Académique Documents
Professionnel Documents
Culture Documents
SYNOPSIS
A comparison is made of the seismic design provisions for
reinforced concrete beam-column joints required by the new New
Zealand concrete design code NZS 3101 and recently proposed United
States procedures. Large differences are shown to exist between
these new provisions of the two countries. Results are reported
of cyclic load tests which were conducted according to the require-
ments of the new NZS 3101. The test results showed that location
of plastic hinges in beams away from the column faces may be of
considerable advantage in the design of joints, when member sizes are
small and joint shears are high, due to less congestion of rein-
forcement and better anchorage conditions.
3h (A. provided)
jh = h (1) c 3v
(5a)
v
b j c
4 h ( A j required)
b v
A. V /f (7)
where the horizontal design shear force sv' y
3V
to be resisted by this shear reinforce-
ment is given by where the vertical design shear force
to be resisted by this shear reinforcement
V , = V. - V . (3) is
sh 3h ch u v
'
V = V. - V (8)
sv jv cv
In Eq. 3, ch should be taken as
zero unless one of the following situations In Eq. 8, V is given by
applies:
(9)
V +
200 mm and in no case should there be d,b <— h,b /2 5 when f = 3 80 MPa.
less than one intermediate bar in each y
side of the column in that plane. When columns are not intended to develop
plastic hinges:
(iv) Confinement
d
b 1 h /15 when
b f y = 275 MPa, or
The horizontal transverse confinement
reinforcement in the joint core should d,D <— h£>/20 when
u fy = 380 MPa.
not be less than that required in the
potential plastic hinge regions in the (vi) Bar Anchorage at Exterior Joints
adj acent columns. Thus for columns
with hoops and supplementary cross ties The basic development length of a
the total area of transverse steel in deformed bar in tension terminating with
each of the principal directions of the a standard 90° hook is
cross section should be at least equal
to 66d, f
b _y_ (14)
*hb 275
A s h « 0.3s h«
h -2-1
c Yh
(11) *db =
°- 2 4 d
b y f / / F
i ( 1 5 )
However if the joint has beams fram- but not less than 0.044d f . b y (15a)
ing into all four column faces and is
designed using the conditions applicable Where the concrete is suitably confined
for Eq. 5, the transverse reinforcement the value may be reduced to 0. 7 5 £ ,. .
in the joint core may be reduced to one-half
of that required by Eqs 10 and 11. db
The anchorage is considered to
s
— <j'>Y /Fb
r
c c hc
but not less than 8d. or 150 mm, which-
where <f> is the strength reduction b
factor for shear taken as 0.85, and b ever is greater. Bar diameters should
and h are the gross width and c
not exceed 35 mm and hooks should be
c
thickness of the column, respectively. situated in the column core located as
far from the critical section as possible.
However, the value for b in Eq. 16 If the confinement steel spacing does
c not exceed 3db' *dh may be reduced by
should not be taken as greater than 20%. The anchorage is considered to
twice the width of the beam framing into commence at the edge of the concrete core.
the joint. The value for f'
used in Eq. 16 should not be taken as Comparison of the NZS 3101 and the Draft
larger than 34 MPa. The value of y ASCE-ACI Committee 352 Approaches
depends on the joint configuration and
is 1.33 for an interior joint, 1.00 The main differences I
for an exterior joint, and 0.67 for other
joints. To be classified as an There are large differences in the
interior joint, members must frame into approaches to joint core shear design
all four sides of the joint and cover at adopted in NZS 3101 and in the draft
least three-quarters of the width and ASCE-ACI Committee 3 52 procedures.
depth of the joint face. To be classified
as an exterior joint, members must frame
into three sides of the joint and the The NZS 3101 requirements are based
width and total depth of the beams on on a rational model for the mechanisms
opposite faces of the joint must not of shear resistance of the joint core,
vary by more than 25%. namely a mechanism consisting of a concrete
diagonal strut and a mechanism consisting
(iii) Vertical Joint Shear of truss action of a concrete diagonal
compression field and shear reinforcement.
No calculation procedure is Account is taken of the reduced capacity
recommended to check resistance for of the diagonal compression strut mech-
vertical joint shear forces. anism, particularly in interior joints,
when plastic hinging forms adjacent to
(iv) Confinement the core faces and results in full depth
flexural cracking there during reversed
Where rectangular hoop and cross tie loading. Increased concrete shear
transverse reinforcement is used, the capacity and less severe bond and anchorage
total area of a single or overlapping criteria are permitted if plastic hinging
hoops, or hoops with cross ties of the is forced to occur away from the joint
same size, in each direction should be core faces. Both horizontal and vertical
at least equal to shear reinforcement are designed to carry
that shear in excess of the concrete
s, h"f' A capacity.
= 0.3 -5 £ (17)
A
S h f
yh A The draft ASCE-ACI Committee 352
c approach assumes that providing the design
but not less than horizontal shear force on the joint core
does not exceed a quantity
A = 0.09
S
h " c
h £
(18)
sh
yh <by/lH~h h , the amount of transverse
f
c c c
For interior joints, the required reinforcement required for column
transverse steel can be one-half of that confinement, reduced by one half in those
required by Eqs. 17 and 18. The hoop cases where the joint is adequately
spacing s^ should not exceed one quarter confined by structural members on all
four faces, will also be adequate for
7
shear resistance in the joint core. That If P /f"A = 0.1, from Eq. 4 V . = 0
is, once the size and spacing of transverse e c g ch
reinforcement in the potential plastic Design joint horizontal shear force,
hinge regions in the ends of the column from Eqs. 2, 3 and 4 and assuming
have been established, that quantity that
or one half is continued through the
joint core. This approach has been A , h. /s, ,
adopted evidently because Meinheit and sh b' h'
Jirsa (8) have concluded that shear
strength of joint cores was not as V A f. A , f , h, /s,
sh jh yh sh yh b h /
demand.
C. 0.5, from Eq. 5
3
The anchorage requirements of the
draft ASCE-ACI Committee 352 approach V
ch = ° - 5 V
j h ( 1 +
°' 0?4°' '
5 1
= ° - " 6 V j h
yh c
Say f' 25 MPa and h./h = 1, then
.*. A , f ,/s, = 0.0405b f f
b c
V., = 0.463/f b h T
sh yh h c c (I)
jh c c c
Also from Eq. 16, the shear strength
of the joint core is But from Eq. ii, draft ASCE-ACI
approach would allow V., = l.lS/f^b h
V = 0.85 x 1.33/f b h T
jh c c c
allowed
u c c c
which is 2.4 times the V jh
= 1.13/Fb h /' '\ by NZS 3101.
C C C (ll) Note: For higher axial load levels
That is, the amount of joint shear than 0.1 f A , more shear will be 1
satisfy the horizontal joint shear NZS 3101 approach than in the above
force imposed in Eq. ii. example and the difference between
the two approaches would be reduced.
NZS 3101 Approach
(2) Comparison of a corner joint.
(a) For plastic hinge forming adjacent
to joint core: Draft ASCE-ACI Approach
8
sh yh n
A f 0.081b f' (i.e. twice that for
/ S
under simulated seismic loading to compare
c c
the interior joint) the performance resulting from the different
design approaches.
V = 0.85 x 0.67/f'b h = 0.57 /f »b h
u c c c c c c The overall dimensions of the units are
shown in Fig. 1. The size of the cross
NZS 3101 Approach sections may be taken as being represent-
ative of about h to *|- of that of full scale
(a) For plastic hinges forming adjacent
to joint core without a beam stub. members of a multistorey building frame.
The units can be regarded as being that
If P /f'A o.i, A; part of the joint regions of a plane frame
e c g between the midspan of the beams and the
C. = 0.5 h = h, , midheight of the columns. The columns
3
f
c b of the units were designed to be stronger
and A. provided = A. required, than the beams so that during severe
jv jv ' n
which is 0.81 times the V.. allowed The concrete was from Ordinary
by NZS 3101. j n
TEST PROGRAMME:
COLUMN
UNITS 1&2
Loading of Units 1 and 2
^ 4 5 7
, 229
UNIT 3
V
t
1
L o a d i n g of Units 3 and U
Bending
2667 SECTION A-A
Moment
UNIT 4
All dimensions in milti metres. Diagram
500mm for Beam
Fig. 1 Dimensions of the Test Units
Conventional Design
Reinforcement is provided so
that r e q u i r e d M is a c h i e v e d
u
w i t h c r i t i c a l plastic h i n g e
00 s e c t i o n at A.
00
:40(H Relocated Plastic Hinge D e s i g n :
Reinforcement is p r o v i d e d so
that r e q u i r e d M is a c h i e v e d
u
30CH
D16(Grade 275)
x
w i t h c r i t i c a l plastic hinge
D20(Grade 275)
R12 (Grade 275)
S s e c t i o n at B and so t h a t
20CH yielding at A c a n n o t o c c u r
u n l e s s the moment at B
reaches i t s overstrength value.
100H
Table 2 :
Grade of Bar Grade 2 75 Grade 380
Properties of
Steel Bar designation RIO R12 R16 D16 D20 D24 D20 D2 4
Reinforcement Measured f^ (or
f , ) MPa 321 286 320 315 307 303 485 473
yh
Measured f , MPa 437 414 468 463 458 453 784 767
u
relatively high steel content led to The design was such that yielding of the
considerable congestion of shear beam flexural reinforcement at the column
reinforcement in the joint core, as face was not expected unless a moment of
shown in Fig. 4. 1.20 times the theoretical flexural strength
based on the measured f and f values 1
core shear forces were similar for the flexural strengths above and below
two units. The ratios of longitudinal the joint to the beam theoretical flexural
steel for the beams at the critical sections strength calculated using the measured
500 mm from the column faces were p = p =
1
material strengths were 1.78 and 1.75,
1.32% and at the column face were p - p ' = respectively. The relatively high
2.04%. The design was such that yielding flexural strengths of the columns was
of the beam flexural reinforcement at the partly due to the high measured yield
column faces was not expected unless a strength of the Grade 380 steel in the
moment of 1.16 times the theoretical columns.
flexural strength, based on the measured
The required shear strength of the
f and f' values, was reached at the joint cores, V . - ^ and V \ , required, tj
y c
calculated from the forces acting on the
critical sections 500 mm from the joint, are shown in Table 3 for units
column face. Units 1 and 2 can be
regarded as alternative solutions to the 1, 2, 3 and 4 and also for a unit SI of a
same design problem. previous test ( 9 ) . The ratios of
V
jh ^c //y a r e
i the table,
a l s o s n o w n n
2667 330
/16-D16x
1 /•
if)
rsi o
CO R10
1 stirrups
.1. -1
161 161
R10 ties
SECTION 1 SECTION 2
44 3'a) 51
SECTION 3
Notes > (All units) 229
( 1} Unit is symmetrical about centrelines SECTION 4
(2) Cover = 30mm to all main bars UNIT 1
v
Ft 1 2 5
! 1 2 5
! 11-R1Q ® 89 crs 1178 | 7-R10 'a) 178 crs h00 4~V0
(4 legs)
J3l
500
f | ^ ^ / 1 2 - D 2 0 bars
Note
UNIT 2 /R10 stirrups Column as for Unit 1
(4 legs on first
11 sets)
iky
SECTION 1
ii) V., . h / h
jh b c
iii) v., = V., /b .h
jh jh j c
iv) V , and V prov'd are calculated using the measured f.
sh sv ^ yh
o R10
E i-stirrups
4 (4tegson first
11 sets.)
30 8-D24 bars
cover
160 Note :-
UNIT 3 Beam and Column
transverse steel
R10 as for Unit 1
stirrups
2-HD204-HD16
bars bars
300
8-D2£ b a r s 4-D24 b a r s
WW
16 18
Displacement Ductility 3 3 2-2 2-2 4-4 4 -4 6-6 6-6 8-8 8-8 8-8 > -
Factor, y & -
4 4 to tr
> cu d)
Measured Percentage Unit 1 9 12 7 10 9 6 11 5 8 10 35 32 36 u in
of Total Deflection Unit 2 18 21 15 15 18 16 12 12 17 20 32 66 59 73 64 o -P
of Beam Ends clue to Unit 3 11 18 8 15 16 23 8 13 8 14 5 8 10 16 12 18 23 30 35 43 ro CD
Joint Core Shear Unit 4 9 6 9 6 10 8 7 7 10 10 11 21 35 51 70 cn
O
u
Deformation N <D
£ Oi
"As shown on the beam end load-deflection curves in Figs. 9a, 10a, 11a and 12a.
80 -
150 200
DEFLECTION (mm)
Ff = 76.2
i 1 1
LOAD RUN NQ -
©CD ® ® @ |,YIELD
I UNIT 11
^ r, YiEL
^ N N L Estimated
0 400 800 1200 1600 2000 0 400 800 1200 1600 2000
MiCROSTRAIN
(c) Strains in Joint Core Hoops
MICROSTRAIN MICROSTRAIN
LOAD RUNS 1 TO 8, JOINT ELASTIC LOAD RUNS 9 TO END, JOINT INELASTIC
indeed carried during the first load cycle to the NZS 3101 approach, the quantity
to y = 6. Yielding of joint core hoops of joint core hoop steel required is
had commenced in the first cycle to y = 4 that necessary to carry the shear actually
(see Fig. 12c) but this did not cause present (Eqs. 2 to 5) but should not be
a marked decrease in the shear strength less than that required for confinement
or stiffness of the joint core, as is (Eqs. 10 and 11). The A /s, values
shown in Table 4. calculated for the four s
units
using these two approaches are shown in
The strains measured along the Table 5; also tabulated is the A ,/s,
longitudinal bars shown in Fig. 12b ' sh h /
indicated that initially the beam underwent actually provided for each unit. Note
plastic rotations in the designed plastic that the quantity actually provided in
hinge region, but in the later stages unit 3 satisfied the NZS 3101 requirement
of the test yielding of longitudinal for shear but was 76% of the NZS 3101
steel penetrated along the beam to the requirement for confinement. In all other
column face and into the joint core cases NZS 3101 was satisfied.
resulting in plastic rotation occurring
over a greater region. No slip of It is of interest to note that
beam bars was noticeable. This yield according to the draft ASCE-ACI approach
penetration occurred because strain the horizontal shear force on the joint
hardening of the beam reinforcing at the cores should not exceed the value given
design plastic hinge region 500 mm from by Eq. 16, namely V = 1.0 x 0.67/34 x 305 x
the face raised the flexural capacity there 406N = 484 kN for all units, whereas accord-
sufficiently to cause yielding in the ing to NZS 3101 the horizontal shear
beam at the column face as well. Sliding strength of the joint cores as reinforced
shear deformation was noticeable at the was 1030, 997, 543 and 625 kN for units 1,
designed critical section in the later 2, 3 and 4, respectively, assuming a
stages of testing, but this was not strength reduction factor of unity for both
serious since at the theoretical strength approaches. Thus the four test units
of the unit the nominal shear stress in reinforced according to NZS 3101 were able
the beam was only 0.15/F^ MPa. Damage to sustain much greater horizontal joint
core shears than permitted by the draft
to the unit visible during testing is ASCE-ACI recommendations. Note also
illustrated in Fig. 13. that units 1 and 2 contained more hoops
that required by the ASCE-ACI approach
Comparison of NZS 3101 and the Draft but units 3 and 4 contained less hoops than
ASCE-ACI Committee 3 52 Design Recommendations required by the ASCE-ACI approach.
for the Joint Cores of the Units
These considerable differences between
The measured percentage of the the two design approaches arise because
horizontal shear force in the joint core in the draft ASCE-ACI method no consideration
carried by the joint core hoops (V^/V..^) is given to the mechanisms of shear resist-
in the first loading cycle to y = 6 ance in the joint core. Thus the draft
shown in Table 1 compared very well with ASCE-ACI approach may be conservative in
the values of 100, 37, 37 and 38% some cases and unconservative in others,
recommended by NZS 3101 for units 1, 2, 3 depending on the particular joint conditions.
and 4, respectively, for the column axial
load level of O.lf'A applied in these Table 5 : Comparison of Quantity of Joint
eg Core Hoops Required for Shear and
tests. It is of interest also to recall Confinement by NZS 3101 and Draft
the result from the previously tested unit ASCE-ACI Committee 352 Recommend-
SI (9), which was an interior beam-column ations, and Quantity Actually
joint with a column axial load level of Provided, A . /s, mm /mm.
0.24f'A and with plastic hinging occurring sh h
in the beams at the column faces. As
Table 3 shows, unit SI had only 6 8% of the
horizontal joint core shear reinforcement Unit 1 2 3 4
required by NZS 3101. In that test the
beams did not reach their theoretical
flexural strength and shear failure occur- Draft ASCE-ACI Require-
red in the joint core which resulted in ments for Confinement
the strength of the unit falling to 61% and Shear 3.22 3.97 2. 84 2. 89
of the theoretical strength based on
beam moment capacity after two load
cycles to y = 2, two load cycles to NZS 3101 Requirements:
u = 4 and one load cycle to y = 6.
f
For Confinement 2.68 3. 31 2. 37 2.41
Hence the NZS 420 3 criterion for adequate For Shear 10.5 4.48 1. 83 2.4 8
ductility was not met by unit SI.
Notes cont' d. . .
(iii) Horizontal shear strength according improved bond conditions meant that the
to the NZS 3101 requirements (Eqs. diameter of longitudinal beam bars could
2 to 5) for the joints as actually be 25% greater than in unit 6. Also,
reinforced were 1030, 99 7, 543 and because the joint core was considered to
625 kN for units 1, 2, 3 and 4, remain in the elastic range the concrete
respectively. diagonal compression strut mechanism could
be considered to carry significant shear
CONCLUSIONS: and only 37% of the horizontal shear in
the joint core needed to be allocated to
1. The recent draft recommendations for the hoops.
the design of reinforced concrete beam-
column joints of ASCE-ACI Committee 352 5. Unit 3 was an exterior beam-column
show large differences from the approach joint with the critical plastic hinge
used in NZS 3101. The NZS 3101 approach section in the beam designed to be located
for joint core shear strength is based at the column face and with the beam bars
on a rational model which sums the shear anchored in a beam stub at the far face
carried by the concrete diagonal compress- of the column. In exterior joints, even
ion strut and the shear carried by truss when plastic hinging occurs in the beam
action of the shear reinforcement. The at the column face, the concrete diagonal
draft ASCE-ACI approach assumes that compression strut mechanism can be
providing the horizontal shear stress in preserved quite well during cyclic loading,
the joint core does not exceed a limiting evidently because a steeper diagonal
value the amount of transverse steel strut can form between the bend in the
required for column confinement is beam tension steel at the far face of the
satisfactory, and vertical shear is column and the column ties at the near
considered by the requirement of at least face just outside the joint core. As
an eight bar column. In the opinion of a result, only 37% of the joint core
the authors, the design of joint core horizontal shear needed to be allocated
hoop reinforcement on the basis of the to the hoops. The penetration of steel
quantity of transverse steel required to yield along the beam bars into the joint
confine the ends of columns is ilJbgical core demonstrated that requiring the
and cannot produce any degree of accuracy anchorage to commence within the joint
because it does not take into account core as specified by NZS 3101 was
the possible varying conditions for shear reasonable. This anchorage requirement
in joint cores. This is especially had meant that to provide sufficient
the case when the wide range of joint anchorage length for the beam bars a
types and column axial loads used in stub was required at the far face of the
design in practice is considered. column because of the relatively small
Recognition of the different concrete column depth.
diagonal compression strut mechanisms
existing in interior and exterior joints 6. Unit 4 was an exterior beam-column
also appears necessary. joint with the critical plastic hinge
section in the beam designed to be located
2. The four reinforced concrete beam- 500 mm away from the column face. This
column joint units 1, 2, 3 and 4 which design permitted anchorage of the beam
had been designed according to the bars within the column core, because
requirements of NZS 3101 were shown by the beam steel was designed not to yield
tests under simulated seismic loading at the column face, and therefore anchorage
to satisfy the approximate criterion could be considered to commence at the
for adequate ductility of NZS 420 3. column face of entry. Hence an anchorage
It was apparent that the detailing stub was not needed. Because the joint
requirements of NZS 3101 for joint core core was designed to remain in the elastic
design were not overly conservative for range only 3 8% of the joint core shear
these designs. needed to be allocated to the hoops.
yield there, should lead to satisfactory 5. ACI Committee 318, "Building Code
design. The overstrength factor used in Requirements for Reinforced Concrete
the design of the interior beam-column (ACI 318-77)", American Concrete
joint unit 2 was 1.16 and for the exterior Institute, Detroit, 1977, 102p.
beam-column joint unit 4 was 1.20. In
both of these units during the tests, 6. ASCE-ACI Committee 352, "Recommend-
strain hardening of the longitudinal ations for Design of Beam-Column
reinforcing at the relocated plastic Joints in Monolithic Reinforced
hinge raised the flexural capacity there Concrete Structures", Journal of
sufficiently to cause yield of longitudinal American Concrete Institute,
steel to spread along the beam to the Proceedings Vol. 73, No. 7, July
column face and to penetrate into the 1976, pp. 375-393.
joint core, leading eventually to yield of
the joint core hoops. Hence use of 7. ASCE-ACI Committee 352, Revised
an overstrength factor of less than 1.25 Recommendations with Commentary,
for Grade 275 reinforcement would be June 1982. (In draft form
inadvisable. and unpublished).
10. In general, the use of relocated 8. Meinheit, D.F. and Jirsa, J.0., "The
plastic hinges, as employed in units 2 Shear Strength of Reinforced Concrete
and 4 seems to be a practical design Beam-Column Joints", CESRL Report
alternative to conventional design. No. 77.1, University of Texas, Austin,
Note however that if the ratio of gravity January 1977. (See also Journal
load to seismic load induced moment is of the Structural Division, ASCE,
high the moment gradient may not allow the Vol. 107, No. ST11, November 1982 ,
use of such a design because only a pp. 2227-2244).
short length of beam will have negative
moment. Also, the use of relocated 9. Park, R., Gaerty, L. and Stevenson,E.C.
plastic hinges will impose a higher "Tests on an Interior Reinforced
curvature ductility demand on those Concrete Beam-Column Joint", Bulletin
plastic hinge sections, because the smaller of New Zealand National Society for
length of beam between the critical Earthquake Engineering, Vol. 14, No. 2
positive and negative moment sections June 1981, pp. 81-92.
will mean that greater plastic hinge
rotations are required at these sections 10. New Zealand Standard Code of Practice
to achieve the required displacement for General Structural Design and
ductility factor. This increased Design Loadings for Buildings, NZS
curvature ductility demand should not 4203:1976, Standards Association of
be of concern except for beams with short New Zealand, Wellington, 1976.
spans.
11. Paulay, T. and Scarpas, A., "The
ACKNOWLEDGEMENTS Behaviour of Exterior Beam-Column
Joints", Bulletin of the New Zealand
The tests were conducted by J.R. National Society for Earthquake
Milburn during Master of Engineering Engineering, Vol. 14, No. 3, September
studies under the supervision of R. Park. 1981, pp. 131-144.
The experimental work was made possible
by financial assistance provided by the NOTATION
Ministry of Works and Development which
is gratefully acknowledge. Mr G.H.F. (All units are mm and N)
McKenzie, Chief Structural Engineer,
MWD, is thanked for his interest and = area of concrete core section
support. measured t© outside of peripheral
hoop.
REFERENCES
Ag = gross area of section
1. New Zealand Standard Code of Practice
for the Design of Concrete Structures, total area of effective horizontal
NZS 3101 Parts 1 & 2 : 1982, joint shear reinforcement
Standards Association of New Zealand,
Wellington, 1982. total area of effective vertical
V joint shear reinforcement
2. Milburn, J.R. and Park, R.,
"Behaviour of Reinforced Concrete total area of tension beam
Beam-Column Joints Designed to reinforcement
NZS 3101", Research Report 82-7,
Department of Civil Engineering, total area of compression beam
University of Canterbury, New reinforcement
Zealand, February 1982, 107p.
area of tension reinforcement in
3. Park, R. and Paulay, T., "Reinforced one face of the column section
Concrete Structures", John Wiley
and Sons, New York, 1975, 769p. A' area of compression reinforcement
sc in one face of the column section
4. Paulay, T., Park, R, and Priestley,
M.J.N., "Reinforced Concrete Beam- total effective area of hoop
Column Joints Under Seismic Actions", sh bars and supplementary cross ties
Journal of American Concrete in direction under consideration
Institute, Proceedings Vol. 75, within spacing s.
No. 11, November 1978, pp. 585-593.
overall width of column V" u = total horizontal shear force
across joint
effective width of joint
Y = joint shear strength factor
web width of column
p = ratio of longitudinal tension
participation factor = V \ / ( j
h
V
x
+ V
j )
z reinforcement = A /bd where
b and d are beam width and
bar diameter effective depth, respectively
compressive cylinder strength of pi = ratio of longitudinal.compression
concrete reinforcement = A'/bd where
s
yield strength of longitudinal b and d are beam width and
reinforcement effective depth, respectively