Académique Documents
Professionnel Documents
Culture Documents
The power system itself, at the point of end use, may be An aside: for crimped power connections, some countries
called “mains”, “mains voltage”, “service”, “utility”, or insist that the crimp be covered with insulation such as
“power line”. In the context of an electric utility, the end- heat shrink tubing, on the basis that it provides both
use voltage may be referred to as “low voltage”; in the mechanical support and insulation. Other countries insist
context of the user of the exact same service the end-use that the crimp be uncovered, to permit visual inspection.
voltage may be referred to as “high voltage”. Some countries require ring terminals for power
connections as opposed to spade terminals or box lugs,
“Phase”, “line”, “hot” are all used interchangeably to because they are less likely to become accidentally
designate a non-neutral current-carrying conductor. detached.
“Neutral” (or its literal translation) is almost always used “Single-phase” and “one-phase” are used interchangeably,
– it has no common synonyms. It is sometimes with “single-phase” being the more common term.
abbreviated “W” on systems that use X-Y-Z terminology.
“Dual-phase”, “two-phase”, “double-phase”, and “split-
“Ground”, “Earth”, “Protective Earth”, “PE” (pronounced phase” all refer to a center-tapped single phase supply like
“pee-ee”) are all used interchangeably to designate the that shown in Fig 1E, except in some rare cases where
conductor that is attached to a chassis for protection. they are used to incorrectly describe a two-transformer
three-phase system of the type shown in Fig 2D. Just to
A range of voltages is generally designated by a tilde keep things confusing, this term is sometimes used to
(“~”), while alternate voltages are generally separated by discuss one phase of a specific type of three-phase system
slashes (“/”). For example, a power supply rated at shown in Fig 2C and Fig 2E.
“90V~270V” should operate properly at any voltage
between 90V and 270V. In contrast, a power supply rated “Three-phase” and “triple-phase” are used
interchangeably, with “three-phase” being more common.
For the moment ignoring phase rotation and nominal
voltage and frequency, there are at least 7 different three-
phase arrangements used around the world, so “three-
phase power required” is not a sufficient description.
“Y”, “wye”, and “star” are used interchangeably to (neutral), and newer wiring is brown(hot) and
designate a three-phase system with a centered neutral blue(neutral), so a blue wire can indicate either hot or
conductor. neutral, depending on the age of the wiring.
“Delta” or “Triangle” are used interchangeably to To make things even more complicated, industrial plants
designate a three-phase system without a neutral that belong to multinational companies may be
conductor, or one in which the neutral conductor has no constructed using the color code of their home country
connection to the equipment. (e.g. a French factory located in South Africa may use
French colors for three-phase wiring instead of South
African colors). And to make things still more
III. PHASE DESIGNATION AND COLORS complicated, minor electrical changes in these factories
are often made using the local color coding.
On pure single-phase systems, the three conductors are
almost always designated as “line” or one of the With the exception of protective earth, do not rely on
variations mentioned above, “neutral”, and “protective insulation colors for world-wide applications. Use L1-
earth” or one of the variations mentioned above. L2-L3 to designate the phases, N to designate neutral, and
PE or the standard IEC symbol to designate protective
On single-phase systems that are actually one phase of a earth.
three-phase system, the terminology of the associated
three-phase system is generally used (e.g. the three III. NOMINAL VOLTAGES
conductors will be designated L1, L2, and PE). However,
this is an area where labeling mistakes are common – the The concept of “nominal voltage” should be treated with
equipment may be labeled “Line”, “Neut”, and “PE”, but some skepticism, especially in developing countries.
it may be perfectly acceptable to run the equipment Even in advanced countries, the nominal voltage is
between two phases of a three-phase supply. If you are generally regulated at the service entrance (the location
the equipment designer, try to avoid this labeling error. where the electric power is delivered to the building), and
it is often considerably lower at the point within the
building where you are trying to use it. It may even be
Conductor Designation Comments considerably higher if a large load has been removed
L1-L2-L3 Universally understood recently.
A-B-C
R-S-T In some countries, an “old-fashioned”
designation but still understood. The specified nominal voltage is going through a decades-
U-V-W May indicate the secondary of a long change in most countries. In North America, the
transformer (e.g. Japan) or may nominal voltage has migrated from 110V to 115V to
indicate current (e.g. Austria) 117V to 120V. Nevertheless, equipment marked “110V”
X-Y-Z Fairly common in North America
0-4-8 or 8-0-4 or 12-4-8 Indicates phase angle corresponding is certainly expected to work on a 120V outlet. Similarly,
to hours on an analog clock (Spain, the 220V standard in many parts of the world is migrating
Italy) from 220V to 230V to 240V.
Red-Yellow-Blue Common designation outside North
America; sometimes abbreviated with
the first letters of the local language
The above nominal voltages may be phase-to-neutral
Brown-Black-Purple, Standard local color codes (South voltages on a three-phase system, so the phase-to-phase
Red-White-Blue, Africa, Austria, etc.) Each country voltages are going through a similar transition (e.g. on a
Yellow-Green-Violet, may have its own color convention, 220V to 230V transition, the phase-to-phase voltages will
etc. so it can be dangerous to rely on
transition from 380V to 400V).
color to indicate phase.
Table 1: Common three-phase conductor designations
There can be dangerous confusion if a split-phase or
three-phase system is referred to with a single nominal
The protective earth conductor is almost always color-
coded green-with-a-yellow-stripe. However, the color voltage. For example, a 240V three-phase system in
code for the other conductors varies so widely as to be North America is understood to be 240V from phase-to-
phase. A 240V three-phase system in Hong Kong is
almost useless. For example, depending on country and
understood to be 240V from phase-to-neutral, with 415V
voltage, the Neutral conductor may be white, blue, or
from phase-to-phase.
black. Three-phase conductors may be Red-Yellow-Blue,
Black-Brown-Purple, Red-White-Blue, Yellow-Green-
Violet or a wide variety of other colors. In some For this reason, the nominal voltage for three-phase
countries older single-phase wiring is blue (hot) and black systems should always be specified either as a pair of
voltages (e.g. “120/208 three-phase”) or explicitly as IV. NUMBER OF CONDUCTORS – THREE-PHASE
phase-to-phase voltage (e.g. “240V phase-to-phase”). SYSTEMS
It is worth noting that in some countries, the same Fig 2C shows a “tapped-leg” delta. This configuration
conductor may be used for both neutral and protective provides three-phase power (e.g. 240V phase-to-phase,