VICINITY MAP
4

Manatee County, Florida


5

SHEET NO.
INDEX

FILENAME: Filename
Flow Meter Replacement
Cortez Road Injection Well

OF
6

DESCRIPTION
DRAWINGS

PLOT DATE: $PLOTDATE

4350 WEST CYPRESS ST SUITE 600


DWG
PROJ
DATE

TAMPA, FLORIDA 33607-4155


SHEET
0

LB 0002934 AA C000656

CIVIL MANATEE COUNTY


N.T.S.

CORTEZ ROAD INJECTION WELL


VERIFY SCALE

FLOW METER REPLACEMENT


ORIGINAL DRAWING.
BAR IS ONE INCH ON

1 of

NO. DATE REVISION BY APVD


1"

COVER SHEET MANATEE COUNTY, FLORIDA DSGN DR CHK APVD JOSEPH C. GOLDBACH
6
PLOT TIME: $PLOTTIME
704019
JANUARY 2019

C1

J. GOLDBACH B. KLEIN J.GOLDBACH A. LEWIS FL P.E. No. 22385


REUSE OF DOCUMENTS: THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF c JACOBS 2018. ALL RIGHTS RESERVED.
CONSTRUCTION DRAWING SET JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
1 2 3 4 5 6

JOSEPH C. GOLDBACH
GENERAL CONSTRUCTION NOTES

c JACOBS 2018. ALL RIGHTS RESERVED.


FL P.E. No. 22385
1. DETAILING AND DIMENSIONS OF EXISTING PIPING AND STRUCTURES IS BASED ON BEST CONSTRUCTION SEQUENCE REQUIREMENTS:
INFORMATION AVAILABLE AND DO NOT NECESSARILY REPRESENT THE AS-CONSTRUCTED 1. CONNECTION OF NEW PIPING TO EXISTING PIPING WILL REQUIRE INJECTION WELL TO BE SHUT
CONDITIONS. THE CONTRACTOR SHALL FIELD VERIFY DIMENSIONS AND DETAILING OF EXISTING DOWN.
PIPING AND STRUCTURES PRIOR TO SUBMITTING SHOP DRAWINGS.
2. CONTRACTOR SHALL SCHEDULE 4 WEEKS IN ADVANCE WITH MANATEE COUNTY UTILITIES AN
2. CONTRACTOR SHALL TAKE ALL MEASURES NECESSARY TO POSITIVELY PRECLUDE EROSION OR ACCEPTABLE TIME WHEN INJECTION WELL CAN BE SHUT DOWN AND WHEN MANATEE COUNTY
WASHING OF SEDIMENT FROM SITE.THE CONTRACTOR SHALL PROVIDE PERIODIC MAINTENANCE WILL HAVE SUFFICIENT POND STORAGE CAPACITY AVAILABLE (TYPICALLY DURING PERIODS OF
OF ALL EROSION AND SEDIMENTATION CONTROL DEVICES INSTALLED AND SHALL CLEAN-UP DRY WEATHER).
AND RESTORE ALL AREAS IMPACTED BY EROSION CONTROL ACTIVITIES AS THE WORK
PROCEEDS 3. CONTRACTOR SHALL PLAN WORK TO LIMIT TIME THAT INJECTION WELL IS SHUT DOWN TO BE NO
LONGER THAN FIVE (5) DAYS. OPERATION OF WELL REQUIRES THAT FLOW AND PRESSURE

APVD

A. LEWIS
A 3. EXISTING SURFACES OR STRUCTURES DISTURBED BY CONSTRUCTION SHALL BE RESTORED BY INSTRUMENTATION BE FUNCTIONAL AND CONNECTED TO SCADA.
CONTRACTOR TO AN EQUAL OR BETTER CONDITION. DISTURBED GRASSED AREAS SHALL BE
RESTORED WITH SOD. 4. VALVES MAY ONLY BE OPERATED BY A REPRESENTATIVE OF MANATEE COUNTY UTILITIES.

BY
4. CONTRACTOR SHALL PROVIDE ALL LABOR, EQUIPMENT, AND TOOLS TO PERFORM AND
SATISFACTORILY COMPLETE THE WORK SHOWN BY THESE DRAWINGS. PIPING MATERIALS AND APPURTENANCES:
5. THE CONTRACTOR SHALL USE CAUTION IN PERFORMING THE WORK TO PREVENT DAMAGE TO 1. PIPE - FLANGED, AWWA C115/A21.15, THICKNESS CLASS 53 MINIMUM, 250 PSI MINIMUM WORKING
EXISTING UTILITY SYSTEMS AND SHALL COORDINATE WITH UTILITY COMPANIES LISTED AND PRESSURE.

APVD
OTHER UTILITY COMPANIES PRIOR TO AND DURING CONSTRUCTION. THE CONTRACTOR SHALL 2. FLANGES SHALL BE CLASS 125 FLAT FACE, DUCTILE IRON UNLESS OTHERWISE NOTED.

THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF
PROVIDE A MINIMUM OF 48 HOURS NOTICE TO UTILITY COMPANIES PRIOR TO CONSTRUCTION. 3. BOLTING: ASTM A320 / A320M GRADE B 8M HEX HEAD BOLTS, ASTM A194 / A194M GRADE 8M HEAD
THE CONTRACTOR SHALL OBTAIN FIELD LOCATES OF EXISTING UNDERGROUND UTILITIES IN THE NUTS, TYPE 316 STAINLESS STEEL WASHERS.

J.GOLDBACH
JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
VICINITY OF NEW CONSTRUCTION.
4. GASKETS: 1/8-INCH-THICK, HOMOGENEOUS BLACK RUBBER (EPDM), HARDNESS 60 (SHORE A),
6. THE CONTRACTOR SHALL PERFORM WORK IN ACCORDANCE WITH THE REQUIREMENTS OF THE RATED TO 275 DEGREES F, CONFORMING TO ASME B16.21 AND ASTM D2000 4CA 415 A25 B35 C32
SUNSHINE STATE ONE CALL OF FLORIDA, EXCAVATION GUIDE, LATEST EDITION. THE EA14 F19.
CONTRACTOR SHALL CONTACT SUNSHINE 811 (SUNSHINE811.COM) AT 1-800-432-4770 A MINIMUM
5. FITTINGS - FLANGED, AWWA C110/A21.10 DUCTILE IRON, FACED AND DRILLED, CLASS 125 FLAT
OF 48 HOURS PRIOR TO THE PLANNED EXCAVATION OR CONSTRUCTION DATE TO ARRANGE FOR
FACE.
THE FIELD LOCATION OF BURIED UTILITIES WITHIN THE CONSTRUCTION AREA.

REVISION
6. PIPE AND FITTING LINING - PROTECTO 401 BY INDURON COATING, OR EQUAL; 40-MILS TOTAL DFT.

CHK
7. THE CONTRACTOR SHALL PERFORM THE WORK TO MINIMIZE IMPACT AND DAMAGE TO PRIVATE
NEW FITTINGS LINED SAME AS PIPE.
PROPERTY. DAMAGE TO ADJACENT PROPERTY CAUSED BY THE CONTRACTOR SHALL BE
REPAIRED AND RESTORED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE COUNTY. 7. PIPE, FITTINGS, AND STEEL SURFACE COATINGS -- SSPC SP-10 SURFACE PREPARATION, 1 COAT

B. KLEIN
EPOXY PRIMER (2.5-MILS MINIMUM DFT), 1 COAT HIGH BUILD EPOXY (4-MILS MINIMUM DFT), 1
8. THE CONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS THAT ARE LOCATED ADJACENT
COAT POLYURETHANE ENAMEL (3-MILS MINIMUM DFT); TNEMEC OR EQUAL. FINAL COAT COLOR
TO THE NEW WORK.
TO MATCH EXISTING CONNECTING PIPE.
9. THE CONTRACTOR SHALL PREPARE RECORD DRAWINGS AND PROVIDE O&M MATERIALS AS
8. FLANGED COUPLING ADAPTERS - SMITH-BLAIR (SERIES 911) FLANGED-LOCK RESTRAINED FCA,
DESCRIBED BY THE CONSTRUCTION CONTRACT DOCUMENTS.
OR EQUAL, WITH TYPE 316 STAINLESS STEEL HARDWARE, EPDM GASKETS, AND FUSION-BONDED
10. USE "316 SST" FOR CONNECTION TO EXISTING THRUST TIES TO REMAIN. EPOXY COATED.

DR
B
SHOP DRAWINGS:

J. GOLDBACH
1. SUBMIT SHOP DRAWINGS TO ENGINEER FOR APPROVAL PRIOR TO FABRICATION AND SHIPPING
OF PRODUCTS.
2. SHOP DRAWING SUBMITTALS SHALL INCLUDE THE FOLLOWING INFORMATION:

DATE
a) CATALOG CUT SHEETS WHICH INCLUDES INFORMATION ON THE ELECTROMAGNETIC FLOW
METER, PIPE (INCLUDING LININGS AND COATINGS), FITTINGS, FLANGED COUPLING
ADAPTERS, AND SADDLES.

DSGN
NO.
b) DETAILED PIPE LAYOUT DRAWING PREPARED BY THE PIPE SUPPLIER.

c) CATALOG CUT SHEETS FOR FLOW METER TRANSMITTER SURGE PROTECTION AND

4350 WEST CYPRESS ST SUITE 600


ELECTRICAL AND PANEL COMPONENTS AS REQUIRED FOR NEW FLOW METER
INSTALLATION.

TAMPA, FLORIDA 33607-4155

CORTEZ ROAD INJECTION WELL

MANATEE COUNTY, FLORIDA


FLOW METER REPLACEMENT
d) FLOW METER FACTORY CALIBRATION SHEETS.

LB 0002934 AA C000656

MANATEE COUNTY
e) ELECTRICAL SITE PLAN FOR NEW CONDUIT ROUTING BETWEEN THE FLOW TRANSMITTER
FLOWMETER NOTES AND EXISTING CONTROL/ELECTRIC PANEL FOR POWER AND FLOW SIGNAL WIRING.
1. ELECTROMAGNETIC FLOWMETER SHALL HAVE THE FEATURES DESCRIBED BELOW AND
BE EITHER AN ABB PROCESSMASTER FEP300 OR AN E&H PROLINE PROMAG L 440. f) INSTALLATION DETAIL OF THE FLOW TRANSMITTER WHICH INCLUDES THE STANCHION
MOUNT, RAIN HOOD, AND SURGE PROTECTION. MATERIAL OF CONSTRUCTION AND
DIMENSIONS SHALL BE INCLUDED ON THIS DETAIL SHEET.
2. PROVIDE SURGE PROTECTORS FOR FIELD (EDCO SLAC OR EQUIVALENT)
g) DETAILS AND DRAWINGS SHOWING MODIFICATIONS TO THE EXISTING CONTROL/ELECTRIC
PANEL AND RTU PANEL FOR THE NEW FLOW SIGNAL.

REUSE OF DOCUMENTS:
DESCRIPTION VALUE
C GENERAL GENERAL PIPING NOTES:
NOMINAL SIZE 24-INCH 1. ALL FLANGED COUPLING ADAPTERS SHALL BE PROVIDED WITH THRUST TIES, AND ANCHORS,
UNLESS OTHERWISE NOTED. THRUST PROTECTION SHALL BE ADEQUATE FOR TEST PRESSURE
PROCESS FLUID RECLAIMED WATER SPECIFIED.
MINIMUM CONDUCTIVITY 5 MICRO S/CM
TEMPERATURE 32 TO 110 DEGREES F 2. HYDROSTATICALLY TEST COMPLETED PIPING AT 150 PSI. MAINTAIN TEST PRESSURE
OPERATING PRESSURE 150 PSI CONTINUOUSLY FOR 30 MINUTES, MINIMUM, AND FOR SUCH ADDITIONAL TIME AS NECESSARY
TO CONDUCT EXAMINATIONS FOR LEAKAGE. FOR A SUCCESSFUL TEST, THERE SHALL BE NO
DESIGN FLOW RANGE VISIBLE LEAKAGE AND NO APPARENT DROP IN PRESSURE.
MINIMUM 1,562 GPM (2.25 MGD)
MAXIMUM 10,416 GPM (15 MGD)

PROJECT NOTES
MEASURING ACCURACY ±0.5% OR READING
LAYING LENGTH 3' ALLOWANCE

FLOW SENSOR

CIVIL
LOCATION NEMA 4X
AMBIENT TEMPERATURE MINUS 5 TO 140 DEGREES F

MATERIALS OF CONSTRUCTION

CONSTRUCTION DRAWING SET


SENSOR HOUSING CARBON STEEL, FACTORY FINISH COATED
FLANGES ASME, CLASS 150, CARBON STEEL, FACTORY FINISH COATED
LINER HARD RUBBER
ELECTRODES STAINLESS STEEL

TRANSMITTER
LOCATION REMOTE MOUNT
D AMBIENT TEMPERATURE MINUS 5 TO 140 DEGREES F
POWER SUPPLY 120 VAC, 60-Hz
CURRENT OUTPUT 4 - 20 mA
DISPLAY INDICATION MGD
COMMUNICATION HART PROTOCOL N.T.S.
HOUSING NEMA4X VERIFY SCALE
BAR IS ONE INCH ON
ACCESSORIES ORIGINAL DRAWING.
GROUNDING RINGS TWO, STAINLESS STEEL 0 1"
SPLITTER / ISOLATOR
DATE JANUARY 2019
SURGE PROTECTOR ONE
PROJ 704019
DWG C2
SHEET 2 of 6
$PWURL $PWPATH FILENAME: Filename PLOT DATE: $PLOTDATE PLOT TIME: $PLOTTIME
1 2 3 4 5 6

CONTROL VALVE BUILDING

JOSEPH C. GOLDBACH
TEMPORARY STRAP-ON

c JACOBS 2018. ALL RIGHTS RESERVED.


FL P.E. No. 22385
FLOW METER (SEE NOTE)

APVD

A. LEWIS
A

BY
APVD

THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF
VALVE BUILDING
PIPE REMOVAL LIMITS

J.GOLDBACH
JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
WELL

REVISION
CHK
BFV (TO REMAIN)

B. KLEIN
BFV (TO REMAIN)

DR
VENTURI METER LIMIT PIPE REMOVAL OUTSIDE
B INSERT (REMOVE)

J. GOLDBACH
VENTURI METER
INSERT (REMOVE)

EXISTING CONDITIONS EAST ELEVATION

DATE
EXISTING CONDITIONS WEST ELEVATION
NOTE:

DSGN
AFTER NEW FLOW METER PLACED INTO SERVICE AND IS OPERATING PROPERLY, SALVAGE

NO.
TEMPORARY STRAP-ON METER AND DELIVER TO COUNTY. CONTRACTOR SHALL REMOVE
WIRING BETWEEN STRAP-ON METER AND CONTROL PANEL.

4350 WEST CYPRESS ST SUITE 600


TAMPA, FLORIDA 33607-4155

CORTEZ ROAD INJECTION WELL

MANATEE COUNTY, FLORIDA


FLOW METER REPLACEMENT
LB 0002934 AA C000656

MANATEE COUNTY
CONTROL / ELECTRIC
PANEL

REUSE OF DOCUMENTS:
C 12'-63
4"
CONCRETE PIPE
SADDLE PIPE REMOVAL
PROVIDE TEMPORARY (INSIDE)
EXST 24" BFV SUPPORT UNDER BFV
FLANGED (TO
REMAIN)
EXTENT OF TIE-RODS BOTH SIDES PIPE (MID-POINT) & ALONG TOP
1"
5'-12
INSERT TYPE VENTURI
METER (REMOVE) 6"
24" FLGxMJ 24" 45° BEND
7" SPOOL PIECE (TURNED DOWN)
8 1"
2'-112

DEMO PLAN
4'-11" 2'-113
4" 1'-05
8" 4'-43
8"

CIVIL
FLOW
CONTROL

24" BFV
24" FLOW
FCA

TO EXST WELL 1" VALVE


CONTROL 10'-102
VALVE

CONSTRUCTION DRAWING SET


10" FLOW DIRECTION

1'-4" REMOVE EXISTING PIPE &


7" TIE-RODS F&I NEW 24" PIPE PROVIDE TEMPORARY
SUPPORT UNDER FLOW
EXISTING CONDITIONS INSIDE VALVE BUILDING
D REMOVE EXISTING PIPING, CONTROL VALVE
TIE-RODS, FLOWMETER &
FLOWMETER INSTRUMENTATION
TO LIMITS INDICATED.
N.T.S.
EXISTING WOOD VALVE BUILDING
STRUCTURE TO BE REMOVED BY VERIFY SCALE
OTHERS PRIOR TO START OF FLOW EXST CONTROL / BAR IS ONE INCH ON
METER REPLACEMENT PROJECT ELECTRIC PANEL ORIGINAL DRAWING.
0 1"

EXST CONCRETE DATE JANUARY 2019


PIPE SADDLE (TYP) PROJ 704019
DWG D1
SHEET 3 of 6
$PWURL $PWPATH FILENAME: Filename PLOT DATE: $PLOTDATE PLOT TIME: $PLOTTIME
1 2 3 4 5 6
11'-0"

JOSEPH C. GOLDBACH
BLIND FLANGE

c JACOBS 2018. ALL RIGHTS RESERVED.


FL P.E. No. 22385
1/2" NPT NOZZLE ON INLET
BASKET STRAINER
AND OUTLET.
HINGE LOCATION

24" TEE W/ BRANCH


TURNED UPWARD

LONG RADIUS 90°

APVD

A. LEWIS
A
BEND TURNED DOWN
FABRICATED BASKET
STRAINER LONG RADIUS 90°
FLANGED COUPLING BEND

BY
ADAPTER 64" LAY LENGTH
FLANGED COUPLING
(RESTRAINED)
ADAPTER (RESTRAINED)

45° BEND

APVD

THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF
SAMPLE TAP, 3/4" HOSE
BIBB WITH DOUBLE STRAP FLANGED COUPLING

J.GOLDBACH
JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
SADDLE ADAPTER (RESTRAINED)

CONCRETE PIPE SUPPORT


(TYP. OF 5)

REVISION
SAMPLE TAP, 3/4" HOSE BIBB

CHK
24" DIP WITH DOUBLE STRAP

N
FLOW DIRECTION
SADDLE

O
18'-8"

B. KLEIN
TI
EC
IR
D
W
O
PROVIDE WEATHER TIGHT

FL
CLOSURE AROUND NEW
24" DIP
24" PIPE

DR
B INSTALL NEW

J. GOLDBACH
CONCRETE PIPE
SADDLE
CONCRETE PIPE
SADDLE

DATE
24" BFV

6' 7'-23
4" 5'-8"

DSGN
NO.
24" 45° BEND
(TURNED DOWN)

4350 WEST CYPRESS ST SUITE 600


TAMPA, FLORIDA 33607-4155

CORTEZ ROAD INJECTION WELL

MANATEE COUNTY, FLORIDA


FLOW METER REPLACEMENT
LB 0002934 AA C000656
24" BFV
24" FLOW
FCA

FCA

FCA

MANATEE COUNTY
CONTROL
VALVE
EXISTING WELL
SHUT-OFF VALVE

NPT TAP ON TOP OF FLOW DIRECTION


TEE - PROVIDE WITH 24" ELECTROMAGNETIC
FLOWMETER (36" LAY 24" FLG x PE DIP
EXISTING PLUG
WELLHEAD W/ LENGTH ALLOWANCE)
24" TEE INSTALL GROUND ROD

REUSE OF DOCUMENTS:
24" TEE THROUGH EXISTING
BLIND FLANGE CONCRETE SLAB
C

CONCRETE PIPE SADDLE


PLAN VIEW
FLOWMETER INSTRUMENT ON
STANCHION SUPPORT WITH
NOTE: RAINHOOD. FIT DISPLAY TO
EXIST CONTROL / ELECTRIC PANEL
FACE NORTH
1. ALL PIPING SHOWN IN PLAN IS LOCATED
ON AN EXISTING CONCRETE SLAB

PIPING LAYOUT
CIVIL
24" ELECTROMAGNETIC
BUILDING WALL 24" FLOW CONTROL
FLOWMETER
24" FLG x PE SPOOL VALVE
24" FLG x PE SPOOL 6"
PIECE

CONSTRUCTION DRAWING SET


24" BFV FLANGED PIECE 4'-23
4"±
ADJUST FOR ACTUAL 5'-8"
6' FLOWMETER LAY LENGTH
24" TEE
FCA

FCA

FCA
D

1'-9" 1'-83
4" N.T.S.
FLOW DIRECTION
VERIFY SCALE
1"
2'-32 1'-4"
1'-4" BAR IS ONE INCH ON
1" ORIGINAL DRAWING.
1'-114 0 1"
EXIST CONCRETE PIPE CONCRETE PIPE
SADDLE (TYP) (SEE SHEET ELEVATION VIEW 24" FLG x PE SPOOL SADDLE DATE JANUARY 2019
S1 FOR NEW STRAP PIECE PROJ 704019
REQUIREMENTS)
DWG M1
INSTALL NEW CONCRETE
PIPE SADDLE SHEET 4 of 6
$PWURL $PWPATH FILENAME: Filename PLOT DATE: $PLOTDATE PLOT TIME: $PLOTTIME
1 2 3 4 5 6

JOSEPH C. GOLDBACH
3

c JACOBS 2018. ALL RIGHTS RESERVED.


FOR ELEVATION, 8"X 3"BAR STRAP "S" BENT TO OD OF

FL P.E. No. 22385


PIPE, TYPE 316 STAINLESS STEEL
SEE PLAN 6"
24" PIPE DIA MIN UNBOLT EXIST STRAP FROM 3 34" 2 41"
CONCRETE SADDLE AND
REPLACE WITH NEW STRAP
121" 241"
1" MIN NON-SHRINK
1
GROUT, POURABLE 4"
16" SADDLE WIDTH
⅊ 1
2"X3"X4" (SEE
NOTE 3)

1-1/2"

4"
CLR

APVD

A. LEWIS
A

121"
60 ° 3/16
D/4

° 60 ANCHOR NEW STRAP TO


12" EMBEDMENT CONCRETE SADDLE WITH NEW

BY
DRILLED-IN SS ANCHOR BOLTS,
#3 6"
(5'-6" MAX)

NUTS & WASHERS. (STAINLESS


VARIES

30° 2" CLR STEEL)


TYP
3

APVD
VERTICAL REINFORCING "V", 4"DIAMETER ANCHOR

THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF
2"

EXTEND TO 1-1/2" CLR AT TOP BOLTS WITH LEVELING


OF CONCRETE NUTS CTR IN SADDLE

J.GOLDBACH
JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
MIN
6"

ROUGHEN SURFACE OF
EXISTING CONCRETE TO FULL 41" NOTES:
#6@12" MAX AMPLITUDE AND CLEAN
VERTICAL SPACING 1. FORM 3/4" BEVEL ON ALL EXPOSED CORNERS OF SUPPORT
2 LAYERS OF ROOFING
(2 LAYERS)

REVISION
FEET SECURE TIGHT TO 2. NEW PIPE STRAP REQUIRED FOR ALL SUPPORTS ASSOCIATED WITH NEW 24" DIP

CHK
6"

PIPE DURING POURING 3. PROVIDE 3/4" NEOPRENE PAD BELOW STRAP PLATE
EXISTING CONCRETE SLAB 4. CONCRETE SHALL HAVE A 28-DAY COMPRESSIVE STRENGTH OF 4,000 PSI, WITH A MAXIMUM
ADHESIVE ANCHORS

B. KLEIN
W/C RATIO OF 0.50, A MAXIMUM SLUMP OF 5". CONCRETE SHALL BE MIXED AND PLACED PER
ACI 304 AND 308 (LATEST EDITION) AND SHALL BE CURED WITH AN APPROVED CURING
PIPE SUPPORT - CONCRETE SADDLE DETAIL COMPOUND MEETING ASTM C1315.
NTS

DR
B

J. GOLDBACH
DATE
DSGN
NO.
4350 WEST CYPRESS ST SUITE 600
TAMPA, FLORIDA 33607-4155

CORTEZ ROAD INJECTION WELL

MANATEE COUNTY, FLORIDA


FLOW METER REPLACEMENT
LB 0002934 AA C000656

MANATEE COUNTY

REUSE OF DOCUMENTS:
C

PIPE SUPPORT DETAIL


CIVIL

CONSTRUCTION DRAWING SET


D

N.T.S.
VERIFY SCALE
BAR IS ONE INCH ON
ORIGINAL DRAWING.
0 1"

DATE JANUARY 2019


PROJ 704019
DWG S1
SHEET 5 of 6
$PWURL $PWPATH FILENAME: Filename PLOT DATE: $PLOTDATE PLOT TIME: $PLOTTIME
1 2 3 4 5 6

UNPROTECTED
SIGNAL LINES 5

JOSEPH C. GOLDBACH

c JACOBS 2018. ALL RIGHTS RESERVED.


TAPE BACK SHIELD - SHIELD

FL P.E. No. 22385


NOT TO BE GROUNDED COVER THIS
PROTECTED PORTION WITH OUTER
SHLD JACKET
SHRINK TUBING

4-WIRE
L1 INSTRUMENT
120VAC L1
N WRAPPED SHIELD
N 1 GREEN
GND 2
GND INSULATED WIRE CRIMPED SPLICE

APVD

A. LEWIS
A (SEE SHEET NOTE 2) CONNECTOR
SURGE
SUPPRESSOR PROTECTED SIDE 3
TO 4-WIRE
TO GROUND GRID TYPE 4 SURGE SUPPRESSOR INSTRUMENT

BY
(SEE SHEET NOTE 1) COVER THIS
WIRING DIAGRAM PORTION WITH OUTER
SHRINK TUBING JACKET

APVD

THIS DOCUMENT, AND THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN INSTRUMENT OF PROFESSIONAL SERVICE, IS THE PROPERTY OF
4-WIRE INSTRUMENT SHIELD

J.GOLDBACH
JACOBS AND IS NOT TO BE USED, IN WHOLE OR IN PART, FOR ANY OTHER PROJECT WITHOUT THE WRITTEN AUTHORIZATION OF JACOBS.
FLOW
MOUNT SUPPRESSOR 4 4
SHRINK TUBING SHIELD
ADJACENT TO INSTRUMENT
SERVED. EXCEPT FOR

(MAX)
24"
RAINHOODS AND SOLARSHADES
MOUNT SUPPRESSOR USING 5 TIMES PIPE DIA 5 TIMES PIPE DIA

REVISION
DETAIL FOR INSTRUMENT UNOBSTRUCTED (MIN) UNOBSTRUCTED (MIN) SIGNAL LEADS
SERVED. OUTER JACKET

CHK
4 WIRE INSTRUMENT REMOTE TRANSMITTER
SURGE SUPPRESSOR. NOTES:
LUG, TYP

B. KLEIN
1. CABLE TO BE PROVIDED BY INSTRUMENT VENDOR (NO LONGER THAN 164')(REMOTE
TRANSMITTER ONLY) NON-SPLICING CABLE. CONTRACTOR ROUTE CABLE IN FLEXIBLE
CONDUIT.

WATERTIGHT 2. REMOVABLE LIFTING LUGS FOR INSTALLING FLOW TUBE. GROUND LEAD SHRINK TUBING
CORD FITTING
CONDUCTORS AND 3. GROUNDING SHIELD, SEE NOTE 7.
#6 BARE SOLID
CONDUITS AS PER
COPPER GROUND,

DR
PLAN 4. FOUNDATION MOUNTS REQUIRED FOR METERS ABOVE 12". NOTE:
CONNECT TO
B SUPPRESSOR GROUND SHIELD GROUNDED ONLY AT CONTROL ENCLOSURE.

R. OSEGUEDA
5. TRANSMITTER STANCHION, SEE STANCHION MOUNTED DETAIL, 4091-383GD
TO GROUND GRID
6. MEASURING ELECTRODES MUST BE IN HORIZONTAL PLANE.

DATE
TERMINATION OF SHIELDED CONTROL CABLE
TYPE "4" SURGE SUPPRESSOR 7. TIE GROUND RINGS TO TRANSMITTER EQUIPMENT GROUND WITH A MINIMUM OF 12 AWG NTS
INSTALLATION
NTS 4-WIRE INSTRUMENT GROUND WIRE.

DSGN
NO.
NTS 8. ENSURE INSTRUMENT IS ADEQUATELY SUPPORTED PER MANUFACTURER'S
RECOMMENDATIONS. 4091-425G
4091-420BG FLOW TRANSMITTER - MAGNETIC 4091-273

4350 WEST CYPRESS ST SUITE 600


NTS

TAMPA, FLORIDA 33607-4155

CORTEZ ROAD INJECTION WELL

MANATEE COUNTY, FLORIDA


FLOW METER REPLACEMENT
LB 0002934 AA C000656

MANATEE COUNTY
BACK FORMED OF SINGLE INSTRUMENT/HOOD
MOUNTING HOLES TO SUIT INSTRUMENT SHEET 10 GA ALUMINUM, SUPPORT ANGLE OR SHEET NOTES:
SECURE INSTRUMENT TO STANCHION TACK WELD TO TOP & UNISTRUT (SHOWN) 1. BORE HOLE THRU EXISTING CONCRETE SLAB AND INSTALL GROUND ROD (5 ohms OR
W/SST BOLTS, NUTS & WASHERS SIDES AS REQUIRED AS APPLICABLE LESS) FOR GROUNDING RINGS AND INSTRUMENT PANEL.

RAIN HOOD REQUIRED RAINHOOD 2. 120 VAC POWER FOR NEW FLOW METER INSTRUMENT TO BE SUPPLIED FROM
FOR OUTDOOR APPLICATION, DEDICATED CIRCUIT BREAKER LOCATED INSIDE EXISTING CONTROL / ELECTRIC
SEE PANEL. CONTRACTOR TO PROVIDE CONDUIT AND CONDUCTORS BETWEEN SURGE
4091-384
INSTRUMENT SUPPRESSOR AND EXISTING DEDICATED CIRCUIT BREAKER.

1 1/2"

REUSE OF DOCUMENTS:
MOUNTING
C 3/16 FOOT 3. CONTRACTOR TO ROUTE NEW FLOW METER 4-20MA SIGNAL LINES IN FLEXIBLE
CONDUIT TO EXISTING TERMINATION INSIDE THE EXISTING CONTROL/ELECTRIC PANEL.
INSTRUMENT

L 2-1/2"x2"x1/4" INSTRUMENT
TOP & SIDES
TO SUIT

AL LENGTH TO ENCLOSURE 4. THE EXISTING FLOW METER PROVIDES A 4-20MA FLOW INDICATION FROM THE
SUIT INSTRUMENT FORMED OF
SINGLE SHEET EXISTING PANEL TO AN RTU LOCATED ADJACENT TO THE ONSIDE GROUND STORAGE
INSTRUMENT 10 GA ALUMINUM 3/8" SST STUD BOLT TANK. DISCONNECT THE EXISTING FLOW METER AND CONNECT AND TERMINATE THE
AND SURGE WITH SST NUTS AND NEW FLOW METER SIGNAL WIRING. REUSE THE EXISTING PANEL SIGNAL WIRING AND
INPUT INTO THE RTU FOR THE CONNECTION TO THE COUNTY'S PLANT SCADA.

INSTRUMENTATION DETAILS
SUPRESSOR WASHERS, TYP OF 4

L 2-1/2"x2"x1/4" AL 2'-0" MIN 5. CONTRACTOR TO TEST NEW FLOW METER SIGNAL AT THE EXISTING RTU PANEL AND
LENGTH TO SUIT 3/16 THE COUNTY'S PLANT SCADA LOCATION. TESTING SHALL INCLUDE FIELD CALIBRATION
6" 6" 6" (FLOW SIGNAL RANGE: 0%, 25%, 50%, AND 100%) OF THE NEW FLOW TRANSMITTER
INSTRUMENT G WITH FLOW VERIFICATION AT THE PLANT SCADA SYSTEM FLOW DISPLAY. MAXIMUM
4'-6"

2" SCHED 40 AL PIPE FLOW (100%) PERMITTED TO THE WELL IS 10,416 GPM.
6"

4"x2" AL REDUCER
2'-0" MIN

ROUND

CIVIL
4" SCHED 40 AL PIPE EDGES &
CORNERS
2'-6"

PL 1/2"x12"x12", AL

CONSTRUCTION DRAWING SET


SECURE TO SLAB WITH 3/16
(4) 1/2" SST CONCRETE
ANCHORS
1" NONSHRINK
MIN

INSTRUMENT
3"

GROUT OR SMALL PANEL 2"

D
NOTES: NOTES:
1. ROUND OFF ALL EXPOSED EDGES AND CORNERS. 1. ALL EXPOSED EDGES TO BE GROUND SMOOTH AND BURR FREE.
N.T.S.
2. PAINT ALUMINUM IN CONTACT WITH CONCRETE ACCORDING TO 2. MOUNT RAIN HOOD BETWEEN INSTRUMENT AND MOUNTING
SPECIFICATIONS FOR PAINTING. BRACKET. DRILL HOLES IN RAIN HOOD AS PER MOUNTING VERIFY SCALE
HOLES FOR INSTRUMENT, SEE 4091-273 4091-383GD BAR IS ONE INCH ON
ORIGINAL DRAWING.

STANCHION SUPPORT FOR CASE MOUNTED INSTRUMENTS RAIN HOOD INSTALLATION 0 1"

NTS NTS DATE JANUARY 2019


PROJ 704019
DWG I1
4091-383GD 4091-384
SHEET 6 of 6
$PWURL $PWPATH FILENAME: Filename PLOT DATE: $PLOTDATE PLOT TIME: $PLOTTIME