PETROKEMYA(SABIC)
Presentation by Farhan Ansari
1.Details of
existing
Skid
2.Existing
Cable Block
diagram
3.1 Communication Protocol between Flow meters and Flow computers:
As we see from the existing cable block diagram, the communication between turbine
flow meters and Schlumberger Flow computer was via pulse signal. The communication
between densitometer and Flow computer was also via Pulse signal.
Since the new flow meter is Coriolis type, initially the plan was to retain the pulse signal as
communication between Endress Hauser flow meter and OMNI flow computer. As we
know that Coriolis flow meter can measure density as well, plan was to take density via 4-
20mA to flow computer. Hence client purchased Coriolis flow meter with two pulse
3.Design
outputs and one 4-20 mA output. Later on client instructed to take the flow readings via
Serial communication(RS-485) to flow computer because client had experienced issues
with transmission of pulse signal from the same location. To implement this the I/O
module of flow meter had to be changed from analog to serial.
During later design stages, PICS decided not to go ahead with serial communication
Challenges During
because of below 2 reasons:
a) As pet the latest OMNI firmware, OMNI Flow computer can receive flow inputs only
as pulse.
Skid Upgrade b) Changing the I/O module from analog to serial voids certain
classifications/approvals of Endress Hauser flow meter.
Blue: New
Grey: Existing
Pulse signal
4-20mA 4-20mA 4-20mA
4-20mA
Marshalling Marshalling
New FC
O-CA-E6 O-MB-54 O-MB-55 DCS
Cabinet
Date 30-OCT-2019 MR
5. 4-20mA to Pulse converter
Can be programmed via software
6. Key design drawings
developed during project
During project execution many design drawings
& documents were developed. Below are some of
the key design drawings: