Type VAJ relays are fast operating multi-contact attracted armature relays
with a high degree of mechanical stability and are suitable for control duties
where a number of simultaneous switching operations are required.
Control relays generally have lower burdens than tripping relays and are used
for applications such as starting and shutting down apparatus in automatic
stations.
Cut-off contacts are provided on electrically reset relays. The contacts are
time delayed on opening, and after a short time delay cut off the operating
current.
Standard voltage ratings Cut-off Contacts
Operating and reset coils : 24, 30, 48, The electrically reset relays are fitted
110, 125, 220, 230, 240 and 250 volts with heavy duty cut-off contacts. These
d.c. contacts interrupt the operating circuit
instantaneoulsy when the relay has
Satisfactory operation and reset is operated and latched in, to reduce relay
between 80% and 120% of rated voltage. burden and possible heating effect.
Contacts
The number of pairs of contacts available
for tripping of contacts available are
shown in the table. Any combination
of normally open or normally closed
contacts can be fitted. Contacts are of
silver/copper alloy, shaped and positioned
to ensure low resistance and maximum
reliability.
Customer Benefits
• Electrical Reset
• High Reliabiltiy
• High speed operation
GRID
1
VAJC
Contacts Ratings
Thermal rating
The control relays are arranged so that 120% rated voltage can be applied continuously. Reset coils, which are normally energised
through a push button, are short time rated.
2
VAJC
Dimension Details
Figure 1 : Case and panel cut-out dimensions for case 1/2 N Ver. (all dimensions in mm)
Figure 2 : Case and panel cut-out dimensions for case 1D (all dimensions in mm)
Cases are suitable for flush or projecting mounting. All cases are finished phenolic black as standard. Standard relays are finished to
B.S.2011: 20/40/4 and are satisfactory for normal tropical use. Relays for use in exceptionally severe environments can be finished to
B.S.2011:20/50/56 at extra cost.
3
Case:
Issue:
8 N/O
Burden
With flag
Contacts:
48/54 Vdc
30/34 Vdc
24/27 Vdc
Relay Type:
Low Burden
Flag Option:
4 N/O 4 N/C
5 N/O 3 N/C
6 N/O 2 N/C
7 N/O 1N/C
220/250 Vdc
110/125 Vdc
Factory Defined
www.grid.alstom.com
Contact Combination:
http://www.alstom.com/contactcentre/
ALSTOM T&D Worldwide Contact Centre:
1D V Drawout Case with CT shorting links
Information required with your order.
4
3
2
1
0
A
A
B
ZF
11
BF
100
075
050
025
000
VAJC
GRID
VAJC
“Alstom logo and any alternative version thereof are trademarks and service marks of Alstom. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in
the document are provided for information only. Neither ALSTOM, its officers nor employees accept responsibility for or should be taken as making any representation or warranty (whether express or implied) as to the accuracy or
4
completeness of such data or the achievements of any projected performance criteria where these are indicated. No liability is accepted for any reliance placed upon the information contained in this brochure. Alstom reserves the right to
revise or change these data at any time without further notice.”