MAKING MODERN LIVING POSSIBLE

Transcritical Refrigeration Systems


with Carbon Dioxide (CO2)
How to design and operate a small-capacity
(< 10 kW) transcritical CO2 system

REFRIGERATION &
aIR CONDITIONING DIVISION Article
Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Contents Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Carbon dioxide - System basics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


Properties of carbon dioxide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Transcritical cycle process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Effect of gas cooler pressure on system performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
System design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

System components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Expansion device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Gas cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Lubricant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Filter drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Safety components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

System handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Refrigerant grades . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Evacuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Charging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Material compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Water in CO2 systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Safety and design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19


Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Safety standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Introduction The purpose of this guide is to provide


the background for understanding how to
design and operate a small-capacity (<10 kW)
transcritical carbon dioxide (CO2) system.

Q GC
Pressure

3 2

4 1 W
Specific enthalpy

QE

 Danfoss A/S (RA Marketing/MWA), July 2008 DKRCI.PZ.000.F1.02 / 520H3002 3


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Carbon dioxide - System basics


Properties of Carbon dioxide (CO2) is a natural substance that above the natural level in atmospheric air, it will
carbon dioxide plays an important role in many natural and cause the human breathing rate to increase. It
industrial processes. In nature, carbon dioxide is heavier than air, so if large quantities escape
plays a role in photosynthesis in plants and is one in a closed room the highest concentrations will
of the most important contributors to the global typically be found close to the floor.
warming effect. In industry, carbon dioxide is
used as dry ice for transport cooling, to generate When carbon dioxide is used as a refrigerant it
the sparkling effect in some beverages, and as a is often referred to by its refrigerant number -
protection. which is R744.

It is odourless, non-flammable, and non-toxic,


but if the concentration of carbon dioxide rises

1000
800
600 Solid Liquid Fluid
400
(Supercritical)
200

100
80
Pressure [bar]

60
40
Criticalpoint
Critical point
20
(31.0°C,
(31.0 °C , 73.8
73.8 bar)
bar)

10
8 Vapour
6
4
Triplepoint
Triple point
2
(-56.6°C,
(-56.6 °C , 5.2 bar)
1
-80 -70 -60 -50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100
Temperature [°C]
Figure 1: Phase diagram for R-744

Figure 1 shows a phase diagram of R744. The marks the upper limit for heat transfer processes
three well-known phases: solid, liquid and vapour based on evaporation or condensation.
are shown as coloured areas. A phase change
occurs when a process crosses a boundary At temperatures and pressures higher than those
between areas - like evaporation or condensation at the critical point, no clear distinction can be
for a process crossing the boundary between drawn between what is called liquid and what is
liquid and vapour phases. At the boundaries, the called vapour. Thus there is a region extending
two phases exist in equilibrium, and properties, indefinitely upward from, and indefinitely to
such as temperature and pressure, become the right of, the critical point –and this region
dependent. The boundary line between liquid is called the fluid region. The fluid region is
and vapour are often referred to as the vapour bounded by dashed lines that do not represent
pressure curve. phase changes, but which conform to arbitrary
definitions of what is considered a liquid and
Two important state points are marked in the what is considered vapour [1]. A condition in
figure: the triple point and the critical point. the fluid region is referred to as a supercritical
The triple point represents the condition where condition – or very often also as a gas condition.
all three phases can co-exist in equilibrium. At
temperatures below the triple point temperature, All substances have a triple point and a critical
liquid can not exist - in other words the triple point - but for most of the substances used as
point temperature sets the lower temperature refrigerants, the triple point and critical point are
limit for any heat transfer process based on found for conditions that lie outside the region
evaporation or condensation. At the other end where they are normally used.
of the vapour pressure curve, the critical point
 Danfoss A/S (RA Marketing/MWA), July 2008 DKRCI.PZ.000.F1.02 / 520H3002 5
Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Properties of The term “critical point” has been the cause of conditions close to this state point with specific
carbon dioxide misunderstandings as the word “critical” today danger. Instead, the term “critical” should be
(continued) often is used in the sense of “dangerous” or interpreted as “difficult” - describing e.g. practical
“serious”. Its use to describe a specific state point problems related to distinguishing between
of a substance can therefore incorrectly associate liquid and vapour at conditions close to - or at -
the use of this substance (e.g. as refrigerant) at this state point.

Critical pressure Critical temperature


Refrigerant
[bar] [°C]
R22 49.9 96.1
R134a 40.6 101.1
R404A 37.3 72.0
R410A 49.0 71.4
R600a (Isobutane) 36.4 134.7
R717 (Ammonia) 113.3 132.3
R744 (Carbon dioxide) 73.8 31.0
Table 1: Critical properties of selected refrigerants

Table 1 compares the critical pressure and much lower than necessary for rejecting heat
temperature of a number of refrigerants. to the atmosphere for many refrigeration
Typically, refrigerants have critical temperatures applications. Considering the temperature
above 90°C but some of the refrigerants often difference needed in the heat exchanger,
used today (e.g. R404A, R410A and R744) have a practical upper limit for a heat rejection
critical temperatures below that. process based on condensation is reached
at temperatures 5 to 10 K below the critical
For R134a the critical temperature is found to be temperature.
101.1°C. This means that for R134a heat rejection
processes by condensation can be established For many refrigeration applications, the ambient
at temperatures up to 101.1°C. This temperature temperature will exceed a level of 25°C, making
is higher than necessary for rejecting heat to it practically impossible to reject heat by
the atmosphere for almost all refrigeration condensing carbon dioxide. However, this doesn’t
applications. mean that carbon dioxide cannot be used as a
refrigerant in these applications. Carbon dioxide
For R744 the critical temperature is only 31.0°C. can indeed be used as a refrigerant for these
This means that for R744 heat rejection process applications - but the heat rejection process from
by condensation can only be established at these applications must be based on a different
temperatures up to 31°C. This temperature is process than condensation.

Transcritical cycle process

Gas cooling
3 2
Pressure (logarithmic scale)
Pressure (logarithmic scale)

CP CP
3 2
Condensation
Expansion Compression

Expansion Compression

4 1 4 1
Evaporation Evaporation

Specific enthalpy Specific enthalpy

Figure 2: Subcritical and transcritical refrigeration cycle processes

Figure 2 shows two refrigeration cycle processes: a process is referred to as a subcritical cycle
one where the pressure in all parts of the process process. The subcritical cycle process is the well-
is kept below the critical pressure and one where known traditional refrigeration cycle process.
the pressure during the heat rejection process is When parts of the cycle process take place at
kept above the critical pressure. pressures above the critical point and other parts
below the critical pressure the cycle process is
Since the pressure in all parts of the first cycle referred to as transcritical cycle process.
process is below the critical pressure, such
6 DKRCI.PZ.000.F1.02 / 520H3002  Danfoss A/S (RA Marketing/MWA), July 2008
Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Transcritical cycle process The terminology used for describing the Figure 3 shows a more detailed pressure-
(continued) processes and components are almost the same enthalpy diagram with a simple one-stage
for the two cycle processes except for the heat transcritical cycle process. The critical point is
rejection parts. In the transcritical cycle process, marked in the figure with a yellow dot. Colour
the heat rejection takes place at pressures and (green and dark green) is used to indicate phases
temperatures above the critical point – that is, in and transitions between them. The supercritical
the fluid region. A condition in the fluid region fluid region (gas) is coloured light green.
is often referred to as a gas condition. For the System components have been included, and
transcritical cycle process, the heat rejection is coloured according to the change of state for the
therefore called gas cooling and subsequently refrigerant as it passes through them.
the heat exchanger used is called a gas cooler.

Q GC
GASCOOLER
GAS COOLER

3 2
Pressure

Compressor
C OMPRESSOR

E Expansion
XPANSION
valve
VALVE

4 1 W
Specific enthalpy

Evaporator
EVAPORATOR

QE
Figure 3: Transcritical cycle process & main system components

The transcritical cycle process begins with a one- The flow of heat and work is marked in the figure
stage compression from state point 1 to 2. with arrows. The evaporator heat transfer rate is
During this process, the temperature rises QE and the compressor power consumption is
significantly – and, for carbon dioxide, can reach W. The heat transfer rate in the gas cooler is QGC
a level of 130°C. - and ideally the energy balance gives QGC = QE +
W.
The heat rejection process from state point 2 to
3 occurs at constant pressure above the critical Specifying the operating conditions of a
point. The temperature during this process varies transcritical refrigeration cycle is different than
continuously from the inlet temperature (at state for subcritical cycle processes. For subcritical
point 2) to the outlet temperature (at state point processes, it is normally only necessary to specify
3). evaporating and condensing temperatures – and
if more details are needed – also superheat and
The expansion process from state point 3 to 4 subcooling.
occurs at constant specific enthalpy. The inlet
condition is supercritical (above the critical point)
and the outlet is two-phase (mixture of liquid and
vapour).

The heat absorption process (evaporation) from


state point 4 to 1 occurs at constant pressure,
and the evaporation part also at constant
temperature. The outlet condition (compressor
inlet condition) is slightly superheated.

 Danfoss A/S (RA Marketing/MWA), July 2008 DKRCI.PZ.000.F1.02 / 520H3002 7


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Transcritical cycle process


(continued)
t GC ,OUT Outlet temperature
Gas cooler pressure from gas cooler
pGC 3
2

CP

Pressure (logarithmic scale) tE


1
4
Evaporation
temperature

Specific enthalpy
Figure 4: Pressure-Enthalpy Diagram for a transcritical refrigeration cycle process

Figure 4 shows a pressure-enthalpy diagram with do not apply. Instead, the outlet condition of
a simple transcritical cycle process. Specifying the gas cooler (state point 3) must be specified
the evaporating process is done the same way as directly using temperature and pressure. In
for subcritical processes, using the evaporating figure 4 the isotherm labelled tGC,OUT represents
temperature and superheat. In figure 4, the the temperature of the refrigerant after the heat
isotherm labelled tE represents the evaporating rejection. In addition to specifying tGC,OUT the gas
temperature. cooler pressure pGC must also be specified. The
intersection between the isotherm tGC,OUT and the
For the transcritical cycle process, there is no isobar pGC identifies the outlet condition (state
condensing process and consequently the point 3).
terms condensing temperature and subcooling

Effect of gas cooler pressure The operation of a transcritical refrigeration In a simple system without receiver the answer
on system performance system using R744 is, in many respects, different is: the refrigerant charge. In a system with a fixed
from the operation of a subcritical refrigeration restriction expansion device (e.g. capillary tube),
system using a traditional refrigerant such as the pressure in the gas cooler will depend on
R134a. how much refrigerant the system is charged with
and its distribution between the components.
In the subcritical refrigeration cycle process, the Having concluded that it is the charge of
heat rejection process involves condensing of the refrigerant that determine the gas cooler
refrigerant. A large part of the condenser volume pressure, the obvious next question must be:
on the refrigerant side will therefore be occupied Does the gas cooler pressure have an influence
by a two-phase mixture of liquid and vapour. For on capacity and energy efficiency of the system?
a two-phase mixture in thermal equilibrium, the
pressure will be the saturation pressure at the Figure 5 illustrates how the gas cooler pressure
temperature of the mixture. influences the cycle process. In the figure three
different cycle processes are represented. They all
For a transcritical process, the heat rejection have the same evaporating temperature, same
process does not involve condensing but only evaporator outlet/compressor inlet condition
cooling of a gas in the fluid region. Consequently, and the same gas cooler outlet temperature. The
the temperature of the refrigerant will change compression process for all three cycle processes
continuously throughout the entire heat is assumed to be reversible and adiabatic (ideal =
rejection process. Because this is not a phase isentropic efficiency equal to 1).
change process, the temperature and pressure
become independent. So what then determines The main difference between the three cycle
the pressure in the gas cooler? processes is the gas cooler pressure.

8 DKRCI.PZ.000.F1.02 / 520H3002  Danfoss A/S (RA Marketing/MWA), July 2008


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Effect of gas cooler pressure


on system performance
(continued)
t G C, OUT

∆pG C
3H 2H
3 2
∆pG C 3L 2L
CP

Pressure (logarithmic scale)


tE
1
4H 4 4L
Q E = m·∆hE V AP
W = m·∆hC OMP
C OP = ∆hE V AP /∆hC OMP ∆hE V AP ∆hC OMP

C OP L = 1.8, Q E = 64 %
C OP = 2.6, Q E = 100 %
C OP H = 2.5, Q E = 106 %

Specific enthalpy
Figure 5: Influence of gas cooler pressure on cycle process

Figure 5 illustrates the changes in state point both the processes with higher and lower gas
locations and cycle performance as the gas cooler pressures, the values for COP are lower,
cooler pressure is either increased or decreased indicating that an optimum gas cooler pressure
from a nominal value. The cycle process with exists.
the nominal gas cooler pressure is referred to as
the nominal cycle process. The state points with Figure 6 shows the variations in refrigerating
index L represent the cycle with a lower pressure, capacity and COP for a system operating with
state points with index H represent the cycle with constant evaporating temperature, superheat
a higher pressure. and gas cooler outlet temperature. The figure is
based on simulation using mathematical models
The numbers in the figure show the of the components. The model of the compressor
consequences of a change of app. ±5 bars in reflects “true” compressor behaviour – meaning
the gas cooler pressure. The influence on cycle isentropic and volumetric efficiencies vary with
refrigerating capacity can be observed by the operating conditions.
comparing the changes in specific enthalpy in
the evaporator DhEVAP. For the cycle process with It can be seen that the optimum condition for
a lower pressure, the refrigerating capacity is only refrigerating capacity is found for a higher gas
64% of that of the nominal cycle process. For the cooler pressure than for the optimum condition
cycle process with a higher pressure, the capacity for COP. For a system operating at conditions
is 106% of that of the nominal cycle process. close to the optimum COP, the extra refrigerating
This shows that the gas cooler pressure has a capacity that can be obtained by increasing the
significant influence on the refrigerating capacity. gas cooler pressure is relatively small - normally
only a few percent.
The influence of gas cooler pressure on
compressor power consumption can be observed In almost all practical applications the
by comparing the changes in specific enthalpy in operating conditions (evaporating temperature,
the compressor DhCOMP. The pressure change of superheat and ambient temperature) will vary.
±5 bars causes changes in the compressor power Consequently the optimum gas cooler pressure
consumption of app. ±10%. also varies. Depending on the application, and
also magnitude and duration of the variations
Together the changes in refrigerating capacity in operating conditions, different types of high
and compressor power consumption cause pressure control must be used to ensure efficient
changes in the Coefficient of Performance (COP). and economical operation.
The figure shows that the gas cooler pressure
has a significant influence on the COP. For the
nominal cycle process, the COP is 2.6, but for

 Danfoss A/S (RA Marketing/MWA), July 2008 DKRCI.PZ.000.F1.02 / 520H3002 9


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Effect of gas cooler pressure


on system performance 1.50
(continued)
C OP

Refrigerating capacity [kW] and COP [-]


1.25

1.00
QE

0.75

0.50

0.25
Operating condition
t E = -10 °C , ∆tS H = 10 K
t G C ,OUT = 35°C
0.00
75 80 85 90 95 100 105 110 115 120
Gas cooler pressure [bar]

Figure 6: Effect of gas cooler pressure on refrigerating capacity and COP

System design Figure 7 shows a pipe diagram for a very simple


transcritical system. The system consists of a
compressor, a gas cooler, an evaporator, and an
expansion device.

Compressor

Evaporator Gas cooler

Expansion device
Figure 7: Layout of simple refrigeration system for transcritical operation

The most simple expansion device that can be Use of an internal heat exchanger between the
used is a fixed flow restriction (e.g. an orifice suction line and the gas cooler discharge line can
or a capillary tube). In such a system, the high enhance the performance of the system (figure
pressure is not controlled and the system 8). If the expansion device is a capillary tube, the
will consequently only be operating with internal heat exchange can be established by
the optimum high pressure - and maximum soldering the capillary tube, or parts of it, to the
efficiency (or capacity) - at one single operating suction line.
condition.

10 DKRCI.PZ.000.F1.02 / 520H3002  Danfoss A/S (RA Marketing/MWA), July 2008


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

System design
(continued) Internal heat
exchanger 1
6 22

Evaporator 4 Gas cooler


Compressor

5 33

HP Expansion device
(cap. tube or orifice)

Figure 8: Layout of a transcritical refrigeration system with internal heat exchanger and fixed flow restriction as
expansion device

The layout shown in figure 8 can be used for In addition, it may be necessary to install a low-
systems that operate with medium variations pressure receiver to compensate for the charge
in ambient temperature but with requirements variations on the high-pressure side.
for capacity or efficiency at only one fixed rating
point. For simple systems, it is possible to use the
expansion device as the high pressure control
When the operating conditions change device, and omit control of refrigerant flow into
(e.g. ambient temperature, or evaporating the evaporator. Different types of expansion
temperature during a pull-down of refrigerated valves can be used (automatic, thermostatic, and
cabinet), the distribution of the refrigerant electronic) as shown in figures 9 to12.
between the components will change thus
the gas cooler pressure also changes. For A system with an automatic valve is shown in
uses requiring high variability in operating figure 9. The valve senses the inlet pressure
conditions and that must satisfy capacity and (the gas cooler pressure) and opens and closes
efficiency requirements under varying operating according to a set-point for inlet pressure. The
conditions, and meet capacity and efficiency valve set-point may be manually adjustable.
requirements at varying operating conditions,
high pressure control devices must be used.

Internal heat
exchanger 11
6 22

Evaporator 4 Gas cooler


Compressor

55 33

HP Expansion valve
(automatic)

Figure 9: Layout of a transcritical refrigeration system with internal heat exchanger and an automatic valve as
expansion device

 Danfoss A/S (RA Marketing/MWA), July 2008 DKRCI.PZ.000.F1.02 / 520H3002 11


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

System design The automatic expansion valve can be used Alternatively, the bulb can sense the air inlet
(continued) for systems that operate with small variations temperature of an air-cooled gas cooler.
in ambient temperature (e.g. for ambient
temperatures above the critical temperature
only) but with requirements for capacity or
efficiency at two or more rating points.

A system with a thermostatic valve is shown in


figure 10. The valve uses a traditional bulb (filled
with a liquid/vapour mixture of a substance) to
sense the refrigerant outlet temperature of the
gas cooler to control the inlet pressure (the gas
cooler pressure).

Internal heat
exchanger 11
66 22

Gas cooler or
Evaporator 44
Compressor Condenser

55 33

HP Expansion valve
(thermostatic)
Figure 10: Layout of a transcritical refrigeration system with internal heat exchanger and a thermostatic valve as
expansion device

The thermostatic expansion valve can be used


for systems that operate with large variations
in ambient conditions and with requirements
for capacity or efficiency at two or more rating
points.

Low-pressure Internal heat


receiver exchanger 1
6 2

Evaporator 4 Gas cooler


Compressor

5 3

HP Expansion valve
(thermostatic)
Figure 11: Layout of a transcritical refrigeration system with internal heat exchanger, a thermostatic valve as expansion
device and a low-pressure receiver

12 DKRCI.PZ.000.F1.02 / 520H3002  Danfoss A/S (RA Marketing/MWA), July 2008


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

System design Improvements of performance for this type of Full control flexibility can be obtained with a
(continued) system can be obtained by using a low-pressure system using an electronic expansion valve
receiver as shown on figure 11. and an electronic system controller receiving
As the temperature at the termostatic expansion information about one or more temperatures
valve changes, the high-pressure refrigerant is and pressures in the system. The figures show a
taken from or added to the low-pressure receiver. controller receiving information about gas cooler
Special care must be taken to avoid oil build-up outlet pressure and temperature, but much more
in the receiver. This can be avoided by an oil drain advanced controllers could be envisioned. The
line allowing a small flow of liquid oil/refrigerant complexity of the controller and the number of
to exit the receiver and enter the internal heat sensors/transducers can be selected according to
exchanger. the specific purpose of the system.

Internal heat
exchanger 11
66 22

Gas cooler or
Evaporator 44
Compressor Condenser

55 33

HP Expansion valve P T
M
(electronic)
Controller
Controller

Figure 12: Layout of a transcritical refrigeration system with internal heat exchanger and an electronically controlled
valve as expansion device

The layout shown in figure 12 can be used The design and use of receivers and pressure
for systems that operate with large variations control devices for transcritical systems are
in ambient conditions and with extreme covered by a number of patents. References to
requirements for capacity or efficiency at a few of these patents can be found later in this
all operating conditions. Often it is only for document [2], [3], and [4]. It is strongly advised to
systems that are to be analysed experimentally conduct a thorough patent search and analysis
in a laboratory that such control flexibility is before making a specific transcritical refrigeration
necessary. or air conditioning system commercially
available.
Other system configurations than the ones
shown in this document are possible. The
choice of system configuration depends on the
requirements for performance under a given set
of design conditions – or maybe even within a
given application design envelope.

 Danfoss A/S (RA Marketing/MWA), July 2008 DKRCI.PZ.000.F1.02 / 520H3002 13


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

System components
Compressor Danfoss Compressors has developed the TN For details about the compressor design and
compressor series for transcritical applications application, how to install it, and the application
with the refrigerant CO2. The TN compressor envelope, check the available instructions and
series is based on a one-cylinder reciprocating the data sheets supplied by Danfoss.
design, as this is the optimal solution to manage
the high pressures of CO2 while also being able All TN compressors are equipped with a burst disc
to handle the high pressure difference between connected to the discharge line. This burst disc
discharge and suction side. The two external will release the discharge gas to the ambient if
mufflers, one on the suction side and one on the discharge pressure exceeds its burst pressure
the discharge side, are integral parts of the of 130 bars ± 5%. It is necessary to ensure that, in
compressor design and should not be removed. the event of a burst, no one will be injured by the
release of the hot oil/gas mixture.
For the selection of the right compressor type
please check the data sheets or check with the
calculation tool. Both are available from Danfoss
or can be downloaded from our website.

Expansion device Depending on the location and type of system, Danfoss has a number of developments both
variation in ambient conditions as well as with regard to automatic constant pressure
variations in load, a specific type of expansion regulation, and automatic thermostatic pressure
device can be recommended. A general regulation. For more information about
description of the mechanisms that can be expansion devices available for small transcritical
employed for expansion is given in the System CO2 systems, please contact Danfoss.
Design section of this guide.

Gas cooler The gas cooler design has to be adapted to the Unlike condensers where most of the heat
application of CO2 as refrigerant. Aside from the exchange takes place at a constant temperature,
high pressures of up to 137 bars, there are two the temperature of the CO2 steadily drops while
further issues that must be addressed: the refrigerant flows through the gas cooler.
a) The gas cooler outlet temperature of the CO2. This also means that the part of the gas cooler
b) The temperature change of the CO2 during where the CO2 enters into the gas cooler has a
the cooling. higher temperature than any other part while
the lowest temperature occurs at the exit. With
The gas cooler outlet temperature of the CO2 a standard design, heat would flow from the
has to be as low as possible in order to obtain warmer parts to the colder parts of the gas
the highest capacity and the best COP. This cooler. This would not only lower the ability to
effect has been described in section “Effect of reject heat to the ambient but also result in an
gas cooler pressure on system performance’. increased temperature of the CO2 leaving the gas
The complete heat exchange between the gas cooler. To minimize this heat flow, the thermal
cooler and the air has to be counter-current flow contact between the gas cooler sections has to
or cross-counter-current. The last tubes with the be minimized as shown in figure 13.
refrigerant before leaving the gas cooler should
be located where the coldest air is entering.

14 DKRCI.PZ.000.F1.02 / 520H3002  Danfoss A/S (RA Marketing/MWA), July 2008


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Gas cooler To get the air-flow as cold as possible to the gas


(continued) cooler, the compressor should be located in the
air flow behind the gas cooler. For optimum
efficiency, the temperature of the CO2 when
leaving the gas cooler should not be more than
2-3 K above the temperature of the ambient air
before entering the gas cooler.

Broken thermal contact

Ambient
air in

Hot CO2 in Cold


CO 2 Out
Figure 13: Principle of gas cooler design to avoid internal heat flow and to minimize the refrigerant exit temperature

Lubricant Standard refrigeration oils cannot be applied in It is strongly recommended to use only the oil
transcritical CO2 systems due to the very different type and viscosity grade as specified by the
solubility and miscibility with CO2 compared with compressor manufacturer. Whenever possible,
other refrigerants. the same oil as originally charged by the
compressor manufacturer should be used.
Oil suppliers have developed special lubricants to
guarantee the wear protection in the compressor For small hermetic systems, the oil amount
under the influence of CO2. Equally important is charged by the compressor manufacturer should
the solubility and miscibility behaviour of the oil be sufficient. If due to an oil loss or for a remote
together with CO2 to ensure the oil circulation system some oil has to be added, please contact
in the system, especially at low evaporation Danfoss for the oil type specification.
temperatures.

Filter drier In fluorinated refrigeration systems, filter driers Activated alumina is often used in filter driers to
are commonly used to remove water, usually the remove acids produced in the reaction between
type with a zeolite core. The zeolite has extremely oil and water. However, many of the reactions
small pores, and acts like a molecular sieve. Water that produce acids will not take place in a
molecules are small enough to penetrate the well-maintained CO2 system, where the water
sieve, and being very polar, they are adsorbed content is below the maximum solubility limit.
inside the zeolite molecules. R134a molecules Therefore, Danfoss recommends 100% MS for use
are too large to penetrate the sieve. When the with CO2 to maximize water removal. For more
replaceable core is removed, the water goes with information about filter driers available for CO2
it. systems please contact Danfoss.

CO2 is a non-polar molecule, so the removal


process is different. Like water molecules, CO2
molecules are small enough to penetrate the
molecular sieve. However, the water molecules
adsorbed onto the molecular sieve, act in such
a way as to “kick out” the CO2 molecule, due to
the difference in polarity. Even though the driers
function differently in this respect in CO2 systems,
the efficiency is fairly good.

 Danfoss A/S (RA Marketing/MWA), July 2008 DKRCI.PZ.000.F1.02 / 520H3002 15


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Piping Due to the high volumetric capacity of CO2 tubes


with a smaller diameter than in conventional
systems of similar capacity can be used.

Smaller diameters should be preferred as they


decrease the refrigerant charge and withstand
higher pressures. For the existing range of TN
compressors, in most cases a tube of 6 x 1 mm
will be sufficient. The maximum working pressure
of the tubes must be observed (table 2).

Diameter Max. allowable Diameter Max. allowable


working pressure working pressure
[mm] [bar] [inch] [psig]
6x1 200 1/4 775
8x1 143 3/8 662
10 x 1 111 1/2 613
12 x 1 91 5/8 537
15 x 1 71 3/4 495
Table 2: Maximum allowable working pressure for standard copper tubes as used in refrigeration

Safety components The burst disc integrated in the discharge muffler It is strongly recommended to install a safety
of the TN compressor series opens if the high device like a burst disc or a pressure relief valve in
pressure of the system exceeds 130 bars ±5%. each section of the refrigeration system that can
It is recommended to additionally integrate a be separated from the existing safety device, e.g.
pressure switch that cuts off the compressor by closing a valve.
before the burst disc would open to release the
refrigerant and make the system operational.

16 DKRCI.PZ.000.F1.02 / 520H3002  Danfoss A/S (RA Marketing/MWA), July 2008


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

System handling
Refrigerant grades To avoid problems caused by too high water
content in the CO2, it is recommended to keep
the concentration below the max. solubility limit.
CO2 with maximum 10 ppm water is suitable for
common used CO2 systems.

Evacuation Due to the low acceptable water concentration, The same vacuum pump and procedure can be
the evacuation process of the system is very used for all refrigerants if it is charged with ester
important. oil.

Charging It is important to start up with CO2 in the vapour CO2 can only exist as a solid or vapour inside
phase and continue until the pressure has the refrigeration system. Also, the system will
reached approximately 5 bars. One must be exhibit very low temperatures until the pressure
aware when charging a refrigerant system that, is sufficiently raised. For example, at 1 bar, the
until the pressure reaches the triple point, the sublimation temperature will be –78.4°C.

Material compatibility CO2 is compatible with almost all common ensure that components released for use with
metallic materials, like the fluorinated CO2 can withstand the impact of CO2 in all
refrigerants. There are no restrictions in terms of aspects.
compatibility, when using copper or brass.
Tests have shown that CO2 is different, in
The compatibility of CO2 and polymers is much particular when it is used in transcritical
more complex. Because CO2 is a very inert application, where a large amount of CO2 can
and stable substance, the chemical reaction dissolve in polymers, has to be taken into
with polymers is not critical. The main concern consideration.
with CO2 is the physiochemical effects, such
as permeation, swelling and the generation of Only a few specific types of polymers are suitable
cavities and internal fractures. These effects are for use as sealing materials in transcritical CO2
associated with the solubility and diffusivity of components.
CO2 in the actual material.

Danfoss has carried out a number of tests to

Water in CO2 systems In figure 14, the water solubility in the vapour vapour phase. Below these levels, water remains
phase of different refrigerants is shown. The dissolved in the refrigerant and does not harm
acceptable level of water in CO2 systems is much the system. Water (H2O) molecules are dissolved
lower than with other common refrigerants. The if the concentration is lower than the maximum
diagram in figure 15 is shows the solubility of solubility limit, but if the water concentration is
water in both liquid and vapour phases of the higher than the maximum solubility limit, the
CO2 as a function of temperature. The solubility H2O molecules precipitate out of the solution into
in the liquid phase is much higher than in the droplets.

Water solubility in various refrigerants in vapour phase Water solubility in CO 2


Maximum solubility [ppm] (mg/kg)

R717 1000 Liquid


2000
Maximum solubility [ppm]

Vapour
100
(mg/kg)

1000

R134a 10

R404A
CO 2
0 1
-50 -30 -10 10 [o C] -50 -30 -10 10 [ o C]

Figure 14: Water solubility of various refrigerants Figure 15: Water solubility of CO2

 Danfoss A/S (RA Marketing/MWA), July 2008 DKRCI.PZ.000.F1.02 / 520H3002 17


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Water in CO2 systems If the water is allowed to exceed the maximum To avoid unforseen problems with water in CO2
(continued) solubility limit in a CO2 system, problems may systems, a molecular sieve filter drier can be used.
occur, especially if the temperature is below 0°C.
In this case, the water will freeze, and the ice
crystals may affect the operation of e.g. control
valves.

In small hermetic transcritical CO2 systems, water


is generally not a major problem. These systems
do not normally operate at very low temperature,
and do not have sensitive control equipment.

18 DKRCI.PZ.000.F1.02 / 520H3002  Danfoss A/S (RA Marketing/MWA), July 2008


Article Transcritical Refrigeration Systems with Carbon Dioxide (CO2)

Safety and design


Safety CO2 is a non-flammable and non-toxic fluid. All components must be designed for the
However, if the concentration of CO2 exceeds adequate pressures. For this, all relevant national
a certain level, the amount of oxygen in the and international laws, regulations, and standards
atmosphere for breathing is reduced. In extreme must be followed. Safety devices such as burst
cases this can be fatal. The CO2 cannot be noticed discs and pressure relief valves or pressure cut-
as it does not have an odour that can be detected outs are recommended to cover unintended
by humans. operational conditions.

CO2 is heavier than air, so highest concentration After assembling the system, it is necessary
levels will be found close to the bottom. to conduct a pressure test to ensure that all
Especially for systems installed below ground soldered connections are tight. The use of
level, there is a risk of a high CO2 concentration a pressure switch will avoid exceeding the
in the event of a leakage. The installation of a CO2 pressure limit, which may lead to an accident.
sensor with an alarm is recommended. In the discharge muffler, a burst disc that opens
if the pressure exceeds 130 bars +/- 5% has
The second safety issue with CO2 involves been integrated. This pressure is the maximum
the higher pressures by comparison with the allowable pressure (PS). The test pressure must
traditional refrigerants. In the transcritical cycle, be 1.43 x PS.
the discharge pressure will be between 80 and
120 bars. The pressure at the low-pressure side
depends on the evaporation temperature but
during off-conditions, the standstill pressure can
be significantly higher.

Safety standards When this paper was prepared, no international Danfoss has tested its components to its best
standard had been established explicitly knowledge. But as safety conditions for the
covering hermetic or semi-hermetic type motor products are not definitive, the user must ensure
compressors for CO2 or appliances for household that the system is safe.
and similar applications with a CO2 transcritical
cycle.

There are some standards such as EN378 covering


also systems with CO2 as refrigerant. It may be
necessary to comply with other national or
safety regulations such as PED when setting up,
operating, servicing or in another way working
with a CO2 system.

References [1] “Theory and ”, M.M. Abbott & H.C. van Ness, Schaum’s outline series, McGraw-Hill, Second edition,
1989.
[2] “Control of high-pressure in transcritical vapour compression cycle”, EP 0 604 417 B1
[3] “Method of operating a vapour compression cycle under trans- or supercritical conditions”, EP 0
424 472 B2.
[4] “Refrigerating system with pressure control valve”, WO 5890370

 Danfoss A/S (RA Marketing/MWA), July 2008 DKRCI.PZ.000.F1.02 / 520H3002 19


The Danfoss product range for the
refrigeration and air conditioning industry
Danfoss Refrigeration & Air Conditioning is We focus on our core business of making
a worldwide manufacturer with a leading quality products, components and systems
position in industrial, commercial and that enhance performance and reduce
supermarket refrigeration as well as air total life cycle costs – the key to major
conditioning and climate solutions. savings.

Controls for Controls for Electronic Controls &


Commercial Refrigeration Industrial Refrigeration Sensors

Industrial Automation Household Compressors Commercial Compressors

Sub-Assemblies Thermostats Brazed plate


heat exchanger

We are offering a single source for one of the widest ranges of innovative refrigeration
and air conditioning components and systems in the world. And, we back technical
solutions with business solutions to help your company reduce costs,
streamline processes and achieve your business goals.

Danfoss A/S • www.danfoss.com

DKRCI.PZ.000.F1.02 / 520H3002  Danfoss A/S (RA Marketing/MWA), July 2008