Standard condition
The following conditions have been used to calculate the current rating in the catalouge

Ambient air temperature 30 °C


Ground temperature 15 °C

Thermal resistivity of soil(g) 1.2 K.m/W

Depth of burial from ground surface to centre of cable, O.Sm for 600/1 OOOV cables

Voltage drop in consumers' installations

The voltage drop between the origin of an installation and any load point should not be greater than
the values in Table X-01 expresed with respect to the value of the nominal voltage of the installation.

The calculated voltage drop should include any effects due to harmonic currents.

Table X-01 - Voltage Drop

Lighting Other uses

01. Low voltage installations supplied directly from


a public !ow voltage distribution system 3% 5%

02. Low voltage installation supplied from private


LV supply(*) 6% 8%

cr.i The voltage drop within each fi nal circuit should not exceed !he Vdlues given lll (01 ).
VVhcrc the \.Viring systerns {lf the ins!allaiion zire longer than 1OOm, the voltage drops indicc1ted ai)()ve rnay be
increased bv OJ)OS'~/;) per 1rn~lre of the vviring system beyond l OOrn 1 without this inocase being greater than
0.5% .
The vo ltage drop is determined fron1 the demand of 1he current ming equipnwnt. ;~pplying f.:-ic tors
vvhere applicable, or from the value of the design current of ihe circui1.

Minimum internal radii of bends in cables for fixed wiring

Overall Diameter Minimum Internal Radii of Bends


(In time of overall diameter)

* PVC Insulated Unarmoured 3


Not exceeding 10 mm

* PVC/XLPE Insulated Unarmoured 4


Exceeding 10 mm but not exceeding 25 mm

Exceeding 25 mm 6

* PVC/XLPE Insulated Armoured -Circular Conductor 6

* PVC/XLPEInsulated Armoured or
8
Unarmoured - Solid Al or Shaped Cu Conductor
18

18. Adjustment Tables

T&lble Y - 01: Rating fa ctors for ambient air temperatures.


tOther th .. n 30 °C to be applied to Lh ~ current-carrying capaciti s for cables in free cir)

Ambient air temperature °C


Insulation
25 30 35 40 45 50 55 60 65 70 75 80

70 °C thermoplastic 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50

90 °C thermosetting 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71 0.65 0.58 0.50 0.4~

Suurcc· IEE wiring regulations - seventeenth edition

Rating factors for ground


(Rating tactors for ambient ground temperatures other than 15°C to be applied to the
current-curry111g capacities for cables buried direct in the ground)

Ground temperature °C
Insulation
15 20 25 30 35 40 45 50
70 °C Thermoplastic 1.0 0.95 0.90 0.85 0.80 0.74 0.67 0.60

90 °C Thermosetting 1.0 0.97 0.93 0.89 0.86 0.82


Source: ERA f hnology publication - 69-30 series.

Table Y-03: Rating factors for one circuit or one multicore cable or for a group of circuits, or a group
of mullicore cables, to be use with current carrying capacities of tables A 1 --Q2 .

To be used with
No of circuits or multicore cables
current c~!·rying
Arrangement (cables touching) capacities,
1 2 3 4 5 6 7 8 9 12 16 20 Reference
Bunched in air, on a surface, Method
embedded or enclosed 1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.45 0.41 0.38
A to F

Single layer on wall or floor Method


1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 0.70 0.70 0.70
c

Single layer multicore on a perforated 1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72 0.72 0.72 0.72
horizontal or vertical cable tray system Method
E and F

Single layer multicore on cable 1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78 0.78 0.78 0.78
ladder system or cleats etc. ..

Source: IEE wiring regulations - seventeenth edition

NOTE:
1. The foctc r are appli able to uniform groups of cables, "qually loade .
2. Where horizontal clearances 1etween , djacent cables exceeds twice their overall diameter,
no rating factor need be <.1pplied.
• 18

Group rating factors for 600/1 OOOV cables - laid direct in ground

Table Y-04 : For circuits of two single core cables, Table Y-05 : For circuits of two single core cables,
laid flat spaced, horizontal formation laid flat touching, horizontal formation

o~ Spacing
~ 0 0 0
~ pacing
cD
____. CD
Spacing (m) Spacing (m)
No of
Touching
Circuits 0.15 0 .30 0.45 0.60 0.15 0.30 0.45 0.60

2 0.83 0.88 0.91 0.93 0.79 0.84 0.89 0.91 0.93


3 0.72 0.79 0.84 0.87 0.68 0.74 0.80 0.85 0.88

4 0.67 0.76 0.81 0.85 0.62 0.69 0.77 0.82 0.86

5 0.63 0.72 0.79 0.83 0.57 0.65 0.74 0.80 0.84

6 0.61 0.71 0.77 0.82 0.54 0.63 0.72 0.79 0.83


7 0.59 0.69 0.76 0.81 0.52 0.60 0.7 1 0.7 8 0.83

8 0.57 0.68 0.76 0.81 0.50 0.59 0.70 0.77 0.82

9 0.56 0.67 0.75 0.80 0.48 0.57 0.69 0.76 0.82

10 0.55 0.67 0.74 0 .80 0.47 0.56 0.68 0.76 0.81


11 0.54 0.66 0.74 0.80 0.46 0.56 0.67 0.75 0.8 1
12 0.53 0.65 0.74 0.80 0.45 0.55 0.67 0.75 0.81

S urce: ERA 1i chnology publication - 69-30 series.

Table Y-06 : For circuits of three single core cables, Table Y-07 : For twin or multi core cables,
laid flat spaced, horizontal formation in horizontal formation

o~ Spacing ~o OOO
t- .
Spacing__.
() 0

No of Spacing (m) Spacing (m)


Circuits /No
of Cables in Touching
0.15 0.30 0.45 0.60 0.15 0.30 0.45 0.60
Group
2 0.81 0.86 0.90 0.92 0.81 0.87 0.91 0.93 0.95
3 0.70 0.77 0.82 0 .86 0.70 0.78 0.84 0.88 0.90
4 0.65 0.74 0.79 0.84 0.63 0.74 0.81 0.86 0.89

5 0.61 0.70 0.77 0.82 0.59 0.70 0.78 0.84 0.87

6 0.59 0.68 0.75 0.81 0.55 0.68 0. 77 0.83 0.87


7 0.56 0.67 0.74 0.80 0.52 0.66 0.75 0.82 0.8 6
8 0.55 0.66 0.74 0.79 0 .5 0 0.64 0.75 0.81 0.86

9 0.54 0.65 0.73 0.79 0.48 0.63 0.74 0.81 0.85

10 0.53 0.64 0.72 0.78 0.47 0.62 0.73 0.80 0.85


11 0.52 0.64 0.72 0.78 0.45 0.61 0.73 0.80 0.85
12 0.51 0.63 0.72 0.78 0.44 0.60 0.72 0.80 0.84

Source: ERA Technology publi Jtion - 69-30 erie .


Table Y-08 : For twin or multi core cables in tier formation Table Y-09 : For circuits of three single core cables in
trefoil touching, tier formation.

Formation of cable Formation of cable circuits

coco co coco
J1t ~
Spacing of 00 OOO OOO OOO Spacing
OOO OOO OOO
cables
(m)
00
OOO OOO
of cable
circuits coco coco coco
I•

Spacing
OOO (m)
Spac ing coco coco
Touching 0.69 0.62 0.53 0.44 0.40 Touching 0.66 0.59 0.53 0.49
0.15 0.77 0.71 0.62 0.53 0.48 0.15 0.71 0.65 0.58 0.55
0.30 0.81 0.77 0.68 0.58 0 .53 0.30 0. 76 0.71 0.63 0.60

0.45 0.83 0.80 0.72 0.62 0.56 0.45 0.79 0.74 0.66 0.63
0.60 0.85 0.82 0.74 0.64 0.59 0 .60 0.80 0.77 0.68 0.65

Source: ERA Technology publication - 69-. 0 s ries.

Table Y-10 : Three single core cables in trefoil touching or laid flat touching, horizontal formation

-c:&ac~ CX:O~ac~
Touching Spacing (m)
No of circuits
Trefoil Laid Flat 0.15 0.3 0 0.45 0.60
"'

2 0.78 0.81 0.83 0.88 0.91 0.9 3

3 0.66 0 .70 0. 73 0. 79 0.84 0.87


4 0.61 0. 64 0.68 0 .73 0.81 0.85

5 0.56 0. 60 0.64 0.73 0.79 0.83

6 0.53 0 .57 0.61 0.7 1 0.78 0.82

7 0.50 0.54 0.59 0.69 0.76 0.82

8 0.49 0. 53 0.5 7 0.68 0.76 0.81

9 0.47 0. 5 1 0.56 0.6 7 0.75 0.81

10 0.46 0.50 0.55 0 .67 0.75 0 .80

11 0.44 0.49 0.54 0.66 0.74 0.80


12 0.43 0.48 0.53 0.66 0.74 0.80

Source: ERA Technology publication - 69-30 series.


18

Table Y-13 : Rating factors for variation in depth of laying - 600/1 OOOV cables
Laid direct in the ground In single - way ducts

Depth of Burial (m) Up to 50mm2 Above 50mm 2 up Above 300mm 2 Single core Multi core
to 300mm 2
0.5
0.6
- 1.00
0.99
1.00
0.98
1.00
0.97
1.00
0.98
1.00
0.99
0.8 0.97 0.96 0.94 0.95 0.98
1.0 0.95 0.93 0.92 0.93 0.96
1.25 0.94 0.92 0.89 0.91 0.95
1.5 0.93 0.90 0.87 0.89 0.94
1.75 0.92 0.89 0.86 0.88 0.94
2.0 0.91 0.88 0.85 0.87 0.93
2.5 0.90 0.87 0.84 0.86 0.92
3 .0 (or deeper) 0.89 0.85 0.82 0.85 0.91
Sot1.<.e. t"A TLLnnnl11 • puhli-. lion (,< - 0. ie .

Table Y-14 : Rating factors for variation in thermal resistivity of soil for two or three single core cables laid direct in the ground.

Nominal area Va lue of g, Km/W


of conductor
0.7 0.8 0.9 1.0 1.5 2.0 2.5 3.0 3.5 4.0
mm 2
50 1 .21 1 .1 6 1 .11 1.07 0.91 0.81 0.73 0.68 0.63 0. 59
70 1.22 1.16 1 .12 1.07 0.91 0.81 0.73 0.68 0.63 0.59
95 1.22 1.16 1.12 1.07 0.91 0 .81 0.73 0.68 0.63 0.59
120 1.22 1.16 1.12 1.07 0.91 0.81 0.73 0.68 0.63 0. 59
150 1.22 1.16 1.12 1.07 0.9 '1 0.81 0.73 0.68 0.63 0.59
185 1.22 1.1 7 1 .12 1.07 0.91 0.81 0.73 0.68 0.62 0.59
240 1.23 1 .1 7 1 .12 1.07 0.91 0.80 0.73 0.68 0.62 0.59
300 1.23 1.17 1.12 ·1.07 0.91 0.80 0.73 0.68 0.62 0.59
380/400 1.23 1.1 7 1."12 1.07 0.91 0.80 0.73 0.67 0.62 0.58
J
480/500 1.23 1."17 1 .12 1.07 0.91 0.80 0.73 0.67 0.62 0.58
600/630 1.23 1.17 1.12 1.07 0.91 0.80 0.73 0.67 0.61 0.58
740/800 1.23 1 .1 7 1.12 1.07 0.91 0.80 0.72 0.66 0.61 0.58
960/1 OOO 1.24 1.18 1.12 1.07 0.91 0.80 0.72 0.66 0.61 0. 58
1200 1.24 1.18 1 .12 1.08 0.90 0.80 0.72 0.66 0.61 0.58
ourc.e. ER,\ Tf't 'in >lo mbli al101 - <)-j riP

Table Y-15 : Rating factors for variation in thermal resistivity of soil for twin or multi core cables laid direct in the ground.

Nominal area Value of g, Km/W


of conductor
0.7 0.8 0.9 1.0 1.5 2.0 2.5 3.0 3.5 4.0
mm 2
1.5/2.5 1 .12 1.09 1.07 1.04 0.94 0.86 0.80 0.75 0.70 0.66
4 1.13 1.10 1.07 1.05 0.94 0.85 0.79 0.74 0.69 0.65
6 1 .14 1.10 1.07 1.05 0.93 0.85 0.79 0.74 0.68 0.64
10 1.15 1 .11 1.08 1.05 0.93 0.85 0.78 0.73 0.67 0.63
16 1.16 1 .12 1.08 1.05 0.93 0.84 0.77 0.72 0.66 0.62
25 1 .17 1.13 1.09 1.05 0.93 0.83 0.77 0.71 0.65 0.61
35 1.17 1.13 1.09 1.06 0.92 0.83 0.76 0.71 0.65 0.61
50 1.17 1.13 1.09 1.06 0.92 0.83 0.76 0.71 0.65 0.61
70 1.18 1 .14 1.09 1.06 0.92 0.83 0.75 0.70 0.64 0.60
95 1 .18 1.14 1.09 1.06 0.92 0.83 0.75 0.70 0.64 0.60
120 1 .19 1.14 1.10 1.06 0.92 0.82 0.75 0.69 0.64 0.60
150 1 .19 1 .14 1.10 1.06 0.92 0.82 0.75 0.69 0.63 0.59
185 1 .19 1 .14 1.10 1.06 0.92 0.82 0.74 0.69 0.63 0.59
240 1.20 1.15 1.10 1.07 0.92 0.81 0.74 0.69 0.63 0.59
3001400 1.20 1 .15 1.10 1.07 0.92 0.81 0.74 0.69 0.63 0.59

Source: ERA Technology publicJtion - 69-30. erie~.


SHORT CIRCUIT CURRENT CURVES FOR COPPER CONDUCTOR PVC INSULATED CABLES

lsc = k A k = 0.115/0.103* *for conductor cross


Tt sectional area greater
than 300mm2

lsc - Short Circuit Current in kA


A - Conductor Area in Sqmm
t - Short Circuit time in Sec.

I I

400 4
.... ..._
300 3
......
...........
I
II

:-..._
........
.......

200 2

100 102 II
9
8
1000
70 7
6 800
50 5 .............
............
....
....,.,,
,......
...... ...._
....
630
<(
.:::,(. ,.,,_ ...... :-.u ..........
4 ...... ....,
I-
zL.U ...... ":-..
:-......._
...... ....._
...........
.... ..._
I'
500
......
0::
0::
::i
30 3 ........
......
,.........
.... ..._
..... ......
I'
400 E
u E
I- ....... 0-
su 300 Vl
<(
0::: 20 2 L.U
0:::
0 240 <(
~
~ 0
0


I
Vl
185 I-
u
:J
><
<( 150 0
z
~ 10 10 I
0
u
9
120
8
77 95


.... s ~~

66
55 ...... , .....
70
.... - c..
I
I ~ .....
4 l"'j...
- : : "' ,.... ,...
I
........ 50
,...--1- ·- :-.""
r-
J I
,......
..._ .........
3 f"' .........
-- -- -- -
---r -- -
- ~ ........
......
35
-- ,_- t-t-
-
2
-i.- ·- ~ ~ -~

..L
->- -- ~
25
·-·- - ~
. ·- ..... ,.... -=±
- - - ~
16
-. ·- == ~
~

0.1 0.5 1.0 2.0


SHORT CIRCUIT TIME (Sec) t.
18

SHORT CIRCUIT CURRENT CURVES FOR COPPER CONDUCTOR XLPE INSULATED CABLES

lsc = k A k=0.143
TT
lsc - Short Circuit Current in kA
A· - Conductor Area in Sqmm
t - Short Circuit Time in Sec.

50 0 5 ::: : : : :1::r1_-r-r-r
,l l,..,-,--,',..,.lnl-nrrrrrlrTI
llrtrr-Jm,-llllrrr
m l!TTTnlTTTl
1' !mlTTTU 111111
~ I I I .~ '" 1 II I 11 1 [ 1
11 '
400 5 l---:-'-F-""C:--t--t-r-:l'-r.-~11~1~1r.-'1~11~'! 11:l":~l;;+ll~i-tlT!
~ I +ill~lrr.-ti
l ~llw'llt-ili-+---:---'i--!---i-+-I
i"'-... 1111 I II 1111 I 'I I I II I I

1000
------:.---.--'
8 ;-
•tt; ........ . .
800
7
6 _ _ ,... ~
630
50 5 500
<
..::.!.
1-
zLJ.J 400
C'£'.
:5u 30 3
300 E
E
t:: 0-
Vl
=:i
u 240 <
0 20 2
LJ.J
C'£'.
<
~
185 ~
0I-
0 u
I
Vl 150 =:i
x 0
z
< -,- :.;.::::: 120
~ 0
10 u
95
70

50

35

25

16

SHORT CIRCUIT TIME (Sec) t.


Table Z-01: Maximum resistance of armour wire single, two, three, four, and five core cables having wire armour

Nominal Cab le w ith strand copper conductor Cable w ith sol id alum in ium conductor
cross-
sectional Single core Two core Three core Four core Five core Single core Two core Three core Four core
area of 600/1 OOO V 1900/3300 v 600/ lOOOV 600/lOOOV 1900/3300 v 600/1OOO V 600/lOOOV 600/1 ooov 1900/3300V 600/lOOOV 600/lOOOV 1900/3300V 600/1 ooov
conductors XLPE PVC XLPE PVC XLPE PVC XLPE PVC XLPE PVC XLPE PVC XLPE PVC XLPE PVC XLPE PVC XLPE PVC XLPE PVC XLPE PVC XLPE PVC
mm 2 Q n Q n n Q Q Q n Q n Q n n n Q n Q n n n n n Q n Q
1.5 - - - - 10 .2 10.2 9 .5 9 .5 - - 8 .8 8 .8 8 .2 8 .2 - - - - - - - - - - - -
2 .5 - - - - 8 .8 8 .8 8 .2 8 .2 - - 7.7 7.7 6 .8 6 .8 - - - - - - - - - - - -
4 - - - - 7.9 7.5 7.5 7.0 - - 6.8 4 .6 6.2 4 .1 - - - - - - - - - - -
6 - - - - 7.0 6 .8 6.7 4 .6 - - 4 .3 4 .1 3 .9 3 .8 - - - - - - - - - - - -
10 - - - - 6.0 3 .9 4 .0 3.7 - - 3 .7 3.4 3.4 2.3 - - - - - - - - - - -
16 - - - 3 7 3.4 3 .5 3 .1 1.9 1.9 3 .1 2 .2 2.2 2 .0 - - - - 4 .0 3.7 3.8 3.4 2.0 1 .9 3.4 2.4
25 - - - 1.7 2.6 2.5 2.4 1.7 1.7 2.3 2.1 1.8 1.7 - - - - 4 .1 2.9 2.7 2.5 1.9 1.8 2.4 2 .3
35 - - - 2.6 2.4 2 .3 2.1 1.8 1.7 2.0 1.9 1.6 1.5 - - - - 2 .9 2.7 2.5 2.3 1.9 1.9 2 .2 2 .0
50 1.3 0.82 0.75 0 .73 2.3 2.1 2 .0 1.9 1 .3 1.3 1.8 1.3 1.1 1.1 1.40 0 .90 0 .79 0 .79 2.6 2.4 2 .2 2 .0 1.4 1.4 1.9 1.4
70 0 .75 0 .73 0.67 0.65 2.0 1.9 1.8 1.4 1.2 1.2 1.2 1.2 0 .94 0 .89 0 .84 0 .79 0 .73 0 .71 2.1 2.1 1.9 1.4 1.3 1.2 1.3 1.3
95 0 .67 0 .64 0 .61 0.45 1.4 1.3 1.3 1.2 1.1 1.1 1.1 0 .98 - - 0 .75 0 .7 1 0 .67 0.49 1.6 1.5 1.4 1 .3 1 .2 1.1 1.2 1.1
120 0 .61 0.45 0.42 0.42 1.3 1.2 1.2 1 .1 0.76 0.74 0 .76 0.71 - - 0 .69 0 .49 0.47 0.46 - - 1.2 1 .2 0 .82 0 .80 0 .82 0 .78
150 0.42 0.40 0 .39 0 .39 1.2 1.1 0.78 0.74 0 .71 0 .69 0 .68 0 .65 - - 0 .47 0.45 0.43 0.43 - - 0 .86 0 .82 0 .76 0 .74 0.74 0.71
185 0 .38 0 .37 0 .37 0 .36 0 .82 0.78 0 .71 0 .68 0.65 0 .64 0 .61 0.59 - - 0.42 0.41 0.40 0.40 - - 0.76 0.73 0.71 0 .69 0.67 0 .64
240 0 .3 4 0.33 0 .34 0 .33 0 .73 0 .69 0 .63 0 .60 0 .59 0 .58 0 .54 0 .5 2 - - 0 .38 0.37 0 .37 0 .37 - 0 .68 0 .65 0 .64 0 .63 0 .59 0 .57
300 0 .3 1 0 .30 0.31 0 30 0.67 0 .63 0 .58 0 .54 0 .55 0 .5 3 0.49 0.47 - - 0 .35 0.34 0.34 0.34 - - 0 .63 0 .59 0 .59 0.57 0 .5 4 0 .52
400 0 .22 0 .21 0 .22 0 .21 0 .59 0.56 0 .52 0.49 0.50 0.48 0 .35 0.34 - - - -- - - - - - - - - - -
500 0 .20 0 .1 9 0 .20 0 .1 9 - - - - - - - - - - - - - - - - - - - - - -
630 0 .18 0 .1 8 0.18 0 .1 8 - - - - - - - - - - - - - - - - - - - -
800 0 .13 0.13 0 .13 0. 13 - - - - - - - - - - - - - - - - - - - - -
1000 0 .12 0 .1 2 0 .12 0 .1 2 - - - - - - - - - - - - - - - - - - - - - -
19

20. Schedule of installation methods of cables for determining current carrying capacity

Installation Method
Reference Method
Description Example

In a thermally insulated
wall with an inner skin Room

having a thermal
conductance of not less Non shealhed cables in conduit
than 10 W/m 2 K

Method -A

Mult ico re ca ble in condu it

Room

Multicore cable dir et

In conduit on a wooden
Method - B
or masonry wa II or ·
spaced less than 0.3 x
conduit diameter from it No n Sheathed cables
!

Multi co rc c1 blc

In cable trunking on a
wooden or masonry
wall

run honzontally
Non sheathed cables

'run horiz on/a/Iv 1


'1un vPrtic,1//v
Mu lti core c;:ib le Multicore cabl e

In suspended cable
trunking

No n sheathed cab le M ulti cnre ca ble

* Sti ll under consideration in IEC


20

20. Schedule of installation methods of cables for determining current carrying - capacity Cont ...

Installation Method
Reference Method
Description Example
Non sheathed cables run in
mouldings
Method -A

TV
Method - B
In skirting trunking JCT

Non sheathed cable Multi-core cable


Non sheathed cables in
conduit or single-core or
multi-core cable in architrave
Method -A
Non sheathed cables in conduit
or single-core or multi-core cable
in window frames

Fixed on (Clipped direct), or spaced Method - C


less than 0.3 x cable diameter from
a wooden or masonry wall.
Single-core or mu lti-core ca bl es

Method - B
Fixed directly under a wooden or (Higher than standard ambient
temperatures may occur with this
masonry ceiling
installcition method)
Si ngle-core or mul ti-core cc-1 bles

Method - E, F or G
(Higher than standard ambient
Spaced from a cei Ii ng temperatures m ay occur with this
installation method)

Single-core or multi -core C(lb les

Single-core or multi-core cables: - - 2: O.J De


on unperforated tray
run horizontally or vertically Method - C
with item 2 of table Y-03

- ?.: 0. 3De

Single-core or multi-core cables: 2: 0.3 De


on perforated tray
run horizontally or vertically

Method - E or F

2: 0. 3De
20

20. Schedule of installation methods of cables for determining current carrying - capacity Cont...

Installation Method
Reference Method
Description Example
Single-core or multi-core cables: - - 2: 0 .3 Dc
on brackets or on a wire mesh tray
run horizontally or vertically Method - E or F

- - 2: 0.3De

Single-core or multi-core cables:


spaced more than 0.3 times the
cable diameter from a wall Method - E, F or G

Single-core or multi-core cables:


on a ladder
Method - E or F

Single-core or multi-core cable


suspended from or incorporating a
, support wire or harness
Method - E or F

Bare or non-sheathed
cables on insulators Method - G

Single core or multi-core cable in a


building void
v Method - B
Where 1.5 De ~V < 20 De
De

Non sheathed cables


in conduit Method - B
in a building void Where 1.5 De :::;V
in masonry having a thermal v
De
resistivity not greater than 2 K.m/W
• • •
1 1
LU

20. Schedule of installation methods of cables for determining current carrying - capacity Cont...

Installation Method
Reference Method
Description Example
Single core or multi-core cable
in conduit in a building void Method - B
in masonry having a thermal
De
v Where 1.5 De ::;V
resistivity not greater than 2 K.m/W

Non sheathed cables I I

in cable ducting in a building void Method - B


v
in masonry having a thermal Where 1.5 De ::;V
resistivity not greater than 2 K.m/W

Single core or multi-core cable


in cable ducting in a building void I I I

in masonry having a thermal Method - B


v Where 1.5 De ::;V
resistivity not greater than 2 De
K.m/W

Non sheathed cables


I Method - B
in cable ducting in masonry
v Where 1.5 De ::;V < 50 De
having a thermal resistivity not Dt'
greater than 2 K. m/W

Single core or multi-core cable


in cable ducting
Method - B
in masonry having a thermal y
De Where 1.5 De ::; V < 50 De
resistivity not greater than 2 I I

K.m/W

Single core or multi-core cable


- in a ceiling void
Method - B
- in a suspended floor
v Where 1.5 De ::;V < 50 De
De I

Non sheathed cables


in flush cable trunking in the floor
Method - B

Multi-core cable
in flush cable trunking in the floor
Method - B
20

20. Schedule of installation methods of cables for determining current carrying - capacity Cont ...

Installation Method
Reference Method
Description

Non sheathed cables


in flush trunking Method - B

ICT JCT

Multi-core cable
in flush trunking • • Ir• I

Non-sheathed cables Method - B


or single core cables in Where 1.5 De :::; V
conduit in an unventilated
cable channel run
horizontally or vertically
De
. ..
Non-sheathed cables
in conduit in an open or
Method - B
ventilated cable channel
in the floor

Sheathed single-core or
multi core cable in an open
or ventilated cable channel Method - B
run horizontally or
verticall y

Single-core or multi core


cable direct in masonry
having a thermal resistivity Method - C
not greater than 2 K. m/W -
without added mechanical
protection

Single-core or multicore
cable direct in masonry Method - C
having a thermal resistivity
not greater than 2 K.m/W
- with added mechanical
protection (e.g. capping)

Non-sheathed cables or
single-core cables in Method - B
conduit
In masonry having a
thermal resistivity not
greater than 2 K.m/W

Multicore cables in conduit


Method - B
In masonry having a
thermal resistivity not
greater than 2 K.m/ W
L..V

20 Schedule of installation methods of cables for determining current carrying - capacity Cont ...

Installation Method Installation Method


Description Exampl e
Multicore unarmoured cable
mtUitE
a
in conduit or in cable Method- D
ducting in the ground

Single-core unarmoured W ItttJ tt±i;j 8El±tl3

1:;:::1
cable in conduit or in cable Method - D
ducting in the ground

Sheathed, armoured or multicore


cables direct in the ground:
UJ±LI$ U±U B±IHS
--~ /~~ r--
- without added mechanical
- l I
I I
Method- D
I I
protection II'.,,.
;~
I I

Sheathed, armoured or multicore


cables direct in the ground:
twi Itt;LI Ltt:J;J 8 ! L1iU
~ ~ Method - D
With added mechanical ,,,.
protection (e.g. cable covers) -·-
•I•
I
7
Installation methods for flat twin
and earth cable clipped direct to a

~ll JI}
wooden joist above a plasterboard Method - 01
ceiling with a minimum U value
D
of 0.1 W/m 2 K and with thermal
insulation not exceeding 100 mm
in thickness

Installation methods for flat twin


and earth cable clipped direct to a
wooden joist above a plasterboard
ceiling with a minimum U value
-o -
Method - 02
of 0.1 W/m 2 K and with thermal
r
insulation exceeding 100 mm in
thickness
- ~
./

Installation methods for flat twin

~~
and earth cable in a stud wall with
thermal insulation with a mini-
mum U value of 0.1 W/m 2 K with
the cable touching the inner wall
surface
Q JI} Method - 03

Installation methods for flat twin


and earth cable in a stud wall with

~[~
thermal insulation with a mini-
mum U value of 0.1 W/m 2 k with
the cable not touching the inner
wal I surface
0

II} Method-04

Sour < IEE wiring Regulatil 11' se ent • ·th editi n


21

21 Current Carrying Capacity and Voltage Drop

SINGLE - CORE PVC INSULATED NON -ARMOURED

BS 6004/BS 6346

Ambient air temperature 30°C


Conductor operating temperature 70°C

PVC PVC Copper 0.310.5, 0.45/0.75, 0.6/1 kV

TABLE - A 1- Current carrying capacity

(Method F)
In free air or on a perforated cable tray
(Method A) (Method B) horizontal or vertical
Enclosed in conduit Enclosed in conduit (Method C)
In thermally on a wall, Clipped direct
insulating wall etc. .. or in trunking etc. .. Touching Spaced
Conduct by one diameter
or cross
sectional
area 2 Cables 3 or 4 2 Cables 3 or 4 2 Ca[,les 3 or 4 2 Cables 3 Cables 3 Cables 2 Cables
single cables single cables single cables single three three single phase ac or de
phase ac three phase ac three phase ac three phase ac
phase ac phase ac or 3 cables three
or de phase ac ordc phase ac or de flat phase ac or de
and flat and flat trefoi I phase ac flat
flat
touching touching
(mm 2) or trefoil. Horizontal Vertical
(A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
1 11 1.() .5 13.5 12 15.5 14 - - - - -
1.5 14.5 13.5 17.5 15.5 20 18 - - - - -
2.5 20 18 24 21 27 25 - - - - -
.4 26 24 32 28 37 33 - - - - -
6 34 31 41 36 47 43 - - - - -
10 46 42 57 50 65 59 - - - - -
16 61 56 76 68 87 79 - - - - -
25 80 73 101 89 114 104 131 114 110 146 130
35 99 89 125 110 141 129 162 143 137 181 162
50 119 108 151 134 182 167 196 174 167 219 ·197
70 151 136 192 171 234 214 251 225 216 281 254
95 182 164 232 207 284 261 304 275 264 341 311
120 210 188 269 239 330 303 352 321 308 396 362
150 240 216 300 262 381 349 406 372 356 456 419
185 273 245 341 296 436 400 463 427 409 521 480
240 321 286 400 346 515 472 546 507 485 615 569
300 367 328 458 394 594 545 629 587 56 '1 709 659
400 - - 546 467 694 634 754 689 656 852 795
500 - - 626 533 792 723 868 789 749 982 920
630 - - 720 611 904 826 1005 905 855 1138 1070
800 - - - - 1030 943 1086 1020 971 1265 1188
1000 - - - - 1154 1058 1216 1149 1079 1420 1337

Note - For rating factors-VCJri tion in ambient air temperature ref~r ta.hie Y-01
The data i tak n from BS 7( 71: 2008, Requirement ior Ele tri ill lnstllllation. IEE Wiring
Regu lations-Seventeenth Edition.
- See Table A2 for Voltage Drop.
L. I

21. Current Carrying Capacity and Voltage Drop

SINGLE - CORE PVC INSULATED NON - ARMOURED

BS 6004/BS 6346

Ambient air temperature 30°(


Conductor operating temperature 70°(

PVC PVC Copper 0.3/0.5, 0.45/0.75, 0.6/1 kV

TABLE - A2- Voltage drop

Voltage Drop (mV I A Im)

2 Cables single phase ac 3 or 4 cables three phase ac

Reference Reference Methods


Reference
C & F (clipped direct, Reference method C & F
Conduct 2 Cables Method Method
or on tray or in free air) (clipped direct, or on tray or in free air)
or cross
de A&B A&B
sectional (enclosed (enclosed Cables Cables Cables
area Cables Cables
in conduit in conduit touching, touching, spaced,
(mm
2
) or trunking) touching Spaced* or trunking) Trefoil Flat Flat
1 44 44 44 44 38 38 38 38
1.5 29 29 29 29 25 25 25 25
2.5 18 18 18 18 15 15 15 15
4 11 11 11 11 9.5 9.5 9 .5 9.5
6 7.3 7.3 7. 3 7.3 6.4 6.4 6.4 6.4'
10 4.4 4.4 4.4 4.4 3.8 3.8 3.8 3.8
16 2. 8 2.8 2.8 2.8 2.4 2.4 2.4 2.4
25 1.75 1.80 1.75 1.80 1.55 1.50 1.55 1.55
35 1.25 1.30 1.25 1.30 1.10 1.10 1 .10 1.15
50 0.93 1.00 0.95 0.97 0.85 0.82 0.84 0 .86
70 0.63 0.72 0.66 0.69 0.61 0.57 0.60 0.63
95 0.46 0 ..56 0.50 0.54 0.48 0.43 0.47 0 .51
120 0.36 0.47 0.41 0.45 0.41 0. 36 0.40 0.44
150 0.29 0.41 0.34 0.39 0. 3 6 0.30 0. 34 0.40
185 0.23 0.37 0.29 0.35 0. 32 0.26 0.31 0.36
240 0 .180 0.33 0.2 5 0.31 0.29 0.22 0.27 0.34
300 0.145 0 .31 0 .22 0 .29 0.27 0.190 0.25 0.32
400 0.105 0.29 0.20 0.27 0.25 0.175 0.24 0.31
500 0.086 0.28 0.185 0.26 0.25 0.160 0.23 0.30
630 0.068 0.27 0.175 0.25 0.24 0.150 0.22 0.29
800 0.05 3 - 0.165 0.25 - 0.145 0.22 0.29
1000 0.042 - 0.160 0.24 - 0.140 0.21 0 .28

Not -Ref r 1 ble /-0 I for ma irnum value of vollage drop in omumer in tallcition
-The cl, ta i · taken from B 7671: 008, Requirements for El 'ctri al In t, llation , IEE Wiring
R ·gulation -_ evente( nth Editi n
21

21 Current Carrying Capacity and Voltage Drop

SINGLE - CORE XLPE INSULATED NON - ARMOURED

BS 7889/BS 7211

Ambient air temperature 30°C


Conductor operating temperature 90°C

PVC XLPE Copper 0.6/1 kV

TABLE - 81- Current Carrying Capacity

(Method A) (Method B) (Method C) (Method F) (Method G)


Coduct-
Enclosed in Enclosed in Clipped direct In free air or on a In free air
or cross
conduit In conduit on a wall perforated cable
sectional
thermally or trunking tray etc horizontal Spaced
area
insulating wall or vertical etc by one cable
etc. .. diameter
Touching

2 Cables 3 or 4 2 Cables 3 or 4 2 Cables 3 or 4 2 Cables 3 cables 3 cables 2 Cables single


single- cables, single- cables single cables single three three phase ac or de or 3
phase three phase ac three- phase three phase ac phase ac phase ac cables three phase
phase ac
ac or de phase ae or de phase ac ae or de flat and or de flat flat trefoil ac flat
flat and touch in~ Horizontal Vertical
touching or trefoi
(mm 2 ) (A) . (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
1 14 13 17 15 19 17.5 - - -
1.5 19 17 23 20 25 23 - - -
2.5 26 23 31 28 34 31 - - -
4 35 31 42 37 46 41 - - -
6 45 40 54 48 59 54 - - -
10 61 54 75 66 81 74 - - -
16 81 73 100 88 109 99 - - -
25 106 95 133 11 7 143 130 161 141 135 182 161
35 131 117 164 144 176 161 200 176 169 226 201
50 158 141 198 175 228 209 242 216 207 275 246
70 200 179 253 222 293 268 310 279 268 353 318
95 241 216 306 269 355 326 377 342 328 430 389
120 278 249 354 312 413 379 437 400 383 500 454
150 318 285 393 342 476 436 504 464 444 577 527
185 362 324 449 384 545 500 575 533 510 661 605
240 424 380 528 450 644 590 679 634 607 781 719
300 486 435 603 514 743 681 783 736 703 902 833
400 - - 683 584 868 793 940 868 823 1085 1008
500 - - 783 666 990 904 1083 998 946 1253 1169
630 - - 900 764 1130 1033 1254 1151 1088 1454 1362
800 - - - - 1288 1179 1358 1275 1214 1581 1485
1000 - - - - 1443 1323 1520 1436 1349 1775 1671

Not .. - For rating Iactor. -Vari.Hi on in .imhienl , 11 tc1 ip ·'rdtur ref ·rt, bi"' Y-01
Th data i. taken fr m lL 7 >71: _()08, Require ment f ir El tri I In tallation , IEE\ 'irin
R gulcl ions-S venteenth dition.
- Se Table 132 for Volt, ge Dr )p.
LI

21. Current Carrying Capacity and Voltage Drop

SINGLE - CORE XLPE INSULATED NON -ARMOURED

BS 7889/BS 7211

Ambient air temperature 30°C


Conductor operating temperature 90°C

PVC XLPE Copper 0.6/1 kV

TABLE - 82- Voltage drop

Voltage Drop (mV I A Im)

2 Cables, single phase ac 3 or 4 cables, three phase ac

Conduc- 2 Reference Reference Methods C, F & Reference


Reference Methods C,F & G (clipped
tor cross Cables Method G (clipped direct, on tray Method
direct, on tray or in free air)
sectional de A&B or in free air) A&B
area (enclosed (enclosed
in conduit Cables Cables in conduit Cables Cables Cables
or touching spaced* or touching, touching, Spaced*
trunking) trunking) Trefoil Flat Flat
(mm 2)
1 46 46 46 46 40 40 40 40
LS 31 31 31 31 27 27 27 27
2.CJ 19 19 19 19 16 16 16 16
4 12 12 12 12 10 10 10 10
6 7.9 7.9 7.9 7.9 6.8 6.8 6.8 6.8
rn 4.7 4.7 4.7 4.7 4 4 4 4
16 2.9 2.9 2.9 2.9 2.5 2.5 2.5 2.5
25 1.85 1.90 1.85 1.85 1.65 1.60 1.60 1.65
35 ·1.35 1.35 1.35 1.35 1 .15 1.15 1.15 1.20
50 0.99 1.05 1.00 1.00 0.90 0.87 0.87 0.89
70 0.68 0.75 0.71 0.73 0.65 0.6 "1 0.62 0.65
95 0.49 0.58 0.52 0.56 0.50 0.45 0.46 0.49 I

120 0.39 0.48 0.43 0.47 0.42 0.3 7 0.38 0.42


I
150 0.32 0.43 0.36 0.41 0.37 0.31 0.32 0.37
I
I 185 0.25 0.37 0.30 0.36 0.32 0.26 0.28 0.33
240 0.'190 0.33 0.25 0.31 0.29 0.22 0.24 0.29
300 0.155 0.3 I 0.22 0.29 0.27 0.195 0.21 0.27
400 0.120 0.29 0.20 0.27 0.25 0.175 0.195 0.26
500 0.093 0.28 0.185 0.26 0.24 0.160 0.180 0.25
630 0.072 0.27 0.175 0.2S 0.23 0.150 0.170 0.24
800 O.OS6 - 0.170 0.25 - 0.145 0.165 0.24
1000 0.045 - 0.165 0.24 - 0.140 0.165 0.24

'ot -R er table X-01 fr r n irnum vdlUL' >f \Oltage dr pin con umcr in tallation
-Th data ic; lilk n fn m l3 ~671: _008 R quirem nt or El tri al Install tion , IEE Wiring
Reguldtion -S v ntP •nth Fditton.
21

21. Current Carrying Capacity and Voltage Drop

SINGLE - CORE PVC INSULATED ARMOURED

BS 6346
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 70°C

PVC Aluminium PVC Copper 0.6/1 kV

TABLE - Cl- Current carrying capacity

Coduct- Clipped direct In free air or on a perforated cable tray, horizontal or vertical
or cross Laid direct (Method C) (Method F)
setional in ground
area

(mm 2 ) Touching Touching Spaced by one cable diameter

2 Cables 3 Cables 2 Cables 3 or 4 2 Cables 3 cables 3 cables


single three single cables single three three 2 cables single phase
phase ac phase ac phase three phase ac phase phase ac a.c 3 or 4 cables
touching touching ac or de phase or de ac trefoil three-phase a.c
flat ac flat flat flat
Horizontal Vertical Horizontal Vertical
(A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
50 238 202 193 179 205 189 181 229 217 230 212
70 292 247 245 225 259 238 231 287 272 286 263
95 349 294 296 269 311 285 280 349 332 338 313
120 396 332 342 309 360 327 324 401 383 385 357
150 443 369 393 352 413 373 373 449 429 436 405
185 497 412 447 399 469 422 425 511 489 490 456
240 571 470 525 465 550 492 501 593 568 566 528
300 640 521 594 515 624 547 567 668 640 616 578
400 708 569 687 575 723 618 657 737 707 674 632
500 780 618 763 622 805 673 731 810 777 721 676
630 858 668 843 669 891 728 809 893 856 771 723
800 895 695 919 710 976 777 886 943 905 824 772
1000 939 729 975 737 1041 808 945 1008 967 872 816

onditions rnn id ·r d for bi I id dir t in gr und

tandard depth of laying 0.5 m


Thermal resi_ tivil 'of oil 1.2 K.m/W
tc nclard ground temp rature I '1°C

Ford 'plh nth r than 0.5 m, refer table Y-1~


For thermal r sistivity in different oil onditi n , refer table Y-14
For rating foclors-Variation in ground temperatur r fer t ble '-02

For re ting fa !ors-Vari tion in ambi nt air t mp ralure r fer tabl Y-01

Note: The data ar" taken from l3 7671: 2008, Requir •m "nt for fie lrical In. tallations,
I -E Wiring R gulations- ev nteenth Edition ER 69- 'O erie 0 r ubli cltion tFor L.1hles l..rnl dired 111 ground nwtho !).
Sec Table C-2 for Voltage Drop
.L I

21. Current Carrying Capacity and Voltage Drop

SINGLE - CORE PVC INSULATED ARMOURED

BS 6346
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 70°C

PVC Aluminium PVC Copper 0.6/1 kV

TABLE - C2- Voltage drop

Clipped direct, on tray or free air


(Methods C & F)
2 cables d.c.

Conductor 2 cables, single phase a.c. 3 or 4 cables, three phase a.c.


cross
sectional
area

Touching Spaced Trefoil and Flat and Flat and


touching Touching spaced

(mm 2 ) (mV/Nm) (mV/Nm) (mV/Nm) (mV/A/m) (mV/Nm) (mV/Nm)

50 0.93 0.95 0.97 0.82 0.84 0.86


70 0.63 0.68 0.72 0.58 0.62 0.68
95 0.46 0.52 0.58 0.45 0.50 0.57
120 0.36 0.43 0.50 0.37 0.43 0.50
150 0.29 0.3 7 0.44 0.32 0.38 0.45
185 0.23 0.32 0.39 0.27 0.34 0.41
240 0.180 0.27 0.35 0.23 0.30 0.37
300 0.145 0.24 0.32 0.21 0.28 0.34
400 0.105 0.22 0.30 0.195 0.26 0.32
500 0.086 0.21 0.29 0.180 0.25 0.30
630 0.068 0.195 0.27 0.170 0.23 0.28
800 0.053 0.185 0.25 0.160 0.22 0.26
1000 0.042 0.180 0.24 0.155 0.21 0.24

Nole : -Refer table · -0 I for maximum valu of voltage drop in consum r in tallation
-The datJ is taken from BS 7671: 2008, Requirements for Ele tri al Installations, IEE Wiring
Regulations-Sevenleenlh Edition.
21

21. Current Carrying Capacity and Voltage Drop

SINGLE - CORE XLPE INSULATED ARMOURED

BS 5467
Ambient air temperature 30°C
Standard ground temperature 1 5°C
Conductor operating temperature 90°C
PVC Aluminium XLPE Copper 0.6/1 kV

TABLE - Dl- Current carrying capacity

Laid
direct in Clipped direct In free air or on a perforated cable tray, horizontal or vertical
ground (Method C) (Method F)
'
Spaced by one cable dia meter
Touching Touching
2 Cab I · s single 3 or 4 cables
pha e ac three pha e ac
Conductor 2 Cables 3 cables 2 Cables 3 or 4 2 Cables 3 cables 3 cables Horizontal Vertical Horizontal Vertical
cross single three single cables single three three
sectional phase ac pha. e cc phase ac three phase ac phase ac pahase
area touching touching or de phase ac or de flat ac trefoil
flat flat flat

(mm 2 ) A A A A A A A A A A A
50 274 231 237 220 253 232 222 282 266 288 266
•.: 70 337 283 303 277 322 293 285 357 33 7 358 331
95 403 337 367 333 33 g 352 346 436 412 425 393
120 458 381 425 383 449 405 402 504 477 485 449
150 510 424 488 437 516 462 463 566 539 549 510
185 574 474 557 496 587 524 529 643 614 6 '18 574
240 661 542 656 579 689 612 625 749 714 715 666
300 739 601 755 662 792 700 720 842 805 810 755
400 820 657 853 717 899 767 815 929 889 848 797
500 910 720 962 791 1016 851 918 1032 989 923 871
630 1001 781 1082 861 1146 935 1027 1139 1092 992 940
800 1055 8'16 1170 904 1246 987 1 ·119 1204 1155 1042 978
1000 1155 860 1261 961 1345 1055 '1214 1289 1238 1110 1041

Conditi ms considered for abl s laid dire t in ground

Standard depth of laying O.S m


Thermal resistivity of soil 1.2 K.rn/W
Standard ground temperature 15°C

For depth other than 0.5 m, ref r tab! ' Y- -13


For Lhermal re istivily in different soilonclitions, ref r table Y- 14
For rating factors-Variation in ground t •rnperature refer table Y-02

For rating factors-Variation in ambi nl air temperalur refer table Y-01

Not : Thes data are taken from BS 7671: 2008, Requirements for Electri <I lnstall<ltions,
IEE Wiring Regulation -Seventeenth [dition & ERA 69-30 eries of publications For uhl ·s kiid direc.t in Liround m thi d).
See Table 02 for Voll age drop
21. Current Carrying Capacity and Voltage Drop

SINGLE - CORE XLPE INSULATED ARMOURED

BS 5467
Ambient air temperature 30°C
Standard ground temperature 15 °C
Conductor operating temperature 90°C
PVC Aluminium XLPE Copper 0.6/1 kV

TABLE - 02 - Voltage Drop

Clipped direct, on tray or free air


(Methods C & F)
2 cables d.c.

Conductor
2 cables, single phase a.c. 3 or 4 cables, three phase a.c.
cross
sectional
area

Touching Spaced Trefoil and Flat and Flat and


touching Touching spaced

,
(mm 2 ) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m)

50 0. 98 1.00 1.00 0.87 0.88 0.90


70 0.67 0 .71 0.75 0.62 0 .65 0.70
95 0.49 0.55 0.60 0.47 0.52 0.58
120 0.39 0.45 0.51 0.39 0.44 0.51
150 0.31 0.38 0.45 0.3 3 0.39 0.45
185 0.25 0.33 0.40 0 .28 0.34 0.41
240 0.195 0 .28 0.35 0 .24 0.30 0.37
300 0.155 0.25 0.32 0.21 0.28 0.34
400 0.115 0 .22 0.30 0.195 0.27 0.33
500 0.09 3 0.21 0 .29 0.180 0 .25 0.31
630 0.07 3 0.195 0.27 0.170 0.24 0.29
800 0.056 0.190 0.27 0.165 0.23 0.26
1000 0 .045 0.180 0.25 0 .155 0 .2 1 0.24

Note: -Refer table /-01 ior ma.·irnum value of vollage drop in consumer in tallation
-The data is taken from 85 7671: 2008, Requirements ior Electrical Installations, IEE Wiring
RegulJtions- ·eventeenth Edition.
21

21 Current Carrying Capacity and Voltage Drop

MULTI -CORE PVC INSULATED NON - ARMOURED

BS 6004/BS 6346

Ambient air temperature 30°C


Conductor operating temperature 70°C

PVC PVC Copper 0.310.5, 0.6/1 kV

TABLE - E

Enclosed in conduit Enclosed in conduit Clipped direct In free air or on a Voltage drop
in thermally on a wall or in perforated cable
insulating wall etc. trunking etc. tray etc., horizontal
or vertical
Conductor (Method A) (Method B) (Method C) (Method El (mV/Nm)
cross
sectional
1 Two 1Three or 1 Two 1Three or 1 Two 1Three or 1 Two 1Three or 2 core 2 core 3 or 4
area core cable 4 core core cable 4 core core 4 core core 4 core cable de cable core
single cable, single cable, cable cable, cable cable, single cable
phase ac three phase ac three single three single three phase three
or de phase ac or de phase ac phase ac phase ac phase ac phase ac ac phase
or de or de ac
(mm 2) (A) (A) (A) (A) (A) (A) (A) (A)
1 11 10 13 11.5 15 1.1.5 17 14.5 44 44 38
1.5 14 13 16.5 15 19.5 17.5 22 18.5 29 29 25
2.5 18.5 17.5 23 20 27 24 30 25 18 18 15
4 25 23 30 27 36 32 40 34 11 n 9.5
6 32 29 38 34 46 41 51 43 7.3 7.3 6.4
10 43 39 52 46 63 57 70 60 4.4 4.4 3.8
16 57 52 69 62 85 76 94 80 2.8 2.8 2.4
25 75 68 90 80 112 96 119 101 ·1.75 1 .75 LS
35 92 83 111 99 138 1"19 148 126 1.25 1.25 1 .1
50 110 99 133 118 168 144 180 153 0.93 0.94 0.81
70 139 125 168 149 213 184 232 196 0.63 0.65 0.57
95 167 150 201 179 258 223 282 238 0.46 0.50 0.43
120 192 172 232 206 299 259 328 276 0.36 0.41 0.35
150 219 196 258 225 344 299 379 319 0.29 0.34 0 .29
185 248 223 294 255 392 341 434 364 0.23 0.29 0.25
240 291 261 344 297 461 403 514 430 0.18 0.24 0.21
300 334 298 394 339 530 464 593 497 0.145 0.21 0.185
400 - - 470 402 634 557 715 597 0.105 0.185 0.160

For rating fa tars - Variation in ambient air temperature refer table Y-0 J

Note: -Ref r table X-o-1 for maximum valu of voltag, drop in consumer in tallation
-The data is taken from BS 7 71: 2008, Requiremen ior Ele trical In. tc II tion , IEE Wiring
Regulation -Seventeenth Edition.
21

21 Current Carrying Capacity and Voltage Drop

MULTI - CORE XLPEINSULATED NON - ARMOURED

BS 5467

Ambient air temperature 30°C


Conductor operating temperature 90°C

PVC XLPE Copper 0.6/1 kV

TABLE - F

Enclosed in conduit Enclosed in conduit Clipped direct In free air or on a Voltage drop
in thermally on a wall or in perforated cable
insulating wall etc. trunking etc. tray etc., horizontal
or vertical
Conductor (Method A) (Method 8) (Method Cl (Method E) (mV/A/m)
cross
sectional
area 1 Two 1Three or 1 Two 1Three or 1 Two 1Three or 1 Two 1Three or 2 core 2 core 3 or 4
core cable 4 core core cable 4 core core 4 core core 4 core cable cable core
single cable, single cable, cable cable, cable cable, de single cable
phase ac three phase ac three single three single three phase three
or de phase ac or de phase ac phase ac phase ac phase ac phase ac ac phase
(mm 2 ) ordc or de ac
(A) (A) (A) (A) (A) (A) (A) (A)
1 14.5 13 17 15 19 17 21 18 46 46 40
1.5 18.5 16.5 22 19.5 24 22 26 23 31 31 27
2.5 25 22 30 26 33 30 36 32 19 19 16
4 33 30 40 35 45 40 49 42 12 12 10
6 42 38 51 44 .58 52 63 54 7.9 7.9 6.8
10 57 51 69 60 80 71 86 75 4.7 4.7 4
16 76 68 91 80 107 96 11 5 100 2.9 2.9 2.5
25 99 89 119 105 138 119 149 127 1.85 1.9 1.65
35 121 109 146 128 1 71 147 185 158 1.35 1.35 1.15
50 145 no 175 154 209 179 225 192 0.98 1.00 0.87
70 183 164 221 194 269 229 289 246 0.67 0.69 0.60
95 220 197 265 233 328 278 352 298 0.49 0.52 0.45
120 253 227 305 268 382 322 410 346 0.39 0.42 0.37
150 290 259 334 300 441 3 71 473 399 0.31 0.35 0.30
185 329 295 384 340 506 424 542 456 0.25 0.29 0.26
240 386 346 459 398 599 500 641 538 0.195 0.24 0.21
300 442 396 532 455 693 576 741 621 0.155 0.21 0.185
400 - - 625 536 803 667 865 741 0.12 0.19 0.165

For rating factor - Variation in ambient air t rnperc tur refer t. ble Y-0 I

Note: -R"fer tnhle X-01 for ma, imum value of 1oltage drop in onsumer inst,1llcllion
-The data is taken from B 7671: 2008, Requir menL ior Electri Ji Installations, JEE Wiring
Regulations-Seventeenth Edi ! ion.
21

21 Current Carrying Capacity and Voltage Drop

MULTI -CORE PVC INSULATED ARMOURED

BS 6346
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 70°C

PVC Steel PVC PVC Copper 0.6/1 kV

TABLE - G

Conductor Laid direct in Clipped direct In free air or on a Voltage drop


cross sectional ground (Method C) perforated
area cable tray etc.,
horizontal or vertical
(mV/Nm)
(Method E)

1 three or four 1 two core 1 three or 1 two core 1 three or Two core 2 core cable 3 or 4 core ,
core cable three cable, single four core cable, single four core cable de single phase cable three !
phase phase ac or cable three phase ac or cable three ac phase ac :
ac de phase de phase
ac ac
(mm 2 ) (A) (A) (A) (A) (A)
1.5 27 21 18 22 19 29 29 25
2.5 y=-.) 28 2c
.) 31 26 18 18 15
4 47 38 33 41 35 11 n 9.5
. 6 59 49 42 53 45 7.3 7.3 6.4
10 78 67 58 72 62 4.4 4.4 3.8
16 101 89 77 97 83 2.8 2.8 2.4
25 132 118 102 128 110 1 .75 1 .75 1.5
35 159 145 125 15 7 135 1.25 1.25 1.1
50 188 175 151 190 163 0.93 0.94 0.81
70 233 222 192 241 207 0.63 0.65 0.57
95 279 269 231 291 251 0.46 0.50 0.43
120 317 310 267 336 290 0.36 0.41 0.35
150 355 356 306 386 332 0.29 0.34 0.29
185 401 405 348 439 378 0.23 0.29 0.25
240 462 476 409 516 445 0.18 0.24 0.21
300 517 547 469 592 510 0.145 0.21 0.185
400 580 621 540 683 590 0.105 ().185 0.16

Conditions con idered for cables laid direct in ground

tandard depth of laying o.s Ill


Stc ndard th rmal resistivity of oil 1.2 K.m/W
Stancbrd ground temperature 15°C

For depth other than 0.5 m, refer table Y-11


For thermal resistivity in differ nt soil ondition , rc:.i rt hie Y-15
For rating factors-Variation in ground temperature ref r tJble Y-02

For rating factor.-Variation in ambi =-nt Jir t mperatur ref r table Y-01

Nol<: : -Refer tabl X-01 ior maximum value oi voltag drop in consumer installation
-The data i taken from BS 7671: 2008, Requir m nts for Etectrical Installations, IEE Wiring
Regula lion -S ·venteenth Edition & ERA 69- ' 0 s ries of publications (I ot ohlC's laid din•ct in ground methorl1.
21

21 Current Carrying Capacity and Voltage Drop

MULTI - CORE XLPE INSULATED ARMOURED

BS 5467
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 90 °C

PVC Steel PVC XLPE Copper 0.6/1 kV

TABLE - H

Conductor Laid direct in Clipped direct In free air or on a Voltage drop


cross sectional perforated cable tray
area ground (Method C) etc.,
horizontal or certical
(Method E) (mV/Nm)

1 three or four 1 two core 1 three or 1 two core 1 three or Two core 2 core cable 3 or 4 core
core cable three cable, single four core cable, single four core cable de single phase cable three
phase ac phase ac or cable three phase ac or cable three ac phase ac
de phase ac de phase ac

(mm 2) (A) (A) (A) (A) (A)


1.5 32 27 23 29 25 31 31 27 .
2.5 42 36 31 39 33 19 19 16
4 55 49 42 52 44 12 12 10
6 69 62 53 66 56 7.9 7.9 6.8
10 92 85 73 90 78 4.7 4.7 4.0
16 119 110 94 115 99 2.9 2.9 2.5
25 152 146 124 152 131 1.85 1.90 1.65
35 182 180 154 188 '162 1.35 1.35 us
50 217 219 187 228 197 0.98 1.00 0.87
70 266 279 238 291 251 0.67 0.69 0.60
95 319 338 289 354 304 0.49 0.52 0.45
120 363 392 335 410 353 0.39 0.42 0.37
150 406 451 386 472 406 0.31 0.35 0.30
185 458 515 441 539 463 0.25 0.29 0.26
240 529 607 520 636 546 0.195 0.24 0.21
300 592 698 599 732 628 0.155 0.21 0.185
400 667 787 673 847 728 0.120 0.190 0.165

Con lition consider cl for ahl I 1id dire t in ground

St, ndard depth of I. ing 0.5 m


St nclard thermal resistivit of ~oil J ._ K.m/W

Stl ndarcl ground temperature I r.: oc

Fe r depth other rhan 0.5 m, refer table Y-1 .


For thermal re ·istivit 'in differ nt ·oil conditions, re ·rt bi Y-1 r:
For rating factors-Variuti m in ground temperatur refer table Y-02

For rating factors-Variation in ambient air ternperatur r •ier table Y-01

Not : -Refer table /-01 for maximu~ value of volttige drop 111 con umer instzilhtion
-The datJ i tak n from HS 7671: ?008, Requir m m for El ctrical In ·ttillations, IEE Wiring
Regulations-Seventeenth Edition & ERA 69-30 series of publi ~atiom (for cclbl 'S 1.)1(1 din·l t in ground nwtho
21

21 Current Carrying Capacity and Voltage Drop

MULTI-CORE XLPE INSULATED NON -ARMOURED

BS 5467

Ambient air temperature 30°C


Conductor operating temperature 90°C

PVC XLPE Aluminium 0.6/1 kV

TABLE - I

Enclosed in conduit in Enclosed in Clipped direct In free air or on a Voltage drop


thermally insulating conduit on a wall perforated cable
wall etc. or in trunking etc. tray etc, horizontal
Conductor (Method C) or vertical
cross (Method 8) (Method E) (mV/Nm)
sectional (Method A)
area

1 Two con 1Three or 1 Two 1Three or 1 Two 1Three or 1 Two 1Three or 2 core 2 core 3 or 4
cable 4 core core cablE 4 core core cable 4 core core cablE 4 core cable de cable core
single cable, single cable, single cable, single cable, single cable
phase ac three phase ac three phase ac three phase ac three phase three
or de phase ac or de phase ac or de phase ac or de phase ac ac phase
(mm 2 ) ac
(A) (A) (A) (A) (A) (A) (A) (A)
16 60 55 72 64 84 76 91 77 4.8 4.8 4.2
25 78 71 94 84 101 90 108 97 3.1 3.1 2.7
, 35 96 87 115 103 126 112 135 120 2.2 2.2 1.95
50 115 104 138 124 154 136 164 146 1.60 1.65 1.45
70 145 131 175 156 198 174 211 187 1.1 () 1 .1 5 0.97
95 175 157 210 188 241 211 257 227 0.82 0.84 0.72
120 - 180 - 216 - 245 - 263 - 0.58
150 - 206 - 240 - 283 - 304 - 0.47
185 - 233 - 272 - 323 - 347 - 0.39
240 - 273 - 318 - 382 - 409 - 0.31
300 - 313 - 364 - 440 - 471 - 0.26

For rating factors - Variation in ambient air temp rature refer table Y-01

Note : -Refer table X-01 for maximum value of voltage drop in consum r installt; tion
-The data is tak n from BS 7671: 2008, Requir ments for Electrical In tallations, IEE Wiring
Regulations-Seventeenth Edition.
21

21 Current Cur 1 ing Capacity and Voltage Drop

MULTI - CORE XLPE INSULATED ARMOURED

BS 5467
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 90°C

PVC Steel PVC XLPE Aluminium 0.6/1 kV

TABLE - J

Conductor cross Laid direct in ground Clipped direct In free air or on a Voltage drop
sectional area (Method C) perforated cable tray etc.,
horizontal or vertical
(Method E)
(mV/Nm)

1 two core 1 three or 1 two core 1 three or Two core 2 core cable 3 or 4 cme J
1 three or four core cable, singl E four core cable, single four core cable de single phase cable three I
(mm 2 ) cable three phase ac phase ac or cable three phase ac or cable three ac phase ac
de phase ac de phase ac

(A) (A) (A) (A) (A)


16 91 82 71 85 74 4.8 4.8 4.2
25 116 108 92 112 98 3.1 3.1 2.7
35 139 132 113 138 120 2.2 2.2 1.95
50 165 159 137 166 145 1.60 1.65 1.45
70 203 201 174 211 185 1.10 1 .15 0.97
95 244 242 214 254 224 0.82 0.84 0.72
120 278 - 249 - 264 - - 0.58
150 311 - 284 - 305 - - 0.47
185 .353 - 328 - 350 - - 0.39
240 409 - .386 - 418 - - 0.31
300 461 - 441 - 488 - - 0.26

Conditions considered for cable icJ clir et in ground

~ tllndard depth of laying 0.5 m


Standard thermal resistivity of soil 1.2 K.m/W
StandJrd ground l mperature sc
1 0

For cl pth other than 0.5 m, ref •r tc1blc Y-13


For thermal resistivity in differ nt soil conditions, refer table Y-15
For rating factors-Variation in ground temperature refer table Y-02

For rating f'" ctors-Variation in ambient cir temperature refer table Y-01

Note: -R fer table X-01 for maximum value of voltag' drop in consumer installation
-The data is tak n from BS 7671: 200B, Requir •ment for Electrical lnstallations,IEE Wiring
Regulations-~event nth Edi ion & ERA 69- 0 series of publication rror (,.lhle ... l,ml drre 1 in ground rnethocl).
21

21 Current Carrying Capacity and Voltage Drop

SINGLE - CORE XLPE INSULATED NON - ARMOURED

BS 7889/BS 7211

Ambient air temperature 30°C


Conductor operating temperature 90°C

PVC XLPE Aluminium 0.6/1 kV

TABLE - K1- Current Carrying Capacity

In free air
Enclosed in Enclosed in Clipped direct In free air or on a perfo- (Method G)
conduit in conduit on a wall (Method C) rated cable tray, horizontal Spaced by one
thermally or in trunking etc. or vertical cable diameter
insulating wall etc. (Method B) (Method F)
Conductor 2 cables, single
(Method A) Touching phas a.c or d.c or 3
cross cable. . pha e a.c
sectional flat
area

2 Cables 3 or 4 2 Cables 3 or 4 2 Cables 3 or 4 2 Cables 3 cables 3 cables Horizonta l Vertical


single cables single cables single cables single three three
phase.ac three phase ac three phase ac three phase ac phase ac phase ac
or de phase ac or de phase ac or de flat phase ac or de flat flat trefoil
and flat and
touching touching
(mm 2 ) or trefoil
(A) (A) (A) {A) (A) {A) (A) (A) (A) (A) (A)

50 125 113 157 140 154 136 184 165 159 210 188
70 158 142 200 179 198 174 237 215 206 271 244
95 19"1 171 242 217 241 211 289 264 253 332 300
120 220 197 281 251 280 245 337 308 296 387 351
150 253 226 307 267 324 283 389 358 343 448 408
185 288 256 351 300 371 323 447 413 395 515 470
240 338 300 412 351 439 382 530 492 471 611 561
300 387 344 471 402 508 440 613 571 544 708 652
380 - - - - 658 594 679 628 638 798 742
480 - - - - 765 692 786 728 743 927 865
600 - - - - 871 791 903 836 849 1058 990
740 - - - 1001 911 1025 951 979 1218 1143
960 - - 1176 1072 1191 1108 1151 1440 1355
1200 - - - - 1333 1217 1341 1249 1307 1643 1550

For rating iactors - Variation in ambient air 1·empC'rature refer tdbl Y-0 l

Nole -R fer tabl X-0 I for ma.'imum value of voltilge drop in onsum Jr instc llation
-The data is taken from BS 7671: 2008, Requi1emenls for Electric'11 lnstalbtion. , !E E VVinng

Regulations-Seventeenth Edition .

-See Table K2 for Voltage Drop.


21

21 Current Carrying Capacity and Voltage Drop

SINGLE - CORE XLPE INSULATED NON - ARMOURED

BS 7 889/ BS 7211

Ambient air temperature 30°C


Conductor operating temperature 90°C

PVC XLPE Aluminium 0.6/1 kV

TABLE - K2- Voltage Drop

Voltage Drop (mV I A Im)

2 Cables single phase ac 3 or 4 cables three phase ac

Conduc- 2 Cables Enclosed in Enclosed in Clipped direct, on tray or


Clipped direct, on tray
tor cross de conduit or or in free air conduit or in free air
sec- trunking (Methods C, F & G) trunking (Methods C, F & G)
tional (Methods (Methods
area A & B) A & B) Cables Cables Cables
Cables Cables touching, touching, spaced,
touching spaced
trefoil flat flat
(mm 2)
50 1.65 1.72 1.66 1.68 1.46 1.45 1.46 1.48 !
70 1 .1 3 1.21 1.14 1.15 1.04 0.98 1.00 1.02
95 0.82 0.91 0.84 0.94 0.79 0.73 0 .75 0 .78
120 0.65 0.74 0.67 0.70 0.64 0.59 0.61 0.64
150 0.5 3 0.61 0. 55 0.58 0.54 0.47 0.5 0 0.54
185 0.42 0.5 3 0.46 0.49 0.45 0.3 9 0.43 0.47
240 0.32 0.4 3 0.36 0.41 0.38 0.3 2 0.3 5 0.41
300 0.26 0.38 0.3 1 0.36 0.34 0.27 0.31 0.37
380 0.20 - 0.27 0.33 0.31 0.23 0.28 0.34
480 0.160 - 0.2 3 0.30 0.28 0 .20 0.27 0 .3 2
600 0.130 - 0.21 0.28 0.2 6 0.185 0.25 0.31
740 0.105 - 0.19 0.27 - 0.170 0.23 0.30
960 0.080 - 0.18 0.26 - 0.160 0 .23 0.30
1200 0.064 - 0.17 0.25 - 0.150 0.22 0.29

Note: -Ref r table X-01 for maximum value of voltage drop in consumer installation

-The datJ i taken from BS 7671: 2008, Requirements for Ele trical In tallations, IEE Wiring

Regulations-Seventeenth Edition.
21

21 . Current Carrying Capacity and Voltage Drop

SINGLE- CORE XLPE INSULATED ARMOURED

BS 5467
Ambient air temperature 30°C
Standard ground temperature 15 °C
Conductor operating temperature 90°C
PVC Aluminium XLPE Aluminium 0.6/1 kV

TABLE - L1- Current carrying capacity

Clipped direct In free air or on a perforated cable tray, horizontal or vertical


(Method C) (Method F)
Laid direct
in ground
Conductor Spaced by one cable diameter
Touching Touching
cross
2 cables single 3 or 4 cables
sectional phase ac 3 phase ac
area
2 Cables 3 cables 2 Cables 3 or 4 2 Cables 3 Cables, 3 cables Horizon- Vertical Horizon- Vertical
single three single cables single 3 phase 3 phase tal tal
phase phase phase three phase ac a.c
ac ac ac or de phase ac or de flat trefoil
touching touching flat ac flat
(mm 2 ) flat
(A) (A) (A) (A) (A) (A) (A) (A) (A) (A) (A)
50 209 176 179 165 192 176 162 212 199 215 192
70 257 217 228 209 244 222 207 269 254 270 244
95 308 259 276 252 294 267 252 328 310 324 296
120 350 293 320 291 340 308 292 378 358 372 343
150 391 327 368 333 390 352 337 429 409 424 394
185 442 369 419 378 444 400 391 490 467 477 447
240 512 425 494 443 521 468 465 576 549 554 523
300 575 475 568 508 597 536 540 654 624 626 595
380 645 528 655 573 688 608 625 735 704 693 649
480 722 586 747 642 786 685 714 825 790 765 717
600 795 640 836 706 880 757 801 909 872 832 780
740 868 689 934 764 988 824 897 989 950 890 835
960 960 753 1056 838 1121 911 1014 1094 1052 970 911
1200 1037 806 1163 903 1236 990 1118 1187 1141 1043 980

Condition con -idered for .( ble lnid direct in ground

Stand ml depth oi laying 0.5 m


Therm( I resistivity of soil 1.2 K.m/W
Standard ground temperature 1s c
0

For depth other thJn 0. S rn, reier le ble Y-1


For thermal r "'.i. tivity in diff renl soil onditions, ref r tabl Y-15
For rating foctor -VJriation in ground temperature r fer table Y-02

For rating factor -Variation in ambi nt air temperature refer table Y-0 I

Note: Th e ciata are taken from BS 7671: 2008, Requirements for Ele tri al Installations,
IEE Wiring Regu lations-Seventeenth Edition & ERA Gq-· 0 series of pul lications (I or al les IJicl direct in ground m >lhocO.

S e Table L2 for Voltage Drop.


21

21. Current Carrying Capacity and Voltage Drop

SINGLE - CORE XLPE INSULATED ARMOURED

BS 5467
Ambient air temperature 30°C
Standard ground temperature 15°C
Conductor operating temperature 90°C
PVC Aluminium XLPE Aluminium 0.6/1 kV

TABLE - L2- Voltage drop

Voltage Drop
(mV I A Im)

Conductor
cross 2 cables, single phase a.c. 3 or 4 cables, three ph ase a.c.
sectional
area

2 cabl es d.c. Touching Spaced In trefoil Flat & touching Flat an d sp ,1c<:' cl
tou ching

(111111 2)

I
50 1.60 1.60 1.60 1.40 1.40 1.40
70 1.10 us 1.15 0.98 1.00 1.05
95 0.82 0.85 0.90 0.74 0.78 0.83
120 0.66 0.69 0. 74 0.60 0.64 0.70
150 0.52 0.57 0.62 0.49 0.54 0.60
185 0.42 0.47 0.54 0.41 0.47 0.53
240 0 .32 0.39 0.45 0.34 0.39 0.46
300 0.26 0.33 0.40 0.29 0.34 0.41
380 0.21 0.29 0.36 0.25 0.32 0.38
480 0.160 0.25 0.34 0.22 0.29 0.35
600 0.130 0.24 0. 31 0.20 0.27 0.33
74 0 0.105 0.22 0 .29 0 .190 0.26 0.30
960 0.080 0.20 0.27 0.175 0.24 0.28
1200 0.064 0.190 0.25 0.165 0.22 0.26

Note : -Ret ·r table, -0 I for mJximum value of volte. ge drop in consumer installation
-The data i tak n from B 767 I: .... 008, Requirem nls for Electrical In tallation , IEE Wiring
Regulations-Seventeenth Edition.
21

21 Current Carrying Capacity and Voltage Drop

MULTI CORE PVC/XlPE INSULATED FLEXIBLE CORDS

BS 6500

Ambient air temperature 30°(


Conductor operating temperature 60°(

PVC PVC/XLPE Copper 0.3/0.5 kV

TABLE - M

Conductor Current-carrying capacity Voltage drop Maximum mass


Cross- sectional supportable by
area Single Three d.c. or Three-phase twin flexible cord
phase Phase single-phase a.c.
a.c. a.c. a.c.

(mm 2) (A) (A) mV/A/m mV/A/m kg


0.5 3 3 93 80 2
0.75 6 6 62 54 3
1 10 10 46 40 5
1.25 13 - 37 - 5
1.5 16 16 32 27 5
2.5 25 20 19 16 5
4 32 25 12 10 5
,
CORRECTION FACTOR FOR AMBIENT TEMPERATURE

60 °C thermoplastic (pvc) or thermosetting insulated cords

Ambient Temperature °C 35 40 45 50 55
Correction factor 0.91 0.82 0.71 0.58 0.41

85 °C and 90 °C thermoplastic (pvc) or thermosetting insulated cords

Ambient Temperature °C 35 to 50 55 60 65 70
Correction factor 1.0 0.96 0.83 0.67 0.47

180 °C thermosetting insulated cords:


Ambient Temperature °C 35 to 120 125 130 135 140 145
Correction factor 1.0 0.96 0.85 0.74 0.60 0.42

Note: ~The voltage drop tabulat d <1bove are ior 60 "C lh rmopla tic or thermo etting insulated fie ible cords and
for other types of fle:ible cords they are lo be multiplied by the following fa ~tors.

For 90 °C thermoplastic or thermosetting in ulated 1.09


180 "C thermosetting insulated 1.3 ·1
185 ''C gla s iibre 1.43

Note : R ier table X-01 ior maximum value of voltage drop in on umcr in. tal Iat ion
Th data i. taken from BS 7671: ... 008, Requirements for Electrical lnslc llnlions, IEE Wiring
Regulations-Sevente nth Edition.
21

21 Current Carrying Capacity and Voltage Drop

FLAT CABLE WITH EARTH PVC INSULATED

BS 6004

Ambient air temperature 30°C


Conductor operating temperature 70°C

PVC PVC Copper 0.310.5 kV

TABLE - N

_,
Above a plasterboard ceiling In a stud wall with
Conductor covered by thermal insulation thermal insulation
Cross-sectional Enclosed in
With cable Voltage
area Not exceeding With cable conduit in an drop
Exceeding not
lOOmm in 100mm in touching Clipped direct insulated
touching Method C
thickness thickness the inner wall
inner wall
Method 01 Method 02 wall surface Method A
surface
Method 03
Method 04
(mm 2) (A) (A) (A) (A) (A) (A) (mV/Nm)
1 13 10.5 13 8 16 11.5 44
1.5 16 13 16 10 20 14.5 29
2.5 21 17 21 13.5 27 20 18
4 27 22 27 17.5 37 26 11
6 34 27 35 23.5 47 32 7. 'J
10 45 36 47 32 64 44 4.-+
16 57 46 63 42.5 85 57 2 .8

For raling factors -Variation in r mbient air temperature refer table Y-0 I

Note: -The datil is lal'en from B 7671: 2008, Requirements for ElectricCJl lnstallation , IEE Wiring
Regulations-Seventeenth Edition.
21

21 Current Carrying Capacity and Voltage Drop

MULTI CORE 60°C XLPE INSULATED FLEXIBLE CABLES

BS 7919
Ambient air temperature 30°C
Conductor operating temperature 60°C

PVC XLPE Copper 0.3/0.5 kV

TABLE - P1

Single Phase a.c or d.c Three Phase a.c Single Phase a.c
Conductor
or d.c
Cross-
sectional 1 two core cable, with or without 1 three core, four core or 2 single core
area protective conductor five core cable cables

(mm 2) (A) (A) (A)


4 30 26 -
6 39 34 -
10 51 47 -
16 73 63 -
25 97 83 -
35 - 102 140
50 - 124 175
! 70 - 158 216
95 - 192 258
120 - 222 302
150 - 255 347
185 - 291 394
240 - 343 471
300 - 394 541
400 - - 644
500 - - 738
630 - - 861

For rating factors - Variation in ambient air temperature re er table Y-0 I


Nole : -The data is taken from BS 7671: 2008, R · quir.,mcnt for Ele trical Installations, IEE Wiring
Regu lations-Seventeenth Edition.
-See Tabl P2 for Voltag Drop
21

21 Current Carrying Capacity and Voltage Drop

MULTI CORE 60°C XLPE INSULATED FLEXIBLE CABLES

BS 7919
Ambient air temperature 30°C
Conductor operating temperature 60°C

PVC XLPE Copper 0.3/0.5 kV

TABLE - P2- Voltage Drop

Voltage Drop
I
(mV/ A Im)
I

Two core cable Two core cable 1 Three core, Four


Conductor d.c single phase a.c core or Five core cable 2 Single core cables touching
cross three phase a.c
sectional
area
d.c Single phase a.c

(mm 2 ) (mV/A/m) (mV/A/m) (mV/A/m) (mV/A/m) (mV/ A/ m

4 12 12 10 - -
6 7.8 7.8 6.7 - -
10 4.6 4.6 4.0 - -
16 2.9 2.9 2.5 - -
25 1.80 1.85 1.55 - -
35 - - 1.15 1 .31 1.32
50 - - 0.84 0.91 0.93
70 - - 0.58 0 .64 0.67
95 - - 0.44 0.49 0.5.3
120 - - 0.36 0.38 0.43
150 - - 0.30 0.31 0.36
185 - - 0.26 0.25 0.32
240 - - 0.21 0.190 0.27
300 - - 0 .185 0 .150 0 .24
400 - - - 0.115 0.21
5 00 - - - 0.090 0.20
630 - - - 0.068 0.185

Note: -R !er t~ bi -01 for maximum alue of voltag drop in con urner in_ tall~ tion

-Th data i tak"'n from BS 7671: 2008, R ·quir menl. for El ctrical Install tions, IEE Wiring

R 'guliltions-Sevcnt enth Edition.


21

21 Current Carrying Capacity and Voltage Drop

MULTI CORE 90°C and 180°C XLPE INSULATED FLEXIBLE CABLES

BS 7919
Ambient air temperature 30°C
Conductor operating temperature 90°C

PVC XLPE Copper 0.3/0.5 kV

TABLE - Ql- Current Carrying Capacity

Single Phase a.c


Single Phase a.c or d.c Tree Phase a.c
or d.c
Conductor
Cross- sectional 1 two core cable, with or 1 three core, four core or 2 single core
area without protective conductor five core cable cables
touching

(mm 2 ) (A) (A) (A)

4 42 37 -

6 SS 49 -
10 76 66 -
16 103 89 -
25 136 11 9 -
35 - 146 200

I
50 - 177 250
70 - 225 310
95 - 273 369
120 - 316 432
150 - 363 497
185 - 414 564
240 - 487 673
300 - 560 773
400 - 924
500 - - 1062
630 - 1242

Note: -Th data is tciken from 85 7671: 2008, Requirement for Electrical Installations, IEE Wiring
Regulations-S vent "Cnth Edition.
- See Table Q2 for Voll age drop
21

21 Current Carrying Capacity and Voltage Drop

MULTI CORE 90T and 180°C XLPE INSULATED FLEXIBLE CABLES

BS 7919

Ambient air temperature 30°C


Conductor operating temperature 90°C

PVC XLPE Copper 0.310.5 kV

TABLE - Q2- Voltage Drop

Voltage Drop
Conductor (mV/Nm)
cross
sectional 1 Two core or 2 Two core cable 1 Three core, Four core or 2 Single core cables touching
area single core cables single phase a.c Five core cable three phase Single phase a.c
(mm 2) d.c a.c

4 "13.2 13.2 11 .1 -
6 8.5 8.5 7.4 -
10 5.-1 5.1 4.4 -
16 3.2 3. 2 2. 7 - I
25 2.03 2.04 1.73 -
35 1.42 - 1.2 3 1.46
50 1.00 - 0.9 3 1.02 •
70 0. 71 - 0.64 0. 73
95 0.54 - 0.49 0.57
120 0.42 - 0.3 9 0.46
150 0.34 - 0.32 0.39
185 0.27 - 0.27 0.3 3
240 0.21 - 0.23 0.28
300 0.16 7 - 0.195 0.25
400 0.127 - - 0.22
500 0.100 - - 0.20
630 0.074 - - 0.190

Ambient Temperature 35 °C 40°C 45 °C 50°C 55 °C 60°C 65 °C 70°C 75 °C 80°C 85 °C

Rating Factor 0.95 0.91 0.86 0.82 0.76 0.70 0.64 0.57 0.50 0.40 0.28

I 80tlC thermosetting in~ ul, ted cible..;

Ambient 35 °C - 90°C 95 °C 100°c 105°C 110°C 115 °C 120°c 125 °C 130°C 135°C 140°C 145°C
Temperature
Rating Factor 1.0 0.96 0.91 0.86 0.81 0.76 0.70 0.64 0 .57 0.50 0.40 0.28

Note: -Ref r table X-0 I for nM ·imum v.1lue of voltJgc drop in consumer installation

-Th data is tak '11 frnm 135 7(>71: 200B, R quirements ior Electrical lnstdllations, IEE Wiring-
Regulat1on.:;- v "nleenth Edition.
22

PACKING

F = Flange Diameter

B = Barrel Diameter

T = Inner Traverse

F B T
Code
mm in mm in mm in
Ke l 1 914 36 508 20 508 20
Ke l 2 940 37 508 20 508 20
Kel 3 940 37 508 20 610 24
Kel 4 940 37 508 20 686 27
Kel 5 1219 48 508 20 610 24
Ke l 6 1219 48 508 20 686 27
Ke l 7 1219 48 762 30 686 27
Ke l 8 1372 54 610 24 610 24
Ke l 9 1372 54 610 24 686 27
Ke l 10 1524 60 610 24 686 27
Ke! 11 1778 70 889 35 914 36
Ke l 12 1829 72 1016 40 762 30
Ke l 13 1829 72 1270 50 762 30
Kel 14 1829 72 914 36 686 27
Ke l 15 1829 72 813 32 762 30
HARMONIZED CABLE CORE COLOURS
Cable to BS 6004

Cable type Old core colours New core colours


Single core Red or Black Brown or Blue
Two core Red, Black Brown, Blue
Three core Red, Yellow, Blue Brown, Black, Grey

Standard 600/1 OOOV armoured cable BS 6346, BS 5467 or BS 6724

Cable type Old core colours New core colours


Single core Red or Black Brown or Blue
Two core Red, Black Brown, Blue
Three core Red, Yellow, Blue Brown, Black, Grey
Four core Red, Yellow, Blue, Black Brown, Black, Grey, Blue
Five core Red, Yellow, Blue, Black, Green and Brown, Black, Grey, Blue,
Yellow Green and Yellow

Flexible cable to BS 6500


Cable type Old core colours New core colours
Two core Brown or Blue No change
Three core Brown, Blue, Green and Yellow No change
Four core Black Blue, Brown / Green and Yellow Brown, Black, Grey, Green and Yellow
Five core Black, Blue, Brown, Black, Brown, Black, Grey, Blue,
Green and Yellow Green and Yellow

l<ELANI

KC
CABLES

Kelani Cables PLC


Company Registration Number PQ117
ISO 9001: 2008 CERTIFIED COMPANY
ISO 14001 : 2004 CERTIFIED COMPANY
P.O. Box 14, Wewelduwa, Kelaniya, Sri Lanka
Tel: 94-11-2911224-6, 94-11-5399600,
Fax: 94-11-2910481
E-mail : info@kelanicables.com
Web: www.kelanicables.com
2 Indoor Cables

2.1 Single core insulated, non-sheathed

Application : For indoor fixed ins!all ati ons in drv locations. Shall he enclo. ed in condu it, ducting 01
trunking.

Engineering Specifications
onduct( r
Type . Cl.1/PVC
Standard · SLS 73 L iEC 60227, BS b004
Nominal Voltage 4.S0/7SO V
insulation 70 °C rc:ited PVC cornpound
Packing - · Supplied in co ils of l 00 meters or as per
customer requi rement
PVC 111~ul.1t1on
Conductor : Soft annealed solid or stranded copper wires

Technical Information
Condu ctor Cable Packing

KE LANI Nominal
Cross No.& Nominal Max. Approx. Max. d.c. Cable
Cable Code Dia. of Insulation Overall Resistance at Drum Type Length
sectional Weight
area wires Thickness Diameter 20 °C I

mm 2 x/mm mm mm kg/km .Q/km m


I I
Copper Solid Conductors
1 U119138ZZ 1.5 1/1.38 0.70 3.2 21 12.1 Coils 100
1 U122178ZZ 2.5 l/1 .78 0.80 3 .9 33 7.4'1 Coils 100
Copper Stranded Conductor
1 U119053ZZ 1.5 7/0.53 0.70 3.3 21 12 .1 Coils 100
1U122067ZZ 2.5 7/0.67 0.80 4.0 34 7.41 Coils 100
1U124085ZZ 4 7/0.85 0.80 4.6 50 4.61 Coil s 100
1U126104ZZ 6 7/1.04 0.80 5.2 71 3.08 Coil s 100
1U129135ZZ 10 7/1.35 1.0 6.7 119 1.83 Coils 100
1 U131170ZZ 16 7/1.70 1.0 7.8 179 1.1 5 Coils 100
1U132214ZZ 25 7/2.14 1.2 9.7 281 0.727 Kel 01 1000
1U133153ZZ 35 19/1 .53 1.2 10.9 382 0.524 Kel 01 1000
1 U135178ZZ 50 19/1.78 1.4 12.8 518 0.387 Kel 01 1000
1 U137214ZZ 70 19/2.14 1.4 14.6 730 0.268 Kel 03 1000
1 U138252ZZ 95 19/2.52 1.6 17.1 1008 0.193 Kel 05 1000
1 U139203ZZ 120 37/2.03 1.6 18.8 1261 0.153 Kel 05 1000
1Ul41225ZZ 150 37/2.25 1.8 20.9 1552 0.124 Kel 05 1000
1Ul42252ZZ 185 37/2.52 2.0 23.3 1945 0.0991 Kel 06 1000
1U143225ZZ 240 61/2.25 2.2 26.6 2547 0.0754 Kel 10 1000
1U144252ZZ 300 61/2.52 2.4 29.6 3187 0.0601 Kel 10 1000
1 U145285ZZ 400 61/2.85 2.6 33.2 4059 0.0470 Kel 12 1000
1U146320ZZ 500 61/3.20 2.8 36.9 5098 0.0366 Kel 15 1000
1 U147252ZZ 630 127/2 .52 2.8 41.1 6518 0.0283 Kel 10 500

Note·· Refer Table A 1 & A2 for cu rren t carrying capacity and voltc:ige d rop .
..
2 Indoor Cables

2.2 Single core insulated, non-sheathed - flexible conductor

Application: For indoor fixed in s 1,:1 : i;' ~ n 1n J 11 I b P I in ( o 1duit,ducting or


trunking. Can use in '.; it i ia ?;, ,;-, ( 1 It I r I 1 r

Engineering Specificatif'ns

Type : LI I
. I I ·i, ( »'•-'.1< or
--- -------- - - - - -

Standard
Nominal Voltage : 4.30 :-:_:;o \'
Insulation : 70 ()C rated PVC compound
Packing : Supplied in coils of 100 meters or as per
customer requirement
PVC !nsula1ion
-------·-------
Conductor · Soft annealed copper fine wires (Class V)

Technical Information

Cable Packing

KELA NI Nominal No.& Nominal Max. Max. d.c.


Cross Dia. of Insulation Overall ~pro. Resistance at Cable
Cable Code eight Drum Type
sectional wires Thickness Diameter 20°c Length
area

mm 2 x/mm mm mm kg/km .Q/km m


' 1V119025ZZ 1.5 30/0.25 0.7 3.4 23 13.3 Coils 100
1V122025ZZ 2.5 50/0.25 0.8 4.1 34 7.98 Coils 100
,1 Vl24030ZZ 4 56/0.30 0.8 4.8 48 4.95 Coils 100
1 126030ZZ 6 8410.30 0.8 5.3 70 3.30 Coils 100
1V129040ZZ 10 8010.40 1.0 6.8 115 1.91 Co ils 100
1V131040ZZ 16 126/0.40 1.0 8.1 168 1.21 Coils 100
1V132040ZZ 25 196/0.40 1.2 10.2 258 0.780 Coils 100
1V133040ZZ 35 276/0.40 1.2 11.7 350 0.554 Coils 100
·1V135040ZZ 50 396/0.40 1.4 13.9 495 0.386 Kel02 1000
1V137050ZZ 70 36010.50 1.4 16.0 680 0.272 Kel 04 1000
lVI 8050ZZ 95 475/0.50 1.6 18.2 890 0.206 Kel05 1000
IVl 39050ZZ 120 608/0.50 1.6 20.2 1120 0.161 Kel05 1000
1V1 4 1050ZZ 150 756/0.50 1.8 22.5 1410 0.129 Kel 06 1000
IV142050ZZ 185 925/0.50 2.0 24.9 1700 0.106 Kel 08 1000
1V143050ZZ 240 1221/0.50 2.2 28.4 2259 0.0801 Kel 10 1000

Note - Refer Table A 1 & A2 for current carrying capacity and voltage drop.
2 Indoor Cables

_.3 Single core insulated and sheathed.

i Jfir>J • Fnr indoor fj 'Pd in taJJati n_ in drv le cdti n , lav in c nduits ov r or und ,,. w II .

, IEC 60227, BS 6004


00/r:c OV
: 70 °C rct d PV . comp und
: PV 'ornpound
ing : u1 pi i d in i ls of 1 00 meter or as p r
cu. tom r r·quir rn nt
o d tor : o t c. nn r st re ndecl op per wire

Technical Information

Cond uctor Packing


Nominal Nominal Nominal Max. Max d.c.
l< ELANI Approx .
Cross No. & Dia. Insulation Sheathing Overall Resistance Drum Cable
,1hl e Code Weight
sectional of wires Thickness Thickness Diameter at 20 °C Type Length
area
mm 2 x/mm mm mm mm kg/km Q/km m
I l 6113ZZ 1 1/1.13 0.6 0.8 4.5 25.30 18.1 Coils 100
1 l CJ138ZZ 1.5 1/1.38 0.7 0.8 4.9 32.99 12 .1 Coils 100
; l 19053ZZ 1.5 7/0.53 0.7 0.8 4.9 33.57 12 .1 Coils 100
~

rn I 22178ZZ 2.5 1/ 1.78 0.8 0.8 5.8 46.78 7.41 Coils 100
1B 122067ZZ 2.5 710.67 0.8 0.8 5.8 49.73 7.41 Coils 100
1 f; l .:'.4085ZZ 4 7/0.85 0.8 0.9 6.8 70.60 4.61 Coils 100
11\ 1.2G104ZZ 6 7/1.04 0.8 0.9 7.4 93.74 3.08 Coil s 100
1B i ..29135ZZ 10 7/ 1.35 1.0 0.9 8.8 146.55 1.83 Coils 100
... 1BU 1170ZZ 16 7/1.70 1.0 1.0 10.5 215.41 1.15 Co il s 100
IP '.:\ 2214ZZ 25 19/1.35 1.2 1.1 12.5 33 0.21 0.727 Kel 01 1000
1 ·d 153 ZZ 35 19/ 1 .53 1.2 1.1 13.5 437.79 0.524 Kel 02 1000

ote - I fer Tabl A I & A2 for current carrying capacity and \oltage drop.
.. ..
2 Indoor Cables

2.4 Multicore insulated and sheathed - Flat Cable.

~ A pp li cation : For indoor fixed installations in dry loca tions, lay in conduits over or under w all s.

Engineering Specification s

Type • Cu/PVC/PV C
Standard SLS 73 3, IEC 60227, BS 6004
Nominal Voltage · 300/SOOV
Insulation · 70 °C rated PVC compound
Sheathing : PVC compou nd
Packing : Su ppli ed in coi ls of 100 meters or as per
customer requirement
Conductor . Soft annea led solid or stranded copper w ires

Technical Information

Cond uctor Packing


Nominal Nominal Nominal Max. Max d.c.
KELANI Approx .
Cross No. & Dia. Insulation Sheathing Overall Resistance Drum Cable
Cab le Code Weight
sectional of wires Thi ckness Thickness Diameter at 20 °C Type Length
I
area
mm 2
-~-~-~
x/mm mm mm mm kg/km
~
O/km m
Two cor~futcables (Flat twin)
~-

1J219138ZZ ~ -~ 1/1.38 0.7 0.9 5.4 x 8.4 64"];3 ~ 12.1 - ~ 1 5 - 1()()--

1J222178ZZ 2.5 1/ 1.78 0.8 1.0 6.2 x 9.8 96.39 7.41 Coils 100
1J219053ZZ 1.5 7/0.53 0.7 0.9 5.4 x 8.4 65.88 12.1 Coils 100
1J222067ZZ 2.5 710.67 0.8 1.0 6.2 x 9.8 102 .83 7.41 Coils 100
1J224085ZZ 4 710.85 0.8 1.0 7.2 x 11 .5 140.63 4.61 Coils 100
1J226104ZZ 6 7/1 .04 0.8 1 .1 8.0 x 13.0 192.54 3.08 Coils 100
1J229135ZZ 10 7/1.35 1.0 1.2 9.6 x 16.0 308.17 1.83 Coils 100
1J231170ZZ 16 7/1 .70 1.0 1.3 11 .0 x 18.5 449.19 1.15 Coils 100
Th ree core flat cables
lJ3,19138ZZ 1.5 1/1 .38 0.7 0.9 5.4x11.5 96.95 12.1 Coils 100
1J322178ZZ 2.5 1/1 .78 0.8 1.0 6.2 x 13.5 144.59 7.41 Coils 100
1J319053ZZ 1.5 710 .53 0.7 0.9 5.4x11.5 98.82 12.1 Coils 100
1J322067ZZ 2 .5 710 .67 0.8 1.0 6.2 x 13 .5 154.25 7.41 Coils 100
1J324085ZZ 4 7/0.85 0.8 1.1 7.4 x 16.5 210.95 4.61 Coils 100
1J326104ZZ 6 7/1 .04 0.8 1 .1 8.0 x 18.0 288.81 3.08 Coils 100
1J329135ZZ 10 7/ 1.35 1.0 1.2 9.6 x 22.5 462.26 1.83 Coils 100
11331170ZZ 16 7/1 .70 1.0 1.3 11.0 x 26 .5 673.79 1.15 Coils 100

Note - Refer Table A 1 1 /\2 or N ( flat cable with earth) for current carrying capacity and voitage drop.
2 Indoor Cables

2 .5 Multi core insulated and sheathed - flexible conductor

lication .
din ra cl11

p
ndard
mi ~~ l

meters
custon·icr rernent
on LH1or

Technical Information

Conductor Packing
I KE LANI
Nominal
Cross No. & Dia.
Nominal
Insulation
Nominal
Sheathing
Max.
Overall
Approx.
Max d.c
Resistance Drum Cable
i

CJble Code Weight


sectional of wires Thickness Thickness Diameter at 20 °C Type Length
area

mm 2 xlmm mm mm mm kg/km O/km m


Twisted Twi n
1U212020WZ 2 x 0.5 16/0.20 TT 0.6 (2.6) each 1 19 39.0 Coils 100
Parallel Twi n
1U212020ZZ 2 x 0.5 16/0.20 PT 0.8 3.0 x 6.0 23 39.0 Coils 100
Li Jht flexible cords
1F212020ZZ 2 x 0.5 16/0.20 0.5 0.6 6.0 37 39.0 Coils 100
1F215020ZZ 2 x 0.75 2410.20 0.5 0.6 6.4 47 26.0 Coils 100
1F312020ZZ 3 x 0.5 16/0.20 0.5 0.6 6.2 45 39.0 Coil s 100
1F315020ZZ 3 x 0.75 24/0.20 0.5 0.6 6.8 57 26.0 Coil s 100
1F412020ZZ 4 x 0.5 16/0.20 0.5 0.6 6.8 55 39.0 Coil s 100
1F415020ZZ 4 x 0.75 2410.20 0.5 0.6 7.4 71 26.0 Coil s 100
Normal Flexible cords
1F315020ZZ 2 x 0.75 24/0.20 0.6 0.8 7.6 58 26.0 Coil s 100
1F216020ZZ 2 x 1.0 3210.20 0.6 0.8 8.0 66 19.5 Coi ls 100
1F219025ZZ 2 x 1.5 30/0.25 0.7 0.8 9.0 88 13.3 Coi ls 100
1F222025ZZ 2 x 2.5 50/0.25 0.8 1.0 11.0 135 7.98 Coi ls 100
1 F315020ZZ 3 x 0.75 24/0.20 0.6 0.8 8.0 69 26.0 Coi ls 100
1F316020ZZ 3 x 1.0 32/0.20 0.6 0.8 8.4 80 19.5 Coi ls 100'
1F319025ZZ 3 x 1.5 30/0.25 0.7 0.9 9.8 111 13.3 Coi ls 100
1 F322025ZZ 3 x 2.5 50/0.25 0.8 1 .1 12.0 170 7.98 Coi ls 100
1F415020ZZ 4 x 0.75 24/0.20 0.6 0.8 8.6 85 26.0 Coi ls 100
1 F416020ZZ 4 x 1.0 3210.20 0.6 0.9 9.4 102 19.5 Coi ls 100
1F419025ZZ 4 x 1.5 3010.25 0.7 1.0 11.0 142 13.3 Coil s 100
1F422025ZZ 4 x 2.5 50/0.25 0.8 1 .1 13.0 211 7.98 Coil s 100

>~ote - Flex ible conductor with XLPE insulation rnul ti a: available upon
Refer Tab le ;\r\ for curre nt

Refer or PF insulated cables.


3 Outdoor Cables - Copper Conductor

3.1 Single core unarmoured - PVC insulated

Appli ation : For outdoor in tclll"1ti >n in air, ondu1. duct rn tr;_~y. They are norrnal!y usecl for povver
di tribution in url an net vorl , in indu trial plant , i 1 d w,n Jnd

Engineering

Type C u/PVC/PVC
Standard . IEC 601)02, BS 6J,:.Jf)
Nominal Voltage 600/! ooov
Insulation : 70 °C ra ted PVC cornpound
Sheathing · PVC con-ipou nd
Packing The cables are de livered on non--rctuma ble
wooden drums as per customer requiremellt
Conductor . Soft anneal ed stranded copper wi res

Technical Information

Conductor Pac~ _
Nominal I Nominal Nominal Max. I Max d.c.
KE LANI
Cross No. & Dia. / lnsu Iation Sheat hing Overa II Approx.
we·i ·ht .
Resistance Drum I Ca bi e
Cable Code
I Thickness I Diam-et-er- i-- g O
I sectional

1 Pl 2 61 04ZZ
1P129135ZZ
+:::
10
I ~
of wires

x/mm
7/1 ..tl±_____l_:Q_
7/1.35 1.0
I
I
Thickness

mm +- mm I mm
__2_::'I_ _L_ 8.:'I__
__2_::'1_ ~ 9.3
11 5
164
-

kg/km
- I
+
at 20 C

3 .08
1.83
n/km
Type

---~--+--
Coi I
Coil
Length

1 08
100
m

1P131170ZZ 16 7/1.70 _ 1.0 1.4 ~10.3 228 1.15 _j~ I !00


1P132214ZZ 1-
2_5 _ - --m:i 4 1.2 1.4 i = 11.8 336 0.727 ~01----1--1-0- 00---j
1P133252ZZ 35 7/2.52 1.2 1.4 13.0 445 0.524 Kel 02 1GOO
-- --- l -- - - - + -- - -----1
1P135178ZZ 50 19/1.78 1.4 1.4 15.0 580 0.387 1000
- ---
1P137214ZZ 70 19/2.14 1.4 1.4 16.8 790 1000
1P138252ZZ
~103zz
f-fi;i :if
22szz
95
120
1 50
----,--gf2 _52
3712.03 -f--1.6
3112 .25
1.6

1.8
I
1.H
1.5

1 .6
1-9-.2_ _ ,

2 3 .o
1080
2 1_._o _ -+---_
1_3_3_-o_ -1-- 0.153
1640
-
0.124
Kel 05
Kel 06
1000
1000
1 noo ~
--
1P1422s_2zzi l 85 _ _E_12.52 2-.0- - 1. ~-2- 5.-6--+----201 o Kel 09
0.0991 --+-------+---1000
1 P143225ZZ 1 240 61/2.25 2.2 1.8 28.6 2650 0.0754 Ke l 10 1000
----- -- -- -- --
Kel 12

:~::m~~ t ;~~ it~rn ~· ~ ~· ~ I ~::~ :H~ ~~;~~ ~:: ~~ ~i~~~


0.0601

1P147252ZZ 630 ~ 27/2.52 ~ 2.-2 - 43.2 6620 ___Q,CJ2 83 Ke l 12 - sooJ


1P148285ZZ 800 --!--2 27/2.85 2.8 2.3 48.0 8450 0.0221 Kel 14 S•:JO
1-Pl-4932-0Z
-Z 1
1000 127/-3-.2-0- - - 3.0 2.5 -5-3.-0 10- 5_4_0__, 0.0176~e l _1_
-+----- 5~1 500

N t - Ref 1 TJblc.") A1 ior C\ 1rrcnt an d vr1 g ~drop.


3 Outdoor Cables - Copper Conductor

3.2 Single core unarmoured - XLPE insulated

pplicati Hl : For ciut I or in t 111 ti ns in aii~ conduit, du I or Lra '·Th y ar norrnc II / u · I for f ower
di triLuti 111 in urb .. n netvv', i 1~ ""' in industrial pl.rnL, in therm power< nd h dropow 'r sl ti n .

Engine ring Specifications

Typ : Cu I XLPF/ PVC


Standard : BS 788
Nominal Voltage : 600/1 OOO V
Insulation : go C re ted LPE ompouncl
Sheathing : PVC comp und
Racking : The abl are cl Ii' r don non-returnable
\ ooden lrum as per cu~tomer requir m nt
Conductor : Scft anne I d stranded copper" ir

Technical Information

Conductor Pack~n_g

KE LANI
Cable Code
Nomi~ -
Cross
sectional
area
mm-
of wires

xlmm
h:
- - - , Nominal
No. & Dia. Insulation
hickne s

mm
Nominal
Sheathing
Thickness

mm
Max.
Overall
Dia mete r

mm
Approx.
Weight

k km ~km
Max d.c.
Re isLance
at 20°c
Drum
Type
Cabl
Lcnglh

m
I

1X135178ZZ 50 19/1 .78 ! 1.0 1 .4 14.2 554 0.387 Kel 03 1000


1Xl17214ZZ 10 1912.14 I 1.1 1.4 ·16.2 771 0.268 Kel 04 1000
lXI 8252ZZ 95 19/2.52 1.1 1.5 18.3 1045 0.193 KelOS 1000
--
1X139203ZZ
1X141225ZZ ------
120
150
3712.03
3712.25
L2
1.4
- -

-
1.5
1.6
- -
20.2
22.4
1304
1600
0.153
0.124
Kel 05
Kel05
1000
10 0
1Xl42252ZZ 185 37/ 2.5 2 1.6 1.6 24.7 1989 0.0991 Kel08 1 00
1X143225--Z___
Z "J-----;----------<-
240 27 .7 Kel 10 -1000
61 /2.25 1 .7 1.7 2587 0.0754
1X144252ZZ 300 61/2.52 1.8 1.8 30.6 3221 0.0601 Kel 12 1000
--
1 X145285ZZ 400 61/2.85 2.0 1.9 34.2 4096 0.0470 Kel 12 I 1000
1 X I 46320ZZ--ijc-----
500 t 61/3.20 2.2
f---

->-
2.0 38.0 T 5 f35 0.0 66 Kel 10 500
1 x·147252zz 630 12712 .52 2.4 2.2 42.9 6607 0.0283 Kel 10 500
1Xl48285ZZ 800 127/2.85 2.6 2.3 47.8 8393 0.0221 Kel 12 500
1 Xl49320ZZ 1000 12 7/ 3.20 2.8 2.4 53.0 10518 0.017 Kel 15 500

Not - Refer Table B 1 " 132 for current an 1 ing capacit and v ltage drop.
3 Outdoor Cables - Copper Conductor

3.3 Multi core unarmoured circular condutor - PVC insulated

Appl icat ion : For ou tdoor insta l lations in air, crn \dt. 1 ckct ( r tra '·Th 'V re nmrn.:1ll y
distribution in urban networks, in indust1ial ''· P 1ht rnnpow r, ~)PO"ver sta1ions.

Engineering Specifications
onclutr n

Type . Cu/PVC/PVC
Standard IEC 60.S02 PVCl11 ulati n

Nominal Voltage . 600/1 ooov


PVl he.itli
Insulation 70 °C rated PVC compound
Sheathing · PVC compound
· The cables are 1vc1 on non-retumahie
customer requ irement
Conductor · Soft a.nnealcd stranded copper vvires

Technical Information

KE LANI
Cross
-1- --
Conductor
Nominal
No. & Dia.
Nominal
Insulation
Nominal
Sheathing
Approx.
Overall
Approx.
Max d.c.
Resistance
__ Packing

Drum I Cable
+
Cable Code Weight
sectional I of wires Thickness Thickness Diameter at 20 °C Type Length
area
mm 2 xlmm _,___
m_m
mm _~__m _ m_ _.._--"
kg..._/_km
_ _,___n_/_k_m__..____ __,___m_--i
Two core cables
f-----~--.-----~---------,-- -~~~ ------.---- ----~--
1 P219053ZZ 1.5 7/0.53 0.8 1.8 10.0 118 12.1 Coils 100
1P222067ZZ j 2.5 7/0.67 0.8 1.8 10.9 146 7.41 Coils 100
1 P224085ZZ ~ 7/0.85 1.0 1.8 12.8 203 4.61 Coils 100
1P226104ZZ
1 P~29135. ZZi 6
10
7/1.04
I
7/1.35
1.0
1.0
1.8
1.8
13 .9
15.8
256
358
3.08
1.83
Coils
Kel 05
100
1000
1P231170ZZ
1P232214ZZ - -
1P233252ll
16
25
35
7/1.70
712.14 \
\ 7/2 .52
1.0
1.2
1_.2__
1.8
1.8
1.8
+ 17.9
21.3
23.6 \ 950
498
732
1.15
0.727
. KelOS
I
1000
Kel 06 1 1000
0.52i_L_KeLQ<L_ 1000_
Three core cables
1_P_31_905_3_ZZ
1P322067ZZ
1 P324085ZZ
- , _.s_ _ _7_/0.53
2.5
4
7/0.67
0.8
0.8
I
----YI0.85 -\--1.0__
1.8
1.8
t
I 1jl__j___!Q.5=c 14S ~2.1
I
11 :i__!_ 186 T l .41
13 4-- j ~ 265
Coils I 100
Co.il5 r100
4.Ji1__ Kel 041 100
-, P32_6_104ZZ l ~=6 7/1.04 I 1.0 I 1.8 14.7 340 3.08 KefOS 1000
1 P329135ZZ L 10_ 7/1.3
1 t i 1.0 1jl_ I16.7 4ll7 1.83 Kel 05 1000
1P331170ZZ 16 7/1.70 1.0 1.8 18.9 688 1.15 Kel05 L-J_Q90
1P332214ZZ ! 25 7/2.14 1.2 - 1_.8_ _ 1_ 22.6 1033 on? Kel OU_l9.QO J

1p3332s2zz 35 112.52 l__J .2 I 1.8 I 25.1 1348 _ _o_.524 1 K~ 1000

Note - Refer Table E ror c unent cmying capacity z-md vo ltage drop.
3 Outdoor Cables - Copper Conductor

3.3 Multi core unarmoured circular conductor - PVC insulated cont. ..

I pl ication : For outdoor installations in ;Ji r1 conduit, or They are 1iorrnal ly Lhcd fu1 power
d i :!"ibution in urb.:in net\vorks, in industrial plants, in therrnopovver and hydropovver stations.

gh1eering Specifications
1 11duttrn

p ~=­ : Cu r i ! ! t_ ~i ~,i'\:Vi ,~1f )ping 1d .! H:


---
"'·ndard . IEC 60502
zninai Voltage . 600/1 OOO V
- : 70 °C rated PVC
1
hing • PVC cornpound
. The cables are delivered on non-returnable
wooden as customer requirement
Soft a nnealed stranded copper wires

Technical Information

Conductor
-------1
I L Packing
,,-
Nominal Nominal I Nominal Nominal I Max d.c.
l\ELANI Approx.
Cross No . & Dia. Insulation Sheathing Over II Resistance Drum Cable
Cable Code Weight
tional 0f wires Thickness Thickness Diameter at 20°c Type Length
are
-----!-- -~--
! I
~
mm1 x/mm mm mm mm kg/km Q/km m
Four core cables
1P-tl9053ZZ 1.5 710.53 0.8 1.8 11 .4 240 12.1 Kel 02 1000-
'. P..+22067ZZ 2 .5 _ 7/0.67 0.8 1.8 L.4 I 3 15 7.41 Kel03 1000
-
-
l P-t24085ZZ 4 710.85 1.0 1.8 14.8 440 4.61 Kel 05 1000
1 P-+26104ZZ 6
-+---
7t l.04 1.0 1.8 16.0
I
I
560 3.08 Kel05 IOOO
----+- I I
: P..+29135ZZ 10 7/1 .35 1.0 1.8 18.6 780 1.83 Kel 05 1000
--

l
~
JP.Bl 170ZZ 16 7/ 1.70 1.0 1.8 21.6 1080 1.1 5 Ke! 05 1QQQ_
- ---- ~ .-
1P432214ZZ 25 712.14 L2 1.8 25.9 I 1560 0.727 Kel 10 1000
. P-+33252ZZ 35 712 .52 I 1.2 1.8 28.9 2030 0.524 Ke] 10 r 1000
Five core cables
1.5 12.1
-
1P519053ZZ
----
710.53 0.8 1.8 13.4 2 90 I Kel03 1000
. P522067ZZ
---
2.5 7/0.67 I 0.8 1.8 14.4
- 360 7.41 Kel 04 1000
4 r.30 ' KelOS
1P.524085ZZ 7/0.85 1.0 1.8 17.4 4 .61 1000
IP526104ZZ 6 7/ 1.04 1.0 T.8 "18.9 670 3.08 Kel 05 1000
1PS29135ZZ 10 --+---
7/1.35
--~
1.0 r 1.8 I 22.4 970 1.83 Kel04 1000
1P531170ZZ 16 7/1.70 1.0 1.8 25.0 1340 1.15 Kel08 lOOQ__
1 P532214ZZ
-
25 7/2. 14 1.2
-
1.8 30.0 1990 0 .727 Kel 10 ·1000
i P533252ZZ 35 712.52 1.2 I 1.8 I 33.6 I 2630 0 .524 Kel 12 1000

l - Refer Tab le E fo r cu rrent ca rry ing capacity and voltage drop .


3 Outdoor Cables - Copper Conductor

3.4 Multi core unarmoured shaped conductor - PVC insulated

AJ r n c ti n: F r outdoc r in t lll(lti m in ir l nduit, duel or tray. The' are normally d for I ower
dislribution in u1+ C111 n !work , in industrial plmt , in th rrnopovver < ncl I\ dr pov 1 r t 1i n .

Engine~ring Sp cification

Type : Cu/PVC/PVC
"I : BS 6 4
: E00/10 V
· 70 °C rated PVC c mp un I
: PVr: - ompou n I
Pack mg : The Cc hies are cleliv r I on non-return I le
wooden drum as p r customer requir ment
Conductor : Soft anne led strand d opp r \ ire

Technical Information

-~ELAN-1 -iN~~~~~~(~ ': 1


0
Nominal [ Nominal I Max. IA Max d.c. ~ __Pa~rR__

Crossi
t
0
C bi C d J D"o.
1
f 1 Insu lation hea1h1ng Overall 0P'. ~· Resistance at I Cable
a e
0
e sectional ~· 0
/ Thickness / Thickness J Diameter eig t 20 °C Drum Type I Length
~
1

1P432214ZZCm~'--j 11;_~4k ~;=- =9:~ t ~~ ~; ~ on;;~ [


/ area wires

1~0
1 p433252zzL_ 35 =f?72.52ti.2
_!E435178Zfj ___2_0 - i-J-211-Z_~ _ 1 .±_
1.s_ + 25.4
_ 1:2__ ~ _±g
± 1655 o.524
Kel a&
Ke1 ~ 1 ooo

t
_ll_32_ _ 0.387 _!<elJ_Q 1000
1P437214ZZ I 70 JJ_9/2.14 I 1.4 r 2.0 _j 33.0 3081 0.268 Kel 12 1000

f~~:~~;~;~~1 ~~r +~~-7~:~; ~ ~-:f~ -1


-~~-~Wo g:;~; - ~~~~1- ~~~
[ 1P'!_4J.~iZ]'.+= 1_50~f 7/2.25 _-l-
1 P442252ZZ 185 37/2.52 1=
1.8-
2.0 =--t- 2.5
2.6
_16.1_
51.3 L
6455
8018_)
0.124
0.09 1
Kel12
Kel 15
500
500

~fl!~f~1 ~~ ~~:~g t ~}- t ;:~- ~~:~ ~~61~ i g:g~~~ 1 --~:: ~;- ~~g-
1
rtr44s2s2-z --4ooj--61n.8sj_~6 - c 3.3-~/ nJ) 16.570 - 0JM10 1<e1u 200

Nole - Refer Tab I ' f ior cur renl (arr 1 ing 'di acily and voltage drop.
3 Outdoor Cables - Copper Conductor

3.5 Multi core unarmoured circular conductor - XLPE insulated.

Appli ~ati 1 : F r outcloo1 in le llali n in :iir, Jnduit, du t r tra,. Th y ar;) n rmally u ed f r I w r


di tributi m in url n n >tw rk , in in lu tri I pi nt , in th rm p )w rand h dror O\ r t tion~.

Engineering Specifications
\onduclor

Type : u I LPE/ PVC


l PI: In ul,1t10n
Standard : B -4 7: 1 B
Nominal Voltage : 600/1 ooov
l'V hC'.itli
Insulation : 0 C rated XU E omp und
Sheathing : PVC ompound
Packing : Th ·abl c. re cl I iver d on non-return ble
w o I n drums a p 'r u tom ·r requir rn nt
Condu tor : S ft nn I I trand cl copper wires

Technical Information
Conductor Pac~ing

~able
Nominal i - - Nominal Nominal Max. A Max d.c.
KELA NI
Cross No. & Dia.
J Insulation Sheathing Overall 0p·ro~. Resistance Drum I
Cable Code 1
sectional of wires at 20°c Type Length
Th-ic-kn-e-ss---+--
T-hi- kness l Diameter I eig
area
--~-~--~.__~ _ _,___ m_m_ _ ~~ k_/_k_m_,__~~~~-~~~~~
i
mm ·i x/mm
2 mm Q/km m
- - - -·-···
Two core cables ~~-~-- ~-.----

1 X231170ZZ 16 7/1 .70 0.7 1. 8 F - 17.2 460 1.15 Kel 05 1000


1X232214ZZ 25 7/2.14 0.9 1.8 20.8 680 0.727 i<el 05 1000
1 X233252ZZ 35 7/2.52 0.9 1.8 23.2 890 0.524 Kel06 1000
Three core cables
- - - 711.7Q:T - o.7 ----+-------+.8 - 1- 8-. 3---.--- 6-25 Kel 05
1 X331170ZZ 16 i 1.15 1000
I
1

---~-------_j-=:}·~=E};•~. -~-+-_-_-_1-2~~--o~~:~~~~~~=-~Kel08
1X332214ZZ 25 712. 14 1- 0. 9 9 5 0.727 KelOS 1000
1 X3 3252ZZ 35 7/2.52 0.9 0 .524 1000
Four core cabl es
·1X4311 70ZZ 16 7/1.70 0.7 1.8 I
20.0 795 1 .15 Kel 05 1~
1 X4U214ZZ 25 7/2.14 0.9 1.8 24.3 1220 0.727 ~ 08 1000
1X433252ZZ 35 712.52 0.9 1.8 27.3 1620 0.524 Kel 10 1000 I

Note - Refer Table F ior urr nt carrying apa ity ~rnd vo ltag · drop.
3 Outdoor Cables - Copper Conductor

3.6 Multi core unarmoured shaped conductor - XLPE insulated

Application : Frn (1 Utrloor in tc llation_ in air, onclu it,. duct or tray. They are normally lJsed for power
distribution in urt:.,:; n n l\Nork , in indu trial plants in thennopower and hydropower stations.

Engineering Spedfications
Conduttor

Type : Cu/XLPE/PVC
Standard • BS 6346 .· 1PI:111~ulc111 m
Nominal Voltage ~ 600/1 ooov
Insulation . 90 °C rated XLPE compound PVC Sfw.11h
Sheathing : PVC compound
Packing : The cables are delivered on non-returnable
wooden drums as per customer requirements
Conductor : Soft annealed stranded copper wires

Technical Information

ca:~~~:~e
1
1I Nominal
Cr~ss I ~i:: ~f
sectional
/

.
Nominal

Insulation
Thickness
Nominal

Sheathing
Thickness
Max.

Overall
Diameter
~~i;;;
Max d.c.

Resi2stoaoncce at

~
_
I Drum Type Cable
Length

~ea_ 1__
wires ---------
mm2 xlmm mm ~m_J_ mm _ ___Bik~ Q/km - - m
1X43ll14ZZ I 25 = + 7/2.14 _ 0.9_ _,_---~ I ~1 .:!___ ~ ---+_ _o_.727 Kel os 1000
1X433252ZZ 35 7/2.52 0.9 1.8 J-2~ 1563 0.524 Kel 08 1000
1X4351781 Z E_2.9=1 ~1.78 _ 1.0 .. 8_ _
1_ -_j,_ 26.9 2078 _-0.-3~8_7_______K=e--l=-
10~-...- -10-0_0_-;
1X_43_7214_Z_Z _7_0 1_9_/2.14 _ 1_.1 _ __ 2.0_ ---+-_3_1_.5_ _ ,c 2920 0.268 Kel 12
--- - - - - -1000 -
1X438252ZZ 95 19/2.52 1.1 2.1 35.6 3992 0.193 Kel 14 1000
- -- -- -+----+--------+-------+----
1 X439203ZZ 120 37/2.03 1.2 2.2 39.5 5005 0.153 Kel 06 750
1 X441225ZZ 150 37/2.25 1.4 2.4 44.1 6166 0.124 Kel 07 500
-- ---
1.6 - - + - -2.-6- r49.3 _ _,___ 7839
1 X442252Zr+=Z _]_82_ - -0.0991
-- Kel 08
-500
--
1X443225ZZ 240 61/2.25 1.7 2.8 55.5 10201 0.0754 Kel 09 375
-- - - - - - -
1X444252ZZ 300 61 /2.52
1 - - -
1.8 _,
- -
_ ____
-
3.0
- - -
61.4
- -
12712
- ---
0.0601 Kel 12 325
1X445285ZZ 400 61/2.85 2.0 3.2 68.8 16172 0.0470 Kel 12 180

Note - Refer Tablet= h r cu 1e nt ca rrying cJpaci ty and voltage drop.


3 Outdoor Cables - Copper Conductor

3.7 Single core armoured circular conductor - XLPE insulated.

1 ppli at ion : For outdoor in t llation where rnechc ni , I prote~tion i required. Thes abl scan be
install din air, on a perforated abl tray, Jir et in ground or in ducting in ground.

( <>ndur I ir
Engineering Specifications
LP[ In ul.itirm
P C Beddin•'
Type : Cu//LPE/AWNPVC Al wire• ,mnour

Standard : BS 5467 r t 'h •,111i


Nominal Voltage : 600/1 ooov
Insulation : 90 °C rated XLPE compound
Sheathing : PVC ompouncl
Packing : Th abl s r d liver cl< n n )n-returnable
wooden drums , per cu tomer requirement
Conductor : Soft anneal cl stranded opper wir _

Technical Information
Packing
Conductor 1000 m
500 ni
Nominal Nominal ominal Nominal Max. Ma. d.. Armour
KELA NI Approx.
able Code Nominal Insulation B dding Al Armour Sheathin~ Overall Resistance wire
Weight
I Cross No. & Dia. thicknes thickness Wir thi kness Diameter
1 at 20°c area Drum
_ectional oi wires Die meter Type
are

---
mm 2 x/mm mm mm mm mm mm n/km mm 2
so 19/1 .78 I 1.0 0.8 0.9 1.5 ·11.s 0.387 26 Kel 05
70 19/2.14 1 .1 0.8 1.25 1.5 20.2 ( _0.268 42 Kel 05
95 19/2.52 1.1 0.8 l .25 I 1.6 22. 0.193 47 Kel OS
120 3712 .03 1.2 0.8 1.25 1.6 24.2 0.153 52 l<elOB
150 37/2.25 1.4 1.0 1.6 1.7 27.4 1971 0.124 76 Kel 10
'185 37/2.52 1.6 1.0 +
L6 1.8 '-30.0 2413 0.0 91 84 Kel 10
1/2.25 1.7 1.0 1.6 1.8 32.8 047 0.0754 94 Kel 12
61/2.52 1.8 1.0 1.6 1.9 35.6 3728 0.0601 104 Kel 14
61/2.85 2.0 1.2 2.0 2.0 40.5 4778 0.0470 147 Kel 10
61 /3.20 2.2 1.2 2.0 2.1 44.2 5894 0.0366 163 Kel 12
127/2.52 2.4 1.2 2.0 2.2 48.8 7402 0.0281 182 Kel12--
127/2.85 2.6 1.4 2.5 2.4 55.4 9507 0.0221 260 Kel 15
127/3.20 2.8 1.4 2.5 2.5 60.6 11776 0.0176 284 Kel 15

Note - Reier Tc. bi 0 I 02 for current e<m,'ing apacity and voltage drop.
3 Outdoor Cables - Copper Conductor

3.8 Multi core armoured circular conductor - PVC insulated

Appli-l ti n : F )r outdot r in tc1llc1ti n wh re me h nical prote tion i r 1uir cl. Th s cabl an b


in ta lied in air, on d 1wrf rat( d ell le tra , lire( t 111 ground or in ducting in ground.

Engineering Specifications

: u /PVC/SWA/PVC
: BS 6">46
: 00/1 OOO V
: 70 ° rated I V< crnnpt und
: PVC compound
: The ea! I s , re <I Iiverecl on non-r turnc bi
w oden drums, s pe1 cu_tomer r quirem nt
: oft nn died tranded _opper wire·

Technical Information
Packing

KELANI .
Conductor _ _ /
I
] Nominal Nominal Nominal . Nominal
I Max. A I I
I Max d.c. Armour/
I 1_000 m

C bi ·· C. d Nomrnal I No. & Insulation/ Bedding / Steel wire! Sheathing Overall 0p.ro~. Resistance wir • /
0 0
a e e j Cr?- 5 Dia. of / thickness thickness diameter thickness !Diameter! erg at 20°C J are. Trum
section< 1

area _ ·I
.
wires
_ _ _ J 1
l _ -+- _ _ I
ype

mm 1 x/mm mm mm 1 mm mm 1 mm kl km ' .Q/km mm1


Two core cables
1 R2J90s3Zz~--:.:_i_,_s
1 R222067ZZ
1

2.5---t7/Q.67
110.s3 o.6
0.7
o.s
0.8
j- ~
0.9 ~ 1.4
- 1.4 -112.3 I
T l3.6 34~__1
211_J_ -, 1.1
7.41 J
I _JJ__ 'l<ef 01
j7 TKel 02
~-:-J_7/Q]s - o.s- o.B - OJ)__ _ J:-4 1s+f
1 s12 _ K~el 03
LJ2o_IK
1 R224085ZZj_
1 R226104Z~1 . 6 ~/1.04 0.8
~
0.8 f 0.9_ -i- 1.5
J

16.5 613
4.6_
1 __
.08
1.83~ 4cJ
22 j jKel 05
1 R229135ZZ - 10
1R2}1170W- ~
1R232214ll j - 25
711 .35
7/1. 70 -
712.14
1.0
1.2
0.8
- 0 8
1.0
[ 1.25
1.6
I=
1 .22_1 _ IT
1.6 I
1.7 -l 26.71
20.1
ill
845

1650 f 0.727
1
I i 190 I -~12___ _ 46
60
Kel 05
Kel 05
Kel10
1RD32llZ -J 3s 7!"231 I 1T -,- 1F-. 1T 1.8 29.2 200 -Io.524 66 i<ef 10
Three core cables
1R319053ZZ LSI 7/0.53 o.6 ~ o.s T o._9 _ , 1.4 I 12.s 292 12.1 I 16_ _ Kaj__Q_l

l
J 1

1:_5~ 710.61 ~-r~ r-~ 7.i1._~ 1q_ Ke103


1 ~el
1RJ22067zz o.7 1-+.1 37s
1 R324085ZZ
1R326104Z~J
1 R329135ZZ
4
6_
7/0.85
7/1.Q:!_
I 0 ~/1.35
0.8
0.8
1.0
0.88
O.B_ I _0.9 I

0.8
1.25
1.25
i .4
L.:5
1.6
15.8
18.0 +f
21.2
467
b6Q__
916
4.61
1
3.08
1.83 [
22
34
42 l
Kel 04
05
Kel 05
1R33111ozz J_ 16 111Jo E 1.o j o.a__ -- 1.2s _ -~ - 23J_- 1179 1 .1s s ol Keloo
1R3322:!_4ZZ 25 712.14 ~ ~ l:Q_ _ 1.L _ 1.7 28.2 1822 0.727 66 I Kel 10
1 R333252ZZ 35 7/2.52 1.2 I 1.0 l 1.6 1 1.8 30.8 2236 0.524 74 Ke! 12

Note - P fer Tdbk G ior ( urr •nt carrying


1
pd it 1 and v It age cir p.
3 Outdoor Cables - Copper Conductor

3.8 Multi core armoured circular conductor - PVC insulated Cont...

A1 plicction: For outd >Or i1Uc II lion wh rem h ni al I rot ction is requir d. The e c bles can b
in Lall cl in ir, on I c.al I' tra 1, dir et in 7 rouncl r in du ting in ground.

Engtnie~:d:ng Specifications

Type : Cu/PV /SWAIPV~

: BS 6346
Norn~nat Voltage : 600/1 OOO V
In ulation : 70 °C rated PV com1 ound P (' hr>Hh
·- - - - ---
Sheathing : PVC compound
'i:J:ii.···lr~ll"i\·f~
I ~ .. t.h~nt~ : Th cables ar d Iiver cl n non-returnal le
wooden drums as per cu tomer r quirement
: Soft annealed tranded copper wires

Technical Information

I Packing
I I
KE LANI Nominal
Conduct r
Nominal Nominal
Nominal ! .
Nominal
IMax. A
I Max d.c. Armour
t-,_J OOOm

No. Insulation Bedding t~e 1 Sheathing Overall 0P:~x~ Resistance wire


Cable Code thickness Diameter Drum
Cros Dia. of thickness thickness .wir t etgl at 20°C area
sectional d Type
area
wires
1ameer I ----+---~----+--
1---~~~~-~~
--1mm 2 x/mm mm mm mm mm -1- mm :g/'-k_m~l_nJ
k..... _k_m_.L--m~m_2 _1.__ __ --i

Four core cabl es


1 R41905'3Zlf1 .5 7/0.53 -0- .6-~-0-.8-- 0.9 1.4 I 13.5 32 6 j )J:__ 1 ---+--1_7_ - ... Kel 02
1 R422067ZZ I 2.5 7/0.67 >- 0.7 0.8 0.9 1.4 15.0 427 7.41 20 Kel 03
1 R424085ZZ I 4 -~77Q.Bs ->-- 0.8 - o-.8-+--- 1.25 1.5 -l--1-1-.8-1--- 6 36 ___-+--+----_
4.61 ---·-=_-}- _4 KeTOS
1R4.26fo4ZZ 6 7/ 1.04 0.8 ,__0-.8- -+---1-.2-5- 1.5 - 19.2 1 769 3.08 38 KeTOS-
1R429135ZZ 10 7/1.35 1.0 0.8 1.25 1.6 22.8 1081 1.83 46 - - t --Kel 06
- ---1
1R431170ZZ 16 I 7/1.70 1.0 1.0 1.6 1.7 26.3 1421 1.15 72 Kel 09

l
-~---+-----+-

1 R432214ZZ 25
---+---+---
7/2.14 1.2 1 .0 1.6 I 1.8 30.7 2022 0.727 76 Kel 12
1R433252ZZ 35 7/2.52 1.2 1.0 ·--_ 1._6_ _.___ 1._9_ _ 3_3 .7_ ..__2_5_25_ .__o_._52_4_-'-,_84_ _. KeT12
_,__I

Five core cables


1R519053ZZ 1.5 710 .53 0.6 I 0.8 0.9 1.4 I 14.3 510 12 .1 19 Kel 03
IR522067ZZ 2.5 710 .67 _0_.7_~_ 0.8 0.9 1.5 16.3 615 7.41 ( 22 - - l f -Kel 05
-----1
1 R52Lt085ZZ 4 l /0.85 0.8 0.8 1.25 1.5 19 .0 790 4.61 38 Kel 05
'1R526104ZZ 6 7/1 .04 0_.8_ _,___0.8 1.25 1.6 20.9 990 3.08 41 Kel05
---!---- 4----l--
1R529135ZZ 10 7/1.35 1.0- + -1.0--
1.6 1.7 25.8 1680 1 .83 68 Kef09
1R531170ZZ~ 7/1.70 1.0 1.0 for 1.6 1.7 28.4 I 2140 1.15 78 Kel 10
1R532214ZZ ~ 7/2.14 1.2 - 1-.0--'-- 1.6 1
1.9 33. 5 2950 0- .-72- 7--t--9-4- t - Kel l l
~.1 R53:g52ZZ j --~ 7_/2- .5- 2-+-1-1- .-2 1.0 1.6 - 1.9 1 36.6 3920 0.524 106 Kel -,--S-
-

Note - Refer Trthle G for currenl carrying apa ily '- nd voltag drop.
3 Outdoor Cables - Copper Conductor

3.9 Multi core armoured shaped conductor - PVC insulated.

whc·i
tray, 1 !i

Con<luctor

P In ul.11inn
• BS 6346
PVC Bedding
: 600/ ! ooov teel wire ;irmour
. 70

non
irernen1

Technical Information

j
Packing
Conductor I I 1000 m
~750 m
---.----------1 Nominal Nominal Nominal Nominal Max. A Max d.c. Armour _
KE LANI pprox
Cable Code Nominal Insulation Bedding Steel wire' Sheathing Overall W . h · Resistance wire
No. & thickness thickness diameter thickness Diameter eig t at 20°C area Drum
Cross
Dia. of
sectional Type
wires
area

mm2 x/mm mm mm mm -----+-'-


mm mm
~--------+-----;-----~-
kg/km
-~
Q/km mm 2
-+----------<
1R4322J4ZZ 25 7/2.14 1.2 __ 1.0 _ 1.6 1.8 27.8 2_02_2_.__o _ ._72_ 7_ _1 76 Kel 10
l R433252ZZ +-_3_5_-+--_
7 /_2_
.5_2 1.2 1.0 1.6 ___ 1 9 30 3 2525 0.524 84 Kel 10
1 R435178ZZ 50 19/1.78 1.4 1.2 2.0 2 . o- -35:4 - 3481 0.387 122 -- Kel 1S
1R437214ZZ 70 19/2.14 1.4 1.2 2.0 2.1 39.2- r 4_4_8_1 --+--- 0-.2-6_ 8_ 138 Kel 14
11 R438252ZZ 95 19/2.52 -------, .6--+---
1 -.2--+---2- _-o -+---2- .-2-+---
4-4 _
-3-l-----5-3_3_7---+--0- .-19_3_-+----
1-60--+--.-Ke-1_1_2____,
1 R43 92 03ZZ 12 0 _J 3 7/2_.0_3--l--_1_.6_-+---_ 1._4_+--_2_.5_--+-_2_.4_--l--_4_9_.3_ _ _ 74_3_4-----+--_0_._15_3_+---2
_2_0_-i---K_e_I _12___,
1R441 22 5ZZ 15 0 3 712 .2 5 1_.8
_ --+-_1_.4_-+--_2_ ._5 _+--_2_._5 _+--5_3_._
6 ----+1_ 8_83_4--+_ 0_.1_2_4 --+_2_4_0----+-_
Ke_l_l _5___.
1R442252ZZ 185 37/2.52 2.0 1.6 2.5 2.6 59.0 I 10760_ 0.0991 265 Kel 12
1 R443225ZZ 240 61/2.25 2.2 1.6 - - 2-.5- 2.8 65.7 113505 o.0754 299 Kel 12
1R444252ZZ
..._1_R_4 4_5_2_8_5Z
_Z__
300 61/2.52
4-0~0~~-=-~
6~1_
/-2~
2~
.8~5-=-~~~2~
1.6
.6~~-=-~~~
1_
2.5
.-8~~=--3 .1 5 -=-
- 3
- .-0 --+-72.0 I 16391
3 .3 ~~ 81 .3 I
0.0601 ... 333
212 75 _ 0.04 7_0_.__4_6_
Kel 13
7 __.__Kel 13

Note - Refer Table C for cur renl and


3 Outdoor Cables - Copper Conductor

3.10 Multicore armoured circular conductor - XLPE insulated

r\ppltL«.1iron : For outdoor in. tallation wh re rne h ni al prot 1 ction i r quirecJ. Th c1bl s ·an be
in tailed 111 air~ on a pcrfor t cl able tray, dir tin ground or in du tin 1 in ground.

Engineering Specifications
oncluuor
Type : Cu I XLPE/SWA/PVC XI l'E ln"lll.1tion

Standard : BS 54 7
Nominal Voltage : 600/1 OOO V
Insulation : 90 ° - rat d 'LPE c rnpound
Sheathing - : P IC compound
Packing : The able are delivered >n non-returnabl
wooden drums as per customer requirement
Conductor : oft c nnealed stranded opper wires

Technical Information
Packing
Conductor I I 1OOO m
'500m
KELANI Nominal Nomin I Nominal Nominal Ma . A Max d.c. Armour
C bi C0 d & Insulation Bedding I teel wire h athing Overall J:/.r
II
Nominc I N ,x; Resi tance wire
a e e I Cr? s I Di~~
se t1onal wires
area
.
I
of rhickness l thickness diameter thickness Diameter eig
l ·
1
at 20° area Drum
Type

m~ x/mm mm mm I mm mm mm k km il/km·-i--m
-m--
2

i- T
1----~~~~~~--'--

Tw o core cabl es
1S23117oiZl - 16 --171110 o f _I o.:I 125- , - LS .. 2o.4 I 895 _ 1_.12Q__l__1

Kel 05 4L
152322_1_42:* 25_ f_Zg_Jj_~_ 0.9 _j__
__Q_._8 __ 1 ) L __ J .§____L]_Q_ 1220 -H· OJ2 7 .~ 42 Kel_()B
1S233252ZZ 32.__L 7/2.52 ! __Q}_ l ______LQ_ ~&__ . 1.7 __j_J_ZJ 1690 ~ 524 60 Kel 1_Q_
Three co re cab les
1S331170ZZ 16 I 7/1.70 ~1-o-_-7 ·--- 0.-8~1-1.25 1.6 21._6 -+-_1_10_4-+-_1 .150 4 5 Kel05
1~~32214ZZC__25 7/2.14 lI 0.9 ______LQ_ 1.6 1.7- - 26.7 1718 0.727 62 Kel 10
15333252.£Zi~ 7/2.52 0.9 ~ 1.6 __l_L _,_2_ 9_.4_ , _2_1_2 3_ 0.524 _,~_6_8_ Kel 10
Four core cab les

~~~z~~~ I 1L__
~~ ~ ;;~:ifi:lr_p
1 ~~33252ZZ 712 '.~ i_ 0.9 ..
u ~--1= ~~::1 ~~: ~ I ~~i-~ p~~~ -~
1 .0_j_~6 1--- 1._§___L31.9 2586 _ o._524 78
~=:~~
KeW
Five co re cabl es
1S531170ZZ 1
16 ~ 7/1. 70'- 0 .7 1.0 1.6 1.7 ~ 1.150 72 Kel 10
1S532214ZZ l 25 7/2 .14 ----0.9 1.0 1.6 ml
5 1442_ 0.727-----t-- 88~ Ke112
1S533252ZZ 35 712.52 0.9 1.0 1.6 3067 0.524 ~ Kel 12
1 S535178ZZ 50 19/1.78 _1_.o_ -. _ _ 1._2_ 2.0---+--- 4236 ·-0.3_8_7 - Kel 10
1 SS 3 7 21 4 ZZ 70 1 9/2 .1 4 1. 1 1 .2 2. 0 --+------+--4-6-.3----;- 5-6_0_0--+--0-.2-6 8- -+ 1 66 Kef12

Note - Refer Tabl ' H for current carrying capacity and voltage drop.
3 Outdoor Cables - Copper Conductor

3.11 Multicore armoured shaped conductor - XLPE insulated

Appl ioii : f m ' JUtdo r.in )tc.1llc lion\ here rn he nic il pwtection is required . These can be
insta! in 11 , ··n c1 p :>iforat·'d , bi tr , dirr•rt in gr w i in ducting in ground.

Engineering

Type Cu/Xl PE/ S\V/\/PVC


Standard • BS S467
Nominal Voltage . 600ilOOOV
Insulation 90 °C rJted XLPE cornpound
Sheathing : PVC compound
Packing The cab les are delivered on non-returnJb!e
\/VOoden drums as per customer requirement
Conductor Soft an11ea!ed stranded copper wires

Technical Information

Packing

Q
~
Conductor I I L~~~Omm

L
KELANI __ Nominal Nominal Nominal Nominal Max. Approx. Max d.c. Armour __
Noml.nal Insulation Bedding I
Steel wire Sheathing Overall Weight Resistance wire
I
Cable Code
,______r~;;~~al
1

j
8
~~re;f I thickness dia~ thicknq ~~~:
1

thickness css -
Diameter J at 20°c

1.S432214ZZ 2
35
mm'
5 -
7/2.52 0.9
x/mm +
712.14
1.0
mm
o. 9
l 28.8
mm
mm -f--i;g/km
1.0
2 6.1 1871
2343
mm
!l/km
0.72 7
1.6
0.524
mm
mm'
---i:;;- 1 1-2____..
1.8
70
78
Kel 09
I
Kel 10
j I
1S435178ZZ _ 2.Q__ 19/1.78 ~-1.0FP.O _ ____J_~ ~_BJ 2976 ~0.38~

l
90 Kel 12
1S437214Z ~
15438252. ZZ
1..$439203. zz
70

120
19/2.14

37/2.03
1.1
-gs 1912.52 1 1.1 ~ !2_
!.l___lli
1.2

.4
2.0
2.0
2.5
2.1
2.2
_ll__
37.7
41.7
47.1
4278
5488
7058
I 0.268_ - ~
~
0.153
__L_ 147
~
Kel 15
I
154412 . 25ZZ ~ 37/2.2~
5 1_.4_ __li_ _ _2 ~ ~ _,___5 1_.4 8404 230
1S442252ZI T 185 37/2.52 1.6 1.4 2.5 2.6 56.6 10205 I
1S443225m 240 6112.25 1.7 j 1.6 2.5 63.0 12850 ---u
0.0754_ _ 289
1S444252ZZ 300 61/2.52 1.8 1.6 2.5 2.9 68.8 15609 0.0 ~ 319
1s44s2aszzD oo 61 12.8SCJJ? ~ _ _ 3.15 I 3.2 78.1 J 20350D.o'±ZQ__ J__4_52-:~~--_i

Note .. Refer Table H for cu rre nt carrying capacity and voltage drop.
4 Outdoor Cables - Aluminium Conductor

4.1 Single core unarmoured - XLPE insulated.

ppli ation:For outdo rin ~ t,11 tin in air, conduit, du t<rtray.Theyar"n rmall 1u.edf rp wer
distribution in urban n tw rks, in indu ·trial r I nt , in th rrnc I ow r and hy lr I ower st tion .

Engineering Sp cification

( omlu ctur
Type : Al/XLPE/PVC
Standard : B 7889/1 60502
Nominal Voltage 0/1000V l l'f ln<.uf 1t1m1

Insulation : 90 °C r, ted , LPE ·ornpounci


PV h .ith
Sheathing : PVC ompound ·-------

Packing : The cables are delivered on non-returnable


wooden drums as per customer ref]uirements
Conductor : tranded aluminium wires

Technical Information
Conductor Packing
--~ -.-
I
KELANI
N minal Nominal Nominal I Max. I Max d.c. I
Cable Code
Cross No. & Dia. Insulation Sheathing Overall
Approx.
Weight
IResistance Drum Cable
sectional of wires Thickness Thickness Diameter at 20°c Type Length
I
area
I ,_ I
I
--
mm 2 x/mm mm mm mm kg/km Q/km m
1L135178ZZ I 50 19/1.78 1.0 1.4 14.2 I 256 0.641 Kel 03 ' 1000
- -
1LI37214ZZ___,_
,______ 70 19/2 .14 1 .1 1.4 f 16.2 I
340 0.443 Kel 04 1000
- - ---~- ---· ~

448 0.320 Kel 05 1000


-
1 Ll38252ZZ
-
5 19/2 .52 1.1 ~-i-~ --
1L13 203ZZ 120 3712.03 1.2 1.5 j 20 .2 547 0.253 Kel 05 1000
1L141225ZZ 150 37/2.25 1.4 1.6 22.4 672 0.206 Kel 05 1000
-- -
1L142252ZZ 185 3 7/2.52 1.6 1.6 24.7 824 0.164 Kel 08 1000
--- -
1L14 225ZZ 240 61/2.25 1.7 L7 27.7 1056 0.125 Kel 10 1000
-
1L144252ZZ 00 61/2.52 1.8 1.8 30.6 1331 0.100 Ke! 12 1000

Note - Refer T.. ble l<r & K2 for current carrying capacity and voltage drop.