STING – Compact Air Handling Unit

Technical data
STING
STING CATALOGUE
CATALOGUE

Contents

Sheet
Contents ......................................................................... 2
Unit Description............................................................... 3
Delivery Configuration............................................. 4
Quick Selection........................................................... 5
Design ......................................................................... 6
Technical Details ....................................................... 8
Size 10..................................................................... 8
20..................................................................... 9
20 Top........................................................... 11
30................................................................... 12
30 Top........................................................... 14
35................................................................... 15
35 Top........................................................... 17
40................................................................... 18
50................................................................... 19
65................................................................... 20
80................................................................... 21
85................................................................... 22
Cooler ....................................................................... 23
Sizing ....................................................................... 28
Controls ....................................................................... 29
Accessories...................................................................... 37
Space required................................................................ 46
Ordering Codes.............................................................. 47

Fläkt Woods 8210 GB 2009.02 2 Specifications are subject to alteration without notice
STING
STING CATALOGUE
CATALOGUE

Unit Description

The STING is a compact air handling unit produced prepared for a wide range of external functions. The
in 9 sizes. The STING is the flexible unit that is easy cables of the temperature sensor and actuators have
to install and commission. easy-to-connect quick connectors.
The air handling unit is supplied with direct-driven,
supply air and extract air fans, supply air and ex-
tract air filters and rotary heat exchanger. Typical applications
STING is a compact one-piece unit that is well-suit-
The STING has a wide range of air-handling acces- ed for installation in public buildings such as day
sories for installation in the ducting; these include nurseries, schools, offices, shops etc. The STING is
dampers, air heaters, air coolers, sound attenuators, designed for indoor or outdoor installation.
etc.
The control system is integrated into the unit and is
Flow range
Flödesområde

85 STING 85

80 80

65 65

50 50
Storlek

40 40
Size

35 35

30 30
20 20

10 10
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 8 8,5
3
m /s

A darker area indicates flow at SFPv >2,5 at 250 Pa external pressure.

Fläkt Woods 8210 GB 2009.02 3 Specifications are subject to alteration without notice
STING CATALOGUE

Unit Description

Delivery configuration, sizes 10-20 Delivery configuration, sizes 30-85


The units are always supplied with an indivisible cas- The units can be supplied with customized fan ar-
ing as standard. The units are supplied with a bottom rangement. The standard configuration is a top or
right-hand supply air fan and can be changed with bottom right-hand supply air fan. The unit can be
ease to a top left-hand supply air fan. This is done by changed with ease to a configuration with a top or
means of a simple switching operation in the control bottom left-hand supply air fan. This is done by
system. means of a simple switching operation in the control
For available configurations, see table below. system.
The units can be installed horizontally or vertically. A The unit can be ordered with an outlet and/or inlet
stand is available as an accessory for installation in a for upward air discharge. To be specified when order-
vertical configuration. ing.
The size 10 unit has dimensions that makes it possible The size 30-85 units can only be installed horizontally.
to transport them through a 900 mm wide door with- STING Top size20-35 is available with all connections
out having to dismantle them. on top.

Size

10 • •

20 • • • • •

30 • • • •

35 • • • •

40 • • •

50 • • •

65 • • •

80 • • •

85 • • •

= Exhaust air = Outdoor air = Extract air = Supply air = Delivery version

Split casing sections for transport within


the site
For simple transport through narrow doorways within
the building site, the size 20 – 85 units can be ordered in
a divisible version. The size 30 – 50 units are always di-
visible. The size 20, 65 – 85 units are also available in the
one-piece version.
The unit sections are bolted together and most of the
cables are fitted with a quick connector.

Fläkt Woods 8210 GB 2009.02 4 Specifications are subject to alteration without notice
STING CATALOGUE

Technical Details, Quick Selection

Size Width Height Length Max. length of Weight Duct Duct connection
(mm) (mm) (mm) block (mm) (kg) connection /STING Top

10 836 875 1270 – 238 ø 315 –


**)
20 1036 1075 1600 550 352 ø 400 ø 400

30 1186 1225 1900 700 424 800 x 400 ø 500

35 1186 1225 1900 700 442 800 x 400 ø 500

40 1436 1475 2200 750 646 1000 x 500 –

50 1736 1775 2400 850 858 1200 x 600 –

65 2004 2074 2712 1104 1441 1600 x 800 –

80 2604 2674 2912 (3112) *) 1204 (1404) *) 2230 2000 x 1000 –

85 2604 2674 3112 (3212) *) 1304 (1404) *) 2278 2000 x 1000 –

*) the dimensions within brackets are for an inlet in the top panel. **) split casing version

Dimension sketch, Size 10-20 Dimension sketch, Size 30-85

Duct
connec- Duct
tion connec­
tion
Height
Height
Duct
connec­
tion

Duct Width Length


connec-
tion
Width
STING 10 - 85
Length

Pressure flow chart, for STING Sizes 10-85


1400
1200
1000

500
Pa
extern , Pa
∆ p External.

200

100

Size 10 20 30 35 40 50 65 80 85
50
0.2 0.4 0.6 0.8 1.0 2 3 4 5 6 7 8 9 10 m 3/s
qv
2000 3000 4000 5000 10000 20000 30000 m 3/h

Fläkt Woods 8210 GB 2009.02 5 Specifications are subject to alteration without notice
STING CATALOGUE

Unit Description – Design

Unit casing Components inside the casing


The unit casing is made of double-skin galvanized
sheet steel with an intervening layer of insulation
consisting of 50 mm thick mineral wool; sturdy longi-
Filter
Supply and extract air
tudinal edge sections.
Service doors with adjustable hinges, handle and filters made of glass
lock for access to fans and filters. fibre. Filter class F7
Unit size 10-20 is supplied with stable base feet. (EU7).
Unit sizes 30-85 are supplied with base frame. An easy-to-operate
clamping device is
• Environmental Class: The casing conforms used to press the filter
to Class C3 against sealing strips inside
• Tightness to CEN Class L3 the
• Tensile strength to CEN Class D2 casing.
• Thermal insulation to CEN Class T3 The complete filter wall can be pulled
• Condensation insulation to CEN Class TB3 out to ease cleaning and changing of the filters.
STING Top has so called extensible ultra compact
filter.

Rotary heat exchanger


The rotary heat exchanger
is used for recycling and
transferring of heat (at
summertime sometimes
Size 10-20 chilled air) and eventual
moist out of exhaust air
into the input air. The rota-
ry heat exchanger is deliv-
ered as an non-hygroscopic
(only heat transferring)
and as hygroscopic ( heat and
moisture transferring). It is made
Size 30-85 out of aluminium, equipped with a
purging sector, electronic speed control
and Rotation monitor. Defrosting is not
necessary with normal comfort ventilation. If the
relative humidity of the exhaustair is higher than
30% and the outside temperature is less than -15
celsius there might be a risk of FREEZE UP. Check
with Fläkt Woods if there is a need for defrosting.

Adjustment panels
Flow adjustment panels are supplied with the unit
size 10-50 to create the correct pressure balance
across the rotor so that purging air flow will pass in
the right direc-
tion. The panels
should be placed
upstream of the
extract air filter,
if their use is nec-
essary.
(Not STING Top).

Fläkt Woods 8210 GB 2009.02 6 Specifications are subject to alteration without notice
STING CATALOGUE

Unit Description – Design

Fan
The STING fans have been selected with focus on
their best all-round economy. The size 10 units have
double-inlet centrifugal fans with forward-curved
blades. This allows for a very short unit; and this is
advantageous where space for installation is limited.
The size 20-85 units have newly developed efficient
Centriflow Plus plug fans that offer up to 77% efficien-
cy. The fans are driven by efficient motors that make
the air handling units extremely energy-saving.
The speed of the fans is variably controlled by means
of integral or EC-motors.
Size 20-85

Connections

Size 10 Size 20-35

The duct mountings fitted on the circular with a rub-


ber ring and the rectangular with PG joint.
The size 20-85 units can be ordered with fan and/or
filter inlet for upward discharge/suction, respectively.
To be specified when ordering.
For the size 20-85 units, it is possible to connect exter-
nal functional sections such as an air heater or cooler,
silencers, etc., directly to the air handling unit.

Environmental Declaration
Materials that are part of the unit

Material Quantity Reusable Recyclable Energy recyclable Refuse material
material material material

Metals 91 % x

Polymer materials 2.5 % x x

Mineral wool insulation 6 % x

Other 0.5 % x

Fläkt Woods 8210 GB 2009.02 7 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 10

STING-1
Fan performance chart Centrifugal fan
The chart is intended for use as a general survey chart. 1400
58 Hz
Precise data can be obtained in our air handling unit 55 Hz 3310 r/min
3138
selection program, ACON. The diagram shows avail-
50 Hz
able external pressure drops for duct systems and 1000 2861
external functional sections. It can be used on both the
supply air and the extract air sides and is valid for the 45 Hz
2559
dimensioning pressure drop of the filter.
The indicated sound power level in dB(A) refers to 40 Hz
2279
noise in the ducting on the fans exhaust side.
500
The SFPv figures have been calculated according to 35 Hz
2001
the
method described in Swedish Association of Air Han-
SFPv
dling Industries Publication 1995:1 (Revised 2000
extern, PaPa 3
edition), i.e. the pressure drop of clean filters and the
∆ p External,
200 2.5
balancing pressure are included. The figures require
that even the air flow and external pressure drop is 2
100
the same on both the supply air and the extract air LwA,dB 75 80 85
sides. 50
0.1 0.2 0.3 0.4 0.5 0.6 0.7 m3/s
qv
1000 1500 2000 2500m3/h

Dimensions,

Weights and Electrical Specifications
Electrical specifications Unit weight Filter
Size 10
Integral motor Electrical connections Total (kg) Type (mm) Filter length (mm)
Direct-driven 3 x 400 VAC,
centrifugal 50/60 Hz
IP 55 238 1 pc 592 x 287 300
fan with forward- max 16 A (25 A) *,
curved blades max 4 mm2

*) The unit can also be wired to a single-phase 230 V supply.

06-18-2004 / STING17D.FIL

Unit viewed from the rear.

Fläkt Woods 8210 GB 2009.02 8 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 20 & 20 Top

Fan performance chart


The chart is intended for use as a general survey chart. The indicated sound power level in dB(A) refers to
Precise data can be obtained in our air handling unit noise in the ducting on the fans exhaust side.
selection program, ACON. The SFPv figures have been calculated according to
The chart shows for plenum fans with integral motor, the method described in Swedish Association of Air
available external pressure drops for duct systems and Handling Industries Publication 1995:1 (Revised 2000
external functional sections. For plenum fans with EC edition), i.e. the pressure drop of clean filters and the
motor the diagram shows available external pressure balancing pressure have been included in the calcula-
drop for “nude” fan. tion. The figures require that even the air flow and
They can be used on both the supply air and the external pressure drop is the same on both the supply
extract air sides and is used when dimensioning air and the extract air sides.
pressure drop of the filter.

Plenum fan with integral motor, 20 Plenum fan with EC-motor, 20 & 20 Top
Charts below shows available external pressure drops
STING-20 Chart shows available external pressure drop for
for duct systems and external functional sections. “nude” fan. When the fan is assembled in a air hand-
STING storlek 20
GPEB-3-031
ling unit a ”built in pressure loss” will arise.
External, Pa

Plenum fan with integral motor, 20 Top

03-31-2005 / STING20D.FIL
External, Pa

Reduced air flow operation is alowable within


the coloured area.

Fläkt Woods 8210 GB 2009.02 9 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 20 & 20 Top

Dimensions, Weights and Electrical specifications, size 20


300
518
Unit viewed from the rear.
35

40
Ø 400

1076
500

500
288

288
150

2)
550
2)
Ø 400 500
29 2)
3 550 160
0
74
3 2) Applicable to the split version
10
36

Electrical specifications Unit weight (divided into blocks) Unit weight (hole) Filter
Size 20 EC-motor Electrical Fan/filter Filter length
Integral motor1) connection Total (kg) section (kg) Rotordel (kg) Total (kg) Type (mm) (mm)
3 x 400 VAC,

Direct-driven 50/60 Hz
Plenum fan IP55 max 16A 390 125 105 352 1 st 392 x 792 360
(25 A)1),
max 4 mm2
1) The unit can also be wired to a single-phase 230 V supply.Applies only for integral motors.

Dimensions, Weights and Electrical specifications, size 20 Top

280 ø 400
35

271
1076

494
150

Vy uppifrån
0
55

0
50
1 00
0 16
3 0
5 55

Electrical specifications Unit weight (divided into blocks) Unit weight (hole) Filter
Storlek 20
Top EC-motor Electrical Fan/filter Filter length
Integral motor1) connection Total (kg) section (kg) Rotordel (kg) Total (kg) Type (mm) (mm)
3 x 400 VAC,

Direct-driven 50/60 Hz
Plenum fan IP55 max 16 A 390 125 105 352 2 st 450 x 450 80
(25 A)1),
max 4 mm2
1) The unit can also be wired to a single-phase 230 V supply.Applies only for integral motors.

Fläkt Woods 8210 GB 2009.02 10 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 30 & 30 Top

Fan performance chart


The chart is intended for use as a general survey chart. The indicated sound power level in dB(A) refers to
Precise data can be obtained in our air handling unit noise in the ducting on the fans exhaust side.
selection program, ACON. The SFPv figures have been calculated according to
The chart shows for plenum fans with integral motor, the method described in Swedish Association of Air
available external pressure drops for duct systems and Handling Industries Publication 1995:1 (Revised 2000
external functional sections. For plenum fans with EC edition), i.e. the pressure drop of clean filters and the
motor the diagram shows available external pressure balancing pressure have been included in the calcula-
drop for “nude” fan. tion. The figures require that even the air flow and
They can be used on both the supply air and the external pressure drop is the same on both the supply
extract air sides and is used when dimensioning air and the extract air sides.
pressure drop of the filter.

Plenum fan with integral motor, 30 Plenum fan with EC-motor, 30 & 30 Top
Charts below shows available external pressure drops
STING-2 Chart shows available external pressure drop for
for duct systems and external functional sections. “nude” fan. When the fan is assembled in a air hand-
1100 ling unit a ”built in STING storlek
GPEB-3-035/1,7
pressure 30kWwill arise.
loss”
47 Hz
1000 2696 r/min
45 Hz
2594

40 Hz
2322

35 Hz
500 2040

SFPv
30 Hz 2.5
1755

2
extern, PaPa

200 1.5
∆p External,

86

100
LwA,dB 78 82

50
0.2 0.4 0.6 0.8 1.0 1.2 1.4 m3/s
qv
3000 4000 5000m3/h

STING-30 TOP
Plenum fan with integral motor, 20 Top
1100

1000 47 Hz
2696 r/min
45 Hz
2594

40 Hz
2322

35 Hz 86
500 2040

SFPv
30 Hz 2.5
06-18-2004 / STING27D.FIL 1755

2
82
Pa
extern , Pa

200 1.5
∆ p External,

L wA dB 78

100

50
Reduced air flow operation is alowable within
0.2 0.4 0.6 0.8 1.0 1.2 1.4 m3/s the coloured area.
qv
2000 3000 4000 5000 m3/h

Fläkt Woods 8210 GB 2009.02 11 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 30 & 30 Top

Dimensions, Weights and Electrical specifications, size 30


35

20
400
720

1225
400
105

150

1
9
5

0
70
8
0
0 0
50
1 00
1 19
8 0
6 70

Electrical specifications Unit weight Filter


Storlek 30 EC-motor Electrical Fan-/filter- Rotor Filter
Integral motor connections Total (kg) section (kg) section (kg) Type (mm) length (mm)
3 x 400 VAC,
Direct-driven
IP55 50/60 Hz 424 137 116 1 st 892 x 490 547 (380)1)
Plenum fan max 16 A,
max 4 mm2
1) If the unit has a top inlet, the filter is shorter than standard.

Dimensions, Weights and Electrical specifications, size 30 Top


35

340 ø 500
307
1225

572
150

0
70
View from above
0
50
1 00
1 19
8 0
6 70

Electrical specifications Unit weight Filter


Size 30
Top EC-motor Electrical Fan-/filter- Rotor Filter
Integral motor connections Total (kg) section (kg) section (kg) Type (mm) length (mm)
3 x 400 VAC,
Direct-driven
IP55 50/60 Hz 424 137 116 2 st 520 x 520 80
Plenum fan max 16 A,
max 4 mm2

Fläkt Woods 8210 GB 2009.02 12 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 35 & 35 Top

Fan performance chart


The chart is intended for use as a general survey chart. The indicated sound power level in dB(A) refers to
Precise data can be obtained in our air handling unit noise in the ducting on the fans exhaust side.
selection program, ACON. The SFPv figures have been calculated according to
The chart shows for plenum fans with integral motor, the method described in Swedish Association of Air
available external pressure drops for duct systems and Handling Industries Publication 1995:1 (Revised 2000
external functional sections. For plenum fans with EC edition), i.e. the pressure drop of clean filters and the
motor the diagram shows available external pressure balancing pressure have been included in the calcula-
drop for “nude” fan. tion. The figures require that even the air flow and
They can be used on both the supply air and the external pressure drop is the same on both the supply
extract air sides and is used when dimensioning air and the extract air sides.
pressure drop of the filter.

Plenum fan with integral motor, 35 Plenum fan with EC-motor, 35 & 35 Top
Charts below shows available external pressure drops Chart shows available external pressure drop for
STING-3
for duct systems and external functional sections. “nude” fan. When the fan is assembled in a air hand-
1100
ling unit a ”built in pressure
STING loss”
storlek
GPEB-3-040 35 will arise.
85 Hz
1000 2451 r/min

70 Hz
2061

60 Hz
500 1780

SFPv

50 Hz 2.5
1490

2
, PaPa

200 40 Hz
External,

1192
∆p extern

1.5

100

LwA,dB 80 84 88
50
0.2 1 1.8 m3/s
qv
3000 5000 m3/h

STING-35 TOP
Plenum fan with integral motor, 35 Top
1100
85 Hz
1000
2451 r/min

70 Hz
2061

500 60 Hz
1780
SFPv

06-18-2004 / STING37D.FIL 2.5


50 Hz
1490
88
2
Pa
, Pa

200
External,

40 Hz 84
∆ p extern

1192 1.5

100
L wAdB 80
Reduced air flow operation is alowable within the
50
0.2 1 1.8 m3/s
coloured area.
qv
3000 5000 m3/h

Fläkt Woods 8210 GB 2009.02 13 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 35 & 35 Top

Dimensions, Weights and Electrical Specifications, size 35


35

20
400
720

1225
400
105

150

1
9
5

0
70
8
0
0 0
50
1 00
1 19
8 0
6 70

Electrical specifications Unit weight Filter


Size 35 EC-motor Electrical Fan-/filter- Rotor Filter
Integral motor connections Total (kg) section (kg) section (kg) Type (mm) length (mm)
3 x 400 VAC,
Direct-driven
IP55 50/60 Hz 442 146 116 1 st 892 x 490 547 (380)1)
Plenum fan max 20 A,
max 4 mm2
1) If the unit has a top inlet, the filter is shorter than standard.

Dimensions, Weights and Electrical Specifications, size 35 Top


340 ø 500
35

307
1225

572
150

View from above


0
70

0
50
1 00
1 19
8 0
6 70

Electrical specifications Unit weight Filter


Size 35
Top EC-motor Electrical Fan-/filter- Rotor Filter
Integral motor connections Total (kg) section (kg) section (kg) Type (mm) length (mm)
3 x 400 VAC,
Direct-driven
IP55 50/60 Hz 442 148 116 2 st 520 x 520 80
Plenum fan max 20 A,
max 4 mm2

Fläkt Woods 8210 GB 2009.02 14 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 40

STING-4
Fan performance chart Plenum fan with integral motor
The chart is intended for use as a general survey 1400
85 Hz
2435 r/min
chart. Precise data can be obtained in our air handling
unit selection program, ACON. The chart shows
available external pressure drops for duct systems 1000
70 Hz
and external functional sections. This diagram shows 2053
available external pressure drop for the duct system
and duct fitted components. It can be used on both 60 Hz
1776
the supply air and the extract air sides and is used
when dimensioning pressure drop of the filter. 500 SFPv
The indicated sound power level in dB(A) refers to 50 Hz
1488 2.5
92

noise in the ducting on the fans exhaust side.


The SFPv figures have been calculated according to 2
40 Hz
the
Pa
1190

, Pa
External,
method described in Swedish Association of Air Han- ∆p extern
200
1.5

dling Industries Publication 1995:1 (Revised 2000


edition), i.e. the pressure drop of clean filters and the 100
balancing pressure have been included in the calcula- LwA,dB 80 84 88

tion. The figures require that even the air flow and 50
0.4 1 2 2.4 m3/s
external pressure drop is the same on both the supply 2000
qv
4000 6000 8000 m3/h
air and the extract air sides.

Dimensions, Weights and Electrical Specifications



Electrical specifications Unit weight Filter
Size 40
Integral motor Electrical connections Total (kg) Fan/filter section (kg) Rotor section (kg) Type (mm) Filter length
(mm)

3 x 400 VAC,
Direct-driven
IP 55 50/60 Hz 646 195 221 2 pc 592 x 592 547
Plenum fan
max 25 A

06-18-2004 / STING47D.FIL
35

20
500
855

1475
500
120

150

2
2
0

0
75
1
0
0 0
0 70
1 0 0
4 22
3 0
6 75

Fläkt Woods 8210 GB 2009.02 15 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 50

STING-5
Fan performance chart Plenum fan with integral motor
The chart is intended for use as a general survey chart. 1100
60 Hz
Precise data can be obtained in our air handling unit 1000
1740 r/min

selection program, ACON. The chart shows available 55 Hz


1609
external pressure drops for duct systems and external
functional sections. This diagram shows available ex- 50 Hz
1471
ternal pressure drop for the duct system and duct fit-
45 Hz
ted components. It can be used on both the supply air 1323
and the extract air sides and is used when dimension- 500 SFPv
ing pressure drop of the filter. 40 Hz
1172 2.5

The indicated sound power level in dB(A) refers to


2
noise in the ducting on the fans exhaust side. 35 Hz
1022
The SFPv figures have been calculated according to
the 1.5

Pa
200

extern, Pa
method described in Swedish Association of Air Han- ∆p External,
dling Industries Publication 1995:1 (Revised 2000
edition), i.e. the pressure drop of clean filters and the 100

balancing pressure have been included in the calcula- LwA,dB 80 84 88

tion. The figures require that even the air flow and 50
0.5 1 1.5 2 3 3.5 m3/s
external pressure drop is the same on both the supply qv
6000 8000 10000 12000 m3/h
air and the extract air sides.

Dimensions, Weights and Electrical Specifications



Electrical specifications Unit weight Filter
Size 50
Integral motor Electrical connections Total (kg) Fan/filter section (kg) Rotor section (kg) Type (mm) Filter length (mm)

3 x 400 VAC,
Direct-driven 2 pc 592 x 592
IP 55 50/60 Hz 858 270 273 547
Plenum fan 1 pc 287 x 592
max 25 A

06-18-2004 / STING57D.FIL
35

20
600
1030

1775
600
145

150

2
7
0

0
85
1
2
0 0
0 70
1 0 0
7 24
3 0
6 85

Fläkt Woods 8210 GB 2009.02 16 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 65

STING-65
Fan performance chart Plenum fan with integral motor
The chart is intended for use as a general survey chart. 1400

Precise data can be obtained in our air handling unit 51 Hz


1200 1470 r/min
selection program, ACON. The chart shows available
external pressure drops for duct systems and external 1000
45 Hz
functional sections. This diagram shows available ex- 1305

ternal pressure drop for the duct system and duct fit-
40 Hz
ted components. It can be used on both the supply air 1160

and the extract air sides and is used when dimension-


35 Hz
ing pressure drop of the filter. 500 1015
SFPv
The indicated sound power level in dB(A) refers to 2.5
noise in the ducting on the fans exhaust side. 30 Hz
870
The SFPv figures have been calculated according to 2

the

extern, PaPa
method described in Swedish Association of Air Han-
∆p External,
200
1.5
dling Industries Publication 1995:1 (Revised 2000
edition), i.e. the pressure drop of clean filters and the 100
balancing pressure have been included in the calcula- LwA,dB 80 84 88 92
tion. The figures require that even the air flow and 50
1 1.5 2 3 4 5 6 m3/s
external pressure drop is the same on both the supply 6000
qv
10000 14000 18000 m3/h
air and the extract air sides.

Dimensions, Weights and Electrical Specifications


 
Electrical specification Unit weight [divided into blocks] Unit weight (hole) Filter
Size 65
Electrical Fan/filter section Rotor section
Integral motor connections Total (kg) [kg] [kg] Total (kg) Type (mm) Filter length (mm)

3 x 400 VAC,
Direct-driven 3 pc 592 x 592
IP 55 50/60 Hz 1441 506 429 1373 547
Plenum fan 3 pc 287 x 592
max 45 A

09-23-2005 / STING65D.FIL
800
1137

800
137

1104
16
00 504

1104 2712

Fläkt Woods 8210 GB 2009.02 17 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 80

STING-80
Fan performance chart Plenum fan with integral motor
The chart is intended for use as a general survey 1200
43 Hz
chart. Precise data can be obtained in our air handling 1235 r/min

unit selection program, ACON. The chart shows 1000 40 Hz


1162
available external pressure drops for duct systems
and external functional sections. This diagram shows 35 Hz
available external pressure drop for the duct system 1016

and duct fitted components. It can be used on both SFPv


the supply air and the extract air sides and is used 500
30 Hz
871
2.5
when dimensioning pressure drop of the filter.
The indicated sound power level in dB(A) refers to 2
25 Hz
noise in the ducting on the fans exhaust side. 726

The SFPv figures have been calculated according to 1.5


the
, PaPa
200

External,
method described in Swedish Association of Air Han- ∆p extern
dling Industries Publication 1995:1 (Revised 2000
edition), i.e. the pressure drop of clean filters and the 100

balancing pressure have been included in the calcula- LwA,dB 80 84 88


50
tion. The figures require that even the air flow and 1.5 2 3 4 5 6 7 7.5 m3/s
external pressure drop is the same on both the supply 8000
qv
12000 16000 20000 24000 m3/h
air and the extract air sides.

Dimensions, Weights and Electrical Specifications


 
Electrical specification Unit weight [divided into blocks] Unit weight (hole) Filter
Size 80
Electrical Fan/filter section Rotor section
connections
Integral motor Total (kg) [kg] [kg] Total (kg) Type (mm) Filter length
(mm)

3 x 400 VAC,
Direct-driven
IP 55 50/60 Hz 2230 735 760 2150 8 pc 592 x 592 547
Plenum fan
max 45 A

09-23-2005 / STING80D.FIL
1000

2674
1487

1000
187

20
2 1204 ) *)
4
(140
20
00 504
2) *)
1204 (311
26
04 2912

*) The dimensions within brackets apply to inlets in the top panel.

Fläkt Woods 8210 GB 2009.02 18 Specifications are subject to alteration without notice
STING CATALOGUE

Technical data, size 85

STING-85
Fan performance chart Plenum fan with integral motor
The chart is intended for use as a general survey 1600
48 Hz
chart. Precise data can be obtained in our air handling 1400
1398 r/min

unit selection program, ACON. The chart shows 45 Hz


1307
available external pressure drops for duct systems 1200

and external functional sections. This diagram shows 1000


40 Hz
1162
available external pressure drop for the duct system
and duct fitted components. It can be used on both 35 Hz
the supply air and the extract air sides and is used 1016

when dimensioning pressure drop of the filter.


30 Hz SFPv
The indicated sound power level in dB(A) refers to 500 871
2.5
noise in the ducting on the fans exhaust side.
The SFPv figures have been calculated according to 25 Hz
726 2

the
, PaPa
External,
method described in Swedish Association of Air Han- 1.5
∆p extern
200
dling Industries Publication 1995:1 (Revised 2000
edition), i.e. the pressure drop of clean filters and the 100
balancing pressure have been included in the calcula- LwA,dB 80 84 88 92

tion. The figures require that even the air flow and 50
1.5 2 3 4 5 6 7 8 9 m3/s
external pressure drop is the same on both the supply 8000
qv
12000 16000 20000 24000 28000 32000m3/h
air and the extract air sides.

Dimensions, Weights and Electrical Specifications


 
Electrical specifications Unit weight [divided into blocks] Unit weight (hole) Filter
Motor with
Size 85
frequency Electrical Fan/filter section Rotor section
Total (kg) Total (kg) Type (mm) Filter length
inverter connections [kg] [kg]
(mm)
Direct-driven IP 55 3 x 400 VAC, 2278 759 760 2198 8 pc 592 x 592 547
Plenum fan 50/60 Hz
max 63 A

09-23-2005 / STING85D.FIL
1000

2674
1487

1000
187

30
2 1304 ) *)
4
(140
20
00 504
)
2) *
26
04 1304 2 (3
21
311

*) The dimensions within brackets apply to inlets in the top panel.

Fläkt Woods 8210 GB 2009.02 19 Specifications are subject to alteration without notice
STING CATALOGUE

Cooling – ETKC Cooler

to handle about 50% of the total condenser rating of


the corresponding output variant. The water-cooled
condenser must be connected to the mains water
supply (cold water) and drain. The condenser is self-
regulating and provides cooling when the condensa-
tion temperature is higher than the preset set point.
No adjustments need be made.

Location
The cooling unit should be located so that the con-
denser is always nearest to and upstream of the ex-
haust air fan. See Figure.

Technical data
The cooling unit is controlled by an external 0–10 V
control signal. The cooling unit contains 2 or 3 com-
pressors, depending on the unit size, and these are
switched in three output stages. Detailed particulars
are given under each size.
Description
If the cooling unit is equipped with a water-cooled
The ETKC cooling unit is a complete unit section,
condenser, this is switched in as necessary. A me-
which is fully installed in the EC air handling unit.
chanical pressure-controlled water-saving valve,
The cooling unit is available in seven sizes for air
which senses the condensation pressure, opens to ad-
flows
mit cooling water to the water-cooled condenser
ranging from 0.6 to 8.0 m3/s. The cooling unit is cost
effective, environment friendly and easy to use. The
cooling unit is a reliable, high quality product which Project design
is simple to engineer and install, and requires a mod- In the project design work, it is normally assumed
est amount of service. that the exhaust air flow is higher than or equal to
The cooling unit has the same casing and frame as the supply air flow, in order to guarantee satisfac-
other unit sections, and has an evaporator and con- tory cooling of the condenser. The product selection
denser with copper tubing and aluminium fins. computer program is used for more accurate project
The cooling unit cools the supply air by means of design work.
type R407C refrigerant. The supply air is cooled by an The cooling unit is designed for outdoor air tempera-
air cooler (evaporator) in which the heat is absorbed tures between +20 °C – +32 °C and a min. supply air
by the refrigerant which then transfers the heat to the temperature of +12 °C. The lowest permissible air
condenser. The condenser is located in the exhaust flow is specified below each unit size.
air flow path. The heat from the supply air is thus The cooling unit is not suitable for use in conjunction
transferred to the exhaust air. The cooling unit can be with supply air temperature control.
equipped with a water-cooled condenser connected
upstream of the ordinary air-cooled condenser and in
series with it. The water-cooled condenser is cooled
by means of mains water.

The function of the water-cooled condenser is:


– to allow for heat recovery for heating the domestic
hot water, for instance
– to allow for operation with an exhaust air flow
which is lower than the supply air flow
– to safeguard the performance of the cooling unit
even at extremely high outdoor temperatures.

The water-cooled condenser is an option which is


integrated into the unit at the factory. It is equipped
with a water connection and water-saving valve.
The water cooled condenser has sufficient capacity

Fläkt Woods 8210 GB 2009.02 20 Specifications are subject to alteration without notice
STING CATALOGUE

Cooling – ETKC Cooler

Dimensions and weights


Sting Difference in width Length Difference in height Output variant 1 Output variant 2 Output variant 3 Min. flow
Size (mm) (mm) (mm) Weight (kg) Weight (kg) Weight (kg) m3/s

10 - - - - - - -

20 +268 +1074 +1 - 198 213 0,3

30 +318 +1074 +1 221 226 252 0,5

35 +318 +1074 +1 221 226 252 0,5


1)
40 +418 +1074 +1 258 268 346 0,7

50 +450 +1074 +101 299 356 463 1,2

65 +450 +1074 +1 441 504 643 1,6

80 +450 +1074 +74 1064 2009 1292 3,3

85 +450 +1074 +74 1064 2009 1292 3,3

1) At output variant 3 and 230  V (Norwegian version)

Constructions data
3 x 400 V 3 x 230 V Approximate Refrigerant charge, kg
Size Capacity Rated Rated Rec. Rated Rec. Circuit Circuit Circuit Circuit Total
(a) Variant Cooling Input fuse Input fuse 1 2 3 4
(c) power (kW) current (A) (A) current (A) (A)

20 2 13 8,2 16 19 25 1 1 2

20 3 18 11,2 16 23 32 1 2 3

30 1 13 8,2 16 19 25 1 2 3

30 2 18 11,2 16 23 32 1 2 3

30 3 26 16,2 20 33 40 2 3 5

35 1 13 8,2 16 19 25 1 2 3

35 2 18 11,2 16 23 32 1 2 3

35 3 26 16,2 20 33 40 2 3 5

40 1 18 11,2 16 50 63 2 3 5

40 2 26 16,2 20 33 40 2 3 5

40 3 43 24,6 35 50 63 3 4 7

50 1 43 26,2 35 83 100 4 5 9

50 2 56 32,9 50 67 80 4 5 9

50 3 68 41,6 50 83 100 5 7 12

65 1 56 32,9 50 67 80 5 6 12

65 2 68 41,6 63 83 100 5 6 12

65 3 91 55,8 63 112 125 5 5 5 16

80 1 92 55,8 63 103 125 7 7 7 21

80 2 138 81,0 100 N.A. N.A. 7 7 7 21

80 3 183 97,4 125 N.A. N.A. 9 9 9 27

85 1 92 55,8 63 103 125 7 7 7 21

85 2 138 81,0 100 N.A. N.A. 7 7 7 21

85 3 183 97,4 125 N.A. N.A. 7 7 7 7 27

Fläkt Woods 8210 GB 2009.02 21 Specifications are subject to alteration without notice
STING CATALOGUE

Cooling – ETKC Cooler

Description of operation, two compressors

1) Option: code suffix -d


Cold
Water-cooled condenser Design pressure: 29.3 bar (e) = effective
water
inlet Test pressure: 33.0 bar (e) = effective
Fan section
VW Water-cooled
condenser 1)
KD-W

Direction
of flow

Applicable to
ECKA-08 only

Fan section

Survey of Components Operation


Symbols used The cooling unit is started and stopped by an ex-
EV:1, EV:2, EV:3 = Evaporator
FT:1, FT:2, FT3 = Filter-dryer ternal 0–10 V control signal. When the first cooling
GP1:1, GP1:2, GP1:3 = Protective pressure switch - high pressure stage is to start, the solenoid valve (MV:1) will first
GP1 a:1 = In-service pressure switch - high pressure
open. The lowpressure pressure switch (GP2:1)
GP2:1, GP2:2, GP2:3 = In-service pressure switch - low pressure
KD:1, KD:2, KD:3 = Condenser closes on an increase in evaporator pressure, and
KD-W = Water-cooled condenser (option) the controller will then start the compressor (KK:1),
KK:1, KK:2, KK:3 = Compressor
MU1:1, MU1:2, MU1:3 = Measurement tapping – high pressure
depending on the control signal. In order to switch
MU2:1, MU2:2, MU2:3 = Measurement tapping – low pressure out each cooling stage, the controller closes the sole-
MV:1, MV:2, MV:3 = Solenoid valve noid valve (MV:x), and the refrigerant will then be
RK = Refrigerant receiver
SG:1, SG:2, SG:3 = Sight glass
drawn out of the evaporator to the condenser, and
SÄV = Safety valve the compressor will stop when the low-pressure in-
VAA:1, VAA:2, VAA:3 = Shut-off valve - low pressure service pressure switch (GP2:x) has tripped. GP2:x
VAB:1, VAB:2, VAB:3 = Shut-off valve - high pressure
VAC:1, VAC:2, VAC:3 = Shut-off valve has automatic reset.
VAD:1, VAD:2 = Shut-off valve After a compressor has stopped, a restarting delay of
VAE:1, VAE:2 = Shut-off valve 5 min will be switched in.
VS:1, VS:2, VS:3 = Expansion valve
VW = Pressure-controlled water-saving valve (op-
tion)
x = Circuit 1, 2 or 3

Fläkt Woods 8210 GB 2009.02 22 Specifications are subject to alteration without notice
STING CATALOGUE

Cooling – ETKC Cooler

Electrical connections
Check that the power supply to the cooling unit is iso- The alarm circuit of the unit provides a group alarm
lated at the main circuit breaker. The electrical connec- signal, which can be connected to an external control-
tions are made at the main circuit breaker located on ler. This group alarm can be obtained as potential-free
the control panel or on the outside of the unit. contacts at pins 57, 58 at the terminal board. To pre-
Important note! The cable glands supplied must be vent unnecessary stops and alarms from the cooling
used to achieve the correct enclosure class. The direc- unit, it should be interlocked from the extract air fan
tion of rotation of the compressors is dependent on FF. Connect the unit as shown in the diagram below.
the phase sequence. Phase error relays are included in
the control panel and a error signal is displayed on the
PLC screen should the incoming power be incorrectly
phase sequenced.

Wiring diagram

Power supply: 1 1
Inkommande L1 QO1.2
3 x 400 V 2 2
matning 3x400V L2 QO1.4
To be Ansluts
connected
på on 3 3
L3 QO1.6
the main circuit break-
huvudbrytare 4 4
N N
er on ithe
kylenhet.
control panel PE PE
on the Cooler PE PE

1 1
Groupe alarm
Utgående 57 C
2 2
outputsummalarm
signal 58 NO
(slutning vid larm) PE PE
PE

Interlock fromöver ev.


Förregling 1 1
C 53
utetermostat,
outdoor sensor,GT if 2 2
(annars byglas) NC 54
any, GT PE PE
PE

Interlock fromöver
Förregling
C
1 1
55
extractfrånluftsfläkt
fan 2 2
NO 56
PE PE
PE
0-10 V DC control 1 1
0-10V DC styrsignal +
signal from external 51
0-10V 2 2
controller – 52

Fläkt Woods 8210 GB 2009.02 23 Specifications are subject to alteration without notice
STING CATALOGUE

Cooling – ETKC Cooler

Control Mollier Chart is used. For simple and quick sizing


The external control signal should be adapted to suit a use the Sting COOLER product selection program.
minimum temperature sensor (minimum temperature For optimum performance of the cooling unit, the
limiter) located in the supply air duct, as far as pos- exhaust flow rate should be the same or higher than
sible from the unit, but upstream of the first supply the supply air flow rate. If they are not, check that the
air device, and a temperature sensor located in the condensation temperature t1 is <57 °C when the unit
premises or in the exhaust air stream. The cooling unit is operating at maximum capacity
controller includes an input for controlling with the
exhaust air fan and outdoor sensor as interlocks.
Necessary information for sizing
Overheating of the condenser (KD) Outdoor air temperature . ........................................... °C
If the condenser heat cannot be absorbed by the ex- Relative humidity........................................................... %
haust air and the condensation temperature rises to Supply air flow ........................................................ m3/s
approx. 57 °C (corresponds to an exhaust air tem- Exhaust air flow ...................................................... m3/s
perature of approx. 53 - 55 °C downstream of KD:x), Exhaust air temperature
GP1a:1 (highpressure in-service pressure switch) will (upstream of the cooling unit ..................................... °C
stop compressor KK:1 in order to reduce the load. If
the condensation temperature should increase to the Connection of KD-W water-cooled con-
maximum permissible (+65 ° C), GP1:x will stop the denser to mains water supply
corresponding compressor and an alarm will be initi- If the cooling unit is equipped with a water-cooled
ated. GP 1:x has manual reset. condenser, it must be connected to a mains water sup-
ply having a min. pressure of 50 kPa and max. pres-
Alarm sure of 1000 kPa (0.5 – 10 Bar).
The cooling unit has a group alarm for motor protec-
tion, phase sequence, 3-phase indicator, high and low Important! The water must flow through the con-
pressure alarms. The high pressure switch is reset by denser in the flow direction specified in order to ob-
pressing the ”button” on the appropriate pressure tain the best efficiency.
switch GP1:x. after appropriate corrective action.
If necessary, reset the motor protection breakers. Trip The water-cooled condenser includes a factory-adjust-
the power supply and then switch it back on again at ed water-saving valve that regulates the water flow
the main circuit breaker in order to reset the control- through the condenser. The inlet mains water flow
ler. The group alarm can be connected to an external must not be shut off.
controller or BMS
Important! If the unit is located outdoors, a heating
medium containing a suitable mixture of anti-freeze
Water-cooled condenser (KD-W) agent must always be used.
The water-cooled condenser is used for heat recovery
or when the exhaust air flow rate is too low for cool-
ing the refrigerant upstream of the air-cooled con-
denser (it should therefore be located upstream of the
ordinary air-cooled condenser in refrigerant circuit 2
if the system has 2 circuits or in refrigerant circuit 3 if
the system has 3 circuits). The water-cooled condenser
KD-W is equipped with a pressure-controlled water-
saving valve VW, which enables the condenser to
come into service automatically to cool whenever the
need arises.
Sizing
The project design work on the cooling unit is basical-
ly the same as that for other unit sections. The cooling
unit is fully integrated into the Sting and is equipped
with complete control equipment.
The following information is necessary for selecting
the appropriate output variant of the cooling unit:
Manual sizing presupposes knowledge on how a

Fläkt Woods 8210 GB 2009.02 24 Specifications are subject to alteration without notice
STING CATALOGUE

Sizing

Unit Sizing via the Web


Airhandlingconfiguration - ACON is the name of To enable you to access to the program, you need a
the new generation of web-based product selection user ID and a password.
programs. With ACON, the STING can be sized You can obtain these by contacting our nearest
quickly and easily. The program offers an air han- sales representative.
dling unit specification and all the facts needed, To find the nearest sales representative, visit out
such as dimensions, efficiencies, acoustic levels, home page at www.flaktwoods.com.
etc. The program also provides product specific
documentation concerning installation, mounting
and maintenance.

• You always work with the latest version of the


software
• Requires no installation
• Always available on the Internet
• F an performance curves with duty points, etc.
• T he unit drawing can be exported to CAD
• You obtain current delivery times from the or-
dering function.

Fläkt Woods 8210 GB 2009.02 25 Specifications are subject to alteration without notice
STING CATALOGUE

Controls

General Installation
The control equipment for the STING is developed If it is desirable to switch from right-hand to left-hand
with focus on making it simple to install, easy to use configuration or vice versa, it is easy to adapt the con-
and easy to supervise. trol equipment for this switch. If it becomes necessary
The control equipment can be supplied in two ver- to split the air handling unit for transport to the
sions. The air handling unit can be delivered in two building’s plant room, the quick connectors used
versions: one version is delivered complete with simplify unit division into blocks. The most common
microprosessor and all the necessary equipment sup- external components are supplied with all the neces-
plied with the unit, and the other version is delivered sary wiring for connection via quick connector to the
with a terminal block solution inwhich the air han- appropriate socket in the electrical equipment cubicle.
dling unit is supplied without controlunit and sensors,
though with fan drive equipment androtary heat ex- Operation
changer wired to a terminal block inter-face.
The control equipment is supplied for a 3 x 400 VAC, The STING is supplied as standard with control unit
50 Hz, 5-conductor system. and this includes a control panel for operating the air
handling unit. All the functions are displayed in plain
text. All the settings can be entered and readings can
be
viewed via the control panel.

Control equipment with display

Fläkt Woods 8210 GB 2009.02 26 Specifications are subject to alteration without notice
STING CATALOGUE

Controls

Flow chart

Component explanation
CP1 Circulation pump, air heating GT5 Frost protection sensor GS1 Rotation sensor
CP2 Circulation pump, air cooling GT6 Overheating electric air heater ST1 Damper actuator, outside air
FF1 Extract air fan sensor ST2 Damper actuator, extract air
TF1 Supply air fan GT7 Thermostat, electric air heater SV1 Valve actuator, air heater
U1 Integral motor, supply air fan GT12 Duct sensor, extract air control SV2 Valve actuator, air cooler
U2 Integral motor, extract air fan GF1 Flow transmitter, supply air SK1 Step controller, electric air
KM1 Cooler GF2 Flow transmitter, extract air heater
GT1 Supply air temperature sensor GP5 Pressure transmitter, supply air SU1 Timer/push-button
GT2 Room temperature sensor GP6 Pressure transmitter, extract air VVX Control unit, rotary heat
GT3 Outside air temperature sensor GN1 Presence detector exchanger

Technical data
• Control circuit for pumps, max 2 A(not applicable to terminal block solution).
• Auxiliary transformer for 24 V AC (not applicable to terminal block solution).
• Integral motors for fan operation.
• Speed controller for regulating the speed of the heat exchanger rotor.
• Time switch for 24-hour/one-week operation incorporated into the control unit. Battery backup for 72-hour
power failure (not applicable to terminal block solution).
The air handling unit is equipped with a system of quick connectors for connecting the peripheral equipment in
the immediate vicinity of the STING; damper actuators, sensors, valve actuators, display for the control unit, RJ-
45 (Ethernet)1) and serial communication, RS232 (not applicable to terminal block solution).
The STING models that are divided into blocks are also equipped with quick connectors for simple installation.

Flow Chart for air handling units without controller

Fläkt Woods 8210 GB 2009.02 27 Specifications are subject to alteration without notice
STING CATALOGUE

Controls

Connection data Environmental demands


Electrical data: The power supply is connected to the Permissible ambient temperature range while the unit
unit via the junction box on top of the unit. The main is operating: 0 –40 °C.
switch is situated in the control panel. The power supply
cable must be fitted with an external load interrupter that Standards
is capable of opening the supply to the entire air handling
unit. Load interrupters are available as accessories. The cubicle with control equipment complies with the
The air handling unit must be supplied with 3-phase, following standards and regulations:
400 V AC 50/60 Hz. Size 10 and 20 can be connected to EU Machinery Directive 98/37/EG, electrical equip-
ment in machinery, EN 60204-1.
1-phase 230 V.Recommended short-circuit protection is
EMC Directive: 89/336/EEC, EN 61800-3 (Emissions
tabulated below.
EN61000-6-3:2001and Immunity EN61000-6-2:2001)
Low Voltage Directive 72/23/EEC[DF2], (EN50178).
Testing
Every unit is isolation and performance tested prior to
Transformer
delivery. The insulation and performance of the control
To enable the use of STING units in Norway, where
equipment in each air handling unit is tested before de-
3-phase 400 V power isn’t available, a transformer that
livery.
converts 3-phase 230V power till 3-phase 400V + N is
required. Norway: 3-phase 230 V for indirectly earthed (IT)
mains power supply.
Fuse and fuse load interrupter (STYZ-39)
Integral motor
Size Power Voltage Constant current1) Rec.1) STYZ-39 kVA Trafo
kW V A Fuse, AT A kVA

10 2x1.4 1x230 26,3 32 32


6,5 12,5
6,512,5
10 2x1.4 3x400 <9,9 16 16

20 2x1.4 1x230 26,3 32 32


6,4 12,5
20 2x1.4 3x400 <9,7 16 16

30 2x1.5 3x230 21,3 40 45


8,5 12,5
30 2x1.5 3x400 12,9 16 16

35 2x2.2 3x230 25,9 50 63


10,3 16
35 2x2.2 3x400 15,7 20 25

40 2x4.0 3x230 36,8 50 63


14,7 16
40 2x4.0 3x400 22,3 25 25

50 2x4.0 3x230 36,8 80 80


14,7
14,7 20
20
50 2x4.0 3x400 22,3 25 25

65,80 2x7.5 3x230 61,6 100 125


24,6
24,6 25
25
65,80 2x7.5 3x400 37,3 45 45

85 2x11 3x230 91,0 160 160


34,4 40
85 2x11 3x400 52,3 63 63

EC-motor
Size Power Voltage Constant current*) Rec.*) STYZ-39 kVA Trafo
kW V A Fuse, AT A kVA

20 2x1.7 3x230 26,3 32 32


6,4 12,5
6,512,5
20 2x1.7 3x400 <9,7 16 16

30 2x1.7 3x230 21,3 40 45


8,5
6,4 12,5
30 2x1.7 3x400 12,9 16 16

35 2x3.0 3x230 25,9 50 63


10,3
8,5 16
12,5
35 2x3.0 3x400 15,7 20 25

1) Magnetising of the transformer at 3 x 230 V has been taken into consideration.

Fläkt Woods 8210 GB 2009.02 28 Specifications are subject to alteration without notice
STING CATALOGUE

Controls

Full transformer Prolonged or forced operation


The full transformer must be used at locations with net­ Via timer, push-button or presence detector.
work structure of type IT (indirectly earthed). The trans-
former forms a TN system on its secondary side which Timer, low speed for fitting externally or recessed.
means that no modification from the Swedish version is Setting: 0-2 hours.
required. Function: To start the unit at low speed or switch over
to low speed when running high speed.
Primary protection
The transformer must be equipped with primary pro­tec­ Timer, high speed for fitting externally or recessed.
tion. The primary protection consists of a conventional Setting: 0-2 hours.
micro circuit breaker that is connected to the incoming
Function: To start the unit at high speed or switch
supply to the transformer on the 230 V side to protect
the same against overloading. No micro circuit breaker over to high speed when running low speed.
is supplied by us. The electrical contractor should pro-
vide the necessary equipment. Presence detector for mounting externally. Delay
setting: 2-15 minutes.
Standards Function: To start either high or low speed according
to the timer function high or low speed.
The transformers comply with the following standards
and regulations:
Low Voltage Directive: LVD 73/23/EEC, 93/68/EEC To set the integral motors
EN61558-2-4:1997 The integral motors of the supply air fan and the extract
EMC Directive 89/336/EEC, 91/263/EEC air fan have been preset prior to delivery.
EN 61000-3-2:1995, EN61000-3-3:1995 Air flow/pressure set point corrections can be entered
via the control panel of the control unit. Air handling
Enclosure units ordered and supplied without control unit have
The transformer is supplied enclosed in a standard terminal blocks inside the electrical equipment cubicle
sheet-metal casing to IP23, max. permissible ambient for start signals (potential-free) control signals (0-10 V)
temperature: 30 °C. and in-operation indicating signals.

Temperature control
Speed control The following methods of temperature control are
available:
Flow control
The preset values for the supply air fan and the extract Supply air temperature control
air fan are set using the control panel. Two preset Function: keeps the supply air temperature constant at
values for each fan make switching fan speed possible the set point setting.
using a time switch, timer, push-button, presence
detector or via a preset comfort control. Extract air control
Function: To keep a constant flow in the duct system. Function: keeps the extract air temperature constant at
the preset value through cascade control of the supply
Pressure control air temperature with max/min limiting.
The preset values for the supply air fan and the extract
air fan are set using the control panel. Two preset Room control
values for each fan make switching fan speed possible Function: keeps room temperature constant at the
using a time switch, timer, push-button, presence preset value through cascade control of the supply air
detector or via a preset comfort control. temperature with max/min limiting.
Function: To keep a constant pressure in the duct
system.

NB! It is not possible to supply the unit with pressure


control on one fan and flow control on the other.

Fläkt Woods 8210 GB 2009.02 29 Specifications are subject to alteration without notice
STING CATALOGUE

Controls

Flow compensation Outdoor temperature controlled fan speed


(STYZ-01, h=1)
Conventional sequential control Asimple way of preventing temperature drop in a
room is to prevent forced fan operation when the
Flow / outdoor temperature drops below the preset value.
control Setting: Adjust the break point for outdoor tempera-
signal tures using the control unit.

– +
Outdoor air Comfort control (Heat exchanger-
Cooler
Energy recovery temperature heatflow reduction)(STYZ-01, h=5)
Heater It is advantageous to utilize this function in places with
extremely low outdoor temperatures. When the
outdoor temperature is so low that even with full heat
The heat exchanger will start if heat is necessary, the
recovery and full effect on heating, more heat is
heater starts when full heat recovery is given and heat
required, the fan speed is decreased so that the desired
is required. When both the heat exchanger and the
supply air temperature is obtained.
heater are at maximum effect and there is a need for
Adjusting fan speed on both fans is done to prevent
extra heat the supply air temperature will drop. This
negative pressure in the building.
can be prevented with comfort control.
Setting: Adjust the maximum flow / pressure limit
using the control unit.
Summer / winter compensated flow /
pressure (STYZ-01, h=2)
One way to prevent a temperature drop in a room is
Flow /
to reduce the flow / pressure when the outdoor control
temperature drops. signal
To prevent a temperature increase in a room the flow
/ pressure is increased when the outdoor temperature – +
increases. The preset values for flow / pressure Outdoor air
Cooler
are adjusted independently with the help of a four Energy recovery temperature
point graph coupled to the outdoor temperature if Heater
the heat exchanger and heater gives full effect. Change in flow
Regulating fan speed on both fans is done to prevent
negative pressure in the building.
Setting: Adjust the four point break points also the
max and min flow / pressure using the control unit.

Relative flow / pressure


(100% = preset value)
%

Fu 120
110
Fn 100
90
Fl 80

°C
-30 -20 -10 0 10 20 30 Out-
Tlw Tuw Tls Tus door
tempera-
Fu Flow compensation, upper limit ture
Fn Flow, normal
Fl Flow compensation, lower limit

Tlw Temperature break point, lower winter limit


Tuw Temperature break point, upper winter limit
Tls Temperature break point, lower summer limit
Tus Temperature break point, upper summer limit

Fläkt Woods 8210 GB 2009.02 30 Specifications are subject to alteration without notice
STING CATALOGUE

Controls

Other – Night-time ventilation External components

Nightpurging (Night free cooling) Control of air heater


The nightpurging setting is used during the summer Control signal: 0-10 V for valve actuators or for electric air
period. Cool outdoor night air is used to cool the room heaters with built-in thyristor and stepping switch, if
during the night. Used outside the ordinary operating used.
period. Freeze protection device: When the air handling isn’t
Function: Starts the unit to cool the room with fresh air operating, the water temperature is kept constant at
when the room temperature and outside temperature 25 °C. When the unit is operating, in response to control
exceed the preset values and the difference between signals the valve regulates the water flow so that the
these values exceeds the preset difference. Cooler is not return temperature won’t drop below 12 °C. Should the
activated. water temperature drop below 7 °C, the control unit will
stop the air handling unit and initiate an alarm.
Unoccupied heating mode
Unoccupied heating mode is used to prevent the room Circulation pump for air heater
temperature dropping too much outside ordinary oper- Max permissible current: approx 2 A, 1-phase, 230 V.
ating time. The
Function: Starts the unit for full heat recovery and opens control unit is programmed to exercise the pump when-
for full effect from air heater if room temperature drops ever the unit isn’t operating. The design of the pump
below the preset value. prevents it from clogging. Should the built-in thermo-
contact trip, it will initiate an alarm.
Cooling recovery
Function: Starts the rotary heat exchanger for full Valve actuator for air heater
recovery for cooling the outdoor air when the extract air The valve actuators are designed for a valve for 5.5 mm
temperature is lower than the outdoor temperature and height of lift and G 3/4” threaded connections.
cooling is necessary.
Control of air cooler
Outdoor temperature compensation Control signal: 0-10 V for air coolers for chilled water.
(Summer and winter compensation) Control signal for coolers for direct expansion, DX,
Function: Offsets the preset value for supply air, extract normally-open contacts or 0-10V signals.
air or room temperature.
Circulation pump for air cooler
Max permissible current: approx 2 A, 1-phase, 230 V.
Relative The
temperature preset value design of the pump prevents it from clogging. Should
°C the built-in thermo-contact trip, it will initiate an alarm.
Tow 5
Tos Valve actuator for air cooler
The valve actuators are designed for a valve for 5.5 mm
0
height of lift and G 3/4” threaded connections.

-5

°C
-20 -10 0 10 20 30 Out-
Tlw Tuw Tls Tus door
tempera-
Tow Temperature preset value, offset, winter ture
Tos Temperature preset value, offset, summer
TLS Temperature break point, lower winter limit
Tuw Temperature break point, upper winter limit
Tlw Temperature break point, lower summer limit
Tus Temperature break point, upper summer limit

Fläkt Woods 8210 GB 2009.02 31 Specifications are subject to alteration without notice
STING CATALOGUE

Controls

Fire/smoke controller • Cable for 24 V power supply and should be connected


Afire/smoke controller can be wired to the unit. to the monitoring unit.
Operation: Stops the air handling unit and initiates a • Permissible ambient temperature range: -10 to
group alarm. +50 °C.
The fire dampers are exercised every 48 hours.
In-operation indication/Group alarm
Control and monitoring unit for fire/ outputs
fire gas Supply air fan and extract air fan in-operation indica-
The unit is incorporated into a plastic enclosure with a tions and separate Aand B alarms can be obtained via
glazed front panel that conforms to Enclosure Class terminal block connections.
IP66 and is CE labelled.
In the event of a tripped alarm, the air handling unit Communication
will shut down. The STING unit offers a variety of communication
possibilities: Among others, communications circuit
Technical Data: cards for connection to intelligent-building monitoring
• Damper blade position indicator systems, to the Internet and to mobile telephones.
• Detector indication of service alarms/tripped detec-
tor/malfunction alarms BACnet
• Automatic performance test The Sting can be equipped with a communication
• Group alarm circuit card for integration into the BACnet System.
• Reset button BACnet is an open world-wide standard, especially
• Performance test button developed for the building automation field.
• Input for signals from external fire alarm equipment BACnet is connected via the TCP/IP Network.
• Output for controlling the combustion gas fan
• 24 V AC power supply to damper actuator
• Permissible ambient temperature range: 0 °C to +30 °C
OPC
The Sting can be fitted with a card with OPC server that
• Voltage measurement in the unit, 230 V AC.
communicates via TCP/IP. OPC has a few more
features than Lon Works: it is possible, for instance to
Operation:
alter the internal time channels.
The air handling unit will be interlocked if the air
handling unit’s group alarm is wired to the appropriate
terminal inside the unit cubicle. The air handling unit LonWorks
fans will stop when an alarm is initiated. The Sting can be fitted with a communication card for
connection to LonWorks. The Lon card provides auto-
matic transmission of all SNVTs and this facilitates
Junction box for fire/fire gas damper
commissioning. The LonWorks card has 64 SNVTs and
The junction box makes it easier to route wiring to the
standard SNVT.
control and monitoring unit.

Technical Data Modbus


• Power supply: Designed for 24 V AC actuators. The Sting can be equipped with a communication
• Enclosure Class: IP54 circuit card for connection to a Modbus computer
• Permissible ambient temperature range: -30 °C to substation or to a Modbus supervisory system.
+70 °C Modbus is an open industrial defacto standard and is
• Inputs (max. cable cross-sectional area of 2. 5 mm 2) connected via RS 485.The Modbus card can be config-
• Heat detector input, opens the circui,t potential free, ured either as a master or a slave.
in the event of a malfunction.
• Dimensions: 85 x 85 x 38 mm (W x H x D)
Smoke detector
The smoke detector is of a make with ionizing action
for connection to the control and monitoring unit.
The smoke detector is designed for duct installation.
The insertion section (venturi tube) must be cut to the
appropriate length.

Technical Data:

Fläkt Woods 8210 GB 2009.02 32 Specifications are subject to alteration without notice
STING CATALOGUE

Controls

Web Communication
A web application that offers you the same functionality as
a conventional supervisory system although at consider-
ably lower cost is available as an optional extra for STING
units. Since the web server is integrated into the unit, there
are no extra hidden costs or subscription fees.

HINT! Because a GSM module is used, it is advantageous to


utilise a so-called refill card which spares you from having
to pay subscription fees. At present, cell phone users have
to refill their accounts once every year in Sweden to avoid
blockage. This can be done when changing the air filters,
for example.

The web application is completely independent of opera-


tive systems in PCs, i.e. no special software is necessary
- only a web browser and an ordinary computer. The
web server can be connected to a common local TCP/
IP network. In this way you can communicate with the
air handling unit from an optional computer in its local
network. If no network is available, then it is possible to
either connect a cable between the unit and the computer,
or utilise a modem.

TCP/IP INTERNET
PC linked to intranet/
PC direct PC linked via Hand held PC network with internet
online link intranet/network with web browser connection

PC linked via modem

Modem

Modem

PPP

Fläkt Woods 8210 GB 2009.02 33 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories

Shut-off damper for duct mounting, ETVA Duct sound attenuator, ETLD
Damper for duct mounting. Conforms to tightness Circular connections, sizes10-20 and
Class CEN 3. The damper is made of galvanized
STING Top 30-35
sheet steel and fitted with an on/off actuator and
Suited to size 10-20 the straight circular duct sound
has spring-return action. The damper actuator cable
attenuator is filled with 100 mm rock wool and a baffle.
has a quick connector for connection to the appropri-
The duct connections are equipped with a rubber ring.
ate socket inside the electrical equipment cubicle.
The sound attenuator consists of a perforated sheet
Supplied without actuator if air handling unit with-
metal tube enclosed by a mantle and end walls made
out control unit is supplied. Duct connections for
of galvanized sheet metal. The space between is filled
round dampers are with a rubber seal ring.
with rock wool that is covered by staple fibre fabric to
Rectangular dampers are designed for PG-jointing
prevent fibre entrainment. Fire class EI30.
to the ducting and if requested can be mounted
Connection straight, 300 mm from fan outlet.
directly to the unit. The damper vanes are coupled
via externally mounted gears that are manufactured
in PP-plastic. For unit sizes 65 – 85, the outdoor air Duct sound attenuator, rectangular
damper and the extract air damper are mounted connections, size 30-85
inside the air handling unit. The sound attenuator suited to size 30-85 is a rectan-
The design can accommodate up to 50 mm thick duct gular baffle sound attenuator. The casing is made of
insulation. galvanized sheet metal. The baffles are filled with glass
At air velocities below 10 m/s, the sound power level fibre with staple fibre fabric as protection against fibre
of a fully open damper is lower than 20 dB. entrainment. The duct connections are designed for
PG-jointing to ducting. The baffle sound attenuators are
not fire classified. Connection of sound attenuators can
be made directly onto the fan outlet.

ETLD-aa-b
Size Connection Outer dim., mm Length, mm Wgt., kg

10 ø 315 ø 515 900 28

20 ø 400 ø 630 1200 42

20 Top ø 400 ø 630 1200 42

30,35 800 x 400 800 x 400 1200 32

30,35 Top ø 500 ø 711 1200 71


ETVA-aa-b-c-2 40 1000 x 500 1000 x 500 1200 44
Size aa Connection Length Weight 50 1200 x 600 1200 x 600 1200 55
10 ø 315 130 4 65 1600 x 800 1600 x 800 1200 93
20 ø 400 130 5 80,85 2000 x 1000 2000 x 1000 1200 129
20 Top ø 400 130 5

30 800 x 400 120 15

30 Top ø 500 130 9

35 800 x 400 120 15

35 Top ø 500 130 9

40 1000 x 500 120 20

50 1200 x 600 120 25

65 1600 x 800 220 38

80 2000 x 1000 220 55

85 2000 x 1000 220 55

Fläkt Woods 8210 GB 2009.02 34 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories

Electric air heater, For in-duct mounting, The air heater should be installed at least 600 mm from
ETKK a fan or duct bend. The air heater can be installed either
Circular connection, sizes 10-20, 20-35 STING TOP horizontally or vertically. If installed horizontally the
terminal box must not face downwards. The air heater is
equipped with 2 overheating circuit breakers, one that
resets automatically and one that has to be reset manu-
ally which is done via the cover on the heater. The air
heater is controlled by means of a 0-10 V signal from the
units controlpanel.
The air heater is CE labelled. Minimum air velocity is
1,5 m/s. Maximum permissible operating temperature
is 40 °C. The air heater is interlocked across the supply
air fan via circuitry inside the electrical equipment
cubicle.
Power must be supplied separately; the power supply
Electric in-duct air heater with integrated thyristor. cable is not included in the delivery. Signal cable for
Casing made of galvanized sheet steel and heating alarms, and operating the air heater has a quick connec-
elements made of grade SS2337 stainless steel. Degree tor for connection to the appropriate socket inside the
of protection IP43. Connections with rubber seal ring. electrical equipment cubicle in the STING.

ETKK-aa-b-c-d-e-1
Size Output variant Connection Effect Outside dimension Weight Min.air flow Max.consumption of
aa b mm kW (BxHxL) kg m3/s current, A 230 V/ 400 V
1) 1) 1)
10 1 ø 315 3 317x400x375 11 0,12 13.1 /7.5

10 2 ø 315 6 317x400x375 11 0,12 15/9

10 3 ø 315 9 317x400x375 11 0,12 23/13

20 1 ø 400 6 405x480x375 12 0,19 15/9

20 2 ø 400 9 405x480x375 12 0,19 23/13

20 Top 1 ø 400 6 405x480x375 12 0,19 15/9

20 Top 2 ø 400 9 405x480x375 12 0,19 23/13

30 Top 1 ø 500 12 540x720x730 20 0,16 31/18

30 Top 2 ø 500 17 540x720x730 21 0,16 43/25

35 Top 1 ø 500 17 540x720x730 21 0,16 43/25

35 Top 2 ø 500 24 540x720x730 23 0,16 61/35

1) 3 kW Air heater connected to 1-phase (230 V) or 2-phase (400 V)

Fläkt Woods 8210 GB 2009.02 35 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories

Electric air heater, For in-duct mounting, the same casing. Can be connected directly to the unit
ETKK or out in the duct system. Specify this when ordering
Rectangular connections, sizes 30-85 because the end connections in the heater casing vary
depending on how it is connected. On the size 20 – 50
STING units, the air heater can be mounted directly to
the air discharge connection of the unit. The distance
from the bend to the air heater should be at least a
distance equal to the diagonal distance across the duct.
The air heater can be installed either horizontally or
vertically. If installed horizontally the terminal box
must only be on the side, not on the top or the underside.
The air heater is equipped with 2 overheating circuit
breakers, one that resets automatically and one that has
to be reset manually which is done via the cover on the
heater. The air heater is controlled from the unit’s elec-
trical equipment cubicle by means of a 0–10 V signal.
The air heater bears the CE label. Min permissible air
Air heater, electric in-duct heater with integrated thyris- velocity: 1.5 m/s. Max permissible operating tempera-
tor. Casing made of aluminium-zinc plated sheet steel ture: 40 °C. The air heater is interlocked via terminal
and heating elements made of grade SS2337 stainless block inside unit’s electrical equipment cubicle. Power
steel. Degree of protection IP43. Duct connections are must be supplied separately; the power supply cable
designed for PG jointing to ducting. For the STING 65 – 85, is not included in the delivery. Signal cable for alarms,
the coil is built into the air handling unit casing and is and operating the air heater has a quick connector for
mounted together with the possible cooling coil inside connection to the appropriate socket inside the electrical
equipment cubicle in the STING.

ETKK-aa-b-c-d-e-1
Size Output variant Connection Effect Outside dimension Weight Min.air flow Max.consumption of
aa b mm kW (BxHxL) kg m3/s current, A 230 V/ 400 V

30 1 800x400 12 1019x438x600 20 0,48 30/17

30 2 800x400 17 1019x438x600 21 0,48 43/25

35 1 800x400 17 1019x438x600 21 0,48 43/25

35 2 800x400 24 1019x438x600 23 0,48 60/35

40 1 1000x500 24 1219x538x600 26 0,75 60/35

40 2 1000x500 30 1219x538x600 29 0,75 75/43

50 1 1200x600 27 1419x638x600 35 1,1 68/39

50 2 1200x600 35 1419x638x600 36 1,1 88/51


1) 2) 3)
65 1 1600x800 40 2004x1074x400 75 2,2 101/58
1) 2) 3)
65 2 1600x800 80 2004x1074x400 90 2,2 201/116
1) 2) 3)
80,85 1 2000x1000 64 2604x1374x400 110 4 161/93
1) 2) 3)
80,85 2 2000x1000 128 2604x1374x400 145 4 322/185

1) The connection dimensions of the coil casing,


2) The outer dimensions and functional length of the coil casing
3) Weight of the function

Fläkt Woods 8210 GB 2009.02 36 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories

Air heater, water, for duct mounting, ETKE Rectangular connection, sizes 30-85
Circular connection, sizes 10-20 Air heater for hot water; consists of copper tubing
Air heater for hot water; consists of copper tubing and aluminium fins. The air heater has exposed head-
and aluminium fins. The air heater is incorporated ers. Duct connections are designed for PG-jointing to
into a casing made of galvanized sheet steel. The ducting. The air heater for sizes 30-85 can be mounted
casing has a removable cover for cleaning and spigots directly onto the units outlet.
The air heater is reversible for right-hand or left-hand
with rubber seal ring for connection to the ducting.
connection.
The air heater for size 10 should be installed at least
The coil for the size STING 65-85 units can be ordered
600 mm from a fan or duct bend upstream of the air
as a duct-mounted coil without casing or as a coil
heater.
incorporated into the casing of the air handling unit.
The air heater is reversible for right-hand or left-hand Can be mounted together will a possible cooling coil
connection. in the same casing. Can be connected directly onto
An anti-frosting sensor (strap-on sensor) is included the air handling unit or out in the duct system. This
in the control equipment. must be specified when ordering, since the end walls
Venting and drainage should be carried out from of the casing differ.
the pipe work. The pipe connections are smooth and The anti-frosting sensor (insertion sensor) is included
designed for clamp coupling. in the control equip-
Maximum operating pres- ment. The headers are
sure: 1.0 MPa equipped with plugged
Maximum operating temper- connections for vent-
ature: 100°C ing and drainage. The
headers are fitted with
plugged outlets for
venting and drainage,
joint number 8 with
female pipe threads.
The pipe joints have
male pipe threads.
Maximum operating
pressure: 1.6 MPa
ETKE-aa-b-c-1 Maximum operating temperature: 100°C.
Size Output variant Fin spacing Air connection Pipe connection Outside dimension Weight

aa b mm mm (BxHxL) kg

10 1 2,5 ø 315 22 mm 460x408x380 10

10 2 2,5 ø 400 22 mm 540x483x440 14

20 1 2,5 ø 400 22 mm 540x483x440 14

20 2 2,5 ø 500 22 mm 690x533x475 17

30,35 1 2,0 800x400 DN15 908x438x150 17

30,35 2 3,0 800x400 DN25 908x438x150 21

40 1 2,0 1000x500 DN25 1108x538x150 22

40 2 3,0 1000x500 DN25 1108x538x150 27

50 1 2,0 1200x600 DN25 1308x638x150 27

50 2 3,0 1200x600 DN25 1308x638x150 34


1) 2) 3)
65 1 2,0 1600x800 DN25 2004x1074x300 70
1) 2) 3)
65 2 2,0 1600x800 DN32 2004x1074x300 110
1) 2) 3)
80,85 1 2,0 2000x1000 DN32 2604x1374x300 105
1) 2) 3)
80,85 2 2,0 2000x1000 DN50 2604x1374x300 140
1) The connection dimensions of the coil casing
2) The outer dimensions and functional length of the coil casing
3) Weight of the function

Fläkt Woods 8210 GB 2009.02 37 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories

Air cooler, water, for duct mounting, ETKN Rectangular connection, sizes 30-50
Circular connection, sizes 10-20 Air cooler for chilled water; consists of copper tubing
Air cooler for chilled water; consists of copper tubing and aluminium fins. The air cooler has exposed head-
and aluminium fins. ers and tube bends. Duct connections are designed for
The air cooler is incorporated into a casing made of PG-jointing to ducting. The air cooler for sizes 30-50
galvanized sheet steel with 9 mm insulation. The can be mounted directly onto the unit’s outlet. The coil
for the size STING 65-85 units can be ordered as a
casing has a removable cover for cleaning and spigots
duct-mounted coil without casing or as a coil incor-
with rubber seal ring for connection to the ducting.
porated into the casing of the air handling unit.To be
The size 10 air cooler should be installed at least 600
mounted together with possible air heater in the same
mm from a fan or duct bend upstream of the cooler and
casing. Can be connected directly onto the air handling
is available for left-hand connection only. unit or out in the duct system. This must be specified
Venting and drainage should be carried out from when ordering, since the end walls of the casing differ.
the pipe work. The pipe connections are smooth, The headers are fitted with plugged outlets for venting
located on the outlet end wall and designed for clamp and drainage, joint number 8 female pipe threads.
coupling. The pipe joints for the chilled water
The drainage tray is made of stain- have external pipe threads. The
less steel and has a 19 mm pipe drainage tray is made partially of
connection. stainless steel, 32 mm pipe connec-
Maximum operating pressure: tion with male pipe threads and is
1.0 MPa suitable for ESAZ-30 water trap.
Maximum operating temperature: Maximum operating pressure:
100°C 1.0 MPa
Maximum operating temperature:
100°C.
ETKN-aa-b-c-1
Size Output variant Fin spacing Air connection Pipe connection Outside dimension Weight
aa b mm mm (BxHxL) kg
10 1 2,5 ø 315 22 mm 540x486x440 16
20 1 2,5 ø 400 22 mm 690x536x475 21
30,35 1 2,0 800x400 DN25 1000x489x300 26
30,35 2 2,0 800x400 DN25 1000x489x300 30
40 1 2,0 1000x500 DN25 1200x589x300 36
40 2 2,0 1000x500 DN32 1200x589x300 42
50 1 2,0 1200x600 DN32 1400x689x300 47
50 2 2,0 1400x800 DN50 1600x889x300 68
1) 2) 3)
65 1 2,0 1600x800 DN50 2004x1074x400 160
1) 2) 3)
65 2 2,0 1600x800 DN50 2004x1074x500 205
1) 2) 3)
80,85 1 2,0 2000x1000 DN80 2604x1374x400 230
1) 2) 3)
80,85 2 2,0 2000x1000 DN80 2604x1374x500 295
1) The connection dimensions of the coil casing, 2) The outer dimensions and functional length of the coil casing, 3) Weight of the function

Air velocity – Chilled water coil


Size Max. flow, m3/s Max. flow, m3/s
STING without droplet eliminator without droplet eliminator
max.3 m/s max.4 m/s
10 0,23 –
20 0,37 –
30 0,96 –
35 0,96 –
40 1,5 –
50 2,1 –
50, b = 2 3,3 –
65 4,7 6,3
80 8,2 11,0
85 8,2 11,0

Fläkt Woods 8210 GB 2009.02 38 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories

Air cooler, dx, for duct mounting, ETKP


Rectangular connection
Air cooler for direct expansion, dx, in 2 stages, 1/3 + Refrigerant connections: 15 and 28 mm respectively.
2/3 interlace connection. The air cooler consists of Refrigerant options: R22 1), R134a, R404a and R407c.
copper tubing and aluminium fins. Exposed head-
ers, pipe bends and distributor. Duct connections are 1) not permissible in cooling systems in Sweden.
designed for PG jointing to ducting. The air cooler
for sizes 30-50 can be mounted directly onto the unit’s
outlet. The air cooler can have right-hand or left-hand
connection side. The coil for the size STING
65-85 units can be ordered as a duct-mounted coil
without casing or as a coil incorporated into the
casing of the air handling unit. To be mounted
together with possible air heater in the same casing.
Can be connected directly onto the air handling unit
or out in the ducting. This must be specified when
ordering, since the end walls of the casing differ.
The drainage tray is made partially of stainless steel,
pipe connection with 32 mm male threads and
ETAZ-30 water trap.

ETKP-aa-b-c-d-e-1
Size Output variant Output step Fin spacing Air connetion Pipe connection Outside dimension Weight
aa b c mm mm mm (BxHxL) kg
10-35 1 1 2,0 800x400 1x15/1x28 1000x489x300 26
10-35 1 3 2,0 800x400 1x15,1x12/1x28,1x12 1000x489x300 26
40 1 3 2,0 1000x500 1x15,1x12/1x28,1x12 1200x589x300 36
50 1 3 2,0 1200x600 1x22,1x15/2x28 1400x689x300 46
50 2 3 2,0 1400x800 2x15/2x28 1600x889x300 54
65 1 3 2,0 1600x800 1) 2x22/2x34.9 2004x1074x500 2) 205 3)
80-85 1 3 2,0 2000x1000 1) 2x22/2x54 2604x1374x500 2) 295 3)
1) The connection dimensions of the coil casing
2) The outer dimensions and functional length of the coil casing
3) Weight of the function

Air velocity – Dx-coil


Size Max.flow, m3/s Max.flow, m3/s
STING without droplet eliminator without droplet eliminator
max.3 m/s max.4 m/s
10 0,96 –
20 0,96 –
30 0,96 –
35 0,96 –
40 1,5 –
50 2,1 –
50, b = 2 3,3 –
65 4,7 6,3
80 8,2 11,0
85 8,2 11,0

Fläkt Woods 8210 GB 2009.02 39 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories

Adjustable foot, ETAZ-20 Stainless steel mounting frame, ETAZ-23


The unit can be Filter mounting frame
placed directly onto made of grade SS2333
floor if it is smooth (AISI 304) stainless steel
and horizontal. The with drip tray below the
adjustable foot can be outdoor air filter (without
used for height drainage). For humid
adjustment. The climate applications to
range of adjustment protect the unit casing
is 15-85 mm. A rubber against corrosion.
disc is included. The filters placement ,
over or under floor in the
Size Quantity per size unit , has to be chosen
10, 20, 30 4 when ordering.
35, 40, 50 6 Not STING Top.
65, 80, 85 6

HK Instruments Oy MM ….
Keihästie 7
June 2004
40950 MUURAME, FINLAND
Tel +358 14 337 2000

Differential pressure gauge, ETAZ-24


Fax +358 14 337 2020

Spare filter, ETAZ-21 Pressure gauge forINCLINED TUBE MANOMETER


1 spare filter cassette,
measuring air flow.
F7(EU7).
Can be mounted on
the end wall of the
unit and connected
to measurement
nipples.
Supplied unmounted.
Model summary Model code Manometer range Accuracy Gauge fluid

MM±50 -50… 0 … +50 Pa 1 Pa Red


Arrangement (b) MM100
MM±100
-20… 0 … +100 Pa
-100… 0 … +500 Pa
1 Pa
5 Pa/25 Pa
Red
Red

1 = size 10, inclined tube manometer MM200600


MM5001500
0… 600 Pa
0… 1500 Pa
5 Pa/25 Pa
10 Pa/50 Pa
Red
Blue

Accessories Standard accessories:


2 = size 20-85, U-tube manometer 2 fixing screws
Gauge fluid

Flexible connection, 2 m tube ∅ 4 / 7 mm


Red/green stickers

ETAZ-22 Technical data


Flexible sleeve made of glass fibre Materials Housing
Cover
ABS
PMMA
fabric for flexible connection to Screws
Sealings
PC
NBR

ducts. Weight 420 grams

Ambient conditions Operation -40…+60°C

Max. Pressure 200 kPa (2 bar)

Gauge fluid Red, s.g. 0,786 kg/dm³ (15 °C)


Blue, s.g. 1,870 kg/dm³ (15 °C)
Size

ETAZ-22-bb-c Connection Type of connection
________________________________________________________________________________________________
bb=10 ø 315 Clamps
bb=20 ø 400 Clamps
bb=20 Top ø 400 Clamps
bb=30, 35 800 X 400 PG-joints
bb=30, 35 Top ø 500 Clamps
bb=40 1000 X 500 PG-joints
bb=50 1200 X 600 PG-joints
bb=65 1700 X 800 PG-joints
bb=80, 85 2000 X 1000 PG-joints

Fläkt Woods 8210 GB 2009.02 40 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories

Dual-purpose cowl for wall mounting, STING Dual-purpose cowl for roof mounting,
10-30, ETAZ-25 ETAZ-26
The cowl is designed for wall mounting, the intake of The cowl is designed for roof mounting, the intake of
outdoor air through its bottom opening and the outdoor air through its bottom opening and the
discharge of exhaust air straight out. The cowl is made upward discharge of exhaust air. The extract air section
of galvanized sheet steel and has a black epoxy painted is equipped with a non-return damper. A metal screen
finish. Ametal screen covers the inlet and outlet open- covers the outdoor air openings to prevent rodents and
ings to prevent rodents and other small animals from other small animals from entering the system.
entering the system. The cowl is made of galvanized sheet steel. The roof
cowl can be fitted to an ETAZ-27 roof duct.

E D
c/c

C
50
F
G
A
B



ETAZ-25-b Connection Outside dimension C/C Wgt.
ETAZ-26-b A B C D E F G Vikt
(B x H x L) kg
kg
bb=1 (STING 10) 2 x ø 400 1000 x 580 x 220 500 15
b= 1(STING 10,20, 30) 1050 550 525 1450 850 1000 500 45
bb=2 (STING 20,30) 2 x ø 500 1200 x 720 x 300 600 22
b=2 (STING 35,40) 1450 750 675 1950 1150 1400 700 75
b=3 (STING 50) 1850 950 750 2400 1400 1800 900 105

Pressure drop, outdoor air and extract air Exhaust air


Pressure drop, Pa

3
Pressure drop, Pa

Pressure drop, Pa

Size
b

200
/s

Exhaust air Outdoor air 100 10


,m
ity

30 50
oc

10
el
tv

00
tle

0 5
0 ø5 20 5
Ou

10 ø4
10
Air flow
0 0
m3/s
0 0,2 0,4 0,6 0,8 1,0 1,2 0,1 0,2 0,5 1,0 2,0
m3/h
Air flow, m3/s 500 1000 2000 5000

Outdoor air
1

2
=

Size
b

b
Pressure drop, Pa

300
3

200
=
b

100

50

20

10
Air flow
m3/s
0,1 0,2 0,5 1,0 2,0
m3/h
500 1000 2000 5000

Fläkt Woods 8210 GB 2009.02 41 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories

Roof duct, ETAZ-27 Water trap, ETAZ-30


The roof duct is designed for the ETAZ-26 dual- Compact water trap with
purpose cowl. The roof duct is insulated with 50 mm overpressure valve for air
thick mineral wool covered by perforated sheet steel. coolers. Maximum over-
The roof duct is equipped with angle brackets for secur- pressure 1700 Pa.
ing it to the roof structure. 255


ETAZ-27-b Outside dimension Duct Hole dimen- A Wgt.
(B x H x L) connection sion kg
bb=1
(STING 1000 x 500 x 800 2 x ø 400 1010 x 510 500 56
10, 20, 30)
bb=2 U-tube manometer, ETAZ-31
(STING 1400 x 700 x 800 600 x 600 1410 x 710 700 72 A simple manometer for measuring
35, 40) pressure drop across the filter. Can be
bb=3 fitted to
(STING 1800 x 900 x 800 800 x 800 1810 x 910 900 92 the end wall of the unit and connected to
50)
measurement nipples. Supplied
unmounted.

Stand for vertical configuration, ETAZ-28


Stand for Sizes
10-20 for vertical
configuration of unit.
The stand, feet and
doorstop to top door
are included in the kit.
Not STING Top.

Max. 700

Max. 560

Fläkt Woods 8210 GB 2009.02 42 Specifications are subject to alteration without notice
STING CATALOGUE

Accessories, Service area

Version for outdoor installation Service area


The STING can be installed outdoor if the unit is fit- The area around the unit should be planned to allow
ted with a roof, air intake louvre with cowl and an for routine service work such as changing filters and
exhaust air cowl. The control cubicle is equipped with cleaning of the fan and unit casing. An open service
a heater. Outdoor version must be specified when or- path must be provided in front of the unit’s electrical
dering (STET h=3) so that the heater will be included equipment cubicle. The width of this path shall
in the supply. It cannot be installed afterward. The conform to the recommendations outlined in EL-
roof can be ordered mounted on the unit or supplied SÄKRFS 2004:1 Electric Power Regulations drawn
as loose parts. If it is supplied mounted on the unit, up by the National Swedish Electrical Safety Board.
its joints will have been sealed at the factory. If the In addition, allowance should be made for future re-
roof is ordered as loose parts, the supply will include placement of air handling unit components. Planning
sealing compound for sealing at the building site. of this service area is a condition that must be fulfilled
Not STING Top. before the installation can comply with requirements
for
Air intake grille with cowl, ETAZ-15 CE-labelling.
Air intake grille with cowl made of galvanized sheet
steel and blades made of weather-resistant poly­ Service area requirements (mm)
propylene plastic. The air intake section has space for Unit width = A
an internal damper, if required. Change of components= A
Change of filter = B
Aggregatet sett uppifrån
Exhaust air cowl, ETAZ-16
Equipped with protective screen. Circular connection
for the STING 10-20 and rectangular for the STING
30-85. A

Roof for outdoor installation, ETAZ-33


The roof is convex for good drainage. The roof for the
size 10-50 units is split in such as way that the control
cubicle on the roof is easily accessible.
B
A
Sizes 10-20
ETAZ-16
Unit viewed from above

Size A B
ETAZ-15
10 840 800
20 1040 (1340*) 800
30 1190 (1490*) 900
35 1190 (1490*) 900
40 1440 (1740*) 900
50 1740 (2040*) 900
65 2010 (2310*) 900
Sizes 30-85
80 2610 (2910*) 900
ETAZ-33
85 2610 (2910*) 900
ETAZ-16
*) Unit with Cooler
It is advisable to allow a minimum open space of 300
mm for sizes 10-50 above the unit which will facilitate
ETAZ-15 the electrical installation work. The unit should be
situated or arranged in a way that will provide easy
access to the electrical equipment cubicle for servic-
ing. This applies chiefly to the size 40 and 85 units
from which the electrical wiring is routed relatively
high up.

Fläkt Woods 8210 GB 2009.02 43 Specifications are subject to alteration without notice
STING CATALOGUE

Ordering Codes

STING ETAS-aa-b-c-d-1-f-2-h-1 Coil casing ETGA-aa-bbb-c-1


Air handling unit
Unit size (aa)
Size (aa) 65, 80, 85
10, 20, 30, 35, 40, 50, 65, 80, 85
Length, cm (bbb)
Supply air location (b)
1 = supply air, bottom, right-hand Connection variant (c)
(standard) 0 = connection in ductwork
2 = supply air, bottom, left-hand. 2 = connection to air handling unit
Not aa = 10
3 = supply air, top, right-hand (standard). Accessories
Not aa = 10
4 = supply air, top, left-hand End wall for coil casing ETGV-aa-b-1

Connection (c) Unit size (aa)


1 = inlet/outlet in end wall (standard) 65, 80, 85
2 = outlet in top panel, not aa=10
3 = inlet in top panel, not aa=10 Location (b)
4 = inlet/outlet in top panel, not aa=10 1 = end wall on inlet side
5 = Top ( aa= 20, 30, 35, d=2, b=1,4) 2 = end wall on outlet side

One-piece, sectionalized unit (d) Empty section ETTC-aa-b-c-d-1


1 = one-piece unit,
(applicable to sizes 10, 20, 65-85) Unit size (aa)
2 = sectionalized unit (applicable to sizes 30-85) 60, 80, 85
5 = divisible with Cooler (not applicable to size 10)
Length (b)
Rotary heat exchanger (e) 2 = 200
1 = non-hygroscopic (standard) 3 = 300
2 = hygroscopic 4 = 400 (standard)
6 = non-hygroscopic TURBOTERM
7= hygroscopic TURBOTERM Inspection door (c)
1 = with door
Delivery configuration (f)
0 = without controls (applicable to size 85 only) Inspection side (d)
1 = with controls 1 = right-hand
2 = pre-wired for external control cubicle 2 = left-hand
4 = with controls and communication

Voltage (g) Damper ETVA-aa-b-1


2 = 3 x 400 V
Unit size (aa)
Post-treatment section (h) 10, 20, 30, 35, 40, 50, 65, 80, 85
0 = without (standard)
1 = with, on supply air side (not size 10) Delivery configuration (b)
2 = post-treatment section (sizes 60-85) connected 0 = without damper actuator
directly to air handling unit (refers to external control cubicle)
1 = on/off with spring return
Execution (i) 2 = on/off
i = 1 = with integral motor
i = 3 = with EC-motor (only a = 20, 30, 35) Location (c)
1 = external (delivered separately)
2 = internal (extract air side) 65-85,
not for inlet in top panel
3 = internal (outdoor air side) 65-85,
not for inlet in top panel
5 = Top (ETAS c = 5)

Fläkt Woods 8210 GB 2009.02 44 Specifications are subject to alteration without notice
STING CATALOGUE

Ordering Codes

Sound attenuator ETLD-aa-b Air cooler for chilled water ETKN-aa-b-c-d-1


Mounted in ductwork
Unit size (aa)
10, 20, 30, 35, 40, 50, 65, 80, 85 Unit size (aa)
10, 20, 30, 35, 40, 50, 65, 80, 85
Location (b)
1 = standard (ETAS c = 1-4) Output variant (b)
2 = Top (ETAS c = 5) 1, available for size 10 - 20
2, Not available for the size 10 – 20 units
2, size 50 has connection dimensions 1400 x 800
Electric air heater ETKK-aa-b-c-d-e-1
Mounted in ductwork Droplet eliminator (c)
0 = without (size 10-85)
Unit size (aa) 1 = with (size 65-85)
10, 20, 30, 35, 40, 50, 65, 80, 85
Connection side (d)
Output variant (b) 1 = right-hand (aa= 30-85)
1, 2 2 = left-hand (aa =10-85)
3, available for aa=10 only

Version (c)
1 = heating bar type (size 85) Air cooler, DX ETKP-aa-b-c-d-e-1
2 = heating bar type with thyristor and Mounted in ductwork
stepping switch
3 = heating bar type with thyristor and Unit size (aa)
stepping switch (Top size 30-35) 10, connection dimensions: 800 x 400 mm
20, connection dimensions: 800 x 400 mm
Power supply (d) 30, 35, 40, 50, 65, 80, 85
1 = 3 x 230 V AC, output variant 1, i.e. 3 kW heater is
to be wired to a single-phase (230 V) or 2-phase Output variant (b)
(400 V) supply. 1
2 = 3 x 400 V AC, output variant 1, i.e. 3 kW heater is 2 = available for size 50 only,
to be wired to a single-phase (230 V) or 2-phase connection dimensions: 1400 x 800 mm
(400 V) supply.
Output stages (c)
Connection side (e) 1 = 1 output stage (size 10-35)
1 = right-hand 3 = 2 output stage 1/3 + 2/3 interlace
2 = left-hand (sizes 10-85)

Droplet eliminator (d)


0 = without (size 10-85)
Air heater for hot water ETKE-aa-b-c-1
1 = with (size 65-85)
Mounted in ductwork
Connection side (e)
Unit size (aa)
1= right-hand
10, 20, 30, 35, 40, 50, 65, 80, 85
2= left-hand
Output variant (b)
1
2 = size 10 has a 400 mm dia. connection ,
size 20 has a 500 mm dia. connection.

Connection side (c)


1 = right-hand
2 = left-hand

Fläkt Woods 8210 GB 2009.02 45 Specifications are subject to alteration without notice
STING CATALOGUE

Ordering Codes

Cooling unit Cooler ETKC-aa-b-c-dd-e-f-g-h-i-j-k-l Outlet cowl ETAZ-16-bb-1-1

Unit size (aa) Unit size (bb)


20-85 10-85

Capacity variant (b) Adjustable foot ETAZ-20-b-1


1, 2, 3 (set, supplied unmounted)

Design (c) Number of feet (b)


1 = supply air, down, counter-flow 1 = 4 feet (sizes 10, 20, 30, 35))
3 = supply air, up, counter-flow 2 = 6 feet (sizes 40, 50)
3 = 6 feet (sizes 65-85)
Fin pitch (dd)
(supply air) / (exhaust air)
Spare filter (for one airflow path) ETAZ-21-bb-c-1
20 = 2,0 mm / 1,8 mm
25 = 2,5 mm / 2,0 mm Unit size (bb)
10-85
Material, coil (e)
Only supply air coil Location (c)
1 = Cu/Al 1 = inlet – end connection
2 = inlet in top panel
Water cooled condesor (f) 3 = Top (ETAS c = 5)
0 = without
1 = with
Flexible connection ETAZ-22-bb-c
Droplet eliminator (g) (supplied unmounted)
0 = without
1 = with Unit size (bb)
10-85
Refrigerent (h)
1 = R407C Location (c)
1 = standard (ETAS c = 1-4)
2 = Top (ETAS c = 5)
Capacity control (i)
0 = without
Stainless filter frame, accessory set ETAZ-23-bb-c-1
1 = with hot gas bypass
Unit size (bb)
Voltage (j) 10-85
1 = 3 x 400V, 50 Hz
2 = 3 x 230V, 50 Hz (Norway) Location (c)
1 = lower level and upper level, to the right of the rotor
Material (k) 2 = lower level and upper level, to the left of the rotor
1 = galvanized steel sheet 3 = inlet in top panel

Differential pressure gauge,


Inspection side, supply air (l)
flow measurement ETAZ-24-bb-1
1 = right (For units without control unit only)
2 = left
Unit size (bb)
10 = sloping tube manometer
Lifting tubes, set of 2 ETAZ-05-bb 20-85 = U-tube manometer
Unit size (b)
10-85 Dual-purpose cowl for wall mounting,
sizes 10, 20 ETAZ-25-b
Air intake louvre with cowl ETAZ-15-bb-1-1 Duct connection dimensions (b)
1 = 2 x 400 mm (size 10)
Unit size (bb) 2 = 2 x 500 mm (sizes 20, 30)
10-85

Fläkt Woods 8210 GB 2009.02 46 Specifications are subject to alteration without notice
STING CATALOGUE

Ordering Codes

Dual-purpose cowl, roof mounting ETAZ-26-b Control equipment STET-a-b-ccc-ddd-e-f-g-h-ii-j

Connection dimensions (b) Fan motor, TF (a)


1 =1000 x 500 mm (sizes 10, 20, 30) 4 = speed control, FO
2 =1400 x 700 mm (sizes 35, 40)
3 =1800 x 900 mm (size 50) Fan motor, FF (b)
4 = speed control, FO
Roof duct ETAZ-27-b Fan output (ccc)
014 = 1.4 kW (size 10, 20)
Connection dimensions (b)
015 = 1.5 kW (size 30)
1 =1000 x 500 mm (sizes 10, 20, 30)
022 = 2.2 kW (size 35)
2 =1400 x 700 mm (sizes 35, 40)
3 =1800 x 900 mm (size 50) 040 = 4.0 kW (size 40, 50)
075 = 7.5 kW (size 65, 80)
110 = 11 kW (size 85)
Stand for vertical configuration ETAZ-28-bb-1
Air heater (ddd)
Unit size (bb) 000 = without post heating
10, 20 003 = hot water, external shunt
004 = electric, with built-in thyristor
Water trap for positive pressure ETAZ-30 999 = unspecified
(supplied unmounted) (dealer’s version) (not in ACON)

U-tube manometer, for filter ETAZ-31 Heat exchanger (e)


(supplied unmounted) 1 = rotary heat exchanger

Air cooler (f)


Roof for outdoor installation ETAZ-33-bb-c-d-e-1 0 = no cooler
1 = chilled water
Unit size (bb) 2 = evaporative refrigerant, 1 stage
10, 20, 30, 35, 40, 50, 65, 80, 85 3 = evaporative refrigerant, 2 stages
Sequential mode
Material (c)
4 = evaporative refrigerant, 2 stage
1= galvanized sheet steel
Binary mode
Version (d) 7 = ETCK Cooler
0 = unmounted
1 = mounted Voltage (g)
4 = 3 x 400 V AC
Location (e)
1 = roof for air handling unit Delivery option (h)
2 = unit with empty section 1 = built in
3 = built in, outdoor version
Assembly instructions ETAZ-36-bb-3 6 = terminal box

Language variant (bb) Control unit (ii)


02 = Swedish 00 = without control equipment
03 = English 82 = Fläkt Woods standard
06 = Finnish
Control unit display (j)
Reinforced packaging ETAZ-37-bb-1-1 0 = without display/standard display
5 = character-based, 8 lines
Unit size (bb)
10, 20, 30, 35, 40, 50, 65, 80, 85

Fläkt Woods 8210 GB 2009.02 47 Specifications are subject to alteration without notice
STING CATALOGUE

Ordering Codes

Temperature control STYZ-01-bb-c-d-e-f-g-h-i-j-k-1 Speed control STYZ-02-bb-c-d-e-f-1

Control unit (bb) Control unit (bb)


00 = without control equipment 00 = without control equipment
82 = Fläkt Woods standard 82 = Fläkt Woods standard

Control situation (c) Speed control, supply air (c)


1 = supply air control, includes 4 = airflow control
1 in-duct sensor 5 = CO2-control, in-duct sensor (d=7)
2 = extract air control, includes 6 = CO2-control, room sensor (d=7)
1 in-duct sensorand 1 factory-fitted 7 = slave-controlled supply airflow
extract air sensor inside air 9 = pressure control with flow readings
handling unit
3 = room control, includes Speed control, extract air (d)
1 in-duct sensor and 1 room sensor 4 = airflow control
5 = CO2-control, in-duct sensor (c=7)
Night-time cooling (d) 6 = CO2-control, room sensor (c=7)
0 = without 7 = slave-controlled extract airflow
1 = with, includes necessary room 9 = pressure control with flow readings
sensor and façade sensor
Pressure range (e)
Night-time heating (e) 0 = without
0 = without 1 = 0-1000 Pa, designed for airflow control
1 = with size 10, and pressure control all sizes.
2 = with 100% recirculated air includes 2 = 0-3000 Pa, designed for airflow control
necessary room sensor and sizes 20-85
façade sensor
Delivery configuration (f)
Cooling energy recovery (f) 2 = unmounted with cable and quick connector
0 = without 5 = mounted and connected with quick connector
1 = with, includes necessary in-duct sensor

Set point displacement (g)


0 = without
1 = outdoor air compensated temperature
set point includes necessary in-duct sensor

Airflow compensation (h)


0 = none
1 = blocking, high speed at low outdoor
temperatures
2 = outdoor temperature compensated airflow
via transfer curve
4 = summer-/winter compensated airflow/
pressure
5 = comfort control, (reduced airflow
through heat exchanger)

Efficiency measurement (i)


0 = without
2 = supply airs measurement

Type of sensor (j)


2 = NI –1000 LG

Connection (k)
1 = unmounted
5 = mounted and wired with quick connector

Fläkt Woods 8210 GB 2009.02 48 Specifications are subject to alteration without notice
STING CATALOGUE

Ordering Codes

Communication STYZ-05-bb-c-d-e-2 Fire detection STYZ-20-b

Control unit (bb) Control unit (b)


82 = Fläkt Woods standard 1 = alarm from external fire alarm function
(for potential-free contact)
Function/protocol (c) 2 = with control unit and alarm function
0 = without (no damper control)
3 = LonWorks 6 = with control unit, alarm function and exercising of
5 = SMS in event of alarm max 2 dampers
6 = OPC server 7 = with control unit, alarm function and exercising of
7 = Modbus RTU max 4 dampers
8 = BacNet

Accessories (d) Smoke detectors STYZ-22-b-c-dd


0 = without
3 = GSM modem incl. antenna Supply air (b)
0-9 = quantity
Fl@ktNET (e)
0 = without Extract air (c)
1 = web pages only 0-9 = quantity
3 = web pages + SMS
Mounting shelf (dd)
00-18 = quantity
Communication cable STYZ-06-bb-cc-0
Extension cable, display
Smoke damper function STYZ-23-b-c-d-e
Control unit (bb) (Two-position damper actuator, 230 VAC.)
82 = Fläkt Woods standard
Supply air (b)
Length (cc) 0-9 = quantity (normally open)
05 = 5 m
10 = 10 m Extract air (c)
0-9 = quantity (normally open)

Defrosting STYZ-10-82-1-1-9-2 Supply air evacuation (d)


0-1 = quantity

Frost protection sensor STYZ-11-b-c-d Extract air evacuation (e)


0-1 = quantity
Type of sensor (b)
2 = NI –1000 LG

Version (c) Fire thermostat STYZ-24-b-c


1 = insertion sensor
(rectangular air heater, ETKE-aa, Supply air (b)
aa = 30-85 except ETKE-30-1, 35-1) 0-1 = quantity
2 = strap-on sensor (cirkular heating coil, ETKE-aa,
aa = 10, 20, and ETKE-30-1, 35-1) Extract air (c)
0-1 = quantity
Connection (d)
2 = unmounted with cable and quick connector

Fläkt Woods 8210 GB 2009.02 49 Specifications are subject to alteration without notice
STING CATALOGUE

Ordering Codes

Damper actuator STYZ-27-b-cc-d Load interrupter STYZ-39-bbb-c-1

Location (b) Max permissible current (bbb)


1 = outdoor air damper 016 = 16 A
2 = extract air damper 025 = 25 A
8 = exhaust air damper 032 = 32 A
045 = 45 A
Type of actuator (cc) 063 = 63 A
31 = two-position damper with spring return, 080 = 80 A
15 Nm, 24 V AC 125 = 125 A
160 = 160 A
Delivery configuration (d)
2= unmounted, with cable and quick connector Auxiliary contact (c)
0 = without
1 = with breaking, 1 closing switch
Filter monitor STYZ-28-b-c
Delivery configuration (d)
Location (b) 1 = unmounted
1 = supply air
2 = extract air
3 = supply air and extract air Prolonged/forced operation STYZ-40-b-c-d-0-f

Delivery configuration (c) Forced operation (b)


2 = unmounted, with cable and quick connector 1 = prolonged operation
2 = forced operation
3 = forced airflow, prolonged operation

Modified designations / STYZ-36-bb-4-dd-e-f-g-1 Control via external timer (c)


Language 0-5 timers

Control unit (bb) Control via external push-button (d)


00 = without control equipment 0-5 push-buttons
82 = Fläkt Woods standard
Control via motion detector (f)
Unit size (dd) 0-5 motion detectors
01-99

Delivery configuration (e)


0 = without control unit
1 = with control unit

Language in wiring diagram (f)


1 = Swedish
2 = German
3 = English
4 = Finnish
5 = Danish

Language in DUC display (g)


0 = without
1 = Swedish
2 = German
3 = English
4 = Finnish
5 = Danish

Fläkt Woods 8210 GB 2009.02 50 Specifications are subject to alteration without notice
STING CATALOGUE

Ordering Codes

Remote control unit STYZ-41-b Service code SERV-03-b

Version (b) Type of service (b)


1 = timer with in-operation LED, alarm LED 1 = commissioning
(Norwegian version) 2 = participation during inspection
2 = switch, off/remote/hand (Finland version) 3 = refurbishing

Transformer STYZ-55-b-cc-d Frequency inverter STRF-a-bb-ccc-d-e-f-g-h-ii-00

Voltage (b) Air handling unit family (a)


1 = 230 to 400 V AC 4 = ET

Output (cc) Unit size (bb)


12 = 12.5 kVA(sizes 10, 20, 30) 10, 20, 30, 35, 40, 50, 65, 80, 85
16 = 16 kVA(sizes 35-40)
20 = 20 kVA(sizes 50) Output (ccc)
25 = 25 kVA(sizes 65-80) 014 = 1.4 kW (sizes 10, 20)
40 = 40 kVA(size 85) 015 = 1.5 kW (size 30)
017 = 1.7 kW EC-motor (size 20, 30)
Version (d) 022 = 2.2 kW (size 35)
1 = full 031 = 3.0 kW EC-motor (size 35)
040 = 4.0 kW (sizes 40, 50)
075 = 7.5 kW (sizes 65, 80)
Valve/Valve actuator STYZ-70-bb-c-d-e-f-ggg 110 = 11 kW (size 85)

Brand (bb) Voltage (d)


20 = Siemens 4 = 3x400 V AC

Scope of supply (c) Number of phases (e)


1 = actuator only 1 = single-phase (size 10, 20)
2 = valve with actuator 3 = 3-phase (size 30-85)

Type of valve (d) Number of motor poles (f)


0 = without 2 = 2 poles (sizes 10-30)
2 = 2-way 4 = 4 poles (sizes 35-85)
3 = 3-way
Version (g)
Location (e) 1 = mounted (85)
1 = heating 4 = included in integral motor (10-80)
2 = cooling
Enclosure class (h)
Connection (f) 2 = IP 54
1 = unmounted, supplied at same time as control
equipm. Operating frequency, high speed (ii)
2 = unmounted with cable and quick connector (Hz)
Set to 00 for airflow and/pressure control
Kvs-value (ggg)
006 = 0.63 Make (jj)
010 = 1.0 Kvs-value Siemens 00 = FWG standard
016 = 1.6 actuator
025 = 2,5
0.25-2.5 SQS65
040 = 4.0
4.0-6.3 SQS65
063 = 6.3
10-40 SQX62
100 = 10.0
49 SKB62
160 = 16.0
63 SKB62
250 = 25.0
78 SKB62
400 = 40.0
63-99.9 SKC62
490 = 49.0

Fläkt Woods 8210 GB 2009.02 51 Specifications are subject to alteration without notice
We Bring Air to Life

Solutions for all your air climate and air movement needs
Fläkt Woods is a global
Fläkt Woods is providing solutions for ventilation and air climate for buildings as well
leader in air management. as fan solutions for Industry and Infrastructure.
We specialise in the design
Air Handling Units (AHUs) Fans
and manufacture of a wide
Modular, compact and small Advanced axial, centrifugal and
range of air climate and air AHU units. Designed to ensure boxed fans for general and specialist
movement solutions. And optimisation of indoor air quality, applications. Comprehensive range
our collective experience operational performance and including high temperature and ATEX
service life. compliant options. Engineered for
is unrivalled. energy efficiency and minimised life
Air Terminal Devices and Ducts cycle cost.
Our constant aim is to
Supply and exhaust diffusers and
provide systems that valves for installation on walls, ceiling
Chillers
precisely deliver required or floor are all included in our large Air-cooled and water-cooled chillers
function and performance, range and fit all types of applications. with cooling capacity up to 1800kW.
Designed to minimise annual energy
as well as maximise Chilled Beams consumption in all types of buildings.
energy efficiency. Active induction beams for
ventilation, cooling and heating,
Controls and drives
and passive convection beams Variable speed drives and control
Condesign Info Productions AB ABF5498

for cooling. For suspended or systems, all tested to ensure total


flush-mounted ceiling installation – compatibility with our products.
and multi-service configuration. Specialist team can advise on energy
saving and overall system integration.
With unique Comfort Control and
Flow Pattern Control features.

Residential ventilation
A complete range of products for resi-
FWG-AHU-STING-2009.02-GB 8210 © Copyright 2009 Fläkt Woods Group

dential ventilation. Consists of ventila-


tion units, exhaust air fans and cooker
hoods designed to optimise indoor
comfort and save energy.


Fläkt Woods Group SA


18, avenue Louis Casaï, CH-1209 Geneva, Switzerland
Tel. +41 22 309 3800
email info@flaktwoods.com www.flaktwoods.com
See global website for international sales offices www.flaktwoods.com