Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)

COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-1

1C1 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 96.3 -1.6 -4.2 89.3 3.7 10.1
2 97.3 -1.5 -4.4 90.4 3.8 10.1
3 97.3 -1.5 -4.5 90.4 3.6 10.2
4 81.9 -0.9 -4.2 75.0 2.1 10.1
5 73.2 -1.6 -2.3 66.3 3.6 6.1
6 96.3 -1.6 -4.2 89.4 3.7 10.1
7 96.3 -1.6 -4.2 89.3 3.7 10.1
8 81.9 -0.9 -4.2 75.0 2.1 10.1
9 73.2 -1.6 -2.3 66.3 3.6 6.1
10 97.3 -1.5 -4.4 90.4 3.8 10.1
11 97.3 -1.5 -4.4 90.4 3.6 10.2
12 79.4 0.5 -4.2 73.5 1.7 8.9
13 82.1 -3.2 -2.9 76.1 4.5 8.1
14 79.9 -1.3 -1.3 74.0 3.1 7.3
15 81.5 -1.3 -5.8 75.6 3.1 9.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 96.3 - 96.3
M1 (kN.m) 3.7 1.0 3.7 350
M2 (kN.m) 10.1 1.7 10.1
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 10.2 < 15.0 200
Beta = 0.00 Le2/b2 = 6.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.7 / 4.8 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.78 / 0.69 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.03 / 0.08 N/mm2
Links = Y8-150

2C1 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 29.9 -4.2 -12.0 23.0 3.1 9.4
2 30.3 -4.2 -12.3 23.4 3.0 9.6
3 30.4 -4.3 -12.5 23.5 3.2 9.9
4 24.8 -2.4 -12.0 17.9 1.5 9.4
5 21.3 -4.2 -6.2 14.3 3.1 3.5
6 29.9 -4.2 -12.0 23.0 3.1 9.4
7 29.9 -4.3 -12.0 23.0 3.2 9.4
8 24.8 -2.4 -12.0 17.9 1.5 9.4
9 21.3 -4.2 -6.1 14.3 3.1 3.5
10 30.3 -4.2 -12.3 23.4 3.0 9.6
11 30.5 -4.3 -12.6 23.5 3.2 10.0
12 24.3 -3.1 -10.0 18.4 1.9 7.8
13 25.1 -4.0 -10.1 19.1 3.3 7.5
14 24.5 -3.6 -10.0 18.5 2.6 7.1
15 24.9 -3.5 -10.0 19.0 2.5 8.2
Critical Combination:11 - ((G+Q)P52 *F)
Min Design
N (kN) 30.5 - 30.5
M1 (kN.m) -4.3 -0.3 -4.3 350
M2 (kN.m) -12.6 -0.5 -12.6
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 9.9 < 15.0 200
Beta = 0.00 Le2/b2 = 7.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.4 / 7.1 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.75 / 0.64 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.04 / 0.12 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-2

1C2 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 146.5 -0.8 1.7 139.6 2.0 -2.1
2 148.3 -0.7 1.4 141.4 2.2 -2.0
3 108.9 0.0 2.9 102.0 0.6 -4.9
4 131.6 -0.4 1.7 124.7 1.2 -2.0
5 123.0 -0.9 -0.2 116.1 2.3 1.7
6 146.5 -0.8 1.7 139.6 2.0 -2.1
7 147.8 -0.8 1.6 140.9 2.1 -1.9
8 131.6 -0.4 1.7 124.7 1.2 -2.1
9 121.7 -0.9 -0.1 114.7 2.2 1.5
10 148.3 -0.7 1.4 141.4 2.2 -2.0
11 109.0 0.0 2.9 102.1 0.6 -4.9
12 121.4 0.9 0.7 115.4 0.6 -1.3
13 122.7 -2.1 2.1 116.8 2.7 -2.2
14 122.3 -0.6 3.8 116.4 1.7 -3.4
15 121.8 -0.6 -1.0 115.8 1.6 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 146.5 - 146.5
M1 (kN.m) 2.0 1.5 2.0 350
M2 (kN.m) -2.1 -2.6 -2.6
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 10.1 < 15.0 200
Beta = 0.00 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.3 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.75 / 0.70 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.01 N/mm2
Links = Y8-150

2C2 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 54.4 -4.6 3.0 47.4 6.3 -2.5
2 55.2 -4.6 2.6 48.3 6.3 -2.0
3 35.8 -1.3 7.2 28.9 1.8 -6.7
4 45.5 -2.6 3.0 38.6 3.5 -2.3
5 45.5 -5.1 -2.7 38.6 6.9 3.2
6 54.4 -4.6 3.0 47.4 6.3 -2.4
7 55.0 -4.8 2.7 48.1 6.5 -2.1
8 45.5 -2.6 3.0 38.6 3.5 -2.4
9 44.9 -4.9 -2.3 37.9 6.7 2.7
10 55.2 -4.6 2.6 48.3 6.3 -2.0
11 35.9 -1.3 7.1 28.9 1.8 -6.6
12 44.3 -3.5 2.4 38.4 4.6 -1.8
13 44.7 -3.9 2.6 38.8 5.6 -2.2
14 44.6 -3.8 3.0 38.7 5.2 -2.9
15 44.4 -3.7 2.0 38.5 5.0 -1.1
Critical Combination:5 - ((G+Q)P22 *F)
Min Design
N (kN) 45.5 - 45.5
M1 (kN.m) 6.9 0.5 6.9 350
M2 (kN.m) 3.2 0.8 3.2
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 9.8 < 15.0 200
Beta = 0.00 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 4.0 / 4.6 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.76 / 0.65 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.07 / 0.07 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-3

1C3 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 155.2 -1.3 0.7 148.3 3.2 -0.1
2 156.0 -1.3 0.5 149.1 3.3 0.0
3 131.5 -1.4 -1.1 124.6 3.2 3.4
4 137.5 -0.7 0.7 130.6 1.7 0.0
5 132.7 -1.4 2.4 125.8 3.2 -3.7
6 155.2 -1.4 0.7 148.3 3.2 -0.1
7 131.5 -1.3 2.4 124.6 3.1 -3.5
8 137.5 -0.7 0.7 130.6 1.7 0.0
9 157.3 -1.4 0.7 150.3 3.3 -0.1
10 156.0 -1.3 0.5 149.1 3.3 0.0
11 130.7 -1.4 -1.1 123.8 3.2 3.2
12 128.0 0.2 0.0 122.1 1.6 0.3
13 131.4 -2.4 1.3 125.4 3.8 -0.5
14 129.7 -1.1 3.0 123.8 2.7 -1.7
15 129.6 -1.1 -1.8 123.7 2.7 1.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 155.2 - 155.2
M1 (kN.m) 3.2 1.7 3.2 350
M2 (kN.m) 0.7 2.7 2.7
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 10.1 < 15.0 200
Beta = 0.00 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.5 / 0.1 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.78 / 0.72 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y8-150

2C3 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 49.0 -4.1 1.1 42.1 3.5 -1.5
2 49.4 -4.1 0.7 42.4 3.5 -1.1
3 39.7 -4.1 -4.5 32.8 3.5 4.1
4 42.0 -2.0 1.0 35.1 1.5 -1.4
5 40.6 -4.1 6.1 33.6 3.5 -6.5
6 49.0 -4.1 1.0 42.1 3.5 -1.5
7 40.0 -4.0 6.0 33.1 3.4 -6.3
8 42.0 -2.0 1.0 35.1 1.5 -1.5
9 50.0 -4.2 1.0 43.0 3.6 -1.5
10 49.4 -4.1 0.7 42.4 3.5 -1.1
11 39.3 -4.1 -4.3 32.4 3.5 3.9
12 39.7 -3.0 0.8 33.8 2.3 -1.0
13 40.6 -3.9 1.0 34.7 3.4 -1.5
14 40.2 -3.4 1.3 34.3 2.9 -2.2
15 40.1 -3.4 0.4 34.2 2.9 -0.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 49.0 - 49.0
M1 (kN.m) -4.1 -0.5 -4.1 350
M2 (kN.m) -1.5 -0.9 -1.5
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 9.8 < 15.0 200
Beta = 0.00 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.5 / 4.2 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.76 / 0.66 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.05 / 0.07 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-4

1C4 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 137.6 -0.3 1.3 130.6 1.1 -1.2
2 138.6 -0.3 1.0 131.7 1.2 -1.1
3 116.9 -0.3 2.5 109.9 1.0 -4.1
4 124.9 0.1 1.2 117.9 0.3 -1.1
5 113.3 -0.4 -0.5 106.4 1.2 2.3
6 137.6 -0.3 1.2 130.7 1.1 -1.2
7 113.2 -0.3 -0.4 106.2 1.2 2.3
8 124.8 0.1 1.3 117.9 0.3 -1.1
9 115.9 -0.3 2.5 108.9 1.1 -3.9
10 138.6 -0.3 1.0 131.7 1.2 -1.1
11 138.7 -0.3 1.1 131.8 1.1 -1.3
12 113.3 0.8 0.4 107.4 0.1 -0.5
13 116.1 -1.2 1.7 110.2 1.7 -1.4
14 114.7 -0.2 3.5 108.7 0.9 -2.6
15 114.8 -0.2 -1.4 108.8 0.9 0.7
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 137.6 - 137.6
M1 (kN.m) 1.1 1.5 1.5 350
M2 (kN.m) 1.3 2.4 2.4
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 10.1 < 15.0 200
Beta = 0.00 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.9 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.77 / 0.71 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.01 N/mm2
Links = Y8-150

2C4 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 46.5 -1.9 2.1 39.6 2.2 -1.9
2 47.2 -2.0 1.7 40.2 2.3 -1.5
3 38.5 -1.8 6.3 31.6 2.0 -6.2
4 40.3 -0.5 1.9 33.4 0.5 -1.7
5 37.3 -2.0 -3.1 30.4 2.3 3.1
6 46.6 -1.9 2.0 39.6 2.2 -1.9
7 37.3 -1.9 -2.9 30.4 2.2 2.9
8 40.3 -0.4 2.0 33.4 0.5 -1.8
9 38.0 -1.8 6.2 31.1 2.1 -6.1
10 47.2 -2.0 1.7 40.2 2.3 -1.5
11 47.1 -1.9 1.9 40.2 2.2 -1.8
12 37.8 -1.1 1.6 31.8 1.3 -1.3
13 38.5 -1.9 1.8 32.6 2.2 -1.8
14 38.1 -1.5 2.2 32.2 1.7 -2.5
15 38.2 -1.5 1.2 32.2 1.7 -0.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 46.5 - 46.5
M1 (kN.m) 2.2 0.5 2.2 350
M2 (kN.m) 2.1 0.8 2.1
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 9.7 < 15.0 200
Beta = 0.00 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.4 / 4.2 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.76 / 0.66 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.03 / 0.07 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-5

1C5 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 79.3 -0.3 3.4 72.4 1.1 -5.5
2 80.0 -0.4 3.1 73.1 1.2 -5.5
3 59.7 -0.3 2.1 52.8 1.2 -3.3
4 70.9 -0.1 3.5 64.0 0.6 -5.8
5 80.4 -0.4 3.4 73.5 1.1 -5.7
6 79.4 -0.3 3.4 72.4 1.1 -5.5
7 80.3 -0.3 3.5 73.4 1.1 -5.7
8 70.9 0.0 3.5 64.0 0.6 -5.8
9 60.0 -0.4 2.2 53.1 1.2 -3.3
10 80.0 -0.4 3.1 73.1 1.2 -5.5
11 79.2 -0.3 3.2 72.2 1.1 -5.6
12 65.6 0.4 2.3 59.7 0.4 -4.5
13 68.2 -1.0 3.4 62.2 1.5 -5.0
14 67.7 -0.3 5.1 61.8 0.9 -5.9
15 66.1 -0.3 0.7 60.2 1.0 -3.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 79.3 - 79.3
M1 (kN.m) 1.1 0.8 1.1 350
M2 (kN.m) -5.5 -1.4 -5.5
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 10.1 < 15.0 200
Beta = 0.00 Le2/b2 = 6.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 1.4 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.74 / 0.66 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.02 N/mm2
Links = Y8-150

2C5 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 26.6 -1.3 7.9 19.7 0.9 -7.0
2 26.9 -1.5 7.6 20.0 1.1 -6.7
3 18.6 -1.4 3.9 11.6 1.1 -2.6
4 22.9 -0.5 8.3 16.0 0.0 -7.5
5 27.1 -1.4 8.1 20.2 1.0 -7.2
6 26.6 -1.3 7.9 19.7 0.9 -7.0
7 27.1 -1.3 8.2 20.1 0.9 -7.3
8 22.9 -0.4 8.3 16.0 0.0 -7.5
9 18.7 -1.4 4.1 11.8 1.1 -2.8
10 26.9 -1.5 7.6 20.0 1.1 -6.7
11 26.5 -1.3 7.6 19.6 1.0 -6.7
12 21.7 -0.8 6.7 15.7 0.4 -5.7
13 22.4 -1.3 6.5 16.5 1.1 -5.8
14 22.3 -1.0 6.5 16.3 0.7 -6.2
15 21.8 -1.1 6.7 15.9 0.8 -5.3
Critical Combination:8 - ((G+Q)P41 *F)
Min Design
N (kN) 22.9 - 22.9
M1 (kN.m) -0.4 -0.2 -0.4 350
M2 (kN.m) 8.3 0.4 8.3
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.000 Le1/b1 = 9.7 < 15.0 200
Beta = 0.00 Le2/b2 = 7.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.8 / 5.3 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.74 / 0.63 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.01 / 0.08 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-6

1C6 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 117.0 0.2 1.3 110.1 1.2 -2.3
2 101.3 0.8 1.4 94.3 -0.3 -2.5
3 91.4 0.1 0.1 84.5 1.3 0.1
4 107.1 -0.1 1.4 100.2 1.9 -2.4
5 119.5 0.0 1.5 112.6 1.3 -2.6
6 117.2 0.1 1.3 110.2 1.3 -2.3
7 119.6 0.1 1.5 112.7 1.3 -2.6
8 106.9 -0.1 1.4 100.0 1.9 -2.4
9 92.1 0.1 0.2 85.2 1.3 0.0
10 101.3 0.8 1.4 94.3 -0.3 -2.5
11 116.3 0.1 1.3 109.3 1.3 -2.2
12 97.7 2.1 1.0 91.7 -0.4 -1.8
13 97.2 -1.7 1.1 91.3 2.4 -1.8
14 98.0 0.1 1.9 92.1 1.0 -2.4
15 96.9 0.2 0.2 90.9 1.0 -1.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 117.0 - 117.0
M1 (kN.m) 1.2 2.0 0.0 200
M2 (kN.m) -2.3 -1.2 -3.2
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.061 Le1/b1 = 6.3 < 15.0 350
Beta = 0.93 Le2/b2 = 11.0 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.0 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.67 / 0.74 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-150

2C6 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 46.2 -0.9 5.7 39.2 0.0 -7.9
2 40.3 1.1 6.0 33.4 -1.8 -8.1
3 32.3 -1.0 0.8 25.4 0.1 -1.6
4 41.7 -2.0 5.9 34.8 1.3 -8.1
5 47.6 -1.2 6.4 40.7 0.3 -8.8
6 46.3 -1.0 5.7 39.3 0.1 -7.9
7 47.6 -1.0 6.5 40.7 0.1 -8.9
8 41.6 -1.9 5.9 34.7 1.3 -8.1
9 32.8 -1.1 1.0 25.8 0.2 -2.0
10 40.3 1.1 6.0 33.4 -1.8 -8.1
11 45.7 -1.0 5.4 38.8 0.1 -7.5
12 37.9 -0.3 4.6 32.0 -0.7 -6.4
13 37.8 -1.2 4.6 31.9 0.7 -6.4
14 38.0 -0.7 4.8 32.1 0.0 -6.7
15 37.7 -0.8 4.4 31.7 0.1 -6.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 40.3 - 40.3
M1 (kN.m) -1.8 -0.7 0.0 200
M2 (kN.m) -8.1 -0.4 -9.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.021 Le1/b1 = 6.2 < 15.0 350
Beta = 0.97 Le2/b2 = 10.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 5.1 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.62 / 0.76 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.09 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-7

1C7 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 83.6 1.4 0.1 76.7 -1.3 0.3
2 68.1 0.7 0.2 61.2 -0.1 0.0
3 83.9 1.4 0.0 77.0 -1.2 0.3
4 76.3 1.7 0.1 69.4 -1.9 0.2
5 75.8 1.3 -0.1 68.8 -1.4 0.7
6 76.6 1.7 0.1 69.6 -1.9 0.1
7 83.5 1.4 0.1 76.6 -1.3 0.3
8 83.4 1.5 0.0 76.5 -1.3 0.3
9 84.1 1.3 0.1 77.2 -1.2 0.3
10 68.1 0.7 0.2 61.2 -0.1 0.0
11 75.6 1.4 -0.1 68.7 -1.4 0.6
12 69.4 3.1 0.3 63.5 -2.6 0.1
13 70.8 -0.8 -0.1 64.9 0.4 0.4
14 71.2 1.1 0.9 65.3 -1.0 -0.4
15 69.1 1.2 -0.8 63.1 -1.1 0.9
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 83.6 - 83.6
M1 (kN.m) 1.4 1.5 0.0 200
M2 (kN.m) 0.3 0.8 1.6
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.043 Le1/b1 = 6.3 < 15.0 350
Beta = 0.95 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.0 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.67 / 0.73 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-150

2C7 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 29.1 1.9 0.3 22.2 -1.7 -0.8
2 23.7 0.0 0.6 16.7 0.2 -1.1
3 29.3 1.8 0.2 22.3 -1.6 -0.6
4 26.0 2.9 0.3 19.1 -2.8 -0.8
5 25.0 1.9 -0.5 18.1 -1.7 0.1
6 26.1 2.8 0.5 19.1 -2.6 -1.0
7 29.1 1.8 0.3 22.2 -1.6 -0.8
8 29.1 2.0 0.1 22.1 -1.8 -0.6
9 29.3 1.7 0.2 22.4 -1.6 -0.7
10 23.7 0.0 0.6 16.7 0.2 -1.1
11 25.0 2.0 -0.5 18.0 -1.9 0.2
12 23.9 2.1 0.2 17.9 -2.2 -0.7
13 24.2 1.0 0.1 18.3 -0.6 -0.6
14 24.3 1.5 0.5 18.4 -1.4 -1.0
15 23.7 1.6 -0.1 17.8 -1.4 -0.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 29.1 - 29.1
M1 (kN.m) 1.9 0.5 3.4 200
M2 (kN.m) -0.8 -0.3 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.015 Le1/b1 = 6.2 < 15.0 350
Beta = 0.98 Le2/b2 = 10.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 0.6 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.63 / 0.74 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.03 / 0.01 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-8

1C8 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 57.9 0.9 0.6 51.0 -0.3 -0.9
2 58.2 0.8 0.7 51.3 -0.3 -0.9
3 57.5 0.9 0.6 50.6 -0.3 -0.8
4 50.0 0.8 0.6 43.1 0.0 -0.9
5 49.3 0.9 0.4 42.4 -0.6 -0.5
6 50.2 0.8 0.7 43.3 -0.1 -1.0
7 57.7 0.9 0.6 50.8 -0.3 -0.9
8 57.7 1.0 0.6 50.8 -0.3 -0.8
9 50.1 1.0 0.4 43.1 -0.6 -0.5
10 58.2 0.8 0.7 51.3 -0.3 -0.9
11 56.9 0.9 0.6 50.0 -0.3 -0.8
12 51.3 2.5 0.9 45.3 -1.4 -1.0
13 46.9 -1.0 0.2 40.9 0.8 -0.5
14 50.7 0.7 1.4 44.7 -0.2 -1.4
15 47.5 0.9 -0.3 41.5 -0.4 0.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 57.9 - 57.9
M1 (kN.m) 0.9 1.0 0.0 200
M2 (kN.m) -0.9 -0.6 -1.4
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.030 Le1/b1 = 6.6 < 15.0 350
Beta = 0.96 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.1 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.65 / 0.75 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-150

2C8 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 19.1 1.0 1.3 12.1 -1.5 -1.1
2 19.1 0.8 1.3 12.2 -1.2 -1.1
3 18.9 1.0 1.1 12.0 -1.5 -0.9
4 15.8 0.6 1.3 8.9 -0.9 -1.1
5 15.9 1.2 0.7 9.0 -1.6 -0.6
6 15.9 0.5 1.5 9.0 -0.8 -1.3
7 19.0 1.0 1.3 12.1 -1.4 -1.1
8 19.0 1.1 1.1 12.0 -1.5 -0.9
9 16.3 1.4 0.7 9.4 -1.8 -0.6
10 19.1 0.8 1.3 12.2 -1.2 -1.1
11 18.6 0.9 1.1 11.6 -1.3 -1.0
12 16.5 0.9 1.1 10.6 -1.6 -1.0
13 15.3 0.8 1.0 9.4 -0.8 -0.8
14 16.4 0.8 1.4 10.4 -1.2 -1.3
15 15.4 0.9 0.8 9.5 -1.2 -0.5
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 19.1 - 19.1
M1 (kN.m) -1.5 -0.3 0.0 200
M2 (kN.m) 1.3 0.2 2.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 6.7 < 15.0 350
Beta = 0.99 Le2/b2 = 10.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.1 / 0.9 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.61 / 0.74 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.02 / 0.02 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-9

1C9 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 177.6 0.7 0.5 170.7 0.1 -0.6
2 157.1 1.6 0.4 150.1 -1.7 -0.5
3 151.3 0.6 1.7 144.3 0.2 -3.1
4 161.9 0.0 0.5 155.0 1.4 -0.5
5 145.1 0.5 -0.9 138.2 0.3 2.2
6 177.6 0.7 0.5 170.7 0.2 -0.6
7 145.3 0.6 -0.8 138.3 0.2 2.1
8 162.0 0.0 0.5 155.0 1.4 -0.5
9 146.8 0.5 1.6 139.8 0.3 -2.8
10 157.1 1.6 0.4 150.1 -1.7 -0.5
11 182.0 0.7 0.6 175.0 0.1 -0.9
12 145.2 3.4 0.4 139.3 -1.9 -0.4
13 144.6 -2.1 0.5 138.7 2.1 -0.5
14 144.8 0.6 1.3 138.8 0.1 -1.3
15 145.1 0.6 -0.5 139.1 0.1 0.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 177.6 - 177.6
M1 (kN.m) 0.7 3.1 0.0 200
M2 (kN.m) -0.6 -1.8 -3.2
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.092 Le1/b1 = 6.4 < 15.0 350
Beta = 0.89 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 1.0 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.65 / 0.82 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.02 N/mm2
Links = Y8-150

2C9 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 89.5 -0.2 0.3 82.6 0.4 0.4
2 79.3 3.1 0.2 72.4 -3.5 0.5
3 75.9 -0.3 5.0 69.0 0.5 -5.3
4 81.7 -2.5 0.2 74.8 3.1 0.5
5 73.3 -0.5 -4.4 66.3 0.7 5.6
6 89.5 -0.2 0.3 82.6 0.4 0.4
7 73.4 -0.3 -4.2 66.4 0.5 5.5
8 81.7 -2.5 0.2 74.8 3.1 0.5
9 73.3 -0.5 4.3 66.3 0.7 -4.3
10 79.3 3.1 0.2 72.4 -3.5 0.5
11 92.1 -0.3 0.9 85.2 0.4 -0.5
12 73.1 0.5 0.2 67.2 -0.8 0.4
13 72.9 -0.7 0.3 67.0 1.3 0.3
14 73.0 -0.1 0.7 67.0 0.3 -0.2
15 73.1 -0.1 -0.2 67.1 0.2 0.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 89.5 - 89.5
M1 (kN.m) 0.4 1.6 0.0 200
M2 (kN.m) 0.4 0.9 1.7
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.046 Le1/b1 = 6.2 < 15.0 350
Beta = 0.94 Le2/b2 = 10.1 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 3.3 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.68 / 0.79 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.06 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-10

1C10 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 232.2 0.6 1.3 225.3 0.3 -2.1
2 204.9 2.1 1.1 197.9 -2.5 -1.9
3 194.4 0.6 -0.8 187.4 0.3 1.9
4 208.7 -0.6 1.2 201.8 2.4 -2.0
5 200.8 0.4 2.6 193.8 0.4 -4.9
6 232.2 0.6 1.3 225.3 0.3 -2.1
7 200.0 0.5 2.6 193.1 0.4 -4.9
8 208.7 -0.6 1.2 201.8 2.4 -2.0
9 235.6 0.5 1.2 228.7 0.3 -1.9
10 204.9 2.1 1.1 197.9 -2.5 -1.9
11 191.7 0.6 -0.6 184.8 0.3 1.6
12 191.1 4.1 1.0 185.2 -2.5 -1.7
13 190.6 -3.1 1.1 184.7 2.8 -1.8
14 190.8 0.5 2.0 184.9 0.2 -2.5
15 190.9 0.5 0.1 185.0 0.2 -1.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 232.2 - 232.2
M1 (kN.m) 0.6 4.1 0.0 200
M2 (kN.m) -2.1 -2.3 -4.1
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.120 Le1/b1 = 6.4 < 15.0 350
Beta = 0.86 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 0.4 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.63 / 0.83 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.01 N/mm2
Links = Y8-150

2C10 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 98.2 0.1 4.2 91.3 -0.2 -5.1
2 86.9 4.4 3.7 80.0 -4.6 -4.5
3 79.1 -0.1 -3.0 72.1 -0.1 3.2
4 88.3 -3.5 3.9 81.4 3.4 -4.6
5 82.6 -0.3 8.9 75.7 0.2 -10.4
6 98.2 0.0 4.2 91.3 -0.2 -5.1
7 82.2 -0.1 8.9 75.2 0.0 -10.3
8 88.3 -3.5 3.9 81.4 3.4 -4.6
9 100.4 -0.1 3.8 93.4 0.0 -4.6
10 86.9 4.4 3.7 80.0 -4.6 -4.5
11 77.4 -0.1 -2.5 70.5 -0.1 2.5
12 80.1 0.8 3.4 74.1 -1.5 -4.1
13 79.9 -0.6 3.5 74.0 1.1 -4.2
14 80.0 0.0 3.9 74.1 -0.2 -4.7
15 80.0 0.1 3.0 74.1 -0.3 -3.7
Critical Combination:5 - ((G+Q)P22 *F)
Min Design
N (kN) 82.6 - 82.6
M1 (kN.m) -0.3 -1.4 0.0 200
M2 (kN.m) -10.4 -0.8 -11.2
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.043 Le1/b1 = 6.3 < 15.0 350
Beta = 0.95 Le2/b2 = 10.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 6.5 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.62 / 0.80 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.11 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-11

1C11 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 174.7 0.2 -1.4 167.8 0.0 4.3
2 155.9 0.3 -0.9 149.0 0.1 3.0
3 114.7 0.2 1.2 107.8 0.0 -1.4
4 159.9 0.1 -1.2 153.0 0.0 3.7
5 141.2 0.2 -3.0 134.3 0.0 7.4
6 174.7 0.2 -1.4 167.8 0.0 4.3
7 176.5 0.2 -1.6 169.6 0.0 4.7
8 159.9 0.2 -1.1 153.0 0.0 3.7
9 139.2 0.2 -2.9 132.3 0.0 7.1
10 155.9 0.3 -0.9 149.0 0.1 3.0
11 114.9 0.2 1.2 108.0 0.0 -1.4
12 142.6 1.4 -1.2 136.6 -0.5 3.6
13 142.5 -1.0 -1.0 136.6 0.5 3.5
14 143.1 0.2 1.3 137.1 0.0 1.8
15 142.0 0.2 -3.6 136.1 0.0 5.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 174.7 - 174.7
M1 (kN.m) 0.2 1.7 0.0 350
M2 (kN.m) 4.3 3.1 7.4
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.090 Le1/b1 = 11.7 < 15.0 200
Beta = 0.89 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.2 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.78 / 0.63 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.00 N/mm2
Links = Y8-150

2C11 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 90.8 0.0 -9.1 83.9 0.0 12.6
2 81.4 0.1 -6.8 74.4 0.0 9.7
3 58.2 0.0 2.4 51.2 0.0 -2.4
4 81.7 0.0 -7.4 74.7 0.0 9.8
5 74.4 0.0 -15.2 67.5 0.0 20.0
6 90.8 0.0 -9.2 83.9 0.0 12.6
7 91.8 0.0 -9.9 84.9 0.0 13.6
8 81.7 0.0 -7.3 74.8 0.0 9.8
9 73.2 0.0 -14.3 66.2 0.0 18.7
10 81.4 0.1 -6.8 74.4 0.0 9.7
11 58.3 0.0 2.2 51.4 0.0 -2.2
12 74.0 -0.4 -7.5 68.1 0.0 10.3
13 74.0 0.5 -7.4 68.1 0.0 10.1
14 74.2 0.0 -6.9 68.2 0.0 9.3
15 73.9 0.0 -7.9 67.9 0.0 11.1
Critical Combination:5 - ((G+Q)P22 *F)
Min Design
N (kN) 74.4 - 74.4
M1 (kN.m) 0.0 0.7 0.0 350
M2 (kN.m) 20.0 1.3 21.4
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.039 Le1/b1 = 11.1 < 15.0 200
Beta = 0.95 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 11.7 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.76 / 0.71 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.19 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-12

1C12 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 127.4 0.5 -1.2 120.4 -0.6 3.8
2 111.5 1.4 -1.3 104.5 -2.0 3.9
3 131.0 0.6 -1.4 124.1 -0.6 3.9
4 110.7 -0.3 -1.2 103.8 0.8 3.8
5 104.0 0.4 0.0 97.1 -0.5 1.3
6 127.4 0.5 -1.2 120.5 -0.6 3.8
7 127.1 0.5 -1.2 120.2 -0.6 3.8
8 110.7 -0.3 -1.2 103.8 0.7 3.8
9 104.3 0.4 0.0 97.3 -0.5 1.3
10 111.5 1.4 -1.3 104.5 -2.0 3.9
11 131.0 0.6 -1.4 124.1 -0.6 3.9
12 106.1 2.5 -1.0 100.1 -2.4 3.1
13 105.9 -1.6 -0.8 100.0 1.3 3.0
14 104.8 0.5 1.4 98.8 -0.5 1.7
15 107.2 0.4 -3.2 101.2 -0.5 4.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 127.4 - 127.4
M1 (kN.m) -0.6 -1.3 0.0 350
M2 (kN.m) 3.8 2.2 6.1
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.066 Le1/b1 = 10.5 < 15.0 200
Beta = 0.92 Le2/b2 = 6.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.1 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.80 / 0.62 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y8-150

2C12 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 43.8 1.0 -5.9 36.9 -1.0 6.8
2 38.3 3.1 -6.4 31.4 -2.9 7.4
3 46.2 1.0 -7.1 39.3 -1.0 8.7
4 38.0 -1.1 -6.3 31.1 1.0 7.3
5 32.2 0.8 -0.9 25.3 -0.7 0.3
6 43.8 1.0 -6.0 36.9 -1.0 6.8
7 43.6 1.0 -5.9 36.7 -0.9 6.7
8 38.0 -1.1 -6.2 31.1 0.9 7.3
9 32.4 0.8 -0.9 25.4 -0.7 0.4
10 38.3 3.1 -6.4 31.4 -2.9 7.4
11 46.2 1.0 -7.1 39.3 -1.0 8.7
12 35.9 1.8 -4.8 30.0 -1.9 5.5
13 35.9 -0.1 -4.8 29.9 0.3 5.4
14 35.6 0.8 -4.7 29.6 -0.8 4.9
15 36.3 0.9 -4.9 30.3 -0.9 6.1
Critical Combination:2 - ((G+Q)P11 *F)
Min Design
N (kN) 38.3 - 38.3
M1 (kN.m) 3.1 0.4 0.0 350
M2 (kN.m) 7.4 0.7 13.1
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.020 Le1/b1 = 10.0 < 15.0 200
Beta = 0.98 Le2/b2 = 7.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.0 / 4.6 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.76 / 0.65 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.04 / 0.07 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-13

1C13 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 62.1 1.4 0.0 55.2 -1.2 0.4
2 61.7 1.3 0.1 54.8 -1.2 0.4
3 61.5 1.3 0.0 54.6 -1.1 0.4
4 53.3 1.1 -0.1 46.4 -0.7 0.6
5 53.3 1.3 0.2 46.4 -1.4 0.1
6 62.2 1.3 0.0 55.2 -1.2 0.4
7 62.2 1.3 0.0 55.2 -1.2 0.4
8 53.3 1.1 -0.1 46.3 -0.7 0.6
9 53.4 1.3 0.2 46.5 -1.4 0.1
10 61.7 1.3 0.1 54.8 -1.2 0.4
11 61.3 1.3 0.0 54.4 -1.1 0.4
12 54.2 3.3 0.4 48.3 -2.4 0.0
13 50.7 -1.0 -0.3 44.8 0.4 0.7
14 51.0 1.2 0.9 45.1 -1.1 -0.4
15 53.9 1.1 -0.9 48.0 -0.9 1.0
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 62.1 - 62.1
M1 (kN.m) 1.4 1.1 2.5 200
M2 (kN.m) 0.4 0.6 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.032 Le1/b1 = 6.6 < 15.0 350
Beta = 0.96 Le2/b2 = 10.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.9 / 0.0 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.68 / 0.75 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.03 / 0.00 N/mm2
Links = Y8-150

2C13 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 19.2 2.1 -0.1 12.3 -2.2 -0.1
2 19.1 2.0 -0.1 12.1 -2.1 -0.2
3 19.0 1.8 -0.3 12.0 -1.9 0.1
4 16.3 1.3 -0.5 9.4 -1.5 0.2
5 16.0 2.2 0.3 9.1 -2.2 -0.4
6 19.3 2.1 -0.1 12.3 -2.2 -0.1
7 19.3 2.1 -0.1 12.4 -2.2 -0.1
8 16.3 1.4 -0.5 9.4 -1.5 0.3
9 16.2 2.2 0.3 9.2 -2.3 -0.5
10 19.1 2.0 -0.1 12.1 -2.1 -0.2
11 18.8 1.8 -0.3 11.9 -1.8 0.1
12 16.5 1.9 0.0 10.6 -2.4 -0.3
13 15.5 1.6 -0.3 9.6 -1.2 0.1
14 15.6 1.9 0.2 9.7 -1.9 -0.5
15 16.4 1.6 -0.4 10.5 -1.7 0.3
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 19.2 - 19.2
M1 (kN.m) -2.2 -0.3 -2.6 200
M2 (kN.m) -0.1 -0.2 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.010 Le1/b1 = 6.7 < 15.0 350
Beta = 0.99 Le2/b2 = 10.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 1.5 / 0.0 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.62 / 0.73 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.02 / 0.00 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-14

1C14 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 76.8 -0.9 0.7 69.9 3.5 -0.9
2 76.8 -1.0 0.6 69.9 3.5 -0.9
3 65.4 -0.8 0.4 58.5 3.2 -0.4
4 69.0 -0.5 0.6 62.1 2.5 -0.8
5 65.2 -1.0 0.8 58.3 3.3 -1.2
6 76.8 -0.9 0.7 69.8 3.5 -0.9
7 79.0 -1.0 0.7 72.1 3.5 -1.0
8 69.0 -0.5 0.6 62.1 2.5 -0.8
9 65.9 -0.9 0.4 58.9 3.3 -0.4
10 76.8 -1.0 0.6 69.9 3.5 -0.9
11 62.5 -0.8 0.7 55.6 3.2 -1.1
12 61.9 1.5 0.8 56.0 1.3 -0.9
13 66.0 -3.0 0.4 60.0 4.5 -0.6
14 64.4 -0.8 1.6 58.5 3.0 -1.7
15 63.4 -0.7 -0.4 57.5 2.9 0.2
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 76.8 - 76.8
M1 (kN.m) 3.5 1.3 5.1 200
M2 (kN.m) -0.9 -0.8 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.040 Le1/b1 = 6.6 < 15.0 350
Beta = 0.95 Le2/b2 = 10.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 0.6 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.61 / 0.77 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.01 N/mm2
Links = Y8-150

2C14 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 30.7 -4.0 1.2 23.7 2.9 -0.9
2 30.5 -4.1 1.2 23.6 3.0 -0.9
3 26.0 -3.7 0.4 19.1 2.7 -0.1
4 28.1 -2.7 1.0 21.2 1.8 -0.7
5 24.6 -3.8 1.7 17.7 2.6 -1.4
6 30.6 -4.0 1.2 23.7 2.9 -0.9
7 31.6 -4.1 1.3 24.7 3.0 -1.0
8 28.1 -2.7 1.0 21.2 1.7 -0.7
9 26.2 -3.7 0.5 19.3 2.7 -0.3
10 30.5 -4.1 1.2 23.6 3.0 -0.9
11 23.4 -3.6 1.5 16.5 2.5 -1.2
12 24.8 -3.0 1.1 18.8 1.6 -0.9
13 25.8 -3.7 1.0 19.9 3.1 -0.7
14 25.4 -3.3 1.7 19.5 2.4 -1.4
15 25.2 -3.4 0.4 19.2 2.4 -0.1
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 30.7 - 30.7
M1 (kN.m) -4.0 -0.5 -6.3 200
M2 (kN.m) 1.2 0.3 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 6.7 < 15.0 350
Beta = 0.98 Le2/b2 = 9.8 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.3 / 1.1 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.64 / 0.75 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.04 / 0.02 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-15

1C15 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 122.9 0.7 3.7 116.0 -1.0 -6.2
2 106.1 0.1 3.6 99.2 0.3 -6.1
3 114.6 0.8 3.9 107.7 -1.1 -6.9
4 122.8 0.7 3.6 115.9 -1.0 -6.2
5 97.5 0.8 2.0 90.6 -1.3 -3.0
6 123.0 0.7 3.6 116.1 -1.0 -6.2
7 97.1 0.9 2.1 90.1 -1.3 -3.0
8 122.7 0.7 3.6 115.8 -1.0 -6.2
9 113.2 0.7 3.9 106.3 -1.1 -6.8
10 106.1 0.1 3.6 99.2 0.3 -6.1
11 124.8 0.7 3.6 117.9 -1.0 -6.3
12 103.2 1.5 3.6 97.3 -1.5 -5.6
13 101.6 -0.4 2.5 95.7 0.0 -4.8
14 101.4 0.6 5.6 95.4 -0.8 -7.0
15 103.4 0.6 0.6 97.5 -0.7 -3.4
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 122.9 - 122.9
M1 (kN.m) -1.0 -1.2 0.0 350
M2 (kN.m) -6.2 -2.2 -8.4
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.064 Le1/b1 = 10.8 < 15.0 200
Beta = 0.92 Le2/b2 = 6.3 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.1 / 1.3 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.76 / 0.70 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.02 N/mm2
Links = Y8-150

2C15 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 42.9 2.4 8.8 36.0 -3.4 -7.8
2 35.1 0.3 8.7 28.1 -0.9 -7.6
3 40.0 2.5 9.7 33.0 -3.4 -8.7
4 43.0 2.5 8.7 36.1 -3.4 -7.7
5 32.9 2.8 3.9 26.0 -3.6 -2.9
6 43.0 2.4 8.8 36.1 -3.3 -7.8
7 32.7 2.9 4.1 25.8 -3.8 -3.1
8 42.9 2.5 8.7 36.0 -3.4 -7.7
9 39.3 2.5 9.6 32.3 -3.3 -8.6
10 35.1 0.3 8.7 28.1 -0.9 -7.6
11 43.9 2.4 8.6 36.9 -3.3 -7.7
12 35.4 2.2 7.4 29.5 -3.1 -6.6
13 35.0 1.6 7.2 29.1 -2.3 -6.2
14 34.9 2.0 7.9 29.0 -2.7 -7.4
15 35.5 1.9 6.7 29.6 -2.7 -5.4
Critical Combination:3 - ((G+Q)P12 *F)
Min Design
N (kN) 40.0 - 40.0
M1 (kN.m) -3.4 -0.4 0.0 350
M2 (kN.m) 9.7 0.7 15.9
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.021 Le1/b1 = 10.5 < 15.0 200
Beta = 0.98 Le2/b2 = 6.2 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.2 / 6.1 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.75 / 0.66 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.04 / 0.10 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-16

1C16 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 168.0 1.4 0.6 161.1 -2.4 0.1
2 146.9 0.6 0.6 140.0 -0.6 0.1
3 143.5 1.6 -1.2 136.6 -2.7 3.5
4 168.5 1.4 0.5 161.6 -2.4 0.1
5 144.4 1.5 2.2 137.4 -2.7 -3.4
6 168.0 1.4 0.6 161.1 -2.4 0.1
7 143.5 1.6 2.2 136.6 -2.7 -3.3
8 168.6 1.4 0.5 161.6 -2.4 0.1
9 169.0 1.4 0.6 162.1 -2.3 0.0
10 146.9 0.6 0.6 140.0 -0.6 0.1
11 143.3 1.6 -1.2 136.4 -2.7 3.5
12 141.8 2.4 1.0 135.8 -3.0 -0.3
13 138.9 -0.1 0.0 132.9 -1.0 0.5
14 140.3 1.2 3.0 134.4 -2.0 -1.6
15 140.3 1.2 -1.9 134.4 -2.0 1.8
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 168.0 - 168.0
M1 (kN.m) -2.4 -1.7 -3.7 350
M2 (kN.m) 0.6 2.9 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.087 Le1/b1 = 10.8 < 15.0 200
Beta = 0.90 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.3 / 0.2 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.79 / 0.71 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.01 / 0.00 N/mm2
Links = Y8-150

2C16 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 53.4 3.5 0.6 46.5 -3.4 -0.8
2 45.3 1.0 0.6 38.4 -1.0 -0.7
3 43.7 3.9 -4.8 36.8 -3.7 4.6
4 53.6 3.5 0.3 46.7 -3.3 -0.5
5 44.2 3.9 5.7 37.2 -3.7 -5.8
6 53.4 3.5 0.6 46.5 -3.4 -0.7
7 43.8 4.0 5.5 36.8 -3.8 -5.7
8 53.7 3.5 0.3 46.7 -3.4 -0.5
9 53.9 3.5 0.7 47.0 -3.3 -0.9
10 45.3 1.0 0.6 38.4 -1.0 -0.7
11 43.6 3.9 -4.8 36.7 -3.7 4.6
12 44.2 3.3 0.5 38.2 -3.3 -0.8
13 43.4 2.5 0.5 37.4 -2.2 -0.5
14 43.7 2.9 0.9 37.8 -2.8 -1.5
15 43.8 2.9 0.1 37.8 -2.8 0.2
Critical Combination:7 - ((G+Q)P32 *F)
Min Design
N (kN) 43.8 - 43.8
M1 (kN.m) 4.0 0.4 6.9 350
M2 (kN.m) -5.7 -0.8 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.023 Le1/b1 = 10.5 < 15.0 200
Beta = 0.97 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.6 / 3.8 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.77 / 0.67 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.05 / 0.06 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-17

1C17 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 159.4 1.1 1.1 152.4 -1.7 -0.9
2 139.5 0.3 1.1 132.6 0.0 -0.9
3 113.7 0.2 2.6 106.8 0.1 -4.3
4 160.6 1.0 1.0 153.7 -1.8 -0.9
5 136.5 1.3 -0.7 129.6 -2.2 2.6
6 159.4 1.1 1.1 152.4 -1.7 -0.9
7 160.6 1.1 1.0 153.7 -1.8 -0.8
8 160.6 1.0 1.0 153.7 -1.8 -0.9
9 135.2 1.3 -0.6 128.2 -2.1 2.5
10 139.5 0.3 1.1 132.6 0.0 -0.9
11 113.7 0.2 2.6 106.8 0.1 -4.3
12 133.1 2.3 1.5 127.2 -2.3 -1.2
13 132.0 -0.6 0.4 126.0 -0.3 -0.4
14 132.7 0.9 3.4 126.8 -1.4 -2.5
15 132.3 0.8 -1.5 126.4 -1.3 0.9
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 159.4 - 159.4
M1 (kN.m) -1.7 -1.6 -3.0 350
M2 (kN.m) 1.1 2.8 0.0
N-max (kN) 0.0
Concrete Cover = 25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.082 Le1/b1 = 10.8 < 15.0 200
Beta = 0.90 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 2.3 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.74 / 0.75 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.04 N/mm2
Links = Y8-150

2C17 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 56.0 4.1 1.9 49.1 -5.5 -1.7
2 46.8 1.3 1.8 39.8 -2.4 -1.7
3 36.6 0.6 6.5 29.7 -1.4 -6.4
4 56.8 4.0 1.6 49.9 -5.4 -1.4
5 47.2 4.8 -3.7 40.3 -6.2 3.9
6 56.0 4.1 1.8 49.1 -5.4 -1.7
7 56.7 4.1 1.5 49.8 -5.6 -1.4
8 56.8 4.0 1.6 49.9 -5.4 -1.5
9 46.5 4.7 -3.3 39.6 -6.1 3.5
10 46.8 1.3 1.8 39.8 -2.4 -1.7
11 36.6 0.6 6.5 29.7 -1.4 -6.3
12 46.0 3.4 1.6 40.1 -4.8 -1.5
13 45.7 3.1 1.5 39.8 -4.0 -1.3
14 45.9 3.3 2.0 40.0 -4.4 -2.3
15 45.8 3.2 1.1 39.9 -4.4 -0.5
Critical Combination:5 - ((G+Q)P22 *F)
Min Design
N (kN) 47.2 - 47.2
M1 (kN.m) -6.2 -0.5 -8.2 350
M2 (kN.m) 3.9 0.8 0.0
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.024 Le1/b1 = 10.5 < 15.0 200
Beta = 0.97 Le2/b2 = 6.6 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 3.7 / 4.3 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.76 / 0.65 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.07 / 0.07 N/mm2
Links = Y8-150

Project: ProposedTwoStoreyResidential
Proposed Two Storey Residential w/ Roof Deck None (*1ZH-579V-9HGG-KYGA)
COLUMN REINFORCEMENT DESIGN Orion Building Design System 18.0 (04.2012) / Page: CD-18

1C18 Storey: 1 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 98.2 1.4 -4.1 91.2 -2.3 9.9
2 83.7 0.9 -4.1 76.7 -1.0 9.9
3 99.3 1.4 -4.4 92.4 -2.3 10.0
4 99.3 1.3 -4.2 92.3 -2.5 9.8
5 74.8 1.5 -2.4 67.9 -2.6 6.1
6 98.2 1.4 -4.1 91.3 -2.3 9.9
7 98.1 1.4 -4.1 91.2 -2.3 9.9
8 99.2 1.3 -4.2 92.3 -2.5 9.8
9 74.9 1.5 -2.4 68.0 -2.6 6.1
10 83.7 0.9 -4.1 76.7 -1.0 9.9
11 99.3 1.4 -4.3 92.4 -2.3 10.0
12 83.7 3.0 -3.0 77.8 -3.3 8.0
13 81.0 -0.6 -4.0 75.1 -0.6 8.6
14 81.5 1.2 -1.2 75.5 -2.0 7.0
15 83.3 1.1 -5.7 77.3 -1.9 9.6
Critical Combination:1 - (G+Q *F)
Min Design
N (kN) 98.2 - 98.2
M1 (kN.m) -2.3 -1.0 0.0 350
M2 (kN.m) 9.9 1.7 14.1
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.051 Le1/b1 = 10.8 < 15.0 200
Beta = 0.94 Le2/b2 = 6.9 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 0.0 / 4.7 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.74 / 0.70 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.00 / 0.08 N/mm2
Links = Y8-150

2C18 Storey: 2 (Con.:C27.6/30 / Steel:Grade 410 (Type 2))


Loadings (Combination):
No N (Bot) M1 (Bot) M2 (Bot) N (Top) M1 (Top) M2 (Top)
1 30.6 3.0 -11.8 23.7 -2.4 9.4
2 25.7 1.5 -11.8 18.8 -1.1 9.4
3 31.1 3.0 -12.4 24.2 -2.4 10.0
4 31.0 3.0 -12.0 24.1 -2.3 9.6
5 21.5 3.4 -6.1 14.6 -2.8 3.6
6 30.6 3.0 -11.8 23.7 -2.4 9.4
7 30.6 3.0 -11.8 23.6 -2.4 9.4
8 31.0 3.0 -12.0 24.1 -2.4 9.6
9 21.6 3.4 -6.1 14.6 -2.8 3.5
10 25.7 1.5 -11.8 18.8 -1.1 9.4
11 31.2 3.0 -12.4 24.2 -2.4 10.0
12 25.7 2.9 -9.9 19.7 -2.7 7.6
13 24.9 2.1 -9.8 19.0 -1.3 7.8
14 25.0 2.5 -9.9 19.1 -2.0 7.2
15 25.6 2.6 -9.8 19.6 -2.0 8.2
Critical Combination:11 - ((G+Q)P52 *F)
Min Design
N (kN) 31.2 - 31.2
M1 (kN.m) 3.0 0.3 0.0 350
M2 (kN.m) -12.4 -0.5 -18.1
N-max (kN) 0.0
Concrete Cover =25.0 mm
BS8110-Cl.3.8.4.5 Short Column...
N/bhFcu = 0.016 Le1/b1 = 10.5 < 15.0 200
Beta = 0.98 Le2/b2 = 7.4 < 15.0
M-add(1/2)= 0.0 / 0.0 kN.m
Vd(1/2)= 2.1 / 7.1 kN As (Required): %0.40 (min) 280.00 mm2 6Y13
vc'(1/2)= 0.75 / 0.64 N/mm2 As (Provided): %1.14 796.39 mm2
v (1/2)= 0.04 / 0.11 N/mm2
Links = Y8-150