx. 1 sec.
After pressing the red buttons (system reset), the LED "ANL" must light up on both
VAU boards for approx. 3 sec.
After the LED "ANL" on the VAU boards has gone off, the LED "VGL" will light
up.
During computer start-up, all LEDs 0 to 11 on the STEU boards light up for max. 10
sec. As soon as the LEDs change to normal display (see Section "Normal Display"),
the evaluation computer is operable (LED 0 shows steady light).
When an evaluation computer is restarted, it is guaranteed that all track vacancy
detection sections are first indicated as being "occupied" and displayed accordingly.
In accordance with the configured reset type (AzGrT or vAzGrT) and the railway
regulations the authorised person must then perform the axle count reset. No train
movement should be carried out during this procedure.
Switching OFF
The evaluation computer may only be switched off in consultation with the SM/
authorised person.
For switching OFF a computer for corrective maintenance or long-term shutdown
purposes:
Set the switch of the power supply board to "0".
In case of long-term computer shutdown, the supply voltage must be switched off. Do
not exceed the admissible out-of-service period as given in 4.8.1 on page 13.
Observe that
The LED "PAB" on the VAU board is on.
The LED "0" is flashing (emergency shutdown).
Note down the LED display (fault record) and interpret it for diagnostics.
Set the switches of all power supply boards to "0" (wait until all LEDs are off).
3.13 Special Board Replacement Conditions
Special Board replacement conditions must be observed while replacing boards.
The slot assignment and DIP switch positions of the BLEA12 board are different in the
Az S 350 U. The program revision level of the VAU board determines the special
conditions for the settings on the BLEA12 board.
Determine the program revision level of the VAU board by means of the Siemens code
number.
Depending on the program revision level of the VAU board, the slot assignment is given
in sections (A), (B) & (C).
When replacing the BLEA12 board, the DIP switch positions on switch bank 1 and
switch bank 12 must be checked. This refers to the BLEA12 board in slot 11 and the
BLEA12 board in slot 71 only.
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
ON ON Use the same DIP switch positions
OFF OFF
Set DIP switches 1 to 6 of switch bank 12 of the spare board as indicated in the table
below (Fig. on page shows switch bank 12 on the board).
Before switching on the evaluation computer, set the potentiometers (for V1, V2) as far
to the left as they will go.
After having replaced or moved the VESBA board to another slot, its proper operation
must be checked by carrying out or simulating a train movement over the counting heads
connected.
CAMTECH/S/PROJ/2013-14/HB- DAC(T)
SEPTEMBER 2013
4.1 Introduction 1
Go to Chapter index
Section IV
Troubleshooting
DACF 710 A & DACF 710 P
CEL SINGLE SECTION DIGITAL AXLE COUNTER
4.1 Introduction
The LED indications are provided on the facial plate i.e. on front side of different modules of
SSDAC viz. SCC cards, MLB Cards, Modem Card, Relay Driver, DC-DC Converter and
Event Logger to indicate OK or Error condition. These indications are helpful in the
troubleshooting of DACF 710A & 710 P SSDAC.
MLB Cards
Sr. No. LED Colour Information
1. 8 LED BLOCK All RED Normally OFF, ON when error appears
2. CLEAR GREEN ON for clear condition
3. OCCUPIED RED ON for occupied condition
Modem Card
Sr. No. LED Colour Information
1. Tx GREEN Transmitting the signal when LED is flashing.
2. RX GREEN Receiving the signal when LED is flashing
3. MODEM GREEN Normally OFF, Glows and again goes low when system is reset.
4. CD GREEN Carrier is detected when LED is flashing
Relay Driver
Sr. No. LED Colour Information
1. MLB 1 CLEAR GREEN ON when section clear, OFF when section occupied
2. MLB 1 CLOCK GREEN LED flashes when section is clear.
3. MLB 2 CLEAR GREEN ON when section clear, OFF when section occupied
4. MLB 2 CLOCK GREEN LED flashes when section is clear
5. RELAY DRIVE GREEN ON when section clear, OFF when section occupied.
DC-DC Converter
Sr. No. LED Colour Information
1. +5V RED ON when +5V supply available
2. +12V RED ON when +12V supply available
3. +24V RED ON when +24V supply available
4. +15V ISO RED ON when +15V ISO supply available
Event Logger
Sr. No. LED Colour Information
1. RUN GREEN Blinks continuously indicating normal working of Event
Logger Card
2. LOG GREEN Blinks whenever data is being logged into the flash memory
(approx. after every 2 minutes)
3. DNLD GREEN ON when data is being downloaded from the flash memory of
the card, OFF when download is complete.
24 V DC Supply (Battery)
Measure the DC 24 V input to the system with charger ON, charger OFF condition with all
the units connected (i.e. on load) or using dummy load.
Fig 5.2: Adjustment of Receiver coil with the help of dummy wheel
S.No. Parameter Measuring Limit (DC volts) Measured output (DC volts)
1. Clear mode >20 V
2. Occupied mode <2 V
The errors occurring in the system during the operation of the SSDAC are encoded and are
indicated by means of the 8 - LED block present on the front panel of the MLB cards. A
glowing LED implies a 1 while OFF LED indicates a 0. All the LEDs are numbered as given
below. DS1 to DS4 are designated for Least Significant Bits (LSB) and DS5 to DS8 are
designated for High Significant Bits (HSB). The value given to each LED is given in Fig. (b)
below:
Fig. 5.6: (a) Numbering of LED indications for errors (b) Values given to each LED
The Errors are given in Hexa decimal codes which can be read as given below:
Example
If LEDs 1 & 3 of LSB glow and LEDs 5 & 6 of HSB glow and all other LEDs are OFF. By
adding LSB+HSB LED values, (1 + 4) + (10 + 20) = 35. Thus error no. is 35.
2. SM s Key actuator
7. 9 pin D-sub connector is given on the motherboard of reset box which can be used for
downloading the data from flash for analysis purpose.
The reset box is connected in the Station master’s room and is used for applying the reset by
station master.
(ii) After the checksum, the reset box will wait for the user to apply the reset to SSDAC
system. The screen will display RESET THE SYSTEM .
(iii) The reset shall be applied as defined in the resetting procedure given below. On
pressing of Reset button and SM s Key, the PREPRESET indication will start
flashing. The remote unit also required to be reset. When reset is applied to both the
local and remote SSDAC units, the flashing PREP reset indication will become
Steady when the system attains the Preparatory state. At this point the LCD will
display the following message.
(iv) When Pilot train is moved in the section, the LCD will display the axle counts in
local DP on the Entry side Reset Box and in Remote DP on the Exit side Reset
Box as shown below. The section status is displayed as Preparatory state.
(v) When Pilot train is moved out of the section, The LCD displays the axle counts in
Remote DP on the Entry side reset Box and in Local DP on the exit side reset
Box. When the axle counts are matched, the section status is displayed as Clear
and Section CLEAR indication glows.
(vi) The axle counts are incremented or decremented according to the direction of
train movements. In case of failure, Error code is displayed at both the ends. The
Error code along with its description is displayed. This Error code is required to
be recorded by SM s before applying Reset.
(vii) On applying the reset, this Error code will get refreshed and is stored in flash. List
of 10 recent error codes are stored in Error log entry. This Error Log can be
viewed by maintainer at all times without the use of PC. By pressing reset button
for 10 secs, last 10 Errors will be displayed with Date and time one by one. After
the complete Error log, the LCD display will come back to its original state. This
Error log can be activated at any time but is recommended not to done during the
reset procedure.
(viii) One reset switch is provided on the interface card or motherboard which can be
used for resetting the display of LCD. This switch can be accessed by removing
the top cover of the reset box. This reset will not affect the status of the section
and be applied at any time but it is recommended to not to use it during the reset
operation.
(ix) In case the cable pair from location box to SSDAC unit is not provided, the
display information on the reset box will not appear.
For capturing the signals of SSDAC unit, Event Logger card is required to be plugged in the
SSDAC unit in the appropriate slot
a) COM port setting: Select COM port Settings from the drop down menu of card function
(use default setting for the selected Com Port as 19200, n, 8, 1).
Erase flash: To erase all 4096 pages of the flash memory, click on to “Erase flash” and then
click on to “Erase” button. “Flash erased” message will be displayed on the host computer
screen. Further writing of the flash memory will start from page number 0.Before erasing the
flash, time stamping is recommended.
Time stamping:
Click on to the “Time stamping” option.
Click on the “Select the current time”
Click on “Form packet”.
Click on “Send packet”, time packets are sent to the event logger card.
Show current time stamping: Once clicked on this option the system shows the current time
stamping. The date time will appear in the following format: {15:03:2005|12:27:00}
4.7.3Downloading data
Data from the Event Logger card is downloaded from flash memory of event logger.
Case 1: When flash page number is >0 and flash is not circulated, the controller generates a
message downloading buffer followed by page number of current page. Once the command
is executed, data is downloaded from the flash memory from page number 0 to the current
page number.
Case 2: When flash is circulated, the controller generates a message downloading buffer
followed by page number of current page. Here in this case data is downloaded from current
page to last page (4096) of the flash and then page number 0 to the current page number.
Go to card function.
Check the setting for 19200 bauds, parity none, data bits 8 and stop bit 1.
Forced download: In forced download; we get complete flash data from page 0 to page 4096
irrespective of restored page number and loop number. This is given to download data if
flash pointer is restored and one is interested for the old data. But this will always download
data from page 0 to page 4096.
4.7.4Data analysis
Run the Data Analyzer Application
Click on select data, then select file form the list or from the path where the files are saved.
Give name of station or station code. Station name / code should be at least 3 characters long.
Click on OK button. Then files will start getting created.
After creating the files message will appear “Files are created and now you can analyze the
data”.
The required time slots in “From” and “To” windows for which the analyzing is to be done
should be selected. After time zone selection, click on VIEW, The result menu comes on
having information regarding serial packets and Card removal information.
Current Report and Error Report for the selected *.dat file are ready to be viewed. The
current report can be exported in the Excel format by clicking on “Export to Excel” button. If
Microsoft Excel is not installed in the PC or Laptop, then the user can use the Print button to
print the report directly or the “Save Report button” to save the report in a text file.
Search feature is provided in data analyzer software to search and analyze the data on the
basis of time stamps or error codes.
Detailed help instructions are provided in the help menu of the software.
Section IV - Troubleshooting - DACF 710 A & DACF 710 P CEL SSADC September 2013
CAMTECH/S/PROJ/13-14/HB-DAC (T) 26
Section IV - Troubleshooting - DACF 710 A & DACF 710 P CEL SSADC September 2013
CAMTECH/S/PROJ/13-14/HB-DAC (T) 27
Section IV - Troubleshooting - DACF 710 A & DACF 710 P CEL SSADC September 2013
CAMTECH/S/PROJ/13-14/HB-DAC (T) 28
Note: In the wiring circuit of Reset Box contacts of PPR & VPR are not proved. Hence reset voltage is extended to system in
PPR or VPR pick up condition. Reset is however possible only in error or occupied state after registration of at least one
out count.
Section IV - Troubleshooting - DACF 710 A & DACF 710 P CEL SSADC September 2013
CAMTECH/S/PROJ/13-14/HB-DAC (T) 29
2. Reset applied (SM s key inserted, VPR PPR VR PR VPR PPR VR PR
reset button operation, etc)
3. System enters preparatory reset VPR PPR VR PR VPR PPR VR PR
mode
4(a) First train enters the section (Pilot VPR PPR VR PR VPR PPR VR PR
train)
4(b) First train clears the section (after VPR PPR VR PR VPR PPR VR PR
counts equal in both units
5(a) Subsequent trains when occupy VPR PPR VR PR VPR PPR VR PR
the section
5(b) Subsequent trains when clears VPR PPR VR PR VPR PPR VR PR
the section
Go to index
Section IV - Troubleshooting - DACF 710 A & DACF 710 P CEL SSADC September 2013
Section V
Troubleshooting
of
SSDAC-G36
G.G.Tronics Single Section Digital Axle Counter
5.1 Introduction 1
5.3 Configurations 1
5.7 Maintenance 3
5.8 Troubleshooting 5
Go to Chapter index
Section V
Troubleshooting of
SSDAC-G36
G.G.Tronics Single Section Digital Axle Counter
5.1 Introduction
SSDAC G36 manufactured by M/s G.G.Tronics India Pvt. Ltd., is a microcontroller
based system with 2 out of 2 architecture suited for proving station and block section.
5.3 Configurations
SSDAC-G36 units can be installed to work in the following configurations:
Fig. 3.4.:
Reset box
front view
Reset Push Button – This switch is meant for sending the reset command to the system.
For sending the reset command, both the SM Key and the reset push button are to be held
pressed simultaneously and momentarily.
Indications
One 10 mm Green and Red LED are provided for indicating status of block section.
One 5 mm green LED for indicating the status of preparatory reset. Flashing- when local
reset is applied. Steady - when reset is applied at the other end also & the system is
waiting for pilot train. OFF – when the section becomes clear.
One 5 mm Yellow LED for indicating the line verification status. Normally OFF; glows
only when line verification key is operated for executing direct reset.
One 5 m Yellow LED for indicating power ON condition.
Counter
One 6 digit non-resettable counter is provided which increments after each resetting
operation.
Display
One LCD display with 4 lines & 40 characters gives display of events, System Status,
Checksum and Version No, Counts and error code.
The reset box is connected to the system with one pair of quad cable for FSK
communication and 12 core signal cable for transfer of reset commands and reception of
the signals from the system.
The reset box required may be one per unit or two per unit depending upon the
configurations. Process of resetting required for a particular configuration also differs.
For example a single stationmaster or two separate stationmasters can do reset.
Table A -Fuses
Path FTB Point Rating Quantity
Input 24 V DC Power supply to system 1,2 6.3 Amps 2 Nos. on + limbs
Spare 5,6,7,8 6.3 Amps 4 Nos.
DC 24 V supply to Relay Box 11,12,13,14 6.3 Amps 4 Nos.
Connection from System to Relay box 15 to 22 2 Amps 8 Nos.
Connection to VPR & PPR relays in 23,24,25,26 2 Amps 4 Nos.
Relay room
Quad cable to system 27,28 2 Amps 2 Nos.
To reset box in the station 35,36,43,44 2 Amps 4 Nos.
Tx/Rx coil connections 51 to 58 2 Amps 8 Nos.
5.7 Maintenance
Adjustments required in the field
The adjustment has to be done after measuring the voltages at monitoring points provided on
different modules, tabulated in the Table C.
Relay Drive
PD
5.8 Troubleshooting
For ease of maintenance in the field messages are provided in the Display Module
both during healthy and Error conditions
About 61 possible conditions have been identified which drives the system into Error
mode.
The errors are displayed in plain English on the Display Module
Many Error Messages are displayed that suggest faulty module to take immediate
corrective action by the service personnel. Detail report can be downloaded from
Event Logger card for analysis and the corrective action to be taken
Troubleshooting chart
Error Errors Analysis Corrective measure
Code on
display of
CPU
1 PD1_BOARD_MISSING Error occurred due to Place the PD1 module
missing of the Phase in the slot and reset the
detector 1 module (PD1- system
21KHz) during run time
and boot time diagnosis
2 PD2_BOARD_MISSING Error occurred due to Place the PD1 module
missing of the Phase in the slot and reset the
detector 2 module (PD2- system
25KHz) during run time
and boot time diagnosis.
3 SM_CPU_MISSING Error occurred due to Place the SM-CPU
missing of the SM-CPU module in the slot and
module during run time reset the system
and boot time diagnosis.
4 MODEM_MODULE_A_MISSING Error occurred due to Place the
Go to Chapter index
ANNEXURE I
ABBREVIATIONS
Section I :Az LS Eldyne SSDAC
AC Alternating Current
AzLM Thales Multi Section Digital Axle Counter
AzLS Thales Single Section Digital Axle Counter
DC Direct Current
DIP Dual in line Packeged
DP Detection Point
EAK Tack side Electronic Unit
ETU001 Test equipment (Tool Kit)
Hz Hertz
LED Light Emitting Diode
MESSAB1 Rx voltage for SK1
MESSAB2 Rx voltage for SK2
PCB Printed circuit Board
PEGUE1 Reference voltage for SK1
PEGUE2 Reference voltage for SK2
RMS Root Mean Square
Rx Reciever
Sk1, Sk2 Tx /Rx coil sets
SK30H Rail contacts
Tx Transmitter
Zp30CA-2. Detection points
VR Vital Relay
AH Ampere Hour
CF Centre Fed
CPU Central Processing Unit
CFVR Vital Relay for Centre Fed
DC Direct Current
2DP1S Two detection points Single section
3DP1S Three detection points Single section
3DP2S Three-detection points for two consecutive sections in a straight line
EF End Fed
EFVR Vital Relay for End Fed
FSK Frequency Shift Keying
FTB Fused Terminal Blocks
GND Ground
Hz Hertz
KHz Kilo Hertz
LCD Liquid Crystal Diode
LDU Lightning Detector Unit
LED Light Emitting Diode
MS Mild Steel
PD Phase Detector
PPR Repeater relay for Preparatory Relay
PR Preparatory Relay
QNA1 Style Q AC immunized relay
RDSO Research Design & Standards Organisation
Rx Receiver
SF Start Fed
SFVR Vital Relay for Start Fed
SM Station master
SSDAC Single Section Digital Axle Counter
Tx Transmitter
VPR Repeater relay for Vital Relay
VR Vital Relay
ANNEXURE II
REFERENCES
Installation Manuals - Single section Digital Axle Counter DACF -710 A &
DACF 710 P – M/s Central Electronics Ltd.
For quick remedy of faults in any equipment, troubleshooting procedures must be well
defined based on the symptoms during the failure. Digital Axle Counters are
microcontroller and software based systems, hence sometimes the faults cannot be seen
physically unlike in some signaling gears such as signals, track circuits, points etc. As we
all know that failures can be avoided upto a great extent by doing preventive
maintenance, but still the faults are sometimes unavoidable hence troubleshooting
methods should be effective.
There may be a large number of possible faults in each type of Digital Axle Counter
system. Troubleshooting can be done by following methods according to the nature of
failure:
The subsequent sections of this handbook cover the information on Digital Axle Counters
of different RDSO approved manufacturers which shall be useful in diagnostics and
troubleshooting.
Go to Index