NOOITGEDACHT
1719
A water sample was submitted to Aquatico Laboratories on 29 July 2019 for testing the quality for
intended use as domestic water. The water quality test results are displayed on the attached Test
Report. Water quality is compared to the SANS 241-1:2015 Drinking Water Standard (SABS, 2015).
The water quality of the sample called 'Borehole 1' can be described as neutral (pH 6.0 - 8.5), saline
(TDS 450 - 1000 mg/l) and very hard (total hardness > 300 CaCO 3) with no E.coli and no total
coliforms detected.
Compliance with the 'SANS 241-1:2015 Drinking Water Standard (SABS, 2015)' guidelines is as
follows:
In terms of the classification system of the 'Quality of Domestic water supplies' (WRC,1998) the
quality is classified as follows:
According to the Langelier Saturation Index, slight corrosion is possible but the water is non-scale
forming.
Based on the assessment of variables analysed in comparison to 'SANS 241-1:2015 Drinking Water
Standard (SABS, 2015)' and 'Quality of Domestic water supplies' (WRC, 1998), the tested water
sample is Not Fit for use as potable water and domestic use.
DATA TABLE
Electrical conductivity (EC) @ 25°C mS/m 170 134 Insignificant effect on sensitive users
Manganese (Mn) mg/l 0.1 0.773 Slight health effects in sensitive users only
Temperature °C - 19.6
123 COPPERHOUSE RD
NOOITGEDACHT
1719
A water sample was submitted to Aquatico Laboratories on 29 July 2019 for testing the quality for
intended use as domestic water. The water quality test results are displayed on the attached Test
Report. Water quality is compared to the SANS 241-1:2015 Drinking Water Standard (SABS, 2015).
The water quality of the sample called 'Borehole 2' can be described as neutral (pH 6.0 - 8.5), very-
saline (TDS 1000 - 2400 mg/l) and moderately hard (total hardness 150 - 200 CaCO3) with no E.coli
and no total coliforms detected.
Compliance with the 'SANS 241-1:2015 Drinking Water Standard (SABS, 2015)' guidelines is as
follows:
Chronic health Risk: Mn 0.570 mg/l (> 0.400 mg/l ), TOC 169 mg/l (> 10.0 mg/l )
Acute health Risk: All compliant
Operational (non-health): All compliant
Aesthetic (non-health): NH4-N 25.4 mg/l (> 1.50 mg/l ), Na 309 mg/l (> 200 mg/l )
Mn 0.570 mg/l (> 0.100 mg/l )
In terms of the classification system of the 'Quality of Domestic water supplies' (WRC,1998) the
quality is classified as follows:
According to the Langelier Saturation Index, the water is slightly scale forming and corrosive.
Based on the assessment of variables analysed in comparison to 'SANS 241-1:2015 Drinking Water
Standard (SABS, 2015)' and 'Quality of Domestic water supplies' (WRC, 1998), the tested water
sample is Not Fit for use as potable water and domestic use.
DATA TABLE
Sodium (Na) mg/l 200 309 Slight risk to some sensitive users
Manganese (Mn) mg/l 0.1 0.570 Slight health effects in sensitive users only
Temperature °C - 20.0
511 COMMISSIONER ST
BOKSBURG EAST
GATE 1 SIDING ROAD
A water sample was submitted to Aquatico Laboratories on 19 August 2019 for testing the quality for
intended use as domestic water. The water quality test results are displayed on the attached Test
Report. Water quality is compared to the SANS 241-1:2015 Drinking Water Standard (SABS, 2015).
The water quality of the sample called 'Ceoco 1' can be described as neutral (pH 6.0 - 8.5), non-saline
(TDS < 450 mg/l) and moderately soft (total hardness 50 - 100 CaCO3) with no E. coli and no total
coliforms detected.
Compliance with the 'SANS 241-1:2015 Drinking Water Standard (SABS, 2015)' guidelines is as
follows:
In terms of the classification system of the 'Quality of Domestic water supplies' (WRC,1998) the quality
is classified as follows:
According to the Langelier Saturation Index, slight corrosion is possible but the water is non-scale
forming.
Based on the assessment of variables analysed in comparison to 'SANS 241-1:2015 Drinking Water
Standard (SABS, 2015)' and 'Quality of Domestic water supplies' (WRC, 1998), the tested water sample
is Fit for use as potable water and domestic use.
DATA TABLE
CLIENT NAME Central Edible Oil Pty Ltd DATE COMPILED 2019-08-27
SANS 241-1:2015 Drinking
ASSESSMENT SET COMPILED BY Rolien Visser
Water Standard (SABS, 2015)
*Value exceeds the assessment set
ASSESSMENT SAMPLE NAME :
VARIABLE UNITS POSSIBLE HEALTH EFFECTS
SET Ceoco 1
pH @ 25°C pH Range 5.0 - 9.7 8.43 No health effects
Aquatico sampled: No No
Sample type: Uncertainty Water Water
SANS 241-
of measure-
1:2015
ment %
Locality description:
Borehole 1 Borehole 2
Analyses
Unit Method
A pH @ 25°C pH ALM 20 4.23 5 - 9.7 6.86 7.46
A Electrical conductivity (EC) @ 25°C mS/m ALM 20 9.52 < 170 134 162
A Total dissolved solids (TDS) mg/l ALM 26 < 1200 865 1098
A Total alkalinity mg CaCO3/l ALM 01 10.41 522 894
A Chloride (Cl) mg/l ALM 02 11.39 < 300 64.0 53.4
A Sulphate (SO₄) mg/l ALM 03 9.39 < 500 182 66.5
A Nitrate (NO₃) as N mg/l ALM 06 9.85 < 11 <0.194 <0.194
A Ammonium (NH₄) as N mg/l ALM 05 8.59 < 1.5 19.8 25.4
A Orthophosphate (PO₄) as P mg/l ALM 04 6.42 <0.005 0.105
A Fluoride (F) mg/l ALM 08 10.11 < 1.5 0.321 0.345
A Calcium (Ca) mg/l ALM 30 8.78 88.4 43.1
A Magnesium (Mg) mg/l ALM 30 7.54 29.0 18.6
A Sodium (Na) mg/l ALM 30 7.96 < 200 133 309
A Potassium (K) mg/l ALM 30 12.05 23.4 29.1
A Aluminium (Al) mg/l ALM 31 8.59 < 0.3 <0.002 <0.002
A Iron (Fe) mg/l ALM 31 7.97 < 0.3 0.473 <0.004
A Manganese (Mn) mg/l ALM 31 8 < 0.1 0.773 0.570
A Chromium (Cr) mg/l ALM 31 7.61 < 0.05 <0.003 <0.003
A Copper (Cu) mg/l ALM 31 4.55 <2 <0.002 <0.002
A Nickel (Ni) mg/l ALM 31 7.56 < 0.07 <0.002 <0.002
A Zinc (Zn) mg/l ALM 31 9.31 <5 <0.002 <0.002
A Cobalt (Co) mg/l ALM 31 7.94 <0.003 <0.003
A Cadmium (Cd) mg/l ALM 31 7.89 < 0.003 <0.002 <0.002
A Lead (Pb) mg/l ALM 31 8.85 < 0.01 <0.004 <0.004
A E.coli CFU/100ml ALM 40 7.74 0 <1 <1
A Total coliform CFU/100ml ALM 40 7.76 < 10 <1 <1
A Total hardness mg CaCO3/l ALM 26 340 184
A Total organic carbon (TOC) mg/l ALM 63 6.46 < 10 4.61 169
A = Accredited N = Non accredited Out = Outsourced Sub = Sub-contracted NR = Not requested RTF = Results to follow NATD = Not able to determine ATR = Alterna/ve
test report ; The results relates only to the test item tested; Results reported against the limit of detection; Results marked 'Non SANAS Accredited' in this report
are not included in the SANAS Schedule of Accreditation for this laboratory; Uncertainty of measurement available on request for all methods included in the
SANAS Schedule of Accreditation; The report shall not be reproduced except in full without approval of the laboratory
The results apply to the sample received.
www.aquatico.co.za 89 Regency Drive, R21 Corporate Park, Centurion, South Africa Tel: +27 12 450 3800 Fax: +27 12 450 3851
Test Report Page 2 of 2
Aquatico sampled: No No
Sample type: Uncertainty Water Water
SANS 241-
of measure-
1:2015
ment %
Locality description:
Borehole 1 Borehole 2
Analyses
Unit Method
A Langelier Saturation Index LSI ALM 26 -0.47 0.05
N Temperature °C ALM 20 19.6 20.0
A = Accredited N = Non accredited Out = Outsourced Sub = Sub-contracted NR = Not requested RTF = Results to follow NATD = Not able to determine ATR = Alterna/ve
test report ; The results relates only to the test item tested; Results reported against the limit of detection; Results marked 'Non SANAS Accredited' in this report
are not included in the SANAS Schedule of Accreditation for this laboratory; Uncertainty of measurement available on request for all methods included in the
SANAS Schedule of Accreditation; The report shall not be reproduced except in full without approval of the laboratory
The results apply to the sample received. Authenticated signature on first page
www.aquatico.co.za 89 Regency Drive, R21 Corporate Park, Centurion, South Africa Tel: +27 12 450 3800 Fax: +27 12 450 3851
Test Report Page 1 of 1
Client: Central Edible Oil Pty Ltd Date of certificate: 23 August 2019
Address: 511 Commissioner St, Boksburg East, Gate 1 Siding Road, 1459 Date accepted: 19 August 2019
Report no: 73183 Date completed: 23 August 2019
Project: Central Edible Oil Date received: 19 August 2019
Aquatico sampled: No
Sample type: Uncertainty Water
SANS 241-
of measure-
1:2015
ment %
Locality description:
Ceoco 1
Analyses
Unit Method
A pH @ 25°C pH ALM 20 4.23 5 - 9.7 8.43
A Electrical conductivity (EC) @ 25°C mS/m ALM 20 9.52 < 170 19.0
A Total dissolved solids (TDS) mg/l ALM 26 < 1200 125
A Total alkalinity mg CaCO3/l ALM 01 10.41 90.1
A Chloride (Cl) mg/l ALM 02 11.39 < 300 10.9
A Sulphate (SO₄) mg/l ALM 03 9.39 < 500 12.8
A Nitrate (NO₃) as N mg/l ALM 06 9.85 < 11 0.656
A Ammonium (NH₄) as N mg/l ALM 05 8.59 < 1.5 0.902
A Fluoride (F) mg/l ALM 08 10.11 < 1.5 <0.263
A Calcium (Ca) mg/l ALM 30 8.78 22.5
A Magnesium (Mg) mg/l ALM 30 7.54 6.95
A Sodium (Na) mg/l ALM 30 7.96 < 200 9.36
A Potassium (K) mg/l ALM 30 12.05 3.07
A Aluminium (Al) mg/l ALM 31 8.59 < 0.3 <0.002
A Iron (Fe) mg/l ALM 31 7.97 < 0.3 <0.004
A Manganese (Mn) mg/l ALM 31 8 < 0.1 0.001
A Chromium (Cr) mg/l ALM 31 7.61 < 0.05 <0.003
A Copper (Cu) mg/l ALM 31 4.55 <2 <0.002
A Nickel (Ni) mg/l ALM 31 7.56 < 0.07 <0.002
A Zinc (Zn) mg/l ALM 31 9.31 <5 0.082
A Cadmium (Cd) mg/l ALM 31 7.89 < 0.003 <0.002
A Lead (Pb) mg/l ALM 31 8.85 < 0.01 <0.004
A E.coli CFU/100ml ALM 40 7.74 0 <1
A Total coliform CFU/100ml ALM 40 7.76 < 10 <1
A Turbidity NTU ALM 21 7.63 <1 0.263
A Total hardness mg CaCO3/l ALM 26 85
A Total organic carbon (TOC) mg/l ALM 63 6.46 < 10 3.34
A Langelier Saturation Index LSI ALM 26 -0.17
A = Accredited N = Non accredited Out = Outsourced Sub = Sub-contracted NR = Not requested RTF = Results to follow NATD = Not able to determine ATR = Alterna0ve
test report ; The results relates only to the test item tested; Results reported against the limit of detection; Results marked 'Non SANAS Accredited' in this report
are not included in the SANAS Schedule of Accreditation for this laboratory; Uncertainty of measurement available on request for all methods included in the
SANAS Schedule of Accreditation; The report shall not be reproduced except in full without approval of the laboratory
The results apply to the sample received.