Vous êtes sur la page 1sur 2

WORK SHEET

MIX DESIGN SUBMISSION (revision)


No.Mix design sub: JMX/ W1001534/MIX/XII-2019
Client : Waringin Megah,PT Date : 12-Dec-2019

Attn. : Puji,Mr Project : Taruma City Jalan Tuparev Karawang

Fax/Telp :

We present the following mix design for your consideration

GRADE ( N/mm2 ) FC'25 FC'30 FC'35

WATER CEMENTITIOUS RATIO 0,48 0,44 0,38

NOMINAL SLUMP (Cm) 12 ± 2 12 ± 2 12 ± 2

CEMENT CONTENT (Kg/m3) 330 360 416

FLY ASH CONTENT (Kg/m3) 10 % 38 40 48

NOMINAL WATER (Lt/m3) 176 176 176

ADMIXTURE 1 : RETARDER (%) 0.20 – 0.90 0.20 – 0.90 0.20 – 0.90

ADMIXTURE 2 : SUPERPLAST ( L/m³ ) 0,00 0,00 0,00

COARSE AGGREGATE (Kg/m³) 850 860 870

FINE AGGREGATE (Kg/m3) 970 930 870


Note :
1. The batch weights are in Kilogram per cubic meter.
2. Yield measurements should meet the requirements of ASTM.
3. All batch weights are assumed saturated surface dry.
4. Admixture dosage rate
a) CC per 100 kg of cement material.
b) Liter per cubic meter or
c) Milliliters per cubic meter of supply.
d) kg or gram per cubic meter of supply
5. Aggregates - Splits & Fine depend on Quality limits at time of supply.
6. Cementitious content may include cement, fly ash or silica fume, pending requirements.
The above mixes will comply with all the current requirements of ACI provided all aspects of sampling
preparation and testing is carried out in accordance with current editions of ASTM.
The mixes are subject to proportion changes depend on material & site performance at the time of supply
Your Faithfully, Acknowledge by
Waringin Megah,PT

for
Somkriat Petchsom Puji,Mr
Tech Manager

No.Doc.WS-TSE-03-00-01 Rev 0 Date : 16 Juni 2014 Page 1 of 1

[Type text]
WORK SHEET
MIX DESIGN SUBMISSION (revision)
No.Mix design sub: JMX/ W1001536/MIX/XII-2019
Client : Waringin Megah,PT Date : 12-Dec-2019

Attn. : Puji,Mr Project : Taruma City Jalan Tuparev Karawang

Fax/Telp :

We present the following mix design for your consideration

GRADE ( N/mm2 ) FC'30 INT FC'35 INT

WATER CEMENTITIOUS RATIO 0,43 0,37

NOMINAL SLUMP (Cm) 10 ± 2 10 ± 2

CEMENT CONTENT (Kg/m3) 360 416

FLY ASH CONTENT (Kg/m3) 10 % 40 48

NOMINAL WATER (Lt/m3) 170 170

ADMIXTURE 1 : RETARDER (%) 0.20 – 0.90 0.20 – 0.90

ADMIXTURE 2 : SUPERPLAST ( L/m³ ) 0,00 0,00

COARSE AGGREGATE (Kg/m³) 870 880

FINE AGGREGATE (Kg/m3) 940 880


Note : *)INTEGRAL WATER PROOFING BY APPLICATOR
1. The batch weights are in Kilogram per cubic meter.
2. Yield measurements should meet the requirements of ASTM.
3. All batch weights are assumed saturated surface dry.
4. Admixture dosage rate
a) CC per 100 kg of cement material.
b) Liter per cubic meter or
c) Milliliters per cubic meter of supply.
d) kg or gram per cubic meter of supply
5. Aggregates - Splits & Fine depend on Quality limits at time of supply.
6. Cementitious content may include cement, fly ash or silica fume, pending requirements.
The above mixes will comply with all the current requirements of ACI provided all aspects of sampling
preparation and testing is carried out in accordance with current editions of ASTM.
The mixes are subject to proportion changes depend on material & site performance at the time of supply
Your Faithfully, Acknowledge by
Waringin Megah,PT

for
Somkriat Petchsom Puji,Mr
Tech Manager

No.Doc.WS-TSE-03-00-01 Rev 0 Date : 16 Juni 2014 Page 1 of 1