Vous êtes sur la page 1sur 1

Technical Specification of 3×16 RM 2xY

SL Technical Particulars Unit Offered Data


No.
1.0 Name & address of the manufacturer - SQ Wire & Cable Co. Ltd.
124 Kewdhala, Madanpur, Bandar,
Narayangonj.
2.0 Party name - National Cement Mills Ltd
3.0 Type of Cable - 2xY
4.0 Voltage grade V 600/1000
5.0 Reference Standard - IEC 60228, 60502-1
6.0 No. of cores x Conductor cross sectional area no. x mm2 3 × 16
7.0 Conductor:
7.1 Material & Class - Annealed copper & class-2
7.2 Shape of conductor - Circular Stranded
7.3 Number & Diameter of wire no./mm 7/1.71
7.4 Diameter of conductor mm 5.13
7.5 Max.m D.C resistance of conductor Ohm / km 1.15
8.0 Insulation:
8.1 Material - Cross-linked Polyethylene (XLPE)
8.2 Nominal thickness of insulation mm 0.7
8.3 Min.m thickness of insulation mm 0.53
8.4 Colour of insulation - Red, Yellow & Blue
9.0 Laid Up: - Three Core Laid up together
10.0 Inner covering:
10.1 Material & colour - Polyvinyl Chloride (PVC) & Black
10.2 Approx. thickness of inner covering mm 1.0
11.0 Outer sheath:
11.1 Material - Polyvinyl Chloride (PVC)
11.2 Nominal thickness of outer sheath mm 1.8
11.3 Min.m thickness of outer sheath mm 1.43
11.4 Colour of Sheath - Black
12.0 Approx. overall diameter of complete cable mm 20.3
13.0 Current rating in underground at 300C amps 110
13.1 Current rating in air at 350C amps 98

DESIGNED BY CHECKED BY

Jamil Sharif Md. Iqbal Hasan


Asst. Engr. (QC) Asst. Manager (QC)