ENGINEERING COMMUNICATION SHEET 発行番号 ECS-RH-C421A


宛先 TO 発行日付 DATE ISSUED

TMIND 26, Sep, 2019

回答希望日 REPLY DEAD LINE


□ 御検討用 FOR REVIEW □ 依頼 REQUEST

■ 御確認用 FOR CONFIRMATION □ 回答 REPLY

□ 御参考用 FOR INFORMATION □ ■ 回答不要 NO REPLY REQUIRED

プラント PROJECT 機器名 EQ/SYS. 製造/見積番号 JOB/QUOT.NO.


N/A U-PCS N/A
題 目 SUBJECT

Interference suppression between each inverters in parallel operation

This document presents the interference suppression between each inverters in parallel
operation of U-PCS.
.
1. The description of interference by resonant phenomenon
In case of the parallel connection between each inverters, the interference can be occurred if there is no
buffer reactor at output side. When the switching operation of two or more inverters get to be different, the
resonant phenomenon is occurred through each filter capacitors.

Figure 1. The resonant phenomenon in parallel connection.

社内配付先 部数 発行部課名 承 認 調 査 担 当
DISTRIBUTION COPY ISSUED BY APPROVED REVIEWED PREPARED
BY BY BY
環境・エネルギー
パワーエレクトロニクスシステム部
木下 田中 柴田
2019. 9.26 2019. 9.26 2019. 9.26
TEL: 042-306-5394 雅博 尚哉
嗣大
FAX: 042-367-1127 M.Kinoshita T,Tanaka N.Shibata

TOSHIBA MITSUBISHI-ELECTRIC INDUSTRIAL SYSTEMS CORPORATION 東 芝 三 菱電 機産業 シス テム株 式会 社


技術連絡書 2/2
ENGINEERING COMMUNICATION SHEET

2. The comparison in parallel connection


The following table shows the comparison in parallel connection.

Table 1. The comparison in parallel connection


No. Circuit topology Application example Description

The inverters are connected in


parallel through buffer reactor. Even
500kW, 630kW though the switching operation is
1
(Japan) different between each inverters, the
resonant current through each filter

Buffer reactor capacitors can be suppressed.

The inverters are directly connected


in parallel but the damping resister is
installed in series on the filter circuit.
2 U-PCS
Therefore, the resonant current is
suppressed even though the
switching operation is different.
Damping resistor

3. Conclusion
U-PCS has the damping resister for the purpose of interference suppression between each
inverters. Therefore, there is no problem even though two or more U-PCS are connected on the
same winding of the transformer.
-END-