Reference: SEC
Issued by : JAD
CG4107
Outdoor air temperature 48.0 °C Unit fluid flow 167.3 m³/h
Glycol WATER Sea level 611 m
Inlet fluid temperature 15.0 °C Refrigerant R134a
Outlet fluid temperature 10.0 °C Unit power supply 400 V/3 ph/60 Hz
Unit performances
Model CG4107 SPL (@ 1m, f.f, re.ISO3744)(*) 84.5 dB(A)
Cooling capacity 973.3 kW PWL (re.ISO3744)(*) 106.5 dB(A)
Unit power input 428.7 kW Unit OA 699 A
Unit EER 2.27 Unit FLA 951 A
Outlet fluid temperature 10.0 °C Unit LRA 1306 A
Inlet fluid temperature 15.0 °C Width 9586 mm
Unit fluid flow 167.30 m³/h Depth 2308 mm
Unit fluid side pressure drop 37 kPa Height 2581 mm
Airflow 315000 m³/h Weight 10282 kg
Compressors
Number of compressors 2 n° Compressor Operating Amp. 2 x 324 A
Total compressors power input 396.3 kW Compressors COP 2.46
Evaporators
Number of evaporators 2 n° Fluid side pressure drop 37 kPa
Condensers
Number of condensing coils 4 n° Heat rejection 1370 kW
Condenser fan
Number of fans 14 n° Full load Ampere 14 x 4.4 A
Power input 14 x 2.3 kW Locked rotor Ampere 14 x 0 A
Operating Ampere 14 x 3.6 A Fan speed 956 rpm