Automatic controllers are used onboard ships for the adjustment of one or more parameters in a
system. Function of the controller is to maintain the parameter as per desired value (value set by the
operator). The parameter could be jacket water temperature (for engine jacket water cooling system),
lubricating oil temperature (for engine lube oil system), fuel oil pressure (for boiler fuel oil system), etc.
Follow Us
PID controls are commonly used for these applications. Advantage of automatic indicating controller is
that it controls as well as indicates the parameter reading. Refer to the diagram and explanation below
to understand the basic principle of PID controllers. These controllers are normally located near the Marine Engin…
variable measuring point so that use of a transmitter (to transmit parameter signals to the controller) is Like Page
not required.
fuel oil starts increasing. When the temperature rises to the set point, controller shuts the steam valve.
Insulation Resistance Tests of High
The system response is illustrated down below.
Voltage Equipment
https://marineengineeringonline.com/basic-principles-of-pid-controllers/ 1/9
9/28/2019 Basic Principles of PID Controllers
Tags
marine
system main engine
engineering marine
Now as we know there is a thermal inertia in this system. Or in other words the position of temperature engineering
sensor and that of steam coil is different. That is why we cannot observe an increase in temperature as study materials
meo class
marine main switch board
soon as the steam valve opens. The same phenomenon explains why temperature is increasing even
after the steam valve is shut. Anyway disadvantage of this control is the large deviation from the exam questions panting pid
desired value or set point. Hence the application of such control is limited. controller positive displacement pumps
pounding proportional control pumps
relief valve safeties in main switch board
Proportional Action
sewage treatment plant smoke detectors
stp systems of main engine types of chemical
This is a continuous control action in which the controller output is proportional to the deviation
tankers
between measured value and desired value. Let us take an example of a simple water lever control as
shown in the figure below.
Consider a water tank with an outlet valve, a water supply valve, control lever on a pivot, control
strings, and float as shown in the figure. One end of the control lever is connected to the float while
other end to the water supply valve. The system is designed in such a way that, when float goes down
supply valve is opened more thereby increasing water supply to the tank. Similarly an elevation of the
float results in closure of the supply valve. At this point quantity of water supplied and flown out of the
tank is same or the system is in equilibrium. Suddenly demand of water increases or the discharge
valve is opened more. This result in reduction in water level inside the tank and causes float to lower.
As float lowers it raises the control string connected to the water supply valve, thereby increasing the
supply of water.
https://marineengineeringonline.com/basic-principles-of-pid-controllers/ 2/9
9/28/2019 Basic Principles of PID Controllers
As shown in the figure above, a new equilibrium is attained by the system. Once again supply and
demand of water is same. But we can see a drop in water level from the desired value. This deviation
from the measured value and desired value is known as offset. It is an inherent property of the
proportional control. Offset can be reduced but cannot be eliminated in such systems. The amount by
which the input signal value must change to move the correcting unit between its extreme positions is
known as proportional band. This concept can be made clear from the figures shown above. Move
the position of the pivot towards right (closer towards the float). Now we can see that a small change in
water level causes an amplified effect in opening or closing the supply valve. In other words the system
becomes more sensitive. Also here the offset is reduced comparing to the scenario before. Similarly,
moving the pivot towards the left cause minor changes for the supply valve even though float lowers or
rises drastically. Here sensitivity of the system is less. It is clear that offset can be reduced to minimum
when sensitivity is higher. But this results in hunting of the system. Hunting means excessive
fluctuation of the measured value around desired value. System response to proportional action is
shown below.
https://marineengineeringonline.com/basic-principles-of-pid-controllers/ 3/9
9/28/2019 Basic Principles of PID Controllers
So far we have discussed proportional action with reference to a simple float and valve system. Same
can be explained using a flapper-nozzle mechanism too. In fact such an example is much closer to the
actual control system.
Referring to the diagram above, as the measured value deviates from set point, flapper moves closer to
the nozzle. This results in an increase in output air pressure. This increase in output air pressure
changes the controlled condition (parameter to be controlled), say by closing or opening a valve. At the
same time the increased output air pressure act on the feedback bellows also. This negative feedback
pushes the flapper away from the nozzle, thereby reducing output air pressure. Now the system is in
equilibrium. Remember that an offset is inevitable here. Moving the nozzle away from the feedback
bellows increase sensitivity and hunting of the system. Also moving nozzle towards feedback bellows
reduces hunting and increases offset. So position of the nozzle (or Proportional Band) can be
adjusted carefully to obtain a stable system with minimal offset and hunting.
Integral action or reset action is used in conjunction with proportional action, to remove offset from the
system. Here controller output varies at a rate proportional to the deviation between measured and
desired value. Refer to the figure below.
https://marineengineeringonline.com/basic-principles-of-pid-controllers/ 4/9
9/28/2019 Basic Principles of PID Controllers
Here in addition to the feedback bellows, we have integral action bellows also. Consider the integral
action valve is open. Now as the flapper moves closer to the nozzle because of a deviation, output air
pressure increases, the same air pressure acts on feedback bellows to move the flapper away from
nozzle to an equilibrium position. Now there is an offset. Again the same control air pressure acting on
the integral bellows moves the flapper towards the nozzle to increase control air pressure. Hence a
new equilibrium is attained with no offset. Note that all these actions take place simultaneously. When
the integral action valve is fully open, integral action will be too fast that result in hunting. When the
valve is crack open, there is no hunting but it takes long time to remove offset. In other words time
required to remove the offset (Reset Time) can be adjusted by opening or closing integral action valve.
Closure of the integral action valve means no integral action. Reset time to be set in such a way that
system operates fast to remove offset and minimal hunting. All pressure control systems onboard ships
are normally proportional-integral (PI) controls.
Derivative action is utilized along with proportional and integral actions. This is applied in systems
where time delay between changes in measured value and their correction is long. Example is
temperature control for jacket water system. Here controller output is proportional to the rate of change
of deviation. Refer to the figure below.
https://marineengineeringonline.com/basic-principles-of-pid-controllers/ 5/9
9/28/2019 Basic Principles of PID Controllers
Here a derivative action valve is introduced as shown in the figure. Closing this valve any amount
would introduce derivative action in the system. Consider the derivative action valve is closed 70%.
When flapper moves towards nozzle because of a deviation, controller output pressure increases, the
same pressure acts on the feedback bellows through the derivative action valve. As the valve is only
little open, it takes time to move the flapper away from the nozzle by negative feedback, thereby
allowing control air output pressure to be higher for long time, which again allow more time for
corrective action. Also derivative action can be varied by adjusting opening or closing derivative action
valve. When derivative action valve is fully open, there is no derivative action.
https://marineengineeringonline.com/basic-principles-of-pid-controllers/ 6/9
9/28/2019 Basic Principles of PID Controllers
https://marineengineeringonline.com/basic-principles-of-pid-controllers/ 7/9
9/28/2019 Basic Principles of PID Controllers
Related Posts
May 2, 2014 May 6, 2014 May 2, 2014 April 30, 2016 May 2, 2014
Proportional, Basic Adjustment for Pneumatic Control Troubles,
Integral and Temperature Operation – PID Systems on Ships Investigation of
Derivative Control Control System Controller causes and
Action Counter-measures
– PID Controllers
May 2, 2014 May 2, 2014 February 6, 2016 October 4, 2015 May 2, 2014
Automatic Maintenance of Troubleshooting Pumping Down of Fuel Oil Viscosity
Indicating PID Controllers Alarm Monitoring the Refrigeration Controller Working
Controller and and Control Plant on Ships Principle
Specifications System on ships
Posted in: Instrumentation and Control | Tagged: automatic controller, derivative control, integral control, pid control,
pid controller, pressure control, proportional control, temperature control
mahbubul alam
on September 18, 2016 at 11:32 pm said:
Very helpful and easy to understand the system. Good topic for engineers.
Reply↓
Leave a Reply
Your email address will not be published. Required fields are marked *
Name *
Email *
Website
https://marineengineeringonline.com/basic-principles-of-pid-controllers/ 8/9
9/28/2019 Basic Principles of PID Controllers
Post Comment
https://marineengineeringonline.com/basic-principles-of-pid-controllers/ 9/9