COMPACT VACUUM CONTACTOR
CV Series
Features
• Front Accessible • Quiet, Rugged Design
• Long Mechanical & Electrical Life • Standard with On/OFF Indicator
• Mounts in any plane • Compact, Lightweight
• Class 20 Bi-metallic overload relays • Side mounted auxiliary contacts
2 | www.joslynclark.com
COMPACT VACUUM CONTACTOR
CV Series
Rated Insulating & Operating Voltage 600V 1,000V 1,500V -76 110/120VAC 50/60Hz
Rated Operating Current - AC1 135A 200A 200A -26 220/240VAC 50/60Hz
Rated Operating Power - AC3 100HP 460/575V 250HP 185KW-660V 500HP 370KW-1,500V -125 125VDC
Rated Operating Power - AC4 60HP 460/575V 175HP 130KW-660V 315HP 235KW-1,500V -150 250VDC
Rated Frequency 50-400Hz Motor HP/KW AC3
Making Current 2,000A
Breaking Current 1,600A Voltage 135A 200A
Dielectric Strength / B.I.L. 6,000V (1 Minute per Interrupter) 200/208V 43/30 60/45
Interupting Current 2,200A 220/240V 50/37 75/56
Short Time Withstand Current (50ms) 10,000A 380/415V 75/56 125/93
Short Time Current (1s) 5,000A 440V 100/75 125/93
Short Time Current (10s) 1,600A 460/480V 100/75 150/112
Mechanical Life - No Load 1,200,000 cycles 575V 125/93 150/112
Electrical Life at Rated Current 600V 125/93 200/149
1,000,000 cycles 660/690V - 200/149
(AC3 Duty Cycles)
Switching Frequency 600 cycles per hour 1,000V - 300/224
Chopping Current 0.9A 1,500V - 500/373
Operating Range at Rated Voltage -15% +10% Three Phase Transformer Load KVA
Closing Power / Duration 1,200VA | 20 ms Duration
Holding Power 12VA Voltage 135A 200A
Average Opening Time 120ms 200/208V 44/46 66/68
Average Closing Time 20-40ms 220/240V 49/53 72/79
Average Pick-Up at Rated Voltage ≤85% 380/415V 84/92 125/137
Average Drop-Out at Rated Voltage ≤70% 440V 98 145
Recommended Control Transformer 400VA Machine Tool Transformer; 5% Regulation at 20%pf 460/480V 102/107 151/158
575V 128 189
Application Ratings 600V 133 197
Mounting Installation All Planes (Contactor only) 660/690V - 217/227
Altitude Up to 6600 ft. (2000 m) 1,000V - 329
Operating Temperature Range -40oF (-40oC) +122oF (50oC) 1,500V - 494
Vibration / Shock 40Hz - 2G. / 30G. Three Phase Transformer Load KVAR
Weight 21 lbs. (9.53 kg)
Auxiliary Contacts 1 N.C. & 1 N.O. (standard); 3 N.C. & 3 N.O. (optional) Voltage 150A 200A
** Coil Voltage 208V 40 54
3.5
88.9
.90
22.9
220/240V 43 62
*6.44 4X .38
.41
380/400V 74 104
415/440V 81 114
163.6 9.5 10.4
* 5.97
* WIDTH DIMENSION FOR CV
5.3
151.6
DC COIL DESIGNS 460V 90 127
134.6
OPTIONAL AUX.
3.5
575/600V 115 156
CONTACT KIT .90
1,000V 195 260
88.9 5.93 7.5
22.9 MOUNTING PLATE
MTG.PLATE 150.6 HOLE PATTERN 190.5
NOTES:
10.4
8.32
211.3
7.5 8.66
6.25
190.5 220.0
158.7
MTG. PLATE
1.69
.97
42.8
24.5
TYP.
1.0 3.3
1.0 4.36
25.4 83.8
25.4 110.8
MTG. PLATE
www.joslynclark.com | 3
COMPACT VACUUM CONTACTOR
CV Series
.38
** Coil Voltage 200/208V 66/68 98/102
9.7
6.83
4X .38
220/240V 72/80 108/118
173.5
9.5
380/415V 126/138 186/204
.59 440V 146 216
460/480V 152/160 226/236
15.0
2X .75
19.1
MOUNTING PLATE
NOTES:
.6
15.2
1
Consult factory for certifications
and approvals.
9.25
235.0
OVERALL
8.25 9.16
209.6 7.75
9.0 232.6
MTG. PLATE 196.7
228.6 MTG. PLATE
OPTIONAL AUX.
CONTACT KIT
.71
6X .4 17.9
2.54
10.2 1.46
64.6 * WIDTH DIMENSION FOR CV
37.0
TYP. DC COIL DESIGNS & ALL CVC
* 8.59 COIL DESIGNS. NOTE:
218.2
9.1 1. ALL DIMENSIONS IN INCHES [mm]
231.1 DEPTH OF CONTACTOR 6.46" (164mm)
4 | www.joslynclark.com
COMPACT VACUUM CONTACTOR
CV Series
8.0
203.2
6.46 575V 380 423
164.0 2X .75
600V 400 444
4X .38 6.83
2X 2.89 1.25 19.1
9.5 173.5 MOUNTING PLATE
73.4 31.8 HOLE PATTERN
MTG. PLATE 8.25
660/690V - 486/510
MTG. PLATE
209.6
.59 NOT TO SCALE
14.9
1,000V - 734
.38 2X .75
9.7 19.1
2X .38
1,500V - 1,110
9.5
.6
NOTES:
15.2
12.05 9.25
1
Consult factory for certifications
10.36
305.9
OVERALL
235.0
and approvals.
8.25 263.1
9.16
209.6 9.0 232.6
MTG. PLATE 228.6 MTG PLATE
OPTIONAL AUX.
CONTACT KIT
1.64
41.6
www.joslynclark.com | 5
HEAVY DUTY VACUUM CONTACTOR
1140 Series
Features
• Designed to Standards IEC 60947-4, CSA22.2 & UL508 • Visual ON/OFF indicator
• Heavy Duty Mining Design • Visual wear indicator
• Standard contactor includes 2NO & 2NC Aux. Contacts • Line & Load Terminal Hex Bolts
• Optional contactor includes 4NO & 4NC Aux. Contacts • Mounts in any plane
6 | www.joslynclark.com
HEAVY DUTY VACUUM CONTACTOR
1140 Series
Specifications
Catalog Numbers CV77U033A12-** Coil Voltages
Application Ratings
Mounting Installation All Planes (Contactor only)
Altitude Up to 6600 ft. (2000 m)
Operating Temperature -13oF (-25oC) +140oF (60oC)
Vibration / Shock 10-50Hz - 2G/30G
Weight 17 lbs. (7.71 kg.)
Auxiliary Contacts 2 N.O. & 2 N.C. (standard); 4 N.O. & 4 N.C. (optional)
** Coil Voltage
143.7
2X 5.66
3.8
.15 134.6
5.30
142.5
11.8 5.61
6X .47
14.9 110.4 120.0
.59 9.1 12.7 4.35 11.1 4.72
4X .36 .50 .44
14.6
.58
3.5
6X .14
17.8
.70
11.8 11.1
42.4 .47 .44
4X 1.67
8.9 29.4
6X .35 84.9 4X 1.16
2X 3.34
www.joslynclark.com | 7
LOW & MEDIUM VOLTAGE VACUUM CONTACTOR
VC Series
Features
• Front Accessible • Quiet Operation • Energy efficient control module
• Mounts in any plane • Compact, Lightweight • Fully phase insulated
• Tamper resistant, dust protected • Self-adjusting power contacts • Rugged modular construction
auxiliary contacts
8 | www.joslynclark.com
LOW & MEDIUM VOLTAGE VACUUM CONTACTOR
VC Series
Specifications
Catalog Numbers Coil Voltages
1,500V VC77U03415-** VC77U03515-** VC77U03615-** 2
Suffix Coil Voltage
3,600V VC77U03436-** VC77U03536-** VC77U03636-** 2 -76 110/120VAC 50/60Hz
-26 220/240VAC 50/60Hz
Power Ratings Enclosed -125 125VDC
Rated Insulating & Operating Voltage 1500V-3600V1 -150 250VDC
Rated Operational Current 160A 320A 600A Motor HP/KW AC3
Rated Frequency 50-400Hz
Making Current 1,600A 3,200A 6,000A Voltage 160A 320A 600A
Breaking Current 1,600A 3,200A 6,000A 230V 60 125 200
Dielectric Strength / B.I.L. 6,000V (1 min. per Interrupter); 4,500V (60ms per Interrupter) 460V 125 250 400
Interupting Current 4,400A 5,000A 6,000A 1,000V 250 500 1000
Withstand Current 30,000A-3Hz. 1,500V 400 800 1500
Short Time Current 1 Sec. 5,000A 7,000A 9,000A 2,300V 600 1200 2250
Short Time Current 2 Sec 2,000A 5,000A 7,000A 3,300V 800 1750 3175
Mechanical Life - No Load 2,000,000 cycles
Three Phase Transformer Load KVA
Electrical Life at Rated Current
1,000,000 cycles
(AC3 Duty) Voltage 160A 320A 600A
Switching Frequency 600 cycles per hour 230V 60 120 225
Chopping Current 0.9A 460V 120 225 450
Operating Range at Rated Voltage +10% -25% 1,000V 250 500 975
Closing Power / Duration 950VA/17ms 950VA/17ms 1,900VA/17ms 1,500V 375 750 1450
Holding Power 9VA 9VA 18VA 2,300V 600 1200 2250
Average Opening Time 90ms at 60Hz 3,300V 850 1700 3250
Average Closing Time 17ms at 60Hz
Three Phase Transformer Load KVAR
Average Pick-Up at Rated Voltage ≤75%
Average Drop-out at Rated Voltage ≤70% Voltage 160A 320A 600A
Recommended Control Transformer 250VA 250VA 500VA 230V 45 90 170
460V 90 180 340
Application Ratings
1,000V 195 390 720
Mounting Installation All Planes (Contactor only) 1,500V 290 580 1050
Altitude 6600 ft. (2000 Meters) 2,300V 435 870 1650
Operating Temperature Range -40oF (-40oC) +122oF (50oC) 3,300V 625 1250 2350
Vibration / Shock 40Hz - 2G. / 30G.
Weight 12 lbs. (5.45 kg) 12 lbs. (5.45 kg) 24 lbs. (11 kg) NOTES:
Auxiliary Contacts 2 sets of Form C Contacts 4 1
3600V Model has a B.I.L. rating of 45
kV and an interrupt rating of 4000A.
** Coil Voltage 2
Contact factory for dimensions and
outline drawings.
3.0 2.56 3
Consult factory for certifications and
76.2 65.0
MTG. PLATE MTG. PLATE 4X .38 approvals.
9.7
MTG. PLATE
4
Excluding DC Coil Voltages
.38 8.1
9.7 206.2
MTG. PLATE 3.0
76.2
2.56
3X .44 .38 65.0
11.1 9.5
7.91
5.28 200.8
4.5 MTG. PLATE
134.0 4.5 HOLE PATTERN 5.28
114.3
114.3 134.0
MTG. PLATE
NOT TO SCALE
4.14 6.39
105.3 162.4
4X .38
9.7 6.5
165.1
.81
20.6
.51
1.12
12.8
28.4 NOTE:
3X .56 TYP. 3.38
14.3 3.0 .81 85.8 1. ALL DIMENSIONS IN INCHES [mm]
1.44
76.2 20.6 7.49
36.5
TYP. 6.5 190.1
165.1
8.12 MTG. PLATE
206.2
MTG.PLATE 8.88
225.4
www.joslynclark.com | 9
MEDIUM VOLTAGE VACUUM CONTACTOR
MVC Series
Features
• Front Accessible • Rugged design
• Panel mount or table mount • Compact, Lightweight
• Field selectable power terminals • Low Maintenance
• Full phase insulated, B.I.L. 60kV • Self-adjusting power contacts
10 | www.joslynclark.com
MEDIUM VOLTAGE VACUUM CONTACTOR
MVC Series
Specifications
Catalog Numbers 1, 2 Coil Voltages
2,500V MVC77U032A25-** MVC77U034A25-** MVC77U036A25-**
Suffix Coil Voltage
5,000V MVC77U032A50-** MVC77U034A50-** MVC77U036A50-** -76 110/120VAC 50/60Hz
7,200V MVC77U032A72-** MVC77U034A72-** MVC77U036A72-** -26 220/240VAC 50/60Hz
-125 125VDC
Power Ratings Enclosed -150 250VDC
Rated Operational Current 200A 400A 600A Motor HP/KW AC3
Rated Frequency 50/60Hz
Voltage Power Factor 200A 400A 600A
E1 Interrupt Rating 2,500V - 20 MVA equivilent to 4.62KA
MVA & KA Values 5,000V - 40 MVA equivilent to 4.62KA 2,500V 0.8 800 1,625 2,500
Contactor Only 7,200V - 60 MVA equivilent to 4.62KA 2,500V 1.0 1,000 2,000 3,000
E2 Fuse Coordination (5000V) 400 MVA 45.7 KA RMS (38R max. fuse size) 3,300V 0.8 1,050 2,125 3,175
Peak Withstand Current (5000V) 57.8 KA - Peak (38R max. fuse size); 50 KA (24R max. fuse size) 3,300V 1.0 1,350 2,750 4,000
Short Time Current (1s) 6,000V 7,000V 9,000V 4,160V 0.8 1,350 2,750 4,000
Short Time Current (5s) 4,000V 5,000V 6,000V 4,160V 1.0 1,625 3,350 5,000
Short Time Current (15s) 2,000V 2,600V 3,000V 6,600V 0.8 2,125 4,250 6,000
Switching Frequency 300 cycles per hour 6,600V 1.0 2,750 5,500 8,000
Elec. Life at Rated Current 600,000 cycles 400,000 cycles 250,000 cycles Transformer Load KVA
Mechanical Life - No Load 750,000 cycles
Dielectric Strength / B.I.L. 20,000V (1 min. per Interrupter) Voltage 200A 400A 600A
60,000V (60ms per Interrupter) 2,500V 800 1,600 2,400
Chop Current Max 0.9A 3,300V 1,000 2,100 3,200
Operating Range at Rated Voltage +10% -15% 4,160V 1,350 2,700 4,100
Closing Power VA/Duration 650VA / 45ms 6,600V 2,100 4,300 6,500
Holding Power 7VAC / 0.47VDC
Three-Phase Capacitor Load KVAR
Average Opening Time 90ms
Average Closing Time 40ms Voltage 200A 400A 600A
Average Pick-Up at Rated Voltage ≤85% 2,500V 550 1,100 1,650
Average Drop-out at Rated Voltage ≤70% 3,300V 750 1,500 2,250
Recommended Control Transformer 300VA 600VA 4,160V 1,000 2,000 3,000
6,600V 1,500 3,000 4,500
Application Ratings
Mounting Installation All Planes (Contactor only) NOTES:
Altitude 6600 ft. (2000 Meters)
1
Consult factory for 2, 4, 5 Pole Contactors, and
Mechanically Interlocked Contactors.
Operating Temperature Range 32oF (0oC) +134oF (57oC) 2
Consult factory for certifications and approvals.
Vibration / Shock 40Hz - 2G. / 30G. 3
Excludes DC Voltages.
Weight 56 lbs. (25.4 kg)
Auxiliary Contacts 2 N.O. & 2 N.C. (standard); 4 N.O. & 4 N.C. (optional) 3
** Coil Voltage
10.0 1.76
254.0 44.8
MTG. PLATE MTG. PLATE
4X .38 12.68 10.0 1.76
.91 3X .57 9.5 .50 322.1 254.0 44.8
23.1 14.4 MTG. PLATE 12.7 5.18 .50
MTG. PLATE 4X .38
131.7 9.5 12.7
3X .59 1.23
15.1 31.2
2X 11.93
5.0 302.9
1.76
127.0
44.8 NOTE:
TYP. 13.52
343.5 1. ALL DIMENSIONS IN INCHES [mm]
14.5 MTG. PLATE
368.3
www.joslynclark.com | 11
SPECIAL PURPOSE VACUUM CONTACTOR
SVC Series
Designed to Standards
IEC 60470 | GB/T 14808 | GB 11022
Features
• High Current Capacity • Long product life
• 3-Phase synchronization ≤2ms • Mechanically latched, electriclly held
12 | www.joslynclark.com
SPECIAL PURPOSE VACUUM CONTACTOR
SVC Series
Specifications
Catalog Numbers SVC77U034A120-** SVC77U036120-** Coil Voltages
Application Ratings
Altitude Up to 6,500 ft. (1,981 m)
Operating Temperature Range 5oF (-15oC) +104oF (40oC)
Relative Humidity 90% (at 77oF)
Weight 67 lbs. (30.39 kg)
Auxiliary Contacts 3 N.0. & 2 N.C. (standard); 4 N.O. & 4 N.C. (optional)
** Coil Voltage
www.joslynclark.com | 13
SPECIAL PURPOSE VACUUM CONTACTOR
SVC Series
VC Series Framework
Voltage 1,500V Open Type 3,600V Open Type Coil Voltages
14 | www.joslynclark.com
JOSLYN CLARK VACUUM CONTACTORS
Advantages
Long Mechanical Life
Up to 3 million operations at 30 operations per day. . Life expectancy of approx. 274 years.
Low Maintenance
No special maintenance skills or adjustments required
Minimal Downtime
Important in 24 hours operating processes
Arc Containment
No ironized gases reducing risk of flash ovens.
Weld Free
Minimal contact bounce, low arc energy and temperatures minimizes risks of contact welding
Impervious to Environment
Contacts sealed from atmospheric contamination such as H2S Chlorine, dust, salt atmospheres, etc.
Industrial Users
Petro Chemical plants and refineries Petro Chemical exploration and pumping facilities
Petro Chemical transportation - pipelines Paper Mills
Saw Mills Textile Mills
Steel Mills Underground for Coal and Minerals Mining
Water Sewage Treatment Plants Surface Mining for Coal and Minerals
Solar Panels Material Handling
Electrical Utilities Locomotive Transportation
Stone Crushing and Quarrying Cement Plants
Tire and Rubber Plants Water Pumping Irrigation
Oil Pumping AC and DC Drives, Power Supplies & Traction
Surface Mining Equipment Underground Mining Equipment
Induction Heating - Furnaces Capacitor Switching - Power Factor Correction
Hazardous Area Flameproof Equipment Air Handling - Compressor Equipment
Crane Control MCC Manufacturers
Panel Builders Harmonic Filters
Transfer Switches Lighting
Mining Shovels Drag Lines
Conveyors & Crushers Wind Turbines
Wood Chippers Bucket Wheel Excavators
Tunnel Boring Machines Electronic Soft Starters
www.joslynclark.com | 15
A History of Setting the Standard by Which Others Are Measured
Dating back to the 1920’s, Joslyn Clark began as the Clark Controller Company.
Instantly recognized as a pioneer of innovation and quality, Clark products were
recognized for their advanced design and reliability. Although our name has
www.joslynclark.com changed through the years, our commitment to excellence, unrivaled safety and
reliability has not.
Push Buttons
Selector Switches
Limit Switches
JCC1801 REV. A