EARTHPIT RESISTANCE VALUE OF RE-

Earth Pit Resistance


recorded on Nov-2017 (With
Electrode out Grid) in ꭥ
Earth Pit
S.No. length in Area Location
No Meters

Earth Strip -
01
Crude Tank
1 EP-08 3 Area Near Tank FR-01B 28.5
Crude Tank
2 EP-78 40 Area Near Tank FR-01A 9.8
Crude Tank
3 EP-77 40 Area Near HM -32 15.4
Crude Tank
4 EP-76 40 Area Betwa Gate 9.7
Crude Tank
5 EP-75 40 Area Near Tank FR-01B 6.65
Crude Tank
6 EP-09 3 Area Near Tank FR-01C 12.5
Crude Tank
7 EP-10 3 Area Near Tank FR-01C 16.1

8 EP-IOT-04 40 IMT Area Near Tank FR-09A 1.2

9 EP-IOT-05 40 IMT Area Near Tank CR-13A 2.5

10 EP-50 3 IMT Area Near Tank CR-05B 3.4

11 EP-51 3 IMT Area Near Tank CR-05C 18

12 EP-49 3 IMT Area Near Tank CR-13A 4.5

13 EP-100 40 IMT Area Near HM-36 3.2

14 EP-104 3 IMT Area Near Tank DR-18 3.2

15 EP-47 3 IMT Area Near HM-43 8.7

16 EP-IOT-03 40 IMT Area Near Tank CR-04B 1.4

17 EP-97 40 IMT Area Near Tank CR-04C 7.5


18 EP-IOT-02 40 IMT Area Near Tank CR-04C 11.5

19 EP-57 3 IMT Area Near HM-42 45.1

20 EP-98 40 IMT Area East side of CR-2B 5.7

21 EP-46 3 IMT Area East Tank of CR-19 1.5

22 EP-45 3 IMT Area Near CR-07 17.1

23 EP-IOT-01 40 IMT Area Near Tank CR-19A 1.4


CE VALUE OF RE-FURBISHED PIT
Earth Pit Resistance
Earth Pit Resistance Earth Pit Resistance recorded
corded on Nov-2017 (With recorded (With
(With out Grid) in ꭥ after
out Grid) in ꭥ Grid) in ꭥ
refurbishment Date of
Measurement

Earth Strip - Earth Strip - Earth Strip -


Earth Strip - 02 01 02 01 Earth Strip - 02

28.6 0.038 0.078

9.5 0.13 0.14

14.5

9.5

6.75

13.1

16.3

1.3 0.038 0.078 1.12 1.2

2.6 0.13 0.14

3.2

19

4.4

3.7

3.4

105

1.3

7.4
11.6

50.2

5.8

1.4