1. Working Space around Indoor Panel/Circuit Board (NES 312.2)
2. Clearance around an Indoor electrical panel (NEC 110.26)
3. Clearance for Conductor Entering in Panel (NES 408.5)
4. Clearance between Bare Metal Busbar in Panel (NES 408.5)
5. Clearance of Outdoor electrical panel to Fence/Wall (NES 110.31)
6. Working Space around Indoor Panel/Circuit Board (NES 110.34)
7. Clearance around an Outdoor electrical panel (NES 110.31)
8. Elevation of Unguarded Live Parts above Working Space (NES 110.34E)
9. Working Space for Panel (Code Georgia Power Company)
Go to Content ↑
Opposite Opposite
Polarity Polarity Where Live Parts to
Voltage
Mounted on Held Free in Ground
Same Surface Air
Up to 125 V 19.1 mm 12.7 mm 12.7 mm
125 V to 250
31.8 mm 19.1 mm 12.7 mm
V
250 V to 600
50.8 mm 25.4 mm 25.4 mm
V
Go to Content ↑
Exposed live
Exposed live
parts to Exposed live
parts to Not live
Voltage Grounded parts parts on both
parts (or
(concrete/brick/ sides
grounded parts)
walls)
601 V to 2.5 KV 0.914 Meter (3 Ft) 1.2 Meter (4 Ft) 1.5 Meter (5 Ft)
2.5 KV to 9.0
1.2 Meter (4 Ft) 1.5 Meter (5 Ft) 1.8 Meter (6 Ft)
KV
9.0 KV to 25 KV 1.5 Meter (5 Ft) 1.8 Meter (6 Ft) 2.5 Meter (8 Ft)
25 KV to 75 KV 1.8 Meter (6 Ft) 2.5 Meter (8 Ft) 3.0 Meter (10 Ft)
Above 75 KV 2.5 Meter (8 Ft) 3.0 Meter (10 Ft) 3.7 Meter (12 Ft)