LG HRC Power Fuses


Current without
Power Fuse
(40kA ms)

Ipeak
Let through current

e
Cycl
.5
low0
Be

Rated voltage(kV) 3.6 7.2 12 15.5 24 36


Initiation of
56�85�90�45�70�89�48�80�82� 47�72�88�47�85� 85�45�85�90�
arcing(degree)
Ipeak(kA) 6.5 7.2 7.3 5.2 6.0 7.3 5.2 7.1 7.1 5.3 6.1 7.3 5.1 7.2 7.2 5.2 7.2 7.3
Power Factor 0.07 ~ 0.15
�Test current : 40kA �Basis : 63A
�I peak : Let through current(under the short circuit test)

1
���Contents���
Introduction 4

Ratings and specifications 4

Conditions of selection 6

Characteristics curves 8

Fuse holder dimensions 12

Ordering information 14

2
LG HRC Power Fuses
Introduction

Features
�The LG HRC Power Fuses belong to the PRIME MEC series. It interrupts high currents before the first loop of fault
current has reached its natural peak value and therefore cuts down the required withstand capacity of the associated
equipment on the electric system.
�Though small in size, it has a high breaking capacity and its enclosed type is suitable for use inside of the panel board.
�PRIME MEC fuses are equipped with striker pins for trip indicators as well as for operating the related load break
switches.
�Link type fuse holder enables easy maintenance and high stability when replacing the fuses.
�With Fuse Checker, checking the conditions of a fuse in the panel board or by telecommunication is possible.(Optional)

Applied standards
�IEC 282-1, DIN 43625, BS 2692, KSC 4612

Applications
�Transformer protection
- To protect against short circuit current in the secondary part of
a transformer and fault current in the transformer circuit.
�Condenser protection
- To protect against fault current in the condenser circuit.
�Motor protection
- To protect against fault current in the motor circuit
�Cable protection
- Fault current protection secures the cable

Ratings and specification


Fuse link Fuse holder
Rated Rated Breaking Minimum Dimensions Weight Rated Rated Insulation
breaking
Type voltage current current voltage current level
current (A) (B) (kg) Type
(kV) (A) (kA, rms) (A) (kV) (A) (BIL, kV)
(mm)
LFL-3G-5B 5
LFL-3G-10B 10
LFL-3G-20B 20
LFL-3G-30B 30 55 1.0

LFL-3G-40B 40 192 LFL-6G- 100


3~4In
LFL-3G-50B 50 D1HB 7.2 45
3.6 40 In: Rated
LFL-3G-60B 63 current
LFL-3G-75B 75 2.0
LFL-3G-100B 100
77
LFL-3G-125B 125
LFL-6G-
LFL-3G-160B 160 292 2.8 200
D2HB
LFL-3G-200B 200

3
Ratings

Fuse link Fuse holder


Rated Rated Breaking Minimum Dimensions Weight Rated Rated Insulation
breaking
voltage current current voltage current level
Type current (A) (B) (kg) Type
(kV) (A) (kA, rms) (A) (mm) (kV) (A) (BIL, kV)

LFL-6G-5B 5
LFL-6G-10B 10
LFL-6G-20B 20
LFL-6G-30B 55 1.0
30
LFL-6G-40B 40 192 LFL-6G-D1HB 100
LFL-6G-50B 50 3~4In
7.2 40 In: Rated 7.2 60
LFL-6G-60B 63 current
LFL-6G-75B 75
LFL-6G-100B 100 2.0
LFL-6G-125B 125 77
LFL-6G-160B 160
292 2.8 LFL-6G-D2HB 200
LFL-6G-200B 200
LFL-12G-5B 5
LFL-12G-10B 10
LFL-12G-20B 20
LFL-12G-30B 30 55 1.3
LFL-12G-40B 40 292 LFL-12G- 100
LFL-12G-50B 50 D1HB
12 50 3~6In 12 75
LFL-12G-60B 63
LFL-12G-75B 75
2.8
LFL-12G-100B 100
LFL-12G-125B 125 77 LFL-12G-
LFL-12G-160B 160 442 4.2 200
D2HB
LFL-12G-200B 200
LFL-15G-5B 5
LFL-15G-10B 10 55 1.3
LFL-15G-20B 20
LFL-15G-30B 30 LFL-15G- 63
LFL-15G-40B 15.5 40 40 3~4In 292 2.8 D60B 15 110
LFL-15G-50B 50 77
LFL-15G-60B 63
LFL-15G-75B 75 LFL-15G-
442 4.2 100
LFL-15G-100B 100 D1HB
LFL-20G-5B 5
LFL-20G-10B 10 55 2.0
LFL-20G-20B 20
LFL-20G-30B 30 442 LFL-20G- 200
LFL-20G-40B 40 D2HB
77 4.2
LFL-20G-50B 50
LFL-20G-60B 63 40 24 125
24 3~4In
LFL-20G-75B 75 LFL-20G-
537 77 5.1 100
LFL-02G-100B 100 D1HB
LFL-20G-75B 75
LFL-02G-100B 100
5.1 LFL-20G-
LFL-20G-125B 125 442 87 200
D2HB
LFL-20G-160B 160
LFL-20G-200B 200
LFL-30G-5B 5
LFL-30G-10B 10
55 2.4
LFL-30G-20B 20
LFL-30G-30B 30 LFL-30G- 36 63 170
36 25 3~4In 537
LFL-30G-40B 40 D1HB
LFL-30G-50B 50 77 5.1
LFL-30G-60B 63
�Application site : Indoor use
�For fuse link & fuse holder type, refer to page 15.
4
LG HRC Power Fuses
Conditions of selection

Basic conditions for selecting the Power Fuses


�The rated current of a Power Fuse should be higher than sum of the total rated current of the electric equipment on the
circuit.
�Back-up protection with electric equipment on the circuit.
-Set the operating characteristics of the Power Fuses to satisfy the over-current characteristics of the protected loads on the circuit. Also, set the
occurred calories, by the l2t operation, to be smaller than the short-circuit intensity of the electric equipment and circuit.
-When using the Power Fuses for backup usage with other protective equipment, set the operating times of the protective equipment below the
minimum breaking current to be faster than those of the Power Fuses.

For transformer protection


Circuit Transformer Circuit Transformer Circuit Transformer Circuit Transformer
Phase voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses
(kV) (kVA) (kV) (kVA) (kV) (kVA) (kV) (kVA)

4~8 LFL-3G-5B 8~16 LFL-6G-5B 10~22 LFL-12G-5B 20~43 LFL-20G-5B


6~13 LFL-3G-10B 13~25 LFL-6G-10B 22~45 LFL-12G-10B 43~90 LFL-20G-10B
15~31 LFL-3G-20B 30~62 LFL-6G-20B 45~103 LFL-12G-20B 99~206 LFL-20G-20B
21~42 LFL-3G-30B 40~84 LFL-6G-30B 75~155 LFL-12G-30B 149~310 LFL-20G-30B
40~82 LFL-3G-40B 80~165 LFL-6G-40B 133~279 LFL-12G-40B 267~557 LFL-20G-40B
ф
1ф 3.3 49~102 LFL-3G-50B 6.6 98~204 LFL-6G-50B 11 173~359 LFL-12G-50B 22.9 345~719 LFL-20G-50B
66~137 LFL-3G-60B 132~275 LFL-6G-60B 215~448 LFL-12G-60B 430~897 LFL-20G-60B
68~165 LFL-3G-75B 134~330 LFL-6G-75B 290~572 LFL-12G-75B 580~1145 LFL-20G-75B
128~220 LFL-3G-100B 256~440 LFL-6G-100B 462~763 LFL-12G-100B 923~1527 LFL-20G-100B
151~275 LFL-3G-125B 302~550 LFL-6G-125B 682~954 LFL-12G-125B 1364~1908 LFL-20G-125B
211~352 LFL-3G-160B 425~704 LFL-6G-160B 950~1221 LFL-12G-160B 2125~2443 LFL-20G-160B
265~4402 LFL-3G-200B 437~880 LFL-6G-200B 1300~1525 LFL-12G-200B 2650~3050 LFL-20G-200B
6.7~14 LFL-3G-5B 13~28 LFL-6G-5B 18~37 LFL-12G-5B 36~75 LFL-20G-5B
11~22 LFL-3G-10B 21~44 LFL-6G-10B 37~78 LFL-12G-10B 75~157 LFL-20G-10B
25~53 LFL-3G-20B 51~107 LFL-6G-20B 70~179 LFL-12G-20B 172~358 LFL-20G-20B
35~73 LFL-3G-30B 70~145 LFL-6G-30B 129~269 LFL-12G-30B 258~538 LFL-20G-30B
69~143 LFL-3G-40B 137~286 LFL-6G-40B 232~482 LFL-12G-40B 464~965 LFL-20G-40B
85~77 LFL-3G-50B 170~354 LFL-6G-50B 299~623 LFL-12G-50B 598~1246 LFL-20G-50B
ф
3ф 3.3 6.6 11 22.9
114~238 LFL-3G-60B 229~476 LFL-6G-60B 372~777 LFL-12G-60B 745~1554 LFL-20G-60B
117~285 LFL-3G-75B 233~571 LFL-6G-75B 500~991 LFL-12G-75B 1000~1983 LFL-20G-75B
222~381 LFL-3G-100B 443~762 LFL-6G-100B 800~1322 LFL-12G-100B 1600~2645 LFL-20G-100B
261~476 LFL-3G-125B 522~952 LFL-6G-125B 1181~1652 LFL-12G-125B 2362~3304 LFL-20G-125B
365~610 LFL-3G-160B 735~1220 LFL-6G-160B 1840~2116 LFL-12G-160B 3680~4232 LFL-20G-160B
459~762 LFL-3G-200B 755~1520 LFL-6G-200B 2296~2643 LFL-12G-200B 4593~5287 LFL-20G-200B

When ordering 15.5, 36kV Power Fuse, Refer to page 9.10. For further information contact the manufacturer.
Selecting �The inrush current of a transformer is selected assuming that the current is 10 time that of the full-load transformer current in 0.1sec.
conditions �The rated current of the Power Fuses is selected to continuously flow at 1.5time of the transformer rated current.
�Power Fuses for proteting against short-circuit in the secondary part of a transformer are selected assuming that the current is 25times that of
the transformer rated current in 2seconds.

5
For condenser protection
Circuit Transformer Circuit Condenser Circuit Condenser Circuit Condenser
Phase voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses voltage capacity Applied fuses
(kV) (kVA) (kV) (kVA) (kV) (kVA) (kV) (kVA)

~9.8 LFL-3G-5B ~19 LFL-6G-5B ~22 LFL-12G-5B ~46 LFL-20G-5B


9.8~12 LFL-3G-10B 19~24 LFL-6G-10B 22~39 LFL-12G-10B 46~83 LFL-20G-10B
12~31 LFL-3G-20B 24~61 LFL-6G-20B 39~~97 LFL-12G-20B 83~203 LFL-20G-20B
31~46 LFL-3G-30B 61~92 LFL-6G-30B 97~152 LFL-12G-30B 203~317 LFL-20G-30B
46~64 LFL-3G-40B 92~128 LFL-6G-40B 152~204 LFL-12G-40B 317~425 LFL-20G-40B

ф
3ф 3.3 64~81 LFL-3G-50B 6.6 128~163 LFL-6G-50B 11 204~270 LFL-12G-50B 22.9 425~564 LFL-20G-50B
81~105 LFL-3G-60B 163~210 LFL-6G-60B 270~341 LFL-12G-60B 564~710 LFL-20G-60B
105~150 LFL-3G-75B 210~300 LFL-6G-75B 341~490 LFL-12G-75B 710~1021 LFL-20G-75B
150~222 LFL-3G-100B 300~445 LFL-6G-100B 490~795 LFL-12G-100B 1021~1655 LFL-20G-100B
222~275 LFL-3G-125B 445~550 LFL-6G-125B 795~1138 LFL-12G-125B 1655~2370 LFL-20G-125B
275~370 LFL-3G-160B 550~742 LFL-6G-160B 1138~1522 LFL-12G-160B 2370~3170 LFL-20G-160B
370~500 LFL-3G-200B 742~1000 LFL-6G-200B 1522~1921 LFL-12G-200B 3170~4000 LFL-20G-200B

�The inrush current of a condenser is selected to withstand 71time of the condenser rated current in 0.002sec.
Selecting �The rated current of the Power Fuses is selected to continuously flow at 1.43 times of the condenser rated current.
conditions

For motor protection For cable protection


Circuit Circuit Cable Rated(A)
Phase voltage Motor output Applied fuses voltage Motor output Applied fuses diameter current of PF
(kV) (kVA) (kV) (kVA) (mm2) (A)

6.5~10.7 LFL-3G-5B 13~22 LFL-6G-5B


0.8 40
10.7~28 LFL-3G-10B 22~36 LFL-6G-10B
28~57 LFL-3G-20B 36~86 LFL-6G-20B 1.6 50
50~85 LFL-3G-30B 86~117 LFL-6G-30B
85~115 LFL-3G-40B 117~230 LFL-6G-40B 2 75

ф
3ф 3.3 115~142 LFL-3G-50B 6.6 230~284 LFL-6G-50B
3.5 100
138~191 LFL-3G-60B 276~382 LFL-6G-60B
181~252 LFL-3G-75B 362~503 LFL-6G-75B 5.5 150
235~369 LFL-3G-100B 469~739 LFL-6G-100B
293~435 LFL-3G-125B 586~870 LFL-6G-125B 8 200
343~572 LFL-3G-160B 751~1223 LFL-6G-160B
22 200
375~630 LFL-3G-200B 1154~1760 LFL-6G-200B

�The starting current of a motor is selected to withstand 5 times of �Under the short-circuit condition, the power fuse
Selecting the full-loads current in 10sec. breaks the circuit in high speed. Therefore, with
conditions relatively high rated current, the Power Fuse
protects small size cables.
�Selected to protect from above 10 times of the
short-circuit current.

6
LG HRC Power Fuses
Characteristics curves

3.6/7.2kV Cut-off characteristics 3.6/7.2kV Pre-arcing time-


current characteristics
1000 1000
800 800
600 600 5A 125A
400 400 10A 100A

200 200 20A 75A

100 100 30A 63A


80 80
60 60 40A
Cut-off current (peak value:kA) →

40 40
125A 50A
20 100A 20

Operating time (sec) →


75A
10 63A 10
8 8
6 50A 6
4 40A 4
30A
2 20A 2

10A
1 1
0.8 5A 0.8
0.6 0.6
0.4 0.4

0.2 0.2

0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04

0.02 0.02

0.01 0.01
2

10

20

40
60
80
0.02

0.04
0.06
0.08

800
200

600
0.1

100
0.2

1000
100

400
0.4

20

40

2000
0.6
0.8

10

4000
1

8
4
6

Prospective breaking current(rms : kA) → Prospective rated current(rms : A) →

3.6kV Cut-off characteristics 3.6kV Pre-arcing time-


current characteristics

1000 1000
800 800
600 600
200A
400 400
160A
200 200

100 100
80 80
60 60
Cut-off current (peak value:kA) →

40 40
200A
Operating time (sec) →

20 20
160A
10 10
8 8
6 6
4 4

2 2

1 1
0.8 0.8
0.6 0.6
0.4 0.4

0.2 0.2

0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04

0.02 0.02

0.01 0.01
0.02

0.04
0.06
0.08
0.1

2
0.2

10

20

40
60
80
100

800
0.4

200

600
20

40
0.6
0.8

100
4

8
2

10

1000
1

400
4
6

2000

4000

Prospective breaking current(rms : kA) → Prospective rated current(rms : A) →

7
7.2kV Cut-off characteristics 7.2kV Pre-arcing time-
current characteristics
1000 1000
800 800
600 600 200A
400 400
160A
200 200

100 100
80 80
60 60
Cut-off current (peak value:kA) →

40 40
200A
20 160A 20

Operating time (sec) →


10 10
8 8
6 6
4 4

2 2

1 1
0.8 0.8
0.6 0.6
0.4 0.4

0.2 0.2

0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04

0.02 0.02

0.01 0.01
1

2
0.02

0.04
0.06
0.08

0.2

0.4

10

40
0.1

100
20
0.6
0.8

4
6
8

10

20

40
60
80
6

800
200

600
4

100

1000
400

2000

4000
6000
8000
10000
Prospective breaking current(rms : kA) → Prospective rated current(rms : A) →

15.5kV Cut-off characteristics 15.5kV Pre-arcing time-


current characteristics

1000
800
600
400
30A 100A
200 75A
20A 63A
100 50A
80 10A
60 40A
Cut-off current (peak value:kA) →

40 40 5A

20
Operating time (sec) →

100A 20
75A
10 63A 10
8 50A 8
6 40A 6
30A
4 20A 4
10A
5A
2 2

1
1
0.8
0.8
0.6 0.6
0.4 0.4

0.2 0.2

0.1
0.08 0.1
0.06 0.08
0.06
0.04
0.04

0.02
0.02
0.01
0.01
0.02

0.04
0.06

0.1

0.2

0.4
0.6
0.8

10

20

40
1

4
6
8

1000

2000

4000
6000
8000
100

200

400
600
800
10

20

40
60
80
2

4
6
8

Prospective breaking current(rms : kA) → Prospective rated current(rms : A) →

8
LG HRC Power Fuses
Characteristics curves

24kV Cut-off characteristics 24kV Pre-arcing time-


current characteristics
1000 1000
800 800
600 5A 200A
600
400 400 10A 160A

200 200 20A 125A

100 30A 100A


100
80 200A 80
60 60 40A 75A
160A
Cut-off current (peak value:kA) →

40 40
125A 50A 63A
100A 20
20

Operating time (sec) →


75A
10 10
63A 8
8
6 50A 6

4 40A 4

30A
2 2
20A
1 10A 1
0.8 0.8
5A 0.6
0.6
0.4 0.4

0.2 0.2

0.1 0.1
0.08 0.08
0.06 0.06

0.04 0.04

0.02 0.02

0.01 0.01
20

40
60
80

400

800
200

600

4000
100

2000
4

6000
8000
2

1000

10000
10
6
0.1

0.2

2
0.02

0.04
0.06
0.08

0.4
0.6
0.8

6
8
10

100
40
4

20

Prospective breaking current(rms : kA) → Prospective rated current(rms : A) →

36kV Cut-off characteristics 36kV Pre-arcing time-


current characteristics
1000
800
600
400

63A
200
50A
40A
100
80 30A
60
20A
Cut-off current (peak value:kA) →

40 40
10A
5A
Operating time (sec) →

20 20

10 63A 10
8 50A 8
6 6
40A
4 30A 4
20A
2 10A 2
5A
1 1
0.8 0.8
0.6 0.6
0.4 0.4

0.2 0.2

0.1 0.1
0.08 0.08
0.06 0.06
0.04 0.04

0.02 0.02

0.01 0.01
0.02

0.04
0.06
0.08
0.1

0.2

0.4
0.6
0.8

10

20
25
1

4
6
8

1000

2000

4000
6000
8000
100

200

400
600
800
10

20

40
60
80
2

4
6
8

Prospective breaking current(rms : kA) → Prospective rated current(rms : A) →

9
Striker operating characterstics
Operating weight (kgf) →

Operating distance(mm) →

Operating characteristics of the Power Fuses


The characteristics of the Power Fuses are native and fixed. Therefore it can not be regulated like a circuit breaker or over-
load relay. When ordering, please select the Power Fuses with proper current and operating characteristics by considering its
usage and circuit condition.

Breaking a small current.


Power Fuses are not adequate to protect small current. So, the manufacturer specifies and guarantees the minimum breaking
current by regulation.
1) Select the rated current of the Power Fuse, which does not operate below the minimum breaking current.
2) Protect the current below the minimum value by use of other protective equipment.

10
LG HRC Power Fuses
Fuse holder dimensions

Indoor use Power Fuse holder


LFH-6G-D1HB Type
C (Peak height in open condition)

250 Fuse size(A) B C


B ф12.5(Hold) 70 ф 55 242.3 376
200.5
ф 77 253.3 380

Earth hole
Mounting hold
15
176
421

323

55
35
Below1

6 Fuse checker
35
14

123.7 76.2
155.2

Indoor use Power Fuse holder


LFH-6G-D2HB/LFH-12G-D1HB/LFH-15G-D60B Type
456.5 (Peak height in open condition)

253.3
250
ф12.5(Hold) 70
Fuse size(A) B C D Applied Holder
200.5
ф 55 294.6 492.9 156 LFH-12G-D1HB
ф 77 285.6 488.8 156 LFH-15G-D60B
Mounting hole

Earth hole Fuse size(A) B C D Applied Holder


15
ф 77 253.3 456.5 123.7 LFH-6G-D2HB
180
521
423

Below1

6 Fuse checker 35
14

123.7 76.2
155.5

Indoor use Power Fuse holder


LFH-12G-D2HB/LFH-15G-D1HB/LFH20-D2HB LFH-30G-D60B Type
C (Peak height in open condition)
B
370 ф12.5(Hold)
320.5

Mounting hold
Fuse size(A) B C D E Applied Holder
Earth hole 15 ф 55 362.3 687.5 243.7 671 LFH-12G-D2HB
ф 77 373.3 691.6 243.7 671 LFH-15G-D1HB
300
671
616

296
ф 87 378.3 695 243.7 671 LFH-20G-D2HB

Fuse size(A) B C D E Applied Holder


ф 55 444.6 769.8 326 766
6 Fuse checker
LFH-30G-D60B
35 ф 77 455.6 773.9 326 766
14

243.7 100
184

11
Power Fuse holder

D Panel Conductor Panel


C
B
A

E F E F

Rated Rated Circuit Insulation Dimensions(mm)


PH Holder type voltage current voltage level Applied fuse
(kV) (A) (kV) (BIL, kV) A B C D E F

3.3 45 421 250 376 477 97 130 LFL-3G-5B, 10B, 20B, 30B, 40B, 50B

3.3 45 421 254 380 477 97 130 LFL-3G-60B, 75B, 100B


LFH-6G-D1HB 7.2 100
6.6 60 421 250 376 503 123 158 LFL-6G-5B, 10B, 20B, 30B, 40B, 50B

6.6 60 421 254 380 503 123 158 LFL-6G-60B, 75B, 100B

3.3 45 521 254 457 564 97 130 LFL-3G-125B, 160B, 200B


LFH-6G-D2HB 7.2 200
6.6 60 521 254 457 590 123 158 LFL-6G-125B, 160B, 200B

22.9 125 671 363 688 734 - 260 LFL-20G-5B, 10B, 20B

LFH-20G-D2HB 24 200 22.9 125 671 374 692 957 - 260 LFL-20G-30B, 40B, 50B, 60B

22.9 125 671 379 695 957 - 260 LFL-20G-75C, 100C 125B, 160B, 200B

12
LG HRC Power Fuses
Ordering information

Types of P/F Link & P/F Holder

P/F Link

LFH

Model name General use Revision No.

3 3.6kV Rated 5 10 20 30 40 50 60 75 100 125 160 200


6 7.2kV current 5A 10A 20A 30A 40A 50A 63A 75A 100A 125A 160A 200A
Rated 12 12kV
voltage 15 15.5kV
20 24kV
30 36kV

P/F Holder

LFH

Model name General use Indoor use Revision No.

6 3.6/7.2kV 60 63A Fuse 0 Without


Rated
12 12kV 1H 100A checker 1 with
Rated current
15 15.5kV 2H 200A
voltage
20 24kV
30 36kV

13
Basic conditions for selecting the Power Fuse

Ratings

Operating Voltage (____V) Frequency (____Hz) Ampere (____A) Breaking capacity (____kV)

Schematic diagram of the installation

�Initial symmetrical short-circuit current of the primary network


�Rated power/Impedance/Reactance/Voltage generators/Transformers/Reactors
�Rated capacity of motors (over 1MW)
�Rated capacity of capacitor bank and the inductance connected in series with them.

Applications

�Transformers
Set to allow continuous flow at 1.5 times of the rated current of a transformer and to break at 25 times of the rated current of a
transformer within 2 seconds when a short circuit condition occurs in the secondary part.

�Condenser
- Inrush current : set to allow flows at 71 times of the rated current of a condenser for 0.002 seconds.
- Rated current : set to allow continuous flows at 1.43 times of the rated current of a condenser.

�Motor

�Cable

�Upstream protection by circuit breakers or contactors

Operation & accessories

Installed site � Indoor � Outdoor

Fuse holder(base) � Not needed � Needed

Fuse checker � Not needed � needed

Example of ordering

Rated voltage : 24kV, Hz : 60Hz, Rated current : 200A, Breaking capacity : 40kA

Application �
� Upstream protection with circuit breaker

Installed site �
� Indoor � Out door

Fuse holder � Not needed �


� Needed

Fuse checker � Not needed �


� Needed
→ LFH-20G-200B/LFH-20G-D 2H B 1

※ When ordering, please include this sheet

14
2003-08

Safety Instructions
For your safety, please read user’s manual thoroughly before operating.
Contact the nearest authorized service facility for examination, repair,
or adjustment.
Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
Any maintenance and inspection shall be performed by the personnel having
expertise concerned.

srjo@hn.vnn.vn

LG Industrial Trading (Shanghai) Co., Ltd China


Address: Room1705-1707, 17th Floor Xinda
Commerical Building No 318, Xian Xia Road Shanahai
Tel: 86-21-6252-4291 Fax: 86-21-6278-4372
e-mail: hgseo@lgis.com

Room 303, 3F

LG Industrial Systems Shanghai Office China


Address: Room1705-1707, 17th Floor Xinda Commerical Building
No 318, Xian Xia Road Shanahai, China
Tel: 86-21-6278-4370 Fax: 86-21-6278-4301
sdhwang@lgis.com

LG Industrial Systems Guangzhou Office China


Address: Room 303, 3F, Zheng Sheng Building, No 5-6, Tian He
Bei Road, Guangzhou, China
Tel: 86-20-8755-3410 Fax: 86-20-8755-3408

younsupl@lgisusa.com
Specifications in this catalog are subject to change without notice due to
continuous product development and improvement.

HRC(A) 2001 / Aug. 2003 Printed in Korea STAFF