MOM BETWEEN CLEAR WATER AND HFL, HYD

Date - 20/12/2019
Training given by Nilesh bharmbe to HFL employee for ETP operation as per bellow,

1 Equilization tank PH to be maintain 8-9


a)If PH < 8 or Acid Need to Add lime powder
solution - 5kg lime +100 ltr water
b)If PH >9 Alkaline , need to Add HCL Acid
solution 30% concentrated HCL
2 DAF or Oil and grease remover
a) poly -1 ltr +100 ltr water for 8 HR
b) Allum-4kg +100 ltr water for 8 HR
3 MBBR Tank Or Aeration tank-1,2,3 chemical addition
a) DAP 4kg/day -manual at start only
b) Urea 10kg/daymanual at start only
c ) Joggary 5kg +100 ltr water for 24 HRS
d) cow dung - 50kg one time for 24 HRS
c) STP water addation in MBBR-1
Secondary calrifier to MBBR-1 Sludge Recirculation in every 2Hrs once run pump 10 mints
4

a) NAOCL (hypho ) dosing in chlorination tank


5 Polymer dosing in filter press
solution -3 ltr polymer+ 100 ltr water WHEN filter press runing
6 Instead of caustic soda we have to use lime powder
7 Aeration tank to MBBR MLSS to be maintain at 3500 to 4500
8 Aeration tank PH To be maintain in the range of 7-8.
9 Disolved oxigen Demand (DO) should maintain 2.0

Requirement from clear water


1 ETP Opeartion is running as per clear water instructions.
We are not getting ETP Outlet as Pollution control board accepted criteria,So Full
2 coommissioning not completed.

3 All electrical instuments like PH Meter,Level sensors,water metrs are not working with interlocks.

4 All snag list for IQ,OQ attached with to be completed.


5 All Instruments Catalauges,Programme,Waranty card,Test cerificates not received.
6 All snag list for PQ has to be complete as per mail.
Video training to be provided when full commissioning of all electrical instuments completed.
6

From HFL,Hydrabad From ,Clear water


Raghu Sir Nilesh Bharambe
R senthil
Vinod Koli
Ranjit
mints

h interlocks.

mpleted.
ETP Plant
Make pump S.no(Pump) CE( 3Phase Induction Motor)

1.Equalization tank, Secondary Spxflow Johnson KGEC 11-4-G6


clarifier tank, Sludge pump recycle pump MachineNO 1.10KNE2KW
(HP):1.10(1.50) RPM:2880
REF:SGGM61019

Spxflow Johnson
Chlorination tank KGEC 16-3-G6
pump Machine No :2.20KNE2
KW(HP)2.20 RPM 2850
REF:SFGM67325

Spxflow Johnson Machine No:5.50KNE2TOP


treated water tank KGEC 11-4-G6 KW(HP):5.50(7.50) RPM:2905
pump
REF: SGGM03364

Dosing Pump Alum ,Pac,custic,Alkalic Sr No:190593101


, Defoamer,cl tank, M/CNO:1000827647
CE( 3Phase Induction KW/HP:0.18/0.25
Motor)LHP laxmi Rpm:1305 Dosing
Hydraulics Pvt Ltd Rate:200 lit/Hr

Agitator Alum ,Pac,custic,Alkalic , Sr NO: SHBM3064


Defoamer,cl tank, CE( 3Phase Induction M/C NO:0.37KEG4FLG
Motor)LHP laxmi KW(HP):0.7(0.50)
Hydraulics Pvt Ltd RPM:1400

MODEL NO:
TMVT ROOTS BLOWER AIR FILTER 3MIL 125
M/CNO.18235
CAP:1200M3/HR
PRE,/VAC 0.55
KG/CM2 RPM:1570
MO:4910

Pvc material
Material Name size Qty
Ball Valve 50mm 10
L Bend 50mm 10
Sackets 50mm 20
MTA 50mm 5
PVC Nontetun Valve 50mm 10
Leanth Pipe 50mm 3
Ball Valve 65 mm 10
L Bend 65 mm 6
Sackets 65 mm 6
MTA 65 mm 2
PVC Nontetun Valve 65 mm 10
Leanth Pipe 65 mm 2

Ball Valve 25mm 5


L Bend 25mm 10
Sackets 25mm 10
MTA 25mm 4
PVC Nontetun Valve 25mm 4
Leanth Pipe 25mm 3
1/2 inches Ball valve 1/2 inch 4
Flow meter LZS-50 10/H 50 MM 2
12mm*8mm white tube for
chemical Dosing 12mm*8mm 20mtr
Pressure gaguge EN 837-1 100 psi
(7kg) 20
Air Blower Air filter 4
10kl sintack tank 10 kl 1
(pump/motor) QTY. Remarks

3 nos

2 nos

2 nos

4 nos

Nos 4

Nos 4