Vous êtes sur la page 1sur 2

Lithium-Ion Battery Solution for

Telecom Base Station & UPS


Features
The Standalone battery modules (EM048063P3S and
EM048126P3S series) have the following features :
▪ Built-in Battery Management System (BMS) : A battery
module’s BMS moniitors it’s operation and prevents the
battery from operating outside design limitations. When a
battery module enters abnormal state, the BMS issues an
alert and restricts or disables the battery’s operation.
▪ How-swap capability : Faulty battery modules can be
replaced while the ESS remains in operation.
(this feature is not supported with the residential models)
▪ Scalability : An ESS can comprise up to 10 units connected
in parallel.
▪ Power Saving : When a battery voltage drops below the
limit, it turns off.

Battery Cell
Customized cells for ESS purpose.
Energy cell for long duration energy storage.
Power cell for high power output energy storage.

Battery Module
19-inch standard module.
Product composed of sub-modules and BMS. EM048063P3Sx
Battery Pack
ESS Pack composed of sub-modules, BMS, and BPU.
Paraallel expansions or Main Pack independent
operation.

Battery Rack System


ESS Battery Rack composed of BPU, BMS, and
modules connected in series/parallel.
Flexible system design : Fan-cooling or air cooling
options available depending on heat dissipation.
EM048126P3Sx

SOHO PANCORAN,
Splendor Tower 12th floor unit 1205-1206
Jl. MT. Haryono Kav 2-3, Jakarta Selatan, 12810
Indonesia. Phone : 021-80625888
e-mail : sales@ataenergi.com
www.ataenergi.com
Lithium-Ion Battery Solution for
Telecom Base Station & UPS
Battery Specification
Model EM048063P3Sx EM048126P3Sx
Nominal Capacity1 63 Ah 126 Ah
Nominal Energy1 3.26 kWh 6.52 kWh
Nominal Voltage 51.8 V
Operating Voltage 42.0 - 58.8 V
Floating Voltage 57.4 V Max.
Peak Pulse Voltage Max. 80V / under 50 ms
Max. Charge/Discharge Current2 63 A (1C) 63 A (0.5C)
Max. Charge/Discharge Power2 3.26 kW 3.26 kW
Continous Charge/Discharge Power2 3.0 kW 3.0 kW
Round-Trip Efficiency 95% or more
Ingress Protection Rating IP20
3
Cooling Forced air cooling Natural convection
Or Natural convection
Flow rate 30 m3/h per fan
Communication Interface Protocol : Modbus 485 | Port RJ48
Dry Contact 2Ch (Warning or Fault 1/Fault 2)
Cycle 7000 Cycle at DOD 80%
Dimensions (WHD) 455 x 110 x 338.8 mm 455 x 110 x 586.6 mm
Weight 26.5 kg 44 kg
Operating Conditions
Available Operating Temperature -100 ~ 450 C
Optimal Operating Temperature 150 ~ 300 C
Storage Temperature -150 ~ 600 C
Self-Discharge Rate During Storage Less than 6% per year at 250 C
Humidity 5% ~ 95%
Altitude Below 2,000 m
Scalability & Certification
Scalability Up to 10 units with parallel
Safety Cell UL1642
Safety Module CE / RCM / FCC /TUV (IEC 62619) / UL1973 / S-mark
( JIS C8715-2 )
Transportation UN 38.3 (UNDOT)
1. At standard conditions :
2. It can be derated in accordance with the power limit by the BMS
3. Fan operation noise = 80 dB (Distance measured at 1 m, from module’s fan)