Transfer Function parameters for AVR

Transfer function parameter Parameter description Test Report parameter Unit


TR Filter time constant of sec
voltage sensing.
TC2 Tb – Differential time sec
constant
TB2 Tb x Vp/V∞ sec
KR V0 – Steady state gain pu
TC1 Ta – Integral time constant sec
TB1 Ta x V0/Vp sec
UP+ Ceiling factor = pu
Up/Uf0(from regulator)
UP- Ceiling factor = Up/Uf0 Pu
(from regulator)
UP+ Ceiling factor = Pu
Up/Uf0(with rectifier limit
of 30◦ as per Test report)
UP- Ceiling factor = Pu
Up/Uf0(with inverter limit
of 149◦ as per Test report)
Ts Filter time constant of sec
firing card
K∞ Commutation voltage drop pu
constant (based on
UN0663 settings)
KE Exciter constant
TE Exciter open circuit field sec
time constant (T`d0)
T1 Transducer time constant sec
for power measurement
T2 Time constant for washout sec
filter (lead block)
T3 Transducer time constant sec
for frequency
measurement
T4 Time constant for washout sec
filter (lead block)
KSS1 Phase compensation for pu
power (lag block)
KSS2 Gain for lag block pu
USS1 MAX Positive signal limit Pu
USS1 MIN Negative signal limit pu