Vous êtes sur la page 1sur 1

SP : 24-1983

Tolerances for reinforcements are diameter ratio, if this is less than 2.0,
specified in 11.3. Once the concrete is the factor being obtained from
placed, it is difficult to check the tolerance IS : 516-1959* _
of reinforcements. However, the position of Strength of
= Kx 1.08x&
steel near the surface of concrete (say within standard core I
70 mm) can be determined by using a d) Convert this result’ into equivalent
magnetic cover meter. cube strength. Compressive strength
of 150 mm cube = 1.25 (compressive
16. INSPECTION AND TESTING OF strength of 150 x 300 mm cylinder)
STRUCTURES = 1.25x (Kx l.O8xf,).
e) Compare the average value of three
16. I Inspection specimens with the specified strength.
Correction for age of concrete may be
16.2 (See also 15.1 and 15.2 and their obtained from 5.2.2 (see also com-
comments). Concrete will be deemed not to ments on 5.2.1, especially for the
comply with the strength requirements: influence of the type of cement).

a) if there are stray -cases of extremely 16.4 The number of test cores should be as
low strength; and large as possible with due regard to
economic considerations. In practice, it is
b) if the average of all the samples is usual to secure only three cores (the
extremely low. minimum recommended by the Code) and
In such cases core tests may be required to average the strength results. This sample
decide further measures. mean is only an approximation of the
strength of concrete in the structure and the
16.3 - results are dependent on the number of
cores. It is important, therefore, that struc-
16.3.1 - ture should not unnecessarily be declared
unfit simply because the sample mean may
26.3.2 Core cutting that is, drilling fall below 85 percent of the required strength
wherever possible, should be avoided in rein- especially when only a small number of cores
forcements. The procedure for preparing are tested. Either further core tests may be
and testing cores drilled from concrete are carried out or a load test is resorted to or the
given in IS : 516-1959*. The cores should be load-carrying capacity of the structure
undamaged representative of the concrete. recalculated in the light of existing core
The cores should be capped before testing, results.
using the procedure given in IS : 516-1959*.
16.5 Load Tests on Parts of Structures-
Standard diameter of core is 150 mm; (See Ref 13). This clause and its sub-clauses
however cores of 100 mm diameter may also are intended to provide reassurance or other-
be used and the strength assessed from both wise as to the adequacy of doubtful struc-
cores will be about the same. The length of tural units. These rules are not to be used as
core should be at least 95 percent of the core a substitute for normal design procedure.
diameter. The equivalent cube strength (on
150 mm cubes) may be obtained in the When it is required that a static load test is
following manner: to be carried out cognizance should be taken
of the effect on the test of the loading pat-
tern. The loading medium should not be
a) Strength of core =f, (on 100 mm stored temporarily on any part of’~ the
diameter core) structure where it could affect the test.
b) Apply correction for diameter: if
diameter is less than 100 mm, correc- Members other than flexural members
tion factor = 1.08 should preferably be investigated by
Strength of analytical procedures due to problems of
150 mm core 1 = 1.08 xfO load application and the difficulty of
detecting incipient failure.
c) Apply correction ’ for height to
_ The loads are expected to be applied and
*Methods of test for strength of concrete. removed incrementally. The procedure for

39

Vous aimerez peut-être aussi