Vous êtes sur la page 1sur 10

Mitigation of Power Quality Disturbances using DVR

Riyatri Roy[1] Abisanka Bhattacharya[2] Suddhadipta Paul[3] Saptarshi Chatterjee[4] Beauty[5]


P.Suresh Kumar [6]

[1], [2], [3], [4], [5] Student of SRM Institute of Science and Technology, Department of
Electrical and Electronics
[6] Assistant Professor, Department of Electrical and Electronics Faculty of SRM Institute of
Science and Technology

ABSTRACT: The main aim of the paper is Persistent faults, Symmetrical faults and
to identify and restore the faults that occurred Asymmetrical faults. A transient fault is a
in a Power System. The Paper carries a fault where the fault is diminished as soon as
decent comprehensive characterization of the the power is disconnected for a very short
faults along with the overcoming techniques period of time. For example: tree contact,
of it. During a fault, the current and voltage animal contact, lightning strikes etc. A
waveforms are disturbed. In order to persistent fault is a fault that cannot diminish
overcome the disturbances, we are using itself as soon as the power is disconnected.
DVR (Dynamic Voltage Restorer) that acts For example: mechanical damages.
as a compensator. The vital role of DVR is to An unsymmetrical fault is a fault that occurs
provide a smooth flow of the voltage on all the three phases of the power system
waveforms without any disturbances in the equally. Generally this falls under rare case
system .The principle of DVR follows the fault category fault, nearly 5% of the total
injection of voltage and frequency which is faults can be considered as the symmetrical
necessary for the restoration of voltage at the faults. For example: line to line to line fault
load side of desired value. In this paper, the (that is the fault between all the lines) and line
voltage and current waveforms are also to line to ground fault (that is fault between
demonstrated after the incident of fault. the lines and ground)
Asymmetrical faults are the faults that are
INTRODUCTION: Technically our world unbalanced in nature and portrays an effect in
has a high velocity up gradation, which leads each of the three phases. This fault can
to the enhancement of the demand of further be classified as: a) Line to line fault
electricity day by day. Today, electricity is (the fault occurring between two lines of the
transmitted in most parts of the world. During power system) b) Line to Ground fault (the
transmission sometimes there forms some fault occurring between a phase and ground)
faults. In a Power System, any abnormality in and c) Double line to ground fault (the fault
the flowing of electric current is referred to as occurring between the two phases and the
a fault. For example if there is any failure in ground) Power Quality demands much
the circuit, then the fault is said to be an open attention as it plays a very vital role that
circuit fault. A fault is classified as Transient ensures the quality delivery of the power to
faults, the customers. Power Quality Disturbances can
be classified as Variations and Events. Variations
can be defined as a steady state disturbances that
requires persistent scrutinization of voltage system is a basic set of elements of
magnitude variations, frequency variations etc. dimensionless arrays.
On the contrary, voltage transients, voltage swell,
voltage sag, voltage interruptions are the power PROPOSED WORK:
quality disturbances derived from Power The schematic diagram represents IEEE
Quality events. Power Quality disturbances standard 9 bus system as our proposed work.
may be categorized as voltage sag, swell, Our Power system network comprised three
transient, harmonics, voltage flicker and generators, two non-linear loads, nine buses,
notch. The study of various types of one DVR model and one fault block for
phenomena which forms power quality creation of faults. At the generating side, we
disturbances and lead to the formation and are generating 25 kV, 15 kV and 18 kV at
development of mitigation energy. In order to Buses 1, 5 and 9 respectively. One of the non-
develop a proper mitigation strategy, linear loads is installed in Bus 6 and the other
understanding the phenomena of power is in Bus 7. A fault is generated between Bus
quality disturbances and its root cause falls 6 and Bus 8. In a parallel manner we have
under its utmost importance. Simulation of also installed a DVR (Dynamic Voltage
Power Quality disturbances is possible due to Restorer) which compensates the voltage sag.
the decent up gradation of the technology in The switching components of DVR are
terms of software. In this paper the proper mainly IGBT’s,
Simulation is executed by MATLAB which

Fig. 1
is a high level language for performing which are connected in a H-bridge and the
technical computations. This interactive pulses are generated by some PWM DVR
compensates the voltage sag by converting
DC supply to AC. DVR can also play a role The basic model of DVR is given below:
of generating or absorbing controllable real
and reactive powers at the load side. As a
power switching converter it infuses a three
phase ac output voltage in series and in a
synchronous manner with the transmission
and distribution line voltages.
The features of DVR includes a) fast dynamic
responses b) not expensive c) Power flow can
be controlled. This paper is a modified
version of the base paper, where no
compensators were introduced. The base
paper focused about the current and voltage
waveforms and analyzed the flow of power in
the buses. Our upgraded paper focused on
The continuity of the voltage waveforms Fig. 2
using a compensator which enhances the The basic block diagram of the single line
efficiency and moreover the safety of the load implementation of DVR model consists of a
side components. VSI (Voltage Source Inverter), a DC supply,
The table listed below shows the data of load a filter and a transformer.
and generating side:
TRANSFORMER DATA
GENERATOR DATA:- Parameters T1 T2 T3
Parameters G1 G2 G3
Voltage 25kV 15kV 18kV Power 4000 4000 4000

Frequency 50Hz 50Hz 50Hz Frequency 50 50 50

Source 0.8929 0.8929 0.8929 Voltage(Primary) 25e3 15e3 18e3


Resistance
Source 16.58e-3 16.58e-3 16.58e-3 Voltage(secondary) 230 230 230
Inductance
R1 0.02 0.02 0.02

L1 0.02 0.02 0.02


LOAD DATA:-
Parameters L1 L2 R2 0.02 0.02 0.02
Resistance 100 100 L2 0.02 0.02 500
Inductance 0.01e-3 0.01e-3
Rm 500 500 500

Lm 500 500 500


The simulation of the Power system model
was executed using the above table values.
The DVR model diagram implemented on compensator as represented in Figure 8 and
the paper is represented below: Figure 13, the voltages at all the three phases
become minimum and the current at all the
three phases becomes maximum.

During triple line to ground fault under the


category of symmetrical fault without using
DVR compensator as represented in Fig 9
and Fig 14,. During this fault also the
voltages at all the three phases becomes
minimum and the current at all the three
phases becomes maximum.
Fig. 3
During line to ground fault voltage and
current after implementing the DVR
RESULTS
compensator as represented in Fig 15 and Fig
As in our model, we have created different 18. Here the voltage sag is compensated by
types of faults between bus 6 and bus 8, the the DVR which generates the compensated
current and voltage waveforms of the voltage injected to three phase faulted line.
different types of faults are listed below with So to get the continuous voltage at the load
and without using DVR compensator. side.
During no fault condition in the power During line to line fault voltage and current
system there is no disturbances in the load after implementing the DVR compensator as
voltages and load currents thus attains an represented in Fig 16 and Fig 19. Here the
equilibrium condition as represented in Fig 4. voltage sag is compensated by the DVR
which generates the compensated voltage
During single line to ground fault in power injected to three phase faulted line. So to get
system without using DVR compensator, as the continuous voltage at the load side
represented in Fig 5 and Fig 10, the voltage
sag takes place and the current becomes During double line to ground fault voltage
maximum for the particular phase. and current after implementing the DVR
compensator as represented in Fig 17 and Fig
During line to line fault in power system 20, generates the compensated voltage
without using DVR compensator as injected to three phase faulted line. So to get
represented in Fig 6 and Fig 11, the voltage the continuous voltage at the load side
of both the phases becomes minimum and
current becomes maximum.

During double line to ground fault in power


system without using DVR compensator, as
represented in Fig 7 and Fig 12, the voltages
at both the lines become minimum and the

current becomes maximum hence


equilibrium condition breaks.

During triple line fault under the category of


symmetrical fault without using DVR
Fig. 4 Voltage Waveform during No Fault

Fig. 5 Voltage Waveform during LG Fault without DVR

Fig. 6 Voltage Waveform during LL Fault without DVR

Fig. 7 Voltage Waveform during LLG Fault without DVR


Fig. 8 Voltage Waveform during LLL Fault without DVR

Fig. 9 Voltage Waveform during LLLG Fault without DVR

Fig. 10 Current Waveform during LG Fault without DVR

Fig. 11 Current Waveform during LL Fault without DVR


Fig. 12 Current Waveform during LLG Fault without DVR

Fig. 13 Current Waveform during LLL Fault without DVR

Fig. 14 Current Waveform during LLLG Fault without DVR


Fig. 15 Voltage Waveform during LG Fault with DVR

Fig. 16 Voltage Waveform during LL Fault with DVR

Fig. 17 Voltage Waveform during LLG Fault with DVR

Fig. 18 Current Waveform during LG Fault with DVR


Fig. 19 Current Waveform during LL Fault with DVR

Fig. 20 Current Waveform during LLG Fault with DVR

CONCLUSION: This paper is a thorough Milisavljevic, “Trends in power system


study about the Power system, where protection and control,” Decision Support
different types of fault are formed in a Syst., vol. 30, no. 3, pp. 269–278, Jan. 2001.
transmission line. In order to improve the [2] C. Concordia, L. H. Fink, and G.
power quality in the transmission line due to Poullikkas, “Load shedding on an isolated
the fault, DVR is used, whose main function system,” IEEE Trans. Power Syst., vol. 10,
is to compensate the voltage, so there will be no. 3, pp. 1467–1472,Aug. 1995.2.
consistent voltage throughout the power [3] C. W. Taylor, “Concepts of under voltage
system. Thereafter if fault is occurred then load shedding for voltage stability,”IEEE
due to DVR, the load voltage and the load Trans. Power Del., vol. 7, no. 2, pp. 480–488,
current will not be affected. As a result the Apr. 1992.
load side will be protected against the fault. [4] A. V. Kulkarni, W. Gao, and J. Ning
“Study of Power System Load Shedding
REFERENCES: Scheme Based On Dynamic Simulation”,
[1] M. Begovic, D. [1] Novosel, and M. Transmission and Distribution Conference
and Exposition, 2010 IEEE PES .
[6] H. Bevrani, G. Ledwich and J. J. Ford,
“On the use of df/dt in power system
emergency control,” IEEE/PES Power
Systems Conference and Exposition, 2009,
pp. 1-6, March 15-18, 2009.

[7] H. Seyedi and M. Sanaye-Pasand,


“Design of new load shedding special
protection schemes for a double area power
system,” American journal of Applied
Sciences, Vol. 6, No. 2, pp. 317-327, Feb
2009.
[8] Rosli Omar , N.A.Rahim , Marizan
Sulaiman of Faulty of Electrical, University
Teknikal Malaysia Melaka, Karung Berkunci
1752 “Dynamic Voltage Restorer application
for power quality improvement in electrical
distribution system”.
[9] Risha Dastagir, Mariam Asif ,
Department of electrical engineering, Trinity
Institute of Technology and Research,
Bhopal “Power Quality improvement using a
DVR”.

Vous aimerez peut-être aussi